jji-joists site guide floor details · 2019-03-22 · 3.35 x 65mm skew nailing or approved clip...

11
System 02 Site storage and restrictions 03 Installation guide 04 Floor details 05 Floor layout 10 Floor details 12 Service holes 15 JJ-Beam and JJ-LVL Beam fixing details 16 JJI-JOISTS SITE GUIDE FLOOR DETAILS FIRST EDITION | APRIL 2019 www.jamesjones.co.uk

Upload: others

Post on 29-Jul-2020

2 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: JJI-JOISTS SITE GUIDE FLOOR DETAILS · 2019-03-22 · 3.35 x 65mm skew nailing or approved clip Minimum bearing 90mm d MASONRY WALL RESTRAINT JJI-JOIST PARALLEL F8 DETAIL 1 Galvanised

System 02Site storage and restrictions 03Installation guide 04Floor details 05Floor layout 10Floor details 12Service holes 15JJ-Beam and JJ-LVL Beam fixing details 16

JJI-JOISTSSITE GUIDEFLOOR DETAILSFIRST EDITION | APRIL 2019

www.jamesjones.co.uk

Page 2: JJI-JOISTS SITE GUIDE FLOOR DETAILS · 2019-03-22 · 3.35 x 65mm skew nailing or approved clip Minimum bearing 90mm d MASONRY WALL RESTRAINT JJI-JOIST PARALLEL F8 DETAIL 1 Galvanised

Protect joists from the elements.Keep them dry

Use supports at about 3.0mspacing to keep joists clean,level and above the ground

Use suitable liftingequipment to o�oadjoist bundles

Transport joists on edge,not �at

Store joists on edge

DO NOT store joists �at

DO NOT lift joists by top �ange DO NOT lift joists on the �at

TIMBER SYSTEMS DIVISION

JJI-Joist site storage

DO NOT hammer on theweb or �ange

DO NOT bevel cut thejoists past the insideface of the wall

DO NOT supportthe joist on the web

DO NOT walk on joists untilproper bracingis in place

DO NOT stack building materialson unbraced joists

DO NOT usenon-approvedhangers

DO NOT over-cutweb holes

DO NOT split the �ange, ensureproper toe nailing

DO NOT cut holes too close to each other – see hole installation guide

DO NOT cut ornotch �anges

Attention! The following conditions are not allowed

JJI-Joist flange sizes

www.jamesjones.co.uk

System

47mm 63mm 72mm 97mm

45mm

A+ B+ C D45mm

JoistDepth

mm

Flange sizes in mmA+47

B+63

C72

D97

195 220 235 245 300 350 400 450

JJI-Joist range JJI-Joists are available in a comprehensive range of sizes, designed specifically for the UK market.

JJI-Joist identification and marking

For onsite identification and traceability, all JJI-Joists are clearly marked with product and manufacturing information. The large markings on the OSB web detail the joist depth, flange size, manufacturing time/date and ETA product approval. Further information printed on the top and bottom timber flanges detail the timber strength class, chain of custody confirmation and a warning ‘DO NOT CUT FLANGES’.

Metalwork

James Jones recommend using Cullen and Simpson Strong-Tie metalwork.

2 3

www.jamesjones.co.uk

Site storage and restrictions

Section Depthmm

Width in mm38 45 90

195 220 235 245 300 350 400 450

JJ-LVL product range

JJ-LVL-Beam and JJ-LVL-Rim is available in depths to suit the JJI-Joist product range and four standard widths depending on the grade. See table below for our standard range.

Intermediate width can be achieved by fixing multiple settings together with suitably specified fixings.

Section Depthmm

Width in mmJJ-LVL-Rim JJ-LVL- Beam

30 39 45 75195 220 235 245 300 350 400

JJ-Beam product range

JJ-Beam is supplied as part of the JJI-Joist system. It is available in depths that match the JJI-Joist product range and three standard widths. See table below for standard range.

Intermediate width can be achieved by fixing multiple settings together with suitably specified fixings.

Page 3: JJI-JOISTS SITE GUIDE FLOOR DETAILS · 2019-03-22 · 3.35 x 65mm skew nailing or approved clip Minimum bearing 90mm d MASONRY WALL RESTRAINT JJI-JOIST PARALLEL F8 DETAIL 1 Galvanised

REMOVE SAFETY BRACING AS DECKING PROCEEDS

22 x 97mm diagonal brace

22 x 97mm continuous longitudinal binders mustbe connected to a diagonally braced and blockedsystem at one end of the joist run

38 x 125mm solid timber stability blocks or I-Joist blocking panels

Decking can be laid in lieu of diagonal bracing

Do not store constructionmaterial close to trimmers

Construction materials shall only be stored in the 1.5m edge zone at one end of the joist only

Nail all binders and braces to eachjoist with 2 no. 3.35 x 65mm nails

Min 675mm cured masonry abovehanger level or as advised byhanger manufacturer

1.5m max

2.4m max

2.4m max

6. Lateral strength should be provided by a diagonally braced and blocked system across at least 3 joists as shown in the Erection Bracing Details (diagram below). Additional braced and blocking systems should be provided at 12m spacing in long joist runs 7. Once a JJI-Joist floor has been fully braced, construction materials may be placed on the floor provided that the overall weight of material to be placed on a single joist does not exceed 250kg (200kg for 195mm deep joists). Please refer to Technical Bulletin 47, ‘Loading out JJI-Joist Floors’8. Flooring should be fully fixed to the JJI-Joists before additional loads are placed on the floor9. The ends of cantilevers should be stabilised with longitudinal binders fixed to the top and bottom flanges

Stability blocking notes

• Use timber blocks or JJI-Joist blocking pieces• Timber blocks to be minimum 38 x 125mm cut squarely and accurately to maintain joist spacing. Fasten with minimum 2 no. 3.35 x 65mm nails• Stability blocks need to be fixed to 3 joists and cover a minimum distance of 1200m• Timber blocks in the diagonally braced systems are required in each run of joists and at cantilever supports• When joists butt on an interior support, block both sets of joists• Additional braced and blocked systems should be provided at 12m spacing in long joist runs

Installation guidelines

This diagram indicates temporary erection bracing only. It is applicable to both timber frame and masonry construction.

Temporary erection bracing notes

The builder is responsible for identifying and minimising the risks involved in erecting JJI-Joists to ensure that the health and safety of all workers is maintained. Builders should be aware of the health and safety responsibilities imposed on them by the Construction (Design and Management) Regulations 2015. Proper erection procedures and bracing are vital to the safe construction of JJI-Joists floors. The following notes may assist builders in preparing a safety assessment.

1. Do not allow workers to walk on unbraced joists2. Do not store building materials on unbraced joists3. JJI-Joists should be erected straight and vertical. The

maximum deviation from horizontal should not exceed 10mm and the maximum deviation from the vertical should not exceed 2mm

4. JJI-Joists are unstable until fully braced. Bracing includes: longitudinal binders, diagonal bracing, stability blocking, rim joist/rim boards5. All longitudinal binders, diagonal braces, stability blocks, and hangers should be completely installed and fully nailed as detailed

CONTINUOUS JJI-JOIST ON WALLF1

Minimum 89mm bearing length

Any type of load bearing support

Continuous Joist

Web stiffeners may be required, see F22

SPLIT JJI-JOIST ON WALLF2

3mm gap at top of splice block

18 x 200mm plywood splice block one side only, fix with 6 no. 3.35 x 65mm nails clenched over

Minimum joist bearing 45mm

Any type of load bearing support

Either blockwork or JJI-Joist blocking is required

Where split joist(s) of different widths meet on the wall a double row of blocking is required to suit joist widths

Example of JJI-Joist floor system

When cantilever situations exist refer to specific details provided by the JJI-Joist distributor

See notes and details for temporary erection bracing and procedure

Glulam/LVL

For any construction situation not addressed by the following floor details, please contact the JJI-Joist distributor

Masonry

General

F4

F15

F2

F1

F3

F9

F7

F10

F13

F11

F5

F23

F12

F14

Timber Frame

www.jamesjones.co.uk www.jamesjones.co.uk

4 5Installation guide Floor details

The full library of construction details can be found in the JJI-Joist Technical Manual.

Scan QR Code

Page 4: JJI-JOISTS SITE GUIDE FLOOR DETAILS · 2019-03-22 · 3.35 x 65mm skew nailing or approved clip Minimum bearing 90mm d MASONRY WALL RESTRAINT JJI-JOIST PARALLEL F8 DETAIL 1 Galvanised

RESTRAINT STRAPS ARE THE RESPONSIBILITY OF THE BUILDING DESIGNER

WALL AT 90˚ TO JJI-JOISTSF3

Partition wall

Floor decking

Wall sole plate nailed to each joist

The floor designer is responsible for ensuring the joist design is adequate to support the wall

NON-LOAD BEARING WALL PARALLEL TO JJI-JOISTSF4

Wall sole plate nailed to each nogging/dwang

Non-load bearing wall maximum self weight 0.8kN/m

Nogging/dwang

Floor decking

38 x 75mm nogging/dwang or JJI-C flange at maximum 600 c/c attached with 2 no. 3.35 x 65mm nails skew nailed at each end, alternatively use approved clipsThe floor designer is responsible for ensuring the joist design is adequate to support the wall

INTERMEDIATE BEARING WITH LOAD BEARING WALL ABOVEF5

JJI-Joist or Glulam/LVL blocking

Load bearing wall aligned under wall above

TERMINATING JJI-JOIST ON WALLF6

Either blockwork or JJI-Joist blocking is required

Minimum bearing 45mm

Any type of load bearing support

Suitable detailing required if used on an external wall

JJI-JOIST BEARING IN BLOCK WALLF7

Construct blockwork around joist and fill all voids with web fillers, mortar and point with mastic sealantAlternative proprietary systems my be used if approved by JJ&SRestraint straps will be required for greater than 2 storeys**Straps required on all floors

Nogging/dwang (min 38 x 45mm) securely fixed with 3.35 x 65mm skew nailing or approved clip

Minimum bearing 90mm

d

MASONRY WALL RESTRAINT JJI-JOIST PARALLEL DETAIL 1F8

Galvanised restraint strap at maximum 2.0m centres, over a minimum of 3 joists Blocking between

JJI-Joist and wall

Nogging/dwang (can be vertically aligned full depth JJI-Joist blocking) securely fixed with 3.35 x 65mm skew nailing or approved clip

Refer to approved connector manufacturer’s guidelines for installation instructions

Block wall

Refer to strap supplier for width requirement

RESTRAINT STRAPS ARE THE RESPONSIBILITY OF THE BUILDING DESIGNER

d

MASONRY WALL RESTRAINT JJI-JOIST PARALLEL DETAIL 2F9

Do not notch the JJI-Joist flange under any circumstances

5 x 30mm galvanised restraint strap at maximum 2.0m centres over a minimum of 3 joists

Strap through slot in web at level to suit block course

Min 0.5d

Block wall

Blocking between JJI-Joist and wall

WALL RESTRAINT, BLOCK WALL HANGER SUPPORTF10

Web fillers may be required. Refer to joist design and/or approved connector manufacturer’s guidelines

External masonry wall requires restraint

675mm of cured masonry before hanger loaded, see approved connector manufacturer’s H&S guidelines

Twisted offset restraint strap fixed to side of joist and built into masonry bed joint at appropriate centres

Nogging/dwang (min 38 x 45mm or JJI-Joist blocking) securely fixed with 3.35 x 65mm skew nailing or approved clip

JJI-JOIST BEARING ON EXTERNAL WALLF12

Additional blocking may be required to Engineer’s specification, to improve sound, structural performance and fixing

Only applicable where a maximum of one storey is built above

JJI-Joist

JJI-JOIST BEARING ON EXTERNAL WALLF11

Additional blocking may be required to Engineer’s specification, to improve sound, structural performance and fixing

Glulam/LVL

JJI-JOIST PARALLEL TO EXTERNAL WALLF13

JJI-Joist

Only applicable where a maximum of one storey is built above

SINGLE JJI-JOIST TO JJI-JOISTF14

Approved face or top fix hanger secured through specified nail holes (refer to approved connector manufacturer’s guidelines)

Ensure the minimum nails fixed through hanger into incoming joist

Backer block fixed to BOTH SIDES of principle joist. Refer to detail F21

www.jamesjones.co.uk www.jamesjones.co.uk

6 7Floor details Floor details

Page 5: JJI-JOISTS SITE GUIDE FLOOR DETAILS · 2019-03-22 · 3.35 x 65mm skew nailing or approved clip Minimum bearing 90mm d MASONRY WALL RESTRAINT JJI-JOIST PARALLEL F8 DETAIL 1 Galvanised

SINGLE JJI-JOIST TO MULTIPLE JJI-JOISTF15

Approved face or top fix hanger secured through specified nail holes (refer to approved connector manufacturer’s guidelines)

Ensure the minimum 4 no. nails fixed through hanger into incoming joist

Backer block fixed to loaded side of principle joist. Refer to detail F21

Filler block fixed as detail F19

SINGLE JJI-JOIST TO JJI-JOIST (LIGHT LOAD)F16

Approved metalwork secured through all nail holes (refer to approved connector manufacturer’s guidelines)

MULTIPLE JJI-JOIST TO MULTIPLE JJI-JOISTF17

Backer block fixed to loaded side of principle joist. Refer to detail F21

Filler block fixed as detail F19

Ensure the minimum 4 no. nails fixed through hanger into incoming joist Approved face or top fix

hanger secured through specified nail holes (refer to approved connector manufacturer’s guidelines)

JJI-JOIST TO ENGINEERED TIMBERF18

Glulam/LVL or engineered timber

Approved face or top fix hanger secured through specified nail holes (refer to approved connector manufacturer’s guidelines)

Ensure the minimum 4 no. nails fixed through hanger into incoming joist

FILLER BLOCK – DOUBLE OR TREBLE JJI-JOISTF19

Provide filler blocks at all ends and bearings of joist and at points of incoming loads (see F15). Alternatively provide continuous filler block when repeated loads are applied (see detail F40)

See F21 for filler block nailing information

(Treble ‘D’ Not Allowed)

Nail clenched over

Example

Step 1 Double

Step 2 Treble

Filler and backer blocks should be kiln dried timber, structural grade plywood or OSB/3

JJI-JoistDepth(mm)

Filler and backer block depth (mm)

195 100

220 125

235 145

245 150

300 200

350 125+125

400 150+150

450 200+150

JJI-Joist Flange Type

Backer block/web

thickness (mm)

Filler block thickness (mm)

A+ 19 38

B+ 27 54

C 32 63

D 44 2x44

FILLER AND BACKER BLOCK TABLEF20

Refer to details provided by the JJI-Joist supplier for required locations of filler and backer blocksWhere a continuous filler block is used (see detail F40)

40

40

25

25

25

25

60

60

FILLER AND BACKER BLOCK NAILING DETAILF21

All filler and backer blocks for face fix hangers to be fixed tight to bottom flange with a minimum 3mm gap at the topBacker blocks for top fix hangers to be fixed tight to the top flange with a minimum 3mm gap at the bottom

Denotes nails from rear face Denotes nails from front face

FlangeSpec

BackerBlock

FillerBlock

A+ 65 65

B+ 65 90

C 90 90

D 90 90

Minimum nail diameter 3.1mm

For A, B and C flange size

For D Flange size only

L=300mm to 600mm

L=350mm to 600mm

WEB STIFFENERF22

19 thick for JJI A+ -65mm nails27 thick for JJI B+ -65mm nails31 thick for JJI C -65mm nails44 thick for JJI D -90mm nails

Web stiffeners are required where indicated on drawings provided by the JJI-Joist supplier

Fixed with 6 no. 3.35mm diameter nails length as noted above

100mm wide plywood, OSB/3 or kiln dried timber stiffener block fitted to both sides

3mm gap (min)

CANTILEVERF24

Back span of cantilever must be at least 3 times the cantilever length1.2m maximum cantilever length

Cantilever closer required

Full depth JJI-Joist blocking pieces required between joists

Any type of load bearing support

LOAD BEARING WALL PARALLEL TO JJI-JOIST RUNF27

Load bearing or shear wall parallel to joist span

Fix sole plate of wall to joist at centres specified by building designer

Add JJI-Joist or Glulam/LVL parallel with joist run under load bearing wall

NEWEL POST TO JJI-JOIST TRIMMERF28Backer block fixed to loaded side of principal JJI-Joist. Refer to detail F21

Filler block fixed as detail F19

Cut and recess newel to fit over trimmer to staircase manufacturer's details

JJI-JOIST TO STEEL BEAM FACE FIXINGF29

Continuous timber packing fixed to building designer’s detail

Beam top level

Beam soffit level

Ensure the minimum 4 no. nails fixed through hanger into incoming joist

Approved face fixed hangers fixed through all nail holesRefer to approved metalwork supplier’s literature for further information

www.jamesjones.co.uk www.jamesjones.co.uk

8 9Floor details Floor details

Page 6: JJI-JOISTS SITE GUIDE FLOOR DETAILS · 2019-03-22 · 3.35 x 65mm skew nailing or approved clip Minimum bearing 90mm d MASONRY WALL RESTRAINT JJI-JOIST PARALLEL F8 DETAIL 1 Galvanised

Client James Jones HomesAddress 123 Andover RoadSite 345 Winchester StreetJAMES JONES & SONS LTD GRESHOP INDUSTRIAL ESTATE, FORRES - IV36 2GW

House Type. SALISBURY - FIRST FLOORDesigner. MT 3.31.091 U13 September 2018 16:44:32Revision A

Copyright ? James Jones & Sons Ltd. (1999-2017) FloorMaster Version 3.31.091 on Friday 14th September 2018 15:25:05 File:C:\James Jones V3.31.091\Test Jobs\Ockwells

Joist RequirementsMark Type Size Span Ply Weight(kg) Qty MakeupJ1 JJI220A+-24 47x220 1150 1 3.10 1J2 JJI220A+-24 47x220 3274 1 8.84 4J3 JJI220A+-24 47x220 4500 1 12.15 12B1 JJ-Beam 76x220 2674 1 21.91 1 (2@38mm)B2 JJI220B+-24 63x220 4500 2 30.15 2 Metalwork RequirementsMark Type QtyA UH-50-220-(i) 5B UH-78-220-(ii) 2

PFS 1500/100 4Cullen I-220-46 8Cullen HV-GR 220-1 29Cullen HV-GR 220-2 8UZ-38 28

UH/HUH hangers found in more than one configuration.Please refer to the graphical details for illustrationsof installation.

Extra Timber RequirementsType Material Size Len QtyPerimeter Nogging CLS 38x50 9333 1Partition Nogging CLS 38x90 5942 1Strap Nogging CLS 38x125 5600 1 Decking RequirementsDescription Size Qty22mm Egger PCX 600x2400 28D4 Glue (1L) 6

Construction NotesIf in doubt ASK.

Do not scale this drawing.

Designed in accordance with BS 5268: Part2.

Plasterboard specification as per manufacturer's guidelines.

A water cylinder/thermal store load provision of 150kg has been allowed unlessnoted otherwise.

JJI-Joists at 400mm centres unless noted otherwise.

Loading: 0.500kN/m2 Dead Load, 1.500kN/m2 Imposed Load.

JJI-Joists maximum deflection limit = Floors: span x 0.003 or 12mm

This layout is for an Intermediate Floor.

Multiple JJ-Beam members fixed in accordance with manufacturer's guidelines.

Restraint Straps are the responsibility of the Building Designer.

Any CO2e figures reported in this layout apply to the JJI-Joists only. Noaccount has been made for any other products.

Scale 1:40

7800

1210

SOP

4500

1050

2450

1500

9731

340

040

060

060

060

060

040

040

040

040

040

040

040

040

040

029

397

SVP...O

1

4 *

J2

9 *

J33

* J3

B2

B2

B1

J1

A

A

B

B

A

A

A

F4

F10

F16

F41F42

F48

F53

Floor layoutJoist scheme showing JJI/Glulam/LVL joist layout; Joist ID marks, hanger marks, masonry restraint strap locations, noggin requirements, building dimensions

Job/Layout detailsFloor layout details including; house type, design revision, design date, site address, layout scale

NotesFloor layout design notes including; joist spacing, design code and loadings, restraint strap responsibilities

Safety hatch systemSystem component description, codes and dimensions (optional)

Carbon captureDetails the amount of carbon dioxide (CO2) captured within the JJI-Joists in the floor layout (optional)

BOQComplete breakdown of floor layout materials showing quantities, weights, ID marks, material descriptions

MetalworkSpecific metalwork images of the hangers and associated ironmongery used within the floor layout

Fixing detailsExamples of how to connect JJI-Joists, Glulam, LVL, blocking pieces, restraint straps etc

www.jamesjones.co.uk www.jamesjones.co.uk

10 11Floor layout Floor layout

Page 7: JJI-JOISTS SITE GUIDE FLOOR DETAILS · 2019-03-22 · 3.35 x 65mm skew nailing or approved clip Minimum bearing 90mm d MASONRY WALL RESTRAINT JJI-JOIST PARALLEL F8 DETAIL 1 Galvanised

RESTRAINT STRAPS ARE THE RESPONSIBILITY OF THE BUILDING DESIGNER

JJI-JOIST TO STEEL BEAM/MASONRYF30

675mm of cured masonry before hanger loaded, see approved connector manufacturer’s H&S guidelines

Brick course may be required where steel is shallower than incoming joistApproved

masonry hanger built into bed jointDo not fix joist to steel lintels unless approved by lintel manufacturerBottom of hanger must rest against bottom flange of steel beamRefer to approved metalwork supplier’s literature for further information

JJI-JOIST TO STEEL BEAM TOP FIXINGF31Timber packing fixed to building designer’s detail

Timber packing piece fitted 3mm proud of inside face of steel flange

Approved top fix hanger secured through specified nail holes

Bottom of flange must rest against bottom flange of steel beamDo not fix joist to steel lintels unless approved by lintel manufacturerRefer to approved metalwork supplier’s literature for further information

x

JJI-JOIST BEARING ON PARTY WALLF32

Minimum thickness of Glulam/LVL rimboard to be dictated by fire requirements

Dimension X not to exceed half the member width

Timber/Plywood/Rockwool void fillers x

JJI-JOIST PARALLEL TO PARTY WALLF33

Overall minimum thickness of solid rimboard and blocking to be 76mm

Dimension X not to exceed half the member width

INDICATIVE DISPROPORTIONATE COLLAPSE JJI-JOIST PARALLEL TO WALLF35

Specification to Engineer’s detail

x

JJI-JOIST PARALLEL TO EXTERNAL WALLF36

Additional blocking may be required to provide adequate structural performance, to engineer’s detail

Dimension X not to exceed half the flange width

Glulam/LVL

INDICATIVE DISPROPORTIONATE COLLAPSE JJI-JOISTS AT 90˚ TO WALLF34

Specification to Engineer’s detail

Glulam/LVL

F39 ENHANCED HANGER UPLIFT

Approved face or top fix hanger secured through specified nail holes

JJI-Joist or engineered timber

Where JJI-Joists are used web fillers are required (see F22)

All triangular optional nail holes filled to provide enhanced uplift value (see hanger manufacturer’s literature for further information)

CONTINUOUS FILLER BLOCKSF40

= nails from rear face= nails from front face

300 300

300300

A continuous filler block should be utilised with multiple incoming loadsA continuous backer block could also be providedWhere continuous filler block is used, fix with 2 rows of nails at 300mm centres from both faces

BACKER FREE JJI-JOIST TO JJI-JOISTF41

Ensure minimum 4 no. nails fixed through hanger into incoming joist

Approved backer free hanger secured through specified nail holesRefer to approved connector manufacturer’s guidelines

FIXING DOUBLE OR TREBLE JJI-JOISTSF42

Refer to approved metalwork supplier’s technical literature for specification and installation guidelines

MASONRY RESTRAINT HANGER DETAIL 1F45

Nogging/dwang (min 38 x 45mm) securely fixed with 3.35 x 65mm skew nailing or approved clip

Refer to approved metalwork supplier’s technical literature for specification and installation guidelines

RESTRAINT STRAPS ARE THE RESPONSIBILITY OF THE BUILDING DESIGNER

www.jamesjones.co.uk www.jamesjones.co.uk

12 13Floor details Floor details

Page 8: JJI-JOISTS SITE GUIDE FLOOR DETAILS · 2019-03-22 · 3.35 x 65mm skew nailing or approved clip Minimum bearing 90mm d MASONRY WALL RESTRAINT JJI-JOIST PARALLEL F8 DETAIL 1 Galvanised

SST END CAP AIRTIGHTNESS DETAIL F47

ITW GRIPPER AIRTIGHTNESS DETAIL F48

Nogging/dwang (min 38 x 45mm) securely fixed with 3.35 x 65mm skew nailing or approved clip

Refer to ITW’s technical literature for specification and installation guidelines

JJI-JOIST BEARING ON EXTERNAL WALL LOW LOADF49

18mm external grade structural plywood

JJI-Joist, Glulam/LVL blocking offcuts

Web of blocking material must be fully supported

Alternatively use Glulam/LVL blocking in lieu of JJI-JoistsJJI-Joist blocking offcuts can be of any joist width

Maximum 610mm

Minimum 3.1 x 90mm nails

38 approx

JJI-JOIST PARALLEL TO EXTERNAL WALL LOW LOADF50

JJI-Joist, Glulam/LVL blocking offcuts

Web of blocking material must be fully supported

38 approx

Minimum 3.1 x 90mm nails

JJI-JOIST PARALLEL DETAIL – SPROCKETSF51

Glulam/LVL or other engineered timber

JJI-Joist blocking sprockets

18mm external grade structural plywood

MASONRY RESTRAINT HANGER DETAIL 2F46Nogging/dwang (min 38 x 45mm) securely fixed with 3.35 x 65mm skew nailing or approved clip

Refer to Simpson Strong-Tie’s technical literature for specification and installation guidelines

Nogging/dwang (min 38 x 45mm) securely fixed with 3.35 x 65mm skew nailing or approved clip

Refer to Simpson Strong-Tie’s technical literature for specification and installation guidelines

LSee hole charts

LSee hole charts

2 x D b

D D1 D 2 D3mm

3mm

Hole spacing2 x larger of

D1 or D2 Span

Hole spacing2 x larger of

b or D2

Link to Technical Manual

Alternative solutions - reinforcing plates

For holes outside this guidance please contact your distributor

The table below gives the minimum required distance , L (mm), from inside face of support to nearest edge of hole for uniformly loaded, simply supported joists. See table notes.

For Glulam and LVL holes contact your distributor

RESTRAINT STRAPS ARE THE RESPONSIBILITY OF THE BUILDING DESIGNER

www.jamesjones.co.uk

Joist Depth(mm)

Joist Span(mm)

Hole Size (mm)

50 75 100 125 150 175 200 + + + + + + +

220 3000 300 300 361 656 721 838 838 11593500 300 300 500 824 895 1024 1024 13754000 300 300 651 1001 1078 1216 1216 15964500 300 449 813 1186 1268 1415 1415 18194890 300 566 945 1334 1420 1574 1574 1996

235 3000 300 300 300 566 656 873 873 12173500 300 300 325 725 824 1062 1062 14404000 300 300 463 894 1000 1258 1258 16654500 300 300 612 1072 1185 1460 1460 18935066 300 382 794 1282 1402 1693 1693 2154

245 3000 300 300 300 482 586 865 865 1252 955 12523500 300 300 300 632 747 1053 1053 1478 1152 14784000 300 300 300 794 918 1248 1248 1706 1355 17064500 300 300 457 965 1097 1449 1449 1937 1563 19375184 300 300 666 1212 1353 1731 1731 2256 1854 2256

300 4000 300 300 300 300 300 803 803 1308 1230 1542 1477 1883 1572 18834500 300 300 300 300 300 975 975 1513 1430 1762 1693 2126 1795 21265000 300 300 300 300 449 1154 1154 1722 1635 1985 1912 2369 2019 23695500 300 300 300 535 670 1341 1341 1935 1844 2210 2135 2613 2247 26135803 300 300 300 687 822 1456 1456 2066 1972 2348 2271 2761 2385 2761

1. This table has been calculated for joists in intermediate domestic floors (Gk=0.75kN/m2,qk=1.5kN/m2,Qk=2kN) at 600mm centres2. Where more than one hole is to be cut, the minimum spacing between holes must be 2 times the width of the largest hole3. The rectangular hole width b should not exceed 1.5 x D4. Cut all holes carefully, do not overcut and do not cut flanges5. Where holes are required in rim and header joists of timber frame construction refer to the building designer

6. Plastic plumbing is ideal with JJI-Joists. Where copper plumbing is to be used, careful consideration of the sequence of pipe installation is required

7. The bearing support length used for this table is 45mm8. A 35mm hole may be drilled anywhere on the centre line

of the web material provided there is a minimum of 35mm from the edge of the hole to the end of the joist and it is not directly over a support

www.jamesjones.co.uk

14 15Floor details Service holes

Page 9: JJI-JOISTS SITE GUIDE FLOOR DETAILS · 2019-03-22 · 3.35 x 65mm skew nailing or approved clip Minimum bearing 90mm d MASONRY WALL RESTRAINT JJI-JOIST PARALLEL F8 DETAIL 1 Galvanised

Fixing Detail A - 2 ply JJ-Beam/JJ-LVL Beam - 2 rows of 3.1 x 75mm nails @300mm centres

Notes 1.

Capacities for nail details are based on 3.1mm diameter power driven nails (75mm long for 38/39mm thick plies and 90mm long for 45mm plies), hammer driven nails up to 4.5mm diameter may be used

2.

Fixing details can be advised by Distributor or noted on layout drawing

Nails in two ply members to be �xed in two rows 45mm in from the top and bottom edge, driven from alternate sides. The minimum end distance should be 90mm.

A

90

45

A Section A-A 300 300 300

= Fixings from front face = Fixings from rear face

Fixing Detail B - 3 ply JJ-Beam/JJ-LVL Beam - 3 rows of 3.1 x 75mm nails @300mm centres

Notes 1.

Capacities for nail details are based on 3.1mm diameter power driven nails (75mm long for 38/39mm thick plies and 90mm long for 45mm plies), hammer driven nails up to 4.5mm diameter may be used

2.

Fixing details can be advised by Distributor or noted on layout drawing

Nails in three ply members to be �xed in two rows 45mm in from the top and bottom edge and one row along the centre line driven through each outer ply into the central one. Note that nails from any one face should be at the speci�ed centres with the nails from the opposite face o�set by half the centres distance.

45

45

90 300300 300

300 300 150 300 B

B Section B-B

= Fixings from front face = Fixings from rear face

The minimum end distance should be 90mm

65

65

300 48 300

C

C Multiply Glulam

Fixing Detail E - Multiply JJ-Beam/JJ-LVL Beam - 2 rows of M12 bolts @300 centres

1. 38mm diameter x 3mm thick washers are required under each head and nut on M12 bolts. Bolts to be minimum 4.6 grade

2. Bolt length to be no less than the overall width of beam + 18mm, e.g. a 90mm JJ-Beam would require a 108mm bolt

3. Fixing details can be advised by Distributor or noted on layout drawing

Bolts should be �xed in two rows 65mm in from the top and bottom edge, bolts should be drilled at Ø12mm and bolts tapped into place. The minimum end distance should be 48mm.

Notes

65

65

400 48 400

C

C Multiply Beam

Fixing Detail D - Multiply JJ-Beam/JJ-LVL Beam - 2 rows of M12 bolts @400 centres

1. 38mm diameter x 3mm thick washers are required under each head and nut on M12 bolts. Bolts to be minimum 4.6 grade

2. Bolt length to be no less than the overall width of beam + 18mm, e.g. a 90mm JJ-Beam and JJ-Rim would require a 108mm bolt

3. Fixing details can be advised by Distributor or noted on layout drawing

Bolts should be �xed in two rows 65mm in from the top and bottom edge, Bolts should be drilled at Ø12mm and bolts tapped into place. The minimum end distance should be 48mm.

Notes

65

65

600 48 600

C

C Multiply Beam

Fixing Detail C - Multiply JJ-Beam/JJ-LVL Beam - 2 rows of M12 bolts @600 centres

1. 38mm diameter x 3mm thick washers are required under each head and nut on M12 bolts. Bolts to be minimum 4.6 grade

2. Bolt length to be no less than the overall width of beam + 18mm, e.g. a 90mm JJ-Beam and JJ-Rim would require a108mm bolt

3. Fixing details can be advised by Distributor or noted on layout drawing

Bolts should be �xed in two rows 65mm in from the top and bottom edge, Bolts should be drilled at Ø12mm and bolts tapped into place. The minimum end distance should be 48mm.

Notes 45

45

=

=

9090 9090 9090

= Fixings from front face/hanger location = Fixings from rear face

Fixing Detail F - 3 ply JJ-Beam/JJ-LVL Beam - 3 rows of 3.1 mm nails @90mm spacing

Notes 1. Capacities for nail details are based on 3.1mm diameter power driven nails (75mm long for 38/39mm thick plies and 90mm long for 45mm plies), hammer driven nails up to 4.5mm diameter may be used

2. Fixing details can be advised by Distributor or noted on layout drawing

Nails in three ply members to be �xed in 2 rows 45mm in from the top and bottom edge, and one row along the centre line driven through each outer ply into the central one.

www.jamesjones.co.uk www.jamesjones.co.uk

16 17JJ-Beam/JJ-LVL Beam fixings JJ-Beam/JJ-LVL Beam fixings

Page 10: JJI-JOISTS SITE GUIDE FLOOR DETAILS · 2019-03-22 · 3.35 x 65mm skew nailing or approved clip Minimum bearing 90mm d MASONRY WALL RESTRAINT JJI-JOIST PARALLEL F8 DETAIL 1 Galvanised

65

65

9090

Notes 1. 38mm diameter x 3mm thick washers are required under each head and nut on M12 bolts. Bolts to be minimum 4.6 grade

2. Bolt length to be no less than the overall width of beam + 18mm, e.g. a 90mm JJ-Beam would require a 108mm bolt

3. Fixing details can be advised by Distributor or noted on layout drawing

Fixing Detail G - Multiply JJ-Beam/JJ-LVL Beam - 2 rows of M12 bolts @90mm spacing

Bolts should be �xed in two rows 65mm in from the top and bottom edge, bolts should be drilled at Ø12mm and bolts tapped into place.

Notes

www.jamesjones.co.uk www.jamesjones.co.uk

18 19JJ-Beam/JJ-LVL Beam fixings

For further information on JJI-Joist system design, use and installation please refer to our Technical Manual by clicking the QR code link below.

Page 11: JJI-JOISTS SITE GUIDE FLOOR DETAILS · 2019-03-22 · 3.35 x 65mm skew nailing or approved clip Minimum bearing 90mm d MASONRY WALL RESTRAINT JJI-JOIST PARALLEL F8 DETAIL 1 Galvanised

www.jamesjones.co.uk

Greshop Industrial Estate, Forres, Moray. IV36 2GW. 01309 671111

Norbord (Chipboard deck)01463 792424

PRODUCT SUPPORT

Distributor details

If in doubt, phone your distributor

MetalworkSimpson StrongTie (Metalwork)01827 255600

Cullen ITW (Metalwork) 01592 777570

Egger (Chipboard deck)01434 602191