laboratory manual elec 365 applied electronics and ...elec365/lib/exe/... · elec 365 applied...
TRANSCRIPT
LABORATORY MANUAL
ELEC 365
APPLIED ELECTRONICS AND ELECTRICAL
MACHINES
by
J.M.-S. Kim
Revised by Babak Manouchehrinia, 2015
University of Victoria
Department of Electrical and Computer Engineering
©University of Victoria, 1990
Revised July 2009
Revised July 2010
Revised July 2015
EXPERIMENT 2
DC MACHINES
2.1 Objective
To study the steady state operation and performance characteristics of a DC
machine both as a motor and generator running with the separate field excitation.
2.2 Introduction
The stator or field of a DC generator or motor (Fig. 2.1) consists of an even
number of magnetic poles (alternating N and S around the circumference) excited
by direct current flowing in the field windings. The rotor or armature consists of a
cylindrical iron core carrying the active conductors embedded in slots and
connected to the segments of the commutator. Stationary brushes riding on the
commutator carry the direct current to and from the armature winding. Switching
of the conductors is done automatically by the commutator so that the external
current from a generator or the torque from a motor is steady and unidirectional.
Thus the commutator acts as a rectifier as far as the external circuit is concerned.
Both the stator and rotor produce magnetic fields. The angle between these two
fields is called torque angle δ (Fig. 2.1a) and in the case of a DC machine δ = 90◦.
Section 2.2.1 describes the basic relation among the DC machine parameters at
steady state. The relation between the generated electromotive force (emf) and the
field current is explained by the magnetization curve in section 2.2.2. Different
modes of field excitation are discussed briefly in section 2.2.3. In section 2.2.4
and section 2.2.5 the operating characteristics of a DC machine as a motor and
generator are examined. The operation with only the separate field excitation is
discussed.
2.2.1 Basic Relations
Each conductor in the armature generates an emf e = Blu, where B is the flux
density; l is the length of conductor and u is the velocity of the conductor. The
total emf is determined by the number of conductors in series at any time. In the
steady state, the total emf generated is given by
𝐸𝑎 = 𝐾𝜑𝛺 (2.1)
where ϕ is the air gap flux per pole in webers, Ω is the angular velocity in
radians/second, and K is a constant for a given machine. The value of K is given
by
𝐾 = 𝑍⋅𝑃
2𝛱⋅𝑎 (2.2)
where
Z = Number of conductors in the armature winding.
P = Number of poles (an even number).
a = Number of parallel paths in the armature winding.
The torque developed in any conductor can be calculated from Td = Blir where i
is the current carried by the conductor and r is the radius of armature.
The total torque is the summation of the individual contributions. The steady state
torque is given by
𝑇𝑑 = 𝐾𝜑𝐼𝑎 (2.3)
where Ia is the armature current in amperes; K and ϕ have the same meaning as in
Eq. (2.1).
Eq. (2.1) and Eq. (2.3) are the basic relations of a DC machine. They apply at the
air gap; the terminal voltage differs from the emf by the armature resistance drop
and the shaft torque differs from the developed torque by the mechanical
resistance torque.
A DC machine is a bilateral energy converter so that at the air gap the developed
mechanical power is just equal to the generated electrical power or
𝑇𝑑𝛺 = 𝐸𝑎𝐼𝑎 (2.4)
The air gap power represents only the reversible portion of the electromechanical
energy conversion. It must be noted that in practical machines, all losses
occurring are irreversible forms of energy.
2.2.2 Magnetization Curve
In a DC machine, the relation between generated emf and field current is defined
by a magnetization curve (or open circuit characteristic)(Fig. 2.2). Eq. (2.1) shows
that Ea is proportional to ϕ. Also the field current IF is proportional to the mmf F.
This is similar to the ϕ-F curve for a magnetic circuit with an air gap. Running the
DC machine at a constant rated speed and measuring the no-load voltage for
different values of field currents gives the magnetization curve. A small emf is
generated when there is no field current and this is due to the residual magnetism.
The magnetization curve is almost linear over a wide range. However, at higher
values of IF, saturation of the iron core occurs and hence the curve deviates from
linearity above certain values of IF.
2.2.3 Field Excitation
The magnetic field of the DC machine is normally supplied by means of a set of
coils placed on each pole piece and collectively called as the field winding,
although there are examples of DC machines where the field is produced by a set
of permanent magnets. Depending on the arrangement of supplying current to the
field winding, the DC machine can be classified into one of four major categories:
1. separately excited
2. shunt excited
3. series excited
4. compound excited
The conventional symbols and connection diagrams for the above types of
excitation are shown in Fig. 2.3. In the case of a separately-excited DC machine,
the field winding is supplied by an independent DC supply through a rheostat.
The separately-excited machine has well-defined operating characteristics and is
easy to control. For a shunt machine, the field winding is connected directly
across the armature. The operating characteristics of shunt machines are very
similar to those of separately-excited machines. In both cases, the field winding
consists of many turns of fine wire, as the field current is a few percent of the
armature current. These two modes of field excitation are the most commonly
used.
A field winding for a series connected machine consists of a few turns of heavy
wire since it carries the entire armature current. This is essential in order to
minimize the losses. Series connected generators are unsatisfactory for most
applications and series motors are mainly used in transportation systems, such as
street cars and subway systems.
In a compound machine, all field poles have both shunt and series windings.
Depending on the type of connection used, the total mmf is either the sum or
difference of ampere turns produced by the two windings.
2.2.4 DC Generators
A DC machine acts as a generator when driven by a prime mover (external
rotating device). The field of the dc generator can be excited by one of the
methods suggested in section 2.2.3. The circuit models and the characteristics of
dc generators with different field excitation are presented below.
Separate Excitation
Since the field current is independent of the terminal voltage of the armature, in
an ideal machine, changes in armature current have no effect on the field current.
Both the armature winding and field winding have inductances and winding
resistances. Under steady-state conditions only the resistances are to be taken into
account. Hence the circuit model for a separately excited generator is shown in
Fig. 2.4. The terminal voltage is given by,
𝑉𝑡 = 𝐸𝑎 − 𝑅𝑎𝐼𝑎 (2.5)
In practice Vt will be further reduced due to reduction in Ea with increases in Ia
and this effect is referred to as armature reaction. A plot of terminal voltage
versus load current (Ia) is the external characteristic of the DC generator (Fig.
2.5).
Shunt Excitation
This type of excitation is also called self-excitation. In shunt excited DC
generators, the field winding is connected directly across the armature winding
(Fig. 2.6). Any change in armature current will cause a change in the resistive
drop (IaRa). Hence, both the terminal voltage and the field current must also
change and thus the induced voltage (Ea) is dependent on the armature current.
However, the armature terminal voltage is still given by Eq.(2.5), but Ea is no
longer constant as in the case of separate excitation, even when the effect of
armature reaction is neglected.
The armature current I a must supply both load current (IL) and the field current
(IF). Therefore
𝐼𝑎 = 𝐼𝐿 + 𝐼𝐹 (2.6)
As load current is increased, Vt decreases due to an IaRa drop. A further increase
in Ia (i.e. load resistance RL is reduced) results in a condition wherein Ea has
greater effect on the value of the load current than a decrease in the load RL and
consequently IL begins to decrease or the characteristic ‘turns back’. Fig. 2.7
shows the external characteristic of a shunt excited dc generator.
The external characteristic of a shunt excited DC generator can be obtained from
the open-circuit characteristic and the RF -line as shown in Fig. 2.8.
The build-up of voltage in a self-excited generator can be explained referring to
Fig. 2.6. When the generator is rotating, a small voltage exists due to the residual
magnetism. This voltage gives rise to a field current which increases the flux
which in turn increases the voltage, etc. This cumulative process continues until a
stable operating point is reached. No further increase in voltage is possible, except
by lowering the resistance of the field circuit (Note: The minimum value of the
resistance of the field circuit is the winding resistance).
A shunt-excited dc generator cannot build-up if
1. there is no residual magnetism,
2. if the field is connected in a wrong-way around, opposing the permanent
magnetism, and
3. the value of the field resistance is greater than a value called critical
resistance.
Series Excitation
Fig. 2.9 shows the circuit model. The external characteristic (Fig. 2.10) is
obtained directly from the magnetization curve by noting that the armature and
field currents are the same in this case.
Compound Excitation
Using a set of coils (series field and shunt field) in an appropriate connection, the
characteristics of a shunt generator can be modified. Depending on the fields
aiding or opposing, they are respectively called cumulative compound generators
or differential compound generators.
Load Regulation of DC Generators
The load regulation of a dc generator is defined as
𝐿𝑜𝑎𝑑𝑅𝑒𝑔𝑢𝑙𝑎𝑡𝑖𝑜𝑛 = (𝑁𝑜𝐿𝑜𝑎𝑑𝑉𝑜𝑙𝑡𝑎𝑔𝑒)−(𝐹𝑢𝑙𝑙𝐿𝑜𝑎𝑑𝑉𝑜𝑙𝑡𝑎𝑔𝑒)
𝑁𝑜𝐿𝑜𝑎𝑑𝑉𝑜𝑙𝑡𝑎𝑔𝑒
2.2.5 DC Motors
A DC machine operates as a motor when electric power is supplied. In the case of
a dc motor the direction of current, and hence torque, is opposite to that of a
generator. DC motors are classified in the same way as DC generators. The
generated voltage in the case of a motor opposes the flow of current, and is called
back emf. The convention used is that of a passive circuit since electric energy is
absorbed. Only shunt and series motors are explained below.
Shunt Excited
When the same supply voltage is used for both the armature and the field, then the
separately excited case also belongs to this case. The terminal voltage is given by
(Fig. 2.11)
𝑉𝑡 = 𝐸𝑎 + 𝐼𝑎𝑅𝑎 (2.7)
where
Vt = supply voltage and
Ea = armature generated voltage (or back emf )
= KϕΩ.
Therefore
𝛺 = 𝑉𝑡+𝐼𝑎𝑅𝑎
𝐾𝜑rad/sec (2.8)
Since IaRa is usually less than 5% of Vt
𝛺 ≃ 𝑉𝑡
𝐾𝜑rad/sec (2.9)
Equation (2.8) can be written as
𝛺 =𝑉𝑡
𝐾𝜑−
𝐼𝑎𝑅𝑎
𝐾𝜑 (2.10)
𝛺 =𝑉𝑡
𝐾𝜑−
𝑅𝑎𝑇𝑑
(𝐾𝜑)2using eqn. (2.3)
𝛺 = 𝛺𝑛𝑙 − 𝑚𝑇𝑑rad/sec (2.11)
where Ω nl is the no-load speed and
𝑚 =𝑅𝑎
(𝐾𝜑)2 = 𝑐𝑜𝑛𝑠𝑡𝑎𝑛𝑡
Hence, the speed-torque characteristic of a shunt motor is a straight line as shown
in Fig. 2.12.
𝑉𝑡𝐼𝑎 = 𝐸𝑎𝐼𝑎 + (𝐼𝑎)2𝑅𝑎watts (2.12)
where
VtIa = electrical power supplied to the armature, (2.13)
EaIa = gross mechanical power developed by the armature,
some of which is absorbed in friction and core losses,
= Ωtd
From Eq. (2.3), for constant ϕ, Td is proportional to Ia. For a shunt machine, ϕ
is constant, for a constant Vt. Hence the torque varies linearly with armature
current (Fig. 2.13). The net torque is obtained by subtracting the frictional torque.
Also, note that
𝐼𝑎 = 𝑉𝑡−𝐸𝑎
𝑅𝑎 =
1
𝑅𝑎(𝑉𝑡 − 𝐾𝜑𝛺) (2.14)
Therefore
𝑇𝑑 = 𝐾𝜑
𝑅𝑎(𝑉𝑡 − 𝐾𝜑𝛺)Nm (2.15)
If ϕ can be assumed constant, Td varies linearly with speed, and maximum (brake)
torque occurs when Ω = 0 (Fig. 2.14). For E a > V t i.e. in the generating region,
Td reverses its sign. The effect on the characteristics with variations in IF is also
shown in Fig. 2.14.
One most important result from Eq. (2.8) is that if ϕ → 0, Ω → ∞. Hence, the
field of a shunt DC motor must never be open circuited.
Series Excited DC Motor
The terminal voltage is given by
𝑉𝑡 = 𝐸𝑎 + 𝐼𝑎(𝑅𝑎 + 𝑅𝐹) (2.16)
and
𝐼𝐹 = 𝐼𝑎 (2.17)
As was shown earlier on
𝛺 = 𝑉𝑡−𝐼𝑎(𝑅𝑎+𝑅𝐹)
𝐾𝜑rad/sec (2.18)
Since the field winding carries Ia
𝜑 ∝ 𝐼𝑎(assuming linear relation) (2.18)
and therefore
𝛺 ∝ 1
𝐼𝑎 (2.19)
Now, since𝑇𝑑 = 𝐾𝜑𝐼𝑎 (2.20)
𝑇𝑑 ∝ 𝐼𝑎2(using (eqn. 2.19)) (2.21)
However, when IF (= Ia) causes magnetic saturation, it produces a constant ϕ and
Td ∝ Ia.
The characteristics are shown in Fig. 2.15. Neglecting the resistance drop
𝛺 ≃ 𝑉𝑡
𝐾𝜑 (2.22)
Then
𝐼𝑎 = 𝑉𝑡
𝐾𝛺 (2.23)
where ϕ = kIa and K1 = Kk
Therefore
𝑇𝑑 = 𝑉𝑡
2
𝐾1𝛺2
or
𝑇𝑑 ∝ (𝑉𝑡
𝛺)
2
(2.24)
Hence, the torque/speed characteristic is as shown in Fig. 2.16. Note that
speed becomes dangerously high on light load and hence a series dc motor
must never run uncoupled to a load.
Starting and Speed Control
From Eq. (2.14) it can be observed that when normal supply voltage is applied to
a dc motor before the speed builds up, the value of Ia will be limited only by Ra,
resulting in an extremely high current. In order to limit this, starting resistances
are added until the motor picks up speed.
In a DC motor starter, series resistances are added to the armature at the
beginning and as the motor speeds up, resistances are cut in steps. Finally all the
external resistors are shorted.
From Eq. (2.8)
𝛺 = 𝑉𝑡+𝐼𝑎𝑅𝑎
𝐾𝜑rad/sec (2.25)
it can be seen that the speed of a dc motor can be controlled using one of
the following methods:
1. The field flux can be varied to vary the speed, i.e. the value of the field
current IF controls the speed. IF can be varied by supplying the field
voltage separately and controlling this voltage, or by inserting a variable
resistance in series with the field winding.
2. The value of Vt, the supply voltage, can be varied to control the speed.
This value of Vt can be varied by generating Vt, using a separate generator.
This is an old method and the present day method is to use solid state
controllers to vary Vt. A variable supply can be obtained from an ac supply
using phase-controlled converters, or from a dc supply using choppers.
These power electronic converters are very efficient. With such
converters, the power flow can even be reversed. Soft-starting of the
motor is possible by slowly increasing the voltage at the start.
3. Additional resistance in series with the armature. This method is very
inefficient, since the additional resistance carries the full armature current
and, therefore, leads to increased power losses.
Efficiency
The efficiency of a dc motor is defined as
𝜂 = 𝑠ℎ𝑎𝑓𝑡𝑜𝑢𝑡𝑝𝑢𝑡𝑝𝑜𝑤𝑒𝑟
𝑖𝑛𝑝𝑢𝑡𝑝𝑜𝑤𝑒𝑟
Where
Shaft Output Power = TΩ watts
= Input power − losses
The different losses incurred are shown in the power flow diagram of Fig. 2.17.
Loading a DC Motor
In the laboratory, a DC motor is loaded using a dynamometer or a synchronous
generator. A dynamometer is a DC machine with its armature having the
provision for limited angle of rotation and a provision for reading the torque. The
DC motor under test is coupled to a dynamometer (or synchronous generator) and
the armature of dynamometer (or stator of synchronous generator) is loaded using
appropriate resistors. By loading the dynamometer (or synchronous generator)
appropriately, the armature of a dc motor can be made to draw the required
current.
2.2.6 Armature Reaction
Armature reaction is the secondary (undesirable) magnetic field set-up in a DC
machine due to the armature current. In a large DC machine they are nullified in
the polar region by a compensating winding (Fig. 2.18), which is mounted on the
main pole faces and connected in series with the armature.
2.2.7 Commutation Poles or Interpoles
When coils come in contact with brushes, they enter ideally a zero flux region so
that the current in them can change smoothly. This process is called commutation
of a coil. However due to armature reaction, the flux in the interpolar region is not
zero. Hence arcing and sparking takes place during commutation, damaging
brushes and commutator segments. To prevent this, small poles (Figs. 2.18 and
2.19) are placed between the main poles. They are called interpoles or commutation
poles. Since the flux to be zeroed in the interpolar region is proportional to armature
reaction, they are connected in series with the armature.
However, interpoles cannot replace compensating windings and vice versa.
2.3 Apparatus/Instruments
A separately excited DC machine is used as the test object in this experiment.
A synchronous machine is used as a source or a sink of mechanical energy. It is
coupled to the DC machine to be tested. A tachometer is attached to the shaft of
the machine to indicate the rotational speed.
The motor torque can be read on the torque meter mounted on the DC machine.
Devices Required
DC Motor Generator, model 8501 1
Wiring Module DC Motor/Generator, model 8502 1
Synchronous Motor/Generator, model 8507 1
Wiring Module for Synchronous Motor/Generator, model 8508 1
Variable Resistance, model 8509 6
DC Volt-Ammeter, model 8513 1
Field Rheostat Module with built-in 125V, 2A power supply 8524 x 1
Synchronous Motor Starter, model 8520 1
Field Rheostat, model 8524 2
Three-Phase Power Supply, model 8525-10 1
Precision Hand Tachometer, model 8920 1
Electrical Tachometer, model 8930 1
Coupler, model 8943 1
2.4 Preparation
1. Study the relevant parts of your lecture notes, the recommended text and the
laboratory manual section 2.2.
2. Prepare complete connection diagrams for all of the tests called for in the
Procedure using standard electrical symbols and showing clearly all
instrumentation.
3. Inspect the machines on which you will be working with and make sure that
you understand the information on the name plates. (Do this at the beginning
of the lab period).
4. Prepare tables for the measurements specified in the Procedure.
5. Sketch the characteristics you expect to measure for the generator and motor
operation and discuss them.
6. Try to answer the questions provided at the end of section 2.6. Include the final
answers in the report.
2.5 Procedure
2.5.1 Construction of DC Machine
1. Examine the construction of DC machine through the transparent insulation
material, and identify the following:
armature winding, stator poles, commutators shunt-field winding, series-
field winding, brushes, commutating poles or interpoles with winding.
2. While making an observation, answer the following questions:
- How many stator poles are there?
- Approximately how many commutator segments are there?
- How many brushes are there?
- How is the shunt-field winding different from the series-field windings,
and what is the reason for the difference?
- Why are commutator poles or interpoles used?
15
2.5.2 Operation of a Separately Excited Motor
1. Set up the DC machine to be operated as a separately excited motor. Use a
synchronous generator as the load to the DC motor. (Fig. 2.20 shows the
required connection diagram for the synchronous generator).
2. Connect 125 V (2A) DC source available on field rheostat module. Adjust
the field current, by varying the rheostat to If=0.9 A.
3. Provide the armature current of the DC motor from a 0-120 V DC variable
supply. Also connect the commutating poles in series with the armature.
Make sure that the variac reads zero before switching on/off the power
supply.
4. Observe the motor characteristics by taking at least five readings between
no load and 100% of rate torque (rated amature current of 23 A and
maximum torque 11 Nm). Record speed, armature current, armature
voltage and torque. The load to the motor can be varied by changing the
resistors connected across stator terminals of the synchronous generator and
also varying its field rheostat. Before taking any measurement, try to
change the resistors and the field rheostat, and observe how the torque
changes. Do not increase the armature current higher than the rated value.
Take one measurement at rated Ia and calculate the efficiency of the motor.
5. Draw the motor characteristics in the plot of speed vs load torque.
2.5.3 Operation of a Separately-Excited Generator
To achieve this operation, the synchronous machine and the DC machine have to
interchange their functions. The synchronous machine is set up as a motor to drive
the DC generator at a constant speed of 1800 rpm.
1. Set up the synchronous motor as shown in Fig. 2.22. Adjust the field
rheostat for max. Resistance and ensure the field circuit toggle switch is
closed (up position).
2. Provide the field current to the DC generator from 125 V (2A) DC source
available on field rheostat module
3. With the DC machine armature terminals open, turn on the power supply
and start the synchronous motor through a three phase variac. Once the
speed reaches near rated speed after the variac ac output reaches the rated
voltage of the motor, the DC excitation of the synchronous motor is
switched on to lock the motor into synchronism.
4. Increase the DC field current of the synchronous motor by varying the
rheostat until the stator currents are at their minimum.
5. Measure the terminal voltage of the DC generator by DMM and adjust the
field current of the DC generator by varying the supply voltage until the
terminal voltage is the rated 120 V DC.
6. Turn off the power supply.
7. Load the DC generator by connecting a variable resistor (made up of two
variable resistance modules connected in parallel) to the armature terminals
of the DC generator as a load. Arrange instruments to measure the load
current and generator terminal voltage, Vt. Adjust the load resistance to the
maximum. Connect the commutating poles in series with the armature.
8. Turn on the power supply and start the synchronous motor.
9. Take at least six readings with armature current varying between 0 to 90%
of the rated value and record the corresponding terminal voltage. Plot the
external characteristics Vt vs Ia.
2.5.4 Measurement of Steady-State Machine Parameters
1. Measure the resistance of the DC machine shunt field by means of a DMM.
2. The armature resistance, Ra, can be measured as follows:
With the machine at a standstill, lock the rotor and disconnect the field.
Connect a variable resistor (made up of three variable resistance modules
connected in parallel) to the armature and supply 120 V DC to this circuit.
Adjust the resistor to vary the armature current between 0 to 110% of rated
value. Take readings and plot armature voltage vs armature current. Obtain
the brush drop and armature circuit resistance from this graph.
3. Use the Ra measured in the previous step and the name plate data to
determine the constant KØ of the DC generator at the rated condition.
Verify the value of KØ by comparing it to the measurement at no load in
Procedure 2.5.2(5).
2.6 Report
The report should include
1. Objectives
2. Preparations (of all group members)
3. Name-plate data
4. Experimental Results
(a) Answer the questions included in procedure 2.5.1.
(b) The plot of speed-torque characteristics of DC motor (Procedure
2.5.2(5)).
(c) Calculate the efficiency of the separately-excited motor at rated
condition (Procedure 2.5.2(5)).
(d) The plot of external characteristics vt vs ia (Procedure 2.5.3(9)).
(e) Calculate the voltage regulation of the separately excited DC generator
(Procedure 2.5.3(9)).
(f) Draw an equivalent circuit of the DC machine using the parameters
measured in Procedure 2.5.4.
5. Conclusions