OPTIMIZATION OF

DISTRICT HEATING SYSTEMS

STEAM VS. HOT WATER

TKDA PresentersTKDA Presenters

Lon Fiedler and Rusty Steitz

Page 2: OPTIMIZATION OF DISTRICT HEATING SYSTEMS · 2020-02-03 · Optimization of District Heat Systems – Steam vs. Hot Water istrict Heat System Brief History and D Advantages Heating

Optimization of District Heat Systems –

Steam vs. Hot Water

� District Heat System Brief History and

Advantages

� Heating Medium -Steam or Hot Water

� Considerations for Converting from � Considerations for Converting from

Steam to Hot Water

� Alternative Fuels and Energy Evaluation

� Optimization of a District Hot Water

System

Page 3: OPTIMIZATION OF DISTRICT HEATING SYSTEMS · 2020-02-03 · Optimization of District Heat Systems – Steam vs. Hot Water istrict Heat System Brief History and D Advantages Heating

600

800

1000

District Heating Systems in

US

5%

1%2%

0%

District Heating Installations

(2009)

Colleges &

Universities

Community

Utilities

Healthcare

Installations

US District Heating Systems History

0

200

400

600

1877 1909 1959 2009

48%

14%

30%Installations

Military/Gov

Installations

Airports

Industrial

Other

Majority of Existing District Heating Systems Use Steam

Page 4: OPTIMIZATION OF DISTRICT HEATING SYSTEMS · 2020-02-03 · Optimization of District Heat Systems – Steam vs. Hot Water istrict Heat System Brief History and D Advantages Heating

Advantages of District Heating Systems

� Use of Combined Heat and Power (CHP)

� Efficiency: 80% CHP vs. 45% Combined Cycle

� Use of absorption chillers for cooling

� Reduced costs for users� Reduced costs for users

� Can allow for greater fuels flexibility

� Hot water systems allow great flexibility in

utilizing additional heating sources

Page 5: OPTIMIZATION OF DISTRICT HEATING SYSTEMS · 2020-02-03 · Optimization of District Heat Systems – Steam vs. Hot Water istrict Heat System Brief History and D Advantages Heating

� Advantages: Hot Water vs. Steam

� Heating Loop First Costs

� Operation and Maintenance Costs

Heating Medium – Steam or Hot Water

� Operation and Maintenance Costs

Page 6: OPTIMIZATION OF DISTRICT HEATING SYSTEMS · 2020-02-03 · Optimization of District Heat Systems – Steam vs. Hot Water istrict Heat System Brief History and D Advantages Heating

Advantages: Hot Water Vs. Steam

Steam Systems Hot Water Systems

� Open System –

Does not require condensate to

be returned

� Applicable for use with building

•Lower heating losses (vs. Steam)

•Flexible piping materials

•Lower installation and material costs

•Lower chemical treatment costs

(closed loop)� Applicable for use with building

hot water or steam heating

� Circulating Pumps are not

required

(closed loop)

•Allows for hot water storage

•Lower maintenance costs

•Increased CHP efficiency

•Easier energy metering

•Modern buildings utilize hot water

for heating

•Allows for inclusion of lower temperature

heat from industrial waste

or renewable energy

Page 7: OPTIMIZATION OF DISTRICT HEATING SYSTEMS · 2020-02-03 · Optimization of District Heat Systems – Steam vs. Hot Water istrict Heat System Brief History and D Advantages Heating

Heating Loop Initial Costs

HIGHER INITIAL COST ASSOCIATED

WITH STEAM SYSTEMS

� Additional Expansion Loops

� Drip Leg Vaults

� Higher Piping Material and

Installation Costs

� Supply and return pipes

are both full size

� Require Circulating Water Pump

� Conversion of existing building

HIGHER INITIAL COST ASSOCIATED

HOT WATER SYSTEMS

Installation Costs

High Temp Insulation

Additional Drip Leg Piping

� Heat Exchangers at Building

� Condensate return pumping

system

� Conversion of existing building

steam systems to hot water

Page 8: OPTIMIZATION OF DISTRICT HEATING SYSTEMS · 2020-02-03 · Optimization of District Heat Systems – Steam vs. Hot Water istrict Heat System Brief History and D Advantages Heating

Steam Vault

Drip Leg

Expansion Loops

Page 9: OPTIMIZATION OF DISTRICT HEATING SYSTEMS · 2020-02-03 · Optimization of District Heat Systems – Steam vs. Hot Water istrict Heat System Brief History and D Advantages Heating

Steam and Hot Water Pipe Systems

Steam Pipe

Condensate

High Pressure Drip Leg

Page 10: OPTIMIZATION OF DISTRICT HEATING SYSTEMS · 2020-02-03 · Optimization of District Heat Systems – Steam vs. Hot Water istrict Heat System Brief History and D Advantages Heating

Operation and Maintenance Costs

HIGHER O&M COSTS ASSOCIATED

WITH STEAM SYSTEMS

� Steam Traps and Vaults

� Heat Losses

� Chemical Treatment

� Lower CHP Electrical Output

� Higher Aux Loads

HIGHER O&M COSTS ASSOCIATED

HOT WATER SYSTEMS

� Lower CHP Electrical Output

� Condensate Piping Wear

Page 11: OPTIMIZATION OF DISTRICT HEATING SYSTEMS · 2020-02-03 · Optimization of District Heat Systems – Steam vs. Hot Water istrict Heat System Brief History and D Advantages Heating

Why Convert?

� For Equivalent Pipe Lengths, Operating and

Maintenance Costs for Steam Systems are Twice that

of Hot Water

Considerations for Converting from Steam to

Hot Water

of Hot Water

� Lower Line Losses, Increased Efficiency, and Better

System Control Can Significantly Lower Fuel Usage in

Boilers by 25 to 50% or in CHP Plants Potentially

Double the Steam Turbine Efficiency

Page 12: OPTIMIZATION OF DISTRICT HEATING SYSTEMS · 2020-02-03 · Optimization of District Heat Systems – Steam vs. Hot Water istrict Heat System Brief History and D Advantages Heating

Considerations for Converting from Steam to

Hot Water

� Evaluate Existing Steam System

� Evaluate Plant Efficiency Increases

� Evaluate Operational and Maintenance Cost

SavingsSavings

� Alternative Fuels and Energy Source Evaluation

� Existing Customer Perceptions, Willingness to

Convert, and Necessary Incentives

� Potential for New Customers

Page 13: OPTIMIZATION OF DISTRICT HEATING SYSTEMS · 2020-02-03 · Optimization of District Heat Systems – Steam vs. Hot Water istrict Heat System Brief History and D Advantages Heating

Effect of Loop Temperature on Steam

Turbine Efficiency

20%

25%

30%

35%

Ste

am

Tu

rbin

e E

ffic

ien

cy

Hot Water Supply Range

0%

5%

10%

15%

100 150 200 250 300 350 400

Ste

am

Tu

rbin

e E

ffic

ien

cy

Loop Temperature (F)

Steam Supply Range

Page 14: OPTIMIZATION OF DISTRICT HEATING SYSTEMS · 2020-02-03 · Optimization of District Heat Systems – Steam vs. Hot Water istrict Heat System Brief History and D Advantages Heating

Alternative Fuels and Energy Evaluation

� Solar

� River Centre – District Energy

� Heat Pumps

Page 15: OPTIMIZATION OF DISTRICT HEATING SYSTEMS · 2020-02-03 · Optimization of District Heat Systems – Steam vs. Hot Water istrict Heat System Brief History and D Advantages Heating

Alternative Fuels and Energy Evaluation

� Waste Incinerator

� Polk County

Page 16: OPTIMIZATION OF DISTRICT HEATING SYSTEMS · 2020-02-03 · Optimization of District Heat Systems – Steam vs. Hot Water istrict Heat System Brief History and D Advantages Heating

Alternative Fuels and Energy Evaluation

� Biomass/Biogas

� Andersen Inc.

Page 17: OPTIMIZATION OF DISTRICT HEATING SYSTEMS · 2020-02-03 · Optimization of District Heat Systems – Steam vs. Hot Water istrict Heat System Brief History and D Advantages Heating

Alternative Fuels and Energy Evaluation

� Industrial Waste Heat

� Andersen Inc.

Page 18: OPTIMIZATION OF DISTRICT HEATING SYSTEMS · 2020-02-03 · Optimization of District Heat Systems – Steam vs. Hot Water istrict Heat System Brief History and D Advantages Heating

� District heating system utilizes a CHP system to

maximize efficiency and operating cost

� Buildings are capable of heating with 160 degree

water (low temp)

� Temperature differential between supply and return

Elements of an Ideal Hot Water System

� Temperature differential between supply and return

is 50 degrees or more

� Summer excess heat from CHP provides heat for

absorption chillers

� A hot water storage tank in winter and chilled water

storage tank in the summer shifts loads to match

thermal to electrical loads

Page 19: OPTIMIZATION OF DISTRICT HEATING SYSTEMS · 2020-02-03 · Optimization of District Heat Systems – Steam vs. Hot Water istrict Heat System Brief History and D Advantages Heating

Questions and Answers

Thank you!