Lightning Protection and Earth Electrode Resistance By Steven McFadyen (/users/steven) on November 22nd, 2009 Most installations involve some form of lightning protection system which is connected to an earth electrode. The function of the earth electrode is to dissipate the lightning strike safely in to the ground. Often the performance of the earth electrode is specified and verified by stating a maximum resistance and ensuring that the installed system MEETS this. Resistance is easily understood and an easy property to measure. However, it is only indicative of the performance of the earth electrode under lightning conditions. Other parameters have a more signification effect. The detailed analysis of a system is relatively complicated. However, it is fairly easy to examine some of the concepts and see how resistance fits into the overall picture. The attached image shows a standard short stroke (duration less than 2 ms) as defined by IEC 62305 [1]. Although lightning strokes will be different, the important thing is the fast di/dt on the rise. Actual parameters vary stroke by stroke, but for a typical first stroke the mean peak current I is 33.3 kA with a dt/dt of 24.3 kA/μs [2][3]. We can use a a typical earth electrode specification of maximum resistance 10 , achieved by using an earth rod to illustrate some concepts. Typically an earth rod will have an inductance of 5x10 H/m [4]. If we assume the rod is 5 m long then the induced voltages due to resistance V and inductance V during the initial rise are: and As can be seen the voltage due to the inductance is twice that due to the resistance. A lightning peak of 65 kA or earth rod of 10 m the difference in voltage drops would be further exaggerated. This clearly illustrates the importance of inductance in the design of any lighting protection earth electrode. The use of resistance itself is not an accurate measure of performance. This is further complicated by soil ionizations. Due to the nature of lightning surges, soil ionization is likely to take place, reducing the apparent resistance [5]. The effect of this is to reduce resistive voltage drop and further increase the importance of the inductance of the system. The lighting stroke can also be looked at as a traveling wave. In this instance the current will have to contend with the surge impedance View a random note! (/randomnote.aspx) Subscribe Latest Questions: (/questions) lightning and grounding (/questions/view/question /id/539) 1. Power Transformer Temperature Measurement (/questions/view/question/id/538) 2. Voltage Conversion (/questions/view/question /id/536) 3. Arc Flash (/questions/view/question/id/534) 4. Voltage Transformer (/questions/view/question /id/535) 5. Earth Leakage Protection for 3 Phase Motor (Rating < 5.5kw) (/questions/view/question/id/530) 6. Power Swing (/questions/view/question/id/529) 7. Grounding Transformers above Ground Level (/questions/view/question/id/523) 8. more questions... (/questions) Most Popular Notes: (/notes) more notes... (/notes) Our Newsletter (http://myelectricalengineering.co.uk) Register (http://myelectrical.com/register?returnurl=http%3a%2f%2fmyelectrical.com%2fnotes) Login (http://myelectrical.com/login?returnurl=%2fnotes%2fentryid%2f30%2flightning-protection-and-earth-electrode-resistance) (http://myelectrical.com/) 30/90% -6 r l Receive updates on new posts by email HOME (HTTP://MYELECTRICAL.COM/) NOTES (HTTP://MYELECTRICAL.COM/NOTES) QUESTIONS (HTTP://MYELECTRICAL.COM/QUESTIONS) TOOLS (HTTP://MYELECTRICAL.COM/TOOLS) COMMUNITY (HTTP://MYELECTRICAL.COM/COMMUNITY) DIRECTORY (HTTP://MYELECTRICAL.COM/DIRECTORY) STORE (HTTP://MYELECTRICAL.COM/STORE) SUPPORT (HTTP://MYELECTRICAL.COM/SUPPORT) Lightning Protection and Earth Electrode Resistance http://myelectrical.com/notes/entryid/30/lightning-protection-and-earth-... 1 of 3 10/9/2014 5:07 μμ

Upload: mipanos

Post on 04-Oct-2015

4 views

Category:

Documents


0 download

DESCRIPTION

lightning

TRANSCRIPT

  • Lightning Protection and Earth Electrode Resistance

    By Steven McFadyen (/users/steven) on November 22nd, 2009

    Most installations involve some form of lightning protection

    system which is connected to an earth electrode. The function

    of the earth electrode is to dissipate the lightning strike safely in

    to the ground. Often the performance of the earth electrode is

    specified and verified by stating a maximum resistance and

    ensuring that the installed system MEETS this. Resistance is

    easily understood and an easy property to measure. However,

    it is only indicative of the performance of the earth electrode

    under lightning conditions. Other parameters have a more

    signification effect.

    The detailed analysis of a system is relatively complicated. However, it is fairly easy to examine some of the concepts and

    see how resistance fits into the overall picture. The attached image shows a standard short stroke (duration less than 2

    ms) as defined by IEC 62305 [1]. Although lightning strokes will be different, the important thing is the fast di/dt on the

    rise. Actual parameters vary stroke by stroke, but for a typical first stroke the mean peak current I is 33.3 kA with a

    dt/dt of 24.3 kA/s [2][3].

    We can use a a typical earth electrode specification of maximum resistance 10 , achieved by using an earth rod to

    illustrate some concepts. Typically an earth rod will have an inductance of 5x10 H/m [4]. If we assume the rod is 5 m

    long then the induced voltages due to resistance V and inductance V during the initial rise are:

    and

    As can be seen the voltage due to the inductance is twice that due to the resistance. A lightning peak of 65 kA or earth

    rod of 10 m the difference in voltage drops would be further exaggerated. This clearly illustrates the importance of

    inductance in the design of any lighting protection earth electrode. The use of resistance itself is not an accurate measure

    of performance.

    This is further complicated by soil ionizations. Due to the nature of lightning surges, soil ionization is likely to take place,

    reducing the apparent resistance [5]. The effect of this is to reduce resistive voltage drop and further increase the

    importance of the inductance of the system.

    The lighting stroke can also be looked at as a traveling wave. In this instance the current will have to contend with the

    surge impedance

    View a random note! (/randomnote.aspx)

    Subscribe

    Latest Questions: (/questions)lightning and grounding (/questions/view/question

    /id/539)

    1.

    Power Transformer Temperature Measurement

    (/questions/view/question/id/538)

    2.

    Voltage Conversion (/questions/view/question

    /id/536)

    3.

    Arc Flash (/questions/view/question/id/534)4.

    Voltage Transformer (/questions/view/question

    /id/535)

    5.

    Earth Leakage Protection for 3 Phase Motor (Rating

    < 5.5kw) (/questions/view/question/id/530)

    6.

    Power Swing (/questions/view/question/id/529)7.

    Grounding Transformers above Ground Level

    (/questions/view/question/id/523)

    8.

    more questions... (/questions)

    Most Popular Notes: (/notes)more notes... (/notes)

    Our Newsletter

    (http://myelectricalengineering.co.uk)

    Register (http://myelectrical.com/register?returnurl=http%3a%2f%2fmyelectrical.com%2fnotes)

    Login (http://myelectrical.com/login?returnurl=%2fnotes%2fentryid%2f30%2flightning-protection-and-earth-electrode-resistance)

    (http://myelectrical.com/)

    30/90%

    -6

    r l

    Receive updates on new posts by email

    HOME (HTTP://MYELECTRICAL.COM/) NOTES (HTTP://MYELECTRICAL.COM/NOTES) QUESTIONS (HTTP://MYELECTRICAL.COM/QUESTIONS)

    TOOLS (HTTP://MYELECTRICAL.COM/TOOLS) COMMUNITY (HTTP://MYELECTRICAL.COM/COMMUNITY) DIRECTORY (HTTP://MYELECTRICAL.COM/DIRECTORY)

    STORE (HTTP://MYELECTRICAL.COM/STORE) SUPPORT (HTTP://MYELECTRICAL.COM/SUPPORT)

    Lightning Protection and Earth Electrode Resistance http://myelectrical.com/notes/entryid/30/lightning-protection-and-earth-...

    1 of 3 10/9/2014 5:07

  • . In this analysis the resistance has no effect and it can be noted that the most efficient earth electrode system is one with

    a low inductance and high capacitance. An earth rod performs poorly in this regard and a better earth electrode system is

    a mesh type arrangement.

    While the above examples are conceptual, they do illustrate the influence of inductance, capacitance are important on the

    performance of a lighting protection system and that of resistance is less so. Good lightning earth electrode design should

    go beyond merely specifying a performance parameter based on resistance.

    References

    [1] - IEC 62305 'Protection against lightning - Part 1 General Principals', Annex A, 2006

    [2] - Berger K., Anderson R.B., Kroninger H., "Parameters of lightning flashes', CIGRE Electra No.41, 1975

    [3] - Anderson R.B., Eriksson A.J., "Lighting parameters for engineering application', CIGRE, Electra No.69, 1980

    [4] - William D. Stevenson, "Elements of power system analysis", p44-47, 1982, McGraw Hill

    [5] - Z. Stojkovic , 'The soil ionization influence on the lightning performance of transmission lines', University of

    Belgrade, 1999

    Generator Operation Limits

    In this situation I would do

    a software model of the system. That way I could

    verify exactly what is happening.Your

    How to refer fault levels across a transformer

    This is the level of short

    circuit fault (in MVA) the transformer has been

    designed to withstand. 2 seconds is the

    Photovoltaic (PV) - Electrical Calculations

    Thanks Steven, You have

    done really a great job by posting solar PV

    calculations online for many users

    How a Digital Substation Works

    Any voltage level. From an

    economic view, it is likely restricted to medium

    voltage and above (not low voltage

    0 Comments 1

    Lightning (http://myelectrical.com/notes/tag/lightning), Earthing (http://myelectrical.com/notes/tag/earthing), Insulation

    Coordination (http://myelectrical.com/notes?tag=insulation+coordination), Theory (http://myelectrical.com/notes

    /tag/theory)

    More interesting Notes:

    Harmonised Cable Codes and Colours (http://myelectrical.com/notes/entryid/228/harmonised-cable-codes-

    and-colours)

    Cables for MV Power Distribution - Earthed versus Unearthed Systems (http://myelectrical.com/notes/entryid

    /226/cables-for-mv-power-distribution-earthed-versus-unearthed-systems)

    Electromagnetic Compatibility (EMC) (http://myelectrical.com/notes/entryid/196/electromagnetic-compatibility-emc)

    Estimating Power Demand Using IEC Methods (http://myelectrical.com/notes/entryid/74/estimating-power-demand-

    using-iec-methods)

    IEC 60287 Current Capacity of Cables - An Introduction (http://myelectrical.com/notes/entryid/207/iec-60287-

    current-capacity-of-cables-an-introduction)

    (/users/steven)

    Steven McFadyen (/users/steven)

    Steven has over twenty five years experience working on some of the largest construction projects. He

    has a deep technical understanding of electrical engineering and is keen to share this knowledge.

    About the author

    Lightning Protection and Earth Electrode Resistance http://myelectrical.com/notes/entryid/30/lightning-protection-and-earth-...

    2 of 3 10/9/2014 5:07

  • View 3 Comments (old system)

    Popular Tags

    View All Tags (http://myelectrical.com/notes/viewtag/true)

    Have some knowledgeto shareIf you have some expert knowledge or

    experience, why not consider sharing this

    with our community.

    By writing an electrical note, you will be educating

    our users and at the same time promoting your

    expertise within the engineering community.

    To get started and understand our policy, you can read

    our How to Write an Electrical Note (/notes/entryid

    /149/how-to-write-an-electrical-note) .

    Click here to view the notes list in a table format

    (/notes/notes-table-view)

    Click here to view the notes indexed by tag (/notes

    /notes-index-view)

    COPYRIGHT (C) 2014 MYELECTRICAL HOME (/) CONTACT (/HOME/CONTACT-US) TERMS OF USE (HTTP://MYELECTRICAL.COM/TERMS)

    PRIVACY STATEMENT (HTTP://MYELECTRICAL.COM/PRIVACY)

    REGISTER (HTTP://MYELECTRICAL.COM/REGISTER?RETURNURL=HTTP%3A%2F

    %2FMYELECTRICAL.COM%2FNOTES)

    LOGIN (HTTP://MYELECTRICAL.COM/LOGIN?RETURNURL=%2FNOTES%2FENTRYID%2F30%2FLIGHTNING-

    PROTECTION-AND-EARTH-ELECTRODE-RESISTANCE)

    Automation (http://myelectrical.com/notes/tag/automation) Batteries (http://myelectrical.com/notes/tag/batteries)

    Buildings (http://myelectrical.com/notes/tag/buildings) Cable Sizing (http://myelectrical.com/notes?tag=cable+sizing)

    Cables (http://myelectrical.com/notes/tag/cables) Circuit Breakers (http://myelectrical.com/notes?tag=circuit+breakers)Commissioning (http://myelectrical.com/notes/tag/commissioning) Control Systems (http://myelectrical.com/notes?tag=control+systems)

    Earth Fault (http://myelectrical.com/notes?tag=earth+fault) Earthing (http://myelectrical.com/notes/tag/earthing)

    Editing (http://myelectrical.com/notes/tag/editing) Education (http://myelectrical.com/notes/tag/education)

    Electrical Installations (http://myelectrical.com/notes?tag=electrical+installations) Electronics (http://myelectrical.com/notes/tag/electronics)

    Energy (http://myelectrical.com/notes/tag/energy) Equipment (http://myelectrical.com/notes/tag/equipment)Equipment Data (http://myelectrical.com/notes?tag=equipment+data)

    Equipment Ratings (http://myelectrical.com/notes?tag=equipment+ratings)

    Equipment Sizing (http://myelectrical.com/notes?tag=equipment+sizing) Fault Calculation (http://myelectrical.com/notes?tag=fault+calculation)

    Fundamentals (http://myelectrical.com/notes/tag/fundamentals)Generation (http://myelectrical.com/notes/tag/generation) High Voltage (http://myelectrical.com/notes?tag=high+voltage)

    History (http://myelectrical.com/notes/tag/history) IEC Standards (http://myelectrical.com/notes?tag=iec+standards)

    Innovation (http://myelectrical.com/notes/tag/innovation) Lighting (http://myelectrical.com/notes/tag/lighting)

    Materials (http://myelectrical.com/notes/tag/materials) Medium Voltage (http://myelectrical.com/notes?tag=medium+voltage)

    Motor Control (http://myelectrical.com/notes?tag=motor+control) Motors (http://myelectrical.com/notes/tag/motors)myElectrical (http://myelectrical.com/notes/tag/myelectrical)

    Off-Topic (http://myelectrical.com/notes/tag/off-topic) Power Quality (http://myelectrical.com/notes?tag=power+quality)Power Systems (http://myelectrical.com/notes?tag=power+systems)

    Protection (http://myelectrical.com/notes/tag/protection) Protective Devices (http://myelectrical.com/notes?tag=protective+devices)

    Safety (http://myelectrical.com/notes/tag/safety) Scientists (http://myelectrical.com/notes/tag/scientists)

    Software (http://myelectrical.com/notes/tag/software) Standards (http://myelectrical.com/notes/tag/standards)Switchboards (http://myelectrical.com/notes/tag/switchboards) Testing (http://myelectrical.com/notes/tag/testing)

    Theory (http://myelectrical.com/notes/tag/theory)Transformers (http://myelectrical.com/notes/tag/transformers) Voltage (http://myelectrical.com/notes/tag/voltage)

    Wire Sizes (http://myelectrical.com/notes?tag=wire+sizes) Writing (http://myelectrical.com/notes/tag/writing)

    Lightning Protection and Earth Electrode Resistance http://myelectrical.com/notes/entryid/30/lightning-protection-and-earth-...

    3 of 3 10/9/2014 5:07