option guide
TRANSCRIPT
August 2021 CG-PRC037B-GB
Conquest
CGAX, air-cooled scroll chillers
CXAX, air-to-water scroll heat pumps
Refrigerant R454B or R410A
Models CGAX/CXAX from 015 to 060
Option Guide
2 | P a g e
Table of contents: 1 CONQUEST™ Range Overview .......................................... 4
1.1 CGAX Range ........................................................................................................... 4 1.2 CXAX Range ............................................................................................................ 5 1.3 Coil’s distribution ...................................................................................................... 6 1.4 Unit Appearance ...................................................................................................... 7
2 Efficiency level, Digit 12 ...................................................... 9
2.1 Standard efficiency, Digit 12 = 1 ............................................................................... 9 2.2 High efficiency, Digit 12 = 2 ...................................................................................... 9 2.3 AC & EC fans Characteristics. .................................................................................. 9
3 Operating map – airside, Digit 15 ..................................... 13
3.1 Standard Ambient temperature, Digit 15 = A .......................................................... 15 3.2 Low ambient temperature, Digit 15 = C .................................................................. 15
4 Freeze protection, Digit 18 ................................................ 15
4.1 None, Digit 18 = X .................................................................................................. 15 4.2 With electric heaters, Digit 18 = 2 ........................................................................... 15 4.3 With pump activation, Digit 18 = 3 .......................................................................... 17
5 Refrigerant type, Digit 20 .................................................. 17
5.1 Full charge R410A, Digit 20 = A ............................................................................. 18 5.2 Nitrogen charge, R410A ready, with oil, Digit 20 = 2 .............................................. 18 5.3 Pre-charge R410A, Digit 20 = 8 .............................................................................. 18 5.4 Full charge R454B, Digit 20 = B ............................................................................. 18 5.5 Nitrogen charge, R454B ready, with oil, Digit 20 = 3 .............................................. 18
6 Operating map water side, Digit 21 .................................. 19
6.1 Comfort cooling, Digit 21 = A .................................................................................. 19 6.2 Process cooling, Digit 21 = B.................................................................................. 19
7 Water connection, Digit 22 ............................................... 19
7.1 Grooved pipe connection (standard) digit 22 = 1 .................................................... 19 7.2 Grooved pipe connection with coupling and pipe stub digit 22 = 3 .......................... 20
8 Condenser coating, Digit 23 ............................................. 20
8.1 Standard aluminum fins, Digit 23 = B ..................................................................... 20 8.2 Epoxy aluminum fins Digit 23 = E. .......................................................................... 21 8.3 Aluminum Micro Channel, Digit 23 = H. .................................................................. 22 8.4 E-coated Micro Channel, Digit 23 = J ..................................................................... 23
9 Heat Recovery, Digit 24 ..................................................... 24
9.1 None Heat Recovery, Digit 24 = X .......................................................................... 24 9.2 Partial Heat Recovery (PHR), Digit 24 = 2 .............................................................. 24
10 Starter type, Digit 26 .......................................................... 27
10.1 Across the Line Starter/Direct on Line Digit 26= A .................................................. 27 10.2 Solid-state Soft Starter Digit 26 = B ........................................................................ 27
11 Refrigerant detector, Digit 29 ........................................... 29
11.1 Without, Digit 29 = X .............................................................................................. 29 11.2 With refrigerant detector, Digit 29 = 2 ..................................................................... 29
12 Human interface, Digit 30 ................................................. 30
12.1 Without interface, Digit 30= X ................................................................................. 30 12.2 Interface PGD1, Digit 30= A ................................................................................... 30
3 | P a g e
13 Smart Com protocol, Digit 31 ........................................... 31
13.1 No remote digital communication, Digit 31 = X ....................................................... 32 13.2 Modbus interface, Digit 31 = 1 ................................................................................ 32 13.3 LonTalk® interface, Digit 31 = 2 ............................................................................. 32 13.4 BACNet™ Interface; Digit 31= 4 ............................................................................. 33
14 External customer input/output option, Digit 32 ............ 33
14.1 Without, Digit 32 = X .............................................................................................. 33 14.2 With, Digit 32 = A ................................................................................................... 33
15 Smart Sequencer, Digit 33 ................................................ 36
15.1 Without, Digit 33 = X .............................................................................................. 36
16 Hydraulic module, Digit 35 ............................................... 36
16.1 No pumps and no contactors, Digit 35 = X ............................................................. 37 16.2 Contactors single pump, Digit 35 = 2 ...................................................................... 37 16.3 Contactors dual pump, Digit 35 = 4 ........................................................................ 37 16.4 Single pump standard pressure, Digit 35 = 5 .......................................................... 37 16.5 Single pump high pressure, Digit 35 = 6 ................................................................. 39 16.6 Dual pump standard pressure, Digit 35 = 7 ............................................................ 40
17 Smart Flow Control, Digit 36 ............................................ 41
17.1 No pump flow control; Digit 36 = X ......................................................................... 41 17.2 Manual flow control, Digit 36 = B ............................................................................ 41 17.3 Variable primary flow (Constant ΔT), Digit 36 = C .................................................. 42
18 Buffer tank, Digit 37 ........................................................... 44
18.1 Without Buffer tank; Digit 37 = X ............................................................................ 44 18.2 Buffer Tank, Digit 37 = 1 ......................................................................................... 44
19 Installation accessory, Digit 39 ........................................ 45
19.1 None, Digit 39 = 1 .................................................................................................. 45 19.2 Neoprene Pads, Digit 39 = 4 .................................................................................. 45
20 Acoustic level, Digit 41 ..................................................... 48
20.1 Standard Noise (SN), digit 15 = X .......................................................................... 48 20.2 Low Noise (LN), digit 15 = L ................................................................................... 48 20.3 HESP, Digit 41 = 2 ................................................................................................. 50
21 Condenser protection, Digit 42 ........................................ 51
21.1 No option, Digit 42 = X ........................................................................................... 51 21.2 Condenser guard grill, Digit 42 = A ......................................................................... 51
22 Literature Language, Digit 44 ........................................... 52
23 Under/over voltage protection, Digit 45 .......................... 52
23.1 None, Digit 45 = X .................................................................................................. 52 23.2 Included, Digit 45 = 1 ............................................................................................. 52
24 Suplemental Heat Control, Digit 49 .................................. 53
24.1 Without, Digit 49 = X .............................................................................................. 53 24.2 With, Digit 49 = 1 .................................................................................................... 53
25 Design Special, Digit 50 .................................................... 54
4 | P a g e
1 CONQUEST™ Range Overview
Before explaining the different options and accessories available, let’s first take a look at the
current range and review the definition of CONQUEST™ Air-cooled heat pumps and chillers.
The CONQUEST Air-cooled heat pumps and chillers family covers a capacity range between
40 kW and 165 kW, which includes Cooling only and Heat pump units. For the “Cooling only”
unit, it is called CGAX and the Heat pump is named CXAX. The units come divided by its
efficiency and their acoustic level which won’t comprise the efficiencies.
The best value chiller and heat pump on the market.
Optimized efficiencies
Lowest sound levels
High quality finish
Smart and versatile
1.1 CGAX Range
Indicative cooling capacity for a SE SN unit, without HYM
CGAX COMPRESSOR FAN UNIT DIMENSIONS (SN)
Size Net Cooling
Capacity
(kW)
Compressor
Number per
Circuits
Model Circuit1 /
Circuit 2 #
Unit
Length
(mm)
Unit
Width
(mm)
Unit
Height
(mm)
015 45 2 7,5+7,5 1 2346 1285 1524
017 51 2 7,5+10 1 2346 1285 1524
020 60 2 10+10 2 2346 1285 1524
023 67 2 10+13 2 2346 1285 1524
026 76 2 13+13 2 2346 1285 1524
030 84 2 15+15 2 2346 1285 1724
036 101 3 12+12+12 2 2327 2250 1524
039 114 3 13+13+13 3 2327 2250 1524
045 129 3 15+15+15 3 2327 2250 1524
035 100 2 7,5+10 / 7,5+10 2 2327 2250 1524
040 118 2 10+10 / 10+10 4 2327 2250 1524
046 133 2 10+13 /10+13 4 2327 2250 1524
052 149 2 13+13 / 13+13 4 2327 2250 1524
060 165 2 15+15 / 15+15 4 2327 2250 1724
Table 1 CGAX Range
5 | P a g e
1.2 CXAX Range
CXAX COMPRESSOR FAN UNIT DIMENSIONS (SN) Si
ze Net
Cooling Capacity
(kW)
Net Heating Capacity
(kW)
Compressor Number per
Circuits
Model Circuit1 / Circuit 2
# Unit
Length (mm)
Unit Width (mm)
Unit Height (mm)
15 44 44 2 7,5+7,5 1 2346 1285 1524
17 50 50 2 7,5+10 1 2346 1285 1524
20 60 58 2 10+10 2 2346 1285 1524
23 66 64 2 10+13 2 2346 1285 1524
26 73 71 2 13+13 2 2346 1285 1524
30 80 80 2 15+15 2 2346 1285 1724
36 96 96 3 12+12+12 2 2327 2250 1524
39 110 110 3 13+13+13 3 2327 2250 1524
45 119 121 3 15+15+15 3 2327 2250 1524
35 98 100 2 7,5+10 / 7,5+10 2 2327 2250 1524
40 115 116 2 10+10 / 10+10 4 2327 2250 1524
46 128 130 2 10+13 /10+13 4 2327 2250 1524
52 144 142 2 13+13 / 13+13 4 2327 2250 1524
60 155 161 2 15+15 / 15+15 4 2327 2250 1724
Table 2 CXAX Range
Figure 1 CGAX & CXAX comparison
6 | P a g e
1.3 Coil’s distribution
CGAX CXAX
Size Frame # Cricuits Right Side
Left Side
Right Side
Left Side 015 Simplex 1
017 Simplex 1
020 Simplex 1
023 Simplex 1
026 Simplex 1
030 Simplex 1
036 Simplex Large 1 039 Simplex Large 1
045 Simplex Large 1
035 Duplex 2 040 Duplex 2
046 Duplex 2
052 Duplex 2
060 Duplex 2
Table 3 Frame & Coil's type
Note: Coil dimensions available on Submital Drawing
Figure 2 Frames' configuration
7 | P a g e
1.4 Unit Appearance
1.4.1 External appearance
The color of the unit is RAL 9002, but the axial fans will rest RAL 7016.
When a buffer tank is delivered, the buffer tank is RAL 7016.
Image 1 CONQUEST - Duplex frame – STD NOISE
Image 2 CONQUEST - Duplex frame – LN or
HESP
Image 3 Unit Nameplate sample
8 | P a g e
1.4.2 Inside apparence
Image 4 Unit w/o hydraulic module
Image 5 Unit with hydraulic module
Image 6 Electrical panel
9 | P a g e
2 Efficiency level, Digit 12
2.1 Standard efficiency, Digit 12 = 1
2.1.1 Description
EER at 12/7 OAT=35°C: SE is class B or C (Eurovent efficiency) when operating at full load.
Standard efficiency units use AC fan motors with three-phase on the condenser. The motor
and the ball bearings are permanently lubricated and overload protection is provided.
However, if the unit has Low Ambient (Digit 15= C) then it will have one EC fan per circuit.
2.2 High efficiency, Digit 12 = 2
2.2.1 Description
HE version remains with the same compressors, exchangers and airflow of SE version.
The EER in High efficiency unit is the same value of a standard unit, but the SEER is much
higher because it counts with an adaptive control that improves the efficiency in partial load
operation. Best compromise between number of compressors in operation and airflow (fans’
rotation)
High efficiency units are always equipped EC fan brushless motor, operating with direct
current. EC Fan: the basis is similar to the principle of a frequency inverter; the motor speed
depends on the voltage provided by the integrated module. All fans are driven at the same
speed.
2.2.2 Benefits
High efficiency and a significant reduction of energy consumption at partial load.
2.3 AC & EC fans Characteristics.
The motors of both fans are Insulation class F and Ingress protection marking IP54.
Image 7 AC fans model
Image 8 EC fans model
AC Motor Number of poles: 8
Nominal Speed: 680 RPM
Same grid design as AC fan With EC motor
10 | P a g e
2.3.1 Fan’s type
Figure 3 Fans' distribution
FAN CKT 1 FAN CKT 2
1A 1B 1C 2A 2B
Simplex
SE - Std Ambient
High/Low Speed (AC fan)
High Speed (AC fan) if any
SE - Low Ambient
Variable Speed (EC fan)
High Speed (AC fan) if any
HE/HESP Variable Speed
(EC fan) Variable Speed (EC fan) if any
Simplex Large
SE - Std Ambient
High/Low Speed (AC fan)
High Speed (AC fan)
High Speed (AC fan)
SE - Low Ambient
Variable Speed (EC fan)
High Speed (AC fan)
High Speed (AC fan)
HE/HESP Variable Speed
(EC fan) Variable Speed
(EC fan)
Variable Speed
(EC fan)
Duplex
SE - Std Ambient
High/Low Speed (AC fan)
High Speed (AC fan) if any
High/Low Speed (AC fan)
High Speed (AC fan) if any
SE - Low Ambient
Variable Speed (EC fan)
High Speed (AC fan) if any
Variable Speed (EC fan)
High Speed (AC fan) if any
HE/HESP Variable Speed
(EC fan) Variable Speed (EC fan) if any
Variable Speed (EC fan)
Variable Speed (EC fan) if any
Table 4 Fans operation
11 | P a g e
2.3.2 Performance curves
Figure 4 EC fans Pressure vs Airflow
Figure 5 AC fans Pressure vs Airflow
10
119
197208
228
243252256257
53
0
33
53
90
136
173
199
217
22
2131
40
89
129
158
183
45
3
45
60
86
109
127138
147
37
3
37
52
78
101
120131
140
0
20
40
60
80
100
120
140
160
180
200
220
240
260
2804
00
0
5 0
00
6 0
00
7 0
00
8 0
00
9 0
00
10
00
0
11
00
0
12
00
0
13
00
0
14
00
0
15
00
0
16
00
0
17
00
0
18
00
0
19
00
0
20
00
0
21
00
0
22
00
0
23
00
0
24
00
0
25
00
0
26
00
0
27
00
0
To
tal p
ressu
re (
Pa)
qv (m3/h)
EC fan
Airflow1020RPM
Airflow 910RPM
Airflow 810RPM
Airflow 710RPM
Airflow 690RPM
0
13
27
39
51
62
71
79
89
99
0
8
16
25
3035
3943
4953
0
10
20
30
40
50
60
70
80
90
100
40
00
50
00
60
00
70
00
80
00
90
00
10
000
11
000
12
000
13
000
14
000
15
000
16
000
17
000
18
000
19
000
To
tal p
ressu
re (
Pa)
qv (m3/h)
AC fan
High speed680 RPM
Low speed500 RPM
12 | P a g e
2.3.3 Power input/Airflow curves
Figure 6 EC fans Power input vs Airflow
Figure 7 AC fans Power input vs Airflow
1764
2219
243424252376
22872193
2077
1401
1192
13231401
1534
167517451746
1638
861861963
1 1511 255
1 3061 294
725
605
725838
895937958971
654562
654766
824869893911
0
250
500
750
1000
1250
1500
1750
2000
2250
2500
4 0
00
5 0
00
6 0
00
7 0
00
8 0
00
9 0
00
10
00
0
11
00
0
12
00
0
13
00
0
14
00
0
15
00
0
16
00
0
17
00
0
18
00
0
19
00
0
20
00
0
21
00
0
22
00
0
23
00
0
24
00
0
25
00
0
26
00
0
27
00
0
Po
wer
inp
ut
(W)
qv (m3/h)
EC fan
Input 1020RPM
Input 910RPM
Input 810RPM
Input 710RPM
Input 690RPM
722752
778804
839870
911938945
971
480490504514523532543552553564
0
100
200
300
400
500
600
700
800
900
1000
40
00
50
00
60
00
70
00
80
00
90
00
10
000
11
000
12
000
13
000
14
000
15
000
16
000
17
000
18
000
19
000
Po
wer
Inp
ut[
W]
qv [m3/s]
AC fan
High speed
Low speed
13 | P a g e
3 Operating map – airside, Digit 15 Operating Maps are similar for units with R410A and units with R454B.
14 | P a g e
Figure 8 Operating map (air side) CGAX & CXAX Cooling mode
Figure 9 Operating map CXAX Heating mode
15 | P a g e
3.1 Standard ambient air temperature, Digit 15 = A
The operating range as Standard ambient option is the same for both chiller (CGAX) and heat
pump (CXAX) in cooling mode: 5°C ≤ Air temperature ≤ 46°C
For the heating mode of the heat pump (CXAX); the operation range is:
-15°C≤ Air temperature ≤ 33°C.
In mobile TOPSS, the selections in heating mode are limited to 20°C ambient. Still, the unit
can operate in heating until 33°C. This is useful for swimming pools applications, for example.
3.2 Low ambient air temperature, Digit 15 = C
With Low ambient option, EC fans are mounted on the unit. EC fans allow operation in
cooling mode with air temperature down to -18°C on CGAX and -10 ° C on CXAX.
The EC fans are used to reduce the airflow when necessary.
4 Freeze protection, Digit 18
4.1 None, Digit 18 = X
Glycol in the water loop in charge of the freeze protection.
4.2 With electric heaters, Digit 18 = 2
4.2.1 Application
- When the unit is exposed to ambient temperature between 0°C and -18°C.
- When the unit needs to be protected from freezing (no glycol in the water loop).
4.2.2 Description
These freeze protection consist in electrical heaters that could be placed in different parts
depending the modules that have been chosen for the unit:
Unit without hydraulic module:
On the evaporator a blanket heater is installed at the bottom of the brazed plate heat
exchanger (BPHE).
Image 9 BPHE's heater
Unit with hydraulic module:
16 | P a g e
- Same as above plus hydraulic module protection
- Antifreeze heater on the expansion tank plus flexible pipe and antifreeze heater with
water pipe between the pump and the brazed plate heater exchanger (BPHE).
- Image 10 Hydraulic module's heaters
Unit with hydraulic module plus buffer tank:
Same as above but there are also immersion heaters on the buffer tank.
Image 11 Buffer tank's heaters
CGAX CXAX
Sizes Pump package anti-freeze heater power (W)
Buffer tank anti-freeze heater power (W)
Sizes Pump package anti-freeze heater power (W)
Buffer tank anti-freeze heater power (W)
15
280 780
15
280 780
17 17
20 20
23 23
26 26
30 30
36 340 1180
36 340 1180 39 39
45 45
35 280 1120
35 280 1120
40 40 340 1180
46 46 280 1120
52 340 1180
52 340 1180
60 60
Table 5 CGAX & CXAX Heaters' power (W) on buffer tanks
17 | P a g e
Note: The water piping between the chiller and the building has to be protected
against freezing by installing heating cable
4.2.3 Operation
Freeze protection via the CH535 control turns on the heaters based on ambient
temperature (below 3°C).
4.2.4 Benefits
- All the components are protected.
- No additional or dedicated electrical connection when installing.
4.2.5 Incompatibilities
No incompatibility.
4.3 With pump activation, Digit 18 = 3
4.3.1 Application
No heaters are provided but the anti-freeze protection is possible with the pump activation
using external temperature sensor. This system allows reducing the price and consumption
of the unit.
4.3.2 Description
As no heaters are provided, the system will make water flows so it heats by friction. The
system counts with a 3 way valve that will let the water flows throw the system or make it flow
in a loop without entering to customer water circuit.
Figure 10 Pump activation Option’s system diagram
4.3.3 Operation
While the unit is OFF, the pumps are controlled by the CH535 control depending on the
temperature read by the external temperature sensor. The pumps will start when the ambient
temperature is less than 2°C AND the leaving water temperature is less than 15°C; if
conditions both conditions are valid, the operation of the pump will be 5 min ON / 10 min
OFF.
5 Refrigerant type, Digit 20 All units are available with refrigerants R410A and R454B. R454B has an advantage in term
of GWP.
18 | P a g e
• R410A is a refrigerant blend HFC/HFC
▪ Composition: 50% R125 + 50% R32
• R454B is a refrigerant blend HFO/HFC
▪ Composition: 31.1% R1234yf + 68.9% R32
The PED directive classifies R410A and R454B differently. From manufacturing perspective,
the CGAX R454B requires additional brazing certifications and a material traceability on
several components and a ventilation of the electrical cabinet.
5.1 Full charge R410A, Digit 20 = A
Unit delivered with full refrigerant R410A and with oil charge.
5.2 Nitrogen charge, R410A ready, with oil, Digit 20 = 2
Unit is R410A ready, delivered with Nitrogen charge and with oil.
5.3 Pre-charge R410A, Digit 20 = 8
Unit is R410A ready, delivered with a pre-charge of refrigerant and with oil.
5.4 Full charge R454B, Digit 20 = B
Unit R454B ready, delivered with full refrigerant (R454B) and with oil charge.
On R454B units, a fan ventilates the electrical cabinet.
5.5 Nitrogen charge, R454B ready, with oil, Digit 20 = 3
Unit R454B ready delivered with Nitrogen charge and with oil.
Ventilation of the
electrical cabinet of a
R454B unit
19 | P a g e
Leaving water temperature
6 Operating map water side, Digit 21
MEG: Mono-Ethylen-Glycol
Figure 11 Conquest's operating map water side
The illustration above shows the application that can be adapted for evaporator. In standard,
the evaporator is provided with comfort cooling application which the evaporator leaving
temperature is in a range of 5°C to 20°C.
Process cooling application with the range of leaving water temperature between -12°C
and 5°C is an option.
6.1 Comfort cooling, Digit 21 = A
- The range for the two units is the same [5/20] °C
- Glycol is mandatory for leaving chilled water temperature below 6°C
6.2 Process cooling, Digit 21 = B
- The range of this option depends on the chosen unit; for the CGAX, it is [-12/5] °C
and for the CXAX it is [-10/5] °C.
- It’s mandatory to use Glycol. Minimum LWT with MPG is -8°C.
7 Water connection, Digit 22 There are 2 ways which are suggested by Trane for water pipe connections (chilled water
and HR hot water (if any) connections).
7.1 Grooved pipe connection (standard) digit 22 = 1
Process cooling application
-12 °C -10°C - 8°C
CGAX CXAX
0 °C +6°C +5°C +20°C
With glycol
Comfort cooling application
MEG only
20 | P a g e
Image 12 Grooved water connection
7.1.1 Description
- This type of pipe has a grooved end.
- This groove provides a gripping area for the coupling to engage around the full pipe
circumference.
- Easy piping connection.
7.2 Grooved pipe connection with coupling and pipe stub digit 22 = 3
Image 13 Coupling and pipe stub
7.2.1 Description
Used when costumer is not able to grove its own pipe.
Pipe stub and coupling are now shipped in electrical panel.
8 Condenser coating, Digit 23
8.1 Standard aluminum fins, Digit 23 = B
21 | P a g e
Image 14 Aluminum fins
8.1.1 Application
- When the chiller is installed in standard condition
- Non polluted ambiance
- Non corrosive ambiance
8.1.2 Description
Aluminum fin is a standard fin used on all CXAX heat pumps.
8.1.3 Incompatibilities
CGAX.
8.2 Epoxy aluminum fins Digit 23 = E.
Image 15 Gold epoxy aluminum fins
8.2.1 Application
- When the heat pump is requested for coastal or salt mist environments.
- When the aluminum fin is exposed to hard weather conditions (acid rain, moisture,
pollution, salt …).
22 | P a g e
8.2.2 Description
- The fins are made out of aluminum coated sheets.
- Condenser epoxy coated; epoxy slows down the corrosion process on the aluminum
fins when the unit is installed on sea side or in a polluted area.
- Epoxy layer is between 2 to 3 µm thick per surface
8.2.3 Benefits
This option allows installation near the sea and avoids aluminum corrosion. The epoxy also
provides a barrier protection at the fin collar to stop galvanic corrosion action between the
aluminum fins and the copper tubes.
8.2.4 Incompatibilities
CGAX
8.2.5 More detail
For information, there are 192 fins per foot installed in the condenser.
See engineering bulletin PROD_PRB004_E4 on Litweb.
8.3 Aluminum Micro Channel, Digit 23 = H.
Image 16 Micro Channel Heat Exchanger
23 | P a g e
8.3.1 Application
Aluminum Micro Channel Heat Exchanger is standard for all CGAX chillers.
8.3.2 Description
- The fully-brazed construction micro channel coil increases the coil rigidity making
them more rugged to resist the rigors of job site handling and damage due to
shipping. The micro channel coil's headers, tubes and fins are assembled and then
sprayed with a powder flux bonding agent. The coil is then sent through a large
controlled air automated brazing furnace that completely joins these separate pieces
as one solid micro channel coil.
- The bottom and top tubes of each coil section are always inactive refrigerant paths,
this is done to prevent refrigerant leaks due to corrosion that may be present from
moisture resting between the top or bottom tube and the gasket material and also
serve as a buffer during the installation and removal of the coil section.
Image 17 MCHE's parts
8.3.3 Benefits
This process substantially decreases the chances of leaks due to improper brazing
techniques. Each fin surface is angled and louvered to create air turbulence through the coil
which provides more efficient and enhanced heat transfer without additional air pressure
drop through the coil.
8.3.4 Incompatibilities
CXAX
8.4 E-coated Micro Channel, Digit 23 = J
24 | P a g e
Image 18 E-Coated MCHE
8.4.1 Application
Refer to the following document to know when is necessary to apply the coating PROD_PRB
005 A, on LitWeb.
8.4.2 Description
The condenser is provided already coated before unit assembly.
8.4.3 Benefits
This option allows installation in high chemical concentrated or coastal environment and
avoids aluminum corrosion.
8.4.4 Incompatibilities
CXAX
9 Heat Recovery, Digit 24
9.1 None Heat Recovery, Digit 24 = X
All refrigerant’s heat is rejected to the atmosphere.
9.2 Partial Heat Recovery (PHR), Digit 24 = 2
9.2.1 Application
When part of the rejected heat needs to be recovered and will be reused for the production of
hot water.
9.2.2 Description
One brazed plate heat exchanger per circuit is placed on the discharge line between the
compressor and the condenser coil as shown in the following picture (CXAX). The system
has neither freeze protection nor isolation on water side.
25 | P a g e
Figure 12 CXAX PHR diagram
Image 19 PHR's location
9.2.3 Operation
At the discharge line of the compressor, refrigerant is de-superheated by transferring its
sensible heat to the water which will rise its temperature. At full load conditions (PHR EWT=
40°C / LWT=45°C - OAT = 35°C - EVAP EWT= 12°C / LWT= 7°C), 20% of the cooling
capacity can be recovered.
26 | P a g e
Figure 13 PHR’s Operating map
Even if the heat exchanger has on site water connections, the customer shall provide the
water loop for partial heat recovery; that means: a circulation pump provides constant
water flow rate from the tank; three-way valve to adjust the water flow of PHR heat
exchanger based on the heat exchanger leaving water temperature (As the leaving water
temperature increases, the PHR water flow rate increases) and safety elements such as
expansion tanks and safety valves
Figure 14 Customer's connection diagram
9.2.4 Benefits
- Recuperation of part of the heating rejected capacity.
- Energy saving
27 | P a g e
10 Starter type, Digit 26 Starters installed have an IP-54 gasketed enclosure. It is a protection index which is able to
protect the starters against dust deposit and splash water projection from all directions.
10.1 Across the Line Starter/Direct on Line Digit 26= A
This is the standard starter located in electrical panel of the unit.
Image 20 Direct on Line starter
10.2 Solid-state Soft Starter Digit 26 = B
Image 21 Soft starter
28 | P a g e
10.2.1 Application
To reduce inrush current when the compressors start.
10.2.2 Description
Factory-installed, located in electrical panel of the unit.
10.2.3 Operation
- In this circuit, the soft starter replaces the direct on line starter.
- It controls the current flow which will generate the compressors to start gradually.
10.2.4 Benefits
- With the soft starter, the starting current drops down to 2.5 - 3 IN (IN: nominal
intensity).
- The compressor can start smoothly as the starting current is reduced.
- Smooth starting reduces motor and compressor wear.
- Less stress on the power supply.
10.2.5 Incompatibilities
Direct on Line.
10.2.6 More detail
There is a device called Silicon Controlled Rectifier (SCR) that soft starter works with. The
SCR is an electronic switch which allows current to flow through it only when electronic signal
is applied to its gate.
Comparison between across line starter and soft starter:
By installing soft starter in the circuit, it will reduce the starting current. There are 5 different
size of compres
Table 6 Inrush currents
Table 9 starting times
As shown in table 8, inrush current is reduced by installing soft starter to the electrical circuit.
Thus, the compressor will be started up with small quantity of current and it improves the
stability of the power supply. In table 9, it shows that the compressor with soft starter will
take more time to run than with across the line starter. It means that the compressor starts
progressively.
Compressor
size
7,5 10 12 13 15
Across Line
(A) (()Starter
(A)
98 142 147 158 197
Soft Starter
(A)
59 85 88 95 118
% current
reduction
39 40 40 40 40
Compressor
size
7,5 10 12 13 15
Across (Line
Starter (ms) 70 70 100 100 68
Soft Starter
(ms) <500 <500 <500 <500 <500
29 | P a g e
Figure 15 Inrush current vs time (Left DoL starter - Right Soft starter)
11 Refrigerant detector, Digit 29
11.1 Without, Digit 29 = X
No refrigerant leak detector.
11.2 With refrigerant detector, Digit 29 = 2
• Refrigerant detector option
– Available only on R454B units.
– Factory installed and set according R454B critical thresholds
11.2.1 Description:
Refrigerant leak detector is available only on R454B units. A refrigerant detector is placed in
each circuit, inside the unit, close to the compressors and below the electrical cabinet.
11.2.2 Application:
The refrigerant detector allows detecting a refrigerant leak, which avoids the risk of the
flammability. It ensures safety for the customer by taking appropriate actions in the case of the
leak
11.2.3 Operation:
• Two relays available: Relay 1 for warning + Relay 3 for critical
– Customer needs to connect to these relays
0 200 400 600
Am
ps
Time (ms)0 200 400 600
Am
ps
Time (ms)
30 | P a g e
– On wiring diagrams: detector is identified as 3A6 and is on line 596/597
– When reaching warning / critical levels of R454B concentrations, customer has to
shutdown the electrical power to the unit
– Customer can use a disconnect switch upstream from CGAX/CXAX operated
remotely that will open electric circuit to the unit when there is a refrigerant leak
12 Human interface, Digit 30
The human interface will let the operator control chiller’s water set points, scheduling,
enable/disable options, etc…
Figure 16 Control architecture
12.1 Without interface, Digit 30= X For starting the chiller it’s necessary to have an interface even if the chiller was ordered
without it. The customer won’t have any information of chiller’s operation except if it’s
connected to BMS. Also only remote ON/OFF would be possible.
12.2 Interface PGD1, Digit 30= A
12.2.1 Description
Hu
ma
n in
terf
ace
PD
G1
or
PD
G T
ou
ch
31 | P a g e
This panel has a greyscale display, for programing the chiller and view operation values.
For details, see CH535 user guide.
Image 22 PGD1 Interface
13 Smart Com protocol, Digit 31
Image 23 CH535 Controller
32 | P a g e
Figure 17 CH535 Communication terminal
13.1 No remote digital communication, Digit 31 = X
13.2 Modbus interface, Digit 31 = 1
Image 24 RS485 Serial card
13.2.1 Application
When the unit needs to communicate with a Modbus network at the unit level.
13.2.2 Description
- BMS RS485 serial card. , allows direct interfacing with an RS485 network.
- Modbus index are in file CGAX-CXAXProtocole_datalists.xls available on Litweb.
13.2.3 Incompatibility:
- Other communication cards
13.3 LonTalk® interface, Digit 31 = 2
Image 25 LonTalk® interface card
13.3.1 Application
Allows CH535 controller to communicate on a LonTalk® network at the unit level.
13.3.2 Description
- Inputs and outputs for LonTalk® communication with Trane or LonTalk® BMS.
- Allows connecting to a LonTalk® TP/FT 10 network.
33 | P a g e
- LonTalk NV and names are in file CGAX-CXAXProtocale_datalists.xls available on
Litweb
13.3.3 Incompatibility:
- Other communication cards
13.4 BACNet™ Interface; Digit 31= 4
Image 26 BACnet™ interface card
13.4.1 Application
Allows CH535 controller to communicate on BACnet network at the unit level.
13.4.2 Description
- Allows connecting the controller to a BACnet MS/TP (Master/Slave Token pass) net-
work.
- BACnet object ID are in file CGAX-CXAXProtocale_datalists.xls available on Litweb
13.4.3 Incompatibility:
- Other communication cards
14 External customer input/output option, Digit 32
14.1 Without, Digit 32 = X
14.2 With, Digit 32 = A
14.2.1 Package included:
• Customer inputs:
Auxiliary Set point validation.
External water Set point*.
External current demand limit Set point
• Customer outputs:
Programmable relays (x4)
14.2.2 Relay costumer information
For more details, Refer to table 22 of the IOM
34 | P a g e
14.2.3 Wiring diagram:
Figure 18 CH535 Extension terminal
LEGEND
Device
Designation Description
6F1 Fuse, customer supplied, programmable relays
6K1 Relays, customer provided, unit status, unit is running
6K2
Relays, customer provided, unit status (Programmable), default is latching alarm -
circuit 1
6K3
Relays, customer provided, unit status (Programmable), default is latching alarm -
circuit 2
6K4 Relays, customer provided, unit status (Programmable), default is chiller limit mode
Table 7 Components' description
14.2.4 Description
35 | P a g e
- Auxiliary water Set point: It’s another set point for leaving water temperature that can
be switched with the front panel set point.
- External water Set point: Based on an external signal input (0-20mA or 4-20mA), it
will be possible to offset the active set point from 0°C to 20°C.
- External current demand limit set point: limits the maximum number of running
compressors in order to control chiller power consumption.
- % Capacity output: Indicates the percentage of load in which the unit is operating.
14.2.5 More detail
More information in User Guide CG-SVU007 available on LitWeb.
*Note: Automatic water reset based on the outside ambient temperature is a STD possibility:
Active cold water set point based on outside air temperature could be configured on CGAX or
CXAX cooling mode and also active hot water set point based on outside air temperature for
CXAX heating mode.
36 | P a g e
15 Smart Sequencer, Digit 33
15.1 Without, Digit 33 = X
16 Hydraulic module, Digit 35 The hydraulic module will be factory mounted as shown, pending the chosen option.
The picture below shows its components:
Figure 19 Hydraulic module diagram
1 VALVE FOR PRESSURE POINT 1/4" Gas NPT
2 WATER STRAINER 1,6 mm Staintless Steel 304
3 EXPANSION TANK
4 SAFETY RELIEF VALVE 4 Bar
5 WATER PUMP
6 CHECK VALVE
7 AIR RELEASE VALVE
8 TEMP. SENSOR
9 FLOW SWITCH
10 DRAIN VALVE 1/2" Gas NPT
37 | P a g e
16.1 No pumps and no contactors, Digit 35 = X
Hydraulic module is not integrated in the unit; the costumer provides pump and pump’s
electrical systems.
16.2 Contactors single pump, Digit 35 = 2 Hydraulic module is not integrated in the unit, the customer provides the pump but there will
be power and control supply from the unit, on the electrical panel.
Size (Ton) Pump Current (A)
015 4-6,3
017 4-6,3
020 4-6,3
023 4-6,3
026 4-6,3
030 4-6,3
036 6-10
039 6-10
045 6-10
035 6-10
040 6-10
046 6-10
052 6-10
060 6-10
Table 8 Contactors operating current
16.3 Contactors dual pump, Digit 35 = 4
The customer provides dual pump, but there will be power and control supply from the unit.
(NOTE: Redundancy pump operation) Two contactors from Table 12, will be provided.
16.4 Single pump standard pressure, Digit 35 = 5
16.4.1 Application
Simplifies installation of the unit.
16.4.2 Description
38 | P a g e
Image 27 Single pump hydraulic module
- The supplier is Grundfos.
- The pump is integrated into unit’s hydraulic module.
16.4.3 Pump reference:
Pumps available:
CGAX / CXAX STD Pressure Sizes Pump
015 AC 25-109
017 AC 25-109
020 AC 25-109
023 AC 25-116
026 AC 25-116
030 AC 25-116
036 AC 25-116
039 AC 25-125
045 AC 25-125
035 AC 25-116
040 AC 25-125
046 AC 25-125
052 AC 25-125
060 AC 25-125
Table 9 Standard head available pumps
16.4.4 Operation / Benefits
- Compact design: Pump and motor are integrated in a compact and user-friendly
design, the pump is fitted to a low-profile base plate, making it ideal for installation in
systems.
- High reliability: State-of-the-art mechanical shaft seal design and materials offering
high wear resistance and long operative life. Also the pumps are less sensitive to
impurities in the pumped liquid.
AC 25 - 109 Size of the pump
case Diameter of the impeller
(mm)
39 | P a g e
- Low noise level: The AC pumps offer very silent operation.
16.4.5 Material specification
Description Material
Pump housing Composite PP 30 % GF
Impeller Composite, brass
Table 10 Material specification
16.4.6 Performance curves
Figure 20 Standard head pumps performance
16.4.7 Electrical data
Pump type P1 [kW] P2 [kW] IN [A] Cos ϕ1/1 n1/1 [min-1]
AC 25-109 1,20 0,87 2,44 0,75 2838
AC 25-116 1,50 1,26 3,5 0,72 2892
AC 25-125 2,30 1,90 5,03 0,78 2863
Table 11 Standard head pumps electrical data
16.5 Single pump high pressure, Digit 35 = 6
16.5.1 Application
When the requested available pressure is not archived by the standard pressure pumps.
0
20
40
60
80
100
120
140
160
180
200
220
0 1 2 3 4 5 6 7 8 9 10 11
P [
kP
a]
Q [lps]
AC 25-109
AC 25-116
AC 25-125
40 | P a g e
16.5.2 Description
Pumps available:
CGAX / CXAX High Pressure Sizes Pump
015 AC 25-125
017 AC 25-125
020 AC 25-125
023 AC 25-125
026 AC 25-125
030 AC 25-125
036 AC 30-142
039 AC 30-142
045 AC 30-142
035 AC 30-142
040 AC 30-142
046 AC 30-142
052 AC 30-142
060 AC 30-142
Table 12 High head available pumps
16.5.3 Operation / Benefits
Same as single pump standard pressure.
16.5.4 Material specification
Same as single pump standard pressure.
16.5.5 Performance curves
Figure 21 High head pumps performance
16.5.6 Electrical data
Pump type P1 [kW] P2 [kW] IN [A] Cos ϕ1/1 n1/1 [min-1] AC 30 3,00 2,56 6,20 0,78 2865
Table 13 High head pumps electrical data
16.6 Dual pump standard pressure, Digit 35 = 7
0
30
60
90
120
150
180
210
240
270
0 1 2 3 4 5 6 7 8 9 10 11
P [
kP
a]
Q [lps]
A…AC 30-142
41 | P a g e
Image 28 Dual pump hydraulic module
16.6.1 Application
Guard pump for increasing reliability of the water circulation
16.6.2 Description
Just one of the pumps works at the time, the other is in stand-by but in case there is a failure
on the active pump the other will take the place automatically.
16.6.3 Dual pump high pressure, Digit 35 = 8
It’s the same but uses the high pressure single pump.
17 Smart Flow Control, Digit 36
17.1 No pump flow control; Digit 36 = X
The pump will always work at its nominal speed and the customer will have to use balancing
valves to adjust the operation point.
17.2 Manual flow control, Digit 36 = B
17.2.1 Application
The goal of this alternative is to provide appropriate flow rate and hydraulic balance, without
the need of mechanical balancing valve, but, taking advantage of the energy consumption
optimization of the pump.
17.2.2 Description
Unit is equipped with a pump package driven by a speed inverter, but without providing
continuous modulation of the speed, the water flow is fixed during the commissioning.
Image 29 VFD Interface representation
42 | P a g e
17.2.3 Operation
The pump speed limits must be set during the chiller commissioning, and in accordance with
below rules:
• Pump speed high limit should be referenced to the Nominal Water Flow Rate
• Pump speed low limit should be referenced to the Minimum Water Flow Rate
Figure 22 Frequency vs Speed behavior
Important note: When VPF works at 30 Hz, the absorbed power of the pump get reduced by
80% compared to 50Hz pump operation.
17.2.4 Incompatibilities
No pumps and no contactors option; Digit 35 = X
17.3 Variable primary flow (Constant ΔT), Digit 36 = C
17.3.1 Application
The goal of this alternative is to provide a flow rate in order to maintain constant the delta
between the inlet and outlet temperatures in the evaporator. This solution can be applied on
water loops with 2 or 3 ways valves, and can deliver higher energy saving than constant DP
in the majority of the comfort applications.
17.3.2 Description
With this option, Conquest chillers will be equipped with a pump package driven by a speed
inverter, the modulation of the pump speed is handle to ensure that chiller DT keeps
constant. At minimum system partial load, minimum flow rate must be ensured through the
chiller evaporator.
43 | P a g e
Figure 23 Contant ΔT Control diagram
17.3.3 Operation
Entering and Leaving temperatures at the evaporator will be measured directly by the chiller
controller, through the sensors factory supplied. A Delta T set point will be preset on the unit
controller.
Figure 24 Control’s logic
17.3.4 Incompatibilities
- No pumps and no contactors option; Digit 35 = X
- Multiple units on primary loop (Means that Smart sequencer is also incompatible.
44 | P a g e
18 Buffer tank, Digit 37
18.1 Without Buffer tank; Digit 37 = X
18.2 Buffer Tank, Digit 37 = 1
18.2.1 Application
- Used to increase water chiller inertia
- Allows to meet the two minutes water loop circulation
- Stable water temperature operation
18.2.2 Description/Operation
- Consists in a tank of water placed before the pump, Factory-installed
- Placed below the unit structure
- It doesn’t modify unit dimensions but the height increases +330mm
Image 30 Unit w/o buffer tank & with it
Image 31 Buffer tank & Hydraulic module
45 | P a g e
18.2.3 Volumes
Size Buffer Tank Volume (L)
015
324
017
020
023
026
030
036
444
039
045
035
040
046
052
060
Table 14 Buffer tank Volumes
18.2.4 Incompatibilities
No contactors and no pumps hydraulic module option.
19 Installation accessory, Digit 39
19.1 None, Digit 39 = 1
19.2 Neoprene Pads, Digit 39 = 4
19.2.1 Application
Used to avoid direct contact of the chiller and the ground.
19.2.2 Description
They are installed under the chiller.
46 | P a g e
Figure 25 Location of the pads
Shipped on the hanging eyes.
Image 32 Neoprene pads
A 90 mm
B 225 mm
Thickness 8 mm
47 | P a g e
Figure 26 Neoprene pads dimensions
19.2.3 Operation/Benefits
Avoid direct contact of the base frame with the ground.
19.2.4 Inconvenience
Neoprene pad do not filter effectively the vibrations.
19.2.5 More detail
The vibration level of the scroll chiller is 1 mm/s at a fundamental frequency of 49 Hz and
harmonics at 97 145.5 194 242.5 and 291 Hz
48 | P a g e
20 Acoustic level, Digit 41
CGAX/CXAX
Noise Level
Digit 41
SIMPLEX
015/017/020/023/026/030
SIMPLEX LARGE
036/039/045
DUPLEX
035/040/046/052/060
SN (D41=3)
LN (D41=4)
HESP
(D41=2)
Table 15 CONQUEST's aspect depending on acoustic level
20.1 Standard Noise (SN), digit 15 = X
20.1.1 Application
When the unit is requested for a non-noise sensitive area.
20.1.2 Description
The fans are placed below the roof.
20.1.3 Operation
The chiller operates with a sound power level in between 83 to 89 dB(A)
20.2 Low Noise (LN), digit 15 = L
20.2.1 Application
49 | P a g e
When the unit is requested for a noise sensitive area.
20.2.2 Description
20.2.3 Operation/Benefits
Low noise units are equipped with a pre-formed ’sound box’ encapsulating each compressor,
as a consequence it will attenuate acoustical diffusion. It’s sound level will be in between 77
to 83 dB(A).
Figure 27 Low noise differences from Std
- Compressors are insulated with sound jacket attenuator.
- Diffusor on condenser’s fans to avoid turbulent flow of the air through the
fans so fans area above the roof.
- Even with the reduction of the sound level, the other unit performances are same as Standard noise version.
50 | P a g e
Figure 28 Sound levels
20.3 HESP, Digit 41 = 2
20.3.1 Application
When the air flow will be ducted.
20.3.2 Description
EC fans with a stronger motor will be used to provide high external static pressure up to 100
Pa
Image 33 HESP fans dimensions
20.3.3 Operation
- Provide airflow similar to standard/low noise unit but the sound level increases.
- Sound level is provided by the mobile TOPSS selection software.
51 | P a g e
21 Condenser protection, Digit 42
21.1 No option, Digit 42 = X
21.2 Condenser guard grill, Digit 42 = A
21.2.1 Application
The unit is requested for polluted, susceptible to be damaged or a persons’ high frequency
areas.
21.2.2 Description
Protection Grills are made of stainless steel, and they are available as a factory-fitted option in order to protect the external coil. Guard grill are affixed with screws and can be easily removed on site.
• Grill shall prevent any user from injury caused by contact with fins. • Grill shall limit coil clogging due to dust and other external objects. • Grill shall protect the coil from the hail. • Grill causes reduced air pressure drop (less than 10 Pa at nominal airflow).
Image 34 Condenser guard grill
Image 35 Guard grill structure
c = 0,5 mm
W = 2 mm
P = 2,5 mm
Vacuum coef. = 64%
52 | P a g e
22 Literature Language, Digit 44 Literature language, Digit 44
A Bulgarian
B Spanish
C German
D English
E French
H Dutch SI (Netherland)
J Italian
K Finish
L Danish
M Swedish
N Turkish
P Polish
R Russian
T Czech
U Greek
V Portuguese
W Slovene
Y Romanian
Z Norwegian
1 Slovak
2 Croatian
3 Hungarian
Table 16 Languages Codes
23 Under/over voltage protection, Digit 45
23.1 None, Digit 45 = X
23.2 Included, Digit 45 = 1
23.2.1 Application
A RM4 TR relay is used to control unit phase sequence and under/over voltage protection.
23.2.2 Description
- Factory installed, located in the control panel.
- Only one relay for each unit.
53 | P a g e
Image 36 RM4 TR Relay
23.2.3 Operation
- If any fault linked is detected, the compressor is stopped.
- Overvoltage and undervoltage detection (RM4TR):
o In normal operation, the relay is energized and LEDs U and R are lit.
o If the average of the three voltages between phases fluctuates outside the
range to be monitored, the output relay is de-energized.
- Overvoltage: the Red LED “> U” on
- Undervoltage: the Red LED “< U” on
23.2.4 Benefits
- All motors are fully protected.
- Relay RM4 TR provides a phase reversal protection and under/over voltage
protection
23.2.5 Summary
Phase reveral protection Under/over voltage protection
Compressors Fans (and pump) Compressors Fans (and pump)
CGAX - CXAX Digit 45 = X YES YES NO NO
CGAX - CXAX Digit 45 = 1 YES YES YES YES
Image 37 Available protections
24 Suplemental Heat Control, Digit 49
24.1 Without, Digit 49 = X
24.2 With, Digit 49 = 1
24.2.1 Application
When the heating capacity of the heating pump isn’t enough, supplemental heat is required
and so a controller.
R Yellow LED: Indicates the relay state. U Green LED: Indicates that the relay power supply is on. > U Red LED: Overvoltage fault. < U Red LED: Under voltage fault. P Red LED: Phase failure or phase
reversal.
54 | P a g e
Figure 29 Supplemental heat location & Control
24.2.2 Description
- The electric heaters for supplemental heat are provided by the customer.
- 3 stages of electric heaters (Maximum) can be controlled with 3 digital outputs (dry
contacts); the number of stages is configurable by the user.
- The control is based on LIFO logic (Last In First Out).
24.2.3 Inconvenient
- No possibility to disable electric heater on an outdoor temperature condition or
through digital input from customer.
- No modulating heat output.
24.2.4 Incompatibilities
CGAX
25 Design Special, Digit 50
55 | P a g e
Trane - by Trane Technologies (NYSE: TT), a global climate innovator - creates comfortable, energy efficient indoor environments for commercial
and residential applications. For more information,
please visit trane.eu or tranetechnologies.com.
Trane has a policy of continuous product and product data improvement and reserves the right to change design and specifications without notice.
Confidential and proprietary Trane information
CG-PRC037B-GB_0821 ©2021 Trane
Supersedes CG-PRC037B-GB_0817