pmu for smartpmu for smart grid

Upload: majorhasan

Post on 03-Jun-2018

217 views

Category:

Documents


0 download

TRANSCRIPT

  • 8/12/2019 PMU for SmartPMU for Smart Grid

    1/47

  • 8/12/2019 PMU for SmartPMU for Smart Grid

    2/47

    KTH Royal Institute of TechnologyStockholm, Sweden

    E-mail: [email protected]

    Web: http://www.vanfretti.com

    International Workshop:

    The use of Synchrophasors in Power Systems

    D 12

    th

    2012

    Ri d J i B il

    Developing Real-Time PMU Applications for

    Smart Transmission Grids

    Scientific Advisor

    Smart Operation R&D Program

    R&D Department

    Statnett SF, Oslo Norway

    Dr.-Ing. Luigi VanfrettiDocent and Assistant Professor

    In a Real-Time Hardware-in-the-Loop Laboratory

    mailto:[email protected]://www.vanfretti.com/http://www.vanfretti.com/mailto:[email protected]
  • 8/12/2019 PMU for SmartPMU for Smart Grid

    3/47

    Outline

    Motivation:

    - The paradigm shiftor whyare Smart Grids needed (also at the Power Transmission Level)

    - STRONgrid project

    Goals, partners and LV PMU Network

    Development of Smart Grid Apps:

    - SmarTS Lab: A real-time Hardware-in-the-Loop Laboratory

    - Flexible Tools for Detecting and Monitoring Power SystemOscillations

    Q&A

  • 8/12/2019 PMU for SmartPMU for Smart Grid

    4/47

    Intermitted generationbrings renewableenergy capacity

    New production ofelectricity:

    - Wind: variable - uncertain

    - Solar: variable - uncertain

    Location:

    - Most new wind is located

    at distant locations (Long-distance transmissionrequired)

    - Most new solar sources

    sited closer to the

    customeron all voltage

    levels (becoming bigger)

    And more to come!

    - In Norwaygreat potentialfor micro hydro plants atremote locations.

    Small Hydro

    PV

    Wind

  • 8/12/2019 PMU for SmartPMU for Smart Grid

    5/47

  • 8/12/2019 PMU for SmartPMU for Smart Grid

    6/47

    To deal with new generation sources requiresa paradigm shift also at the transmission level

    Future generation patternsbringfaster power transferinteractions

    It will become necessary toquickly attain a system wide

    visibility andawareness

    of thesystems condition

    Real-time monitoring canprovide real-time visibility ofHV networks across traditionaloperational boundaries

    Real-time controlcan helphandling operation understringent conditions

  • 8/12/2019 PMU for SmartPMU for Smart Grid

    7/47

    System dynamics become increasingly important for system operation

    Flexibilitybecomes availablewith advancements in

    -d d l

    Need for Flexibility:

    Near-voltage-collapse example

    1 2 3 4Voltage

    North

    Center

    South

    1: Line tripped2 & 3:OLTC activation

    4: Manual load

    Shedding

    Events

  • 8/12/2019 PMU for SmartPMU for Smart Grid

    8/47

    Smart Grids Also at the Transmission LevelMonitoring, Operation, Control and Protection in Real-Time

    A challenge also in

    Scandinavia:

    Picture of the RegionalControl Center at Alta,Norway.

    Operators have the challengeof running a power systemunder severe weatherconditions and guaranteeingsupply to critical heavyindustries

  • 8/12/2019 PMU for SmartPMU for Smart Grid

    9/47

    Smart Grids Also at the Transmission LevelMonitoring, Operation, Control and Protection in Real-Time

    A challenge also in

    Scandinavia:

    Picture of the RegionalControl Center at Alta,Norway.

    Operators have the challengeof running a power systemunder severe weatherconditions and guaranteeingsupply to critical heavyindustries

  • 8/12/2019 PMU for SmartPMU for Smart Grid

    10/47

    Develop innovative applications that will enable operation and control of the Nordic

    power grid more reliably and with better information about security margins. Develop a research platform comprised by a power systems emulator (software and

    hardware labs), PMUs, PDCs and specialized software.

    Develop a set of software interfaces allowing PMU- data application development,and implementation

    Partners:

    Project Goals and Partners

    Institute of Physical

    Energetics

    Industry

    Academia

  • 8/12/2019 PMU for SmartPMU for Smart Grid

    11/47

    Build up from initiative by Lund University. PMUs are connected at the LV network

    - Inputs: 3 phase voltage

    - Outputs: Voltage magnitude, angle, frequencyand df/dt

    LV PMU Network

    Extension in STRONg2rid

    On-line PDC

    Planned PMU

    On-line PMU

    NI ABB SEL

    SEL PDCOpen PDC

    PMUs

    PDCs

    PRL

  • 8/12/2019 PMU for SmartPMU for Smart Grid

    12/47

    Build up from initiative by Lund University. PMUs are connected at the LV network

    - Inputs: 3 phase voltage

    - Outputs: Voltage magnitude, angle, frequencyand df/dt

    LV PMU Network

    Extension in STRONg2rid

    On-line PDC

    Planned PMU

    On-line PMU

    NI ABB SEL

    SEL PDCOpen PDC

    PMUs

    PDCs

    PRL

    5 On-line PMUs:- KTH (Stockholm), CTH (Gothemburg), LTH

    (Lund), LTH (Lule), Tampere

    2 On-line PDCs:

    - Lund (homebrew PDC)

    - KTH (openPDC) 4 New PMUs will be installed on 2012:

    - NTNU (Trondheim), DTU (Bingby), TUT(Estonia), IPE (Latvia)

  • 8/12/2019 PMU for SmartPMU for Smart Grid

    13/47

    The incident happened on Nov 6th 2012 at 2pm

    All newspapers wrote about it:http://www.dn.se/sthlm/totalstopp-for-sl

    - Fault due to bad reconnection during plannedmaintenance work in lsj (Stockholm area). Thistriggered protection on one line

    - All railway systems affected (T-bana, Pendeltg andlocal trains)

    - Some households (84000) without power during onehour

    More stories available under #strmavbrott on

    Twitter How we noticed:

    - The lights blinked in KTH, some electric protectiontriggered in our Lab

    Sample Event: Totalstopp fr SLOutage affecting the whole railway system in Stockholm

  • 8/12/2019 PMU for SmartPMU for Smart Grid

    14/47

    The fault had an impactacross the whole Nordicnetwork.

    - Approx. 0.15 Hz deviation!

    The grid mode frequencymeasured on the graph isapprox 0,04 Hz

    - Frequency/load governingmode of the network

    Measurements and preliminary analysis:The Nordic Grid is quite sensitive!

    0 50 100 150 200 250

    49.85

    49.9

    49.95

    50

    50.05

    50.1

    50.15

    50.2

    50.25

    T i me (sec)

    f

    (Hz)

    LT H

    CT H

    Tampere

    LT U

    K T H

    The total generated capacity for the Nordic grid is roughly 50 GW.

    - The lost load during the fault was 300 MW. This is less than 1% of the generation capacityin the grid.

    Such a small fraction of disconnected load should not have such far reaching

    impact in the entire grid.

    With a larger availability of detailed and time-syncrhonized measurements (fromPMUs) spread over the grid there is a possibility of using them as inputs to controls.

  • 8/12/2019 PMU for SmartPMU for Smart Grid

    15/47

    SmarTS Lab

    A real-time hardware-in-the-loop laboratory for WAMPAC /PMU Application Development

  • 8/12/2019 PMU for SmartPMU for Smart Grid

    16/47

    Smart Grid require Smart Operation, Smart Control and Smart Protection:

    - The ultimate goal should be to attain an automatic-feedback self-healing control system

    MeasureCommunicateAnalyze (System Assessment and reallimits)DeterminePreventive/Corrective ActionsCommunicateControl and protect

    To achieve this vision, new applications need to be developed in a controlled environment, allowing

    testing and considering the ICT chain

    How to develop a controlled environment fordeveloping Smart Transmission Apps?

    Sync. Timing

    Phasor Measurement Data

    Controllable and Protective Device

    Measurement and Status Data

    Data Alignment

    and

    Concentration

    CommunicationNetworks

    Data Storage

    and Mining

    Monitoring

    Transmission System

    Control Center

    AdvancedDisplays Early Warning

    System

    Near Real-Time

    Security

    Assessment Automatic

    Determination of

    Control Actions

    Decision/Control Support System

    Smart-Automatic Control Actions

    Smarter Operator

    Decision Support

    Smarter Operator Control

    Actions

  • 8/12/2019 PMU for SmartPMU for Smart Grid

    17/47

    The SmarTS Lab ArchitectureOpal-RT

    Real-Time Simulator

    CommunicationNetwork

    (WAN /NetworkEmulator)

    StationBus

    Low-LevelAnalog I/Os

    Physical DevicesLow-Power

    Prototypes

    Vand IAmplifiers

    Digital I/Os

    Amplified analog outputs(current/voltage)

    SEL PMUs /Relays

    ABB Relays

    NI- cRIO 9076

    SynchrophasorData

    WAMS

    Applications

    PDC(s)

    WAPS

    Applications

    PMUs

    External Controllers

    Vand IAmplifiers

    GOOSE

    Sampled Values

    GOOSE

    Sampled Values

    ProtectiveRelays

    WACS

    Applications

    WAMPACApplication

    Host Platform

    GOOSE

    ProcessBus

    GOOSE

    DigitalI/Os

  • 8/12/2019 PMU for SmartPMU for Smart Grid

    18/47

    SmarTSLa

    b

    Hard

    wareImplem

    entation

  • 8/12/2019 PMU for SmartPMU for Smart Grid

    19/47

    SmarTS LabComm. and Synchronization Architecture and Implementation

    GPS - Signal

    IRIG-B

    Process Bus

    (IEC 61850-9-2)

    Station Bus

    (IEC 61850-8-1)

    Synchrophasor Bus

    (IEEE C37.118)

  • 8/12/2019 PMU for SmartPMU for Smart Grid

    20/47

    MATLAB/SimulinkSimPowerSystems

    Model

    Model Splitting intoSub-systems forRT-Simulation

    Real-Time ModelSimulation

    RT-Lab SoftwareInterface Compiles andLoads the Model into

    RT-Targets

    EthernetPort

    OP5949 Active Monitoring Panel

    OP 5600 I/O Extension Chasis

    eMEGAsim (12 Cores)

    64 Analog Out

    16 Analog In

    Current Inputs Voltage Inputs

    OPAL-RT

    MATLAB/Simulink

    Design models for real-

    time simulation

    Simulator Analog

    and Digital I/Os

    1

    2

    4

    5

    Ethernet

    Switch

    The model is compiled and loaded

    into the simulator using Opal-RTLab Software

    Real-Time Digital simulation is

    converted to Analog / Digital Signals

    through I/O s

    The Analog outputs of the

    Simulator are fed into the CT

    Inputs of the SEL-487E

    RealTime simulations are accessed from

    the console generated by OPAL-RT Lab

    software

    OP 5251 (128

    DIgital I/O))

    Digital Outputs Digital Inputs

    Receiving Data

    from SEL 487E

    using SEL

    AcSELerator

    Quickset

    The current and voltage from the

    analog outputs of the simulator

    amplified by using Megger SMRT-1

    Amplifier and fed into the CT/VT

    inputs of the relay

    3

    Off-line to RT ModelCode Generation

    Model-to-DataWorkflow

  • 8/12/2019 PMU for SmartPMU for Smart Grid

    21/47

    Model-to-Data Proof of Concept Experiment(Hardware-in-Open-Loop)

    Real-TimeSimulator

    Amplifier

    PMU/Relay

    Media Converter

    SEL Synchrowave PDCHardwired Ethernet

    Generate 3-Phase RTSignals (Voltages and

    Currents)

    Output signals, low

    level throughsimulator I/Os

    (+/- 16 V., +/- 20 mA)

    Amplifying from low-level to standard

    rating(1-60 Amp, 60-300 V)

    PMU Transmits

    ComputedPhasors through

    Serial Port

    RS232 to TCP/IPover Ethernet

    l i h f i li

  • 8/12/2019 PMU for SmartPMU for Smart Grid

    22/47

    Megger SMRT1(Back Panel)

    Ethernet Port

    Data Stream on

    IEEE C37.118

    GPS Antenna

    InputThree-Phase

    Voltage &

    Current Signals

    Opal-RT OP5600 Computational Target

    Analog Outputs from IO to

    Megger SMRT1

    SEL-421 Relay with PMU functionality

    Monitoring OutputMeasurement

    (3-Phase signals)

    GPS Antenna

    Megger SMRT1(Front Panel)

    GPS SignalsSpliter

  • 8/12/2019 PMU for SmartPMU for Smart Grid

    23/47

    Modeling for Real-TimeHardware-in-the-Loop

    Simulation

    Video!

    http://www.youtube.com/watch?v=vAywcqYYhLAhttp://www.youtube.com/watch?v=vAywcqYYhLA
  • 8/12/2019 PMU for SmartPMU for Smart Grid

    24/47

    What is observed at the PMU at 50 fpsreporting rate?

    Generator mechanicalpower perturbation

    Generator mechanical power perturbation

    The whole process in real-time:Interaction with the model in real-time (Hardware-in-open-loop)

    Synchronous

    Generartor

    500MVA , 20kV

    Step Up Transformer

    20kV / 380 kV

    Bus 2

    Bus 3

    Thevenin

    Equivalent

    Bus 1Transmission Line

    L 1-3

    Transmission Line

    L 1-3 a

    Transmission

    Line

    L 3-5

    M

    `

    Bus 4

    Step Down

    Transformer

    380 kV / 6.3 kV

    Bus 5

    Induction Motor

    4.9 MVA , 6.3 kV

    OLTC Controlled Load

    Damped oscillations captured by the PMU at 50 fps inthe frequency computed by the PMU

    One-Line Diagram

  • 8/12/2019 PMU for SmartPMU for Smart Grid

    25/47

    A LabView PMU Application

    Software Development Toolkit (SDK)

  • 8/12/2019 PMU for SmartPMU for Smart Grid

    26/47

    Connection mechanims for the IEEE C37.118 protocoland IEC 61850-9-5

    Make PMU-data available in a buffer

    Allow data access from the buffer with adjustable

    update rate

    Allow selection of channels

    Allow receiving data on a queue

    PMU App. SDKA LabView-Based PMU Application SDK

  • 8/12/2019 PMU for SmartPMU for Smart Grid

    27/47

    Building Smart Appsthe last mile

    PMU Data Bus

    (IEEE C37.118)

    Phasor Data

    Concentrator(s)

    Real-Time

    Simulator

    +

    Amplifiers

    +

    PMUs

    +

    Comm.

    Network

    000101 Parser

    Labview PMU Application

    Software Development Toolkit

    (SDK)

  • 8/12/2019 PMU for SmartPMU for Smart Grid

    28/47

    SDK Platform

    C37.118

    PDC

    DLL

    Live Buffer

    Access Buffer

    PRL

    SnapShooter

    Data- Time Stamp- Voltage Phasors- Current Phasors- Frequency

    Selector

    Custom Application

    Remote

  • 8/12/2019 PMU for SmartPMU for Smart Grid

    29/47

    PMU Recorder Light (PRL)

    DLL

    ?

    ?

    ?

    SnapShooter

    PRL

  • 8/12/2019 PMU for SmartPMU for Smart Grid

    30/47

    Prototype Implementation (PMU App. SDK Beta)

    Connection with PDC

    Configuration

    PC Loading MonitorData Channel Selection

  • 8/12/2019 PMU for SmartPMU for Smart Grid

    31/47

    Real-Time Data Access

    Straightforward Development

    of Monitoring Application

  • 8/12/2019 PMU for SmartPMU for Smart Grid

    32/47

    FAST REAL TIME OSCILLATION DETECTION AND

    MONITORING TOOL

    32

  • 8/12/2019 PMU for SmartPMU for Smart Grid

    33/47

    BackgroundProblem that we are aiming to address

    Awareness of system dynamics is becoming increasingly important for system operationdue to uncertainties of intermittent generation:

    This is an example of the dynamic operation challenges that intermittent generationbrings.

    NEED for innovation: SCADA is too slow, can never capture the phenomena.

    Operators can benefit from new real-time operation tools, that can allow them tomonitor, track and control these oscillations without resorting to curtail power orisolated wind eneration.

    In December 2010, OG&E monitoredoscillations on the transmission system innorthwestern Oklahoma.

    Occurring during periods of high wind

    generation.

    5% fluctuation at a frequency of 13-15 Hz.

    The oscillations were product of

    interactions between controllers in two

    different wind farms. Countermeasures:

    Switching to electrically isolate the

    wind farms.

    Curtail the power output!

    ~2sec

    PMU Data

  • 8/12/2019 PMU for SmartPMU for Smart Grid

    34/47

    The PMUs stream data to the PDC. PDC concentrates and sends to Bable Fish, afterhand-shaking (config.), the application runs in real-time.

    34

    Fast Real-Time Oscillation Detectionand Monitoring Tool

    PDC

    PRL

    PMU PMU

    Fast Oscillations

    RT Monitoring

    Tool

    Fast Oscillations

    RT Monitoring Tool

    Upper-level overview of

    the software developed

  • 8/12/2019 PMU for SmartPMU for Smart Grid

    35/47

    Algorithms used: oscillation detectorsand spectral estimators.

    Oscillation Detector:- A tool used to detect oscillatory activity.

    - Provides fast generalized alarm of oscillation activity in real-time for a given frequency range.

    - Once initialized, it requires only the latest data sampleto provide a new indication (recursive filtering )

    Spectral Estimator:- A tool used to estimate the spectrum of a signal

    - Uses digital signal processing methodsnon-parametric Welchs method (fft averaging), FFT and others

    - It requires a larger parcel of data (few minutes, slower update)speed up by recursive data parceling.

    Fast RT Oscillation Detection and Monitoring Tool Components:

    - Real-time data stream display (measured variable to display to be selected by the user)

    Provides real-time monitoring of the selected measurement and its corresponding overall spetrum estimation (range [0 fs/2])

    - Oscillation detectors at four different and configurable ranges (low frequency inter-area modes, local modes,and fast modes (up to Nyquist freq.))

    - Detection and Alarming:

    Energy of the oscillation at the given frequency

    Alarm levels at configurable thresholds (green = ok, orange = high activity, red = dangerous activity)

    Fast Real-Time Oscillation Detection and Monitoring Tool

    Fast Real Time Oscillation Detection

  • 8/12/2019 PMU for SmartPMU for Smart Grid

    36/47

    36

    Illustration of where the algorithms are used

    Fast Real-Time Oscillation Detectionand Monitoring Tool

    PDC

    PRL

    PMU PMU

    Fast Oscillations

    RT Monitoring

    Tool

    Real-Time Data Stream

    Overall Spectrum Estimation(shows the full frequency spectrum and activity of

    the oscillationsnon-parametric Welch metod)

    PMUat KTHs LV.

    Network, shows16.7 Hz freq. from

    railway supply.

    Hand-shaking (config.)with Bable Fish

    Oscillation Detector and

    Spectrum Estimator 1

    (inter-area freqs.)

    Oscillation Detector and

    Spectrum Estimator 2

    (local freqs.)

    Oscillation Detector andSpectrum Estimator 3

    (other freqs.)

    Oscillation Detector andSpectrum Estimator 4

    (fast freqs.)

    l ll

  • 8/12/2019 PMU for SmartPMU for Smart Grid

    37/47

    37

    Real-Time Execution Example

    Fast Real-Time Oscillation Detectionand Monitoring Tool

    PDC

    BabelFish

    PMU PMU

    Fast Oscillations

    RT Monitoring

    Tool

    Real-Time Data Stream

    Overall Spectrum Estimation(shows the full frequency spectrum and

    activity of the oscillations)

    PMUat KTHs LV.

    Network, shows16.7 Hz freq. from

    railway supply.

    Hand-shakingwith Bable Fish

    Oscillation Detector and

    Spectrum Estimator 1

    (inter-area freqs.)

    Oscillation Detector and

    Spectrum Estimator 2

    (local freqs.)

    Oscillation Detector andSpectrum Estimator 3

    (other freqs.)

    Oscillation Detector andSpectrum Estimator 4

    (fast freqs.)

    Energy of the Detected Oscillation is Low becausethis is a Harmonic! (no power swings)

    PMUat KTHs LV.Network, shows 16.7Hz freq. from railway

    supply.

    Alarms are not set off (this is correct!), andrailway frequency component is correctlydetected.

  • 8/12/2019 PMU for SmartPMU for Smart Grid

    38/47

    Oscillation Detectors:

    - RMS Energy Computation

    - Frequency bands:

    - Configurable frequency range for detecting oscillations forparticular dynamic behaviour.

    - Recommended frequency bands:

    FB1: 0.01 Hz to 0.15 Hz, 200 sec. response time. (Slow governor-loaddynamics, i.e. balancing)

    FB2: 0.15 Hz to 1.00 Hz, 12 sec. response time. (Low frequency inter-areamodes, i.e. power swings)

    FB3: 1.00 Hz to 5.00 Hz, 6 sec. response time. (Low frequency intra-areaand local area modes, i.e. internal plant swings)

    FB4: 5 Hz to 15 Hz, 3 sec. response time. (High frequency oscillations, i.e.

    wind farm controller interactions)

    FB5: 15 Hz to 25 Hz, less than 3 sec. response time. (Sub-synchronousoscillations)

    38

    Fast Real-Time Oscillation Detectionand Monitoring Tool

    InputsSynchrophasor

    Signals from PMUs

    Pre-Processing(Outlier removal,

    interpolation, etc.)

    Band Pass

    Filter(Selection of

    frequency range ofinterest)

    Moving Average

    Filter(Smooth out fast fluctuations

    and highlight dominanttrend)

    OutputRMS

    Energy

    Detrending(Remove quasi-steady

    state variations)

    Input(PMU SignalV. mag)

    OutputRMS Energy

    Wind Farm Oscillations

    Detected at 13.4 Hz

    Oscillations Detector

  • 8/12/2019 PMU for SmartPMU for Smart Grid

    39/47

  • 8/12/2019 PMU for SmartPMU for Smart Grid

    40/47

    Spectral Estimators:

    - Estimation of the spectrum of the signal

    - Uses a configurable parametric YW AR method to estimate

    the spectrum in each frequency band.

    - Frequency bands:- Configurable frequency range for estimating the spectrum of the signal at the

    given frequency range.

    - Recommended frequency bandssame as with the oscillation detector

    Aim: allow correlation between the input signal, its spectrum and

    the oscillation frequency that is active (and detected)40

    Fast Real-Time Oscillation Detectionand Monitoring Tool

    InputsSynchrophasor

    Signals from PMUs

    Pre-Processing(Outlier removal,

    interpolation, etc.)

    Band Pass Filter(Selection of frequency

    range of interest)

    Non-parametric

    Spectral Estimation(Determine the spectrum using

    YW Method)

    OutputPower Spectrum

    Density

    40

    Input(PMU SignalV. mag)

    Spectral

    Estimator

    Wind Farm Oscillations

    Detected at 13.4 Hz

    Signal

    d

  • 8/12/2019 PMU for SmartPMU for Smart Grid

    41/47

    KTH and COPPE/UFRJ have obtained a grant for collaboration from STINT

    and CAPES.

    We will work in implementing methods for voltage stability monitoring.

    KTH will try to aid COPPE in developing their own RT lab.

    The openPMU will be provided to COPPE next year for educational andresearch purposes.

    We hope this collaboration can continue into the future!

    Going Forward:Collaboration with COPPE/UFRJ and KTH

  • 8/12/2019 PMU for SmartPMU for Smart Grid

    42/47

    Thank [email protected]://www.vanfretti.com

    mailto:[email protected]://www.vanfretti.com/http://www.vanfretti.com/mailto:[email protected]
  • 8/12/2019 PMU for SmartPMU for Smart Grid

    43/47

    Software and HardwareDemostration

  • 8/12/2019 PMU for SmartPMU for Smart Grid

    44/47

    Software and Hardware Demonstration

    Devices:

    - PMUs: openPMU, cRIO PMU (National Instruments)

    - PDCs: openPDC and SEL PDC

    Software:

    - PMU Connection Tester- PRLPMU Recorder Light

    - Real-time and off-line fast oscillation detection tool

    Real-time- Wind farm models with Hardware-in-the-Loop Simulation

    - HVDC Models

  • 8/12/2019 PMU for SmartPMU for Smart Grid

    45/47

    Developed by Queens University of Belfast

    Replicated at KTH in 2012.

    MeasurementPhase

    EstimationTelecoms

    Voltages

    Currents IEEE C37.118.2SynchrophasorTransient Detection

    Local Storage

  • 8/12/2019 PMU for SmartPMU for Smart Grid

    46/47

    OpenPMU KTHs Replica

  • 8/12/2019 PMU for SmartPMU for Smart Grid

    47/47

    How welldoes it work?