passive solar design. design techniques
TRANSCRIPT
Design Techniques http://www.montanagreenpower.com/faq/passive_solar_design.php#q2
Direct Gain – Solar radiation directly penetrates and is stored in the living space
Indirect Gain – Solar radiation is collected and stored and distributed using thermal storage material. Trombe Wall
Isolated Gain – Solar radiation is collected in a space that can be isolated like a sunroom.
Emissivity or Emittance
Material Surface Emittance
Asphalt 0.90 - 0.98
Aluminum foil 0.03 – 0.05
Brick 0.93
Fiberglass 0.80 – 0.90+
Glass 0.95
Steel 0.12
Wood 0.90
Cost
Additional Cost Glazing Added thermal mass Larger roof overhangs
Cost Savings Less mechanical heating Less mechanical cooling Less maintenance
Passive Solar Design Techniques Select, orient and size glass to optimize
winter heat gain and minimize summer heat gain.
Size south-facing overhangs to shade windows in summer and allow solar gain in winter
Add thermal mass in walls for heat storage Use natural ventilation to reduce or
eliminate cooling needs Use daylight to provide natural light
U-FactorU-FACTORThe rate of heat loss is indicated in terms of the U-Factor of a window assembly. The insulating value is indicated by the R-Value which is the inverse of the U-Value.
The lower the U-Value the greater a windows resistance to heat flow and the better the insulating value.
Solar Heat Gain CoefficientThe SHGC is the fraction of incident solar radiation admitted through a window.
SHGC is expressed as a number between 0 and 1. The lower a windows solar heat gain coefficient, the less solar heat it transmits.
Visible Transmittance
The visible transmittance is an optical property that indicates the amount of visible light transmitted.
Theoretical values vary between 0 and 1, but most values are between 0.3 and 0.8
Heat loss and gain occur by infiltration through cracks in the window assembly.
Air leakage is expressed in cubic feet of air passing through a square foot of window area.
.3 is recommended for Oregon
High number for cold climate. Low number for warm climates
The lower the number the better the insulating value
The best windows have air leakage rating between 0.1 and 0.6 cfm/ft.
Varies from 0 to 1.0 The higher the # the more light is transmitted.
Window Selection
Heating Climates Reduce window area on north, east and
west facing walls. South facing windows should have a high
Solar Heat Gain Coefficient (SHGC) 0.60 or greater
Low U-Factor 0.35 or less to reduce conductive heat transfer
Window Selection
Cooling Climates Use north facing windows along with
shaded south facing windows Shading can come from landscaping,
overhangs, shutters, and solar window screens
Use windows with U-Factors below 0.4 and a SHGC below 0.55, which will help cut cooling costs