machine lab 3

5
International Islamic University, Islamabad Electrical Machines LAB EXPERIMENT # 03: Testing of Single Phase Transformers (Turn Ratio and Polarity Test) Name of Student: ………………………………….. Roll No.: …………………………………………… Date of Experiment: ……………………………….. Report submitted on: ……………………………….. Marks obtained: …………………………………… Remarks: …………………………………………… Instructor’s Signature: ……………………………...

Upload: khurram-hussain

Post on 20-Oct-2015

8 views

Category:

Documents


0 download

DESCRIPTION

Transformer Tests: Polarity and Turn ratio test

TRANSCRIPT

  • International Islamic University,

    Islamabad

    Electrical Machines LAB

    EXPERIMENT # 03:

    Testing of Single Phase Transformers

    (Turn Ratio and Polarity Test)

    Name of Student: ..

    Roll No.:

    Date of Experiment: ..

    Report submitted on: ..

    Marks obtained:

    Remarks:

    Instructors Signature: ...

  • Experiment 3

    Testing of Single Phase Transformer and Equivalent Circuit

    Determination

    Turn Ratio Test

    Apparatus

    Theory

    The induced emf in primary and secondary winding in transformer is given by following equations:

    max11 44.4 fNV

    max22 44.4 fNV

    Taking ratio of these equations, we would have

    KN

    N

    E

    E

    V

    V

    1

    2

    1

    2

    1

    2

    If the secondary and primary voltages are measured on no-load, their ratio is very nearly equal to the true

    value. Measurement of primary and secondary currents in short circuit test also gives fairly accurate

    results, especially if the transformer has little leakage flux and low core reluctance.

    Procedure

    1. Make the connections as shown in figure.

    2. Now connect the primary winding of the transformer to the variable AC supply, connect a

    voltmeter on the secondary winding at no-load.

    3. Make sure that for various voltages the turn ratio comes out to be

    394.0127

    50

    1

    2

    1

    2 N

    N

    V

    V

    Circuit Diagram

  • Readings and Observations

    S. No Primary Voltage ( 1V ) Secondary Voltage ( 2V ) 1

    2

    V

    VK

    1 20V

    2 40V

    3 60V

    4 80V

    5 100V

    6 115V

    7 127V

    S. No Primary Current ( 1I ) Secondary Current ( 2I ) 2

    1

    I

    IK

    1

    2

    3

    4

    5

    6

    7

  • Polarity Test

    Apparatus

    Theory

    On the primary side of a two winding transformer, one terminal is positive with respect to the other one at

    any instant. At the same instant, one terminal of the secondary winding is positive with respect to the

    other one. Polarity test is performed to determine the terminals having the same instantaneous polarity

    (assuming that the terminals are not marked). The relative polarities of the primary and secondary

    terminals at any instant must be known for connecting windings of the same transformer in parallel, or

    series, or for interconnecting two or more transformers in parallel, or for connecting single phase

    transformers for polyphase transformation of voltages.

    For determination of relative polarity of the two windings of a transformer the two windings are

    connected in series across a voltmeter, while one of the windings (preferably HV winding) is excited from

    a suitable AC voltage source. IF the polarities of the windings are as marked on the diagram i.e., when the

    transformer has subtractive polarity the voltmeter will read the difference of 1E and 2E . If the voltmeter

    reads 21 EE , the polarity markings of one of the windings must be interchanged.

    In subtractive polarity, the voltage between 1A and 1a is reduced. The leads connected to these

    terminals and the two windings are, therefore, not subjected to high voltage stress. On the other hand in

    additive polarity the two windings and leads connected to 2121 &,, aaAA are subjected to high voltage

    stress. This is the reason that subtractive polarity is preferred over additive polarity.

    Procedure

    1. Make the connections as shown in figure.

    2. Now apply some voltage on the primary from variable AC voltage source.

    3. If the polarities of the windings are as marked on the diagram, the voltmeter should read the

    difference of 1E and 2E (subtractive polarity).

    4. If it reads 21 EE , the polarity marking of one of the windings must be interchanged.

  • Circuit Diagram

    Subtractive Polarity

    Sr. 1V (Primary) 2V (Secondary) V (Voltmeter)

    1 20

    2 40

    Additive Polarity

    Sr. 1V (Primary) 2V (Secondary) V (Voltmeter)

    1 10

    2 20