550720 Revision F

Liquid-Level TransmitterModel M-SeriesAnalog Output

Operation and Installation

l

L e v e l P l u s ®

Page 2: Liquid-Level Transmitter Model M-Series Analog Outputmskcorp.co.kr/pdf_file/mts/M/M-Series-Manual.pdf · Liquid-Level Transmitter Model M-Series Analog Output ... the transmitter

TABLE OF CONTENTSSection Page

Notices used in this book iiiRelated publications iiiHow this book is organized iiiGetting information, help, and service iv

1.0 INTRODUCTION 12.0 PRODUCT DESCRIPTION 2

2.1 Level Plus M-Series transmitter specifications 32.2 Accuracy 42.3 Theory of operation 42.4 Enclosure options for a Level Plus M-Series transmitter 5

3.0 INSTALLATION AND MOUNTING 63.1 Rigid and flexible transmitter mounting options 6

3.1a Threaded-flange mounting 63.1b Welded-flange mounting 7

3.2 Sanitary transmitter mounting 83.3 Installing a flexible sensor pipe with a bottom-fixing weight or magnet 83.4 Installing a flexible sensor element 9

4.0 ELECTRICAL CONNECTIONS AND WIRING PROCEDURES 124.1 Agency controlled drawing references, M-Series Analog 13

4.1a Installation drawing, M-Series transmitter with explosionproof enclosure, part no. 650805 (revision D) sheet 1 of 2. 13

4.1b Installation drawing, M-Series transmitter with explosionproof enclosure, part no. 650805 (revision D) sheet 2 of 2. 14

4.2 Electrical conduit installation 154.3 Cable specifications 164.4 Safety guidelines for the M-Series transmitter 174.5 Safety barriers for IS installation 17

5.0 SYSTEM CHECK 185.1 Performing a loop #1 test 185.2 Performing a loop #2 test (if applicable) 18

6.0 FLOATS 187.0 MAINTENANCE 19

7.1 Replacing an M-Series electronic module (puck) or interconnect board 197.1a Replacing an M-Series electronics module (puck) 197.1b Replacing the interconnect board 20

8.0 USING THE KEYPAD DISPLAY TO CALIBRATE THE LEVEL PLUS M-SERIES 20TRANSMITTER8.1 Modes of operation 208.2 LCD display and keypad (optional) 228.3 Alarm settings 238.4 Manual calibration 23

9.0 USING THE HART COMMUNICATION PROTOCOL TO CALIBRATE THE M-SERIES TRANSMITTER 249.1 Preparing the transmitter for re-calibration 249.2 Setting the low value 259.3 Setting the high value 25

10.0 INSTALLING AND USING THE M-SERIES FIELD SETUP SOFTWARE V1.01 (CD-ROM) T0 SETUP PARAMETERS AND ADJUST CALIBRATION 2610.1 Installing the M-series Field Setup software v1.0 2610.2 Calibration and setup parameters 2710.3 Instrument parameters 27

ii

Page 3: Liquid-Level Transmitter Model M-Series Analog Outputmskcorp.co.kr/pdf_file/mts/M/M-Series-Manual.pdf · Liquid-Level Transmitter Model M-Series Analog Output ... the transmitter

Notices used in this book

This book contains notices to highlight specific information as follows:

Notes

These notices provide important tips, guidance, or advice.

Important

These notices provide information that might help you avoid inconvenient or problem situations.

Attention

These notices indicate possible damage to programs, devices, or data. An attention notice is placed justbefore the instruction or situation in which damage could occur.

Caution

These notices indicate situations that can be potentially hazardous to you. A Caution notice is placed justbefore a description of a potentially hazardous procedure, step, or situation.

Related publications

The following publications are available in Adobe Acrobat Portable Document Format (PDF) athttp://www.mtssensors.com.

550731 Installation sheet, M-Series Electronics Module550677 Product Specification, Level Plus M-Series Analog550537 Product Specification, Level Plus M-Series Floats and Accessories

For information about safe work procedures, refer to the following documentation:National Electric Code ANSI/NFPA 70

How this book is organized

1.0 “Introduction”, on page 1 provides an overview of the Level Plus M-Series transmitter and its features.

2.0 “Product Description”, on page 2 gives an overall product description for the Level Plus liquid level sensor, its specifications, use output, and electronics.

3.0 “Installation and Mounting” on page 6 provides detailed installation and mounting information.

4.0 “Electrical Connections and Wiring Procedures” on page 12 provides Engineering specifications and wiring diagrams to assist in the installation process.

5.0 “System Check” on page 18 provides information about testing Loop 1 and Loop 2.

6.0 “Floats” on page 18 provides guidelines for selecting the appropriate float for your application.

7.0 “Maintenance” on page 19 provides the procedures required for replacing the M-Series electronic module or electronic transmitter?

8.0 “Using the Keypad Display to Calibrate the Level Plus M-Series Transmitter” on page 21 describes modes of operation, LCD display functionality, alarm settings and how to calibrate the unit manually.

9.0 “Using the HART Communication Protocol to Calibrate the M-Series Transmitter” on page 24 provides procedures for recalibration and setting low and high values.

10.0“Installing and Using the M-Series Field Setup Software v1.01 (CD-ROM) to Setup Parameters and Adjust Calibration“ on page 26 provides software installation, parameter setup, and calibration procedures.

iii

Page 4: Liquid-Level Transmitter Model M-Series Analog Outputmskcorp.co.kr/pdf_file/mts/M/M-Series-Manual.pdf · Liquid-Level Transmitter Model M-Series Analog Output ... the transmitter

iv

Getting information, help, and service

Ordering information and software updates

You can get the latest ordering information and software updates by using the World Wide Web. Go towww.mtssensors.com.

For information relating to HART® Communication Foundation , go to www.hartcomm.org.

HART Communication Foundation (USA)9390 Research Blvd., Suite I-350Austin TX 78759

Fax: 512.794.3904Phone: 512.794.0369

Contact information

Fax: 800.943.1145919.677.2545

Phone: 800.457.6620919.678.2769

Email: [email protected]

Shipping address

MTS Systems CorporationSensors Division3001 Sheldon DriveCary, North Carolina 27513

Office hoursMonday - Friday: 8:00 a.m. to 5:00 p.m. EST

Page 5: Liquid-Level Transmitter Model M-Series Analog Outputmskcorp.co.kr/pdf_file/mts/M/M-Series-Manual.pdf · Liquid-Level Transmitter Model M-Series Analog Output ... the transmitter

1.0 INTRODUCTION

MTS is recognized as the pioneer, innovator and leader in magnetostrictive sensing. The Level Plus® M-Seriestransmitter design represents a continuation of our on-going effort to provide effective, innovative and reliableproducts to the liquid-level marketplace.

Throughout this document, the following “short names” are used:

• Level Plus M-Series Transmitter is referred to as M-Series transmitter or transmitter• Transmitter electronics interconnect board is referred to as interconnect board.• HART hand-held converter is referred to as HART converter• Electronics module is referred to as puck• Housing is referred to as enclosure• Bottom-fixing weight, magnet or hook is referred to as retaining hardware

Go to www.mtssensors.com for:

• Current Level Plus M-Series model numbers.

• Detailed ordering information.

• Ordering online using our interactive application worksheets.

• Downloading Software updates.

1

Page 6: Liquid-Level Transmitter Model M-Series Analog Outputmskcorp.co.kr/pdf_file/mts/M/M-Series-Manual.pdf · Liquid-Level Transmitter Model M-Series Analog Output ... the transmitter

2.0 PRODUCT DESCRIPTION

The Level Plus M-Series transmitter is multi-functional with two 4-20 mA loops that utilize HighwayAddressable Remote Transducer (HART) communications. It provides up to two analog outputs of level, inter-face, or temperature. An optional electronics module displays simultaneous readouts of level, interface, or tem-perature. The optional electronics module is designed with three push buttons for local setup of all parameters.Outputs can be monitored using 4-20 mA signal output, when you use a RS-232 to HART Hand-Held Converterwith an optional integral display or MTS PC-compatible M-Series Field Setup software.

Level Plus M-Series transmitters can be housed in three types of enclosure configurations: • NEMA 4X electropolished• Stainless steel with I.S. approval• Single cavity or dual-cavity explosionproof enclosure with epoxy-powder coating.

The outer pipe is constructed of a variety of configurations (Contact factory for other materials):• 5/8 in. diameter rigid outer pipe of 316L stainless steel • 5/8 in. diameter rigid outer pipe of polished 316L stainless steel with sanitary process connection

and end-plug.• 7/8 in. diameter flexible pipe of 316L stainless steel

M-Series transmitters utilize a special sensor element which allows easy removal or replacement while the tank orvessel is in service, leaving the tank connection or seal intact. This design allows the sensor element to beinstalled or removed in situations where there is a low overhead clearance.

A temperature sensing function is optional with the M-Series transmitter. The temperature sensing device is aResistive Temperature Device (RTD) mounted inside the transmitter’s outer tube assembly. The RTD is a 1000ohm platinum film device.

2

Page 7: Liquid-Level Transmitter Model M-Series Analog Outputmskcorp.co.kr/pdf_file/mts/M/M-Series-Manual.pdf · Liquid-Level Transmitter Model M-Series Analog Output ... the transmitter

3

2.1 Level Plus M-Series transmitter specifications

P A R A M E T E R S P E C I F I C A T I O N

LEVEL OUTPUTMeasured variable: Product level and interface levelOutput: 4-20 mA, 2 loops with HART interfaceFull range: Flexible gauges: 120 to 480 in. (3050 to 11890 mm)

Rigid gauges: 20 in. to 300 in (508 mm to 7620 mm)vt

Notes: Rigid sensor pipes have a rigid sensor element. Flexible sensor pipes have a flexible sensor element. Flexible sensor elements are available for rigid pipe configuration as an option.

Non-linearity: Flexible gauges: 0.035% F.S. (independent BSL) or 1/32 in. (0.794 mm)HRigid gauges: 0.020% F.S. (independent BSL) or 1/32 in. (0.794 mm)H

Repeatability: Flexible gauges: Up to 0.01% F.S. or 0.015 in. (0.381 mm)HRigid gauges: Up to 0.005% F.S. or 0.005 in. or (0.127 mm)H

Sensor operating temperature: -40 to 257 oF (-40 to 125 oC) (Consult factory for higher temperature applications.)GAUGE LOOPInput voltage range: 10.5 to 36.1 VdcReverse polarity protection: Series diodeTransient protection: Stage 1: Line-to-ground surge suppressors; 2500 Amps peak (8/20 µsec)

Stage 2: Line-to-line and line-to-ground transient suppressors; 1500 Watts peak (10/1000 µsec)CALIBRATIONZero adjust range: Anywhere within the active lengthSpan adjust range: Full scale ≥ 0.5 ft. (152 mm) from zeroTEMPERATURE OUTPUTType: 4-20 mA from 1,000 ohm platinum RTD at 0 oCRepeatability: ±0.18 oF (0.1 oC)Accuracy: ±2.7 oF (±1.5 oC)Drift: ±0.9 oF (0.5 oC) per yearZero adjust: -40 to 255 oF (-40.to 124 oC)Span adjust: 45 oF (7.2 oC) minimum, full scale (maximum) = 300 oF (149 oC)ENVIRONMENTALHumidity: 0 to 100% R.H., non-condensingElectronics operating temperature: -30 to 160 oF (-34 to 71 oC)Vessel pressure: Dependent on float pressure rating, refer to MTS document part number 550537 for more information.s

Materials (wetted parts): 316L stainless steel lFIELD INSTALLATION:Length (including housing): 20 in to 40 ft. (508 to 12,192 mm)vt

Mounting: 3/4 in. NPT adjustable fitting (rigid pipe) 1 in. NPT adjustable fitting (flex pipe)

Wiring: 2-wire connection, shielded cable or twisted pair to screw terminals through a 3/4 in. NPT conduit opening. NEMA 4X:15 ft. (457 cm) pigtail integral cable or Daniel Woodhead (part number 70807SS) 6-pole Male 1/4 in.-18

MNPT key-way receptacle.DISPLAY (Optional)Measured variables: Level 1, Level 2 and temperature.Update rate: 3 secondSize: 0.5 in. (12.7 mm)Number of digits: 16HART communicationsMethod of communication: Frequency Shift Keying (FSK) conforms with Bell 202 Modem Standard with respect to baud rate and digital “1” and “0”

frequencies.Baud rate: 1200 bps.Digital “0” frequency: 2200 Hz.Digital “1” frequency: 1200 Hz.Data-byte structure: 1 Start bit, 8 data bits, 1 odd parity bit, and 1 stop bitDigital process variable rate: Poll/Response Midel 2.0 per second

Page 8: Liquid-Level Transmitter Model M-Series Analog Outputmskcorp.co.kr/pdf_file/mts/M/M-Series-Manual.pdf · Liquid-Level Transmitter Model M-Series Analog Output ... the transmitter

4

2.2 Accuracy

The absolute accuracy of the transmitter is a function of the manufacture of the waveguide. That is, any imper-fections in the waveguide are reflected in the linearity of its output. MTS tolerances reflect a maximum non-lin-earity of 0.035% of full scale. Due to its high degree of repeatability, the differential accuracy is extremely high.

2.3 Theory of operation

The magnetostrictive Level Plus M-Series transmitter will pre-cisely sense the position of an external float by applying an inter-rogation pulse to a waveguide medium. This current pulse causesa magnetic field to instantly surround the waveguide. The mag-net installed within the float also creates a magnetic field. Wherethe magnetic fields from the waveguide and float intersect, arotational force is created (waveguide twist). This, in turn, cre-ates a torsional-sonic pulse that travels along the waveguide asshown in Figure 2-1 “Principal of magnetostriction”.

The head of the sensing element houses the sensing circuit,which detects the torsional-sonic pulse and converts it to an elec-trical pulse. The distance from a reference point to the float isdetermined by measuring the time interval between the initiatingcurrent pulse and the return pulse and precisely knowing thespeed of these pulses. The time interval is converted into a 4-20mA loop signal.

The Level Plus M-Series transmitter offers level, interface, ortemperature outputs. There are two current loops available; anyoutput may be assigned to either of the two loops.

Float(moves as level changes)

Waveguide

Outer pipe

Float magnets

Magnetic fieldfrom float magnets

Waveguide twist(at intersection ofmagnetic field)

Magnetic field frominterrogation pulse

Figure 2-1Principle of magnetostriction

P A R A M E T E R S P E C I F I C A T I O N

AGENCY/SAFETY Approval: FM/CSA: Explosion-proof FM/CSA: Intrinsically Safe Class I, Groups B,C,D Class I, Groups A,B,C,DClass II, Groups E,F,G Class II, Groups E,F,GDivision 1, NEMA 4X Division I, NEMA 4XModels: Explosion-proof housing req. Models: All

H Whichever is greaterHHMust specify at time of order, not on all unitstContact factory for longer lengths. l Contact factory for other materialss Contact factory for higher pressure ratings.v Flexible sensor elements are available for rigid pipe configurations as an option.All Specifications are subject to change. Please contact MTS for specifications critical to your needs.

Page 9: Liquid-Level Transmitter Model M-Series Analog Outputmskcorp.co.kr/pdf_file/mts/M/M-Series-Manual.pdf · Liquid-Level Transmitter Model M-Series Analog Output ... the transmitter

5

2.4 Enclosure options fora Level Plus M-Series transmitter

There are three M-Series transmitter enclosure options: NEMA 4X, single-cavity and dual-cavity enclosure. TheNEMA 4X enclosure is constructed of 316L stainless steel. The single and dual-cavity enclosures are ratedNEMA 7 explosionproof. Enclosure dimensions are shown in Figure 2-2a, 2b and 2c below.

Figure 2-2 M-Series transmitter enclosure dimensions

Figure 2-2bSingle-cavity explosionproof enclosure

Figure 2-2cDual-cavity explosionproof enclosure

4.84 in. (123 mm)5 in. (127 mm)

8.25 in.(210 mm)

5 in. (127 mm)

8.25 in.(210 mm)

Optionaldisplay

3/4 in. NPT conduit access

5 in. (127 mm)

8.25 in.(210 mm)

5 in. (127 mm)

8.25 in.(210 mm)

6.95 in. (176 mm)

3.48 in.(88 mm)

Optionaldisplay

3/4 in. NPT conduit access

Figure 2-2aNEMA 4X enclosure

4.85 in. (123 mm)

3.19 in.(81 mm)

6.0 in.(152 mm)

4.85 in. (123 mm)

Factory supplied pigtailcable (15 ft.)

Page 10: Liquid-Level Transmitter Model M-Series Analog Outputmskcorp.co.kr/pdf_file/mts/M/M-Series-Manual.pdf · Liquid-Level Transmitter Model M-Series Analog Output ... the transmitter

3.0 INSTALLATION AND MOUNTING

The method you use to mount the M-Series transmitter is dependent on the vessel or tank in which it is beingused, and what type of sensor is being mounted. Most applications will require one of two methods; threaded orflange mounting, as shown in Figure 3-1a “Threaded-flange mounting for rigid and flexible pipe” and Figure 3-1b“Welded-flange mounting for rigid and flexible pipe”. (For detailed information about Sanitary application mount-ing, go to 3.2 “Sanitary Sensor Mounting” on page 8.)

3.1 Rigid and flexible transmitter mounting options

3.1a Threaded-flange mountingIn applications with smaller vessels and tanks, the transmitter can be mounted directly to the tank or flange byusing a threaded NPT fitting, assuming there is a proper threaded connection available. If the float will not fitthrough the tank flange, there must also be some means to mount the float on the transmitter from inside the ves-sel; this may require a float access port nearby the entry point of the transmitter (as shown in Figure 3-1a“Threaded-flange mounting for rigid and flexible pipe” on page 6).

Complete the following steps to mount the transmitter using the threaded-flange method:

1. Remove the float(s) retaining hardware, then remove the transmitter.

2. Insert the transmitter tip through the threaded vessel opening or flange.

3. The transmitter tip can now be lowered to the vessel bottom and the connection can be made from the thread-ed NPT fitting to the vessel. In general, there should not be more than 12 inches of the transmitter’s pipeassembly extending above the vessel.

Important:Before you completely insert the transmitter to the bottom of the vessel, you must remount the float(s) through anaccess port and also reattach the float retaining hardware.

Figure 3-1aThreaded-flange mountingfor rigid and flexible pipe

Riser

NPT Fitting

Tip of transmitter

Tank flange(provided by customeror ordered separately)

Float access port

Retaining hardware

Pipe assembly

6

Page 11: Liquid-Level Transmitter Model M-Series Analog Outputmskcorp.co.kr/pdf_file/mts/M/M-Series-Manual.pdf · Liquid-Level Transmitter Model M-Series Analog Output ... the transmitter

7

3.1b Welded-flange mounting

The M-Series transmitter can also be mounted to a tank flange as shown in Figure 3-1b “Welded-flange mountingfor rigid and flexible pipe”. Complete the following steps to mount the transmitter onto a tank flange:

1. Install the product and interface floats onto the flexible-sensor pipe.

2. Install the bottom-fixing weight, magnet or hook (also referred to as retaining hardware) on to the tip of the trans-mitter.

3. To complete the installation, mount the transmitter, tank flange, flexible-sensor pipe and product/interface floats asan assembled unit in to the tank.

Note:In general, there should not be more than 12 inches of the transmitter’s sensor pipe length extending above the vessel.

Figure 3-1bWelded-flange mountingfor rigid and flexible pipe

Stainless steelflexible sensor pipe

Interfacefloat

Riser

Productfloat

Welding sleeve1.125 in.(28.6 mm) dia.

Flange (welded)

Tank flange

Bottom-fixing weight,magnet, or hook

Page 12: Liquid-Level Transmitter Model M-Series Analog Outputmskcorp.co.kr/pdf_file/mts/M/M-Series-Manual.pdf · Liquid-Level Transmitter Model M-Series Analog Output ... the transmitter

3.2 Sanitary transmitter mounting

In sanitary applications, the M-Series transmitter is mounted to the tank using a standard sanitary process connec-tion and sanitary clamp* as shown in Figure 3-2 “M-Series transmitter, tank-mounted sanitary connection”. In mostcases, it is not necessary to remove the sanitary float as the sanitary end-plug fitting is sized to allow installationwith the float in place. Please note that some sanitary end-plug styles have the float(s) permanently mounted.

3.3 Installing a flexible sensor pipe with a bottom-fixing weight or magnet

Complete the following steps to install a flexible sensor pipe with a bottom-fixing weight or magnet:

1. With assistance, feed the flexible sensor pipe through the NPT opening of the tank flange until the flange ispositioned at the rigid section of flexible sensor pipe near the top of the transmitter. Insert the threaded por-tion of the adjustable fitting into the customer flange (apply pipe thread sealant if required). See Figure 3-1a“Threaded-flange mounting for rigid and flexible pipe” on page 6.

2. Slide the product float onto the flexible sensor pipe. See Figure 3-1b “Welded-flange mounting for rigid and flexi-ble pipe” on page 7.

3. Slide the interface float (optional) onto the flexible sensor pipe. Figure 3-1b “Welded-flange mounting for rigidand flexible pipe” on page 7.

4. If you are using a weight or magnet, mount the weight or the magnet to the welded end-plug section of the flexi-ble sensor pipe (this is the bottom rigid section of the flexible sensor pipe) using the supplied nut, spacer andwasher as shown in Figure 3-3 “Retaining hardware” on page 9. Securely tighten mounting nut using 1/2-inchwrench.

Attention:Be careful not to drop the flange on flexible sensor pipe as damage may result.

Important:When assembling and installing the M-Series transmitter, be careful not to allow the flexible hose to kink or becoiled in less than an 16-inch diameter.

To ensure proper and safe assembly and mounting of the transmitter, a minimum of two (2) individuals are required.Gloves are also required.

Sanitary process connnection*(welded to sensor pipe)

Sanitary clamp(customer supplied)

Mating process connection(customer supplied)

Factory supplied pigtailcable (15 ft.)

Sanitary float(permanently mounted withT-bar and drain-in-place endplug styles)

Tip of transmitter

Top viewRiser

*�When using the adjustable tri-clamp(version 401537-1 through -14), thetri-clamp must be removed andmanually cleaned per 3A guidelines.

*�When using the adjustable tri-clamp(version 401537-1 through -14), thetri-clamp must be removed andmanually cleaned per 3A guidelines.

Figure 3-2M-Series transmitter, tank-mounted sanitary connection

Attention:Do not drop the float(s) or allow them to free fall along the flexible sensor pipe as damage may result.

8

Page 13: Liquid-Level Transmitter Model M-Series Analog Outputmskcorp.co.kr/pdf_file/mts/M/M-Series-Manual.pdf · Liquid-Level Transmitter Model M-Series Analog Output ... the transmitter

9

5. Slide the float(s) back down to the weight or magnet to prevent them from free falling during installation intothe tank. Insert the flexible sensor pipe (with floats) through the tank riser pipe and lower the transmitterassembly into the tank until it rests on the bottom. DO NOT DROP OR DAMAGE THE PIPE.

6. If you are using a flexible sensor pipe with a bottom-fixing hook, fasten the bottom-fixing hook to the appropri-ate customer-supplied mating hardware at the tank bottom.

7. Secure the flange onto the tank riser pipe.

8. Pull the flexible sensor pipe upward to straighten the pipe until the resistance of the weight or magnet is feltwithout raising the weight or magnet off the floor of the tank. Tighten the adjustable fitting to hold the sensorin place.

9. Terminate the field-wire cables noting proper wire orientation.

3.4 Installing a flexible sensor element

Complete the following steps to replace an transmitter electronics housing and flexible sensor element into an exist-ing pipe assembly:

Attention:• Do not bend flexible sensor element to less than a 16-inch bending diameter or damage may result.• Always use safe handling procedures when handling electronics equipment.• Be sure that the inside of the existing outer pipe is clean and dry, and free of debris before installing the M-Series

transmitter.

Attention:Do not kink or bend the flexible sensor pipe in less that a 16-inch diameter as damage may result.

Weight

Flexible sensor pipe Flexible sensor pipe

Magnet

Gauge retention using weight

Weldedend-plug

Flexible sensor pipe

Weldedend-plug

Bottom-fixing hook (mates with customer-supplied

hardware mounted on tank bottom)

Nut Nut

Weldedend-plug

Washer Washer

Spacer Spacer

Gauge retention using hookGauge retention using magnet

Figure 3-3Retaining hardware

Page 14: Liquid-Level Transmitter Model M-Series Analog Outputmskcorp.co.kr/pdf_file/mts/M/M-Series-Manual.pdf · Liquid-Level Transmitter Model M-Series Analog Output ... the transmitter

1. Sensor pipe and floats should already be installed (see 3.2 “Sanitary Sensor Mounting” on page 8). The electron-ics housing and sensor element portion of the gauge should be separate from the sensor pipe, as shown inFigure-3-4 “Flexible sensor element installation”.

The M-Series transmitter is shipped with the following mounting hardware (as shown in Figure 3-5 “Installing themounting hardware”):

1 hex nut1 ferrule1 rubber sleeve

2. Install the hex nut onto the existing sensor pipe to ensure the threads on the inside of the hex nut are facing up.

3. Install the ferrule onto the sensor pipe, ensuring that the tapered end is down.

4. Install the rubber sleeve onto the sensor pipe and push the rubber sleeve down into the hex nut.

Important:The mounting hardware must be installed in a specific order, and when installed, the ferrule and rubber sleeve collapseinside of the hex nut.

NPT Fitting

Tip of transmitter

Tank

Existing pipeassembly

installation

Sensorcartridge

Flexible sensorelement

M-Series transmitterelectronics housing withsensor element

Enclosure

Figure 3-4 Flexible sensor element installation

Tank flangeNPT Fitting

Mountinghardware

Hex nut

Ferrule

Rubber sleeve

Installed sensor pipe

Figure 3-5 Installing the mounting hardware

10

Page 15: Liquid-Level Transmitter Model M-Series Analog Outputmskcorp.co.kr/pdf_file/mts/M/M-Series-Manual.pdf · Liquid-Level Transmitter Model M-Series Analog Output ... the transmitter

5. Mount the sensor element into the existing sensor pipe. Do not damage or kink the flexible sensor element inless than a 16-inch bend diameter while installing the element. Guide the sensor downward until the matingsurface of the enclosure installs over the existing sensor pipe, as shown in Figure 3-6a.

6. Make sure that the sensor pipe seats firm against the sensor cartridge nut and then pull up the mounting hard-ware to engage it with the threads of the sensor cartridge, as shown in Figure 3-6b. Ensure that you are notcross-threading as you begin to screw the hex nut onto the threads.

7. Hand tighten the mounting hardware and tighten another two full turns with a wrench. Hold the sensor car-tridge nut while tightening the mounting hardware to ensure that the electronics housing does not swivel withthe turning of the wrench.

8. Ensure that the enclosure and existing pipe assembly are properly tightened; pull up on the enclosure, theenclosure and pipe assembly should not move.

NPT Fitting

Tank

Existing pipeassembly installation

Sensor element

Mountinghardware

Enclosure

Figure 3-6a Figure 3-6b

Tank

Mountinghardware

Sensor cartridge nut

Enclosure

11

Page 16: Liquid-Level Transmitter Model M-Series Analog Outputmskcorp.co.kr/pdf_file/mts/M/M-Series-Manual.pdf · Liquid-Level Transmitter Model M-Series Analog Output ... the transmitter

4.0 ELECTRICAL CONNECTIONS AND WIRING PROCEDURES

A typical intrinsically-safe connection for the Level Plus transmitter includes protective safety barriers, a powersupply, and a reading or monitoring device. Refer to MTS drawing number 650805 (Revision D) in section 4-1aand 4-1b on pages 13 and 14 for detailed installation and wiring information.

If you are using an integral connector with a NEMA 4X Intrinsically safe enclosure, see section 4-1b “Installationdrawing, M-Series transmitter with NEMA 4X enclosure” on page 14 MTS drawing part number 650805 forwiring information.

A typical explosionproof connection for the Level Plus transmitter includes a power supply and a reading or monitoring device connected using an explosionproof conduit (see section 4.1 “Agency controlled drawing refer-ences, M-Series Analog” on page 13 for a typical conduit installation). Refer to MTS engineering drawing number650805 (Revision D) for detailed installation and wiring information. See also section 4.2 “Electrical Conduitinstallation”.

Notes:1. Loop #1 must be powered on for the M-Series transmitter to operate properly.2. For explosionproof installation, safety barriers are not required and wiring must be installed in accordance with the

National Electric Code ANSI/NFPA 70.

12

Page 17: Liquid-Level Transmitter Model M-Series Analog Outputmskcorp.co.kr/pdf_file/mts/M/M-Series-Manual.pdf · Liquid-Level Transmitter Model M-Series Analog Output ... the transmitter

4.1 Agency controlled drawing references, M-Series analog

4.1a. Installation drawing, M-Series transmitter with explosionproof enclosure, 650805 (Revision D) sheet 1 of 2

M-S

erie

s Tr

ansm

itte

rLe

vel P

lus

LO

OP

1 T

ES

T

RR

HA

RT

LO

OP

2 T

ES

T

Æ

+-

+-

J4 LOO

P 2

+

+

J2

TB1

J3

J1

J6

J7

J5

J6J6J2J2

J3J3

J5J5TB1

TB1

J7J7

J4J4

J1J1

LOO

P 1

-

1

1

++

-

-

-

NO

REV

ISIO

NS

SHA

LL B

E M

AD

E W

ITH

OU

T N

OTI

FIC

ATI

ON

TO

APP

ROV

AL

AG

ENC

Y(S

).

A

ND

CLA

SS

HA

ZA

RDO

US

LOC

ATI

ON

S.

15. U

SE O

NLY

NRT

L LI

STED

AN

D C

SA C

ERTI

FIED

DU

ST-T

IGH

T SE

AL

FOR

CLA

SS

O

NLY

BE

CO

NN

ECTE

D IN

AC

CO

RDA

NC

E W

/MFG

IS IN

STA

LLA

TIO

N IN

STRU

CTI

ON

S.

14. H

ART

CO

MM

UN

ICA

TOR

WH

ICH

FM

& C

SA A

PPRO

VED

(AS

APP

LIC

AB

LE) M

UST

* RU

NN

ING

LO

OPS

IN S

EPA

RATE

GRO

UN

DED

SH

IELD

S.

* RU

NN

ING

LO

OPS

IN S

EPA

RATE

CA

BLE

S.

13. A

PPRO

VED

MET

HO

DS

FOR

SEPA

RATI

ON

OF

EAC

H L

OO

P A

RE:

CLA

SS II

IC

LASS

, D

IVIS

ION

1, G

ROU

PS E

, F A

ND

G,

11. E

AC

H L

OO

P EN

TITY

PA

RAM

ETER

S

WIT

H N

EMA

/TY

PE 4

X, F

OR

OU

TDO

OR

USE

.

Vm

ax=

36V

Imax

= 1

18m

AC

= 0

L =

200

uH

W

ITH

TH

E C

OU

NTR

Y IN

USE

(eg

CA

NA

DIA

N E

LEC

TRIC

AL

CO

DE,

PA

RT 1

, NA

TIO

NA

L

N

OT

EXC

EED

BA

RRIE

R La

. (SE

E N

OTE

14)

B

ARR

IER

Ca.

TRA

NSM

ITTE

R Li

PLU

S TO

TAL

CA

BLE

IND

UC

TAN

CE

FOR

EAC

H L

OO

P M

UST

7. T

RAN

SMIT

TER

Ci P

LUS

TOTA

L C

AB

LE C

APA

CIT

AN

CE

FOR

EAC

H L

OO

P M

UST

NO

T EX

CEE

D

A

ND

TRA

NSM

ITTE

R Im

ax IS

GRE

ATE

R TH

AN

BA

RRIE

R Is

c.

APP

ROV

ED C

ON

FIG

URA

TIO

N W

HER

E TR

AN

SMIT

TER

Vm

ax IS

GRE

ATE

R TH

AN

BA

RRIE

R V

oc

6. S

AFE

TY B

ARR

IERS

ARE

FM

RC A

ND

CSA

EN

TITY

APP

ROV

ED S

AFE

TY B

ARR

IERS

USE

D IN

AN

4. F

OR

FMRC

& C

SA A

PPRO

VED

GA

UG

ES, B

ARR

IERS

MU

ST B

E FM

RC &

CSA

APP

ROV

ED.

8. G

AU

GE

ENC

LOSU

RE S

HA

LL B

E G

ROU

ND

ED T

O E

ART

H G

ROU

ND

TH

ROU

GH

TH

E PR

OV

IDED

A

PPRO

VED

SA

FETY

BA

RRIE

RS A

ND

SY

STEM

EA

RTH

GRO

UN

D M

UST

BE

LESS

TH

AN

1 o

hm

.

5. T

HE

CO

NN

ECTI

ON

BET

WEE

N T

HE

EART

H G

ROU

ND

TER

MIN

AL

3. C

ON

TRO

L RO

OM

EQ

UIP

MEN

T SH

OU

LD N

OT

USE

OR

GEN

ERA

TE M

ORE

TH

AN

250

V R

MS.

1. F

OR

I.S. F

IELD

INST

ALL

ATI

ON

WIR

ING

SH

ALL

BE

INST

ALL

ED IN

AC

CO

RDA

NC

E

I=4

TO 2

0 m

A

10

CLA

SS I,

DIV

ISIO

N 1

, GRO

UPS

A, B

, C A

ND

D

INTR

INSI

CIA

LLY

SA

FE F

OR:

9. N

O R

EVIS

ION

S SH

ALL

BE

MA

DE

WIT

HO

UT

GRO

UN

D L

UG

IN T

HE

ENC

LOSU

RE.

CA

BLE

CA

PAC

ITA

NC

E SH

ALL

BE

LESS

TH

AN

30

PF P

ER F

OO

T.

.2. S

HIE

LDED

TW

ISTE

D C

AB

LE O

F 24

AW

G O

R H

EAV

IER

SHO

ULD

BE

USE

D.

NO

TES:

1 TO

5 V

OLT

S

CO

MPU

TER

OR

OTH

ER D

EVIC

E

(SEE

NO

TE 3

)

250

oh

ms

24 V

DC

NO

N H

AZ

ARD

OU

S LO

CA

TIO

N

(SEE

NO

TE 3

)

(MA

X 3

6 V

DC

)

POW

ER S

UPP

LY 1

TO 5

VO

LTS

-

(SEE

NO

TE 3

)

OTH

ER D

EVIC

EC

OM

PUTE

R O

R

I=4

TO 2

0 m

A 250

oh

ms

NO

N H

AZ

ARD

OU

S LO

CA

TIO

N

OF

FMRC

OR

CSA

EN

TITY

NO

TIFI

CA

TIO

N O

F A

PPRO

VA

L A

GEN

CY

(S).

FMRC

OR

CSA

EN

TITY

APP

ROV

ED S

AFE

TYB

ARR

IER

EART

H G

ROU

ND

(SEE

NO

TE 5

)

12. T

EMPE

RATU

RE C

OD

E IS

T4.

HA

ZA

RDO

US

LOC

ATI

ON

APP

ROV

ED S

AFE

TYFM

RC O

R C

SA E

NTI

TY

BA

RRIE

R

EART

H G

ROU

ND

(SEE

NO

TE 5

)

BU

SS B

AR

(SEE

NO

TE 5

)EA

RTH

GRO

UN

D

BU

SS B

AR

SEE

NO

TE 1

6IN

TERC

ON

NEC

T B

OA

RD

LEV

EL T

RAN

SMIT

TER

INST

ALL

ATI

ON

DRA

WIN

G--

----

-

----

---

1 2

4/27

/99

---

BB

6508

05

M-S

ERIE

S G

AU

GE

D

HA

RT C

OM

MU

NIC

ATO

RSU

CH

AS

ROSE

MO

UN

T

(SEE

NO

TE 1

4)M

OD

EL 2

75

SEE

NO

TE 8

CO

NN

ECTI

ON

S W

ILL

BE

MA

DE

AT

TERM

INA

L B

LOC

K O

N P

OW

ER

16. F

OR

TRA

NSM

ITTE

RS W

ITH

DU

AL-

CA

VIT

Y E

NC

LOSU

RES,

CU

STO

MER

SID

E O

F H

OU

SIN

G (N

OT

TO T

ERM

INA

L B

LOC

K O

N IN

TERC

ON

NEC

T B

OA

RD)

LEV

EL T

RAN

SMIT

TER

SEE

NO

TE 1

6

EX H

OU

SIN

G

VIE

W S

HO

WN

AB

OV

E

SIN

GLE

CA

VIT

Y H

OU

SIN

G

DU

AL

CA

VIT

Y H

OU

SIN

GLE

VEL

TRA

NSM

ITTE

R (S

EE N

OTE

16)

SHIE

LD

SHIE

LDSH

IELD

SHIE

LD

EL

ECTR

IC C

OD

E A

NSI

/NFP

A 7

0 A

RTIC

LE 5

04-3

0.)

17.

CA

UTI

ON

: FL

EXIB

LE P

ROB

ES H

AV

E A

MIN

IMU

M B

END

RA

DIU

S O

F 15

INC

HES

(380

mm

).

D

5/

19/0

0

KLP

407

7

AD

DED

NO

TES

FOR

MC

B

11

/23/

99

KLP

39

06

CH

AN

GED

NO

TES

1, 6

, 10,

11,

13,

14

& 1

5 O

N P

G 1

AN

D 2

.

C

3/

16/0

0

LJH

40

21

AD

DED

NO

TE 1

7 M

IN B

END

RA

DIU

S.

CO

NN

ECTI

ON

SO

PTIO

NA

L SE

CO

ND

LO

OP

ECO

NO

.B

YD

ATE

REV

.D

ESC

RIPT

ION

UN

LESS

OTH

ERW

ISE

SPEC

IFIE

D:

REM

OV

E B

URR

S A

ND

SH

ARP

EDG

ES .0

15 M

AX

DIM

. LIM

ITS

HEL

D A

FTER

PLA

TIN

G O

R C

ON

VER

SIO

N

.XX

X =

.0

05A

NG

ULA

R =

1

.XX

=

.01

DRI

LL D

EPTH

S A

RE T

OFU

LL D

IAM

ETER

TAP

DEP

THS

ARE

MIN

IMU

MFU

LL T

HRE

AD

S

CO

ATI

NG

++

+

+

DRA

WIN

GSC

ALE

DO

NO

T

FIN

ISH

MA

TERI

AL

DA

TE

DA

TE

DA

TE

DA

TE

DA

TE

SHEE

T

SCA

LE

QC

MFG

OF

ENG

R

DRA

WN

CH

K

DW

G N

O.

TITL

E

REV

LOOP 2

LOOP 1

+-

SEE

NO

TE17

RESE

ARC

H T

RIA

NG

LE P

ARK

, NO

RTH

CA

ROLI

NA

277

09

SEN

SORS

DIV

ISIO

N

13

Page 18: Liquid-Level Transmitter Model M-Series Analog Outputmskcorp.co.kr/pdf_file/mts/M/M-Series-Manual.pdf · Liquid-Level Transmitter Model M-Series Analog Output ... the transmitter

LO

OP

2 T

ES

TLO

OP

2 T

ES

TLO

OP

1 T

ES

TLO

OP

1 T

ES

TH

AR

TH

AR

T+ +

--+ +

--

1 TO

5 V

OLT

S

250

oh

ms

CO

MPU

TER

OR

OTH

ER D

EVIC

E

24 V

DC

POW

ER S

UPP

LY

-

BA

RRIE

R

I=4

TO 2

0 m

A

----

---

BB

4/27

/99

---

2 2

6508

05

INST

ALL

ATI

ON

DRA

WIN

G, I

.S.

MC

& M

-SER

IES

GA

UG

E--

----

-

(MA

X 3

6 V

DC

)

EART

H G

ROU

ND

(SEE

NO

TES

5 &

8)

BU

SS B

AR

NO

N H

AZ

ARD

OU

S LO

CA

TIO

N

FMRC

OR

CSA

EN

TITY

HA

ZA

RDO

US

LOC

ATI

ON

(SEE

NO

TE 3

)

(SEE

NO

TE 3

)

APP

ROV

ED S

AFE

TY

NO

TES:

1. F

OR

I.S. F

IELD

INST

ALL

ATI

ON

WIR

ING

SH

ALL

BE

INST

ALL

ED IN

AC

CO

RDA

NC

E

CA

BLE

CA

PAC

ITA

NC

E SH

ALL

BE

LESS

TH

AN

30

PF P

ER F

OO

T.

3. C

ON

TRO

L RO

OM

EQ

UIP

MEN

T SH

OU

LD N

OT

USE

OR

GEN

ERA

TE M

ORE

TH

AN

250

V R

MS.

2. S

HIE

LDED

TW

ISTE

D C

AB

LE O

F 24

AW

G O

R H

EAV

IER

SHO

ULD

BE

USE

D.

INST

RUM

ENT

GRO

UN

D.

9. N

O R

EVIS

ION

S SH

ALL

BE

MA

DE

WIT

HO

UT

NO

TIFI

CA

TIO

N O

F A

PPRO

VA

L A

GEN

CY

(S).

5. T

HE

CO

NN

ECTI

ON

BET

WEE

N T

HE

EART

H G

ROU

ND

TER

MIN

AL

OF

FMRC

OR

CSA

EN

TITY

A

PPRO

VED

SA

FETY

BA

RRIE

RS A

ND

SY

STEM

EA

RTH

GRO

UN

D M

UST

BE

LESS

TH

AN

1 o

hm

.

8. G

AU

GE

SHA

LL B

E G

ROU

ND

ED T

O E

ART

H G

ROU

ND

TH

ROU

GH

TH

E PR

OV

IDED

GRO

UN

D L

UG

CLA

SS ,

DIV

ISIO

N 1

, GRO

UPS

E, F

AN

D G

, CLA

SS II

IW

ITH

NEM

A/T

YPE

4X

, FO

R O

UTD

OO

R U

SE.

10.

INTR

INSI

CIA

LLY

SA

FE F

OR:

CLA

SS I,

DIV

ISIO

N 1

, GRO

UPS

A, B

, C A

ND

D

4. F

OR

FMRC

& C

SA A

PPRO

VED

GA

UG

ES,

BA

RRIE

RS M

UST

BE

FMRC

& C

SA A

PPRO

VED

.12

. TEM

PERA

TURE

CO

DE

IS T

4.

13. A

PPRO

VED

MET

HO

DS

FOR

SEPA

RATI

ON

OF

EAC

H L

OO

P A

RE:

* RU

NN

ING

LO

OPS

IN S

EPA

RATE

CA

BLE

S.

* RU

NN

ING

LO

OPS

IN S

EPA

RATE

GRO

UN

DED

SH

IELD

S. 6

. SA

FETY

BA

RRIE

RS A

RE F

MRC

AN

D C

SA E

NTI

TY A

PPRO

VED

SA

FETY

BA

RRIE

RS U

SED

IN A

N

APP

ROV

ED C

ON

FIG

URA

TIO

N W

HER

E TR

AN

SMIT

TER

Vm

ax IS

GRE

ATE

R TH

AN

BA

RRIE

R V

oc

A

ND

TRA

NSM

ITTE

R Im

ax IS

GRE

ATE

R TH

AN

BA

RRIE

R Is

c.

7. T

RAN

SMIT

TER

Ci P

LUS

TOTA

L C

AB

LE C

APA

CIT

AN

CE

FOR

EAC

H L

OO

P M

UST

NO

T EX

CEE

D

B

ARR

IER

Ca.

TRA

NSM

ITTE

R Li

PLU

S TO

TAL

CA

BLE

IND

UC

TAN

CE

FOR

EAC

H L

OO

P M

UST

NO

T EX

CEE

D B

ARR

IER

La. (

SEE

NO

TE 1

4)

NO

N H

AZ

ARD

OU

S LO

CA

TIO

N

1 TO

5 V

OLT

S

BU

SS B

AR

I=4

TO 2

0 m

A

250

oh

ms

(SEE

NO

TE 3

)

OTH

ER D

EVIC

EC

OM

PUTE

R O

R

APP

ROV

ED S

AFE

TYFM

RC O

R C

SA E

NTI

TY

BA

RRIE

R

(SEE

NO

TES

5 &

8)

EART

H G

ROU

ND

W

ITH

TH

E C

OU

NTR

Y IN

USE

(eg

CA

NA

DIA

N E

LEC

TRIC

AL

CO

DE,

PA

RT 1

, NA

TIO

NA

L

11. E

AC

H L

OO

P EN

TITY

PA

RAM

ETER

S (P

RIN

TED

ON

LA

BEL

)

L =

200

uH

C =

0

ii

Imax

= 1

18m

AV

max

= 3

6V

14. H

ART

CO

MM

UN

ICA

TOR

WH

ICH

FM

& C

SA A

PPRO

VED

(AS

APP

LIC

AB

LE) M

UST

O

NLY

BE

CO

NN

ECTE

D IN

AC

CO

RDA

NC

E W

ITH

MFG

IS IN

STA

LLA

TIO

N IN

STRU

CTI

ON

S.

15. U

SE O

NLY

NRT

L LI

STED

AN

D C

SA C

ERTI

FIED

DU

ST-T

IGH

T SE

AL

FOR

CLA

SS

A

ND

CLA

SS

HA

ZA

RDO

US

LOC

ATI

ON

S.

(SEE

NO

TE 5

)EA

RTH

GRO

UN

D

MO

DEL

275

(SEE

NO

TE 1

4)

SUC

H A

S RO

SEM

OU

NT

HA

RT C

OM

MU

NIC

ATO

R

NO

REV

ISIO

NS

SHA

LL B

E M

AD

E W

ITH

OU

T N

OTI

FIC

ATI

ON

TO

APP

ROV

AL

AG

ENC

Y(S

).

LEV

EL T

RAN

SMIT

TER

NEM

A 4

X H

OU

SIN

G

SHIE

LD

SHIE

LD

SHIE

LD

SHIE

LD

D

EL

ECTR

IC C

OD

E A

NSI

/NFP

A 7

0 A

RTIC

LE 5

04-3

0.)

IN T

HE

ENC

LOSU

RE.

WH

ERE

INTE

GRA

L C

AB

LE IS

PRO

VID

ED, L

OO

P 2

SHIE

LD IS

NO

T A

VA

ILA

BLE

ON

MC

OPT

ION

AL

SEC

ON

D L

OO

PC

ON

NEC

TIO

NS

(NO

T A

VA

ILA

BLE

ON

MC

)

SIG

NA

LW

IRE

CO

LOR

LOO

P 1

+RE

D

BLA

CK

LOO

P 1

-

WH

ITE

LOO

P 2

+

BLU

ELO

OP

2 -

WIR

E TE

RMIN

ATI

ON

CH

ART

6 PI

N C

ON

N C

AB

LE W

IRE

CO

LOR

RED

RED

W/W

HIT

E TR

AC

E

RED

W/Y

ELLO

W T

RAC

E

GRE

EN

GRO

UN

D

(SEE

NO

TE 8

)

RED

W/B

LUE

TRA

CE

BA

RE

MR

(M-S

ERIE

S)

MC

MO

DEL

REV

.D

ATE

BY

DC

R N

O.

DES

CRI

PTIO

N

+

FULL

TH

REA

DS

TAP

DEP

THS

ARE

MIN

IMU

M

FULL

DIA

MET

ERD

RILL

DEP

THS

ARE

TO

MFG

QC

ENG

R

CH

K+

.XX

=

.01

DO

NO

T SC

ALE

DRA

WIN

G

++

AN

GU

LAR

=

1.X

XX

=

.005

CO

ATI

NG

PLA

TIN

G O

R C

ON

VER

SIO

N

DIM

. LIM

ITS

HEL

D A

FTER

EDG

ES .0

15 M

AX

REM

OV

E B

URR

S A

ND

SH

ARP

UN

LESS

OTH

ERW

ISE

SPEC

IFIE

D:

DRA

WN

DA

TE

DA

TE

DA

TE

DA

TE

DA

TE

SCA

LE

SHEE

TO

FRE

VD

WG

NO

.

TITL

E

MA

TERI

AL

FIN

ISH

RESE

ARC

H T

RIA

NG

LE P

ARK

, NO

RTH

CA

ROLI

NA

277

09

SEN

SORS

DIV

ISIO

N

4.1b Installation drawing M-Series transmitter with NEMA 4X enclosure, 650805 (Revision D) sheet 2 of 2

14

Page 19: Liquid-Level Transmitter Model M-Series Analog Outputmskcorp.co.kr/pdf_file/mts/M/M-Series-Manual.pdf · Liquid-Level Transmitter Model M-Series Analog Output ... the transmitter

4.2 Electrical conduit installation

Attention:• Use an explosionproof type conduit sealing fitting. • Tighten housing cover (both front and back covers if dual cavity) to full stop against “O” ring.• Do not over-tighten compression fittings.• Use side conduit entry only.• Do not use plugged housing entry for termination of conduit.• In high humidity areas, use a breather drain type conduit sealing fitting to minimize moisture intrusion.

Figure 4-2Typical transmitter installation

NPT FittingDo not over-tightencompression fitting!

Interface float(ordered

separately)

Product float(ordered

separately)

View shown withcover removed

Plugged entryDo not use(see notes)

Do not remove cover with circuit livein hazardous locations!

Follow safe work procedures.

3/4 NPT conduit accessUse NPT conduit fitting only!

Conduit (flexible or rigid)

Explosionproof-typeconduit sealing fitting

Conduit fromcontrol room

l

Loop 1 Test + —

Loop 2 Test + —

HART

Level Plus®M-Series Transmitter

TOREM

OVEELECTRONICS MODULE, PULL UNIT IN UPWARD DIRECTION - DO NOT TW

IST

ORTU

RN

l

Loop 1 Test + —

Loop 2 Test + —

HART

Level Plus®M-Series Transmitter

TOREM

OVEELECTRONICS MODULE, PULL UNIT IN UPWARD DIRECTION - DO NOT TW

IST

ORTU

RN

15

Page 20: Liquid-Level Transmitter Model M-Series Analog Outputmskcorp.co.kr/pdf_file/mts/M/M-Series-Manual.pdf · Liquid-Level Transmitter Model M-Series Analog Output ... the transmitter

4.3 Cable specifications

The following section lists cable parameters and specifications for the M-Series transmitter. The list is not inclu-sive of all cable types and cable manufacturers and should serve only as a guideline when choosing cables. Othercable types can be selected that meet the requirements.

Parameter SpecificationMinimum cable size: 24 AWG or heavier (0.51 mm diameter)

Contact MTS for additional assistance in selecting proper cableCable type: Single pair shielded or multiple pair with overall shieldMaximum cable length: Twisted pair: 10,000 ft. (3,048 m)

Multiple twisted-pair: 5,000 ft. (1,524 m)Maximum cable length formula: Use the following formula to determine the maximum cable length for a

specific application:

L = [(65 x 106) ÷ (R x C)] - [(Cf + 10,000) ÷ C]

Where: L = Length in feet or metersR = Resistance in ohm, current sense resistance plus barrier resistanceC = Cable capacitance in pF/ft, or pF/mCf = Maximum shunt capacitance of smart field devices in pF

Example:Assume a high performing smart transmitter, a control system,and a single pair of shielded wires.R = 250 ohmC = 50 pF/ftCf = 5,000 pF

L = [(65 x 106) ÷ 250 x 50)] - [(5,000 + 10,000) ÷ 50]

L = 4,900 ft (1,494 m)

16

Page 21: Liquid-Level Transmitter Model M-Series Analog Outputmskcorp.co.kr/pdf_file/mts/M/M-Series-Manual.pdf · Liquid-Level Transmitter Model M-Series Analog Output ... the transmitter

4.4 Safety guidelines for the M-Series transmitter

Be sure you:

* Follow any applicable local and national electrical codes and observe polarity when making electrical connec-tions.

* Never make electrical connections to the M-Series transmitter when it is powered on.

* Check that no wire strands are loose or sticking out of the terminal block connection on the interconnect boardwhich could short and cause a problem. see Figure 7-2a “Transmitter electronics interconnect board” on page 20/.

* Check that no wire strands, including shield, are in contact with the electronics module or interconnect board.

* Ensure that the electronics module is grounded through interconnect board and electrically isolated from theexplosionproof enclosure.

* Refer to the safe operating power chart in Figure 4-4 “Loop resistance vs power supply” which shows the relation-ship between loop resistance and operating voltage.

4.5 Safety Barriers for IS Installation

Figure 4-5, “Safety barrier types for the M-Series transmitter” illustrates passive/active safety barriers. See page 13 and14 for wiring and entity parameters.

800

750

700

650

600

550

500

450

400

350

300

250

200

150

100

50

0

10 12 14 16 18 20 22 24 26 28 30 32 34 36 38 40

INSUFFICIENTOPERATING POWER

EXCESS POWER

Resistance(Ohms)

Supply Voltage (Volts DC)

Figure 4-4Loop resistance vs power supply

Transmitter

+Passive

+ 24 Vdc Input

+ 1 to 5 V Output

Power & signal common

250 ohm0.1%, 2.5 W

HAZARDOUS AREA NON-HAZARDOUS AREA

SHUNT BARRIERS (I.S. Ground Connection REQUIRED)

Transmitter

ISOLATED BARRIERS (I.S. ground connection NOT REQUIRED)

I.S. ground connection

+24 Vdc

-

+ 1 to 5 V Output

1 to 5 V Return

250 ohm0.1%, 2.5 W

-

+

-

ActiveLoad

Load

Figure 4-5Safety barrier types for the M-Series

transmitter

Notes:• When selecting barrier types, the electrical

specifications for the M-Series transmitterare: Vmax = 36.1 Vdc, Imax = 118 mA (totalcurrent), Ci = 0.0 µF, Li = 0.0 µHy

• MTS stocks Stahl barriers 9001/01-280-100-10 (MTS part number 560669).

17

Page 22: Liquid-Level Transmitter Model M-Series Analog Outputmskcorp.co.kr/pdf_file/mts/M/M-Series-Manual.pdf · Liquid-Level Transmitter Model M-Series Analog Output ... the transmitter

5.0 SYSTEM CHECK

After you complete the M-Series wiring, complete the following steps to perform the system check:1. Apply power to the transmitter.

2. Using a DC volt meter, measure the voltage at loop #1 connections. The voltage must be ≥ 10.5V. If loop #2is being used, measure the voltage at the loop #2 connections, it also must be at ≥ 10.5V. If the voltage levelsare too low, turn off power to the transmitter..

3. Check for shorts, power supply voltage, and excessive loop resistance. Refer to Figure 4-4,”Loop resistance vspower supply” on page 17) which shows the relationship between loop resistance and operating voltage.

5.1 Performing a loop #1 test

To test loop #1, lay the transmitter on a flat surface and move the float along the operational range of the M-Series transmitter. If the transmitter is functioning properly, the output current will change as the float moves.

If the output current is less than 4 mA or greater than 20 mA, this could indicate a problem with the M-Seriestransmitter.

5.2 Performing a loop #2 test (if applicable)

If you are using loop #2, complete the following steps to test the loop (the following test varies depending on theconfiguration):

1. To access loop #2, power on loop #1.

2. If loop #2 is set for level measurement, test the transmitter in the same manner as defined in section 5.1,“Performing a loop #1 test” on page 18.

3. If loop #2 is assigned to measure temperature, first read the output current. Then, if the setpoint values areknown, calculate the temperature using the following formula:

T = [(T20mA - T4mA) ÷ 16] (I - 4) + T4mAWhere: T = TemperatureT20mA = Temperature @ 20 mA setpoint (Factory Setting: 300 °F)

T4mA = Temperature @ 4 mA setpoint (Factory Setting: -30 °F)

I = Output current (in mA)

The M-Series transmitter’s sensing Resistance Temperature Device (RTD) is located at approximately three inchesfrom the transmitter’s tip. Measure the temperature near the tip to see if it is an approximation of the calculatedvalue. If the output current is less than 4 mA or greater than 20 mA, there may be a problem with the sensingRTD (i.e., it may be shorted or open).

6.0 FLOATS

For information about floats, go to www.mtssensors.com and refer to the float specification, MTS part number550537. For float application information, please contact the MTS Level Plus Applications Engineering.

When contacting MTS for assistance on floats, please have the following information available:

• Specific gravity of liquid(s) being measured• Process temperature• Vessel pressure

18

Page 23: Liquid-Level Transmitter Model M-Series Analog Outputmskcorp.co.kr/pdf_file/mts/M/M-Series-Manual.pdf · Liquid-Level Transmitter Model M-Series Analog Output ... the transmitter

7.0 MAINTENANCE

M-Series transmitter assemblies use magnetostrictive technology and only have one moving part, the float. Thistechnology ensures no scheduled maintenance or recalibration is required. However, it is necessary that you checkthe sensor pipe annually for build up of process material. Floats should move freely along the sensor pipe. If theydo not, routine cleaning should be performed.

7.1 Replacing an M-Series electronics module (puck) or interconnect board

The M-Series electronics module, also referred to as a puck, is modular in design. The puck or interconnect boardcan be replaced in the field without onsite MTS Applications Engineering Support.

7.1a Replacing an M-Series electronics module (puck)

Complete the following steps to install the puck:

1. Remove any dirt, debris, or liquid from the top of the instrument enclosure (see Figure 7-1a, “Instrument enclo-sure”).

2. Remove the instrument housing cover (see Figure 7-1a, “Instrument enclosure”).

3. Remove the existing puck by grasping the perimeter of the puck and lifting upward. the puck will slide freefrom the two female interconnects that are mounted on the transmitter electronics interconnect board (see Figure 7-1b, “Electronics Module (puck)”)

4. Remove the replacement puck from its package. To ensure that the new puck installs correctly, align the inter-connects on the back of the puck with the male interconnects on the interconnect board as shown in Figure 7-1c, Transmitter electronics interconnect board”. Secure the puck into the instrument housing by pressing downaround the parameter of the puck face. The puck should feel secure and not “rock”.

5. install the instrument housing cover.6. Continue with section 8.0, “Using the keypad to calibrate M-Series transmitters”, on page 21 for calibration and

setup instructions.

19

Attention:Ensure that all power is disconnected and that all lockout procedures are followed prior to opening the M-Series instru-ment housing.

Figure 7-1bElectronics module (puck)

Figure 7-1aInstrument enclosure

Figure 7-1cTransmitter electronics (baseboard)

Instrumentenclosure

Housingcover

Transmitter electronicsinterconnect board

puck(front view)

Puck(rear view)

Female interconnects

Male interconnects

Page 24: Liquid-Level Transmitter Model M-Series Analog Outputmskcorp.co.kr/pdf_file/mts/M/M-Series-Manual.pdf · Liquid-Level Transmitter Model M-Series Analog Output ... the transmitter

20

7.1b Replacing the interconnect board

Complete the following steps to replace the transmitter electronics interconnect board:

1. Remove any dirt, debris, or liquid from the top of the instrument enclosure.

2. Remove the instrument housing cover (see Figure 7-1a “Instrument enclosure” on page 19.

3. Remove the existing puck by grasping the perimeter of the puck and lifting upward (see Figure 7-1b,“Electronics Module (puck)” on page 19. The puck will slide free from the two female interconnects that aremounted on the interconnect board (see Figure 7-2a “Transmitter electronics interconnect board components”. Placethe puck in a safe area.

4. Disconnect the terminal block connector (replacement included if needed) and wired connector see Figure 7-2a.

5. Disconnect the sensing element connector and RTD cable connector if present (see Figure 7-2a).

6. Unscrew the four standoffs and remove the interconnect board from the instrument enclosure (see Figure 7-2a). 7. Remove the replacement interconnect board from its package. line the board up with the four mounting screws

(see Figure 7-2a). Secure the interconnect board to the instrument enclosure with four standoffs (includedwith kit).

8. Connect the wired connector and the terminal block connector (see Figure 7-2a).

9. Connect the sensing element connector and RTD cable connector.

11. To install the new puck, Using even pressure, press down firmly on the face of the puck until the male andfemale interconnects engage fully. Ensure that the new puck is installed correctly in the instrument housing bypressing down around the parameter of the puck face. The puck should feel secure and not “rock”.

12. Replace the instrument housing cover.

AttentionBefore you begin, ensure that all power is disconnected and that all lockout procedures are followed prior to opening theM-Series instrument housing.

Figure 7-2aTransmitter electronics

interconnect board components

Terminal Block

Sensing elementconnector

Transmitter electronicsinterconnect board

Female interconnects

RTD connector

Wired connector

Female interconnects

Mounting screws

Page 25: Liquid-Level Transmitter Model M-Series Analog Outputmskcorp.co.kr/pdf_file/mts/M/M-Series-Manual.pdf · Liquid-Level Transmitter Model M-Series Analog Output ... the transmitter

8.0 USING THE KEYPAD DISPLAY TO CALIBRATE THE LEVEL PLUS M-SERIES TRANSMITTERThe M-Series transmitter can be calibrated by using the HART communications protocol or it may be manuallycalibrated using the optional keypad display. This section explains modes of operation and the steps you need toperform to calibrate your transmitter manually using the keypad display.

8.1 Modes of operation

The M-Series transmitter runs in one of the following modes of operation. You can use these modes to calibrateand set up various operating parameters.

Run modeRun mode is the primary mode of operation. This mode will perform measurements, display data, and respondto HART commands. The run mode can be configured for various output options. The minimum configurationwill only perform a single-level measurement. More complex configurations will perform a second float measure-ment (interface), or temperature measurements.

Program modeThe program mode is only applicable to M-Series transmitter with the keypad display option. Enter this mode bypressing any of the three keys, Up keypad, Down keypad, and Enter keypad as shown in Figure 8-2, “M-Series key-pad display”. Menus guide the user through various programming options. When in the program mode, HARTcommunications are not functional. An automatic timeout feature is provided so that the transmitter does notremain inadvertently in program mode.

Display test modeThis mode is invoked through the keypad.

Keypad display usage in program modeThe M-Series transmitter can be configured by pressing three keys, the Up keypad, Down keypad, and Enter key-pad as shown in Figure 8-2, “M-Series keypad display”. This gives the user a means to calibrate and set up variousoperating parameters.

l

Loop 1 Test + —

Loop 2 Test + —

HART

Level Plus®M-Series Transmitter

TOREM

OVEELECTRONICS MODULE, PULL UNIT IN UPWARD DIRECTION - DO NOT TW

IST

ORTU

RN

Loop 1 test port Loop 2 test port

HART test port

Up key Enter key

Down key

Custom LCD display

8. 8. 8. 8. 8. 8. 8. 8. 8. 8. 8. 8. 8. 8. 8. 8.% mA in ft mm cm m % mA in ft mm cm m °C °F

LEVEL 1 LEVEL 2 TEMP

Level 1 Data Field Temperature Data Field

Level 2 Data Field

Level 1 iconis always enabled

in Run Mode

Level 2 icon is enabled onlywhen in Run Mode and Level 2measurement is enabled

Temp icon is enabled onlywhen in Run Mode andtemperature is enabled

Level 1 Unit icons Level 2 Unit icons Temperature Unit icons

Figure 8-2M-Series keypad display

21

Page 26: Liquid-Level Transmitter Model M-Series Analog Outputmskcorp.co.kr/pdf_file/mts/M/M-Series-Manual.pdf · Liquid-Level Transmitter Model M-Series Analog Output ... the transmitter

The three keypads are identified with “t” “”, and “<—”. The “s” keypad may be used to indicate Up responses,the “t” symbol indicates Down responses, and “<—” indicates an Enter response. Normally, the M-Series trans-mitter will remain in run mode. When you press any three keys, the transmitter will enter program mode. In pro-gram mode, the electronics module menu displays options that you can scroll through using the Up and Downkeypads. To select an option, press Enter.

Program mode TimerAfter you enter the programming mode, a one-minute timer is started. Each time you press a button, the timer isreset. If you do not press a menu button within one minute, the timer will expire and the transmitter will returnto the run mode (See “run” mode on page 21).

Loop #1 and loop #2 test portsUsing a standard multi-meter set the meter to DC current and attach across the terminals, loop current can beread directly from ports #1 and #2 see Figure 8-2, “M-Series keypad display”. The current read on the meter shouldcorrespond with the data being displayed. These ports allow the loop current to be read directly without havingto interrupt power.

HART portThis port allows for direct connection of the Rosemount-275 or 375 field calibrator or other HART host deviceas long as there is a load on loop 1.

8.2 LCD display and keypad (optional)

A sixteen character, seven-segment LCD display and three button keypad option is available. Level and tempera-ture measurements are displayed when the transmitter is in run mode. When power is applied to the transmitter,a Start message displays. When the transmitter is in run mode, the display is refreshed every three seconds. Thereare three data fields on the display; Level 1, Level 2 and Temperature see Figure 8.2 “M-Series keypad display”. If ameasurement is not available, dashes (- - - - -) will display in the corresponding field.

Note:In program mode, the transmitter will not respond to incoming HART commands. This function will prevent a user ata remote terminal from overwriting a parameter that is being entered at the same time from a local site.

l

Loop 1 Test + —

Loop 2 Test + —

HART

Level Plus®M-Series Transmitter

TOREM

OVEELECTRONICS MODULE, PULL UNIT IN UPWARD DIRECTION - DO NOT TW

IST

ORTU

RN

Loop 1 test port Loop 2 test port

HART test port

Up key Enter key

Down key

Custom LCD display

8. 8. 8. 8. 8. 8. 8. 8. 8. 8. 8. 8. 8. 8. 8. 8.% mA in ft mm cm m % mA in ft mm cm m °C °F

LEVEL 1 LEVEL 2 TEMP

Level 1 Data Field Temperature Data Field

Level 2 Data Field

Level 1 iconis always enabled

in Run Mode

Level 2 icon is enabled onlywhen in Run Mode and Level 2measurement is enabled

Temp icon is enabled onlywhen in Run Mode andtemperature is enabled

Level 1 Unit icons Level 2 Unit icons Temperature Unit icons

Figure 8-2M-Series keypad display LCD display

22

Page 27: Liquid-Level Transmitter Model M-Series Analog Outputmskcorp.co.kr/pdf_file/mts/M/M-Series-Manual.pdf · Liquid-Level Transmitter Model M-Series Analog Output ... the transmitter

8.3 Alarm settings

When a fault condition is detected by the internal microprocessor, the 4 to 20 mA current will go to the currentselected. If in the 4 mA alarm mode when a fault is detected, the output will be continuous at 3.8 ± 0.1 mA. Ifin the 20 mA alarm mode when a fault is detected, the output will be continuous at 21.5 ±0.2 mA.

8.4 Manual calibration

Figure 8-4, “Manual calibration matrix” illustrates the procedure to enter calibration mode and modify levels 1 and2, adjust LCD contrast and perform a LCD test.

23

Figure 8-4Manual calibration matrix

Calibrate Level 1?

Calibrate Level 2?

AdjustLCD Contrast?

PerformLCD Test?

Press any button to Enter Menu

+

‘Enter’ or ‘Carriage Return’Down arrow button

Up arrow button

Accept new value?If No: +If Yes:

Reads current floatposition, Move floatto desired position

= Calibrate Span

= Calibrate Zero

= Calibrate Span

= Calibrate Zero

Reads current floatposition, Move floatto desired position

Increases Value

Decreases Value

Shows currentLCD contrast value

Accept new value?If No: +If Yes:

Tests all segmentsof LCD

(lasts 10 seconds)

To exit Calibration Modeat any time, press all threebuttons simultaneously:

+ +

+ hold for 1 second

+ hold for 1 second

+ hold for 1 second

Page 28: Liquid-Level Transmitter Model M-Series Analog Outputmskcorp.co.kr/pdf_file/mts/M/M-Series-Manual.pdf · Liquid-Level Transmitter Model M-Series Analog Output ... the transmitter

24

9.0 USING THE HART COMMUNICATION PROTOCOL TO CALIBRATE THE LEVEL PLUS M-SERIES TRANSMITTER

Refer to the documentation that comes with the HART Model 275 and 375 Hand-Held Terminal for specificsensor calibration information. This section describes how the HART protocol is applied to the Level Plus M-Series transmitter only.

Using the HART interface allows for calibration without having to remove the transmitter from the process andposition of the floats. You can perform this function by using HART commands 35 and 65.

Any measured output may be assigned to any variable. Loop #1 is always the primary variable (PV); level one isusually assigned to loop #1. Loop #2 is always the Second Variable (SV); usually represents temperature or level32. The Third Variable (TV) and Fourth Variable (FV) may be assigned to any remaining output such as, level 2,temperature. Analog output codes are 0, 1, and 2 respectively.

Calibration set points for level are given as the absolute displacement (in the appropriate units) from the tip ofthe sensor pipe. For example, if the Zero (LRV) position for level 1 is given as 5 inches, the transmitter will pro-duce 4 mA when the float is 5 inches from the tip of the sensor pipe. If the Span (URV) position for level 1 isgiven as 30 inches, the transmitter will produce 20 mA when the float is 35 inches from the top of the sensorpipe. To calibrate the temperature set points, the Zero (LRV) and Span (URV) points are given in degrees. Fortemperature, the Zero (LRV) value (in degrees) must always be less than the Span (URV) value (in degrees).

9.1 Preparing the transmitter for re-calibration

The M-Series transmitter can be re-calibrated by using the HART model 275 and 375 hand-held terminal.Complete the following procedure to reset the low and high values for loop #1 (only loop #1 can be calibratedwith the HART hand-held terminal using the generic XMTR type driver. To access both loops as well as otherparameters, the MTS device driver must be purchased and installed in to the 275/375 hand-held device. Formore information about the HART device driver, go to HARTcomm.org.

Before you begin, do the following:

1. Connect the transmitter to a clean 24 Vdc power supply. Use a linear supply, switching types does not provideripple-free power. HART cannot tolerate more than a 25 mV voltage ripple.

2. If the unit is installed in a live application, place your automatic controllers in manual mode and be advisedthat the output current will change during calibration.

3. Follow safe working procedures for working on live equipment in a hazardous location before you remove thehousing cover.

4. Connect the HART hand-held terminal to the terminals that are labeled HART located on the front panel dis-play of the Level Plus transmitter.

5. Press the black and white I/O button on the HART terminal. The HART terminal will perform an automaticself test. The Main window displays. If the device is not connected properly, the message “No device found”displays.

6. In the Main window, press the key #1, the Device Setup window displays.

7. In the Device setup window, press Key #3. The Basic Setup window displays.

Attention:Be sure you have loop #1 connected to a load of 250 to 500 ohm. A transmitter installed in a control loop is a goodexample of the loop load. You might also use a load resistor in the range of the above value.

Page 29: Liquid-Level Transmitter Model M-Series Analog Outputmskcorp.co.kr/pdf_file/mts/M/M-Series-Manual.pdf · Liquid-Level Transmitter Model M-Series Analog Output ... the transmitter

25

8. In the Basic Setup window, press Key #3. The Range Values window displays.

9.2 Setting the low value

Complete the following steps to set the low value:

1. To set the low value, Process Variable, Low Range Value (PV LRV) to 4 mA, select Key #1. The PV LRV win-dow displays the current low value. Below the highlighted value located under the current value, key in thelow value you want (example 3.00 in. is shown; if 4 inches is the value you want, key in 4.) and press Enter(F4) located below the LCD display.

2. To write the changed lower value to memory, press the Send key.

3. Two Warning messages will display before the new values take affect; if your new low values are correct, respondto the Warning messages by pressing OK when prompted. This action resets the Low Range Value, or 4 mAposition into the transmitter's memory.

4. Go back to the Range Values window to verify that the new parameters have been accepted into the transmit-ter’s memory.

5. Do one of the following:5.a Exit program mode.

5.b To reset the upper value, continue to 9.3 “Setting the Upper Range Value”.

9.3 Setting the Upper Range Value

Complete the following steps to set the Upper Range Value:

1. Open the Range Values window. To set the 20 mA Upper Range Value, press Key #2. The Process Variable,Upper Range Value (PV URV) window displays.

2. As shown the Lower Value window, the current value displays with a highlighted number below the value dis-played. To change the upper value, key in the new value. You can use whole numbers or whole numbers anddecimals (example, 40 = 40 inches, or 40.5 = 40.50 inches.) Whole numbers will be converted as decimalequivalents automatically by the HART terminal.

3. Key in the new Upper Range Value and press Enter or (F4). The Range Values window displays.

4. Verify that the upper and lower values are correct. If the values are correct, press Send.

5. You will be prompted with two Warning messages, press OK in response to both warnings.

Caution:DO NOT enter a high value that exceeds the active length of the sensor.

Page 30: Liquid-Level Transmitter Model M-Series Analog Outputmskcorp.co.kr/pdf_file/mts/M/M-Series-Manual.pdf · Liquid-Level Transmitter Model M-Series Analog Output ... the transmitter

10.0 INSTALLING AND USING THE M-SERIES FIELD SETUP SOFTWARE V1.01 (CD-ROM) TO SETUP PARAMETERS AND ADJUST CALIBRATION

Adjustments to the calibration and setup parameters of the transmitter may be done using the M-Series FieldSetup software v1.0 and a RS-232 to HART converter (SMAR HI-311, MTS Part # 380068). Be sure you areinstalling the latest software package, go to www.mtssensors.com for more information. The following parameterscan be viewed or modified when using the M-Series Field Setup software:

Basic: Manufacturing informationAdvanced: Gauge length, Gradient, Head Adder, Enable Display, Enable Loop 2,

and Set Alarm Output to Low or HighCalibration: Level 1 Span and Offset. Level 2 Span and Offset, Temperature Span and OffsetOutput: Level 1 Units of Measure, Level 2 Units of Measure, Temperature Units of Measure,

Output Units of Measure, Output Designations and View Output Data

10.1 Installing the M-Series Field Setup software

Before you begin, do the following:

1. Obtain a Linear Power Supply, Multi-meter, PC and a HART RS-232 Converter.

2. Complete the following steps to install the M-Series Field Setup Software package and/or modify calibration andsetup parameters:

a. Insert the CD into the proper drive.

b. Browse to to CD-ROM drive and run setup.exe.

c. Follow the instructions on screen to install the program.

3. Connect the amp meter, power supply and transmitter. Set the proper scale on the meter. Ensure a 250 ohmresistor is installed in the line to enable uninterrupted communication.

4. Connect the HART adapter/converter to the RS-232 COM port on the back of the PC.

5. Attach the HART converter to the HART connection pins located on top of the M-Series Electronic module(puck) or across the resistor.

4. Connect HART adapter/converter clip leads to HART port on M-Series Electronic module (puck).

5. Apply power to the M-Series Transmitter and PC.

26

Page 31: Liquid-Level Transmitter Model M-Series Analog Outputmskcorp.co.kr/pdf_file/mts/M/M-Series-Manual.pdf · Liquid-Level Transmitter Model M-Series Analog Output ... the transmitter

10.2 Calibration and setup parameters

1. From your desktop double-click the MSeries Field Setup icon to start the software.

2. Setup will automatically search and receive configuration data from the transmitter. The M-Series Field Setupwindow displays as shown in Figure 10-1 “M-Series Field Setup software - Basic Setup window”, click the BasicSetup tab to review the data. If there is no data, assign a different serial communications port and click theFind button in the top left corner to rerun the search program.

27

Figure 10-1M-Series Field Setup software - Basic Setup window

Page 32: Liquid-Level Transmitter Model M-Series Analog Outputmskcorp.co.kr/pdf_file/mts/M/M-Series-Manual.pdf · Liquid-Level Transmitter Model M-Series Analog Output ... the transmitter

3. In the M-Series Field Setup window as shown in Figure 10-2 “M-Series Field Setup software-Advanced setupwindow, click the Advanced Setup tab. Confirm that the Gradient, Length, and Head Adder have beenreceived from the level transmitter. If the information does not display, click the Read button at the bottomof the window and manually enter the missing data. The sensor information fields are defined as follows:

Sensor information:Gradient: Is slightly different for each transmitter. It can be found on sensor element head.

Units: Determines the units of measure for Length and Head Adder. This is used when writing new val-ues of Order Length and Head Adder to the transmitter. Click the Output Tab to change units of meas-ure for all data.

Length: Is equal to the order length of the transmitter being used.

Head Adder: Is the distance between the sensing element and the order length. Each model has a slightlydifferent adder as follows:Gauge Style: Length in Inches:NEMA 4X housing, standard rigid pipe 4.3 to 4.5Explosionproof housing with/without display with rigid pipe 5.6 to 5.7NEMA 4X housing with flex pipe < 10 feet 14.0 to 14.5Explosionproof housing with or without display with flex pipe < 10 feet 14.0 to 14.5.

10.3 Instrument parameters:

Display Units: Type of level data displayed on the optional LCD display; Units, mA and Percent.Float #2: optional float #2; Enable/Disable .Temperature: optional temperature data; Enable and Disable.Display: optional LCD display; Enable and Disable.Alarm: Output current value defined as Low (3.8 mA) or High (21.5 mA), if the float(s) or temperaturesensor should fail.

28

Figure 10-2M-Series Field Setup software - Advanced Setup window

Page 33: Liquid-Level Transmitter Model M-Series Analog Outputmskcorp.co.kr/pdf_file/mts/M/M-Series-Manual.pdf · Liquid-Level Transmitter Model M-Series Analog Output ... the transmitter

4. In the M-Series Field Setup window as shown in Figure 10-3 “M-Series Field Setup software - Calibration Setupwindow”, click the Calibration tab. Adjust the Zero (LRV) value and Press the Write button. Adjust the Span(URV) value and Units value from the appropriate channel and press the Write button.

The Calibration window fields are defined as follows:

The Calibration window contains the Zero (LRV) and Span (URV) set points for all three variables. Tochange a value, type in the new value and press the Write button to save your change. To confirm thevalue change, press the Read button.

The Units field shows the units of measure for the Zero (LRV) and Span URV). To change the units ofmeasure for the Zero(LRV) and Span (URV) press the arrow and select from the pull down menu. Pressthe Write button to confirm any changes to the settings. Press the Read button to confirm that thetransmitter has accepted the new value.

The Offset field is used for making adjustments to the optional LCD display, not the current output.

Example: If the float is at the 4-mA point, but the display reads +.25 inches. Enter in -.25 inches in theblock and press the W key to save, Now the display will read 0.00 inches even though the current hasremained at 4 mA.

29

Figure 10-3M-Series Field Setup software - Calibration Setup window

Page 34: Liquid-Level Transmitter Model M-Series Analog Outputmskcorp.co.kr/pdf_file/mts/M/M-Series-Manual.pdf · Liquid-Level Transmitter Model M-Series Analog Output ... the transmitter

UNITED STATESMTS Systems CorporationSensors Division3001 Sheldon DriveCary, NC 27513Tel: 800-457-6620Fax: 919-677-2545

[email protected]

GERMANYMTS Sensor TechnologieGmbH & Co. KGAuf dem Schüffel 9D - 58513 LüdenscheidTel: +49 / 23 51 / 95 87-0Fax: +49 / 23 51 / 56 [email protected]

JAPANMTS Sensors TechnologyCorporationUshikubo Bldg.737 Aihara-cho, Machida-shiTokyo 194-0211, JapanTel: + 81 (42) 775-3838Fax:+ 81 (42) [email protected]

Part Number: 10-04 550720 Revision FMTS is a registered trademerk of MTS Systems Corporation.

Level Plus is a registered trademark of MTS Systems Corporation.All other trademarks are the property of their respective owners.

All Temposonics sensors are covered by US patent number 5,545,984. Additional patents are pending.Printed in USA. Copyright © 2004 MTS Systems Corporation. All Rights Reserved.FM

APPROVED