ngt calculation
TRANSCRIPT
Sheet1CALCULATION FOR NEUTRAL GROUNDING TRANSFORMERPROJECT : 11KV, 40MW CONDENSING TYPE TURBO GENERATOR Generator MW Rating57**Generator KV Rating11**Generator Capacitance/Ph (U(Micro Farad)0.286**Connected Capacitance(assumed)/Ph (Micro Farad)0.0572**Connected Capacitance(assumed)/Ph (Micro Farad)0.006**Net Capacitance/Ph 0.3492LAPT Capacitance/Ph (Micro Farad)0.3**Total Capacitance (Micro Farad)0.64923 X Capacitance1.9476Xc1634.3699228989Capacitor Current/Amps3.885811206Field Forcing Allowance (a)5.8287168089NGT Vk (KV) (b)11**Insulation (KV) (Vp)11**NGT KVA (a x b)64.1158848984Rounded off KVA65Equ. Primary Resistance ( c )1634.3699228989Secondary Voltage Selected (Vs)240**Secondary Resistance c x ( Vs/Vp) Sq.0.7780141121Trafo. Resistance (assumed)/Ohms0.05708External Resistance/Ohms(Total Res. - Tr.Resistance) Rs0.7209341121Current Rating/Amps KVA/Rs = Isq =90160.805145535I =300.2678889684Rounded Off Current Rating301NGA Rating :65KVAFor 30secNGR Rating (LR):0.7209341121 +/_ 10%Ohms** values to be entered