limit switching wsh for manually operated valves wsh 10.1 – 16.1

28
Limit switching WSH for manually operated valves WSH 10.1 – WSH 16.1 Operation instructions

Upload: vothien

Post on 14-Feb-2017

244 views

Category:

Documents


2 download

TRANSCRIPT

Page 1: Limit switching WSH for manually operated valves WSH 10.1 – 16.1

Limit switching WSHfor manually operated valves

WSH 10.1 – WSH 16.1

Operation instructions

Page 2: Limit switching WSH for manually operated valves WSH 10.1 – 16.1

Table of contents Page

1. Safety instructions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4

1.1. Range of application 41.2. Commissioning (electrical connection) 41.3. Maintenance 41.4. Warnings and notes 4

2. Short description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4

3. Technical data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5

4. Transport and storage . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6

4.1. Transport 64.2. Storage 64.3. Packaging 6

5. Mounting to valve/gearbox. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7

6. Electrical connection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9

6.1. Connection with AUMA plug/socket connector in crimp version 96.2. Heater 9

7. Switch compartment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10

7.1. Opening the switch compartment 107.2. Pulling off the indicator disc 10

8. Setting the limit switching . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11

8.1. Clockwise closing 118.2. Counterclockwise closing 12

9. Setting the DUO limit switching (option) . . . . . . . . . . . . . . . . . . . . . . . . . . . 13

9.1. Clockwise closing 139.2. Counterclockwise closing 14

10. Setting/testing the reduction gearing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15

11. Setting the potentiometer (option) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16

12. Setting the electronic position transmitter RWG (option) . . . . . . . . . . . . . . . . . . 17

12.1. Setting 2-wire system 4 – 20 mA or 3-/4-wire system 0 – 20 mA 1812.2. Setting 3-/4-wire system 4 – 20 mA 19

13. Setting the mechanical position indicator . . . . . . . . . . . . . . . . . . . . . . . . . . . 20

13.1. Closing the switch compartment 20

14. Enclosure protection IP 68 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21

15. Maintenance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22

16. Lubrication. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22

2

Limit switching WSH 10.1 – WSH 16.1 Operation instructions

Scope of these instructions: These instructions apply to limit switching WSH 10.1 – WSH 16.1for manually operated valves.

Page 3: Limit switching WSH for manually operated valves WSH 10.1 – 16.1

Page

17. Disposal and recycling . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22

18. Service . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22

19. Declaration of Conformity and Declaration of Incorporation. . . . . . . . . . . . . . . . . 24

Index . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25

Addresses . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26

3

Operation instructions Limit switching WSH 10.1 – WSH 16.1

Page 4: Limit switching WSH for manually operated valves WSH 10.1 – 16.1

1. Safety instructions1.1. Range of application AUMA limit switchings WSH are designed to signal actual position and end

position of manually operated valves.For other applications, please consult AUMA. The manufacturer is not liablefor any possible damage resulting from use in other than the designatedapplications. Such risk lies entirely with the user.

Observance of these operation instructions is considered as part of thedesignated use.

1.2. Commissioning(electrical connection)

During electrical operation, certain parts inevitably carry hazardous volt-ages. Work on the electrical system or equipment must only be carried outby a skilled electrician himself or by specially instructed personnel under thecontrol and supervision of such an electrician and in accordance with theapplicable electrical engineering rules.

1.3. Maintenance The maintenance instructions (refer to page 22) must be observed, other-wise a safe operation of the limit switching WSH is no longer guaranteed.

1.4. Warnings and notes Failure to observe the warnings and notes may lead to serious injuries ordamage. Qualified personnel must be thoroughly familiar with all warningsand notes in these operation instructions.Correct transport, proper storage, mounting and installation, as well ascareful commissioning are essential to ensure a trouble-free and safe oper-ation.The following references draw special attention to safety-relevant proce-dures in these operation instructions. Each is marked by the appropriatepictograph.This pictograph means: Note!“Note” marks activities or procedures which have major influence on thecorrect operation. Non-observance of these notes may lead to consequen-tial damage.This pictograph means: Electrostatically endangered parts!The printed circuit boards are equipped with parts which may be damagedor destroyed by electrostatic discharges. If the boards need to be touchedduring setting, measurement, or for exchange, it must be assured thatimmediately before a discharge through contact with an earthed metallicsurface (e.g. the housing) has taken place.This pictograph means: Warning!“Warning” marks activities or procedures which, if not carried out correctly,can affect the safety of persons or material.

2. Short description AUMA limit switchings WSH 10.1 – WSH 16.1 are designed for continuous,mechanical position indication and electric position feedback.For manually operated valves, the necessity to display valve position infor-mation in a control station incidentally arises. In some applications, it mightbecome imperative, for example, to only open a valve whilst another valve isclosed. The AUMA limit switching WSH for manually operated valves isideally appropriate for these types of applications.

4

Limit switching WSH 10.1 – WSH 16.1 Operation instructions

Page 5: Limit switching WSH for manually operated valves WSH 10.1 – 16.1

3. Technical data

Limit switching Output torque Thrustpermissible for

Valve attachment Valve stemdiameter

Handwheel Weight

Typemax.Nm

output drive Amax.Nm

StandardEN ISO 5210

OptionDIN3210

for a risingvalve stem1)

max. mm Ø mmReduction

ratio approx. kg

WSH 10.1 170 70 F10 G 0 40 400 1 : 1 10WSH 14.1 400 160 F14 G ½ 57 400/500 1 : 1 16WSH 16.1 800 250 F16 G 3 65 630 1 : 1 22.2

Features and functionsLimit switching Counter gear mechanism for end positions CLOSED and OPEN

for 2 to 500 turns per stroke (optional for 8 to 2,000 turns per stroke)Standard: Single switch for each end positionOptions: Intermediate position switch (DUO limit switching), adjustable for any

intermediate positionRating of the switches: 5A, for gold plated contacts 0.1 A

Position feedback, analogue(option)

Potentiometer: Conductive film, 1 kΩ or 5 kΩ/0,25 W, linearity ± 2.5 %Position transmitter: Electronic position transmitter RWG:

0/4 – 20 mA in 3- or 4-wire version4 – 20 mA in 2-wire versionFor further information on the RWG, refer to page 17

Mechanical position indicator Continuous indication, adjustable indicator disc with symbols OPEN and CLOSEDHeater in switch compartment Standard: Self-regulating PTC heater; 5 – 20 W, 110 – 250 V AC/DC

Option: 24 – 48 V AC/DCElectrical connection Standard: AUMA plug/socket connector with crimp type connection for flexible conductors

40 poles, cross section 0.75 – 1.0 mm²Option: Cross sections 0.5 mm² or 1.5 mm²

Threads for cable glands Standard: Metric threadsOptions: Pg-threads

Terminal plan APG AG 101 (basic version)Output drive types A, B1, B2, B3, B4 in compliance with EN ISO 5210

A, B, E according to DIN 3210Service conditionsEnclosure protection accordingto EN 60 5292)

Standard: IP 67Options: IP 68

Corrosion protection Standard: KN Suitable for installation in industrial units, in water or power plantswith a low pollutant concentration

Options: KS Suitable for installations in occasionally or permanently aggressiveatmosphere with moderate pollutant concentration)(e.g. wastewater treatment plants, chemical industry)

KX Suitable for installation in extremely aggressive atmosphere with highhumidity and high pollutant concentration

Finish coating Standard: Two-component iron-mica combinationColour Standard: AUMA silver-grey (similar to RAL 7037)

Option: Other colours are possible on requestAmbient temperature Standard: – 25 °C to + 80 °C

Options: – 25 °C to + 70 °C (in combination with position transmitter RWG)– 40 °C to + 60 °C (low temperature)

Further informationEU Directives Electromagnetic Compatibility (EMC): (2004/108/EC)

Low Voltage Directive: (2006/95/EC)Machinery Directive: (98/37/EC)

Reference documents Product description Limit switching WSH 10.1 – WSH 16.1Technical data WSH 10.1 – WSH 16.1Dimensions WSH 10.1 – WSH 16.1

1) For output drives types A2) For version in enclosure protection IP 68, higher corrosion protection KS or KX is strongly recommended

5

Operation instructions Limit switching WSH 10.1 – WSH 16.1

Page 6: Limit switching WSH for manually operated valves WSH 10.1 – 16.1

4. Transport and storage4.1. Transport .Transport to place of installation in sturdy packing..For products equipped with handwheel, do not attach ropes or hooks to

the handwheel for the purpose of lifting by hoist.. If the limit switching WSH and gearbox are mounted on the valve, attachropes or hooks for the purpose of lifting by hoist to the valve and not to thelimit switching/gearbox.

4.2. Storage .Store in well-ventilated, dry room..Protect against floor dampness by storage on a shelf or on a woodenpallet..Cover to protect against dust and dirt..Apply suitable corrosion protection agent to bare surfaces.

In case limit switching WSH is to be stored for a long period(more than 6 months), the following points must be observed additionally:.Prior to storage: Protect bare surfaces, in particular the output drive parts

and mounting surface, with long-term corrosion protection agent..Check for corrosion approximately every 6 months. If first signs of corro-sion show, apply new corrosion protection.

After mounting the limit switching WSH, connect the unit immediately toelectrical mains, so that condensation is prevented by the heater.

4.3. Packaging Our products are protected by special packaging for the transport ex works.The packaging consists of environmentally friendly materials which caneasily be separated and recycled.For the disposal of the packaging material, we recommend recycling andcollection centres.We use the following packaging materials: wood, cardboard, paper, and PE foil.

6

Limit switching WSH 10.1 – WSH 16.1 Operation instructions

Page 7: Limit switching WSH for manually operated valves WSH 10.1 – 16.1

5. Mounting to valve/gearbox

.Prior to mounting, the limit switching WSH must bechecked for damage. Damaged parts must be replaced byoriginal spare parts..After mounting to valve/gearbox, touch up any possibledamage to paint finish.

The limit switching WSH leaves the factory in position CLOSED(limit switch CLOSED tripped)..Check if mounting flange fits the valve/gearbox.

Spigot at flanges should be loose fit!

The output drive types B1, B2, B3, or B4 (figure 1) are delivered with boreand keyway (usually according to EN ISO 5210).

For output drive type A (figure 2), the internal thread of the stem nut mustmatch the thread of the valve stem. If not ordered explicitly with thread, thestem nut is unbored or with pilot bore when delivered. For finish machiningof stem nut, refer to next page..Check whether bore and keyway match the input shaft of valve/gearbox..Thoroughly degrease mounting faces at limit switching WSH and valve/

gearbox..Apply a small quantity of grease to input shaft of valve/gearbox..Place limit switching WSH on valve/gearbox and fasten. Fasten bolts(quality min. 8.8, refer to table 1) evenly crosswise.

7

Operation instructions Limit switching WSH 10.1 – WSH 16.1

Figure 1

Output drive type B1/ B2Plug sleeve

Output drive type B3/ B4Bore with keyway

Strength class 8.8 TA (Nm)

M10 51M16 214M20 431

Table 1: Fastening torques for bolts

Page 8: Limit switching WSH for manually operated valves WSH 10.1 – 16.1

Finish machining of stem nut (output drive type A):

The output drive flange does not have to be removed from the limit switchingWSH..Remove spigot ring (80.2, figure 2) from mounting flange..Take off stem nut (80.3) together with thrust bearing (80.01) and thrust

bearing races (80.02)..Remove thrust bearing and thrust bearing races from stem nut..Drill and bore stem nut and cut thread.When fixing in the chuck, make sure stem nut runs true!.Clean the machined stem nut..Apply Lithium soap EP multi-purpose grease to thrust bearing and races,then place them on stem nut..Re-insert stem nut with thrust bearings into the mounting flange. Ensurethat dogs are placed correctly in the slots of the hollow shaft..Screw in spigot ring until it is firm against the shoulder..Press Lithium soap EP multi-purpose grease on mineral oil base into thegrease nipple with a grease gun (for quantities, please refer to table):

Protection tube for rising valve stem.Seal thread of protection tube with hemp, Teflon tape, or thread sealingmaterial..Screw protection tube (1) into thread (figure 3) and tighten it firmly..Push down the sealing (2) to the housing..Check whether cap (3) is available and without damage.

8

Limit switching WSH 10.1 – WSH 16.1 Operation instructions

Output drive A 10.2 A 14.2 A 16.2

Qty1) 2 g 3 g 5 g

1) For greases with a density ρ = 0.9 kg/dm³

Table 2: Grease quantities for output drive A

Figure 2

80.3

80.2

Output drive type AStem nut

80.01/80.02

3

1

2

Figure 3: Protection tube for rising valve stem

Page 9: Limit switching WSH for manually operated valves WSH 10.1 – 16.1

6. Electrical connection .Work on the electrical system or equipment must only becarried out by a skilled electrician himself or by speciallyinstructed personnel under the control and supervision ofsuch an electrician and in accordance with the applicableelectrical engineering rules..Before connection check whether type of current and volt-age fulfil the indications on the wiring diagram

6.1. Connection with AUMA plug/socket connector in crimp version

.Loosen bolts (50.01) (figure 4) and remove plug cover..Loosen screws (51.01) and remove socket carrier (51.0) from plug cover (50.0).. Insert cable glands suitable for connecting cables(The enclosure protection stated on the name plate is only ensured ifsuitable cable glands are used)..Seal cable entries which are not used with suitable plugs..Connect cables according to order-related wiring diagram..The pertaining wiring diagram is attached to the product in aweather-proof bag, together with these operation instructions. In case theterminal plan is not available, it can be obtained from AUMA (statecommission no., refer to name plate) or downloaded directly from theInternet (www.auma.com).

Crimp sockets are supplied separately and in sufficient number inside theplug cover.For crimping, a suitable tool, e.g. the BUCHANAN four indent crimp tool,must be used.

Cross sections:0.75 – 1 mm2, on request 0.5 mm2 or 1.5 mm2

6.2. Heater To reduce condensation within the housing, the heater must be connected.

9

Operation instructions Limit switching WSH 10.1 – WSH 16.1

Figure 4: Connection

50.0

50.01

51.0

51.01

Technical data Protective earth Control pinsNumber of contacts max. 1 (leading contact) 50 pins/sockets (40 are used)Designation according to VDE A1 to I4Connecting voltage max. – 250 VNominal current max. – 16 AType of customer connection Crimp connection Crimp connectionCross section max. 1.5 mm2 1.5 mm2

Material: Pin/socket carrier Polyamide PolyamideContacts Brass Brass tin-plated or gold-plated (option)

Table 3: Technical data AUMA plug/ socket connector as crimp version

Page 10: Limit switching WSH for manually operated valves WSH 10.1 – 16.1

7. Switch compartment The following sub-assemblies are located within the switch compartment:

.Limit switching (page 11)..DUO limit switching (option) (page 13).Potentiometer (option) (page 16).Electronic position transmitter (option) (page 17).Mechanical position indicator (page 20 )

The switch compartment must be opened to perform the setting of thesesub-assemblies.

7.1. Opening the switchcompartment

Work on the electrical system or equipment must only becarried out by a skilled electrician himself or by speciallyinstructed personnel under the control and supervision ofsuch an electrician and in accordance with the applicableelectrical engineering rules.

.Remove 4 bolts and take off the cover at the switch compartment(figure 5).

7.2. Pulling off the indicator disc .Pulling off the indicator disc (figure 6). Open end wrench may be used aslever.

Limit switching WSH 10.1 – WSH 16.1 Operation instructions

10

Figure 5: Cover with indicator glass

DSR

WDR

Figure 6: Pulling off the indicator disc

Indicator disc

Page 11: Limit switching WSH for manually operated valves WSH 10.1 – 16.1

8. Setting the limitswitching

If a gearbox is mounted, the end stops within the gearbox must be set priorto setting the limit switching (refer to operation instructions of gearbox).

8.1. Clockwise closing The following description is only valid for “clockwise closing”, i.e. driven shaftturns clockwise to close the valve.Identification within the wiring diagram:APG- -AP... for “clockwise closing”.

Setting end position CLOSED (black section).Turn handwheel clockwise until valve is closed..Connect continuity tester via limit switch LSC (WSR) to electrical connec-tion (figure 7). As standard version, this connection is made via pins A2and A4 (refer to terminal plan attached)..Press down and turn setting spindle A (figure 8) with screw driver indirection of arrow, thereby observe cam B.While a ratchet is felt and heard, the cam B moves 90° every time until thelimit switch LSC (WSR) is operated. The connected continuity testersignals the operation of the switch.Stop turning and release setting spindle.When overriding the tripping point inadvertently (ratchet is heard after thecam has snapped), continue turning the setting spindle in the same direc-tion and repeat setting process.Attention: Ensure that setting spindle A is released by spring action afterthe setting process is completed.

Setting end position OPEN (white section).Turn handwheel counterclockwise until valve is open..Connect continuity tester via limit switch LSO (WÖL) to electrical connec-tion (figure 7). As standard version, this connection is made via pins B2and B4 (refer to terminal plan attached)..Press down and turn setting spindle C (figure 8) with screw driver indirection of arrow, thereby observe cam D.While a ratchet is felt and heard, the cam D moves 90° every time until thelimit switch LSO (WÖL) is operated. The connected continuity testersignals the operation of the switch.Stop turning and release setting spindle.When overriding the tripping point inadvertently (ratchet is heard after thecam has snapped), continue turning the setting spindle in the same direc-tion and repeat setting process.Attention: Ensure that setting spindle C is released by spring action afterthe setting process is completed.

11

Operation instructions Limit switching WSH 10.1 – WSH 16.1

Figure 7: Electrical connection Figure 8: Control unit (example with scale 1 to 8)

A

B

C

LSC (WSR)

D

LSO (WÖL)

Page 12: Limit switching WSH for manually operated valves WSH 10.1 – 16.1

8.2. Counterclockwise closing The following description is only valid for “counterclockwise closing”, i.e.driven shaft turns counterclockwise to close the valve.Identification within the wiring diagram:APG-1AP... for “counterclockwise closing”.

Setting end position CLOSED (black section).Turn handwheel counterclockwise until valve is closed..Connect continuity tester via limit switch LSC (WSL) to electrical connec-tion (figure 9). Pins A2 and A4 (please refer to terminal plan attached)..Press down and turn setting spindle C (figure 10) with screw driver indirection of arrow, thereby observe cam D.While a ratchet is felt and heard, the cam D moves 90° every time until thelimit switch LSC (WSL) is operated. The connected continuity testersignals the operation of the switch.Stop turning and release setting spindle.When overriding the tripping point inadvertently (ratchet is heard after thecam has snapped), continue turning the setting spindle in the same direc-tion and repeat setting process.Attention: Ensure that setting spindle C is released by spring action afterthe setting process is completed.

Setting end position OPEN (red section).Turn handwheel clockwise until valve is open..Connect continuity tester via limit switch LSO (WÖR) to electrical connec-tion (figure 9). Pins B2 and B4 (please refer to terminal plan attached)..Press down and turn setting spindle A (figure 10) with screw driver indirection of arrow, thereby observe cam B. While a ratchet is felt andheard, the cam B moves 90° every time until the limit switch LSO (WÖR)is operated. The connected continuity tester signals the operation of theswitch.Stop turning and release setting spindle.When overriding the tripping point inadvertently (ratchet is heard after thecam has snapped), continue turning the setting spindle in the same direc-tion and repeat setting process.Attention: Ensure that setting spindle A is released by spring action afterthe setting process is completed.

12

Limit switching WSH 10.1 – WSH 16.1 Operation instructions

Figure 9: Electrical connection Figure 10: Control unit counterclockwise closing (example with scale 1 to 8)

A

B

C

LSOR (WÖR)

D

LSCL (WSL)red

field

blackfield

Page 13: Limit switching WSH for manually operated valves WSH 10.1 – 16.1

9. Setting the DUO limit switching (option)Any application can be switched on or off via the two intermediate positionswitches.

For setting, the switching point (intermediate position) mustbe approached from the same direction as afterwards inoperation.

9.1. Clockwise closing The following description is only valid for “clockwise closing”, i.e. driven shaftturns clockwise to close the valve.Identification within the wiring diagram:APG- -AP...for “clockwise closing”.

Setting direction CLOSE (black section).Move valve to desired intermediate position..Connect continuity tester via limit switch LSA (WDR) to electrical connec-tion (figure 11). As standard version, this connection is made via pins C2and C4 (refer to terminal plan attached)..Press down and turn setting spindle E (figure 12) with screw driver indirection of arrow, thereby observe cam F.While a ratchet is felt and heard, the cam F moves 90° every time until thelimit switch LSA (WDR) is operated. The connected continuity testersignals the operation of the switch.Stop turning and release setting spindle.When overriding the tripping point inadvertently (ratchet is heard after thecam has snapped), continue turning the setting spindle in the same direc-tion and repeat setting process.Attention: Ensure that setting spindle E is released by spring action afterthe setting process is completed.

Setting direction OPEN (white section).Move valve to desired intermediate position..Connect continuity tester via limit switch LSB (WDL) to electrical connec-tion (figure 11). As standard version, this connection is made via pins D2and D4 (refer to terminal plan attached)..Press down and turn setting spindle G (figure 12) with screw driver indirection of arrow, thereby observe cam H.While a ratchet is felt and heard, the cam H moves 90° every time until thelimit switch LSB (WDL) is operated. The connected continuity testersignals the operation of the switch.Stop turning and release setting spindle.When overriding the tripping point inadvertently (ratchet is heard after thecam has snapped), continue turning the setting spindle in the same direc-tion and repeat setting process.Attention: Ensure that setting spindle G is released by spring action afterthe setting process is completed.

Operation instructions Limit switching WSH 10.1 – WSH 16.1

13

Figure 11: Electrical connection Figure 12: Control unit (example with scale 1 to 8)

E

F

G

LSB (WDL) H

LSA (WDR)

Page 14: Limit switching WSH for manually operated valves WSH 10.1 – 16.1

9.2. Counterclockwise closing The following description is only valid for “counterclockwise closing”, i.e.driven shaft turns counterclockwise to close the valve.Identification within the wiring diagram:APG-1AP... for “counterclockwise closing”.

Setting direction CLOSE (black section).Move valve to desired intermediate position..Connect continuity tester via limit switch LSA (WDL) to electrical connec-tion (figure 13). Pins C2 and C4 (please refer to terminal plan attached)..Press down and turn Setting spindle G (figure 14) with screw driver indirection of arrow, thereby observe cam H.While a ratchet is felt and heard, the cam H moves 90° every time until thelimit switch LSA (WDL) is operated. The connected continuity testersignals the operation of the switch.Stop turning and release setting spindle.When overriding the tripping point inadvertently (ratchet is heard after thecam has snapped), continue turning the setting spindle in the same direc-tion and repeat setting process.Attention: Ensure that setting spindle G is released by spring action afterthe setting process is completed.

Setting direction OPEN (red section).Move valve to desired intermediate position..Connect continuity tester via limit switch LSB (WDR) to electrical connec-tion (figure 13). Pins D2 and D4 (please refer to terminal plan attached)..Press down and turn setting spindle E (figure 14) with screw driver indirection of arrow, thereby observe cam F.While a ratchet is felt and heard, the cam F moves 90° every time until thelimit switch LSB (WDR) is operated. The connected continuity testersignals the operation of the switch.Stop turning and release setting spindle.When overriding the tripping point inadvertently (ratchet is heard after thecam has snapped), continue turning the setting spindle in the same direc-tion and repeat setting process.Attention: Ensure that setting spindle E is released by spring action afterthe setting process is completed.

14

Limit switching WSH 10.1 – WSH 16.1 Operation instructions

Figure 13: Electrical connection

12

3

4 56

78

WDR

WÖR WSL

WDL

LSO

LSB LSA

LSC

Figure 14: Control unit counterclockwise closing (example with scale 1 to 8)

E

F

G

LSB (WDL) H

LSA (WDR)

redfield

blackfield

Page 15: Limit switching WSH for manually operated valves WSH 10.1 – 16.1

10. Setting/testing the reduction gearing

To ensure correct mechanical position indication, the reduction gearing mustbe adapted to the turns per stroke of the valve position indicator.

The following versions are possible:2 to 500 turns per stroke = scale 1 to 8 (figure 15)8 to 2,000 turns per stroke = scale 3 to 10 (not shown).Check whether turns/stroke of the valve position indicator correspond to

the stage setting of the reduction gearing, using table 4).

If the setting is not correct:

Set stage by offsetting the locking screw (03).

To make best use of the electrical rotation angle of the potentiometer forversions equipped with potentiometer (page 16) or RWG (page 17), thereduction gearing (stages 1 to 10) is additionally divided by a furthergearwheel set (A, B, C). If it is required to modify the stage pre-set in thefactory for these versions, we recommend to contact AUMA.

15

Operation instructions Limit switching WSH 10.1 – WSH 16.1

Turns/strokeabove – to

Gearstage

2 – 4 14 – 8 28 – 16 3

16 – 32 432 – 63 5

Turns/strokeabove – to

Gearstage

63 – 125 6125 – 250 7250 – 500 8

500 – 1,000 91,000 – 2,000 10

Table 4: Reduction gearing

Figure 15: Control unit (here as example with scale 1 to 8)

03

Page 16: Limit switching WSH for manually operated valves WSH 10.1 – 16.1

11. Setting the potentiometer (option)

The potentiometer records the valve position.

If an electronic position transmitter (RWG) is installed, the potentiometersetting is performed with the RWG setting(please refer to pages 17 et seqq.).

Prior to potentiometer setting, make sure to correctly set the reductiongearing (refer to page 15)..Move valve to end position CLOSED.

.Turn potentiometer (figure 16) to the stop in compliance with table 5.End position CLOSED corresponds to 0 %, end position OPEN to 100 %.

.Turn potentiometer slightly back from the stop.

Limit switching WSH 10.1 – WSH 16.1 Operation instructions

16

Figure 16: Control unit (example with scale 1 to 8)

Potentiometer

01

02

Version forclockwise closing (standard)

Version forcounterclockwise closing

Reduction stage is set to Reduction stage is set to1, 3, 5, 7, 9 2, 4, 6, 8, 10 1, 3, 5, 7, 9 2, 4, 6, 8, 10

Table 5: Potentiometer direction of rotation

Page 17: Limit switching WSH for manually operated valves WSH 10.1 – 16.1

12. Setting the electronic position transmitter RWG (option)

The electronic position transmitter records the valve position and generatesa current signal between 0/4 and 20 mA, using the actual position valuemeasured by the potentiometer.

After mounting to the gearbox, the setting must be checked(refer to clauses 12.1. or 12.2.).

2-wire or 3-/4-wire-systemThe 2-wire or 3-/4-wire version are set at slide switch S1 in the factory incompliance with the purchase order.

Dot visible:3-/4-wire system 0/4 – 20 mA

Dot not visible:2-wire system 4 – 20 mA

Jumper positionThe lock screw (figure 17) shows the pre-set reduction stage(refer also to page 15)

Operation instructions Limit switching WSH 10.1 – WSH 16.1

17

Figure 17: Control unit with RWG

S1

Jumpers

Lock screw

Wiring diagrams APG AP_ 2 / _ _ _APG1AP_ 2 / _ _ _3- or 4- wire system

APG AP _3 _ / _ _ _APG1AP _3 _ / _ _ _

for 2-wire systemOutput current Ia 0 – 20 mA, 4 – 20 mA 4 – 20 mAPowersupply

Uv 24 V DC 14 V DC + (I x RB),max. 30 V

max.current input

I 24 mA at 20 mAoutput current

20 mA

Max. load RB 600 � (Uv - 14 V)/20 mA

Table 6: Technical data RWG

Version forclockwise closing (standard)

Version forcounterclockwise closing

Reduction stage is set to Reduction stage is set to1, 3, 5, 7, 9 2, 4, 6, 8, 10 1, 3, 5, 7, 9 2, 4, 6, 8, 10

Jumper arrange-ment to the right

Jumper arrange-ment to the left

Jumper arrange-ment to the left

Jumper arrange-ment to the right

Table 7: Jumper position

Page 18: Limit switching WSH for manually operated valves WSH 10.1 – 16.1

12.1. Setting 2-wire system 4 – 20 mA or 3-/4-wire system 0 – 20 mA

Prior to RWG setting, make sure to correctly set the reduction gearing(refer to page 15)..Connect voltage to electronic position transmitter..Move valve to end position CLOSED..Connect ammeter for 0 – 20 mA to measuring points (figure 18).

The circuit (external load) must be connected(max. load RB), or the appropriate poles at the terminals(refer to wiring diagram) must be linked, otherwise novalue can be measured.

.Set potentiometer (refer to page 16).

.Turn potentiometer “Rmin” clockwise until output current starts to increase..Turn potentiometer “Rmin.” back until the following value is reached:for 3- or 4- wire system approx. 0.1 mAfor 2-wire system: approx. 4.1 mA.This ensures that the signal remains above the dead and live zero point..Move valve to end position OPEN..Set potentiometer “Rmax.” to end value 20 mA..Approach end position CLOSED again and check minimum value(0.1 mA or 4.1 mA). If necessary, correct the setting.

18

Limit switching WSH 10.1 – WSH 16.1 Operation instructions

Figure 18

“Rmin.” (0/4 mA) “Rmax.” (20 mA)

(+) Meas. points(– ) 0/4 – 20 mA

Potentiometer“R”

Page 19: Limit switching WSH for manually operated valves WSH 10.1 – 16.1

12.2. Setting 3-/4-wire system 4 – 20 mA

Prior to RWG setting, make sure to correctly set the reduction gearing(refer to page 15)..Connect voltage to electronic position transmitter..Move valve to end position CLOSED..Connect ammeter for 0 – 20 mA to measuring points (figure 19).

The circuit (external load) must be connected(max. load RB), or the appropriate poles at the terminals(refer to wiring diagram) must be linked, otherwise novalue can be measured.

.Set potentiometer (refer to page 16).

.Turn potentiometer “Rmin” clockwise until output current starts toincrease..Turn back potentiometer “Rmin.” until a residual current of approx. 0.1 mAis reached..Move valve to end position OPEN..Set potentiometer “Rmax.” to end value 16 mA..Move valve to end position CLOSED..Set potentiometer “Rmin.” from 0.1 mA to initial value 4 mA.This results in a simultaneous shift of the end value by 4 mA, so that thetravel range is now 4 – 20 mA..Approach both end positions again and check setting. If necessary,correct the setting.

19

Operation instructions Limit switching WSH 10.1 – WSH 16.1

Figure 19

“Rmin.” (0/4 mA) “Rmax.” (20 mA)

(+) Meas.points(– ) 0/4 – 20 mA

Potentiometer“R”

Page 20: Limit switching WSH for manually operated valves WSH 10.1 – 16.1

13. Setting the mechanical position indicator

When changing the mounting position the mechanical posi-tion indicator may have to be set again.

.Place indicator disc on shaft..Move valve to end position CLOSED..Turn lower indicator disc (figure 20) until symbol CLOSED is in align-ment with the mark on the cover (figure 21)..Move valve to end position OPEN..Hold lower indicator disc CLOSED in position and turn upper disc withsymbol OPEN until it is in alignment with the mark on the cover.

Indicator disc rotates by approximately 140° to 280° at full travel from OPENto CLOSED or vice versa (depending on the reduction ratio). For thispurpose, a suitable reduction gearing was installed in our works.If the turns per stroke are changed at a later date, the gear stage of thereduction gearing might have to be adapted (refer to page 15).

13.1. Closing the switchcompartment

After having worked at the switch compartment:

.Clean sealing faces of housing and cover..Check whether O-ring is in good condition..Apply a thin film of non-acidic grease to the sealing faces..Replace cover on switch compartment and fasten bolts evenly crosswise.

If damage to paint-finish has occurred after mounting, it hasto be touched up to avoid corrosion.

20

Limit switching WSH 10.1 – WSH 16.1 Operation instructions

Figure 20

Indicator disc

Mark

Figure 21

Page 21: Limit switching WSH for manually operated valves WSH 10.1 – 16.1

14. Enclosure protection IP 68

Definition According to DIN EN 60 259, the conditions for meeting the requirements ofenclosure protection IP 68 are to be agreed between manufacturer anduser.AUMA devices in enclosure protection IP 68 meet the following require-ments according to AUMA:.Duration of submersion in water max. 72 hours.Head of water max. 6 m.Up to 10 operations during submersion

If submersed in other media, additional measures for corrosion protectionmay be necessary; please consult AUMA. Submersion in aggressive media,e.g. acids or alkaline solutions, is not permitted.

Cable glands .For devices with electrical components, appropriate cable glands in enclo-sure protection IP 68 must be used for the entries of electrical cables. Thesize of the cable glands must be suitable for the outside diameter of thecables, refer to recommendations of the cable gland manufacturers..Devieces are usually supplied without cable glands. For delivery, thethreads are sealed with plugs in the factory..When ordered, cable glands can also be supplied by AUMA at an addi-tional charge. For this, it is necessary to state the outside diameter of thecables..The cable glands must be sealed against the housing at the thread withan O-ring.. It is recommended to additionally apply a liquid sealing material (Loctite orsimilar).

Notes: .The enclosure protection IP 68 refers to the interior..When using output drive type A (stem nut), it cannot be prevented thatwater enters the hollow shaft along the valve stem during submersion.This leads to corrosion. The water also enters the thrust bearings ofoutput drive type A, causing corrosion and damage to the bearings. Theoutput drive type A should therefore not be used.. If the limit switching WSH is likely to be repeatedly submersed, a highercorrosion protection KS or KX is required.

Commissioning When commissioning, the following should be observed:.Sealing faces of housing and covers must be clean.O-rings of the covers must not be damaged.A thin film of non-acidic grease should be applied to sealing faces.Covers should be tightened evenly and firmly

Following an ingress of water .Check:In case of ingress of water, dry device correctly and check for proper func-tion.

21

Operation instructions Limit switching WSH 10.1 – WSH 16.1

Page 22: Limit switching WSH for manually operated valves WSH 10.1 – 16.1

15. Maintenance After commissioning, check device for damage to paint finish. Do a thoroughtouch-up to prevent corrosion. Original paint in small quantities can be suppliedby AUMA.

AUMA products require only very little maintenance.Precondition for reliable service is correct commissioning.

Seals made of elastomers are subject to ageing and must therefore regu-larly be checked and, if necessary, be exchanged.

It is also very important that the O-rings at the covers are placed correctlyand cable glands fastened firmly to prevent ingress of dirt or water.

We recommend additionally:. If rarely operated, perform a test run about every 6 months. This ensuresthat the device is always ready to operate..Approximately six months after commissioning and then every year checkbolts between limit switching WSH and gearbox for tightness. If required,tighten applying the torques given in table 1, page 7.

16. Lubrication AUMA products are lubricated for life. Subsequent lubrication is notrequired.

17. Disposal and recyclingAUMA devices have a long lifetime. However, they have to be replaced atone point in time.The devices have a modular design and may, therefore, easily be separatedand sorted according to materials used, i.e.:.electronic scrap.various metals.plastics.greases and oils

The following generally applies:.Collect greases and oils during disassembly. As a rule, these substancesare hazardous to water and must not be released into the environment..Arrange for controlled waste disposal of the disassembled material or forseparate recycling according to materials..Observe the national regulations for waste disposal.

18. Service AUMA offers extensive services such as maintenance and inspection foractuators. Addresses of AUMA offices and representatives can be found onpage 26 to 27 and on the Internet (www.auma.com).

22

Limit switching WSH 10.1 – WSH 16.1 Operation instructions

Page 23: Limit switching WSH for manually operated valves WSH 10.1 – 16.1

Notes

23

Operation instructions Limit switching WSH 10.1 – WSH 16.1

Page 24: Limit switching WSH for manually operated valves WSH 10.1 – 16.1

19. Declaration of Conformity and Declaration of Incorporation

24

Limit switching WSH 10.1 – WSH 16.1 Operation instructions

Page 25: Limit switching WSH for manually operated valves WSH 10.1 – 16.1

25

Operation instructions Limit switching WSH 10.1 – WSH 16.1

IndexCCorrosion protection 6,22Cross sections 9

DDeclaration of Conformity 24Declaration of Incorporation 24Disposal and recycling 22DUO limit switching 13

EElectrical connection 9Electronic position transmitter RWG

2-wire system 183- or 4-wire system 19

Enclosure protection IP 68 21

FFinish machining of stem nut 8

HHeater 9

IIndicator disc 10,20

LLimit switching 11,13Lubrication 22

MMaintenance 4Mechanical position indicator 20Mounting to valve/gearbox 7

OOutput drive types 7

PPackaging 6Position indicator 20Position transmitter RWG 17Potentiometer 16Protection tube 8

RRWG 17

SSafety instructions 4Service 22Storage 6Switch compartment 10

TTechnical data 5Transport 6

Page 26: Limit switching WSH for manually operated valves WSH 10.1 – 16.1

EuropeAUMA Riester GmbH & Co. KGPlant MüllheimDE-79373 MüllheimTel +49 7631 809 - 0Fax +49 7631 809 - [email protected]

Plant Ostfildern-NellingenDE-73747 OstfildernTel +49 711 34803 - 0Fax +49 711 34803 - [email protected]

Service-Center KölnDE-50858 KölnTel +49 2234 2037 - 9000Fax +49 2234 2037 - [email protected]

Service-Center MagdeburgDE-39167 NiederndodelebenTel +49 39204 759 - 0Fax +49 39204 759 - [email protected]

Service-Center BayernDE-85386 EchingTel +49 81 65 9017- 0Fax +49 81 65 9017- [email protected]

AUMA Armaturenantriebe GmbHAT-2512 TribuswinkelTel +43 2252 82540Fax +43 2252 [email protected]

AUMA (Schweiz) AGCH-8965 BerikonTel +41 566 400945Fax +41 566 [email protected]

AUMA Servopohony spol. s.r.o.CZ-250 01 Brandýs n.L.-St.BoleslavTel +420 326 396 993Fax +420 326 303 [email protected]

OY AUMATOR ABFI-02230 EspooTel +358 9 5840 22Fax +358 9 5840 [email protected]

AUMA France S.A.R.L.FR-95157 Taverny CedexTel +33 1 39327272Fax +33 1 [email protected]

AUMA ACTUATORS Ltd.GB- Clevedon North Somerset BS21 6THTel +44 1275 871141Fax +44 1275 [email protected]

AUMA ITALIANA S.r.l. a socio unicoIT-20023 Cerro Maggiore (MI)Tel +39 0331 51351Fax +39 0331 [email protected]

AUMA BENELUX B.V.NL-2314 XT LeidenTel +31 71 581 40 40Fax +31 71 581 40 [email protected]

AUMA Polska Sp. z o.o.PL-41-219 SosnowiecTel +48 32 783 52 00Fax +48 32 783 52 [email protected]

OOO Priwody AUMARU- 124365 Moscow a/ya 11Tel +7 495 221 64 28Fax +7 495 221 64 [email protected]

ERICHS ARMATUR ABSE-20039 MalmöTel +46 40 311550Fax +46 40 [email protected]

GRØNBECH & SØNNER A/SDK-2450 København SVTel +45 33 26 63 00Fax +45 33 26 63 [email protected]

IBEROPLAN S.A.ES-28027 MadridTel +34 91 3717130Fax +34 91 [email protected]

D. G. Bellos & Co. O.E.GR-13671 Acharnai AthensTel +30 210 2409485Fax +30 210 [email protected]

SIGURD SØRUM A. S.NO-1300 SandvikaTel +47 67572600Fax +47 [email protected]

INDUSTRAPT-2710-297 SintraTel +351 2 1910 95 00Fax +351 2 1910 95 [email protected]

MEGA Endüstri Kontrol Sistemieri Tic. Ltd.Sti.TR-06810 AnkaraTel +90 312 217 32 88Fax +90 312 217 33 [email protected]

CTS Control Limited Liability CompanyUA-02099 KiyivTel +38 044 566-9971, -8427Fax +38 044 [email protected]

AfricaAUMA South Africa (Pty) Ltd.ZA-1560 SpringsTel +27 11 3632880Fax +27 11 [email protected]

A.T.E.C.EG- CairoTel +20 2 23599680 - 23590861Fax +20 2 [email protected]

AmericaAUMA ACTUATORS INC.US-PA 15317 CanonsburgTel +1 724-743-AUMA (2862)Fax +1 [email protected]

AUMA Argentina Representative OfficeAR-BoulogneTel/Fax +54 232 246 [email protected]

AUMA Automação do Brasil Ltda.BR-Sao PauloTel +55 11 [email protected]

AUMA Chile Representative OfficeCL-9500414 BuinTel +56 2 821 4108Fax +56 2 281 [email protected]

TROY-ONTOR Inc.CA-L4N 8X1 Barrie OntarioTel +1 705 721-8246Fax +1 705 [email protected]

MAN Ferrostaal de Colombia Ltda.CO- Bogotá D.C.Tel +57 1 401 1300Fax +57 1 416 [email protected]

PROCONTIC Procesos y Control AutomáticoEC- QuitoTel +593 2 292 0431Fax +593 2 292 [email protected]

Corsusa International S.A.C.PE- Miralflores - LimaTel +511444-1200 / 0044 / 2321Fax [email protected]

PASSCO Inc.PR-00936-4153 San JuanTel +18 09 78 77 20 87 85Fax +18 09 78 77 31 72 [email protected]

SuplibarcaVE- Maracaibo Estado, ZuliaTel +58 261 7 555 667Fax +58 261 7 532 [email protected]

AsiaAUMA Actuators (Tianjin) Co., Ltd.CN-300457 TianjinTel +86 22 6625 1310Fax +86 22 6625 [email protected]

AUMA (INDIA) PRIVATE LIMITEDIN-560 058 BangaloreTel +91 80 2839 4655Fax +91 80 2839 [email protected]

AUMA JAPAN Co., Ltd.JP-210-0848 Kawasaki-ku, Kawasaki-shiKanagawaTel +91 80 2839 4655Fax +81 44 366 [email protected]

AUMA ACTUATORS (Singapore) Pte Ltd.SG-569551 SingaporeTel +65 6 4818750Fax +65 6 [email protected]

26

AUMA worldwide

Page 27: Limit switching WSH for manually operated valves WSH 10.1 – 16.1

AUMA Actuators Middle East W.L.L.AE- 15268 Salmabad 704Tel +973 17877377Fax +973 [email protected]

PERFECT CONTROLS Ltd.HK- Tsuen Wan, KowloonTel +852 2493 7726Fax +852 2416 [email protected]

DW Controls Co., Ltd.KR-153-702 SeoulTel +82 2 2624 3400Fax +82 2 2624 [email protected]

Sunny Valves and Intertrade Corp. Ltd.TH-10120 Yannawa BangkokTel +66 2 2400656Fax +66 2 [email protected]/

Top Advance Enterprises Ltd.TW- Jhonghe City Taipei Hsien (235)Tel +886 2 2225 1718Fax +886 2 8228 [email protected]

AustraliaBARRON GJM Pty. Ltd.AU-NSW 1570 ArtarmonTel +61 294361088Fax +61 [email protected]

2010-06-17

27

Page 28: Limit switching WSH for manually operated valves WSH 10.1 – 16.1

Certificate Registration No.12 100/104 4269

AUMA Riester GmbH & Co. KGP.O.Box 1362D-79373 MüllheimTel +49 7631 809 - 0Fax+49 7631 809 - [email protected]

For detailed information on AUMA products refer to the Internet: www.auma.comY001.145/003/en/1.10