machine lab 3
DESCRIPTION
Transformer Tests: Polarity and Turn ratio testTRANSCRIPT
-
International Islamic University,
Islamabad
Electrical Machines LAB
EXPERIMENT # 03:
Testing of Single Phase Transformers
(Turn Ratio and Polarity Test)
Name of Student: ..
Roll No.:
Date of Experiment: ..
Report submitted on: ..
Marks obtained:
Remarks:
Instructors Signature: ...
-
Experiment 3
Testing of Single Phase Transformer and Equivalent Circuit
Determination
Turn Ratio Test
Apparatus
Theory
The induced emf in primary and secondary winding in transformer is given by following equations:
max11 44.4 fNV
max22 44.4 fNV
Taking ratio of these equations, we would have
KN
N
E
E
V
V
1
2
1
2
1
2
If the secondary and primary voltages are measured on no-load, their ratio is very nearly equal to the true
value. Measurement of primary and secondary currents in short circuit test also gives fairly accurate
results, especially if the transformer has little leakage flux and low core reluctance.
Procedure
1. Make the connections as shown in figure.
2. Now connect the primary winding of the transformer to the variable AC supply, connect a
voltmeter on the secondary winding at no-load.
3. Make sure that for various voltages the turn ratio comes out to be
394.0127
50
1
2
1
2 N
N
V
V
Circuit Diagram
-
Readings and Observations
S. No Primary Voltage ( 1V ) Secondary Voltage ( 2V ) 1
2
V
VK
1 20V
2 40V
3 60V
4 80V
5 100V
6 115V
7 127V
S. No Primary Current ( 1I ) Secondary Current ( 2I ) 2
1
I
IK
1
2
3
4
5
6
7
-
Polarity Test
Apparatus
Theory
On the primary side of a two winding transformer, one terminal is positive with respect to the other one at
any instant. At the same instant, one terminal of the secondary winding is positive with respect to the
other one. Polarity test is performed to determine the terminals having the same instantaneous polarity
(assuming that the terminals are not marked). The relative polarities of the primary and secondary
terminals at any instant must be known for connecting windings of the same transformer in parallel, or
series, or for interconnecting two or more transformers in parallel, or for connecting single phase
transformers for polyphase transformation of voltages.
For determination of relative polarity of the two windings of a transformer the two windings are
connected in series across a voltmeter, while one of the windings (preferably HV winding) is excited from
a suitable AC voltage source. IF the polarities of the windings are as marked on the diagram i.e., when the
transformer has subtractive polarity the voltmeter will read the difference of 1E and 2E . If the voltmeter
reads 21 EE , the polarity markings of one of the windings must be interchanged.
In subtractive polarity, the voltage between 1A and 1a is reduced. The leads connected to these
terminals and the two windings are, therefore, not subjected to high voltage stress. On the other hand in
additive polarity the two windings and leads connected to 2121 &,, aaAA are subjected to high voltage
stress. This is the reason that subtractive polarity is preferred over additive polarity.
Procedure
1. Make the connections as shown in figure.
2. Now apply some voltage on the primary from variable AC voltage source.
3. If the polarities of the windings are as marked on the diagram, the voltmeter should read the
difference of 1E and 2E (subtractive polarity).
4. If it reads 21 EE , the polarity marking of one of the windings must be interchanged.
-
Circuit Diagram
Subtractive Polarity
Sr. 1V (Primary) 2V (Secondary) V (Voltmeter)
1 20
2 40
Additive Polarity
Sr. 1V (Primary) 2V (Secondary) V (Voltmeter)
1 10
2 20