modelling for potential increases in lighting power ... · cynthia jolley-rogers is a lighting...
TRANSCRIPT
AIRAH and IBPSA’s Australasian Building Simulation 2017 Conference, Melbourne, November 15-16.
1
MODELLING FOR POTENTIAL INCREASES IN LIGHTING POWER
DENSITY STRINGENCY IN SECTION J6 OF THE NCC
CYNTHIA JOLLEY-ROGERS Secretary, Canberra branch IESANZ, NSW Chapter
Energy Action Australia Pty Ltd
Suite H, 59-69 Lathlain Street
Belconnen ACT 2617
LYNLEY BOLAND Energy Action Australia Pty Ltd
Suite H, 59-69 Lathlain Street
Belconnen ACT 2617
PAUL BANNISTER, F.AIRAH, FIEAUST, MIPENZ Energy Action Australia Pty Ltd
Suite H, 59-69 Lathlain Street
Belconnen ACT 2617
ABOUT THE AUTHOR
Cynthia Jolley-Rogers is a lighting consultant with Energy Action and Secretary of the ACT branch
of the IESANZ. She has worked in lighting for 30 years, and in energy efficiency for 8 years.
Cynthia designs lighting upgrades, provides analysis on lighting energy efficiency policies,
strategies and training courses, and peer review for lighting designs for clients from a wide range of
industries, bodies and government departments. Cynthia has previously presented a paper at the
Improving Energy Efficiency in Commercial Buildings 2016 in Frankfurt on the pros and cons of
using LED in lighting upgrades.
ABSTRACT
Energy Action was engaged to provide analysis and recommendations on updating Section J for the
2019 version of the NCC (National Construction Codes), including Section J6 for Artificial
Lighting. The analysis involved running 20 lighting simulations across 14 models to test the
existing lighting IPD (W/m2) which were based on existing fluorescent and metal halide technology
and establish a baseline. A further 20 lighting simulations were run across the 14 models to provide
a test case exploring the possible stringency of new requirements which could be developed based
on current LED technology. This paper presents the results of these simulations and discusses some
of the insights revealed by our analysis of those results regarding the potential stringency of Section
J6 as LED technology increasingly becomes the main player in lighting efficiency.
AIRAH and IBPSA’s Australasian Building Simulation 2017 Conference, Melbourne, November 15-16.
2
1. INTRODUCTION
1.1 Background
The National Construction Code (NCC) is seen as a major policy instrument which may address
rising energy prices and pressure for improved energy productivity and reduced greenhouse gas
emissions.
The NCC provides two methods for complying with energy efficiency requirements. The first is by
building simulation which provides an opportunity to calculate an entire building’s energy
efficiency including all services and the building fabric. This means that trade-offs between more or
less efficient services or structures can be made, but the building must meet the energy efficiency
requirements as a whole. The second method for complying with NCC energy efficiency
requirements is by complying with the Deemed to Satisfy clauses.
The provisions of NCC Volume 1 Section J – Energy Efficiency Deemed to Satisfy clauses
comprise parts 1 through 8. This paper is concerned with Section J6 which deals with the energy
efficiency of artificial lighting in commercial building interiors and perimeters and includes many
technical concepts which are specific to lighting. Definitions are provided for words and concepts in
the Nomenclature section of this paper. All words with definitions provided have been italicised.
Section J6 covers interior lighting and perimeter lighting in separate sections, and using different
methods. Interior lighting energy efficiency is primarily addressed through maximum requirements
for Illumination Power Density (IPD) as described in Table J6.2a of the Code, and adjustment
factors for unusual room aspect ratios (RAR) and for lighting controls. Some alternative
requirements are described for specific lighting situations such as track lighting and perimeter
lighting.
Section J6 was first introduced along with the rest of Section J in 2006. Parts of Section J were
updated in 2009, but the improved efficiencies afforded by electronic ballasts and T5 fluorescent
tubes prompted only marginal improvements to the efficiency requirements of lighting. This is clear
from the maximum IPDs still required by the 2017 code which are very easily achieved using
technology which was in wide use in 2009.
Since 2009, lighting technology has advanced at such a rate that the industry is now barely
recognisable as the same industry which functioned at the time that Section J6 was first introduced.
In fact, lighting technology has advanced to such an extent that in 2017 the maximum IPDs
required by the existing code are regularly double the IPDs achieved in the most routine lighting
designs.
The key brief for the current project was therefore to investigate the viability of increasing the
stringency of Section J6 through data collection, simulation, calculation and analysis to match
current economic, construction and environmental circumstances for updates in the 2019 version of
the NCC.
For lighting this meant that a base case was required in order to understand where the industry had
arrived in terms of pre-LED technology’s performance against the existing code. The base case was
set up via a series of simulations using pre-LED technology and the results of these simulations
were compared to the requirements of the existing code.
AIRAH and IBPSA’s Australasian Building Simulation 2017 Conference, Melbourne, November 15-16.
3
The question of how LED would perform compared with pre-LED technology was then analysed
using a series of test case simulations and the results of these simulations were used to propose new
IPD requirements for the code.
2. METHODOLOGY
2.1 Simulations
A base case simulation was created in AGi32 version 17.4 with 16 standard rooms. Each standard
room is a model – numbered 1 through 16. The 16 models are defined by their Room Aspect Ratio
(RAR).
Section J6 defines the equation for Room Aspect Ratio (RAR) as: 𝐴
𝐻 𝑥 𝐶
where A= the area of the room, H= ceiling height and C=the perimeter of the room.
The first 11 models have an RAR below 1.5, and qualify under the existing rules for use of an
adjustment factor to increase the required IPD. The last 5 have an RAR above 1.5 and do not qualify
for the use of an adjustment factor under the existing rules.
Section J6 defines the equation for the RAR adjustment factor as:
0.5 + (𝑅𝐴𝑅/3)
The maximum required IPD is divided by result of this equation to increase the maximum allowed
IPD for that space.
Standard room shapes were selected to represent space types typically encountered in most
buildings. The standard room shapes were:
• a long thin rectangle representing a corridor or a long thin room;
• a short fat rectangle representing a square or nearly square room, and
• an L-shape room representing a room with unusual shapes or which contains corners.
Each room area was allocated a room shape which correspondended to the typical shape or use for a
room of that size for most buildings. Table 1 lists the range of standard room models with their
corresponding room areas, room aspect ratios (RAR) and room shapes which were used in the
simulations.
AIRAH and IBPSA’s Australasian Building Simulation 2017 Conference, Melbourne, November 15-16.
4
Model number Room area (m2)
Ceiling heights (m)
RAR Room shape
1 15 10.0 0.05 Long thin rectangle
2 15 10.0 0.10 Short fat rectangle
3 100 5.0 0.20 Long thin rectangle
4 100 5.0 0.33 L-shape
5 15 2.4 0.40 Short fat rectangle
6 500 10.0 0.54 Short fat rectangle
7 100 2.7 0.62 L-shape
8 100 2.4 0.69 L-shape
9 500 5.0 0.83 Long thin rectangle
10 100 2.7 0.89 Short fat rectangle
11 100 2.4 1.00 Short fat rectangle
12 500 2.7 1.54 Long thin rectangle
13 500 2.7 2.01 Short fat rectangle
14 1000 2.7 2.44 Long thin rectangle
15 1000 2.7 2.92 Short fat rectangle
16 1000 2.4 3.28 Short fat rectangle
Table 1. Standard rooms simulated in AGi32
To deliver the project within the required timelines some trade offs were required. To prevent the
calculation speed of the simulations from running overly long, the impact of windows, furniture and
furnishings absorbing light was compensated for by setting the rooms surface reflectances to very
low levels.
The first group of simulations were used to establish models which could achieve:
• the targeted maximum IPD for
• a maintained average of 320 lux
• on a working plane of 0.7m with
• AGi32 pre-set surface reflectances of Floor = 0.2, Walls = 0.5, Ceiling = 0.8
• A maintenance factor of 0.8 using
• T8 fluorescent recessed troffers.
The maintained averages achieved were well above the recommended levels.
A number of simulations were run, gradually reducing the surface reflectance’s to a level where the
IPD became more difficult to achieve and the average maintained illuminance levels dropped by 12-
18%, but still achieved the target. From this point all models used the very poor surface reflectance’s
of Floor = 0.1, Walls = 0.2, Ceiling = 0.2, which would essentially be an almost black room.
Models 1 and 2 were discarded from further simulations because their geometry was unrealistic;
their ceiling heights for such small areas not being representative of any space which would require
artificial lighting.
Table 2 lists the simulations run for each of the illuminance targets in each model. Notice in Table 2
that average maintained illuminance levels recommended in AS/NZS1680 relate to specific tasks or
AIRAH and IBPSA’s Australasian Building Simulation 2017 Conference, Melbourne, November 15-16.
5
work spaces, and most of these spaces come in a range of shapes. However the target of 800 lux
relates only to the daylight adjustment zone of car park entry ramps which are all long thin spaces
by their nature.
Note also in Table 2 that the NCC mandates a minimum illuminance for safe movement, which is
described in AS/NZS1680.0 as 20 lux, however since targeting an average of 40 lux generally
achieves a minimum of 20 lux no extra simulations were run for the target of 20 lux minimum.
Illuminance targets per room shape
Long thin
rectangle
Short fat
rectangle L-shape
2016 maximum
illumination
Power Density
(W/m²)
1 N/A N/A
20 20 N/A
40 40 40 6
80 80 80 5
160 160 160 7
240 240 240 8
320 320 320 9
600 600 600 15
800 N/A N/A 25
Retail Retail Retail N/A
Table 2. Illuminance targets simulated for each room shape.
A base case was created for all maintained average illuminance targets to find the capacity of pre-
LED technology to meet existing IPD requirements and ensure that the simulations could achieve
those existing requirements.
The base cases used the following technology types:
• T5 and T8 linear fluorescent troffers and battens
• Metal halide (MH) high bays (HB)
• Compact fluorescent (CFL) down lights (DL)
• Metal halide (MH) down lights (DL)
Linear fittings and downlight scenarios were modelled separately. For models with very high
ceilings in simulations where high illuminance levels where required, linear fittings were
inadequate for the job so high bay fittings were used.
Existing adjustments for RAR were applied to achieve the required IPD in rooms with an RAR that
qualified for that adjustment, where required, though at all times the maximum IPD without
recourse to the adjustment for RAR was targeted.
A further series of test case simulations was run to test how low the IPD could be reduced while
achieving the target maintained illuminance using LED technology for each model and illuminance
target, using adjustments for RAR only where absolutely necessary.
AIRAH and IBPSA’s Australasian Building Simulation 2017 Conference, Melbourne, November 15-16.
6
The test cases used the following LED luminaire types:
• Troffers and battens
• High bays (HB)
• Down lights (DL)
2.2 Retail simulations
Retail lighting posed its own issues. There are no Australian Standards on which to base target
illuminance for retail. To source target illuminance levels for retail lighting we measured the
average illuminance of the shops at the local mall and compared the results to the recommended
retail illuminance targets provided in the CIBSE SLL Lighting Guides. The Society of Light and
Lighting (SLL) are part of CIBSE in the UK.
Table 3 shows the results of illuminance measurements taken in shops at Belconnen Mall in
Canberra in January 2017 using a calibrated Hagner brand illuminance (lux) meter. The technology
in the first 4 shops was predominantly linear fluorescent, and in the last shop was LED. This audit
indicated that illuminance levels in Australian shops with fluorescent technology range between 330
to 1,000 lux and that at least some shops using LED technology are exessively bright with
illuminance levels above 2,000 lux.
Retailer Average vertical
illuminance on a
selection of shelves
Average horizontal
illuminance on
merchandise
Average illuminance
on floor
Supermarket 1 336, 373 986 465, 483
Supermarket 2 332, 389 666 498
Department store 1 446, 1175 822 796
Department store 2 332, 375, 378, 723 585 609
Jewellery store 1830, 1720, 1320 1254, 2206
Table 3. Average illuminances measured in retailers at Belconnen Mall, January 2017
The Society of Light and Lighting (SLL) recommend between 500-1,000 lux vertical illuminance on
merchandise for low budget shops, 100 – 200 lux plus accent lighting on merchandise in high
budget shops, and 250- 500 lux on merchandise with some accent lighting on merchandise in value
for money and quality profile shops.
In arriving at a target illuminance for the retail sector for use in simulations for this project,
consideration was given to the difference in recommended illuminance between Australian offices
and European offices. The Australian Standards recommend a maintained average of 320 lux on the
task in an office, while European standards call for 500 lux. Given the existing Australian retail
illluminance levels tend to be around the 300-400 lux range, with some spikes up to 700 or 1,000
lux, and CIBSE’s recommendations sit between 500 and 1,000 lux for their brighter shops, a
recommended target of between 250-500 lux on the merchandise could be reasonably interpolated
for Australia, with circulation style levels of 160-240 lux on the floor.
AIRAH and IBPSA’s Australasian Building Simulation 2017 Conference, Melbourne, November 15-16.
7
In order to achieve the various horizontal and vertical illuminance targets the lighting technology
types were combined in the retail lighting simulations. The base case retail simulation used the
following technology types in the one simulation:
• T5 linear fluorescent battens
• Metal halide (MH) high bays (HB)
• Metal halide (MH) down lights (DL)
The LED retail simulation used LED down lights (DL) and shop lighters.
3. RESULTS
Table 4 shows the IPD results achieved in the simulations with pre-LED technology and with LED
technology for each of the illuminance targets (lux levels) recommended in AS/NZS1680.
Item 40 lux 80 lux 160
lux
240
lux
320
lux
400
lux
600
lux
Retail
250-
500
lux
800
lux
Existing max
basic IPD 6 5 7 8 9 10 15 22 25
Base case
Fluorescent,
CFL & MH
max basic IPD
1.58 2.16 4.03 6.3 7 8.5 14 22 16.9
Test case
LED max
basic IPD
0.83 1.04 2.3 2.9 4.2 5.8 9.6 13.8 11.2
Recommended
new max basic
IPD
1 1.5 2.5 3 4.5 6 10 14 11.5
Table 4. IPD results achieved in base & test cases.
From the simulation results it was determined that the current code requirements could be readily
surpassed with pre-LED technology, and that the use of LED fittings allows the extent of
improvement to be increased further.
The bottom row of Table 4 shows the proposed new maximum IPDs based on the simulation
results.
Table J6.2a in Section J6 of the NCC lists the maximum required IPD requirements for a range of
space types and tasks based on recommended illuminance levels from AS/NZS1680. Table 5.
Proposed revised stringencies based on an update of Table J6.2a from the Deemed to Satisfy clauses
of Section J of the NCC
of this report shows Table J6.2a with the existing maximum IPD requirements next to the proposed
maximum IPD requirements. The proposed maximum IPD listed in Table 5 are all derived from the
recommended new maximum basic IPD in Table 4.
AIRAH and IBPSA’s Australasian Building Simulation 2017 Conference, Melbourne, November 15-16.
8
Space types
Illuminance
target
2016
maximum
illumination
Power
Density
(W/m²)
Proposed 2019
maximum
illumination
Power Density
(W/m²)
Auditorium, church and public hall 160 10 2.5
Board room and conference room - during AV
presentation
Minimum of
20 lux 10 1
Board room and conference room -
intermittent use, minimal note taking or
reading
240 10 3
Board room and conference room - regular or
constant use, regular note taking or reading 320 10 4.5
Carpark – general 40 6 1
Carpark - entry zones (first 20m of travel
during the day) 800 25 11.5
Carpark - entry zones (first 20m of travel at
night) 160 25 2.5
Common rooms, spaces and corridors in a
Class 2 building 160 8 2.5
Control room, switch room and the like -
intermittent monitoring 240 9 3
Control room, switch room and the like -
constantly monitoring 320 9 4.5
Corridors 160 8 2.5
Courtroom 320 12 4.5
Dormitory of a Class 3 building used for
sleeping only 80 6 1.5
Dormitory of a Class 3 building used for
sleeping and study
160 in the
room, 320
on the desk
9 4.5
Entry lobby from outside the building 160-400 15 6
Health care - children's ward, infants wards,
emergency dept to operating room, bed head
reading
240 10 3
Health care - examination room 320 10 4.5
Health care - examination room in intensive
care and high dependency wards (use of task
lighting)
400 10 6
Health care - patient ward 160 7 2.5
Health care - other patient care areas including
corridors where cyanosis lamps are used -
wards and general transit areas
160 13 2.5
Health care - other patient care areas including
corridors where cyanosis lamps are used -
emergency dept to operating room
240 13 3
Kitchen and food preparation area 240 8 3
AIRAH and IBPSA’s Australasian Building Simulation 2017 Conference, Melbourne, November 15-16.
9
Space types
Illuminance
target
2016
maximum
illumination
Power
Density
(W/m²)
Proposed 2019
maximum
illumination
Power Density
(W/m²)
Laboratory - artificially lit to an ambient level
of 400 lx or more 400 12 6
Library - stack and shelving area 160 12 2.5
Library - reading room 320 9 4.5
Lounge area for communal use in a Class 3 or
9c building 240 10 3
Museum and gallery - circulation, cleaning
and service lighting 160 8 2.5
Office - artificially lit to an ambient level of
200 lx or more 320 9 4.5
Office - artificially lit to an ambient level of
less than 200 lx 160 7 2.5
Plant room 80 5 1.5
Restaurant, café, bar, hotel lounge and a space
for the serving and consumption of food and
drinks
80-400 18 6
Retail space including a museum and gallery
whose purpose is the sales of objects 250-500 22 14
School - general purpose learning areas and
tutorial rooms
320 on
desks 8 4.5
Sole occupancy unit of a Class 3 building 160 5 2.5
Sole occupancy unit of a Class 9c building 160 7 2.5
Storage with shelving higher than 75% of the
height of the aisle lighting 80 8 1.5
Service area, cleaner's room and the like 80 10 1.5
Toilet, locker room, staff room, rest room and
the like 80 5 1.5
Wholesale storage and display area 80 6 1.5
Stairs 80 10 1.5
Fire stairs used only for emergency egress 1 10 1
Table 5. Proposed revised stringencies based on an update of Table J6.2a from the Deemed to
Satisfy clauses of Section J of the NCC
For other spaces or illuminance levels, the required stringency should be set based on 1.4W/m² per
100 lux.
4. CONSULTATION STAGE
A consultation stage is in progress involving stakeholders throughout the lighting industry in
particular the representatives and members of the Lighting Council of Australia (LCA), the
Illuminating Engineers Society (IESANZ) and the Dark Sky Association (DSA). The original
AIRAH and IBPSA’s Australasian Building Simulation 2017 Conference, Melbourne, November 15-16.
10
analysis report was made available to these stakeholders, and several drafts of the proposed Section
J 2019 have been issued and consulted on. Feedback has been primarily around concern that the
proposed maximum IPD may be too low to achieve good quality lighting as defined by experienced
designers of lighting for complex spaces with complex lighting design needs such as high-end
offices, lobbies, retail, hospitality and the like. Concerns were raised around the following issues:
• The ability to achieve adequate lighting quality and levels in corridors, and in amenities with
high partitions, especially without adjustments for controls.
• The ability to achieve adequate light levels on ceilings and walls in line with LG7. It has
long been postulated that upcoming versions of the Australian Standards will include similar
requirements and the concern is that the proposed maximum IPD s will not allow for that.
• The ability to achieve IPD requirements using light sources with a colour temperature of
3,000K or below, or tunable white light sources.
• The tendency for very cool colour temperature lights to be used both externally and
internally to achieve the required IPD resulting in high levels of blue content lighting. Cool
colour temperature lights have a higher lm/W efficacy than warm colour temperature lights,
but as a result are often used in unsuitable applications instead of more appropriate warm
colour temperature lighting.
• The tendency for high glare luminaires to be used to achieve the required IPD as opposed to
luminaires with well screened LEDs which will make the luminaire more pleasant and more
suitable for use, but less efficient.
• The loss of an adjustment factor for controls. The original draft removed the IPD adjustment
factors for controls in an attempt to encourage designers to achieve the maximum IPD and
then add controls rather than using controls as a method to increase the IPD allowance.
However, it was considered that this would more likely discourage people from using
controls at all, which was not the intention.
• The impact on designs using high colour rendering (CRI) light sources which are typically
less efficient than standard CRI light sources.
• The efficacy stringency around perimeter lighting being so strict that decorative
architectural external luminaires which are heavily baffled to strategically target lighting and
protect the surrounding environment from excessive light spill will not qualify.
• The requirements to prevent external light from spilling direct beams of light into the sky
which would disqualify the use of low level orientation up-lights such as path lights and up-
lights on deciduous trees.
AIRAH and IBPSA’s Australasian Building Simulation 2017 Conference, Melbourne, November 15-16.
11
In response to these issues raised further analysis has been conducted and amendments made to the
drafts as follows:
• IPD adjustments for the use of controls has been re-instated with some tweaks to allow for
modern developments in dimming technology.
• IPD adjustments for lighting quality have been added including upward adjustments for the
use of warm white and high colour rendition light sources, and a penalty for using colour
temperatures over 5,300K.
• The minimum perimeter luminaire efficacy which was proposed for 105lm/W has been
reduced to 85lm/W and will be reviewed again after more data has been provided by the
LCA on the range of efficacies of architectural luminaires.
• Continuing work on the wording of requirements for the control of obtrusive exterior
lighting.
• Max IPD in Table J6.2a for corridors and amenities was adjusted up to 2.5W/m2 to correlate
with the illuminance target of 160 lux.
• The ABCB has agreed to engage interested stakeholders in the lighting industry to produce
case studies to prove or disprove the achievability of the proposed maximum IPDs and their
adjustment factors during 2018.
CONCLUSIONS
The results of the base case simulations using pre-LED technology which was available in 2009
show that it would have been possible to increase the stringency of maximum IPDs in Section J by
between 14% to 64% in 2009.
The results of the test case simulations which use LED technology available in 2017 show that it is
possible to increase the stringency of maximum IPDs in Section J by between 17% to 83% in 2019.
Industry consultation has raised issues around more complex spaces and lighting design issues
which the initial simulations and analysis did not have the opportunity to investigate. As more data
becomes available and further analysis is done on architectural luminaire efficacy and case studies
of complex spaces and lighting designs further drafts of the 2019 Section J will be produced which
should lead to an effective and useful tool for guidance on energy efficient and good quality lighting
design.
NOMENCLATURE
AGi32 – a lighting industry simulation software package produced by the US company Lighting
Analysis and distributed in Australia by Lighting Lab.
AIRAH and IBPSA’s Australasian Building Simulation 2017 Conference, Melbourne, November 15-16.
12
Average illuminance – the average light level calculated from a group of at least 3 measurements
taken on a working plane in a space as per measurement guidelines in AS/NZS1680.3
Ballast – an electrical device used in fluorescent and HID luminaires to limit the amount of current
in the circuit. Originally ballasts consisted of copper wire wound around an iron core. These are
known as magnetic ballasts and are still used to run high powered HID luminaires. Magnetic
ballasts in fluorescent luminaires and lower powered HID luminaires are still present in legacy
lighting equipment. Electronic ballasts are more efficient than magnetic ballasts and are used to run
modern fluorescent luminaires and low powered HID luminaires.
Batten - a surface mounted light fitting comprised solely of a lamp holder/s and a bare lamp. A
linear fluorescent batten comes with control gear included and may incorporate a diffuser.
CFL – Compact fluorescent Lamp
CIBSE – Chartered Institute of Building Services Engineers, London
Colour Rendering Index (CRI) – a meaurement out of 100 of the accuracy of the colour of an object
as it is percieved under a light source. Daylight is rated as having a CRI of Ra=100, as is a halogen
or an incandescent lamp. A typical fluorescent tube in Australia has a CRI of Ra = >80, and a
typical metal halide has a CRI of Ra=>70.
Colour Temperature (CCT) – the perceived colour of a white light source measured in according to
the Kelvin scale. 2,700K is the colour of incandescent light globes, while a warm white fluorescent
lamp of LED is typically 2,900K - 3,200K. 4,000K is a nuetral white colour popular in office
fluoresent lighting, 5,000K is a more natural daylight colour, 6,000K is a cool daylight colour and
8,000K is a very blue, white daylight colour more commonly used in the Europe than Australia. A
white LED is created by coating a blue LED with phosphor. The more phosphor, the warmer the
colour temperature of the light, hence the warmer the colour temperature, the less efficient the
LED chip becomes.
Warm colour temperature lighting is used in spaces to enhance feelings of relaxation and calm such
as hospitality and entertainment spaces and break out spaces in hospitals and commercial buildings.
Some major retail chains specify that warm white lighting must be used throughout their stores.
Cool colour temperature light sources are useful to increase alertness and help to see more clearly
when working on a detailed task but if used indiscriminately they have can have a detrimental
impact on our circadian rhythms and when used for exterior lighting, on plant and animal life
including pollination, biodiversity and food security.
Tunable white light sources are also less efficient but can be used to achieve balance in our
circadian rhythm by changing the colour temperature over the course of the day. Tunable white
LEDs can be preset to suit the needs of the occupants of the same space with varied needs at
different times –for example a cool colour temperature for older people playing bingo in a hall will
help them to see more clearly and stay alert, while a warm colour temperature will provide a calm
atmosphere for doing yoga and winding down at the end of the day in the same hall.
Daylight adjustment zone – AS/NZS1680 recommends that the first 15m of a car park entrance
ramp is lit to a maintained average of 800 lux during the day to provide a distance of travel into the
AIRAH and IBPSA’s Australasian Building Simulation 2017 Conference, Melbourne, November 15-16.
13
car park where the eyes are able to adjust from the bright daylight outside which can be well over
2,000 lux to the dimmer interior light levels for which the standard recommends a maintained
average of 40 lux.
Design life – the length of time that a system is designed to meet specified requirements. This
differs from the actual life of the system which may be forced to run much longer than it is designed
to do while decreasing in efficacy as it ages.
Down light – a square or circular luminaire typically using a halogen lamp, a CFL or a HID. It may
be recessed into the ceiling or mounted on the surface.
Electronic ballast – refer to the definition for “ballast”.
Fluorescent - an electric tube that produces light by creating an electric arc through a gaseous
mixture thus exciting a layer of phosporous powder on the inside of the tube causing the powder to
fluores. The original linear fluorescent tube was also made into a more compact form by reducing
the diameter and bending and twisting the tube to form compact fluorescent lamps. Original
fluorescent lamps and tubes contained only 1 layer of phosphor, but tri-phosphor technology was
developed in the 1990s which increased the performance to such a degree that single phosphor or
halo phosphor tubes were outlawed in Australia for tubes above 15W under the MEPS legislation.
Horizontal illuminance – the amount of light falling on a horizontal plane, measured in lumens per
square metre (lm/m2).
Illuminance - the amount of light that falls on a surface. This is measured in lumens per square
metre (lm/m2) and is commonly referred to as the lux level (lx).
IPD – Illumination Power Density is the term used in the NCC to express the amount of power used
to illuminate a particular space. IPD calculations are based on luminaire system wattage. Expressed
as W/m2
Lamp – commonly referred to as a light globe in technical lighting nomenclature a lamp is a light
source. A table lamp or standard lamp are not technically lamps, but are referred to as luminaires.
LED – an electronic lamp which produces light through the interaction of electrons passing through
layers of a semi-conductor.
Linear fitting – a long thin luminaire, usually housing a fluorescent tube or linear array of LEDs.
Luminaire – commonly referred to as a light fitting or fixture, a luminaire is a system which
includes a lamp, a lamp holder, and/or a reflector and/or a diffuser and/or control gear.
LPD- Lighting Power Density or LPD is the more commonly used term for the amount of power
used to light a particular space. Technically LPD is based on lamp wattage, but it is more
commonly used interchangeably with the term IPD where luminaire system wattage is used.
Expressed as W/m2. Green Star uses LPD and bases its calculations on luminaire system wattage.
Green Star LPD is expressed as W/m2/100 lux.
AIRAH and IBPSA’s Australasian Building Simulation 2017 Conference, Melbourne, November 15-16.
14
LUX (lx) - the unit of measurement used for illuminance - the number of lumens on a surface per
m2.
MEPS – Minimum Energy Performance Standards. These govern the efficiency of electrical
products available in Australia including lamps equipment and white goods.
Halogen lamp - an incandescent lamp with a halogen gas to improve its efficiency. These lamps
produce 70% heat and 30% light, and so are an inefficient light source compared to fluorescent,
HID or LED.
HID – High Intensity Discharge - a family of lamps which includes metal halide, sodium and
mercury vapour.
High bay – a luminaire used to light from heights typically using CFL or HID lamps combined with
a bell shaped reflector. LED versions are also available.
Incandescent lamps - a family of lamps which uss a filament that glows, or incandesces to produce
light. A filament lamp is easy to control because it will switch on and off instantly, and can dim.
These lamps produce 90% heat and 10% light, and so are a very inefficient light source compared to
fluorescent, HID or LED.
Maintained average –the average illuminance measured in a space at the end of the lighting systems
design life.
Maintenance factor – a percentage expressed as a decimal applied to the lumen output of a
luminaire to represent its lumen depreciation at the time it is expected to fail or be replaced. A
maintenance factor of 1 represents a new lamp or luminaire.
Metal halide – an electric lamp that produces light by creating an electric arc through a gaseous
mixture of vaporized metal compounds. The most commonly used type of HID lamp.
Perimeter lighting - lighting affixed to the exterior walls or soffits of a building used to light the
entrances, signage, exterior walls, paths or car parks around the building.
RAR (Room Adjustment Factor) – the ratio of a rooms volume to its perimeter and height,
expressed as a decimal. The RAR of a room impacts on the quality of the distribution of light in the
room, especially when the room is very narrow or the ceiling is very high.
RAR adjustment factor - the maximum required IPD of the space is divided by the adjustment
factor to increase the allowed maximum IPD of the space. To qualify for use of the adjustment
factor a room must have an RAR below 1.5.
Recessed luminaire – a luminaire inserted into a ceiling so that the front face sits flush with the
ceiling and the body of the luminiare is recessed into the ceiling cavity.
Recessed troffer– a square or rectanglar recessed box shaped luminaire typically using a linear
fluorescent tube or a linear array of LEDs.
SLL – Society for Light and Lighting – part of CIBSE
AIRAH and IBPSA’s Australasian Building Simulation 2017 Conference, Melbourne, November 15-16.
15
Recessed down light – a square or circular recessed luminaire typically using a halogen lamp, a
CFL or a HID.
T5 fluorescent tube – a fluorescent tube with a diameter of 5/8ths of an inch or 26mm. T5 tubes are
the latest development in fluorescent technology and only run on electronic control gear. The T5
tube was developed by reducing the diameter of the T8 tube, thus achieving a lower powered
alternative. For instance a 1200mm 36W T8 tube was reduced to a 1200mm 28W T5 tube, with a
corresponding drop in light output.
T8 fluorescent tube – a fluorescent tube with a diameter of 8/8ths of an inch or 16mm. A T8 tube
may run on magnetic or electronic control gear. The T8 tube was developed by reducing the
diameter of the original T12 tube, thus achieving a lower powered alternative. For instance a
1200mm 40W T12 tube was reduced to a 1200mm 36W T8 tube with a corresponding drop in light
output. However the development of tri-phophor technology which occurred several years later
improved the light output significantly.
Track lighting – a lighting system comprised of a track or a bar containing a power feed suspended
from or affixed to a ceiling. Individual light fittings are easily clipped in or out of the track to
provide a flexible system for lighting displays or merchandise which may change position regularly.
Surface reflectance – the proportion of light reflected from the surfaces in the room including walls,
ceiling and floor, and furnishings. This is influenced by the colour and texture of the surfaces. For
instance a tile floor is more reflective than carpet, and a white painted plaster wall is more reflective
than a wood panelled wall.
Troffer– a square or rectanglar box shaped luminaire typically using a linear fluorescent tube or a
linear array of LEDs. May be mounted directly on a ceiling or recessed into the ceiling cavity.
Working plane – the surface at which a task is performed. If the task is writing at a desk the
working plane is the desktop. If the task is walking down a corridor the working plane is the floor.
AIRAH and IBPSA’s Australasian Building Simulation 2017 Conference, Melbourne, November 15-16.
16
REFERENCES
1. Section J6 NCC 2016, Deemed to Satifsy clauses
2. AS/NZS1680.0 Australian/New Zealand Standard, Interior and Workplace Lighting, Safe
movement
3. AS/NZS1680.2.1 Australian/New Zealand Standard, Interior and Workplace Lighting, Specific
applications – Circulation spaces and other general areas
4. AS/NZS1680.2.2 Australian/New Zealand Standard, Interior and Workplace Lighting, Specific
applications – Office and screen based tasks
5. AS/NZS1680.2.3 Australian/New Zealand Standard, Interior and Workplace Lighting, Specific
applications – Educational and training facilities
6. AS/NZS1680.2.4 Australian/New Zealand Standard, Interior and Workplace Lighting, Specific
applications – Industrial tasks and processes
7. AS/NZS1680.2.5 Australian/New Zealand Standard, Interior and Workplace Lighting, Specific
applications – Hospital and medical tasks
8. AS/NZS1680.3 Australian/New Zealand Standard, Interior and Workplace Lighting,
Measurement, calculation and presentation of photometric data
9. AS/NZS4282 CIBSE Lighting Handbook Section 12.3 Retail Lighting recommendations
10. Artificial light at night as a new threat to pollination, Nature 10 August 2017, Page 206, Eva
Knopp, Leana Zoller, Remo Ryser, Christopher Gerpe, Moran Horler, Colin Fontaine,
University of Bern, Institute of Ecology and Evolution.