ENABLING OBJECTIVES

• DESCRIBE the purpose, function, component parts, operating characteristics and maintenance requirements of the ship’s firemain system

• DESCRIBE bi-metallic corrosion, its effect on seawater systems, and how to inspect for its presence

Page 3: LT.3111 Firemain S W O S T E A M D A M A G E C O N T R O L American LaFrance

LT.311 3

• EXPLAIN how to isolate and bypass ruptures of the firemain system using the firemain damage control diagram

ENABLING OBJECTIVES

Page 4: LT.3111 Firemain S W O S T E A M D A M A G E C O N T R O L American LaFrance

LT.311 4

WHAT IS THE PRIMARYPRIMARY FUNCTION OF THE FIREMAIN

SYSTEM?

TO SUPPLY SEAWATER TO FIGHT FIRES

Page 5: LT.3111 Firemain S W O S T E A M D A M A G E C O N T R O L American LaFrance

LT.311 5

FIREMAIN

• “NO INFORMATION IS OF GREATER IMPORTANCE TO THE DAMAGE CONTROL ORGANIZATION THAN A COMPLETE KNOWLEDGE OF THE SHIP’S FIREMAIN SYSTEM”– NSTM 079 VOL 2

Page 6: LT.3111 Firemain S W O S T E A M D A M A G E C O N T R O L American LaFrance

LT.311

KNOW YOUR FIREMAIN SYSTEM

TRACE IT !!!

Page 7: LT.3111 Firemain S W O S T E A M D A M A G E C O N T R O L American LaFrance

LT.311 7

Firemain

• Firefighter should have a working knowledge of– Firemain piping

– Firemain valves

– Measures to be taken after battle damage to assure water service for firefighting

Page 8: LT.3111 Firemain S W O S T E A M D A M A G E C O N T R O L American LaFrance

LT.311 8

Firemain Systems

- Design Features- Types- Components- Operation- Maintenance

Page 9: LT.3111 Firemain S W O S T E A M D A M A G E C O N T R O L American LaFrance

LT.311 9

Design Features Reliability:

Resistant to Saltwater CorrosionRedundancy: Multiple fire pumps Optimum Sectionalization: Independent stations practical during battle

Page 10: LT.3111 Firemain S W O S T E A M D A M A G E C O N T R O L American LaFrance

LT.311 10

System Types

•Single Main•Horizontal Loop•Vertical Loop•Composite

Page 11: LT.3111 Firemain S W O S T E A M D A M A G E C O N T R O L American LaFrance

LT.311 11

• Extends longitudinally near the centerline of ship

• Pumps discharge into risers

• Risers direct water into main

• Main supplies fireplugs & other services

• Usually found on FF’s and DDG’s

Single Main

Page 12: LT.3111 Firemain S W O S T E A M D A M A G E C O N T R O L American LaFrance

LT.311 12

Single Main

Page 13: LT.3111 Firemain S W O S T E A M D A M A G E C O N T R O L American LaFrance

LT.311

Single Main

Page 14: LT.3111 Firemain S W O S T E A M D A M A G E C O N T R O L American LaFrance

LT.311 14

HORIZONTAL LOOP

• 2 Single Mains on DC Deck

• Separated athwartship– Minimizes

damage– Cross-connected

to form series of horizontal loops

• Risers connected into Cross Connects

• Allows water into either or both loops

• Service Risers & Branches

Page 15: LT.3111 Firemain S W O S T E A M D A M A G E C O N T R O L American LaFrance

LT.311 15

HORIZONTAL LOOP

Page 16: LT.3111 Firemain S W O S T E A M D A M A G E C O N T R O L American LaFrance

LT.311 16

VERTICAL LOOP• 2 Single Mains• Installed in oblique

plane• Separated vertically &

athwartship• Upper Main installed

on DC deck• Lower Main is low in

ship

• Mains are cross-connected to form series of loops

• Risers discharge port/stbd into either main

• Service Risers led from Main

Page 17: LT.3111 Firemain S W O S T E A M D A M A G E C O N T R O L American LaFrance

LT.311 17

VERTICAL LOOP

Page 18: LT.3111 Firemain S W O S T E A M D A M A G E C O N T R O L American LaFrance

LT.311 18

Page 19: LT.3111 Firemain S W O S T E A M D A M A G E C O N T R O L American LaFrance

LT.311 19

COMPOSITE

• 2 or 3 service mains on DC deck

• Separated athwarthship

• By-pass main installed at lower level near C/L

• Cross-connects installed alternately between service mains & by-pass main

• Risers discharge into cross-connects

• Service risers led from service main

Page 20: LT.3111 Firemain S W O S T E A M D A M A G E C O N T R O L American LaFrance

LT.311 20

COMPOSITE

Page 21: LT.3111 Firemain S W O S T E A M D A M A G E C O N T R O L American LaFrance

LT.311 21

SERVICES PROVIDED(PARASITIC SYSTEMS)

MAGAZINE SPRINKLING

CMWDDECON

SHOWERSFLUSHINGBALLASTING

EMERGENCY ELECTRONIC COOLING WATER

EDUCTOR OPERATION

MISSILE BOOSTER SUPPRESSION SYSTEM

Page 22: LT.3111 Firemain S W O S T E A M D A M A G E C O N T R O L American LaFrance

LT.311 22

Fire Pumps Single Stage Centrifugal

Capacity of 1000 GPM at 150 psig

Electric Motor

Page 23: LT.3111 Firemain S W O S T E A M D A M A G E C O N T R O L American LaFrance

LT.311 23

Piping

4" to 12" diameter

Cu-Ni construction

Depending on capacity requirements

Resistant to seawater corrosion

Page 24: LT.3111 Firemain S W O S T E A M D A M A G E C O N T R O L American LaFrance

LT.311 24

IsolationGate (handwheel) or Globe

SectionalizationButterfly - 1 motion handlePressure Reducing

VALVES

Page 25: LT.3111 Firemain S W O S T E A M D A M A G E C O N T R O L American LaFrance

LT.311 25

FireplugsStation Isolation ValveMarine strainer

Fire hose and nozzles

Spanner Wrenches (2)

Removed upon receipt of vari-nozzles

Size, Capacity, and Quantity dependent on requirements

Wye-gateWhen required

Page 26: LT.3111 Firemain S W O S T E A M D A M A G E C O N T R O L American LaFrance

LT.311 26

GaugesLocal

Remote

Fire Stations, Magazine Sprinkling, Flushing Stations

D C Central, Repair Lockers, Main Control

Page 27: LT.3111 Firemain S W O S T E A M D A M A G E C O N T R O L American LaFrance

LT.311 27

MARINE GROWTH • Common cause of firemain malfunction

• Builds up in pipes, decreasing internal cross-section area

• Results in decreased supply of water

• Accumulates on valve seats, discs & stems– Prevents valve from seating

• Tropical waters

Page 28: LT.3111 Firemain S W O S T E A M D A M A G E C O N T R O L American LaFrance

LT.311

MARINEMARINEMARINEMARINE

GROWTHGROWTHGROWTHGROWTH

Flush system every 3 months. Operate pumps at one end of the ship & open weather deck fire plugs on other end.

Flush with freshwater if possible

Page 29: LT.3111 Firemain S W O S T E A M D A M A G E C O N T R O L American LaFrance

LT.311 29

Bimetallic Corrosion

- Dissimilar metals

- Pipe hangers/flanges - (Rubber spacer)

- Ferrous fasteners - flanges

- Use a magnet

- All seawater systems

Firemain System

Page 30: LT.3111 Firemain S W O S T E A M D A M A G E C O N T R O L American LaFrance

LT.311 30

• LOSS OF FIREMAIN LOSS OF FIREMAIN PRESSUREPRESSURE

• FLOODED FLOODED COMPARTMENTSCOMPARTMENTS

Must isolate damaged portions

Restore pressure to intact system

May be able to re-align segregation valves

May have to rig temporary jumper between fire hose stations or special jumper flanged connnections

Bypasses damaged section

RUPTURED FIREMAIN

Page 31: LT.3111 Firemain S W O S T E A M D A M A G E C O N T R O L American LaFrance

LT.311 31

Secure isolation valves at either end of rupture

Remove wye-gates from required fireplugs

Attach 2-1/2 in. hose to each fireplug

Connect 2 lengths of hose using a 2-1/2 inch double female coupling

Open fireplugs

PROCEDURES

Page 32: LT.3111 Firemain S W O S T E A M D A M A G E C O N T R O L American LaFrance

LT.311 32

PROVIDING TEMPORARY FIREMAIN BY USING HOSE AND DOUBLE FEMALE COUPLING

Page 33: LT.3111 Firemain S W O S T E A M D A M A G E C O N T R O L American LaFrance

LT.311

DOUBLE

FEMALE

JUMPER

FIREPLUG

STOP VLV

Page 34: LT.3111 Firemain S W O S T E A M D A M A G E C O N T R O L American LaFrance

LT.311 34

Secure isolation valves nearest rupture

Remove ruptured section of firemain at flanged joints

Bolt on adapters at flanges1 male and 1 female

Connect length of 2-1/2 inch hoseOpen isolation valvesUse trigate

PROCEDURES - Rigging jumpers between firemain flanges

Page 35: LT.3111 Firemain S W O S T E A M D A M A G E C O N T R O L American LaFrance

LT.311 35

PROVIDING TEMPORARY FIREMAIN SERVICE BY USING FLANGES AND A FIRE HOSE

Page 36: LT.3111 Firemain S W O S T E A M D A M A G E C O N T R O L American LaFrance

LT.311 36

• PIPING• STRAINERS• INSULATION• REMOTE

OPERATORS (MANUAL, ELECTRICAL, HYDRAULIC)

• VALVES• LABELING• HANGERS• PUMPS• CONTROLLERS• GAUGES• JOINTS (WELDED

& MECHANICAL)

INSPECTION AREAS

Page 37: LT.3111 Firemain S W O S T E A M D A M A G E C O N T R O L American LaFrance

LT.311 37

DC DIAGRAM

• FIREMAIN, SPRINKLER, FOAM & WASHDOWN SYSTEMS– Shows cutout valves

– Location of all fireplugs

– CMWD valves

– Sprinkler groups

– Foam system valves

Page 38: LT.3111 Firemain S W O S T E A M D A M A G E C O N T R O L American LaFrance

LT.311 38

• Fire pumps– How many, what type, location

– Start/stop locations

• Type of firemain

• Zebra valves

• Fire stations

• Magazine Sprinkler groups

DC BOOK SECTION IIe

Page 39: LT.3111 Firemain S W O S T E A M D A M A G E C O N T R O L American LaFrance

LT.311 39

FIREMAIN SEGREGATION - Condition ZEBRA

ALL PUMPS AVAILABLE FOR OPERATION OF THE MK13 GMLS, SPRINKLER SYSTEM, BOOSTER SUPPRESSION & DRAINAGE EDUCTORS

LOWER LOOP - FP1-(E), FP2-(E), & FP5-(E)

UPPER LOOP - FP3-(E), & FP4-(E) THE FIREMAIN LOOP IS SEGREGATED INTO TWO SECTIONS. IN CONDITION “ZEBRA” AS INDICATED ABOVE. TO ESTABLISH CONDITION “ZEBRA” FROM CONDITION “X-RAY” OR ”YOKE”, THE FOLLOWING THREE “ZEBRA” VALVES ARE CLOSED.

VALVE NO. LOCATION REMOTE CONTROL

2-106-2 2-100-4-L 2-292-01-C

3-232-1 5-212-0-E 2-292-01-C

3-303-1 5-292-0-E 2-292-01-C

3-103-1 3-100-1-L

Page 40: LT.3111 Firemain S W O S T E A M D A M A G E C O N T R O L American LaFrance

LT.311 40

MOB-D-20-SFISOLATING & PATCHING DAMAGED

PIPING

• Train repair parties to isolate a damaged section of the firemain or other piping & make emergency repairs

• Pipe patching kit

• Firemain chart available & used to identify all systems affected

Page 41: LT.3111 Firemain S W O S T E A M D A M A G E C O N T R O L American LaFrance

41LT.311

LESSON 3.11 SUMMARY Design features

Types of systems

Parasitic systems

Fire pumps

Additional equipment

Required maintenance

Bimetallic corrosion

Page 42: LT.3111 Firemain S W O S T E A M D A M A G E C O N T R O L American LaFrance

LT.311 42

QUESTION #1

• WHAT ARE THE FOUR TYPES OF FIREMAIN SYSTEMS?

Page 43: LT.3111 Firemain S W O S T E A M D A M A G E C O N T R O L American LaFrance

LT.311 43

• SINGLE MAIN

• HORIZONTAL LOOP

• VERTICAL LOOP

• COMPOSITE

ANSWER

Page 44: LT.3111 Firemain S W O S T E A M D A M A G E C O N T R O L American LaFrance

LT.311 44

QUESTION #2

• NAME SOME OF THE SERVICES PROVIDED BY THE FIREMAIN SYSTEM.

Page 45: LT.3111 Firemain S W O S T E A M D A M A G E C O N T R O L American LaFrance

LT.311 45

• CMWD• FLUSHING• MAGAZINE

SPRINKLING• BALLASTING• EMERGENCY

ELECTRONIC COOLING

• DECON STATION• EDUCTOR

OPERATION

ANSWER

Page 46: LT.3111 Firemain S W O S T E A M D A M A G E C O N T R O L American LaFrance