iso9001:2008 document no: version no.------- date ......iso9001:2008 document no: irs:s:99/2006...

118
ISO9001:2008 Document No: IRS:S:99/2006 Version No.------- Date Effective :------ Document Title: Draft Specification for Data Logger System for Railway S & T Installation Prepared By: SSRE/Signal Checked By : ADE/Signal Issued By: Director/Signal-III Printed: Page 1of 118 SPECIFICATION FOR DATA LOGGER SYSTEM FOR RAILWAY S&T INSTALLATIONS IRS: S: 99/ 2006 October 2012 Pages : 118 Research Designs & Standards Organisation Lucknow – 226 011

Upload: others

Post on 04-Feb-2021

13 views

Category:

Documents


0 download

TRANSCRIPT

  • ISO9001:2008 Document No: IRS:S:99/2006 Version No.------- Date Effective :------

    Document Title: Draft Specification for Data Logger System for Railway S & T Installation

    Prepared By: SSRE/Signal Checked By : ADE/Signal Issued By: Director/Signal-III Printed: Page 1of 118

     

       

    SPECIFICATION  FOR 

    DATA LOGGER SYSTEM  FOR  

    RAILWAY S&T INSTALLATIONS  

       

    IRS: S: 99/ 2006   

                       October 2012 Pages : 118 

      

    Research Designs & Standards Organisation Lucknow – 226 011 

  • ISO9001:2008 Document No: IRS:S:99/2006 Version No.------- Date Effective :------

    Document Title: Draft Specification for Data Logger System for Railway S & T Installation

    Prepared By: SSRE/Signal Checked By : ADE/Signal Issued By: Director/Signal-III Printed: Page 2of 118

     DOCUMENT DATA SHEET  Designation  IRS:S:99/ 2006                             

        Amendment   4 

    Title of Document  Data Logger System for Railway S & T Installations. 

     

       

    Authors:      Shri Alok Katiyar Designation: Director / Signal/ RDSO                          

       

  • ISO9001:2008 Document No: IRS:S:99/2006 Version No.------- Date Effective :------

    Document Title: Draft Specification for Data Logger System for Railway S & T Installation

    Prepared By: SSRE/Signal Checked By : ADE/Signal Issued By: Director/Signal-III Printed: Page 3of 118

    Approved by       Name: Shri Mahesh Mangal Designation: Sr. Executive Director/ Signal,RDSO  

       

    Abstract  This document defines Data Logger System for Railway S & T installation. 

                

       

  • ISO9001:2008 Document No: IRS:S:99/2006 Version No.------- Date Effective :------

    Document Title: Draft Specification for Data Logger System for Railway S & T Installation

    Prepared By: SSRE/Signal Checked By : ADE/Signal Issued By: Director/Signal-III Printed: Page 4of 118

     DOCUMENT CONTROL SHEET    

    ORGANIZATION  FUNCTION  LEVEL  

     Shri M K Mohanty 

     RDSO 

     Member 

     Prepare 

     Shri Pradeep Saxena  RDSO  Member  Prepare 

     Shri Alok Katiyar  RDSO  Member  Prepare 

      Shri Mahesh Mangal  

     RDSO 

     Approver  Approval 

             

  • ISO9001:2008 Document No: IRS:S:99/2006 Version No.------- Date Effective :------

    Document Title: Draft Specification for Data Logger System for Railway S & T Installation

    Prepared By: SSRE/Signal Checked By : ADE/Signal Issued By: Director/Signal-III Printed: Page 5of 118

      AMENDMENTS  

    Version   Chapter/ Annexure  

    Amendment  Effective date  

    IRS: S: 99/ 2001    FIRST ISSUE  August 2001  

    IRS: S: 99/ 2001    Amendment 1  12th February 2002  

    IRS: S: 99/ 2001    Amendment 2  30th  September 2004  

    IRS: S: 99/ 2006  

      Amendment 3  5th April 2006 

    IRS: S: 99/ 2006  

      Amendment 4  ‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐ 

     

  • ISO9001:2008 Document No: IRS:S:99/2006 Version No.------- Date Effective :------

    Document Title: Draft Specification for Data Logger System for Railway S & T Installation

    Prepared By: SSRE/Signal Checked By : ADE/Signal Issued By: Director/Signal-III Printed: Page 6of 118

    Amendment 3 ( Details )  

    Clause  Amendment  status  Remarks 1.   1.2  2  Add  To  clarify  The  scope  of  inspection 

    of Modem & CMU 2.   3.3  3  Modified  Output relay   capable to drive 24V 

    Q‐Series Relay 3.   3.4  3  Modified  Field gear shall not load >2mA  4.   3.7  3  Modified  Forced Cooling to be deleted  5.   3.8  3  Modified  To Print in user friendly mode 6.   3.9  3  Modified  Format  to  include  location name& 

    Channel no. 7.   3.10.1 (vii) & 

    (xvii) 3  Deleted & 

    Subsequent Clause renumbered 

    To delete Three position inputs 

    8.   3.10.2 (iv)  3  Deleted & Subsequent Clause renumbered 

    Covered by Digital Input 

    9.   3.13  3  Add  To include Version control 10.   4.1(vi)  2 & 3  Add  To add modem 11.   4.2.2  3  Modified  RTU Event Capacity Defined  12.   4.2.7.1  1&3  Deleted  To  delete  synchronization  of 

    control office digital clock  13.   4.2.10  3  Modified  Storing  capacity  to  increase  upto 

    10 lac 14.   4.2.12  1&3  Add & Modified To  clarify  input    variation  storing 

    percentage  of analog  15.   4.2.17  3  Modified  Power Supply as per spn 144 16.   4.2.18  3  Modified  To  make  modular  &  Ergonomic 

    design 17.   4.2.19  2 & 3  Add  To include transmission media 18.   4.2.20  2   Add  Common protocol between RTU & 

    DL 19.   4.2.21  3  Add  Capacity  of  one  cabinet  1024 

    Digital & 64 Analog 20.   4.2.22  3  Add  Termination of All  input Like Wago 

    etc 

  • ISO9001:2008 Document No: IRS:S:99/2006 Version No.------- Date Effective :------

    Document Title: Draft Specification for Data Logger System for Railway S & T Installation

    Prepared By: SSRE/Signal Checked By : ADE/Signal Issued By: Director/Signal-III Printed: Page 7of 118

    21.   4.3.1  2 & 3  Modified  Specification  of  PC  for  CMU upgraded  to  state  of  art & Sub clause added 

    22.   4.3.8  3  Modified  FEP must have capacity to store 10 lac telegrams 

    23.   4.3.9  1 & 3  Modified  Details of common protocol 24.   5.5  3  Modified  Transmission rate to increase up to 

    57600 BPS 25.   5.6.1  3  Modified  Sub clause Number given 26.   5.6.2  3  Modified  Sub clause Number given 27.   6.3.1  3  Add  Applied high voltage test added 28.   7.1  3  Add   Sub clause number given 29.   7.2  3  Modified  IR test as per RDSO/SPN/144/2006 

    & Sub clause added 30.   7.3  3  Modified  Environmental  as  per 

    RDSO/SPN/144/2006    &  Sub clause added 

    31.   7.4  3  Add  Applied  high  voltage  test  as  per RDSO/SPN/144/2006 &  Sub clause added 

    32.   10.4  3  Add  Pre‐commissioning  check  list  & DOs and DON’Ts  

    33.   11.1.1  3  Modified  Sub clause given number 34.   11.2   3  Modified  “Additional” ward added 35.   11.4 (c)  2  Delete  Deleted against Cl:4.1.(a) (vi) 36.   11.5 & 

    11.5.1 

    3  Delete  Deleted against Cl:4.2.17 

    37.   Annexure  3  Add  Added as per clause 4.3.9 

  • ISO9001:2008 Document No: IRS:S:99/2006 Version No.------- Date Effective :------

    Document Title: Draft Specification for Data Logger System for Railway S & T Installation

    Prepared By: SSRE/Signal Checked By : ADE/Signal Issued By: Director/Signal-III Printed: Page 8of 118

     Amendment 4 (details) 

    Sn   Clause   Amendment   Status   Remarks  1   3.1  4  Modified   New parameters to be logged are added 

    2   3.4  4  modified  Analog input isolation voltage mentioned. Means of current sensing given 

    3   3.8   4  Modified   Printer connection by blue tooth added 

    4   3.10.1  & 3.10.2 

    4  Deleted   Inputs to be monitored are given in annexure 

    5   3.10.3  4  New   Monitoring  parameters  of  Point,  Track  circuit  and  Signal and their location given in annexure 

    6   4.2.2  4  Modified   Modified requirements of RTUs given 

    7   4.2.3  4  deleted  Covered in modified clause 4.2.2 

    8   4.2.6  4  Modified   Number  of  fault  alarms  to  be  stored  and  displayed  are given 

    9   4.2.8  4  Modified   Isolation voltage and method of isolation clarified  

    10   4.2.10  4  Modified   Requirement of External back‐up memory covered 

    11   4.2.16  4  Modified   List of Equipment to be monitored by data logger expanded 

    12   4.2.17  4  Modified   Crow bar protection for power supply included 

    13   4.2.19  4  Modified   Networking methods expanded  

    14   4.2.22  4  Modified   Feature of the terminals clarified  

    15   4. 3. 2. 1  4  Modified   Configuration of PC used as CMU upgraded 

    16   4.3.2.2   4  Modified   Floppy  replaced  by  DVD.  Methodology  for  monitoring signaling gears more effectively from central location added

    17   4.3.10    New   Data logger user interface software features added 

    18   4.3.11    New   Recommended network with redundancy  

    19   4.3.12    New   Recommended specifications of various network elements  

    20   5.3  4  Modified   Response  time  given  in  terms  of  sec  is modified  as  data speed to be maintained in terms of packets per sec at each stage  

  • ISO9001:2008 Document No: IRS:S:99/2006 Version No.------- Date Effective :------

    Document Title: Draft Specification for Data Logger System for Railway S & T Installation

    Prepared By: SSRE/Signal Checked By : ADE/Signal Issued By: Director/Signal-III Printed: Page 9of 118

    21   5.6.1  & 5.6.2 

    4   Deleted   Exception reports given as annexure  

    22   11.1.1  4  Modified  Requirement  of  Analog/Digital  I/Ps  information  to  be supplied by purchaser is added in annexure. 

    23   11.6   4  New   Requirement of network ports added  in  information  to be supplied by purchaser 

    24   Annexure   4  Deleted   Replaced by Annexure A 

     

     

     

     

     

     

     

     

     

     

     

     

     

     

     

     

          

  • ISO9001:2008 Document No: IRS:S:99/2006 Version No.------- Date Effective :------

    Document Title: Draft Specification for Data Logger System for Railway S & T Installation

    Prepared By: SSRE/Signal Checked By : ADE/Signal Issued By: Director/Signal-III Printed: Page 10of 118

    TABLE OF CONTENTS  

    S. No.  Item  Page No. 1  Foreword  11 2  Scope  12 3  Terminology  12 4  General requirements  12 5  Technical requirements  14 6  Data logger equipment  15 7  Central monitoring unit  20 8  Functional requirements  22 9  Exception report  23 10  Test and requirements  23 11  Test equipment  23 12  Type tests  24 13  Acceptance test  24 14  Routine test  25 15  Test procedure  25 16  Visual inspection  25 17  Insulation resistance test  26 18  Environmental/climatic tests  26 19  Applied high voltage test  26 20  Quality assurance   26 21  Plant & machinery  26 22  Packing  27 23  Information to be supplied by the manufacturer  27 24  Information to be supplied by the purchaser  27 25  Annexure  29‐119   A  29   B  77   C  83   D  90   E  96   F  99   G  103   H  106   I  109 

     

  • ISO9001:2008 Document No: IRS:S:99/2006 Version No.------- Date Effective :------

    Document Title: Draft Specification for Data Logger System for Railway S & T Installation

    Prepared By: SSRE/Signal Checked By : ADE/Signal Issued By: Director/Signal-III Printed: Page 11of 118

     

    GOVERNMENT OF INDIA MINISTRY OF RAILWAYS 

    (RAILWAY BOARD)    

    INDIAN RAILWAYS STANDARD SPECIFICATIONS 

     FOR  

    DATA LOGGER SYSTEM  

    (TENTATIVE)  

    Serial No. S 99/ 2006    0  FOREWORD  0.1    This specification is issued under the fixed serial number followed by the year of 

    adoption as standard or in case of revision, year of latest revision.  0.2    This specification requires reference to the following specifications: ‐    IRS: S23    Electrical signaling and interlocking equipment  

    RDSO/SPN/144  Safety  and  reliability  requirement  of  electronic  signalling equipment 

     IS: 9000  Basic environmental testing procedures for electronic and 

    electrical items    Wherever,  reference  to any  specification appears  in  this document,  it  shall be 

    taken as a reference to the latest version of that specification unless the year of issue of the specification is specifically stated. 

  • ISO9001:2008 Document No: IRS:S:99/2006 Version No.------- Date Effective :------

    Document Title: Draft Specification for Data Logger System for Railway S & T Installation

    Prepared By: SSRE/Signal Checked By : ADE/Signal Issued By: Director/Signal-III Printed: Page 12of 118

     1  SCOPE 1.1  This  specification  covers  the  technical  and  operational  requirements  of  data 

    logger equipment, which is installed to monitor the status of the signaling gears at  stations.  It  also  covers  minimum  configuration  of  central  monitoring  unit (CMU)  

    1.2     Inspection shall be carried out for data logger equipment consisting of RTU, FEP, and CMU software. Standard accessories used external to the data logger like PC for CMU, UPS  for CMU and modem etc.  shall be  checked during  inspection  for their  functional  performance  only  required  for  data  logger  system  as  per specification.  

     2  TERMINOLOGY  2.1 For the purpose of this specification, the terminology given in IRS: S23 and RDSO/ 

    SPN/144 shall apply.  2.2 Input module means an electronic module/  card used  to  read  status of  relays 

    (digital input) and/or level of analog signals.  2.3 Signal Conditioner means an electronic module or card used  to convert analog 

    signals to a suitable level for recording.  2.4 SSI/  Electronic  interlocking  is  a  processor  based  electronic  system  to  control 

    signaling equipment/ functions at any interlocked station.  

    2.5  Integrated power supply  (IPS)  is a composite module delivering various AC and DC voltage for signaling equipment. 

      3  GENERAL REQUIREMENTS  3.1  The system shall chronologically monitor and  record  the status of various  field 

    functions  like  track  circuits,  points,  signals,  operator’s  push  buttons/switches (digital Inputs) and level of various analog signals like DC and AC supply voltages, Axle counter signals, DC track circuit currents, Point machine currents, Signal lamp currents etc. 

      3.2  The equipment  shall also have  the  capability of  statistical analysis, predict  the 

    faults and generate failure reports. It shall be possible for the user to define fault 

  • ISO9001:2008 Document No: IRS:S:99/2006 Version No.------- Date Effective :------

    Document Title: Draft Specification for Data Logger System for Railway S & T Installation

    Prepared By: SSRE/Signal Checked By : ADE/Signal Issued By: Director/Signal-III Printed: Page 13of 118

    logics  taking  digital/analog  inputs  into  consideration  and  generate  reports  for such faults. 

     3.3  The equipment shall be capable of generating audio‐visual alarm under defined 

    conditions.  In  addition,  it  shall  be  able  to  deliver  non‐vital  relay  outputs  on receipt  of  command  from  CMU.  At  least  8  non‐vital  relay  outputs  shall  be provided.  The  non‐vital  relay  output  shall  be  in  the  form  of  potential  free contacts capable of driving 24V  'Q' series relays These outputs may be used for non‐vital functions like radio patching of control circuits etc. 

     3.4  For digital  inputs, potential  free contacts  shall be used. Analog  signals  shall be 

    scaled  to  a  suitable  limit  using  signal  conditioner  before  converting  to  digital signal. Each analog  input  shall be  isolated  (at  least 2KV  isolation voltage)  from the system and one another.   While  tapping analog  input,  it shall not  load  the analog channel/ field gear by more than 2ma. 

                DC & AC analog currents shall be measured with suitable sensors which provide galvanic isolation to the source being monitored. 

    3.5  The system shall be suitable for working on non‐electrified, AC electrified and DC 

    electrified  areas  and  where  passenger/freight  trains  hauled  by  single  phase thyristor controlled or three phase induction motor controlled AC locomotives or chopper controlled EMU stock are operated . 

     3.6  The  system  shall be capable of working  in conjunction with conventional  relay 

    interlocking,  multi‐aspect  color  light  signaling  installations  operated  by  lever frames/ slides & Electronic Interlocking systems. It shall have facility to log data received from Electronic Interlocking through a serial port. 

     3.7 The system (except commercial PC used for CMU) shall be capable of working in 

    an ambient temperature range of  ‐100 C to +700 C   and relative humidity up to 95% at ambient temperature of 400 C. Special protection against ingress of dust, moisture etc. shall be provided. 

     3.8   The  data  logger  shall  be  capable  of  being  connected  to  a  printer  on wireless 

    (blue  tooth)    for  obtaining  a  hard  copy  of  the  function  recorded.  It  shall  be possible to print the  following on the connected printer by selecting  from user friendly menu. 

                (i)  on line events as they are generated.             (ii) to print the exception report 

  • ISO9001:2008 Document No: IRS:S:99/2006 Version No.------- Date Effective :------

    Document Title: Draft Specification for Data Logger System for Railway S & T Installation

    Prepared By: SSRE/Signal Checked By : ADE/Signal Issued By: Director/Signal-III Printed: Page 14of 118

              (iii) to print the status of user specified inputs for user definable time period  

    3.9  The  data  logger  shall  record  various  field  functions  as  indicated  in  para  3.10 below chronologically in the following format with name of the location at top of every page: 

     Date,       time,        channel no.,         field function,         status / value 

     3.10 The status of various functions shall be recorded in the following way: ‐   3.10.1 Digital Input: given in the Annexure-B                                      

    3.10.2  Analog inputs given in the Annexure-B   3.10.3 Parameters to be monitored for Point machine, DC track circuit, Signal lamp and   

    their location are given in Annexure‐G as guidance                 

    3.11 The  system  shall  be  easily  re‐configurable  to  any  changes  required  by  user, whenever modifications are carried out in the yard  

    3.12 Provision for networking and remote monitoring of several data loggers from the central place shall be provided. 

     3.13 Implementation  of  version  control  and  change  of  software  shall  be  as  per 

    RDSO/SPN/144       4  TECHNICAL REQUIREMENTS  4.1  Data logger system consists of:  

    (a) Data  logger  equipment which  is  provided  near  the  signaling  gears  to  be monitored has following modules: 

     (i) Processor module. (ii) Input module (digital/ analog) (iii) Signal conditioning module (iv) Communication module  (v) Printer 80 Col. Dot matrix (Optional) (vi) Modem(s)  

  • ISO9001:2008 Document No: IRS:S:99/2006 Version No.------- Date Effective :------

    Document Title: Draft Specification for Data Logger System for Railway S & T Installation

    Prepared By: SSRE/Signal Checked By : ADE/Signal Issued By: Director/Signal-III Printed: Page 15of 118

     (b) Central monitoring unit (if provided) with communication facility to retrieve 

    data  from data  logger(s) provided at station(s). The central monitoring unit shall run the diagnostic software to generate alarm and exception reports  

     4.2  Data Logger Equipment:  4.2.1  The  equipment  shall  cater  for  minimum  512  digital  inputs  (in  the  form  of 

    potential  free contacts) and 32 analog  inputs.   The system shall be expandable up  to  4096  digital  &  96  analog  inputs  by  expansion/cascading  the  similar equipment.  

     4.2.2  The equipment shall have facility to interface with Remote Terminal Unit (RTU).               RTU shall be able to monitor potential free contacts, analog voltages, analog    

       Currents (AC&DC), receive data packets from equipment like IPS, EI, DAC, BMU     [Battery Monitoring Unit], SSBPAC‐D, FMS [Fuse Monitoring Unit] etc. and change their protocol if required to common protocol. It shall be possible to network RTUs and also RTU to data logger or FEP. Since all the above functionalities are not required for all applications, the RTUs are categorized as follows. Type1: (Used for IBS, LC Gate, Auto signal  etc.) 

    i. Shall monitor digital inputs in the form of potential free contacts with capacities :128/64, Analog voltages(DC/AC):16, Analog currents(AC/DC):4 

    ii. Networking: by leased line modem[2 or 3] or GSM or GPRS or Wireless or dark fiber [Purchaser to provide type of networking and number of connections for networking]  

    iii. Local PC Connectivity : by isolated RS232 serial port iv. Printer connectivity: by blue‐tooth v. Keyboard of 3X4 vi. 7 segment display  vii. Temperature measurement viii. Memory: NonVolatile‐1 lakh events capacity ix. housing: Shall be of 6U and able to be accommodated in a 

    location box   x. Secondary backup memory (Removable): Secondary data backup 

    shall be provided with isolation [of power supply and data] and hot pluggable by the user. It shall be possible to copy data from RTU in to secondary data backup device on request by user. Necessary hardware and software tools shall be available to post 

  • ISO9001:2008 Document No: IRS:S:99/2006 Version No.------- Date Effective :------

    Document Title: Draft Specification for Data Logger System for Railway S & T Installation

    Prepared By: SSRE/Signal Checked By : ADE/Signal Issued By: Director/Signal-III Printed: Page 16of 118

    data from the device into data base through NMDL. Its capacity shall be 10 lakh events 

    xi. Scanning interval shall be similar to data logger  Type II: (Used for Point Machine, Signal, DC Track circuit)  

    i. Shall monitor 16 digital inputs, 8 Analog voltages, 6 Analog Currents 

    ii. Networking: by wireless or isolated asynchronous serial communication (Optional) 

    iii. Additional RS 485 port for connecting additional RTU for augmentation of capacity. 

    iv. Memory:1000 events ‐volatile memory v. Scanning interval: digital and analog voltages same as data 

    logger, currents – one sample per 40 milli sec with averaging the sample values   

    vi. No need for keyboard, LED/LCD display, connectivity of PC/printer and secondary memory  

    vii. Housing: Shall be of 2U height and able to be accommodated in a location box   

     Type III: (Used for IPS, EI, DAC, SSBPAC‐D, BMU, FMS etc. )  

    i. Shall receive data from EI, IPS, DAC, SSBPAC‐D, Battery Monitoring Unit, Fuse Monitoring Unit or any other solid state equipment which gives its diagnostics in packet form through appropriate interface.  

    ii. It shall be the joint responsibility of the original equipment manufacturer of the equipment being monitored, data logger vendor and RDSO to develop appropriate hard ware and software to correctly depict the status of the equipment   

    iii. The packet protocol of the equipment monitored is converted to common protocol where required 

    iv. Shall monitor 16 digital inputs v. Shall have 16 asynchronous isolated serial communication ports vi. Memory 10 lakh events‐ non‐volatile vii. Network connectivity: by wireless or isolated asynchronous 

    serial communication viii. 24 V DC power taken from data logger supply shall be isolated ix. Housing: shall be of 6U size  

  • ISO9001:2008 Document No: IRS:S:99/2006 Version No.------- Date Effective :------

    Document Title: Draft Specification for Data Logger System for Railway S & T Installation

    Prepared By: SSRE/Signal Checked By : ADE/Signal Issued By: Director/Signal-III Printed: Page 17of 118

    NOTE: i. All types of RTUs shall work on 24VDC (+20%,‐30%). While 

    using common supply isolation shall be achieved within the equipment 

    ii. Shall generate packets as per common protocol and shall have their own RTC for time stamping. 

    iii. RTC of RTUs shall synchronize with data logger. iv. Each RTU shall have its own ID. v. Digital and analog inputs being monitored shall be isolated 

    like in data logger vi. Wireless technology used for networking shall support mesh 

    network and frequency shall be in free band  Block diagrams of data logger system with all 3 types of RTUs connected at a station and individual RTUs and Data logger connectivity interfaces are given in Annexure‐F 

         4.2.3  Signal conditioning module shall convert analog signals  like 230 VAC, 110 VAC, 

    110 VDC, 60 VDC, 24 VDC, 12VDC and axle counter RX voltages etc. to suitable level for recording. Normally all AC voltages shall be at commercial frequency of 50 HZ except for Axle counter which is at 5KHZ.  When an analog channel is not connected, it shall not pick up any noise. Provision shall be made to set a channel as not connected. 

     4.2.5 Configuration of analog channels may be as under;   

    Channel  Nominal Voltage DC or AC (RMS) 

    Voltage Range for no alarm (adjustable) 

    1  230 AC  207‐ 253 2  110 AC  99‐ 121 3  110 DC  99‐ 121 4  110 DC  99‐ 121 5  60 DC  55‐ 69 6  48 DC  55‐ 69 7  24 DC  22.5‐28 8  12DC  10 ‐ 14 9‐16  1.0 AC,5KHz  ‐ 

        Or as specified by purchaser.  

  • ISO9001:2008 Document No: IRS:S:99/2006 Version No.------- Date Effective :------

    Document Title: Draft Specification for Data Logger System for Railway S & T Installation

    Prepared By: SSRE/Signal Checked By : ADE/Signal Issued By: Director/Signal-III Printed: Page 18of 118

    4.2.6  Display  shall  be  provided  on  the  front  panel  of  the  data  logger  to  display current  status  /  faults/ alarms along with  time  stamp.  It  shall be possible  to display latest 500 faults/ alarms generated by data logger on the panel. At least two row display shall be used with at least 16 characters in each row. 

     4.2.7  The equipment shall have real time clock for recording time at which the status 

    of the particular  information has changed. The real time clock on data  logger should get synchronized with  the central monitoring unit. The cascaded Data logger(s) shall also synchronize their clocks with the real time clock of master Data logger.  

     4.2.8 Opto‐coupler for each input shall be provided to electrically isolate (at least 4KV 

    Isolation  voltage)  each  external  digital  inputs  (relay  contacts)  from  the equipment.  Self‐diagnostics  shall  be  provided  in  the  system.  Any  fault  in  the system shall generate error message  in the system panel and generate alarm  in the CMU.  The system shall generate the following diagnostic signals and displayed on the CMU in graphical form. Digital card failure Low/high voltage of data logger supply Link failure with sub‐units  like analog unit, EI, DAC, IPS, BMU, FMS or any other electronic equipment connected through serial port. Communication failure between two equipment where modem is provided Internal memory failure   

    4.2.9  The hardware structure of the system shall be modular.  4.2.10  Event  logging  facility  for minimum  10  Lac  events  shall  be  provided  in  a Data 

    logger. Data  shall be  recorded on  first  in –  first out basis  so  that  latest data  is available  in  the  system. There  should be no  loss of data  from  the data  logger memory in case of power supply failure of data logger. 

                  Secondary  data  backup  shall  be  provided with  isolation  [of  power  supply    and data] and hot pluggable by the user. It shall be possible to copy data from data logger  in  to  secondary  data  backup  device  on  request  by  user.  Necessary hardware and software tools shall be available to post data from the device into data base through NMDL. Its capacity shall be 10 lakh events 

     4.2.11  Scanning interval for digital inputs shall be less than 20 milliseconds. Change in 

    status of digital signal shall only be recorded. 

  • ISO9001:2008 Document No: IRS:S:99/2006 Version No.------- Date Effective :------

    Document Title: Draft Specification for Data Logger System for Railway S & T Installation

    Prepared By: SSRE/Signal Checked By : ADE/Signal Issued By: Director/Signal-III Printed: Page 19of 118

     4.2.12  Scanning interval for analog signals like DC or AC supply voltage, temperature, 

    axle counter RX voltage etc. shall be less than 1 second. Variation of more than 5% of the nominal value from the last recorded value, provided it has gone 5% beyond the nominal value, shall be recorded.  

     4.2.13  Accuracy  of measurement  of  analog  signals  shall  be  better  than  1% within 

    ±40% of nominal value.  4.2.14   The equipment shall have facility to receive serial data from external equipment 

    like  Electronic  Interlocking,  Integrated  Power  Supply  etc.  and  record  it with time stamp.  

     4.2.15   The  software  of  the  system  shall  be  of  approved  type  and  written  in  a 

    structured  format  so  that  the  purchaser  can  reconfigure  it,  if  required.The software shall have clear bifurcation between generic software and application software. 

     4.2.16  At  least   12 serial ports shall be provided  for communication with other data 

    loggers, CMU, RTU, EI, IPS, BMU, SSBPAC‐D, FMS etc. which generates packets in common protocol format given in the annexure 

     4.2.17  Power Supply: The  system  shall work on 24V DC  (+20%,  ‐30%). Railways will 

    provide 24VDC input supply. Crowbar protection shall be provided   4.2.18 19” rack mountable and 3/4/6 U high cabinets made of aluminum of minimum 

    thickness 2mm should be used for housing the PCB cards to achieve modular and  ergonomic  design  for  good maintainability  for  data  logger.  The  cabinet should be powder coated. The  front and backsides of the cabinets shall have the facility for locking the equipment.  

     4.2.19 Data Logger shall be capable of working with different transmission media like 

    underground  telecom  cable,  microwave  (Digital  or  Analog)  &  OFC.  The provision of either in‐built modem or external modem is acceptable. The data logger  equipment  will  continuously  check  the  modem  status  and  give  the necessary  reset  as  required  to  eliminate  modem  hanging  condition.  The modem will be housed within the data logger cabinet. The data logger shall be  compatible to the following media: 

       (i) Main telecom cable. 

  • ISO9001:2008 Document No: IRS:S:99/2006 Version No.------- Date Effective :------

    Document Title: Draft Specification for Data Logger System for Railway S & T Installation

    Prepared By: SSRE/Signal Checked By : ADE/Signal Issued By: Director/Signal-III Printed: Page 20of 118

                (ii) Quad cable.             (iii) Analog channel of OFC, digital microwave or analog microwave. 

    (iv) E1 data channel on OFC or digital microwave. (v) Dark fiber (vi) Wireless 2.4 GHz/GSM/GPRS  NOTE: Wireless technology used for networking shall support mesh network     and frequency shall be in free band  

                Where  copper  cable  is  used  for  networking,  protection  arrangements  like connecting  screen  and  armour  to  earth  and  provision  of  1:1  isolation transformer [both in RE and NON‐RE areas] shall be ensured by railways before connecting the cable to data logger or RTU. As far as possible there shall not be intermediate termination of communication cable. Where provided, they shall be  of  screw‐less  type  of  connection.  No  copper  conductor  of  data  logger network shall be taken through conventional  ‘U’  link test panel as they cause loose connection. 

      Where  railway communication network  is not available, networking by GSM, GPRS can be done as given in Annexure‐D  

     4.2.20 Communication  between  data  logger  &  RTU  shall  also  be  as  per 

    communication protocol mentioned in clause 4.3.9.  4.2.21  Cards and terminals required for up to minimum 1024 digital inputs 32 analog 

    inputs, signal conditioning modules etc. shall be accommodated in one rack of 19" width. 

     4.2.22 For  termination  of  external  digital  and  analog  inputs,  international  quality 

    terminals of  screw  less  type  like  that of WAGO/ Phoenix etc. makes  shall be used as per RDSO SPN/144. All wires should be neatly bunched  in horizontal and vertical channels.                                                                         

      4.3  CENTRAL MONITORING UNIT (CMU):  4.3.1  SOFTWARE CONFIGURATION 

     4.3.1.1    The  database management  system  i.e. MS  SQL  server  or  Interbase  shall  be   

    used       to cater for basic function of Data  loggers at CMU  level. Only  licensed software shall be used. 

     4.3.2     HARDWARE CONFIGURATION 

  • ISO9001:2008 Document No: IRS:S:99/2006 Version No.------- Date Effective :------

    Document Title: Draft Specification for Data Logger System for Railway S & T Installation

    Prepared By: SSRE/Signal Checked By : ADE/Signal Issued By: Director/Signal-III Printed: Page 21of 118

     4.3.2.1 Central monitoring  unit  shall  be  state  of  art  PC  (  of  reputed  brand  )  based 

    system  working  on  commercial  supply  of  230VAC,  50Hz.  The  minimum configuration  shall  be  as  specified  by  RDSO  from  time  to  time.  Presently minimum configuration must be as under: 

     i. Core  i7‐860 2.8GHz, 8MB  cache or  latest  ‐ 2 GB Memory  or  as 

    required  for  latest  OS  and  application  software  ‐  500  GB  Hard Drive  ‐        Dual  Gigabit  Ethernet  ports  –  2  USB    Ports  for connecting to FEP or data logger ‐ Keyboard (USB) ‐ Mouse   (USB Optical)  ‐ Windows 8 or  latest OS  ‐ Antivirus  software  ‐ 22” TFT Monitor‐1 No – display adopter to support dual monitors, monitor resolution of 1280x1024 Make: HP/IBM/DELL 

    NOTE:  One 40 inch monitor to be procured for signal monitoring of each section consisting of about 32 data loggers 

    ii. UPS with minimum 6 hours battery backup for central monitoring unit.  

    iii. Software tools.   4.3.2.2   Central  monitoring  unit  shall  have  Graphical  User  Interface  (GUI)  based 

    software  and  retrieve  data  from  all  Networked  data  loggers  (up  to  32)  at various stations.  It shall store data  in standard data base files. The CMU shall also be capable of analyzing the data & generate reports & audio visual alarms on defined conditions. It shall be possible to compress the data and take back‐up on DVD.  Methodology for Centralized Monitoring of alarms is given in Annexure‐H To make monitoring  of  signalling  gears more  affective  from  central  location online status of data loggers in a section displayed in a CMU shall be shown in single screen. In case user selected unusual alarms occur at any of the stations, the  same  shall be displayed  in graphical  form  so  that  the person monitoring the  system  takes  appropriate  action.  Status  of  data  logger  network  i.e.  link breaks,  data  lag  also  shall  be  displayed.  A  typical  screen  is  given  in  the Annexure‐H.   

    4.3.3  Software used for analysis of data, prediction of faults etc. in central monitoring unit  shall  be  of  approved  type  and  written  in  a  structured  format  so  that purchaser can reconfigure it, if required. A copy of software shall be supplied in CD. 

  • ISO9001:2008 Document No: IRS:S:99/2006 Version No.------- Date Effective :------

    Document Title: Draft Specification for Data Logger System for Railway S & T Installation

    Prepared By: SSRE/Signal Checked By : ADE/Signal Issued By: Director/Signal-III Printed: Page 22of 118

     4.3.4  It shall be possible to display the status of signaling gears at any selected time in 

    graphic form for any selected station yard on the central monitoring unit.  4.3.5  It shall be possible to retrieve the stored data & simulate train movement on the 

    central monitoring equipment.   4.3.6 It shall be possible to send commands to various Data loggers to activate audio, 

    visual alarm or operate an electromagnetic relay.   4.3.7 It shall be possible to share data available in CMU by other PCs through available 

    local area network where  this data  can be used  for  train  charting  / passenger information purpose. 

     4.3.8 Front End Processor (FEP) shall be provided to continuously retrieve   data from 

    station data loggers. FEP must have capacity to store 10 lac telegrams.  It should have 6 ports. 

     4.3.9 The communication protocol for transmitting data and command between data 

    logger and CMU is given in Annexure‐A.  4.3.10 Some of the desirable features of data logger user interface software is given in 

    the Annexure‐I  4.3.11 To  ensure  data  availability  continuously  recommended  data  loggers  network 

    configuration with  redundancy enables data  access by  field officials  as well  as zonal HQ  is given in the annexure  

     4.3.12 Recommended  specifications  of  hardware  required  for  data  logger  network 

    elements are given in the Annexure‐E   5 FUNCTIONAL REQUIREMENTS:   5.1   The system shall generate audiovisual alarm in ASM’s/ Signal Maintainer’s room in 

    the  case  of  power  supply  failure  (battery  voltage  low)  or  battery  charger defective with acknowledgement facility. 

     5.2  Each  data  logger  shall  have  its  own  identity  code which  shall  be  transmitted 

    along with data packet to central monitoring unit.  

  • ISO9001:2008 Document No: IRS:S:99/2006 Version No.------- Date Effective :------

    Document Title: Draft Specification for Data Logger System for Railway S & T Installation

    Prepared By: SSRE/Signal Checked By : ADE/Signal Issued By: Director/Signal-III Printed: Page 23of 118

    5.3  Events  recorded  at  each  station  shall  be  continuously  transmitted  to  central monitoring unit for online monitoring.  The following data transfer speeds are to be fulfilled: 

                         i. Data logger to Data logger/FEP – 125 packets per sec                      ii. FEP to CMU – 1000 Packets per sec                      iii. RTU to Data logger – 40 packets per sec                       iv. Data logger to Local PC – 1 sec    5.4       In case of loss of data, retransmission of data shall take place.   5.5  Data transfer rate shall be 57600 BPS with fallback facility to lower rates.  

     5.6      EXCEPTION REPORT: 

    Exception  condition  shall  be  stored  in  the  data  logger  chronologically  and displayed  one  by  one  on  the  front  panel  through  a  toggle  switch. Details  of exception report are attached in Annexure‐C 

     5.8  Data  loggers of all stations shall send status report to the Central monitoring 

    unit  continuously.  Status  information  shall  be  processed  at  the  central monitoring unit and audio visual alarm generated for the fault / alarm condition It  shall be possible  to  send  important alarms as SMS  to maintenance  staff as given in Annexure‐C 

     6  TESTS AND REQUIREMENTS  6.1  Conditions of Tests               Unless otherwise specified all tests shall be carried out at ambient atmospheric 

    conditions.  6.2  For  inspection of material,  relevant  clauses of  IRS:  S 23 and RDSO/SPN/144 

    shall apply.   6.2.1  Test Equipment 

     i. Dual beam oscilloscope of 20 MHz bandwidth 

  • ISO9001:2008 Document No: IRS:S:99/2006 Version No.------- Date Effective :------

    Document Title: Draft Specification for Data Logger System for Railway S & T Installation

    Prepared By: SSRE/Signal Checked By : ADE/Signal Issued By: Director/Signal-III Printed: Page 24of 118

    ii. Digital multimeters  ‐ 3.1/2 digit display with  facility of diode & transistor testing with 1% accuracy 

    iii. EPROM Programmer and UV eraser iv. Megger (500V) v. PC  vi. Test jig vii. Any other test equipment considered necessary. 

     6.3  Type Tests  6.3.1   The following tests shall constitute type tests:  

    a)  Visual inspection as per Clause 7.1 b)  Insulation Resistance tests as per Clause 7.2 c)  Card‐level functional tests on all the cards.  d)  System level functional tests. e)         Environmental/climatic tests as per Clause 7.3  f)  Applied High Voltage Test as per Clause 7.4 

       6.3.2   Any other tests shall be carried out as considered necessary by the purchaser.    6.3.3  Only one equipment  shall be  tested  for  this purpose. The equipment  shall 

    successfully  pass  all  the  type  tests  for  proving  conformity  with  this specification. If the equipment fails in any of the type tests, the purchaser or his nominee at his discretion, may call for another equipment/card(s) of the same type and subject it to all tests or to the test(s) in which failure occurred. No failure shall be permitted in the repeat test(s). 

     6.4  Acceptance Tests  6.4.1  The following shall comprise acceptance tests:  

    a)  Visual inspection (Clause 7.1). b)  Insulation Resistance tests (Clause 7.2). c)  System level functional tests.  

     6.4.2  Any other tests shall be carried out as considered necessary by the purchaser.    

  • ISO9001:2008 Document No: IRS:S:99/2006 Version No.------- Date Effective :------

    Document Title: Draft Specification for Data Logger System for Railway S & T Installation

    Prepared By: SSRE/Signal Checked By : ADE/Signal Issued By: Director/Signal-III Printed: Page 25of 118

    6.5  Routine tests  6.5.1  The  following  shall  comprise  the  routine  tests  and  shall  be  conducted  by 

    manufacturer on every equipment and the test results will be submitted to the inspection  authority  before  inspection.  The  application  software  in  proper format shall also be submitted to the inspection authority in advance. 

     i. Visual inspection (Clause 7.1) ii. Insulation Resistance tests (Clause 7.2) iii. Card level functional test on all the cards. iv. System level functional test. 

     6.5.2  Any other tests shall be carried out as considered necessary by the purchaser.    7  TEST PROCEDURE  

    The test procedure shall be based on the system design. The methodologies to be adopted  for various  tests  shall be decided  taking  into account  the  system design/configuration.  

     7.1  Visual Inspection  

    The  equipment  shall  be  visually  inspected  to  ensure  compliance  with  the requirement of Clauses 3  to 5 of  this  specification.  The  visual  inspection will broadly include – 

     7.1.1 System level checking:  

    Constructional details.  Dimensional check .  General workmanship.  Configuration.  Mechanical polarisation on cards . 

     7.1.2  Card level checking: 

      General track layout .  Quality of soldering and component mounting.  Conformal coating.  Legend printing. 

  • ISO9001:2008 Document No: IRS:S:99/2006 Version No.------- Date Effective :------

    Document Title: Draft Specification for Data Logger System for Railway S & T Installation

    Prepared By: SSRE/Signal Checked By : ADE/Signal Issued By: Director/Signal-III Printed: Page 26of 118

    Green masking.  7.1.3  Module level checking:  

    General shielding arrangement of individual cards.  Indications and displays.  Mounting and clamping of connectors.  Proper housing of cards. 

     7.2  Insulation Resistance Test  7.2.1  Insulation Resistance Test shall be conducted as per RDSO/SPN/144  7.3 Environmental / climatic tests  7.3.1  Environmental / climatic tests shall be conducted as per RDSO/SPN/144  7.4      Applied High Voltage Test  7.4.1   Applied High Voltage Test shall be conducted as per RDSO/SPN/144  8  QUALITY ASSURANCE  8.1  All materials & workmanship shall be of good quality.   8.2  Since  the  quality  of  the  equipment  bears  a  direct  relationship  to  the 

    manufacturing process and the environment under which it is manufactured, the  manufacturer  shall  ensure  Quality  Assurance  Program  of  adequate standard. 

     8.3  Validation and system of monitoring of QA procedure shall form a part of type 

    approval.  The  necessary  Plant,  Machinery  and  Test  instruments  as  given below shall be available with the manufacturer. 

     8.3.1   Plant & Machinery:  

    i)  Ultrasonic cleaner/Aqueous cleaner for automatic cleaning    ii)  Burn in chamber      iii)  Anti‐static assembly iv)  EPROM Programmer and UV Eraser 

  • ISO9001:2008 Document No: IRS:S:99/2006 Version No.------- Date Effective :------

    Document Title: Draft Specification for Data Logger System for Railway S & T Installation

    Prepared By: SSRE/Signal Checked By : ADE/Signal Issued By: Director/Signal-III Printed: Page 27of 118

    v)  Microprocessor development system vi)  Computer aided design system 

     8.3.2   All  test  instruments  as  given  in  Cl.  6.2.1  shall  be  available  with  the 

    manufacturer.  8.4  Along with the prototype sample  for type test, the manufacturer shall submit 

    the Quality Assurance Manual.  9  PACKING    The equipment and  its  sub assemblies  shall be packed  in  thermocole boxes 

    and  the  empty  spaces  shall  be  filled  with  suitable  filling  material.  Before keeping in the thermocole box, the equipment shall be wrapped with bubble sheet. The equipment  shall be  finally packed  in a wooden  case of  sufficient strength so that it can withstand bumps and jerks encountered in a road/ rail journey.   

     10  INFORMATION TO BE SUPPLIED BY THE MANUFACTURER    Following documents should be supplied along with the system:  10.1 Mechanical drawings of each sub‐system/ rack.  10.2 Trouble shooting chart.   10.3 Installation and Maintenance Manual.  10.4 Pre‐commissioning check list, DOs and DON'Ts of data logger system including 

    RTU, CMU & FEP in the User’s manual.  11  INFORMATION TO BE SUPPLIED BY THE PURCHASER  11.1  Total  number  of  digital  and  analog  inputs  to  be  monitored  calculated  as 

    under.  11.1.1  The tenderer should give number of digital inputs required by calculating the 

    inputs as given in the Annexure‐B  11.1.2  Details of Analog inputs to be monitored as per Annexure‐B.  

  • ISO9001:2008 Document No: IRS:S:99/2006 Version No.------- Date Effective :------

    Document Title: Draft Specification for Data Logger System for Railway S & T Installation

    Prepared By: SSRE/Signal Checked By : ADE/Signal Issued By: Director/Signal-III Printed: Page 28of 118

     11.1.3 Whether RTU is required for monitoring of the equipment at distant place, no. 

    of digital and analog inputs required in RTU.   Details  of  analog  inputs  to  be monitored  from  RTU  should  be  given  in  the format as given below: 

     Type of input (Digital/Analog) 

    No. ofchannels Approximate  distance  from data‐logger 

      11.2  Additional exception  reports  (other  than  those mentioned  in Annexure‐C  to 

    be  generated.   11.3  List of functions (in addition those mentioned in Annexure‐B to be monitored. 

     

    11.4  (a) Central monitoring equipment (CMU) required – Yes/ No. 

      (b)FEP required – Yes/NO 

                If YES, indicate whether it is to be provided at the same station or at a remote place like control office etc. 

     

    11.5  Whether printer is required with data logger (at the station) : Yes/ No 

    11.6  Type of network ports . 

     

     

     

     

     

     

     

     

     

  • ISO9001:2008 Document No: IRS:S:99/2006 Version No.------- Date Effective :------

    Document Title: Draft Specification for Data Logger System for Railway S & T Installation

    Prepared By: SSRE/Signal Checked By : ADE/Signal Issued By: Director/Signal-III Printed: Page 29of 118

    Annexure‐A 

    Data Logger Protocol A.1 EVENT PACKET:

    A.1.1 EVENT PACKET FORMAT:

    Block 0

    AAH START (2 BYTES) 66H

    ID NO

    ADDRESS (2 BYTES)

    SERL NO

    SERIAL NUMBER (2 BYTES)

    PACKED TIME

    PACKED TIME (4 BYTES)

    PACKED YEAR LSB PACKED YEAR LSB (1 BYTE)

    Block 1

    TYPE IDENTIFICATION PACKET TYPE (1 BYTE)

    DATA

    PACKET DATA (8 BYTES)

    Block 2

    CRC

    VALIDATION (2 BYTES)

    BBH END (2 BYTES) BBH

    Event packet consists of 3 blocks as shown above.

    1. Block 0.

  • ISO9001:2008 Document No: IRS:S:99/2006 Version No.------- Date Effective :------

    Document Title: Draft Specification for Data Logger System for Railway S & T Installation

    Prepared By: SSRE/Signal Checked By : ADE/Signal Issued By: Director/Signal-III Printed: Page 30of 118

    2. Block 1.

    3. Block 2.

    1.1.i. BLOCK 0: The size of the BLOCK 0 is 11 bytes. The structure of Block 0 is

    common for any type of event packet and it is having the following five fields.

    START: AAH and 66H are the start of the event packet. Here the Header second byte

    is changed to 66 H from 55 h, and acknowledgement header second byte is changed to

    99 H from 33 h. To identify the old units connected to this data logger and also to

    provide the backward compatibility [To support data logger common protocol].

    ID NO: This is used for the identification of various devices like FEP,

    DATALOGGER and RTU etc.

    Serial Number: It is the sequence number of packet. With this CMU will identify that

    it is receiving all the packets or not. Serial no will start from 0000H, whenever a

    packet is created count will be incremented by one, and will roll over to 0000H after

    reaching FFFFH.

    PACKED TIME:

    Time will be stored in the Packed Form. This is a long word size and time will be

    calculated in multiples of 1/64 second. This long word will hold time for one year. The

    equation to build packed time from the real time is given below.

    FIELD NAME SIZE IN BYTES START 2 ID NO 2 SERL NO 2 PACKED TIME 4 PACKED YEAR LSB 1

  • ISO9001:2008 Document No: IRS:S:99/2006 Version No.------- Date Effective :------

    Document Title: Draft Specification for Data Logger System for Railway S & T Installation

    Prepared By: SSRE/Signal Checked By : ADE/Signal Issued By: Director/Signal-III Printed: Page 31of 118

    Packed time = (Days x 24 x 60 x 60 x 64) + (Hr x 60 x 60 x 64)+(Mt x 60 x 64) + (Sec

    x 64). Here Days = Number of completed days till present date

    Hr = Hours

    Mt = Minutes

    Sec = Seconds

    PACKED YEAR LSB: It will represent the YEAR LSB of the packet in which year

    it was created. Here year LSB means in 2012 year 12 will be the LSB and it will be

    stored as 0C H.

    1.1. ii. BLOCK 1: Block 1 size is 9 bytes. The values in the BLOCK 1 will vary

    depending upon the type of event packet. BLOCK1 is having the following fields.

    0 TYPE IDENTIFIER (1 bytes).

    1 DATA (8 bytes).

    a). TYPE IDENTIFIER (TI):

    This is a byte-sized value and it indicates packet type. Each packet will have a

    unique type identifier. The Event records are classified into two types.

    1.Functional Records (type id’s 00 H to 7F H).

    2.Diagnosis Records (type id’s 80 H to FF H).

    The following table shows Functional records and its type identifiers.

    S.No Details Type id Usage 1 Digital Record 00 H Compulsory

    2 Analog Record 01 H Compulsory

    3 Time Difference Record 02 H Compulsory

    4 Time Write(Update) Record 03 H Compulsory

    5 Communication status Record 04 H Optional

  • ISO9001:2008 Document No: IRS:S:99/2006 Version No.------- Date Effective :------

    Document Title: Draft Specification for Data Logger System for Railway S & T Installation

    Prepared By: SSRE/Signal Checked By : ADE/Signal Issued By: Director/Signal-III Printed: Page 32of 118

    6 Health Record (Time packet) 05 H Compulsory

    7 Digital Periodical All Inputs Status Record 06 H Compulsory

    8 Digital All Inputs Status At Reset Record 07 H Compulsory

    9 Reserved 08 H

    10 Configuration Record 09 H Optional

    11 Reserved 0A H

    12 Analog Chatter ON Record 0B H Compulsory

    13 Analog chatter OFF Record 0C H Compulsory

    14 Digital Fault Record 0D H Optional

    15 Analog Fault Record 0E H Optional

    16 Reserved 0F H

    17 Digital Chatter ON Record 10 H Compulsory

    18 Digital chatter OFF Record 11 H Compulsory

    19 Modem Link Status Record 12 H Compulsory

    20 Reserved 13 H

    21 Reserved 14 H

    22 Reserved 15 H

    23 Reserved 16 H

    24 Reserved 17 H

    25 Modem Reset Record 18 H Compulsory

    26 Internal Temperature Record 19 H Compulsory

    28 Reserved 20 H

    29 Reserved 21 H

    30 Reserved 22 H

  • ISO9001:2008 Document No: IRS:S:99/2006 Version No.------- Date Effective :------

    Document Title: Draft Specification for Data Logger System for Railway S & T Installation

    Prepared By: SSRE/Signal Checked By : ADE/Signal Issued By: Director/Signal-III Printed: Page 33of 118

    31 Reserved 23 H

    32 Communication ports Link Status Record 24 H Compulsory

    33 Reserved 25 H

    34 Modem’s Periodical Link Status Record 27 H Compulsory

    35 Analog Periodical Chatter inputs Record 28 H Reserved

    36 Digital Periodical Chatter inputs Record 29 H Optional

    37 Reserved 2A H Reserved

    38 Analog Periodical All inputs Status Record 2B H Reserved

    39 Reserved 2C H

    40 Reserved 2D H

    41 Reserved 2E H

    42 Reserved 2F H

    43 Reserved 30 H

    44 Reserved 31 H

    45 Reserved 32 H

    46 Reserved 33 H

    47 Secondary Data Backup Module Status Record 34 H Compulsory

    48 Primary Data Backup Module Status Record 35 H Compulsory

    48 Reserved

    36 H

    To

    7F H

  • ISO9001:2008 Document No: IRS:S:99/2006 Version No.------- Date Effective :------

    Document Title: Draft Specification for Data Logger System for Railway S & T Installation

    Prepared By: SSRE/Signal Checked By : ADE/Signal Issued By: Director/Signal-III Printed: Page 34of 118

    The following table shows Diagnosis records and its type id’s.

    S.No Details Type id Usage 1 Data Logger Reset Record 80 H Compulsory

    2 Digital / Analog / Communication Card Health Record 81 H Optional

    3 Communication Errors status Record 82 H Compulsory

    4 Data Base Status Record 83 H Compulsory

    5 Reserved

    84 H

    To

    FF H

    b). DATA:

    This field is having 8 bytes, last 3 bytes are reserved and first 5 bytes will vary

    depending upon packet.

    Byte No Description

    1 to 5 Used as per record format

    6 to 8 Reserved

    1.1.ii. BLOCK 2:

    BLOCK 2 size is 4 bytes. The structure of Block 2 is common for any type of

    event packet and it is having the following two fields.

    FIELD NAME SIZE IN BYTES CRC 2 END 2

  • ISO9001:2008 Document No: IRS:S:99/2006 Version No.------- Date Effective :------

    Document Title: Draft Specification for Data Logger System for Railway S & T Installation

    Prepared By: SSRE/Signal Checked By : ADE/Signal Issued By: Director/Signal-III Printed: Page 35of 118

    I. CRC: The CRC field is a 16 bit value calculated as per CCITT polynomial "x16+x12+x5+1". This CRC will be calculated to the block 0 and block 1 of the

    event packet fields with an exclusive of start bytes. It should be calculate from

    top to bottom.

    II. END: It is the event packet end identifier.

    A.1.2 Event Records Data Bytes Description:

    1. Digital Record:

    This record will be created to indicate the change in status of the digital input.

    Occurrence: This record will be created whenever a digital input changes its state

    (From ON to OFF or OFF to ON). Its record ID is 00H.

    BLOCK 0

    BLOCK 1

    TI = 00 H(1 byte)

    Input Number (2 bytes)

    Status of Input (1 byte)

    Dummy (2 bytes)

    Reserved (3 bytes)

    BLOCK 2

    Input Number: 1 TO 4096

    Status of Input: 00 H Picked UP

    FF H Drop.

  • ISO9001:2008 Document No: IRS:S:99/2006 Version No.------- Date Effective :------

    Document Title: Draft Specification for Data Logger System for Railway S & T Installation

    Prepared By: SSRE/Signal Checked By : ADE/Signal Issued By: Director/Signal-III Printed: Page 36of 118

    2. Analog Record:

    This record will be created whenever there is variation in the any of analog inputs.

    Occurrence: This record will be created whenever the difference of previous recorded

    channel value and present scanned channel value of a particular input crosses the

    configured tolerance limit..

    BLOCK 0

    BLOCK 1

    TI = 01 H(1 byte)

    Channel Number (2 bytes)

    Channel Value (3 byte)

    Reserved (3 bytes)

    BLOCK 2

    CHANNEL VALUE : 0 TO 4095 (Value 4095 is equivalent to Maximum possible

    Channel value for that input). The nominal voltages and their corresponding maximum

    voltages are shown in the below table

    Nominal voltage Maximum voltage Maximum value

    230V AC 330V AC 4095

    110V AC 170V AC 4095

    110V DC 170V DC 4095

    60V DC 90V DC 4095

    24V AC 50V DC 4095

    24V DC 50V DC 4095

  • ISO9001:2008 Document No: IRS:S:99/2006 Version No.------- Date Effective :------

    Document Title: Draft Specification for Data Logger System for Railway S & T Installation

    Prepared By: SSRE/Signal Checked By : ADE/Signal Issued By: Director/Signal-III Printed: Page 37of 118

    18V DC 50V DC 4095

    12V DC 25 VDC 4095

    150mv 150 mv 4095

    3V or 2V, 5KHZ 3000mv 4095

    6V DC 10V DC 4095

    CHANNEL NUMBER: 1 TO 96.

    The External temperature record will also be created with the same analog record ID with channel number as 00 H. Channel value of temperature is as shown.

    Byte 1: Sign Value. 00 – “-VE” temperature.

    FF – “+VE” temperature.

    Byte 2 & 3: Temperature (2 bytes). It is in terms of 0.5oC. It is ranging from 0 to 128oC.

    3. Time Difference Record:

    This record was created to notify the difference between the packed time and with

    RTC chip time.

    Occurrence: This record will be created whenever there is a difference in packed

    time and RTC chip time. The data logger compares the chip time with the packed

    time periodically and to record the difference if any

  • ISO9001:2008 Document No: IRS:S:99/2006 Version No.------- Date Effective :------

    Document Title: Draft Specification for Data Logger System for Railway S & T Installation

    Prepared By: SSRE/Signal Checked By : ADE/Signal Issued By: Director/Signal-III Printed: Page 38of 118

    STATUS BYTE:

    S.No Status Byte Value Details

    1 00 H RTC Time > Packed Time

    2 FF H RTC Time < Packed Time

    DIFFERNCE TIME VALUE: RTC Time ~ Packed Time

    4. Time Write record:

    This record will be created whenever time set command was sent from CMU/user

    interface.

    Occurrence: This record is created whenever time was set from CMU.

    BLOCK 0

    BLOCK 1

    TI = 02 H(1 byte)

    Status Byte (1 byte)

    Time difference value (4 bytes)

    Reserved (3 bytes)

    BLOCK 2

  • ISO9001:2008 Document No: IRS:S:99/2006 Version No.------- Date Effective :------

    Document Title: Draft Specification for Data Logger System for Railway S & T Installation

    Prepared By: SSRE/Signal Checked By : ADE/Signal Issued By: Director/Signal-III Printed: Page 39of 118

    BLOCK 0

    BLOCK 1

    TI = 03 H(1 byte)

    Packed time (4 bytes)

    Year LSB (1 byte)

    Reserved (3 bytes)

    BLOCK 2

    5. Communication Status Record:

    These records were created to log network status for later analysis. the network

    communication health status.

    Occurrence: These records will be created for every 68 minutes approximately.

    BLOCK 0

    BLOCK 1

    TI = 04 H(1 byte)

    Packets Count (4 bytes)

    Serial Number (1 byte)

    Reserved (3 bytes)

    BLOCK 2

    PACKET COUNT: This count may be Transmitted packets (or) Received packets

    (or) Pending packets (or) Duplication packets (or) Fail packets count for two network

    ports.

    SERIAL NUMBER: It specifies the type of Packets count.

    The MSB of the serial number indicates port number 0 – 15 ports.

    The LSB of the serial number indicates packet type as shown below.

  • ISO9001:2008 Document No: IRS:S:99/2006 Version No.------- Date Effective :------

    Document Title: Draft Specification for Data Logger System for Railway S & T Installation

    Prepared By: SSRE/Signal Checked By : ADE/Signal Issued By: Director/Signal-III Printed: Page 40of 118

    LSB Details

    0 Transmitted Packets Count

    1 Receive Fail Packets Count

    2 Pending Packets Count

    3 Received Packets Count

    4 Duplication Packets Count

    6. Health Record:

    This record will be created to notify the health of data logger to the CMU.

    Occurrence: This record will be created for every one minute if any other record is not

    created.

    BLOCK 0

    BLOCK 1

    TI = 05 H(1 byte)

    Dummy (5 bytes)

    Reserved (3 bytes)

    BLOCK 2

    DUMMY BYTES: 00H

    7. Digital Periodical All Inputs Status:

    In these records the status of all the digital inputs will be sent. So as the CMU can

    synchronize with the latest input status.

    Occurrence: These records are created for every 34 minutes approximately and also

    on request of the CMU. The number of records created will depend upon the number

  • ISO9001:2008 Document No: IRS:S:99/2006 Version No.------- Date Effective :------

    Document Title: Draft Specification for Data Logger System for Railway S & T Installation

    Prepared By: SSRE/Signal Checked By : ADE/Signal Issued By: Director/Signal-III Printed: Page 41of 118

    of inputs configured. In each record, status of 32 inputs will be sent. Each inputs status

    can be 0 or 1(‘0’ for pickup and ‘1’ for drop). If the number of inputs configured is

    512, 16 records will be created. The configuration should be in the multiples of 512

    inputs. The 1st record will have inputs of 1 to 32, 2nd record will have 33 to 64 and so

    on up to the total number of inputs.

    BLOCK 0

    BLOCK 1

    TI = 06 H(1 byte)

    Bytes number / bit positions B7 B6 B5 B4 B3 B2 B1 B0

    Byte 1 Status of 1-8 inputs 8 7 6 5 4 3 2 1

    Byte 2 Status of 9-16 inputs 16 15 14 13 12 11 10 9

    Byte 3 Status of 17-24 inputs 24 23 22 21 20 19 18 17

    Byte 4 Status of 24-32 inputs 32 31 30 29 28 27 26 25

    Serial Number ( 1 byte)

    Reserved (3 bytes)

    BLOCK 2

    STATUS: Status of a set of 16 inputs

    SERIAL NUMBER: 00 H-7F H.

    For the first 1 to 32 inputs 00h is given as serial number and continued up to7F h.

    8. Digital All Inputs Status at RESET:

    These records have been created at the time of Data Logger Reset. This is identical

    to the Periodical All Inputs Status except the type identifier.

    Occurrence: These records will be created whenever the data logger resets.

  • ISO9001:2008 Document No: IRS:S:99/2006 Version No.------- Date Effective :------

    Document Title: Draft Specification for Data Logger System for Railway S & T Installation

    Prepared By: SSRE/Signal Checked By : ADE/Signal Issued By: Director/Signal-III Printed: Page 42of 118

    BLOCK 0

    BLOCK 1

    TI = 07 H(1 byte)

    Bytes number / bit positions B7 B6 B5 B4 B3 B2 B1 B0

    Byte 1 Status of 1-8 inputs 8 7 6 5 4 3 2 1

    Byte 2 Status of 9-16 inputs 16 15 14 13 12 11 10 9

    Byte 3 Status of 17-24 inputs 24 23 22 21 20 19 18 17

    Byte 4 Status of 24-32 inputs 32 31 30 29 28 27 26 25

    Serial Number ( 1 byte)

    Reserved (3 bytes)

    BLOCK 2

    9. Configuration Record: This record will be created to store the all configurations of the Data Logger.

    Occurrence: This record will be created whenever data logger is reset/powered on.

    This record will also be sent for every 34 minutes along with the Periodical all input

    status packets.

    BLOCK 0

    BLOCK 1

    TI = 09 H(1 byte)

    Version (2 bytes)

    Configuration (2 bytes)

    Device Id (1 byte)

    Reserved (3 bytes)

    BLOCK 2

  • ISO9001:2008 Document No: IRS:S:99/2006 Version No.------- Date Effective :------

    Document Title: Draft Specification for Data Logger System for Railway S & T Installation

    Prepared By: SSRE/Signal Checked By : ADE/Signal Issued By: Director/Signal-III Printed: Page 43of 118

    CONFIGURATION BYTES:

    Byte1 & 2: version details.

    Byte3: Bit7 to Bit3 : 0s

    Bits B2, B1, B0 will indicate the digital inputs configuration.

    Byte 4 :

    S.No Byte Value Analog inputs configuration

    1 00 H Analog channels are Disabled

    2 01 H 32 Analog input channels configured

    3 02 H 64 Analog input channels configured

    4 03 H 96 Analog input channels configured.

    Byte 5: Device Id

    00 H – Data Logger.

    01 H – RTU type 1.

    02 H – RTU type 2

    03 H – RTU type 3

    B2

    B1

    B0

    Number of digital inputs configured

    DL RTU & others

    0 0 0 512 8

    0 0 1 1024 16

    0 1 0 1536 32

    0 1 1 2048 64

    1 0 0 2560 128

    1 0 1 3072 512

    1 1 0 3584 1024

    1 1 1 4096 1536

  • ISO9001:2008 Document No: IRS:S:99/2006 Version No.------- Date Effective :------

    Document Title: Draft Specification for Data Logger System for Railway S & T Installation

    Prepared By: SSRE/Signal Checked By : ADE/Signal Issued By: Director/Signal-III Printed: Page 44of 118

    11. Digital Fault record:

    This record will be created whenever the digital fault sequence occurs.

    No specific data format is defined since the digital fault sequence is dependent on

    local PC.

    Occurrence: This record is created, whenever the predefined sequence of operations

    will occur.

    Fault Logic Entry number: The fault logic id entered at local station.

    BLOCK 0

    BLOCK 1

    TI = 0D H(1 byte)

    Fault logic Entry number (2 bytes)

    Dummy(3 bytes)

    Reserved (3 bytes)

    BLOCK 2

    12. Analog Fault Record:

    This record will be created to indicate that the analog channels exceeded

    configured safe limits.

    Occurrence: This record is created whenever an analog channel crosses the

    configured minimum or maximum channel limits.

  • ISO9001:2008 Document No: IRS:S:99/2006 Version No.------- Date Effective :------

    Document Title: Draft Specification for Data Logger System for Railway S & T Installation

    Prepared By: SSRE/Signal Checked By : ADE/Signal Issued By: Director/Signal-III Printed: Page 45of 118

    This record is identical to analog record except type identifier.

    CHANNEL VALUE: Data bytes 1 to 2 will give channel value ranging from 0 to

    4095.

    And Data byte 3 will indicate as follows.

    ‘FF’ Fault is due to exceeding maximum value.

    ‘00’ Fault is due to falling below minimum value.

    CHANNEL NUMBER: Data bytes 4 and 5 will give channel

    14. Digital Chatter on Record:

    This record is created whenever any relay is chattering.

    Occurrence: This record will be created whenever digital input changes from

    NORMAL state to CHATTERING state.

    A digital input is said to be in chattering state, if its status changes by 8 times or

    more in 4 seconds. Normal state is the state where the input status does not

    change so.

    BLOCK 0

    BLOCK 1

    TI = 0E H(1 byte)

    Channel Number (2 bytes)

    Channel Value (3 bytes)

    Reserved (3 bytes)

    BLOCK 2

  • ISO9001:2008 Document No: IRS:S:99/2006 Version No.------- Date Effective :------

    Document Title: Draft Specification for Data Logger System for Railway S & T Installation

    Prepared By: SSRE/Signal Checked By : ADE/Signal Issued By: Director/Signal-III Printed: Page 46of 118

    BLOCK 0

    BLOCK 1

    TI = 10 H(1 byte)

    Input Number (2 bytes)

    Input Status (1 bytes)

    Dummy (2 bytes)

    Reserved (3 bytes)

    BLOCK 2

    Input Number: 01 TO 4096

    Input Status: No significance

    15. Digital Chatter off Record:

    This record is created whenever any relay is normalized from chattering.

    Occurrence: This record will be created whenever digital input changes from

    CHATTERING state to NORMAL state.

    BLOCK 0

    BLOCK 1

    TI = 11 H(1 byte)

    Input Number (2 bytes)

    Input Status (1 bytes)

    Dummy (2 bytes)

    Reserved (3 bytes)

    BLOCK 2

  • ISO9001:2008 Document No: IRS:S:99/2006 Version No.------- Date Effective :------

    Document Title: Draft Specification for Data Logger System for Railway S & T Installation

    Prepared By: SSRE/Signal Checked By : ADE/Signal Issued By: Director/Signal-III Printed: Page 47of 118

    Input Number: 01 TO 4096

    Input Status: 00H- PICKUP

    FFH- DROP

    16. Modem Link Status Record:

    This record will be created whenever the modem establishes or losses the link with

    the other modem.

    Occurrence: This record will be created whenever 'Carrier Detect' bit of the

    modem changes its state.

    BLOCK 0

    BLOCK 1

    TI = 12 H(1 byte)

    CD Status (1 byte)

    Port Number (1 byte)

    Dummy (3 bytes)

    Reserved (3 bytes)

    BLOCK 2

    PORT NUMBER: 01H- Direction A

    02H- Direction B

    CD Status: 00 h- ‘CD’ NOT EXISTING

    FF h- ‘CD’ EXSISTING

  • ISO9001:2008 Document No: IRS:S:99/2006 Version No.------- Date Effective :------

    Document Title: Draft Specification for Data Logger System for Railway S & T Installation

    Prepared By: SSRE/Signal Checked By : ADE/Signal Issued By: Director/Signal-III Printed: Page 48of 118

    A.2 Functional Records:

    A.2.1 Analog Chatter ON Record:

    This record is created whenever any Analog input is chattering.

    Occurrence: This record will be created whenever Analog input changes from

    NORMAL state to CHATTERING state.

    BLOCK 0

    BLOCK 1

    TI = 0B H(1 byte)

    Channel Value (3 bytes)

    Channel Number (2 bytes)

    Reserved (3 bytes)

    BLOCK 2

    Channel Number: 01 TO 96

    Channel Value: No significance

    A.2.2 Analog chatter OFF Record:

    This record is created whenever any Analog input is normalized from

    chattering.

    Occurrence: This record will be created whenever Analog input changes

    from CHATTERING state to NORMAL state.

  • ISO9001:2008 Document No: IRS:S:99/2006 Version No.------- Date Effective :------

    Document Title: Draft Specification for Data Logger System for Railway S & T Installation

    Prepared By: SSRE/Signal Checked By : ADE/Signal Issued By: Director/Signal-III Printed: Page 49of 118

    BLOCK 0

    BLOCK 1

    TI = 0C H(1 byte)

    Channel Value (3 bytes)

    Channel Number (2 bytes)

    Reserved (3 bytes)

    BLOCK 2

    Channel Number: 01 TO 96

    Cannel Value: This will give the present channel value.

    A.2.3 Modem Reset Record:

    Occurrence: This record will created whenever the modem hardware reset

    happened.

    BLOCK 0

    BLOCK 1

    TI = 18 H (1 byte)

    Port Number (1 byte)

    Hard Reset Type (1 byte)

    CD Status (1 byte)

    Dummy (2 bytes)

    Reserved (3 bytes)

    BLOCK 2

    Port Number: It is ranging from 1 to N (basing on number of ports available

    in that equipement).

  • ISO9001:2008 Document No: IRS:S:99/2006 Version No.------- Date Effective :------

    Document Title: Draft Specification for Data Logger System for Railway S & T Installation

    Prepared By: SSRE/Signal Checked By : ADE/Signal Issued By: Director/Signal-III Printed: Page 50of 118

    Hard Reset Type: 01 – Normal Reset

    02 – Reset caused by User Interface.

    03 – Reset caused by CMU.

    CD Status: 00 H - CD Present

    FF H – CD Absent.

    A.2.4 Internal Temperature Record:

    Occurrence: Created whenever the Internal temperature of the data logger

    crosses the 5% tolerance value of the previous temperature.

    BLOCK 0

    BLOCK 1

    TI = 19 H (1 byte)

    Temperature Sign (1 byte)

    Temperature value (2 bytes)

    Dummy (2 bytes)

    Reserved (3 bytes)

    BLOCK 2

    Temperature Sign: 00 H – Positive temperature.

    FF H – Negative temperature

    Temperature Value: it is in terms of 0.5oC. It is ranging from 0 to 128oC.

  • ISO9001:2008 Document No: IRS:S:99/2006 Version No.------- Date Effective :------

    Document Title: Draft Specification for Data Logger System for Railway S & T Installation

    Prepared By: SSRE/Signal Checked By : ADE/Signal Issued By: Director/Signal-III Printed: Page 51of 118

    A.2.5 Communication ports Link Status Record:

    Occurrence: Created when ever link status of communication ports changed

    from one status to another status (fail to ok / ok to fail).

    BLOCK 0

    BLOCK 1

    TI = 24 H (1 byte)

    Link Status (1 bytes)

    Port Number (1 byte)

    Dummy (3 bytes)

    Reserved (3 bytes)

    BLOCK 2

    Link Status: 00 H – Link Ok

    FF H – Link Fail.

    A.2.6 Modem’s Periodical Link Status Record:

    Occurrence: This Record will be created for modem status for the purpose of

    hour packet. It will created along with periodical all input status records.

  • ISO9001:2008 Document No: IRS:S:99/2006 Version No.------- Date Effective :------

    Document Title: Draft Specification for Data Logger System for Railway S & T Installation

    Prepared By: SSRE/Signal Checked By : ADE/Signal Issued By: Director/Signal-III Printed: Page 52of 118

    BLOCK 0

    BLOCK 1

    TI = 27 H (1 byte)

    Port Number (2 bytes)

    CD Status (1 byte)

    Dummy (2 bytes )

    Reserved (3 bytes)

    BLOCK 2

    PORT NUMBER: 01H- Direction A

    02H- Direction B

    CD Status:

    00 h- ‘CD’ NOT EXISTING

    FF h- ‘CD’ EXSISTING

    A.2.7 Analog Periodical Chatter Inputs Record:

    Occurrence: This Record will be created to notify the CMU about the Analog

    Chatter inputs of Data logger. It will create along with Analog periodical all

    input status records.

  • ISO9001:2008 Document No: IRS:S:99/2006 Version No.------- Date Effective :------

    Document Title: Draft Specification for Data Logger System for Railway S & T Installation

    Prepared By: SSRE/Signal Checked By : ADE/Signal Issued By: Director/Signal-III Printed: Page 53of 118

    BLOCK 0

    BLOCK 1

    TI = 28 H (1 byte)

    Channel Number(2 bytes)

    Channel value (3 byte)

    Reserved (3 bytes)

    BLOCK 2

    Channel Number: 01 TO 96

    Channel Value: No significance

    A.2.8 Digital Periodical Chatter Inputs Record:

    Occurrence: This Record will be created to notify the CMU about the Chatter

    inputs of Data logger. It will created along with periodical all input status

    records.

    BLOCK 0

    BLOCK 1

    TI = 29 H (1 byte)

    Input Number (2 bytes)

    Input Status (1 byte)

    Dummy (2 bytes )

    Reserved (3 bytes)

    BLOCK 2

  • ISO9001:2008 Document No: IRS:S:99/2006 Version No.------- Date Effective :------

    Document Title: Draft Specification for Data Logger System for Railway S & T Installation

    Prepared By: SSRE/Signal Checked By : ADE/Signal Issued By: Director/Signal-III Printed: Page 54of 118

    Input Number: 01 TO 4096

    Input Status: No significance

    A.2.9 Analog Periodical all input Status Record:

    B.2.9 This record will be created at power-on/Reset. And this will be created at every

    68 minutes.

    Occurrence: This record will be created whenever the difference of previous

    recorded channel value and present scanned channel value of a particular input

    crosses the configured tolerance limit..

    BLOCK 0 BLOCK 1

    TI = 01 H(1 byte)

    Channel Number (2 bytes)

    Channel Value (3 byte)

    Reserved (3 bytes)

    BLOCK 2

    CHANNEL VALUE : 0 TO 4095 (Value 4095 is equivalent to Maximum

    possible Channel value for that input). The nominal voltages and their

    corresponding maximum voltages are shown in the below table

    Channel Number: 1 TO 96

    A.2.10 Primary Data Backup Module Status Record:

    This record will be created to notify the health Data Logger SD Card to CMU.

    Occurrence: This record will be created at regular time intervals, or when the

    failure occurred with reference to SD-card.

  • ISO9001:2008 Document No: IRS:S:99/2006 Version No.------- Date Effective :------

    Document Title: Draft Specification for Data Logger System for Railway S & T Installation

    Prepared By: SSRE/Signal Checked By : ADE/Signal Issued By: Director/Signal-III Printed: Page 55of 118

    BLOCK 0

    BLOCK 1

    TI = 34 H (1 byte)

    HELTH BYTES (3 bytes)

    Dummy (2 bytes )

    Reserved (3 bytes)

    BLOCK 2

    HEALTH BYTES:

    1ST BYTE

    2ND-BYTE 3RD - BYTE DESCRIPTION

    00 00 00 Back-up module is reset

    01 00 00 Back-up module is formatted due to no data

    01 00 01 Card formatted due to Boundary validation fail

    01 00 02 Card formatted due to Linearity validation fail

    02 00 00 Card not found at Power On/Reset

    02 01 00 Card not found in running condition

    03 00 00 Card failure at Power On/Reset due to erase failure

    03 01 00 Card fail at power on due to card functionality fail

    03 02 00 Card fail at running condition due to root directory sector fail

    03 03 00 Card fail at running condition due to more no. of bad sectors

  • ISO9001:2008 Document No: IRS:S:99/2006 Version No.------- Date Effective :------

    Document Title: Draft Specification for Data Logger System for Railway S & T Installation

    Prepared By: SSRE/Signal Checked By : ADE/Signal Issued By: Director/Signal-III Printed: Page 56of 118

    04 02 00 Retrieving completed

    04 03 00 Retrieving terminated abnormally

    05 00 Sector no. Root sector read operation fail

    05 01 Sector no. Root sector write operation fail

    MSB bits 01

    Bad sector count

    Card is in healthy condition and no. of bad data sectors in the card.

    Bad sec cnt

    09 Card size in MB Card size available.

    A.2.11 Secondary Data Backup Module Status Record:

    This record will be created to notify the health Data Logger SD Card to CMU.

    Occurrence: This record will be created at regular time intervals, or when the

    failure occurred with reference to SD-card.

    BLOCK 0

    BLOCK 1

    TI = 35 H (1 byte)

    HELTH BYTES (3 bytes)

    Dummy (2 bytes )

    Reserved (3 bytes)

    BLOCK 2

  • ISO9001:2008 Document No: IRS:S:99/2006 Version No.------- Date Effective :------

    Document Title: Draft Specification for Data Logger System for Railway S & T Installation

    Prepared By: SSRE/Signal Checked By : ADE/Signal Issued By: Director/Signal-III Printed: Page 57of 118

    HEALTH BYTES:

    1ST BYTE

    2ND-BYTE 3RD - BYTE DESCRIPTION

    00 00 00 Back-up module is reset

    01 00 00 Back-up module is formatted due to no data

    01 00 01