is456
TRANSCRIPT
-
7/28/2019 is456
1/14
7
Design of flat slabs by IS: 456
The term flat slab means a reinforced concrete slab with or without drops, supported generally without
beams, by columns with or without flared column heads (see Fig. 12). A flat slab may be solid slab or
may have recesses formed on the soffit so that the sof fit comprises a series of ribs in two directions.The recesses may be formed by removable or permanent filler blocks.
Components of flat slab design:
a) Column strip :
Column strip means a design strip having a width of 0.25 I,, but not greater than 0.25 1, on each side
of the column centre-line, where I, is the span in the direction moments are being determined,
measured centre to centre of supports and 1, is the -span transverse to 1,, measured centre to centre of
supports.
b) Middle strip :
Middle strip means a design strip bounded on each of its opposite sides by the column strip.
c) Panel:
Panel means that part of a slab bounded on-each of its four sides by the centre -line of a
Column or centre-lines of adjacent-spans.
Division into column and middle strip along:
Longer span Shorter span
1L =6.6 m , 2L
=5.6 m
( i ) column strip
= 0.252L = 1.4 m
But not greater than 0.251
L = 1.65 m
(ii) Middle strip
= 5.6 (1.4+1.4) = 2.8 m
1L =5.6 m , 2L
=6.6 m
( i ) column strip
= 0.25 2L = 1.65 m
But not greater than 0.251
L = 1.4 m
(ii) Middle strip
= 6.6 (1.4+1.4) = 3.8 m
-
7/28/2019 is456
2/14
8
d) Drops :
The drops when provided shall be rectangular in plan, and have a length in each direction not less than
one- third of the panel length in that direction. For exterior panels, the width of drops at right angles to
the non- continuous edge and measured from the centre -line of the columns shall be equal to one -half
the width of drop for interior panels.
Since the span is large it is desirable to provide drop.
Drop dimensions along:
Longer span Shorter span
1L =6.6 m , 2L =5.6 m
Not less than 1L /3 = 2.2 m
1L =5.6 m , 2L =6.6 m
Not less than1L /3 = 1.866 m
Hence provide a drop of size 2.2 x 2.2 m i.e. in column strip width.
e) column head :
Where column heads are provided, that portion of a column head which lies with in the largest right
circular cone or pyramid that has a vertex angle of 90and can be included entirely within the outlines
of the column and the column head, shall be considered for design purposes (see Fig. 2).
5.6 m
3.8 m
M.S
1.4 m
C.S
1.4 m
C.S
6.6 m
2.8 m
M.S
1.4 m
C.S
1.4 m
C.S
Fig 1:
-
7/28/2019 is456
3/14
9
Fig 2:
Column head dimension along:
Longer span Shorter span
1L =6.6 m ,
2L =5.6 m
Not greater than1
L /4 = 1.65 m
1L =5.6 m ,
2L =6.6 m
Not greater than1
L /4 = 1.4 m
Adopting the diameter of column head = 1.30 m =1300 mm
f) Depth of flat slab:
The thickness of the flat slab up to spans of 10 m shall be generally controlled by considerations of span
(L ) to effective depth ( d) ratios given as below:
Cantilever 7; simply supported 20; Continuous 26
For slabs with drops, span to effective depth ratios given above shall be applied directly; otherwise the
span to effective depth ratios in accordance with above shall be multiplied by 0.9. For this purpose, the
longer span of the panel shall be considered. The minimum thickness of slab shall be 125 mm.
-
7/28/2019 is456
4/14
10
Depth of flat slab:
Considering the flat slab as a continuous slab over a span not exceeding 10 m
L
d= 26
26
Ld
Depth considering along:
Longer span Shorter span
1L =6.6 m , 2L =5.6 m
6600
26 26
Ld =253.8 mm
Say 260 mm
1L =5.6 m , 2L =6.6 m
5600
26 26
Ld =215.3 mm
Say 220 mm
Taking effective depth of 25mm
Overall depth D = 260 +25 = 285 mm 125 mm (minimum slab thickness as per IS: 456)
It is safe to provide depth of 285 mm.
g) Estimation of load acting on the slab:
Dead load acting on the slab = 0.285 x 25 = 6.25 2/KN m = 1dw
Floor finishes etc. load on slab = 1.45 2/KN m = 2dw
Live load on slab = 7.75 2/KN m = lw
Total dead load = 1dw + 2dw =7.72/KN m = dw
-
7/28/2019 is456
5/14
11
The design live load shall not exceed three times the design dead load.
Check:
7 . 7 51 .0 0 6 3
7 .7
l
d
wo k
w
Total design load =2
15.45 KN/md l
w w
h) Total Design Moment for a Span
The absolute sum of the positive and average and is given by negative bending moments in each
direction shall be taken as:
0
8
nW l
M
0M = total moment.
W= design load on an area 1 2l l
nl = clear span extending from face to face of columns, capitals, brackets or walls, but not less than
0.651
l
1l = length of span in the direction of
0M .
2l = length of span transverse to 1l .
Circular supports shall be treated as square supports havi ng the same area.Equivalent side of the column head having the same area:
2 2(1.3) 1.1524 4
a d m
Clear span along long span = nl =1 1
6.6 (1.152) (1.152) 5.448 4.292 2
m
(Should not be less than 0.651
l ) ok
Clear span along long span = nl =1 15.6 (1.152) (1.152) 4.44 3.642 2
m m
(Should not be less than 0.651
l ) ok
-
7/28/2019 is456
6/14
12
Total design load along:
Longer span Shorter span
nl =5.448 m , 2l =5.6 m
2 nW w l l
15.45 5.6 5.448 471.36W K N
nl =4.44 m , 2l =6.6 m
2 nW w l l
1 5 . 4 5 6 . 6 4 . 4 4 4 5 2 . 7 4W K N
The absolute sum of ve and +ve moment in a panel along:
Longer span Shorter span
nl =5.448 m , 2l =5.6 m
0
4 7 1 . 3 6 5 . 4 4 8
8 8
nW l
M
03 2 0 . 9 9M K N m
nl =4.44 m , 2l =6.6 m
0
4 5 2 . 7 4 4 . 4 4
8 8
nW l
M
02 5 1 . 2M K N m
(i) Negative and Positive Design Moments:
The negative design moment shall be at the fac e of rectangular supports, circular supports being
treated as square supports having the same 31.4.5.1 Columns built integrally with the slab system
area. Shall be designed to-resist moments arising from loads .
In an interior span, the total design moment 0M shall be distributed in the following proportions:
Negative design moment 0.65
Positive design moment 0.35
In an end span, the total design moment0
M shall be distributed in the following proportions:
Interior negative design moment: 1
0.100.75
1c
Positive design moment: 1
0.280.63
1c
-
7/28/2019 is456
7/14
13
Exterior negative design moment: 1
0.65
1c
c Is the ratio of flexural stiffness of the exterior columns to the flexural stiffness of the slab at a
joint taken in the direction moments are being determined and is given by:
c
c
s
K
K
cK =sum of the flexural stiffness of the columns meeting at the joint.
sK =flexural stiffness of the slab, expres sed as moment per unit rotation
It shall be permissible to modify these design moments by up to 10 percent, so lon g as the total
design moment0M for the panel in the direction considered is not less than that required by:
0
8
n
W lM
The negative moment section shall be designed to resist the larger of the two interior negative
design moments determined for the spans framing into a common support unless an analysis is
made to distribute the unbalanced moment in accordance with the stiffness of the adjoining parts.
Column strip :
Negative moment at an interior support: At an interior support, the column strip shall be
designed to resist 75 percent of the total negative moment in the panel at that support.
Negative moment at an exterior support:
a) At an exterior support, the column strip shall be designed to resist the t otal negative moment inthe panel at that support.
b) Where the exterior support consists of a column or a wall extending for a distance equal to or
greater than three-quarters of the value of 2l . The length of span transverse t o the direction
moments are being determined, the exterior negative moment shall be considered to be uniformly
distributed across the length 2l .
Positive moment for each span: For each span, the column strip shall be designed to r esist 60
percent of the total positive moment in the panel.
Moments in the middle strip:
a) That portion of-the design moment not resisted by the column strip shall be assigned to the
adjacent middle strips.
-
7/28/2019 is456
8/14
14
b) Each middle strip shall be proportione d to resist the sum of the moments assigned to its two half
middle strips. cl The middle strip adjacent and parallel to an edge supported by a wall shall be
proportioned, to resist twice the moment assigned to half the middle strip corresponding to the fir st
row of interior columns.
Stiffness calculation:
let the height of the floor = 4.0 m
clear height of the column = height of floor depth of drop thickness of slab thickness of head.
= 4000 140 285 300 = 3275 mm
Effective height of column = 0.8 x 3275 = 2620 mm
(Assuming one end hinged and other end fixed)
stiffness coefficient
sum of f lexura l s t i f fness of co lum n a c t i ng a t the jo in t
f lexu ra l s t if fness o f the s labc
c
s
K
K
Longer span
34 2 4 520 104 4 4 4 502 2
12 327.5c
BOTTOM TOP
EEI EI EI EK
L L L L
34 660 28.5 2 4 1587.731.39
12 560 4 2273.5
cS C
s
E K EK
K E
From table 17 of IS: 456-2000
2 L
1 D
, m i n
, m i n
W0 . 8 4 8 & 1 . 0 0
W
0 . 7c
c c
L
L
Hence correction for pattern of loading in the direction of longer span is not required.
-
7/28/2019 is456
9/14
15
Shorter span
42 (50)3975.8
12 262cK
3
560 28.5 1421.412 760
3975.82.79
1421.4
c
c
K
From table 17 of IS: 456-2000 for
2 L
1 D
,m in
,m in
W1 .17 & 1 .00
W
0 . 7 5
o k
c
c c
L
L
Hence the correction for pattern loading in the direction of short span is not required.
From table 17 of IS 456-2000
Imposed load/dead loadRatio 2
1
l
lValue of ,min
c
(1) (2) (3)
0.5
1.0
1.0
1.0
1.0
1.0
2.0
2.0
2.0
2.02.0
3.0
3.0
3.0
3.0
3.0
0.5 to 2.0
0.5
0.8
1.0
1.25
2.0
0.5
0.8
1.0
1.252.0
0.5
0:8
1.0
1.25
2.0
0
0.6
0.7
0.7
0.8
1.2
1.3
1.5
1.6
1.94.9
1.8
2.0
2.3
2.8
13.0
-
7/28/2019 is456
10/14
16
Distrubution of bending moment across the panel width
It is an exterior panel.
Longer span
column strip
-ve B.M at exterior support = 00 . 6 5 0 .6 5 3 2 0 .9 91 .0 1 .0 1 2 1 .3 4 K N m1 1
1 11 . 3 9
c
M
+ve span BM =0
0 .2 8 0 .2 80 .6 3 0 .6 0 0 .6 3 3 2 0 .9 9 0 .6 0 9 0
1 11 1
1 . 3 9c
M K N m
-ve span BM at interior support =
0
0 .1 0 0 .1 00 .7 5 0 .7 5 0 .7 5 3 2 0 .9 9 0 .7 5 1 6 6 .5 0 K N m
1 11 1
c c
M
Middle strip
-ve BM at exterior support = 00 . 6 5 0 . 0 0 . 0 K N m1
1c
M
+ve span BM =0
0 .2 8 0 .2 80 .6 3 0 .4 0 0 .6 3 3 2 0 .9 9 0 .4 0 5 9 .9 6
1 11 1
1 . 3 9c
M K N m
-ve BM at interior support =
0
0 .1 0 0 .1 00 .7 5 0 .7 5 0 .7 5 3 2 0 .9 9 0 .2 5 5 5 .5 0 K N m
1 1
1 1 1 . 3 9c
M
-
7/28/2019 is456
11/14
17
Short span
column strip
-ve moment at exterior support = 00 . 6 5 0 .6 5 2 5 1 .21 .0 1 .0 1 2 0 .1 9 K N m1 1
1 12 . 7 9
c
M
+ve moment0.28
0.63 251.2 0.60 63.881
12.79
KNm
-ve moment at exterior support =
0
0 .1 0 0 .1 00 .7 5 0 .7 5 0 .7 5 2 5 1 .2 0 .7 5 1 2 7 .4 3 K N m
1 11 1
2 . 7 9c
M
Middle strip
-ve moment at exterior support = 00 . 6 5 0 . 0 0 . 0 K N m1
1c
M
+ve mid-span moment =0
0 .2 8 0 .2 80 .6 3 0 .4 0 0 .6 3 2 5 1 .2 0 .4 0 4 2 .5 9
1 11 1
2 . 7 9c
M K N m
-ve moment at interior span =
0
0 .1 0 0 .1 00 .7 5 0 .7 5 0 .7 5 2 5 1 .2 0 .2 5 4 2 .4 4 K N m
1 11 1
2 . 7 9c
M
j) Effective depth of the slab
Thickness of the slab, from consideration of maximum positive moment any where in the slab.
Maximum +ve BM occurs in the column strip (long span) = 90.91 KNm
factored moment = 1.50 x 90.91 = 136.36 KNm
-
7/28/2019 is456
12/14
18
2
0
6
0.138 ( 2800 mm)
136.36 10d= (M-20 grade concrete)
0.138 20 2800
d=132.83 mm 140 mm
ckM f bd b
Using 12 mm (diameter) main bars.
Overall thickness of slab =12
140 15 161 mm 170 mm2
Depth (along longitudinal direction) =12
170 15 150 mm2
Depth (along longitudinal direction) = 150 12 138 mm
k) Thickness of drop from maximum ve moment consideration
Thickness of drop from consideration of maximum ve moment any where in the panel.
Max ve BM occurs in the column strip = 166.6 KNm2
6 2
0.138
1.5 166.6 10 0.138 20 1400
254.3 mm
u ckM f bd
d
d
Say 260 mm. Use 12 mm bars
Over all thickness of flat slab:12
260 15 281 mm2
D
1300 mm
300 mm
300
mm
045 5.6 m
6.6 m
2340 mm
2200 mm
d/2
d/2
1.3 m
d/2
d/2
-
7/28/2019 is456
13/14
19
l) Shear in Flat Slab
The critical section for shear shall be at a distance d/2 from the periphery of the
column/capital/ drop panel, perpendicular to the plane of the slab where d is the effective
depth of the section (Fig. 2). The shape in plan is geometrically similar to the support
immediately below the slab.
check for shear stress developed in slab
The critical section for shear for the slab will be at a distance d/2 from the face of drop.
Perimeter of critical section = 4 x 2340 = 9340 mm
Total factored shear force:
0 1 21.5 15.45 [ (2.34)(2.34)]
= 1.5 15.45 [6.6 5.6-(5.47)]
= 729.78 KN
V L L
Nominal shear stress =3
2729.78 10 0.55 N/mm9340 140
uv
V
bd
shear strength of concrete = 20.25 =0.25 20 =1.11 N/mmc ckf
Permissible shear stress = v s ck
2
v
(0.5 ), 0.848
(0.5 0.848)
1.348 1 1
1 1.11
1.11 N/mm
safe design ok
if 1.5 then the slab should be re-designed
s c c
s
s
v c
c
k
k
k
m) check for shear in drop
0 0
2
( ) (1.3 0.26) 4.89 m
V=1.5 15.45[5.6 6.6- (1.3 0.26) ]4
V 812.27 KN
b D d
Nominal shear stress :
32
2
812.27 100.683 N/mm
4890 260
0.25 1.11 N/mm
[safe in shear]
v
c ck
v c
f
-
7/28/2019 is456
14/14
20
n) Reinforcement details
Longer span
-ve exterior reinforcement:
6
2
0.87 [ 0.42 ]
1.5 121.34 10 0.87 415 [150 0.42 0.48 150]4209 mm
u y st u
st
st
M f A d x
AA
Use 12 mm bars =4209
38 No.s113
1.4 1000c/c spacing is = 36 mm c/c
38
+ve steel:-6
2
1.5 90 10 43239.3
3122 mm
3122
Use 12 mm bars = 28 .113
3.8 1000/ spacing = 135 mm c/c
28
st
st
A
A
No s
c c
Reinforcement along shorter span:
Column strip:
6
2
0.87 [ 0.42 ]
1.5 127.5 10 0.87 415 [140 0.42 0.48 140]
3768.9 mm
u y st u
st
st
M f A d x
A
A
Use 12 mm bars =2
3768.933 No.s
(12)
4
1.4 1000c/c spacing is = 42 mm c/c
33
Middle strip:
6
2
0.87 [ 0.42 ]
1.5 63.88 10 0.87 415 [281 0.42 0.48 281]1182 mm
u y st u
st
st
M f A d x
AA
Use 12 mm bars =2
118210 No.s
(12)
4
2.8 1000c/c spacing is = 280 mm c/c
10