CHAINTREUIL JENSEN STARK HVAC GENERAL NOTES HVAC ABBREVIATIONS HVAC DUCTWORK SYMBOLS HVAC CONTROL SYMBOLS ARCHITECTURAL 1. DO NOT SCALE DRAWINGS. REFER TO ARCHITECTURAL DRAWINGS AND REFLECTED CEILING PLANS FOR EXACT LOCATION OF DOORS, WINDOWS, CEILING DIFFUSERS, ETC. 2. LIGHT FIXTURE LOCATIONS TAKE PRECEDENCE OVER DIFFUSER AND GRILLE LOCATIONS. LOCATE DIFFUSERS AND GRILLES TO ACCOMMODATE LIGHTING LAYOUT. 3. REFER TO ARCHITECTURAL FLOOR PLANS FOR LOCATION AND RATING OF ALL FIRE WALLS. GENERAL 1. THE HVAC CONTRACTOR SHALL VISIT THE JOB SITE AND BE FAMILIAR WITH ALL PROJECT CONDITIONS PRIOR TO FABRICATING DUCTWORK, EQUIPMENT, ETC. NO ALLOWANCES WILL BE MADE FOR CONTRACTOR'S UNFAMILIARITY WITH PROJECT CONDITIONS. 2. PIPING AND DUCTWORK ROUTING SHOWN IS SCHEMATIC. HVAC CONTRACTOR SHALL PROVIDE ANY ADDITIONAL OFFSETS AND FITTINGS, INCLUDING DIVIDED DUCTS, REQUIRED FOR PROPER INSTALLATION AND TO MAINTAIN CLEARANCES AS ENCOUNTERED IN THE FIELD. 3. FURNISH ALL LABOR, MATERIAL AND EQUIPMENT REQUIRED FOR THE COMPLETE INSTALLATION AND OPERATION OF ALL SYSTEMS IN THIS SECTION OF WORK IN ACCORDANCE WITH ALL APPLICABLE CODES, ASHRAE, SMACNA, NFPA, EPA, ETC. 4. PRIOR TO INSTALLATION OF ASSOCIATED WORK; INSTALLER SHALL MEET AT PROJECT SITE WITH GENERAL CONTRACTOR, INSTALLER OF EACH COMPONENT OF ASSOCIATED WORK, INSPECTION AND TESTING AGENCY REPRESENTATIVES (IF ANY), INSTALLERS OF OTHER WORK REQUIRING COORDINATION WITH WORK OF THIS SECTION AND ARCHITECT / OWNER FOR PURPOSE OF COORDINATING LOCATIONS OF PROPOSED SYSTEMS, REVIEWING MATERIAL SELECTIONS, AND PROCEDURES TO BE FOLLOWED IN PERFORMING THE WORK IN COMPLIANCE WITH REQUIREMENTS SPECIFIED. 5. COORDINATE INSTALLATION AND LOCATIONS OF DUCTWORK AND PIPING WITH BUILDING STRUCTURE, PLUMBING PIPING, ELECTRICAL CONDUIT, LIGHTING, ETC. PRIOR TO PURCHASING OR INSTALLING EQUIPMENT AND MATERIALS. 6. ALL PIPING, DUCTS, VENTS, ETC. EXTENDING THROUGH WALLS AND ROOF SHALL BE FLASHED AND COUNTERFLASHED IN A WATERPROOF MANNER. 7. MAINTAIN MINIMUM OF TEN (10) FEET BETWEEN OUTDOOR AIR INTAKES AND EXHAUST FAN DISCHARGE, PLUMBING VENTS, ETC. 8. REFER TO PLUMBING DRAWINGS FOR LOCATION AND ROUTING OF ALL CONDENSATE DRAIN LINE CONNECTION POINTS, GAS PIPING, AND WATER HEATER COMBUSTION / EXHAUST AIR DUCTWORK. 9. DIVISION 23 SHALL BE LICENSED TO PERFORM MECHANICAL WORK IN THE MUNICIPALITY IN WHICH THE PROJECT IS LOCATED. 10. DIVISION 23 SHALL GUARANTEE ALL WORK PERFORMED AND MATERIALS FURNISHED UNDER THIS CONTRACT AGAINST DEFECTS IN MATERIALS AND WORKMANSHIP FOR A PERIOD OF ONE (1) YEAR FROM THE DATE OF THE OWNER'S FINAL ACCEPTANCE OF THE WORK. ANY DEFECTS SHALL BE RECTIFIED BY DIVISION 15 WITHOUT ANY ADDITIONAL COST TO THE OWNER. 11. WORK SHALL COMPLY WITH THE LATEST REVISIONS OF NEW YORK STATE BUILDING CODE, NEW YORK STATE MECHANICAL CODE, NEW YORK STATE UNIFORM FIRE PROTECTION AND CONSTRUCTION CODE, NEW YORK STATE ENERGY CONSERVATION CODE, AND ANY STATE AND LOCAL CODES OR REGULATIONS THAT APPLY. A. IN CASE OF CONFLICTS BETWEEN DRAWINGS, SPECIFICATIONS, AND INTERPRETATION OF CODES BY LOCAL AUTHORITY, LATER SHALL GOVERN. EQUIPMENT 1. ALL HVAC EQUIPMENT SHALL BE INSTALLED PER MANUFACTURER'S REQUIREMENTS AS SHOWN. UTILIZE FACTORY FILTERS DURING CONSTRUCTION AND REPLACE (IN KIND) JUST PRIOR TO TESTING AND BALANCING. ALL FILTERS SHALL BE 2-INCHES THICK. PROVIDE ONE (1) SET OF EXTRA FILTERS FOR EACH UNIT INSTALLED. 2. ALL EQUIPMENT SHALL HAVE A ONE (1) YEAR WARRANTY; COMPRESSORS SHALL HAVE AN ADDITIONAL FIVE (5) YEAR EXTENDED WARRANTY, ROOFTOP UNIT HEAT EXCHANGERS SHALL HAVE AN ADDITIONAL TEN (10) YEAR EXTENDED WARRANTY; PROVIDE WRITTEN GUARANTEE. 3. GENERAL CONTRACTOR SHALL STORE ALL HVAC EQUIPMENT (ROOFTOP UNITS, DUCTWORK, ETC.) THAT ARRIVES AT THE PROJECT SITE. STORE ALL EQUIPMENT IN A DRY PLACE, PROTECTING ALL EQUIPMENT FROM THE WEATHER, CONSTRUCTION TRAFFIC AND THEFT. 4. ROOF CURBS SHALL HAVE A BASE THAT FITS SLOPE OF ROOF AS REQUIRED. TOP OF ROOF CURB SHALL BE LEVEL. 5. FLEXIBLE CONNECTORS SHALL BE INSTALLED ON SUPPLY, RETURN, AND EXHAUST AIR DUCTS AT ALL EQUIPMENT CONNECTIONS. DUCTWORK 1. RUN ALL DUCTWORK AND PIPING AS TIGHT TO BOTTOM OF STEEL AS POSSIBLE OR RUN THRU OPEN JOIST WEBBING. 2. DUCTWORK SHALL NOT BE SUPPORTED FROM BRIDGING, CONDUIT, PIPING, ETC. OF ANY KIND. DO NOT USE FASTENERS THAT PENETRATE ROOF DECKS. 3. ASPECT RATIO SHALL NOT EXCEED 3:1. 4. ALL DUCTWORK INSTALLATION SHALL RUN CONTINUOUSLY THROUGH PARTITIONS. 5. LOCATE ALL DUCT BALANCING DAMPERS, CONTROL DAMPERS AND FIRE DAMPERS ABOVE ACCESSIBLE CEILINGS OR PROVIDE CEILING ACCESS DOORS. A. WHERE DUCTWORK PASSES THROUGH A FIRE-RATED ASSEMBLY, AND THERE ARE NO FIRE DAMPERS SHOWN ON THE PLANS (DUCTWORK SIZE IS LESS THAN 100 SQUARE INCHES), PROVIDE THE FOLLOWING, MINIMUM: 1). A MINIMUM OF 12-INCH LONG BY 0.060-INCH THICK STEEL SLEEVE SHALL BE CENTERED IN EACH DUCT OPENING. 2). THE SLEEVE SHALL BE SECURED TO BOTH SIDES OF THE WALL AND ALL FOUR SIDES OF THE SLEEVE WITH A MINIMUM OF 1-1/2" x 1-1/2" X 0.060" STEEL RETAINING ANGLES. 3). THE RETAINING ANGLES SHALL BE SECURED TO THE SLEEVES AND THE WALL WITH NO. 10 (M5) SCREWS. 4). THE ANNULAR SPACE BETWEEN THE STEEL SLEEVE AND WALL SHALL BE FILLED WITH SILICONE ELASTOMER TO PROVIDE A MINIMUM 2-HOUR RATED FIRESTOP. 6. PROVIDE VOLUME CONTROL DAMPERS WITH QUADRANT AND LOCK AND STANDOFF COLLAR AT ALL BRANCH DUCTS TO DIFFUSERS. INSTALL AT A MINIMUM OF TWO DUCT WIDTHS FROM BRANCH TAKEOFF. 7. DUCTWORK SIZES INDICATED ON DRAWINGS ARE INSIDE, FREE AND CLEAR DIMENSIONS. INCREASE DUCT OUTSIDE DIMENSION SIZE BY TWO (2) TIMES THE THICKNESS OF THE INSULATION. 8. ALL DUCTWORK SHALL BE CONSTRUCTED AND INSTALLED IN ACCORDANCE WITH SMACNA STANDARDS. 9. ALL DUCTWORK SHALL BE GALVANIZED SHEET METAL IN AREAS WITH FINISHED CEILINGS. 10. WHERE RECTANGULAR DUCTWORK IS INDICATED, AND AT INSTALLERS OPTION, SPIRAL AND ROUND DUCTWORK MAY BE SUBSTITUTED FOR RECTANGULAR DUCTWORK PROVIDED THEY ARE EQUIVALENT TO THE RECTANGULAR DIMENSIONS INDICATED ON THE DRAWINGS (i.e.: 8x4 = 8"0, 10x6 = 10"0). 11. PROVIDE INTERNALLY LINED SUPPLY AIR DUCTWORK FROM ROOFTOP UNITS TO A MINIMUM OF 10-FEET AWAY FROM THE UNIT. REMAINING SUPPLY AIR DUCTWORK SHALL BE EXTERNALLY INSULATED WITH MINIMUM 1-1/2" THICK, 0.75 LB DENSITY, FOIL-BACK INSULATION WITH VAPOR BARRIER AND A MINIMUM R-VALUE OF R-6, FLAME SPREAD RATING OF 25 OR LESS, AND SMOKE-DEVELOPED RATING OF 50 OR LESS. 12. ALL RETURN AIR DUCTWORK SHALL BE INTERNALLY LINED. 13. ALL DUCT LINERS SHALL BE MINIMUM 1-1/2" THICK, COATED TO PREVENT ELEMENTS FROM ENTERING THE AIRSTREAM (COATING SHALL MEET ASHRAE 62 - LATEST EDITION), AND ENVIRONMENTALLY FRIENDLY WITH A MINIMUM R-VALUE OF R-6. LINER SHALL BE BLACK IN COLOR SO IT IS NOT NOTICEABLE FROM THE INSIDE OF REGISTERS AND GRILLES. 14. ALL SQUARE ELBOWS SHALL HAVE AIRFOIL TYPE TURNING VANES. 15. MAXIMUM FLEXIBLE DUCT LENGTH SHALL BE 5'-0". ALL FLEXIBLE DUCT SHALL CONFORM TO THE REQUIREMENTS OF U.L. 181 FOR CLASS 1 FLEXIBLE AIR DUCTS, WITH A MINIMUM R-VALUE OF R-6. SUPPORT FLEXIBLE DUCT TO ELIMINATE KINKING AND SAGGING. (FLEXIBLE DUCT IS NOT PERMITTED IN EXPOSED AREAS, RETURN AIR GRILLE AND EXHAUST AIR GRILLE CONNECTIONS). PIPING 1. ALL PIPING LINES, INCLUDING CONDENSATE DRAINS, SHALL BE FULLY INSULATED WITH MINIMUM 1-1/2" THICK, 0.75 LB DENSITY, INSULATION WITH ALL SERVICE JACKET AND VAPOR BARRIER, FLAME SPREAD RATING OF 25 OR LESS, AND SMOKE-DEVELOPED RATING OF 50 OR LESS. 2. CONDENSATE PIPING FROM AIR CONDITIONING EQUIPMENT SHALL BE PITCHED A MINIMUM OF 1/4" PER FOOT, IN THE DIRECTION OF FLOW. 3. CONDENSATE DRAIN PIPES SHALL HAVE CLEANOUTS AT EVERY CHANGE IN DIRECTION, DISTANCES GREATER THAN 3 FEET, AND AT THE BEGINNING OF LONG STRAIGHT RUNS. 4. HVAC CONTRACTOR SHALL BE RESPONSIBLE FOR THE SIZING OF REFRIGERANT LINES (LONG LINE APPLICATION) GREATER THAN 50'-0". HVAC EQUIPMENT SUPPLIER SHALL VERIFY REFRIGERANT PIPE LINE SIZES AND CONFIGURATIONS BASED ON CONTRACTOR'S PROPOSED PIPE ROUTING. AFU F BHP CFM CU DB DDC EAT EER E/F EWH F FCU HP HVAC IN KW LAT LBS MBH MCA OED RPM RTU SEER SP TU VAV W/ WB ANNUAL FUEL UTILIZATION EFFICIENCY BRAKE HORSEPOWER CUBIC FEET PER MINUTE CONDENSING UNIT DRY BULB DIRECT DIGITAL CONTROL ENTERING AIR TEMPERATURE ENERGY EFFICIENCY RATIO EXHAUST FAN ELECTRIC WALL HEATER FAHRENHEIT FAN COIL UNIT HORSEPOWER HEATING, VENTILATING, AIR CONDITIONING INCHES KILOWATT LEAVING AIR TEMPERATURE POUNDS 1,000 BRITISH THERMAL UNITS MINIMUM CIRCUIT AMPACITY OPEN END DUCT REVOLUTIONS PER MINUTE ROOFTOP UNIT SEASONAL ENERGY EFFICIENCY RATIO STATIC PRESSURE TERMINAL UNIT VARIABLE AIR VOLUME WITH WET BULB 303 South Park Avenue Buffalo, N.Y. 14204 716.856.6448 tel 716.852.1722 fax 266 Alexander Street Rochester, N.Y. 14607 585.244.3780 tel 585.244.1294 fax www.cjsarchitects.com SYMBOL DESCRIPTION SYMBOL DESCRIPTION SUPPLY DUCT RISER TEMPERATURE SENSOR S RETURN DUCT RISER PROGRAMMABLE, 7-DAY, 24-HOUR THERMOSTAT T CONTROL WIRING (PLENUM RATED) EXHAUST DUCT RISER AIRFOIL TURNING VANES EBS ENGINEERING, PC DUCT RISE OR DROP ENGINEERED BUILDING SYSTEMS MECHANICAL / ELECTRICAL ENGINEERS 4050 RIDGE LEA ROAD BUFFALO NEW YORK 14228 HVAC DRAWING LIST FLEXIBLE DUCT PHONE: FAX: E-MAIL: (716) 836-9600 (716) 836-9636 INTERNALLY LINED DUCTWORK [email protected] M-1 M-2 M-3 M-4 M-5 HVAC SCHEDULES, LEGENDS AND ABBREVIATIONS HVAC SCHEDULES FLOOR PLAN - HVAC DUCTWORK AND PIPING ROOF PLAN - HVAC DUCTWORK AND PIPING HVAC DETAILS WEBSITE: WWW.EBSPE.COM 4- MANUAL VOLUME DAMPERS COPYRIGHT C 2016 ENGINEERED BUILDING SYSTEMS DIRECTION OF SLOPE (DOWN IN DIRECTION OF ARROW) 0 ROUND (p D. 8o s o j 0 47 S o SUPPLY AIR DEVICE - FIRST NO. CFM, SECOND NO. TYPE THIRD NO. NECK SIZE 200-1 (REFER TO SCHEDULE FOR SIZE) RETURN / EXHAUST AIR DEVICE - FIRST NO. CFM, SECOND NO. TYPE THIRD NO. NECK SIZE (IF REQUIRED) 200-2 G 8"0 (REFER TO SCHEDULE FOR SIZE) I AIR DISTRIBUTION DEVICE SCHEDULE VARIABLE AIR VOLUME TERMINAL UNIT SCHEDULE KEY PLAN INLET DUCT SIZE (DIA.) AIR QUANTITY STYLE & DEVICE SIZE MINIMUM OUTSIDE AIR CFM MOUNTING DESCRIPTION MANUFACTURER SYMBOL MODEL NO. MARK AREA SERVED MANUFACTURER MODEL NO. TOTAL CFM 40wVIILiTM1$ SUPPLY ESMB-08 (BYPASS) 8"0 TU-01 MIT OFFICE 39 TITUS 200 75 [O] TYPE 1 cOmpanies construction I development SUPPLY 24x24 ARCHITECTURAL PLAQUE FACE, STEEL CONSTRUCTION, LAY-IN 3 SLOTS (SLOT WIDTH IS 1-1/2"), OPPOSED BLADE VOLUME DAMPER, 4-WAY THROW, WHITE FINISH TITUS DAT ESMB-08 (BYPASS) 8"0 TU-02 MIT OFFICE 43 TITUS 300 100 OWNER: 49 S. WATER STREET, LLC RETURN MULTIPURPOSE CONFERENCE ROOM 14 ESMB-10 (BYPASS) 10"o TU-03 TITUS 500 125 RETURN 24x24 PERFORATED FACE, STEEL CONSTRUCTION, OPPOSED BLADE LAY-IN VOLUME DAMPERS, PROVIDE 22"x22" BACKPAN FOR FULL PANEL LAY-IN APPLICATION, WHITE FINISH 500 SENECA ST - SUITE 508 BUFFALO, NY 14204 (71 6) 332-5959 tel. (716) 332-5968 fax. 0 TITUS PAR VESTIBULE 1, WAITING 2, TOILET 3, RECEPTION DESK 4 ESMB-12 (BYPASS) TYPE 2 12"0 TU-04 TITUS 850 200 EXHAUST ESMB-08 (BYPASS) 8"0 TU-05 MIT OFFICE 40 TITUS 300 100 EXHAUST 24x24 PERFORATED FACE, STEEL CONSTRUCTION, OPPOSED BLADE LAY-IN VOLUME DAMPERS, PROVIDE 22"x22" BACKPAN FOR FULL PANEL LAY-IN APPLICATION, WHITE FINISH Q FLEX BUILDINNG OFFICE/EDICALREIAIL TITUS PAR ESMB-10 (BYPASS) TYPE 3 10"o MULTIPURPOSE ROOM 41 TU-06 TITUS 500 125 OFFICE 12, OFFICE 13, OFFICE 15, OFFICE 16, OFFICE 18, OFFICE 20 ESMB-12 (BYPASS) AIR DISTRIBUTION DEVICE NOTES: 49 S. WATER STREET VILLAGE OF GOWANDA NEW YORK 14070 12"0 1,000 TU-07 TITUS 200 1. ALL DEVICES SHALL BE FROM A SINGLE MANUFACTURER. 2. ALL DEVICES SHALL HAVE MATCHING MATTE, WHITE FINISH (UNLESS OTHERWISE NOTED IN DESCRIPTION ABOVE). 3. MAXIMUM NC OF 20. 4. ACCESSORIES: A. OPERATING KEYS: TOOLS DESIGNED TO FIT THROUGH DIFFUSER FACE AND OPERATE VOLUME CONTROL DEVICE AND / OR PATTERN ADJUSTMENT 5. ACCEPTABLE MANUFACTURER'S - TITUS, PRICE. OFFICE 6, OFFICE 7, OFFICE 9, OFFICE 11 ESMB-10 (BYPASS) 10"o TU-08 TITUS 700 175 DRAWING TITLE 6. THE BIDDER MUST SUBMIT IN WRITING TO THE ARCHITECT / OWNER, WHO WILL FORWARD TO THE ENGINEER, ANY REQUEST FOR A PROPOSED DEVIATION, MODIFICATION, OR SUBSTITUTION TO THESE DRAWINGS AND SPECIFICATIONS FOR EVALUATION NO LATER THAN TEN (10) DAYS PRIOR TO THE BID DATE. A. A REQUEST FOR ANY SUBSTITUTION SHALL BE ACCOMPANIED BY TECHNICAL DATA, DRAWINGS, PRODUCT SAMPLES, AND COMPLETE DATA SUBSTANTIATING COMPLIANCE OF PROPOSED SUBSTITUTION THAT MEET / EXCEED SPECIFIED MATERIALS AND IN COMPLIANCE WITH THESE DRAWINGS AND SPECIFICATIONS. 1). REQUESTS FOR SUBSTITUTION SHALL BE MADE ONLY BY THE BIDDER; REQUESTS FOR SUBSTITUTION FROM SALES REPRESENTATIVES, VENDORS, OR SUPPLIERS ARE NOT ACCEPTABLE. B. NO MATERIALS SHALL BE DEEMED ACCEPTABLE IF NOT IN STRICT AND FULL COMPLIANCE WITH THESE DRAWINGS AND SPECIFICATIONS. C. ALL BIDDERS MUST BID SOLELY ON THE SPECIFIED MATERIALS UNLESS ACCEPTANCE BY THE ENGINEER OF A DEVIATION, OMISSION, MODIFICATION, OR SUBSTITUTION IS GRANTED IN WRITING THROUGH THE ARCHITECT / OWNER TO ALL BIDDERS PRIOR TO THE BID DATE. 1). FAILURE TO SUBMIT PROPOSED SUBSTITUTED EQUIPMENT / MATERIALS PRIOR TO THE BID EVALUATION DATE, AND IS INCLUDED IN THE BIDDERS PRICE / SUBMITTAL REVIEW DRAWINGS (AFTER THE PROJECT IS AWARDED); WILL RESULT IN A "REJECTED" SUBMITTAL PACKAGE. HVAC SCHEDULES, LEGENDS AND ABBREVIATIONS VARIABLE AIR VOLUME TERMINAL UNIT NOTES: CONTROLS 1. ALL CONTROL WIRING AND CONDUIT SHALL COMPLY WITH THE NATIONAL ELECTRIC CODE (NEC) AND NFPA 70. 2. ALL CONTROL WIRING AND POWER CONDUCTOR INSULATION SHALL BE PLENUM RATED. 3. ALL EXPOSED CONTROL WIRING SHALL BE INSTALLED IN 3/4" EMT CONDUIT. 4. PROVIDE ALL RELAY, CONTACTORS, ETC. REQUIRED TO ACHIEVE INTERLOCK OPERATION OF EQUIPMENT. BALANCING 1. MECHANICAL CONTRACTOR, WHO IS CERTIFIED BY EITHER THE ASSOCIATED AIR BALANCE COUNCIL (AABC) OR NATIONAL ENVIRONMENTAL BALANCING BUREAU (NEBB); UPON COMPLETION OF THE PROJECT, SHALL PERFORM A COMPLETE TESTING AND BALANCING OF ALL EQUIPMENT. BALANCE SYSTEM TO WITHIN ±5% OF AIR QUANTITIES INDICATED ON PLANS AND SCHEDULES AND PROVIDE THE OWNER WITH A COMPLETE, SIGNED AND SEALED BALANCE REPORT. 1. MINIMUM 20-GAUGE GALVANIZED STEEL HOUSING WITH INTEGRAL SOUND ATTENUATOR. 2. LOW LEAKAGE BYPASS DIVERTING CONTROL DAMPER WITH EDGE SEALS. 3. MINIMUM 1/2" THICK (CLOSED-CELL) FIBRE-FREE INTERNALLY LINED. 4. FACTORY INSTALLED MODULATING ACTUATOR (0-10V DC, CONTROLLED BY THERMOSTAT). 5. MAXIMUM AIR PRESSURE DROP OF 0.40 INCHES WG. 6. ACCESSORIES: A. DISCHARGE AIR SENSOR. B. WALL MOUNTED THERMOSTAT (MODULATING (0-10V DC OUTPUT). C. FACTORY INSTALLED ACCESS DOOR. 7. MAXIMUM RADIATED NC OF 25 AND DISCHARGE NC OF 22. 8. ACCEPTABLE MANUFACTURERS: CARRIER, TITUS, PRICE. JOB NO. 1210 SCALE NONE ELECTRIC WALL HEATER SCHEDULE 4.15.2016 DATE VOLTS / PH MANUFACTURER SERIES AMPS MARK AREA SERVED MODEL NO. TYPE MBH WATTS DRAWN BY 3450 SERIES (HEAW DUTY FAN FORCED) SEMI- RECESSED MOUNTING CHECKED BY 208/1/60 2,000 EWH-1 VESTIBULE 1 MARKEL F3453T 6.8 9.6 REVISIONS ELECTRIC WALL HEATER NOTES: 1. ELECTRIC WALL HEATERS SHALL CONTAIN AN INTEGRAL, TAMPERPROOF THERMOSTAT. 3. ELECTRIC WALL HEATERS SHALL BE EQUIPPED WITH BUILT-IN THERMAL OVERLOAD PROTECTION. 4. FURNISHED AND INSTALLED BY DIVISION 23. A. WIRING BY DIVISION 26. 5. FURNISH 2" SEMI-RECESSED MOUNTING FRAME #3450EX16 FOR EACH SEMI-RECESSED MOUNTED ELECTRIC WALL HEATER. 6. COLOR, INCLUDING CUSTOM COLOR, AS SELECTED BY ARCHITECT. 7. ACCEPTABLE MANUFACTURERS - MARKEL, Q'MARK, INDEECO. THIS IS A SINGLE SHEET OF A COHESIVE SET OF CONSTRUCTION DOCUMENTS (INCLUDING DRAWINGS AND SPECIFICATIONS). INTERPRETATION OF THE INFORMATION AS PRESENTED SHOULD BE BASED ON THE ENTIRE SET OF DOCUMENTS. DRAWING NO. M-1 100% DESIGN SUBMISSION *1 ARCHITECTS, LLP

Upload: dinhcong

Post on 29-Apr-2018

241 views

Category:

Documents


8 download

TRANSCRIPT

CHAINTREUIL JENSEN STARKHVAC GENERAL NOTES HVAC ABBREVIATIONS HVAC DUCTWORK SYMBOLS HVAC CONTROL SYMBOLSARCHITECTURAL

1. DO NOT SCALE DRAWINGS. REFER TO ARCHITECTURAL DRAWINGS AND REFLECTEDCEILING PLANS FOR EXACT LOCATION OF DOORS, WINDOWS, CEILING DIFFUSERS,ETC.

2. LIGHT FIXTURE LOCATIONS TAKE PRECEDENCE OVER DIFFUSER AND GRILLELOCATIONS. LOCATE DIFFUSERS AND GRILLES TO ACCOMMODATE LIGHTING LAYOUT.

3. REFER TO ARCHITECTURAL FLOOR PLANS FOR LOCATION AND RATING OF ALL FIREWALLS.

GENERAL

1. THE HVAC CONTRACTOR SHALL VISIT THE JOB SITE AND BE FAMILIAR WITH ALLPROJECT CONDITIONS PRIOR TO FABRICATING DUCTWORK, EQUIPMENT, ETC.NO ALLOWANCES WILL BE MADE FOR CONTRACTOR'S UNFAMILIARITY WITH PROJECTCONDITIONS.

2. PIPING AND DUCTWORK ROUTING SHOWN IS SCHEMATIC. HVAC CONTRACTOR SHALLPROVIDE ANY ADDITIONAL OFFSETS AND FITTINGS, INCLUDING DIVIDED DUCTS,REQUIRED FOR PROPER INSTALLATION AND TO MAINTAIN CLEARANCES ASENCOUNTERED IN THE FIELD.

3. FURNISH ALL LABOR, MATERIAL AND EQUIPMENT REQUIRED FOR THE COMPLETEINSTALLATION AND OPERATION OF ALL SYSTEMS IN THIS SECTION OF WORK INACCORDANCE WITH ALL APPLICABLE CODES, ASHRAE, SMACNA, NFPA, EPA, ETC.

4. PRIOR TO INSTALLATION OF ASSOCIATED WORK; INSTALLER SHALL MEET AT PROJECTSITE WITH GENERAL CONTRACTOR, INSTALLER OF EACH COMPONENT OF ASSOCIATEDWORK, INSPECTION AND TESTING AGENCY REPRESENTATIVES (IF ANY), INSTALLERS OFOTHER WORK REQUIRING COORDINATION WITH WORK OF THIS SECTION ANDARCHITECT / OWNER FOR PURPOSE OF COORDINATING LOCATIONS OF PROPOSEDSYSTEMS, REVIEWING MATERIAL SELECTIONS, AND PROCEDURES TO BE FOLLOWED INPERFORMING THE WORK IN COMPLIANCE WITH REQUIREMENTS SPECIFIED.

5. COORDINATE INSTALLATION AND LOCATIONS OF DUCTWORK AND PIPING WITHBUILDING STRUCTURE, PLUMBING PIPING, ELECTRICAL CONDUIT, LIGHTING, ETC.PRIOR TO PURCHASING OR INSTALLING EQUIPMENT AND MATERIALS.

6. ALL PIPING, DUCTS, VENTS, ETC. EXTENDING THROUGH WALLS AND ROOF SHALLBE FLASHED AND COUNTERFLASHED IN A WATERPROOF MANNER.

7. MAINTAIN MINIMUM OF TEN (10) FEET BETWEEN OUTDOOR AIR INTAKES ANDEXHAUST FAN DISCHARGE, PLUMBING VENTS, ETC.

8. REFER TO PLUMBING DRAWINGS FOR LOCATION AND ROUTING OF ALLCONDENSATE DRAIN LINE CONNECTION POINTS, GAS PIPING, AND WATER HEATERCOMBUSTION / EXHAUST AIR DUCTWORK.

9. DIVISION 23 SHALL BE LICENSED TO PERFORM MECHANICAL WORK IN THEMUNICIPALITY IN WHICH THE PROJECT IS LOCATED.

10. DIVISION 23 SHALL GUARANTEE ALL WORK PERFORMED AND MATERIALS FURNISHEDUNDER THIS CONTRACT AGAINST DEFECTS IN MATERIALS AND WORKMANSHIP FOR APERIOD OF ONE (1) YEAR FROM THE DATE OF THE OWNER'S FINAL ACCEPTANCEOF THE WORK. ANY DEFECTS SHALL BE RECTIFIED BY DIVISION 15 WITHOUT ANYADDITIONAL COST TO THE OWNER.

11. WORK SHALL COMPLY WITH THE LATEST REVISIONS OF NEW YORK STATE BUILDINGCODE, NEW YORK STATE MECHANICAL CODE, NEW YORK STATE UNIFORM FIREPROTECTION AND CONSTRUCTION CODE, NEW YORK STATE ENERGY CONSERVATIONCODE, AND ANY STATE AND LOCAL CODES OR REGULATIONS THAT APPLY.

A. IN CASE OF CONFLICTS BETWEEN DRAWINGS, SPECIFICATIONS, AND INTERPRETATIONOF CODES BY LOCAL AUTHORITY, LATER SHALL GOVERN.

EQUIPMENT

1. ALL HVAC EQUIPMENT SHALL BE INSTALLED PER MANUFACTURER'S REQUIREMENTSAS SHOWN. UTILIZE FACTORY FILTERS DURING CONSTRUCTION AND REPLACE(IN KIND) JUST PRIOR TO TESTING AND BALANCING. ALL FILTERS SHALL BE2-INCHES THICK. PROVIDE ONE (1) SET OF EXTRA FILTERS FOR EACH UNITINSTALLED.

2. ALL EQUIPMENT SHALL HAVE A ONE (1) YEAR WARRANTY; COMPRESSORS SHALLHAVE AN ADDITIONAL FIVE (5) YEAR EXTENDED WARRANTY, ROOFTOP UNIT HEATEXCHANGERS SHALL HAVE AN ADDITIONAL TEN (10) YEAR EXTENDED WARRANTY;PROVIDE WRITTEN GUARANTEE.

3. GENERAL CONTRACTOR SHALL STORE ALL HVAC EQUIPMENT (ROOFTOP UNITS,DUCTWORK, ETC.) THAT ARRIVES AT THE PROJECT SITE. STORE ALL EQUIPMENTIN A DRY PLACE, PROTECTING ALL EQUIPMENT FROM THE WEATHER,CONSTRUCTION TRAFFIC AND THEFT.

4. ROOF CURBS SHALL HAVE A BASE THAT FITS SLOPE OF ROOF AS REQUIRED.TOP OF ROOF CURB SHALL BE LEVEL.

5. FLEXIBLE CONNECTORS SHALL BE INSTALLED ON SUPPLY, RETURN, AND EXHAUSTAIR DUCTS AT ALL EQUIPMENT CONNECTIONS.

DUCTWORK

1. RUN ALL DUCTWORK AND PIPING AS TIGHT TO BOTTOM OF STEEL AS POSSIBLEOR RUN THRU OPEN JOIST WEBBING.

2. DUCTWORK SHALL NOT BE SUPPORTED FROM BRIDGING, CONDUIT, PIPING, ETC.OF ANY KIND. DO NOT USE FASTENERS THAT PENETRATE ROOF DECKS.

3. ASPECT RATIO SHALL NOT EXCEED 3:1.

4. ALL DUCTWORK INSTALLATION SHALL RUN CONTINUOUSLY THROUGH PARTITIONS.

5. LOCATE ALL DUCT BALANCING DAMPERS, CONTROL DAMPERS AND FIRE DAMPERSABOVE ACCESSIBLE CEILINGS OR PROVIDE CEILING ACCESS DOORS.

A. WHERE DUCTWORK PASSES THROUGH A FIRE-RATED ASSEMBLY, AND THERE ARENO FIRE DAMPERS SHOWN ON THE PLANS (DUCTWORK SIZE IS LESS THAN 100SQUARE INCHES), PROVIDE THE FOLLOWING, MINIMUM:

1). A MINIMUM OF 12-INCH LONG BY 0.060-INCH THICK STEEL SLEEVE SHALLBE CENTERED IN EACH DUCT OPENING.

2). THE SLEEVE SHALL BE SECURED TO BOTH SIDES OF THE WALL AND ALLFOUR SIDES OF THE SLEEVE WITH A MINIMUM OF 1-1/2" x 1-1/2" X 0.060"STEEL RETAINING ANGLES.

3). THE RETAINING ANGLES SHALL BE SECURED TO THE SLEEVES AND THE WALLWITH NO. 10 (M5) SCREWS.

4). THE ANNULAR SPACE BETWEEN THE STEEL SLEEVE AND WALL SHALL BEFILLED WITH SILICONE ELASTOMER TO PROVIDE A MINIMUM 2-HOUR RATEDFIRESTOP.

6. PROVIDE VOLUME CONTROL DAMPERS WITH QUADRANT AND LOCK AND STANDOFFCOLLAR AT ALL BRANCH DUCTS TO DIFFUSERS. INSTALL AT A MINIMUM OF TWODUCT WIDTHS FROM BRANCH TAKEOFF.

7. DUCTWORK SIZES INDICATED ON DRAWINGS ARE INSIDE, FREE AND CLEARDIMENSIONS. INCREASE DUCT OUTSIDE DIMENSION SIZE BY TWO (2) TIMES THETHICKNESS OF THE INSULATION.

8. ALL DUCTWORK SHALL BE CONSTRUCTED AND INSTALLED IN ACCORDANCE WITHSMACNA STANDARDS.

9. ALL DUCTWORK SHALL BE GALVANIZED SHEET METAL IN AREAS WITH FINISHEDCEILINGS.

10. WHERE RECTANGULAR DUCTWORK IS INDICATED, AND AT INSTALLERS OPTION,SPIRAL AND ROUND DUCTWORK MAY BE SUBSTITUTED FOR RECTANGULAR DUCTWORKPROVIDED THEY ARE EQUIVALENT TO THE RECTANGULAR DIMENSIONS INDICATED ONTHE DRAWINGS (i.e.: 8x4 = 8"0, 10x6 = 10"0).

11. PROVIDE INTERNALLY LINED SUPPLY AIR DUCTWORK FROM ROOFTOP UNITS TO AMINIMUM OF 10-FEET AWAY FROM THE UNIT. REMAINING SUPPLY AIR DUCTWORKSHALL BE EXTERNALLY INSULATED WITH MINIMUM 1-1/2" THICK, 0.75 LB DENSITY,FOIL-BACK INSULATION WITH VAPOR BARRIER AND A MINIMUM R-VALUE OF R-6,FLAME SPREAD RATING OF 25 OR LESS, AND SMOKE-DEVELOPED RATING OF 50OR LESS.

12. ALL RETURN AIR DUCTWORK SHALL BE INTERNALLY LINED.

13. ALL DUCT LINERS SHALL BE MINIMUM 1-1/2" THICK, COATED TO PREVENT ELEMENTSFROM ENTERING THE AIRSTREAM (COATING SHALL MEET ASHRAE 62 - LATESTEDITION), AND ENVIRONMENTALLY FRIENDLY WITH A MINIMUM R-VALUE OF R-6.LINER SHALL BE BLACK IN COLOR SO IT IS NOT NOTICEABLE FROM THE INSIDE OFREGISTERS AND GRILLES.

14. ALL SQUARE ELBOWS SHALL HAVE AIRFOIL TYPE TURNING VANES.

15. MAXIMUM FLEXIBLE DUCT LENGTH SHALL BE 5'-0". ALL FLEXIBLE DUCT SHALLCONFORM TO THE REQUIREMENTS OF U.L. 181 FOR CLASS 1 FLEXIBLE AIRDUCTS, WITH A MINIMUM R-VALUE OF R-6. SUPPORT FLEXIBLE DUCT TO ELIMINATEKINKING AND SAGGING. (FLEXIBLE DUCT IS NOT PERMITTED IN EXPOSED AREAS, RETURNAIR GRILLE AND EXHAUST AIR GRILLE CONNECTIONS).

PIPING

1. ALL PIPING LINES, INCLUDING CONDENSATE DRAINS, SHALL BE FULLY INSULATEDWITH MINIMUM 1-1/2" THICK, 0.75 LB DENSITY, INSULATION WITH ALL SERVICE JACKETAND VAPOR BARRIER, FLAME SPREAD RATING OF 25 OR LESS, AND SMOKE-DEVELOPEDRATING OF 50 OR LESS.

2. CONDENSATE PIPING FROM AIR CONDITIONING EQUIPMENT SHALL BE PITCHED AMINIMUM OF 1/4" PER FOOT, IN THE DIRECTION OF FLOW.

3. CONDENSATE DRAIN PIPES SHALL HAVE CLEANOUTS AT EVERY CHANGE IN DIRECTION,DISTANCES GREATER THAN 3 FEET, AND AT THE BEGINNING OF LONG STRAIGHT RUNS.

4. HVAC CONTRACTOR SHALL BE RESPONSIBLE FOR THE SIZING OF REFRIGERANTLINES (LONG LINE APPLICATION) GREATER THAN 50'-0". HVAC EQUIPMENTSUPPLIER SHALL VERIFY REFRIGERANT PIPE LINE SIZES AND CONFIGURATIONSBASED ON CONTRACTOR'S PROPOSED PIPE ROUTING.

AFU F

BHP

CFMCU

DBDDC

EATEERE/FEWH

FFCU

HPHVAC

IN

KW

LATLBS

MBHMCA

OED

RPMRTU

SEERSP

TU

VAV

W/WB

ANNUAL FUEL UTILIZATION EFFICIENCY

BRAKE HORSEPOWER

CUBIC FEET PER MINUTECONDENSING UNIT

DRY BULBDIRECT DIGITAL CONTROL

ENTERING AIR TEMPERATUREENERGY EFFICIENCY RATIOEXHAUST FANELECTRIC WALL HEATER

FAHRENHEITFAN COIL UNIT

HORSEPOWERHEATING, VENTILATING, AIR CONDITIONING

INCHES

KILOWATT

LEAVING AIR TEMPERATUREPOUNDS

1,000 BRITISH THERMAL UNITSMINIMUM CIRCUIT AMPACITY

OPEN END DUCT

REVOLUTIONS PER MINUTEROOFTOP UNIT

SEASONAL ENERGY EFFICIENCY RATIOSTATIC PRESSURE

TERMINAL UNIT

VARIABLE AIR VOLUME

WITHWET BULB

303 South Park AvenueBuffalo, N.Y. 14204716.856.6448 tel716.852.1722 fax

266 Alexander StreetRochester, N.Y. 14607585.244.3780 tel585.244.1294 fax

www.cjsarchitects.com

SYMBOL DESCRIPTION SYMBOL DESCRIPTION

SUPPLY DUCT RISER TEMPERATURE SENSORS

RETURN DUCT RISER PROGRAMMABLE, 7-DAY, 24-HOUR THERMOSTATT

CONTROL WIRING (PLENUM RATED)EXHAUST DUCT RISER

AIRFOIL TURNING VANES

EBS ENGINEERING, PCDUCT RISE OR DROPENGINEERED BUILDING SYSTEMSMECHANICAL / ELECTRICAL ENGINEERS

4050 RIDGE LEA ROADBUFFALO NEW YORK 14228HVAC DRAWING LISTFLEXIBLE DUCT

PHONE:FAX:E-MAIL:

(716) 836-9600(716) 836-9636INTERNALLY LINED DUCTWORK

[email protected]

M-2

M-3

M-4

M-5

HVAC SCHEDULES, LEGENDS AND ABBREVIATIONS

HVAC SCHEDULES

FLOOR PLAN - HVAC DUCTWORK AND PIPING

ROOF PLAN - HVAC DUCTWORK AND PIPING

HVAC DETAILS

WEBSITE: WWW.EBSPE.COM4- MANUAL VOLUME DAMPERSCOPYRIGHT C 2016 ENGINEERED BUILDING SYSTEMS

DIRECTION OF SLOPE (DOWN IN DIRECTION OF ARROW)

0 ROUND

(p

D. 8o

s o j

0 47

S o

SUPPLY AIR DEVICE -FIRST NO. CFM, SECOND NO. TYPETHIRD NO. NECK SIZE

200-1

(REFER TO SCHEDULE FOR SIZE)RETURN / EXHAUST AIR DEVICE -FIRST NO. CFM, SECOND NO. TYPETHIRD NO. NECK SIZE (IF REQUIRED)

200-2 G8"0(REFER TO SCHEDULE FOR SIZE)

IN®

AIR DISTRIBUTION DEVICE SCHEDULE VARIABLE AIR VOLUME TERMINAL UNIT SCHEDULEKEY PLAN

INLETDUCTSIZE(DIA.)

AIR QUANTITYSTYLE &DEVICE

SIZEMINIMUM

OUTSIDE AIRCFM

MOUNTING DESCRIPTION MANUFACTURERSYMBOL MODEL NO. MARK AREA SERVED MANUFACTURER MODEL NO. TOTALCFM

40wVIILiTM1$SUPPLY ESMB-08(BYPASS) 8"0TU-01 MIT OFFICE 39 TITUS 200 75

[O]TYPE 1

cOmpaniesconstruction I development

SUPPLY24x24

ARCHITECTURAL PLAQUE FACE, STEEL CONSTRUCTION,LAY-IN 3 SLOTS (SLOT WIDTH IS 1-1/2"), OPPOSED BLADE

VOLUME DAMPER, 4-WAY THROW, WHITE FINISHTITUS DAT

ESMB-08(BYPASS) 8"0TU-02 MIT OFFICE 43 TITUS 300 100

OWNER:

49 S. WATER STREET, LLCRETURN MULTIPURPOSECONFERENCE ROOM 14

ESMB-10(BYPASS) 10"oTU-03 TITUS 500 125

RETURN24x24

PERFORATED FACE, STEEL CONSTRUCTION, OPPOSED BLADELAY-IN VOLUME DAMPERS, PROVIDE 22"x22" BACKPAN FOR FULL

PANEL LAY-IN APPLICATION, WHITE FINISH

500 SENECA ST - SUITE 508BUFFALO, NY 14204(71 6) 332-5959 tel.(716) 332-5968 fax.

0 TITUS PARVESTIBULE 1, WAITING 2,TOILET 3,RECEPTION DESK 4

ESMB-12(BYPASS)

TYPE 212"0TU-04 TITUS 850 200

EXHAUST ESMB-08(BYPASS) 8"0TU-05 MIT OFFICE 40 TITUS 300 100

EXHAUST24x24

PERFORATED FACE, STEEL CONSTRUCTION, OPPOSED BLADELAY-IN VOLUME DAMPERS, PROVIDE 22"x22" BACKPAN FOR FULL

PANEL LAY-IN APPLICATION, WHITE FINISH

Q FLEX BUILDINNGOFFICE/EDICALREIAIL

TITUS PARESMB-10(BYPASS)

TYPE 310"oMULTIPURPOSE ROOM 41TU-06 TITUS 500 125

OFFICE 12, OFFICE 13,OFFICE 15, OFFICE 16,OFFICE 18, OFFICE 20

ESMB-12(BYPASS)AIR DISTRIBUTION DEVICE NOTES: 49 S. WATER STREET

VILLAGE OF GOWANDANEW YORK 14070

12"0 1,000TU-07 TITUS 200

1. ALL DEVICES SHALL BE FROM A SINGLE MANUFACTURER.

2. ALL DEVICES SHALL HAVE MATCHING MATTE, WHITE FINISH (UNLESS OTHERWISE NOTED IN DESCRIPTION ABOVE).

3. MAXIMUM NC OF 20.

4. ACCESSORIES:

A. OPERATING KEYS: TOOLS DESIGNED TO FIT THROUGH DIFFUSER FACE AND OPERATE VOLUME CONTROL DEVICEAND / OR PATTERN ADJUSTMENT

5. ACCEPTABLE MANUFACTURER'S - TITUS, PRICE.

OFFICE 6, OFFICE 7,OFFICE 9, OFFICE 11

ESMB-10(BYPASS) 10"oTU-08 TITUS 700 175

DRAWING TITLE

6. THE BIDDER MUST SUBMIT IN WRITING TO THE ARCHITECT / OWNER, WHO WILLFORWARD TO THE ENGINEER, ANY REQUEST FOR A PROPOSED DEVIATION,MODIFICATION, OR SUBSTITUTION TO THESE DRAWINGS AND SPECIFICATIONS FOREVALUATION NO LATER THAN TEN (10) DAYS PRIOR TO THE BID DATE.

A. A REQUEST FOR ANY SUBSTITUTION SHALL BE ACCOMPANIED BY TECHNICALDATA, DRAWINGS, PRODUCT SAMPLES, AND COMPLETE DATA SUBSTANTIATINGCOMPLIANCE OF PROPOSED SUBSTITUTION THAT MEET / EXCEED SPECIFIEDMATERIALS AND IN COMPLIANCE WITH THESE DRAWINGS AND SPECIFICATIONS.

1). REQUESTS FOR SUBSTITUTION SHALL BE MADE ONLY BY THE BIDDER;REQUESTS FOR SUBSTITUTION FROM SALES REPRESENTATIVES, VENDORS,OR SUPPLIERS ARE NOT ACCEPTABLE.

B. NO MATERIALS SHALL BE DEEMED ACCEPTABLE IF NOT IN STRICT AND FULLCOMPLIANCE WITH THESE DRAWINGS AND SPECIFICATIONS.

C. ALL BIDDERS MUST BID SOLELY ON THE SPECIFIED MATERIALS UNLESSACCEPTANCE BY THE ENGINEER OF A DEVIATION, OMISSION, MODIFICATION,OR SUBSTITUTION IS GRANTED IN WRITING THROUGH THE ARCHITECT / OWNERTO ALL BIDDERS PRIOR TO THE BID DATE.

1). FAILURE TO SUBMIT PROPOSED SUBSTITUTED EQUIPMENT / MATERIALSPRIOR TO THE BID EVALUATION DATE, AND IS INCLUDED IN THE BIDDERSPRICE / SUBMITTAL REVIEW DRAWINGS (AFTER THE PROJECT IS AWARDED);WILL RESULT IN A "REJECTED" SUBMITTAL PACKAGE.

HVACSCHEDULES, LEGENDSAND ABBREVIATIONS

VARIABLE AIR VOLUME TERMINAL UNIT NOTES:CONTROLS

1. ALL CONTROL WIRING AND CONDUIT SHALL COMPLY WITH THE NATIONAL ELECTRICCODE (NEC) AND NFPA 70.

2. ALL CONTROL WIRING AND POWER CONDUCTOR INSULATION SHALL BE PLENUMRATED.

3. ALL EXPOSED CONTROL WIRING SHALL BE INSTALLED IN 3/4" EMT CONDUIT.

4. PROVIDE ALL RELAY, CONTACTORS, ETC. REQUIRED TO ACHIEVE INTERLOCK OPERATIONOF EQUIPMENT.

BALANCING

1. MECHANICAL CONTRACTOR, WHO IS CERTIFIED BY EITHER THE ASSOCIATED AIR BALANCECOUNCIL (AABC) OR NATIONAL ENVIRONMENTAL BALANCING BUREAU (NEBB); UPONCOMPLETION OF THE PROJECT, SHALL PERFORM A COMPLETE TESTING AND BALANCINGOF ALL EQUIPMENT. BALANCE SYSTEM TO WITHIN ±5% OF AIR QUANTITIES INDICATEDON PLANS AND SCHEDULES AND PROVIDE THE OWNER WITH A COMPLETE, SIGNED ANDSEALED BALANCE REPORT.

1. MINIMUM 20-GAUGE GALVANIZED STEEL HOUSING WITH INTEGRAL SOUND ATTENUATOR.

2. LOW LEAKAGE BYPASS DIVERTING CONTROL DAMPER WITH EDGE SEALS.

3. MINIMUM 1/2" THICK (CLOSED-CELL) FIBRE-FREE INTERNALLY LINED.

4. FACTORY INSTALLED MODULATING ACTUATOR (0-10V DC, CONTROLLED BY THERMOSTAT).

5. MAXIMUM AIR PRESSURE DROP OF 0.40 INCHES WG.

6. ACCESSORIES:

A. DISCHARGE AIR SENSOR.

B. WALL MOUNTED THERMOSTAT (MODULATING (0-10V DC OUTPUT).

C. FACTORY INSTALLED ACCESS DOOR.

7. MAXIMUM RADIATED NC OF 25 AND DISCHARGE NC OF 22.

8. ACCEPTABLE MANUFACTURERS: CARRIER, TITUS, PRICE.

JOB NO. 1210

SCALE NONEELECTRIC WALL HEATER SCHEDULE4.15.2016DATE

VOLTS / PHMANUFACTURER SERIES AMPSMARK AREA SERVED MODEL NO. TYPE MBH WATTSDRAWN BY

3450 SERIES(HEAW DUTYFAN FORCED)

SEMI-RECESSEDMOUNTING

CHECKED BY208/1/602,000EWH-1 VESTIBULE 1 MARKEL F3453T 6.8 9.6

REVISIONS

ELECTRIC WALL HEATER NOTES:

1. ELECTRIC WALL HEATERS SHALL CONTAIN AN INTEGRAL, TAMPERPROOF THERMOSTAT.

3. ELECTRIC WALL HEATERS SHALL BE EQUIPPED WITH BUILT-IN THERMAL OVERLOAD PROTECTION.

4. FURNISHED AND INSTALLED BY DIVISION 23.

A. WIRING BY DIVISION 26.

5. FURNISH 2" SEMI-RECESSED MOUNTING FRAME #3450EX16 FOR EACH SEMI-RECESSED MOUNTED ELECTRIC WALL HEATER.

6. COLOR, INCLUDING CUSTOM COLOR, AS SELECTED BY ARCHITECT.

7. ACCEPTABLE MANUFACTURERS - MARKEL, Q'MARK, INDEECO.

THIS IS A SINGLE SHEET OF A COHESIVESET OF CONSTRUCTION DOCUMENTS

(INCLUDING DRAWINGS AND SPECIFICATIONS).INTERPRETATION OF THE INFORMATIONAS PRESENTED SHOULD BE BASED ON

THE ENTIRE SET OF DOCUMENTS.

DRAWING NO.

M-1100% DESIGN SUBMISSION

*1

AR

CH

ITE

CT

S,

LLP

CHAINTREUIL JENSEN STARKROOFTOP UNIT SCHEDULESTATICPRESS.IN. WG

EXT.

DX COOLING COIL GAS HEATING SECTION SUPPLY AIR FANSUPPLY I RETURN I OUTSIDE OPERATINGWEIGHT(LBS.)

303 South Park AvenueBuffalo, N.Y. 14204716.856.6448 tel716.852.1722 fax

266 Alexander StreetRochester, N.Y. 14607585.244.3780 tel585.244.1294 fax

www.cjsarchitects.com

MOTORMARK AREA SERVED TONS AIRCFM

AIRCFM

AIRCFM

MANUFACTURER MODEL NO. EER MCAMIN.ROWS

MBHINPUT

MBHOUTPUT

AFUE%

MBH EAT 'F LAT 'F EAT 'F LAT 'F RPMVOLTS / PHBHP HP

180.0 147.0(1ST STAGE) |(1ST STAGE) 460/3/603,625 2,875 1,450ENTRY 36, STORAGE 37, KITCHEN 38, MIT OFFICE 39, COMMUNITY ROOM 42, MIT OFFICE 43RTU-1 8.5 750 0.60 CARRIER 48HCF-09 97.0 80 67 4 82% 58 95 855 1.86 3 12.0 25.0224.0 184.0(2ND STAGE) 1(2ND STAGE)

82.0 66.0(1ST STAGE) 1 (1ST STAGE) 460/3/601,225 1,400RTU-2 FAMILY CARE OFFICE 21, SUPERVISOR 22, ENTRY 23. OFFICE 24, MECHANICAL 25, STORAGE 32, JANITOR 34 3.0 975 250 0.60 CARRIER 48HCE-04 36.0 80 67 3 80% 58 95 935 0.55 12.5 14.01115.0 89.0(2ND STAGE) 1(2ND STAGE)

192.0 156.0 * EBS ENGINEERING, PCVESTIBULE 1, WAITING 2, TOILET 3, RECEPTION DESK 4, CORRIDOR 5, DATA 5A, TOILET 8, TOILET 10,MULTIPURPOSE CONFERENCE ROOM 14, STORAGE 17, TREATMENT ROOM 19, STORAGE 26, BREAKROOM 27,OFFICE 28, OFFICE 29, RECORDS 30, WOMENS TOILET 33, MENS TOILET 35, MIT OFFICE 40, MULTIPURPOSE ROOM 41

(1ST STAGE) 1 (1ST STAGE) ENGINEERED BUILDING SYSTEMSMECHANICAL / ELECTRICAL ENGINEERS4050 RIDGE LEA ROADBUFFALONEWYORK 14228

460/3/605,500 4,375 1,1.25 2,400RTU-3 12.5 0.80 CARRIER 48HCF-14 146.0 80 67 4 81% 58 95 760 2.99 5 12.2 34.0240.0 195.0(2ND STAGE) 1(2ND STAGE) ,PHONE:

FAXEAIL:

(716) 836-9600(716) 836-963682.0 66.0

(1ST STAGE) 1 (1ST STAGE) [email protected]/3/601,700 1,325 1,400RTU-4 OFFICE 6, OFFICE 7, OFFICE 9, OFFICE 11, OFFICE 12, OFFICE 13, OFFICE 15, OFFICE 16, OFFICE 18, OFFICE 20 5.0 375 0.60 CARRIER 48HCE-06 57.5 80 67 4 81% 57 95 1196 1.05 2 12.45 17.0115.0 90.0 WEBSITE: WWW.EBSPE.COM

(2ND STAGE) 1(2ND STAGE) COPYRIGHT C 2016 ENGINEERED BUILDING SYSTEMS

4OF NEw0

CO0 Ujo L

47t,k9o4ss\

ROOFTOP UNIT NOTES:

9. CONTROLS ACCESSORIES:

A. COMFORTLINK CONTROLS: SYSTEM CONTROLLER WITH VISUAL SCROLLING MARQUEE DISPLAY (LCDDISPLAY CONTROLLER). COORDINATE EXACT LOCATION IN FIELD WITH OWNER PRIOR TO INSTALLATION.

1. I-VU CONTROL SYSTEM (COORDINATE EXACT LOCATION IN FIELD WITH OWNER PRIOR TO INSTALLATION).2. TOUCH PILOT (LCD DISPLAY CONTROLLER WITH TOUCH SCREEN). COORDINATE EXACT LOCATION IN

FIELD WITH OWNER PRIOR TO INSTALLATION.

31. SPACE TEMPERATURE SENSORS WITH OVERRIDE.4 .PRIMARY AIR SENSORS.5 .ACTUATOR WITH 4-2OmA OUTPUT.6 .INTERLOCKS FOR OTHER EQUIPMENT.

10. INSTALLATION:

A. UNITS SHALL BE ON MANUFACTURER PROVIDED, FULL PERIMETER, INSULATED ROOF CURBSUITABLE FOR THE ROOF DECK, INSULATION AND MEMBRANE (REFER TO ARCHITECTURALDRAWINGS FOR ROOF CONSTRUCTION).

B. ALL SERVICES TO THE UNIT SHALL ENTER WITHIN THE ROOF CURB. NO SEPARATE ROOFPENETRATIONS ARE ALLOWED.

11. ACCEPTABLE MANUFACTURER'S - CARRIER, MON, McQUAY.

8. ACCESSORIES:

A. 2'-0" HIGH, SOLID BOTTOM THERMAL / ACCOUSTICAL ROOF CURB.

B. OUTSIDE AIR INTAKE HOOD AND RELIEF / EXHAUST HOOD.

C. MODULATING, LOW-LEAKAGE, OPPOSED BLADE OUTSIDE AIR DAMPERS.

D. POWER EXHAUST.

E. CARBON DIOXIDE (C0 2 ) SENSOR FOR OUTSIDE AIR CONTROL OVERRIDE,MOUNTED IN RETURN AIR DUCTWORK.

F. DISCHARGE AIR SENSOR MOUNTED IN SUPPLY AIR DUCTWORK.

G. HUMIDI-MIZER DEHUMIDIFICATION CONTROL.

H. STAINLESS STEEL, DOUBLE-SLOPE DRAIN PAN WITH P-TRAP ASSEMBLY.

I. FACTORY INSTALLED AND WIRED NON-FUSED DISCONNECT SWITCH.

J. FACTORY INSTALLED AND WIRED 120 VOLT GFI DUPLEX RECEPTACLE.

7. UNIT SHALL HAVE:

A. R41OA REFRIGERANT.

B. ALL SECTIONS SHALL HAVE HINGED ACCESS DOORS.

C. MOTORS SHALL HAVE BUILT-IN OVERLOAD PROTECTION.

D. UNITS SHALL HAVE ADJUSTABLE PITCH MOTOR SHEAVES AND MOTOR PULLEYS.

E. 2-STAGE GAS HEATING AND SINGLE-STAGE COOLING (RTU-2, RTU-4).

F. 2-STAGE GAS HEATING AND 2-STAGE COOLING (RTU-1, RTU-3).

G. 30% PLEATED FILTERS.

H. ALUMINIZED STEEL HEAT EXCHANGER.

1. FACTORY INSTALLED REMOTE SHUTDOWN TERMINALS.

J. DOUBLE-SLOPE DRAIN PAN WITH P-TRAP ASSEMBLY.

K. UNIT MOUNTED CONTROLS WITH FACTORY MOUNTED CONTROL BOARD.

1. UNITS SHALL BE LISTED AND LABELED WITH THE ENERGY STAR LOGO.

2. FACTORY ASSEMBLED, PACKAGED UNIT WITH ROOF CURB AND ALL STANDARD ACCESSORIES.

3. UNIT SHALL BE SINGLE-WALL CONSTRUCTION.

4. UNIT SHALL BE U.L. OR AGA APPROVED.

5. UNIT SHALL BE OF DOWNFLOW DESIGN AND SHALL HAVE 100% ECONOMIZER FUNCTION.

A. UNIT SHALL HAVE 100% ECONOMIZER FUNCTION WITH DIFFERENTIAL ENTHALPY CONTROLAND MINIMUM OUTSIDE AIR SETTING, AND BAROMETRIC RELIEF.

6. COMPRESSORS SHALL BE HIGH EFFICIENCY DESIGN.

IN0KEY PLAN

ROOF EXHAUST FAN SCHEDULE FAN COIL UNIT SCHEDULESTATICPRESS.IN. WG

EXT.

STATICPRESS.IN. WG

EXT.

FAN MOTOR DX COOLING COIL ELECTRIC HEAT SUPPLY FANROOFCURBSIZE

OPERATINGWEIGHT(LBS.)

SUPPLYAIRCFM

OPERATINGWEIGHT(LBS.) - do4Tlt1$W1MARK AREA SERVED CFM MANUFACTURER MODEL NO. MARK AREA SERVED MANUFACTURER MODEL NO. MCA SEERMIN.

ROWSVOLTS / PH VOLTS / PHFAN TYPE DRIVE TYPE RPM SONES HP MBH EAT 'F LAT *F MBH KW FLA RPM WATTS

companiesconstruction I development

450(LOW)600

(HIGH)

RAV-SP18OUTUL(IN-CEILING) 208/1/601/10 120/1/60E/F-1 JANITOR 34 125 0.125 GREENHECK LD-80-VG CENTRIFUGAL DIRECT 858 1.4 GPI-19-A12 75 FCU-1 MULTIPURPOSE ROOM 41 CARRIER 19.0 80 67 18.8 20.5 50

OWNER:450

(LOW)600

(HIGH)

TOILET 3,WOMENS TOILET 33,MENS TOILET 35

RAV-SP180UTUL(IN-CEILING)1/6 120/1/60 208/1/60E/F-2 450 0.25 GREENHECK LD-95-VG CENTRIFUGAL DIRECT 1162 4.6 GPI-19-A12 75 FCU-2 MULTIPURPOSE CONFERENCE ROOM 14 CARRI ER 19.0 80 67 18.8 20.5 50 49 S. WATER STREET, LLC

500 SENECA ST - SUITE 508BUFFALO, NY 14204(71 6) 332-5959 tel.(716) 332-5968 fax.

1/10 120/1/60E/F-3 TOILET 8, TOILET 10 200 0.25 GREENHECK LD-90-VG CENTRIFUGAL DIRECT 1046 2.7 GPI-19-A12 75FAN COIL UNIT NOTES:

4. ACCESSORIES:

A. LOW AMBIENT CONTROLS.

B. SERVICE VALVES WITH SCHRADER PORTS.

C. VIBRATION ISOLATION HANGERS.

5. ACCEPTABLE MANUFACTURERS - CARRIER, LG, McQUAY.

*NOTE: FAN COIL UNITS ARE POWERED BY IT'S ASSOCIATED CONDENSING UNIT POWER.

1. UNITS SHALL BE LISTED AND LABELED WITH THE ENERGY STAR LOGO.

2. HEAT PUMP UNIT.

3. UNIT SHALL HAVE:

A. R41OA REFRIGERANT.

B. MINIMUM 20-GAUGE, FACTORY FINISHED, BONDERIZED STEEL CABINET.

C. 3-SPEED CENTRIFUGAL MOTOR.

D. FAN MOTOR THERMAL OVERLOAD PROTECTOR.

E. MICROPROCESSOR CONTROLS.

F. SELF-DIAGNOSTICS.

G. CONDENSATE DRAIN PAN WITH CONDENSATE PUMP.

H. INTERNAL TRANSFORMER FOR WALL MOUNTED 24V THERMOSTAT CONTROL.

I. FREEZESTAT.

J. FILTER TRACK WITH CLEANABLE FILTERS.

K. ALL NECESSARY CEILING BRACKETS AS REQUIRED FOR A COMPLETE INSTALLATION.

ROOF EXHAUST FAN NOTES:

FLEX BUILDINNGOFFICE/MEDICAL/RETAIL

1. HOUSING - "LOW PROFILE" ANODIZED ALUMINUM WITH HINGED HOOD AND ALUMINUM BIRDSCREEN.

2. FAN - BACKWARD INCLINED ANODIZED ALUMINUM.

3. BUILT-IN POWER DISCONNECT.

4. MOTORS SHALL HAVE BUILT-IN THERMAL OVERLOAD PROTECTION.

5. ACCESSORIES:

A. MOTORIZED, OPPOSED BLADE, LOW LEAKAGE ALUMINUM CONTROL DAMPERS (120V ACTUATOR).

B. 1" THICK FAN HOUSING INSULATION.

C. VARI-GREEN EC MOTOR WITH MOUNTED POTENTIOMETER DIAL.

6. ROOF CURBS:

A. EACH EXHAUST FAN SHALL BE EQUIPPED WITH AN INSULATED, ANODIZED ALUMINUM ROOF CURB (0.080" MINIMUM THICKNESS), ALL WELDED JOINT CONSTRUCTION.

B. ALL CURBS SHALL BE MINIMUM 1'-0" HIGH.

7. INTERLOCK EXHAUST FAN (E/F-1) WITH ASSOCIATED ROOFOTP UNIT (RTU-2) OPERATION.

8. INTERLOCK EXHAUST FANS (E/F-2 AND E/F-3) WITH ASSOCIATED ROOFOTP UNIT (RTU-3) OPERATION.

9. MAXIMUM SONES TO BE 5.1 OR LESS, UNLESS OTHERWISE INDICATED.

10. ACCEPTABLE MANUFACTURER'S - GREENHECK, COOK.

49 S. WATER STREETVILLAGE OF GOWANDA

NEW YORK 14070

DRAWING TITLE

HVAC SCHEDULES

JOB NO. 1210CONDENSING UNIT SCHEDULE

SCALE NONEREFRIGERANT CONNECTIONS MOTOR OPERATING

WEIGHT(LBS.)

MARK AREA SERVED MANUFACTURER MODEL NO. MBH MCA SEER 4.15.2016DATEVOLTS / PHLIQUIDSUCTION RPM HP

DRAWN BY1/2" 1/4" 208/1/60CU-i FCU-1 CARRIER RAV-SP180AT2-UL 19.0 VARIABLE 17.0 20.5 100

CHECKED BY

REVISIONS1/2" 1/4" 208/1/60CU-2 FCU-2 CARRIER RAV-SP1 80AT2-UL 19.0 VARIABLE 17.0 20.5 100

CONDENSING UNIT NOTES:

10. ACCESSORIES:

A. LOW AMBIENT CONTROLS.

B. WINTER START CONTROL.

C. CRANKCASE HEATER.

D. PE MOUNTING BASE (INSULATED PIPE RISER CURB).

E. EQUIPMENT RAIL (MINIMUM 1'-0" HIGH).

11. ACCEPTABLE MANUFACTURERS - CARRIER, LG, McQUAY.

9. UNIT SHALL HAVE:

A. R41OA REFRIGERANT.

B. LIQUID LINE SOLENOID VALVE.

C. LINE SET.

D. FILTER DRIER.

E. THERMOSTATIC EXPANSION VALVES.

1. UNITS SHALL BE LISTED AND LABELED WITH THE ENERGY STAR LOGO.

2. UNIT CABINET SHALL BE CONSTRUCTED OF HEAVY-GAUGE, CORROSION RESISTANT STEEL, WITHFACTORY POWDER COAT PAINT.

3. UNIT CABINET SHALL BE EQUIPPED WITH COATED STEEL SAFETY WIRE GUARDS TO PROTECT CONDENSERFAN OPENING.

4. UNIT ENCLOSURE SHALL CONTAIN FACTORY WIRING, PIPING, CONTROLS, COMPRESSOR, REFRIGERANT CHARGE,AND SPECIAL FEATURES.

5. CONDENSER COIL SHALL BE CONSTRUCTED OF ALUMINUM FINS MECHANICALLY BONDED TO COPPER TUBES.

6. CONDENSER FAN SHALL BE DIRECT DRIVE DIRECT DRIVE, PROPELLER TYPE, MULTIPLE SPEED OPERATION.

7. COMPRESSORS SHALL BE VARIABLE SPEED (INVERTER) TYPE.

8. MOTORS SHALL HAVE BUILT-IN THERMAL OVERLOAD PROTECTION.

THIS IS A SINGLE SHEET OF A COHESIVESET OF CONSTRUCTION DOCUMENTS

(INCLUDING DRAWINGS AND SPECIFICATIONS).INTERPRETATION OF THE INFORMATIONAS PRESENTED SHOULD BE BASED ON

THE ENTIRE SET OF DOCUMENTS.

DRAWING NO.

m.2100% DESIGN SUBMISSION

AR

CH

ITE

CT

S,

LLP

CHAINTREUIL JENSEN STARK

DA B C SUPERVISOR

22

24x10 TO RTU-2ON ROOF(975 CFM)

10xlO TO E/F-1ON ROOF(125 CFM)

125-3

16x12 FROM RTU-2ON ROOF(1225 CFM) 303 South Park Avenue

Buffalo, N.Y. 14204716.856.6448 tel716.852.1722 fax

266 Alexander StreetRochester, N.Y. 14607585.244.3780 tel585.244.1294 fax

www.cjsarchitects.com

975 CFM

'7ENTRY

2324x12 OEDW/ BIRDSCREEN150-1 150-1 150-1 150-1

100" 8"0 8"0 NOTES: O2

125-2 STORAGE10"o

MECHANICAL- -JAN ---- 10Ox8 251- 10x4

200-2 348x6S100-112x8

75-1 M-3OFFICE

24

1488x6

. 8x4-

150-1

150-1 8x68"0 8x6 1. 1" CONDENSATE DRAIN TO NEAREST SANITARY DRAIN. REFER

TO PLUMBING DRAWINGS FOR DRAIN LOCATION.

2. 3/8" REFRIGERANT LIQUID (RL) FROM CONDENSING UNIT ONROOF, 5/8" REFRIGERANT SUCTION (RS) TO CONDENSING UNITON ROOF.

225-1 225-110-'0 10-0

FAMILY CAREOFFICE

21

II 1 8"0125-2

STORAGE 10"016x8 12x8 10x6 10x6 EBS ENGINEERING, PC37 ENGINEERED BUILDING SYSTEMS

MECHANICAL / ELECTRICAL ENGINEERS-4050 RIDGE LEA ROAD/8-0ENTRY

36/ | j_ |I I

KITCHEN38 10x6

BUFFALO, NEW YORK 142284375 CFM16x8

325-2

I 425-2fw1x12 If4fI

x

I 1 II

| | -

125-2~jj PHONE: (716) 836-9600FAX:

150-2 v46x18 OEDW/ BIRDSCREEN

, 716) 836-9636r10-.0 -TORTU-2

-J A" [email protected]:I'I III I

WEBSITE: WWWEBPE.COMI II I S I I

F d9-- E- r COPYRIGHT ( 2016 ENGINEERED BUILDING SYSTEMSE EI'll ~ v I, Li 7Lii150-2 IN DDC F- -7- -11004

-175-1225-1 PANEL11111 II 1 1 .BREAKROOM8"010"o 125~-1 175-1 46x12 TO RTU-3

ON ROOF(4375 CFM)

250-110O

-34x18 I I

I r OFFICE8x6 CORR 8"O STORAGE U1111

L -- -- -- --- 31 -8x6 8x4 26 xo86-- 18X10 . 86

TO 150-2 I

TU-01 100----i~:200-1 175-2 8x6 _ _

100 MENM1 T 10"O TOILET 150-1

OFFICE II 80 75-2--- 3539 L 80

39 ,,150-1 1 14x8- 5-18"Olo r 80- 8 '

8 027 4OF N"D

o

08 4 7 A

PESs0

8x61 0"o2 14 L --20Ix- _ __ _

ID TO34x26 FROM RTU-3ON ROOF(5500 CFM)

TU-07 I-- x10 L 28x16

16x8

175-1

175-1

16x8 ------ ( )

8xE 8x6200-2OFFICE12"028LI+- TU-04 ,

150-214x8/10-"0luxo10x6

225-1

18x10

8x6 8x6- 10x6

)TU-06-14x8 - 8"0

TU-0310x6 10x6OFFICELI~ OFFICE

29

-

WOMENS 14x8 -175-3 14x8150-28x4TOILET33

150-11-1 1, o16x108"0 18. 10O0H GENERAL NOTES:K

KF 150-18"0 U11 3- 150-18-0

8x6150-1TU-01

DNFt15-3 M-3

no8"012x6 -14x8200-28-0 8x6

125-2' 12"o300-1 300-1 8x6II11 I1 F-110O0IIII~1I 1 0x812-'0 12-0 8x68x6 - 1. PROVIDE VOLUME DAMPERS AT ALL BRANCH DUCTWORK TAPS.

2. COORDINATE EXACT LOCATIONS OF TEMPERATURE SENSORS ANDTHERMOSTATS IN FIELD WITH ARCHITECT AND OWNER PRIOR TOINSTALLATION TO AVOID CONFLICTS WITH WALL MOUNTED ARCHITECTURALITEMS.

8x6 112x6- L

650-2

-14x8

300-2

-125-1r--

TOFCU-1

125-18x6 150-1|8-0

10x0 TO E/F-2lox~2

16x10 8"O

KEY PLAN

I IIT

8'

8x4-

12"0TO

N014"o 1Ox6-- 18x10 T

sTU-03

TOFCU-2

ON ROOF250-1 8x6OFFICEE

1 1I(450 CFM)

RECORDSCOPY / MAIL

30

IU1II IIthlill n10-.0 450-2 --16x8- 16TO

TU-06FCU-2 14"0 150-1II IMULTIPURPOSE E 8"10

AL12x6-1 12x6 ROOM 150-1 2r==

I lill EIIw wTh450-2 125-1 a~z~iis8"010x6 -- -E41FCU-1

11 ,14"0 125-1 14x8., 300-28x6 8x6IN

F

I-

12x8

16x12

E 8-0COmparies

construction I development

OWNER:

49 S. WATER STREET, LLC

214"o2 8x6--- 7 8x6550-214"0

F-lI--I24x10 - . MULTIPURPOSE--

1 L|_JO.E-

12x6

CONFIRM

1J4>

---- ,

I300-1 300-1 10 075-1 175-1150-1 1 TO12"o 12"0 8"-0 8"0 TU-07 100-2

1O0

24x10 TO RTU-4ON ROOF(1325 CFM)

150-1

8"0 .100-3250-1T

RTU-336x12 TO 8"0AV. TREATMENT 16x12

ROOMRTU-1 ON ROOF A &

1 M

~' ~% /.- iiiiI(2875 CFM) >Ii2.219 , 8x6 500 SENECA ST - SUITE 508

BUFFALO, NY 14204(716) 332-5959 tel.(71 6) 332-5968 fax.

8x68X4

STORAGE

12x6 17-00-3

4 II' lk 12"0F]

I I I I1 1I

28x14 FROM RTU-1ON ROOF(3625 CFM)

2875 CFM36x14 OED

I---1L 14x8

I 7

ZL -----150-2 --

OFFICEhi TORECEPTION TU-04

DESK

8x6 1325 -

1325 CFM

- Il IW/ BIRDSCREEN

TO '

10"-015I 1I100-3300-1

L8-0I12"0 24x12 OED

W/ BIRDSCREEN

16x12 FROMRTU-4 ON ROOF(1700 CFM)

- TOTU-05

250-2

12x8-I TOILET3

STU-05

RTU-1 175-2T

O 8x4- li -- 1x8I I ' 16x10 - -

1 1 150-1

II__ 88x68x4

8x4- 8x6 150-1

150-1675-2 '----L2 12x6

75-1

COMMUNITY 8x4-\ FLEX BUILDINNGOFFICE/MEDICAL/RETAIL

F, E8-014-0ROOM

42III I IlI 75-1MIT

8x410x6

20x 10 12"o OFFICE 8"0

12x6 40

225-1T DATA5o

10"0 III A12x6 12x6 F p'~ j~ TOILET

8/~

-4LS. 21K 2. U300-1300-1 III I I 49 S. WATER STREETVILLAGE OF GOWANDA

NEW YORK 14070

12"012"o 'j47'I -rTtt 8"0I IIT-

18x10* 75-1

,]

8x6

OFFICE

13 ,TU-02

1 10x6L 8x4 I II 100-210x10 TO E/F-3 8..olxe8 10O0425-2 TOILET

1 0250-2ON ROOF 14x8

10x614"0 8x6 12"0(200 CFM) 14x6200-1IIIII~II -8x6

125-2

DRAWING TITLE10"1650-2 C 75-1225-1 125-1I 71---

1-

14"o 10x8 10x8 8"010"0 8"OTOTU-02

125-1 10"o--_CORR

< 5[|1 el ~~2221 FLOOR PLAN -

HVAC DUCTWORKAND PIPING

I l l 8 0

8."07

TU-08/A I 1 00- r-l

I II I

10x6 1 0x8 16x10

I 1EEI00 -2 1 xI I10x6H' r-7m I III I I IOFFICE

12

T 1 1 1'11 11 150-1I I I II I18x6- 8"0I1 - T 7*z 41 1 lII I II10"0

OFFICE wA'IlI . -

VESTOFFICE

7175-2 1V 12x6 12x6 THS8x6-8x6 8x6- WAITING

29

8x6-

10-0250-2I J 125-2 JOB NO. 1210OFFICE300-1 300-1 12"oIII I I TO TO10"0 --12"o 12"0 8x6- 8x6MIT

OFFICE

43

TU-08 RTU-4 11,ISCALE 3/16" = 1'-0"OFFICE

6 ,125-110x6I8"0 4.15.2016DATE200-1

Q-

S10x6<II 12x810-0 1150-1 150-1

EWH-1 DRAWN BY8"0 8"01 F EK

CHECKED BY150-1 125-210 0r-

150-1 150-1 125-2-10O---

200-212"0

250-18"O0 8"O0 8"0 10-0

REVISIONS

THIS IS A SINGLE SHEET OF A COHESIVESET OF CONSTRUCTION DOCUMENTS

(INCLUDING DRAWINGS AND SPECIFICATIONS).INTERPRETATION OF THE INFORMATIONAS PRESENTED SHOULD BE BASED ON

THE ENTIRE SET OF DOCUMENTS.

FLOOR PLAN - HVAC DUCTWORK AND PIPING1M-3 SCALE: 3/16" =

DRAWING NO.

M-3100% DESIGN SUBMISSION

CA

)

91

AR

CH

ITE

CT

S,

LLP

CHAINTREUIL JENSEN STARK

303 South Park AvenueBuffalo, N.Y. 14204716.856.6448 tel716.852.1722 fax

266 Alexander StreetRochester, N.Y. 14607585.244.3780 tel585.244.1294 fax

www.cjsarchitects.com

ROOF PLAN GENERAL NOTES:2M-4

1. DIVISION 7 AND DIVISION 23 TO COORDINATE ALL ROOF OPENING, ROOFPENETRATIONS, AND EQUIPMENT PAD INSTALLATIONS.

2. DIVISION 7 TO CUT ALL ROOF OPENINGS.

3. DIVISION 23 TO PROVIDE AND INSTALL ALL EQUIPMENT PADS AND CURBS.

4. DIVISION 7 TO PROVIDE ROOF FLASHING AND SEALING OF ALL ROOF OPENINGS.

5. COORDINATE LOCATION AND SPACING OF ROOF TRUSSES WITH DIVISION 6 FORDUCTWORK PENETRATIONS PRIOR TO INSTALLING ROOF TRUSSES. DIVISION 6SHALL ADJUST TRUSS SPACING TO ALLOW FOR A MINIMUM OF 2" CLEAR (ALLSIDES) AROUND OPENING AND PROVIDE ANY ADDITIONAL SUPPORTS REQUIREDTO SUPPORT DIVISION 15 EQUIPMENT.

a

EBS ENGINEERING, PCENGINEERED BUILDING SYSTEMSMECHANICAL I ELECTRIC ENGINEERS4050 RIDGE LEA ROADBUFFALO, NEW YORK 14228,PHONE:FAX:E-MAIL:

(716) 836-9600(716) 836-9636

[email protected]: WWW.EBSPE.COM

COPYRIGHT C 2016 ENGINEERED BUILDING SYSTEMS0

LN 10x10 FROMBELOW(125 CFM)

E/F-1(75 LBS)

I

RTU-2 -(1400 LBS)

l_- IIl4OF N

0 Lu

SS0(oo

L, '-+-46x12 FROM0 0BELOW(4375 CFM)

34x26 TO

F-7x16x12 TO

BELOW 0(1225 CFM) I/- 1'

BELOW(5500 CFM)

RTU-3(2400 LBS)

,

24x10 FROMBELOW(975 CFM)

IK -I10x10 FROMBELOW

N0(450 CFM)

KEY PLANE/F-2(75 LBS)

EVeiLiYijT*]

companiesconstruction IdevelopmentCU-2

CU-1(100 LBS)

1/4" REFRIGERANT LIQUID (RL) TO BELOW,1/2" REFRIGERANT SUCTION (RS) FROM BELOW

0 (100 LBS)OWNER:

RTU-1(1450 LBS)

F-

I ,'II 49 S. WATER STREET, LLC1/4" REFRIGERANT LIQUID (RL) TO BELOW,1/2" REFRIGERANT SUCTION (RS) FROM BELOW

500 SENECA ST - SUITE 508BUFFALO, NY 14204(71 6) 332-5959 tel.(716) 332-5968 fax.

028x14 TOBELOW RTU-4 -

(1400 LBS) F 7(3625 CFM)

36x12 FROMBELOW(2875 CFM) FLEX BUILDINNG

OFFICE/MEDICAL/RETAIL16x12 TOBELOW(1700 CFM)

24x10 FROMBELOW(1325 CFM)/ 49 S. WATER STREET

VILLAGE OF GOWANDANEW YORK 14070

R - 10x10 FROMBELOW(200 CFM)

E/F-3(75 LBS) DRAWING TITLE,

ROOF PLAN -HVAC DUCTWORK

AND PIPING

JOB NO. 1210II

I ISCALE 3/16" = 1'-iI I

I III I4.15.2016DATEI I

I II II II

DRAWN BYI

CHECKED BY

REVISIONS

THIS IS A SINGLE SHEET OF A COHESIVESET OF CONSTRUCTION DOCUMENTS

(INCLUDING DRAWINGS AND SPECIFICATIONS).INTERPRETATION OF THE INFORMATIONAS PRESENTED SHOULD BE BASED ON

THE ENTIRE SET OF DOCUMENTS.

ROOF PLAN - HVAC DUCTWORK AND PIPING1M-4 SCALE: 3/16" =

DRAWING NO.

M-4100% DESIGN SUBMISSION

AR

CH

ITE

CT

S,

LLP

I - HANGER STRAP(DO NOT MOUNT TO ROOF DECK,FASTEN TO ROOF TRUSSES)

LOAD RATED FASTENERWITH WASHERS

INSULATED DUCTWORK

DUCT BAND(SAME SIZE AS HANGER STRAP)

TRANSITION INSTALL AFTERLAST TAKEOFF CHAINTREUIL JENSEN STARKINSULATED DUCTWORK

rI II II IIlIII I

METAL SPIN-IN FITTING WITH VOLUME DAMPER AIR FLOW AIR FLOW 303 South Park AvenueBuffalo, N.Y. 14204716.856.6448 tel716.852.1722 fax

266 Alexander StreetRochester, N.Y. 14607585.244.3780 tel585.244.1294 fax

www.cjsarchitects.com

DRAW BAND(TYPICAL)

STEEL SUPPORT ROD(TYPICAL)

TRANSITION TO DUCT

VARIABLE AIRVOLUME BOX

ROUND ORRECTANGULARDUCT TRANSITION TOVAV AIR CONNECTION(SEE PLANS FORSIZES)

OPPOSED BLADEMANUAL VOLUMEDAMPER

"645' ANGLE TAP COLLARr

I I I I

II II I I I

--1(1" MINIMUM ON TOP ANDBOTTOM, SEAL ALL AROUND)PROVIDE ADJUSTABLE ELBOWRINGS FOR RECTANGULAR TO

SUPPORT FROMSTRUCTURE ABOVE

INTERNALLY LINED-DUCTWORK

OPEN END

(SEE PLANS FOR SIZE)

SUPPLY

VOLUME DAMPERWITH QUADRANTAND LOCK ANDSTANDOFF COLLAR(TYPICAL)

HANGER SIZES FOR ROUND DUCTAIRNUMBER

OFHANGERS

ROUND DUCT CONNECTIONROUNDHANGERS

MAXIMUMSPACING 0

-J_

<

DUCT DIAMETER STRAP HANGERS '-UINSULATED FLEXIBLE DUCT(5'-0" MAXIMUM LENGTH)

NECK SIZE

OPPOSED BLADEVOLUME DAMPER

DAMPER OPERATOR(REMOVABLE)

EBS ENGINEERING, PC,,ENGINEERED BUILDING SYSTEMSMECHANICAL / ELECTRICAL ENGINEERS

4050 RIDGE LEA ROAD1/4" RODUP THRU 30" 1" x 16 GAUGE 10'-O 1

OPPOSED BLADEVOLUME DAMPER

DAMPER OPERATOR(REMOVABLE)

BUFFALO, NEW YORK 142281-1/2" x 1-1/2" x 1/8"3/8" ROD31" THRU 60" 10'-O" 1 EXHAUST BRANCH TAKEOFF FITTING DETAIL PHONE: (716) 836-9600FAXTAKE-OFF FITTING2'-0" 716) 836-9636

EXTENSIONDUCTCOLLAR

'[email protected]:HANGER STRAPS(DO NOT MOUNT TO ROOF DECK,FASTEN TO ROOF TRUSSES)

(MINIMUM)WEBSITE: WWW.EBSPE.COM^'---

_ _ COPYRIGHT C 2016 ENGINEERED BUILDING SYSTEMS'NECK SIZE FLEXIBLE CONNECTION -------II DUCT RING

60" MAXIMUM_ - SELF TAPPING CADMIUM PLATED HEX OUTER CONE

3'-0" MINIMUM, STRAIGHT,HARD METAL DUCT

OUTER CONEDUCT RING

CEILINGGASKETFACE SIZE

TRANSITION INSTALL AFTERLAST TAKEOFFI

CEILINGFACE SIZEL1=1 HEAD SHEET METAL SCREW, STRAPS

TO BE TIGHT AGAINST DUCT ' d-^ OF ND 8o0 ~r0S D. O

o4719Css\

AIR FLOW AIR FLOW' 'I ITEEL~J

-~ ~-1 TRUNK DUCT

6"45' ANGLE TAP COLLARHANGER SIZES FOR RECTANGULAR DUCT(1" MINIMUM ON TOP ANDBOTTOM, SEAL ALL AROUND)PROVIDE ADJUSTABLE ELBOWRINGS FOR RECTANGULAR TOROUND DUCT CONNECTION

VOLUME DAMPERWITH QUADRANTAND LOCK ANDSTANDOFF COLLAR(TYPICAL)

INSTALLATION NOTES:LONGESTDIMENSIONOF DUCT

ROUNDHANGERS

MAXIMUMSPACINGSTRAP HANGERS

1. FASTEN DUCT RING TO EXTENSION DUCT COLLAR WITH SHEETMETAL SCREWS.

2. "TAP-OUT" EITHER SIDE OR BOTTOM OF DUCT; TOP "TAP-OUT"IS NOT ACCEPTABLE.

0-j1/4" RODUP THRU 18" 1" x 16 GAUGE 10'-0"

1/4" ROD19" THRU 30" 1" x 16 GAUGE 10'-0"

SUPPLY BRANCH TAKEOFF FITTING DETAIL VAV BOX DETAILDUCT HANGER DETAIL CEILING DIFFUSER CONNECTION DETAIL RETURN GRILLE CONNECTION DETAIL

DISCONNECT SWITCH 2" x 6" PRESSURE TREATEDNAILER

14 GAUGE GALVANIZEDCAP/ ROOFTOP UNIT

UNION

CLEANOUT PLUG

SLOPE AT MINIMUM1/4" PER FOOTAWAY FROM UNIT

GASKET MATERIAL

PRESSURE TREATED WOODEN NAILER

RIGID / THERMAL INSULATION

ACOUSTICAL LINING

KEY PLAN

MOTOR

1~EXHAUST FAN

N0-11 I 4' 'ml

PAN HEADWOOD SCREW U

COUNTERSUNKSHEETMETALSCREW

CONDUIT CHASE VVj_,

COUNTER FLASHI-BIRDSCREEN

EXHAUST FAN METAL CURB CAP

INSULATED ROOF CURB

COUNTERFLASHING

BONDING ADHESIVE

r-

LVIILViIiI.]14 GAUGE GALVANIZEDBASE & BASE PLATE.END CAPS & SEAMSTO BE CONTINUOUSWELDED

FLASHINGMEMBRANE

BONDINGADHESIVE

COmpaniesconstruction I development

OWNER:

49 S. WATER STREET, LLC

"A"

TYPE "L" COPPER OR0MEMBRANE FLASHING - "B"

SPLICING CEMENT SCHEDULE 40 PVC PIPE SPLASH(TYPICAL)

ROOF- 1

BLOCK 3"3" MINIMUM 4'- 1'-C

1" MINIMUM-{ LAP SEALANT

ROOFINGMATERIAL]

LAP SEALANT

/ 500 SENECA ST - SUITE 508BUFFALO, NY 14204(71 6) 332-5959 tel.(716) 332-5968 fax.

INSULATIONROOF MEMBRANEDIMENSION "A" DIMENSION "B"COIL CONFIGURATION

INSULATION

ROOF DECK

fZ~Iw '/z z/

/ /L ROOFCURB

FAN DISCHARGE STATICPRESSURE PLUS 1"1BLOW-TH RU ,

PRESSURE TREATED WOOD BLOCKING

STEEL ANGLE FRAMING

ROOF DECKFAN SUCTION STATICPRESSURE PLUS 1"

2-1/2"DRAW-THRUTWO-POSITION MOTORIZED LOWLEAKAGE BACKDRAFT DAMPER

EXHAUST DUCTWORK

DAMPER ACTUATOR

ROOF

FLEX BUILDINNGOFFICE/MEDICAL/RETAIL

NOTES:

1. MINIMUM "A" OR "B" DIMENSION SHALL NOT BE LESS THAN 1".

2. COPPER CONDENSATE DRAIN LINES SHALL BE INSULATED WITH MINIMUM1-1/2" THICK ARMAFLEX II SLIP-ON TYPE INSULATION.

3. DISCHARGE CONDENSATE PIPING A MINIMUM OF 3'-0" AWAY FROM UNITTO RSPLASH BLOCK ON ROOF (UNLESS PROHIBITED BY LOCAL CODE).

2"x6" PRESSURE TREATED WOODBLOCKING BY DIVISION 7

SECURE CURB TO ROOF WITHSHEETMETAL SCREWS, LAG BOLTS,WITH ROOF CONSTRUCTION

ROOFING SHALL EXTEND UP ANDOVER TOP OF CURB

LEAD SHIELD ANCHOROR ANCHORS AS PERROOF CONSTRUCTION

JOIST

14 GAUGE GALVANIZED BASE-& BASE PLATE. ENDCAPS & SEAMS TO BECONTINUOUS WELDED

NOTES:

1. SECURE UNIT CURB CAP TO ROOF CURB WITH WITH SHEET METAL SCREWS 1'-0" ON CENTER ALL AROUND.

2. SECURE ROOF CURB TO ROOF WITH SHEET METAL SCREWS, LAG BOLTS OR OTHER METHOD CONSISTENT WITHROOF CONSTRUCTION AT 1'-0" ON CENTER ALL AROUND.

ROOF MOUNTED EXHAUST FAN DETAIL

49 S. WATER STREETVILLAGE OF GOWANDA

NEW YORK 14070

THERMAL / ACOUSTICAL ROOFTOP UNITCONDENSATE TRAP DETAIL

DRAWING TITLEROOF MOUNTED EQUIPMENT RAIL DETAILROOF CURB DETAIL

HVAC DETAILS

JOIST OR BEAM

LOCKNUTS

STRAPS

DUCT-SEAL

CRIMP OR

JOB NO. 1210THREADED HANGER ROD LOW VOLTAGE

WIRE SCALE NONEPIPE INSULATIONADJUSTABLE CLEVIS HANGER

PIPE

METAL PIPE SADDLE

ALL SERVICE PVC JACKET

-] [--2" OVERLAP

T I I TOR,

COVER

THERMISTOR

4.15.2016DATE

PIPE DRAWN BYINSULATION

CHECKED BY

REVISIONSSOLDER LEADS

END STAGGERED SEAM(SEAL WITH ADHESIVE) JUNCTION BOX-I-

THREADED ROD

PROVIDE 2 LOCKNUTS

ADJUSTABLE CLEVISHANGER

=

- WALL

MOUNT 4'-6" (MINIMUM)ABOVE FINISHED FLOOR,AND 4'-0" (MINIMUM)ABOVE FINISHED FLOORFOR ADA APPLICATIONS

THIS IS A SINGLE SHEET OF A COHESIVESET OF CONSTRUCTION DOCUMENTS

(INCLUDING DRAWINGS AND SPECIFICATIONS).INTERPRETATION OF THE INFORMATIONAS PRESENTED SHOULD BE BASED ON

THE ENTIRE SET OF DOCUMENTS.

PIPE INSULATION NOTE:

1. ALL PIPING EXPOSED IN OCCUPIED AREAS SHALL BE JACKETEDWITH MATERIALS SUITABLE FOR PAINTING., ~ METAL PIPE SADDLE

DRAWING NO.

INSULATION SHIELD M-5THERMOSTAT / TEMPERATURESENSOR MOUNTING DETAILSINGLE PIPE HANGER DETAIL PIPING INSULATION JACKET DETAIL 100% DESIGN SUBMISSION

AR

CH

ITE

CT

S,

LLP