Presentation,description 3
Zelio Control - modular measurement and control relays 3
3-phase voltage control relays RM17 UB3 and RM35 UB3
Presentation Voltage measurement and control relays RM35 UB330, RM17 UB310 and RM35 UB3N30 monitor the following, on 3-phase supplies:
RM35 UB330 RM17 UB310 RM35 UB3N30
Failure of one or more phases,Absence of neutralOvervoltage and undervoltageVoltage between phases 220…480 V 208…480 VVoltage between phases and neutral. 120…277 V
Function performedFunction not performed
They monitor their own supply voltage, measured as a true rms value.Settings are protected by a sealable cover.Control status is indicated by a LED.The relays are designed for clip-on mounting on � rail
Applications� Control for connection of moving equipment (site equipment, agricultural equipment, refrigerated trucks).� Control for protection of persons and equipment against the consequences of reverse running (lifting, handling, elevators, escalators, etc.).� Control of sensitive 3-phase supplies.� Protection against the risk of a driving load (phase failure).� Normal/emergency power supply switching.
DescriptionRM35 UB330 RM35 UB3N30
1a Voltage range selector switch (220, 380, 400, 415, 440 and 480 V).
1b Voltage range selector switch (120, 127, 220, 230, 240, 260 and 277 V).
2 Overvoltage setting potentiometer. >U3 Undervoltage setting potentiometer. <U4 Undervoltage threshold delay setting
potentiometer. Tt25 Overvoltage threshold delay setting
potentiometer. Tt16 Spring for clip-on mounting on 35 mm �
rail.
Un Green LED: indicates that supply to the relay is on.R1 Yellow LED: indicates relay output state. High voltage threshold.R2 Yellow LED: indicates relay output state. Low voltage threshold.
RM17 UB3101 Voltage range selector switch (208, 220,
380, 400, 415, 440 and 480 V).2 Time delay adjustment potentiometer. Tt3 Overvoltage setting potentiometer. >U4 Undervoltage setting potentiometer. <U5 Spring for clip-on mounting on 35 mm �
rail.
Un Green LED: indicates that supply to the relay is on.R Yellow LED: indicates relay output state.
RM17 UB310RM35 UB3���
1064
38
1056
64
L1
12 22 21 2411 14
L3L2
R1
Un
R2
1a2345
6
L1
12 22 21 2411 14
L3 NL2
R1
Un
R2
1b2345
6
5
L1 L2 L3
12 11 14
1234
Operation:pages 3/29 to 3/31
Characteristics:page 3/32
References, dimensions :page 3/33
3/29
3
Operation 3 Zelio Control - modular measurement and control relays 3
3-phase voltage control relays RM17 UB3 and RM35 UB3
Operating principle3-phase voltage control relays monitor: � Undervoltage and overvoltage:Un Phase/phase 208 V 220 V 380, 400, 415,
440 V480 V
RM17 UB310 > U (%) + 2…+ 20 + 2…+ 20 + 2…+ 20 + 2…+ 10
< U (%) - 12…- 2 - 17…- 2 - 20…- 2 - 20…- 2RM35 UB30 > U (%) – + 2…+ 20 + 2…+ 20 + 2…+ 10
< U (%) – - 12…- 2 - 20…- 2 - 20…- 2
Un Phase/neutral 120 V 127 V 220, 230, 240, 260 V
277 V
RM35 UB3N30 > U (%) + 2…+ 20 + 2…+ 20 + 2…+ 20 + 2…+ 20
< U (%) - 20…- 2 - 20…- 2 - 20…- 2 - 20…- 2
� Failure of one or more phases,� The presence of neutral (RM35 UB3N30 only).Measurements are made between Phases/Phases for the RM35 UB330 and the RM17 UB310 and between Phases/Neutral for the RM35 UB3N30.Fault signalling is by LED. RM35 UB relays allow differentiation on the source of the fault (one LED for high threshold, one LED for low threshold).
���� Voltage selector switch:� Set the switch to the 3-phase supply voltage Un.� The position of this switch is only taken into account on energisation of the device.� If the switch position is changed while the device is operating, all the LEDs flash, but the product continues to operate normally with the voltage selected at the time of energisation preceding the change of position.The LED's return to their normal state if the switch is returned to the original position selected prior to the last energisation.
Overvoltage/undervoltage control relays: RM35 UB330The relay monitors its own supply voltage Un:� The relay monitors:
- failure of at least one of the three phases (U measured < 0.7 x Un),- the undervoltage,- the overvoltage.
� Each threshold has its own independently adjustable time delay from 0.3 to 30 s.� In the event of a voltage fault, the corresponding relay (one undervoltage output / one overvoltage output) opens at the end of the time delay set by the user.� In the event of phase failure, both relays open instantly without waiting for the end of the time delay set by the user.� On energisation of the device with a fault measured, the relays stay open.
Function diagrams
� Functions: � Phase failure.
� Overvoltage and undervoltage.
Tt 1: overvoltage threshold delay (adjustable on front panel).Tt 2: undervoltage threshold delay (adjustable on front panel).
30 % Un 30 % Un30 % Un
Phase L3
Phase L2
Phase L1
Relays R1/R2
<U
>U
11-1211-14
21-2221-24
L1L2
L3
Tt1 Tt2
Phases L1/L2/L3
Relay R1
Relay R2
Hysteresis
Hysteresis
Presentation, description :page 3/28
Characteristics:page 3/32
References, dimensions :page 3/33
3/30
3
Operation (continued) 3 Zelio Control - modular measurement and control relays 3
3-phase voltage control relays RM17 UB3 and RM35 UB3
Overvoltage/undervoltage + absence of neutral control relay: RM35 UB3N30The relay monitors its own supply voltage Un:� The relay monitors:
- the presence of neutral,- the undervoltage,- the overvoltage,- phase failure.
� Each threshold has its own independently adjustable time delay from 0.3 to 30 s.� In the event of a voltage fault, the corresponding relay (one undervoltage output / one overvoltage output) opens at the end of the time delay set by the user.� In the event of absence of neutral or phase, both relays open instantly without waiting for the end of the time delay set by the user.� On energisation of the device with a fault measured, the relays stay open.
Function diagrams
� Functions: � Phase failure.
� Overvoltage and undervoltage.
Tt 1: overvoltage threshold delay (adjustable on front panel).Tt 2: undervoltage threshold delay (adjustable on front panel).
30 % Un 30 % Un30 % Un
Phase L3
Phase L2
Phase L1
Relays R1/R2
<U
>U
11-1211-14
21-2221-24
L1L2
L3
Tt1 Tt2
Phases L1/L2/L3
Relay R1
Relay R2
Hysteresis
Hysteresis
Presentation, description :page 3/28
Characteristics:page 3/32
References, dimensions :page 3/33
3/31
3
Operation (continued) 3 Zelio Control - modular measurement and control relays 3
3-phase voltage control relays RM17 UB3 and RM35 UB3
Overvoltage/undervoltage control relay: RM17 UB310The relay monitors its own supply voltage Un:� The relay monitors:
- the undervoltage,- the overvoltage,- phase failure.
� An adjustable time delay from 0.3 to 30 s allows inhibition of the output relay if a transient fault occurs.� In the event of a voltage fault, the relay opens at the end of the time delay set by the user.� On energisation of the device with a fault measured, the relay stays open.� In the event of phase failure, the relay opens instantly.
Function diagrams
� Functions: � Phase failure.
� Overvoltage and undervoltage.
Tt: overvoltage and undervoltage threshold delay (adjustable on front panel).
30 % Un 30 % Un30 % Un
Phase L3
Phase L2
Phase L1
Relays
11-12/11-14
<U
>U
L1L2
L3
Tt Tt
Phases L1/L2/L3
Relays
Hysteresis
Hysteresis
Presentation, description :page 3/28
Characteristics:page 3/32
References, dimensions :page 3/33
3/32
3
Characteristics 3 Zelio Control - modular measurement and control relays 3
3-phase voltage control relays RM17 UB3 and RM35 UB3
Environment characteristicsConforming to standards NF EN 60255-6 and IEC 60255-6Product certifications Pending UL, CSA, GL, C-Tick, GOSTMarking �: 3/23/EEC and EMC 89/336/EEC
Ambient air temperature around the device
Storage °C - 40…+ 70Operation °C - 20…+ 50
Permissible relative humidity Conforming to IEC 60068-2-30 2 x 24 hours…+ 95 % RH at + 55 °C (without condensation)
Vibration resistance Conforming to IEC 60068-2-6 0.035 mm from 10…150 HzShock resistance Conforming to IEC 60068-2-27 5 gnDegree of protectionConforming to IEC 60529
Casing IP 30
Terminals IP 20Degree of pollution Conforming to IEC 60664-1 3Overvoltage category Conforming to IEC 60664-1 III
Insulation resistance Conforming to IEC 60664-1, 60255-5
> 500 MΩ, � 500 V
Rated insulation voltage Conforming to IEC 60664-1 V 400Insulation test voltage Dielectric test kV 2, � 50 Hz, 1 min.
Shock wave kV 4
Mounting positionwithout derating
In relation to normal vertical mounting plane
Any position
ConnectionMaximum c.s.a.Conforming to IEC 60947-1
Solid cable without cable end mm2 1 conductor: 0.5…4 (AWG 20…AWG 11)2 conductors: 0.5…2.5 (AWG 20…AWG 14)
Flexible cable with cable end mm2 1 conductor: 0.2…2.5 (AWG 24…AWG 12)2 conductors: 0.2…1.5 (AWG 24…AWG 16)
Tightening torque Conforming to IEC 60947-1 0.6…1 N.m / 5.3…8.8 Lbf.InHousing material Self-extinguishing plasticPower ON indicator Green LED
Relay state indicator Yellow LEDMounting Conforming to IEC/EN 60715 On 35 mm � rail
Supply characteristicsRelay type RM35 UB330 RM35 UB3N30 RM17 UB310
Rated supply voltage Un V � 3 x 220… 3 x 480 � 3 x 120… 3 x 277 � 3 x 208… 3 x 480Operating range V � 194…528 � 114…329 � 183…528 Frequency Of the power supply circuit 50/60 Hz ± 10 %
Galvanic isolation, supply/measurement NoMaximum power consumption VA ��2.9 ��3.9 ��1.8Immunity to microbreaks ms 50 5 80
Immunity to electromagnetic interferenceElectromagnetic compatibility Immunity NF EN 61000-6-2 / IEC 61000-6-2
Emission NF EN 61000-6-4NF EN61000-6-3IEC 61000-6-4IEC 61000-6-3
Input and measurement circuit characteristicsMeasurement range V � 194…528 � 114…329 � 183…528 Phase failure detection threshold V 194 114 183Frequency of the measured signal Hz 50…60 ± 15 % 50…60 ± 15 % 50…60 ± 10 %
Maximum measuring cycle ms 150/measurement as true rms valueFixed hysteresis 2 % UnSetting accuracy ± 10 % of the full scale value
Repeat accuracy (with constant parameters) ± 0.5 %Measurement error with voltage variation < 1 % over the whole rangeMeasurement error with temperature variation 0.05 % / °C
Time delay characteristicsDelay on crossing the threshold s 0.3…30, 0 + 10 %Repeat accuracy (with constant parameters) ± 1 %Reset time ms 1500
Response time in the event of a fault ms < 200Delay on pick-up ms 500
Presentation, description :page 3/28
Operation:pages 3/29 to 3/31
References, dimensions :page 3/33
3/33
3
Characteristics (continued),
references,dimensions,schemes 3
Zelio Control - modular measurement and control relays 3
3-phase voltage control relays RM17 UB3 and RM35 UB3
Output characteristicsRelay type RM35 UB330 RM35 UB3N30 RM17 UB310
Output type 1 C/O + 1 C/O contacts 1 C/O contactContact type Cadmium-free
Maximum switching voltage V �/� 250Rated breaking capacity VA 1250Maximum breaking current A �/� 5
Minimum breaking current mA 10/� 5 VMechanical durability 30 x 106 operating cyclesElectrical durability 1 x 104 operating cycles 1 x 105 operating cycles
Maximum operating rate 360 operations/hour under full loadUtilisation categories Conforming to IEC 60947-5-1 AC-12, AC-13, AC-14, AC-15, DC-12, DC-13, DC-14
ReferencesFunction Rated 3-phase
supply voltage Output Reference Weight
V kg� Overvoltage and
undervoltage between phases
� 220…480 (Phase-phase)
1 C/O+1 C/O1 per threshold5 A
RM35 UB330 0.130
� 208…480(Phase-phase)
1 C/O5 A
RM17 UB310 0.080
� Overvoltage and undervoltage between phases and neutral
� Absence of neutral
� 120…277 (Phase-neutral)
1 C/O+1 C/O1 per threshold5 A
RM35 UB3N30 0.130
DimensionsRM35 UB330, RM35 UB3N30 RM17 UB310
mm/In.
SchemesRM35 UB330 RM17 UB310 RM35 UB3N30
RM17 UB310RM35 UB330
1064
38
1056
64
RM35 UB3N30
1056
69
2,8
0.11
76/2.99
72,5/2.85
72/2.83
90/3
.54
35/1.38
2,8
0.11
76/2.99
72,5/2.85
72/2.83 17,50.69
90/3.54
L1 L2 L3
L1 L2
R1 R2
L3
1112 14 22 21 24
2111
12 14 2422
L1 L2 L3
L1 L2
R
L3
1112 14
11
12 14
L1 L2 L3 (N)
(N)L1 L2 L3
1112 14 22 21 24
2111
12 14 2422
R1 R2
Presentation, description :page 3/28
Operation:pages 3/29 to 3/31
Characteristics:page 3/32
3/34
3
Presentation,description 3
Zelio Control - modular measurement and control relays 3
Single-phase and d.c. voltage control relays RM17 UAS and RM17 UBE
Presentation Single-phase and d.c. voltage measurement and control relays RM17 UAS�� and RM17 UBE�� monitor:
RM17 UAS14 UAS15 UAS16 UBE15 UBE16
OvervoltageUndervoltageOvervoltage and undervoltage (window mode)Nominal voltages (V) � 12 �/�
110…240�/� 24…48
�/� 110…240
�/� 24…48
They allow selection of operating mode.They monitor their own supply voltage, measured as a true rms value.Settings are protected by a sealable cover.Control status is indicated by a LED.The relays are designed for clip-on mounting on � rail
Applications� Protection of electronic or electromechanical devices against overvoltage and undervoltage.� Normal/emergency power supply switching.
DescriptionRM17 UAS��������
1 Configuration: selection of operating mode <U / >U, (with or without memory). Memory - No Memory
2 Setting potentiometer3 Hysteresis adjustment potentiometer H4 Time delay setting potentiometer, Tt5 Spring for clip-on mounting on 35 mm� rail.
Un Green LED: indicates that supply to the relay is on.R Yellow LED: indicates relay output state.
RM17 UBE1����
1 Maximum voltage range selection and setting potentiometer.
2 Minimum voltage range selection and setting potentiometer.
3 Time delay setting potentiometer. Tt4 Spring for clip-on mounting on 35 mm � rail.
Un Green LED: indicates that supply to the relay is on.R Yellow LED: indicates relay output state.
RM17 UAS�� RM17 UBE��
1064
42
1064
44
Function performed
Function not performed
A1 A2
12 11 14
R
<U >U
Un
1234
5
12 11 14
R
Un
123
4
A1 A2
Operation:pages 3/35 and 3/36
Characteristics:pages 3/37 and 3/38
References:page 3/38
Dimensions, schemes :page 3/39
3/35
3
Operation 3 Zelio Control - modular measurement and control relays 3
Single-phase and d.c. voltage control relays RM17 UAS and RM17 UBE
Operating principleVoltage control relays RM17 UAS and RM17 UBE monitor: � The voltages of single-phase and d.c. supplies.
These products monitor their own supply voltage.
RM17 UAS�� relays give the user a choice of two operating modes: � Overvoltage or undervoltage,� Fault memory selected or not.
An adjustable time delay, on crossing the thresholds, provides immunity to transients, so preventing spurious triggering of the output relay.
Fault signalling is by LED.
Overvoltage or undervoltage control relays: RM17 UAS14, UAS15 and UAS16The operating mode is fixed by the user: A switch allows selection between the following modes:� Undervoltage with or without memory� Overvoltage with or without memory.
The position of the switch, and therefore the operating mode, is read by the product on energisation.If the switch is set to an unacceptable position, the product detects a fault, the output relay stays open and the LEDs flash to signal the position error.If the switch position is changed while the device is operating, all the LEDs flash, but the product continues to operate normally with the function selected at the time of energisation preceding the change of position.The LED's return to their normal state if the switch is returned to the original position selected prior to the last energisation.
The undervoltage or overvoltage threshold value is set by means of a graduated potentiometer clearly indicating the Un to be monitored.The hysteresis is adjusted by means of a potentiometer graduated from 5…20 % of the threshold setting. The hysteresis value must not exceed the limit values of the measuring range.If the voltage controlled exceeds the threshold setting for a time greater than that set on the front panel (0.1…10 s), the output relay opens and LED R goes out. As soon as the voltage returns to a value above (or below) the threshold setting minus (or respectively plus) the hysteresis, the relay instantly closes.
"Memory" modeIf "Memory" mode is selected, the relay opens when crossing of the threshold is detected and then stays in that position. The power must be switched off to reset the product.
Function diagrams
� Function: Undervoltage control. <U� without memory. No Memory
� with memory. Memory
11-12/11-14
U
U
Tt
<
Relays
Hysteresis
Supply Un
Threshold
Tt11-12/11-14
UU <
Relays
Hysteresis
Supply Un
Threshold
� Function: Overvoltage control. >U� without memory. No Memory
� with memory. Memory
Tt: time delay after crossing of threshold
11-12/11-14
U >
Tt
URelays
Threshold
Supply Un
Hysteresis
11-12/11-14
U >
U
TtRelays
Threshold
Supply Un
Hysteresis
Presentation, description :page 3/34
Characteristics:pages 3/37 and 3/38
References:page 3/38
Dimensions, schemes :page 3/39
3/36
3
Operation (continued) 3 Zelio Control - modular measurement and control relays 3
Single-phase and d.c. voltage control relays RM17 UAS and RM17 UBE
Overvoltage and undervoltage control relays: RM17 UBE15 and UBE16Relays RM17 UBE operate in window mode: they check that the voltage controlled stays between a minimum threshold and a maximum threshold.
The undervoltage or overvoltage threshold values are set by means of two graduated potentiometers clearly indicating the Un to be monitored.
The hysteresis is fixed at: 3 % of the threshold setting.
If the voltage controlled exceeds the high threshold setting, or falls below the low threshold setting for a time greater than that set on the front panel (0.1…10 s), the output relay opens and LED R goes out. During the time delay, this LED flashes.As soon as the voltage falls below the high threshold setting value minus the hysteresis, or rises above the low threshold setting value plus the hysteresis, the relay instantly closes.
On energisation of the device with a fault measured, the relay stays open.
Function diagrams
� Function: Control of overvoltage and undervoltage in window mode. <U<
Tt: time delay after crossing of threshold
11-12/11-14
Tt Tt
U
U >
U <
Relays
Hysteresis
Supply Un
ThresholdHysteresis
Threshold
Presentation, description :page 3/34
Characteristics:pages 3/37 and 3/38
References:page 3/38
Dimensions, schemes :page 3/39
3/37
3
Characteristics 3 Zelio Control - modular measurement and control relays 3
Single-phase and d.c. voltage control relays RM17 UAS and RM17 UBE
Environment characteristicsConforming to standards NF EN 60255-6 and IEC 60255-6Product certifications Pending UL, CSA, GL, C-Tick, GOSTMarking ����: 73/23/EEC and EMC 89/336/EEC
Ambient air temperature around the device
Storage °C - 40…+ 70Operation °C - 20…+ 50
Permissible relative humidity Conforming to IEC 60068-2-30 2 x 24 hours…+ 95 % RH at + 55 °C (without condensation)Vibration resistance Conforming to IEC 60068-2-6 0.035 mm from 10…150 Hz
Shock resistance Conforming to IEC 60068-2-6 5 gnDegree of protectionConforming to IEC 60529
Casing IP 30Terminals IP 20
Degree of pollution Conforming to IEC 60664-1 3
Overvoltage category Conforming to IEC 60664-1 IIIInsulation resistance Conforming to 60664-1/60255-5 > 500 MΩ, � 500 VRated insulation voltage Conforming to IEC 60664-1 V 250 or 400
Insulation test voltageConforming to IEC 60664-1/60255-5
Dielectric test kV 2, � 50 Hz, 1 min.Shock wave kV 4 (1.2/50 µs)
ConnectionMaximum c.s.a.Conforming to IEC 60947-1
Solid cable without cable end mm2 1 conductor: 0.5…4 (AWG 20…AWG 11)2 conductors: 0.5…2.5 (AWG 20…AWG 14)
Flexible cable with cable end mm2 1 conductor: 0.2…2.5 (AWG 24…AWG 12)2 conductors: 0.2…1.5 (AWG 24…AWG 16)
Tightening torque Conforming to IEC 60947-1 0.6…1 N.m / 5.3…8.8 Lbf.InHousing material Self-extinguishing plastic
Power ON indicator Green LEDRelay state indicator Yellow LED (flashes during the time delay on crossing the threshold)Mounting positionwithout derating
In relation to normal vertical mounting plane
Any position
Mounting Conforming to IEC/EN 60715 On 35 mm � rail
Supply characteristicsRelay type RM17 UAS14 RM17 UAS16
RM17 UBE16RM17 UAS15RM17 UBE15
Rated supply voltage Un V � 12 �/� 24…48 �/� 110…240Operating range V � 7…20 �/� 15…100 �/� 50… 270Setting range V � 9…15 �/� 20…80 �/� 65…260
Polarity on d.c. supply YesFrequency Of the power supply circuit Hz 50/60 Hz ± 10 %Galvanic isolation, supply/measurement No
Maximum power consumption at Un � 1 W � 1.6 W, � 3.9 VA � 1 W, � 3 VAImmunity to microbreaks ms 20 at 12 V 20
Immunity to electromagnetic interferenceElectromagnetic compatibility Immunity NF EN 61000-6-2 / IEC 61000-6-2
Emission NF EN 61000-6-4NF EN 61000-6-3 IEC 61000-6-4IEC 61000-6-3
Input and measurement circuit characteristicsFrequency of the measured signal Hz 50…60 ± 10 %
Maximum measuring cycle ms 250/measurement as true rms valueAdjustable hysteresis or fixed hysteresis RM17 UAS�� 5…20 % of the threshold setting
RM17 UBE�� 3 % of the fixed threshold setting
Setting accuracy 10 % of the full scale valueRepeat accuracy (with constant parameters) ± 0.5 %Measurement error with voltage variation < 1 % over the whole range
Measurement error with temperature variation 0.2 %/ °C
Time delay characteristicsTime delay on crossing the threshold s 0.1…10, 0 + 10 %Repeat accuracy (with constant parameters) ± 1 %
Reset time s 1.5Delay on pick-up ms � 500 / � 1000
Presentation, description :page 3/34
Operation:pages 3/35 and 3/36
References:page 3/38
Dimensions, schemes :page 3/39
3/38
3
Characteristics (continued),references 3
Zelio Control - modular measurement and control relays 3
Single-phase and d.c. voltage control relays RM17 UAS and RM17 UBE
Output characteristicsType of output 1 C/O contact
Contact type Cadmium-free
Maximum switching voltage V �/� 250
Rated breaking capacity VA 1250
Minimum breaking current mA 10/ � 5 V
Maximum breaking current A �/� 5
Electrical durability 1 x 105 operating cycles
Mechanical durability 30 x 106 operating cycles
Maximum operating rate 360 operations/hour under full load
Utilisation categories Conforming to IEC 60947-5-1 AC-12, AC-13, AC-14, AC-15, DC-12, DC-13, DC-14
ReferencesFunction Ranges
controlledNominal voltage
Out-put
Reference Weight
V V kg
� Overvoltage or undervoltage
� 9…15 � 12 1 C/O5 A
RM17 UAS14 0.080
�/� 20…80 �/� 24…48 1 C/O5 A
RM17 UAS16 0.080
�/� 65…260 �/� 110…240 1 C/O5 A
RM17 UAS15 0.080
� Overvoltage and undervoltagein window mode
�/� 20…80 �/� 24…48 1 C/O5 A
RM17 UBE16 0.080
�/� 65…260 �/� 110…240 1 C/O5 A
RM17 UBE15 0.080
RM17 UAS14 RM17 UAS16 RM17 UAS15
1064
42
1064
41
1064
42
RM17 UBE16 RM17 UBE15
1064
44
1064
43
Presentation, description :page 3/34
Operation:pages 3/35 and 3/36
Characteristics:pages 3/37 and 3/38
Dimensions, schemes :page 3/39
3/39
3
Dimensions,schemes 3
Zelio Control - modular measurement and control relays 3
Single-phase and d.c. voltage control relays RM17 UAS and RM17 UBE
DimensionsRM17 UAS�������� RM17 UBE��������
mm/In.
SchemesRM17 UAS14 RM17 UAS16, RM17 UAS15, RM17 UBE��������
Application scheme
17,50.69
90/3.54
A1 A2
12 11 14
R
Un
72/2.83
2,8
0.11
76/2.99
72,5/2.85
72/2.83
2,8
0.11
76/2.99
72,5/2.8517,5
0.69
90
/3.5
4
A1 A2
12 11 14
A1 – A2 +
1112 14
A1
A2
11
12 14
R
1112 14
A1
A2
11
12 14
R
A1 + A2 –
111412
Q2
12
Q2
12
Q11/L1 2
3/L2 4
5/L3 6
Q4
RM17 U
A2
A1
To sensitive loads
Presentation, description :page 3/34
Operation:pages 3/35 and 3/36
Characteristics:pages 3/37 and 3/38
References:page 3/38
3/40
3
Presentation,description 3
Zelio Control - modular measurement and control relays 3
Multifunction voltage control relays RM35 UA
Presentation Multifunction voltage control relays RM35 UA1�MW monitor both a.c. and d.c. voltages.� Automatic � or � recognition,� Measurement ranges from 0.05 V to 600 V,� Selection between overvoltage and undervoltage,� Measurement as true rms value,� Selectable memory function.
Settings are protected by a sealable cover.
Control status is indicated by a LED.
The relays are designed for clip-on mounting on � rail
Applications� d.c. motor overspeed control,� Battery monitoring,� Monitoring of a.c. or d.c. supplies,� Speed monitoring (with tacho-generator).
DescriptionRM35 UA11MW, UA12MW, UA13MW
1 Configuration: selection of operating mode <U / >U, (with or without memory) Memory - No Memory
2 Voltage threshold setting potentiometer. U Value
3 Hysteresis adjustment potentiometer. H4 Time delay setting potentiometer. Tt5 Spring for clip-on mounting on 35 mm � rail.
Un Green LED: indicates that supply to the relay is on.R Yellow LED: indicates relay output state.
RM35 UA1�MW
1056
78
5
A1
12 22 21 241411
A2 E3 E2 E1 M
Un
R
< U > U
1234
Operation:page 3/41
Characteristics:page 3/42
References, dimensions :page 3/43
3/41
3
Operation 3 Zelio Control - modular measurement and control relays 3
Multifunction voltage control relays RM35 UA
Operating principleControl relays RM35 UA1�MW are designed for the monitoring of a.c. or d.c. voltages.
They automatically recognise the form of the � or � (50 or 60 Hz) signal.
Fault signalling is by LED.
Overvoltage and undervoltage control relays: RM35 UA11MW, UA12MW and UA13MW � The operating mode is fixed by the user : A switch allows selection between the following modes: � Undervoltage with or without memory,� Overvoltage with or without memory.
The position of the switch, and therefore the operating mode, is read by the product on energisation.If the switch is set to an unacceptable position, the product detects a fault, the output relay stays open and the LEDs flash to signal the position error.If the switch position is changed while the device is operating, all the LEDs flash, but the product continues to operate normally with the function selected at the time of energisation preceding the change of position.The LED's return to their normal state if the switch is returned to the original position selected prior to the last energisation.
The undervoltage or overvoltage threshold value is set by means of a potentiometer graduated as a percentage of the scale value of Un to be monitored.The hysteresis is adjusted by means of a potentiometer graduated from 5…50 % of the threshold setting. The hysteresis value must not exceed the limit values of the measuring range.In overvoltage mode, if the voltage controlled exceeds the threshold setting for a time greater than that set on the front panel (0.3…30 s), the output relay opens and LED R goes out. During the time delay, this LED flashes.As soon as the voltage drops below the value of the threshold setting, minus the hysteresis, the relay instantly closes. In undervoltage mode, if the voltage controlled falls below the threshold setting for a time greater than that set on the front panel (0.3…30 s), the output relay opens and LED R goes out. During the time delay, this LED flashes.As soon as the voltage rises above the value of the threshold setting, plus the hysteresis, the relay instantly closes.
� "Memory" mode : If "Memory" mode is selected, the relay opens when crossing of the threshold is detected and then stays in that position.The power must be switched off to reset the product.
Function diagrams
� Function: Undervoltage control. < U� without memory. No Memory
� with memory. Memory
11-12/11-1421-22/21-24
U
U
Tt
<
Relays
Hysteresis
Supply Un
Threshold
11-12/11-1421-22/21-24
U
Tt
U <
Relays
Hysteresis
Supply Un
Threshold
� Function: Overvoltage control. > U� without memory. No Memory
� with memory. Memory
Tt: time delay after crossing of threshold (adjustable on front panel)
11-12/11-1421-22/21-24
U >
Tt
URelays
Hysteresis
Supply Un
Threshold
11-12/11-1421-22/21-24
U >
U
Tt
Relays
Hysteresis
Supply Un
Threshold
Presentation, description :page 3/40
Characteristics:page 3/42
References, dimensions :page 3/43
3/42
3
Characteristics 3 Zelio Control - modular measurement and control relays 3
Multifunction voltage control relays RM35 UA
Environment characteristicsConforming to standards NF EN 60255-6 and IEC 60255-6Product certifications Pending UL, CSA, GL, C-Tick, GOSTMarking �: 73/23/EEC and EMC 89/336/EEC
Ambient air temperature around the device
Storage °C - 40…+ 70Operation °C - 20…+ 50
Permissible relative humidity Conforming to IEC 60068-2-30 2 x 24 hours…+ 95 % RH at + 55 °C (without condensation)Vibration resistance Conforming to IEC 60068-2-6 0.035 mm from 10…150 Hz
Shock resistance Conforming to IEC 60068-2-6 5 gnDegree of protectionConforming to IEC 60529
Casing IP 30Terminals IP 20
Degree of pollution Conforming to IEC 60664-1 3
Overvoltage category Conforming to IEC 60664-1 IIIInsulation resistance Conforming to 60664-1/60255-5 > 500 MΩ, � 500 VRated insulation voltage Conforming to IEC 60664-1 V 250 or greater (measured at 600 V)
Insulation test voltageConforming to IEC 60664-1/60255-5
Dielectric test kV 2, � 50 Hz, 1 min.Shock wave kV 4 (1.2/50 µs)
ConnectionMaximum c.s.a.Conforming to IEC 60947-1
Solid cable without cable end mm2 1 conductor: 0.5…4 (AWG 20…AWG 11)2 conductors: 0.5…2.5 (AWG 20…AWG 14)
Flexible cable with cable end mm2 1 conductor: 0.2…2.5 (AWG 24…AWG 12)2 conductors: 0.2…1.5 (AWG 24…AWG 16)
Tightening torque Conforming to IEC 60947-1 0.6…1 N.m / 5.3…8.8 Lbf.InHousing material Self-extinguishing plastic
Power ON indicator Green LEDRelay state indicator Yellow LEDMounting positionwithout derating
In relation to normal vertical mounting plane
Any position
Mounting Conforming to IEC/EN 60715 On 35 mm � rail
Supply characteristicsRated supply voltage Un V �/� 24…240Operating range V �/� 20.4… 264Polarity on d.c. supply No
Voltage limits Of the power supply circuit - 15 %, + 10 %Frequency Of the power supply circuit 50/60 Hz ± 10 %Galvanic isolation, supply/measurement Yes
Maximum power consumption ��3.5 VA, ��0.6 WImmunity to microbreaks ms 10
Immunity to electromagnetic interferenceElectromagnetic compatibility Immunity NF EN 61000-6-2 / IEC 61000-6-2
Emission NF EN 61000-6-4NF EN 61000-6-3 IEC 61000-6-4IEC 61000-6-3
Input and measurement circuit characteristicsRelay type RM35 UA11MW RM35 UA12MW RM35 UA13MW
Measurement range V 0.05…5 1…100 15…600Sub-measurement range E1-M V 0.05…0.5 1…10 15…150
E2-M V 0.3…3 5…50 30…300E3-M V 0.5…5 10…100 60…600
Input resistance E1-M kΩ 5 22 150E2-M kΩ 30 110 300
E3-M kΩ 50 220 600
Frequency of the measured signal Hz 40…70 ± 10 %Maximum measuring cycle ms 30/measurement as true rms valueThreshold setting 10…100 % of the range
Adjustable hysteresis or fixed hysteresis 5…50 % of the threshold settingSetting accuracy 10 % of the full scale valueRepeat accuracy (with constant parameters) ± 0.5 %
Measurement error with voltage variation < 1 % / V over the whole rangeMeasurement error with temperature variation ± 0.05 % / °C
Presentation, description :page 3/40
Operation:page 3/41
References, dimensions :page 3/43
3/43
3
Characteristics (continued)
references,dimensions,schemes 3
Zelio Control - modular measurement and control relays 3
Multifunction voltage control relays RM35 UA
Time delay characteristicsTime delay on crossing the threshold Tt s 0.3…30, 0 + 10 %Repeat accuracy (with constant parameters) ± 2 %Reset time s 1.5
Delay on pick-up ms 600
Output characteristicsType of output 2 C/O contactsContact type Cadmium-free
Maximum switching voltage V �/� 250Rated breaking capacity VA 1250Minimum breaking current mA 10/ � 5 V
Maximum breaking current A �/� 5Electrical durability 1 x 105 operating cyclesMechanical durability 30 x 106 operating cycles
Maximum operating rate 360 operations/hour under full loadUtilisation categories Conforming to IEC 60947-5-1 AC-12, AC-13, AC-14, AC-15, DC-12, DC-13, DC-14
ReferencesFunction Range
controlledSupply voltage
Output Reference Weight
V V kg
� Over-voltage or undervoltage
0.05…5 �/� 24…240 2 C/O5 A
RM35 UA11MW 0.130
1…100 �/� 24…240 2 C/O5 A
RM35 UA12MW 0.130
15…600 �/� 24…240 2 C/O5 A
RM35 UA13MW 0.130
Dimensions Application schemeRM35 UA1����MW Example: overspeed monitoring (undervoltage function)
mm/In.
SchemeRM35 UA1����MW
RM35 UA11MW
1056
78
RM35 UA12MW
1056
79
RM35 UA13MW
1056
80
90/3
.54
72/2.83
2,8
0.11
76/2.99
72,5/2.85
35/1.38
A1
12 22 21 241411
A2 E3 E2 E1 M
111412
212422
KM1
KM1
KM1
12
3
1 1
1
2
2
4
56
U1
W1
V1
M1 3
A1
A2
E2
M
RM35 UA12MW
N
Q1
1/L1
2
3/L2
4
5/L3
6
Q2
Q3 Q42
U
V
Overspeed StartOverspeed
Tacho-generator
Stop
A1 A2 E3 E2 E1 M
12 11 14 22 21 24
A1
A2
11
12 14
21
22 24
R
Presentation, description :page 3/40
Operation:page 3/41
Characteristics:page 3/42
3/44
3
Presentation,description 3
Zelio Control - modular measurement and control relays 3
Current control relays RM17 JC
Presentation The control relay RM17 JC00MW is designed to monitor a.c. currents.
� Integrated current transformer,� Measurement range 2…20 A,� Choice of action on the output relay.
Control status is indicated by a LED.
The relay is designed for clip-on mounting on � rail
Applications� Monitoring of load state of motors and generators,� Monitoring of current drawn by a 3-phase motor,� Monitoring of heating or lighting circuits,� Monitoring of pump draining (undercurrent),� Monitoring of overtorque (crushers),� Monitoring of electromagnetic brakes or clutches.
DescriptionRM17 JC00MW
1 Overcurrent setting potentiometer.2 Spring for clip-on mounting on 35 mm � rail.
Un Green LED: indicates that supply to the relay is on.R Yellow LED: indicates relay output state.
RM17 JC00MW
1064
45
A1 Y1 A2
12 11 14
Un
R1
2
Operation:page 3/45
Characteristics:page 3/46
References, dimensions :page 3/47
3/45
3
Operation 3 Zelio Control - modular measurement and control relays 3
Current control relays RM17 JC
Operating principle� Control relay RM17 JC00MW is designed to monitor overcurrent.� It is equipped with an integrated current transformer
Fault signalling is by LED.
Current control relayRelay RM17 JC00MW controls overcurrent. The relay closes when the current exceeds the threshold setting on the front panel and opens when it drops below the threshold minus the hysteresis.When terminal Y1 is linked to A1 (+), the output is reversed. The relay opens when the current exceeds the threshold setting on the front panel and closes again when it drops below the hystereris value.
Function diagram
I>
I
Y1 A1
Y1 A1 11-1211-14
11-1211-14
Relays
Relays
Hysteresis
Supply Un
Presentation, description :page 3/44
Characteristics:page 3/46
References, dimensions :page 3/47
3/46
3
Characteristics 3 Zelio Control - modular measurement and control relays 3
Current control relays RM17 JC
Environment characteristicsConforming to standards NF EN 60255-6 and IEC 60255-6Product certifications Pending UL, CSA, GL, C-Tick, GOSTMarking ����: 73/23/EEC and EMC 89/336/EEC
Ambient air temperature around the device
Storage °C - 40…+ 70Operation °C - 20…+ 50
Permissible relative humidity Conforming to IEC 60068-2-30 2 x 24 hours…+ 95 % RH at + 55 °C (without condensation)
Vibration resistance Conforming to IEC 60068-2-6 0.035 mm from 10…150 HzShock resistance Conforming to IEC 60068-2-6 5 gnDegree of protectionConforming to IEC 60529
Casing IP 30
Terminals IP 20Degree of pollution Conforming to IEC 60664-1 3Overvoltage category Conforming to IEC 60664-1 III
Insulation resistance Conforming to 60664-1/60255-5 > 500 MΩ, � 500 VRated insulation voltage Conforming to IEC 60664-1 V 400Insulation test voltage Dielectric test kV 2, � 50 Hz, 1 min.
Shock wave kV 4Mounting positionwithout derating
In relation to normalvertical mounting plane
Any position
ConnectionMaximum c.s.a.Conforming to IEC3 60947-1
Solid cable without cable end mm2 1 conductor: 0.5…4 (AWG 20…AWG 11)2 conductors: 0.5…2.5 (AWG 20…AWG 14)
Flexible cable with cable end mm2 1 conductor: 0.2…2.5 (AWG 24…AWG 12)2 conductors: 0.2…1.5 (AWG 24…AWG 16)
Tightening torque Conforming to IEC 60947-1 0.6…1 N.m / 5.3…8.8 Lbf.InHousing material Self-extinguishing plastic
Power ON indicator Green LEDRelay state indicator Yellow LEDMounting Conforming to IEC/EN 60715 On 35 mm � rail
Supply characteristicsRated supply voltage Un V �/� 24…240Operating range V �/� 20.4…264
Polarity on d.c. supply YesVoltage limits Of the power supply circuit - 15 %, + 10 %Frequency Of the power supply circuit Hz 50/60 Hz ± 10 %
Galvanic isolation, supply/measurement YesMaximum power consumption VA 3 VA, 1 WImmunity to microbreaks ms 10
Immunity to electromagnetic interferenceElectromagnetic compatibility Immunity NF EN 61000-6-2 / IEC 61000-6-2
Emission NF EN 61000-6-4, NF EN 61000-6-3, IEC 61000-6-4, IEC 61000-6-3
Input and measurement circuit characteristicsMeasurement range A 2…20
Continuous overload at 25 °C A 100Non repetitive overload < 3 s at 25 °C A 300Frequency of the measured signal Hz 40…70 sinusoidal
Maximum measuring cycle ms 30, measured as true rms valueAdjustment of current threshold % 10…100 % of the rangeFixed hysteresis % 15 % of the threshold setting, fixed
Setting accuracy ± 10 % of the full scale valueRepeat accuracy (with constant parameters) ± 0,5 %Measurement error with voltage variation < 1 % / V over the whole range
Measurement error with temperature variation ± 0,05 % / °C
Time delay characteristicsTime delay in the event of a fault ms < 200
Delay on pick-up ms 500
Output characteristicsOutput type 1 C/O contact
Contact type Cadmium-freeNominal current A 5Maximum switching voltage V �/� 250
Rated breaking capacity VA 1250Minimum breaking current mA 10 / � 5 VElectrical durability 1 x 105 operating cycles
Mechanical durability 30 x 106 operating cyclesMaximum operating rate 360 operations/hour under full loadUtilisation categories Conforming to IEC 60947-5-1 AC-12, AC-13, AC-14, AC-15, DC-12, DC-13, DC-14
Presentation, description :page 3/44
Operation:page 3/45
References, dimensions :page 3/47
3/47
3
Reference,dimensions,scheme 3
Zelio Control - modular measurement and control relays 3
Current control relays RM17 JC
ReferenceFunction Supply Measure-
ment range
Output Reference Weight
V A kg� Overcurrent �/� 24…240 2…20 1 C/O
5 ARM17 JC00MW 0,110
DimensionsRM17 JC00MW
mm/In.
SchemeRM17 JC00MW
RM17 JC00MW
1064
45
97/3.82 17,50.69
90/3
.54
2,8
0.11
101/3.98
97,5/3.84
10/0.39
12 1411
11
12 14
A1 A2Y1
RI>
Presentation, description :page 3/44
Operation:page 3/45
Characteristics:page 3/46
3/48
3
Presentation,description 3
Zelio Control - modular measurement and control relays 3
Current control relays RM35 JA
Presentation Multifunction current control relays RM35 JA3�MW monitor both a.c. and d.c. currents.� Automatic � or � recognition,� Measurement ranges from 2 mA to 15 A, � Selection between overcurrent and undercurrent,� Measurement as true rms value,� Selectable memory function.
Settings are protected by a sealable cover.
Control status is indicated by a LED.
The relays are designed for clip-on mounting on � rail
Applications� Excitation control of d.c. machines,� Control of load state of motors and generators,� Control of current drawn by a 3-phase motor,� Monitoring of heating or lighting circuits,� Control of pump draining (undercurrent),� Control of overtorque (crushers),� Monitoring of electromagnetic brakes or clutches.
DescriptionRM35 JA31MW, RM35 JA32MW
1 Configuration: selection of operating mode <I / >I, (with or without memory) Memory - No Memory.
2 Current threshold setting potentiometer. I %
3 Hysteresis adjustment potentiometer. Hysteresis
4 Time delay adjustment potentiometer. Tt5 Starting inhibit time delay adjustment
potentiometer. Ti6 Spring for clip-on mounting on 35 mm �
rail.
Un Green LED: indicates that supply to the relay is on.R Yellow LED: indicates relay output state.
RM35 JA3�MW
1056
82
A1
12 22 21 241411
A2 E3 E2 E1 M
< I > I
UnR
6
12345
Operation:page 3/49
Characteristics:page 3/50
References, dimensions :page 3/51
3/49
3
Operation 3 Zelio Control - modular measurement and control relays 3
Current control relays RM35 JA
Operating principleControl relays RM35 JA3�MW are designed for the monitor of a.c. or d.c. currents.
They automatically recognise the form of the � or � (50 or 60 Hz) signal and can provide direct monitor up to 15 A. Above this value, a current transformer can be connected.
Fault signalling is by LED.
a.c. or d.c. current control relays: RM35 JA31MW and JA32MWThe operating mode is fixed by the user: A switch allows selection between the following modes: � Undercurrent, with or without memory,� Overcurrent, with or without memory.The position of the switch, and therefore the operating mode, is read by the product on energisation.If the switch is set to an unacceptable position, the product detects a fault, the output relay stays open and the LEDs flash to signal the position error.If the switch position is changed while the device is operating, all the LEDs flash, but the product continues to operate normally with the function selected at the time of energisation preceding the change of position.The LED's return to their normal state if the switch is returned to the original position selected prior to the last energisation.
The undercurrent or overcurrent threshold value is set by means of a potentiometer graduated as a percentage of the scale value of I to be monitored.The hysteresis is adjusted by means of a potentiometer graduated from 5…50 % of the threshold setting. The hysteresis value must not exceed the limit values of the measuring range.In overcurrent (undercurrent) mode, if the current exceeds (falls below) the threshold setting for a time greater than that set on the front panel (0.3…30 s), the relays open and the LED goes out.As soon as the current returns to below (above) the threshold minus (plus) hysteresis, the relay instantly closes again.
"Memory" mode: If "Memory" mode is selected, the relay opens when crossing of the threshold is detected and then stays in that position.The power must be switched off to reset the product.
On energisation, an inhibit time delay (1…20 s) makes it possible to inhibit current peaks (or troughs) on start-up of equipment.
Function diagrams
� Function: Undercurrent detection. < I� without memory. No Memory
� with memory. Memory
�
11-12/11-1421-22/21-24
TiTt Tt Ti
II <
Relays
Hysteresis
Supply Un
Threshold
11-12/11-1421-22/21-24
Ti Ti
II <
Tt Tt
Relays
Hysteresis
Supply Un
Threshold
� Function: Overcurrent detection. > I� without memory. No Memory
� with memory. Memory
Ti: starting inhibit time (adjustable on front panel)Tt: time delay after crossing of threshold (adjustable on front panel)
11-12/11-1421-22/21-24
Tt Tt TiTi
I
I >
Relays
Hysteresis
Supply Un
Threshold
11-12/11-1421-22/21-24
Ti Tt Ti
II >
Tt
Relays
Hysteresis
Supply Un
Threshold
Presentation, description :page 3/48
Characteristics:page 3/50
References, dimensions :page 3/51
3/50
3
Characteristics 3 Zelio Control - modular measurement and control relays 3
Current control relays RM35 JA
Environment characteristicsConforming to standards NF EN 60255-6 and IEC 60255-6Product certifications Pending UL, CSA, GL, C-Tick, GOSTMarking �: 73/23/EEC and EMC 89/336/EEC
Ambient air temperature around the device
Storage °C - 40…+ 70Operation °C - 20…+ 50
Permissible relative humidity Conforming to IEC 60068-2-30 2 x 24 hours…+ 95 % RH at + 55 °C (without condensation)
Vibration resistance Conforming to IEC 60068-2-6 0.035 mm from 10…150 HzShock resistance Conforming to IEC 60068-2-6 5 gnDegree of protectionConforming to IEC 60529
Casing IP 30
Terminals IP 20Degree of pollution Conforming to IEC 60664-1 3Overvoltage category Conforming to IEC 60664-1 III
Insulation resistance Conforming to 60664-1/60255-5 > 500 MΩ, � 500 VRated insulation voltage Conforming to IEC 60664-1 V 250Insulation test voltageTo IEC 60664-1/60255-5
Dielectric test kV 2, � 50 Hz, 1 min.
Shock wave kV 4 (1.2/50 µs)ConnectionMaximum c.s.a.Conforming to IEC 60947-1
Solid cable without cable end mm2 1 conductor: 0.5…4 (AWG 20…AWG 11)2 conductors: 0.5…2.5 (AWG 20…AWG 14)
Flexible cable with cable end mm2 1 conductor: 0.2…2.5 (AWG 24…AWG 12)2 conductors: 0.2…1.5 (AWG 24…AWG 16)
Tightening torque Conforming to IEC 60947-1 0.6…1 N.m / 5.3…8.8 Lbf.InHousing material Self-extinguishing plastic
Power ON indicator Green LEDRelay state indicator Yellow LEDMounting positionwithout derating
In relation to normal vertical mounting plane
Any position
Mounting Conforming to IEC/EN 60715 On 35 mm � rail
Supply characteristicsRated supply voltage Un V �/� 24…240Operating range V �/� 20.4… 264Polarity on d.c. supply No
Voltage limits Of the power supply circuit - 15 %, + 10 %Frequency Of the power supply circuit 50/60 Hz ± 10 %Galvanic isolation, supply/measurement Yes
Maximum power consumption ��3.5 VA, ��0.6 WImmunity to microbreaks ms 50
Immunity to electromagnetic interferenceElectromagnetic compatibility Immunity NF EN 61000-6-2 / IEC 61000-6-2
Emission NF EN 61000-6-4, NF EN 61000-6-3, IEC 61000-6-4, IEC 61000-6-3
Measurement circuit and input characteristicsRelay type RM35 JA31MW RM35 JA32MW
Measurement range 2…500 mA 0.15…15 ASub-measurement range E1-M 2…20 mA 0.15…1.5 A
E2-M 10…100 mA 0.5…5 A
E3-M 50…500 mA 1.5…15 AInput resistance E1-M Ω 5 0.05
E2-M Ω 1 0.015
E3-M Ω 0.2 0.005Frequency of the measured signal Hz 40…70 ± 10 %Maximum measuring cycle ms 30/measurement as true rms value
Threshold setting 10…100 % of the rangeAdjustable hysteresis 5…50 % of the threshold settingSetting accuracy ± 10 % of the full scale value
Repeat accuracy (with constant parameters) ± 0.5 %Measurement error with voltage variation 1 % / V over the whole rangeMeasurement error with temperature variation 0.05 % / °C
Time delay characteristicsTime delay on energisation Ti s 1…20, 0 + 10 %Time delay on crossing the threshold Tt s 0.3…30, 0 + 10 %Repeat accuracy (with constant parameters) ± 2 %
Reset time s 1.5Delay on pick-up ms 300
Presentation, description :page 3/48
Operation:page 3/49
References, dimensions :page 3/51
3/51
3
Characteristics (continued),
references,dimensions,schemes 3
Zelio Control - modular measurement and control relays 3
Current control relays RM35 JA
Output characteristicsType of output 2 C/O contactsContact type Cadmium-freeMaximum switching voltage V �/� 250
Rated breaking capacity VA 1250Minimum breaking current mA 10/ � 5 VMaximum breaking current A �/� 5
Electrical durability 1 x 105 operating cyclesMechanical durability 30 x 106 operating cyclesMaximum operating rate 360 operations/hour under full load
Utilisation categories Conforming to IEC 60947-5-1 AC-12, AC-13, AC-14, AC-15, DC-12, DC-13, DC-14
ReferencesFunction Range
controlledSupply Output Reference Weight
V kg� Overcurrent or
undercurrent2 …500 mA �/� 24…240 2 C/O
5 ARM35 JA31MW 0.130
0.15…15 A �/� 24…240 2 C/O5 A
RM35 JA32MW 0.130
Dimensions SchemeRM35 JA3����MW RM35 JA3����MW
mm/In.
Application schemesExample: detection of jamming on a crusher (overcurrent function)
Current measured ���� 15 A Current measured > 15 A
RM35 JA31MW
1056
82
RM35 JA32MW
1056
83
72/2.83
2,8
0.11
76/2.9972,5/2.85
90/3
.54
35/1.38
A1
12 22 21 241411
A2 E3 E2 E1 M A1 A2 E3 E2 E1 M
12 11 14 22 21 24
A1
A2
11
12 14
21
22 24
R
111412
212422
KM1
KM1
1/L1
2
3/L2
4
5/L3
6
Q1
2/T
1
4/T
2
6/T
3
1
Q2
3 5
KM1
12
34
56
U1
W1
V1
M1 3
E3
M
A1
A2
RM35 JA3
N
StartOK
Stop
111412
212422
KM1
KM1
1/L1
2
3/L2
4
5/L3
6
Q1
2/T
1
4/T
2
6/T
3
1
Q2
3 5
KM1
12
34
56
U1
W1
V1
M1 3
E3
M
A1
A2
RM35 JA3
N
StartOK
Stop
Presentation, description :page 3/48
Operation:page 3/49
Characteristics:page 3/50
3/94
3
Presentation 3 Zelio Control - industrial measurement and control relays 3
Voltage control relays RM4 U
1 Overvoltage setting potentiometer.2 Undervoltage setting potentiometer.3 Time delay function selector:
4 Potentiometer for setting time delay in seconds.
The voltage to be monitored is connected to terminals L1, L3 of the product.
There is no need to provide a separate power supply for RM4 UB relays, they are self-powered by terminals L1, L3.
If the voltage goes outside the range to be monitored, the output relay is de-energised:- overvoltage: the red LED “> U” illuminates,- undervoltage: the red LED “< U” illuminates.When the voltage returns towards its rated value, the relay is re-energised according to the hysteresis value (5 %) and the corresponding red LED goes out.A selector switch allows selection of an adjustable time delay from 0.1 s to 10 s. With function transient "over" or "under" voltages are not taken into account. With function all variations above or below are taken into account and re-energisation of the relay is delayed.In all cases, in order to be detected, the duration of the overvoltage or undervoltage must be greater than the measuring cycle time (80 ms).
t : time delay
FunctionsThese devices are designed for monitoring single-phase voltages.They have a transparent, hinged flap on their front face to avoid any accidental alteration of the settings. This flap can be directly sealed.
Applications� Protection of electronic or electromechanical devices against overvoltage and undervoltage.� Normal/emergency power supply switching.
PresentationRM4 UB
RM4 UB
12
3
4
RU
<U>U
Fault detection delayed.
Fault detection extended.
R Yellow LED: indicates relay state.U Green LED: indicates that supply to the RM4 is on.> U Red LED: overvoltage fault.< U Red LED: undervoltage fault.
Operating principle
Function diagram
t t
< t
t t t t t
< t
15/18 25/2815/16 25/26
15/18 25/2815/16 25/26
RM4 UB34RM4 UB35
UL1 L3 0 Volt
Setting > U0.95 x Setting > U
1.05 x Setting < USetting < U
Function
Function
References :page 3/95
Characteristics :page 3/96
Dimensions, schemes : page 3/97
5610
37
3/95
3
References 3 Zelio Control - industrial measurement and control relays 3
Voltage control relays RM4 U
Relays with adjustable voltage thresholdsAdjustabletime delay
Control threshold
Width Output relay
Reference Weight
s V mm kg0.1…10 Undervoltage
80…12050/60 HzOvervoltage160…220
22.5 2 C/O RM4 UB34 0.110
Undervoltage160…22050/60 HzOvervoltage220…300
22.5 2 C/O RM4 UB35 0.110
RM4 UB
Presentation :page 3/94
Characteristics :page 3/96
Dimensions, schemes : page 3/97
5610
38
3/96
3
Characteristics 3 Zelio Control - industrial measurement and control relays 3
Voltage control relays RM4 U
Output relay and operating characteristicsNumber of C/O contacts 2
Output relay state Energised during fault free operation.De-energised on detection of an overvoltage or undervoltage fault
Accuracy of the switching threshold setting
As % of the set value ± 3 %
Switching threshold drift Depending on the permissible ambient temperature
≤ 0.06 % per degree centigrade
Within the measuring range ≤ 0.5 %
Accuracy of thetime delay setting
As % of the full scale value ± 10 %
Time delay drift Within the measuring range ≤ 0.5 %
Depending on the rated operational temperature
≤ 0.07 % per degree centigrade
Hysteresis Fixed About 5 % of the de-energisation threshold
Measuring cycle ms ≤ 80
Measuring input characteristicsMinimum operational voltage V RM4: 60
RM4 UB35: 160
Maximum permissible voltage between L1 and L3
V RM4 UB34: 300
RM4 UB35: 300
Presentation :page 3/94
References :page 3/95
Dimensions, schemes : page 3/97
3/97
3
Dimensions,schemes 3
Zelio Control - industrial measurement and control relays 3
Voltage control relays RM4 U
DimensionsRM4 UB
Rail mounting Screw fixing
Connection schemesRM4 UB
L1, L3 Voltage to be monitored
15-18 1st C/O contact 15-16 of the output relay
25-28 2nd C/O contact25-26 of the output relay
Application schemeExample
80 22,5
78
89,5
82
66
78
L1 L3
18 15 1628 25 26
1815
16 2825
26
L1 L3
151816
Q2
12
Q2
12
Q11/L1 2
3/L2 4
5/L3 6
Q4
RM4 UB
L3L1
Tosensitiveloads
Presentation :page 3/94
References :page 3/95
Characteristics :page 3/96
3/98
3
Presentation 3 Zelio Control - industrial measurement and control relays 3
Voltage measurement relays RM4 U
1 Adjustment of voltage threshold as % of setting range max. value.2 Hysteresis adjustment from 5 to 30 % (2).3 Fine adjustment of time delay as % of setting range max. value.4 Switch combining: - selection of the timing range: 1s, 3s, 10s, 30s, no time delay,- selection of overvoltage (>) or undervoltage (<) detection.
See table below.
(1) Selection by switch on front face.(2) Value of voltage difference between energisation and de-energisation of the output relay
(% of the voltage threshold to be measured).
FunctionsThese devices are designed to detect when voltage rises above or drops below a preset threshold, on an a.c. or a d.c. supply.They have a transparent, hinged flap on their front face to avoid any accidental alteration of the settings. This flap can be directly sealed.
Relay type Voltage control Overvoltage or undervoltage detection (1)
Measuring range
RM4 UA0�� Yes No 50 mV…500 VRM4 UA3� Yes Yes 50 mV…500 V
Applications :- d.c. motor overspeed control,- battery monitoring,- monitoring of a.c. or d.c. supplies,- speed monitoring (with tacho-generator).
PresentationRM4 UA0�������� RM4 UA3����
Width 22.5 mm Width 22.5 mm
RM4 UA01
12
RU
1234
RU
R Yellow LED: indicates relay state.U Green LED: indicates that supply to the RM4 is on.
Table showing details for switch 4Switch position Function Time delay (t)< 0 Undervoltage control No time delay< 1 Undervoltage control 0.05 to 1 s
< 3 Undervoltage control 0.15 to 3 s< 10 Undervoltage control 0.5 to 10 s< 30 Undervoltage control 1.5 to 30 s
> 0 Overvoltage control No time delay> 1 Overvoltage control 0.05 to 1 s> 3 Overvoltage control 0.15 to 3 s
> 10 Overvoltage control 0.5 to 10 s> 30 Overvoltage control 1.5 to 30 s
References :page 3/100
Characteristics :page 3/101
Dimensions, schemes :page 3/102
Setting-up :page 3/103
5610
46
3/99
3
Presentation (continued) 3 Zelio Control - industrial measurement and control relays 3
Voltage measurement relays RM4 U
The supply voltage is connected to terminals A1-A2. The voltage to be monitored is connected to terminals B1, B2 or B3 and C.
Hysteresis is adjustable between 5 and 30%: for overvoltage h = (US1 - US2) / US1, for undervoltage h = (US2 - US1) / US1. A measuring cycle lasts only 80 ms, which allows rapid detection of changes in voltage.
Relay set for overvoltage detection (RM4 UA0� or selector on “>” for model RM4 UA3�) :If the voltage is > the setting threshold US1, the output relay is energised with or without a time delay. When the voltage returns to a value US2 below the threshold, depending on the hysteresis setting, the relay is instantaneously de-energised.
Relay set for undervoltage detection (selector on “<”, model RM4 UA3� only):If the voltage is < the setting threshold US1, the output relay is energised with or without a time delay. When the voltage returns to a value US2 above the threshold, depending on the hysteresis setting, the relay is de-energised.
���� Functions� Overvoltage control
� Undervoltage control
Note: the measurement ranges can be extended above 500 V by adding a resistor, see page 3/103.The measurement range on � supply can be extended by means of a voltage transformer, the secondary of which is connected to the measuring terminals of the corresponding RM4.
Operating principle
Function diagrams
Voltagemeasured
Relay
Function “>”
t : time delay
t < t
US1US2
15-1815-16
25-2825-26
U supply A1-A2
Relay
Function “<”
t < t
US1US2
15-1815-16
25-2825-26
Voltagemeasured
U supply A1-A2
t : time delay
References :page 3/100
Characteristics :page 3/101
Dimensions, schemes :page 3/102
Setting-up :page 3/103
3/100
3
References 3 Zelio Control - industrial measurement and control relays 3
Voltage measurement relays RM4 U
Voltage measurement relays: overvoltage detectionTime delay Voltage to be
measured depending on connection���� or ��������
Width Output relay
Basic reference,to be completed by adding the voltage code (1)
Weight
V mm kgWithout 0.05...0.5 22.5 1 C/O RM4 UA01���� 0.168
0.3…3
0.5…5
1...10 22.5 1 C/O RM4 UA02���� 0.1685…5010…100
30...300 22.5 1 C/O RM4 UA03���� 0.168
50…500
Voltage measurement relays: overvoltage or undervoltage detectionAdjustabletime delay
Voltage to be measured depending on connection ���� or ����
Width Output relay
Basic reference, to be completed by adding the voltage code (1)
Weight
s V mm kg0.05...30 0.05...0.5 22.5 2 C/O RM4 UA31�������� 0.168
0.3…30.5…5
1...10 22.5 2 C/O RM4 UA32�������� 0.168
5…5010…100
30...300 22.5 2 C/O RM4 UA33�������� 0.16850…500
(1) Standard supply voltages
RM4 UA0��������
Volts 24 110...130 220...240� 50/60 Hz B F M
RM4 UA3���� Volts 24...240 110...130 220...240 380...415� 50/60 Hz MW F M Q� MW – – –
RM4 UA01
Presentation :pages 3/98 and 3/99
Characteristics :page 3/101
Dimensions, schemes :page 3/102
Setting-up :page 3/103
5610
46
3/101
3
Characteristics 3 Zelio Control - industrial measurement and control relays 3
Voltage measurement relays RM4 U
Power supply circuit characteristicsRelay type RM4 UA0�� RM4 UA3�
Rated supply voltage (Un) � 50/60 Hz V 24 110...130 220...240 24...240 110…130 220...240 380...415� V – – – 24...240 – – –
Average consumption at Un � VA 2 1.9…3.3 2.7…3.5 1.5…3.3 1.9…3.3 2.7…3.4 2.7…3
� W – – – 1.2 – – –
Output relay and operating characteristicsRelay type RM4 UA0�� RM4 UA3�
Number of C/O contacts 1 2
Output relay state Energised when:voltage measured > threshold setting
Energised when:voltage measured > threshold setting (“>” function)voltage measured < threshold setting (“<” function)
Setting accuracy of the switching threshold As % of the full-scale value: ± 5 %
Switching threshold drift % ≤ 0.06 per degree centigrade, depending on the permissible ambient temperature
% ≤ 0.5, within the supply voltage range (0.85…1.1 Un)
Hysteresis (adjustable) % 5…30 of the voltage threshold setting
Setting accuracy of the time delay As % of the full-scale value: ± 10 %
Time delay drift % – ≤ 0.5, within the supply voltage range (0.85…1.1 Un)
≤ 0.07 per degree centigrade, depending on rated operating temperature
Measuring cycle ms ≤ 80
Measuring input characteristicsInternal input resistance and permissible overload depending on the voltage measurement rangesRelay type RM4 UA�1 RM4 UA�2 RM4 UA����3
Measurement range� 50-60 Hz and �
V 0.05…0.5 0.3…3 0.5…5 1…10 5…50 10…100 30…300 50…500
Internal input resistance Ri kΩ 6.6 43 71 23 112 225 668 1111
Permissible continuous overload V 20 60 80 90 150 300 400 550
Permissible non repetitive overloadfor t ≤ 1 s
V 25 80 100 100 200 400 500 550
Presentation :pages 3/98 and 3/99
References :page 3/100
Dimensions, schemes :page 3/102
Setting-up :page 3/103
3/102
3
Dimensions,schemes 3
Zelio Control - industrial measurement and control relays 3
Voltage measurement relays RM4 U
DimensionsRM4 UA
� Rail mounting Screw fixing
�
SchemesRM4 UA01, UA02 RM4 UA03 RM4 UA31, UA32 RM4 UA33
A1-A2 Supply voltage Connection and current values to be measured, depending on type of RM4 UAB1, B2, Voltages to be measured RM4 UA�1 B1-C 0.05…0.5 V RM4 UA�2 B1-C 1…10 V RM4 UA�3 B2-C 30…300 V
B3, C (see table opposite) B2-C 0.3…3 V B2-C 5…50 V B3-C 50…500 VB3-C 0.5…5 V B3-C 10…100 V
Application schemeExample: overspeed monitoring (undervoltage function)
80 22,5
78
89,5
82 4
66
78
A1 A2 CB1 B3B2
18 16 15
1815
16
B3
B2
B1
A2
A1
C
A1 A2 CB3B2
18 16 15
1815
16
B3
B2
A2
A1
C
A1 A2 CB1 B3B2
2628 2518 16 15
1815
16
B3
2825
26
B2
B1
A2
A1
C
A1 A2 CB3B2
2628 2518 16 15
1815
16
B3
2825
26
B2
A2
A1
C
Q1
1/L1
2
3/L2
4
5/L3
6 Q41 2Q32 1
Q22 1
151816
252826
RM4 UA
KM1
KM1
A1
A2
B1
C
U
v
KM1
12
34
56
U1
W1
V1
M1 3
Tacho-generator
Overspeed
Stop
Start
Presentation :pages 3/98 and 3/99
References :page 3/100
Characteristics :page 3/101
Setting-up :page 3/103
3/103
3
Setting-up 3 Zelio Control - industrial measurement and control relays 3
Voltage measurement relays RM4 U
Undervoltage threshold to be measured: 12 V �.Output relay time delay: 20 s.Reset voltage threshold: 13.2 VSupply voltage: 230 V at � 60 Hz.
� Adjustments:� Adjustment of function and timing range, switch 4:- determine the timing range, immediately greater than the time required; in the above example 30 s,- determine whether overvoltage or undervoltage detection is required; in this example, undervoltage,- position switch 4 according to the above 2 criteria; in this example, switch 4 on < 30.� Fine adjustment of time delay:Depending on the max. range setting displayed at 4 (in the above example: 30 s) use potentiometer 3 to set the required time delay as a % of value 4.In the above example, the required time = 20 s therefore :
� Set the voltage threshold setting potentiometer 1 as a percentage of the maximum value of the measuring range selected when wiring.In the above example: wiring B2-C, max. value of measuring range = 50 V, therefore:
� Set the hysteresis 2 as a % of the threshold value; in this example:
Setting-upExample of undervoltage to be measured
Product selected RM4 UA32MConnection of voltage to be measured B2-C (5 to 50 V)
Set the time delay potentiometer 3 to 66.
Setting 1 = = 24 % Set the voltage threshold setting potentiometer 1 to 24.
Setting 2 = = 10 % Set the hysteresis 2 to 10.
1234
RU
t x 1004
20 x 10030
= 66 %=
12 x 10050
13.2 - 1212
Extension of the measuring range
���� or ���� supply
Simply connect an additional resistor (Rs) in series with the measuring input B3 or C.If the value of Rs is in the region of: Rs = Ri where:
Ri Internal resistance of input B3-C.Um Maximum value of threshold setting range.U Voltage threshold to be measured.
The tripping threshold of the relay will be towards the maximum graduation on the threshold setting potentiometer.In general, the power consumed by the resistor does not exceed 0.5 W.For a.c. voltages, it is also possible to use a voltage transformer.
Supply by the measured voltage For monitoring mains and power supplies, the
RM4 UA can be supplied by the voltage to be controlled, provided that:- the measurement threshold is within the operating range of the product's power supply (0.85…1.1 Uc), - variations of the voltage to be measured are compatible with the supply and measurement voltage ranges.
RsC
B3
Ri U > 500 V
RM4 UA33U
Um -1
A1
A2
B2/B3
C
RM4 UA
Presentation :pages 3/98 and 3/99
References :page 3/100
Characteristics :page 3/101
Dimensions, schemes :page 3/102
3/104
3
Presentation 3 Zelio Control - industrial measurement and control relays 3
Current measurement relays RM4 J
1 Adjustment of current threshold as % of setting range max. value.2 Hysteresis adjustment from 5 to 30 % (2).3 Fine adjustment of time delay as % of setting range max. value.4 10-position switch combining: - selection of the timing range: 1 s, 3 s, 10 s, 30 s, no time delay,- selection of overcurrent (>) or undercurrent (<) detection.
See table below.
(1) Selection by switch on front face.(2) Value of current difference between energisation and de-energisation of the output relay
(% of the current threshold to be measured).
FunctionsThese devices are designed to detect when current rises above or drops below a preset threshold, on an a.c. or a d.c. supply.They have a transparent, hinged flap on their front face to avoid any accidental alteration of the settings. This flap can be directly sealed.
Relay type Overcurrent detection
Overcurrent or undercurrent detection (1)
Measuring range
RM4 JA01 Yes No 3 mA…1 ARM4 JA31 Yes Yes 3 mA…1 ARM4 JA32 Yes Yes 0.3 A…15 A
Applications :- excitation control of d.c. machines,- control of load state of motors and generators,- control of current drawn by a 3-phase motor,- monitoring of heating or lighting circuits,- control of pump draining (undercurrent),- control of overtorque (crushers),- monitoring of electromagnetic brakes or clutches.
DescriptionRM4 JA01 RM4 JA31 RM4 JA32
Width 22.5 mm Width 22.5 mm Width 45 mm
RM4 JA01
RM4 JA32
12
RU
1234
RU
1234
RU
R Yellow LED: indicates relay state.U Green LED: indicates that supply to the RM4 is on.
Table showing details for switch 4Switch position Function Time delay (t)< 0 Undercurrent detection No time delay
< 1 Undercurrent detection 0.05 to 1 s< 3 Undercurrent detection 0.15 to 3 s< 10 Undercurrent detection 0.5 to 10 s
< 30 Undercurrent detection 1.5 to 30 s> 0 Overcurrent detection No time delay> 1 Overcurrent detection 0.05 to 1 s
> 3 Overcurrent detection 0.15 to 3 s> 10 Overcurrent detection 0.5 to 10 s> 30 Overcurrent detection 1.5 to 30 s
References :page 3/106
Characteristics :page 3/107
Dimensions, schemes :page 3/108
Setting-up :page 3/109
5610
6156
1062
3/105
3
Presentation (continued) 3 Zelio Control - industrial measurement and control relays 3
Current measurement relays RM4 J
The supply voltage is connected to terminals A1-A2.The current to be monitored is connected to terminals B1, B2, B3 and C. See diagram below.
Hysteresis is adjustable between 5 and 30 %: for overcurrent h = (IS1 - IS2) / IS1, for undercurrent h = (IS2 - IS1) / IS1.A measuring cycle lasts only 80 ms, which allows rapid detection of changes in current.
Relay set for overcurrent detection (RM4 JA01 or selector on “>” for model RM4 JA3�).If the current is > the setting threshold IS1, the output relay is energised with or without a time delay, depending on the model. When the current returns to a value IS2 below the threshold, depending on the hysteresis setting, the relay is instantaneously de-energised.
Relay set for undercurrent detection (selector on “<”, model RM4 JA3� only).If the current is <, the setting threshold IS1, the output relay is energised with or without a time delay, depending on the model. When the current returns to a value IS2 above the threshold, depending on the hysteresis setting, the relay is instantaneously de-energised.
� Functions� Undercurrent detection
� Overcurrent detection
Note: The measurement ranges can be extended by means of a current transformer, the secondary of which is connected to the measuring terminals of the RM4 relay, or by means of a resistor connected in parallel with the measuring input (see example page 3/109 “Setting-up”).
Operating principle
Function diagrams
t < t
IS1IS2
15-1815-16
25-2825-26
A1-A2
Current measured
Relay
U supplyFunction “<”
t : time delay
B1, B2, B3RM4 JA
C
LoadU drop < 1 V
Mea
sure
men
t
t < t
IS1IS2
15-1815-16
25-2825-26
A1-A2
Currentmeasured
Relay
U supplyFunction “>”
t : time delay
References :page 3/106
Characteristics :page 3/107
Dimensions, schemes :page 3/108
Setting-up :page 3/109
3/106
3
References 3 Zelio Control - industrial measurement and control relays 3
Current measurement relays RM4 J
Overcurrent detectionTime delay Current to
be measured depending on connection���� or ��������
Width Output relay
Basic reference,to be completed by adding the voltage code (1)
Weight
s mm kgWithout 3...30 mA 22.5 1 C/O RM4 JA01���� 0.172
10...100 mA
0.1...1 A
Overcurrent or undercurrent detectionAdjustabletime delay
Current to be measured depending on connection���� or ��������
Width Output relay
Basic reference, to be completed by adding the voltage code (1)
Weight
s mm kg0.05...30 3...30 mA 22.5 2 C/O RM4 JA31�������� 0.172
10...100 mA
0.1...1 A
0.3...1.5 A 45 2 C/O RM4 JA32������������ 0.204
1...5 A3...15 A
(1) Standard supply voltages
RM4 JA01 Volts 24 110...130 220...240� 50/60 Hz B F M
RM4 JA31 Volts 24...240 110...130 220...240 380...415and RM4 JA32 � 50/60 Hz MW F M Q
� MW – – –
RM4 JA01
RM4 JA32
Presentation :pages 3/104 and 3/105
Characteristics :page 3/107
Dimensions, schemes :page 3/108
Setting-up :page 3/109
5610
6856
1069
3/107
3
Characteristics 3 Zelio Control - industrial measurement and control relays 3
Current measurement relays RM4 J
Power supply circuit characteristicsRelay type RM4 JA01 RM4 JA31 and RM4 JA32
Rated supply voltage (Un) � 50/60 Hz V 24 110...130 220...240 24...240 110…130 220...240 380...415� V – – – 24...240 – – –
Average consumption at Un � VA 2 1.9…3.3 2.7…3.5 1.5…3.3 1.9…3.3 2.7…3.4 2.7…3
� W – – – 1.2 – – –
Output relay and operating characteristicsRelay type RM4 JA01 RM4 JA31 and RM4 JA32
Number of C/O contacts 1 2
Output relay state Energised when: current measured > threshold setting
Energised when:current measured > threshold setting (“>” function)current measured < threshold setting (“<” function)
Setting accuracy of the switching threshold As % of the full-scale value: ± 5 %
Switching threshold drift % ≤ 0.06 per degree centigrade, depending on the permissible ambient temperature
% ≤ 0.5, within the supply voltage range (0.85…1.1 Un)
Hysteresis (adjustable) % 5…30 of the current threshold setting
Setting accuracy of the time delay As % of the full-scale value: ± 10 %
Time delay drift % – ≤ 0.07 per degree centigrade, depending on temperature
≤ 0.5, within the supply voltage range(0.85… 1.1 Un)
Measuring cycle ms ≤ 80
Measuring input characteristicsInternal input resistance and permissible overload depending on the current measurement rangesRelay type RM4 JA01 and RM4 JA31 RM4 JA32
Measurement range��50-60 Hz and ����
3…30 mA 10…100 mA 0.1…1 A 0.3…1.5 A 1… 5 A 3… 15 A
Internal input resistance Ri Ω 33 10 1 0.06 0.02 0.006
Permissible continuous overload A 0.05 0.15 1.5 2 7 20
Permissible non repetitive overloadfor t ≤ 3 s
A 0.2 0.5 5 10 15 100
Presentation :pages 3/104 and 3/105
References :page 3/106
Dimensions, schemes :page 3/108
Setting-up :page 3/109
3/108
3
Dimensions,schemes 3
Zelio Control - industrial measurement and control relays 3
Current measurement relays RM4 J
DimensionsRM4 JA (common side view) RM4 JA���� RM4 JA32
Rail mounting Screw fixing �
Connection schemesRM4 JA01 RM4 JA31 RM4 JA32
A1-A2 Supply voltage Connection and current values to be measured, depending on type of RM4 JA
B1, B2, Currents to be measured RM4 JA01 B1-C 3…30 mA RM4 JA32 B1-C 0.3…1.5 AB3, C (see table opposite) & RM4 JA31 B2-C 10…100 mA B2-C 1…5 A
B3-C 0.1…1 A B3-C 3…15 A
Application schemesExample: detection of blockage on a crusher (overcurrent function)
Current measured ≤ 15 A Current measured > 15 A
80 22,5
78
45
78
89,5
82 66
78
A1 A2 CB1 B3B2
18 16 15
1815
16
B3
B2
B1
A2
A1
C
A1 A2 CB1 B3B2
2628 2518 16 15
1815
16
B3
2825
26
B2
B1
A2
A1
C
A1 A2 C B1 B2 B3
18 16 15 28 26 25
1815
16
B3
2825
26
B2
B1
A2
A1
C
151816
252826
RM4 JA3
KM1
KM1
1/L1
2
3/L2
4
5/L3
6
Q1
2/T
1
4/T
2
6/T
3
1
Q2
3 5
KM1
12
34
56
U1
W1
V1
M1 3
B3
C
A1
A2
N
Overtorque Start
Stop
151816
252826
RM4 JA3
KM1
KM1
1/L1
2
3/L2
4
5/L3
6
Q1
2/T
1
4/T
2
6/T
3
1
Q2
3 5
KM1
12
34
56
U1
W1
V1
M1 3
B3
C
A1
A2
N
Overtorque Start
Stop
Presentation :pages 3/104 and 3/105
References :page 3/106
Characteristics :page 3/107
Setting-up :page 3/109
3/109
3
Setting-up 3 Zelio Control - industrial measurement and control relays 3
Current measurement relays RM4 J
Overcurrent threshold at: 13 A.Output relay time delay: 5 s.Reset current threshold: 11 ASupply voltage: 127 V ����
� Adjustments:� Adjustment of function and timing range, switch 4:- determine whether overcurrent or undercurrent detection is required; in this example, overcurrent,- determine the timing range, immediately greater than the time required; in this example 10 s,- position switch 4 according to the above 2 criteria; in this example, switch 4 on > 10.� Fine adjustment of time delay:Depending on the max. range setting displayed at 4 (in the above example: 10 s) use potentiometer 3 to set the required time delay as a % of value 4.In the above example, the required time = 5 s therefore:
� Set the current threshold setting potentiometer 1 as a percentage of the maximum value of the measuring range selected when wiring.In the above example: wiring B3-C, max. value of measuring range = 15 A, therefore:
� Set the hysteresis 2 as a % of the threshold value; in this example:
� d.c. or a.c. supplySimply connect a resistor “Rs” to terminals B1-C (or B2, B3-C) on the measuring input.The relay energisation threshold will be towards the middle of the setting potentiometer range if the value of Rs is in the region of:
� Application: Use of relay RM4 JA31�� (10 to 100 mA).Connection B2-C to measure a threshold of 1 A, knowing that Ri = 10 Ω for this rating and that Im = 100 mA.The value of Rs will be: = 0.526 Ω
P = (1 - ) 2 x 0.526 i.e. 0.47 W
Select a resistor Rs capable of dissipating at least twice the calculated value, i.e. 1 W for this example, in order to limit temperature rise.On an a.c. supply, it is also possible to use a current transformer.
Setting-UPExample of overcurrent to be measured
Product selected RM4 JA32MWConnection of current to be measured B3-C (3 to 15 A)
Set the time delay potentiometer 3 to 50.
Setting 1 = = 87 % Set the current threshold setting potentiometer 1 to 87.
Setting 2 = = 15.4 % Set the hysteresis 2 to 15(13 - 11 = 2 i.e. 15.4 % of the current to be measured).
1234
RU
t x 1004
5 x 10010
= 50 %=
13 x 10015
13 - 1113
Extension of the measuring range
Rs = where:
Ri Internal resistance of input B1-C,Im Maximum value of threshold setting range, I Current threshold to be measured.
Power dissipated by Rs: P = Rs (I -Im/2)2
Rs
B1
C
RM4 JA
Ri
Ii = Im/2 I
Ri(2I/Im) - 1
10(2 x 1/0.1) - 1
0.12
Presentation :pages 3/104 and 3/105
References :page 3/106
Characteristics :page 3/107
Dimensions, schemes :page 3/108