micom p642, p643 & p645 - transformer protection relay

822
MiCOM P642, P643 & P645 Transformer Protection Relay P64x/EN M/A52 Software Version 04 Hardware Suffix J (P642) & K (P643/645) Technical Manual

Upload: leanh

Post on 02-Jan-2017

412 views

Category:

Documents


21 download

TRANSCRIPT

  • MiCOM P642, P643 & P645

    Transformer Protection Relay

    P64x/EN M/A52

    Software Version 04 Hardware Suffix J (P642) & K (P643/645)

    Technical Manual

  • Note: The technical manual for this device gives instructions for its installation, commissioning, and operation. However, the manual cannot cover all conceivable circumstances or include detailed information on all topics. In the event of questions or specific problems, do not take any action without proper authorization. Contact the appropriate Schneider Electric technical sales office and request the necessary information.

    Any agreements, commitments, and legal relationships and any obligations on the part of Schneider Electric including settlements of warranties, result solely from the applicable purchase contract, which is not affected by the contents of the technical manual.

    This device MUST NOT be modified. If any modification is made without the express permission of Schneider Electric, it will invalidate the warranty, and may render the product unsafe.

    The Schneider Electric logo and any alternative version thereof are trademarks and service marks of Schneider Electric.

    All trade names or trademarks mentioned herein whether registered or not, are the property of their owners.

    This manual is provided for informational use only and is subject to change without notice.

    2010-2011, Schneider Electric. All rights reserved.

  • Contents P64x/EN M/A52

    MiCOM P642, P643 & P645

    CONTENTS

    Safety Section Pxxx/EN SS/G12 SS

    Chapter 1 Introduction P64x/EN IT/A52 IT

    Chapter 2 Technical Data P64x/EN TD/A52 TD

    Chapter 3 Getting Started P64x/EN GS/A52 GS

    Chapter 4 Settings P64x/EN ST/A52 ST

    Chapter 5 Operation P64x/EN OP/A52 OP

    Chapter 6 Application Notes P64x/EN AP/A52 AP

    Chapter 7 Programmable Logic P64x/EN PL/A52 PL

    Chapter 8 Measurements and Recording P64x/EN MR/A52 MR

    Chapter 9 Firmware Design P64x/EN FD/A52 FD

    Chapter 10 Commissioning P64x/EN CM/A52 CM

    Chapter 11 Maintenance P64x/EN MT/A52 MT

    Chapter 12 Troubleshooting P64x/EN TS/A52 TS

    Chapter 13 SCADA Communications P64x/EN SC/A52 SC

    Chapter 14 Symbols and Glossary Pxxx/EN SG/A02 SG

    Chapter 15 Installation P64x/EN IN/A52 IN

    Chapter 16 Firmware and Manual Version History P64x/EN VH/A52 VH

  • P64x/EN M/A52 Contents

    MiCOM P642, P643 & P645

    BLANK PAGE

  • Safety Section Pxxx/EN SS/G12

    MiCOM Pxxx

    SS

    SAFETY SECTION

  • Pxxx/EN SS/G12 Safety Section

    MiCOM Pxxx

    SS

    BLANK PAGE

  • Safety Section Pxxx/EN SS/G12

    MiCOM Pxxx

    Page (SS) - 1

    SS

    CONTENTS Page (SS) - 1 INTRODUCTION 2 2 HEALTH AND SAFETY 3 3 SYMBOLS AND LABELS ON THE EQUIPMENT 4 3.1 Symbols 4 3.2 Labels 4

    4 INSTALLING, COMMISSIONING AND SERVICING 5 5 DE-COMMISSIONING AND DISPOSAL 9 6 TECHNICAL SPECIFICATIONS FOR SAFETY 10 6.1 Protective Fuse Rating 10 6.2 Protective Class 10 6.3 Installation Category 10 6.4 Environment 10

  • Pxxx/EN SS/G12 Safety Section

    Page (SS) - 2

    MiCOM Pxxx

    1 INTRODUCTION

    This guide and the relevant equipment documentation provide full information on safe handling, commissioning and testing of this equipment. This Safety Section also includes reference to typical equipment label markings.

    Documentation for equipment ordered from Schneider Electric is dispatched separately from manufactured goods and may not be received at the same time. Therefore this guide is provided to ensure that printed information which may be present on the equipment is fully understood by the recipient.

    The technical data in this Safety Section is typical only, see the technical data section of the relevant product publication(s) for data specific to a particular equipment.

    SS

    WARNING Before carrying out any work on the equipment the user should be familiar with the contents of this Safety Section and the ratings on the equipments rating label.

    Reference should be made to the external connection diagram before the equipment is installed, commissioned or serviced.

    Language-specific, self-adhesive User Interface labels are provided in a bag for some equipment.

  • Safety Section Pxxx/EN SS/G12

    MiCOM Pxxx

    Page (SS) - 3

    SS

    2 HEALTH AND SAFETY

    The information in the Safety Section of the equipment documentation is intended to ensure that equipment is properly installed and handled in order to maintain it in a safe condition.

    It is assumed that everyone who will be associated with the equipment will be familiar with the contents of that Safety Section, or this Safety Guide.

    When electrical equipment is in operation, dangerous voltages will be present in certain parts of the equipment. Failure to observe warning notices, incorrect use, or improper use may endanger personnel and equipment and also cause personal injury or physical damage.

    Before working in the terminal strip area, the equipment must be isolated.

    Proper and safe operation of the equipment depends on appropriate shipping and handling, proper storage, installation and commissioning, and on careful operation, maintenance and servicing. For this reason only qualified personnel may work on or operate the equipment.

    Qualified personnel are individuals who:

    Are familiar with the installation, commissioning, and operation of the equipment and of the system to which it is being connected;

    Are able to safely perform switching operations in accordance with accepted safety engineering practices and are authorized to energize and de-energize equipment and to isolate, ground, and label it;

    Are trained in the care and use of safety apparatus in accordance with safety engineering practices;

    Are trained in emergency procedures (first aid).

    The equipment documentation gives instructions for its installation, commissioning, and operation. However, the manuals cannot cover all conceivable circumstances or include detailed information on all topics. In the event of questions or specific problems, do not take any action without proper authorization. Contact the appropriate Schneider Electric technical sales office and request the necessary information.

  • Pxxx/EN SS/G12 Safety Section

    Page (SS) - 4

    MiCOM Pxxx

    3 SYMBOLS AND LABELS ON THE EQUIPMENT

    For safety reasons the following symbols which may be used on the equipment or referred to in the equipment documentation, should be understood before it is installed or commissioned.

    3.1 Symbols SS

    Caution: refer to equipment documentation

    Caution: risk of electric shock

    Protective Conductor (*Earth) terminal

    Functional/Protective Conductor (*Earth) terminal

    Note This symbol may also be used for a Protective Conductor (Earth) Terminal if that terminal is part of a terminal block or sub-assembly e.g. power supply.

    *CAUTION The term Earth used throughout this technical manual is the direct equivalent of the North American term Ground.

    3.2 Labels See Safety Guide (SFTY/4L M) for typical equipment labeling information.

  • Safety Section Pxxx/EN SS/G12

    MiCOM Pxxx

    Page (SS) - 5

    4 INSTALLING, COMMISSIONING AND SERVICING

    Manual Handling Plan carefully, identify any possible hazards and determine whether the load needs to be moved at all. Look at other ways of moving the load to avoid manual handling. Use the correct lifting techniques and Personal Protective Equipment to reduce the risk of injury. Many injuries are caused by: Lifting heavy objects

    Lifting things incorrectly

    Pushing or pulling heavy objects

    Using the same muscles repetitively.

    Follow the Health and Safety at Work, etc Act 1974, and the Management of Health and Safety at Work Regulations 1999.

    Equipment Connections Personnel undertaking installation, commissioning or servicing work for this equipment should be aware of the correct working procedures to ensure safety. The equipment documentation should be consulted before installing, commissioning, or servicing the equipment. Terminals exposed during installation, commissioning and maintenance may present a hazardous voltage unless the equipment is electrically isolated. The clamping screws of all terminal block connectors, for field wiring, using M4 screws shall be tightened to a nominal torque of 1.3 Nm. Equipment intended for rack or panel mounting is for use on a flat surface of a Type 1 enclosure, as defined by Underwriters Laboratories (UL). Any disassembly of the equipment may expose parts at hazardous voltage, also electronic parts may be damaged if suitable electrostatic voltage discharge (ESD) precautions are not taken. If there is unlocked access to the rear of the equipment, care should be taken by all personnel to avoid electric shock or energy hazards. Voltage and current connections shall be made using insulated crimp terminations to ensure that terminal block insulation requirements are maintained for safety. Watchdog (self-monitoring) contacts are provided in numerical relays to indicate the health of the device. Schneider Electric strongly recommends that these contacts are hardwired into the substation's automation system, for alarm purposes. To ensure that wires are correctly terminated the correct crimp terminal and tool for the wire size should be used. The equipment must be connected in accordance with the appropriate connection diagram.

    SS

  • Pxxx/EN SS/G12 Safety Section

    Page (SS) - 6

    MiCOM Pxxx

    Protection Class I Equipment Before energizing the equipment it must be earthed using the protective conductor

    terminal, if provided, or the appropriate termination of the supply plug in the case of plug connected equipment.

    The protective conductor (earth) connection must not be removed since the protection against electric shock provided by the equipment would be lost.

    When the protective (earth) conductor terminal (PCT) is also used to terminate cable screens, etc., it is essential that the integrity of the protective (earth) conductor is checked after the addition or removal of such functional earth connections. For M4 stud PCTs the integrity of the protective (earth) connections should be ensured by use of a locknut or similar.

    The recommended minimum protective conductor (earth) wire size is 2.5 mm (3.3 mm for North America) unless otherwise stated in the technical data section of the equipment documentation, or otherwise required by local or country wiring regulations. The protective conductor (earth) connection must be low-inductance and as short as possible. All connections to the equipment must have a defined potential. Connections that are pre-wired, but not used, should preferably be grounded when binary inputs and output relays are isolated. When binary inputs and output relays are connected to common potential, the pre-wired but unused connections should be connected to the common potential of the grouped connections.

    Pre-Energization Checklist Before energizing the equipment, the following should be checked: Voltage rating/polarity (rating label/equipment documentation);

    CT circuit rating (rating label) and integrity of connections;

    Protective fuse rating;

    Integrity of the protective conductor (earth) connection (where applicable);

    Voltage and current rating of external wiring, applicable to the application.

    Accidental Touching of Exposed Terminals If working in an area of restricted space, such as a cubicle, where there is a risk of electric shock due to accidental touching of terminals which do not comply with IP20 rating, then a suitable protective barrier should be provided.

    Equipment Use If the equipment is used in a manner not specified by the manufacturer, the protection provided by the equipment may be impaired.

    Removal of the Equipment Front Panel/Cover Removal of the equipment front panel/cover may expose hazardous live parts, which must not be touched until the electrical power is removed.

    UL and CSA/CUL Listed or Recognized Equipment To maintain UL and CSA/CUL Listing/Recognized status for North America the equipment should be installed using UL or CSA Listed or Recognized parts for the following items: connection cables, protective fuses/fuseholders or circuit breakers, insulation crimp terminals and replacement internal battery, as specified in the equipment documentation. For external protective fuses a UL or CSA Listed fuse shall be used. The Listed type shall be a Class J time delay fuse, with a maximum current rating of 15 A and a minimum d.c. rating of 250 Vd.c., for example type AJT15. Where UL or CSA Listing of the equipment is not required, a High Rupture Capacity (HRC) fuse type with a maximum current rating of 16 Amps and a minimum d.c. rating of 250 Vd.c. may be used, for example Red Spot type NIT or TIA.

    SS

  • Safety Section Pxxx/EN SS/G12

    MiCOM Pxxx

    Page (SS) - 7

    Equipment Operating Conditions The equipment should be operated within the specified electrical and environmental limits.

    Current Transformer (CT) Circuits Do not open the secondary circuit of a live CT since the high voltage produced may be lethal to personnel and could damage insulation. Generally, for safety, the secondary of the line CT must be shorted before opening any connections to it. For most equipment with ring-terminal connections, the threaded terminal block for current transformer termination has automatic CT shorting on removal of the module. Therefore external shorting of the CTs may not be required, the equipment documentation should be checked to see if this applies. For equipment with pin-terminal connections, the threaded terminal block for current transformer termination does NOT have automatic CT shorting on removal of the module.

    External Resistors, including Voltage Dependent Resistors (VDRs) Where external resistors, including Voltage Dependent Resistors (VDRs), are fitted to the equipment, these may present a risk of electric shock or burns, if touched.

    Battery Replacement Where internal batteries are fitted they should be replaced with the recommended type and be installed with the correct polarity to avoid possible damage to the equipment, buildings and persons.

    Insulation and Dielectric Strength Testing Insulation testing may leave capacitors charged up to a hazardous voltage. At the end of each part of the test, the voltage should be gradually reduced to zero, to discharge capacitors, before the test leads are disconnected.

    Insertion of Modules and PCB Cards Modules and PCB cards must not be inserted into or withdrawn from the equipment whilst it is energized, since this may result in damage.

    Insertion and Withdrawal of Extender Cards Extender cards are available for some equipment. If an extender card is used, this should not be inserted or withdrawn from the equipment whilst it is energized. This is to avoid possible shock or damage hazards. Hazardous live voltages may be accessible on the extender card.

    External Test Blocks and Test Plugs Great care should be taken when using external test blocks and test plugs such as the MMLG, MMLB and MiCOM P990 types, hazardous voltages may be accessible when using these. *CT shorting links must be in place before the insertion or removal of MMLB test plugs, to avoid potentially lethal voltages.

    *Note When a MiCOM P992 Test Plug is inserted into the MiCOM P991 Test Block, the secondaries of the line CTs are automatically shorted, making them safe.

    Fiber Optic Communication Where fiber optic communication devices are fitted, these should not be viewed directly. Optical power meters should be used to determine the operation or signal level of the device.

    SS

  • Pxxx/EN SS/G12 Safety Section

    Page (SS) - 8

    MiCOM Pxxx

    Cleaning The equipment may be cleaned using a lint free cloth dampened with clean water, when no connections are energized. Contact fingers of test plugs are normally protected by petroleum jelly, which should not be removed.

    SS

  • Safety Section Pxxx/EN SS/G12

    MiCOM Pxxx

    Page (SS) - 9

    5 DE-COMMISSIONING AND DISPOSAL

    De-commissioning The supply input (auxiliary) for the equipment may include capacitors across the supply or to earth. To avoid electric shock or energy hazards, after completely isolating the supplies to the equipment (both poles of any dc supply), the capacitors should be safely discharged via the external terminals prior to de-commissioning.

    Disposal It is recommended that incineration and disposal to water courses is avoided. The equipment should be disposed of in a safe manner. Any equipment containing batteries should have them removed before disposal, taking precautions to avoid short circuits. Particular regulations within the country of operation, may apply to the disposal of the equipment.

    SS

  • Pxxx/EN SS/G12 Safety Section

    Page (SS) - 10

    MiCOM Pxxx

    6 TECHNICAL SPECIFICATIONS FOR SAFETY

    Unless otherwise stated in the equipment technical manual, the following data is applicable.

    6.1 Protective Fuse Rating The recommended maximum rating of the external protective fuse for equipments is 16A, High Rupture Capacity (HRC) Red Spot type NIT, or TIA, or equivalent. Unless otherwise stated in equipment technical manual, the following data is applicable. The protective fuse should be located as close to the unit as possible.

    SS

    DANGER CTs must NOT be fused since open circuiting them may produce lethal hazardous voltages.

    6.2 Protective Class IEC 60255-27: 2005 Class I (unless otherwise specified in the equipment

    documentation).

    EN 60255-27: 2005 This equipment requires a protective conductor (earth) connection to ensure user safety.

    6.3 Installation Category IEC 60255-27: 2005 Installation Category III (Overvoltage Category III)

    EN 60255-27: 2005 Distribution level, fixed installation.

    Equipment in this category is qualification tested at 5 kV peak, 1.2/50 s, 500 , 0.5 J, between all supply circuits and earth and also between independent circuits.

    6.4 Environment The equipment is intended for indoor installation and use only. If it is required for use in an outdoor environment then it must be mounted in a specific cabinet of housing which will enable it to meet the requirements of IEC 60529 with the classification of degree of protection IP54 (dust and splashing water protected).

    Pollution Degree Pollution Degree 2 Compliance is demonstrated by reference to safety standards.

    Altitude Operation up to 2000m

    IEC 60255-27:2005

    EN 60255-27: 2005

  • 1. Introduction P64x/EN IT/A52

    MiCOM P642, P643 and P645

    IT

    1. INTRODUCTION

    Date: May 2011 Hardware Suffix: J (P642) K (P643/P645) Software Version: 04 Connection Diagrams:

    10P642xx (xx = 1 to 10) 10P643xx (xx = 1 to 6) 10P645xx (xx = 1 to 9)

  • P64x/EN IT/A52 1. Introduction

    MiCOM P642, P643 and P645

    IT

    BLANK PAGE

  • 1. Introduction P64x/EN IT/A52

    MiCOM P642, P643 and P645

    Page (IT) 1-1

    IT

    CONTENTS Page (IT) 1- 1 MICOM DOCUMENTATION STRUCTURE 1-3 2 INTRODUCTION TO MICOM 1-5 3 PRODUCT SCOPE 1-6 3.1 Functional Overview 1-6 3.2 Application Overview 1-9 3.3 Ordering Options 1-9 3.3.1 Information Required with Order - Software Version 04 1-9

    FIGURES Page (IT) 1- Figure 1 - Functional diagram 1-9

    TABLES Page (IT) 1- Table 1 - Protection functions overview 1-8

  • P64x/EN IT/A52 1. Introduction

    Page (IT) 1-2

    MiCOM P642, P643 and P645

    IT

    BLANK PAGE

  • 1. Introduction P64x/EN IT/A52

    MiCOM P642, P643 and P645

    Page (IT) 1-3

    IT

    1 MICOM DOCUMENTATION STRUCTURE

    The manual provides a functional and technical description of the MiCOM protection relay and a comprehensive set of instructions for the relays use and application.

    The chapter contents are summarized as follows.

    P64x/EN IT Introduction

    A guide to the MiCOM range of relays and the documentation structure. General safety aspects of handling Electronic Equipment is discussed with particular reference to relay safety symbols. Also a general functional overview of the relay and brief application summary is given.

    P64x/EN TD Technical Data

    Technical data including setting ranges, accuracy limits, recommended operating conditions, ratings and performance data. Compliance with norms and international standards is quoted where appropriate.

    P64x/EN GS Getting Started

    A guide to the different user interfaces of the protection relay describing how to start using it. This chapter provides detailed information regarding the communication interfaces of the relay, including a detailed description of how to access the settings database stored in the relay.

    P64x/EN ST Settings

    A list of all relay settings, including ranges, step sizes and defaults with a brief explanation of each setting.

    P64x/EN OP Operation

    A comprehensive and detailed functional description of all protection and non-protection functions.

    P64x/EN AP Application Notes

    This chapter includes a description of common power system applications of the relay, calculation of suitable settings, some typical worked examples, and how to apply the settings to the relay.

    P64x/EN PL Programmable Logic

    An overview of the programmable scheme logic and a description of each logical node. This chapter includes the factory default (PSL) and an explanation of typical applications.

    P64x/EN MR Measurements and Recording

    A detailed description of the relays recording and measurements functions including the configuration of the event and disturbance recorder and measurement functions.

    P64x/EN FD Firmware Design

    An overview of the operation of the relays hardware and software. This chapter includes information on the self-checking features and diagnostics of the relay.

    P64x/EN CM Commissioning

    Instructions on how to commission the relay, comprising checks on the calibration and functionality of the relay.

    P64x/EN MT Maintenance

    A general maintenance policy for the relay is outlined.

  • P64x/EN IT/A52 1. Introduction

    Page (IT) 1-4

    MiCOM P642, P643 and P645

    IT

    P64x/EN TS Troubleshooting

    Advice on how to recognize failure modes and the recommended course of action. Includes guidance on whom in Schneider Electric to contact for advice.

    P64x/EN SC SCADA Communications

    This chapter provides an overview regarding the SCADA communication interfaces of the relay. Detailed protocol mappings, semantics, profiles and interoperability tables are not provided in this manual. Separate documents are available for each protocol, downloadable from our website.

    P64x/EN SG Symbols and Glossary

    List of common technical abbreviations used in the product documentation.

    P64x/EN IN Installation

    Recommendations on unpacking, handling, inspection and storage of the relay. A guide to the mechanical and electrical installation of the relay is provided, incorporating earthing recommendations. All external wiring connections to the relay are shown.

    P64x/EN VH Firmware and Service Manual Version History

    History of all hardware and software releases for the product.

  • 1. Introduction P64x/EN IT/A52

    MiCOM P642, P643 and P645

    Page (IT) 1-5

    IT

    2 INTRODUCTION TO MiCOM

    MiCOM is a comprehensive solution capable of meeting all electricity supply requirements. It comprises a range of components, systems and services from Schneider Electric.

    Central to the MiCOM concept is flexibility.

    MiCOM allows you to define an application solution and integrate it with your power supply control system through extensive communication capabilities.

    The components within MiCOM are:

    P range protection relays

    C range control products

    M range measurement products for accurate metering and monitoring

    S range versatile PC support and substation control packages

    MiCOM products include extensive facilities for recording information on the state and behavior of the power system using disturbance and fault records. At regular intervals they can provide measurements of the system to a control center, allowing remote monitoring and control.

    For up-to-date information on any MiCOM product, visit our website:

    www.schneider-electric.com

  • P64x/EN IT/A52 1. Introduction

    Page (IT) 1-6

    MiCOM P642, P643 and P645

    IT

    3 PRODUCT SCOPE

    The MiCOM P642, P643 and P645 preserves transformer service life by offering fast protection for transformer faults. Hosted on an advanced IED platform, the P64x incorporates differential, REF, thermal, and overfluxing protection, plus backup protection for uncleared external faults. Model variants cover two and three winding transformers (including autotransformers), with up to five sets of 3-phase CT inputs. Large CT counts are common in ring bus or mesh corner applications, where the P64x summates currents to create each total winding current, easing application of backup protection. Backup overcurrent can be directionalized, where the user includes the optional 3-phase VT input in their chosen model.

    3.1 Functional Overview The P642/P643/P645 transformer protection relays have a wide variety of protection functions which are summarized in the following table.

    ANSII number Description P64x

    87 Phase-segregated transformer biased differential protection is provided for high-speed discriminative protection for all fault types.

    P643/ P645

    64

    Biased low-impedance restricted earth fault element can be used to provide high-speed earth fault protection. High impedance restricted earth fault element is also available. The 64 function is applicable to conventional transformers and autotransformers.

    P642/ P643/ P645

    50/51/67

    Four overcurrent protection stages are provided which can be selected as non-directional, directional, forward or directional reverse. Stages 1 and 2 can be set as Inverse Definite Minimum Time (IDMT) or Definite Time (DT); stages 3 and 4 can be set as DT only.

    P642/ P643/ P645

    46OC

    Four stages of negative phase sequence overcurrent protection are provided for remote back-up protection for both phase-to-earth and phase-to-phase faults. Each stage can be selected as non-directional, directional forward or directional reverse. Stages 1 and 2 can be set as Inverse Definite Minimum Time (IDMT) or Definite Time (DT); stages 3 and 4 can be set as DT only.

    P642/ P643/ P645

    49

    Thermal overload protection based on IEEE Std C57.91-1995. Thermal trip can be based on either hot spot or top oil temperature, each with three time-delayed stages available. Four cooling modes are available to consider the transformer cooling classes.

    P642/ P643/ P645

    LoL Two one-stage definite time delay alarms based on aging acceleration factor (FAA) or loss of life (LoL) are available.

    Thru

    Through faults are a major cause of transformer damage and failure. Both the insulation and the mechanical effects of fault currents are considered. A one-stage alarm is available for through-fault monitoring.

    50N/51N/67N

    Up to three derived or measured standby earth fault elements are available. Four stages are provided which can be selected as non-directional, directional, forward or directional reverse. Stages 1 and 2 can be set as Inverse Definite Minimum Time (IDMT) or Definite Time (DT); stages 3 and 4 can be set as DT only

    P642/ P643/ P645

    59N

    The 59N element is a two-stage design, each stage having separate voltage and time delay settings. Stage 1 can be set to operate on either an IDMT or DT characteristic, while stage 2 can be set to DT only.

    P642/ P643/ P645

    24 Two five-stage overfluxing (V/Hz) elements protect the transformer, against overexcitation. The first stage is a Definite Time alarm, the second stage can be used to provide an inverse or Definite Time trip characteristic and stages 3, 4 and 5 are Definite Time.

    P642/ P643/ P645

  • 1. Introduction P64x/EN IT/A52

    MiCOM P642, P643 and P645

    Page (IT) 1-7

    IT

    ANSII number Description P64x

    27

    A two-stage undervoltage protection element, configurable as either phase-to-phase or phase-to-neutral measuring is available, Stage 1 can be set as either IDMT or DT and stage 2 is DT only.

    P642/ P643/ P645

    59

    A two-stage overvoltage protection element, configurable as either phase-to-phase or phase-to-neutral measuring is available. Stage 1 can be set as either IDMT or DT and stage 2 is DT only.

    P642/ P643/ P645

    47 A one-stage negative phase sequence overvoltage protection element is available. It is DT only. P642/ P643/ P645

    81U/O Four-stage Definite Time underfrequency and two-stage Definite Time overfrequency protection is provided for load shedding and back-up protection.

    P642/ P643/ P645

    RTD Ten RTDs (PT100) are available to monitor the ambient and top oil temperature accurately. Each RTD has an instantaneous alarm and Definite Time trip stage.

    Option P642/ P643/ P645

    50BF A two-stage circuit breaker failure function is provided with a 3-pole initiation input from external protection. P642/ P643/ P645

    37P Phase undercurrent elements are available for use with, for example, the circuit breaker fail function. P642/ P643/ P645

    VTS Voltage transformer supervision is provided (1, 2 & 3-phase fuse failure detection) to prevent mal-operation of voltage-dependent protection elements when a VT input signal is lost.

    P642/ P643/ P645

    CTS Current transformer supervision prevents mal-operation of current-dependent protection elements when a CT input signal is lost.

    P642/ P643/ P645

    CLIO

    Four analog or current loop inputs are provided for transducers such as vibration sensors and tachometers. Each input has a Definite Time trip and alarm stage, each input can be set to Over or Under operation, and each input can be independently selected as 0 to 1, 0 to 10, 0 to 20 or 4 to 20 mA. Four analogue (or current loop) outputs are provided for the analogue measurements in the relay. Each output can be independently selected as 0 to 1, 0 to 10, 0 to 20 or 4 to 20 mA.

    Option P642/ P643/ P645

    CT saturation and no gap detection algorithms have been included to enhance to low set differential element operating time

    External fault detection algorithm has bee included to maintain stability during external faults.

    Zero crossing detection algorithm has been included to prevent circuit breaker failure mal-operations due to subsidence current.

    Phase rotation. The rotation of the phases ABC or ACB for all 3-phase current and voltage channels can be selected. Also, for pumped storage applications, the swapping of two phases can be emulated independently for the 3-phase voltage and 3-phase current channels.

    P642/ P643/ P645

    32 programmable user alarms P642/ P643/ P645

    10 programmable function keys P642/ P643/ P645

    18 programmable LEDs (tri-color P645, red P642/3/4) P642/ P643/ P645

    8 to 24 digital inputs (order option) depending on the model P642/ P643/ P645

    Front communication port (EIA(RS)232) P642/ P643/ P645

    Rear communication port (K-Bus/EIA(RS)485). The following communications protocols are supported: Courier, MODBUS, P645

    P642/ P643/

  • P64x/EN IT/A52 1. Introduction

    Page (IT) 1-8

    MiCOM P642, P643 and P645

    IT

    ANSII number Description P64x IEC870-5-103 (VDEW), DNP3.0.

    ptic). The following

    BUS, Option P642/ Rear communication port (Fiber Ocommunications protocols are supported: Courier, MODIEC870-5-103 (VDEW) and DNP3.0. P643/ P645

    Second rear communication port, EIA(RS)232/EIA(RS)485. Option P642/

    Courier, and K-Bus protocols. P643/ P644/ P645

    Rear IEC 61850-8-1 Ethernet communication port. P642/ OptionP643/ P645

    Time synchronization port (IRIG-B) Option P642/P643/ P645

    Table 1 - Protection functions overview

    64x supports these relay management functions:

    gic

    s

    pture)

    e menu texts

    uous self-monitoring of the relay

    zation - time synchronization possible from IRIG-B

    In addition to the functions in Table 1, the P

    Measurement of all instantaneous & integrated values

    Trip circuit and coil supervision

    Four alternative setting groups

    Programmable function keys

    Control inputs

    Programmable scheme lo

    Programmable allocation of digital inputs and output

    Sequence of event recording

    Comprehensive disturbance recording (waveform ca

    Fault recording

    Fully customizabl

    Multi-level password protection

    Power-up diagnostics and contin

    Commissioning test facilities

    Real time clock/time synchroniinput, opto input or communications

  • 1. Introduction P64x/EN IT/A52

    MiCOM P642, P643 and P645

    Page (IT) 1-9

    3.2 Application Overview

    FO/Ethernet

    47V2>

    51VDT VCO

    51VIDMT VCO

    ree-phase VT input.ined from any analog signal, but the voltage signals have priority over the current signals.

    27, 47, 59, 59N

    P4249ENgire the thn is obta

    1- The three-phase VT input is optional.2- The 27, 59, 59N and VTS functions requ3- The frequency required by the 81 functio

    IT

    Figure 1 - Functional diagram

    3.3 Ordering Options

    3.3.1 Information Required with Order - Software Version 04

  • P64x/EN IT/A52 1. Introduction

    Page (IT) 1-10

    MiCOM P642, P643 and P645

    IT

    1 2 3 4 5 6 7 8 9 10 11 12 13 14 15

    MiCOM P642 transformer protection P642 0

    Auxiliary voltage rating 24 48 V dc only

    48 110 V dc (40 100 V ac)

    110 250 V dc (100 240 V ac)

    1

    2

    3

    In/Vn rating HV-LV In=1A/5A, Vn=(100/120 V)(8CT/1VT) 1

    Hardware options Nothing

    IRIG-B only (modulated)

    Fiber optic converter only

    IRIG-B (modulated)& fiber optic converter

    Ethernet with 100Mbit/s fibre-optic port

    Second Rear Comms Port (Courier EIA232/EIA485/k-bus)

    Second Rear Comms Port + IRIG-B (Courier EIA232/EIA485/k-bus)

    Ethernet (100Mbit/s) + IRIG-B (modulated)

    Ethernet (100Mbit/s) + IRIG-B (un-modulated)

    IRIG-B (un-modulated)

    Redundant Ethernet Self-Healing Ring, 2 multi-mode fibre ports + Modulated IRIG-B

    Red. Ethernet Self-Healing Ring, 2 multi-mode fibre ports + Un-modulated IRIG-B

    Redundant Ethernet RSTP, 2 multi-mode fibre ports + Modulated IRIG-B

    Redundant Ethernet RSTP, 2 multi-mode fibre ports + Un-modulated IRIG-B

    Redundant Ethernet Dual-Homing Star, 2 multi-mode fibre ports + Modulated IRIG-B

    Red. Ethernet Dual-Homing Star, 2 multi-mode fibre ports + Un-modulated IRIG-B

    1

    2

    3

    4

    6

    7

    8

    A

    B

    C

    G

    H

    J

    K

    L

    M

    Product Specific Options Size 8 (40TE) case, 8 optos + 8 relays

    Size 8 (40TE) case, 8 optos + 8 relays + RTD

    Size 8 (40TE) case, 8 optos + 8 relays + CLIO

    Size 8 (40TE) case, 12 optos + 12 relays

    Size 8 (40TE) Case, 8 Optos + 12 Relays (including 4 High Break)

    A

    B

    C

    D

    E

    Protocol Options K-Bus/Courier

    Modbus

    IEC60870-5-103

    DNP3.0

    IEC61850-8-1 over Ethernet and Courier via rear K-Bus/RS485

    DNP3.0 over Ethernet and Courier via rear K-Bus/RS485

    1

    2

    3

    4

    6

    8

    Mounting Options Panel mounting

    Panel Mounting, with harsh environment coating

    M

    P

    Language Options English, French, German, Spanish

    English, French, German, Russian

    Chinese, English or French via HMI, with English or French only via Communications port

    0

    5

    C

    Software Version Options Unless specified the latest version will be delivered * *

    Settings File Options Default

    Customer settings

    0

    A

    Design Suffix Phase 2 CPU J

    Note design suffix J = Phase 2 CPU and front panel with 2 hotkeys and dual characteristic optos

  • 1. Introduction P64x/EN IT/A52

    MiCOM P642, P643 and P645

    Page (IT) 1-11

    IT

    1 2 3 4 5 6 7 8 9 10 11 12 13 14 15

    MiCOM P643 Transformer Protection P643 0

    Auxiliary voltage rating 24 48 V dc only

    48 110 V dc (40 100 V ac)

    110 250 V dc (100 240 V ac)

    1

    2

    3

    In/Vn rating HV-LV In=1A/5A, Vn=(100/120 V)(12CT/1VT) HV-LV In=1A/5A, Vn=(100/120 V)(12CT/4VT)

    1 2

    Hardware Options Nothing

    IRIG-B only (modulated)

    Fiber optic converter only

    IRIG-B (modulated)& fiber optic converter

    Ethernet with 100Mbit/s fiber-optic port

    Second Rear Comms Port (Courier EIA232/EIA485/k-bus)

    Second Rear Comms Port + IRIG-B (Courier EIA232/EIA485/k-bus)

    Ethernet (100Mbit/s) + IRIG-B (modulated)

    Ethernet (100Mbit/s) + IRIG-B (un-modulated)

    IRIG-B (un-modulated)

    Redundant Ethernet Self-Healing Ring, 2 multi-mode fibre ports + Modulated IRIG-B

    Red. Ethernet Self-Healing Ring, 2 multi-mode fibre ports + Un-modulated IRIG-B

    Redundant Ethernet RSTP, 2 multi-mode fibre ports + Modulated IRIG-B

    Redundant Ethernet RSTP, 2 multi-mode fibre ports + Un-modulated IRIG-B

    Redundant Ethernet Dual-Homing Star, 2 multi-mode fibre ports + Modulated IRIG-B

    Red. Ethernet Dual-Homing Star, 2 multi-mode fibre ports + Un-modulated IRIG-B

    1

    2

    3

    4

    6

    7

    8

    A

    B

    C

    G

    H

    J

    K

    L

    M

    Product Specific Options Size 12 (60TE) case, 16 optos + 16 relays

    Size 12 (60TE) case, 16 optos + 16 relays + RTD

    Size 12 (60TE) case, 16 optos + 16 relays + CLIO

    Size 12 (60TE) case, 24 optos + 16 relays

    Size 12 (60TE) case, 16 optos + 24 relays

    Size 12 (60TE) case, 16 optos + 20 relays (including 4 High Break)

    A

    B

    C

    D

    E

    F

    Protocol Options K-Bus/Courier

    Modbus

    IEC60870-5-103

    DNP3.0

    IEC61850-8-1 over Ethernet and Courier via rear K-Bus/RS485

    DNP3.0 over Ethernet and Courier via rear K-Bus/RS485

    1

    2

    3

    4

    6

    8

    Mounting Options Panel mounting Panel Mounting, with harsh environment coating

    M P

    Language Options English, French, German, Spanish

    English, French, German, Russian

    Chinese, English or French via HMI, with English or French only via Communications port

    0

    5

    C

    Software Version Options Unless specified the latest version will be delivered * *

    Settings File Options Default Customer settings

    0 A

    Hardware suffix Extended Phase 2 CPU K

    Note design suffix K = Extended phase 2 CPU (phase 2 CPU and front panel with 10 function keys and tri-color LEDs and dual characteristic optos)

  • P64x/EN IT/A52 1. Introduction

    Page (IT) 1-12

    MiCOM P642, P643 and P645

    IT

    1 2 3 4 5 6 7 8 9 10 11 12 13 14 15MiCOM P645 Transformer Protection P645 0

    Auxiliary voltage rating 24 48 V dc only

    48 110 V dc (40 100 V ac)

    110 250 V dc (100 240 V ac)

    1

    2

    3

    In/Vn rating HV-LV In=1A/5A, Vn=(100/120 V)(18CT/1VT) HV-LV In=1A/5A, Vn=(100/120 V)(18CT/4VT)

    1 2

    Hardware Options Nothing

    IRIG-B only (modulated)

    Fiber optic converter only

    IRIG-B (modulated)& fiber optic converter

    Ethernet with 100Mbit/s fiber-optic port

    Second Rear Comms Port (Courier EIA232/EIA485/k-bus)

    Second Rear Comms Port + IRIG-B (Courier EIA232/EIA485/k-bus)

    Ethernet (100Mbit/s) + IRIG-B (modulated)

    Ethernet (100Mbit/s) + IRIG-B (un-modulated)

    IRIG-B (un-modulated)

    Redundant Ethernet Self-Healing Ring, 2 multi-mode fibre ports + Modulated IRIG-B

    Red. Ethernet Self-Healing Ring, 2 multi-mode fibre ports + Un-modulated IRIG-B

    Redundant Ethernet RSTP, 2 multi-mode fibre ports + Modulated IRIG-B

    Redundant Ethernet RSTP, 2 multi-mode fibre ports + Un-modulated IRIG-B

    Redundant Ethernet Dual-Homing Star, 2 multi-mode fibre ports + Modulated IRIG-B

    Red. Ethernet Dual-Homing Star, 2 multi-mode fibre ports + Un-modulated IRIG-B

    1

    2

    3

    4

    6

    7

    8

    A

    B

    C

    G

    H

    J

    K

    L

    M

    Product Specific Options Size 12 (60TE) case, 16 optos + 16 relays

    Size 12 (60TE) case, 16 optos + 16 relays + RTD

    Size 12 (60TE) case, 16 optos + 16 relays + CLIO

    Size 12 (60TE) case, 24 optos + 16 relays

    Size 12 (60TE) case, 16 optos + 24 relays

    Size 16 (80TE) case, 24 optos + 24 relays

    Size 16 (80TE) case, 24 optos + 24 relays + RTD

    Size 16 (80TE) case, 24 optos + 24 relays + CLIO

    Size 16 (80TE) case, 24 optos + 24 relays + RTD + CLIO

    Size 12 (60TE) case, 16 optos + 20 relays (including 4 high break)

    Size 16 (80TE) case, 24 optos + 20 relays (including 4 high break)

    Size 16 (80TE) case, 24 optos + 20 relays (including 4 high break) + RTD

    Size 16 (80TE) case, 24 optos + 20 relays (including 4 high break) + CLIO (mA I/O)

    Size 16 (80TE) case, 24 optos + 20 relays (including 4 high break) + RTD + CLIO (mA I/O)

    Size 16 (80TE) case, 16 optos + 24 relays (including 8 high break)

    Size 16 (80TE) case, 16 optos + 24 relays (including 8 high break) + RTD

    Size 16 (80TE) case, 16 optos + 24 relays (including 8 high break) + CLIO (mA I/O)

    Size 16 (80TE) case, 16 optos + 24 relays (including 8 high break) + RTD + CLIO (mA I/O)

    A

    B

    C

    D

    E

    F

    G

    H

    J

    K

    L

    M

    N

    P

    Q

    R

    S

    T

    Protocol options K-Bus/Courier

    Modbus

    IEC60870-5-103

    DNP3.0

    IEC61850-8-1 over Ethernet and Courier via rear K-Bus/RS485

    DNP3.0 over Ethernet and Courier via rear K-Bus/RS485

    1

    2

    3

    4

    6

    8

    Mounting Options Panel mounting

    Rack mounting

    Panel mounting, with harsh environment coating

    Rack mounting, with harsh environment coating

    M

    N

    P

    Q

    Language Options Multilingual English, French, German, Spanish 0

  • 1. Introduction P64x/EN IT/A52

    MiCOM P642, P643 and P645

    Page (IT) 1-13

    IT

    English, French, German, Russian

    Chinese, English or French via HMI, with English or French only via Communications port

    5

    C

    Software Version Options Unless specified the latest version will be delivered * *

    Settings File Options Default 0

    Design Suffix Extended Phase 2 CPU K

    * Note design suffix e 2 CPU (phase 2 CPU and front pane with 0 f cti ke an tri lor LEDs and ual K = Extended phas l 1 un on ys d -co d

    characteristic optos) For rack mounting assembled single rack frames and blanking plates are available

  • P64x/EN IT/A52 1. Introduction

    Page (IT) 1-14

    MiCOM P642, P643 and P645

    IT

    BLANK PAGE

  • 2. Technical Data P64x/EN TD/A52

    MiCOM P642, P643 and P645

    TD

    2. TECHNICAL DATA

    Date: May 2011 Hardware Suffix: J (P642) K (P643/P645) Software Version: 04 Connection Diagrams:

    10P642xx (xx = 1 to 10) 10P643xx (xx = 1 to 6) 10P645xx (xx = 1 to 9)

  • P64x/EN TD/A52 2. Technical Data

    MiCOM P642, P643 and P645

    TD

    BLANK PAGE

  • 2. Technical Data P64x/EN TD/A52

    MiCOM P642, P643 and P645

    Page (TD) 2-1

    TD

    CONTENTS Page (TD) 2- MECHANICAL SPECIFICATIONS 2-5 TERMINALS 2-5 RATINGS 2-6 POWER SUPPLY 2-6 OUTPUT CONTACTS 2-7 ENVIRONMENTAL CONDITIONS 2-7 TYPE TESTS 2-8 ELECTROMAGNETIC COMPATIBILITY (EMC) 2-8 EU DIRECTIVES 2-9 MECHANICAL ROBUSTNESS 2-10 PROTECTION FUNCTIONS 2-10 Transformer Differential Protection 2-10 Circuitry Fault Alarm 2-10 Low Impedance Restricted Earth Fault 2-10 High Impedance Restricted Earth Fault 2-11 Through Fault Monitoring 2-11

    SYSTEM BACK-UP 2-11 Transient Overreach and Overshoot 2-11 Non-Directional/Directional Phase Sequence Overcurrent and Voltage Controlled

    Overcurrent 2-11 Negative Phase Sequence Overcurrent 2-11 Thermal Overload 2-12 Non-Directional/Directional Earth Fault 2-12 2-Stage Neutral Displacement or Residual Overvoltage 2-12 Volts/Hz 2-12 2-Stage Undervoltage 2-12 2-Stage Overvoltage 2-12 1-Stage NPS Overvoltage 2-12 4-Stage Underfrequency 2-13 2-Stage Overfrequency 2-13 CB Fail 2-13 Pole Dead 2-13

    SUPERVISORY FUNCTIONS 2-13 Voltage Transformer Supervision (VTS) 2-13 Differential Current Transformer Supervision (CTS) 2-13

    PROGRAMMABLE SCHEME LOGIC 2-14 MEASUREMENTS AND RECORDING FACILITIES 2-14

  • P64x/EN TD/A52 2. Technical Data

    Page (TD) 2-2

    MiCOM P642, P643 and P645

    TD

    Measurements 2-14 IRIG-B and Real-Time Clock 2-14 Current Loop Inputs and Outputs 2-15 Disturbance Records 2-15 Event, Fault and Maintenance Records 2-15 IEC 61850 Ethernet Data 2-15

    SETTINGS, MEASUREMENTS AND RECORDS LIST 2-16 Settings List 2-16 Date and Time 2-16 Configuration 2-16 CT and VT Ratios 2-17 Sequence of Event Recorder (Record Control) 2-17 Oscillography (Disturbance Recorder) 2-17 Measured Operating Data (Measuret Setup) 2-17 Communications 2-18 Optional Ethernet or Redundant Ethernet Port 2-18 Optional Additional Second Rear Communication (Rear Port2 (RP2)) 2-18 Commission Tests 2-18 Opto Coupled Binary Inputs (Opto Config) 2-19 Control Inputs into PSL (Ctrl. I/P Config.) 2-19 Function Keys 2-19 IED Configurator 2-19 IEC 61850 GOOSE 2-19 Control Input User Labels 2-19 (Ctrl. I/P Labels) 2-19 Settings in Multiple Groups 2-19

    PROTECTION FUNCTIONS 2-20 System Config 2-20 Differential Protection 2-20 REF Protection 2-20 NPS Overcurrent 2-21 Phase Overcurrent 2-21 V CONTROLLED O/C 2-21 Thermal Overload 2-22 4-Stage Directional Earth Fault 2-22 Through Fault 2-23 Residual Overvoltage (nvd) 2-23 Overfluxing (Volts/Hz) 2-23

    VOLTAGE PROTECTION 2-23

  • 2. Technical Data P64x/EN TD/A52

    MiCOM P642, P643 and P645

    Page (TD) 2-3

    TD

    Undervoltage 2-23 Overvoltage 2-23 NPS Overvoltage 2-23

    FREQUENCY PROTECTION 2-24 Underfrequency 2-24 Overfrequency 2-24 RTD Protection 2-24 Current Loop Input 2-24 Current Loop Output 2-24 CB Fail & I< 2-25 Input Labels 2-25 Output Labels 2-25 RTD Labels 2-25

    SUPERVISORY FUNCTIONS 2-25 Voltage Transformer Supervision 2-25 Current Transformer Supervision 2-25

    MEASUREMENTS LIST 2-26 Measurements 1 2-26 Measurements 2 2-28 Measurements 3 2-29

  • P64x/EN TD/A52 2. Technical Data

    Page (TD) 2-4

    MiCOM P642, P643 and P645

    TD

    BLANK PAGE

  • 2. Technical Data P64x/EN TD/A52

    MiCOM P642, P643 and P645

    Page (TD) 2-5

    TD

    MECHANICAL SPECIFICATIONS Design Modular MiCOM Px40 platform relay, P642 in 40TE case, P643 in 60TE and P645 in 60TE or 80TE case. Mounting is front of panel flush mounting, or 19 rack mounted (ordering options). Enclosure Protection Per IEC 60529: 1992:

    IP 52 Protection (front panel) against dust and dripping water. IP 50 Protection for the rear and sides of the case against dust. IP 10 Product safety protection for the rear due to live connections on the terminal block.

    Weight P642 (40TE): 7.9kg P643 (60TE): 11.5kg P645 (60TE): 11.5kg P645 (80TE): 15.5kg

    TERMINALS AC Current and Voltage Measuring Inputs Located on heavy duty (black) terminal block: Threaded M4 terminals, for ring terminal connection. CT inputs have integral safety shorting, upon removal of the terminal block. General Input/Output Terminals For power supply, opto inputs, output contacts and RP1 rear communications. Located on general purpose (grey) blocks: Threaded M4 terminals, for ring terminal connection. Case Protective Earth Connection Two rear stud connections, threaded M4. Must be earthed (grounded) for safety, minimum earth wire size 2.5mm2. Front Port Serial PC Interface EIA(RS)-232 DCE, 9 pin D-type female connector Socket SK1. Courier protocol for interface to MiCOM S1 Studio software. Isolation to ELV (Extra Low Voltage) level. Maximum cable length 15m.

    Front Download/Monitor Port EIA(RS)-232, 25 pin D-type female connector Socket SK2. For firmware and menu text downloads. Isolation to ELV level. Rear Communications Port (RP1) EIA(RS)-485 signal levels, two wire connections located on general purpose block, M4 screw. For screened twisted pair cable, multidrop, 1000 m max. For Courier (K-Bus), IEC-60870-5-103, MODBUS or DNP3.0 protocol (ordering options). Isolation to SELV (Safety Extra Low Voltage) level. Optional Rear Fiber Connection for SCADA/DCS BFOC 2.5 -(ST)-interface for glass fiber, as for IEC 874-10. 850nm short-haul fibers, one Tx and one Rx. For Courier, IEC-60870-5-103, MODBUS or DNP3.0 (Ordering options). Optional Second Rear Communications Port (RP2) EIA(RS)-232, 9 pin D-type female connector, socket SK4. Courier protocol: K-Bus, EIA(RS)-232, or EIA(RS)485 connection. Isolation to SELV level. Maximum cable length 15 m. Optional Rear IRIG-B Interface (Modulated or Unmodulated) BNC plug Isolation to SELV level. 50 ohm coaxial cable. Optional Rear Ethernet or Redundant Ethernet Connection for IEC 61850 or DNP3.0 10BaseT/100BaseTX Communications Interface in accordance with IEEE802.3 and IEC 61850 Isolation: 1.5 kV Connector type: RJ45 Cable type: Screened Twisted Pair (STP) Max. cable length: 100 m 100Base FX Interface Interface in accordance with IEEE802.3 and IEC 61850 Wavelength: 1300 nm Fiber: multi-mode 50/125 m or 62.5/125 m Connector type: BFOC 2.5 -(ST)

  • P64x/EN TD/A52 2. Technical Data

    Page (TD) 2-6

    MiCOM P642, P643 and P645

    TD

    RATINGS AC Measuring Inputs Nominal frequency: 50 and 60 Hz (settable) Operating range: 45 to 66 Hz Phase rotation ABC or ACB AC Current Nominal current (In): 1 and 5 A dual rated. Nominal burden: Phase

  • 2. Technical Data P64x/EN TD/A52

    MiCOM P642, P643 and P645

    Page (TD) 2-7

    TD

    OUTPUT CONTACTS Standard Contacts General purpose relay outputs for signaling, tripping and alarming: Rated voltage: 300 V Continuous current: 10 A Short-duration current: 30 A for 3 s Making capacity: 250 A for 30 ms Breaking capacity:

    DC: 50 W resistive DC: 62.5 W inductive (L/R = 50 ms) AC: 2500 VA resistive (cos = unity) AC: 2500 VA inductive (cos = 0.7) AC: 1250 VA inductive (cos = 0.5)

    Subject to maxima of 10 A and 300 V Response to command: < 5 ms Durability:

    Loaded contact: 10 000 operations minimum, Unloaded contact: 100 000 operations minimum.

    High Break Contacts Relay outputs for tripping: Rated voltage: 300 V Continuous current: 10 A dc Short-duration current: 30 A dc for 3 s Making capacity: 250 A dc for 30 ms Breaking capacity:

    DC: 7500 W resistive DC: 2500 W inductive (L/R = 50 ms) Subject to maxima of 10 A and 300 V Response to command: < 0.2 ms Durability: Loaded contact: 10 000 operations minimum, Unloaded contact: 100 000 operations minimum.

    Watchdog Contacts Non-programmable contacts for relay healthy or relay fail indication: Breaking capacity:

    DC: 30 W resistive DC: 15 W inductive (L/R = 40 ms) AC: 375 VA inductive (cos = 0.7)

    IRIG-B 12X Interface (Modulated) External clock synchronization to IRIG standard 200-98, format B12x Input impedance 6 k at 1000 Hz Modulation ratio: 3:1 to 6:1 Input signal, peak-peak: 200 mV to 20 V IRIG-B 00X Interface (Un-Modulated) External clock synchronization to IRIG standard 200-98, format B00X. Input signal TTL level Input impedance at dc 10 k

    ENVIRONMENTAL CONDITIONS Ambient Temperature Range As for EN 60088-2-1: 2007: EN 60168-2-2: 2007 Operating temperature range:

    -25C to +55C (or -13F to +131F) Storage and transit:

    -25C to +70C (or -13F to +158F) Tested as per:

    IEC 60068-2-1: 2007 -25C storage (96 hours) -40C operation (96 hours)

    IEC 60068-2-2: 2007 +85C storage (96 hours) +85C operation (96 hours)

    Ambient Humidity Range As for EN 60078-2-78: 2002:

    56 days at 93% relative humidity and +40 C

    As for IEC 60068-2-14: 2000 5 cycles, -25C to +55 C 1C / min rate of change

    Corrosive Environments Per IEC 60068-2-60: 1995, Part 2, Test Ke, Method (class) 3 Industrial corrosive environment/poor environmental control, mixed gas flow test. 21 days at 75% relative humidity and +30oC exposure to elevated concentrations of H2S, (100 ppb) NO2, (200 ppb) Cl2 (20 ppb). Per IEC 60068-2-52 Salt mist (7 days) Per IEC 60068-2-43 for H2S (21 days), 15 ppm Per IEC 60068-2-42 for SO2 (21 days), 25 ppm

  • P64x/EN TD/A52 2. Technical Data

    Page (TD) 2-8

    MiCOM P642, P643 and P645

    TD

    TYPE TESTS Insulation As for IEC 60255-27: 2005 (incorporating corrigendum March 2007): Insulation resistance > 100 M at 500 Vdc

    (Using only electronic/brushless insulation tester).

    Creepage Distances and Clearances IEC 60255-27: 2005 (incorporating corrigendum March 2007) Pollution degree 3, Overvoltage category III, Impulse test voltage 5 kV. High Voltage (Dielectric) Withstand (EIA RS-232 ports excepted and normally- open contacts of output relays excepted). (i) As for IEC 60255-27: 2005 (incorporating corrigendum March 2007), 2 kV rms AC, 1 minute:

    Between terminals of all independent circuits. Between all case terminals connected together, and the case earth (ground). 1 kV rms AC for 1 minute, across open watchdog contacts. 1 kV rms AC for 1 minute, across open contacts of changeover output relays. 1 kV rms AC for 1 minute for all D-type EIA(RS)-232 or EIA(RS)-485 ports between the communications port terminals and protective (earth) conductor terminal.

    (ii) As for ANSI/IEEE C37.90-1989 (reaffirmed 1994):

    1.5 kV rms AC for 1 minute, across open contacts of normally open output relays. 1k V rms AC for 1 minute, across open watchdog contacts. 1k V rms AC for 1 minute, across open contacts of changeover output relays.

    Impulse Voltage Withstand Test As for IEC 60255-27: 2005 (incorporating corrigendum March 2007): Front time: 1.2 s, Time to half-value: 50 s, Peak value: 5 kV, 0.5 J Between all independent circuits. Between all independent circuits and case earth ground). EIA(RS)-232 & EIA(RS)-485 ports and normally open contacts of output relays excepted.

    ELECTROMAGNETIC COMPATIBILITY (EMC) 1 MHz Burst High Frequency Disturbance Test As for EN 60255-22-1: 2008, Class III, Common-mode test voltage: 2.5 kV, Differential test voltage: 1.0 kV, Test duration: 2 s, Source impedance: 200 (EIA(RS)-232 ports excepted). 100 kHz Damped Oscillatory Test EN 61000-4-18: 2007: Levels Common mode test voltage: 2.5 kV Differential mode test voltage: 1 kV Immunity to Electrostatic Discharge As for IEC 60255-22-2: 1997, Class 4,

    15 kV discharge in air to user interface, display, communication ports and exposed metalwork. 8 kV point contact discharge in air to all communications ports. 6 kV point contact discharge to any part of the front of the product.

    Electrical Fast Transient or Burst Requirements As for IEC 60255-22-4: 2002 and EN61000-4-4:2004. Test severity Class III and IV: Amplitude: 2 kV, burst frequency 5 kHz (Class III), Amplitude: 4 kV, burst frequency 2.5 kHz (Class IV).

    Applied directly to auxiliary supply, and applied to all other inputs. (EIA(RS)-232 ports excepted).

    Amplitude: 4 kV, burst frequency 5 kHz (Class IV) applied directly to auxiliary.

    Surge Withstand Capability As for IEEE/ANSI C37.90.1: 2002: 4 kV fast transient and 2.5 kV oscillatory applied directly across each output contact, optically isolated input, and power supply circuit. Surge Immunity Test (EIA(RS)-232 ports excepted). As for IEC 61000-4-5: 2006 Level 4, Time to half-value: 1.2 to 50 s,

    Amplitude: 4 kV between all groups and case earth (ground), Amplitude: 2 kV between terminals of each group.

    Conducted/Radiated Immunity For RTDs used for tripping applications the conducted and radiated immunity performance is guaranteed only when using totally shielded RTD cables (twisted leads).

  • 2. Technical Data P64x/EN TD/A52

    MiCOM P642, P643 and P645

    Page (TD) 2-9

    Immunity to Radiated Electromagnetic Energy As for IEC 60255-22-3: 2001, Class III: Test field strength, frequency band 80 to 1000 MHz: 10 V/m, Test using AM: 1 kHz / 80%, Spot tests at 80, 160, 450, 900 MHz As for IEEE/ANSI C37.90.2: 2004: 25, 80 MHz to 1000 MHz, zero and 100% square wave modulated, 1 kHz 80% am and am pulse modulated. Field strength 35 V/m. Radiated Immunity from Digital Communications TD As for EN61000-4-3: 2002, Level 4: Test field strength, frequency band 800 to 960 MHz, and 1.4 to 2.0 GHz:

    30 V/m, Test using AM: 1 kHz/80%.

    Radiated Immunity from Digital Radio Telephones As for EN 61000-4-3: 2002: 10 V/m, 900 MHz and 1.89 GHz. Immunity to Conducted Disturbances Induced by Radio Frequency Fields As for EN 61000-4-6: 1996, Level 3, Disturbing test voltage: 10 V. Power Frequency Magnetic Field Immunity As for EN 61000-4-8: 2001, Level 5,

    100 A/m applied continuously, 1000 A/m applied for 3 s.

    As for EN 61000-4-9: 2001, Level 5, 1000 A/m applied in all planes.

    As for EN 61000-4-10: 2001, Level 5, 100 A/m applied in all planes at 100 kHz to 1 MHz with a burst duration of 2 s.

    Conducted Emissions As for EN 55022: 1998 Class A:

    0.15 - 0.5 MHz, 79 dBV (quasi peak) 66 dBV (average) 0.5 - 30 MHz, 73 dBV (quasi peak) 60 dBV (average).

    Radiated Emissions As for EN 55022: 1998 Class A:

    30 to 230 MHz, 40 dBV/m at 10 m measurement distance 230 to 1 GHz, 47 dBV/m at 10 m measurement distance.

    EU DIRECTIVES EMC Compliance As for 2004/108/EC:

    Compliance to the European Commission Directive on EMC is demonstrated using a Technical File. Product Specific Standards were used to establish conformity: EN 50263: 2000

    Product Safety As for 2006/95/EC: Compliance to the European Commission Low Voltage Directive. Compliance is demonstrated by reference to generic safety standards:

    EN60255-27: 2005 (incorporating corrigendum March 2007)

    R&TTE Compliance Radio and Telecommunications Terminal Equipment (R & TTE) directive 99/5/EC. Compliance demonstrated by compliance to both the EMC directive and the Low voltage directive, down to zero volts. Applicable to rear communications ports. Compliance demonstrated by Notified Body certificates of compliance.

    II (2) G

  • P64x/EN TD/A52 2. Technical Data

    Page (TD) 2-10

    MiCOM P642, P643 and P645

    TD

    MECHANICAL ROBUSTNESS Vibration Test As for IEC 60255-21-1: 1996:

    Response Class 2 Endurance Class 2

    Shock and Bump As for IEC 60255-21-2: 1996:

    Shock response Class 2 Shock withstand Class 1 Bump Class 1

    Seismic Test As for IEC 60255-21-3: 1995:

    Class 2

    PROTECTION FUNCTIONS Transformer Differential Protection Accuracy Pick-up: formula 5% Drop-off: 95% of formula 5% Pick-up and drop-off repeatability:

  • 2. Technical Data P64x/EN TD/A52

    MiCOM P642, P643 and P645

    Page (TD) 2-11

    TD

    High Impedance Restricted Earth Fault Accuracy Pick-up: formula 5% Drop-off: 0.90 formula 5% Pick-up and drop-off repeatability

  • P64x/EN TD/A52 2. Technical Data

    Page (TD) 2-12

    MiCOM P642, P643 and P645

    TD

    Thermal Overload Accuracy Hot Spot> Pick-up: Expected pick-up time 5% or 50ms whichever is greater (expected pick-up time is the time required to reach the temperature setting) Hot Spot> DT: 5%or 50 ms whichever is greater Top Oil> Pick-up: Expected Pick-up Time 5% or 50ms whichever is greater (expected pick-up time is the time required to reach the temperature setting) Top Oil> DT: 5%or 50 ms whichever is greater Repeatability:

  • 2. Technical Data P64x/EN TD/A52

    MiCOM P642, P643 and P645

    Page (TD) 2-13

    TD

    4-Stage Underfrequency Accuracy Pick-up: Setting 0.01 Hz Drop-off: (Setting +0.025 Hz) 0.01 Hz DT operation: 2% or 70 ms whichever is greater. Repeatability: Drop-off: 90% of setting 5% or 50 mA whichever is greater VTS I2> Pick-up: Setting 5% or 50 mA whichever is greater VTS I2> Drop-off: 95% of setting 5% or 50 mA whichever is greater P643/P645 models: VTS V< Pick-up: Fixed Threshold (10 V) 5% VTS V< Drop-off: Fixed Threshold (30 V) 5% P642 model: VTS V< Pick-up: Fixed Threshold (70 V) 5% VTS V< Drop-off: Fixed Threshold (95 V) 5% VTS V2> Pick-up: Fixed Threshold (10 V) 5% VTS V2> Drop-off: Fixed Threshold (9.5 V) 5% Pick-up and drop-off repeatability: 1 Drop-off ratio: setting 5% or 20 mA whichever is greater CTS I2/I1>2 Drop-off ratio: setting 5% or 20 mA whichever is greater Pick-up and drop-off repeatability:

  • P64x/EN TD/A52 2. Technical Data

    Page (TD) 2-14

    MiCOM P642, P643 and P645

    TD

    PROGRAMMABLE SCHEME LOGIC Accuracy Output conditioner timer: Setting 2% or 50 ms whichever is greater Dwell conditioner timer: Setting 2% or 50 ms whichever is greater Pulse conditioner timer: Setting 2% or 50 ms whichever is greater

    MEASUREMENTS AND RECORDING FACILITIES Measurements Accuracy Current: 0.05 to 3 In: 1% or 3 mA of reading Voltage: 0.05 to 2 Vn: 1% of reading Power (W): 0.2 to 2 Vn, 0.05 to 3 In: 5% of reading at unity power factor Reactive Power (VArs): 0.2 to 2 Vn, 0.05 to 3 In: 5% of reading at zero power factor Apparent Power (VA): 0.2 to 2 Vn, 0.05 to 3 In: 5% of reading Energy (Wh): 0.2 to 2 Vn, 0.2 to 3 In: 5% of reading at zero power factor Energy (Varh): 0.2 to 2 Vn, 0.2 to 3 In: 5% of reading at zero power factor Phase accuracy: 0 to 360: 5% Frequency: 5 to 70 Hz: 0.025 Hz

    IRIG-B and Real-Time Clock Performance Year 2000: Compliant Real time accuracy: < 1 second / day External clock synchronisation: Conforms to IRIG standard 200-98, format B Features Real time 24 hour clock settable in hours, minutes and seconds Calendar settable from January 1994 to December 2092 Clock and calendar maintained via battery after loss of auxiliary supply Internal clock synchronization using IRIG-B Interface for IRIG-B signal is BNC

  • 2. Technical Data P64x/EN TD/A52

    MiCOM P642, P643 and P645

    Page (TD) 2-15

    TD

    Current Loop Inputs and Outputs Accuracy Current loop input accuracy: 1% of full scale CLI drop-off threshold Under:

    setting 1% of full scale CLI drop-off threshold Over:

    setting 1% of full scale CLI sampling interval: 50 ms CLI instantaneous operating time: <

    200 ms for 20 Hz to 70 Hz; < 300 ms for 5 Hz to 20 Hz

    CLI DT operating time: 2% setting or 150 ms whichever is the greater for 20 Hz to 70 Hz; 2% setting or 200 ms whichever is the greater for 5 Hz to 20 Hz

    CLO conversion interval: 50 ms CLO latency: < 1.07 s or

  • P64x/EN TD/A52 2. Technical Data

    Page (TD) 2-16

    MiCOM P642, P643 and P645

    SETTINGS, MEASUREMENTS AND RECORDS LIST Settings List Global Settings (System Data) Language: English / French /

    German / Spanish / Russian / Chinese

    Frequency: 50/60 Hz

    Date and Time IRIG-B Sync: Disabled/Enabled Battery Status: data TD Battery Alarm: Disabled/Enabled LocalTime Enable: Disabled/Fixed/Flexible LocalTime Offset: -720 min720 min DST Enable: Disabled/Enabled DST Offset: 30 min60 min DST Start: First / Second / Third /

    Fourth / Last DST Start Day: Sun / Mon / Tues /

    Wed / Thurs / Fri / Sat DST Start Month: Jan / Feb / Mar / Apr /

    May / Jun / Jul / Aug / Sept / Oct / Nov / Dec

    DST Start Mins: 0 min1425 min DST End: First / Second / Third /

    Fourth / Last DST End Day: Sun / Mon / Tues /

    Wed / Thurs / Fri / Sat DST End Month: Jan / Feb / Mar / Apr /

    May / Jun / Jul / Aug / Sept / Oct / Nov / Dec

    DST End Mins: 0 min1425 min RP1 Time Zone: UTC/Local RP2 Time Zone: UTC/Local Tunnel Time Zone: UTC/Local

    Configuration Restore Defaults: No Operation/All

    settings, Setting Group 1, Setting Group 2, Setting Group 3, Setting Group 4

    Setting Group: Select from Menu Select from Opto

    Active Settings: Group 1/2/3/4 Save Changes: No Operation /

    Save / Abort

    Copy From: Group 1/2/3/4 Copy To: Group 1/2/3/4 Setting Group 1: Disabled/Enabled Setting Group 2: Disabled/Enabled Setting Group 3: Disabled/Enabled Setting Group 4: Disabled/Enabled Diff Protection Disabled/Enabled REF Protection Disabled/Enabled Overcurrent Disabled/Enabled NPS Overcurrent Disabled/Enabled Thermal Overload Disabled/Enabled Earth Fault Disabled/Enabled Residual O/V NVD Disabled/Enabled V/Hz Disabled/Enabled Through Fault Disabled/Enabled Volt Protection Disabled/Enabled Freq Protection Disabled/Enabled RTD Inputs Disabled/Enabled CB Fail Disabled/Enabled Supervision: Disabled/Enabled Input Labels: Invisible/Visible Output Labels: Invisible/Visible RTD Labels: Invisible/Visible CT & VT Ratios: Invisible/Visible Record Control Invisible/Visible Disturb Recorder: Invisible/Visible Measuret Setup: Invisible/Visible Comms Settings: Invisible/Visible Commission Tests: Invisible/Visible Setting Values: Primary/Secondary Control Inputs: Invisible/Visible CLIO Inputs: Disabled/Enabled CLIO Outputs: Disabled/Enabled Ctrl I/P Config: Invisible/Visible Ctrl I/P Labels: Invisible/Visible Direct Access: Disabled /

    Enabled / Hotkey

    IEC GOOSE: Invisible/Visible Function Keys: Invisible/Visible LCD Contrast: 031

  • 2. Technical Data P64x/EN TD/A52

    MiCOM P642, P643 and P645

    Page (TD) 2-17

    TD

    CT and VT Ratios Main VT Location HV/LV/TV Aux VT Location HV/LV Main VT Primary: 100...1 000 000 V Main VT Secondary: 80...140 V (100/120 V) Aux VT Primary: 100...1 000 000 V Aux VT Secondary: 80...140 V (100/120 V) T1 CT: CT Polarity

    Standard/Inverted CT Primary: 1 A30 kA CT Secondary: 1 A / 5 A

    T2 CT: CT Polarity Standard/Inverted CT Primary: 1 A30 KA CT Secondary: 1 A / 5 A

    T3 CT: CT Polarity Standard/Inverted CT Primary: 1 A30 KA CT Secondary: 1 A / 5 A

    T4 CT: CT Polarity Standard/Inverted CT Primary: 1 A30 KA CT Secondary: 1 A / 5 A

    T5 CT: CT Polarity Standard/Inverted CT Primary: 1 A30 KA CT Secondary: 1 A / 5 A

    TN1 CT: CT Polarity Standard/Inverted CT Primary: 1 A30 KA CT Secondary: 1 A / 5 A

    TN2 CT: CT Polarity Standard/Inverted CT Primary: 1 A30 KA CT Secondary: 1 A / 5 A

    TN3 CT: CT Polarity Standard/Inverted CT Primary: 1 A30 KA CT Secondary: 1 A / 5 A

    Sequence of Event Recorder (Record Control) Clear Events: No/Yes Clear Faults: No/Yes Clear Maint: No/Yes Alarm Event: Disabled/Enabled Relay O/P Event: Disabled/Enabled Opto Input Event: Disabled/Enabled General Event: Disabled/Enabled Fault Rec Event: Disabled/Enabled Maint Rec Event: Disabled/Enabled Protection Event: Disabled/Enabled Clear Dist Recs: No/Yes DDB 31 - 0: (up to): DDB 2047 - 2016: Binary function link

    strings selects which DDB signals are stored as events and which are filtered out.

    Oscillography (Disturbance Recorder) Duration: 0.1010.50 s Trigger Position: 0.0100.0% Trigger Mode: Single/Extended Analog Channel 1: (up to): Analog Channel 30 (depending on model):

    Disturbance channels selected from: IA-1 / IB-1 / IC-1 / IN-1 / IA-2 / IB-2 / IC-2 / IN-2, etc (depending on model)

    Digital Input 1: (up to): Digital Input 32: Selected binary channel assignment from any DDB status point in the relay such as opto input, output contact, alarms, starts, trips, controls, logic. Input 1 Trigger: No Trigger / (up to): Trigger L/H/ Input 32 Trigger: Trigger H/L Notes L/H (Low to High)

    H/L (High to Low)

    Measured Operating Data (Measuret Setup) Default Display: 3Ph + N Current,

    3Ph Neutral Voltage, Power, Date and Time, Description, Plant Reference, Frequency or Access Level

    Local Values: Primary/Secondary Remote Values: Primary/Secondary Measurement Ref: Vx, VA, VB, VC, IA1,

    IB1, IC1, IA2, IB2, IC2, IA3, IB3, IC3, IA4, IB4, IC4, IA5, IB5, IC5, VAB or VBC

    Measurement Mode: 0 / 1 / 2 / 3

  • P64x/EN TD/A52 2. Technical Data

    Page (TD) 2-18

    MiCOM P642, P643 and P645

    TD

    Communications RP2 Protocol: (data) RP1 Address: (Courier or IEC870-5-

    103): 0255 RP1 Address: (DNP3.0): 065534 RP1 Address: (MODBUS): 1247 RP1 InactivTimer: 130 mins RP1 Baud Rate: (IEC870-5-103):

    9600/ 19200/ 38400 bits/s

    RP1 Baud Rate: (MODBUS, Courier): 9600/ 19200/ 38400 bits/s

    RP1 Baud Rate: (DNP3.0): 9600/ 19200/ 38400 bits/s

    RP1 Parity: Odd/Even/None (MODBUS, DNP3.0)

    RP1 Meas Period: 160 s (IEC870-5-103)

    RP1 PhysicalLink: Copper (EIA(RS)-485 or K bus) or Fiber Optic

    RP1 Time Sync: Disabled/Enabled MODBUS IEC Timer: Standard/Reverse RP1 CS103Blocking: Disabled

    Monitor Blocking Command Blocking

    RP1 Card Status: (data) K-Bus OK EIA485 OK Fiber Optic OK (Courier)

    RP1 Port Config: (Courier): K Bus EIA485 (RS485)

    RP1 Comms Mode: (Courier): IEC60870 FT1.2 IEC60870 10-bit, no

    parity RP1 Baud Rate: 9600/

    19200/ 38400 bits/s

    Note If RP1 Port Config is K Bus the baudrate is fixed at 64 kbits/s

    DNP Need Time: 130 mins DNP App Fragment: 1002048 bytes DNP App Timeout: 1120 s DNP SBO Timeout: 110 s DNP Link Timeout: 0.160 s

    Optional Ethernet or Redundant Ethernet Port NIC Protocol: data NIC MAC Address: data NIC Tunl Timeout: 1...30 mins NIC Link Report: Alarm, Event, None NIC Link Timeout: 0.1...60 s

    Optional Additional Second Rear Communication (Rear Port2 (RP2)) RP2 Protocol: (data) RP2 Card Status: (data)

    Unsupported, Card not fitted, EIA232 OK, EIA485 OK Kbus OK

    RP2 Port Config: EIA(RS)-232 EIA(RS)-485 K-Bus

    RP2 Comms Mode: IEC60870 FT1.2 IEC60870 10-bit, no parity

    RP2 Address: 0255 RP2 InactivTimer: 130 mins RP2 Baud Rate: 9600/

    19200/ 38400 bits/s

    Note If RP2 Port Config is K Bus the baud rate is fixed at 64 kbits/s

    DNP Need Time: 130 mins DNP App Fragment: 1002048 bytes DNP App Timeout: 1120 s DNP SBO Timeout: 110 s

    Commission Tests Opto I/P Status: (data) indicates the

    status of the opt-inputs. Rly O/P Status: (data) indicates the

    status of the output relays.

    Test Port Status: (data) indicates the status of monitor bits 1 to 8.

    Monitor bit 1: Binary function link (up to): strings, selecting which

    Monitor bit 8: DDB signals have their status visible in the

    Commissioning menu, for test purposes

    Test Mode: Disabled Test Mode Blocked Contacts

    Test Pattern: Configuration of which output contacts are to be energized when the contact test is applied

  • 2. Technical Data P64x/EN TD/A52

    MiCOM P642, P643 and P645

    Page (TD) 2-19

    TD

    Opto Coupled Binary Inputs (Opto Config) Global Nominal V: 24 27 V

    30 34 V 48 54 V 110 125 V 220 250 V

    Custom Opto Input 1: (up to):

    Opto Input #. (# = max. opto no. fitted): Custom options allow independent thresholds to be set for each opto, from thesame range as above.

    Opto Filter Control: Binary function link string, selecting which optos have an extra 1/2 cycle noise filter, and which do not.

    Characteristics: Standard 60% - 80% 50% - 70%

    Control Inputs into PSL (Ctrl. I/P Config.) Hotkey Enabled: Binary function link

    string, selecting which of the control inputs are driven from Hotkeys.

    Control Input 1: Latched/Pulsed (up to): Control Input 32: Ctrl Command 1: ON/OFF (up to): SET/RESET Ctrl Command 32: IN/OUT ENABLED/DISABLED

    Function Keys Fn. Key Status 1: Disable (up to): Lock Fn. Key Status 10 Unlock/Enable Fn. Key 1 Mode: Toggled/Normal (up to): Fn. Key 10 Mode: Fn. Key 1 Label: User defined text string (up to): to describe the function Fn. Key 10 Label: of the particular function key

    IED Configurator Switch Conf. Bank: No Action/

    Switch Banks

    IEC 61850 GOOSE GoEna: Disabled/

    Enabled Test Mode: Disabled/

    Pass Through/ Forced

    VOP Test Pattern: 0x00000000... 0xFFFFFFFF

    Ignore Test Flag: No/ Yes

    Control Input User Labels (Ctrl. I/P Labels) Control Input 1: User defined text string (up to): to describe the function Control Input 32: of the particular control input

    Settings in Multiple Groups Note All settings here onwards apply for

    setting groups # = 1 to 4.

  • P64x/EN TD/A52 2. Technical Data

    Page (TD) 2-20

    MiCOM P642, P643 and P645

    TD

    PROTECTION FUNCTIONS System Config Winding Config: HV+LV+TV, HV+LV Winding Type: Conventional/Auto HV CT Terminals: 00001 LV CT Terminals: 10000 TV CT Terminals: 00100 Ref power S: 100kVA to 5GVA HV Connection: D-Delta / Y-Wye /

    Z-Zigzag HV Grounding: Grounded/Ungrounded HV Nominal: 100 V to 100 MV HV Rating: 100 KVA to 5 GVA Reactance: 1.00% to 100.00% LV Vector Group: 0 to 11 LV Connection: D-Delta / Y-Wye /

    Z-Zigzag LV Grounding: Grounded/Ungrounded LV Nominal: 100 V to 100 MV LV Rating: 100 kVA to 5 GVA TV Vector Group: 0 to 11 TV Connection: D-Delta / Y-Wye /

    Z-Zigzag TV Grounding: Grounded/Ungrounded TV Nominal: 100 V to 100 MV TV Rating: 100 kVA to 5 GVA Match Factor CT1: 0.05 to 20 Match Factor CT2: 0.05 to 20 Match Factor CT3: 0.05 to 20 Match Factor CT4: 0.05 to 20 Match Factor CT5: 0.05 to 20 Phase Sequence: Standard ABC /

    Reverse ACB VT Reversal: No Swap / A-B

    Swapped / B-C Swapped / C-A Swapped

    CT1 Reversal: No Swap / A-B Swapped / B-C Swapped / C-A Swapped

    CT2 Reversal: No Swap / A-B Swapped / B-C Swapped / C-A Swapped

    CT3 Reversal: No Swap / A-B Swapped / B-C Swapped / C-A Swapped

    CT4 Reversal: No Swap / A-B Swapped / B-C Swapped / C-A Swapped

    CT5 Reversal: No Swap / A-B Swapped / B-C Swapped / C-A Swapped

    Differential Protection Trans Diff: Enabled/Disabled Set Mode: Simple/Advance Is1: 100.0e-3 to 2.500 PU K1: 0 to 150.0% Is2: 100.0e-3 to 10 PU K2: 15 to 150.00% tDIFF LS: 0 to 10.00 s Is-CTS: 100.0e-3 to 2.500 PU Is-HS1: 2.500 to 32.00 PU H2S status: Enabled/Disabled Is-HS2: 2.500 to 32.00 PU Zero seq filt HV: Enabled/Disabled Zero seq filt LV: Enabled/Disabled Zero seq filt TV: Enabled/Disabled 2nd harmonic blocked: Enabled/Disabled Ih(2)%>: 5.000 to 50.000% Cross blocking: Enabled/Disabled CTSat and NoGap: Enabled/Disabled 5th harm blocked: Enabled/Disabled Ih(5)%>: 0 to 100.00% Circuitry Fail: Enabled/Disabled Is-cctfail>: 30.00e-3 to 1.000 PU K-cctfail: 0 to 50.00% tls-cctfail>: 0 to 10.00 s

    REF Protection REF HV status: LowZ REF/

    HighZ REF/Disabled HV CT input: TN1 HV IS1 Set: 6.00 to 300.00 A HV IS2 Set: 30.00 to 3000.00 A HV IREF K1: 0 to 150.0% HV IREF K2: 15.00 to 150.0% HV tREF: 0 to 10.00 s REF LV status: LowZ REF/

    HighZ REF/Disabled LV CT input: TN2 LV IS1 Set: 6.00 to 300.00 A LV IS2 Set: 30.00 to 3000.00 A LV IREF K1: 0 to 150.0% LV IREF K2: 15.00 to 150.0% LV tREF: 0 to 10.00 s REF TV status: LowZ REF/

    HighZ REF/Disabled TV CT input: TN3 TV IS1 Set: 6.00 to 300.00 A TV IS2 Set: 30.00 to 3000.00 A TV IREF K1: 0 to 150.0% TV IREF K2: 15.00 to 150.0% TV tREF: 0 to 10.00 s REF Auto status: LowZ REF/

    HighZ REF/Disabled Auto CT input: TN1 Auto IS1 Set: 6.00 to 300.00 A Auto IS2 Set: 30.00 to 3000.00 A Auto IREF K1: 0 to 150.0% Auto IREF K2: 15.00 to 150.0% TV tREF: 0 to 10.00 s

  • 2. Technical Data P64x/EN TD/A52

    MiCOM P642, P643 and P645

    Page (TD) 2-21

    TD

    NPS Overcurrent NPS O/C 1: T1/T2/T3/T4/T5/

    HV winding/ LV winding/ TV winding

    2>1 Status: Disabled/Enabled 2>1 Char: DT

    IEC S Inverse IEC V Inverse IEC E Inverse UK LT Inverse UK Rectifier RI IEEE M Inverse IEEE V Inverse IEEE E Inverse US Inverse US ST Inverse

    I2>1 Directional: Non-directional, Directional Fwd, Directional Rev

    I2>1 Current Set: 0.08 to 4.00 In I2>1 Time Delay: 0.00 to 100.00 s I2>1 TMS: 0.025 to 1.200 I2>1 Time Dial: 0.01 to 100.00 I2>1 K (RI): 0.10 to10.00 I2>1 Reset Char: DT/Inverse I2>1 tRESET: 0.00 to 100.00 s I2>2 the same as I2>1 I2>3 Status: Disabled/Enabled I2>3 Directional: Non-directional,

    Directional Fwd, Directional Rev

    I2>3 Current Set: 0.08 to 4.00 In I2>3 Time Delay: 0.00 to 100.00 s I2>4 the same as I2>3 I2> VTS Blocking: 1111 I2> V2pol Set: 0.5 to 25V I2> Char Angle: -95 to 95 NPS O/C 2 and NPS O/C 3 same as NPS O/C 1

    Phase Overcurrent Overcurrent1: T1/T2/T3/T4/T5/

    HV winding/ LV winding/ TV winding

    I>1 Status: Enabled/Disabled I> 1 Char: DT

    IEC S Inverse IEC V Inverse IEC E Inverse UK LT Inverse UK Rectifier RI IEEE M Inverse IEEE V Inverse IEEE E Inverse US Inverse US ST Inverse

    I>1 Direction: Non-directional, Directional Fwd, Directional Rev

    I>1 Current Set: 0.08 to 4.00 In

    I>1 Time Delay: 0.00 to 100.00 s I>1 TMS: 0.025 to 1.200 I>1 Time Dial: 0.01 to 100.00 I>1 K (RI): 0.10 to10.00 I>1 Reset Char: DT/Inverse I>1 tRESET: 0.00 to 100.00 s I>2 the same as I>1 I>3 Status: Disabled/Enabled I>3 Direction: Non-directional,

    Directional Fwd, Directional Rev

    I>3 Current Set: 0.08 to 32.00 In I>3 Time Delay: 0.00 to 100.00 s I>4 the same as I>3 I> Char Angle: -95 to 95 I> Function Link: 1111 Overcurrent2 and Overcurrent3 the same as Overcurrent1

    V CONTROLLED O/C VCO>1: T1/T2/T3/T4/T5/

    HV winding/ LV winding/ TV winding

    VCO>1 Char: DT IEC S Inverse IEC V Inverse IEC E Inverse UK LT Inverse UK Rectifier RI IEEE M Inverse IEEE V Inverse IEEE E Inverse US Inverse US ST Inverse

    VCO>1 Direction: Non-directional, Directional Fwd, Directional Rev

    VCO>1 Curr' Set: 0.08 to 4.00 In VCO>1 Time Delay: 0.00 to 100.00 s VCO>1 TMS: 0.025 to 1.200 VCO>1 Time Dial: 0.01 to 100.00 VCO>1 K (RI): 0.10 to10.00 VCO>1 Reset Char: DT/Inverse VCO>1 tRESET: 0.00 to 100.00 s VCO>1 Angle: -95 to 95 VCO>1 V1 K Setting: 0.1 to 1 VCO>2 the same as VCO>1

  • P64x/EN TD/A52 2. Technical Data

    Page (TD) 2-22

    MiCOM P642, P643 and P645

    TD

    Thermal Overload Mon't Winding: HV/LV/TV/

    Biased Current Ambient T: RTD1 / RTD2 / RTD3 /

    RTD4 / RTD5 / RTD5 / RTD7 / RTD8 / RTD9 / RTD10 / AVERAGE / CLIO1 / CLIO2 / CLIO3 / CLIO4

    Amb CLIO Type: 0-1 / 0-10 / 0-20 / 4-20 mA

    Amb CLIO Min: -9999 to +9999 Amb CLIO Max: -9999 to +9999 Average Amb T: -25.00 to +75.00 Cel Top Oil T: RTD1 / RTD2 / RTD3 /

    RTD4 / RTD5 / RTD5 / RTD7 / RTD8 / RTD9 / RTD10 / CALCULATED / CLIO1 / CLIO2 / CLIO3 / CLIO4

    Top Oil CLIO Typ: 0-1 / 0-10 / 0-20 / 4-20 mA

    Top Oil CLIO Min: -9999 to +9999 Top Oil CLIO Max: -9999 to +9999 IB: 0.1 to 4.0 PU Rated NoLoadLoss: 0.1 to 100 Hot Spot overtop: 0.1 to 200.0 Cel Top Oil overamb: 0.1 to 200.0 Cel Cooling mode: Cooling mode 1 /

    Cooling mode 2 / Cooling mode 3 / Cooling mode 4 / Select Via PSL

    Cooling Status: (data) Cooling mode 1 / Cooling mode 2 / Cooling mode 3 / Cooling mode 4

    Cooling mode 1 Winding exp m: 0.01 to 2.0 Oil exp n: 0.01 to 2.0 Cooling mode 2, Cooling mode 3 and Cooling mode 4 same as Cooling mode 1 Hot spot rise co: 0.01 to 20.0 min Top oil rise co: 1.0 to 1000.0 min TOL Status: Enabled/Disabled Hot Spot>1 to 3 Set: 1.0 to 300.0 Cel tHot Spot>1 to 3 Set: 0 to 60 k min Top Oil>1 to 3 Set: 1.0 to 300.0 Cel tTop Oil>1 to 3 Set: 0 to 60k min tPre-trip Set: 0 to 60 k min LOL Status: Enabled/Disabled Life Hours at HS: 1 to 300 000 hr Designed HS temp: 1 to 200.0 Cel Constant B Set: 1 to 100 000 FAA> Set: 0.1 to 30 tFAA> Set: 0 to 60 k min LOL>1 Set: 0.1 to 300 000hr tLOL> Set: 0 to 60 k min Rst Life Hours: 0 to 300 000 hr

    4-Stage Directional Earth Fault Earth Fault 1: Enabled, Disabled EF 1 Input: Measured / Derived EF 1 Derived: (data) T1/T2/T3/T4/T5/

    HV winding/ LV winding/ TV winding

    EF 1 Measured: (data) TN1/TN2/TN3 IN>1 Status: Enabled/Disabled IN>1 Char: DT

    IEC S Inverse IEC V Inverse IEC E Inverse UK LT Inverse RI IEEE M Inverse IEEE V Inverse IEEE E Inverse US Inverse US ST Inverse IDG

    IN>1 Direction: Non-directional, Directional Fwd, Directional Rev

    IN>1 Current: 0.08 to 4 In IN>1 IDG Is: 1 to 4 In IN>1 Time Delay: 0.00 to 200.0 s IN>1 TMS: 0.025 to 1.200 IN>1 Time Dial: 0.01 to 100.00 IN>1 K(RI): 0.1 to 10.00 IN>1 IDG Time: 1 to 2.00 IN>1 Reset Char: DT, Inverse IN>1 tRESET: 0.00 to 100.00 s IN>2 same as IN>1 IN>3 Status: Disabled, DT IN>3 Current: 0.08 to 32.00 In IN>3 Time Delay: 0.00 to 200.00 s IN>4 same as IN>3 Earth fault 2 and Earth fault 3 same as Earth fault 1 The IDG curve is commonly used for time delayed earth fault protection in the Swedish market. This curve is available in stage 1 of the Earth Fault protection. The IDG curve is represented by:

    t = 5.8 - 1.35 loge

    N > Setting in seconds

    Where: = Measured current N>Setting = An adjustable setting which defines the start point of the characteristic

    Although the start point of the characteristic is defined by the N> setting, the actual relay current threshold is a different setting called IDG s. The IDG s setting is set as a multiple of N>. An additional setting IDG Time is also used to set the minimum operating time at high levels of fault current.

  • 2. Technical Data P64x/EN TD/A52

    MiCOM P642, P643 and P645

    Page (TD) 2-23

    0

    1

    2

    3

    4

    5

    6

    7

    8

    9

    10

    1 10

    I/IN>

    Ope

    ratin

    g tim

    e (s

    econ

    ds)

    100

    IDG Is Setting Range

    IDG Time Setting Range

    TD Figure 1 - IDG Characteristic

    Through Fault Through Fault: Disabled/Enabled Monitored Input: HV / LV / TV TF I> Trigger: 0.08 to 20.00PU TF I2t> Alarm: 0 to 500 000 A2 s

    Residual Overvoltage (nvd) VN>1 Function: Disabled/DT/IDMT VN>1 Voltage Set: 1 to 80 V VN>1 Time Delay: 0 to 100 s VN>1 TMS: 0.5 to 100 VN>1 tReset: 0 to 100 s VN>2 Status: Enabled/Disabled VN>2 Voltage Set: 1 to 80 V VN>2 Time Delay: 0 to 100 s

    Overfluxing (Volts/Hz) Volts/Hz W2 V/Hz Alm Status: Disabled/Enabled V/Hz Alarm Set: 1.5 to 3.5 V/Hz V/Hz Alarm Delay: 0 to 6000 s V/Hz>1 Status: Disabled/Enabled V/Hz>1 Trip Func DT / IDMT V/Hz>1 Trip Set: 1.5 to 3.5 V/Hz V/Hz>1 Trip TMS: 0.01 to 12 V/Hz>1 Delay: 0 to 6000 s V/Hz>1 tReset: 0 to 6000 s V/Hz>2 Status: Disabled/Enabled V/Hz>2 Trip Set: 1.5 to 3.5 V/Hz V/Hz>2 Delay: 0 to 6000 s V/Hz>3 and 4 same as V/Hz>2 TPre-trip Alarm: 1 to 6000.0 s Volts/Hz W1 the same as Volts/Hz W2 The inverse time characteristic is given by

    t = TMS

    (M - 1)2

    Where:

    M = V/f

    ( V/f Trip Setting )

    V = Measured voltage F = Measured frequency

    VOLTAGE PROTECTION Undervoltage V< Measurt Mode: Phase-Phase/

    Phase-Neutral V< Operate Mode: Any Phase/Three Phase V< 1 Function: Disabled/DT/IDMT V2 Time Delay: 0.00 to 100.00 s The inverse characteristic is given by:

    t = K

    (M - 1)

    Where: K = Time multiplier setting t = Operating time in seconds M = Applied input voltage/overvoltage setting

    NPS Overvoltage V2>1 Status: Enabled/Disabled V2>1 Voltage Set: 1 to 110 V V2>1 Time Delay: 0 to 100 s

  • P64x/EN TD/A52 2. Technical Data

    Page (TD) 2-24

    MiCOM P642, P643 and P645

    TD

    FREQUENCY PROTECTION Underfrequency F1

    RTD Protection Select RTD: Bit 0 - Select RTD 1

    Bit 1 - Select RTD 2 through to Bit 9 - Select RTD 10

    Binary function link string, selecting which RTDs (1 - 10) are enabled. RTD 1 Alarm Set: 0C to 200C RTD 1 Alarm Dly: 0 s to 100 s RTD 1 Trip Set: 0C to 200C RTD 1 Trip Dly: 0 s to 100 s RTD2/3/4/5/6/7/8/9/10 the same as RTD1

    Current Loop Input CLIO1 Input 1: Disabled/Enabled CLI1 Input Type: 0 1 mA

    0 10 mA 0 20 mA 4 20 mA

    CLI1 Input Label: 16 characters (CLIO input 1)

    CLI1 Minimum: -9999+9999 CLI1 Maximum: -9999+9999 CLI1 Alarm: Disabled/Enabled CLI1 Alarm Fn: Over/Under CLI1 Alarm Set: CLI1 min to CLI1 max CLI1 Alarm Delay: 0.0 to 100.0 s CLI1 Trip: Disabled/Enabled CLI1 Trip Fn: Over/Under CLI1 Trip Set: CLI1 min to CLI1 max CLI1 Trip Delay: 0.0 to 100.0 s CLI1 I< Alarm (4 to 20 mA input only):

    Disabled/Enabled CLI1 I< Alm Set (4 to 20 mA input only):

    0.0 to 4.0 mA CLI2/3/4 the same as CLI1

    Current Loop Output CLO1 Output 1: Disabled/Enabled CLO1 Output Type: 0 1 mA

    0 10 mA 0 20 mA 4 20 mA

    CLO1 Set Values: Primary/Secondary CLO1 Parameter: As shown below* CLO1 Min: Range, step size and

    unit corresponds to the selected parameter

    CLO1 Max: Same as CLO1 Min CLO2/3/4 the same as CLO1 Current Loop Output Parameters:

    IA-1 Magnitude IB-1 Magnitude IC-1 Magnitude IA-2 Magnitude IB-2 Magnitude IC-2 Magnitude IA-3 Magnitude IB-3 Magnitude IC-3 Magnitude IA-4 Magnitude IB-4 Magnitude IC-4 Magnitude IA-5 Magnitude IB-5 Magnitude IC-5 Magnitude I1-1 Magnitude I2-1 Magnitude I0-1 Magnitude I1-2 Magnitude I2-2 Magnitude I0-2 Magnitude I1-3 Magnitude I2-3 Magnitude I0-3 Magnitude I1-4 Magnitude I2-4 Magnitude I0-4 Magnitude I1-5 Magnitude I2-5 Magnitude I0-5 Magnitude IA HV Magnitude IB HV Magnitude IC HV Magnitude IN HV Measured Mag IN HV Derived Mag IA LV Magnitude IB LV Magnitude IC LV Magnitude IN LV Measured Mag IN LV Derived Mag IA TV Magnitude IB TV Magnitude IC TV Magnitude IN TV Measured Mag IN TV Derived Mag VAB Magnitude VBC Magnitude VCA Magnitude VAN Magnitude

  • 2. Technical Data P64x/EN TD/A52

    MiCOM P642, P643 and P645

    Page (TD) 2-25

    TD

    VBN Magnitude VCN Magnitude Vx Magnitude VN Derived Mag V1 Magnitude V2 Magnitude V0 Magnitude VAN RMS VBN RMS VCN RMS Frequency RTD 1 through to RTD 10 CL Input 1 through to CL Input 4 Volts/Hz W1 V/Hz W1 Thermal Volts/Hz W2 V/Hz W2 Thermal Hot Spot T Top Oil T Ambient T LOL Status

    CB Fail & I< T1 CBF Status: Enabled/Disabled I< Current Set: 5% to 400% IN< Status: Enabled/Disabled IN< Input: Measured/Derived IN< Terminal: TN1/TN2/TN3 IN< Current Set: 5% to 400% CB Fail 1 Status: Enabled/Disabled CB Fail 1 Timer: 0 to 10s CB Fail 2 Status: Enabled/Disabled CB Fail 2 Timer: 0 to