low voltage easypact mvs

90
Catalogue 2014 Low Voltage EasyPact MVS LV power circuit breakers and switch-disconnectors 800 to 4000A

Upload: others

Post on 16-Oct-2021

4 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: Low Voltage EasyPact MVS

Catalogue2014

Low Voltage

EasyPact MVSLV power circuit breakers and switch-disconnectors800 to 4000A

Page 2: Low Voltage EasyPact MVS

Performancewithout compromise

Exceptionalreliability,flexibilityand convenience

Quality and safetyyou can trust

Outstanding value for an optimized feature set

Buildings Industry Panelbuilders

Page 3: Low Voltage EasyPact MVS

3

EasyPact MVS rangeThe easy choice for reliable performance

> Performance without compromise

> Assured quality and safety you can trust

> Deliver exceptional reliability and flexibility in its class

> Outstanding value for an optimized feature set

> Precision engineered to meet your needs

> Unbeatable value throughout its lifecycle

> Simple to choose and easy to install

Page 4: Low Voltage EasyPact MVS

Choose the leader> 800 to 4000A ratings

> Breaking capacity: 65kA

> Suitable for 690V applications

> Complete selectivity with Ics=Icu=Icw (1 s)

> Intelligent ET range of trip system with display

> Fully protected neutral on 4 pole breakers

> Common accessories for complete range

> Conforms to IEC 60947- 2 & 3

Page 5: Low Voltage EasyPact MVS

EasyPact MVS08 to MVS40

EasyPact MVSBenefits for every customer

5

Panel builders/contractors

End Users Designers

> Single frame size from 800 to 4000A with identical door cut-outs

> Suitable for copper & Aluminium termination with a single pole pitch of 115 mm

> Terminal orientation can be converted from horizontal to vertical and vice-versa at workshop

> Direct mounting Door frames (escutcheon) without drilling any holes

> Front fi tted accessories like under-volt release, shunt release & closing coil for complete range

> Conversion of manual operated breaker in to electrical operated, with single bolt fi xing

EasyPact MVS with single frame size,common accessories helps to increase the shop fl oor effi ciency,enabling faster delivery of swith boards.

> Conforms to IEC60947-2 for breakers & IEC60947-3 for disconnectors

> Designed and manufactured using advanced manufacturing methods to match your quality expectations and the needs of each project.

> Continuous rated coils helps in simple interlocking schemes

> Extensive choice of software tools & documentation to reduce design time.

> EasyPact MVS respects the environment throughout their life cycle

EasyPact MVS is designed to meet the needs of your customers with fl exibility to achieve system effi ciency during the design phase

> Moulded case design ensures high endurance without maintenance

> Intelligent ET range of trip system with thermal memory and display for measurements.

> Overload run alarm & individual LED indications enable fault identifi cation

> lcu=lcs=lcw(1sec)=65kA ensures complete selectivity

> Inbuilt safety shutter & interlocks

> Designed to provide utmost user safety during installation, during use, and while under maintenance.

> All 4 pole breakers are with fully rated neutral and protected with adjustable settings at OFF – 50%-100%

EasyPact MVS answers even to the most stringent application with most reliable distribution systems assuring continuity of service

Page 6: Low Voltage EasyPact MVS

The Key values

90%

100%

30%

of applications are

covered

Commitment to

quality

Reduce stock by up to

The performance you need

With the quality you demand

At a cost-effective investment

EasyPact MVS provides the ideal level of capability for your installation from 800 to 4000 A.

Designed and manufactured by Schenider Electric using advanced manufacturing methods and premium mate-rials.

Pay for what you need: Get outstanding durability with the features you need, with the benefit of easy to order and stock.

6

Page 7: Low Voltage EasyPact MVS

Gain peace of mind and optimised cost for every installation

Page 8: Low Voltage EasyPact MVS
Page 9: Low Voltage EasyPact MVS

EasyPact MVS General contents

Functionsand characteristics A-1

Installationrecommendations B-1

Dimensionsand connection C-1

Electrical diagrams D-1

Additionalcharacteristics E-1

Catalogue numbers and order form F-1

Page 10: Low Voltage EasyPact MVS

Functions and characteristics

Page 11: Low Voltage EasyPact MVS

A-1

Functions and characteristics

General overview A-2Detailed contents A-2

Circuit breakers and switch-disconnectors A-4MVS08 to MVS40 A-4

Identifying ET range of trip system A-6

Overview of functions A-8 ET trip system A-8ETA trip system A-10ETV trip system A-12

ET range of trip system A-14 Accessories and test equipment A-14

Connections A-15 Overview of solutions and accessories A-15Accessories and auxiliaries A-16

Locking A-18 On the device A-18On the chassis A-19

Indication contacts A-20

Remote operation A-21 Remote ON / OFF A-21Remote tripping A-23

Source-changeover systems A-24Mechanical interlocking A-24

Accessories A-25

Installation recommendations B-1Dimensions and connection C-1Electrical diagrams D-1Additional characteristics E-1Catalogue numbers and order form F-1

EasyPact MVS

Page 12: Low Voltage EasyPact MVS

A-2

Functionsand characteristics

General overviewDetailed contents

This overview describes all the functions offered byEasyPact MVS devices.

Circuit breakers and switch-disconnectors page A-4 ■ Ratings: ■ EasyPact MVS 800 to 4000 A ■ Circuit breakers type H ■ Switch-disconnectors type HA ■ 3 or 4 poles ■ Fixed or drawout versions

ET trip system page A-8 ■ 2I basic protection ■ 5S selective protection ■ 6G selective + earth-fault protection ■ Standard long-time rating plug: □ Current setting (A) 0.4 to 1 x In

ETA trip system with current measurement page A-10 ■ 2I basic protection ■ 5S selective protection ■ 6G selective + earth-fault protection ■ Standard long-time rating plug: □ Current setting (A) 0.4 to 1 x In ■ External power-supply module

ETV trip system with voltage measurement page A-12 ■ 2I basic protection ■ 5S selective protection ■ 6G selective + earth-fault protection ■ Standard long-time rating plug: □ Current setting (A) 0.4 to 1 x In ■ External power-supply module

Connections page A-15 ■ Rear connection: □ Horizontal □ Vertical ■ Optional accessories: □ Interphase barriers □ Safety shutters and shutter locking blocks

Locking page A-18 ■ Pushbutton locking by padlockable transparent cover

■ OFF-position locking by keylock ■ Chassis locking in disconnected position by keylock

■ Chassis locking in connected, disconnected and test positions

■ Door interlock (inhibits door opening with breaker in ‘connected’ or ‘test’ position

CP

B10

0000

CD

B50

0000

ET2I trip system. ET5S trip system. ET6G trip system.

CD

B50

0001

CD

B50

0002

short time

long timealarm

test

.4.5.6

.7 .8 .9.95.98

1

Ir

x In .512

48

121620

tr(s)

at 6 Ir24

x Ir

22.5

3 4 568

10

Isd

1.5

ET6G Trip System

alarm

Ir

(s)

long time

instantaneous

ET2I Trip System

short time

on I2t

.2

.3.4 .4

.1

.2

.10

long timealarm

4

test

.4.5.6

.7 .8 .9.95.98

1

Ir

x In .512

48

121620

tr(s)

at 6 Ir24

x Ir

22.5

3 4 568

10

Isd

1.5

tsd(s)

x In

3

6 8 101215

off2

.3instantaneous

I i

ET6G Trip System

alarm

Ir

on off off

(s)

(s)

long time

short time instantaneous

ET5S Trip System

delay

short time

on I2t

.2

.3.4 .4

.1

.2

.10

long timealarm

ground fault

setting

4

test

.4.5.6

.7 .8 .9.95.98

1

Ir

x In .512

48

121620

tr(s)

at 6 Ir24

x Ir

22.5

3 4 568

10

Isd

1.5

tsd(s)

x In

3

6 8 101215

off2

BC

D E FGH

I

Ig

Aon I2t

.2

.3.4 .4

.1

.2.3

.10off

tg(s)

.3instantaneous

I i

ET6G Trip System

alarm

Ir

ground fault

test

on off

on off off

(s)

(s)

(s)

long time

short time instantaneous

ET6G Trip System

DB

1011

09

Door interlock

DB

1011

10

Chassis key lock

E46

459

Safety shutters

DB

1011

49

Interphase barriers

Page 13: Low Voltage EasyPact MVS

A-3

Indication contacts page A-20 ■ Standard: □ ON/OFF indication (OF) □ “Fault” trip indication (SDE) ■ Optional: □ Additional ON/OFF indication (OF) □ Ready-to-close contact (PF) □ Carriage switches for connected (CE) disconnected (CD) and test (CT) positions

Remote operation page A-21 ■ Remote ON/OFF: □ Gear motor □ XF closing or MX opening voltage releases

■ Remote tripping function: □ MN voltage release - Standard - Adjustable or non-adjustable

delay

Accessories page A-25 ■ Auxiliary terminal shield ■ Operation counter ■ Escutcheon (Door sealing frame) ■ Transparent cover for escutcheon ■ Escutcheon blanking plate

Source-changeover systems page A-24 ■ Mechanical interlocking using cables: □ Interlocking between two devices □ Interlocking between three devices

PB

1043

54A

40C

PB

1000

03C

PB

1000

15C

PB

1000

16

DB

1011

13

Gear motor

DB

1011

14

MX, XF and MN volagereleases

E46

438

DB

1011

12

Ready-to-close contact

OF contact

CD

B50

0053

Interlocking of two devices

E46

669

E46

668

DB

1011

15

Mechanical operation counter

Escutcheon Transparent cover

Page 14: Low Voltage EasyPact MVS

A-4

Functionsand characteristics

Circuit breakersand switch-disconnectorsMVS08 to MVS40

Common characteristicsNumber of poles 3/4Rated insulation voltage (V) Ui 1000Impulse withstand voltage (kV) Uimp 12Rated operational voltage (V AC 50/60 Hz) Ue 690Suitability for isolation IEC 60947-2 YesDegree of pollution IEC 60664-1 4

Basic circuit-breaker MVS08 MVS10 MVS12 MVS16 MVS20 MVS25 MVS32 MVS40Circuit-breaker as per IEC 60947-2Rated current (A) In at 40°C/ 50°C (1) 800 1000 1250 1600 2000 2500 3200 4000Rating of 4th pole (A) 800 1000 1250 1600 2000 2500 3200 4000Sensor ratings (A) 800 1000 1250 1600 2000 2500 3200 4000Type of circuit breaker H H H H H H H HUltimate breaking capacity (kA rms) Icu 220...440V 65 65 65 65 65 65 65 65V AC 50/60 Hz 690 V 50 50 50 50 50 50 50 50Rated service breaking capacity (kA rms) Ics % Icu 100% 100% 100% 100% 100% 100% 100% 100%Utilisation category B B B B B B B BRated short-time withstand current (kA rms) Icw 1s 220...440 V 65 65 65 65 65 65 65 65V AC 50/60 Hz 690V 50 50 50 50 50 50 50 50

3s 440/690V 36 36 36 36 36 36 36 36Rated making capacity (kA peak) Icm 220...440 V 143 143 143 143 143 143 143 143V AC 50/60 Hz 690 V 105 105 105 105 105 105 105 105Breaking time (ms) between tripping order and arc extinction 25 25 25 25 25 25 25 25Closing time (ms) <70 <70 <70 <70 <70 <70 <70 <70

Switch-disconnector as per IEC60947-3 and Annex A MVS08 MVS10 MVS12 MVS16 MVS20 MVS25 MVS32 MVS40Type of switch-disconnector HA HA HA HA HA HA HA HAOperational current AC23A 800 1000 1250 1600 2000 2500 3200 4000Rated making capacity (kA peak) Icm 143 143 143 143 143 143 143 143Rated short-time withstand current (kA rms) Icw 1s 65 65 65 65 65 65 65 65

3s 36 36 36 36 36 36 36 36

Maintenance/Connection/InstallationService life Mechanical with maintenance 20 20 20 20 20 20 20 20C/O cyclesx1000 without maintenance 10 10 10 10 10 10 10 10

Electrical without maintenance 440 V 6000 6000 6000 6000 6000 5000 5000 5000690 V 4000 4000 4000 4000 4000 2500 2500 2500

Connection Horizontal YesVertical Yes

Dimensions (mm) Drawout 3P 439 x 441 x 395(H x W x D) 4P 439 x 556 x 395

Fixed 3P 352 x 422 x 2974P 352 x 537 x 297

Weight (kg) (approximate)

Drawout 3P/4P 70/85 90/120Fixed 3P/4P 40/50 60/80

CP

B10

0000

CP

B10

0014

Circuit breaker.

Switch disconnector.

(1) 50ºC Rear Vertical Connections, Refer page no. B-11 for details on temperature derating.

Page 15: Low Voltage EasyPact MVS

A-5

Common characteristicsNumber of poles 3/4Rated insulation voltage (V) Ui 1000Impulse withstand voltage (kV) Uimp 12Rated operational voltage (V AC 50/60 Hz) Ue 690Suitability for isolation IEC 60947-2 YesDegree of pollution IEC 60664-1 4

Basic circuit-breaker MVS08 MVS10 MVS12 MVS16 MVS20 MVS25 MVS32 MVS40Circuit-breaker as per IEC 60947-2Rated current (A) In at 40°C/ 50°C (1) 800 1000 1250 1600 2000 2500 3200 4000Rating of 4th pole (A) 800 1000 1250 1600 2000 2500 3200 4000Sensor ratings (A) 800 1000 1250 1600 2000 2500 3200 4000Type of circuit breaker H H H H H H H HUltimate breaking capacity (kA rms) Icu 220...440V 65 65 65 65 65 65 65 65V AC 50/60 Hz 690 V 50 50 50 50 50 50 50 50Rated service breaking capacity (kA rms) Ics % Icu 100% 100% 100% 100% 100% 100% 100% 100%Utilisation category B B B B B B B BRated short-time withstand current (kA rms) Icw 1s 220...440 V 65 65 65 65 65 65 65 65V AC 50/60 Hz 690V 50 50 50 50 50 50 50 50

3s 440/690V 36 36 36 36 36 36 36 36Rated making capacity (kA peak) Icm 220...440 V 143 143 143 143 143 143 143 143V AC 50/60 Hz 690 V 105 105 105 105 105 105 105 105Breaking time (ms) between tripping order and arc extinction 25 25 25 25 25 25 25 25Closing time (ms) <70 <70 <70 <70 <70 <70 <70 <70

Switch-disconnector as per IEC60947-3 and Annex A MVS08 MVS10 MVS12 MVS16 MVS20 MVS25 MVS32 MVS40Type of switch-disconnector HA HA HA HA HA HA HA HAOperational current AC23A 800 1000 1250 1600 2000 2500 3200 4000Rated making capacity (kA peak) Icm 143 143 143 143 143 143 143 143Rated short-time withstand current (kA rms) Icw 1s 65 65 65 65 65 65 65 65

3s 36 36 36 36 36 36 36 36

Maintenance/Connection/InstallationService life Mechanical with maintenance 20 20 20 20 20 20 20 20C/O cyclesx1000 without maintenance 10 10 10 10 10 10 10 10

Electrical without maintenance 440 V 6000 6000 6000 6000 6000 5000 5000 5000690 V 4000 4000 4000 4000 4000 2500 2500 2500

Connection Horizontal YesVertical Yes

Dimensions (mm) Drawout 3P 439 x 441 x 395(H x W x D) 4P 439 x 556 x 395

Fixed 3P 352 x 422 x 2974P 352 x 537 x 297

Weight (kg) (approximate)

Drawout 3P/4P 70/85 90/120Fixed 3P/4P 40/50 60/80

Page 16: Low Voltage EasyPact MVS

A-6

Functionsand characteristics

Identifying ET range of trip system

EasyPact MVS circuit breakers equipped with ET range of trip system are designed to protect power circuit and connected loads.Measurement of current and voltage helps users to maintain continuity of service and optimize installation.

DependabilityIntegration of protection functions in an ASIC electronic component used in all trip units guarantees a high degree of reliability and immunity to conducted or radiated disturbances.On ET range, measurement functions are managed by an independent microprocessor. Protection functions are independent of measurement functions, ensure system protection even at very low load currents.

AccessoriesCertain functions require the addition of trip unit accessories, described on page A-14.

DB

1011

16

CP

B10

0011

DB

1011

17D

B10

1117

Trip unit name codesType of protection

■ 2I for basic protection ■ 5S for selective protection ■ 6G for selective + earth-fault protection

Type of measurement ■ ET for basic ■ ETA for “Current” ■ ETV for “Current” and “Voltage”

ET2I: basic protection

Protection:long time+ instantaneous

2I

CD

B50

0000

short time

long timealarm

test

.4.5.6

.7 .8 .9.95.98

1

Ir

x In .512

48

121620

tr(s)

at 6 Ir24

x Ir

22.5

3 4 568

10

Isd

1.5

ET6G Trip System

alarm

Ir

(s)

long time

instantaneous

ET2I Trip System 2I

CD

B50

0028

long timealarm

ground fault

4

.4.5.6

.7 .8 .9.95.98

1

Ir

x In .512

48

121620

tr(s)

at 6 Ir24

x In

3

6 8 101215

off2

instantaneousI i

alarm

off

(s)

long time

instantaneous

ETA2I

Ir

2I

long timealarm

4

test

.4.5.6

.7 .8 .9.95.98

1

Ir

x In .512

48

121620

tr(s)

at 6 Ir24

x In

3

6 8 101215

off2

instantaneousI i

alarm

Ir

test

off

(s)

long time

instantaneous

2I

CD

B50

0035

ET5S: selective protection

Protection:long time+ short time+ instantaneous

5S

CD

B50

0001

short time

on I2t

.2

.3.4 .4

.1

.2

.10

long timealarm

4

test

.4.5.6

.7 .8 .9.95.98

1

Ir

x In .512

48

121620

tr(s)

at 6 Ir24

x Ir

22.5

3 4 568

10

Isd

1.5

tsd(s)

x In

3

6 8 101215

off2

.3instantaneous

I i

ET6G Trip System

alarm

Ir

on off off

(s)

(s)

long time

short time instantaneous

ET5S Trip System 5S

CD

B50

0029

short time

on I2t

.2

.3.4 .4

.1

.2

.10

long timealarm

ground fault

4

test

.4.5.6

.7 .8 .9.95.98

1

Ir

x In .512

48

121620

tr(s)

at 6 Ir24

x Ir

22.5

3 4 568

10

Isd

1.5

tsd(s)

x In

3

6 8 101215

off2

.3instantaneous

I i

alarm

Ir

on off off

(s)

(s)

long time

short time instantaneous

ETA5S 5S

CD

B50

0030

short time

on I2t

.2

.3.4 .4

.1

.2

.10

long timealarm

4

test

.4.5.6

.7 .8 .9.95.98

1

Ir

x In .512

48

121620

tr(s)

at 6 Ir24

x Ir

22.5

3 4 568

10

Isd

1.5

tsd(s)

x In

3

6 8 101215

off2

.3instantaneous

I i

alarm

Ir

on off off

(s)

(s)

long time

short time instantaneous

ETV5S

ET6G: selective + earth-fault protection

DB

1011

18

Protection:long time+ short time+ instantaneous+ earth fault

6G

CD

B50

0002

delay

short time

on I2t

.2

.3.4 .4

.1

.2

.10

long timealarm

ground fault

setting

4

test

.4.5.6

.7 .8 .9.95.98

1

Ir

x In .512

48

121620

tr(s)

at 6 Ir24

x Ir

22.5

3 4 568

10

Isd

1.5

tsd(s)

x In

3

6 8 101215

off2

BC

D E FGH

I

Ig

Aon I2t

.2

.3.4 .4

.1

.2.3

.10off

tg(s)

.3instantaneous

I i

ET6G Trip System

alarm

Ir

ground fault

test

on off

on off off

(s)

(s)

(s)

long time

short time instantaneous

ET6G Trip System 6G

CD

B50

0003

delay

short time

on I2t

.2

.3.4 .4

.1

.2

.10

long timealarm

ground fault

setting

4

test

.4.5.6

.7 .8 .9.95.98

1

Ir

x In .512

48

121620

tr(s)

at 6 Ir24

x Ir

22.5

3 4 568

10

Isd

1.5

tsd(s)

x In

3

6 8 101215

off2

BC

D E FGH

I

Ig

Aon I2t

.2

.3.4 .4

.1

.2.3

.10off

tg(s)

.3instantaneous

I i

alarm

Ir

ground fault

test

on off

on off off

(s)

(s)

(s)

long time

short time instantaneous

6G

CD

B50

0004

delay

short time

on I2t

.2

.3.4 .4

.1

.2

.10

long timealarm

ground fault

setting

4

test

.4.5.6

.7 .8 .9.95.98

1

Ir

x In .512

48

121620

tr(s)

at 6 Ir24

x Ir

22.5

3 4 568

10

Isd

1.5

tsd(s)

x In

3

6 8 101215

off2

BC

D E FGH

I

Ig

Aon I2t

.2

.3.4 .4

.1

.2.3

.10off

tg(s)

.3instantaneous

I i

alarm

Ir

ground fault

test

on off

on off off

(s)

(s)

(s)

long time

short time instantaneous

Page 17: Low Voltage EasyPact MVS

A-7

Protection and measurement functionsET ETA ETV

■ Fault indications ■ Settings in amperes and in seconds

■ I1, I2, I3, IN, Iearth-fault, and maximeter for these measurements:

□ Fault indications □ Settings in amperes and in seconds

■ Incorporates all the rms measurements of ETA trip unit, plus voltage readings:

□ Calculates the current demand value □ “Quickview” function for the automatic cyclical display of the most useful values

ET2I: basic protection

Protection:long time+ instantaneous

2I

CD

B50

0000

short time

long timealarm

test

.4.5.6

.7 .8 .9.95.98

1

Ir

x In .512

48

121620

tr(s)

at 6 Ir24

x Ir

22.5

3 4 568

10

Isd

1.5

ET6G Trip System

alarm

Ir

(s)

long time

instantaneous

ET2I Trip System 2I

CD

B50

0028

long timealarm

ground fault

4

.4.5.6

.7 .8 .9.95.98

1

Ir

x In .512

48

121620

tr(s)

at 6 Ir24

x In

3

6 8 101215

off2

instantaneousI i

alarm

off

(s)

long time

instantaneous

ETA2I

Ir

2I

long timealarm

4

test

.4.5.6

.7 .8 .9.95.98

1

Ir

x In .512

48

121620

tr(s)

at 6 Ir24

x In

3

6 8 101215

off2

instantaneousI i

alarm

Ir

test

off

(s)

long time

instantaneous

2I

CD

B50

0035

ET5S: selective protection

Protection:long time+ short time+ instantaneous

5S

CD

B50

0001

short time

on I2t

.2

.3.4 .4

.1

.2

.10

long timealarm

4

test

.4.5.6

.7 .8 .9.95.98

1

Ir

x In .512

48

121620

tr(s)

at 6 Ir24

x Ir

22.5

3 4 568

10

Isd

1.5

tsd(s)

x In

3

6 8 101215

off2

.3instantaneous

I i

ET6G Trip System

alarm

Ir

on off off

(s)

(s)

long time

short time instantaneous

ET5S Trip System 5S

CD

B50

0029

short time

on I2t

.2

.3.4 .4

.1

.2

.10

long timealarm

ground fault

4

test

.4.5.6

.7 .8 .9.95.98

1

Ir

x In .512

48

121620

tr(s)

at 6 Ir24

x Ir

22.5

3 4 568

10

Isd

1.5

tsd(s)

x In

3

6 8 101215

off2

.3instantaneous

I i

alarm

Ir

on off off

(s)

(s)

long time

short time instantaneous

ETA5S 5SC

DB

5000

30

short time

on I2t

.2

.3.4 .4

.1

.2

.10

long timealarm

4

test

.4.5.6

.7 .8 .9.95.98

1

Ir

x In .512

48

121620

tr(s)

at 6 Ir24

x Ir

22.5

3 4 568

10

Isd

1.5

tsd(s)

x In

3

6 8 101215

off2

.3instantaneous

I i

alarm

Ir

on off off

(s)

(s)

long time

short time instantaneous

ETV5S

ET6G: selective + earth-fault protection

DB

1011

18

Protection:long time+ short time+ instantaneous+ earth fault

6G

CD

B50

0002

delay

short time

on I2t

.2

.3.4 .4

.1

.2

.10

long timealarm

ground fault

setting

4

test

.4.5.6

.7 .8 .9.95.98

1

Ir

x In .512

48

121620

tr(s)

at 6 Ir24

x Ir

22.5

3 4 568

10

Isd

1.5

tsd(s)

x In

3

6 8 101215

off2

BC

D E FGH

I

Ig

Aon I2t

.2

.3.4 .4

.1

.2.3

.10off

tg(s)

.3instantaneous

I i

ET6G Trip System

alarm

Ir

ground fault

test

on off

on off off

(s)

(s)

(s)

long time

short time instantaneous

ET6G Trip System 6G

CD

B50

0003

delay

short time

on I2t

.2

.3.4 .4

.1

.2

.10

long timealarm

ground fault

setting

4

test

.4.5.6

.7 .8 .9.95.98

1

Ir

x In .512

48

121620

tr(s)

at 6 Ir24

x Ir

22.5

3 4 568

10

Isd

1.5

tsd(s)

x In

3

6 8 101215

off2

BC

D E FGH

I

Ig

Aon I2t

.2

.3.4 .4

.1

.2.3

.10off

tg(s)

.3instantaneous

I i

alarm

Ir

ground fault

test

on off

on off off

(s)

(s)

(s)

long time

short time instantaneous

6G

CD

B50

0004

delay

short time

on I2t

.2

.3.4 .4

.1

.2

.10

long timealarm

ground fault

setting

4

test

.4.5.6

.7 .8 .9.95.98

1

Ir

x In .512

48

121620

tr(s)

at 6 Ir24

x Ir

22.5

3 4 568

10

Isd

1.5

tsd(s)

x In

3

6 8 101215

off2

BC

D E FGH

I

Ig

Aon I2t

.2

.3.4 .4

.1

.2.3

.10off

tg(s)

.3instantaneous

I i

alarm

Ir

ground fault

test

on off

on off off

(s)

(s)

(s)

long time

short time instantaneous

Page 18: Low Voltage EasyPact MVS

A-8

Functionsand characteristics

Overview of functionsET trip system

ProtectionProtection thresholds and delays are set using the adjustment dials.Overload protectionTrue rms long-time protection.Protects cables (phase and neutral) against overloadsThermal memory(1): thermal image before and after tripping.Short-time protection

■ The short-time protection function protects the distribution system against impedant short-circuits

■ The short-time tripping delay can be used to ensure discrimination with downstream circuit breaker

■ The I2t ON and I2t OFF options enhance discrimination with a downstream protection devices

■ Use of I2t curves with short-time protection: □ I2t OFF selected: the protection function implements a constant time curve □ I2t ON selected: the protection function implements an I2t inverse-time curve up to 10 lr. Above 10 lr, the time curve is constant

Earth-fault protection on ET6G trip systemResidual earth fault protection.Selection of I2t type (ON or OFF) for delay.A ground fault in the protection conductors can provoke local temperature rise at the site of the fault or in the conductors. The purpose of the ground-fault protection function is to eliminate this type of fault.Type DescriptionResidual ■ The function determines the zero-phase sequence current, i.e. the

vectorial sum of the phase and neutral currents ■ It detects faults downstream of the circuit breaker

Instantaneous protectionThe Instantaneous-protection function protects the distribution system against solid short-circuits. Contrary to the short-time protection function, the tripping delay for instantaneous protection is not adjustable. The tripping order is sent to the circuit breaker as soon as current exceeds the set value, with a fi xed time delay of 20 milliseconds.Neutral protectionOn three-pole circuit breakers, neutral protection is not possible.On four-pole circuit breakers, neutral protection may be set using a three-positionswitch: neutral unprotected (4P 3d), neutral protection at 0.5 Ir (4P 3d + N/2), neutralprotection at Ir (4P 4d).Zone selective interlocking (ZSI)A ZSI(2) terminal block may be used to interconnect a number of control units to provide total discrimination for short-time and earth-fault protection, without a delay before tripping.

Overload alarmA yellow alarm LED goes on when the current exceeds the long-time trip threshold.

Fault indicationsLEDs indicate the type of fault:

■ Overload (long-time protection Ir) ■ Short-circuit (short-time Isd or instantaneous li protection) ■ Earth fault (Ig) ■ Internal fault (Ap)

Battery powerThe fault indicating LEDs are powered by an in-built battery. The fault indication LEDs remain on until the test/reset button is pressed.

TestA hand-held test kit may be connected to the test connector on the front to check circuit-breaker operation. For ET6G trip unit, the operation of earth-fault protection can be checked by pressing the test button located above the test connector.

Note: ET trip control units come with a transparent leadseal cover as standard.

delay

short time

on I2t

.2

.3.4 .4

.1

.2

.10

long timealarm

ground fault

setting

4

test

.4.5.6

.7 .8 .9.95.98

1

Ir

x In .512

48

121620

tr(s)

at 6 Ir24

x Ir

22.5

3 4 568

10

Isd

1.5

tsd(s)

x In

3

6 8 101215

off2

BC

D E FGH

I

Ig

Aon I2t

.2

.3.4 .4

.1

.2.3

.10off

tg(s)

.3instantaneous

I i

ET6G Trip System

alarm

Ir

ground fault

test

on off

on off off

(s)

(s)

(s)

long time

short time instantaneous

ET6G Trip System

CD

B50

0002

1 Long-time threshold and tripping delay.2 Overload alarm (LED) at 1,125 Ir.3 Short-time pick-up and tripping delay.4 Instantaneous pick-up.5 Earth-fault pick-up and tripping delay.6 Earth-fault test button.7 Long-time rating plug screw.8 Test connector.9 Lamp test, reset and battery test.10 Indication of tripping cause.

7

(1) The thermal memory continuously accounts for the amount of heat in the cables , both before and after tripping , whatever the value of the current(presence of an overload or not).The thermal memory optimises the long-time protection function of the circuit breaker by taking into account the temperature rise in the cables .The thermal memory assumes a cable cooling time of approximately 20 minutes.(2) Refer to page D-5 for more details on ZSI.

ET trip unit protect power circuits, under overload & short-circuit conditions. They are equipped with individual fault trip indication LEDs. ET6G provides earth-fault protection.

Page 19: Low Voltage EasyPact MVS

A-9

Protection ET2ILong time ET2I

DB

1011

26

Current setting (A) Ir = In x ... 0.4 0.5 0.6 0.7 0.8 0.9 0.95 0.98 1Tripping between 1.05 and 1.20 x IrTime setting tr (s) 0.5 1 2 4 8 12 16 20 24Time delay (s) Accuracy: 0 to -30 % 1.5 x Ir 12.5 25 50 100 200 300 400 500 600

Accuracy: 0 to -20 % 6 x Ir 0.7(1) 1 2 4 8 12 16 20 24Accuracy: 0 to -20 % 7.2 x Ir 0.7(2) 0.69 1.38 2.7 5.5 8.3 11 13.8 16.6

Thermal memory 20 minutes before and after tripping(1) 0 to -40 % - (2) 0 to -60 %InstantaneousPick-up (A) Isd = Ir x … 1.5 2 2.5 3 4 5 6 8 10Accuracy: ±10 %Time delay Max resettable time: 20 ms

Max break time: 80 ms

Protection ET5S/ET6GLong time ET5S/ET6G

DB

1011

27

Current setting (A) Ir = In x … 0.4 0.5 0.6 0.7 0.8 0.9 0.95 0.98 1Tripping between 1.05 and 1.20 x IrTime setting tr (s) 0.5 1 2 4 8 12 16 20 24Time delay (s) Accuracy: 0 to -30 % 1.5 x Ir 12.5 25 50 100 200 300 400 500 600

Accuracy: 0 to -20 % 6 x Ir 0.7(1) 1 2 4 8 12 16 20 24Accuracy: 0 to -20 % 7.2 x Ir 0.7(2) 0.69 1.38 2.7 5.5 8.3 11 13.8 16.6

Thermal memory 20 minutes before and after tripping(1) 0 to -40 % - (2) 0 to -60 %Short timePick-up (A) Isd = Ir x … 1.5 2 2.5 3 4 5 6 8 10Accuracy: ±10 %Time setting tsd (s) Settings I2t Off 0 0.1 0.2 0.3 0.4

I2t On - 0.1 0.2 0.3 0.4Time delay (ms) at 10 x Ir tsd (max resettable time) 20 80 140 230 350(I2t Off or I2t On) tsd (max break time) 80 140 200 320 500InstantaneousPick-up (A) Ii = In x … 2 3 4 6 8 10 12 15 offAccuracy: ±10 %Time delay Max resettable time: 20 ms

Max break time: 50 msEarth fault ET6G

DB

1011

28

Pick-up (A) Ig = In x … A B C D E F G H JAccuracy: ±10 % In ≤ 400 A 0.3 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1

400 A < In ≤ 1000 A 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1In ≥ 1250 A 500 640 720 800 880 960 1040 1120 1200

Time setting tg (s) Settings I2t Off 0 0.1 0.2 0.3 0.4I2t On - 0.1 0.2 0.3 0.4

Time delay (ms) tg (max resettable time) 20 80 140 230 350at In or 1200 A (I2t Off or I2t On) tg (max break time) 80 140 200 320 500Note: All current-based protection functions require no auxiliary source.The test / reset button, clears the tripping indication and tests the battery.

Page 20: Low Voltage EasyPact MVS

A-10

Functionsand characteristics

Overview of functionsETA trip system

“Ammeter” measurementsETA trip units measure the true (rms) value of currents.They provide continuous current measurements from 0.2 to 1.2 In and are accurateto within 1.5 % (including the sensors).A digital LCD screen continuously displays the most heavily loaded phase (Imax) ordisplays the I1, I2, I3, IN, Ig, stored-current (maximeter) and setting values bysuccessively pressing the navigation button.The optional external power supply makes it possible to display currents < 20 % In.Below 0.1 In, measurements are not signifi cant. Between 0.1 and 0.2 In, accuracychanges linearly from 4 % to 1.5 %.

ProtectionProtection thresholds and delays are set using the adjustment dials.Overload protectionTrue rms long-time protection.Protects cables (phase and neutral) against overloadsThermal memory(1): thermal image before and after tripping.Short-time protection

■ The short-time protection function protects the distribution system against impedant short-circuits

■ The short-time tripping delay can be used to ensure discrimination with downstream circuit breaker

■ The I2t ON and I2t OFF options enhance discrimination with a downstream protection devices

■ Use of I2t curves with short-time protection: □ I2t OFF selected: the protection function implements a constant time curve □ I2t ON selected: the protection function implements an I2t inverse-time curve up to 10 lr. Above 10 lr, the time curve is constant

Earth-fault protection on ETA6G trip systemResidual earth fault protection.Selection of I2t type (ON or OFF) for delay.A ground fault in the protection conductors can provoke local temperature rise at the site of the fault or in the conductors. The purpose of the ground-fault protection function is to eliminate this type of fault.Type DescriptionResidual ■ The function determines the zero-phase sequence current, i.e. the

vectorial sum of the phase and neutral currents ■ It detects faults downstream of the circuit breaker

Instantaneous protectionThe Instantaneous-protection function protects the distribution system against solid short-circuits. Contrary to the short-time protection function, the tripping delay for instantaneous protection is not adjustable. The tripping order is sent to the circuit breaker as soon as current exceeds the set value, with a fi xed time delay of 20 milliseconds.Neutral protectionOn three-pole circuit breakers, neutral protection is not possible.On four-pole circuit breakers, neutral protection may be set using a three-positionswitch: neutral unprotected (4P 3d), neutral protection at 0.5 Ir (4P 3d + N/2), neutralprotection at Ir (4P 4d).Zone selective interlocking (ZSI)A ZSI(2) terminal block may be used to interconnect a number of control units to provide total discrimination for short-time and earth-fault protection, without a delay before tripping.

Overload alarmA yellow alarm LED goes on when the current exceeds the long-time trip threshold.

Fault indicationsLEDs indicate the type of fault:

■ Overload (long-time protection Ir) ■ Short-circuit (short-time Isd or instantaneous li protection) ■ Earth fault (Ig) ■ Internal fault (Ap)

Battery powerThe fault indicating LEDs are powered by an in-built battery. The fault indication LEDs remain on until the test/reset button is pressed.

TestA hand-held test kit may be connected to the test connector on the front to check circuit-breaker operation. For ETA6G trip unit, the operation of earth-fault protection can be checked by pressing the test button located above the test connector.

CD

B50

0003

ETA trip units include all functions offered by ET trip unit. In addition, they also offer measurements, display and current maximeters.

1 Long-time threshold and tripping delay.2 Overload alarm (LED) at 1,125 Ir.3 Short-time pick-up and tripping delay.4 Instantaneous pick-up.5 Earth-fault pick-up and tripping delay.6 Earth-fault test button.7 Long-time rating plug screw.8 Test connector.9 Lamp test, reset and battery test.10 Indication of tripping cause.11 Digital display.12 Three-phase bargraph and ammeter.13 Navigation button to view menu contents.14 Navigation button to change menu.

Note: ETA trip units come with a transparent leadseal cover as standard.

delay

short time

on I2t

.2

.3.4 .4

.1

.2

.10

long timealarm

ground fault

setting

4

test

.4.5.6

.7 .8 .9.95.98

1

Ir

x In .512

48

121620

tr(s)

at 6 Ir24

x Ir

22.5

3 4 568

10

Isd

1.5

tsd(s)

x In

3

6 8 101215

off2

BC

D E FGH

I

Ig

Aon I2t

.2

.3.4 .4

.1

.2.3

.10off

tg(s)

.3instantaneous

I i

alarm

Ir

ground fault

test

on off

on off off

(s)

(s)

(s)

long time

short time instantaneous

7

1314

(1) The thermal memory continuously accounts for the amount of heat in the cables , both before and after tripping , whatever the value of the current(presence of an overload or not).The thermal memory optimises the long-time protection function of the circuit breaker by taking into account the temperature rise in the cables .The thermal memory assumes a cable cooling time of approximately 20 minutes.(2) Refer to page D-5 for more details on ZSI.

Page 21: Low Voltage EasyPact MVS

A-11

Protection ETA2ILong time ETA2I

DB

1011

26

Current setting (A) Ir = In x ... 0.4 0.5 0.6 0.7 0.8 0.9 0.95 0.98 1Tripping between 1.05 and 1.20 x IrTime setting tr (s) 0.5 1 2 4 8 12 16 20 24Time delay (s) Accuracy: 0 to -30 % 1.5 x Ir 12.5 25 50 100 200 300 400 500 600

Accuracy: 0 to -20 % 6 x Ir 0.7(1) 1 2 4 8 12 16 20 24Accuracy: 0 to -20 % 7.2 x Ir 0.7(2) 0.69 1.38 2.7 5.5 8.3 11 13.8 16.6

Thermal memory 20 minutes before and after tripping(1) 0 to -40 % - (2) 0 to -60 %InstantaneousPick-up (A) Isd = Ir x … 1.5 2 2.5 3 4 5 6 8 10Accuracy: ±10 %Time delay Max resettable time: 20 ms

Max break time: 80 ms

Protection ETA5S/ETA6GLong time ETA5S/ETA6G

DB

1011

27

Current setting (A) Ir = In x … 0.4 0.5 0.6 0.7 0.8 0.9 0.95 0.98 1Tripping between 1.05 and 1.20 x IrTime setting tr (s) 0.5 1 2 4 8 12 16 20 24Time delay (s) Accuracy: 0 to -30 % 1.5 x Ir 12.5 25 50 100 200 300 400 500 600

Accuracy: 0 to -20 % 6 x Ir 0.7(1) 1 2 4 8 12 16 20 24Accuracy: 0 to -20 % 7.2 x Ir 0.7(2) 0.69 1.38 2.7 5.5 8.3 11 13.8 16.6

Thermal memory 20 minutes before and after tripping(1) 0 to -40 % - (2) 0 to -60 %Short timePick-up (A) Isd = Ir x … 1.5 2 2.5 3 4 5 6 8 10Accuracy: ±10 %Time setting tsd (s) Settings I2t Off 0 0.1 0.2 0.3 0.4

I2t On - 0.1 0.2 0.3 0.4Time delay (ms) at 10 x Ir tsd (max resettable time) 20 80 140 230 350(I2t Off or I2t On) tsd (max break time) 80 140 200 320 500InstantaneousPick-up (A) Ii = In x … 2 3 4 6 8 10 12 15 offAccuracy: ±10 %Time delay Max resettable time: 20 ms

Max break time: 50 msEarth fault ETA6G

DB

1011

28

Pick-up (A) Ig = In x … A B C D E F G H JAccuracy: ±10 % In ≤ 400 A 0.3 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1

400 A < In ≤ 1000 A 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1In ≥ 1250 A 500 640 720 800 880 960 1040 1120 1200

Time setting tg (s) Settings I2t Off 0 0.1 0.2 0.3 0.4I2t On - 0.1 0.2 0.3 0.4

Time delay (ms) tg (max resettable time) 20 80 140 230 350at In or 1200 A (I2t Off or I2t On) tg (max break time) 80 140 200 320 500

Ammeter ETA2I/ETA5S/ETA6GType of measurements Range AccuracyInstantaneous currents I1, I2, I3, In 0.2 x In to 1.2 x In ± 1.5 %

Ig (ETA6G) 0.2 x In to In ± 10 %Current maximeters of I1, I2, I3, In 0.2 x In to 1.2 x In ± 1.5 %Note: All current-based protection functions require no auxiliary source.The test / reset button resets maximeters, clears the tripping indication and tests the battery.

Page 22: Low Voltage EasyPact MVS

A-12

Functionsand characteristics

Overview of functionsETV trip system

“Voltage meter” measurementsIn addition to the ammeter measurements of ETAETV trip units measure and display:

■ Current demand ■ Voltages: phase to phase, phase to neutral, average and unbalanced

The range of measurement is the same as current with ETA, depending of an external power supply module.

ProtectionProtection thresholds and delays are set using the adjustment dials.Overload protectionTrue rms long-time protection.Protects cables (phase and neutral) against overloadsThermal memory(1): thermal image before and after tripping.Short-time protection

■ The short-time protection function protects the distribution system against impedant short-circuits

■ The short-time tripping delay can be used to ensure discrimination with downstream circuit breaker

■ The I2t ON and I2t OFF options enhance discrimination with a downstream protection devices

■ Use of I2t curves with short-time protection: □ I2t OFF selected: the protection function implements a constant time curve □ I2t ON selected: the protection function implements an I2t inverse-time curve up to 10 lr. Above 10 lr, the time curve is constant

Earth-fault protection on ETV6G trip systemResidual or source ground return earth fault protection.Selection of I2t type (ON or OFF) for delay.A ground fault in the protection conductors can provoke local temperature rise at the site of the fault or in the conductors. The purpose of the ground-fault protection function is to eliminate this type of fault.Type DescriptionResidual ■ The function determines the zero-phase sequence current, i.e. the

vectorial sum of the phase and neutral currents ■ It detects faults downstream of the circuit breaker

Instantaneous protectionThe Instantaneous-protection function protects the distribution system against solid short-circuits. Contrary to the short-time protection function, the tripping delay for instantaneous protection is not adjustable. The tripping order is sent to the circuit breaker as soon as current exceeds the set value, with a fi xed time delay of 20 milliseconds.Neutral protectionOn three-pole circuit breakers, neutral protection is not possible.On four-pole circuit breakers, neutral protection may be set using a three-positionswitch: neutral unprotected (4P 3d), neutral protection at 0.5 Ir (4P 3d + N/2), neutralprotection at Ir (4P 4d).Zone selective interlocking (ZSI)A ZSI(2) terminal block may be used to interconnect a number of control units to provide total discrimination for short-time and earth-fault protection, without a delay before tripping.

Overload alarmA yellow alarm LED goes on when the current exceeds the long-time trip threshold.

Fault indicationsLEDs indicate the type of fault:

■ Overload (long-time protection Ir) ■ Short-circuit (short-time Isd or instantaneous li protection) ■ Earth fault (Ig) ■ Internal fault (Ap)

Trip historyThe trip history displays the list of the last 10 trips. For each trip, the following indications are recorded and displayed:

■ the tripping cause: Ir, Isd, Ii, Ig or Auto-protection (Ap) tripsBattery powerThe fault indicating LEDs are powered by an in-built battery. The fault indication LEDs remain on until the test/reset button is pressed.

TestA hand-held test kit may be connected to the test connector on the front to check circuit-breaker operation. For ETV6G trip unit, the operation of earth-fault protection can be checked by pressing the test button located above the test connector.

ETV trip units include all the functions offered by ETA.In addition, they measure voltage values.They also offer trip history & display tripping cause.

1 Long-time threshold and tripping delay.2 Overload alarm (LED) at 1,125 Ir.3 Short-time pick-up and tripping delay.4 Instantaneous pick-up.5 Earth-fault pick-up and tripping delay.6 Earth-fault test button.7 Long-time rating plug screw.8 Test connector.9 Lamp test, reset and battery test.10 Indication of tripping cause.11 Digital display.12 Three-phase bargraph and ammeter.13 Navigation button “quick View” (only with ETV).14 Navigation button to view menu contents.15 Navigation button to change menu.

Note: ETV trip units come with a transparent leadseal cover as standard.

delay

short time

on I2t

.2

.3.4 .4

.1

.2

.10

long timealarm

ground fault

setting

4

test

.4.5.6

.7 .8 .9.95.98

1

Ir

x In .512

48

121620

tr(s)

at 6 Ir24

x Ir

22.5

3 4 568

10

Isd

1.5

tsd(s)

x In

3

6 8 101215

off2

BC

D E FGH

I

Ig

Aon I2t

.2

.3.4 .4

.1

.2.3

.10off

tg(s)

.3instantaneous

I i

alarm

Ir

ground fault

test

on off

on off off

(s)

(s)

(s)

long time

short time instantaneous

CD

B50

0004

7

13

1415

(1) The thermal memory continuously accounts for the amount of heat in the cables , both before and after tripping , whatever the value of the current(presence of an overload or not).The thermal memory optimises the long-time protection function ofthe circuit breaker by taking into account the temperature rise in the cables .The thermal memory assumes a cable cooling time of approximately 20 minutes.(2) Refer to page D-5 for more details on ZSI.

Page 23: Low Voltage EasyPact MVS

A-13

Protection ETV2ILong time ETV2I

DB

1011

26

Current setting (A) Ir = In x ... 0.4 0.5 0.6 0.7 0.8 0.9 0.95 0.98 1Tripping between 1.05 and 1.20 x IrTime setting tr (s) 0.5 1 2 4 8 12 16 20 24Time delay (s) Accuracy: 0 to -30 % 1.5 x Ir 12.5 25 50 100 200 300 400 500 600

Accuracy: 0 to -20 % 6 x Ir 0.7(1) 1 2 4 8 12 16 20 24Accuracy: 0 to -20 % 7.2 x Ir 0.7(2) 0.69 1.38 2.7 5.5 8.3 11 13.8 16.6

Thermal memory 20 minutes before and after tripping(1) 0 to -40 % - (2) 0 to -60 %InstantaneousPick-up (A) Isd = Ir x … 1.5 2 2.5 3 4 5 6 8 10Accuracy: ±10 %Time delay Max resettable time: 20 ms

Max break time: 80 ms

Protection ETV5S/ETV6GLong time ETV5S/ETV6G

DB

1011

27

Current setting (A) Ir = In x … 0.4 0.5 0.6 0.7 0.8 0.9 0.95 0.98 1Tripping between 1.05 and 1.20 x IrTime setting tr (s) 0.5 1 2 4 8 12 16 20 24Time delay (s) Accuracy: 0 to -30 % 1.5 x Ir 12.5 25 50 100 200 300 400 500 600

Accuracy: 0 to -20 % 6 x Ir 0.7(1) 1 2 4 8 12 16 20 24Accuracy: 0 to -20 % 7.2 x Ir 0.7(2) 0.69 1.38 2.7 5.5 8.3 11 13.8 16.6

Thermal memory 20 minutes before and after tripping(1) 0 to -40 % - (2) 0 to -60 %Short timePick-up (A) Isd = Ir x … 1.5 2 2.5 3 4 5 6 8 10Accuracy: ±10 %Time setting tsd (s) Settings I2t Off 0 0.1 0.2 0.3 0.4

I2t On - 0.1 0.2 0.3 0.4Time delay (ms) at 10 x Ir tsd (max resettable time) 20 80 140 230 350(I2t Off or I2t On) tsd (max break time) 80 140 200 320 500InstantaneousPick-up (A) Ii = In x … 2 3 4 6 8 10 12 15 offAccuracy: ±10 %Time delay Max resettable time: 20 ms

Max break time: 50 msEarth fault ETV6G

DB

1011

28

Pick-up (A) Ig = In x … A B C D E F G H JAccuracy: ±10 % In ≤ 400 A 0.3 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1

400 A < In ≤ 1000 A 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1In ≥ 1250 A 500 640 720 800 880 960 1040 1120 1200

Time setting tg (s) Settings I2t Off 0 0.1 0.2 0.3 0.4I2t On - 0.1 0.2 0.3 0.4

Time delay (ms) tg (max resettable time) 20 80 140 230 350at In or 1200 A (I2t Off or I2t On) tg (max break time) 80 140 200 320 500

Energy ETV2I/5S/6GType of measurements Range AccuracyInstantaneous currents I1, I2, I3, In 0.2 x In to 1.2 x In ± 1.5 %

Ig (ETV6G) 0.2 x In to In ± 10 %Current maximeters of I1, I2, I3, In 0.2 x In to 1.2 x In ± 1.5 %Demand currents of I1, I2, I3, Ig 0.2 x In to 1.2 x In ± 1.5 %Voltages V12, V23, V31, V1N, V2N, V3N 100 to 690 V ± 0.5 %Note: All current-based protection functions require no auxiliary source.The test / reset button resets maximeters, clears the tripping indication and tests the battery.

Page 24: Low Voltage EasyPact MVS

A-14

Functionsand characteristics

ET range of trip systemAccessories and test equipment

External sensorsExternal sensor for earth-fault protectionThe sensors, used with the 3P circuit breakers, are installed on the neutral conductor for:

■ Residual type earth-fault protection (with 6G trip units)The rating of the sensor (CT) must be compatible with the rating of the circuit breaker:

■ MVS08 to MVS20: TC 400/2000 ■ MVS25 to MVS40: TC 1000/4000

Voltage measurement inputs(1)

As standard, the control unit is supplied by internal voltage measurement inputs placed downstream of the pole for voltages between 220 and 690 V AC.

External 24 V DC power-supply moduleThe external power-supply module makes it possible to use the display (ETA and ETV trip systems) even if the circuit breaker is open or not supplied (for the exact conditions of use, see the “electrical diagrams” part of this catalogue).Characteristics

■ Power supply: □ 110/130, 200/240, 380/415 V AC (+10 % -15 %) □ 24/30, 48/60, 100/125 V DC (+20 % -20 %) ■ Output voltage: 24 V DC ±5 %, 1 A ■ Ripple < 1 % ■ Dielectric withstand : 3.5 kV rms between input/output, for 1 minute ■ Overvoltage category: as per IEC 60947-1 cat. 4

Spare partsLead-seal coversA lead-seal cover controls access to the adjustment dials.When the cover is closed:

■ It is impossible to modify settings using the keypad unless the settings lockout pin on the cover is removed

■ The test connector remains accessible ■ The test button for the earth-fault protection function remains accessible

Characteristics ■ Transparent cover for all trip units

Spare batteryA battery supplies power to the LEDs identifying the tripping causes.The healthiness of the battery to be checked periodically. A test button on the front of the control unit is used to check the battery condition. The battery may be replaced on site when discharged.

Test equipmentHand-held test kitThe hand-held mini test kit may be used to:

■ Check operation of the control unit and the tripping and pole-opening system by sending a signal simulating a short-circuit

■ Power source: standard LR6-AA battery

DB

1015

24P

B10

0775

-32

CD

B50

0038

PB

1010

26-3

2A

External sensor (CT).

Lead-seal cover.

Hand-held test kit.

External 24 V DC power supply module.

(1) Refer to EasyPact MVS user manual on using 3 pole circuit breakers in 4 wire system with ETV trip system for voltage measurement.

Page 25: Low Voltage EasyPact MVS

A-15

ConnectionsOverview of solutions and accessories

Two types of connection are available: ■ Horizontal rear connection ■ Vertical rear connection

The solutions presented are similar in principle for allEasyPact MVS fi xed and drawout devices.

Rear connectionHorizontal

Vertical

Mixed

Simply turn a horizontal rear connector 90° to make it a vertical connector.

Interphase barriers EIPThese barriers are fl exible insulated partitions used to reinforce isolation ofconnection points in installations with busbars, whether insulated or not.For EasyPact MVS devices, they are installed vertically between rear connection terminals. They are not compatible with spreaders.

Safety shutters VOMounted on the chassis, the safety shutters automatically block access to thedisconnecting contact cluster when the device is in the disconnected or test positions(degree of protection IP 20) When the device is removed from its chassis, no liveparts are accessible.The shutter-locking system is made up of a moving block (optional device) that can be padlocked (padlock not supplied). The block:

■ Prevents connection of the device ■ Locks the shutters in the closed position

For EasyPact MVS08 to MVS40A support at the bottom of the chassis is used to store the blocks when they are not used:

■ 2 blocks for MVS08 to MVS40

Note: EasyPact MVS circuit breakers can be connected indifferently with bare-copper, tinned-copper and tinned-aluminium conductors, requiring no particular treatment.

PB

1043

54A

40P

B10

4355

A40

PB

1043

59A

40

CP

B10

0010

PB

1043

64A

50

Page 26: Low Voltage EasyPact MVS

A-16

Accessories and auxiliaries

Type of accessory EasyPact MVS08 to MVS40Fixed breaker Drawout breakerRear connection Rear connection

Interphasebarriers

DB

1011

49

Optional

DB

1011

49

OptionalSafety shutters

DB

1011

53

StandardSafety shutters locking blocks

E46

460

OptionalDoor interlock

E46

452

OptionalPushbutton locking device E

4666

6

OptionalE

4666

6Optional

OFF position locking

CD

B50

0039

Optional

CD

B50

0039

Optional“Disconnected” position locking E

4645

1

OptionalON/OFF indication contacts(OF) E46

689

Standard

E46

689

StandardAdditional ON/OFF indication contacts(OF) E

4668

9

Optional

E46

689

Optional“Fault trip” indication contact(SDE)

CD

B50

0040

Standard

CD

B50

0040

Standard

Functionsand characteristics

Page 27: Low Voltage EasyPact MVS

A-17

Type of accessory EasyPact MVS08 to MVS40Fixed breaker Drawout breakerRear connection Rear connection

“Connected, disconnected, test position”indication contact(CE,CD,CT)

E46

661

Optional“Ready to close” contact(PF) E

4643

8

Optional

E46

438

OptionalEscutcheon(CDP)

CD

B50

0061

Standard

CD

B50

0061

StandardMechanical operation counter(CDM)

DB

1256

17Optional

DB

1256

17

OptionalEscutcheon blanking plate

E46

670

Optional

E46

670

OptionalAuxiliary terminal shield(CB) E

4645

8

OptionalTransparent cover (IP54) E

4666

9

Optional

Page 28: Low Voltage EasyPact MVS

A-18

LockingOn the device

Pushbutton locking VBPThe transparent cover blocks access to the pushbuttons used to open and close the device.It is possible to independently lock the opening button and the closing button.The locking device is often combined with a remote operating mechanism.The pushbuttons may be locked using either:

■ Three padlocks (not supplied) ■ Lead seal ■ Two screws

Device locking in the OFF position by keylocks VSPOThe circuit breaker is locked in the OFF position by physically maintaining theopening pushbutton pressed down:

■ Using keylocks (one or two keylocks, supplied)Keys may be removed only when locking is effective (Profalux or Ronis type locks).The keylocks are available in any of the following confi gurations:

■ One keylock ■ One keylock mounted on the device + one identical keylock supplied separately for interlocking with another device

A locking kit (without locks) is available for installation of one or two keylocks (Ronis,Profalux).

Access to pushbuttons protected by transparent cover.

PB

1008

11-3

2P

B10

0810

-32

Pushbutton locking using a padlock.

Functionsand characteristics

CP

B10

0007

OFF position locking using a keylock.

CD

B50

0036

Profaulx Ronis

Door interlock catch VPECMounted on the right or left-hand side of the chassis, this device inhibits opening ofthe cubicle door when the circuit breaker is in “connected” or “test” position. It thebreaker is put in the “connected” position with the door open, the door may be closedwithout having to disconnect the circuit breaker.

Automatic spring discharge before breaker removal DAEThis option discharges the springs before the breaker is removed from the chassis.

CD

B50

0006

1 Reset button for mechanical trip indication.2 OFF pushbutton.3 OFF position lock.4 Door interlock.5 ON pushbutton.6 Spring charge indication.7 Pushbutton locking.8 Contact position indication.9 Operation counter.

MVS08 N

IEC 60947-2 50/60H

delay

short time

on I2t

.2

.3.4 .4

.1

.2

.10

long time

alarm

ground fault

setting

4

test

.4.5.6

.7.8 .9

.95

.981

Ir

x In

.512

48 12

1620

tr(s)

at 6 Ir24

x Ir

22.5

34 5

68

10

Isd

1.5

tsd(s)

x In3

68 10

1215

off2

BC

DE F

GH

I

Ig

Aon I

2t.2.3

.4 .4

.1

.2.3

.10off

tg(s)

.3

instantaneous

I i

ET6G Trip System

alarm

Ir

ground fault

test

onoff

onoff

off

(s)

(s)

(s)

long time

short time

instantaneous

ET6G Trip System

Door interlock.

CP

B10

0008

Page 29: Low Voltage EasyPact MVS

A-19

On the chassisC

DB

5000

07

1 Door interlock.2 Keylock locking.3 Padlock locking.4 Position indicator.5 Chassis front plate (accessible with cubicle door closed).6 Racking-handle entry.7 Release button.8 Racking-handle storage.

“Connected”, “disconnected” and “test” position racking interlockThe “connected”, “disconnected” and “test” positions are shown by an indicator andare mechanically indexed. The exact position is obtained when the racking handleblocks. A release button is used to free it.

“Disconnected” position locking by padlocks or keylocks VSPDMounted on the chassis and accessible with the door closed, these devices lock thecircuit breaker in the “disconnected” position in two manners:

■ Using padlocks (standard), up to three padlocks (not supplied) ■ Using keylocks (optional), one or two different keylocks are available

Profalux and Ronis keylocks are available in different options: ■ One keylock ■ Two identical key locks - one keylock mounted on the device + one identical keylock supplied separately for interlocking with another device

A locking kit (without locks) is available for installation of one or two keylocks (Ronis, Profalux).

Padlock

CP

B10

0006

CP

B10

0017

“Disconnected” position locking by padlock.

Circuit breaker in “disconnected” position.

Insert the shackle (max. diameter 5 to 8 mm) of the padlock(s).

Pull out the tab.

The crank connot be inserted.

KeylockCircuit breaker in “disconnected” position.

Remove the key(s)

Turn the key(s).

The crank cannot be inserted.

1

8

3

7 56

4

2

“Disconnected” position locking by keylock.

Page 30: Low Voltage EasyPact MVS

A-20

Indication contactsP

B10

0818

-16

PB

1008

07-2

0

“Fault-trip” indication contact (SDE).

ON/OFF indication contacts(OF) (rotary type).

Indication contacts are available: ■ in the standard version for relay applications

ON/OFF indication contacts OFIndication contacts indicate the ON or OFF position of the circuit breaker:

■ Rotary type changeover contacts directly driven by the mechanism for EasyPact MVS. These contacts trip when the minimum isolation distance between the main circuit-breaker contacts is reached

OF MVSSupplied as standard 1 (4 C/O)Optional contact 1 (4 C/O)Breaking capacity (A) Standard Minimum load: 100 mA/24 Vp.f.: 0.3 V AC 240/380 10/6 (1)

AC12/DC12 480 10/6 (1)

690 6V DC 24/48 10/6 (1)

125 10/6 (1)

250 3(1) Standard contacts: 10 A; optional contacts: 6 A.

“Fault-trip” indication contacts SDECircuit-breaker tripping due to a fault is signalled by:

■ A red mechanical fault indicator (reset) ■ One changeover contact SDE

Following tripping, the mechanical indicator must be reset before the circuit breakermay be closed. One SDE is supplied as standard.SDE MVSSupplied as standard 1Breaking capacity (A) Standard Minimum load: 100 mA/24 Vp.f.: 0.3 V AC 240/380 5AC12/DC12 480 5

690 3V DC 24/48 3

125 0.3250 0.15

“Connected”, “disconnected” and “test” position carriage switches CE, CD & CTThree series of optional auxiliary contacts are available for the chassis:

■ Changeover contacts to indicate the “connected” position CE ■ Changeover contacts to indicate the “disconnected” position CD. This position is indicated when the required clearance for isolation of the power and auxiliary circuits is reached

■ Changeover contacts to indicate the “test” position CT. In this position, the power circuits are disconnected and the auxiliary circuits are connected

Additional actuatorsA set of additional actuators may be installed on the chassis to change the functionsof the carriage switches.

MVSContacts CE/CD/CTMaximum number Standard 3 3 3Breaking capacity (A) Standard Minimum load: 100 mA/24 Vp.f.: 0.3 V AC 240 8AC12/DC12 380 8

480 8690 6

V DC 24/48 2.5125 0.8250 0.3

PB

1008

17-3

2

CE, CD and CT “connected/disconnected/test” positioncarriage switches.

Functionsand characteristics

Page 31: Low Voltage EasyPact MVS

A-21

Remote operationRemote ON / OFF

PB

1043

49A

68

DB

1117

83

The remote ON / OFF function is used to remotely open and close the circuit breaker.It is made up of:

■ An electric motor MCH equipped with a “springs charged” limit switch contact CH ■ Two voltage releases: □ A closing release XF □ An opening release MX

Optionally, other function may be added: ■ A “ready to close” contact PF

A remote-operation function is generally combined with: ■ Device ON / OFF indication OF ■ “Fault-trip” indication SDE

Wiring diagram of a point-to-point remote ON / OFF function

A point-to-point solution for remote operation of EasyPact MVS

Note: An opening order always takes priority over a closing order.If opening and closing orders occur simultaneously, themechanism discharges without any movement of the maincontacts. The circuit breaker remains in the open position(OFF).In the event of maintained opening and closing orders, thestandard mechanism provides an anti-pumping function byblocking the main contacts in open position.Anti-pumping function. After fault tripping or intentionalopening using the manual or electrical controls, the closingorder must fi rst be discontinued, then reactivated to close thecircuit breaker.

Page 32: Low Voltage EasyPact MVS

A-22

Electric motor MCHThe electric motor automatically charges and recharges the spring mechanism whenthe circuit breaker is closed. Instantaneous reclosing of the breaker is thus possiblefollowing opening. The spring-mechanism charging handle is used only as a backupif auxiliary power is absent.The electric motor MCH is equipped as standard with a limit switch contact CH thatsignals the “charged” position of the mechanism (springs charged).CharacteristicsPower supply V AC 50/60 Hz 100/130 - 200/240 - 380/415

V DC 24/30 - 48/60 - 100/125 - 200/250Operating threshold 0.85 to 1.1 UnConsumption (VA or W) 180Motor overcurrent 2 to 3 In for 0.1 sCharging time Maximum 4 sOperating frequency Maximum 3 cycles per minuteCH contact 10 A at 240 V

Voltage releases XF and MXTheir supply can be maintained or automatically disconnected.Closing release XFThe XF release remotely closes the circuit breaker if the spring mechanism is charged.Opening release MXThe MX release instantaneously opens the circuit breaker when energised. It locks the circuit breaker in OFF position if the order is maintained.Characteristics XF MXPower supply V AC 50/60 Hz 24 - 48 - 100/130 - 200/250 - 277 - 380/480

V DC 12 - 24/30 - 48/60 - 100/130 - 200/250Operating threshold 0.85 to 1.1 Un 0.7 to 1.1 UnConsumption (VA or W) Hold: 4.5 Hold: 4.5

Pick-up: 200 (200 ms) Pick-up: 200 (200 ms)Circuit-breaker response time at Un 70 ms ±10 50 ms ±10

“Ready to close” contact PFThe “ready to close” position of the circuit breaker is indicated by a mechanical indicator and a PF changeover contact. This signal indicates that all the following are valid:

■ The circuit breaker is in the OFF position ■ The spring mechanism is charged ■ A maintained opening order is not present: □ MX energised □ Fault trip □ Remote tripping MN □ Device not completely racked in □ Device locked in OFF position □ Device interlocked with a second device

CharacteristicsMaximum number 1Breaking capacity (A) Standard Minimum load: 100 mA/24 Vp.f.: 0.3 V AC 240/380 5AC12/DC12 480 5

690 3V DC 24/48 3

125 0.3250 0.15

PB

1008

09-1

6P

B10

0818

-16

DB

1170

37P

B10

0808

-32

MX voltage releases. XF voltage release.

“Ready to close” contacts PF.

Electric motor MCH forEasyPact MVS.

Functionsand characteristics

Remote operationRemote ON / OFF

Page 33: Low Voltage EasyPact MVS

A-23

Remote trippingD

B10

0809

-16

0564

22N

MN voltage release.

MN delay unit.

Instantaneous voltage releases MNThe MN release instantaneously opens the circuit breaker when its supply voltagedrops to a value between 35 % and 70 % of its rated voltage. If there is no supply onthe release, it is impossible to close the circuit breaker, either manually or electrically.Any attempt to close the circuit breaker has no effect on the main contacts. Circuit breaker closing is enabled again when the supply voltage of the release returns to 85% of its rated value.CharacteristicsPower supply V AC 50/60 Hz 24 - 48 - 100/130 - 200/250 - 380/480

V DC 24/30 - 48/60 - 100/130 - 200/250Operating threshold Opening 0.35 to 0.7 Un

Closing 0.85 UnConsumption (VA or W) Pick-up: 200 (200 ms) Hold: 4.5MN consumption Pick-up: 200 (200 ms) Hold: 4.5with delay unit (VA or W)Circuit-breaker response time at Un 90 ms ±5

MN delay unitsTo eliminate circuit-breaker nuisance tripping during short voltage dips, operation ofthe MN release can be delayed. This function is achieved by adding an externaldelay unit in the MN voltage-release circuit. Two versions are available, adjustableand non-adjustable.CharacteristicsPower supply Non-adjustable 100/130 - 200/250V AC 50-60 Hz /DC Adjustable 48/60 - 100/130 - 200/250 - 380/480Operating threshold Opening 0.35 to 0.7 Un

Closing 0.85 UnDelay unit consumption Pick-up: 200 (200 ms) Hold: 4.5Circuit-breaker response time at Un Non-adjustable 0.25 s

Adjustable 0.5 s - 0.9 s - 1.5 s - 3 s

Page 34: Low Voltage EasyPact MVS

A-24

Source-changeover systemsMechanical interlocking

Interlocking of two EasyPact MVS or up to three EasyPact MVS devices using cablesFor cable interlocking, the circuit breakers may be mounted one above the other orside-by-side. The interlocked devices may be fi xed or drawout, three-pole or four-pole, and have different ratings.Interlocking between two devicesThis function requires:

■ An adaptation fi xture on the right side of each device ■ A set of cables with no-slip adjustments ■ The use of a mechanical operation counter CDM is compulsory

The maximum distance between the fi xing planes (vertical or horizontal) is 2000 mm.Interlocking between three devicesThis function requires:

■ A specifi c adaptation fi xture for each type of interlocking, installed on the right side of each device

■ Two or three sets of cables with no-slip adjustments ■ The use of a mechanical operation counter CDM is compulsory

The maximum distance between the fi xing planes (vertical or horizontal) is 1000 mm.InstallationThe adaptation fi xtures, sets of cables and circuit breakers or switch-disconnectorsare supplied separately, ready for assembly by the customer.

Installation conditions for cable interlocking systems: ■ Cable length: 2.5 m ■ Radius of curvature: 100 mm ■ Maximum number of curves: 3

Possible combinations of “Normal” and “Replacement” source circuit breakers“Normal N” “Replacement” RMVS08 to MVS40 MVS08 to MVS40Ratings 800...4000A ■

Possible combinations of three deviceMVS08 to MVS40 MVS08 to MVS40Ratings 800...4000A ■

All combinations of two or three EasyPact MVS devices are possible, whatever the rating of the devices.

CP

B10

0009

Interlocking of two EasyPact circuit breakers using cable.

Functionsand characteristics

Page 35: Low Voltage EasyPact MVS

A-25

AccessoriesP

B10

4740

PB

1043

82A

32D

B10

1173

PB

1007

76-4

2

Escutcheon CDP with blanking plate.

Transparent cover CP for escutcheon.

Auxiliary terminal shield CBOptional equipment mounted on the chassis, the shield prevents access to theterminal block of the electrical auxiliaries.

Operation counter CDMThe operation counter sums the number of operating cycles and is visible on the front panel. It is compatible with manual and electrical control functions.This option is compulsory for all the source-changeover systems.

Escutcheon CDPStandard equipment mounted on the door of the cubicle, the escutcheon increasesthe degree of protection to IP 40 (circuit breaker installed free standing: IP30) .It is available in fi xed and drawout versions.

Blanking plate for escutcheon OPUsed with the escutcheon, this option closes off the door cut-out of a cubicle not yetequipped with a device. It may be used with the escutcheon for both fi xed anddrawout devices.

Transparent cover for escutcheon CPOptional equipment mounted on the escutcheon, the cover is hinged and secured bya screw. It increases the degree of protection to IP54, IK10. It adapts to drawoutdevices.

Page 36: Low Voltage EasyPact MVS

Installationrecommendations

Page 37: Low Voltage EasyPact MVS

B-1

Installation recommendations

Functions and characteristics A-1

Operating conditions B-2

Installation in switchboard B-3

Door interlock catch B-5

Control wiring B-6

Power connection B-7

Recommended busbars drilling B-9

Busbar sizing B-10

Temperature deratingPower dissipation B-11

Dimensions and connection C-1Electrical diagrams D-1Additional characteristics E-1Catalogue numbers and order form F-1

EasyPact MVS

Page 38: Low Voltage EasyPact MVS

B-2

Installationrecommendations

Operating conditions

EasyPact MVS circuit breakers have been tested for operation in industrial atmospheres. It is recommended that the equipment be cooled or heated to the proper operating temperature and kept free of excessive vibration and dust.

CD

B50

0008 Ambient temperature

EasyPact MVS devices can operate under the following temperature conditions: ■ The electrical and mechanical characteristics are stipulated for an ambient temperature of -5°C to +60°C

■ Circuit-breaker closing is guaranteed down to -35°C ■ Storage conditions are as follows: ■ -40 to +85°C for a Easypact MVS device without its control unit ■ -25°C to +85°C for the control unit

CD

B50

0011

CD

B50

0012

AltitudeAt altitudes higher than 2000 metres, the modifi cations in the ambient air (electricalresistance, cooling capacity) lower the following characteristics as follows:

Altitude (m) 2000 3000Impulse withstand voltage uimp (kV) 12 11Rated insulation voltage (Ui) 1000 900Maximum rated operationnalvoltage 50/60 Hz Ue (V)

690 5901000 890

Rated current 40°C 1 x In 0.99 x In

Intermediate values may be obtained by interpolation.

Electromagnetic disturbancesEasyPact MVS devices are protected against:

■ Overvoltages caused by devices that generate electromagnetic disturbances ■ Overvoltages caused by atmospheric disturbances or by a distribution-system outage (e.g. failure of a lighting system)

■ Devices emitting radio waves (radios, walkie-talkies, radar, etc.) ■ Electrostatic discharges produced by users

EasyPact MVS devices have successfully passed the electromagnetic-compatibilitytests (EMC) defi ned by the following international standards:

■ IEC 60947-2, appendix FThe above tests guarantee that:

■ No nuisance tripping occurs ■ Tripping times are respected

MVS08 N

IEC 60947-2 50/60H

delay

short time

on I2t

.2

.3.4 .4

.1

.2

.10

long time

alarm

ground fault

setting

4

test

.4.5.6

.7.8 .9

.95

.981

Ir

x In

.512

48 12

1620

tr(s)

at 6 Ir24

x Ir

22.5

34 5

68

10

Isd

1.5

tsd(s)

x In3

68 10

1215

off2

BC

DE F

GH

I

Ig

Aon I

2t.2.3

.4 .4

.1

.2.3

.10off

tg(s)

.3

instantaneous

I i

ET6G Trip System

alarm

Ir

ground fault

test

onoff

onoff

off

(s)

(s)

(s)

long time

short time

instantaneous

ET6G Trip System

2000(m)

MVS08 N

IEC 60947-2 50/60H

delay

short time

on I2t

.2

.3.4 .4

.1

.2

.10

long time

alarm

ground fault

setting

4

test

.4.5.6

.7.8 .9

.95

.981

Ir

x In

.512

48 12

1620

tr(s)

at 6 Ir24

x Ir

22.5

34 5

68

10

Isd

1.5

tsd(s)

x In3

68 10

1215

off2

BC

DE F

GH

I

Ig

Aon I

2t.2.3

.4 .4

.1

.2.3

.10off

tg(s)

.3

instantaneous

I i

ET6G Trip System

alarm

Ir

ground fault

test

onoff

onoff

off

(s)

(s)

(s)

long time

short time

instantaneous

ET6G Trip System

MVS08 N

IEC 60947-2 50/60H

delay

short time

on I2t

.2

.3.4 .4

.1

.2

.10

long time

alarm

ground fault

setting

4

test

.4.5.6

.7.8 .9

.95

.981

Ir

x In

.512

48 12

1620

tr(s)

at 6 Ir24

x Ir

22.5

34 5

68

10

Isd

1.5

tsd(s)

x In3

68 10

1215

off2

BC

DE F

GH

I

Ig

Aon I

2t.2.3

.4 .4

.1

.2.3

.10off

tg(s)

.3

instantaneous

I i

ET6G Trip System

alarm

Ir

ground fault

test

onoff

onoff

off

(s)

(s)

(s)

long time

short time

instantaneous

ET6G Trip System

Page 39: Low Voltage EasyPact MVS

B-3

Installation in switchboard

CD

B50

0013

CD

B50

0016

CD

B50

0017

CD

B50

0018

CD

B50

0014

CD

B50

0015

Possible positions

Power supplyEasyPact MVS devices can be supplied either from the top or from the bottom without reduction in performance, in order to facilitate connection when installed in a switchboard.

Mounting the circuit-breakerIt is important to distribute the weight of the device uniformily over a rigid mountingsurface such as rails or a base plate.This mounting plane should be perfectly fl at (tolerance on support fl atness: 2 mm).This eliminates any risk of deformation which could interfere with correct operationof the circuit breaker.EasyPact devices can also be mounted on a vertical plane using the special brackets.

Mounting on rails.

MVS08 N

IEC 60947-2 50/60H

delay

short time

on I2t

.2

.3.4 .4

.1

.2

.10

long time

alarm

ground fault

setting

4

test

.4.5.6

.7.8 .9

.95

.981

Ir

x In

.512

48 12

1620

tr(s)

at 6 Ir24

x Ir

22.5

34 5

68

10

Isd

1.5

tsd(s)

x In3

68 10

1215

off2

BC

DE F

GH

I

Ig

Aon I

2t.2.3

.4 .4

.1

.2.3

.10off

tg(s)

.3

instantaneous

I i

ET6G Trip System

alarm

Ir

ground fault

test

onoff

onoff

off

(s)

(s)

(s)

long time

short time

instantaneous

ET6G Trip System

MVS08 N

IEC 60947-2 50/60H

delay

short time

on I2t

.2

.3.4 .4

.1

.2

.10

long time

alarm

ground fault

setting

4

test

.4.5.6

.7.8 .9

.95

.981

Ir

x In

.512

48 12

1620

tr(s)

at 6 Ir24

x Ir

22.5

34 5

68

10

Isd

1.5

tsd(s)

x In3

68 10

1215

off2

BC

DE F

GH

I

Ig

Aon I

2t.2.3

.4 .4

.1

.2.3

.10off

tg(s)

.3

instantaneous

I i

ET6G Trip System

alarm

Ir

ground fault

test

onoff

onoff

off

(s)

(s)

(s)

long time

short time

instantaneous

ET6G Trip System

MVS08 N

IEC 60947-2 50/60H

delay

short time

on I2t

.2

.3.4 .4

.1

.2

.10

long time

alarm

ground fault

setting

4

test

.4.5.6

.7.8 .9

.95

.981

Ir

x In

.512

48 12

1620

tr(s)

at 6 Ir24

x Ir

22.5

34 5

68

10

Isd

1.5

tsd(s)

x In3

68 10

1215

off2

BC

DE F

GH

I

Ig

Aon I

2t.2.3

.4 .4

.1

.2.3

.10off

tg(s)

.3

instantaneous

I i

ET6G Trip System

alarm

Ir

ground fault

test

onoff

onoff

off

(s)

(s)

(s)

long time

short time

instantaneous

ET6G Trip System

MVS08 N

IEC 60947-2 50/60H

delay

short time

on I2t

.2

.3.4 .4

.1

.2

.10

long time

alarm

ground fault

setting

4

test

.4.5.6

.7.8 .9

.95

.981

Ir

x In

.512

48 12

1620

tr(s)

at 6 Ir24

x Ir

22.5

34 5

68

10

Isd

1.5

tsd(s)

x In3

68 10

1215

off2

BC

DE F

GH

I

Ig

Aon I

2t.2.3

.4 .4

.1

.2.3

.10off

tg(s)

.3

instantaneous

I i

ET6G Trip System

alarm

Ir

ground fault

test

onoff

onoff

off

(s)

(s)

(s)

long time

short time

instantaneous

ET6G Trip System

Page 40: Low Voltage EasyPact MVS

B-4

DB

1014

34D

B10

1435

A : Non magnetic material.

PartitionsSuffi cient openings must be provided in partitions toensure good air circulation around the circuit breaker;Any partition between upstream and downstreamconnections of the device must be made of nonmagnetic material.For high currents, of 2500 A and upwards, the metalsupports or barriers in the immediate vicinity of aconductor must be made of non-magnetic material A.Metal barriers through which a conductor passes mustnot form a magnetic loop.

DB

1170

45

DB

1014

36BusbarsThe mechanical connection must be exclude thepossibility of formation of a magnetic loop around a conductor.

CD

B50

0041

DB

1014

39

453

Interphase barrierIf the insulation distance between phases is notsuffi cient (≤ 14 mm), it is advised to install phasebarriers (taking into account the safety clearances).

Installationrecommendations

Installation in switchboard

Page 41: Low Voltage EasyPact MVS

B-5

Door interlock catch

DB

1170

44

Catch not supplied

DB

1038

19

83103

DB

1021

94

Breaker in “connected” or “test” positionDoor cannot be opened

Breaker in “disconnected” positionDoor can be opened

Door interlock VPECMounted on the right or left-hand side of the chassis,this device inhibits opening of the cubicle door whenthe circuit breaker is in “connected” or “test” position.It the breaker is put in the “connected” position with thedoor open, the door may be closed without having todisconnect the circuit breaker.

Dimensions (mm)Type (1) (2)MVS08-40 (3P) 215 215MVS08-40 (4P) 330 215

Note: The door interlock can either be mounted on the right side or the left side of the breaker.

: Datum.

Note: Dimensions are in mm.

CD

B50

0034

Page 42: Low Voltage EasyPact MVS

B-6

Control wiring

Wiring of voltage releasesDuring pick-up, the power consumed is approximately 150 to 200 VA. For low controlvoltages (12, 24, 48 V), maximum cable lengths are imposed by the voltage and thecross-sectional area of cables.Recommended maximum cable lengths (meter).

12 V 24 V 48 V2,5 mm2 1,5 mm2 2,5 mm2 1,5 mm2 2,5 mm2 1,5 mm2

MN U source 100 % – – 58 35 280 165U source 85 % – – 16 10 75 45

MX-XF U source 100 % 21 12 115 70 550 330U source 85 % 10 6 75 44 350 210

Note: The indicated length is that of each of the two wires.

24 V DC power-supply moduleExternal 24 V DC power-supply module (F1-, F2+)

■ Do not connect the positive terminal (F2+) to earth ■ The negative terminal (F1-) can be connected to earth ■ A number of trip units can be connected to the same 24 V DC power supply (the consumption of a trip unit is approximately 100 mA)

■ Do not connect any devices other than a trip unit ■ The maximum length for each conductor is ten metres. For greater distances, it is advised to twist the supply wires together

■ The 24 V DC supply wires must cross the power cables perpendicularly. If this is diffi cult, it is advised to twist the supply wires together

■ The technical characteristics of the external 24 V DC power-supply module are indicated on page A-14.

Note: Wiring of ZSI: it is recommended to use twisted shielded cable. The shield must be connected to earth at both ends.

Installationrecommendations

Page 43: Low Voltage EasyPact MVS

B-7

Power connection

Cables connectionsIf cables are used for the power connections, make sure that they do not apply excessive mechanical forces to the circuit breaker terminals.For this, make the connections as follows:

■ Extend the circuit breaker terminals using short bars designed and installed according to the recommendations for bar-type power connections:

□ For a single cable, use solution B opposite □ For multiple cables, use solution C opposite ■ In all cases, follow the general rules for connections to busbars:

□ Position the cable lugs before inserting the bolts □ The cables should fi rmly secured to the framework E

DB

1014

48

DB

1014

49

DB

1014

50D

B10

1453

DB

1014

51

DB

1014

52Busbars connectionsThe busbars should be suitably adjusted to ensure thatthe connection points are positioned on the terminalsbefore the bolts are inserted BThe connections are held by the support which is solidly fi xed to the framework of the switchboard, such that the circuit breaker terminals do not have to support its weight C. (This support should be placed close to the terminals).

Electrodynamic stressesThe fi rst busbar support or spacer shall be situated within a maximum distance fromthe connection point of the breaker (see table below). This distance must berespected so that the connection can withstand the electrodynamic stressesbetween phases in the event of a short circuit.Maximum distance A between busbar to circuit breaker connection and the fi rst busbarsupport or spacer with respect to the value of the prospective short-circuit current.Isc (kA) 30 50 65Distance A (mm) 350 300 250

Page 44: Low Voltage EasyPact MVS

B-8

DB

1014

54 ClampingCorrect clamping of busbars depends amongst other things, on the tighteningtorques used for the nuts and bolts. Over-tightening may have the sameconsequences as under-tightening.For connecting busbars (Cu ETP-NFA51-100) to the circuit breaker, the tighteningtorques to be used are shown in the table below.These values are for use with copper busbars and steel nuts and bolts, class 8.8. The same torques can be used with AGS-T52 quality aluminium bars (French standardNFA 02-104 or American National Standard H-35-1).Examples

1 Terminal screw factory-tightened to 16 Nm.2 Breaker terminal.3 Busbar.4 Bolt.5 Washer.6 Nut.

DB

1014

55

DB

1014

56

DB

1014

57

Tightening torquesØ (mm)Nominal

Ø (mm)Drilling

Tightening torques (Nm)with grower or fl at washers

Tightening torques (Nm)with contact or corrugatecwashers

10 11 37.5 50

Busbar drillingExamples

DB

1014

58

DB

1014

59

DB

1014

60

DB

1014

61D

B10

1462

Isolation distance

Dimensions (mm)Ui X min600 V 8 mm1000 V 14 mm

Busbar bendingWhen bending busbars maintain the radius indicated below(a smaller radius wouldcause cracks).

Dimensions (mm)e Radius of curvature r

Min Recommended5 5 7.510 15 18 to 20

Installationrecommendations

Power connection

Page 45: Low Voltage EasyPact MVS

B-9

Recommended busbars drillingEasyPact MVS08 to MVS40

Horizontal rear connection MVS08 to MVS32

Vertical rear connection MVS08 to MVS32

MVS40

MVS40

DB

1014

63

DB

1014

64

DB

1014

65

CD

B50

0042

CD

B50

0054

CD

B50

0055

CD

B50

0056

CD

B50

0043

DB

1014

74D

B10

1476

DB

1014

77

Page 46: Low Voltage EasyPact MVS

B-10

Page 47: Low Voltage EasyPact MVS

B-11

Temperature deratingPower dissipation

Temperature deratingThe table below indicates the maximum current rating,for each connection type, as a function of Ti around thecircuit breaker and the busbars.For Ti greater than 60°C, consult us.Ti: temperature around the circuit breaker and its connection.

Version Drawout FixedConnection Rear horizontal Rear vertical Rear horizontal Rear verticalTemp. Ti 40 °C 45 °C 50 °C 55 °C 60 °C 40 °C 45 °C 50 °C 55 °C 60 °C 40 °C 45 °C 50 °C 55 °C 60 °C 40 °C 45 °C 50 °C 55 °C 60 °CMVS (65kA)MVS08H 800 800 800 800MVS10H 1000 1000 1000 1000MVS12H 1250 1250 1250 1250MVS16H 1600 1600 1600 1600MVS20H 2000 1900 1800 2000 1900 2000 1920 2000MVS25H 2500 2400 2300 2200 2500 2400 2300 2500 2500MVS32H 3200 3100 3000 2900 3200 3200 3200MVS40H 4000 3900 3750 3650 4000 3900 4000 3900 3800 4000

Power dissipationTotal power dissipation is the value measured at IN, 50/60 Hz, for a 3 pole or 4 pole breaker (values above the power P = 3RI2). The resistance between input / output is the value measured per pole (cold state).

Type Draw-out Fixed50kA Power loss

(W)Input/output resistance (µohm)

Power loss (W)

Input/output resistance (µohm)

65kAMVS08H 100 30 42 13MVS10H 150 30 70 13MVS12H 230 30 100 13MVS16H 390 30 170 13MVS20H 470 30 250 13MVS25H 600 19 260 8MVS32H 670 13 420 8MVS40H 900 11 650 8

Page 48: Low Voltage EasyPact MVS

Dimensions and connection

462E3000.indd 50 12/16/13 1:49 PM

Page 49: Low Voltage EasyPact MVS

C-1

Dimensions and connection

Functions and characteristics A-1Installation recommendations B-1

MVS08 to MVS32 circuit breakers C-2Fixed 3/4-poles device C-2Drawout 3/4-poles device C-4

MVS40 circuit breakers C-6Fixed 3/4-poles device C-6Drawout 3/4-poles device C-8

Accessories C-10

External modules C-11

Electrical diagrams D-1Additional characteristics E-1Catalogue numbers and order form F-1

EasyPact MVS

462E3000.indd 1 12/16/13 1:49 PM

Page 50: Low Voltage EasyPact MVS

C-2

Dimensionsand connection

MVS08 to MVS32 circuit breakersFixed 3/4-poles device

Dimensions

DB

1012

67

CD

B50

0019

DB

1012

69D

B10

1271

CD

B50

0020

DB

1012

73D

B10

1270

Mounting on base plate or rails Mounting detail

Safety clearances

(1) Without escutcheon.(2) With escutcheon.Note: X and Y are the symmetry planes for a 3-pole device.A(*) An overhead clearance of 50 mm is required to remove the arc chutes.An overhead clearance of 20 mm is required to remove the terminal block.

Insulated Metal Energisedparts parts parts

A 0 0 100B 0 0 60

: Datum.

462E3000.indd 2 12/16/13 1:49 PM

Page 51: Low Voltage EasyPact MVS

C-3

Connections

DB

1012

74D

B10

1279

DB

1012

76

DB

1012

77D

B10

1287

DB

1012

82D

B10

1278

Horizontal rear connection

Vertical rear connection

Detail

Detail

Note: Recommended connection screws: M10 class 8.8.Tightening torque: 50 Nm with contact washer.

DB

1012

80

View A detail.

462E3000.indd 3 12/16/13 1:49 PM

Page 52: Low Voltage EasyPact MVS

C-4

Dimensionsand connection

MVS08 to MVS32 circuit breakersDrawout 3/4-poles device

Dimensions

DB

1012

89

CD

B50

0021

DB

1012

91D

B10

1293

CD

B50

0022

DB

1012

95D

B10

1292

Mounting on base plate or rails Mounting detail

Safety clearances Door cutout

Insulated Metal Energisedparts parts parts

A 0 0 0B 0 0 60

: Datum.(1) Without escutcheon.(2) With escutcheon.Note: X and Y are the symmetry planes for a 3-pole device.

(*) Disconnected position.

DB

1012

94

462E3000.indd 4 12/16/13 1:49 PM

Page 53: Low Voltage EasyPact MVS

C-5

Connections

CD

B50

0044

CD

B50

0045

DB

1012

97D

B10

1301

DB

1012

98D

B10

1307

Horizontal rear connection

Vertical rear connection

Detail

Detail

DB

1012

82

View A detail.

Note: Recommended connection screws: M10 class 8.8.Tightening torque: 50 Nm with contact washer.

DB

1012

78

462E3000.indd 5 12/16/13 1:49 PM

Page 54: Low Voltage EasyPact MVS

C-6

Dimensionsand connection

MVS40 circuit breakersFixed 3/4-poles device

CD

B50

0019

Dimensions

DB

1012

67

Mounting on base plate or rails Mounting detail

DB

1012

69D

B10

1271

DB

1012

73D

B10

1270

Safety clearances

(1) Without escutcheon.(2) With escutcheon.Note: X and Y are the symmetry planes for a 3-pole device.A(*) An overhead clearance of 110 mm is required to remove the arc chutes.An overhead clearance of 20 mm is required to remove the terminal block.

Insulated Metal Energisedparts parts parts

A 0 0 100B 0 0 60

: Datum.

Door cutout

CD

B50

0020

462E3000.indd 6 12/16/13 1:49 PM

Page 55: Low Voltage EasyPact MVS

C-7

Connections

DB

1013

09D

B10

1312

Horizontal rear connection

Vertical rear connection

Detail

Detail

DB

1013

11D

B10

1314

DB

1013

15

DB

1012

76C

DB

5000

49D

B10

1287

DB

1013

13

Note: Recommended connection screws: M10 class 8.8.Tightening torque: 50 Nm with contact washer.

CD

B50

0049

400(3P)15

462E3000.indd 7 12/16/13 1:49 PM

Page 56: Low Voltage EasyPact MVS

C-8

Dimensionsand connection

MVS40 circuit breakersDrawout 3/4-poles device

CD

B50

0021

Dimensions

DB

1012

89D

B10

1291

DB

1012

93

DB

1012

95D

B10

1292

Safety clearances Door cutout

Insulated Metal Energisedparts parts parts

A 0 0 60B 0 0 60

: Datum.

(1) Without escutcheon.(2) With escutcheon.Note: X and Y are the symmetry planes for a 3-pole device.The safety clearances take into account the space required to remove the arc chutes.

(*) Disconnected position.

Mounting on base plate or rails Mounting detail

CD

B50

0022

DB

1012

94

462E3000.indd 8 12/16/13 1:49 PM

Page 57: Low Voltage EasyPact MVS

C-9

Connections

CD

B50

0046

CD

B50

0047

DB

1012

97

DB

1013

07

Horizontal rear connection

Vertical rear connection

Note: Recommended connection screws: M10 class 8.8.Tightening torque: 50 Nm with contact washer.

Detail

Detail

DB

1013

11D

B10

1315

DB

1013

14

CD

B50

0050

DB

1013

19

View A detail.

CD

B50

0050

400(3P)15

462E3000.indd 9 12/16/13 1:49 PM

Page 58: Low Voltage EasyPact MVS

C-10

Dimensionsand connection

AccessoriesD

B12

5695

DB

1013

65

DB

1013

66D

B10

1360

Rear panel cutout (drawout devices)

Escutcheon

MVS08 to MVS40Rear view

EasyPact MVSFixed device

: Datum.

Drawout device

462E3000.indd 10 12/16/13 1:49 PM

Page 59: Low Voltage EasyPact MVS

C-11

External modules

Connection of auxilary wiring to terminal block

External power supply module (AD)

Delay unit for MN release

DB

1013

67

DB

1020

77D

B10

1375

DB

1170

25D

B10

2076

DB

1013

68

One conductor only per connection point.

462E3000.indd 11 12/16/13 1:49 PM

Page 60: Low Voltage EasyPact MVS

C-12

External sensor for external neutral

DB

1170

24D

B10

1386

DB

1013

87D

B11

7023

Dimensions400/2000 A (MVS08 to MVS20) 1000/4000 A (MVS25 to MVS40)

Installation400/2000 A (MVS08 to MVS20) 1000/4000 A (MVS25 to MVS40)

High: 162 mm.High: 162 mm.

Dimensionsand connection

External modules

462E3000.indd 12 12/16/13 1:49 PM

Page 61: Low Voltage EasyPact MVS

C-13

462E3000.indd 13 12/16/13 1:49 PM

Page 62: Low Voltage EasyPact MVS

Electrical diagrams

462E4000_ch4.indd 50 12/16/13 1:51 PM

Page 63: Low Voltage EasyPact MVS

D-1

Electrical diagrams

Functions and characteristics A-1Installation recommendations B-1Dimensions and connection C-1

EasyPact MVS08 to 40 D-2Fixed and drawout devices D-2

EasyPact MVS D-4Earth-fault protection/Neutral protection D-4Zone selective interlocking D-524 V DC external power supply AD module D-6

Additional characteristics E-1Catalogue numbers and order form F-1

EasyPact MVS

462E4000_ch4.indd 1 12/16/13 1:51 PM

Page 64: Low Voltage EasyPact MVS

D-2

Electrical diagrams Masterpact MVS08 to MVS40Fixed and drawout devices

The diagram is shown with circuitsde-energised, all devices open, connectedand charged and relays in normal position.

Power ET/ETA/ETV trip system Remote operation

ET trip system

NCT

ETA/ETV trip system

VN

U

V1 V2 V3

E89

955

StopFaul

t

E89

956

E60

065A

Ope

nE

4613

6A

Clo

seE

4613

7A

Rea

dy-

to-c

lose

E60

066A

Cha

rged

E60

067A

ET trip systemUC1 UC2

Z5

Z3 Z4 T3 T4

Z1 Z2 T1 T2

ETA/ETV trip systemUC1 UC2 UC3

Z5 F2+

Z3 Z4 T3 T4 VN

Z1 Z2 T1 T2 F1-

Remote operationSDE MN MX XF PF MCH

84 D2 C2 A2 254 B2

82 C3 A3 252 B3

81 D1 C1 A1 251 B1

ET/ETA/ETV trip system Remote operationUC1 :Z1-Z5 zone selective interlockingZ1=ZSI OUT SOURCEZ2=ZSI OUT ; Z3 = ZSI IN SOURCEZ4 =ZSI IN ST (short time)Z5 =ZSI IN GF (earth fault)

UC2 :T1, T2, T3, T4=external neutral

UC3 :F2+, F1-: external 24 V DC power supplyVN: external voltage connector (must be connected to the neutral CT with a 3P circuit breaker equipped with ETV trip system)

SDE: Fault-trip indication contact (supplied as standard)MN: Undervoltage releaseMX: Shunt release (standard for Electrical breaker)XF: Closing release (standard for Electrical breaker)PF: “Ready to close”contactMCH: Gear motor (standard for Electrical breaker)

External sensor (CT).

E47

477

External sensors ( Neutral CT)External sensor for earth-fault protectionThe sensors, used with the 3P circuit breakers, are installed on the neutral conductor for:1. Residual type earth-fault protection(ET/ETA/ETV 6G trip system)

The rating of the sensor (CT) must be compatible with the rating of the circuit breaker:1. MVS08 to MVS20: CT 400/2000;2. MVS25 to MVS40: CT 1000/4000;

Note: V1...VN Voltage connections are available in ETV trip system.

462E4000_ch4.indd 2 12/16/13 1:51 PM

Page 65: Low Voltage EasyPact MVS

D-3

Indication contacts

Indication contacts

Chassis contacts

Chassis contacts

DB

1014

09

Indication contactsOF4 OF3 OF2 OF1 OF14 OF13 OF12 OF11

44 34 24 14 144 134 124 114

42 32 22 12 142 132 122 112

41 31 21 11 141 131 121 111

Chassis contactsCD3 CD2 CD1 CE3 CE2 CE1 CT3 CT2 CT1

834 824 814 334 324 314 934 924 914

832 822 812 332 322 312 932 922 912

831 821 811 331 321 311 931 921 911

Standard Optional Optional

OF 4 StandardOF 3 ON/OFFOF 2 Indication contactsOF 1

OF 14 OptionalON/OFFIndication contacts

OF 13OF 12OF 11

CD3 Disconnected CE3 Connected CT3 TestCD2 Position CE2 Position CT2 PositionCD1 Contacts CE1 Contacts CT1 Contacts

Key:

Drawout device only

XXX SDE1, OF1, OF2, OF3, OF4 supplied as standard

Interconnected connections (only one wire per connection point)

462E4000_ch4.indd 3 12/16/13 1:51 PM

Page 66: Low Voltage EasyPact MVS

D-4

Electrical diagrams EasyPact MVSEarth-fault protectionNeutral Protection

External sensor (CT) for residual earth-fault protection

Neutral protection

DB

1256

01Connection of current-transformer secondary circuit for external neutralEasyPact MVS equipped with a ET/ETA/ETV 6G:

■ Shielded cable with 2 twisted pairs ■ T1 twisted with T2 ■ Maximum length 4 meters ■ Cable cross-sectional area 0.4 to 1.5 mm2

■ Recommended cable: Belden 9552 or equivalentFor proper wiring of neutral CT, refer to instructionBulletin 48041-082-03 shipped with it.Do not remove factory-installed jumper between T1and T2 unless neutral CT is connected.If supply is via the top, follow the shematics.If supply is via the bottom, control wiring is identical; forthe power wiring, H1 is connected to the source side,H2 to the load side.For four-pole versions, for residual earth-faultprotection, the current transformer for the externalneutral is not necessary.

■ Three pole circuit breaker: v Neutral protection is impossible ■ Four pole circuit breaker: v The current transformer for external neutral is not

necessary

ET/ETA/ETV 6G

VN

Shield DrainVNExternal

Neutral CT

462E4000_ch4.indd 4 12/16/13 1:51 PM

Page 67: Low Voltage EasyPact MVS

D-5

Zone Selective Interlocking

Zone selective interlocking

DB

1014

20Zone-selective interlocking is used to reduce theelectrodynamic forces exerted on the installation by shorteningthe time required to clear faults, while maintaining timediscrimination between the various devices.A pilot wire interconnects a number of circuit breakers equipped with ET range of trip system, as illustrated in the diagram above.The control unit detecting a fault sends a signal upstream andchecks for a signal arriving from downstream. If there is a signalfrom downstream, the circuit breaker remains closed for the fullduration of its tripping delay. If there is no signal fromdownstream, the circuit breaker opens immediately, regardlessof the tripping-delay setting.

Fault 1.Only circuit breaker A detects the fault. Because it receives nosignal from downstream, it opens immediately, regardless of itstripping delay set to 0.3.

Fault 2.Circuit breakers A and B detect the fault. Circuit breaker Areceives a signal from B and remains closed for the full durationof its tripping delay set to 0.3. Circuit breaker B does notreceive a signal from downstream and opens immediately, inspite of its tripping delay set to 0.2.

Wiring ■ Maximum impedance: 2.7 Ω / 300 m ■ Capacity of connectors: 0.4 to 2.5 mm2

■ Wires: single or multicore ■ Maximum lenght: 3000 m ■ Limits to device interconnection: □ The common ZSI - OUT (Z1) and the output ZSI - OUT (Z2) can be connected to a maximum of 10 upstream device

□ A maximum of 100 downstream devices may be connected to the common ZSI - IN (Z3) and to an input ZSI - IN CR ( Z4) or GF (Z5)

462E4000_ch4.indd 5 12/16/13 1:51 PM

Page 68: Low Voltage EasyPact MVS

D-6

Electrical diagrams EasyPact MVS24 V DC external power supply AD module

■ The 24 V DC external power-supply (AD module) for the ET Trip system (F1- F2+) is not required for basic protections LSIG

■ With ETA/ETV, it is recommended to connect 24 V DC external power-supply (AD module) to the Micrologic control unit (F1- F2+) in order to keep available the display and the energy metering, even if Current < 20 % In

Note: In case of using the 24 V DC external power supply (AD module), maximum cable length between 24 V DC (G1, G2) and the control unit (F1-, F2+) must not exceed 10 meters.

The internal voltage taps are connected to the bottom side of the circuit breaker.

ConnectionThe maximum length for each conductor supplying power to the trip unit is 10 m.Do not ground F2+, F1-, or power supply output:

■ The positive terminal (F2+) on the trip unit must not be connected to earth ground ■ The negative terminal (F1-) on the trip unit must not be connected to earth ground ■ The output terminals (- and +) of the 24 V DC power supply must not be grounded

Reduce electromagnetic interference: ■ The input and output wires of the 24 V DC power supply must be physically separated as much as possible

■ If the 24 V DC power supply wires cross power cables, they must cross perpendicularly. If this is not physically possible, the power supply conductors must be twisted together

■ Power supply conductors must be cut to length. Do not loop excess conductor

ETA/ETV trip system

DB

1283

83

462E4000_ch4.indd 6 12/16/13 1:51 PM

Page 69: Low Voltage EasyPact MVS

D-7

462E4000_ch4.indd 7 12/16/13 1:51 PM

Page 70: Low Voltage EasyPact MVS

Additional characteristics

462E5000.indd 50 12/16/13 1:53 PM

Page 71: Low Voltage EasyPact MVS

E-1

Additional characteristics

Functions and characteristics A-1Installation recommendations B-1Dimensions and connection C-1Electrical diagrams D-1

Tripping curves E-2

Catalogue numbers and order form F-1

EasyPact MVS

462E5000.indd 1 12/16/13 1:53 PM

Page 72: Low Voltage EasyPact MVS

E-2

Additionalcharacteristics

Tripping curves

ET range of trip system - 2I

ET range of trip system - 5S, 6G

DB

1051

12D

B10

5113

462E5000.indd 2 12/16/13 1:53 PM

Page 73: Low Voltage EasyPact MVS

E-3

Earth fault protection (ET range of trip system - 6G)

DB

1015

05

(1)

Ig = In x... A B C D E F G H IIn ≤ 400 A 0.3 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1400 A < In ≤ 1000 A 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1In ≥ 1250A 500 640 720 800 880 960 1040 1120 1200

462E5000.indd 3 12/16/13 1:53 PM

Page 74: Low Voltage EasyPact MVS

Catalogue numbersand order form

Page 75: Low Voltage EasyPact MVS

F-1

Catalogue numbersand order form

Functions and characteristics A-1Installation recommendations B-1Dimensions and connection C-1Electrical diagrams D-1Tripping curves E-2

Nomenclature F-2

EasyPact MVS 800 to 4000A F-3EasyPact MVS fi xed 65kA F-3EasyPact MVS withdrawable 65kA F-4

EasyPact MVS F-5Connection F-5ET Trip System & accessories F-6Remote operation F-7Chassis locking and accessories F-9Clusters F-10Circuit breaker locking and accessories F-11Mechanical interlocking for source changeover F-12Indication contacts F-13Instructions F-14

Order form F-15

EasyPact MVS

Page 76: Low Voltage EasyPact MVS

F-2

Catalogue numbersand order form

Nomenclature

Range Current rating Type Pole Operating mechanism Installation Protection No. TypeEasyPact MVS (from 800 to 4000A) Icu=Ics=Icw (1 sec)=65kAMVS 08 H 3 M F 2 L

10 4 N W 5 A12 O 6 V16 P 0 D20 Q25 R32 S40 T

3 2 1 1 1 1 1 1 11 digitsType

L Basic protectionA Protection+current meteringV Protection+voltage meteringD Switch disconnector

Protections No.2 LI protection5 LSI protection6 LSIG protection0 No protection for switch disconnector

Type of installation F FixedW Withdrawable/drawout

Operating mechanismM Manually operated ACB/SDN Electrical 200/240 VAC MCH + XF + MX O Electrical 110/130 VAC MCH + XF + MX P Electrical 380/415 VAC MCH + XF + MX Q Electrical 200/250 VDC MCH + XF + MX R Electrical 100/125 VDC MCH + XF + MX S Electrical 48/60V DC MCH + XF + MX T Electrical 24/30V DC MCH + XF + MX

Number of poles3P 3 Poles4P 4 Poles

Type based on breaking capacity

H Circuit breaker/ switch disconnector Icu=Ics=Icw(1sec)=65kA

Current rating08 800A10 1000A12 1250A16 1600A20 2000A25 2500A32 3200A40 4000A

Example 1 MVS32H4NW6LMVS 32 H 4 N W 6 L

EasyPact MVS

3200A 65kA 4 Pole Electrical operated240V AC

Withdrawable type

LSIG protection Basic trip unit with LED indications

Example 2 MVS16H3MF0DMVS 16 H 3 M F 0 D

EasyPact MVS

1600A 65kA 3 Pole Manual operated Fixed No protection Switch disconnector

Page 77: Low Voltage EasyPact MVS

F-3

Catalogue numbersand order form

EasyPact MVS 800 to 4000AEasyPact MVS fixed 65kA

EasyPact MVS fi xed type 65kA with ET trip unit3P 4PET2I ET5S ET6G ET2I ET5S ET6G

Manual 800A MVS08H3MF2L MVS08H3MF5L MVS08H3MF6L MVS08H4MF2L MVS08H4MF5L MVS08H4MF6L1000A MVS10H3MF2L MVS10H3MF5L MVS10H3MF6L MVS10H4MF2L MVS10H4MF5L MVS10H4MF6L1250A MVS12H3MF2L MVS12H3MF5L MVS12H3MF6L MVS12H4MF2L MVS12H4MF5L MVS12H4MF6L1600A MVS16H3MF2L MVS16H3MF5L MVS16H3MF6L MVS16H4MF2L MVS16H4MF5L MVS16H4MF6L2000A MVS20H3MF2L MVS20H3MF5L MVS20H3MF6L MVS20H4MF2L MVS20H4MF5L MVS20H4MF6L2500A MVS25H3MF2L MVS25H3MF5L MVS25H3MF6L MVS25H4MF2L MVS25H4MF5L MVS25H4MF6L3200A MVS32H3MF2L MVS32H3MF5L MVS32H3MF6L MVS32H4MF2L MVS32H4MF5L MVS32H4MF6L4000A MVS40H3MF2L MVS40H3MF5L MVS40H3MF6L MVS40H4MF2L MVS40H4MF5L MVS40H4MF6L

Electrical240V AC(1)

800A MVS08H3NF2L MVS08H3NF5L MVS08H3NF6L MVS08H4NF2L MVS08H4NF5L MVS08H4NF6L1000A MVS10H3NF2L MVS10H3NF5L MVS10H3NF6L MVS10H4NF2L MVS10H4NF5L MVS10H4NF6L1250A MVS12H3NF2L MVS12H3NF5L MVS12H3NF6L MVS12H4NF2L MVS12H4NF5L MVS12H4NF6L1600A MVS16H3NF2L MVS16H3NF5L MVS16H3NF6L MVS16H4NF2L MVS16H4NF5L MVS16H4NF6L2000A MVS20H3NF2L MVS20H3NF5L MVS20H3NF6L MVS20H4NF2L MVS20H4NF5L MVS20H4NF6L2500A MVS25H3NF2L MVS25H3NF5L MVS25H3NF6L MVS25H4NF2L MVS25H4NF5L MVS25H4NF6L3200A MVS32H3NF2L MVS32H3NF5L MVS32H3NF6L MVS32H4NF2L MVS32H4NF5L MVS32H4NF6L4000A MVS40H3NF2L MVS40H3NF5L MVS40H3NF6L MVS40H4NF2L MVS40H4NF5L MVS40H4NF6L

EasyPact MVS fi xed type 65kA switch disconnector3P 4P

Manual 800A MVS08H3MF0D MVS08H4MF0D1000A MVS10H3MF0D MVS10H4MF0D1250A MVS12H3MF0D MVS12H4MF0D1600A MVS16H3MF0D MVS16H4MF0D2000A MVS20H3MF0D MVS20H4MF0D2500A MVS25H3MF0D MVS25H4MF0D3200A MVS32H3MF0D MVS32H4MF0D4000A MVS40H3MF0D MVS40H4MF0D

Electrical240V AC(1)

800A MVS08H3NF0D MVS08H4NF0D1000A MVS10H3NF0D MVS10H4NF0D1250A MVS12H3NF0D MVS12H4NF0D1600A MVS16H3NF0D MVS16H4NF0D2000A MVS20H3NF0D MVS20H4NF0D2500A MVS25H3NF0D MVS25H4NF0D3200A MVS32H3NF0D MVS32H4NF0D4000A MVS40H3NF0D MVS40H4NF0D

CD

B50

0062

CD

B50

0062

* Non-standard confi gured products.Use customer order form in page F-15 to order non-standard products

(1) Supplied with spring charge motor(MCH), opening release(MX) andclosing release(XF) with 240V AC control voltage rating.

Page 78: Low Voltage EasyPact MVS

F-4

EasyPact MVS withdrawable 65kA

EasyPact MVS withdrawable type 65kA with ET trip unit3P 4PET2I ET5S ET6G ET2I ET5S ET6G

Manual 800A MVS08H3MW2L MVS08H3MW5L MVS08H3MW6L MVS08H4MW2L MVS08H4MW5L MVS08H4MW6L1000A MVS10H3MW2L MVS10H3MW5L MVS10H3MW6L MVS10H4MW2L MVS10H4MW5L MVS10H4MW6L1250A MVS12H3MW2L MVS12H3MW5L MVS12H3MW6L MVS12H4MW2L MVS12H4MW5L MVS12H4MW6L1600A MVS16H3MW2L MVS16H3MW5L MVS16H3MW6L MVS16H4MW2L MVS16H4MW5L MVS16H4MW6L2000A MVS20H3MW2L MVS20H3MW5L MVS20H3MW6L MVS20H4MW2L MVS20H4MW5L MVS20H4MW6L2500A MVS25H3MW2L MVS25H3MW5L MVS25H3MW6L MVS25H4MW2L MVS25H4MW5L MVS25H4MW6L3200A MVS32H3MW2L MVS32H3MW5L MVS32H3MW6L MVS32H4MW2L MVS32H4MW5L MVS32H4MW6L4000A MVS40H3MW2L MVS40H3MW5L MVS40H3MW6L MVS40H4MW2L MVS40H4MW5L MVS40H4MW6L

Electrical240V AC(1)

800A MVS08H3NW2L MVS08H3NW5L MVS08H3NW6L MVS08H4NW2L MVS08H4NW5L MVS08H4NW6L1000A MVS10H3NW2L MVS10H3NW5L MVS10H3NW6L MVS10H4NW2L MVS10H4NW5L MVS10H4NW6L1250A MVS12H3NW2L MVS12H3NW5L MVS12H3NW6L MVS12H4NW2L MVS12H4NW5L MVS12H4NW6L1600A MVS16H3NW2L MVS16H3NW5L MVS16H3NW6L MVS16H4NW2L MVS16H4NW5L MVS16H4NW6L2000A MVS20H3NW2L MVS20H3NW5L MVS20H3NW6L MVS20H4NW2L MVS20H4NW5L MVS20H4NW6L2500A MVS25H3NW2L MVS25H3NW5L MVS25H3NW6L MVS25H4NW2L MVS25H4NW5L MVS25H4NW6L3200A MVS32H3NW2L MVS32H3NW5L MVS32H3NW6L MVS32H4NW2L MVS32H4NW5L MVS32H4NW6L4000A MVS40H3NW2L MVS40H3NW5L MVS40H3NW6L MVS40H4NW2L MVS40H4NW5L MVS40H4NW6L

EasyPact MVS withdrawable type 65kA switch disconnector3P 4P

Manual 800A MVS08H3MW0D MVS08H4MW0D1000A MVS10H3MW0D MVS10H4MW0D1250A MVS12H3MW0D MVS12H4MW0D1600A MVS16H3MW0D MVS16H4MW0D2000A MVS20H3MW0D MVS20H4MW0D2500A MVS25H3MW0D MVS25H4MW0D3200A MVS32H3MW0D MVS32H4MW0D4000A MVS40H3MW0D MVS40H4MW0D

Electrical240V AC(1)

800A MVS08H3NW0D MVS08H4NW0D1000A MVS10H3NW0D MVS10H4NW0D1250A MVS12H3NW0D MVS12H4NW0D1600A MVS16H3NW0D MVS16H4NW0D2000A MVS20H3NW0D MVS20H4NW0D2500A MVS25H3NW0D MVS25H4NW0D3200A MVS32H3NW0D MVS32H4NW0D4000A MVS40H3NW0D MVS40H4NW0D

CD

B50

0048

CD

B50

0048

* Non-standard confi gured products.Use customer order form in page F-15 to order non-standard products

(1) Supplied with spring charge motor(MCH), opening release(MX) andclosing release(XF) with 240V AC control voltage rating.

Page 79: Low Voltage EasyPact MVS

F-5

EasyPact MVSConnection

Catalogue numbersand order form

Connection3P 4P

Fixed circuit breakersRear connection (vertical or horizontal mounting) / Replacement kit (3 or 4 parts)

800-2000 A Vertical 47964 47965Horizontal 47964 47965

2500/3200 A Vertical 47966 47967Horizontal 47966 47967

4000 A Vertical 47968 47969Horizontal 47970 47971

Installation manual MVS21735Drawout circuit breakersRear connection (vertical or horizontal mounting) / Replacement kit (3 or 4 parts)

800-2000 A Vertical 47964 47965Horizontal 47964 47965

2500/3200 A Vertical 47966 47967Horizontal 47966 47967

4000 A Vertical 47968 47969Horizontal 47970 47971

Installation manual MVS21735

Connection accessoriesInterphase barriers / Replacement kit (3 parts)

For fi xed rear-connected circuit breaker 48599 48599For drawout rear-connected circuit breaker 48600 48600Installation manual MVS21735

E46

446

E46

445

Vertical mounting.

Horizontal mounting.

E46

446

E46

445

Vertical mounting.

Horizontal mounting.

E46

428

Page 80: Low Voltage EasyPact MVS

F-6

ET Trip System & accessoriesE

9554

0E

4667

1D

B10

5360

CD

B50

0038

ET trip units & accessoriesTrip units

ET2I protection relay for MVS 65477ET5S protection relay for MVS 65478ET6G protection relay for MVS 67479ETA2I protection relay for MVS 65577ETA5S protection relay for MVS 65578ETA6G protection relay for MVS 65579ETV2I protection relay for MVS MVS15501ETV5S protection relay for MVS MVS15502ETV6G protection relay for MVS MVS15503

Battery + coverBattery (1 part) 33593Cover (1 part) 33592

External sensorsExternal sensor for earth-fault protection (TCE) / 1 part

Sensor rating 400/2000 A 340351000/4000 A 34036

External power supply module (AD) / 1 part24-30 V DC 5444048-60 V DC 54441100-125 V DC 54442110-130 V AC 54443200-240 V AC 54444380-415 V AC 54445

Test equipments / 1 PartHand held test kit (HHTK) 33594

menu

CD

B50

0057

Page 81: Low Voltage EasyPact MVS

F-7

EasyPact MVSRemote operation

Catalogue numbersand order form

Remote operationGear motor

MCH (1 part)AC 50/60 Hz 100/130 V 47893

200/240 V 47894380/415 V 47896

DC 24/30 V 4788848/60 V 47889100/125 V 47890200/250 V 47891

Terminal block (1 part) For fi xed circuit breaker 47074For drawout circuit breaker 47849

Installation manual MVS21736Closing release (XF)

Standard coil (1 part)AC 50/60 HzDC

24/30 V DC, 24 V AC 3365948/60 V DC, 48 V AC 33660100/130 V AC/DC MVS15511200/250 V AC/DC MVS15512380/480 V AC MVS15513

Terminal block (1 part) For fi xed circuit breaker 47074For drawout circuit breaker 47849

Installation manual MVS21736Opening release (MX)

Standard coil (1 part)AC 50/60 HzDC

24/30 V DC, 24 V AC 3365948/60 V DC, 48 V AC 33660100/130 V AC/DC 33661200/250 V AC/DC 33662380/480 V AC 33664

Terminal block (1 part) For fi xed circuit breaker 47074For drawout circuit breaker 47849

Installation manual MVS21736

E95

172

E95

170

E95

170

E95

169

Fixed.

E95

171

Drawout.

E95

169

Fixed.

E95

171

Drawout.

E95

169

Fixed.

E95

171

Drawout.

Page 82: Low Voltage EasyPact MVS

F-8

Remote operationUndervoltage release MN

Undervoltage release (1 part)AC 50/60 HzDC

24/30 V DC, 24 V AC 3366848/60 V DC, 48 V AC 33669100/130 V AC/DC 33670200/250 V AC/DC 33671380/480 V AC 33673

Terminal block (1 part) For fi xed circuit breaker 47074For drawout circuit breaker 47849

Installation manual MVS21736MN delay unit

MN delay unit (1 part)R (non-adjustable) Rr (adjustable)

AC 50/60 HzDC

48/60 V AC/DC 33680100/130 V AC/DC 33684 33681200/250 V AC/DC 33685 33682380/480 V AC/DC 33683

Installation manual MVS21736

E95

170

E46

694

E95

169

Fixed.

E95

171

Drawout.

Page 83: Low Voltage EasyPact MVS

F-9

EasyPact MVSChassis locking and accessories

Catalogue numbersand order form

Chassis locking“Disconnected” position locking / 1 part

By padlocksVCPO Standard

By Profalux keylocksProfalux 1 lock with 1 key + adaptation kit 64934

2 locks 1 key + adaptation kit 64935Profalux 1 lock+ 1 key (without adaptation kit) 42888Profalux 2 locks + 1 key (without adaptation kit) 42878Adaptation kit (without key locks) 48564

By Ronis keylocksRonis 1 lock with 1 key + adaptation kit 64937

2 locks 1 key + adaptation kit 64938Ronis 1 lock+ 1 key (without adaptation kit) 41940Ronis 2 locks + 1 key (without adaptation kit) 41950Adaptation kit (without key locks) 48564

Installation manual MVS21737Door interlock / 1 part

Right and left-hand side of chassis (VPECD or VPECG) 47914

Installation manual MVS21737

Chassis accessoriesAuxiliary terminal shield (CB) / 1 part

800/4000 A 3P 649424P 48596

Installation manual MVS21737Safety shutters + locking block / 1 part

800/4000 A 3P 487214P 48723

Installation manual MVS21737Shutter locking block (for replacement) / 1 part

2 parts for 800/4000 A 48591

Installation manual MVS21737

Earthing kit for chassis3P 4P

Types for N/H/NA/HA48433 48434

E46

451

E46

452

E46

458

E46

459

E46

460

Page 84: Low Voltage EasyPact MVS

F-10

Clusters

Clusters1 disconnecting contact cluster for chassis (see table below) (part 1) 33166

Table : number of clusters required for the different chassis modelsChassis rating (A) EasyPact MVS(3P) EasyPact MVS(4P)

N H NA HA N H NA HA800 12 12 12 12 16 16 16 161000 12 12 12 12 16 16 16 161250 12 12 12 12 16 16 16 161600 12 12 12 12 16 16 16 162000 12 12 12 12 16 16 16 162500 24 12 24 12 32 16 32 163200 36 36 36 36 48 48 48 484000 42 42 42 42 56 56 56 56

Racking handleRacking handle 47944

E95

538

E95

561

Page 85: Low Voltage EasyPact MVS

F-11

Circuit breaker lockingPushbutton locking device / 1 part

By padlocks 48536

Installation manual MVS21736OFF position locking / 1 part

By Profalux keylocksProfalux 1 lock with 1 key + adaptation kit 64928

2 locks 1 keys + adaptation kit 64929Profalux 1 lock+ 1 key (without adaptation kit) 42888Profalux 2 locks + 1 key (without adaptation kit) 42878Adaptation kit (without key locks) 64925

By Ronis keylocksRonis 1 lock with 1 key + adaptation kit 64931

2 locks 1 keys + adaptation kit 64932Ronis 1 lock+ 1 key (without adaptation kit) 41940Ronis 2 locks + 1 key (without adaptation kit) 41950Adaptation kit (without key locks) 64925

Installation manual MVS21736Mechanical operation counter / 1 part

Operation counter CDM 48535

Installation manual MVS21736Escutcheon and accessories / 1 part

E46

669

E46

670

Escutcheon Cover Blanking plate

Fixed DrawoutEscutcheon 48601 48603Transparent cover (IP 54) - 48604Escutcheon blanking plate 48605 48605

Installation manual MVS21736Front cover (3P / 4P) / 1 part

MVS Front cover MVS21808

Installation manual MVS21736Spring charging handle / 1 part

Spring charging handle 47940

Installation manual MVS21736Arc chute for EasyPact MVS / 1 part

3P 4PType N/NA 3 x MVS21807 4 x MVS21807Type H/HA 3 x MVS21807 4 x MVS21807Installation manual MVS21736

E46

666

E46

735

DB

1256

17C

DB

5000

61C

DB

5000

58E

9553

6C

DB

5000

59

EasyPact MVSCircuit breaker locking and accessories

Catalogue numbersand order form

Page 86: Low Voltage EasyPact MVS

F-12

Mechanical interlocking for source changeover

Mechanical interlocking for source changeoverInterlocking of 2 devices using cables (1)

Choose 2 adaptation sets (1 for each device + 1 set of cables)1 adaptation fi xture for EasyPact MVS fi xed devices 479261 adaptation fi xture for EasyPact MVS drawout devices 479261 set of 2 cables 33209(1) Can be used with any combination of EasyPact MVS, fi xed or drawout devices.

Installation manual MVS21738Interlocking of 3 devices using cables

Choose 3 adaptation (including 3 adaptation fi xtures + cables)3 sources, only 1 device closed, fi xed or drawout devices 486102 sources + 1 coupling, fi xed or drawout devices 486092 normal + 1 replacement source, fi xed or drawout devices 48608Installation manual MVS21738

CD

B50

0053

CD

B50

0060

Page 87: Low Voltage EasyPact MVS

F-13

Indication contactsON/OFF indication contacts (OF) / 12 parts

1 additional block of 4 contacts 47887Wiring For fi xed circuit breaker 47074

For drawout circuit breaker 47849

Installation manual MVS21736“Ready to close” contact (1 max.) / 1 part

1 changeover contact (5 A - 240 V) 47080Wiring For fi xed circuit breaker 47074

For drawout circuit breaker 47849

Installation manual MVS21736“Connected, disconnected, test position” indication contact (carriage switches) / 1 part

Changeover contacts 6 A - 240 V 33170

Installation manual MVS21736Auxiliary terminals for chassis alone

3 wire terminal (1 part) 478496 wire terminal (1 part) 47850Jumpers (10 parts) 47900

E46

689

E46

438

E46

661

EasyPact MVSIndication contacts

Catalogue numbersand order form

Page 88: Low Voltage EasyPact MVS

F-14

Instructions

InstructionsEasyPact MVS User Manual (English) MVS21734Fixed & drawout circuit breaker MVS21735Circuit breaker accessories MVS21736Chassis accessories MVS21737Interlocking of EasyPact MVS devices MVS21738

Page 89: Low Voltage EasyPact MVS

F-15

To indicate your choices, check the applicable square boxes �

And enter the appropriate information in the rectangles

Circuit breaker or switch-disconnector Quantity

Rating A

Circuit breaker N/ H

Switch Disconnector NA/HA

Number of poles 3 or 4

Type of equipment Fixed

Draw out with chassis

Operating Mechanism Manual Operated

Electrical Operated

MCH - Gear motor V

XF - Closing coil V

MX - Shunt/Opening voltage release V

ET Range of Trip SystemET- Without display 2I 5S 6G

ETA - Current Metering 2I 5S 6G

ETV - Voltage Metering 2I 5S 6G

LR - Long-time rating plug Standard 0.4 to 1 Ir

ConnectionHorizontal Top Bottom

Vertical Top Bottom

Trip System functions:2I : Basic protection (long time + inst.)5S : Selective protection (long time + short time + inst.)6G : Selective + earth-fault protection (long time + short time + inst. + earth-fault)

EasyPact MVS

EasyPact MVSCircuit breaker and Switch-disconnectorsCustomer Order form

Indication contactsOF - ON/OFF indication contacts

Standard 1 block of 4 OF 10 A-240/380V AC

Additional 1 block of 4 OF 6 A-240/380V AC

SDE - “fault-trip” indication contact

Standard 1 SDE 5A -240/380V AC

OptionalCarriage switches 8 A-240/380V AC

CE - “Connected” position Max. 3 qty

CT - “Test” position Max. 3 qty

CD - “Disconnected” position Max. 3 qty

Remote tripping MN - Under voltage release V

R - Delay unit (fi xed time delay) 0.25s

Rr - Adjustable delay unit 0.5s……3s

AD - External power-supply module V

TCE - External sensor (NCT) for neutral of 3 Phase-4 Wire systems 400/2000A

TCE - External sensor (NCT) for neutral of 3 Phase-4 Wire systems 1000/4000A

PF - “Ready to close” contact 5A-240/380V AC

LocksVBP - ON/OFF pushbutton locking (by transparent cover using padlock)

VSPO - Device locking in OFF position by key lock (Only one key lock per ACB possible)

Key lock kit (w/o key lock) Profalux Ronis

1 key lock Profalux Ronis

2 identical key locks, 1 key Profalux Ronis

Chassis locking in “Disconnected” position:

VSPD - by key locks Key lock kit (w/o key lock) Profalux Ronis

1 key lock Profalux Ronis

2 identical key locks, 1 key Profalux Ronis

Door Interlock - VPEC On left-hand side of chassis (LH)

On right-hand side of chassis (RH)

Mechanical Interlocking of ACBs with Cable1 Normal source & 1 replacement source (2 devices)

2 normal + 1 replacement source, fi xed or drawout devices

2 sources with coupler on busbars (3 devices)

3 sources, only 1 device closed, fi xed or drawout devices

AccessoriesVO - Safety shutters on chassis Standard

CDP - Escutcheon Standard

Safety Shutter locking blocks

CP - Transparent cover for escutcheon

OP - Blanking plate for escutcheon

CDM - Mechanical operation counter for MVS

CB - Auxiliary terminal shield fi tted on chassis

EIP - Interphase barriers

HHTK - Hand held test kit

Notes:Customer can provide only the reference no. of the product for the listed references. Kindly refer to product catalogue for list of references. Customer to fi ll this order form for non-listed references.All breakers will be provided with 1 OF (4 c/o contacts), 1 SDE (trip contact), Escutcheon (Panel sealing frame) as standard.All draw-out type devices will be supplied with Chassis & safety shutter.For Electrical operated devices, indicate the voltage ratings of MCH,XF & MXRefer to product catalogue for available voltage ratings of MCH/XF/MX/MN & AD ModuleThe orientation of customer connecting terminals can be changed at site from Horizontal to vertical or vice-versa.

Order ref no:

Date:

Product ref no:

Catalogue numbersand order form

Page 90: Low Voltage EasyPact MVS

Enroll TODAY! Classes are FREE , for a limited time only! Visit www.MyEnergyUniversity.com and enter the key code 32323P

Become an energy champion today!Because saving energy is everyone’s business

Schneider Electric FZE

E Wing, Level 4, Dubai Silicon Oasis Headquarters,P.O. Box 341057, Dubai, United Arab EmiratesPhone: + 971 (4) 709 91 00Fax: + 971 (4) 709 91 01www.schneider-electric.com/ae

Schneider Electric Industries SAS

35, rue Joseph MonierCS 30323F- 92506 Rueil Malmaison Cedexwww.schneider-electric.com

As standards, specifications and designs change from time to time, please ask for confirmation of the information given in this publication.

Designed by: Schneider Electric

Make the most of your energy SM

© 2

014

Schn

eide

r Ele

ctric

. All

right

s re

serv

ed.

GFLVED211021EN January 2014

Stay connected all the time. Join us!S ET V“Like” and “Follow” Schneider Electric on

or visit www.schneider-electric.com/ae

> Free Energy Efficiency courses for you and your staff> On-demand training takes less than an hour> More than 50,000 courses completed to date> Courses now available in multiple languages: Arabic, English, Chinese,

Spanish, Italian, Russian, Brazilian Portuguese, German, Dutch, French, Japanese, Korean and Turkish.

> More than 30,000 registered users from 120 plus countries