m-pact plus flyer e - nuova elva fanuc - power controls/guida alla... · combinations of uef, ref...

2
(1) M-PRO 30 units can be provided with REF as standard feature to replace UEF but please specify correct order code. (2) Remote indication becomes a standard feature when the Communications facility is specified. (3) Standard feature when Restricted Earth Fault option is specified. (4) Feature not available if communications option is specified. (5) Requires permanent auxiliary power to operate continuously. L = Low voltage inputs H = High voltage inputs Standard Optional O Trip unit Long Time Protection Pickup adjustable from 0.4 to 1.0x In in steps of 0.1 Pickup adjustable from 0.4 to 1.0x In in steps of 0.01 Long Time Characteristic To IEC 947-4, Class 20 To IEC 947-4, Class 40 (& IEC255, 80 combinations) Fixed Short Time Protection 1.5, 2, 3, 4, 5, 6, 8 ,10 & 12 x Ir (frame 1 & 2 size) 1.5, 2, 3, 4, 6, 8 & 10 x Ir (frame 3 size only) Instantaneous Trip (Ii) OFF, 2, 3, 4, 6, 8 ,10 & 12 x In (frame 1 & 2 size) OFF, 2, 3, 4, 6, 8 & 10 x In (frame 3 size only) Short time delay 0.1, 0.2, 0.4, 0.5, 0.6, 0.8, 1.0s. (frame 1& 2 size) 0.1, 0.2, 0.3, 0.4s. (frame 3 size only) Inst to 1.0s in 0.1 steps Short time I 2 t Protection (Inverse Short Circuit) 0.1 times selected long time Pick-up, 1.5, 2, 3, 4, 6, 8, 10 and 12 x Ir Neutral Protection Fixed Neutral Protection (50% or 100%) Adjustable Neutral Protection Earth fault protection Unrestricted Earth Fault (UEF) Restricted Earth Fault (REF) Standby Earth Fault (SEF) Combinations of UEF, REF & / or SEF Earth fault pickup, OFF, 0.1 to 1.0x In. 0.01In steps Earth fault pickup, OFF, 0.4 to 1.0x In. 0.2In steps Time Delay: <100ms, 0.1, 0.2, 0.4, 0.6, 0.8 and 1.0s Time Delay: Inst. To 1.0s in 0.1 steps Earth fault cropping, 1 (OFF), 1.5, 2, 2.5, 3, 4, 5 and 6 Thermal Memory / Cooling Time Fixed to at time constant of 20 minutes Adjustable time constants, inst., 10,20,30,45,60,120,180 mins Trip Indication Healthy Unit LED Warning & / or Alarm LED Discrete LED’s for each fault type Remote Indication (Fault code via communication facility) Fault Analysis Existing Fault Notification Historic Trips (last 16) Historic Fault (last trip only) System Status Breaker Status Auxiliary Power Supply Output Relays Trip Initiated HV Inter trip (linked to REF) Watchdog/Watchdog disable (No output relay) Remote ACB Switching (Open / Close via Comms. Unit) Communications MODBUS Protocol Trip Reset Manual (Push Button) - Frame 1 & 2 Automatic - Frame 1 & 2 Monitoring Ammeters Load Monitoring Operations Counter Trip Alarm Contact (mechanical C/O) Main Contact Maintenance Indication Inputs 24-48V d.c. 110-130V d.c. or 110-250Va.c. Auxiliary Power Supply Plant Associated Memory Module (PAMM) Circuit Protection Memory Test Connector 16 way DIL Heater 26 way D-Type O O O O (5) O O O O O O O (5) O O O L O (1) O O (5) O (2) O (3) O O (2) O (4) H O (1) O O (5) O (2) O (3) O O (2) O (4) L (5) O O O H (5) O O O M-PRO Microprocessor Relays - Specifications M-PRO 17 Plus M-PRO 18 Plus M-PRO 30 M-PRO 40 Air Circuit Breakers M-PACT Plus GE Consumer & Industrial Power Protection GE imagination at work New M-Pact Plus Air Circuit Breakers New frame size up to 6300A Standard features (Frames 1 & 2) • Trip-free operating mechanism • Positive ON/OFF contact indication • Mechanical/electrical anti-pumping device • Charging spring status indication (optional) • Ergnonomic manual spring charging handle • Field-mountable range of accessories • Auxiliary switches 5NO and 3NC, potential free 10A 250V (standard) • Mechanical trip alarm switch (1NO) (optional) • Padlockable push-button cover • Mechanical cable interlocking (optional) • Termination: rear, horizontal / front access (optional) • Electrical clearances according to IEC 947-2 • Front access of secondary terminals for simple connection NEW NEW 680849 Ref. I/3185/E/EX 10.0 Ed. 09/05 © Copyright GE Power Controls, 2005 GE Power Controls International Sales Nieuwevaart 51 B-9000 Gent - Belgium T +32/9 265 21 11 F +32/9 265 28 90 E [email protected] www.gepowercontrols.com GE POWER CONTROLS Hornhouse Lane Knowsley Industrial Park Liverpool L33 7YQ T 0800 587 1251 F 0800 587 1239 E [email protected] E [email protected]

Upload: hahuong

Post on 23-May-2018

221 views

Category:

Documents


2 download

TRANSCRIPT

Page 1: M-Pact Plus flyer E - Nuova Elva Fanuc - Power Controls/Guida alla... · Combinations of UEF, REF & / or SEF Earth fault pickup, OFF, ... range of advanced protection relay to compliment

(1) M-PRO 30 units can be provided with REF as standard feature to replace UEF but please specify correct order code.(2) Remote indication becomes a standard feature when the Communications facility is specified.(3) Standard feature when Restricted Earth Fault option is specified.(4) Feature not available if communications option is specified.(5) Requires permanent auxiliary power to operate continuously.

L = Low voltage inputsH = High voltage inputsStandard • Optional O

Trip unit

Long Time ProtectionPickup adjustable from 0.4 to 1.0x In in steps of 0.1 Pickup adjustable from 0.4 to 1.0x In in steps of 0.01 Long Time CharacteristicTo IEC 947-4, Class 20 To IEC 947-4, Class 40 (& IEC255, 80 combinations)Fixed Short Time Protection1.5, 2, 3, 4, 5, 6, 8 ,10 & 12 x Ir (frame 1 & 2 size) 1.5, 2, 3, 4, 6, 8 & 10 x Ir (frame 3 size only) Instantaneous Trip (Ii)OFF, 2, 3, 4, 6, 8 ,10 & 12 x In (frame 1 & 2 size) OFF, 2, 3, 4, 6, 8 & 10 x In (frame 3 size only) Short time delay0.1, 0.2, 0.4, 0.5, 0.6, 0.8, 1.0s. (frame 1& 2 size)0.1, 0.2, 0.3, 0.4s. (frame 3 size only)Inst to 1.0s in 0.1 stepsShort time I2t Protection (Inverse Short Circuit)0.1 times selected long timePick-up, 1.5, 2, 3, 4, 6, 8, 10 and 12 x IrNeutral ProtectionFixed Neutral Protection (50% or 100%)Adjustable Neutral ProtectionEarth fault protectionUnrestricted Earth Fault (UEF)Restricted Earth Fault (REF)Standby Earth Fault (SEF)Combinations of UEF, REF & / or SEFEarth fault pickup, OFF, 0.1 to 1.0x In. 0.01In stepsEarth fault pickup, OFF, 0.4 to 1.0x In. 0.2In steps Time Delay: <100ms, 0.1, 0.2, 0.4, 0.6, 0.8 and 1.0sTime Delay: Inst. To 1.0s in 0.1 steps Earth fault cropping, 1 (OFF), 1.5, 2, 2.5, 3, 4, 5 and 6Thermal Memory / Cooling TimeFixed to at time constant of 20 minutesAdjustable time constants, inst., 10,20,30,45,60,120,180 minsTrip IndicationHealthy Unit LEDWarning & / or Alarm LEDDiscrete LED’s for each fault typeRemote Indication (Fault code via communication facility)Fault AnalysisExisting Fault NotificationHistoric Trips (last 16)Historic Fault (last trip only)System StatusBreaker StatusAuxiliary Power SupplyOutput RelaysTrip InitiatedHV Inter trip (linked to REF)Watchdog/Watchdog disable (No output relay)Remote ACB Switching (Open / Close via Comms. Unit)Communications MODBUS ProtocolTrip ResetManual (Push Button) - Frame 1 & 2Automatic - Frame 1 & 2MonitoringAmmetersLoad MonitoringOperations CounterTrip Alarm Contact (mechanical C/O)Main Contact Maintenance IndicationInputs24-48V d.c.110-130V d.c. or 110-250Va.c.Auxiliary Power SupplyPlant Associated Memory Module (PAMM)Circuit Protection MemoryTest Connector16 way DIL Heater26 way D-Type

17Plus*

••

••

••

O

O

OO

• (5)

O

••

O

O

18Plus*

••

••

••

O

O

OO

• (5)

•O

••

•O

O

L

••

•O(1)

OO••

••

• (5)

•••

O(2)

••

••

•O(3)

OO(2)

••

•••O• (4)

H

••

•O(1)

OO••

••

• (5)

•••

O(2)

••

••

•O(3)

OO(2)

••

•••O• (4)

••

L

••

••••••

••

• (5)

••••

••

••

••OO•

••

•••O•

H

••

••••••

••

• (5)

••••

••

••

••OO•

••

•••O•

••

M-PRO Microprocessor Relays - SpecificationsM-PRO 17 Plus M-PRO 18 Plus M-PRO 30 M-PRO 40

Air

Circ

uit B

reak

ers

M-PACT Plus GE Consumer & IndustrialPower Protection

GE imagination at work

NewM-Pact PlusAir Circuit BreakersNew frame size up to 6300A

Standard features (Frames 1 & 2)• Trip-free operating mechanism• Positive ON/OFF contact indication• Mechanical/electrical anti-pumping device• Charging spring status indication (optional)• Ergnonomic manual spring charging handle• Field-mountable range of accessories• Auxiliary switches 5NO and 3NC,

potential free 10A 250V (standard)• Mechanical trip alarm switch (1NO) (optional)• Padlockable push-button cover• Mechanical cable interlocking (optional)• Termination: rear, horizontal / front access (optional)• Electrical clearances according to IEC 947-2• Front access of secondary terminals for simple connection

NEW NEW

6808

49Re

f. I/

3185

/E/E

X 10

.0

Ed. 0

9/05

© C

opyr

ight

GE

Pow

er C

ontr

ols,

200

5

GE Power ControlsInternational SalesNieuwevaart 51B-9000 Gent - Belgium

T +32/9 265 21 11F +32/9 265 28 90E [email protected]

GE POWER CONTROLSHornhouse LaneKnowsley Industrial ParkLiverpool L33 7YQ

T 0800 587 1251F 0800 587 1239E [email protected] [email protected]

Page 2: M-Pact Plus flyer E - Nuova Elva Fanuc - Power Controls/Guida alla... · Combinations of UEF, REF & / or SEF Earth fault pickup, OFF, ... range of advanced protection relay to compliment

M-PACT PlusAi

r Ci

rcui

t Bre

aker

sM-PACT Plus

Air Circuit Breakers

Introducing the M-PRO Plus protection relay

The M-PRO plus range of protection relay is the latestrange of advanced protection relay to compliment the M-Pact Plus air circuit breaker. The relay incorporates theunique features and benefits that have been proven withM-PRO but is an enhanced design for improved reliability,performance and application purposes.

The four types of protection units are M-PRO 17 plus, M-PRO 18 plus, M-PRO 30 and M-PRO 40 units.

Each M-PRO unit has specific features and benefitsdependant on the type of installation and applicationrequired by the user.This range provides inter-changeability essential whenupgrading circuits and providing limited down time foressential services.

M-PRO Plus has retained the innovative measurementcoils which due to their high accuracy and power ensureM-PRO Plus is self powered even when loads are very low.

The M-PRO17 Plus provides basic overcurrent and short-circuit protection with simple rotary switches for adjust-ment and clear indication of protection settings.Protection settings now available as low as 1.5 x Ir forimproved selectivity and co-ordination.'M-PRO17 Plus' has the additional option of Earth faultprotection.

Also introducing the new M-PRO18 Plus with the sameprotection functions as 'M-PRO17 Plus' but complete witha digital display.For ease of reference this unit also has a back light facilityproviding clear indication of the digital display.'M-PRO18 Plus' has the additional option of Earth faultprotection.

The M-PRO 30 and 40 units have a unique and innovativememory system enabling circuit protection settings andhistorical data to be stored remote from the associatedcircuit breaker.

Depending on the type of M-PRO Plus unit specified (see selection table) the following features are available:

- Adjustable protection curves- Auxiliary power inputs- Earth Fault Protection (unique combinations)- Neutral Protection (fixed or adjustable)- Ammeter (multi functions)- Thermal Memory- Historical Tripping data with real time - Reset Switch (manual and auto available)- LCD display (with timed backlit function)- Multiple adjustment and fault indication- Programmable inputs/outputs- Communication facility- Alarm contact- Mechanical Alarm Contact (optional)- Load monitoring- Making Contact Release (50kA)

M-PRO 17 Plus

M-PRO 18 Plus

M-PRO 30 - 40

Rated from 400 to 6300A the M-PACT Plus circuitbreaker has been designed to meet the most stringentdemands in fault detection and safe interruptionthereof.Available in 3 frame sizes:• Frame size 1 ranging from 400 to 2500A• Frame size 2 ranging from 800 to 4000A• Frame size 3 ranging from 5000 to 6300AThe range has been developed aesthetically andtechnically to co-ordinate with other protective deviceswithin our company for industrial/domesticapplications.All 3 frame sizes have unique look available with bothfixed pattern and drawout versions which can bemanually or electrically operated. These ACBs aredesigned to offer multiple mains connection options italso comes with a wide range of easy-to-installaccessories.

Specif ication

M-PACT Plus air circuit breakers comply with thefollowing specifications for low voltage switchgear:• IEC 947-1• IEC 947-2• IEC 947-3• VDE 0660 Part 101 and Part 107• Utilization category B

Approvals

LOVAG certification in accordance with IEC 947-2, BS EN 60947-2 ASTA, KEMA, CCC

Introducing the M-Pact Plus range of Air Circuit Breakers

3 compact frame sizesFrame size 1 - 400 to 2500AFrame size 2 - 800 to 4000AFrame size 3 - 5000 to 6300A• Frame 1 & 2

Fixed & withdrawable version is offered with 3 or 4 pole configuration, front and rear accessconnections (horizontal / vertical).

• Frame 3 Fixed and withdrawable version is offered with 3 Pole only, rear connections (horizontal/vertical)

• Devices provided with or without protection relay• Manual or electrical operation and built-in safety

features e.g. safety shutters

• Wide range of protection settings offering full selectivitycombinations of earth fault protection with simple &easy service on site

4 performance ranges(1)

Type S - 50 kA Icu = Ics = IcwType N - 65 kA Icu = Ics = IcwType H - 80 kA Icu = Ics = IcwType C(2) - 100 kA Icu = Ics = Icw

(1) Ratings shown at 500V AC(2) Ratings shown at 690V AC

Memory available on request

NEW

NEW

NEW

NEW