manual mpi ie

104
s Preface, Contents Introduction 1 Installation 2 Functions in PRODAVE MPI/IE V6.2 3 Glossary, Index SIMATIC PRODAVE MPI/IE V6.2 Manual 01/2012 A5E03681152-01

Upload: ahmedwww

Post on 26-Dec-2015

57 views

Category:

Documents


0 download

DESCRIPTION

prodave 6.2 manual

TRANSCRIPT

Page 1: Manual Mpi Ie

s

Preface, Contents

Introduction 1 Installation 2 Functions in PRODAVE MPI/IE V6.2 3 Glossary, Index

SIMATIC

PRODAVE MPI/IE V6.2 Manual

01/2012 A5E03681152-01

Page 2: Manual Mpi Ie

Siemens AG Industry Automation Postfach 4848 90026 NÜRNBERG GERMANY

A5E03681152-01 01/2012

Copyright © Siemens AG 2012 Technical data subject to change

Safety Guidelines

This manual contains notices you have to observe in order to ensure your personal safety, as well as to

prevent damage to property. The notices referring to your personal safety are highlighted in the manual

by a safety alert symbol, notices referring to property damage only have no safety alert symbol. The

notices shown below are graded according to the degree of danger.

! Danger indicates that death or severe personal injury will result if proper precautions are not taken.

! Warning indicates that death or severe personal injury may result if proper precautions are not taken.

! Caution with a safety alert symbol indicates that minor personal injury can result if proper precautions are not taken.

Caution without a safety alert symbol indicates that property damage can result if proper precautions are not taken.

Notice

indicates that an unintended result or situation can occur if the corresponding notice is not taken into account.

If more than one degree of danger is present, the warning notice representing the highest degree of

danger will be used. A notice warning of injury to persons with a safety alert symbol may also include a

warning relating to property damage.

Qualified Personnel

The device/system may only be set up and used in conjunction with this documentation. Commissioning

and operation of a device/system may only be performed by qualified personnel. Within the context of

the safety notices in this documentation qualified persons are defined as persons who are authorized to

commission, ground and label devices, systems and circuits in accordance with established safety

practices and standards.

Prescribed Usage

Note the following:

! Warning This device and its components may only be used for the applications described in the catalog or the technical description, and only in connection with devices or components from other manufacturers which have been approved or recommended by Siemens. Correct, reliable operation of the product requires proper transport, storage, positioning and assembly as well as careful operation and maintenance.

Trademarks

All names identified by ® are registered trademarks of the Siemens AG.

The remaining trademarks in this publication may be trademarks whose use by third parties for their

own purposes could violate the rights of the owner.

Disclaimer of Liability

We have reviewed the contents of this publication to ensure consistency with the hardware and

software described. Since variance cannot be precluded entirely, we cannot guarantee full consistency.

However, the information in this publication is reviewed regularly and any necessary corrections are

included in subsequent editions.

Page 3: Manual Mpi Ie

PRODAVE MPI/IE V6.1 A5E03681152-01 3

Preface

Purpose of the Manual

This manual gives you a complete overview of the PRODAVE MPI/IE V6.2 functions.

This manual is intended for those responsible for configuring, commissioning, and servicing automation systems.

Required Basic Knowledge

You require a general knowledge in the field of automation engineering to be able to understand this manual.

In addition, you should know how to use computers or devices with similar functions (e.g programming devices) under Windows XP or Vista operating systems.

Where is this Manual valid?

This manual is valid for the software package PRODAVE MPI/IE V6.2.

Page 4: Manual Mpi Ie

Preface

PRODAVE MPI/IE V6.1 4 A5E03681152-01

Further Support

If you have any technical questions, please get in touch with your Siemens representative or agent responsible.

You will find your contact person at:

http://www.siemens.com/automation/partner

You will find a guide to the technical documentation offered for the individual SIMATIC Products and Systems here at:

http://www.siemens.com/simatic-tech-doku-portal

The online catalog and order system is found under:

http://mall.automation.siemens.com/

Training Centers Siemens offers a number of training courses to familiarize you with the SIMATIC S7 automation system. Please contact your regional training center or our central training center in D 90327 Nuremberg, Germany for details:

Internet: http://www.sitrain.com

Page 5: Manual Mpi Ie

Preface

PRODAVE MPI/IE V6.1 A5E03681152-01 5

Technical Support

You can reach the Technical Support for all Industry Automation and Drive Technology products

• Via the Web formula for the Support Request http://www.siemens.com/automation/support-request

Additional information about our Technical Support can be found on the Internet pages http://www.siemens.com/automation/service

Service & Support on the Internet

In addition to our documentation, we offer our Know-how online on the internet at:

http://www.siemens.com/automation/service&support

where you will find the following:

• The newsletter, which constantly provides you with up-to-date information on your products.

• The right documents via our Search function in Product Support.

• A forum, where users and experts from all over the world exchange their experiences.

• Your local representative for Industry Automation and Drive Technology.

• Information on field service, repairs, spare parts and Consulting.

Page 6: Manual Mpi Ie

Preface

PRODAVE MPI/IE V6.1 6 A5E03681152-01

Page 7: Manual Mpi Ie

PRODAVE MPI/IE V6.1 A5E03681152-01 7

Contents

Preface 3

Contents 7

1 Introduction 9

2 Installation 11 2.1 Automation License Manager............................................................................ 11 2.1.1 User Rights through the Automation License Manager..................................... 11 2.1.2 Installing the Automation License Manager....................................................... 13 2.1.3 Guidelines for Handling License Keys............................................................... 14 2.2 Installing PRODAVE MPI/IE V6.2...................................................................... 15 2.2.1 Installation Procedure........................................................................................ 16 2.2.2 Setting the PG/PC Interface .............................................................................. 18 2.2.3 Installing V6.2 over V6.x .................................................................................... 20 2.3 Uninstalling PRODAVE MPI/IE V6.2 ................................................................. 20 2.3.1 Uninstalling PRODAVE MPI/IE V6.2 ................................................................. 20

3 Functions in PRODAVE MPI/IE V6.2 21 3.1 Basic Functions ................................................................................................. 24 3.1.1 LoadConnection_ex6......................................................................................... 24 3.1.2 UnloadConnection_ex6 ..................................................................................... 27 3.1.3 SetActiveConnection_ex6 ................................................................................. 28 3.1.4 SetPassword_ex6.............................................................................................. 29 3.1.5 UnSetPassword_ex6 ......................................................................................... 30 3.1.6 as_info_ex6 ....................................................................................................... 31 3.1.7 as_zustand_ex6................................................................................................. 33 3.1.8 db_buch_ex6 ..................................................................................................... 35 3.1.9 db_read_ex6...................................................................................................... 36 3.1.10 db_write_ex6 ..................................................................................................... 38 3.1.11 bst_read_diag_ex6 ............................................................................................ 40 3.1.12 bst_read_stat_ex6 ............................................................................................. 42 3.1.13 bst_read_ex6 ..................................................................................................... 44 3.1.14 read_diag_buf_ex6 ............................................................................................ 48 3.1.15 field_read_ex6 ................................................................................................... 50 3.1.16 field_write_ex6................................................................................................... 52 3.1.17 szl_read_ex6 ..................................................................................................... 53 3.1.18 get_pb_lifelist_ex6 ............................................................................................. 55 3.1.19 get_ie_lifelist_ex6 .............................................................................................. 57 3.1.20 defrag_ex6......................................................................................................... 59 3.1.21 mb_setbit_ex6 ................................................................................................... 60 3.1.22 mb_bittest_ex6 .................................................................................................. 61 3.2 Functions for Data Transfer to S7-200 .............................................................. 62 3.2.1 as200_as_info_ex6............................................................................................ 62 3.2.2 as200_as_zustand_ex6..................................................................................... 64 3.2.3 as200_field_read_ex6 ....................................................................................... 65 3.2.4 as200_field_write_ex6....................................................................................... 67 3.2.5 as200_mb_setbit_ex6........................................................................................ 69

Page 8: Manual Mpi Ie

Contents

PRODAVE MPI/IE V6.1 8 A5E03681152-01

3.2.6 as200_mb_bittest_ex6....................................................................................... 70 3.3 Convenience Functions ..................................................................................... 72 3.3.1 GetErrorMessage_ex6....................................................................................... 72 3.3.2 kg_2_float_ex6 .................................................................................................. 75 3.3.3 float_2_kg_ex6 .................................................................................................. 76 3.3.4 gp_2_float_ex6 .................................................................................................. 77 3.3.5 float_2_gp_ex6 .................................................................................................. 78 3.3.6 testbit_ex6 ......................................................................................................... 79 3.3.7 byte_2_bool_ex6 ............................................................................................... 80 3.3.8 bool_2_byte_ex6 ............................................................................................... 81 3.3.9 kf_2_integer_ex6, kf_2_long_ex6...................................................................... 82 3.3.10 swab_buffer_ex6 ............................................................................................... 83 3.3.11 copy_buffer_ex6 ................................................................................................ 84 3.3.12 ushort_2_bcd_ex6, ulong_2_bcd_ex6............................................................... 85 3.3.13 bcd_2_ushort_ex6, bcd_2_ulong_ex6............................................................... 87 3.3.14 GetLoadedConnections_ex6 ............................................................................. 89 3.3.15 GetPduSize_ex6................................................................................................ 90 3.4 TeleService Functions ....................................................................................... 91 3.4.1 ts_dial_ex6......................................................................................................... 91 3.4.2 ts_hang_up_dial_ex6......................................................................................... 93 3.4.3 ts_set_ringindicator_ex6.................................................................................... 94 3.4.4 ts_read_info_ex6 ............................................................................................... 95 3.4.5 ts_hang_up_ring_ex6 ........................................................................................ 96 3.4.6 ts_get_modem_name_ex6 ................................................................................ 97 3.5 Data Structures.................................................................................................. 98

Glossary 99

Index 103

Page 9: Manual Mpi Ie

PRODAVE MPI/IE V6.1 A5E03681152-01 9

1 Introduction

PRODAVE MPI/IE V6.2 provides functions which can be combined with a user application. The tools are combined in the development environments of the C and Basic programming languages.

With these functions PRODAVE MPI/IE V6.2 establishes the process data communication via MPI-Profibus or Ethernet communication of the SIMATIC AS between automation system and PG/PC. During communication PRODAVE MPI/IE V6.2 accesses functions of the S7DOS component. The parameters are assigned to the interfaces using the "Set PG/PC interface" of the S7DOS.

The following major extensions to the functions have been incorporated in PRODAVE MPI/IE V6.2:

• Support for the operating system MS Windows 7 (32 bit and 64 bit).

• A new function for reading the PDU size.

All SIMATIC automation systems are supported:

• S7 400

• S7 300

• S7 200

PRODAVE MPI/IE V6.2 only supports the following operating systems: MS Windows XP Professional, MS Windows Vista 32, and MS Windows 7. Also the respective up-to-date service packs are also supported.

The services via industrial Ethernet receive clearance only for MS Windows XP, MS Windows Vista 32 and MS Windows 7 !

PRODAVE MPI/IE V6.2 supports neither Fast-User-Switching nor terminal-server operation!

Page 10: Manual Mpi Ie

Introduction

PRODAVE MPI/IE V6.1 10 A5E03681152-01

Page 11: Manual Mpi Ie

PRODAVE MPI/IE V6.1 A5E03681152-01 11

2 Installation

2.1 Automation License Manager

2.1.1 User Rights through the Automation License Manager

Automation License Manager

A product-specific license key (user rights) is required which is installed by PRODAVE MPI/IE V6.2 with the Automation License Manager from V6.0 on.

Automation License Manager is a software product of Siemens AG. It is a global system toolused to handle license keys (technical license representatives.)

You can find the Automation License Manager:

• On the installation device for the respective software product requiring a license key or

• On a separate installation device as well as

• As a download from the Internet page of A&D Customer Support at Siemens AG.

Automation License Manager provides an integrated Online Help system. You can call this help after installation context-sensitive by pressing F1, or by selecting the Help > Help on License Manager command. This online help contains detailed information on the functionality and operation of the Automation License Manager.

Licenses

Licenses are required to use PRODAVE MPI/IE V6.2 program packages whose legal use is protected by licenses. A license gives the user a legal right to use the product. Evidence of this right is provided by the following:

• The CoL (Certificate of License) and

• The license key

Page 12: Manual Mpi Ie

Installation

PRODAVE MPI/IE V6.1 12 A5E03681152-01

Certificate of License (CoL)

The "Certificate of License" that is included with a product is the legal evidence that a right to use this product exists. This product may only be used by the owner of the Certificate of License (CoL) or by those persons authorized to do so by the owner.

License keys

The license key is the technical representation (an electronic "license stamp") of a license to use software.

SIEMENS AG issues a license key for all software protected by legal license agreement. When the computer has been started, such software can only be used in accordance with the applicable license and terms of use after the presence of a valid license key has been verified.

Notes

• You can use PRODAVE MPI/IE V6.2 without a license key to familiarize yourself with the user interface and functions.

• However, a license is required and necessary for full, unrestricted use in accordance with the license agreement.

• If you have not installed the license key, you will be prompted to do so at regular intervals.

License keys can be stored and transferred among various types of storage devices as follows:

• On license key diskettes

• On the local hard disk

• On network hard disk

If software products for which no license is available are installed, you can then determine which license key is needed and order it as required.

For further information on handling license keys, please refer to the Automation License Manager Online Help.

Page 13: Manual Mpi Ie

Installation

PRODAVE MPI/IE V6.1 A5E03681152-01 13

Licenses

Siemens AG distinguishes between the following user-oriented license types for its software products. The behavior of the software is controlled by different license keys for these license types. The type of use is derived from the relevant Certificate of License.

License Type Description

Single License The software can be used on any single computer desired for an unlimited amount of time.

Floating License The software can be used on a computer network ("remote use") for an unlimited amount of time.

Trial License The software can be used subject to the following restrictions:

• A period of validity of up to a maximum of 14 days,

• A total number of operating days after the day of first use,

• A use for tests and validation (exemption from liability).

Upgrade License An upgrade may require a specific system state:

• An upgrade license can be used to convert an "Old"Version x to a Version >x+... license.

• An upgrade may be necessary due to an increase in the volume of data being handled in the given system.

2.1.2 Installing the Automation License Manager

The Automation License Manager is installed by means of an MSI setup process. The installation software for the Automation License Manager is included on the PRODAVE MPI/IE V6.2 product CD

You can install the Automation License Manager at the same time you install PRODAVE MPI/IE V6.2 or at a later time.

Notes

• For detailed information on how to install the Automation License Manager, please refer to the current "Readme.rtf" file.

• The online help for the Automation License Manager contains all the information you need on the function and handling of license keys.

Page 14: Manual Mpi Ie

Installation

PRODAVE MPI/IE V6.1 14 A5E03681152-01

Subsequent Installation of License Keys

If you start the PRODAVE MPI/IE V6.2 software and no license keys are in place, you will receive a message to that effect.

Notes

• You can use PRODAVE MPI/IE V6.2 without a license key to familiarize yourself with the user interface and functions.

• However, a license is required and necessary for full, unrestricted use in accordance with the license agreement.

• If you have not installed the license key, you will be prompted to do so at regular intervals.

You can subsequently install license keys in the following ways:

• Install license keys from diskettes

• Install license keys downloaded from the Internet. In this case, the license keys must be ordered first.

• Use floating license keys available in a network

For detailed information on installing license keys, refer to the online help for the Automation License Manager. To access this help context-sensitively, press F1 or select the Help > Help on License Manager menu command.

Notes

• In Windows XP/Vista32/7, license keys will only be operational if they are installed on a local hard disk and have write-access status.

• Floating licenses can also be used within a network ("remote" use).

2.1.3 Guidelines for Handling License Keys

! Caution

Please note the information on handling license keys that is available in the online help on the Automation License Manager and also in the PRODAVE MPI/IE V6.2 Readme.wri file on the installation CD-ROM. If you do not follow these guidelines, the license keys may be irretrievably lost.

You can open the Automation License Manager Online Help context-sensitively by pressing F1, or by selecting the Help > Help on Automation License Manager command.

This help section contains all the information you need on the function and handling of license keys.

Page 15: Manual Mpi Ie

Installation

PRODAVE MPI/IE V6.1 A5E03681152-01 15

2.2 Installing PRODAVE MPI/IE V6.2 PRODAVE MPI/IE V6.2 contains a Setup program that performs an automatic installation.On-screen input requests take you through the entire installation procedure step-by-step. Execute Setup using the standard Windows XP/Vista32/7 software installation procedure.

The major stages in the installation are:

• Copying the data to your programming device

• Configuration of communication drivers,

• Installing the license keys (if desired).

Installation Requirements

• Operating system Microsoft Windows XP, Windows Vista32, Windows 7.

• Basic hardware: Programming device or PC with:

- Pentium Processor (for Microsoft Windows XP, P333, for Windows Vista32, x32 processor with 1GHz), for Windows 7 processor with 1.6 GHz.

- RAM Memory extension: for Windows XP 512MB, for Windows Vista32 1024MB, for Windows 7 2048MB.

- Color monitor, keyboard and mouse, all of which are supported by Microsoft Windows.

A programming device (PG) is a PC with a special compact design for industrial use. It is fully equipped for programming SIMATIC PLCs.

• Hard disk space: Refer to the "README.RTF" file for information on required hard disk space.

• MPI interface optional): An MPI interface is only required to interconnect the PG/PC and the PLC if you want to use it for communication with the PLC under PRODAVE MPI/IE V6.2. In this case you require:

- A PC adapter and a zero modem cable (RS232), which are connected to the communications interface of your device, or

- An MPI module (for example, CP 5611) that is installed in your device.

PGs are supplied with a pre-installed MPI interface.

Notes Refer to the information on PRODAVE MPI/IE V6.2 . in the "README.RTF" file

You can find the Readme file in the start menu:

XP: Start > SIMATIC > Information > English

Vista/7: Start > Siemens Automation > SIMATIC > Product Notes > English

Page 16: Manual Mpi Ie

Installation

PRODAVE MPI/IE V6.1 16 A5E03681152-01

2.2.1 Installation Procedure

Preparations

The operating system must be started before you can start your software installation.

• You do not require an external storage medium if the installable PRODAVE MPI/IE V6.2 software is already stored on the hard disk of the PG.

• To run Setup from CD-ROM, place the CD-ROM into the CD-ROM drive of your PC.

Starting the Installation Program

To install the software, proceed as follows:

1. Insert the CD-ROM and double click on the file "SETUP.EXE".

2. Follow the on-screen step-by-step instructions of the installation program.

The program guides you through all steps of the installation. You can go to the next step or return to the previous step.

During installation, the dialog boxes prompt you to make your choice from the displayed options. The following notes will help you to quickly and easily find the right answers.

Selecting the Installation Options

You have three options:

• PRODAVE MPI 5.6: all the functions of version 5.6. Please check the current product information for the hard disk space required.

• PRODAVE MPI/IE V6.2: all the functions of version V6.2. Please check the current product information for the hard disk space required.

• PRODAVE MPI 5.6 and PRODAVE MPI/IE V6.2: all the functions of versions 5.6 and V6.2. Please check the current product information for the hard disk space required.

Page 17: Manual Mpi Ie

Installation

PRODAVE MPI/IE V6.1 A5E03681152-01 17

Installing License Keys

During setup, the program checks to see whether a corresponding license key is installed on the hard disk. If no valid license key is found, a message stating that the software can be used only with a license key is displayed. If you want, you can install the license key immediately or continue setup and then install the key later. If you want to install the license key now, insert the authorization data medium when prompted to do so.

PG/PC Interface Settings

If no SIMATIC product has been installed yet, a dialog box is displayed during installation where you can assign parameters to the programming device/PC interface. You will find more information on it in "Setting the PG/PC Interface."

Setup errors

Setup may be aborted due to the following errors:

• If an initialization error occurs immediately after the start of setup, it is more than likely setup was not started under Windows.

• Insufficient hard disk space: Minimum free hard disk space required for a standard software installation is 50 Mbytes, regardless of the scope of your installation.

• Bad CD-ROM: If the CD is faulty, please contact your local Siemens representative.

• Operator error: Restart setup and follow the instructions carefully.

After the Installation has been Completed…

An on-screen message reports the successful installation.

If any changes were made to system files during the installation, you are prompted to restart Windows. After restarting (warm start) you can use PRODAVE MPI/IE V6.2.

Several entries in the start menu, a directory in the "Program Files" folder and a current PRODAVE DLL in the Windows system directory are available after a successful installation.

Page 18: Manual Mpi Ie

Installation

PRODAVE MPI/IE V6.1 18 A5E03681152-01

2.2.2 Setting the PG/PC Interface

You configure the communication between the PG/PC and the PLC with the settings entered here. If no SIMATIC product has been installed yet, a dialog box is displayed during installation for setting the PG/PC interface. You can also open this dialog box after installation, by calling the program "Setting PG/PC Interface" in the control panel. This enables you to modify the interface parameters at a later time, independently of the installation.

When working with MS Windows 7 you therefor need the classical view of the control panel.

Basic Procedure

To operate an interface, you will require the following:

• Configurations in the operating system

• A suitable interface configuration

If you are using a PC with an MPI card or communications processors (CP), you should check the interrupt and address assignments in the Windows "Control Panel" to ensure that there are no interrupt conflicts and that no address areas overlap.

As of Windows 2000, the ISA component MPI-ISA card is no longer supported and therefore no longer offered for installation.

In order to make it easier to assign parameters to the programming device/PC interface, a dialog box will display a selection list of default basic parameter sets (interface configurations).

Assigning Parameters to the PG/PC Interface

Procedure (details to be found in the Online Help):

Double-click on "Setting PG/PC Interface" in the "Control Panel" of Windows.

1. Set the "Access Point of Application" to "S7ONLINE."

2. In the list "Interface parameter set used", select the required interface parameter set. If the required interface parameter set is not displayed, you must first install a module or protocol via the "Select" button. The interface parameter set is then generated automatically. On plug-and-play systems, you cannot install plug and play CPs manually (CP 5611 and CP 5512). They are integrated automatically in "Setting PG/PC Interface" after you have installed the hardware in your PG/PC.

- If you select an interface with automatic bus parameter recognition (e. g. CP 5611 (Auto)), then you can connect the PG and/or the PC to MPI and/or PROFIBUS without having to set bus parameters. If the transmission rate is < 187.5 Kbps, there may be a delay of up to one minute while the bus parameters are read. Requirement for automatic recognition: Masters who broadcast bus parameters cyclically are connected to the bus. All new MPI components

Page 19: Manual Mpi Ie

Installation

PRODAVE MPI/IE V6.1 A5E03681152-01 19

do this; for PROFIBUS subnets the cyclic broadcast of bus parameters must be enabled (default PROFIBUS network setting).

- If you select an interface which does not automatically recognize the bus parameters, you can display the properties and adapt them to match the subnet.

Changes will also be necessary if conflicts with other settings arise (for example, interrupt or address assignments). In this case, make the appropriate changes with the hardware recognition and Control Panel in Windows (see below).

! Caution

Do not remove any "TCP/IP" parameters from your interface configuration.

This could cause malfunctioning of other applications.

Checking the Interrupt and Address Assignments

If you use a PC with an MPI card, you should always check whether the default interrupt and the default address area are free and, if necessary select a free interrupt and/or address area.

Windows XP

In Windows XP you can

• display the resources under Start > All Programs > Accessories > System > System Programs > System Information > Hardware Resources.

• modify the resources under Control Panel > My Computer > Properties > Device Manager > SIMATIC NET > CP-Name > Properties > Change Resources.

Windows Vista32

Under Windows Vista32 you can

• display the resources under START > All Programs > Accessories > System Tools > System Information > Hardware Resources.

• modify the resources under Control Panel > Device Manager > SIMATIC NET > CP Name > Properties > Resources.

Windows 7

Under Windows 7 you can

• display the resources under START > All Programs > Accessories > System Tools > System Information.

• modify the resources under Control Panel > My Computer > Properties > Device Manager > SIMATIC NET > CP-Name > Properties > Change Resources.

Page 20: Manual Mpi Ie

Installation

PRODAVE MPI/IE V6.1 20 A5E03681152-01

2.2.3 Installing V6.2 over V6.x

If you install PRODAVE MPI/IE V6.2 over an existing PRODAVE MPI/IE V6.x, the file Prodave6.dll is replaced in the Windows directory. The directory "v6.x" in the Prodave directory persists with all source code examples and the old dll file V6.x. PRODAVE MPI/IE V6.2 is installed parallel to the v6.x directory in the directory "V6.2".

2.3 Uninstalling PRODAVE MPI/IE V6.2

2.3.1 Uninstalling PRODAVE MPI/IE V6.2

Use the standard Windows method to uninstall PRODAVE MPI/IE V6.2:

1. Open the "Control Panel" in Windows, then double-click "Software" or "Program" or similar to open the software setup dialog box.

2. Select the PRODAVE MPI/IE V6.2 entry in the displayed list of installed software. Click the button to "Remove" the software.

3. If the "Remove free file" dialog box appears, click "No" if you are uncertain.

Page 21: Manual Mpi Ie

PRODAVE MPI/IE V6.1 A5E03681152-01 21

3 Functions in PRODAVE MPI/IE V6.2

The following table shows a list of all the functions:

Version PRODAVE MPI/IE V6.2

Description

Library PRODAVE6.DLL

Header PRODAVE6.H

Basic Functions

LoadConnection_ex6 x MPI/Profibus, ISO or TCP/IP Protocol

UnloadConnection_ex6 x MPI/Profibus, ISO or TCP/IP Protocol

SetActiveConnection_ex6 x MPI/Profibus, ISO or TCP/IP Protocol

SetPassword_ex6 x Sets the password for a connection

UnSetPassword_ex6 x Resets the password

Functions for Data Communication Traffic to the S7 300/400

as_info_ex6 x Reads different diagnostic data

as_zustand_ex6 x Reads the AS state (RUN or STOP)

db_buch_ex6 x Reads in a list of data blocks

db_read_ex6 x Reads data from a data block

db_write_ex6 x Writes data to a data block

bst_read_ex6 x Reads out the"Advanced" block code

bst_read_diag_ex6 x "Advanced" block lists/header information

bst_read_stat_ex6 x "Advanced" block lists/header information

read_diag_buf_ex6 x Reads out the "Advanced" diagnostic buffer

field_read_ex6 x Reads a number of data

field_write_ex6 x Writes a number of data

szl_read_ex6 x Reads the SSLs from the AS

get_pb_lifelist x Provides a LifeList of the connected MPI/Profibus subnet

get_ie_lifelist x Provides a LifeList of the connected Ethernet subnet

Page 22: Manual Mpi Ie

Functions in PRODAVE MPI/IE V6.2

PRODAVE MPI/IE V6.1 22 A5E03681152-01

mb_setbit_ex6 x Sets a bit

mb_bittest_ex6 x Checks a bit in a memory byte

Functions for Data Communication Traffic to the S7 200

as200_as_info_ex6 x Reads different diagnostic data

as200_as_zustand_ex6 x Reads the AS state (RUN or STOP)

as200_field_read_ex6 x Reads a number of data

as200_field_write_ex6 x Writes a number of data

as200_mb_setbit_ex6 x Sets a bit

as200_mb_bittest_ex6 x Checks a bit in a memory byte

Convenience Functions

GetErrorMessage_ex6 x Provides the error text for an error number

kg_2_float_ex6 x Converts an S5 floating point value to float

float_2_kg_ex6 x Converts float to an S5 floating point value

gp_2_float_ex6 x Converts an S7 floating point value to float

float_2_gp_ex6 x Converts float to an S7 floating point value

testbit_ex6 x

byte_2_bool_ex6 x Converts a byte to eight boolean values

bool_2_byte_ex6 x Converts eight boolean values to a byte

kf_2_integer_ex6 x Swaps the high and low bytes of a 16 bit value

kf_2_long_ex6 x extended by double words

swab_buffer_ex6 x Swaps the high and low bytes of a 32 bit value

copy_buffer_ex6 x Swaps the high and low bytes of a buffer

ushort_2_bcd_ex6 x

bcd_2_ushort_ex6 x

ulong_2_bcd_ex6 x

bcd_2_ulong_ex6 x

GetLoadedConnections_ex6 x Returns a list of all open and closed connections

Page 23: Manual Mpi Ie

Functions in PRODAVE MPI/IE V6.2

PRODAVE MPI/IE V6.1 A5E03681152-01 23

GetPduSize_ex6 x Returns the maximum PDU size for communication with the connected CPU

TeleService Functions

ts_dial_ex6 x

ts_hang_up_dial_ex6 x

ts_set_ringindicator_ex6 x

ts_read_info_ex6 x

ts_hang_up_ring_ex6 x

ts_get_modem_name_ex6 x

Functions

All the functions listed are described from the PRODAVE MPI/IE V6.2 user view. Nevertheless, you must also add the WINAPI call convention / load tool to each function.

int WINAPI load_tool (char chConNo, …).

The old PRODAVE MPI 5.6 Libraries (W95_S7.DLL, KOMFORT.DLL) and the new PRODAVE MPI/IE V6.2 Library (PRODAVE6.LIB) can be used parallel in a user program.

There should be no problems when using programs created for PRODAVE MPI/IE V6.0 with PRODAVE MPI/IE V6.2.

Parallel operation of the older versions V6.x and V6.2 is not supported.

You can continue to use old Prodave V5.6 programs. It is not, however, possible to interlace the two versions, i.e. it is not possible to create a connection to the AS with an old function and then to read data with a new function and vice versa. The connection and the reading or writing of the data must take place homogeneously, with the same Prodave Version.

Page 24: Manual Mpi Ie

Functions in PRODAVE MPI/IE V6.2

PRODAVE MPI/IE V6.1 24 A5E03681152-01

3.1 Basic Functions

3.1.1 LoadConnection_ex6

The basic LoadConnection_ex6 function initializes the adapter, checks if the driver is loaded, initializes the addresses that have been assigned parameters and activates the selected interface.

LoadConnection_ex6 is used to set up a transport connection via MPI/PB- or IP addresses (TCP/IP protocol)

int LoadConnection_ex6 (int ConNr, char* pAccessPoint, int ConTableLen, CON_TABLE_TYPE * pConTable);

Parameters

ConNr

[in] Number of the connection (max. 64 connections).

pAccessPoint

[in] access point (zero-terminated) of the driver used, e.g. "S7ONLINE" for the MPI driver or 0 (default).

ConTableLen

[in] length of the connection structure provided by the user in bytes

pConTable

[in] pointer to address structure of the user

#pragma pack(1)

typedef union {

unsigned char Mpi; // MPI/PB station address (2)

unsigned char Ip[4]; // IP address (192.168.0.1)

unsigned char Mac[6]; // MAC address (08-00-06-01-AA-BB)

} CON_ADR_TYPE;

typedef struct {

CON_ADR_TYPE Adr; // connection address

unsigned char AdrType; // Type of address: MPI/PB (1), IP (2), MAC (3)

unsigned char SlotNr; // Slot number

unsigned char RackNr; // Rack number

} CON_TABLE_TYPE;

#pragma pack(1)

Page 25: Manual Mpi Ie

Functions in PRODAVE MPI/IE V6.2

PRODAVE MPI/IE V6.1 A5E03681152-01 25

Return Values

If there were no errors, the function supplies 0 as the return value.

If an error occurs, the error number is returned; this can be evaluated in accordance with the error table (see GetErrorMessage_ex6).

After eliminating the cause of the error LoadConnection_ex6 has to be executed again in order to create a connection to the AS.

Call example

A new entry in the connection table is prepared for each connection.

int RetValue = 0;

unsigned short ConNr= 0; //First connection (0 ... 63)

char AccessPoint[] = {"S7ONLINE"}; //Default access point S7ONLINE

CON_TABLE_TYPE ConTable[MAX_CONNECTION+1] = {0};

//Connection table

CON_TABLE_TYPE * pConTable = &ConTable[ConNr];

//Pointer on connection structure

unsigned short ConTableLen = sizeof(CON_TABLE_TYPE);

//Length of the connection structure

pConTable[ConNr].Adr.Ip[0] = 192; //Default IP address (192.168.0.1)

pConTable[ConNr].Adr.Ip[1] = 168;

pConTable[ConNr].Adr.Ip[2] = 0;

pConTable[ConNr].Adr.Ip[3] = 1;

pConTable[ConNr].AdrType = 2; //Address type = IP

pConTable[ConNr].SlotNr = 2 //Slot number = 2

pConTable[ConNr].RackNr = 0; //Rack number = 0

RetValue = LoadConnection_ex6 (ConNr, &AccessPoint, ConTableLen, pConTable);

Attention

Please observe that the number of real connections can differ from the 64 possible connections. This depends on the installed software packages and uesed communication media.

For example, for PROFIBUS connections only 28 connections to different CPUs can be established at the same time. Connection 29 is acknowlegded with an error:

0x4104: Online: No resources on the driver available.

If connection errors take place during operation, you must close the connection and reload it.

Page 26: Manual Mpi Ie

Functions in PRODAVE MPI/IE V6.2

PRODAVE MPI/IE V6.1 26 A5E03681152-01

Requirements

V6.2 Load_Connection_ex6

Windows: XP, Vista32, 7

Header: PRODAVE6.H

Library: PRODAVE6.DLL

See also:

UnloadConnection_ex6, SetActiveConnection_ex6, GetLoadedConnections_ex6

Page 27: Manual Mpi Ie

Functions in PRODAVE MPI/IE V6.2

PRODAVE MPI/IE V6.1 A5E03681152-01 27

3.1.2 UnloadConnection_ex6

The basic UnloadConnection_ex6 deinitialises the connections and the adapter and must be called up before exiting the application.

int UnloadConnection_ex6 (unsigned short ConNr);

Parameters

ConNr

[in] Number of the connection, which was assigned with LoadConnection_ex6.

Return Values

If there were no errors, the function supplies 0 as the return value or an error message is given which can be evaluated in accordance with the error table (see GetErrorMessage_ex6).

If the currently active connection has been closed, an (error) warning is returned.

Call example

Has to be called for each connection.

int RetValue = 0;

unsigned short ConNr = 0; //(0 ... 63)

RetVal = UnloadConnection_ex6 (ConNr);

Requirements

V6.2 Unload_Connection_ex6

Windows: XP, Vista32, 7

Header: PRODAVE6.H

Library: PRODAVE6.DLL

See also:

LoadConnection_ex6, SetActiveConnection_ex6, GetLoadedConnections_ex6

Page 28: Manual Mpi Ie

Functions in PRODAVE MPI/IE V6.2

PRODAVE MPI/IE V6.1 28 A5E03681152-01

3.1.3 SetActiveConnection_ex6

The basic SetActiveConnection_ex6 function activates the connection of the PG/PC over which the subsequent data exchange will take place.

int SetActiveConnection_ex6 (unsigned short ConNr);

Parameters

ConNr

[in] Number of a connection assigned with LoadConnection_ex6, which is to be activated.

Return Values

If there were no errors, the function supplies 0 as the return value, otherwise an error number is given which can be evaluated in accordance with the error table (see GetErrorMessage_ex6).

Call examples

int RetValue = 0;

unsigned short ConNr = 7; //(0 ... 63)

RetVal = SetActiveConnection_ex6(ConNr);

Requirements

V6.2 SetActiveConnection_ex6

Windows: XP, Vista32, 7

Header: PRODAVE6.H

Library: PRODAVE6.DLL

See also:

LoadConnection_ex6, UnloadConnection_ex6, GetLoadedConnections_ex6

Page 29: Manual Mpi Ie

Functions in PRODAVE MPI/IE V6.2

PRODAVE MPI/IE V6.1 A5E03681152-01 29

3.1.4 SetPassword_ex6

The SetPassword_ex6 function sets a password for a specific connection with a CPU.

int SetPassword_ex6 (unsigned short ConNr, unsigned char * Password);

Parameters

ConNr

[in] Connection number

Password

[in] Pointer to an UCHAR string, length 8

Return Values

If there were no errors, the function supplies 0 as the return value, otherwise an error number is given which can be evaluated in accordance with the error table (see GetErrorMessage_ex6).

Call examples

If a CPU was saved with a password, a password is required in order to perform changes to the state of the CPU. For this purpose the SetPassword_ex6 must be called after LoadConnection_ex6.

int RetValue = 0;

unsigned char passw[8]; //Passwort (muss exakt 8 Bytes lang sein)

unsigned short ConNr= 13; //Verbindungsnummer

RetValue = SetPassword_ex6 (ConNr, &passw[0]);

Requirements

V6.2 SetPassword_ex6

Windows: XP, Vista32, 7

Header: PRODAVE6.H

Library: PRODAVE6.DLL

See also:

As_zustand_ex6

Page 30: Manual Mpi Ie

Functions in PRODAVE MPI/IE V6.2

PRODAVE MPI/IE V6.1 30 A5E03681152-01

3.1.5 UnSetPassword_ex6

The UnSetPassword_ex6 function removes the password for a specific connection with a CPU.

int UnSetPassword_ex6 (unsigned short ConNr);

Parameters

ConNr

[in] Connection number

Return Values

If there were no errors, the function supplies 0 as the return value, otherwise an error number is given which can be evaluated in accordance with the error table (see GetErrorMessage_ex6).

Call examples

int RetValue = 0;

unsigned short ConNr= 13; //Connection number

RetValue = UnSetPassword_ex6 (ConNr);

Requirements

V6.2 UnSetPassword_ex6

Windows: XP, Vista32, 7

Header: PRODAVE6.H

Library: PRODAVE6.DLL

See also:

As_zustand_ex6

Page 31: Manual Mpi Ie

Functions in PRODAVE MPI/IE V6.2

PRODAVE MPI/IE V6.1 A5E03681152-01 31

3.1.6 as_info_ex6

The as_info_ex6 function reads out the release version of the AS software and the PG interface module as well as the MLFB number of the AS and files it as a zero-terminated ASCII string in the transfer buffer of the PG/PC.

int as_info_ex6 (unsigned long BufLen, AS_INFO_TYPE * pInfoBuffer, unsigned long * pDatLen);

Parameters

BufLen

[in] Length of the transfer buffer provided by the user in bytes.

pInfoBuffer

[out] pointer to transfer buffer with the AS information to be delivered:

typedef struct {

unsigned char Plcas[4]; // release version of the hardware

unsigned char Pgas[2]; // Release version of the hardware

char Mlfb[20]; // MLFB of the connected AS.

} AS_INFO_TYPE;

pDatLen

[out] pointer to the length if the data delivered in the buffer in bytes. If the "Transfer buffer provided too small for data" error occurs, the required size of the buffer is given here.

Return Values

If there were no errors, the function supplies 0 as the return value, otherwise an error number is given which can be evaluated in accordance with the error table (see GetErrorMessage_ex6).

Some AS cannot output the MLFB or the release version of the FW and HW. If this is the case, the MLFB if it had been possible to read it, is written in pInfoBuffer and a corresponding error message is issued.

Page 32: Manual Mpi Ie

Functions in PRODAVE MPI/IE V6.2

PRODAVE MPI/IE V6.1 32 A5E03681152-01

Call examples

int RetValue = 0;

AS_INFO_TYPE Buffer; //Create transfer buffer

AS_INFO_TYPE * pInfoBuffer = &Buffer; //Transfer buffer address

unsigned long BufLen = sizeof(Buffer); //Transfer buffer length

unsigned long DatLen; //Data length

RetValue = as_info_ex6 (BufLen, pInfoBuffer, &DatLen);

Requirements

V6.2 as_info_ex6

Windows: XP, Vista32, 7

Header: PRODAVE6.H

Library: PRODAVE6.DLL

See also:

as_zustand_ex6

Page 33: Manual Mpi Ie

Functions in PRODAVE MPI/IE V6.2

PRODAVE MPI/IE V6.1 A5E03681152-01 33

3.1.7 as_zustand_ex6

The as_zustand_ex6 function reads the operating state (OS) and files the dta in a storage area of the PG/PC.

int as_zustand_ex6 (unsigned char * pState);

Parameters

pState

[out] transfer buffer with the AS states to be supplied (length required 1 byte)

Return Values

If there were no errors, the function supplies 0 as the return value, otherwise an error number is given which can be evaluated in accordance with the error table (see GetErrorMessage_ex6).

Call examples

int RetValue = 0;

unsigned char State; //Transfer bytes for the AS state to be delivered

RetValue = as_zustand_ex6 (&State);

Page 34: Manual Mpi Ie

Functions in PRODAVE MPI/IE V6.2

PRODAVE MPI/IE V6.1 34 A5E03681152-01

"Current operating state (OS)" (values in Hex)

OM ID Meaning

00 Configuration in RUN (EVAL at R-KiR)

01 STOP (update)

02 STOP (memory reset)

03 STOP (self-initialization)

04 STOP (internal)

05 Startup (cold restart)

06 Startup (warm restart)

07 Startup (hot restart)

08 RUN (simple)

09 RUN (redundant)

0A HALT

Bx COUPLE

Cx UPDATE

0D Defect

Ex TEST

FX NOPOWER

Requirements

V6.2 as_zustand_ex6

Windows: XP, Vista32, 7

Header: PRODAVE6.H

Library: PRODAVE6.DLL

See also:

as_info_ex6

Page 35: Manual Mpi Ie

Functions in PRODAVE MPI/IE V6.2

PRODAVE MPI/IE V6.1 A5E03681152-01 35

3.1.8 db_buch_ex6

The db_buch_ex6 function displays which data blocks are available in the AS.

int db_buch_ex6 (unsigned long BufLen, unsigned short * pBuchBuffer, unsigned long * pDatLen);

Parameters

BufLen

[in] Length of the transfer buffer the user provided in bytes.

pBuchBuffer

[out] pointer on transfer buffer for the data blocks already read. The numbers of the data blocks present are written as word values (block number can be 9) in the buffer array.

pDatLen

[out] pointer to the length of the data delivered in the buffer in bytes. If the "Transfer buffer provided too small for data" error occurs, the required size of the buffer is given here.

If pDatLen has the value 0 no data blocks were found.

Return Values

If there were no errors, the function supplies 0 as the return value, otherwise an error number is given which can be evaluated in accordance with the error table (see GetErrorMessage_ex6).

Call examples

int RetValue = 0;

unsigned short Buffer[MAX_BUFFER]; //Transfer buffer

unsigned short * pBuchBuffer = &Buffer[0]; //Transfer buffer address

unsigned long BufLen = sizeof(Buffer); //Transfer buffer length

unsigned long DatLen; //Data length

RetValue = db_buch_ex6 (BufLen, pBuchBuffer, &DatLen);

Requirements

V6.2 db_buch_ex6

Windows: XP, Vista32, 7

Header: PRODAVE6.H

Library: PRODAVE6.DLL

Page 36: Manual Mpi Ie

Functions in PRODAVE MPI/IE V6.2

PRODAVE MPI/IE V6.1 36 A5E03681152-01

3.1.9 db_read_ex6

The db_read_ex6 reads out a number of bytes from a data block in AS and transfers them into a storage area (buffer) of the PG/PC.

It is possible to read out data byte-by-byte/word-by-word/double word-by-word (pAmount = 1) or block-by-block (pAmount > 1) with db_read_ex6.

int db_read_ex6 (unsigned short BlkNr, unsigned char DatType, unsigned short StartNr, unsigned long * pAmount, unsigned long BufLen, unsigned char * pReadBuffer, unsigned long * pDatLen)

Parameters

BlkNr

[in] Number of the data block

DatType

[in] Type of data to be read:

0x02 = BYTE, 0x04 = WORD, 0x06 = DWORD default: DatType = 0x02

StartNo

[in] Start number of the first byte / word / double word to be read

pAmount

[in] Amount of bytes / data words/ double words to be read

BufLen

[in] Length of the transfer buffer provided by the user in bytes.

pReadBuffer

[out] pointer on transfer buffer with the bytes / words / double words already read

pDatLen

[out] pointer to the length of the data delivered in the buffer in bytes.

Return Values

If there were no errors, the function supplies 0 as the return value, otherwise an error number is given which can be evaluated in accordance with the error table (see GetErrorMessage_ex6).

If the data block does not exist, this is shown by a return value = error number.

If more data are to be read than is present in the data block, the data actually read are written in pReadBuffer; the number (in bytes) of the data actually read is written in pDatLen and an error message "block limit exceeded" is returned.

Page 37: Manual Mpi Ie

Functions in PRODAVE MPI/IE V6.2

PRODAVE MPI/IE V6.1 A5E03681152-01 37

Call examples

int RetValue = 0;

unsigned short blkNr = 0; //Block number = 0

unsigned char DatType = 0x04; //Data type = word

unsigned short StartNr = 2; //First word to be read = 2

int Amount = 6; [in] Amount of words to be read = 6

Unsigned char buffer[MAX_BUFFER]; //Transfer buffer

unsigned char * pReadBuffer = &Buffer[0]; //Transfer buffer address

unsigned long BufLen = sizeof(Buffer); //Transfer buffer length

unsigned long DatLen; //Data length

RetValue = db_read_ex6 (BlkNr, DatType, StartNr, &Amount, BufLen, pReadBuffer, &DatLen);

unsigned short * wBuffer = (unsigned short *)Buffer;

//Word-by-word access

unsigned long * dwBuffer = (unsigned long *)Buffer;

//Double word-by-word access

Performance tip:

The function field_read_ex6 is most suitable for reading only a small amount of bytes (<< PDU size [240/480/960]-bytes).

Attention!

When accessing a data block the data words in the buffer are not filed according to Intel notation (little endian, low byte on low address, high byte on higher address), but in STEP5/STEP7 Notation (Motorola big endian, high byte on lower address, low byte on higher address). If the data are to be further processed, attention must be paid to this. The kf_2_integer_ex6, kf_2_long_ex6 and swab_buffer_ex6 functions are available for swapping bytes.

Requirements

V6.2 db_read_ex6

Windows: XP, Vista32, 7

Header: PRODAVE6.H

Library: PRODAVE6.DLL

See also:

db_write_ex6, kf_2_integer, kf_2_long_ex6, swab_buffer_ex6

Page 38: Manual Mpi Ie

Functions in PRODAVE MPI/IE V6.2

PRODAVE MPI/IE V6.1 38 A5E03681152-01

3.1.10 db_write_ex6

The db_write_ex6 writes a number of bytes that are located in a defined storage area (buffer) in the PG/PC into a data block in the AS.

It is possible to read out data byte-by-byte/word-by-word/double word-by-word (pAmount = 1) or block-by-block (pAmount > 1) with db_write_ex6.

int db_write_ex6 (unsigned short BlkNr, unsigned char DatType, unsigned short StartNr, unsigned long * pAmount, unsigned long BufLen, unsigned char * pWriteBuffer);

Parameters

BlkNr

[in] Number of the data block

DatType

[in] Type of data to be written:

0x02 = BYTE, 0x04 = WORD, 0x06 = DWORD default: DatType = 0x02

StartNr

[in] Start number of the first byte / word / double word to be written

pAmount

[in/out] The number of the bytes / words / double words to be written

BufLen

[in] Length of the transfer buffer provided by the user in bytes.

pWriteBuffer

[in] pointer on transfer buffer with the bytes / words / double words already written

Return Values

If there were no errors, the function supplies 0 as the return value, otherwise an error number is given which can be evaluated in accordance with the error table (see GetErrorMessage_ex6).

If the data block does not exist, this is shown by a return value = error number.

If more data are to be written than are present in the data block, the data actually read are written in pReadBuffer; the number (in bytes) of the data actually read is written in pAmount and an error message "Block limit exceeded" is returned.

If the error "Zuwenig Speicher vorhanden" is returned when writing a block you should call the "defrag_ex6" function in order to defragment the memory in the CPU.

Page 39: Manual Mpi Ie

Functions in PRODAVE MPI/IE V6.2

PRODAVE MPI/IE V6.1 A5E03681152-01 39

Call examples

int RetValue = 0;

unsigned short BlkNr = 0; //Block number = 0

unsigned char DatType = 0x04; //Data type = word

unsigned short StartNr = 2; //First word to be written = 2

int Amount = 6; //Number of words to be written = 6

unsigned char pWriteBuffer [MAX_BUFFER]; //Transfer buffer

unsigned char *pBuffer = &Buffer[0]; //Transfer buffer address

unsigned long BufLen = sizeof(Buffer); //Transfer buffer length

RetValue = db_write_ex6 (BlkNr, DatType, StartNr, &Amount, BufLen, pWriteBuffer);

unsigned short * wBuffer = (unsigned short *)Buffer;

// Word-by-word access

unsigned long * dwBuffer = (unsigned long *)Buffer;

// Double word-by-word access

Performance-Tipp:

The function field_write_ex6 is most suitable for writing only a small amount of bytes (<< PDU size [240/480/960]-bytes).

Requirements

V6.2 db_write_ex6

Windows: XP, Vista32, 7

Header: PRODAVE6.H

Library: PRODAVE6.DLL

See also:

db_read_ex6, kf_2_integer, kf_2_long_ex6, swab_buffer_ex6

Page 40: Manual Mpi Ie

Functions in PRODAVE MPI/IE V6.2

PRODAVE MPI/IE V6.1 40 A5E03681152-01

3.1.11 bst_read_diag_ex6

The bst_read_diag_ex6 function reads block lists and header information for the diagnosis.

The information is transferred as a structure containing the blocks that are present and the time stamp of each block making it possible to recognize changed blocks (online/offline comparison).

int bst_read_diag_ex6 (int BlkType, unsigned short StartNr, unsigned long * pAmount, unsigned long BufLen, BST_DIAG_TYPE * pDiagBuffer, unsigned long * pDatLen);

If all blocks are to be read, StartNr and pAmount must be set to = 0. After executing the function pAmount shows the number of blocks that have been read.

If the block with the start number (StartNr) is not found, the next higher block is used as the starting block.

Parameters

BlkType

[in] Type of block to be read:

BlkType: 0x08 = OB, 0x0a = DB, 0x0c = FC, 0x0e = FB default: BlkTyp = 0x0a

StartNr

[in] Start number of the first block to be read

Amount

[in/out] Amount of blocks to be read

BufLen

[in] Length of the transfer buffer provided by the user in bytes.

pDiagBuffer

[out] Pointer on transfer buffer for the data blocks already read.

typedef struct {

unsigned short BlkNr; // Block number

struct tm BlkTimestamp; // Time stamp of the block number

} BST_DIAG_TYPE;

pDatLen

[out] pointer to the length of the data delivered in the buffer in bytes. If the "Transfer buffer provided too small for data" error occurs, the required size of the buffer is given here.

Page 41: Manual Mpi Ie

Functions in PRODAVE MPI/IE V6.2

PRODAVE MPI/IE V6.1 A5E03681152-01 41

Return Values

If there were no errors, the function supplies 0 as the return value, otherwise an error number is given which can be evaluated in accordance with the error table (see GetErrorMessage_ex6).

If more data are to be read than are present in the AS, only the diagnosis information actually read is written in pDiagBuffer; the number of blocks read is written in pAmount and an error message "Block limit exceeded" is returned.

Call examples

int RetValue = 0;

int BlkType = 0x0a; //Block type = DB

unsigned short StartNr = 2; //First block to be read = 2

int Amount = 4; //Amount of blocks to be read = 4

BST_DIAG_TYPE Buffer[MAX_BLK]; //Transfer buffer array with block lists

BST_DIAG_TYPE *pDiagBuffer = &Buffer[0];

//Transfer buffer address

unsigned long BufLen = sizeof(Buffer); //Transfer buffer length

unsigned long DatLen; //Data length

RetValue = bst_read_diag_ex6 (BlkType, StartNr, &Amount, BufLen, pDiagBuffer, &DatLen);

Requirements

V6.2 bst_read_diag_ex6

Windows: XP, Vista32, 7

Header: PRODAVE6.H

Library: PRODAVE6.DLL

See also:

bst_read_stat_ex6, bst_read_ex6, read_diag_buf_ex6

Page 42: Manual Mpi Ie

Functions in PRODAVE MPI/IE V6.2

PRODAVE MPI/IE V6.1 42 A5E03681152-01

3.1.12 bst_read_stat_ex6

The bst_read_stat_ex6 function reads block lists and header information for the status displays (OBs/FCs/FBs/DBs).

int bst_read_stat_ex6 (int BlkType, unsigned long BufLen, BST_STAT_TYPE * pStatBuffer, unsigned long * pDatLen);

Parameters

BlkType

[in] Type of the block to be read

BlkType: 0x08 = OB, 0x0a = DB, 0x0c = FC, 0x0e = FB default: BlkTyp = 0x0a

BufLen

[in] Length of the transfer buffer provided by the user in bytes.

pStatBuffer

[out] Transfer buffer for the data already read.

typedef struct {

unsigned short BlkType; // Block type

unsigned short BlkNumber; // Block number

char BlkName[8]; // Block name

unsigned char BlkVersion; // Block version

unsigned long BlkLength; // Block length

struct tm BlkTimestamp1; // Time stamp 1 of the block number

struct tm BlkTimestamp2; // Time stamp 2 of the block number

unsigned char blkSecurity[4]; // Block password and protection level

} BST_STAT_TYPE;

pDatLen

[out] pointer to the length of the data delivered in the buffer in bytes. If the "Transfer buffer provided too small for data" error occurs, the required size of the buffer is given here.

Return Values

If there were no errors, the function supplies 0 as the return value, otherwise an error number is given which can be evaluated in accordance with the error table (see GetErrorMessage_ex6).

Page 43: Manual Mpi Ie

Functions in PRODAVE MPI/IE V6.2

PRODAVE MPI/IE V6.1 A5E03681152-01 43

Call examples

int RetValue = 0;

int BlkType = 0x0a; //Block type = DB

BST_STAT_TYPE Buffer[MAX_BLK]; //Transfer buffer for the data already read.

BST_STAT_TYPE * pStatBuffer = &Buffer; //Transfer buffer address

unsigned long BufLen = sizeof(Buffer); //Transfer buffer length

unsigned long DatLen; //Data length

RetValue = bst_read_stat_ex6 (BlkType, BufLen, pStatBuffer, &DatLen);

Requirements

V6.2 bst_read_stat_ex6

Windows: XP, Vista32, 7

Header: PRODAVE6.H

Library: PRODAVE6.DLL

See also:

bst_read_diag_ex6, bst_read_ex6, read_diag_buf_ex6

Page 44: Manual Mpi Ie

Functions in PRODAVE MPI/IE V6.2

PRODAVE MPI/IE V6.1 44 A5E03681152-01

3.1.13 bst_read_ex6

The bst_read_ex6 function reads a block into a buffer. "Code" blocks are read in completely (header and data), in the case of OBs and DBs only the header is read.

int bst_read_ex6 (int BlkType, unsigned short blkNr, unsigned long BufLen, unsigned char * pReadBuffer, unsigned long * pDatLen);

Parameter

BlkType

[in] Type of block to be read:

BlkType: 0x08 = OB, 0x0a = DB, 0x0c = FC, 0x0e = FB default: BlkTyp = 0x0a

BlkNr

[in] Block number of the block to be read

BufLen

[in] Length of the transfer buffer specified by the user in bytes

pReadBuffer

[out] Pointer on transfer buffer for read data

pDatLen

[out] Pointer on length of data delivered to the buffer in bytes. In event of error, "Transfer buffer supplied too small for data" is returned and required buffer size given.

Return Values

If there were no errors, the function supplies 0 as the return value, otherwise an error message is given which can be evaluated in accordance with the error table (see GetErrorMessage_ex6).

Know-how protected blocks cannot be read. In this case, an appropriate error code is returned.

Page 45: Manual Mpi Ie

Functions in PRODAVE MPI/IE V6.2

PRODAVE MPI/IE V6.1 A5E03681152-01 45

Block

Byte Name

0 Programming language

2 Block type 4 Block number

6 Attributes System version number

8 Block length (total)

10 PG block header

12 Length of section 1 (L1) MC5 length 14

16 Length of section 2 (L2) SSB length

18

20 Length of section 3 (L3) ADDINFO length

22

24 Length of dyn. local data

26

tm Timestamp 1

62

tm Timestamp 2

98 Block security

100

102 Producer name

110 Block family name

118 Block name

126 Version (release no.) reserved Header extension

128 Checksum

130 CPU type

134 Signature

136 reserved

138 Section 1 (MC5 code)

138+L1 Section 2 (SSB data)

138+L1+L2 Section 3 (ADDINFO data)

Page 46: Manual Mpi Ie

Functions in PRODAVE MPI/IE V6.2

PRODAVE MPI/IE V6.1 46 A5E03681152-01

Header of read block:

typedef struct {

unsigned char ProgLang; // Programing language

unsigned char BlkType; // Block type

unsigned short BlkNumber; // Block number

unsigned char Attribute[8]; // Attributes

unsigned char BlkVersion; // Block version

unsigned long BlkLength; // Block length

unsigned long Length[3]; // Data length

unsigned char DynLen; // Length of dyn. local data

struct tm BlkTimestamp1; // Time stamp 1 of the block number

struct tm BlkTimestamp2; // Time stamp 2 of the block number

unsigned char blkSecurity[4]; // Block level of protection

unsigned char ProducerName[8]; // Producer name

unsigned char BlkFamName[8]; // Block family name

unsigned char BlkName[8]; // Block name

unsigned char Version; // This is a user version and

has nothing to do with block version

.

unsigned short chckSum; // Check sum

unsigned long CPUType; // CPU type

unsigned short signature; // Signature

} BST_HEADER_TYPE;

Page 47: Manual Mpi Ie

Functions in PRODAVE MPI/IE V6.2

PRODAVE MPI/IE V6.1 A5E03681152-01 47

Call examples

int RetValue = 0;

int BlkType = 0x0a; //Block type = DB

unsigned short blkNr = 34; //Block number 34

BST_HEADER_TYPE Buffer[MAX_BUFFER];

//Transfer buffer read data

BST_HEADER_TYPE *pReadBuffer = &Buffer[0];

//Transfer buffer address

unsigned long BufLen = sizeof(Buffer); //Transfer buffer length

unsigned long DatLen; //Data length

RetValue = bst_read_ex6 (BlkType, blkNr, BufLen, &Buffer[0], &DatLen);

Requirements

V6.2 bst_read_ex6

Windows: XP, Vista32, 7

Header: PRODAVE6.H

Library: PRODAVE6.DLL

See also:

bst_read_diag_ 60, bst_read_stat_ex6, read_diag_buf_ex6

Page 48: Manual Mpi Ie

Functions in PRODAVE MPI/IE V6.2

PRODAVE MPI/IE V6.1 48 A5E03681152-01

3.1.14 read_diag_buf_ex6

The function read_diag_buf_ex6 reads data from the diagnostic buffer and SSLs in order to gain specific information about the status of the CPU.

int read_diag_buf_ex6 (unsigned long BufLen, unsigned char * pDiagBuffer, unsigned long * pDatLen);

Parameters

BufLen

[in] Length of the transfer buffer specified by the user in bytes

pDiagBuffer

[out] Pointer on transfer buffer for read data

pDatLen

[out] Pointer on length of data delivered to the buffer in bytes. In event of error, "Transfer buffer supplied too small for data" is returned and required buffer size given.

Return Values

If there were no errors, the function supplies 0 as the return value, otherwise an error message is given which can be evaluated in accordance with the error table (see GetErrorMessage_ex6).

Notes

The maximum deliverable number of available queries can be dependent on operating mode (product-specific definition). For example, a CPU can only return all information when in STOP operating mode.

In RUN operating mode, only a product-specific subset can be returned.

Example of a diagnosis entry

typedef struct {

unsigned short EventID; // EventID

unsigned char EventInfo[20]; // Information about event

unsigned char Timestamp[8]; // Time stamp of event

} DIAG_BUFFER_TYPE;

Page 49: Manual Mpi Ie

Functions in PRODAVE MPI/IE V6.2

PRODAVE MPI/IE V6.1 A5E03681152-01 49

Call examples

int RetValue = 0;

Unsigned char Buffer[MAX_BUFFER]; //Transfer buffer read data

(DIAG_BUFFER_TYPE) &Buffer[0]; //Place structure over buffer

unsigned long BufLen = sizeof(Buffer); //Length of transfer buffer

unsigned long DatLen; //Data length

RetValue = read_diag_buf_ex6 (BufLen, pDiagBuffer, &DatLen);

Requirements

V6.2 read_diag_buf_ex6

Windows: XP, Vista32, 7

Header: PRODAVE6.H

Library: PRODAVE6.DLL

See also:

bst_read_diag_ex6, bst_read_stat_ex6, bst_read_ex6

Page 50: Manual Mpi Ie

Functions in PRODAVE MPI/IE V6.2

PRODAVE MPI/IE V6.1 50 A5E03681152-01

3.1.15 field_read_ex6

The function field_read_ex6 reads a number of bytes or words from a data area of the AS and transfers them to a PG/PC transfer buffer.

int field_read_ex6 (char FieldType, unsigned short BlkNr, unsigned short StartNr, unsigned long Amount, unsigned long BufLen, unsigned char * pBuffer, unsigned long * pDatLen);

Parameters

FieldType

[in] Value types as ASCII characters: Data byte (d/D), input byte (e/E), output byte (a/A), memory byte (m/M), timer word (t/T), counter word (z/Z)

BlkNr

[in] Block number (only required for data blocks), default = 0

StartNr

[in] Start number of the first byte or word to be read

Amount

[in] Amount of bytes or words to be read

BufLen

[in] Length of the transfer buffer specified by the user in bytes

pBuffer

[out] Transfer buffer for the read bytes or words

pDatLen

[out] Pointer on length of data delivered to the buffer in bytes. In event of error, "Transfer buffer supplied too small for data" is returned and required buffer size given.

Return Values

If there were no errors, the function supplies 0 as the return value, otherwise an error message is given which can be evaluated in accordance with the error table (see GetErrorMessage_ex6).

Page 51: Manual Mpi Ie

Functions in PRODAVE MPI/IE V6.2

PRODAVE MPI/IE V6.1 A5E03681152-01 51

Call examples

int RetValue = 0;

char FieldType = ’D’ //Value type = data byte (D)

unsigned short blkNr = 0; //Block number = 0

unsigned short StartNr = 2; //First word to be read = 2

int Amount = 6; //Number of words to be read = 6

unsigned char Buffer[MAX_BUFFER]; //Transfer buffer

unsigned char *pBuffer = Buffer; //Transfer buffer address

unsigned long BufLen = sizeof(Buffer); //Length of transfer buffer

unsigned long DatLen; //Data length

RetValue = field_read_ex6 (FieldType, BlkNr, StartNr, Amount, BufLen, pBuffer, &DatLen);

unsigned short * wBuffer = (unsigned short *)Buffer;

//Word by word access

Requirements

V6.2 field_read_ex6

Windows: XP, Vista32, 7

Header: PRODAVE6.H

Library: PRODAVE6.DLL

See also:

field_write_ex6

Page 52: Manual Mpi Ie

Functions in PRODAVE MPI/IE V6.2

PRODAVE MPI/IE V6.1 52 A5E03681152-01

3.1.16 field_write_ex6

The function field_write_ex6 writes a number of bytes or words from a PG/PC transfer buffer into a data area of the AS.

int field_write_ex6 (char FieldType, unsigned short BlkNr, unsigned short StartNr, unsigned long Amount, unsigned long BufLen, unsigned char * pBuffer);

Parameters

FieldType

[in] Value types as ASCII characters: Data byte (d/D), input byte (e/E), output byte (a/A), memory byte (m/M), timer word (t/T), counter word (z/Z)

BlkNr

[in] Block number (only required for data blocks), default = 0

StartNr

[in] Start number of the first byte or word to be written.

Amount

[in] Amount of bytes or words to be written

BufLen

[in] Length of the transfer buffer specified by the user in bytes

pBuffer

[in] Pointer on transfer buffer for the bytes or words to be written

Return Values

If there were no errors, the function supplies 0 as the return value, otherwise an error message is given which can be evaluated in accordance with the error table (see GetErrorMessage_ex6).

Call examples

int RetValue = 0;

char FieldType = ’D’ //Value type = data byte (D)

unsigned short blkNr = 0; //Block number = 0

unsigned short StartNr = 2; //First word to be written = 2

int Amount = 6; //Number of words to be written = 6

unsigned char Buffer[MAX_BUFFER]; //Transfer buffer

unsigned char *pBuffer = &Buffer[0]; //Transfer buffer address

unsigned long BufLen = sizeof(Buffer); //Length of transfer buffer

RetValue = field_write_ex6 (FieldType, BlkNr, StartNr, Amount, BufLen, pBuffer);

unsigned short * wBuffer = (unsigned short *)Buffer;

//Word by word access

Page 53: Manual Mpi Ie

Functions in PRODAVE MPI/IE V6.2

PRODAVE MPI/IE V6.1 A5E03681152-01 53

Requirements

V6.2 field_write_ex6

Windows: XP, Vista32, 7

Header: PRODAVE6.H

Library: PRODAVE6.DLL

See also:

field_read_ex6

3.1.17 szl_read_ex6

The function szl_read_ex6 reads out the delivered SSL of an AS and transfers it to a storage area (buffer) of the PG/PC.

int szl_read_ex6 (unsigned short SzlId, unsigned short SzlIndex, unsigned long BufLen, unsigned char * pBuffer, unsigned long * pDatLen);

Parameters

SzlId

[in] Number of the SSL to be read

SzlIndex

[in] Index of the SSL to be read

BufLen

[in] Length of the transfer buffer specified by the user in bytes

pBuffer

[out] Pointer on transfer buffer for the read bytes

pDatLen

[out] Pointer on length of data delivered to the buffer in bytes.

Return Values

If there were no errors, the function supplies 0 as the return value, otherwise an error message is given which can be evaluated in accordance with the error table (see GetErrorMessage_ex6).

Page 54: Manual Mpi Ie

Functions in PRODAVE MPI/IE V6.2

PRODAVE MPI/IE V6.1 54 A5E03681152-01

Call examples

Int RetVal = 0;

USHORT szlId = 0;

USHORT szlIndex = 0;

ULONG DatLen = 0; //Length of returned data

unsigned char Buffer[MAX_BUFFER]; //Transfer buffer

unsigned char *pBuffer = &Buffer[0]; //Transfer buffer address

unsigned long BufLen = sizeof(Buffer); //Length of transfer buffer

RetVal = szl_read_ex6(szlId, szlIndex, BufLen, pBuffer, &DatLen);

Requirements

V6.2 szl_read_ex6

Windows: XP, Vista32, 7

Header: PRODAVE6.H

Library: PRODAVE6.DLL

Page 55: Manual Mpi Ie

Functions in PRODAVE MPI/IE V6.2

PRODAVE MPI/IE V6.1 A5E03681152-01 55

3.1.18 get_pb_lifelist_ex6

The function get_pb_lifelist_ex6 returns a list of devices with the device type/status (see StationState) which are in the same bus as the programming device.

int get_pb_lifelist_ex6 (unsigned long BufLen, unsigned char * pBuffer, unsigned long * pDatLen);

Parameters

BufLen

[in] Length of the transfer buffer specified by the user in bytes

pBuffer

[out] Pointer on transfer buffer for the read bytes (fixed size = 127 bytes)

pDatLen

[out] Pointer on length of data delivered to the buffer in bytes. In event of error, "Transfer buffer supplied too small for data" is returned and required buffer size given.

Return Values

If there were no errors, the function supplies 0 as the return value, otherwise an error message is given which can be evaluated in accordance with the error table (see GetErrorMessage_ex6).

Call examples

Int RetVal = 0;

ULONG DatLen = 0; //Length of returned data

unsigned char Buffer[127] = {0xff}; //Transfer buffer (max. 127 stations)

unsigned char *pBuffer = &Buffer[0]; //Transfer buffer address

unsigned long BufLen = sizeof(Buffer); //Length of transfer buffer

RetVal = get_pb_lifelist_ex6(BufLen, pBuffer, &DatLen);

Attention!

In order to execute the function successfully, you need a fully functional physical conntection to an MPI/Profibus net.

get_pb_lifelist_ex6 is a connectionless function, i.e. an opened connection is not necessary.

Page 56: Manual Mpi Ie

Functions in PRODAVE MPI/IE V6.2

PRODAVE MPI/IE V6.1 56 A5E03681152-01

StationState

0x00 = STATION_PASSIVE (Slave)

0x10 = STATION_NON_EXISTANT

0x20 = STATION_ACTIVE_READY (Master)

0x30 = STATION_ACTIVE (Master)

Requirements

V6.2 get_pb_lifelist_ex6

Windows: XP, Vista32, 7

Header: PRODAVE6.H

Library: PRODAVE6.DLL

Page 57: Manual Mpi Ie

Functions in PRODAVE MPI/IE V6.2

PRODAVE MPI/IE V6.1 A5E03681152-01 57

3.1.19 get_ie_lifelist_ex6

The function get_ie_lifelist_ex6 returns a list of the devices (with miscellaneous device properties) which are in the same subnet as the programming device.

int get_ie_lifelist_ex6 (unsigned long BufLen, unsigned char * pBuffer, unsigned long * pDatLen);

Parameters

BufLen

[in] Length of the transfer buffer specified by the user in bytes

pBuffer

[out] Pointer on transfer buffer for the bytes or words to be written

pDatLen

[out] Pointer on length of data delivered to the buffer in bytes. In event of error, "Transfer buffer supplied too small for data" is returned and required buffer size given.

Return Values

If there were no errors, the function supplies 0 as the return value, otherwise an error message is given which can be evaluated in accordance with the error table (see GetErrorMessage_ex6).

Call examples

Int RetVal = 0;

ULONG DatLen = 0; //Length of returned data

unsigned char Buffer[65536]; //Transfer buffer

unsigned char *pBuffer = &Buffer[0]; //Transfer buffer address

unsigned long BufLen = sizeof(Buffer); //Length of transfer buffer

RetVal = get_ie_lifelist_ex6(BufLen, pBuffer, &DatLen);

Attention!

• In order to execute the function successfully, you need a fully functional physical conntection to the Ethernet.

• get_ie_lifelist_ex6 is a connectionless function, i.e. an opened connection is not necessary.

• Some devices do not supply an IP address and/or their name.

Page 58: Manual Mpi Ie

Functions in PRODAVE MPI/IE V6.2

PRODAVE MPI/IE V6.1 58 A5E03681152-01

Structure of the buffer (station list)

Number of found stations

Station 1

Station 2

Station n

Station

Byte 0 Byte 1 MAC address

Byte 2 Byte 3

Byte 4 Byte 5

Byte 0 Byte 1 IP address

Byte 2 Byte 3

Length of type Res1 LengthType

Byte 0 Byte 1 TypeOfStation

… …

Byte 18 Byte 19

Length of name Res2 LengthName

Byte 0 Byte 1 StationName

… …

Byte 254 Res3

Requirements

V6.2 get_ie_lifelist_ex6

Windows: XP, Vista32, 7

Header: PRODAVE6.H

Library: PRODAVE6.DLL

Page 59: Manual Mpi Ie

Functions in PRODAVE MPI/IE V6.2

PRODAVE MPI/IE V6.1 A5E03681152-01 59

3.1.20 defrag_ex6

The function defrag_ex6 defragments and compresses all blocks in the CPU memory in order to establish coherent memory for new blocks.

int defrag_ex6 ();

Return Values

If there were no errors, the function supplies 0 as the return value, otherwise an error message is given which can be evaluated in accordance with the error table (see GetErrorMessage_ex6).

Call example

int RetVal = defrag_ex6();

Attention

You should only execute this function if the CPU is in STOP.

Requirements

V6.2 defrag_ex6

Windows: XP, Vista32, 7

Header: PRODAVE6.H

Library: PRODAVE6.DLL

Page 60: Manual Mpi Ie

Functions in PRODAVE MPI/IE V6.2

PRODAVE MPI/IE V6.1 60 A5E03681152-01

3.1.21 mb_setbit_ex6

The function mb_setbit_ex6 sets a bit memory in the AS to 1 or 0. It is not checked if the memory bit exists in the currently used AS.

int mb_setbit_ex6 (unsigned short MbNr, unsigned short BitNr, unsigned char Value);

Parameters

MbNr

[in] Number of the memory byte

BitNr

[in] Bit number in memory bytes

Value

[in] Value to be set (0/1)

Return Values

If there were no errors, the function supplies 0 as the return value, otherwise an error message is given which can be evaluated in accordance with the error table (see GetErrorMessage_ex6).

Call examples

int RetValue = 0 = 0;

unsigned short MbNr = 2; // Memory byte number 2

unsigned short BitNr = 4; // Bit number 4

unsigned char Value = 1; // Value to be set = 1

RetValue = mb_setbit_ex6 (MbNr, BitNr, Value);

Requirements

V6.2 mb_setbit_ex6

Windows: XP, Vista32, 7

Header: PRODAVE6.H

Library: PRODAVE6.DLL

See also:

mb_bittest_ex6

Page 61: Manual Mpi Ie

Functions in PRODAVE MPI/IE V6.2

PRODAVE MPI/IE V6.1 A5E03681152-01 61

3.1.22 mb_bittest_ex6

The function mb_bittest_ex6 checks a bit in a given memory byte for a given value and returns the state of the given bit into a transfer buffer.

int mb_bittest_ex6 (unsigned short MbNr, unsigned short BitNr, int * pValue);

Parameters

MbNr

[in] Number of the memory byte

BitNr

[in] Bit number in memory bytes

pValue

[out] Pointer on transfer byte with the tested bit value

Value == TRUE Bit set or 1

Value == FALSE Bit not set (or 0)

Return Values

If there were no errors, the function supplies 0 as the return value, otherwise an error message is given which can be evaluated in accordance with the error table (see GetErrorMessage_ex6).

Call examples

int RetValue = 0;

unsigned short MbNr = 2; //Memory byte number 2

unsigned short BitNr = 4; //Bit number 4

int Value; //Transfer byte for the bit value to be tested

RetValue = mb_bittest_ex6 (MbNr, BitNr, &Value);

Requirements

V6.2 mb_bittest_ex6

Windows: XP, Vista32, 7

Header: PRODAVE6.H

Library: PRODAVE6.DLL

See also:

mb_setbit_ex6

Page 62: Manual Mpi Ie

Functions in PRODAVE MPI/IE V6.2

PRODAVE MPI/IE V6.1 62 A5E03681152-01

3.2 Functions for Data Transfer to S7-200

3.2.1 as200_as_info_ex6

Die Function as200_as_info_ex6 reads the AS software release and the PG interface module, as well as the PLC type of the AS and sets these in ASCII string format in the PG/PC’s transfer buffer.

int as200_as_info_ex6 (unsigned long BufLen, AS200_INFO_TYPE * pBuffer, unsigned long * pDatLen);

Parameters

BufLen

[in] Length of the transfer buffer specified by the user in bytes

pBuffer

[out] Pointer on transfer buffer containing AS information to be delivered.

typedef struct {

unsigned char Firmware[4]; // FW release version

unsigned char ASIC[4]; ASIC release version

char Mlfb[16]; // MLFB of connected AS

} AS200_INFO_TYPE;

pDatLen

[out] Pointer on length of data delivered to the buffer in bytes. In event of error, "Transfer buffer supplied too small for data" is returned and required buffer size given.

Return Values

If there were no errors, the function supplies 0 as the return value, otherwise an error message is given which can be evaluated in accordance with the error table (see GetErrorMessage_ex6).

Call examples

int RetValue = 0;

AS200_INFO_TYPE Buffer; //Create transfer buffer

AS200_INFO_TYPE * pBuffer = &Buffer[0]; //Transfer buffer address

unsigned long BufLen = sizeof(Buffer); //Length of transfer buffer

unsigned long DatLen; //Data length

RetValue = as200_as_info_ex6 (BufLen, pBuffer, &DatLen);

Page 63: Manual Mpi Ie

Functions in PRODAVE MPI/IE V6.2

PRODAVE MPI/IE V6.1 A5E03681152-01 63

Requirements

V6.2 as200_as_info_ex6

Windows: XP, Vista32, 7

Header: PRODAVE6.H

Library: PRODAVE6.DLL

See also:

as200_as_zustand_ex6

Page 64: Manual Mpi Ie

Functions in PRODAVE MPI/IE V6.2

PRODAVE MPI/IE V6.1 64 A5E03681152-01

3.2.2 as200_as_zustand_ex6

Die Function as200_as_zustand_ex6 reads the AS state (RUN or STOP) from the AS and stores the data in a storage area on the PG/PC.

int as200_as_zustand_ex6 (unsigned char * pState);

Parameters

pState

[out] Transfer buffer with AS states to be delivered (required length 1 byte)

Return Values

If there were no errors, the function supplies 0 as the return value, otherwise an error message is given which can be evaluated in accordance with the error table (see GetErrorMessage_ex6).

Call examples

int RetValue = 0;

unsigned char State; //Transfer byte for the AS state

RetValue = as200_as_zustand_ex6 (&State);

Current Operating Mode (values in hex)

OM ID Meaning

00 STOP

01 RUN

Requirements

V6.2 as200_as_zustand_ex6

Windows: XP, Vista32, 7

Header: PRODAVE6.H

Library: PRODAVE6.DLL

See also:

as200_as_info_ex6

Page 65: Manual Mpi Ie

Functions in PRODAVE MPI/IE V6.2

PRODAVE MPI/IE V6.1 A5E03681152-01 65

3.2.3 as200_field_read_ex6

The function as200_field_read_ex6 reads a number of bytes or words from a data area of the AS and transfers them to a PG/PC transfer buffer.

int as200_field_read_ex6 (char FieldType, unsigned short BlkNr, unsigned short StartNr, unsigned long Amount, unsigned long BufLen, unsigned char * pBuffer, unsigned long * pDatLen);

Parameters

FieldType

[in] Value types as ASCII characters: Input byte (e/E), output byte (a/A), memory byte (m/M), special memory byte (s/S), variable storage byte (v/V), timer value (t/T), counter value (z/Z)

BlkNr

[in] Block number (only required for data blocks), default = 0

StartNr

[in] Start number of the first byte or word to be read

Amount

[in] Amount of bytes or words to be read

BufLen

[in] Length of the transfer buffer specified by the user in bytes

pBuffer

[out] Transfer buffer for the read bytes or words

pDatLen

[out] Pointer on length of data delivered to the buffer in bytes. In event of error, "Transfer buffer supplied too small for data" is returned and required buffer size given.

Return Values

If there were no errors, the function supplies 0 as the return value, otherwise an error message is given which can be evaluated in accordance with the error table (see GetErrorMessage_ex6).

Page 66: Manual Mpi Ie

Functions in PRODAVE MPI/IE V6.2

PRODAVE MPI/IE V6.1 66 A5E03681152-01

Call examples

int RetValue = 0;

char FieldType = 0x45 //Value type = input byte (E)

unsigned short blkNr = 0; //Block number = 0

unsigned short StartNr = 2; //First word to be read = 2

int Amount = 6; //Number of words to be read = 6

unsigned char Buffer[MAX_BUFFER]; //Transfer buffer

unsigned char *pBuffer = &Buffer[0]; //Transfer buffer address

unsigned long BufLen = sizeof(Buffer); //Length of transfer buffer

unsigned long DatLen; //Data length

RetValue = as200_field_read_ex6 (FieldType, BlkNr, StartNr, Amount, BufLen, pBuffer, &DatLen);

Requirements

V6.2 as200_field_read_ex6

Windows: XP, Vista32, 7

Header: PRODAVE6.H

Library: PRODAVE6.DLL

See also:

as200_field_write_ex6

Page 67: Manual Mpi Ie

Functions in PRODAVE MPI/IE V6.2

PRODAVE MPI/IE V6.1 A5E03681152-01 67

3.2.4 as200_field_write_ex6

The function as200_field_write_ex6 writes a number of bytes or words from a PG/PC transfer buffer into a data area of the AS.

int as200_field_write_ex6(char FieldType, unsigned short BlkNr, unsigned short StartNr, unsigned long Amount, unsigned long BufLen, unsigned char * pBuffer);

Parameters

FieldType

[in] Value types as ASCII characters: Input byte (e/E), output byte (a/A), memory byte (m/M), special memory byte (s/S), variable storage byte (v/V), timer value (t/T), counter value (z/Z)

BlkNr

[in] Block number (only required for data blocks), default = 0

StartNr

[in] Start number of the first byte or word to be written.

Amount

[in] Amount of bytes or words to be written

BufLen

[in] Length of the transfer buffer specified by the user in bytes

pBuffer

[in] Pointer on transfer buffer for the bytes or words to be written

Return Values

If there were no errors, the function supplies 0 as the return value, otherwise an error message is given which can be evaluated in accordance with the error table (see GetErrorMessage_ex6).

Page 68: Manual Mpi Ie

Functions in PRODAVE MPI/IE V6.2

PRODAVE MPI/IE V6.1 68 A5E03681152-01

Call examples

int RetValue = 0;

char FieldType = 0x45 //Value type = input byte (E)

unsigned short blkNr = 0; //Block number = 0

unsigned short StartNr = 2; //First word to be written = 2

int Amount = 6; //Number of words to be written = 6

unsigned char Buffer[MAX_BUFFER]; //Transfer buffer

unsigned char *pBuffer = Buffer; //Transfer buffer address

unsigned long BufLen = sizeof(Buffer); //Length of transfer buffer

RetValue = as200_field_write_ex6 (FieldType, BlkNr, StartNr, Amount, BufLen, pBuffer);

Requirements

V6.2 as200_field_write_ex6

Windows: XP, Vista32, 7

Header: PRODAVE6.H

Library: PRODAVE6.DLL

See also:

as200_field_read_ex6

Page 69: Manual Mpi Ie

Functions in PRODAVE MPI/IE V6.2

PRODAVE MPI/IE V6.1 A5E03681152-01 69

3.2.5 as200_mb_setbit_ex6

The function as200_mb_setbit_ex6 sets a bit memory in the AS at 1 or 0. It is not checked if the memory bit exists in the currently used AS.

int as200_mb_setbit_ex6 (unsigned short MbNr, unsigned short BitNr, unsigned char Value);

Parameter

MbNr

[in] Number of the memory byte

BitNr

[in] Bit number in memory bytes

Value

[in] Value to be set (0/1)

Return Values

If there were no errors, the function supplies 0 as the return value, otherwise an error message is given which can be evaluated in accordance with the error table (see GetErrorMessage_ex6).

Call examples

int RetValue = 0;

unsigned short MbNr = 2; //Memory byte number 2

unsigned short BitNr = 4; //Bit number 4

unsigned char Value = 1; //Value to be set = 1

RetValue = as200_mb_setbit_ex6 (MbNr, BitNr, Value);

Requirements

V6.2 as200_mb_setbit_ex6

Windows: XP, Vista32, 7

Header: PRODAVE6.H

Library: PRODAVE6.DLL

See also:

as200_mb_bittest_ex6

Page 70: Manual Mpi Ie

Functions in PRODAVE MPI/IE V6.2

PRODAVE MPI/IE V6.1 70 A5E03681152-01

3.2.6 as200_mb_bittest_ex6

The function as200_mb_bittest_ex6 checks a bit in a given memory byte and returns the state of the given bit into a transfer buffer.

int as200_mb_bittest_ex6 (unsigned short MbNr, unsigned short BitNr, int * pValue);

Parameters

MbNr

[in] Number of the memory byte

BitNr

[in] Bit number in memory bytes

pValue

[out] Pointer on transfer byte with the tested bit value

Value == TRUE Bit set or 1

Value == FALSE Bit is not set (or 0)

Return Values

If there were no errors, the function supplies 0 as the return value, otherwise an error message is given which can be evaluated in accordance with the error table (see GetErrorMessage_ex6).

Call examples

int RetValue = 0;

unsigned short MbNr = 2; //Memory byte number 2

unsigned short BitNr = 4; //Bit number 4

int Value; //Transfer byte for the bit value to be tested

RetValue = as200_mb_bittest_ex6 (MbNr, BitNr, &Value);

Page 71: Manual Mpi Ie

Functions in PRODAVE MPI/IE V6.2

PRODAVE MPI/IE V6.1 A5E03681152-01 71

Requirements

V6.2 as200_mb_bittest_ex6

Windows: XP, Vista32, 7

Header: PRODAVE6.H

Library: PRODAVE6.DLL

See also:

as200_mb_setbit_ex6

Page 72: Manual Mpi Ie

Functions in PRODAVE MPI/IE V6.2

PRODAVE MPI/IE V6.1 72 A5E03681152-01

3.3 Convenience Functions

3.3.1 GetErrorMessage_ex6

The function GetErrorMessage_ex6 returns the error text corresponding to an error number as a zero-terminated character string.

int GetErrorMessage_ex6 (int ErrorNr, unsigned long BufLen, unsigned char * pBuffer);

Parameters

ErrorNr

[in] Fehlernummer

BufLen

[in] Length of the transfer buffer specified by the user in bytes

pBuffer

[out] Pointer on transfer buffer with the error text

Return Values

If there were no errors, the function supplies 0 as the return value, otherwise the function returns one of the following values:

0x7070 File ERROR.DAT is not available or cannot be opened.

0x7071 Too many error texts in the file ERROR.DAT

0x7072 Error while reading the file ERROR.DAT

0x7073 No error text available for this error number.

Page 73: Manual Mpi Ie

Functions in PRODAVE MPI/IE V6.2

PRODAVE MPI/IE V6.1 A5E03681152-01 73

Call examples

int RetValue = 0;

int ErrorNr = 0x303; //Block boundary exceeded, correct the number

unsigned char Buffer[MAX_BUFFER]; //Transfer buffer for error text

unsigned long BufLen = sizeof(Buffer); //Buffer length

unsigned char *pBuffer = &Buffer[0]; //Transfer buffer address

RetValue = GetErrorMessage_ex6 (ErrorNr, BufLen, pBuffer);

ERROR.DAT should not contain more than 512 error texts. The error text may not exceed 200 characters.

When transferring the error number 0 the file name in "Buffer" may contain the error text file to be transferred (e.g. an English or German language error text file). If no valid file name is available or a NULL (ZERO) pointer is transferred, the ERROR.DAT file in the current directory will be read. For this reason, it should be ensured that the ERROR.DAT file exists and is placed in the same directory as the program.

The ERROR.DAT file will be read when function GetErrorMessage_ex6 is called for the first time and the text will be stored in a field.

It is recommended to call function GetErrorMessage_ex6 with error_no = 0 shortly after the program begins in order to load the ERROR.DAT file. This ensures that execution times for subsequent calls to the function are more or less constant.

Structure of the error text file

[Error number as ASCII Hex]: [Error text]

Page 74: Manual Mpi Ie

Functions in PRODAVE MPI/IE V6.2

PRODAVE MPI/IE V6.1 74 A5E03681152-01

Example for error texts in ERROR.DAT:

0x00E1: Too many open channels

0x00E9: sin_serv.exe not started

0x00CE: Module not found

0x00CF: Driver not loaded

0x00CA: No resources available

0x00F1: No global DOS memory available

0x0101: Connection not established / assigned parameters

0x010a: Negative acknowledgement received / timeout error

0x010c: File does not exist or is blocked

0x0201: Interface given is incorrect

0x0202: Maximum number of interfaces exceeded

0x0203: Toolbox already installed

0x0204: Toolbox already installed with other connections

0x0205: Toolbox not installed

0x0206: Handle cannot be set

0x0207: Data segment cannot be blocked

...

...

0xFFFE: unknown error FFFE hex

0xFFFF Timeout error. Check interface

Requirements

V6.2 GetErrorMessage_ex6

Windows: XP, Vista32, 7

Header: PRODAVE6.H

Library: PRODAVE6.DLL

Page 75: Manual Mpi Ie

Functions in PRODAVE MPI/IE V6.2

PRODAVE MPI/IE V6.1 A5E03681152-01 75

3.3.2 kg_2_float_ex6

The function kg_2_float_ex6 converts an S5 floating point value into a float type value (IEEE format).

int kg_2_float_ex6 (unsigned long kg, float * pieee);

Parameters

kg

[in] S5 floating point value

pieee

[out] Counter on float value

Return Values

If there were no errors, the function supplies 0 as the return value, otherwise 1.

Call examples

int RetValue = 0;

unsigned long kg = S5_FLOAT_VALUE;

float ieee; //The IEEE floating point value will be delivered into ieee

RetValue = kg_2_float_ex6 (kg, &ieee);

Requirements

V6.2 kg_2_float_ex6

Windows: XP, Vista32, 7

Header: PRODAVE6.H

Library: PRODAVE6.DLL

See also:

float_2_kg_ex6

Page 76: Manual Mpi Ie

Functions in PRODAVE MPI/IE V6.2

PRODAVE MPI/IE V6.1 76 A5E03681152-01

3.3.3 float_2_kg_ex6

The function float_2_kg_ex6 converts a value of type float (IEEE format) into a S5 floating point value.

int float_2_kg_ex6 (float ieee, unsigned long * pkg);

Parameters

ieee

[in] Float value

pkg

[out] Pointer on S5 floating point value

Return Values

If there were no errors, the function supplies 0 as the return value, otherwise 1.

Call examples

int RetValue = 0;

float ieee = FLOAT_VALUE;

unsigned long kg; //The S5 floating point value will be delivered to kg

RetValue = float_2_kg_ex6 (ieee, &kg);

Requirements

V6.2 float_2_kg_ex6

Windows: XP, Vista32, 7

Header: PRODAVE6.H

Library: PRODAVE6.DLL

See also:

kg_2_float_ex6

Page 77: Manual Mpi Ie

Functions in PRODAVE MPI/IE V6.2

PRODAVE MPI/IE V6.1 A5E03681152-01 77

3.3.4 gp_2_float_ex6

The function gp_2_float_ex6 converts an S7 floating point value into a value of type float (IEEE format).

int gp_2_float_ex6 (unsigned long kg, float * pieee);

Parameters

gp

[in] S7 floating point value

pieee

[out] Counter on float value

Return Values

If there were no errors, the function supplies 0 as the return value, otherwise 1.

Call examples

unsigned long gp = S7_FLOAT_VALUE;

float ieee; //The IEEE floating point value will be delivered into ieee

gp_2_float_ex6 (gp, &ieee);

Requirements

V6.2 gp_2_float_ex6

Windows: XP, Vista32, 7

Header: PRODAVE6.H

Library: PRODAVE6.DLL

See also:

float_2_gp_ex6

Page 78: Manual Mpi Ie

Functions in PRODAVE MPI/IE V6.2

PRODAVE MPI/IE V6.1 78 A5E03681152-01

3.3.5 float_2_gp_ex6

The function float_2_gp_ex6 converts a value of type float (IEEE format) into a S7 floating point value.

int float_2_gp_ex6 (float ieee, unsigned long * pgp);

Parameters

ieee

[in] Float value

pgp

[out] Pointer on S7 floating point value

Return Values

If there were no errors, the function supplies 0 as the return value, otherwise 1.

Call examples

float ieee = FLOAT_VALUE;

unsigned long gp; //The S7 floating point value will be delivered to gp

float_2_gp_ex6 (ieee, &gp);

Requirements

V6.2 float_2_gp_ex6

Windows: XP, Vista32, 7

Header: PRODAVE6.H

Library: PRODAVE6.DLL

See also:

gp_2_float_ex6

Page 79: Manual Mpi Ie

Functions in PRODAVE MPI/IE V6.2

PRODAVE MPI/IE V6.1 A5E03681152-01 79

3.3.6 testbit_ex6

The function testbit_ex6 checks if a given bit is set in a byte variable The byte variable and bit number are transferred to the function by way of parameters.

int testbit_ex6 (char Value, int BitNr);

Parameters

Value

[in] Value of byte variable

BitNr

[in] Bit to be tested in byte variable

Return Values

Return value TRUE: Bit is set (or 1)

Return value FALSE: Bit is not set (or 0)

Call examples

none

Requirements

V6.2 testbit_ex6

Windows: XP, Vista32, 7

Header: PRODAVE6.H

Library: PRODAVE6.DLL

Page 80: Manual Mpi Ie

Functions in PRODAVE MPI/IE V6.2

PRODAVE MPI/IE V6.1 80 A5E03681152-01

3.3.7 byte_2_bool_ex6

The function byte_2_bool_ex6 converts a byte into 8 logical values (PC representation).

void byte_2_bool_ex6 (unsigned char Value, int * pBuffer);

Parameters

Value

[in] Byte value

pBuffer

[out] pointer on buffer with 8 converted logical values

Return Values

none

Call examples

The transferred pointer should point to an unsigned char field with the following structure:

Buffer[0] Buffer[1] Buffer[2] Buffer[3] Buffer[4] Buffer[5] Buffer[6] Buffer[7]

bit 0 bit 1 bit 2 bit 3 bit 4 bit 5 bit 6 bit 7

#define SIZE_BOOL_BYTE 8

int Buffer[SIZE_BOOL_BYTE]; //Buffer for 8 logical values

unsigned char Value = 1;

byte_2_bool_ex6 (Value, Buffer); //TRUE will be delivered in Buffer[0], FALSE in BUFFER[1]-[7].

Requirements

V6.2 byte_2_bool_ex6

Windows: XP, Vista32, 7

Header: PRODAVE6.H

Library: PRODAVE6.DLL

See also:

bool_2_byte_ex6

Page 81: Manual Mpi Ie

Functions in PRODAVE MPI/IE V6.2

PRODAVE MPI/IE V6.1 A5E03681152-01 81

3.3.8 bool_2_byte_ex6

The function bool_2_byte_ex6 converts 8 logical values (PC representation) into a byte.

unsigned char bool_2_byte_ex6 (int * pBuffer);

Parameter

pBuffer

[in] Pointer on buffer with 8 logical values

Return Values

Converted byte value

Call examples

The transferred pointer should point to an unsigned char field with the following structure:

Buffer[0] Buffer[1] Buffer[2] Buffer[3] Buffer[4] Buffer[5] Buffer[6] Buffer[7]

bit 0 bit 1 bit 2 bit 3 bit 4 bit 5 bit 6 bit 7

unsigned char RetValue;

#define SIZE_BOOL_BYTE 8

int Buffer[SIZE_BOOL_BYTE] = {0}; //Buffer for 8 logical values

Buffer[0] = TRUE ;

RetValue = bool_2_byte_ex6 (Buffer); //RetValue has a value of 1

Requirements

V6.2 bool_2_byte_ex6

Windows: XP, Vista32, 7

Header: PRODAVE6.H

Library: PRODAVE6.DLL

See also:

byte_2_bool_ex6

Page 82: Manual Mpi Ie

Functions in PRODAVE MPI/IE V6.2

PRODAVE MPI/IE V6.1 82 A5E03681152-01

3.3.9 kf_2_integer_ex6, kf_2_long_ex6

The functions swap the high and low bytes of a given value.

kf_2_integer_ex6 swaps the high byte with the low byte of a 16-bit value.

kf_2_long_ex6 puts the 4 bytes of a 32 bit value in reversed order.

unsigned short kf_2_integer_ex6 (unsigned short wValue);

unsigned long kf_2_long_ex6 (unsigned long dwValue);

Parameters

wValue

[in] 16-bit values

dwValue

[in] 32-bit values

Return Values

kf_integer_ex6 delivers a 16-bit value with swapped bytes.

kf_long_ex6 delivers a 32-bit value with swapped bytes.

Call examples

Example: (Double word)

0 1 2 3

…swap…

3 2 1 0

Requirements

V6.2 kf_2_integer_ex6, kf_2_long_ex6

Windows: XP, Vista32, 7

Header: PRODAVE6.H

Library: PRODAVE6.DLL

See also:

swab_buffer_ex6

Page 83: Manual Mpi Ie

Functions in PRODAVE MPI/IE V6.2

PRODAVE MPI/IE V6.1 A5E03681152-01 83

3.3.10 swab_buffer_ex6

The function swab_buffer_ex6 swaps the high and low bytes of words in a given buffer.

void swab_buffer_ex6 (unsigned char * pBuffer, unsigned long Amount);

Parameters

pBuffer

[in/out] Pointer on the buffer in which the bytes are to be swapped

Amount

[in] Number of bytes to be swapped (even number)

Return Values

none

Call examples

The standard C function void_swab(char * src, char * dest, int n) will be called internally.

a b …swap… b a

c d d c

x y y x

Requirements

V6.2 swab_buffer_ex6

Windows: XP, Vista32, 7

Header: PRODAVE6.H

Library: PRODAVE6.DLL

See also:

kf_2_integer_ex6, kf_2_long_ex6, copy_buffer_ex6

Page 84: Manual Mpi Ie

Functions in PRODAVE MPI/IE V6.2

PRODAVE MPI/IE V6.1 84 A5E03681152-01

3.3.11 copy_buffer_ex6

The function copy_buffer_ex6 copies a number of bytes from one buffer into another.

void copy_buffer_ex6 (unsigned char * pTargetBuffer, unsigned char * pSourceBuffer, unsigned long Amount);

Parameters

pTargetBuffer

[out] Pointer on the buffer in which the bytes are to be copied

pSourceBuffer

[in] Pointer on the buffer from which the bytes are to be fetched.

Amount

[in] Amount of bytes to be copied

Return Values

none

Call examples

The standard C function void *memcpy(char * dest, char * src, size_t count) will be called internally.

Requirements

V6.2 copy_buffer_ex6

Windows: XP, Vista32, 7

Header: PRODAVE6.H

Library: PRODAVE6.DLL

See also:

swab_buffer_ex6

Page 85: Manual Mpi Ie

Functions in PRODAVE MPI/IE V6.2

PRODAVE MPI/IE V6.1 A5E03681152-01 85

3.3.12 ushort_2_bcd_ex6, ulong_2_bcd_ex6

The functions are conversion routines that convert a number of binary values into BCD values.

ushort_2_bcd_ex6 converts 16-bit values (words).

ulong_2_bcd_ex6 converts 32-bit values (double words).

void ushort_2_bcd_ex6 (unsigned short * pwValues, unsigned long Amount, int InBytechange, int OutBytechange);

void ulong_2_bcd_ex6 (unsigned long * pdwValues, unsigned long Amount, int InBytechange, int OutBytechange);

Parameters

pwValues

[in] Pointer on 16-bit binary values

pdwValues

[in] Pointer on 32-bit binary values

Amount

[in] Amount of values

InBytechange

[in] TRUE or FALSE (for example, 01, 00 is then interpreted as 256 or as 1)

OutBytechange

[in] TRUE or FALSE

Return Values

After calling the function, pwValues points to 16-Bit BCD values, pdwValuese to 32-bit BCD values.

Call examples

The function can be used, for example, to set counters or provide time functions.

If the parameter 'InBytechange' is set (1) then the high and low bytes will be swapped before the conversion to BCD values. If the parameter ‘OutBytechange’ is set, the high and low bytes will be swapped after the conversion.

If neither of the ByteChange arguments is set, then no high-low conversion will take place.

The available value range for 16-bit BCD values is 0 to 999.

The available value range for 32-bit BCD values is 0 to 9 999 999.

Page 86: Manual Mpi Ie

Functions in PRODAVE MPI/IE V6.2

PRODAVE MPI/IE V6.1 86 A5E03681152-01

Requirements

V6.2 ushort_2_bcd_ex6, ulong_2_bcd_ex6

Windows: XP, Vista32, 7

Header: PRODAVE6.H

Library: PRODAVE6.DLL

See also:

bcd_2_ushort_ex6, bcd_2_ulong_ex6

Page 87: Manual Mpi Ie

Functions in PRODAVE MPI/IE V6.2

PRODAVE MPI/IE V6.1 A5E03681152-01 87

3.3.13 bcd_2_ushort_ex6, bcd_2_ulong_ex6

The functions are conversion routines that convert a number of BCD values into binary values.

bcd_2_ushort_ex6 converts 16-bit values (words).

bcd_2_ulong converts 32-bit values (double words).

void bcd_2_ushort_ex6 (unsigned short * pwValues, unsigned long Amount, int InBytechange, int OutBytechange);

void bcd_2_ulong_ex6 (unsigned long * pdwValues, unsigned long Amount, int InBytechange, int OutBytechange);

Parameters

pwValues

[in/out] Pointer on 16-bit BCD values

pdwValues

[in/out] Pointer on 32-bit BCD values

Amount

[in] Amount of values

InBytechange

[in] TRUE or FALSE

OutBytechange

[in] TRUE or FALSE

Return Values

After calling the function, pwValues points to 16-bit binary values, pdwValuese to 32-bit binary values.

Call examples

The function can be used, for example, to set counters or provide time functions.

If the parameter 'InBytechange' is set (1) then the high and low bytes will be swapped before the conversion to binary values. If the parameter ‘OutBytechange’ is set, the high and low bytes will be swapped after the conversion.

If neither of the ByteChange arguments is set, then no high-low conversion will take place.

The available value range for 16-bit BCD values is 0 to 999.

The available value range for 32-bit BCD values is 0 to 9 999 999.

Page 88: Manual Mpi Ie

Functions in PRODAVE MPI/IE V6.2

PRODAVE MPI/IE V6.1 88 A5E03681152-01

Requirements

V6.2 bcd_2_ushort_ex6, bcd_2_ulong_ex6

Windows: XP, Vista32, 7

Header: PRODAVE6.H

Library: PRODAVE6.DLL

See also:

ushort_2_bcd_ex6, ulong_2_bcd_ex6

Page 89: Manual Mpi Ie

Functions in PRODAVE MPI/IE V6.2

PRODAVE MPI/IE V6.1 A5E03681152-01 89

3.3.14 GetLoadedConnections_ex6

Fills an array with 64 Boolean values The user receives information as to which of the 64 connection numbers (ConNr) are already occupied and which connections are already installed.

void GetLoadedConnections_ex6(unsigned long BufLen, int *pBuffer)

Parameters

BufLen

[in] Length of the transfer buffer specified by the user in bytes

pBuffer

[out] Pointer on an array with Boolean values

Return Values

none

Call examples

none

Requirements

V6.2 GetLoadedConnections_ex6

Windows: XP, Vista32, 7

Header: PRODAVE6.H

Library: PRODAVE6.DLL

See also:

LoadConnection_ex6, UnloadConnection_ex6

Page 90: Manual Mpi Ie

Functions in PRODAVE MPI/IE V6.2

PRODAVE MPI/IE V6.1 90 A5E03681152-01

3.3.15 GetPduSize_ex6

Returns the maximum PDU size for communication with the connected CPU.

int GetPduSize_ex6(unsigned short ConNr)

Parameters

ConNr

[in] Number of the connection for which the PDU size is to be returned.

Return Values

If there were no errors, the function supplies the PDU size as the return value, otherwise 0.

Call Examples

none

Requirements

V6.2 GetPduSize_ex6

Windows: XP, Vista32, Windows7

Header: PRODAVE6.H

Library: PRODAVE6.DLL

Page 91: Manual Mpi Ie

Functions in PRODAVE MPI/IE V6.2

PRODAVE MPI/IE V6.1 A5E03681152-01 91

3.4 TeleService Functions

3.4.1 ts_dial_ex6

The function ts_dial_ex6 calls a remote station via modem and creates a connection to the TS adapter.

int ts_dial_ex6 (char * cModemName, char * cStandort, char * cTelNo, char * cUserName, char * cPassword, HANDLE WindowHandle, unsigned int Message, WPARAM wParam, char * Res1);

Parameters

cModemName

[in] Name of modem to be used, configurable in Control Panel / Phone and Modem Options / Dialing Rules.

cStandort

[in] Name of modem location, configurable in Control Panel / Phone and Modem Options / Dialing Rules.

cTelNo

[in] Telephone number to be called by connected modem.

cUserName

[in] The user name is entered here as set up in TS adapter's parameters.

cPassword

[in] The password is given here as set up in TS adapter’s parameters.

WindowHandle

[in] A window handle can be given here.

Message

[in] Message to be sent to window in the event of successful connection or expired timeout.

wParam

[in] Parameters for the message.

Res1

[in] Reserved for future expansions, must currently be preset to NULL (ZERO).

Page 92: Manual Mpi Ie

Functions in PRODAVE MPI/IE V6.2

PRODAVE MPI/IE V6.1 92 A5E03681152-01

Return Values

If there were no errors, the function supplies 0 as the return value, otherwise an error message which can be evaluated in accordance with the error table (see GetErrorMessage).

Note

When function ts_dial_ex6 is called asynchronously, no error number will be generated in the event of error. In this case, inform the user and allow him/her to decide whether the function should be called again or if more detailed error information is required. For detailed information, please use synchronous call.

Call examples

none

Requirements

V6.2 ts_dial_ex6

Windows: XP, Vista32, 7

Header: PRODAVE6.H

Library: PRODAVE6.DLL

Page 93: Manual Mpi Ie

Functions in PRODAVE MPI/IE V6.2

PRODAVE MPI/IE V6.1 A5E03681152-01 93

3.4.2 ts_hang_up_dial_ex6

The function ts_hang_up_dial_ex6 interrupts the current connection or a currently running asynchronous dial operation.

int ts_hang_up_dial_ex6 (void);

Parameters

none

Return Values

If there were no errors, the function supplies 0 as the return value, otherwise an error message which can be evaluated in accordance with the error table (see GetErrorMessage).

Call examples

none

Requirements

V6.2 ts_hang_up_dial_ex6

Windows: XP, Vista32, 7

Header: PRODAVE6.H

Library: PRODAVE6.DLL

Page 94: Manual Mpi Ie

Functions in PRODAVE MPI/IE V6.2

PRODAVE MPI/IE V6.1 94 A5E03681152-01

3.4.3 ts_set_ringindicator_ex6

The function ts_set_ringindicator_ex6 initializes the low-frequency system for call acceptance, connection set-up and announcement (ring indication).

int ts_set_ringindicator_ex6 (char * ModemName, char * NumberOfRings, HANDLE WindowHandle, unsigned int Message, WPARAM wParam, char * Res1);

Parameters

ModemName

[in] Name of modem to be used for purpose of ring indication, configurable in Control Panel / Modems.

NumberOfRings

[in] Number of rings until modem picks up.

WindowHandle

[in] A window handle can be given here.

Message

[in] Message to be sent to window in the event of successful connection or expired timeout.

wParam

[in] Parameters for the message.

Res1

[in] Reserved for future expansions, must currently be preset to NULL (ZERO).

Return Values

If there were no errors, the function supplies 0 as the return value, otherwise an error message which can be evaluated in accordance with the error table (see GetErrorMessage).

Call examples

none

Requirements

V6.2 ts_set_ringindicator_ex6

Windows: XP, Vista32, 7

Header: PRODAVE6.H

Library: PRODAVE6.DLL

Page 95: Manual Mpi Ie

Functions in PRODAVE MPI/IE V6.2

PRODAVE MPI/IE V6.1 A5E03681152-01 95

3.4.4 ts_read_info_ex6

The function ts_read_about_ex6 delivers information about the alarming station.

int ts_read_info_ex6 (void * IventId, unsigned char * MpiAdr);

Parameters

IventId

[in] Pointer on a 16-byte long field. Information about the alarming station is entered here.

MpiAdr

[in] Pointer on a byte. The MPI address of the alarm-triggering station is entered here.

Return Values

If there were no errors, the function supplies 0 as the return value, otherwise an error message which can be evaluated in accordance with the error table (see GetErrorMessage).

Call examples

none

Requirements

V6.2 ts_read_info_ex6

Windows: XP, Vista32, 7

Header: PRODAVE6.H

Library: PRODAVE6.DLL

Page 96: Manual Mpi Ie

Functions in PRODAVE MPI/IE V6.2

PRODAVE MPI/IE V6.1 96 A5E03681152-01

3.4.5 ts_hang_up_ring_ex6

The function ts_hang_up_ring_ex6 interrupts the connection made by the TS-Adapter.

int ts_hang_up_ring_ex6 (void);

Parameters

none

Return Values

If there were no errors, the function supplies 0 as the return value, otherwise an error message which can be evaluated in accordance with the error table (see GetErrorMessage).

Call examples

none

Requirements

V6.2 ts_hang_up_ring_ex6

Windows: XP, Vista32, 7

Header: PRODAVE6.H

Library: PRODAVE6.DLL

Page 97: Manual Mpi Ie

Functions in PRODAVE MPI/IE V6.2

PRODAVE MPI/IE V6.1 A5E03681152-01 97

3.4.6 ts_get_modem_name_ex6

The function ts_get_modem_name_ex6 delivers the names of all system recognized modems.

The function has to be called repeatedly for all modems until the return value 0x4502 is given. The ModemId must be incremented by one per call (start value = 0).

int ts_get_modem_name_ex6 (int ModemId, char * Buffer, int * BufferLen);

Parameters

ModemId

[in] Modem ID 0 ... n

Buffer

[out] Pointer on the buffer for modem names

BufferLen

[in/out] Pointer on the length of the buffer; contains the actual length of the string with the modem name after the call.

Attention!

BufferLen must be selected large enough for the expected modem name before the function is called.

Return Values

Attention!

RetVal == 0 A modem with the specified ModemId exists.

The buffer containts the modem name.

RetVal != 0x4502 No modem with the specified ModemId exists.

RetVal == 0x4502 No further modems exist.

If there were no errors, the function supplies 0 as the return value, otherwise an error message which can be evaluated in accordance with the error table (see GetErrorMessage).

Call examples

none

Page 98: Manual Mpi Ie

Functions in PRODAVE MPI/IE V6.2

PRODAVE MPI/IE V6.1 98 A5E03681152-01

Requirements

V6.2 ts_get_modem_name_ex6

Windows: XP, Vista32, 7

Header: PRODAVE6.H

Library: PRODAVE6.DLL

3.5 Data Structures

Prodave defines the following structures:

Name Size Explanation

TS_USERID: 16 bytes

CON_ADR_TYPE 6 bytes Address type (MPI/PB, IP, MAC)

CON_TABLE_TYPE 9 bytes Connection type with address information

AS_INFO_TYPE 26 bytes Information structure with MLFB and version information

AS200_INFO_TYPE 48 bytes Information structure with MLFB and version information

BST_DIAG_TYPE 40 bytes Structure with block number and time stamp

DIAG_BUFFER_TYPE 20 bytes Diagnostic buffer

BST_STAT_TYPE 96 bytes Structure with block informationen

BST_HEADER_TYPE 140 bytes Header of a block

IE_NODE 290 bytes Devicee information of an IE station

struct tm 36 bytes Structure by Microsoft (used only)

Page 99: Manual Mpi Ie

PRODAVE MPI/IE V6.1 A5E03681152-01 99

Glossary

Bit Memory (M)

A memory area in the system memory of a SIMATIC S7 CPU. This area can be accessed using write or read access (bit, byte, word, and double word). The bit memory area can be used by the user to store interim results.

Central Processing Unit (CPU)

The CPU is the central module in the programmable control system in which the user program is stored and processed. It consists of an operating system, processing unit, and communication interfaces.

Data Block (DB)

Data blocks are blocks which contain data and parameters with which the user program works. In contrast to all other types of blocks, they contain no logic instructions.

ERROR SEARCH Mode

This is an operating state of the standby CPU in an H system where the CPU executes a complete self-test. At the same time, the master CPU is in RUN mode.

Function (FC)

According to the International Electrotechnical Commission's IEC 1131-3 standard, functions are logic blocks without static data. A function allows you to pass parameters in the user program, which means they are suitable for programming complex functions that are required frequently, for example, calculations. Note: As there is no memory available, the calculated values must be processed immediately following the FC call.

Function Block (FB)

According to the International Electrotechnical Commission's IEC 1131-3 standard, function blocks are logic blocks that reference an instance data block, meaning they have static data. As function blocks have a 'memory' in the form of the associated instance data block, its parameters (outputs, for example) can be accessed at any time and any point in the user program.

Page 100: Manual Mpi Ie

Glossary

PRODAVE MPI/IE V6.1 100 A5E03681152-01

HOLD Mode

The HOLD state is reached from the RUN mode via a request from the programming device. Special test functions are possible in this mode.

Logic Block

In SIMATIC S7, a logic block is a block that contains part of the STEP 7 user program. The other type of block is a data block which contains only data. Logic blocks are: Organization blocks (OB), function blocks (FB), functions (FC), system function blocks (SFB) and system functions (SFC).

Multi Point Interface (MPI)

The multipoint interface is the programming device interface in SIMATIC S7/M7. It allows a number of programmable modules, text displays, and operator panels to be accessed from a central point.

The nodes on the MPI can communicate with each other.

Offline

When offline, no data link between the programming device and the programmable logic controller exists.

Online

When online, a data link between the programming device and the programmable logic controller exists.

Organization Block (OB)

Organization blocks form the interface between the S7 CPU operating system and the user program. The sequence in which the user program should be processed is laid down in the organization blocks.

PLC (AS)

A PLC is a programmable logic controller which consists of a central rack, a CPU, and other I/O modules.

Point-to-Point Interface (PPI)

For the Point-to-Point interface, the communication processor is the interface between a programmable logic controller and a communication partner.

Program Data Unit (PDU)

Describes the maximum size of a data package which can be recieved or sent by the programming device. Usual sizes: 240/480/960 bytes.

Page 101: Manual Mpi Ie

Glossary

PRODAVE MPI/IE V6.1 A5E03681152-01 101

Programming Device (PG)

Personal computer in special industry-suitable and compact form. A PG is completely equipped to configure SIMATIC automation systems.

RUN Mode

In the RUN state the user program is processed and the process image is updated cyclically. In addition, all digital outputs are enabled.

STARTUP Mode

The CPU goes through the STARTUP state during the transition from the STOP mode to the RUN mode. This mode can be set:

• By using the mode selector

• Following power-on

• By an operation on the programming device.

A distinction is made between the STARTUP types cold restart, warm restart, and hot restart.

STOP Mode

The following events place the CPU in the STOP state:

• Moving the mode selector to the STOP position

• An internal error in the CPU

• An operation on the programming device

All modules are switched to a safe state.

In S7: The user program is not processed in STOP mode. Certain programming functions and operator interface functions are, however, possible.

In M7: User programs can still be processed in STOP mode

System Data Block (SDB)

System data blocks are data areas in the CPU which contain the system settings and module parameters. The system data blocks are generated and modified by the STEP 7 Basic software.

System Function (SFC)

A system function (SFC) is a function integrated in the S7 CPU operating system which can be called like a function in the user program when required.

System Function Block (SFB)

A system function block (SFB) is a function block integrated in the S7 CPU operating system which can be called like a function block in the user program when required.

Page 102: Manual Mpi Ie

Glossary

PRODAVE MPI/IE V6.1 102 A5E03681152-01

UPDATE Mode

The standby CPU of an H system reaches the UPDATE state when the H system is in the update system mode. The master CPU updates the dynamic data of the standby CPU

Page 103: Manual Mpi Ie

PRODAVE MPI/IE V6.1 A5E03681152-01 103

Index

A as_info_ex6 34 as_zustand_ex6 36 as200_as_info_ex6 68 as200_as_zustand_ex6 70 as200_field_read_ex6 71 as200_field_write_ex6 73 as200_mb_bittest_ex6 76 as200_mb_setbit_ex6 75 Assigning Parameters to the PG/PC Interface

18 Automation License Manager 11

B bcd_2_ulong _ex6 93 bcd_2_ushort_ex6 93 bool_2_byte_ex6 87 bst_read_diag_ex6 44 bst_read_ex6 48 bst_read_stat_ex6 46 byte_2_bool_ex6 86

C Certificate of License 12 Checking the Address assignment 18 Checking the Interrupt Assignment 19 copy_buffer_ex6 90

D db_buch_ex6 38 db_read_ex6 40 db_write_ex6 42 defrag_ex6 64

F field_read_ex6 54 field_write_ex6 56 Flash memory file system 16 float_2_gp_ex6 84 float_2_kg_ex6 82

G get_ie_lifelist_ex6 62 get_pb_lifelist_ex6 60 GetErrorMessage_ex6 78 GetLoadedConnections_ex6 95

GetPduSize_ex6 96 gp_2_float_ex6 83 Guidelines for Handling License Keys 14

I Installation Procedure 16 Installation Requirements 15 Installing PRODAVE MPI/IE V6.2 15, 16

K kf_2_integer_ex6 88 kf_2_long_ex6 88 kg_2_float_ex6 81

L License Key 14 License types

Floating License 13 Single License 13 Trial License 13 Upgrade License 13

License Types Enterprise License 11 Upgrade License 11

LoadConnection_ex6 27

M mb_bittest_ex6 66 mb_setbit_ex6 65 MPI card in the PG/PC 18 MPI interface 15 MPI Interface 15 MPI-ISA-Card (Auto) 18

P PG/PC Interface 18

Parameter Assignment 18 PRODAVE MPI/IE V6.2

Errors during Installation 17 Installation 15 Uninstalling 21

R read_diag_buf_ex6 52

Page 104: Manual Mpi Ie

Index

PRODAVE MPI/IE V6.1 104 A5E03681152-01

S SetActiveConnection_ex6 31 SetPassword_ex6 32 Setting

PG/PCInterface 18 Setup errors 16 swab_buffer_ex6 89 szl_read_ex6 58

T testbit_ex6 85 ts_dial_ex6 97 ts_get_modem_name_ex6 103 ts_hang_up_dial_ex6 99

ts_hang_up_ring_ex6 102 ts_read_info_ex6 101 ts_set_ringindicator_ex6 100

U ulong_2_bcd_ex6 91 Uninstalling

PRODAVE MPI/IE V6.2 21 User rights 14

UnloadConnection_ex6 30 UnSetPassword_ex6 33 User Rights Through The Automation License

Manager 11 ushort_2_bcd_ex6 91