PRODUCT LINE LEAK DETECTION
Katie SeabornAMERICAN CONTAINMENT SERVICES,
INC.®
Annual GTEC Underground Storage Tank Management & Compliance
Seminar - 2014
Angle Check Valve
OR Foot Check Valve
SUCTION PUMP
Under Pump Check Valve
UST
1. Common Method
Product Pipe
2. Safe-Suction Method
Suction Systems
SUCTION SYSTEM Leak Detection Requirements:
For COMMON systems (one is required):
Product Pipe Tightness Test Every 3 Years Monthly Interstitial Monitoring Monthly Groundwater OR Vapor Monitoring Monthly Statistical Inventory Reconciliation
For SAFE-SUCTION systems (all are required):
Piping must slope back to the tank. Only one check valve, and it must be
installed as close as practical to the pump. The above must be verifiable.
Dispenser
Shear Valve
UST
Product Pipe
Submerged Turbine
Pump
Pump Motor
Pump Head
Pressurized Systems
Must be equipped with an automatic line leak detector which must be tested annually, AND use one of the following:
Annual Line Tightness Testing Monthly Vapor Monitoring Monthly Groundwater Monitoring Monthly Interstitial Monitoring Monthly SIR
PRESSURIZED SYSTEM Leak Detection Requirements:
Federal EPA Requirements for Automatic Line Leak Detectors (LLDs):
Can detect a 3-gallon per hour leak, at a line pressure of 10-psi, within 1 hour.
When a leak is detected, LLDs must shut off the product flow, restrict the product flow, or trigger an audible or visual alarm.
Must have a Third Party Certification.
More PRESSURIZED SYSTEM Leak Detection Requirements:
No leaks at the STP or leak detector
No reduced flow
No liquids in secondary containment
No alarms on electronic monitoring devices
Recommended PRESSURIZED SYSTEM Leak Detection
Checklists:
Monthly
Annually
Leak Detector Functionality Test
Product Line Tightness Testing
Visual Inspection of all accessible piping, fittings, and secondary
containment
ATG System Inspection and Functionality Test
(Electronic Sump Sensor)
FE Petro MLLD
Mechanical Pressurized Line Leak Detectors (MLLDs)
Red Jacket MLLD
Electronic Pressurized Line Leak Detectors (PLLDs)
Incon PLLD’s
V/R PLLD’s
Electronic Line Leak Test
Report
(Wireless PLLD)
POP QUIZ!What kind of system is it, and what is required?
Common Suction Method
Safe-Suction Method Pressurized
Line PTT Every 3-yrs, ORInterstitial Monitoring, OR
Stat. Inv. Reconciliation
No Leak Detection Required for the
Product Piping
PUMP
UST
PUMP
UST
PUMP
UST
Annual LD Test AND Annual Line PTT, OR
Interstice Monitoring, OR Stat. Inv. Reconciliation
POP QUIZ!... continued What kind of system is it, and what is required?
Annual Line PTT OR Stat. Inv. Reconciliation
AND Interstice Monitoring
(if piping is double wall)
UST
GRAVITY/SIPHON
SOLENOID VALVE
POP QUIZ!... (last question)
What kind of system is it, and what is required?
COMING SOON: Annual Line PTT OR
Stat. Inv. Reconciliation AND Interstice Monitoring
(if piping is double wall)
UST
PUMP
EMERGENCY POWER
GENERATOR
SOLENOID VALVES
CURRENTLY: No leak detection required. Emergency Power
Generator Systems are deferred from 40 CFR Part
280 Subpart D.
GRAVITY/SIPHON