EXISTING METAL BUILDING TO BE DEMOLISHED,PATCH AND REPAIR CONCRETE TO MATCH EXISTING
20'-0
"
9'-0"TYP.8'-0"8'-0"
4 SPACESNEW OFFICE
BUILDING
A2.0
1
HEA
RD
RO
AD
601'
±
300'±
EXISTING STORAGEBUILDING (NO WORK)
EXISTING STORAGEBUILDING (NO WORK)
EXISTING STORAGEBUILDING (NO WORK)
EXISTING STORAGEBUILDING (NO WORK)
EXISTING STORAGEBUILDING (NO WORK)
EXISTING STORAGEBUILDING (NO WORK)EXISTING STORAGE
BUILDING (NO WORK)
EXISTING STORAGEBUILDING (NO WORK)
EXISTING STORAGEBUILDING (NO WORK)
EXISTING STORAGEBUILDING (NO WORK)
EXISTING 11,136 SQ. FT. STORAGE BUILDING(CLIMATE CONTROL RENOVATION 1)
EXISTING 8,430 SQ. FT. STORAGE BUILDING(CLIMATE CONTROL RENOVATION 2)
A3.0
2
A3.0
1
ALIGN
ACCE
SSAI
SLE
4" TRAFFIC BLUE PAINTSTRIPING AT ADA ACCESSAISLE AND MARKER
4" TRAFFIC YELLOW PAINT STRIPINGEXISTING EDGE OF CONCRETE
31'-9"
25'-4
"
1 SCALE: 1" = 30'-0"SITE PLAN
project #:
date issued:drawn by:checked by:revisions:
A 1.0
Site Plan &General
Information
c
1874
Prie
n La
ke C
harle
s St
orag
e
Mis
cella
neou
s Ad
ditio
ns &
Ren
ovat
ions
2100
W. P
rien
Lake
Roa
dCa
lcas
ieu
Paris
hLa
ke C
harle
s, L
ouis
iana
706
05
09/04/2018jhjk
phase:
For ConstructionConstruction Bid Documents
stamp:
2018 copyright kudla architecture llc
4 2 9 K i r b y S t r e e tL a k e C h a r l e s , L A 7 0 6 0 1p : 3 3 7 . 4 3 6 . 3 6 5 0f : 3 3 7 . 4 3 6 . 3 6 5 5
w w w . k u d l a a r c h i t e c t . c o m
Drawings and Specifications as instruments of serviceare and shall remain the property of the Architect. They
are not to be used on other projects or extensions tothis project except by agreement in writing and with
appropriate compensation to the Architect. Contractoris responsible for confirming and correlating dimensions
at job site. The Architect will not be responsible forconstruction means, methods, techniques, sequences
or procedures; or for safety precautions and programs inconnection with the project.
Prien Lake Charles StorageMiscellaneous Additions & Renovations2100 W. Prien Lake RoadCalcasieu ParishLake Charles, Louisiana 70605
Project Overview & Code Research
PROJECT SCOPE:THE PROJECT CONSISTS OF THE RENOVATION TO (2)EXISTING METAL STRUCTURAL STEEL STORAGE BUILDINGSTO CLIMATE CONTROLLED WITH (1) EXISTING STORAGEBUILDING BEING DEMOLISHED AND REPLACED WITH ANEW 734 SQ. FT. WOOD FRAMED OFFICE BUILDING.
APPLICABLE CODES AT NEW CONSTRUCTION:INTERNATIONAL BUILDING CODE (IBC) - 2015NFPA 101 LIFE SAFETY CODE (NFPA) - 2015INTERNATIONAL PLUMBING CODE (IPC) - 2015INTERNATIONAL MECHANICAL CODE (IMC) - 2015NATIONAL ELECTRIC CODE (NEC) - 2014AMERICAN NATIONAL STANDARDS INSTITUTE (ANSI) - 2010AMERICAN WITH DISABILITIES ACT (ADA) - 2010
OCCUPANCY TYPE:IBC: BUSINESS/STORAGE (S-1)NFPA: BUSINESS (CHAPTER 39) STORAGE (CHAPTER 42)
CONSTRUCTION:IBC: 2B / 5B AT OFFICENFPA: 2B / 5B AT OFFICE
OCCUPANT LOAD:OFFICETOTAL GROSS = 646 SF / 100 = 7 OCC.
C.C. STORAGE BLDG. 1TOTAL = 11,055 SF / 300 = 37 OCC.
C.C. STORAGE BLDG. 2TOTAL = 8,855 SQ. FT. / 300 = 30 OCC.
1. ALL WORK SHALL COMPLY WITH FEDERAL, STATE, AND LOCAL LAWS.
2. THE CONTRACTOR IS RESPONSIBLE FOR VERIFYING THE EXTENT, NATURE, AND SCOPE OF WORK DESCRIBED IN THESEDOCUMENTS AND IS RESPONSIBLE FOR PROVIDING ALL LABOR, MATERIALS, EQUIPMENT, TRANSPORTATION,DELIVERY, HANDLING, SERVICES, SUPERVISION AND QUALITY CONTROL REQUIRED TO EXECUTE ALL AS WORK ASDELINEATED IN THESE DRAWINGS UNLESS AS SPECIFICALLY NOTED AS OUTSIDE OF THE CONTRACT.
3. THE CONTRACTOR IS RESPONSIBLE FOR COORDINATING ALL WORK WITH ALL TRADES INCLUDING THOSE OPERATINGUNDER SEPARATE CONTRACTS WITH THE OWNER.
4. ALL WORK SHALL BE PERFORMED BY SKILLED AND QUALIFIED WORKERS IN ACCORDANCE WITH ESTABLISHED "BESTPRACTICES."
5. CONTRACTOR SHALL FAMILIARIZE HIMSELF WITH ALL EXISTING CONDITIONS AND ANY DIFFICULTIES OR RESTRICTIONSAFFECTING THE EXECUTION OF THE CONTRACT PRIOR TO SUBMITTING A PROPOSAL.
6. ALL PRODUCTS, MATERIALS, AND EQUIPMENT SHALL BE INSTALLED IN ACCORDANCE WITH THE MANUFACTURER'SSPECIFIC INSTRUCTIONS AS WELL AS IN COMPLIANCE WITH ALL APPLICABLE CODES.
7. JOB SAFETY IS THE SOLE RESPONSIBILITY OF THE CONTRACTOR.
8. CONTRACTOR SHALL VERIFY LOCATIONS, LEVELS, DISTANCES, AND FEATURES THAT MAY AFFECT THE WORK. SHOULDEXISTING CONDITIONS DIFFER FROM THOSE SHOWN OR INDICATED, OR IF IT APPEARS THAT THESE PLANS, STANDARDSPECIFICATIONS, AND SPECIAL PROVISIONS DO NOT ADEQUATELY DETAIL THE WORK TO BE DONE, CONTRACTORSHALL NOTIFY THE ARCHITECT PRIOR TO CONTINUING WITH ANY RELATED WORK. NO ALLOWANCE WILL BE MADE INHIS BEHALF FOR ANY EXTRA EXPENSE RESULTING FROM FAILURE OR NEGLECT IN DETERMINING THE CONDITIONSUNDER WHICH WORK IS TO BE PERFORMED. NOTED DIMENSIONS TAKE PRECEDENCE OVER SCALE.
9. CONTRACTOR SHALL PROVIDE ANY AND ALL NECESSARY TEMPORARY SHORING, BRACING, AND BARRICADESNECESSARY TO INSURE SAFE EXECUTION OF CONSTRUCTION AND DEMOLITION.
10. CONTRACTOR AGREES TO ASSUME SOLE AND COMPLETE RESPONSIBILITY FOR THE JOB SITE DURING THE COURSE OFCONSTRUCTION OF THIS PROJECT, INCLUDING SAFETY OF ALL PERSONS AND PROPERTY; THAT THIS REQUIREMENTSHALL APPLY CONTINUOUSLY AND NOT BE LIMITED TO NORMAL WORKING HOURS; AND THAT THE CONTRACTOR SHALLDEFEND, INDEMNIFY, AND HOLD THE CITY REPRESENTATIVES HARMLESS FROM ANY AND ALL LIABILITY, REAL AND/ORALLEGED, IN CONJUNCTION WITH THE PERFORMANCE OF THIS PROJECT.
11. CONTRACTOR SHALL BE RESPONSIBLE FOR PROVIDING SUITABLE TRASH CONTAINERS AND TIMELY TRASH REMOVALFROM THE SITE CONSISTENT WITH THE STAGE OF CONSTRUCTION. WORK AREA SHALL BE KEPT CLEAN, SAFE, ANDORDERLY AT ALL TIMES.
12. ALL DIMENSIONS, ANGLES, ELEVATIONS, CONDITIONS, AND PHYSICAL CONFIGURATIONS RELATIVE TO EXISTINGCONDITIONS SHALL BE FIELD VERIFIED BY THE CONTRACTOR PRIOR TO COMMENCING WORK OR ORDERING MATERIAL.IF ANY DIFFERENCES ARE FOUND, THE ARCHITECT SHOULD BE NOTIFIED IMMEDIATELY.
13. DO NOT SCALE DRAWINGS! WRITTEN DIMENSIONS SHALL GOVERN. NOTIFY ARCHITECT FOR ANY DIMENSIONS NOTSHOWN.
14. THESE DRAWINGS ARE INTENDED TO DEFINE THE GENERAL DESIGN AND SCOPE OF THE WORK REQUIRED TOCOMPLETE THE PROJECT. IT IS THE INTENT OF THESE DOCUMENTS TO PROVIDE FOR COMPLETE FINISHED WORK ANDOPERATING SYSTEMS. OMISSIONS FOUND IN THESE DRAWINGS DO NOT RELIEVE THE CONTRACTOR OF SUCHRESPONSIBILITIES AS IMPLIED BY THE SCOPE OF WORK UNLESS SPECIFICALLY NOTED.
15. ALL WORK WILL BE SUBJECT TO REVIEW AND ACCEPTANCE BY THE OWNER UPON COMPLETION OF THE WORK.
Index to Drawings
A 1.0 Site Plan and General InformationA 2.0 Plans and Details - Office BuildingA 3.0 Renovated Plans - Climate Control Building
MEP 1.0 Mechanical / Electrical Plans - Office BuildingMEP 2.0 Mechanical / Electrical Plans - C.C. Renov. 1MEP 3.0 Mechanical / Electrical Plans - C.C. Renov. 2
Windspeed
Vicinity Map
PROJECTLOCATION
W. PRIEN LAKE ROAD
NEL
SON
RO
AD
HEA
RD
RO
AD
I-210
WAL-MART
FIRE PROTECTION:N/A
DESIGN DATA:FLOOR LIVE LOAD: 100 PSFROOF LIVE LOAD: 20 PSFWIND DESIGN LOAD: 132 MPHRISK CATEGORY: IIIMPORTANCE FACTOR: 1.0FLOOD DESIGN DATA:ZONING:
General Notes
1REVISED OFFICE BUILDING TOWOOD FRAME10/25/2018
1
35'-714"
29'-334"6'-31
2"
6'-5
1 4"5'
-2"
8'-4
3 4"
20'-0
"
2'-0
5 8"3'
-13 8"
4'-8
"5'
-61 4"
5'-6
1 4"4'
-8"
20'-4
1 2"
6'-312" 29'-33
4"
16'-0
" x 5
'-0" S
USPE
ND
ED M
ETAL
CAN
OPY
2'-10" HIGH MAX.BUILT-IN COUNTER5'
-0"
2'-0
"
9'-6"
11'-1
03 4"
7'-0" 2'-6"
3070
30"x
48"
60"x
58"F.D. Ø5'-0"
TOILET
LAV.
42" GRAB BAR36" G
RAB
BAR
R.R.
SALES AREA
WORK AREA
RES.
3070
3070 EXTERIORMETAL IN PAINTEDH.M. FRAME
3070 EXTERIORTEMPERED ALUM.
PAINTED H.M. FRAME
4060 STOREFRONTTEMPERED
4060 STOREFRONTTEMPERED
A4.05
5'-0"
NOTE: 9'-0" GRID CEILING THROUGHOUT
NOTE: PROVIDE DOUBLE 2x12 HEADERAT ALL DOOR/WINDOW LOCATIONS.
2x8 CEILING JOISTS AT 16" O.C.,TYPICAL ALONG BUILDING
35'-912"
21 4" S
IDIN
G L
EDG
E
20'-4
1 2"
17'-812"18'-1"
714" CMU LEDGE
OMIT LEDGE AT EXTERIOR OPENINGS
F.F. ELEV. SET 6" ABOVE ADJACENT GRADE
214" SIDING LEDGE
21 4" S
IDIN
G L
EDG
E
SEE FOUNDATION PLAN
2x8 RAFTERS AT 16" O.C. W/ 3/4"SHEATHING AND ICE/WATER SHIELDMOISTURE BARRIER
2'x2' SUSPENDEDCEILING GRID
9'-0
"
11'-0
" PLA
TE H
EIG
HT
5/8" EXTERIOR SHEATHING W/MOISTURE BARRIER & 24 GA.
METAL WALL PANEL FINISH
2x6 WOOD STUDS AT 16" O.C.W/ MIN. R-15 INSULATION,PAINTED 5/8" GYP. BOARD
INTERIOR
CONTINUOUS 4" GUTTER W/4x4 DOWNSPOUTS
123R-19 MIN. BATT INSULATION
24 GA. METAL ROOF PANELSON 2x4 SCREEDS AT 24" O.C.
FRAME FOR ZERO OVERHANG
2x8 RIDGE BEAM
CONTINUOUS PRE-FINISHED METAL CAP FLASHING, MIN.24" LAP SEAMS W/ CONTINUOUS CLEAT AT BOTHSIDES, SLOPE TO ROOF MIN. 1/12
PRE-FINISHED SUSPENDEDMETAL CANOPY, BRACE TOBUILDING STRUCTURE, DO
NOT BRACE TO VENEER
PROVIDE CONTINUOUS BASEFLASHING AND MORTAR MESH
W/ WEEP HOLES AT 48" O.C. MAX.
ROOF OUTLINE BEYOND
4"x8"x16" CMU VENEER
7'-2
"
16'-0
"
8'-0
"
11'-0
" PLA
TE H
EIG
HT
24 GAUGE METAL ROOF PANELS
CONTINUOUS 4" GUTTER W/4x4 DOWNSPOUTS
5'-0"
18" M
IN.
24 GAUGE METAL WALL PANELS
24 GA. METAL WALL PANELS,TYPICAL BACK OF PARAPET
24 GAUGE METAL WALL PANELS
7'-0
"
24 GAUGE METAL ROOF PANELS
123
(4) #5 BARS W/ #3TIES AT 24" O.C.
SIDING LEDGE
6x6-D4.0xD4.0 W.W.F.
6 MIL VAPOR BARRIER
COMPACTEDSUB-GRADE
MIN. 4" THK. LAYEROF FILL SAND
5"
2'-0
"
3,000 PSI CONC.
1'-6"
11 2"
238"
(4) #5 BARS W/ #3TIES AT 24" O.C.
BRICK LEDGE
6x6-D4.0xD4.0 W.W.F.
6 MIL VAPOR BARRIER
COMPACTEDSUB-GRADE
MIN. 4" THK. LAYEROF FILL SAND
5"
2'-0
"
3,000 PSI CONC.
1'-6"
11 2" 914"
(2) #5 BARS W/ #3TIES AT 24" O.C.
6x6-D4.0xD4.0 W.W.F.
6 MIL VAPOR BARRIER
COMPACTEDSUB-GRADE
MIN. 4" THK.LAYER OF FILLSAND
5"
2'-0
"
1'-6"
3,000 PSI CONC.
1 SCALE: 1/4" = 1'-0"FLOOR PLAN - NEW OFFICE BUILDING
project #:
date issued:drawn by:checked by:revisions:
A 2.0
Plans and Details- Office Building
c
187409/04/2018jhjk
phase:
For ConstructionConstruction Bid Documents
stamp:
2018 copyright kudla architecture llc
4 2 9 K i r b y S t r e e tL a k e C h a r l e s , L A 7 0 6 0 1p : 3 3 7 . 4 3 6 . 3 6 5 0f : 3 3 7 . 4 3 6 . 3 6 5 5
w w w . k u d l a a r c h i t e c t . c o m
Drawings and Specifications as instruments of serviceare and shall remain the property of the Architect. They
are not to be used on other projects or extensions tothis project except by agreement in writing and with
appropriate compensation to the Architect. Contractoris responsible for confirming and correlating dimensions
at job site. The Architect will not be responsible forconstruction means, methods, techniques, sequences
or procedures; or for safety precautions and programs inconnection with the project.
FOUNDATION AND PAVING NOTES:
1. A 6 MIL POLYETHYLENE BARRIER SHALL BE INSTALLED, PRIOR TO PLACINGREINFORCEMENT OR CONCRETE, AFTER APPROVAL OF PREPARED EARTHWORK.
2. CONCRETE SHALL HAVE A MINIMUM COMPRESSIVE STRENGTH OF 3,000 PSI.
3. REINFORCING STEEL SHALL BE GRADE 60 DEFORMED BARS CONFORMING TO ASTM A-165.
4. WELDED STEEL MESH SHALL CONFORM TO ASTM A-185.
5. ALL REINFORCING RODS SHALL BE BENT AROUND ALL CORNERS A MINIMUM OF 24".
6. REMOVE TOP 24" OF VEGETATION, DELETERIOUS MATERIAL AND TOPSOIL FROM AREA TORECEIVE BUILDING AND DOWN TO 18" BELOW PARKING AREAS. REPLACE EXCAVATEDMATERIAL WITH SELECT FILL AND COMPACT TO 95% STANDARD PROCTOR DENSITY.BUILDING PAD FINAL ELEVATION TO BE 6" ABOVE INITIAL GRADE.
7. MAINTAIN UNIFORM MOISTURE CONDITIONS IN THE EXPOSED SUB-GRADE SOILS PRIOR TOCONSTRUCTION OF FLOOR SLAB. EXPOSED SUB-GRADE SOILS SHOULD NOT BE ALLOWEDTO DRY OUT OR BECOME WET DURING CONSTRUCTION.
8. BACKFILL ALL UTILITY TRENCHES OR OTHER POTENTIAL CONDUITS OF WATER UNDERNEATHSLAB TO A DISTANCE WITHIN 5'-0" OF ADJACENT FLOOR SLABS.
2 SCALE: 1/4" = 1'-0"FOUNDATION PLAN3 SCALE: 3/4" = 1'-0"
FOOTING AT CMU LEDGE
4 SCALE: 3/4" = 1'-0"FOOTING AT SIDING LEDGE
5 SCALE: 3/4" = 1'-0"INTERIOR FOOTING
6 SCALE: 1/4" = 1'-0"EAST ELEVATION7 SCALE: 1/4" = 1'-0"
WEST ELEVATION
8 SCALE: 1/4" = 1'-0"SOUTH ELEVATION9 SCALE: 1/4" = 1'-0"
BUILDING SECTION
Prie
n La
ke C
harle
s St
orag
e
Mis
cella
neou
s Ad
ditio
ns &
Ren
ovat
ions
2100
W. P
rien
Lake
Roa
dCa
lcas
ieu
Paris
hLa
ke C
harle
s, L
ouis
iana
706
05
1REVISED OFFICE BUILDING TOWOOD FRAME10/25/2018
1
1
1
1
10'x15'
10'-0"10'-0"10'-0"10'-0"10'-0"10'-0"10'-0"10'-0"10'-0"5'-0"5'-0"10'-0"10'-0"10'-0"10'-0"10'-0"10'-0"7'-6"7'-6"7'-6"7'-6"7'-6"7'-6"7'-6"7'-6"
1'-0"MIN.
1'-0"MIN.
1'-0
"M
IN.
1'-0
"M
IN.
1'-0
"M
IN.
15'-2
1 2"10
'-0"
5'-0
"10
'-0"
10'-2
1 2"
10'x10'
8'-0"x8'-0" OVERHEAD ROLL-UPDOOR, TYPICAL ALL 10' WIDE UNITS
10'x10'
10'x10'
10'x25'
10'x20'
10'x25'
10'x20'
10'x25'
10'x20'
10'x25'
10'x20'
10'x25'
10'x20'
10'x25'
10'x20'
10'x25'
10'x20'
10'x25'
10'x20'
10'x10'
10'x10'
10'x10'
10'x10'
10'-2
1 2"10
'-0"
10'-0
"5'
-0"
10'-2
1 2"5'
-0"
10'x10'
10'x10'
10'x10'
10'x10'
10'x10'
10'x10'
10'x10'
10'x10'
10'x10'
10'x10'
10'x10'
10'x10'
10'x10'
10'x10'
10'x10'
10'x10'
10'x10'
10'x10'
10'x10'
10'x10'
7.5'x10'
7.5'x10'
7.5'x10'
7.5'x10'
5'-0"x8'-0" OVERHEAD ROLL-UPDOOR, TYPICAL ALL 7.5' WIDE UNITS
7.5'x10'
7.5'x10'
7.5'x10'
7.5'x10'
7.5'x10'
7.5'x10'
7.5'x10'
7.5'x10'
7.5'x10'
7.5'x10'
7.5'x10'
7.5'x10'
7.5'x10'
7.5'x10'
7.5'x10'
7.5'x10'
7.5'x10'
7.5'x10'
7.5'x10'
7.5'x10'
7.5'x10'
7.5'x10'
7.5'x10'
7.5'x10'
7.5'x10'
7.5'x10'
7.5'x10'
7.5'x10'
5'-2
1 2"5'
-0"
7'-6
"7'
-6"
5'-0
"5'
-0"
5'-0
"5'
-0"
5'-2
1 2"
5'x5'
A/C
5'x5'
5'x5'
3'-0"x8'-0" OVERHEAD ROLL-UPDOOR, TYPICAL ALL 5' WIDE UNITS
5'x7.5'
5'x7.5'
5'x5'
5'x5'
CORRIDOR
CORRIDOR
CORRIDOR
COR
RID
OR
220'-0"
50'-5
"
3'-0"x7'-0"METAL
3'-0"x7'-0"METAL
3'-0"x7'-0"METAL
3'-0"x7'-0"METAL
3'-0"x7'-0"METAL
3'-0"x7'-0"METAL
8'-5" 10'-0" 10'-0" 10'-0" 10'-0" 10'-0" 10'-0" 10'-0" 10'-0" 10'-0" 10'-0" 10'-0" 10'-0" 10'-0" 10'-0" 10'-0" 10'-0" 10'-0" 10'-0" 10'-0" 10'-0"
10'-1
1 2"10
'-0"
5'-0
"5'
-0"
10'-1
1 2"
40'-3
"
208'-5"
1'-0
"M
IN.
8'-0"x8'-0" OVERHEAD ROLL-UPDOOR, TYPICAL ALL 10' WIDE UNITS3'-0"x
METAL3'-0"x7'-0"
METAL
3'-0"x7'-0"METAL
20'-1
1 2"5'
-0"
15'-1
1 2"
5'x5' A/C
3'-0"x8'-0" OVERHEAD ROLL-UPDOOR, TYPICAL ALL 5' WIDE UNITS
10'x10'
10'-1
1 2"5'
-0"
5'-0" 5'-0"
10'x10'
5'x10'
10'x10'
10'x10'
10'x15'
10'x20'
10'x15'
10'x20'
10'x15'
10'x20'
10'x15'
10'x20'
10'x15'
10'x20'
10'x15'
10'x20'
10'x15'
10'x20'
10'x15'
10'x20'
10'x15'
10'x20'10'x20'
10'x15'
10'x20'
10'x15'
10'x20'
10'x15'
10'x20'
10'x15'
10'x20'
10'x15'
10'x20'
10'x15'
10'x20'
10'x15'
10'x20'
10'x15'
10'x20'
10'x15'
10'x20'
8'x15'
8'x20'
5'-0"x8'-0" OVERHEAD ROLL-UPDOOR, TYPICAL ALL 8' WIDE UNITS
CORRIDORTRIMMED DOOR FORRETURN AIR BELOW
1 SCALE: 1/8" = 1'-0"FLOOR PLAN - CLIMATE CONTROL RENOVATION 1
project #:
date issued:drawn by:checked by:revisions:
A 3.0
Renovated Plans- Climate Control
Buildings
c
187409/04/2018jhjk
phase:
For ConstructionConstruction Bid Documents
stamp:
2018 copyright kudla architecture llc
4 2 9 K i r b y S t r e e tL a k e C h a r l e s , L A 7 0 6 0 1p : 3 3 7 . 4 3 6 . 3 6 5 0f : 3 3 7 . 4 3 6 . 3 6 5 5
w w w . k u d l a a r c h i t e c t . c o m
Drawings and Specifications as instruments of serviceare and shall remain the property of the Architect. They
are not to be used on other projects or extensions tothis project except by agreement in writing and with
appropriate compensation to the Architect. Contractoris responsible for confirming and correlating dimensions
at job site. The Architect will not be responsible forconstruction means, methods, techniques, sequences
or procedures; or for safety precautions and programs inconnection with the project.
2 SCALE: 1/8" = 1'-0"FLOOR PLAN - CLIMATE CONTROL RENOVATION 2
SCOPE OF WORK:
BOTH BUILDINGS SHOWN ARE EXISTING STRUCTURAL STEEL FRAMED METAL BUILDINGS TO BE GUTTEDBACK TO STEEL FRAME AND REBUILT TO CLIMATE CONTROLLED UNITS AS SHOWN. EXISTING ROOFS TOHAVE RETRO-FIT METAL ROOF UPGRADES INSTALLED AS RECOMMENDED BY MANUFACTURER. ALL WALLSTO BE BUILT USING LIGHT GAUGE METAL STUD FRAMING AND WRAPPED WITH METAL PANELS OVER 7/8"METAL HAT CHANNELS. ALL WALLS CONTINUOUS TO METAL ROOF DECK W/ PERMEABLE UPPER THIRD FORAIR TRANSMISSION THROUGHOUT EXCEPT AT EXTERIOR LOADED UNITS.
Prie
n La
ke C
harle
s St
orag
e
Mis
cella
neou
s Ad
ditio
ns &
Ren
ovat
ions
2100
W. P
rien
Lake
Roa
dCa
lcas
ieu
Paris
hLa
ke C
harle
s, L
ouis
iana
706
05
1REVISED OFFICE BUILDING TOWOOD FRAME10/25/2018
R.R.
SALES AREA
WORK AREA
RES.
B GFI
CU-1
EXIT
E
A
A
A
A
A
A
A
D
C
A-2
A-4
NOTE: RESTROOM RECEPTACLE TIEDINTO SAME CIRCUIT AS LIGHTING
A-9,11
WPGFI
WPGFI
WPGFI
PHOTOCELLTIMERSWITCH
SERVICE METER FEDOVERHEAD FROM NEWPOWER POLE AT ROAD
PANEL A
CT CT
A-1
A-3A-5
A-6
AHU-1
A-8,10
DOUBLECLEANOUT 6" DIA. METAL
EXHAUST DUCT
EXHAUST WALL CAP W/BIRD SCREEN
R.R.
SALES AREAWORK AREA
RES.
CU-12-TON
FRESH AIR INTAKEGRILLE W/ BIRD
SCREEN
3KW ELECTRICHEAT STRIP
4"Ø250cfm
1 2
3250cfm250cfm
50cfm
10"Ø
10"Ø
10"Ø
AHU-12-TON
75cfmEXHAUST
4" DRAIN TO TIE INTO EXISTINGCITY SEWER MAIN AT ROAD
CLEANOUT
2"
4"
F.D.
2"
PROVIDEPOINT-OF-SERVICE
WATER HEATERUNDER SINK
(1) 4"C(2) 4/0 KCMIL(1) #2 KCMIL GROUND
3/4"C WITH 4/0 KCMILGROUND TO GROUND ROD
GRADE
120/240V 1-PHASE 200AINCOMING OVERHEAD
SERVICE, COORDINATE W/SERVICE PROVIDER
3/4"ØX10'-0" COPPERCLADGROUND ROD
OFFICESERVICE
M
NEW SERVICE METER
ALL PANELS TO BEENGRAVED W/
LAMINATED I.D. TAG
PANEL A150A 1Ø
120/240V24-CIRM.L.O.
project #:
date issued:drawn by:checked by:revisions:
MEP1.0
Mechanical /Electrical Plan -New Office Bldg.
c
1874
Prie
n La
ke C
harle
s St
orag
e
Mis
cella
neou
s Ad
ditio
ns &
Ren
ovat
ions
2100
W. P
rien
Lake
Roa
dCa
lcas
ieu
Paris
hLa
ke C
harle
s, L
ouis
iana
706
05
09/04/2018jhjk
phase:
For ConstructionConstruction Bid Documents
stamp:
2018 copyright kudla architecture llc
4 2 9 K i r b y S t r e e tL a k e C h a r l e s , L A 7 0 6 0 1p : 3 3 7 . 4 3 6 . 3 6 5 0f : 3 3 7 . 4 3 6 . 3 6 5 5
w w w . k u d l a a r c h i t e c t . c o m
Drawings and Specifications as instruments of serviceare and shall remain the property of the Architect. They
are not to be used on other projects or extensions tothis project except by agreement in writing and with
appropriate compensation to the Architect. Contractoris responsible for confirming and correlating dimensions
at job site. The Architect will not be responsible forconstruction means, methods, techniques, sequences
or procedures; or for safety precautions and programs inconnection with the project.
1 SCALE: 1/4" = 1'-0"ELECTRICAL PLAN2 SCALE: 1/4" = 1'-0"
MECHANICAL PLAN
3 SCALE: N.T.S.ELECTRICAL RISER DIAGRAM
Luminaire Schedule LABELSYMBOL DESCRIPTION
A
NOTE: COORDINATE WITH OWNER ON FINAL LOCATIONS AND LIGHTFIXTURE SELECTIONS PRIOR TO CONSTRUCTION
2 X 4 LAY-IN LED FIXTUREAMP.SERVING
DESCRIPTION: PANEL
WIREWIRE
19
21
17
23
7
15
13
119
5
1
3
AMP.
A
CKT
MOUNTING:A.I.C.:MAIN:
BKR
VOLT:PHASE:WIRE: 3
BKRSERVING
20
8
14
10
6
2
4
CKT
120/240
SINGLE
18
16
22
24
150A
RECESSED--
12
SAFETY LIGHTING EXIT SIGN COMBO - NOTE: PROVIDEMATCHING REMOTE HEAD AT EXTERIOR DOOR LOCATIONSEXIT - -
20/1#12 LIGHTING - SALES, WORK, RESOURCE#1220/1POWER - WORK AREA
#1220/1 20/1#12
#1220/1 20/1#12
#1220/1
B
C
POWER - SALES AREA
POWER - POINT OF SALE
POWER - EXTERIOR RECEPTACLE GFI
SPACE
SPACE
SPACE
1 X 4 WALL MOUNT LED FIXTURE WITH EMERGENCY BALLAST
1 X 4 SURFACE MOUNT LED FIXTURE RATED FOR OUTDOOR USE
D EXHAUST FAN ONLY - INTEGRATE SWITCH W/ LIGHT UNLESSSHOWN OTHERWISE
E
POWER - WATER HEATER
CU-1 40/2 #8
-- ----
SPACESPACE
ELECTRICAL NOTES:
1. ALL ELECTRICAL WORK TO COMPLY WITHNATIONAL ELECTRICAL CODE 2014 CODEREQUIREMENTS SUPERCEDE ANY DETAIL ORNOTATIONS IN THESE PLANS. VERIFY ALLCONDITIONS PRIOR TO INSTALLATION.
2. ELECTRICAL CONTRACTOR SHALL BERESPONSIBLE FOR ALL LOAD DESIGNREQUIRED FOR ALL LIGHTING POWER,MECHANICAL EQUIPMENT AND ANY OTHERMECHANICAL EQUIPMENT AND ANY OTHEREQUIPMENT REQUIRED AS PART OF THISPROJECT.
3. FURNISH ALL LABOR AND MATERIALSNECESSARY TO PROVIDE THE COMPLETEPROJECT.
4. ALL TELEPHONE/DATA WORK TO BECOORDINATED & PERFORMED BYSUBCONTRACTOR AS SELECTED BY OWNER
5. LIGHT FIXTURES AND DEVICES SHALL BEADEQUATELY SUPPORTED.
6. CONTRACTOR SHALL COORDINATECONNECTION OF NEW DEVICES SUCH THATTHE MAXIMUM LOAD ON ANY ONE 20 AMP, 1POLE CIRCUIT SHALL NOT EXCEED EIGHT (8)2X4, 4 LAMP FLUORESCENT FIXTURES (OREQUIVALENT NUMBER OF LAMPS) OR SEVEN(7) GENERAL PURPOSE CONVENIENCEOUTLETS.
7. ALL LIGHT FIXTURES SHALL BE SELECTED BYOWNER AND INSTALLED BY ELECTRICALCONTRACTOR.
8. PROVIDE GFI OUTLETS IN WET AREAS.
9. DO NOT USE ALUMINUM CONDUIT IN SLAB ORBURIED.
10. PROVIDE TYPE WRITTEN DIRECTORY FORPANELS.
11. WIRE ALL FIELD ASSEMBLED DEVICES FORMECHANICAL EQUIPMENT FURNISHED BYMECHANICAL CONTRACTOR.
12. VERIFY POWER REQUIREMENTS WITHMANUFACTURERS RECOMMENDATIONS ONALL OWNER SELECTED EQUIPMENT PRIOR TOCONSTRUCTION. ADJUST PANEL LAYOUTS ASREQUIRED.
13. ALL OUTDOOR RECEPTACLES TO BE TAMPERPROOF GROUND FAULT INTERRUPTERS (GFI)W/ WEATHER PROOF COVER.
14. ALL DISCONNECTS, METERS AND GUTTERSSHALL BE GROUNDED AND BONDED.
15. GROUNDING PIGTAILS SHALL BE INSTALLEDIN EACH BOX.
KEYNOTES:
PROVIDE 4" DEEP SAFE PAN WITH WAGNER WS-1 WETSWITCH INTERLOCKED WITH CONTROLS TO SHUT UNITDOWN ON DETECTION OF WATER IN SAFE PAN.
PROVIDE SMOKE DETECTOR IN SUPPLY AIR TO SHUT UNITDOWN ON DETECTION OF SMOKE.
1
2
HVAC NOTES:
1. ALL WORK TO COMPLY WITH LOCAL CODES & 2015 ICCCODES.
2. ALL DUCTWORK TO BE LATEST EDITION OF SMACNASTANDARDS.
3. REFRIGERANT LINES TO BE SIZED PER MANUFACTURERSRECOMMENDATIONS. INSULATE SUCTION LINES WITH 1"THICK TUBING INSULATION.
4. PROVIDE DUCT SMOKE DETECTORS AS PER CODE.
5. ALL FLEX DUCT BRANCHES TO HAVE VOLUME DAMPERS.
6. EXHAUST FAN DUCT TO BE SHEET METAL. PROVIDE WALLCAPS W/ BIRD SCREEN. FANS TO HAVE BACK DRAFTDAMPER. INTERLOCK FANS WITH LIGHT SWITCHES.
REQUIRED OUTDOOR VENTILATION AIR:
AS PER TABLE 403.3 OF THE 2015 INTERNATIONALMECHANICAL CODE, PROVIDE HARD DUCTWAYS W/ MANUALDAMPERING TO EXTERIOR OF BUILDING FOR EACH HVACBLOWER UNIT.
NOTE: COORDINATE WITH OWNER ON FINAL LOCATIONS ANDHVAC TONAGE CALCULATIONS PRIOR TO CONSTRUCTION
PLUMBING NOTES:
1. PERFORM ALL PLUMBING WORK IN ACCORDANCE WITHAPPLICABLE LOCAL, STATE, AND NATIONAL CODES.
2. MOUNT ALL WATER SHUTOFFS IN CASEWORK AT 16"AFF. CHECK EQUIPMENT PLAN FOR CASEWORKCONFLICTS. ALL EXPOSED PIPING TO HAVE CHROMEFINISH AND ESCUTCHEON WALL PLATES.
3. FILTERED WATER REQUIRED FOR DRINK DISPENSERAND ICE MACHINE. THIS PIPING SHOULD BE COPPER ORPEX IF CODE ALLOWS.
4. FILTERED LINES ARE COLD ONLY. FLUSH ALL FILTEREDLINES FOR 30 MINUTES MINIMUM PRIOR TOCONNECTING EQUIPMENT.
5. COORDINATE ALL EQUIPMENT CONNECTIONS WITHSUPPLIERS AND INSTALLERS TO ENSURE CORRECT ANDCOMPATIBLE OUTLETS.
6. FLOOR DRAINS (FD) SHOULD BE INSTALLED JUSTBELOW FLOOR LEVEL WITHOUT COLLARS OR LIPS.SLOPE FLOOR TO DRAINS.
7. ALL PLUMBING FIXTURES TO BE SUPPLIED ANDINSTALLED BY PLUMBING CONTRACTOR.
8. VERIFY WITH OWNER PRIOR TO CONSTRUCTION OF ANYEQUIPMENT USING CITY GAS AND PIPE ACCORDINGLY.
9. PROVIDE ANTI-SIPHON DEVICES ON ALL THREADEDFAUCETS, SUCH AS MOP SINK AND 3- COMPARTMENTSINK.
10. MECHANICAL EQUIPMENT CONDENSATE DRAINS SHALLNOT DISCHARGE ONTO A STREET, ALLEY OR SIDEWALKSO AS NOT TO CAUSE A NUISANCE. TIE INTO ADJACENTSEWER LINES WHEN OTHER LOCATIONS AREUNAVAILABLE.
11. PROVIDE FLOOR DRAIN W/ COVER AND HOT/COLDWATER SERVICE AT TRASH ENCLOSURE.
4 SCALE: NONETYPICAL HORIZONTAL AIR HANDLER UNIT DETAIL
RETURN AIR DUCTAHU
3" DEEP SAFE PAN, COATINSIDE WITH COAL TAR EPOXY
WET SWITCH INTERLOCKWITH CONTROLS
ELECTRIC STRIP HEATER
AD
OUTSIDE AIR
SUPPLY AIR
1 X 4 LAY-IN LED FIXTURE
LIGHTING/POWER - RESTROOM
SPACE
AHU-160/2#6
---- --
SPACE
SPACE
SPACE
SPACE
SPACE
SPACE
SPACE
1REVISED OFFICE BUILDING TOWOOD FRAME10/25/2018
10'x15'
10'x10'
10'x10'
10'x10'
10'x25'
10'x20'
10'x25'
10'x20'
10'x25'
10'x20'
10'x25'
10'x20'
10'x25'
10'x20'
10'x25'
10'x20'
10'x25'
10'x20'
10'x25'
10'x20'
10'x10'
10'x10'
10'x10'
10'x10'
10'x10'
10'x10'
10'x10'
10'x10'
10'x10'
10'x10'
10'x10'
10'x10'
10'x10'
10'x10'
10'x10'
10'x10'
10'x10'
10'x10'
10'x10'
10'x10'
10'x10'
10'x10'
10'x10'
10'x10'
7.5'x10'
7.5'x10'
7.5'x10'
7.5'x10'
7.5'x10'
7.5'x10'
7.5'x10'
7.5'x10'
7.5'x10'
7.5'x10'
7.5'x10'
7.5'x10'
7.5'x10'
7.5'x10'
7.5'x10'
7.5'x10'
7.5'x10'
7.5'x10'
7.5'x10'
7.5'x10'
7.5'x10'
7.5'x10'
7.5'x10'
7.5'x10'
7.5'x10'
7.5'x10'
7.5'x10'
7.5'x10'
7.5'x10'
7.5'x10'
7.5'x10'
7.5'x10'
5'x5'
5'x5'
5'x5'
5'x7.5'
5'x7.5'
5'x5'
5'x5'
CORRIDOR
CORRIDOR
CORRIDOR
COR
RID
OR
EXITB-6,8
EXIT
EXIT
EXIT
EXIT
NEW SURFACE MOUNT NEMA-3R LOCKABLE120/240V 1Ø 200A ELECTRICAL PANEL W/OVERHEAD FED SERVICE METER FROM NEW
POWER POLE AT ROAD
CU-2B-7,9
WPGFI
WPGFI
A
A
AHU-26-TON
A
A
AE
A
A
A
A
A
A
A
A
AE
A
AE
A
A
A
A
A
A
A
A
A
AE
A
AE
A
A
A
A
A
A
A
A
A
TIE ALL LIGHTS TO TIMER SWITCHCONTROLS AS EACH DOOR
B-1
B-3
B-2
B-4
10'x15'
10'x10'
10'x10'
10'x10'
10'x25'
10'x20'
10'x25'
10'x20'
10'x25'
10'x20'
10'x25'
10'x20'
10'x25'
10'x20'
10'x25'
10'x20'
10'x25'
10'x20'
10'x25'
10'x20'
10'x10'
10'x10'
10'x10'
10'x10'
10'x10'
10'x10'
10'x10'
10'x10'
10'x10'
10'x10'
10'x10'
10'x10'
10'x10'
10'x10'
10'x10'
10'x10'
10'x10'
10'x10'
10'x10'
10'x10'
10'x10'
10'x10'
10'x10'
10'x10'
7.5'x10'
7.5'x10'
7.5'x10'
7.5'x10'
7.5'x10'
7.5'x10'
7.5'x10'
7.5'x10'
7.5'x10'
7.5'x10'
7.5'x10'
7.5'x10'
7.5'x10'
7.5'x10'
7.5'x10'
7.5'x10'
7.5'x10'
7.5'x10'
7.5'x10'
7.5'x10'
7.5'x10'
7.5'x10'
7.5'x10'
7.5'x10'
7.5'x10'
7.5'x10'
7.5'x10'
7.5'x10'
7.5'x10'
7.5'x10'
7.5'x10'
7.5'x10'
5'x5'
5'x5'
5'x5'
5'x7.5'
5'x7.5'
5'x5'
5'x5'
CORRIDOR
CORRIDOR
CORRIDOR
COR
RID
OR
AHU-26-TON
1 2
UNIT INSTALLED ON PLATFORM W/RETURN AIR PLENUM BELOW AND THRUWALL RETURN AIR FILTER TO CORRIDOR
FRESH AIR INTAKE WALL GRILLE W/ BIRDSCREEN, HARD DUCT SUPPLY TO UNIT
160cfm
160cfm
160cfm
160cfm
160cfm 160cfm
160cfm
160cfm
160cfm
160cfm 160cfm
160cfm
160cfm
160cfm160cfm
NON-CLIMATE CONTROLLED UNITS, TYPICAL CROSS HATCHED AREAS
CU-2
(1) 4"C(2) 4/0 KCMIL(1) #2 KCMIL GROUND
3/4"C WITH 4/0 KCMILGROUND TO GROUND ROD
GRADE
120/240V 1-PHASE 200AINCOMING OVERHEAD
SERVICE, COORDINATE W/SERVICE PROVIDER
3/4"ØX10'-0" COPPERCLADGROUND ROD
OFFICESERVICE
M
NEW SERVICE METER
ALL PANELS TO BEENGRAVED W/
LAMINATED I.D. TAG
PANELB/C
150A 1Ø120/240V
24-CIRM.L.O.
NEMA-3RLOCKABLE
project #:
date issued:drawn by:checked by:revisions:
MEP2.0
Mechanical /Electrical Plans -
C.C. Renov. 1
c
187409/04/2018jhjk
phase:
For ConstructionConstruction Bid Documents
stamp:
2018 copyright kudla architecture llc
4 2 9 K i r b y S t r e e tL a k e C h a r l e s , L A 7 0 6 0 1p : 3 3 7 . 4 3 6 . 3 6 5 0f : 3 3 7 . 4 3 6 . 3 6 5 5
w w w . k u d l a a r c h i t e c t . c o m
Drawings and Specifications as instruments of serviceare and shall remain the property of the Architect. They
are not to be used on other projects or extensions tothis project except by agreement in writing and with
appropriate compensation to the Architect. Contractoris responsible for confirming and correlating dimensions
at job site. The Architect will not be responsible forconstruction means, methods, techniques, sequences
or procedures; or for safety precautions and programs inconnection with the project.
Prie
n La
ke C
harle
s St
orag
e
Mis
cella
neou
s Ad
ditio
ns &
Ren
ovat
ions
2100
W. P
rien
Lake
Roa
dCa
lcas
ieu
Paris
hLa
ke C
harle
s, L
ouis
iana
706
05
1 SCALE: 1/8" = 1'-0"ELECTRICAL PLAN
2 SCALE: 1/8" = 1'-0"MECHANICAL PLAN
3 SCALE: N.T.S.ELECTRICAL RISER DIAGRAM
Luminaire Schedule LABELSYMBOL DESCRIPTION
A
NOTE: COORDINATE WITH OWNER ON FINAL LOCATIONS AND LIGHTFIXTURE SELECTIONS PRIOR TO CONSTRUCTION
1 X 4 WALL MOUNT LED FIXTUREAMP.SERVING
DESCRIPTION: PANEL
WIREWIRE
19
21
17
23
7
15
13
119
5
1
3
AMP.
B
CKT
MOUNTING:A.I.C.:MAIN:
BKR
VOLT:PHASE:WIRE: 3
BKRSERVING
20
8
14
10
6
2
4
CKT
120/240
SINGLE
18
16
22
24
150A
SURFACE MOUNT--
12
SAFETY LIGHTING EXIT SIGN COMBO - NOTE: PROVIDEMATCHING REMOTE HEAD AT EXTERIOR DOOR LOCATIONSEXIT - -
20/1#12 LIGHTING - SW CORRIDOR#1220/1LIGHTING - E CORRIDOR
#1220/1 20/1#12
#1220/1
ELECTRICAL NOTES:
1. ALL ELECTRICAL WORK TO COMPLY WITHNATIONAL ELECTRICAL CODE 2014 CODEREQUIREMENTS SUPERCEDE ANY DETAIL ORNOTATIONS IN THESE PLANS. VERIFY ALLCONDITIONS PRIOR TO INSTALLATION.
2. ELECTRICAL CONTRACTOR SHALL BERESPONSIBLE FOR ALL LOAD DESIGN REQUIREDFOR ALL LIGHTING POWER, MECHANICALEQUIPMENT AND ANY OTHER MECHANICALEQUIPMENT AND ANY OTHER EQUIPMENTREQUIRED AS PART OF THIS PROJECT.
3. FURNISH ALL LABOR AND MATERIALSNECESSARY TO PROVIDE THE COMPLETEPROJECT.
4. ALL TELEPHONE/DATA WORK TO BECOORDINATED & PERFORMED BYSUBCONTRACTOR AS SELECTED BY OWNER
5. LIGHT FIXTURES AND DEVICES SHALL BEADEQUATELY SUPPORTED.
6. CONTRACTOR SHALL COORDINATE CONNECTIONOF NEW DEVICES SUCH THAT THE MAXIMUMLOAD ON ANY ONE 20 AMP, 1 POLE CIRCUITSHALL NOT EXCEED EIGHT (8) 2X4, 4 LAMPFLUORESCENT FIXTURES (OR EQUIVALENTNUMBER OF LAMPS) OR SEVEN (7) GENERALPURPOSE CONVENIENCE OUTLETS.
7. ALL LIGHT FIXTURES SHALL BE SELECTED BYOWNER AND INSTALLED BY ELECTRICALCONTRACTOR.
8. PROVIDE GFI OUTLETS IN WET AREAS.
9. DO NOT USE ALUMINUM CONDUIT IN SLAB ORBURIED.
10. PROVIDE TYPE WRITTEN DIRECTORY FORPANELS.
11. WIRE ALL FIELD ASSEMBLED DEVICES FORMECHANICAL EQUIPMENT FURNISHED BYMECHANICAL CONTRACTOR.
12. VERIFY POWER REQUIREMENTS WITHMANUFACTURERS RECOMMENDATIONS ON ALLOWNER SELECTED EQUIPMENT PRIOR TOCONSTRUCTION. ADJUST PANEL LAYOUTS ASREQUIRED.
13. ALL OUTDOOR RECEPTACLES TO BE TAMPERPROOF GROUND FAULT INTERRUPTERS (GFI) W/WEATHER PROOF COVER.
14. ALL DISCONNECTS, METERS AND GUTTERS SHALLBE GROUNDED AND BONDED.
15. GROUNDING PIGTAILS SHALL BE INSTALLED INEACH BOX.
LIGHTING - NW CORRIDOR POWER - RECEPTACLE INTERIOR
POWER - EXTERIOR GFI
SPACESPACE
SPACE SPACE
AE 1 X 4 WALL MOUNT LED FIXTURE WITH EMERGENCY BALLAST
SPACE
SPACESPACESPACE
KEYNOTES:
PROVIDE 4" DEEP SAFE PAN WITH WAGNER WS-1 WETSWITCH INTERLOCKED WITH CONTROLS TO SHUT UNITDOWN ON DETECTION OF WATER IN SAFE PAN.
PROVIDE SMOKE DETECTOR IN SUPPLY AIR TO SHUT UNITDOWN ON DETECTION OF SMOKE.
1
2
HVAC NOTES:
1. ALL WORK TO COMPLY WITH LOCAL CODES & 2015 ICCCODES.
2. ALL DUCTWORK TO BE LATEST EDITION OF SMACNASTANDARDS.
3. REFRIGERANT LINES TO BE SIZED PER MANUFACTURERSRECOMMENDATIONS. INSULATE SUCTION LINES WITH 1"THICK TUBING INSULATION.
4. PROVIDE DUCT SMOKE DETECTORS AS PER CODE.
5. ALL FLEX DUCT BRANCHES TO HAVE VOLUME DAMPERS.
6. EXHAUST FAN DUCT TO BE SHEET METAL. PROVIDE WALLCAPS W/ BIRD SCREEN. FANS TO HAVE BACK DRAFTDAMPER. INTERLOCK FANS WITH LIGHT SWITCHES.
REQUIRED OUTDOOR VENTILATION AIR:
AS PER TABLE 403.3 OF THE 2015 INTERNATIONALMECHANICAL CODE, PROVIDE HARD DUCTWAYS W/ MANUALDAMPERING TO EXTERIOR OF BUILDING FOR EACH HVACBLOWER UNIT.
NOTE: COORDINATE WITH OWNER ON FINAL LOCATIONS ANDHVAC TONAGE CALCULATIONS PRIOR TO CONSTRUCTION
CU-1 40/2 #8
-- ----
SPACE
SPACE
SPACE
AHU-160/2#6
---- --
SPACESPACE
SPACE
SPACE
1REVISED OFFICE BUILDING TOWOOD FRAME10/25/2018
5'x5'
10'x10' 10'x10'
5'x10'
10'x10'
10'x10'
10'x15'
10'x20'
10'x15'
10'x20'
10'x15'
10'x20'
10'x15'
10'x20'
10'x15'
10'x20'
10'x15'
10'x20'
10'x15'
10'x20'
10'x15'
10'x20'
10'x15'
10'x20'10'x20'
10'x15'
10'x20'
10'x15'
10'x20'
10'x15'
10'x20'
10'x15'
10'x20'
10'x15'
10'x20'
10'x15'
10'x20'
10'x15'
10'x20'
10'x15'
10'x20'
10'x15'
10'x20'
8'x15'
8'x20'
CORRIDOR
EXIT
EXIT
TIE ALL LIGHTS TO TIMER SWITCHCONTROLS AS EACH DOOR
CU-3
NEW SURFACE MOUNT NEMA-3R LOCKABLE 120/240V1Ø 200A ELECTRICAL PANEL W/ OVERHEAD FED SERVICE
METER FROM NEW POWER POLE AT ROAD
AE
A
A
A
A
A
A
A
AE
A
A
A
C-1
A
A
AE
A
A
A
A
A
C-6,8
AHU-35-TON
WPGFI
C-5,7
WPGFI
C-2
C-4
(1) 4"C(2) 4/0 KCMIL(1) #2 KCMIL GROUND
3/4"C WITH 4/0 KCMILGROUND TO GROUND ROD
GRADE
120/240V 1-PHASE 200AINCOMING OVERHEAD
SERVICE, COORDINATE W/SERVICE PROVIDER
3/4"ØX10'-0" COPPERCLADGROUND ROD
OFFICESERVICE
M
NEW SERVICE METER
ALL PANELS TO BEENGRAVED W/
LAMINATED I.D. TAG
PANELB/C
150A 1Ø120/240V
24-CIRM.L.O.
NEMA-3RLOCKABLE
5'x5'
10'x10' 10'x10'
5'x10'
10'x10'
10'x10'
10'x15'
10'x20'
10'x15'
10'x20'
10'x15'
10'x20'
10'x15'
10'x20'
10'x15'
10'x20'
10'x15'
10'x20'
10'x15'
10'x20'
10'x15'
10'x20'
10'x15'
10'x20'10'x20'
10'x15'
10'x20'
10'x15'
10'x20'
10'x15'
10'x20'
10'x15'
10'x20'
10'x15'
10'x20'
10'x15'
10'x20'
10'x15'
10'x20'
10'x15'
10'x20'
10'x15'
10'x20'
8'x15'
8'x20'
CORRIDOR
AHU-35-TON
1 2
UNIT INSTALLED ON PLATFORM W/RETURN AIR PLENUM BELOW AND THRUWALL RETURN AIR FILTER TO CORRIDOR
FRESH AIR INTAKE WALL GRILLE W/ BIRDSCREEN, HARD DUCT SUPPLY TO UNIT
NON-CLIMATE CONTROLLED UNITS, TYPICAL CROSS HATCHED AREAS
165cfm
165cfm165cfm165cfm165cfm165cfm165cfm
165cfm165cfm165cfm165cfm165cfm
CU-3
1 SCALE: 1/8" = 1'-0"ELECTRICAL PLAN
project #:
date issued:drawn by:checked by:revisions:
MEP3.0
Mechanical /Electrical Plans -
C.C. Renov. 2
c
187409/04/2018jhjk
phase:
For ConstructionConstruction Bid Documents
stamp:
2018 copyright kudla architecture llc
4 2 9 K i r b y S t r e e tL a k e C h a r l e s , L A 7 0 6 0 1p : 3 3 7 . 4 3 6 . 3 6 5 0f : 3 3 7 . 4 3 6 . 3 6 5 5
w w w . k u d l a a r c h i t e c t . c o m
Drawings and Specifications as instruments of serviceare and shall remain the property of the Architect. They
are not to be used on other projects or extensions tothis project except by agreement in writing and with
appropriate compensation to the Architect. Contractoris responsible for confirming and correlating dimensions
at job site. The Architect will not be responsible forconstruction means, methods, techniques, sequences
or procedures; or for safety precautions and programs inconnection with the project.
2 SCALE: 1/8" = 1'-0"MECHANICAL PLAN
Prie
n La
ke C
harle
s St
orag
e
Mis
cella
neou
s Ad
ditio
ns &
Ren
ovat
ions
2100
W. P
rien
Lake
Roa
dCa
lcas
ieu
Paris
hLa
ke C
harle
s, L
ouis
iana
706
05
AMP.SERVING
DESCRIPTION: PANEL
WIREWIRE
19
21
17
23
7
15
13
119
5
1
3
AMP.
C
CKT
MOUNTING:A.I.C.:MAIN:
BKR
VOLT:PHASE:WIRE: 3
BKRSERVING
20
8
14
10
6
2
4
CKT
120/240
SINGLE
18
16
22
24
150A
SURFACE MOUNT--
12
20/1#12 LIGHTING - E CORRIDOR#1220/1LIGHTING - W CORRIDOR
#1220/1 20/1#12
ELECTRICAL NOTES:
1. ALL ELECTRICAL WORK TO COMPLY WITHNATIONAL ELECTRICAL CODE 2014 CODEREQUIREMENTS SUPERCEDE ANY DETAIL ORNOTATIONS IN THESE PLANS. VERIFY ALLCONDITIONS PRIOR TO INSTALLATION.
2. ELECTRICAL CONTRACTOR SHALL BERESPONSIBLE FOR ALL LOAD DESIGN REQUIREDFOR ALL LIGHTING POWER, MECHANICALEQUIPMENT AND ANY OTHER MECHANICALEQUIPMENT AND ANY OTHER EQUIPMENTREQUIRED AS PART OF THIS PROJECT.
3. FURNISH ALL LABOR AND MATERIALSNECESSARY TO PROVIDE THE COMPLETEPROJECT.
4. ALL TELEPHONE/DATA WORK TO BECOORDINATED & PERFORMED BYSUBCONTRACTOR AS SELECTED BY OWNER
5. LIGHT FIXTURES AND DEVICES SHALL BEADEQUATELY SUPPORTED.
6. CONTRACTOR SHALL COORDINATE CONNECTIONOF NEW DEVICES SUCH THAT THE MAXIMUMLOAD ON ANY ONE 20 AMP, 1 POLE CIRCUITSHALL NOT EXCEED EIGHT (8) 2X4, 4 LAMPFLUORESCENT FIXTURES (OR EQUIVALENTNUMBER OF LAMPS) OR SEVEN (7) GENERALPURPOSE CONVENIENCE OUTLETS.
7. ALL LIGHT FIXTURES SHALL BE SELECTED BYOWNER AND INSTALLED BY ELECTRICALCONTRACTOR.
8. PROVIDE GFI OUTLETS IN WET AREAS.
9. DO NOT USE ALUMINUM CONDUIT IN SLAB ORBURIED.
10. PROVIDE TYPE WRITTEN DIRECTORY FORPANELS.
11. WIRE ALL FIELD ASSEMBLED DEVICES FORMECHANICAL EQUIPMENT FURNISHED BYMECHANICAL CONTRACTOR.
12. VERIFY POWER REQUIREMENTS WITHMANUFACTURERS RECOMMENDATIONS ON ALLOWNER SELECTED EQUIPMENT PRIOR TOCONSTRUCTION. ADJUST PANEL LAYOUTS ASREQUIRED.
13. ALL OUTDOOR RECEPTACLES TO BE TAMPERPROOF GROUND FAULT INTERRUPTERS (GFI) W/WEATHER PROOF COVER.
14. ALL DISCONNECTS, METERS AND GUTTERS SHALLBE GROUNDED AND BONDED.
15. GROUNDING PIGTAILS SHALL BE INSTALLED INEACH BOX.
POWER - EXTERIOR GFI POWER - INTERIOR
SPACESPACE
SPACE
SPACE SPACE
SPACE
SPACESPACESPACE
KEYNOTES:
PROVIDE 4" DEEP SAFE PAN WITH WAGNER WS-1 WETSWITCH INTERLOCKED WITH CONTROLS TO SHUT UNITDOWN ON DETECTION OF WATER IN SAFE PAN.
PROVIDE SMOKE DETECTOR IN SUPPLY AIR TO SHUT UNITDOWN ON DETECTION OF SMOKE.
1
2
HVAC NOTES:
1. ALL WORK TO COMPLY WITH LOCAL CODES & 2015 ICCCODES.
2. ALL DUCTWORK TO BE LATEST EDITION OF SMACNASTANDARDS.
3. REFRIGERANT LINES TO BE SIZED PER MANUFACTURERSRECOMMENDATIONS. INSULATE SUCTION LINES WITH 1"THICK TUBING INSULATION.
4. PROVIDE DUCT SMOKE DETECTORS AS PER CODE.
5. ALL FLEX DUCT BRANCHES TO HAVE VOLUME DAMPERS.
6. EXHAUST FAN DUCT TO BE SHEET METAL. PROVIDE WALLCAPS W/ BIRD SCREEN. FANS TO HAVE BACK DRAFTDAMPER. INTERLOCK FANS WITH LIGHT SWITCHES.
REQUIRED OUTDOOR VENTILATION AIR:
AS PER TABLE 403.3 OF THE 2015 INTERNATIONALMECHANICAL CODE, PROVIDE HARD DUCTWAYS W/ MANUALDAMPERING TO EXTERIOR OF BUILDING FOR EACH HVACBLOWER UNIT.
NOTE: COORDINATE WITH OWNER ON FINAL LOCATIONS ANDHVAC TONAGE CALCULATIONS PRIOR TO CONSTRUCTION
3 SCALE: N.T.S.ELECTRICAL RISER DIAGRAM
Luminaire Schedule LABELSYMBOL DESCRIPTION
A
NOTE: COORDINATE WITH OWNER ON FINAL LOCATIONS AND LIGHTFIXTURE SELECTIONS PRIOR TO CONSTRUCTION
1 X 4 WALL MOUNT LED FIXTURE
SAFETY LIGHTING EXIT SIGN COMBO - NOTE: PROVIDEMATCHING REMOTE HEAD AT EXTERIOR DOOR LOCATIONSEXIT - -
AE 1 X 4 WALL MOUNT LED FIXTURE WITH EMERGENCY BALLASTCU-3 40/2 #8
-- ----
SPACE
SPACESPACE
AHU-360/2#6
---- --
SPACESPACE
SPACE
SPACE
1REVISED OFFICE BUILDING TOWOOD FRAME10/25/2018