I/O Wiring Conversion Systems PLC-5 1771 to ControlLogix 1756
Selection Guide
2 Rockwell Automation Publication 1492-SG121E-EN-P - July 2016
I/O Wiring Conversion Systems
What’s Inside
Summary of ChangesThis publication contains new and updated information as indicated in the following table.
Topic Page
Product Selection 3
Approximate Dimensions 11
Wiring Diagrams - Digital Inputs 19
Wiring Diagrams - Digital Outputs 47
Wiring Diagrams - Analog Inputs and Outputs 77
Wiring Diagrams - High Resolution Isolated Analog 103
Topic Page
Analog Inputs and Outputs Product Selection - added new options for 1771-IL, 1771-OFE1 and 1771-OFE2 conversions
7
1771-N High Resolution Isolated Analog I/O Modules - New conversion options in standard and combination
8
Product Selection
1771 I/O to 1756 I/O Conversion Modules
I/O Conversion Modules provide a fast and efficient method for converting 1771 PLC-5 I/O to 1756 ControlLogix I/O. The I/O conversion is accomplished without removing any field wires from the existing swing arm, virtually removing the risk of wiring errors. The existing swing arms fit directly onto the edge connector of the conversion modules.
The cables are pre-wired and have a connector for the conversion module on one end and a removable terminal block (RTB) on the other end. The I/O signals are routed through the conversion module and the cable to the appropriate terminals on the I/O module.
The I/O Conversion System includes:• Conversion Modules (Ex: Cat No: 1492-CM1771-LD001)• Cables (Ex: Cat No: 1492-CONACAB005X)• Conversion Mounting Assembly (Ex: Cat No: 1492-MUA4-A13-A17)
Conversion Modules, Cables, and Mounting Assemblies
Conversion Modules Pre-wired Cables, 25-pin
Base Plate Cover PlateThe Conversion Modules are housed in a Conversion Mounting Assembly Base Plate. This base plate has the same footprint and mounting holes as the 1771 chassis. There is no need to drill and tap new mounting holes in the control cabinet.
The Conversion Mounting Assembly Cover Plate covers and helps protectthe Conversion Modules while providing a place to mount the new 1756 chassis. The Cover Plate has pre-drilled and tapped mounting holes allowing the new 1756 chassis to be mounted in several locations – centered, right-justified or left-justified. There is no need to drill and tap new mounting holes in the control cabinet.
Pre-wired Cables, 37-pin
Rockwell Automation Publication 1492-SG121E-EN-P - July 2016 3
Product Selection
Conversion Mounting Assembly Selection
Conversion Modules must be installed in a 1492 Conversion Mounting Assembly (see table below, a complete System Installation Manual is included with each assembly. Use the following steps to select the proper conversion mounting assembly:
1. Determine the quantity of each type of 1771 I/O modules used in the I/O chassis to be converted.
2. From the table below:a. Select the applicable 1492 conversion modules b. Review the Max Slots for I/O and Chassis Width data from the table belowc. Select a 1756 I/O chassis which has enough I/O slots. Two I/O slots are required in the 1756 chassis for conversions
where one 1771 I/O module converts to two 1756 I/O modules.d. Select the conversion mounting assembly which has enough conversion module slots.
(2) conversion module slots are required in the conversion mounting assembly for conversions where (2) 1771 I/O modules convert to (1) 1756 I/O modules.
The combined depth of the conversion mounting assembly with the 1756 chassis mounted on top is 10.25 inches (controller w/key) or 10.0 inches (controller w/o key). Dimension drawings are included in the System Installation Manual that ships with the Assembly.
Chassis Dimensions and Max Slot Information
1771 Chassis 1756 Chassis Conversion Mounting Assembly
Cat. No.Max Slots
for I/O
Chassis Width(2)
in (mm)
(2) Notice that the 1756 Chassis Width sometimes exceeds the 1771 Chassis Width, with or without the Power Supply. The Cover-Plate of the 1492 Conversion Mounting Assembly allows the 1756 Chassis to be Left justified, Right justified or Centered. A complete System Installation Manual ships with the 1492 Conversion Mounting Assembly.
Cat. No.Max Slots
for I/O
Chassis Width
in (mm) Cat. No.
Max Slots for Conversion
ModulesChassis Width
in (mm)
Without Power Supply
With Power Supply
1771-A1B 4 9.01 (229) 12.61 (320)1756-A4 3 10.35 (263)
1492-MUA1B-A4-A7 4 9.01 (229)1756-A7 6 14.49 (368)
1771-A2B 8 14.01 (356) 17.61 (447)1756-A7 6 14.49 (368)
1492-MUA2B-A7-A10 8 14.01 (356)1756-A10 9 19.02 (483)
1771-A3B1(1)
(1) 1771-A3B is not listed as it is used for 19 inch wide instrumentation panels.
12 19.01 (483)1756-A10 9 19.02 (483)
1492-MUA3B-A10-A13 12 19.01 (483)1756-A13 12 23.15 (588)
1771-A4B 16 24.01 (610)1756-A13 12 23.15 (588)
1492-MUA4-A13-A17 16 24.01 (610)1756-A17 16 29.06 (738)
4 Rockwell Automation Publication 1492-SG121E-EN-P - July 2016
Product Selection
Digital Inputs
1. Column 1: find the Catalog Number of the 1771 Module you are converting from.
2. Column 2: find the Catalog Number of the compatible 1756 Module you are converting to. In some cases more than one module exists. Review the matrix carefully and review the I/O module Installation Manuals to determine full compatibility.
3. Column 3: find the Conversion Module catalog number and order quantity.
4. Column 4: find the Conversion Cable catalog number and order quantity.
1 2 3 4 5
Converting From 1771 Module(1)
(1) To understand any issues concerning I/O module compatibility refer to the conversion module wiring diagrams and the Installation Manuals for the specific I/O modules involved (with particular attention to the specification and wiring instructions).
Qty. Converting to 1756 Module Qty.
Conversion Module Conversion Cable(3)
(3) The 005 in the Cat. No. indicates cable length of the 1492 cable. The recommended length of 0.5 M is listed, additional lengths are listed below.
1.0M Cable = 1492-CONCAB010_, 1.0M/1.0M Cable= 1492-C010010X_,0.5M/1.0M Cable = 1492-C005010X_,1.0M/0.5M Cable = 1492-C010005X_
Wiring Diagram
Cat. No. Order Cat. No. Order Page
1771-IA 2 1756-IA16 1 1492-CM1771-LD007 2 1492-C005005XE 1 19
1771-IA2 2 1756-IA16 1 1492-CM1771-LD007 2 1492-C005005XE 1 19
1771-IAD 1 1756-IA16 1 1492-CM1771-LD001 1 1492-CONCAB005X 1 20
1771-IAD 1 1756-IH16I 1 1492-CM1771-LD002 1 1492-CONCAB005Y 1 21
1771-IAN 1 1756-IA32 1 1492-CM1771-LD003 1 1492-CONCAB005Z 1 22
1771-IB 2 1756-IB16 1 1492-CM1771-LD007 2 1492-C005005XE 1 23
1771-IBD 1 1756-IB16 1 1492-CM1771-LD001 1 1492-CONCAB005X 1 24
1771-IBN 1 1756-IB32 1 1492-CM1771-LD003 1 1492-CONCAB005Z 1 25
1771-IC 2 1756-IC16 1 1492-CM1771-LD007 2 1492-C005005XE 1 26
1771-ICD 1 1756-IC16 1 1492-CM1771-LD001 1 1492-CONCAB005X 1 27
1771-ID 2 1756-IA16I 1 1492-CM1771-LD012 2 1492-C005005XL 1 28
1771-ID01 2 1756-IM16I 1 1492-CM1771-LD012 2 1492-C005005XL 1 29
1771-ID16 1 1756-IA16I 1 1492-CM1771-LD004 1 1492-CONCAB005Y 1 30
1771-ID16 1 1756-IH16I 1 1492-CM1771-LD004 1 1492-CONCAB005Y 1 31
1771-IG 2 1756-IG16 1 1492-CM1771-LA003(2)
(2) These 1771 Digital I/O Modules use a Swing Arm that only mounts to these Analog I/O Conversion Modules, which will therefore be used to provide for these 1771 Digital I/O conversions.
2 1492-C005005XS 1 32
1771-IGD 1 1756-IG16 1 1492-CM1771-LD006 1 1492-CONCAB005X 1 33
1771-IH 2 1756-IC16 1 1492-CM1771-LD007 2 1492-C005005XE 1 34
1771-IM 2 1756-IM16I 1 1492-CM1771-LD007 2 1492-C005005XH 1 35
1771-IMD 1 1756-IM16I 1 1492-CM1771-LD002 1 1492-CONCAB005Y 1 36
1771-IN 2 1756-IN16 1 1492-CM1771-LD007 2 1492-C005005XE 1 37
1771-IND 1 1756-IN16 1 1492-CM1771-LD001 1 1492-CONCAB005X 1 38
1771-IND1 1 1756-IN16 1 1492-CM1771-LD001 1 1492-CONCAB005X 1 39
1771-IQ 2 1756-IB16I 1 1492-CM1771-LD007 2 1492-C005005XK 1 40
1771-IQ 2 1756-IB16I 1 1492-CM1771-LD014 2 1492-C005005XJ 1 41
1771-IQ16 1 1756-IB16I 1 1492-CM1771-LD004 1 1492-CONCAB005Y 1 42
1771-IT 2 1756-IB16 1 1492-CM1771-LD007 2 1492-C005005XE 1 43
1771-IV 2 1756-IV16 1 1492-CM1771-LD014 2 1492-C005005XG 1 44
1771-IVN 1 1756-IV32 1 1492-CM1771-LD005 1 1492-CONCAB005Z 1 45
Rockwell Automation Publication 1492-SG121E-EN-P - July 2016 5
Product Selection
Digital Outputs
1. Column 1: find the catalog number of the 1771Module you are converting from.
2. Column 2: find the catalog number of the compatible 1756 Module you are converting to. In some cases more than one module exists. Review the matrix carefully and review the I/O module Installation Manuals to determine full compatibility.
3. Column 3: find the catalog number of the Conversion Module.
4. Column 4: find the catalog number of the Conversion Cable.
1 2 3 4 5
Converting from 1771 Module(1)
(1) To understand any issues concerning I/O module compatibility refer to the conversion module wiring diagrams and the Installation Manuals for the specific I/O modules involved (with particular attention to the specification and wiring instructions).
Converting to 1756 Module Conversion Module Conversion Cable(4)
(4) The 005 in the Cat. No. indicates cable length of the 1492 cable. The recommended length of 0.5 M is listed, additional lengths are listed below.
1.0M Cable = 1492-CONCAB010_, 1.0M/1.0M Cable= 1492-C010010X_0.5M/1.0M Cable = 1492-C005010X_, 1.0M/0.5M Cable = 1492-C010005X_
Wiring Diagram
Cat. No. Qty. Cat. No. Qty.(2)
(2) Where two is indicated, these modules need to be located directly next to each other in the 1756 chassis.
Cat. No. (3)
(3) An “F” at the end of the 1756 catalog number indicates that it is fused to match the functionality of the 1771 module being replaced.
Order Qty. Cat. No. Order Qty. Page
1771-OA 1 1756-OA8E 1 1492-CM1771-LD014 1 1492-CONCAB005U 1 47
1771-OAD 1 1756-OA16 1 1492-CM1771-LD006 1 1492-CONCAB005X 1 48
1771-OAN 1 1756-OA16 2 1492-CM1771-LD013 1 1492-CONCAB005S3 1 49
1771-OB 2 1756-OB16D 1 1492-CM1771-LD014 2 1492-C005005XF 1 50
1771-OBD 1 1756-OB16E 1 1492-CM1771-LD006 1 1492-CONCAB005X 1 51
1771-OBD 1 1756-OC8 2 1492-CM1771-LD008F 1 1492-CONCAB005S1 1 52
1771-OBDS 1 1756-OB16E 1 1492-CM1771-LD006 1 1492-CONCAB005X 1 53
1771-OBN 1 1756-OB32 1 1492-CM1771-LD009F 1 1492-CONCAB005Z 1 54
1771-OC 1 1756-OC8 1 1492-CM1771-LD014 1 1492-CONCAB005V 1 55
1771-OD 2 1756-OA16I 1 1492-CM1771-LD012 2 1492-C005005XM 1 56
1771-OD16 1 1756-OA16I 1 1492-CM1771-LD010F 1 1492-CONCAB005Y 1 57
1771-ODD 1 1756-OA16I 1 1492-CM1771-LD010F 1 1492-CONCAB005Y 1 58
1771-ODZ 2 1756-OA16I 1 1492-CM1771-LD012 2 1492-C005005XP 1 59
1771-OG 2 1756-OG16 2 1492-CM1771-LA003 2 1492-C005005XS 1 60
1771-OGD 1 1756-OG16 2 1492-CM1771-LD006 1 1492-CONCAB005X 1 61
1771-OM 2 1756-OA16 1 1492-CM1771-LD014 2 1492-C005005XG 1 62
1771-OMD 1 1756-OA16 1 1492-CM1771-LD006 1 1492-CONCAB005X 1 63
1771-ON 1 1756-ON8 1 1492-CM1771-LD014 1 1492-CONCAB005W 1 64
1771-OND 1 1756-ON8 2 1492-CM1771-LD006 1 1492-CONCAB005S2 1 65
1771-OQ 2 1756-OB16I 1 1492-CM1771-LA004 2 1492-C005005XT 1 66
1771-OQ16 1 1756-OB16I 1 1492-CM1771-LD010F 1 1492-CONCAB005Y 1 67
1771-OR 2 1756-OA16I 1 1492-CM1771-LD012 2 1492-C005005XR 1 68
1771-OVN 1 1756-OV16E 2 1492-CM1771-LD013 1 1492-CONCAB005S3 1 69
1771-OW 1 1756-OX8I 1 1492-CM1771-LD012 1 1492-CONCAB005Y 1 70
1771-OW16 1 1756-OW16I 1 1492-CM1771-LD011 1 1492-CONCAB005Y 1 71
1771-OWNA 1 1756-OW16I 2 1492-CM1771-LD013 1 1492-CONCAB005S4 1 72
1771-OY 1 1756-OX8I 1 1492-CM1771-LD012 1 1492-CONCAB005Y 1 73
1771-OYL 1 1756-OX8I 1 1492-CM1771-LD012 1 1492-CONCAB005Y 1 74
1771-OZ 1 1756-OX8I 1 1492-CM1771-LD012 1 1492-CONCAB005Y 1 75
1771-OZL 1 1756-OX8I 1 1492-CM1771-LD012 1 1492-CONCAB005Y 1 76
6 Rockwell Automation Publication 1492-SG121E-EN-P - July 2016
Product Selection
Analog Inputs and Outputs
1. Column 1: find the catalog number of the 1771Module you are converting from.
2. Column 2: find the catalog number of the compatible 1756 Module you are converting to. In some cases more than one module exists. Review the matrix carefully and review the I/O module Installation Manuals to determine full compatibility.
3. Column 3: find the catalog number of the Conversion Module.
4. Column 4: find the catalog number of the Conversion Cable.
1 2 3 4 5
Converting from 1771 Module Converting to 1756 Module Conversion Module Conversion Cable Wiring Diagram
Cat. No. Qty. Cat. No. Description Qty. Cat. No. Order Qty. Cat. No. Order Qty. Page
1771-IFE 1 1756-IF16
Differential Current 1 1492-CM1771-LA002 1 1492-CONACAB005D 1 77
Differential Voltage 1 1492-CM1771-LA002 1 1492-CONACAB005C 1 78
Single End Current 1 1492-CM1771-LA001 1 1492-CONACAB005B 1 79
Single End Voltage 1 1492-CM1771-LA001 1 1492-CONACAB005A 1 80
1771-IFF 1 1756-IF16
Differential Current 1 1492-CM1771-LA002 1 1492-CONACAB005D 1 81
Differential Voltage 1 1492-CM1771-LA002 1 1492-CONACAB005C 1 82
Single End Current 1 1492-CM1771-LA001 1 1492-CONACAB005B 1 83
Single End Voltage 1 1492-CM1771-LA001 1 1492-CONACAB005A 1 84
1771-IL 1
1756-IF8ICurrent 1 1492-CM1771-LA004 1 1492-CONACAB005K8 1 85
Voltage 1 1492-CM1771-LA004 1 1492-CONACAB005L8 1 86
1756-IF6I (6-ch)
Current 1 1492-CM1771-LA004 1 1492-CONACAB005K 1 87
Voltage 1 1492-CM1771-LA004 1 1492-CONACAB005L 1 88
1756-IF6I (2x 4-ch)
Current 2 1492-CM1771-LA004 1 1492-CONACAB005T1 1 89
Voltage 2 1492-CM1771-LA004 1 1492-CONACAB005T2 1 90
1771-IR 11756-IRT8I RTD 1 1492-CM1771-LA004 1 1492-CONACAB005F8 1 91
1756-IR6I RTD 1 1492-CM1771-LA004 1 1492-CONACAB005F 1 92
1771-IXE 11756-IT6I2 Thermocouple 1 1492-CM1771-LA005 1 1492-CONACAB005G 1 93
1756-IRT8I Thermocouple 1 1492-CM1771-LA005 1 1492-CONACAB005G8 1 94
1771-IXHR 11756-IT6I2 Thermocouple 1 1492-CM1771-LA005 1 1492-CONACAB005G 1 95
1756-IRT8I Thermocouple 1 1492-CM1771-LA005 1 1492-CONACAB005G8 1 96
1771-OFE1
1 1756-OF6VI Voltage 1 1492-CM1771-LA003 1 1492-CONACAB005E 1 97
1 1756-OF8I Voltage 1 1492-CM1771-LA003 1 1492-CONACABOO5E8V 1 98
2 1756-OF8I Voltage 1 1492-CM1771-LA003 2 1492-C005005E8V 1 99
1771-OFE2
1 1756-OF6CI Current 1 1492-CM1771-LA003 1 1492-CONACAB005E 1 100
1 1756-OF8I Current 1 1492-CM1771-LA003 1 1492-CONACABOO5E8C 1 101
2 1756-OF8I Current 1 1492-CM1771-LA003 2 1492-C005005E8C 1 102
Rockwell Automation Publication 1492-SG121E-EN-P - July 2016 7
Product Selection
1771-N High Resolution Isolated Analog I/O Modules
The 1771-N High Resolution Analog I/O modules are designed for use with 1771-RTPs (Remote Termination Panels) and connected by a 6 or 15 foot cable (Cat. No. 1771-NC6 or 1771-NC15). The conversion of the 1771-N Series I/O to a 1756 ControlLogix I/O can be accomplished without the removal of any field wires from the existing 1771-RTPs.
Simply replace the (2) existing 1771 cables with (2) of the following cables in the table below. Each of these cables has a connector on one end that attaches directly to the existing 1771-RTP and a 1756 RTB (Removable Terminal Block) on the other end for connection to the ControlLogix I/O module.
Use the following steps to select the proper conversion cables:
1. Column 2: find the catalog number of the 1771 Digital I/O module.
2. In column 3, find the catalog number of the compatible 1756 Digital I/O module. In some cases more than one module is required. Review the matrix and the I/O module installation manuals to determine full compatibility
3. In column 4, find the catalog numbers and descriptions of the appropriate cables.
1 2 3 4 5
I/O DescriptionConvert From: Convert To:
Cable DescriptionConversion Cable Catalog Number Wiring
Diagram Page
1771 Module Qty. 1756
Module Qty. Cable "A" Cable "B"
Standard 1771-N High Resolution I/O
1771-NOC
1 1756-OF8I 1 Current (8 Ch) 1492-CONACAB020N88 103
1 1756-OF8 1 Current (8 CH) 1492-CONACAB020N8 104
1 1756-OF6CI 2 Current (4/4 CH) 1492-CONACAB020N1 1492-CONACAB020N1 105
1771-NIS1 1756-IF8I 1 Current (8 CH) 1492-CONACAB020N38 106
1 1756-IF6CIS 2 Current (4/4 CH) 1492-CONACAB020N2 1492-CONACAB020N2 107
1771-NIV
1 1756-IF8I 1 Current (8 CH) 1492-CONACAB020N38 108
1 1756-IF6I 2 Current (4/4 CH) 1492-CONACAB020N3 1492-CONACAB020N3 109
1 1756-IF8I 1 Voltage (8 CH) 1492-CONACAB020N78 110
1 1756-IF6I 2 Voltage (4/4 CH) 1492-CONACAB020N7 1492-CONACAB020N7 111
1 1756-IF6I 2 Current (A - 4 CH) /Voltage (B - 4 CH)
1492-CONACAB020N3 1492-CONACAB020N7 112
1 1756-IF6I 2Voltage (A - 4 CH) / Current (B - 4 CH) 1492-CONACAB020N7 1492-CONACAB020N3 113
1771-NR1 1756-IRT8I 1 RTD (8 CH) 1492-CONACAB020N48 114
1 1756-IR6I 2 RTD (4/4 CH) 1492-CONACAB020N4 1492-CONACAB020N4 115
1771-NT11 1756-IRT8I 1 Thermocouple (8 CH) 1492-CONACAB020N68 116
1 1756-IT6I 2 Thermocouple (4/4 CH) 1492-CONACAB020N5 1492-CONACAB020N5 117
1771-NOV1 1756-OF8I 1 Voltage (8 CH) 1492-CONACAB020N18 118
1 1756-OF6VI 2 Voltage (4/4 CH) 1492-CONACAB020N5 1492-CONACAB020N1 119
1771-NIV11 1756-IF8I 1 Voltage (8 CH) 1492-CONACAB020N78 120
1 1756-IF6I 2 Voltage (4/4 CH) 1492-CONACAB020N7 1492-CONACAB020N7 121
1771-NT21 1756-IRT8I 1 Thermocouple (8 CH) 1492-CONACAB020N68 122
1 1756-IT6I2 2 Thermocouple (4/4 CH) 1492-CONACAB020N6 1492-CONACAB020N6 123
8 Rockwell Automation Publication 1492-SG121E-EN-P - July 2016
Product Selection
Specifications
Combination 1771-N High Resolution I/O
1771-NIVR
1
1756-IRT8I
1
RTD (4 CH) - 1492-CONACAB020N44124
1756-IF8I Voltage (4 CH) 1492-CONACAB020N74 -
1756-IR6I RTD (4 CH) - 1492-CONACAB020N4125
1756-IF6I Voltage (4 CH) 1492-CONACAB020N7 -
1756-IRT8I RTD (4 CH) - 1492-CONACAB020N44126
1756-IF8I Current (4 CH) 1492-CONACAB020N34 -
1756-IR6I RTD (4 CH) - 1492-CONACAB020N4127
1756-IF6I Current (4 CH) 1492-CONACAB020N3 -
1771-NIVT
1756-IRT8I Thermocouple (4 CH) - 1492-CONACAB020N54128
1756-IF8I Voltage (4 CH) 1492-CONACAB020N74 -
1756-IT6I Thermocouple (4 CH) - 1492-CONACAB020N5129
1756-IF6I Voltage (4 CH) 1492-CONACAB020N7 -
1756-IRT8I Thermocouple (4 CH) - 1492-CONACAB020N54130
1756-IF8I Current (4 CH) 1492-CONACAB020N34 -
1756-IT6I Thermocouple (4 CH) - 1492-CONACAB020N5131
1756-IF6I Current (4 CH) 1492-CONACAB020N3 -
Attribute Value
Dimensions (H x D x W) 300 x 111.25 x 38.1 mm (11.81 x 4.38 x 1.5 in.)
Approximate Shipping Weight 260g (0.57 lb)
Storage Temperature Storage Temperature -40...+85 °C (-40...+185 °F)
Operating Temperature Operating Temperature 0...+60 °C (+32...+140 °F)
Operating Humidity Operating Humidity 5...95% at +55 °C (+131 °F)
ShockNonoperating 50 g
Operating 30 g
Operational Vibration 2 g at 10...500 Hz
Agency Certifications UL Classified (UL File No. E113724)
CE Certifications Compliant for all applicable directives
Pollution Degree 2
Environmental Rating IP20
1 2 3 4 5
I/O DescriptionConvert From: Convert To:
Cable DescriptionConversion Cable Catalog Number Wiring
Diagram Page
1771 Module Qty. 1756
Module Qty. Cable "A" Cable "B"
Rockwell Automation Publication 1492-SG121E-EN-P - July 2016 9
Product Selection
Notes:
10 Rockwell Automation Publication 1492-SG121E-EN-P - July 2016
Approximate Dimensions
Dimensions are in. (mm).
Cat No. MUA1B-A4-A7 used with Cat No. 1756-A4
9.0[229.6 ]
11.1[281.7 ]
12.5[317.2 ]
5.4[137 ]
10.4[263.6 ]
6.1[154 ]
9.9[251.9 ]
11.1[281.7 ]
12.5[317.2 ]
2.4[60.1 ]
5.4[137 ]
2.4[60.2 ]
9.1[230.7 ]
10.4[264.1 ]
Left Justified
Right Justified
Rockwell Automation Publication 1492-SG121E-EN-P - July 2016 11
Approximate Dimensions
Cat No. MUA1B-A4-A7 used with Cat No. 1756-A7
9.9[251.9 ]
6.1[154 ]
9.0[229.6 ]]
2.4[60.2 ]]
12.5[317.2 ]
5.4[136.5 ]]
14.6[370.6 ]
11.1[281.7 ]
9.0[229.6 ]
4.1[104.5 ]
2.4[60.2 ]
12.5[317.2 ]
14.6[370.1 ]
5.4[137.3 ]
14.6[370.1 ]
9.1[231.9 ]
2.4[60.2 ]
12.5[317.2 ]
11.1[281.7 ]
5.4[137.3 ]
2.4[60.2 ]
Left Justified
Centered
Right Justified
12 Rockwell Automation Publication 1492-SG121E-EN-P - July 2016
Approximate Dimensions
Cat No. MUA2B-A7-A10 used with Cat No. 1756-A7
11.1[281.7 ]
12.5[317.3 ]
14.0[356.6 ]
.2[5.7 ]
2.4[59.7 ]
.3[7.8 ]
14.6[370.1 ]
5.4[136 ]
9.9[251.9 ]
6.1[154 ]
Centered
Rockwell Automation Publication 1492-SG121E-EN-P - July 2016 13
Approximate Dimensions
Cat No. MUA3-A10-A13 used with Cat No. 1756-A10
19.0[483.6 ]
2.4[60.2 ]
12.5[317.3 ]
5.4[137 ]
11.1[281.7 ]
19.2[486.9 ]
6.1[154.4 ]
9.9[252.3 ]
Centered
14 Rockwell Automation Publication 1492-SG121E-EN-P - July 2016
Approximate Dimensions
Cat No. MUA3-A10-A13 used with Cat No. 1756-A13
23.2[588 ]
2.4[60.2 ]
5.4[137 ]
.7[18 ]
19.0[483.6 ]
12.5[317.3 ]
11.1[281.7 ]
2.2[56.8 ]
1.9[47.4 ]
2.4[59.9 ]
19.0[483.6 ]23.2[588 ]
11.2[285.6 ]
23.2[588 ]
4.1[103.1 ]
2.4[60.2 ]
5.4[137 ] 11.1
[281.7 ]
9.6[243.9 ]
5.7[146 ]
5.4[137 ]
Left Justified
Centered
Right Justified
Rockwell Automation Publication 1492-SG121E-EN-P - July 2016 15
Approximate Dimensions
Cat No. MUA4-A13-A17 used with Cat No. 1756-A13
2.4[60.2 ]
24.0[610.6 ]
23.2[588 ]
12.5[316.7 ]
11.1[281.7 ]
5.4[137 ]
9.6[243.7 ]
5.7[145.9 ]
Centered
16 Rockwell Automation Publication 1492-SG121E-EN-P - July 2016
Approximate Dimensions
Cat No. MUA4-A13-A17 used with Cat No. 1756-A17
29.1[737.9 ]
24.0[610.6 ]
.2[6.2 ]
2.4[60.1 ]
4.8[121 ]
12.5[316.7 ]
11.1[281.7 ]
3.6[91.7 ]2.4
[60.1 ]
5.4[137 ]
1.4[35.6 ]
12.5[316.7 ]
11.1[281.7 ]
24.0[610.6 ]
5.1[130 ].4
60.1 ]
5.4[137 ]
11.1[281.7 ]
12.5[316.7 ]
24.0[610.6 ]
29.1[737.9 ]
29.1[737.9 ]
6.1[154 ]
9.9[251.9 ]
Left Justified
Centered
Right Justified
Rockwell Automation Publication 1492-SG121E-EN-P - July 2016 17
Approximate Dimensions
Notes:
18 Rockwell Automation Publication 1492-SG121E-EN-P - July 2016
Wiring Diagrams - Digital Inputs
1771-IA, IA2 to 1756-IA16
There are several key application considerations and system specifications (bottom of drawing) when using these components (conversion module, cable and input module). Read and understand these considerations before installation.
� This Bul. 1492 cable consists of 2 separate cables (cable “A” and cable “B”) wired to one 1756-IA16 RTB. Recommended cablelengths of 0.5 M / 0.5 M are shown. See table 2 for other lengths.
� The 1771-IA, -IA2 module is rated 87V to 138V AC and 97V to 138V DC. The 1756-IA16 module is rated 79V to 132V AC only.
� Refer to your 1771-IA, -IA2 and 1756-IA16 Installation Manual wiring schematics and diagrams for more details. [Reference Doc: 41170-952 (Version 02)]
� The input delay times for the 1771-IA, -IA2 module versus the 1756-IA16 module are as follows: 1771-IA, -IA2 1756-IA16 w/ 1492-C005005XEa) Off-to-On Delay 24ms (+/-10ms) 10ms max (plus selectable filter)b) On-to-Off Delay 24ms (+/-10ms) 8ms max (plus selectable filter)
Conversion Module Installation and Application Considerations
B
34567
A
1771-WA Swing ArmFrom 1771-IA , -IA2
1771-WA Swing ArmFrom 1771-IA , -IA2
012
Black
WhiteRed
Green
Orange
Blue
White/Black
Red/BlackGreen/Black
Orange/Black
1
19
345678910111213
15161718
20
14
2
24
212223
25
L1
L2
10L2-0
IN-01
IN-12
IN-23
IN-34
IN-45
IN-56
IN-67
IN-78
IN-811
IN-912
IN-1013
IN-1114
IN-1215
IN-1316
IN-1417
IN-1518
L2-120
9L2-0
19L2-1
CABLE “A”
CABLE “B”
Not used
Input 0Input 1
Input 2Input 3Input 4Input 5
Input 6
Input 7L2
B
34567
A012
1
19
345678910111213
15161718
20
14
2
24
212223
25
L1
L2
Not used
Input 8Input 9
Input 10Input 11Input 12Input 13
Input 14
Input 15L2
Black
WhiteRed
Green
Orange
Blue
White/Black
Red/BlackGreen/Black
Orange/Black
Conversion Module1492-CM1771-LD007
Conversion Module1492-CM1771-LD007
Cable1492-C005005XE� 1756-IA16
IMPORTANT
Rockwell Automation Publication 1492-SG121E-EN-P - July 2016 19
Wiring Diagrams - Digital Inputs
1771-IAD to 1756-IA16
Conversion Module Installation and Application Considerations� This Bul. 1492 cable consists of a cable wired to one 1756-IA16 RTB. Recommended cable lengths of 0.5M or 1.0M (005=0.5M, 010=1.0M). See table 2 for other lengths.
� The input delay times for the 1771-IAD module versus the 1756-IA16 module are as follows: 1771-IAD 1756-IA16 w/ 1492-CONCAB005Xa) Off-to-On Delay 5ms (+/-3ms) @120VAC 10ms max (plus selectable filter)b) On-to-Off Delay 25ms (+/-5ms) 8ms max (plus selectable filter)
� The 1771-IAD module is rated 79V to 138V AC or DC. The 1756-IA16 module is rated 74V to 132V AC. If the inputsource voltage is DC use a 1756-IH16l and 1492-CM1771-LD002 conversion module.
� Refer to your 1771-IAD and 1756-IA16 Installation Manual wiring schematics and diagrams for more details. [Reference Doc: 41170-925 (Version 02)]
10L2-0
IN-01
IN-12
IN-23
IN-34
IN-45
IN-56
IN-67
IN-78
IN-811
IN-912
IN-1013
IN-1114
IN-1215
IN-1316
IN-1417
IN-1518
Black
WhiteRed
Green
Orange
Blue
White/Black
Red/BlackGreen/Black
Orange/BlackBlue/Black
Black/White
Red/White
Green/White
Blue/White
Black/Red
White/Red
Orange/Red
Blue/Red
Red/GreenL2-1
20
9L2-0
19L2-1
A
1
00
19
013
024
035
046
057
068
079
E
10111012111312
13151416151716
17 18
20
14
2
Input 14
Input 16Input 15
Input 17
Input 04
Input 06Input 05
Input 07
Input 00
Input 02Input 01
Input 03
Input 10
Input 12Input 11
Input 13
Terminal A
Terminal E
BCD
Terminal BTerminal CTerminal D
L1
L2
24
212223
25
1756-IA16
1771-WH Swing ArmFrom 1771-IAD
There are several key application considerations and system specifications (bottom of drawing) when using these components (conversion module, cable and input module). Read and understand these considerations before installation.
Conversion Module1492-CM1771-LD001
Cable1492-CONCAB005X�
IMPORTANT
20 Rockwell Automation Publication 1492-SG121E-EN-P - July 2016
Wiring Diagrams - Digital Inputs
1771-IAD to 1756-IH16I
1756-IH16I
1771-WH Swing ArmFrom 1771-IAD
There are several key application considerations and system specifications (bottom of drawing) when using these components (conversion module, cable and input module). Read and understand these considerations before installation.
WARNING
Conversion Module Installation and Application Considerations� The input delay times for the 1771-IAD module versus 1756-IH16I module are as follows: 1771-IAD 1756-IH16Ia) Off-to-On Delay 3ms @120V DC 2ms (plus selectable filter)b) On-to-Off Delay 25ms (+/-5ms) 6ms (plus selectable filter)� The 1771-IAD module is rated 79V to 138V AC or DC. The 1756-IH16I module is rated 90V to 146V DC. If the inputspurce voltage is AC use a 1756-IA16 and 1492-CM1771-LD002 conversion module.� Refer to your 1771-IAD and 1756-IH16I Installation Manual wiring schematics and diagrams for more details.
[Reference Doc: 41170-927 (Version 02)]
A
00
01
02
03
04
05
06
07
E
10
11
12
13
14
15
16
17
Input 14
Input 16
Input 15
Input 17
Input 04
Input 06
Input 05
Input 07
Input 00
Input 02
Input 01
Input 03
Input 10
Input 12
Input 11
Input 13
Terminal A
Terminal E
BCD
Terminal BTerminal CTerminal D
+
-
12345678910111213
151617181920
14
21222324252627282930313233
353637
34
IN-0
21
IN-1
43
IN-2
65
IN-3
87
IN-4
109
IN-5
1211
IN-6
1413
Orange
Blue
White/Black
Red/BlackGreen/Black
Orange/BlackBlue/Black
Black/White
Red/White
Green/White
Blue/White
Black/Red
White/Red
Orange/Red
Blue/Red
Red/GreenIN-7
1615
IN-8
1817
IN-9
2019
IN-10
2221
IN-11
2423
IN-12
2625
IN-13
2827
IN-14
3029
Orange/Green
Black/White/Red
White/Black/Red
Red/Black/WhiteGreen/Black/White
Orange/Black/WhiteBlue/Black/White
Black/Red/Green
White/Red/Green
Red/Black/Green
Green/Black/Orange
Orange/Black/Green
Blue/White/Orange
Black/White/Orange
White/Red/Orange
Orange/White/BlueIN-15
3231
GND-0
GND-1
GND-2
GND-3
GND-4
GND-5
GND-6
GND-7
GND-8
GND-9
GND-10
GND-11
GND-12
GND-13
GND-14
GND-15
Conversion Module1492-CM1771-LD002
Cable1492-CONCAB005Y�
IMPORTANT
Rockwell Automation Publication 1492-SG121E-EN-P - July 2016 21
Wiring Diagrams - Digital Inputs
1771-IAN to 1756-IA32
1771-WN Swing ArmFrom 1771-IAN
There are several key application considerations and system specifications (bottom of drawing) when using these components (conversion module, cable and input module). Read and understand these considerations before installation.
WARNING
Conversion Module Installation and Application Considerations� The input delay times for the 1771-IAN module versus 1756-IA32 module are as follows: 1771-IAN 1756-IA32
a) Off-to-On Delay 10ms (+/-7ms) 10ms max (plus selectable filter)b) On-to-Off Delay 20ms (+/-15ms) 8ms max (plus selectable filter)
� The 1771-IAN has 4 groups(allowing 4 seperate power supplies) and the 1756-IA32 has 2 groups. This module/cable combination ties Groups 0 & 1 from the 1771-IAN to Group 0 on the 1756-IA32 and it ties Groups 2 & 3 from the 1771-IAN to Group 1 on the 1756-IA32. Field wiring modification must be made to accommodate this if multiple supplies were used. If 4 supplies were used, 2 must be removed.
� Refer to your 1771-IAN and 1756-IA32 Installation Manual wiring schematics and diagrams for more details.
1756-IA32
18L2-0
IN-01
IN-1619
IN-12
IN-1720
IN-23
IN-1821
IN-34
IN-1922
IN-45
IN-2023
IN-56
IN-2124
IN-67
IN-2225
Black
WhiteRed
Green
Orange
Blue
White/Black
Red/BlackGreen/Black
Orange/BlackBlue/Black
Black/White
Red/White
Green/White
Blue/White
Black/Red
White/Red
Orange/Red
Blue/RedRed/Green
IN-78
1234
3
5
226
4
7
238
5
9
2410
6
11
2512
7
13
26
8
15
2716
9
17
2818
10
1920
14
12
213122
13233224
14
253326
15273428
16293530
17313632
18
3337
30
353836
2
37
34
L2-136
IN-2326
IN-89
IN-2427
IN-910
IN-2528
IN-1011
IN-2629
IN-1112
IN-2730
IN-1213
IN-2831
IN-1314
IN-2932
IN-1415
IN-3033
Orange/Green
Black/White/Red
White/Black/Red
Red/Black/WhiteGreen/Black/White
Orange/Black/WhiteBlue/Black/White
Black/Red/Green
White/Red/Green
Red/Black/Green
Green/Black/Orange
Orange/Black/Green
Blue/White/Orange
Black/White/Orange
White/Red/Orange
Orange/White/Blue
IN-1516
IN-313417
L2-0White/Red/Blue
L2-13519
21
11
Common 0
1
39
2029
40
Common 2
L1
L2
Input 01Input 01Input 02Input 02Input 03Input 03Input 04Input 04
Input 05Input 05Input 06Input 06Input 07Input 07
Input 10
Input 11
Input 10
Input 12
Input 13Input 13Input 14Input 14Input 15Input 15Input 16Input 16Input 17Input 17
Input 00Input 00
Input 11
Input 12
Common 0Common 1Common 1Common 2
Common 3Common 3
Conversion Module1492-CM1771-LD003
Cable1492-CONCAB005Z�
IMPORTANT
22 Rockwell Automation Publication 1492-SG121E-EN-P - July 2016
Wiring Diagrams - Digital Inputs
1771-IB to 1756-IB16
There are several key application considerations and system specifications (bottom of drawing) when using these components (conversion module, cable and input module). Read and understand these considerations before installation.
B
34567
A012
Black
WhiteRed
Green
Orange
Blue
White/Black
Red/BlackGreen/Black
Orange/Black
1
19
345678910111213
15161718
20
14
2
24
212223
25
+
-
1756-IB16
10GND-0
IN-01
IN-12
IN-23
IN-34
IN-45
IN-56
IN-67
IN-78
IN-811
IN-912
IN-1013
IN-1114
IN-1215
IN-1316
IN-1417
IN-1518
GND-120
9GND-0
19GND-1
CABLE “A”
CABLE “B”
Not used
Input 0Input 1
Input 2Input 3Input 4Input 5
Input 6
Input 7GND-1
B
34567
A012
1
19
345678910111213
15161718
20
14
2
24
212223
25
Not used
Input 0Input 1
Input 2Input 3Input 4Input 5
Input 6
Input 7GND-1
� The 1771-IB module is rated 24V DC. The 1756-IB16 module is rated 10 - 31V DC only.
� Refer to your 1771-IB and 1756-IB16 Installation Manual wiring schematics and diagrams for more details. [Reference Doc: 41170-995 (Version 00)]
� The input delay times for the 1771-IB module versus the 1756-IB16 module are as follows: 1771-IB 1756-IB16 w/ 1492-C005005XEa) Off-to-On Delay 24ms (+/-10ms) 1ms max (plus selectable filter)b) On-to-Off Delay 24ms (+/-10ms) 2ms max (plus selectable filter)
Black
WhiteRed
Green
Orange
Blue
White/Black
Red/BlackGreen/Black
Orange/Black
+
-
Conversion Module Installation and Application Considerations� This Bul. 1492 cable consists of 2 separate cables (cable “A” and cable “B”) wired to one 1756-IB16 RTB. Recommended cablelengths of 0.5 M / 0.5 M are shown. See table 2 for other lengths.
1771-WA Swing ArmFrom 1771-IB
1771-WA Swing ArmFrom 1771-IB
Conversion Module1492-CM1771-LD007
Conversion Module1492-CM1771-LD007
Cable1492-C005005XE�
IMPORTANT
Rockwell Automation Publication 1492-SG121E-EN-P - July 2016 23
Wiring Diagrams - Digital Inputs
1771-IBD to 1756-IB16
1756-IB16
10GND-0
IN-01
IN-12
IN-23
IN-34
IN-45
IN-56
IN-67
IN-78
IN-811
IN-912
IN-1013
IN-1114
IN-1215
IN-1316
IN-1417
IN-1518
Black
WhiteRed
Green
Orange
Blue
White/Black
Red/BlackGreen/Black
Orange/BlackBlue/Black
Black/White
Red/White
Green/White
Blue/White
Black/Red
White/Red
Orange/Red
Blue/Red
Red/GreenGND-1
20
9GND-0
19GND-1
A
1
00
19
013
024
035
046
057
068
079
E
10111012111312
13151416151716
17 18
20
14
2
Input 14
Input 16Input 15
Input 17
Input 04
Input 06Input 05
Input 07
Input 00
Input 02Input 01
Input 03
Input 10
Input 12Input 11
Input 13
Terminal A
Terminal E
BCD
Terminal BTerminal CTerminal D
+
-
24
212223
25
Conversion Module Installation and Application Considerations� This Bul. 1492 cable consists of a cable wired to one 1756-IB16 RTB. Recommended cable lengths of 0.5M or 1.0M (005=0.5M, 010=1.0M). See table 2 for other lengths.
� The input delay times for the 1771-IBD module versus the 1756-IB16 module are as follows: 1771-IBD 1756-IB16 w/ 1492-CONCAB005Xa) Off-to-On Delay 1ms 1ms (plus selectable filter)b) On-to-Off Delay 1ms 2ms (plus selectable filter)
� Refer to your 1771-IBD and 1756-IB16 Installation Manual wiring Schematics and diagrams for more details. [Reference Doc: 41170-926 (Version 02)]
1771-WH Swing ArmFrom 1771-IBD
There are several key application considerations and system specifications (bottom of drawing) when using these components (conversion module, cable and input module). Read and understand these considerations before installation.
Conversion Module1492-CM1771-LD001
Cable1492-CONCAB005X�
IMPORTANT
24 Rockwell Automation Publication 1492-SG121E-EN-P - July 2016
Wiring Diagrams - Digital Inputs
1771-IBN to 1756-IB32
1771-WN Swing ArmFrom 1771-IBN
There are several key application considerations and system specifications (bottom of drawing) when using these components (conversion module, cable and input module). Read and understand these considerations before installation.
1756-IB32
18GND-0
IN-01
IN-1619
IN-12
IN-1720
IN-23
IN-1821
IN-34
IN-1922
IN-45
IN-2023
IN-56
IN-2124
IN-67
IN-2225
Black
WhiteRed
Green
Orange
Blue
White/Black
Red/BlackGreen/Black
Orange/BlackBlue/Black
Black/White
Red/White
Green/White
Blue/White
Black/Red
White/Red
Orange/Red
Blue/RedRed/Green
IN-78
1234
3
5
226
4
7
238
5
9
2410
6
11
2512
7
13
26
8
15
2716
9
17
2818
10
1920
14
12
213122
13233224
14
253326
15273428
16293530
17313632
18
3337
30
353836
2
37
34
GND-136
IN-2326
IN-89
IN-2427
IN-910
IN-2528
IN-1011
IN-2629
IN-1112
IN-2730
IN-1213
IN-2831
IN-1314
IN-2932
IN-1415
IN-3033
Orange/Green
Black/White/Red
White/Black/Red
Red/Black/WhiteGreen/Black/White
Orange/Black/WhiteBlue/Black/White
Black/Red/Green
White/Red/Green
Red/Black/Green
Green/Black/Orange
Orange/Black/Green
Blue/White/Orange
Black/White/Orange
White/Red/Orange
Orange/White/Blue
IN-1516
IN-313417
GND-0White/Red/Blue
GND-135
Input 01Input 01Input 02Input 02Input 03Input 03Input 04Input 04
Input 05Input 05Input 06Input 06Input 07Input 07
Input 10
Input 11
Input 10
Input 12
Input 13Input 13Input 14Input 14Input 15Input 15Input 16Input 16Input 17Input 17
Input 00
19
21
11
dc Common 0
1Input 00
Input 11
Input 12
39
2029
40
+
-
dc Common 2
dc Common 0dc Common 1dc Common 1
dc Common 3dc Common 2
dc Common 3
Conversion Module Installation and Application Considerations� The input delay times for the 1771-IBN module versus 1756-IB32 module are as follows: 1771-IBN 1756-IB32
a) Off-to-On Delay 6ms (+/-2ms) 1ms (plus selectable filter)b) On-to-Off Delay 6ms (+/-2ms) 1ms (plus selectable filter)
� The 1771-IBN has 4 groups(allowing 4 seperate power supplies) and the 1756-IB32 has 2 groups. This module/cable combination ties Groups 0 & 1 from the 1771-IBN to Group 0 on the 1756-IB32 and it ties Groups 2 & 3 from the 1771-IBN to Group 1 on the 1756-IB32. Field wiring modification must be made to accommodate this if multiple supplies were used. If 4 supplies were used, 2 must be removed.
� Refer to your 1771-IBN and 1756-IB32 Installation Manual wiring schematics and diagrams for more details.
Conversion Module1492-CM1771-LD003
Cable1492-CONCAB005Z�
IMPORTANT
Rockwell Automation Publication 1492-SG121E-EN-P - July 2016 25
Wiring Diagrams - Digital Inputs
1771-IC to 1756-IC16
There are several key application considerations and system specifications (bottom of drawing) when using these components (conversion module, cable and input module). Read and understand these considerations before installation.
B
34567
A012
Black
WhiteRed
Green
Orange
Blue
White/Black
Red/BlackGreen/Black
Orange/Black
1
19
345678910111213
15161718
20
14
2
24
212223
25
+
-
10GND-0
IN-01
IN-12
IN-23
IN-34
IN-45
IN-56
IN-67
IN-78
IN-811
IN-912
IN-1013
IN-1114
IN-1215
IN-1316
IN-1417
IN-1518
GND-120
9GND-0
19GND-1
CABLE “A”
CABLE “B”
Not used
Input 0Input 1
Input 2Input 3Input 4Input 5
Input 6
Input 7GND-1
B
34567
A012
1
19
345678910111213
15161718
20
14
2
24
212223
25
Not used
Input 0Input 1
Input 2Input 3Input 4Input 5
Input 6
Input 7GND-1
Black
WhiteRed
Green
Orange
Blue
White/Black
Red/BlackGreen/Black
Orange/Black
+
-
� The 1771-IC module is rated 42 to 56V DC. The 1756-IC16 module is rated 42 to 56V DC only.
� Refer to your 1771-IC and 1756-IC16 Installation Manual wiring schematics and diagrams for more details. [Reference Doc: 41170-996 (Version 00)]
� The input delay times for the 1771-IC module versus the 1756-IC16 module are as follows: 1771-IC 1756-IC16 w/ 1492-C005005XEa) Off-to-On Delay 12ms (+/-7ms) 1ms max (plus selectable filter)b) On-to-Off Delay 20ms (+/-7ms) 4ms max (plus selectable filter)
Conversion Module Installation and Application Considerations� This Bul. 1492 cable consists of 2 separate cables (cable “A” and cable “B”) wired to one 1756-IC16 RTB. Recommended cablelengths of 0.5 M / 0.5 M are shown. See table 2 for other lengths.
1771-WA Swing ArmFrom 1771-IC
1771-WA Swing ArmFrom 1771-IC
1756-IC16 Conversion Module1492-CM1771-LD007
Conversion Module1492-CM1771-LD007
Cable1492-C005005XE�
IMPORTANT
26 Rockwell Automation Publication 1492-SG121E-EN-P - July 2016
Wiring Diagrams - Digital Inputs
1771-ICD to 1756-IC16
There are several key application considerations and system specifications (bottom of drawing) when using these components (conversion module, cable and input module). Read and understand these considerations before installation.
10RTN
IN-01
IN-12
IN-23
IN-34
IN-45
IN-56
IN-67
IN-78
IN-811
IN-912
IN-1013
IN-1114
IN-1215
IN-1316
IN-1417
IN-1518
Black
WhiteRed
Green
Orange
Blue
White/Black
Red/BlackGreen/Black
Orange/BlackBlue/Black
Black/White
Red/White
Green/White
Blue/White
Black/Red
White/Red
Orange/Red
Blue/Red
Red/GreenRTN
20
9RTN
19RTN
A
1
00
19
013
024
035
046
057
068
079
E
10111012111312
13151416151716
17 18
20
14
2
Input 14
Input 16Input 15
Input 17
Input 04
Input 06Input 05
Input 07
Input 00
Input 02Input 01
Input 03
Input 10
Input 12Input 11
Input 13
Terminal A
Terminal E
BCD
Terminal BTerminal CTerminal D
� The 1771-ICD module is rated 20V to 60V AC or DC. The 1756-IC16 module is rated 30V to 60V DC.
� This Bul. 1492 cable consists of a cable wired to one 1756-IC16 RTB. Recommended cable lengths of0.5M or 1.0M (005=0.5M, 010=1.0M). See table 2 for other lengths.
� Refer to your 1771-ICD and 1756-IC16 Installation Manual wiring schematics and diagrams for more details.
1771-WH Swing ArmFrom 1771-ICD
� The input delay times for the 1771-ICD module versus the 1756-IC16 module are as follows: 1771-ICD 1756-IC16 w/ 1492-CONCAB005Xa) Off-to-On Delay 6ms (+/-2ms) 1ms max (plus selectable filter)b) On-to-Off Delay 20ms (+/-1ms) 4ms max (plus selectable filter)
+
24
212223
25
Conversion Module Installation and Application Considerations
--
Conversion Module1492-CM1771-LD001
Cable1492-CONCAB005X� 1756-IC16
IMPORTANT
Rockwell Automation Publication 1492-SG121E-EN-P - July 2016 27
Wiring Diagrams - Digital Inputs
1771-ID to 1756-IA16I
There are several key application considerations and system specifications (bottom of drawing) when using these components (conversion module, cable and input module). Read and understand these considerations before installation.
Conversion Module Installation and Application Considerations � This Bul. 1492 cable consists of a cable wired to one 1756-IA16I RTB. Recommended cable lengths of 0.5M or 1.0M (005=0.5M, 010=1.0M). See table 2 for other lengths.
� The input delay times for the 1771-ID module versus the 1756-IA16I module are as follows: 1771-ID 1756-IA16I w/ 1492-C005005XL a) Off-to-On Delay 24ms (+/-10ms) 10ms max (plus selectable filter) b) On-to-Off Delay 24ms (+/-10ms) 8ms max (plus selectable filter)
� The 1771-ID module had a jumper selection of N.O. and N.C. outputs. The 1756-IA16I has both N.O. and N.C. outputs, but selection is by wiring termination on the 1756 swing arm. The 1492-CM1771-LD012 conversion module replaces the functionality of the 1771-ID jumpers with eight jumpers (JMP0 through JMP7). In the default position, the output will be N.O. If a N.C. output is required, change the jumper from pins 1-2 to pins 3-4.
� Refer to your 1771-ID and 1756-IA16I Installation Manual wiring schematics and diagrams for more details. Ensure 1756 output module ratings are not exceeded. [Reference Doc: 41170-993 (Version 00)]
12345
678910111213
151617181920
14
21222324252627282930313233
353637
34
LOAD
123456
Orange
Blue
White/Black
Red/BlackGreen/Black
Orange/BlackBlue/Black
Black/White
Red/White
Green/White
Blue/White
Black/Red
White/Red
Orange/Red
Blue/Red
Red/Green
7891011
Orange/Green
Black/White/Red
White/Black/Red
Red/Black/WhiteGreen/Black/White
Orange/Black/WhiteBlue/Black/White
Black/Red/Green
White/Red/Green
Red/Black/Green
Green/Black/Orange
Orange/Black/Green
Blue/White/Orange
Black/White/Orange
White/Red/Orange
Orange/White/Blue
12
L1L21
56789101112
234
1
3
2
4
N.O.
N.C.
1
3
2
4
N.O.
N.C.
JMP0
JMP1
1
3
2
4
N.O.
N.C.
JMP2
1
3
2
4
N.O.
N.C.
1
3
2
4
N.O.
N.C.
JMP3
JMP4
1
3
2
4
N.O.
N.C.
JMP5
1
3
2
4
N.O.
N.C.
JMP6
1
3
2
4
N.O.
N.C.
JMP7
12345
678910111213
151617181920
14
21222324252627282930313233
353637
34
Orange
Blue
White/Black
Red/BlackGreen/Black
Orange/BlackBlue/Black
Black/White
Red/White
Green/White
Blue/White
Black/Red
White/Red
Orange/Red
Blue/Red
Red/GreenOrange/Green
Black/White/Red
White/Black/Red
Red/Black/WhiteGreen/Black/White
Orange/Black/WhiteBlue/Black/White
Black/Red/Green
White/Red/Green
Red/Black/Green
Green/Black/Orange
Orange/Black/Green
Blue/White/Orange
Black/White/Orange
White/Red/Orange
Orange/White/Blue
1
56789101112
234
1
3
2
4
N.O.
N.C.
1
3
2
4
N.O.
N.C.
JMP0
JMP1
1
3
2
4
N.O.
N.C.
JMP2
1
3
2
4
N.O.
N.C.
1
3
2
4
N.O.
N.C.
JMP3
JMP4
1
3
2
4
N.O.
N.C.
JMP5
1
3
2
4
N.O.
N.C.
JMP6
1
3
2
4
N.O.
N.C.
JMP7
252627282930313233343536
NOT USED
NOT USEDNOT USED
131415161718192021222324
L1-6L2-6L1-7
L2-7L1-8L2-8
L2-9L1-9
L2-10L1-10
L1-11L2-11
NOT USEDNOT USEDNOT USEDNOT USEDNOT USEDNOT USEDNOT USEDNOT USED
L1-0
L2-0
L1-1L2-1L1-2L2-2
L2-3L1-3
L2-4L1-4
L1-5L2-5
LOADL1L2
L1-6
L2-6
L1-7L2-7L1-8L2-8
L2-9L1-9
L2-10L1-10
L1-11L2-11
L1-0L2-0L1-1L2-1L1-2L2-2
L2-3L1-3
L2-4L1-4
L1-5L2-5
CABLE”A”
CABLE”B”NOT USED
Conversion Module1492-CM1771-LD012
Conversion Module1492-CM1771-LD012
1771-WD Swing ArmFrom 1771-ID
1771-WD Swing ArmFrom 1771-ID
Cable1492-C005005XL� 1756-IA16I
IMPORTANT
28 Rockwell Automation Publication 1492-SG121E-EN-P - July 2016
Wiring Diagrams - Digital Inputs
1771-ID01 to 1756-IM16IThere are several key application considerations and system specifications (bottom of drawing) when using these components (conversion module, cable and input module). Read and understand these considerations before installation.
Conversion Module1492-CM1771-LD012
Conversion Module1492-CM1771-LD012
1771-WD Swing ArmFrom 1771-ID01
1771-WD Swing ArmFrom 1771-ID01
Cable1492-C005005XL� 1756-IM16I
12345
678910111213
151617181920
14
21222324252627282930313233
353637
34
LOAD
123456
Orange
Blue
White/Black
Red/BlackGreen/Black
Orange/BlackBlue/Black
Black/White
Red/White
Green/White
Blue/White
Black/Red
White/Red
Orange/Red
Blue/Red
Red/Green
7891011
Orange/Green
Black/White/Red
White/Black/Red
Red/Black/WhiteGreen/Black/White
Orange/Black/WhiteBlue/Black/White
Black/Red/Green
White/Red/Green
Red/Black/Green
Green/Black/Orange
Orange/Black/Green
Blue/White/Orange
Black/White/Orange
White/Red/Orange
Orange/White/Blue
12
L1L21
56789101112
234
1
3
2
4
N.O.
N.C.
1
3
2
4
N.O.
N.C.
JMP0
JMP1
1
3
2
4
N.O.
N.C.
JMP2
1
3
2
4
N.O.
N.C.
1
3
2
4
N.O.
N.C.
JMP3
JMP4
1
3
2
4
N.O.
N.C.
JMP5
1
3
2
4
N.O.
N.C.
JMP6
1
3
2
4
N.O.
N.C.
JMP7
12345
678910111213
151617181920
14
21222324252627282930313233
353637
34
Orange
Blue
White/Black
Red/BlackGreen/Black
Orange/BlackBlue/Black
Black/White
Red/White
Green/White
Blue/White
Black/Red
White/Red
Orange/Red
Blue/Red
Red/GreenOrange/Green
Black/White/Red
White/Black/Red
Red/Black/WhiteGreen/Black/White
Orange/Black/WhiteBlue/Black/White
Black/Red/Green
White/Red/Green
Red/Black/Green
Green/Black/Orange
Orange/Black/Green
Blue/White/Orange
Black/White/Orange
White/Red/Orange
Orange/White/Blue
1
56789101112
234
1
3
2
4
N.O.
N.C.
1
3
2
4
N.O.
N.C.
JMP0
JMP1
1
3
2
4
N.O.
N.C.
JMP2
1
3
2
4
N.O.
N.C.
1
3
2
4
N.O.
N.C.
JMP3
JMP4
1
3
2
4
N.O.
N.C.
JMP5
1
3
2
4
N.O.
N.C.
JMP6
1
3
2
4
N.O.
N.C.
JMP7
252627282930313233343536
NOT USED
NOT USEDNOT USED
131415161718192021222324
L1-6L2-6L1-7
L2-7L1-8L2-8
L2-9L1-9
L2-10L1-10
L1-11L2-11
NOT USEDNOT USEDNOT USEDNOT USEDNOT USEDNOT USEDNOT USEDNOT USED
L1-0
L2-0
L1-1L2-1L1-2L2-2
L2-3L1-3
L2-4L1-4
L1-5L2-5
LOADL1L2
L1-6
L2-6
L1-7L2-7L1-8L2-8
L2-9L1-9
L2-10L1-10
L1-11L2-11
L1-0L2-0L1-1L2-1L1-2L2-2
L2-3L1-3
L2-4L1-4
L1-5L2-5
CABLE”A”
CABLE”B”NOT USED
Conversion Module Installation and Application Considerations� This Bul. 1492 cable consists of 2 separate cables (cable “A” and cable “B”) wired to one 1756-IM16I RTB. Each cable can be either0.5M or 1.0M (005=0.5M, 010=1.0M). Ensure that cable A and cable B are connected to the correct module in the conversion
� The input delay times for the 1771-IM module versus the 1756-IM16I module are as follows: 1771-ID01 1756-IM16I w/ 1492-C005005XLa) Off-to-On Delay 20ms (+/-10ms) 10ms max (plus selectable filter)b) On-to-Off Delay 20ms (+/-10ms) 8ms max (plus selectable filter)
� The 1771-ID01module had a jumper selection of N.O. and N.C. outputs. The 1756-IM16I has both N.O. and N.C. outputs, but selection is by wiring termination on the 1756 swing arm. The 1492-CM1771-LD012 conversion module replaces the functionalityof the 1771-ID01 jumpers with eight jumpers (JMP0 through JMP7). In the default position, the output will be N.O. If a N.C. output isrequired, change the jumper from pins 1-2 to pins 3-4.
� Refer to your 1771-ID01 and 1756-IM16I Installation Manual wiring schematics and diagrams for more details. Ensure1756 output module ratings are not exceeded. [Reference Doc: 41171-015 (Version 00)]
IMPORTANT
Rockwell Automation Publication 1492-SG121E-EN-P - July 2016 29
Wiring Diagrams - Digital Inputs
1771-ID16 to 1756-IA16I
There are several key application considerations and system specifications (bottom of drawing) when using these components (conversion module, cable and input module). Read and understand these considerations before installation.
Conversion Module Installation and Application Considerations� The input delay times for the 1771-ID16 module versus 1756-IA16I module are as follows:
1771-ID16 1756-IA16Ia) Off-to-On Delay 0.57ms 10ms max (plus selectable filter)b) On-to-Off Delay 9ms or 18ms (selectable) 8ms max (plus selectable filter)� The 1771-ID16 module is rated 74V to 138V AC and105V to 138V DC. The 1756-IA16I is rated 79V to 132V AC. If the input source voltage is DC use a 1756-IH16I with this conversion module.� Refer to your 1771-ID16 and 1756-IA16I Installation Manual wiring schematics and diagrams for more details.
[Reference Doc: 41170-931 (Version 02)]
1771-WN Swing ArmFrom 1771-ID16
1 2
436587
121114131615181722212423262528273231343336353837910192029303940
Input 14
Input 16
Input 15
Input 17
Input 4
Input 6
Input 5
Input 7
Input 0
Input 2
Input 1
Input 3
Input 10
Input 12
Input 11
Input 13
Not usedNot usedNot usedNot usedNot usedNot usedNot usedNot used
12345678910111213
151617181920
14
21222324252627282930313233
353637
34
IN-0
21
IN-1
43
IN-2
65
IN-3
87
IN-4
109
IN-5
1211
IN-6
1413
Orange
Blue
White/Black
Red/Black
Green/Black
Orange/Black
Blue/Black
Black/White
Red/White
Green/White
Blue/White
Black/Red
White/Red
Orange/Red
Blue/Red
Red/GreenIN-7
1615
IN-8
1817
IN-9
2019
IN-10
2221
IN-11
2423
IN-12
2625
IN-13
2827
IN-14
3029
Orange/Green
Black/White/Red
White/Black/Red
Red/Black/White
Green/Black/White
Orange/Black/White
Blue/Black/White
Black/Red/Green
White/Red/Green
Red/Black/Green
Green/Black/Orange
Orange/Black/Green
Blue/White/Orange
Black/White/Orange
White/Red/Orange
Orange/White/BlueIN-15
3231
L2-0
L2-1
L2-2
L2-3
L2-4
L2-5
L2-6
L2-7
L2-8
L2-9
L2-10
L2-11
L2-12
L2-13
L2-14
L2-15
L2
L1
L2-0
L2-1
L2-2
L2-3
L2-4
L2-5
L2-6
L2-7
L2-10
L2-11
L2-12
L2-13
L2-14
L2-15
L2-16
L2-17
1756-IA16I
Conversion Module1492-CM1771-LD004
Cable1492-CONCAB005Y�
IMPORTANT
30 Rockwell Automation Publication 1492-SG121E-EN-P - July 2016
Wiring Diagrams - Digital Inputs
1771-ID16 to 1756-IH16I
There are several key application considerations and system specifications (bottom of drawing) when using these components (conversion module, cable and input module). Read and understand these considerations before installation.
Conversion Module Installation and Application Considerations� The input delay times for the 1771-ID16 module versus 1756-IH16I module are as follows:
1771-ID16 1756-IH16Ia) Off-to-On Delay 0.57ms 2ms max (plus selectable filter)b) On-to-Off Delay 9ms or 18ms (selectable) 6ms max (plus selectable filter)� The 1771-ID16 module is rated 74V to 138V AC and105V to 138V DC. The 1756-IH16I is rated 90V to 146V DC. If the input source voltage is AC use a 1756-IA16I with this conversion module.� Refer to your 1771-ID16 and 1756-IH16I Installation Manual wiring schematics and diagrams for more details.
[Reference Doc: 41170-932 (Version 02)]
1771-WN Swing ArmFrom 1771-ID16
IN-0
IN-1
IN-2
IN-3
IN-4
IN-5
IN-6
IN-7
IN-8
IN-9
IN-10
IN-11
IN-12
IN-13
IN-14
IN-15
GND-0
GND-1
GND-2
GND-3
GND-4
GND-5
GND-6
GND-7
GND-8
GND-9
GND-10
GND-11
GND-12
GND-13
GND-14
GND-15
1 2
436587
121114131615181722212423262528273231343336353837910192029303940
Input 14
Input 16
Input 15
Input 17
Input 4
Input 6
Input 5
Input 7
Input 0
Input 2
Input 1
Input 3
Input 10
Input 12
Input 11
Input 13
Not usedNot usedNot usedNot usedNot usedNot usedNot usedNot used
12345678910111213
151617181920
14
21222324252627282930313233
353637
34
2143658710912111413
Orange
Blue
White/Black
Red/Black
Green/Black
Orange/Black
Blue/Black
Black/White
Red/White
Green/White
Blue/White
Black/Red
White/Red
Orange/Red
Blue/Red
Red/Green
16151817201922212423262528273029
Orange/Green
Black/White/Red
White/Black/Red
Red/Black/White
Green/Black/White
Orange/Black/White
Blue/Black/White
Black/Red/Green
White/Red/Green
Red/Black/Green
Green/Black/Orange
Orange/Black/Green
Blue/White/Orange
Black/White/Orange
White/Red/Orange
Orange/White/Blue
3231
L2-0
L2-1
L2-2
L2-3
L2-4
L2-5
L2-6
L2-7
L2-10
L2-11
L2-12
L2-13
L2-14
L2-15
L2-16
L2-17
+
-
1756-IH16I
Conversion Module1492-CM1771-LD004
Cable1492-CONCAB005Y�
IMPORTANT
Rockwell Automation Publication 1492-SG121E-EN-P - July 2016 31
Wiring Diagrams - Digital Inputs
1771-IG to 1756-IG16
There are several key application considerations and system specifications (bottom of drawing) when using these components (conversion module, cable and input module). Read and understand these considerations before installation.
1771-WC Swing ArmFrom 1771-IG
1771-WC Swing ArmFrom 1771-IG
Conversion Module1492-CM1771-LA003
Conversion Module1492-CM1771-LA003
Cable1492-C005005XS� 1756-IG16
Conversion Module Installation and Application Considerations � This Bul. 1492 cable consists of 2 separate cables (cable “A” and cable “B”) wired to one 1756-IG16 RTB. Each cable can be either 0.5M or 1.0M (005=0.5M, 010=1.0M). Ensure that cable A and cable B are connected to the correct module in the conversion.
� The input delay times for the 1771-IG module versus the 1756-IG16 module are as follows: 1771-IG 1756-IG16 w/ 1492-C005005XS a) Off-to-On Delay 1ms (+/-10ms) 270ms max (plus selectable filter) b) On-to-Off Delay 1ms (+/-10ms) 390ms max (plus selectable filter)
� The 1771-IG module is rated 5V DC TTL INPUT MODULE. The 1756-IG16 module is rated 5V DC TTL INPUT MODULE only.
� Refer to your 1771-IG and 1756-IG16 Installation and User Manuals for additional information concerning comparisons of module wiring, features and configuration details. [Reference Doc: 41171-027 (Version 00)]
InputDevice
1325242322211918171612
SH
Input 0 + DC 10
IN-0IN-1
1
IN-2
234567
98
Red/White
Green/Black/White
Black/White/Red
White/Black/Red
Orange/Green
Red/Black/White
Orange/Red
Blue/Red
+ -
A
34567B
012
Common
Input 1 Input 2 Input 3 Input 4 Input 5 Input 6 Input 7
3456789101112141520
IN-3IN-4IN-5IN-6IN-7
+ DC -0
- DC -020
IN-8IN-9IN-10IN-11IN-12IN-13IN-14IN-15
+ DC -1
- DC -1
1325242322211918171612
SH
Red/White
Green/Black/White
Black/White/Red
White/Black/Red
Orange/Green
Red/Black/White
Orange/Red
Blue/Red
A
34567B
012
3456789101112141520
Input 0 + DC
Common
Input 1 Input 2 Input 3 Input 4 Input 5 Input 6 Input 7
111213141516171819
Black/Red
White/Red
Black/Red
White/Red
CABLE”B”
CABLE”A”+
- 5V DCSUPPLY
InputDevice
+ -
+
- 5V DCSUPPLY
IMPORTANT
32 Rockwell Automation Publication 1492-SG121E-EN-P - July 2016
Wiring Diagrams - Digital Inputs
1771-IGD to 1756-IG16
There are several key application considerations and system specifications (bottom of drawing) when using these components (conversion module, cable and input module). Read and understand these considerations before installation.
1771-WH, WHF, WHFB Swing ArmFrom 1771-IGD
Conversion Module1492-CM1771-LD006
Cable1492-CONCAB005X� 1756-IG16
� This Bul. 1492 cable consists of a cable wired to one 1756-IG16 RTB. Recommended cable lengths of 0.5M or 1.0M (005=0.5M, 010=1.0M). See table 2 for other lengths.
� The 1771-IGD module output current limits versus 1756-IG16 limits are as follows: 1771-IGD 1756-IG16 w/ 1492-CONCAB005Xa) Current/Point 122mA 110mAb) Current/Module 500mA 110mA
� The 1771-IGD is rated 5V DC. The 1756-IG16 is rated 4.5V to 5.5V DC.
� Refer to your 1771-IGD and 1756-IG16 Installation Manual wiring schematics and diagrams for more details. Ensure1756 output module ratings are not exceeded. [Reference Doc: 41171-004 (Version 00)]
Conversion Module Installation and Application Considerations
10DC-0+
IN-01
IN-12
IN-23
IN-34
IN-45
IN-56
IN-67
IN-78
IN-811
IN-912
IN-1013
IN-1114
IN-1215
IN-1316
IN-1417
IN-1518
Black
WhiteRed
Green
Orange
Blue
White/Black
Red/BlackGreen/Black
Orange/BlackBlue/Black
Black/White
Red/White
Green/White
Blue/White
Black/Red
White/Red
Orange/Red
Blue/Red
Red/GreenDC-1+
20
9RTN OUT-0
19RTN OUT-1
A
1
00
19
013
024
035
046
057
068
079
E
10111012111312
13151416151716
17 18
20
14
2
Input 00
+ dc
- dc
B
CD
DC InputDevice
+
-
+-
+ dc
+ dc
+ dc
24
212223
25
Input 01Input 02Input 03Input 04Input 05Input 06Input 07Input 08Input 09Input 10Input 11Input 12Input 13Input 14Input 15
IMPORTANT
Rockwell Automation Publication 1492-SG121E-EN-P - July 2016 33
Wiring Diagrams - Digital Inputs
1771-IH to 1756-IC16
There are several key application considerations and system specifications (bottom of drawing) when using these components (conversion module, cable and input module). Read and understand these considerations before installation.
WARNING
� This Bul. 1492 cable consists of 2 separate cables (cable “A” and cable “B”) wired to one 1756-IC16 RTB. Recommended cablelengths of 0.5 M / 0.5 M are shown. See table 2 for other lengths.
� The 1771-IH module is rated 24V - 48V DC. The 1756-IC16 module is rated 30V - 60V DC.
� Refer to your 1771-IH and 1756-IC16 Installation Manual wiring schematics and diagrams for more details. [Reference Doc: 41170-997 (Version 00)]
� The input delay times for the 1771-IH module versus the 1756-IC16 module are as follows: 1771-IH 1756-IC16 w/ 1492-C005005XEa) Off-to-On Delay 15ms (+/-7ms) 1ms max (plus selectable filter)b) On-to-Off Delay 15ms (+/-7ms) 4ms max (plus selectable filter)
Conversion Module Installation and Application Considerations
B
34567
A012
Black
WhiteRed
Green
Orange
Blue
White/Black
Red/BlackGreen/Black
Orange/Black
1
19
345678910111213
15161718
20
14
2
24
212223
25
+
-
10GND-0
IN-01
IN-12
IN-23
IN-34
IN-45
IN-56
IN-67
IN-78
IN-811
IN-912
IN-1013
IN-1114
IN-1215
IN-1316
IN-1417
IN-1518
GND-120
9GND-0
19GND-1
CABLE “A”
CABLE “B”
Not used
Input 0Input 1
Input 2Input 3Input 4Input 5
Input 6
Input 7GND-0
B
34567
A012
1
19
345678910111213
15161718
20
14
2
24
212223
25
Not used
Input 0Input 1
Input 2Input 3Input 4Input 5
Input 6
Input 7GND-1
Black
WhiteRed
Green
Orange
Blue
White/Black
Red/BlackGreen/Black
Orange/Black
+
-
1771-WA Swing ArmFrom 1771-IH
1771-WA Swing ArmFrom 1771-IH
1756-IC16 Conversion Module1492-CM1771-LD007
Conversion Module1492-CM1771-LD007
Cable1492-C005005XE�
IMPORTANT
34 Rockwell Automation Publication 1492-SG121E-EN-P - July 2016
Wiring Diagrams - Digital Inputs
1771-IM to 1756-IM16I
There are several key application considerations and system specifications (bottom of drawing) when using these components (conversion module, cable and input module). Read and understand these considerations before installation.
� This Bul. 1492 cable consists of 2 separate cables (cable “A” and cable “B”) wired to one 1756-IM16I RTB. Recommended cablelengths of 0.5 M / 0.5 M are shown. See table 2 for other lengths.
� The 1771-IM module is rated 220V to 240V AC. The 1756-IM16I module is rated 159 - 265V AC only.
� Refer to your 1771-IM and 1756-IM16I Installation Manual wiring schematics and diagrams for more details. [Reference Doc: 41170-990 (Version 00)]
� The input delay times for the 1771-IM module versus the 1756-IM16I module are as follows: 1771-IM 1756-IM16I w/ 1492-C005005XHa) Off-to-On Delay 20ms (+/-6ms) 10ms max (plus selectable filter)b) On-to-Off Delay 20ms (+/-6ms) 8ms max (plus selectable filter)
Conversion Module Installation and Application Considerations
1756-IM16I Conversion Module1492-CM1771-LD007
Conversion Module1492-CM1771-LD007
Cable1492-C005005XH�
B
34567
A
1771-WA Swing ArmFrom 1771-IM
012
Black
WhiteRed
Green
Orange
Blue
White/Black
Red/BlackGreen/Black
Orange/Black
1
19
345678910111213
15161718
20
14
2
24
212223
25
L1
L2
2L2-0
IN-01
IN-13
IN-25
IN-37
IN-49
IN-511
IN-613
IN-715
IN-817
IN-919
IN-1021
IN-1123
IN-1225
IN-1327
IN-1429
IN-1531
L2-118
4L2-0
20L2-1
CABLE “A”
CABLE “B”
Not used
Input 0Input 1
Input 2Input 3Input 4Input 5
Input 6
Input 7L2
B
34567
A
1771-WA Swing ArmFrom 1771-IM
012
1
19
345678910111213
15161718
20
14
2
24
212223
25
L1
L2
Not used
Input 0Input 1
Input 2Input 3Input 4Input 5
Input 6
Input 7L2
Black
WhiteRed
GreenOrange
BlueWhite/Black
Red/BlackGreen/Black
Orange/Black
L2-0L2-0
6810121416
L2-1
L2-1L2-1L2-1L2-1
L2-1
22
26283032
24
L2-0L2-0L2-0L2-0
IMPORTANT
Rockwell Automation Publication 1492-SG121E-EN-P - July 2016 35
Wiring Diagrams - Digital Inputs
1771-IMD to 1756-IM16I
1756-IM16I
1771-WH Swing ArmFrom 1771-IMD
There are several key application considerations and system specifications (bottom of drawing) when using these components (conversion module, cable and input module). Read and understand these considerations before installation.
Conversion Module1492-CM1771-LD002
Cable1492-CONCAB005Y�
Conversion Module Installation and Application Considerations� The input delay times for the 1771-IMD module versus 1756-IM16I module are as follows: 1771-IMD 1756-IM16Ia) Off-to-On Delay 15ms (+/-8ms) 10ms (plus selectable filter)b) On-to-Off Delay 172ms (+/-56ms) 8ms (plus selectable filter)� The 1771-IMD module is rated 184V AC to 250V AC and 166V-230V DC. The 1756-IM16I module is rated 159V to 265V AC. A1756 input module with an equivalent DC voltage range to convert the 1771-IMD is not available.� Refer to your 1771-IMD and 1756-IM16I Installation Manual wiring schematics and diagrams for more details.
[Reference Doc: 41170-928 (Version 02)]
A
00
01
02
03
04
05
06
07
E
10
11
12
13
14
15
16
17
Input 14
Input 16
Input 15
Input 17
Input 04
Input 06
Input 05
Input 07
Input 00
Input 02
Input 01
Input 03
Input 10
Input 12
Input 11
Input 13
Terminal A
Terminal E
BCD
Terminal BTerminal CTerminal D
12345678910111213
151617181920
14
21222324252627282930313233
353637
34
IN-0
21
IN-1
43
IN-2
65
IN-3
87
IN-4
109
IN-5
1211
IN-6
1413
Orange
Blue
White/Black
Red/BlackGreen/Black
Orange/BlackBlue/Black
Black/White
Red/White
Green/White
Blue/White
Black/Red
White/Red
Orange/Red
Blue/Red
Red/GreenIN-7
1615
IN-8
1817
IN-9
2019
IN-10
2221
IN-11
2423
IN-12
2625
IN-13
2827
IN-14
3029
Orange/Green
Black/White/Red
White/Black/Red
Red/Black/WhiteGreen/Black/White
Orange/Black/WhiteBlue/Black/White
Black/Red/Green
White/Red/Green
Red/Black/Green
Green/Black/Orange
Orange/Black/Green
Blue/White/Orange
Black/White/Orange
White/Red/Orange
Orange/White/BlueIN-15
3231
L2-0
L2-1
L2-2
L2-3
L2-4
L2-5
L2-6
L2-7
L2-8
L2-9
L2-10
L2-11
L2-12
L2-13
L2-14
L2-15
L1
L2
IMPORTANT
36 Rockwell Automation Publication 1492-SG121E-EN-P - July 2016
Wiring Diagrams - Digital Inputs
1771-IN to 1756-IN16
There are several key application considerations and system specifications (bottom of drawing) when using these components (conversion module, cable and input module). Read and understand these considerations before installation.
WARNING
� This Bul. 1492 cable consists of 2 separate cables (cable “A” and cable “B”) wired to one 1756-IN16 RTB. Recommended cablelengths of 0.5 M / 0.5 M are shown. See table 2 for other lengths.
� The 1771-IN module is rated 24V AC. The 1756-IN16 module is rated 24V AC only.
� Refer to your 1771-IN and 1756-IN16 Installation Manual wiring schematics and diagrams for more details. [Reference Doc: 41170-998 (Version 00)]
� The input delay times for the 1771-IN module versus the 1756-IN16 module are as follows: 1771-IN 1756-IN16 w/ 1492-C005005XEa) Off-to-On Delay 18ms (+/-10ms) 10ms max (plus selectable filter)b) On-to-Off Delay 18ms (+/-10ms) 10ms max (plus selectable filter)
Conversion Module Installation and Application Considerations
B
34567
A012
Black
WhiteRed
Green
Orange
Blue
White/Black
Red/BlackGreen/Black
Orange/Black
1
19
345678910111213
15161718
20
14
2
24
212223
25
+
-
1756-IN16
10L2-0
IN-01
IN-12
IN-23
IN-34
IN-45
IN-56
IN-67
IN-78
IN-811
IN-912
IN-1013
IN-1114
IN-1215
IN-1316
IN-1417
IN-1518
L2-120
9L2-0
19L2-1
CABLE “A”
CABLE “B”
Not used
Input 0Input 1
Input 2Input 3Input 4Input 5
Input 6
Input 7GND-1
B
34567
A012
1
19
345678910111213
15161718
20
14
2
24
212223
25
Not used
Input 0Input 1
Input 2Input 3Input 4Input 5
Input 6
Input 7L2
Black
WhiteRed
Green
Orange
Blue
White/Black
Red/BlackGreen/Black
Orange/Black
+
-
1771-WA Swing ArmFrom 1771-IN
1771-WA Swing ArmFrom 1771-IN
Conversion Module1492-CM1771-LD007
Conversion Module1492-CM1771-LD007
Cable1492-C005005XE�
IMPORTANT
Rockwell Automation Publication 1492-SG121E-EN-P - July 2016 37
Wiring Diagrams - Digital Inputs
1771-IND to 1756-IN16
There are several key application considerations and system specifications (bottom of drawing) when using these components (conversion module, cable and input module). Read and understand these considerations before installation.
� This Bul. 1492 cable consists of a cable wired to one 1756-IN16 RTB. Recommended cable lengths of0.5M or 1.0M (005=0.5M, 010=1.0M). See table 2 for other lengths.
Conversion Module Installation and Application Considerations
1756-IN16
10L2-0
IN-01
IN-12
IN-23
IN-34
IN-45
IN-56
IN-67
IN-78
IN-811
IN-912
IN-1013
IN-1114
IN-1215
IN-1316
IN-1417
IN-1518
Black
WhiteRed
Green
Orange
Blue
White/Black
Red/BlackGreen/Black
Orange/BlackBlue/Black
Black/White
Red/White
Green/White
Blue/White
Black/Red
White/Red
Orange/Red
Blue/Red
Red/GreenL2-1
20
9L2-0
19L2-1
A
1
00
19
013
024
035
046
057
068
079
E
10111012111312
13151416151716
17 18
20
14
2
Input 14
Input 16Input 15
Input 17
Input 04
Input 06Input 05
Input 07
Input 00
Input 02Input 01
Input 03
Input 10
Input 12Input 11
Input 13
Terminal A
Terminal E
BCD
Terminal BTerminal CTerminal D
� The 1771-IND module is rated 24V AC or DC. The 1756-IN16 module is rated 10V to 30V AC.
� Refer to your 1771-IND and 1756-IN16 Installation Manual wiring schematics and diagrams for more details.
[Reference Doc: 41170-002 (Version 00)]
1771-WH Swing ArmFrom 1771-IND
� The input delay times for the 1771-IND module versus the 1756-IN16 module are as follows: 1771-IND 1756-IN16 w/ 1492-CONCAB005Xa) Off-to-On Delay 35ms (+/-10ms) @24V AC 10ms max (plus selectable filter)b) On-to-Off Delay 45ms (+/-15ms) 10ms max (plus selectable filter)
L1
L2
24
212223
25
Conversion Module1492-CM1771-LD001
Cable1492-CONCAB005X�
IMPORTANT
38 Rockwell Automation Publication 1492-SG121E-EN-P - July 2016
Wiring Diagrams - Digital Inputs
1771-IND1 to 1756-IN16
There are several key application considerations and system specifications (bottom of drawing) when using these components (conversion module, cable and input module). Read and understand these considerations before installation.
� This Bul. 1492 cable consists of a cable wired to one 1756-IN16 RTB. Recommended cable lengths of0.5M or 1.0M (005=0.5M, 010=1.0M). See table 2 for other lengths.
Conversion Module Installation and Application Considerations
1756-IN16
10L2-0
IN-01
IN-12
IN-23
IN-34
IN-45
IN-56
IN-67
IN-78
IN-811
IN-912
IN-1013
IN-1114
IN-1215
IN-1316
IN-1417
IN-1518
Black
WhiteRed
Green
Orange
Blue
White/Black
Red/BlackGreen/Black
Orange/BlackBlue/Black
Black/White
Red/White
Green/White
Blue/White
Black/Red
White/Red
Orange/Red
Blue/Red
Red/GreenL2-1
20
9L2-0
19L2-1
A
1
00
19
013
024
035
046
057
068
079
E
10111012111312
13151416151716
17 18
20
14
2
Input 14
Input 16Input 15
Input 17
Input 04
Input 06Input 05
Input 07
Input 00
Input 02Input 01
Input 03
Input 10
Input 12Input 11
Input 13
Terminal A
Terminal E
BCD
Terminal BTerminal CTerminal D
� The 1771-IND1 module is rated 48V AC. The 1756-IN16 module is rated 10V to 30V AC.
� Refer to your 1771-IND1 and 1756-IN16 Installation Manual wiring schematics and diagrams for more details.
[Reference Doc: 41170-003 (Version 00)]
1771-WH Swing ArmFrom 1771-IND1
� The input delay times for the 1771-IND1 module versus the 1756-IN16 module are as follows: 1771-IND1 1756-IN16 w/ 1492-CONCAB005Xa) Off-to-On Delay 25ms (+/-5ms) @48V AC 10ms max (plus selectable filter)b) On-to-Off Delay 35ms (+/-10ms) 10ms max (plus selectable filter)
L1
L2
24
212223
25
Conversion Module1492-CM1771-LD001
Cable1492-CONCAB005X�
IMPORTANT
Rockwell Automation Publication 1492-SG121E-EN-P - July 2016 39
Wiring Diagrams - Digital Inputs
1771-IQ to 1756-IB16I— Sinking
There are several key application considerations and system specifications (bottom of drawing) when using these components (conversion module, cable and input module). Read and understand these considerations before installation.
� This Bul. 1492 cable consists of 2 separate cables (cable “A” and cable “B”) wired to one 1756-IB16I RTB. Recommended cablelengths of 0.5 M / 0.5 M are shown. See table 2 for other lengths.
� The 1771-IQ module is rated 5V to 30V DC. The 1756-IB16I module is rated 10V to 30V DC only.
� Refer to your 1771-IQ and 1756-IB16I Installation Manual wiring schematics and diagrams for more details.
� For Sourcing applications use 1492-CM1771-LD014. [Reference Doc: 41170-992 (Version 00)]
� The input delay times for the 1771-IQ module versus the 1756-IB16I module are as follows: 1771-IQ 1756-IB16I w/ 1492-C005005XKa) Off-to-On Delay 12ms (+/-14ms) 1ms max (plus selectable filter)b) On-to-Off Delay 12ms (+/-7ms) 4ms max (plus selectable filter)
Conversion Module Installation and Application Considerations
1756-IB16I Conversion Module1492-CM1771-LD007
Conversion Module1492-CM1771-LD007
Cable1492-C005005XK�
1771-WA Swing ArmFrom 1771-IQ
1771-WA Swing ArmFrom 1771-IQ
B
34567
A012
Black
WhiteRed
Green
Orange
Blue
White/Black
Red/BlackGreen/Black
Orange/Black
1
19
345678910111213
15161718
20
14
2
24
212223
25
+
_
IN-01
IN-13
IN-25
IN-37
IN-49
IN-511
IN-613
IN-715
IN-817
IN-919
IN-1021
IN-1123
IN-1225
IN-1327
IN-1429
IN-153118
2
L2-0
20
CABLE “A”
CABLE “B”
Not usedIN 0
L2 - 0
B
34567
A012
1
19
345678910111213
15161718
20
14
2
24
212223
25
Not used
Input 0Input 1
Input 2Input 3Input 4Input 5
Input 6
Input 7L2 - 1
Black
WhiteRed
GreenOrange
Blue
White/Black
Red/BlackGreen/Black
Orange/Black
IN 1IN 2IN 3IN 4IN 5IN 6IN 7
222426283032
+
_
6810121416
4
L2-0L2-0L2-0L2-0L2-0L2-0
L2-1L2-1L2-1L2-1L2-1L2-1L2-1L2-1
L2-0
IMPORTANT
40 Rockwell Automation Publication 1492-SG121E-EN-P - July 2016
Wiring Diagrams - Digital Inputs
1771-IQ to 1756-IB16I— Sourcing
There are several key application considerations and system specifications (bottom of drawing) when using these components (conversion module, cable and input module). Read and understand these considerations before installation.
1756-IB16I
Conversion Module1492-CM1771-LD0014
Conversion Module1492-CM1771-LD0014
Cable1492-C005005XJ�
1771-WA Swing ArmFrom 1771-IQ
1771-WA Swing ArmFrom 1771-IQ
CABLE”A”
CABLE”B”
Conversion Module Installation and Application Considerations� This Bul. 1492 cable consists of 2 separate cables (cable “A” and cable “B”) wired to one 1756-IB16I RTB. Each cable can be either 0.5M or 1.0M (005=0.5M, 010=1.0M). Ensure that cable A and cable B are connected to the correct module in the conversion.
� The input delay times for the 1771-IQ module versus the 1756-IB16 module are as follows: 1771-IQ 1756-IB16I w/1492-C005005XJa) Off-to-On Delay 12ms (+/-14ms) 1ms max (plus selectable filter)b) On-to-Off Delay 12ms (+/-14ms) 4ms max (plus selectable filter)
� The 1771-IQ module is rated 5V to 30V DC. The 1756-IB16I module is rated 10V to 30V SOURCING DC only.
� Refer to your 1771-IQ and 1756-IB16I Installation Manual wiring schematics and diagrams for more details.
� For Sinking applications use 1492-CM1771-LD007. [Reference Doc: 41170-991 (Version 00)]
B
3
4567
A012
Black
WhiteRed
Green
Orange
Blue
White/Black
Red/BlackGreen/Black
Orange/BlackBlue/Black
Black/White
Red/White
Green/White
Blue/White
Black/Red
White/Red
Orange/Red
Blue/Red
Red/Green
DC+
GND-02
GND-14
GND-26
GND-38
GND-4
1
GND-5
3
GND-6
5
GND-7
7911131510121416
GND-15
NOT-USED
LOAD
-
+
1
19
345678910111213
15161718
20
14
2
24
212223
25
DC -
GND 00GND 01GND 02GND 03
GND 04GND 05GND 06GND 07
B
3
4567
A012
Black
WhiteRed
Green
Orange
Blue
White/Black
Red/BlackGreen/Black
Orange/BlackBlue/Black
Black/White
Red/White
Green/White
Blue/White
Black/Red
White/Red
Orange/Red
Blue/Red
Red/Green
DC +
GND-818
OUT-920
OUT-1022
OUT-1124
GND-12
17
GND-13
19
GND-14
21
GND-15
232527293126283032
LOAD
-
+
1
19
345678910111213
15161718
20
14
2
24
212223
25
DC -
GND 08GND 09
GND -10GND -11
GND -12GND -13GND -14GND -15
IN - 0IN - 1IN - 2IN - 3IN - 4IN - 5IN - 6IN - 7
33
34
35NOT-USED
-
36NOT-USED
IN - 8IN - 9IN - 10IN - 11IN - 12IN - 13IN - 14IN - 15
IMPORTANT
Rockwell Automation Publication 1492-SG121E-EN-P - July 2016 41
Wiring Diagrams - Digital Inputs
1771-IQ16 to 1756-IB16I
There are several key application considerations and system specifications (bottom of drawing) when using these components (conversion module, cable and input module). Read and understand these consid-erations before installation.
Conversion Module Installation and Application Considerations� The input delay times for the 1771-IQ16 module versus 1756-IB16I module are as follows:
1771-IQ16 1756-IB16Ia) Off-to-On Delay 0.57ms 1ms max (plus selectable filter)b) On-to-Off Delay 0.57ms 4ms max (plus selectable filter)� Both the 1771-IQ16 and 1756-IB16I allow operation with sourcing inputs. Refer to installation Instructions for details.� Refer to your 1771-IQ16 and 1756-IH16I Installation Manual wiring schematics and diagrams for more details.
[Reference Doc: 41170-933 (Version 02)]
1771-WN Swing ArmFrom 1771-IQ16
IN-0
IN-1
IN-2
IN-3
IN-4
IN-5
IN-6
IN-7
IN-8
IN-9
IN-10
IN-11
IN-12
IN-13
IN-14
IN-15
Gnd-0
Gnd-1
Gnd-2
Gnd-3
Gnd-4
Gnd-5
Gnd-6
Gnd-7
Gnd-8
Gnd-9
Gnd-10
Gnd-11
Gnd-12
Gnd-13
Gnd-14
Gnd-15
Gnd-0
Gnd-1
Gnd-2
Gnd-3
Gnd-4
Gnd-5
Gnd-6
Gnd-7
Gnd-10
Gnd-11
Gnd-12
Gnd-13
Gnd-14
Gnd-15
Gnd-16
Gnd-17
1 2
436587
121114131615181722212423262528273231343336353837910192029303940
Input 14
Input 16
Input 15
Input 17
Input 4
Input 6
Input 5
Input 7
Input 0
Sinking Input Example
SourcingInputExample
�
Input 2
Input 1
Input 3
Input 10
Input 12
Input 11
Input 13
Not usedNot usedNot usedNot usedNot usedNot usedNot usedNot used
12345678910111213
151617181920
14
21222324252627282930313233
353637
34
1756-IB16I
2143658710912111413
Orange
Blue
White/Black
Red/Black
Green/Black
Orange/Black
Blue/Black
Black/White
Red/White
Green/White
Blue/White
Black/Red
White/Red
Orange/Red
Blue/Red
Red/Green
16151817201922212423262528273029
Orange/Green
Black/White/Red
White/Black/Red
Red/Black/White
Green/Black/White
Orange/Black/White
Blue/Black/White
Black/Red/Green
White/Red/Green
Red/Black/Green
Green/Black/Orange
Orange/Black/Green
Blue/White/Orange
Black/White/Orange
White/Red/Orange
Orange/White/Blue
3231
+
-
+
-
Conversion Module1492-CM1771-LD004
Cable1492-CONCAB005Y�
IMPORTANT
42 Rockwell Automation Publication 1492-SG121E-EN-P - July 2016
Wiring Diagrams - Digital Inputs
1771-IT to 1756-IB16
There are several key application considerations and system specifications (bottom of drawing) when using these components (conversion module, cable and input module). Read and understand these considerations before installation.
� This Bul. 1492 cable consists of 2 separate cables (cable “A” and cable “B”) wired to one 1756-IB16 RTB. Recommended cablelengths of 0.5 M / 0.5 M are shown. See table 2 for other lengths.
� The 1771-IT module is rated 24V DC. The 1756-IB16 module is rated 24V DC only.
� Refer to your 1771-IT and 1756-IB16 Installation Manual wiring schematics and diagrams for more details. [Reference Doc: 41170-999 (Version 00)]
� The input delay times for the 1771-IT module versus the 1756-IB16 module are as follows: 1771-IT 1756-IB16 w/ 1492-C005005XEa) Off-to-On Delay 0.6ms (+/-0.2ms) 1ms max (plus selectable filter)b) On-to-Off Delay 0.6ms (+/-0.2ms) 2ms max (plus selectable filter)
Conversion Module Installation and Application Considerations
B
34567
A012
Black
WhiteRed
Green
Orange
Blue
White/Black
Red/BlackGreen/Black
Orange/Black
1
19
345678910111213
15161718
20
14
2
24
212223
25
+
-
10GND-0
IN-01
IN-12
IN-23
IN-34
IN-45
IN-56
IN-67
IN-78
IN-811
IN-912
IN-1013
IN-1114
IN-1215
IN-1316
IN-1417
IN-1518
GND-120
9GND-0
19GND-1
CABLE “A”
CABLE “B”
Not used
Input 0Input 1
Input 2Input 3Input 4Input 5
Input 6
Input 7GND-1
B
34567
A012
1
19
345678910111213
15161718
20
14
2
24
212223
25
Not used
Input 0Input 1
Input 2Input 3Input 4Input 5
Input 6
Input 7GND-1
Black
WhiteRed
Green
Orange
Blue
White/Black
Red/BlackGreen/Black
Orange/Black
+
-
1771-WA Swing ArmFrom 1771-IT
1771-WA Swing ArmFrom 1771-IT
1756-IB16 Conversion Module1492-CM1771-LD007
Conversion Module1492-CM1771-LD007
Cable1492-C005005XE�
IMPORTANT
Rockwell Automation Publication 1492-SG121E-EN-P - July 2016 43
Wiring Diagrams - Digital Inputs
1771-IV to 1756-IV16There are several key application considerations and system specifications (bottom of drawing) when using these components (conversion module, cable and input module). Read and understand these considerations before installation.
1771-WA Swing ArmFrom 1771-IV
1771-WA Swing ArmFrom 1771-IV
Conversion Module Installation and Application Considerations� This Bul. 1492 cable consists of 2 separate cables (cable “A” and cable “B”) wired to one 1756-IV16 RTB. Each cable can be either 0.5M or 1.0M (005=0.5M, 010=1.0M). Ensure that cable A and cable B are connected to the correct module in the conversion.
� The input delay times for the 1771-IV module versus the 1756-IV16 module are as follows: 1771-IV 1756-IV16 w/1492-C005005XGa) Off-to-On Delay 15ms (+/-7ms) 1ms max (plus selectable filter)b) On-to-Off Delay 15ms (+/-7ms) 2ms max (plus selectable filter)
� The 1771-IV module is rated 12 To 24V DC. The 1756-IV16 module is rated 10V To 30V DC only.
� Refer to your 1771-IV and 1756-IV16 Installation Manual wiring schematics and diagrams for more details.
[Reference Doc: 41170-989 (Version 00)]
1756-IV16
Conversion Module1492-CM1771-LD014
Conversion Module1492-CM1771-LD014
Cable1492-C005005XG�
B
3
4567
A012
Black
WhiteRed
Green
Orange
Blue
White/Black
Red/BlackGreen/Black
Orange/BlackBlue/Black
Black/White
Red/White
Green/White
Blue/White
Black/Red
White/Red
Orange/Red
Blue/Red
Red/Green
+DC-0
+DC-0
IN-01
IN-12
IN-23
IN-34
IN-4
9
IN-5
10
IN-6IN-7
5678
LOAD
-
+
1
19
345678910111213
15161718
20
14
2
24
212223
25
-DC-0
B
3
4567
A012
Black
WhiteRed
Green
Orange
Blue
White/Black
Red/BlackGreen/Black
Orange/BlackBlue/Black
Black/White
Red/White
Green/White
Blue/White
Black/Red
White/Red
Orange/Red
Blue/Red
Red/Green
+DC-1
IN-811
IN-912
IN-1013
IN-1114
IN-12
19
IN-13
20
IN-14IN-15
15161718
LOAD
-
+
1
19
345678910111213
15161718
20
14
2
24
212223
25
-DC-1
+DC-0
+DC-1
INPUT 03INPUT 02INPUT 01INPUT 00
INPUT 07INPUT 06INPUT 05INPUT 04
+DC-1
INPUT 11INPUT 10INPUT 09INPUT 08
INPUT 15INPUT 14INPUT 13INPUT 12
Cable A
Cable B
IMPORTANT
44 Rockwell Automation Publication 1492-SG121E-EN-P - July 2016
Wiring Diagrams - Digital Inputs
1771-IVN to 1756-IV32There are several key application considerations and system specifications (bottom of drawing) when using these components (conversion module, cable and input module). Read and understand these considerations before installation.
18DC-0 (+)
IN-01
IN-1619
IN-12
IN-1720
IN-23
IN-1821
IN-34
IN-1922
IN-45
IN-2023
IN-56
IN-2124
IN-67
IN-2225
Black
White
Red
Green
Orange
Blue
White/Black
Red/Black
Green/Black
Orange/Black
Blue/Black
Black/White
Red/White
Green/White
Blue/White
Black/Red
White/Red
Orange/Red
Blue/Red
Red/Green
IN-78
12345647859
24
10611
25
12713
26
8
9291030
15
27
1617
28
18
2
1920
14
2122
13
2324
14
25
33
26
15
27
34
28
16
29
35
30
17
31
36
32
18
33
37
22
35
38
3637
34
DC-1 (+)36
IN-2326
IN-89
IN-2427
IN-910
IN-2528
IN-1011
IN-2629
IN-1112
IN-2730
IN-1213
IN-2831
IN-1314
IN-2932
IN-1415
IN-3033
Orange/Green
Black/White/Red
White/Black/Red
Red/Black/White
Green/Black/White
Orange/Black/White
Blue/Black/White
Black/Red/Green
White/Red/Green
Red/Black/Green
Green/Black/Orange
Orange/Black/Green
Blue/White/Orange
Black/White/Orange
White/Red/Orange
Orange/White/Blue
IN-1516
IN-313417
DC-0 (+)White/Red/Blue DC-1 (+)
35
Input 01Input 01Input 02Input 02Input 03Input 03Input 04Input 04Input 05Input 05Input 06Input 06Input 07Input 07
Input 10
Input 11
Input 10
Input 12Input 13Input 13Input 14Input 14Input 15Input 15Input 16Input 16Input 17Input 17
Input 00
19392040111
23
10-30V dc (0)
3Input 00
Input 11
Input 12
31
1221
32
+-
10-30V dc (2)
10-30V dc (0)10-30V dc (1)10-30V dc (1)
10-30V dc (3)10-30V dc (2)
10-30V dc (3)
Conversion Module Installation and Application Considerations� The input delay times for the 1771-IVN module versus 1756-IV32 module are as follows: 1771-IVN 1756-IV32a) Off-to-On Delay 6ms (+/-2ms) 1ms (plus selectable filter)b) On-to-Off Delay 6ms (+/-2ms) 2ms (plus selectable filter)� The 1771-IVN has 4 groups (allowing 4 seperate power supplies) and the 1756-IV32 has 2 groups.
This module/cable combination ties Groups 0 & 1 from the 1771-IVN to Group 0 on the 1756-IV32 and it ties Groups 2 & 3 from the 1771-IVN to Group 1 on the 1756-IV32.Field wiring modification must be made to accommodate this if multiple supplies were used. If 4 supplies were used, 2 must be removed.
� Refer to your 1771-IVN and 1756-IV32 Installation Manual wiring schematics and diagrams for more details.[Reference Doc: 41170-934 (Version 02)]
1771-WN Swing ArmFrom 1771-IVN
Conversion Module1492-CM1771-LD005
Cable1492-CONCAB005Z� 1756-IV32
IMPORTANT
Rockwell Automation Publication 1492-SG121E-EN-P - July 2016 45
Wiring Diagrams - Digital Inputs
Notes:
46 Rockwell Automation Publication 1492-SG121E-EN-P - July 2016
Wiring Diagrams - Digital Outputs
1771-OA to 1756-OA8E
There are several key application considerations and system specifications (bottom of drawing) when using these components (conversion module, cable and input module). Read and understand these considerations before installation.
Conversion Module1492-CM1771-LD014
Conversion Module Installation and Application Considerations� This Bul. 1492 cable consists of a cable wired to one 1756-OA8E RTB. Recommended cable lengths of 0.5M or 1.0M (005=0.5M, 010=1.0M). See table 2 for other lengths.
� The 1771-OA module output current limits versus 1756-OA8E limits are as follows: 1771-OA 1756-OA8E w/ 1492-CONCAB005Ua) Current/Point 1.5A 2Ab) Current/Module 6A 4A @ 60°Cc) Surge Current/Pt 4A for 8.3ms 20A for 43 ms
� The 1771-OA has eight (8) 2A, 250V fuses - 1 per output. The 1756-OA8E is electronically fused per point. Refer to the 1756-OA8E Installation Manual for details on electronic fusing.
� Refer to your 1771-OA and 1756-OA8E Installation Manual wiring schematics and diagrams for more details. Ensure 1756 output module ratings are not exceeded. [Reference Doc: 41170-943 (Version 01)]
Cable1492-CONCAB005U�
B
3
4567
A
1771-WA Swing ArmFrom 1771-OA
012
Black
White
Red
Green
Orange
Blue
White/Black
Red/Black
Green/Black
Orange/Black
Blue/Black
Black/White
Red/White
Green/White
Blue/White
Black/Red
White/Red
Orange/Red
Blue/Red
Red/Green
L1
1756-OA8E
2
L2-0OUT-0
3
OUT-15
OUT-27
OUT-39
OUT-4
4
OUT-5
6
OUT-6
8
OUT-7
101214161811131517
L2-119
1Not Used
20L1-1
LOAD
L2
L1
L1-0L1-0L1-0L1-0L1-1L1-1L1-1L1-1
1
19
345678910111213
15161718
20
14
2
24
212223
25
L2
Output 00Output 01Output 02Output 03
Output 04Output 05Output 06Output 07
IMPORTANT
Rockwell Automation Publication 1492-SG121E-EN-P - July 2016 47
Wiring Diagrams - Digital Outputs
1771-OAD to 1756-OA16There are several key application considerations and system specifications (bottom of drawing) when using these components (conversion module, cable and input module). Read and understand these considerations before installation.
1771-WH, WHF, WHFB Swing ArmFrom 1771-OAD
Conversion Module1492-CM1771-LD006
Cable1492-CONCAB005X� 1756-OA16
Conversion Module Installation and Application Considerations� This Bul. 1492 cable consists of a cable wired to one 1756-OA16 RTB. Recommended cable lengths of 0.5M or 1.0M (005=0.5M, 010=1.0M). See table 2 for other lengths.
� The 1771-OAD module output current limits versus 1756-OA16 limits are as follows: 1771-OAD 1756-OA16 w/ 1492-CONCAB005Xa) Current/Point 2A 0.5Ab) Current/Module 8A 4Ac) Surge Current/point 25A for 100ms 5A for 43ms
� The L2 terminal (Terminal E) on the 1771-OAD module was an optional connection, but it is required for the 1756-OA16. This connection must be added if it was not connected.
� The 1771-OAD is rated 10V to 138V AC. The 1756-OA16 is rated 74V to 256V AC.
� Refer to your 1771-OAD and 1756-OA16 Installation Manual wiring schematics and diagrams for more details. Ensure 1756 output module ratings are not exceeded. [Reference Doc: 41170-935 (Version 01)]
10L1-0
OUT-01
OUT-12
OUT-23
OUT-34
OUT-45
OUT-56
OUT-67
OUT-78
OUT-811
OUT-912
OUT-1013
OUT-1114
OUT-1215
OUT-1316
OUT-1417
OUT-1518
Black
White
Red
Green
Orange
Blue
White/Black
Red/Black
Green/Black
Orange/Black
Blue/Black
Black/White
Red/White
Green/White
Blue/White
Black/Red
White/Red
Orange/Red
Blue/Red
Red/GreenL1-1
20
9L2-0
19L2-1
A
1
00
19
013
024
035
046
057
068
079
E
10111012111312
13151416151716
17 18
20
14
2
Output 14
Output 16Output 15
Output 17
Output 04
Output 06
OutputDevice
Output 05
Output 07
Output 00
Output 02Output 01
Output 03
Output 10
Output 12Output 11
Output 13
L1
L2
BCD
L1L1L1
L1
L2
24
212223
25
IMPORTANT
48 Rockwell Automation Publication 1492-SG121E-EN-P - July 2016
Wiring Diagrams - Digital Outputs
1771-OAN to 1756-OA16
1771-WN Swing ArmFrom 1771-OAN
There are several key application considerations and system specifications (bottom of drawing) when using these components (conversion module, cable and input module). Read and understand these considerations before installation.
1756-OA16
1756-OA16
Conversion Module1492-CM1771-LD013
Cable1492-CONCAB005S3�
Conversion Module Installation and Application Considerations� This Bul. 1492 cable consists of a cable wired to two 1756-OA16 RTB. Recommended cable lengths of 0.5M or 1.0M (005=0.5M, 010=1.0M). See table 2 for other lengths.
� The 1771-OAN module output current limits versus 1756-OA16 limits are as follows: 1771-OAN 1756-OA16 w/ 1492-CONCAB005S3a) Current/Point 1A 0.5Ab) Current/Module 8A (32 pts) 2A (16 pts)c) Surge Current/Point 10A for 25ms 5A for 43ms
� The 1771-OAN has 4 groups (allowing 4 separate power supplies). This module/cable combination ties all 4 groups from the 1771-OAN together. Field wiring modification must be made to accommodate this if mulitple supplies were used. If more than 1 supply was used, all but 1 of the power supplies must be removed.
� The 1771-OAN did not allow connections for L2, however the 1756-OA16 requires an L2 connection for proper operation. The 1771-OAN did not use terminals 10, 20, 30, 40. These terminals have been reassigned for an L2 connection in this application. The installer must rewire L2 to one of these terminals.
� Refer to your 1771-OAN and 1756-OA16 Installation Manual wiring schematics and diagrams for more details. Ensure 1756 output module ratings are not exceeded.
� This configuration uses two (2) 1756-OA16 output modules to replace a single 1771-OAN output module. This may require the use of a larger 1756 I/O chassis and conversion mounting assembly. Ensure there is sufficient panel space to allow for this possibility. [Reference Doc: 41170-942 (Version 02)]
10 L1-0L2-01 OUT-02 OUT-13 OUT-24
OUT-12
5
OUT-13
6
OUT-14
7
OUT-15
81112131415161718
BlackWhiteRedGreenOrange
BlueWhite/Black
Red/BlackGreen/Black
Orange/BlackBlue/BlackBlack/WhiteRed/WhiteGreen/WhiteBlue/WhiteBlack/RedWhite/Red
12345
78910
18
111213
151617
14
L1-119
9
OUT-3
20
L2-1
OUT-4OUT-5OUT-6OUT-7OUT-8OUT-9OUT-10OUT-11
10
123456781112131415161718
19
9
20
20 Red/Green21 Orange/Green
22 Black/White/Red
24 Red/Black/White
25 Green/Black/White
26 Orange/Black/White27 Blue/Black/White28 Black/Red/Green29 White/Red/Green
30 Red/Black/Green
31 Green/Black/Orange32 Orange/Black/Green33 Blue/White/Orange
34 Black/White/Orange
35 White/Red/Orange36
White/Red/Blue37
A EL
UD
OM
B EL
UD
OM
30
202
40
43
65
87
129
34
13
1
1615
1817
22
19
2423
2625
2827
3229
11
33
10L2L2
L2L2
Output 00Output 01Output 02Output 03Output 04Output 05Output 06Output 07Output 10Output 11
Output 13
Output 15
Output 12
Output 17
L1
35
31
14
L1
21L1
Output 14
Output 16
38
3637
39
L1
Output 00Output 01Output 02Output 03Output 04Output 05Output 06Output 07Output 10Output 11
Output 13
Output 15
Output 12
Output 17
Output 14
Output 16
Orange/Red
6
L1-0L2-0OUT-0OUT-1OUT-2
OUT-12OUT-13OUT-14OUT-15L1-1
OUT-3
L2-1
OUT-4OUT-5OUT-6OUT-7OUT-8OUT-9OUT-10OUT-11
23 White/Black/Red
Orange/White/Blue
L1
L2
OutputDevice
19 Blue/Red
IMPORTANT
Rockwell Automation Publication 1492-SG121E-EN-P - July 2016 49
Wiring Diagrams - Digital Outputs
1771-OB to 1756-OB16D
1756-OB16D
There are several key application considerations and system specifications (bottom of drawing) when using these components (conversion module, cable and input module). Read and understand these considerations before installation.
WARNING
1771-WA Swing ArmFrom 1771-OB
1771-WA Swing ArmFrom 1771-OB Conversion Module
1492-CM1771-LD014
Conversion Module1492-CM1771-LD014 Cable
1492-C005005XF�
Conversion Module Installation and Application Considerations� This Bul. 1492 cable consists of 2 separate cables (cable “A” and cable “B”) wired to one 1756-OB16D RTB. Each cable can be either 0.5M or 1.0M (005=0.5M, 010=1.0M). Ensure that cable A and cable B are connected to the correct module in the conversion.
� The 1771-OB module output current limits versus 1756-OB16D limits are as follows: 1771-OB 1756-OB16D w/ 1492-C005005XFa) Current/Point 1.5A 2Ab) Current/Module 6A 4A @ 60°Cc) Surge Current/Point 4A for 8.3ms 4A for 10ms
� The 1771-OB has eight (8) 2A, 250V fuses - 1 per output. The 1756-OB16D is a DIAGNOSTIC MODULE. Refer to the 1756-OB16D Installation Manual for details on diagnostics.
� Refer to your 1771-OB and 1756-OB16D Installation Manual wiring schematics and diagrams for more details. Ensure 1756 output module ratings are not exceeded. [Reference Doc: 41170-988 (Version 00)]
B
3
4567
A012
Black
WhiteRed
Green
Orange
Blue
White/Black
Red/BlackGreen/Black
Orange/BlackBlue/Black
Black/White
Red/White
Green/White
Blue/White
Black/Red
White/Red
Orange/Red
Blue/Red
Red/Green
L1GND-0 OUT-0
1
OUT-13
OUT-25
OUT-37
OUT-4
2
OUT-5
4
OUT-6
6
OUT-7
8101214
9111315
GND-016
16
LOAD
-
+
+DC-0+DC-0+DC-0+DC-0+DC-0+DC-0+DC-0
1
19
345678910111213
15161718
20
14
2
24
212223
25
L2
Output 00Output 01Output 02Output 03
Output 04Output 05Output 06Output 07
B
3
4567
A012
Black
WhiteRed
Green
Orange
Blue
White/Black
Red/BlackGreen/Black
Orange/BlackBlue/Black
Black/White
Red/White
Green/White
Blue/White
Black/Red
White/Red
Orange/Red
Blue/Red
Red/Green
L1
OUT-817
OUT-919
OUT-1021
OUT-1123
OUT-12
18
OUT-13
20
OUT-14
22
OUT-15
2426283025272931
GND-132
32
LOAD
-
+
+DC-1+DC-1+DC-1+DC-1+DC-1+DC-1+DC-1
GND-1
1
19
345678910111213
15161718
20
14
2
24
212223
25
L2
Output 00Output 01Output 02Output 03
Output 04Output 05Output 06Output 07
GND-1
CABLE”A”
CABLE”B”
NOT USED
34
NOT USED33
NOT USED35
ONT USED36
IMPORTANT
50 Rockwell Automation Publication 1492-SG121E-EN-P - July 2016
Wiring Diagrams - Digital Outputs
1771-OBD to 1756-OB16E
There are several key application considerations and system specifications (bottom of drawing) when using these components (conversion module, cable and input module). Read and understand these considerations before installation.
WARNING
1771-WH, WHF, WHFB Swing ArmFrom 1771-OBD
Conversion Module1492-CM1771-LD006
Cable1492-CONCAB005X� 1756-OB16E
Conversion Module Installation and Application Considerations� This Bul. 1492 cable consists of a cable wired to one 1756-OA16 RTB. Recommended cable lengths of 0.5M or 1.0M (005=0.5M, 010=1.0M). See table 2 for other lengths.
� The 1771-OBD module output current limits versus 1756-OB16E limits are as follows: 1771-OBD 1756-OB16E w/ 1492-CONCAB005X
a) Current/Point 2A 1Ab) Current/Module 8A 4Ac) Surge Current/point 4A for 10ms 2A for 10ms
� The 1771-OBD has a single 10A, 250V rectifier fuse (1/4 x 1 1/4 inch). The 1756-OB16E is electronically fused pergroup. Refer to the 1756-OB16E Installation Manual for details on electronic fusing.
� The 1771-OBD is rated 10V to 60V DC. The 1756-OB16E is rated 10V to 31.2V DC. If the load source voltage is greater than 30V DC, then use the 1756-OC8 with the 1492-CM1771-LD008F conversion module.
� Refer to your 1771-OBD and 1756-OB16E Installation Manual wiring schematics and diagrams for more details. Ensure 1756 output module ratings are not exceeded. [Reference Doc: 41170-936 (Version 01)]
+
+
-
-
10DC-0+
OUT-01
OUT-12
OUT-23
OUT-34
OUT-45
OUT-56
OUT-67
OUT-78
OUT-811
OUT-912
OUT-1013
OUT-1114
OUT-1215
OUT-1316
OUT-1417
OUT-1518
Black
White
Red
Green
Orange
Blue
White/Black
Red/Black
Green/Black
Orange/Black
Blue/Black
Black/White
Red/White
Green/White
Blue/White
Black/Red
White/Red
Orange/Red
Blue/Red
Red/GreenDC-1+
20
9RTN OUT-0
19RTN OUT-1
A
1
00
19
013
024
035
046
057
068
079
E
10111012111312
13151416151716
17 18
20
14
2
Output 14
Output 16Output 15
Output 17
Output 04
Output 06
dc OutputDevice
Output 05
Output 07
Output 00
Output 02Output 01
Output 03
Output 10
Output 12Output 11
Output 13
+ dc
L2
BCD
+ dc+ dc+ dc
24
212223
25
IMPORTANT
Rockwell Automation Publication 1492-SG121E-EN-P - July 2016 51
Wiring Diagrams - Digital Outputs
1771-OBD to 1756-OC8
Conversion Module Installation and Application Considerations� This Bul. 1492 cable consists of a cable wired to two 1756-OC8 RTB. Recommended cable lengths of 0.5M or 1.0M (005=0.5M, 010=1.0M). See table 2 for other lengths.
� The 1771-OBD module output current limits versus 1756-OC8 limits are as follows: 1771-OBD 1756-OC8 w/ 1492-CONCAB005S1a) Current/Point 2A 2Ab) Current /Module 8A 8Ac) Surge Current /Point 4A for 10ms 4A for 10ms
� The 1771-OBD has a single 10A, 250V rectifier fuse (1/4 x 1 1/4 inch ). The 1756-OC8 is NOT fused ,as such a2AG fuse clip and 10A fuse is provided on the 1492-CM1771-LD008F conversion module.
� The 1771-OBD is rated 10V to 60V DC. The 1756-OC8 is rated 30V to 60V DC. If the load source voltages is lessthan 30V DC, then use 1756-OB16E with the 1492-CM1771-LD006 conversion module.
� This configuration uses two(2) 1756-OC8 output modules to replace a single 1771-OBD output module. This may requirethe use of a larger 1756 I/O chassis and conversion mounting assembly. Ensure there is sufficient panel space to allow forthis possibility.
� Refer to your 1771-OBD and 1756-OC8 Installation Manual wiring schematics and diagrams for more details. Ensure1756 output module ratings are not exceeded. [Reference Doc: 41170-937 (Version 01)]
There are several key application considerations and system specifications (bottom of drawing) when using these components (conversion module, cable and input module). Read and understand these considerations before installation.
1
2
3
4
5
67891011121314151617
18
1920212223
242526272829303132333435
3736
ABCD
010203040506071011121314151617
00
DC(+)
DC(-)
DC(+)DC(+)DC(+)
E
LOAD
+
- Output 01Output 02Output 03Output 04Output 05Output 06Output 07Output 10Output 11Output 12Output 13Output 14Output 15Output 16Output 17
Output 00
1771-WH, WHF, WHFB Swing ArmFrom 1771-OBD
Green/Black/Orange
Orange/Black/Green
Blue/White/Orange
Black/White/Orange
White/Red/Orange
White/Red/Blue
Orange/Green
Black/White/Red
White/Black/Red
Red/Black/White
Green/Black/White
Orange/Black/White
Blue/Black/White
Black/Red/Green
White/Red/Green
Red/Black/Green
Black
White
Red
Green
Orange
Blue
White/Black
Red/Black
Green/Black
Orange/Black
Blue/Black
Black/White
Red/White
Green/White
Blue/White
Black/Red
White/Red
Orange/Red
Blue/Red
Red/Green
1
3
5
7
468101214161811131517
20
21357
468101214161811131517
2019
9
19
9
DC-0(+)
OUT-0
OUT-1
OUT-2
OUT-3
DC-0(+)DC-0(+)DC-0(+)RTN OUT-0DC-1(+)DC-1(+)DC-1(+)DC-1(+)OUT-4OUT-5OUT-6OUT-7
RTN OUT-1
DC-0(+)OUT-0OUT-1OUT-2OUT-3
DC-0(+)DC-0(+)DC-0(+)RTN OUT-0DC-1(+)DC-1(+)DC-1(+)DC-1(+)OUT-4OUT-5OUT-6OUT-7
RTN OUT-1RTN OUT-1
RTN OUT-0
RTN OUT-1
RTN OUT-0
2
MO
DU
LE B
MO
DU
LE A
Conversion Module1492-CM1771-LD008F
Cable1492-CONCAB005S1� 1756-OC8
1756-OC8
IMPORTANT
52 Rockwell Automation Publication 1492-SG121E-EN-P - July 2016
Wiring Diagrams - Digital Outputs
1771-OBDS to 1756-OB16E
There are several key application considerations and system specifications (bottom of drawing) when using these components (conversion module, cable and input module). Read and understand these considerations before installation.
1771-WH, WHF, WHFB Swing ArmFrom 1171-OBDS
� This Bul. 1492 cable consists of a cable wired to one 1756-OB16E RTB. Recommended cable lengths of 0.5M or 1.0M (005=0.5M, 010=1.0M). See table 2 for other lengths.
� The 1771-OBDS module output current limits versus 1756-OB16E limits are as follows: 1771-OBDS 1756-OB16E w/ 1492-CONCAB005Xa) Current/Point 1A 1Ab) Current/Module 8A 8Ac) Surge Current/Point 4A for 10ms 2A for 10ms
� The 1771-OBDS has a single 12A, 250V rectifier fuse (1/4 x 1-1/4 inch). The 1756-OB16E is electronically fused per group. Refer to the 1756-OB16E Installation Manual for details on electronic fusing.
� The 1771-OBDS is rated 10V to 40V DC. The 1756-OB16E is rated 10V to 31.2V DC. If the load source voltage is greaterthan 30V DC, then use the 1756-OC8 with the 1492-CM1771-LD008F conversion module.
� Refer to your 1771-OBDS and 1756-OB16E Installation Manual wiring schematics and diagrams for more details. Ensure1756 output module ratings are not exceeded. [Reference Doc: 41171-005 (Version 00)]
Conversion Module Installation and Application Considerations
Conversion Module1492-CM1771-LD006
Cable1492-CONCAB005X� 1756-OB16E
10DC-0+
OUT-01
OUT-12
OUT-23
OUT-34
OUT-45
OUT-56
OUT-67
OUT-78
OUT-811
OUT-912
OUT-1013
OUT-1114
OUT-1215
OUT-1316
OUT-1417
OUT-1518
Black
WhiteRed
Green
Orange
Blue
White/Black
Red/BlackGreen/Black
Orange/BlackBlue/Black
Black/White
Red/White
Green/White
Blue/White
Black/Red
White/Red
Orange/Red
Blue/Red
Red/GreenDC-1+
20
9RTN OUT-0
19RTN OUT-1
A
1
00
19
013
024
035
046
057
068
079
E
10111012111312
13151416151716
17 18
20
14
2
Output 00
+ dc
- dc
B
CD
dc OutputDevice
Output 01Output 02Output 03Output 04Output 05Output 06Output 07Output 10
Output 11Output 12Output 13Output 14Output 15Output 16Output 17
+
-
+-
+ dc
+ dc
+ dc
24
212223
25
IMPORTANT
Rockwell Automation Publication 1492-SG121E-EN-P - July 2016 53
Wiring Diagrams - Digital Outputs
1771-OBN to 1756-OB32
Conversion Module Installation and Application ConsiderationsThe 1771-OBN module output current limits versus 1756-OB32 limits are as follows:
1771-OBN 1756-OB32w/1492-CONCAB005Za) Current/Point 0.5A 0.35A @ 60˚Cb) Current/Module 8A 6A @ 60˚Cc) Surge Current/Point 2A for 10ms 1A for 10ms
The 1771-OBN has four (4) 4A, 250V rectifier fuses. The 1756-OB32 is NOT fused, as such four (4) 2AG fuse clips and 4A fuses are provided on the 1492-CM1771-LD009F conversion module.
The 1492-CONAB005Z is limited to 3A per pin. The 1771-OBN has 4 groups (allowing 4 separate power supplies) and the 1756-OB32 has 2 groups. This module/cable
combination ties Groups 0 & 1 from the 1771-OBN to Group 0 on the 1756-OB32 and Groups 2 & 3 from the 1771-OBN to Group 1 on the 1756-OB32. Field wiring modification must be made to accommodate this if multiple supplies were used. If 4 supplies were used, 2 must be removed.
Refer to your 1771-OBN and 1756-OB32 Installation Manual wiring schematics and diagrams for more details. Ensure 1756 output module ratings are not exceeded. 41170-938 (01)
There are several key application considerations and system specifications (bottom of drawing) when using these components (conversion module, cable and input module). Read and understand these considerations before installation.
WARNING
12
345678910
1112131415161718192021222324
25262728293031323334353637
Black
White
Red
Green
Orange
Blue
White/Black
Red/Black
Green/Black
Orange/Black
Blue/Black
Black/White
Red/White
Green/White
Blue/White
Black/Red
White/Red
Orange/Red
Blue/Red
Red/Green
Orange/Green
Black/White/Red
White/Black/Red
Red/Black/White
Green/Black/White
Orange/Black/White
Blue/Black/White
Black/Red/Green
White/Red/Orange
Red/Black/Green
Green/Black/Orange
Orange/Black/Green
Blue/White/Orange
Black/White/OrangeWhite/Red/Orange
Orange/White/Blue
White/Red/Blue
LOAD
+
-
10-30V dc(0)10-30V dc(1)10-30V dc(2)10-30V dc(3)
1836
11922032142252362472582692710281129123013311432153316341735
11121312223234245256267278289291232133314341535163617371838193910203040
DC-0(+)DC-1(+)
OUT-0OUT-16OUT-1OUT-17OUT-2OUT-18OUT-3OUT-19OUT-4OUT-20OUT-5OUT-21OUT-6OUT-22OUT-7OUT-23OUT-8OUT-24OUT-9OUT-25OUT-10OUT-26OUT-11OUT-27OUT-12OUT-28OUT-13OUT-29OUT-14OUT-30OUT-15OUT-31RTN OUT-0RTN OUT-1
Output 00Output 00Output 01Output 01Output 02Output 02Output 03Output 03Output 04Output 04Output 05Output 05Output 06Output 06Output 07Output 07Output 10Output 10Output 11Output 11Output 12Output 12Output 13Output 13Output 14Output 14Output 15Output 15Output 16Output 16Output 17Output 17Common 0Common 1Common 2Common 3
Conversion Module1492-CM1771-LD009F
Cable1492-CONCAB005Z 1756-OB32
1771-WN Swing ArmFrom 1771-OBN
IMPORTANT
54 Rockwell Automation Publication 1492-SG121E-EN-P - July 2016
Wiring Diagrams - Digital Outputs
1771-OC to 1756-OC8
There are several key application considerations and system specifications (bottom of drawing) when using these components (conversion module, cable and input module). Read and understand these considerations before installation.
1771-WA Swing ArmFrom 1771-OC
1756-OC8
Conversion Module1492-CM1771-LD014
Cable1492-CONCAB005V�
Conversion Module Installation and Application Considerations� This Bul. 1492 cable consists of a cable wired to one 1756-OC8 RTB. Recommended cable lengths of 0.5M or 1.0M (005=0.5M, 010=1.0M). See table 2 for other lengths.
� The 1771-OC module output current limits versus 1756-OC8 limits are as follows: 1771-OC 1756-OC8 w/ 1492-CONCAB005Va) Current/Point 1.5A 2Ab) Current/Module 8A 8A @ 60°Cc) Surge Current/Point 4A for 1.0ms 4A for 10ms
� The 1771-OC has eight (8) 2A, 250V fuses - 1 per output. Refer to the 1756-OC8 Installation Manual for details.
� Refer to your 1771-OC and 1756-OC8 Installation Manual wiring schematics and diagrams for more details. Ensure 1756 output module ratings are not exceeded. [Reference Doc: 41171-020 (Version 00)]
B
3
4567
A012
Black
WhiteRed
Green
Orange
Blue
White/Black
Red/BlackGreen/Black
Orange/BlackBlue/Black
Black/White
Red/White
Green/White
Blue/White
Black/Red
White/Red
Orange/Red
Blue/Red
Red/Green
+DC9
RTN-0OUT-0
1
OUT-13
OUT-25
OUT-37
OUT-4
2
OUT-5
4
OUT-6
6
OUT-7
81214161811131517
RTN-119
10
20RTN-1
LOAD
-DC
+DC
+DC-0+DC-0+DC-0+DC-0+DC-1+DC-1+DC-1+DC-1
1
19
345678910111213
15161718
20
14
2
24
212223
25
RTN
Output 00Output 01Output 02Output 03
Output 04Output 05Output 06Output 07
RTN-0
IMPORTANT
Rockwell Automation Publication 1492-SG121E-EN-P - July 2016 55
Wiring Diagrams - Digital Outputs
1771-OD to 1756-OA16I
41170-994 (01)
12345
678910111213
151617181920
14
21222324252627282930313233
353637
34
LOAD
1756-OA16I214365
1492-C005005XM
Orange
Blue
White/Black
Red/BlackGreen/Black
Orange/BlackBlue/Black
Black/White
Red/White
Green/White
Blue/White
Black/Red
White/Red
Orange/Red
Blue/Red
Red/Green
8710912
Orange/Green
Black/White/Red
White/Black/Red
Red/Black/WhiteGreen/Black/White
Orange/Black/WhiteBlue/Black/White
Black/Red/Green
White/Red/Green
Red/Black/Green
Green/Black/Orange
Orange/Black/Green
Blue/White/Orange
Black/White/Orange
White/Red/Orange
Orange/White/Blue
11
L1L21
56789101112
1771-WD Swing ArmFrom 1771-OD
234
1
3
2
4
N.O.
N.C.
1
3
2
4
N.O.
N.C.
JMP0
JMP1
1
3
2
4
N.O.
N.C.
JMP2
1
3
2
4
N.O.
N.C.
1
3
2
4
N.O.
N.C.
JMP3
JMP4
1
3
2
4
N.O.
N.C.
JMP5
1
3
2
4
N.O.
N.C.
JMP6
1
3
2
4
N.O.
N.C.
JMP7
2 The 1492-COO5005XM is limited to 3A per pin.
2 The 1771-OD module output resistive current limits versus 1756-OA16I limits are as follows:(NOTE: for switching and inductive current ratings, refer to the modules Installation Instructions) 1771-OD 1756-OA16I w/ 1492-CONCAB005XMa) Current/Point 0.2A @ 138V AC 2A @ 240V AC 1A @ 30V DC 2A @ 30V DC 0.25A@ 125V DC 0.25A @ 125V DC
CONVERSION MODULE INSTALLATION AND APPLICATION CONSIDERATIONS
3 The 1771-OD module had a jumper selection of N.O. and N.C. outputs. The 1756-OA16I has both N.O. and N.C. outputs, but selection is by wiring termination on the 1756 swing arm. The 1492-CM1771-LD012 conversion module replaces the functionalityof the 1771-OD jumpers with eight jumpers (JMP0 through JMP7). In the default position, the output will be N.O.. If a N.C. output isrequired, change the jumper from pins 1-2 to pins 3-4.
4 Refer to your 1771-OD and 1756-OA16I Installation Manual wiring schematics and diagrams for more details. Ensure1756 output module ratings are not exceeded.
There are several key application considerations and system specifications (bottom of drawing) when usingthese components (conversion module, cable and output module). Read and understand these considerationsbefore installation. In addition, refer to the current draw requirements of the existing loads for this configurationto ensure they are within the current ratings of the 1756 output module.
12345
678910111213
151617181920
14
21222324252627282930313233
353637
34
Orange
Blue
White/Black
Red/BlackGreen/Black
Orange/BlackBlue/Black
Black/White
Red/White
Green/White
Blue/White
Black/Red
White/Red
Orange/Red
Blue/Red
Red/Green
Orange/Green
Black/White/Red
White/Black/Red
Red/Black/WhiteGreen/Black/White
Orange/Black/WhiteBlue/Black/White
Black/Red/Green
White/Red/Green
Red/Black/Green
Green/Black/Orange
Orange/Black/Green
Blue/White/Orange
Black/White/Orange
White/Red/Orange
Orange/White/Blue
1
56789101112
1771-WD Swing ArmFrom 1771-OD
234
1
3
2
4
N.O.
N.C.
1
3
2
4
N.O.
N.C.
JMP0
JMP1
1
3
2
4
N.O.
N.C.
JMP2
1
3
2
4
N.O.
N.C.
1
3
2
4
N.O.
N.C.
JMP3
JMP4
1
3
2
4
N.O.
N.C.
JMP5
1
3
2
4
N.O.
N.C.
JMP6
1
3
2
4
N.O.
N.C.
JMP7
252627282930313233343536
NOT USED
NOT USEDNOT USED
141316151817201922212423
L1-6L2-6L1-7
L2-7L1-8L2-8
L2-9L1-9
L2-10L1-10
L1-11L2-11
NOT USEDNOT USEDNOT USEDNOT USEDNOT USEDNOT USEDNOT USEDNOT USED
L1-0
L2-0
L1-1L2-1L1-2L2-2
L2-3L1-3
L2-4L1-4
L1-5L2-5
LOADL1L2
L1-6
L2-6
L1-7L2-7L1-8L2-8
L2-9L1-9
L2-10L1-10
L1-11L2-11
L1-0L2-0L1-1L2-1L1-2L2-2
L2-3L1-3
L2-4L1-4
L1-5L2-5
1492-CM1771-LD012CONVERSION MODULE
1492-CM1771-LD012CONVERSION MODULE
CABLE”A”
CABLE”B”NOT USED
This Bul. 1492 cable consists of 2 separate cables (cable “A” and “B”) wired to one 1756-IM16I RTB. Each cable can be either 0.5M or 1.0M (005=0.5M, 010=1.0M). Ensure that cable A and cable B are connected to the correct module in the conversion.
1
1
IMPORTANT
56 Rockwell Automation Publication 1492-SG121E-EN-P - July 2016
Wiring Diagrams - Digital Outputs
1771-OD16 to 1756-OA16I
There are several key application considerations and system specifications (bottom of drawing) when using these components (conversion module, cable and input module). Read and understand these considerations before installation.
Conversion Module Installation and Application Considerations � This Bul. 1492 cable consists of a cable wired to one 1756-OA16I RTB. Recommended cable lengths of 0.5M or 1.0M (005=0.5M, 010=1.0M). See table 2 for other lengths.
� The 1771-OD16 module output current limits versus 1756-OA16I limits are as follows: 1771-OD16 1756-OA16I w/ 1492-CONCAB005Ya) Current/Point 2A 1Ab) Current/Module 8A 4Ab) Surge Current/Point 20A for 100ms 20A for 43ms
� The 1771-OD16 has sixteen (16) 3A ,250V recifier fuses. The 1756-OA16I is NOT fused,as such sixteen (16) 2AG fuseclips are provided on the 1492-CM1771-LD010F conversion module. Max fuse rating is 1.5A based on 1756-OA16I.
� The 1771-OD16 is rated 74V to 138V AC and 105V to 138V DC. The 1756-OA16I is rated 74V to 265V AC. A1756 isolated output module with an equivalent DC voltage range to convert the1771 -OD16 is not available.
� Refer to your 1771-OD16 and 1756-OA16I Installation Manual wiring schematics and diagrams for more details. Ensure 1756 output module rating are not exceeded. [Reference Doc: 41170-939 (Version 01)]
10 9
19202143
6 5 8 712111413161518172221242326252827323134333635383729303940
Output 10
Output 12
Output 11
Output 13
Output 2
Output 4
Output 3
Output 5
Not Used
Output 0
Not Used
Output 1
Output 6
Output 8
Output 7
Output 9
L1-14 Output 14
L1-15 Output 15
Not usedNot usedNot usedNot used
12345678910111213
151617181920
14
21222324252627282930313233
353637
34
OUT-0
21
OUT-1
43
OUT-2
65
OUT-3
87
OUT-4
109
OUT-5
1211
OUT-6
1413
Orange
Blue
White/Black
Red/BlackGreen/Black
Orange/BlackBlue/Black
Black/White
Red/White
Green/White
Blue/White
Black/Red
White/Red
Orange/Red
Blue/Red
Red/GreenOUT-7
1615
OUT-8
1817
OUT-9
2019
OUT-10
2221
OUT-11
2423
OUT-12
2625
OUT-13
2827
OUT-14
3029
Orange/Green
Black/White/Red
White/Black/Red
Red/Black/WhiteGreen/Black/White
Orange/Black/WhiteBlue/Black/White
Black/Red/Green
White/Red/Green
Red/Black/Green
Green/Black/Orange
Orange/Black/Green
Blue/White/Orange
Black/White/Orange
White/Red/Orange
Orange/White/BlueOUT-15
3231
L1-0
L1-1
L1-2
L1-3
L1-4
L1-5
L1-6
L1-7
L1-8
L1-9
L1-10
L1-11
L1-12
L1-13
L1-14
L1-15
L2
Not Used
Not Used
L1-0
L1-1
L1-2
L1-3
L1-4
L1-5
L1-6
L1-7
L1-8
L1-9
L1-10
L1-11
L1-12
L1-13
LOADL1
1771-WN Swing ArmFrom 1771-OD16
Conversion Module1492-CM1771-LD010F
1756-OA16I Cable
1492-CONCAB005Y�
IMPORTANT
Rockwell Automation Publication 1492-SG121E-EN-P - July 2016 57
Wiring Diagrams - Digital Outputs
1771-ODD to 1756-OA16I
There are several key application considerations and system specifications (bottom of drawing) when using these components (conversion module, cable and input module). Read and understand these considerations before installation.
Conversion Module Installation and Application Considerations� This Bul. 1492 cable consists of a cable wired to one 1756-OA16I RTB. Recommended cable lengths of 0.5M or 1.0M (005=0.5M, 010=1.0M). See table 2 for other lengths.
� The 1771-ODD module output current limits versus 1756-OA16I limits are as follows: 1771-ODD 1756-OA16I w/ 1492-CONCAB005Ya) Current/Point 2A 2Ab) Current/Module 8A 5Ac) Surge Current/Point 20A for 100ms 20A for 43ms
� The 1771-ODD has sixteen (16) 3A, 250V rectifier fuses. The 1756-OA16I is NOT fused, as such sixteen(16) 2AG fuses and clips are provided on the 1492-CM1771-LD010F conversion module. Max fuse rating is 1.5A based on 1756-OA16I.
� The 1771-ODD is rated 74V to 138V AC. The 1756-OA16I is rated 74V to 265V AC.
� Refer to your 1771-ODD and 1756-OA16I Installation Manual wiring schematics and diagrams for more details. Ensure 1756 output module ratings are not exceeded. [Reference Doc: 41171-009 (Version 00)]
12345678910111213
151617181920
14
21222324252627282930313233
353637
34
OUT-0
21
OUT-1
43
OUT-2
65
OUT-3
87
OUT-4
109
OUT-5
1211
OUT-6
1413
Orange
Blue
White/Black
Red/BlackGreen/Black
Orange/BlackBlue/Black
Black/White
Red/White
Green/White
Blue/White
Black/Red
White/Red
Orange/Red
Blue/Red
Red/GreenOUT-7
1615
OUT-8
1817
OUT-9
2019
OUT-10
2221
OUT-11
2423
OUT-12
2625
OUT-13
2827
OUT-14
3029
Orange/Green
Black/White/Red
White/Black/Red
Red/Black/WhiteGreen/Black/White
Orange/Black/WhiteBlue/Black/White
Black/Red/Green
White/Red/Green
Red/Black/Green
Green/Black/Orange
Orange/Black/Green
Blue/White/Orange
Black/White/Orange
White/Red/Orange
Orange/White/BlueOUT-15
3231
L1-0
L1-1
L1-2
L1-3
L1-4
L1-5
L1-6
L1-7
L1-8
L1-9
L1-10
L1-11
L1-12
L1-13
L1-14
L1-15
LOADL1
L2
40
21Ouput 0
3Ouput 1
5Ouput 2
7Ouput 3
11Ouput 4
13Ouput 5
15Ouput 6
17Ouput 7
21Ouput 8
23Ouput 9
25Ouput 10
27Ouput 11
31Ouput 12
33Ouput 13
35Ouput 14
37Ouput 15
L1-0
L1-1
L1-2
L1-3
L1-4
L1-5
L1-6
L1-7
L1-8
L1-9
L1-10
L1-11
L1-12
L1-13
L1-14
L1-15
4
6
8
29
12
14
16
18
30
22
24
26
28
39
32
34
36
38
910
20
19
Not Used
Not UsedNot UsedNot Used
Not Used
Not UsedNot UsedNot Used
1771-WN Swing ArmFrom 1771-ODD
1756-OA16I
Conversion Module1492-CM1771-LD010F
Cable1492-CONCAB005Y�
IMPORTANT
58 Rockwell Automation Publication 1492-SG121E-EN-P - July 2016
Wiring Diagrams - Digital Outputs
1771-ODZ to 1756-OA16I
Conversion Module1492-CM1771-LD012
Conversion Module1492-CM1771-LD012
1771-WD Swing ArmFrom 1771-ODZ
1771-WD Swing ArmFrom 1771-ODZ
Cable1492-C005005XP� 1756-OA16I
There are several key application considerations and system specifications (bottom of drawing) when using these components (conversion module, cable and input module). Read and understand these considerations before installation.
Conversion Module Installation and Application Considerations� This Bul. 1492 cable consists of 2 separate cables (cable “A” and cable “B”) wired to one 1756-OA16I RTB. Each cable can be either0.5M or 1.0M (005=0.5M, 010=1.0M). Ensure that cable A and cable B are connected to the correct module in the conversion
� The 1771-ODZ module output resistive current limits versus 1756-OA16I limits are as follows: 1771-ODZ 1756-OA16I w/ 1492-C005005XP a) Current/Point 2A 2A b) Current/Module 6A 5A @ 60°C c) Surge Current/Point 20A for 100ms 20A for 43ms
� The 1771-ODZ module had a jumper selection of N.O. and N.C. outputs. The 1756-OA16I has both N.O. and N.C. outputs, but selection is by wiring termination on the 1756 swing arm. The 1492-CM1771-LD012 conversion module replaces the functionalityof the 1771-ODZ jumpers with eight jumpers (JMP0 through JMP7). In the default position, the output will be N.O. If a N.C. output isrequired, change the jumper from pins 1-2 to pins 3-4.
� Refer to your 1771-ODZ and 1756-OA16I Installation Manual wiring schematics and diagrams for more details. Ensure 1756 output module ratings are not exceeded. [Reference Doc: 41171-016 (Version 00)]
2
8
1
4
16
6
5710
912
11
33343536
NOT USED
NOT USEDNOT USED
L1-0L1-0L2-0L2-1
L1-1L1-1
L2-3L2-2
L2-4
L1-2L1-2
L2-5
CABLE”A”
NOT USED
12345
678910111213
151617181920
14
21222324252627282930313233
353637
34
LOAD
1492-CONCAB005Y
Orange
Blue
White/Black
Red/BlackGreen/Black
Orange/BlackBlue/Black
Black/White
Red/White
Green/White
Blue/White
Black/Red
White/Red
Orange/Red
Blue/Red
Red/Green
Orange/Green
Black/White/Red
White/Black/Red
Red/Black/WhiteGreen/Black/White
Orange/Black/WhiteBlue/Black/White
Black/Red/Green
White/Red/Green
Red/Black/Green
Green/Black/Orange
Orange/Black/Green
Blue/White/Orange
Black/White/Orange
White/Red/Orange
Orange/White/Blue
L1
L2
+
- LOAD
1
56789101112
+V0/1
Out-0 N.O./N.C.
234
Out-1 N.O./N.C.
+V2/3
Out-2 N.O./N.C.
Out-3 N.O./N.C.
+V4/5
Out-4 N.O./N.C.
Out-5 N.O./N.C.
+V6/7
Out-6 N.O./N.C.
Out-7 N.O./N.C.
1
3
2
4
N.O.
N.C.
1
3
2
4
N.O.
N.C.
JMP0
JMP1
1
3
2
4
N.O.
N.C.
JMP2
1
3
2
4
N.O.
N.C.
1
3
2
4
N.O.
N.C.
JMP3
JMP4
1
3
2
4
N.O.
N.C.
JMP5
1
3
2
4
N.O.
N.C.
JMP6
1
3
2
4
N.O.
N.C.
JMP7
14
1315
L1-3
L2-6L2-7
12345
678910111213
151617181920
14
21222324252627282930313233
353637
34
LOAD
Orange
Blue
White/Black
Red/BlackGreen/Black
Orange/BlackBlue/Black
Black/White
Red/White
Green/White
Blue/White
Black/Red
White/Red
Orange/Red
Blue/Red
Red/Green
Orange/Green
Black/White/Red
White/Black/Red
Red/Black/WhiteGreen/Black/White
Orange/Black/WhiteBlue/Black/White
Black/Red/Green
White/Red/Green
Red/Black/Green
Green/Black/Orange
Orange/Black/Green
Blue/White/Orange
Black/White/Orange
White/Red/Orange
Orange/White/Blue
L1
L2
+
- LOAD
1
56789101112
+V0/1
Out-0 N.O./N.C.
234
Out-1 N.O./N.C.
+V2/3
Out-2 N.O./N.C.
Out-3 N.O./N.C.
+V4/5
Out-4 N.O./N.C.
Out-5 N.O./N.C.
+V6/7
Out-6 N.O./N.C.
Out-7 N.O./N.C.
1
3
2
4
N.O.
N.C.
1
3
2
4
N.O.
N.C.
JMP0
JMP1
1
3
2
4
N.O.
N.C.
JMP2
1
3
2
4
N.O.
N.C.
1
3
2
4
N.O.
N.C.
JMP3
JMP4
1
3
2
4
N.O.
N.C.
JMP5
1
3
2
4
N.O.
N.C.
JMP6
1
3
2
4
N.O.
N.C.
JMP7
L1-4L1-4L2-8L2-9L1-5L1-5
L2-11L2-10
L1-6L1-4
L2-12L2-13
L1-7L1-7
L2-14L2-15
3
L1-3
CABLE”B”18
24
17
20
32
22
212326
2528
27
30
2931
19
IMPORTANT
Rockwell Automation Publication 1492-SG121E-EN-P - July 2016 59
Wiring Diagrams - Digital Outputs
1771-OG to 1756-OG16
There are several key application considerations and system specifications (bottom of drawing) when using these components (conversion module, cable and input module). Read and understand these considerations before installation.
WARNING
1771-WC Swing ArmFrom 1771-OG
1771-WC Swing ArmFrom 1771-OG
Conversion Module1492-CM1771-LA003
Conversion Module1492-CM1771-LA003
Cable1492-C005005XS� 1756-OG16
OutputDevice
1325242322211918171612
SH
Output 0 + DC 10
OUT-0OUT-1
1
OUT-2
234567
98
Red/White
Green/Black/White
Black/White/Red
White/Black/Red
Orange/Green
Red/Black/White
Orange/Red
Blue/Red
+ -
A
34567B
012
Common
Output 1 Output 2 Output 3 Output 4 Output 5 Output 6 Output 7
3456789101112141520
OUT-3OUT-4OUT-5OUT-6OUT-7
+ DC -0
- DC -020
OUT-8OUT-9OUT-10OUT-11OUT-12OUT-13OUT-14OUT-15
+ DC -1
- DC -1
1325242322211918171612
SH
Red/White
Green/Black/White
Black/White/Red
White/Black/Red
Orange/Green
Red/Black/White
Orange/Red
Blue/Red
A
34567B
012
3456789101112141520
Output 8 + DC
Common
Output 9 Output 10 Output 11 Output 12 Output 13 Output 14 Output 15
111213141516171819
Black/Red
White/Red
Black/Red
White/Red
CABLE”B”
+
- 5V DCSUPPLY
OutputDevice
+ -
+
- 5V DCSUPPLY
Conversion Module Installation and Application Considerations � This Bul. 1492 cable consists of 2 separate cables (cable “A” and cable “B”) wired to one 1756-OG16 RTB. Each cable can be either 0.5M or 1.0M (005=0.5M, 010=1.0M). Ensure that cable A and cable B are connected to the correct module in the conversion.
� The input delay times for the 1771-OG module versus the 1756-OG16 module are as follows: 1771-OG 1756-OG16 w/ 1492-C005005XS a) Off-to-On Delay 1ms (+/-10ms) 45ms max (plus selectable filter) b) On-to-Off Delay 1ms (+/-10ms) 145ms max (plus selectable filter)
� The 1771-OG module is rated 5V DC TTL INPUT MODULE. The 1756-OG16 module is rated 5V DC TTL INPUT MODULE only.
� Refer to your 1771-OG and 1756-OG16 Installation and User Manuals for additional information concerning comparisons of module wiring, features and configuration details. [Reference Doc: 41171-028 (Version 00)]
CABLE”A”
IMPORTANT
60 Rockwell Automation Publication 1492-SG121E-EN-P - July 2016
Wiring Diagrams - Digital Outputs
1771-OGD to 1756-OG16
There are several key application considerations and system specifications (bottom of drawing) when using these components (conversion module, cable and input module). Read and understand these considerations before installation.
1771-WH, WHF, WHFB Swing ArmFrom 1171-OGD
� This Bul. 1492 cable consists of a cable wired to one 1756-OG16 RTB. Recommended cable lengths of 0.5M or 1.0M (005=0.5M, 010=1.0M). See table 2 for other lengths.
� The 1771-OGD module output current limits versus 1756-OG16 limits are as follows: 1771-OGD 1756-OG16 w/ 1492-CONCAB005Xa) Current/Point 1mA 24mAb) Current/Module 310mA 384mA
� The 1771-OGD has a single 10A, 250V rectifier fuse (1/4 x 1-1/4 inch). The 1756-OG16 is electronically fused per group. Refer to the 1756-OG16 Installation Manual for details on electronic fusing.
� The 1771-OGD is rated 10V to 60V DC. The 1756-OG16 is rated 10V to 31.2V DC.
� Refer to your 1771-OGD and 1756-OG16 Installation Manual wiring schematics and diagrams for more details. Ensure1756 output module ratings are not exceeded. [Reference Doc: 41171-006 (Version 00)]
Conversion Module Installation and Application Considerations
Conversion Module1492-CM1771-LD006
Cable1492-CONCAB005X� 1756-OG16
10DC-0+
OUT-01
OUT-12
OUT-23
OUT-34
OUT-45
OUT-56
OUT-67
OUT-78
OUT-811
OUT-912
OUT-1013
OUT-1114
OUT-1215
OUT-1316
OUT-1417
OUT-1518
Black
WhiteRed
Green
Orange
Blue
White/Black
Red/BlackGreen/Black
Orange/BlackBlue/Black
Black/White
Red/White
Green/White
Blue/White
Black/Red
White/Red
Orange/Red
Blue/Red
Red/GreenDC-1+
20
9RTN OUT-0
19RTN OUT-1
A
1
00
19
013
024
035
046
057
068
079
E
10111012111312
13151416151716
17 18
20
14
2
Output 00
+ dc
- dc
B
CD
dc OutputDevice
Output 01Output 02Output 03Output 04Output 05Output 06Output 07Output 10
Output 11Output 12Output 13Output 14Output 15Output 16Output 17
+
-
+-
+ dc
+ dc
+ dc
24
212223
25
IMPORTANT
Rockwell Automation Publication 1492-SG121E-EN-P - July 2016 61
Wiring Diagrams - Digital Outputs
1771-OM to 1756-OA16
1756-OA16
There are several key application considerations and system specifications (bottom of drawing) when using these components (conversion module, cable and input module). Read and understand these considerations before installation.
Conversion Module1492-CM1771-LD014
Conversion Module1492-CM1771-LD014
Cable1492-C005005XG�
Conversion Module Installation and Application Considerations� This Bul. 1492 cable consists of 2 separate cables (cable “A” and cable “B”) wired to one 1756-OA16 RTB. Each cable can be either 0.5M or 1.0M (005=0.5M, 010=1.0M). Ensure that cable A and cable B are connected to the correct module in the conversion.
� The 1771-OM module output current limits versus 1756-OA16 limits are as follows: 1771-OM 1756-OA16 w/ 1492-CONCAB005XGa) Current/Point 2A 0.5 @ 60°Cb) Current/Module 6A 4A @ 60°Cc) Surge Current/Point 20A for 100ms 5A for 43ms
� The 1771-OM module is rated 220V to 240V AC. The 1756-OA16 module is rated 74V to 265V AC only.
� Refer to your 1771-OM and 1756-OA16 Installation Manual wiring schematics and diagrams for more details. Ensure 1756 output module ratings are not exceeded. [Reference Doc: 41171-022 (Version 00)]
Cable “A”
B
3
4567
A012
Black
WhiteRed
Green
Orange
Blue
White/Black
Red/BlackGreen/Black
Orange/BlackBlue/Black
Black/White
Red/White
Green/White
Blue/White
Black/Red
White/Red
Orange/Red
Blue/Red
Red/Green
L1-0
L1-0
OUT-01
OUT-12
OUT-23
OUT-34
OUT-4
10
OUT-5OUT-6OUT-7
5678
LOAD
-
+
1
19
345678910111213
15161718
20
14
2
24
212223
25
L2-0
B
3
4567
A012
Black
WhiteRed
Green
Orange
Blue
White/Black
Red/BlackGreen/Black
Orange/BlackBlue/Black
Black/White
Red/White
Green/White
Blue/White
Black/Red
White/Red
Orange/Red
Blue/Red
Red/Green
OUT-811
OUT-912
OUT-1013
OUT-1114
OUT-12
20
OUT-13OUT-14OUT-15
15161718
LOAD
1
19
345678910111213
15161718
20
14
2
24
212223
25
L2-1
1771-WA Swing ArmFrom 1771-OM
1771-WA Swing ArmFrom 1771-OM
L1-1
OUTPUT 03OUTPUT 02OUTPUT 01OUTPUT 00
OUTPUT 07OUTPUT 06OUTPUT 05OUTPUT 04
L1-1
INPUT 11INPUT 10INPUT 09INPUT 08
INPUT 15INPUT 14INPUT 13INPUT 12
L1
L2
L1
L2
Cable “B”
L2-119
L2-09
IMPORTANT
62 Rockwell Automation Publication 1492-SG121E-EN-P - July 2016
Wiring Diagrams - Digital Outputs
1771-OMD to 1756-OA16
Conversion Module1492-CM1771-LD006
Cable1492-CONCAB005X�
There are several key application considerations and system specifications (bottom of drawing) when using these components (conversion module, cable and input module). Read and understand these considerations before installation.
Conversion Module Installation and Application Considerations
10L1-0+
OUT-01
OUT-12
OUT-23
OUT-34
OUT-45
OUT-56
OUT-67
OUT-78
OUT-811
OUT-912
OUT-1013
OUT-1114
OUT-1215
OUT-1316
OUT-1417
OUT-1518
Black
WhiteRed
Green
Orange
Blue
White/Black
Red/BlackGreen/Black
Orange/BlackBlue/Black
Black/White
Red/White
Green/White
Blue/White
Black/Red
White/Red
Orange/Red
Blue/Red
Red/GreenL1-1+
20
9L2-0
19L2-1
A
1
00
19
013
024
035
046
057
068
079
E
10111012111312
13151416151716
17 18
20
14
2
Output 00
L1
L2
B
CD
Output 01Output 02Output 03Output 04Output 05Output 06Output 07Output 10
Output 11Output 12Output 13Output 14Output 15Output 16Output 17
L1
L2
+-
24
212223
25
LOAD
L1
L1
L1
� This Bul. 1492 cable consists of a cable wired to one 1756-OA16 RTB. Recommended cable lengths of0.5M or 1.0M (005=0.5M, 010=1.0M). See table 2 for other lengths.
� The 1771-OMD module output current limits versus 1756-OA16 limits are as follows: 1771-OMD 1756-OA16 w/ 1492-CONCAB005Xa) Current/Point 2A 0.5Ab) Current/Module 8A 4Ac) Surge Current/Point 25A for 100ms 5A for 43ms
� The 1771-OMD has a single 10A, 250V rectifier fuse (1/4 x 1 1/4 inch). The 1756-OA16 has a mechanical 3.15A @250V AC slow blow fuse. Refer to the 1756-OA16 Installation Manual for details on electronic fusing.
� The 1771-OMD is rated 184V to 250V AC. The 1756-OA16 is rated 74V to 265V AC. If the load source voltage is greater than 30V DC, then use the 1756-OC8 with the 1492-CM1771-LD008F conversion module.
� Refer to your 1771-OMD and 1756-OA16 Installation Manual wiring schematics and diagrams for more details. Ensure 1756 output module ratings are not exceeded. [Reference Doc: 41171-007 (Version 00)]
1756-OA16
1771-WH, WHF, WHFB Swing ArmFrom 1771-OMD
IMPORTANT
Rockwell Automation Publication 1492-SG121E-EN-P - July 2016 63
Wiring Diagrams - Digital Outputs
1771-ON to 1756-ON8
There are several key application considerations and system specifications (bottom of drawing) when using these components (conversion module, cable and input module). Read and understand these considerations before installation.
WARNING
1771-WA Swing ArmFrom 1771-ON
Conversion Module1492-CM1771-LD014
1756-ON8 Cable
1492-CONCAB005W�
Conversion Module Installation and Application Considerations� This Bul. 1492 cable consists of a cable wired to one 1756-ON8 RTB. Recommended cable lengths of 0.5M or 1.0M (005=0.5M, 010=1.0M). See table 2 for other lengths.
� The 1771-ON module output current limits versus 1756-ON8 limits are as follows: 1771-ON 1756-ON8 w/ 1492-CONCAB005Wa) Current/Point 1.5A 2Ab) Current/Module 6A 5A @ 60°Cc) Surge Current/Point 4A for 10ms 20A for 43ms
� The 1771-ON has eight (8) 2A, 250V fuses - 1 per output. The 1756-ON8 is electronically fused per point. Refer to the 1756-ON8 Installation Manual for details on electronic fusing.
� Refer to your 1771-ON and 1756-ON8 Installation Manual wiring schematics and diagrams for more details. Ensure 1756 output module ratings are not exceeded. [Reference Doc: 41171-021 (Version 00)]
B
3
4567
A012
Black
WhiteRed
Green
Orange
Blue
White/Black
Red/BlackGreen/Black
Orange/BlackBlue/Black
Black/White
Red/White
Green/White
Blue/White
Black/Red
White/Red
Orange/Red
Blue/Red
Red/Green
L1 2NOT USED
OUT-01
OUT-13
OUT-25
OUT-37
OUT-4
4
OUT-5
6
OUT-6
8
OUT-7
101214161811131517
NOT USED19
9
L1-0
20L1-1
LOAD
L2
L1
L1-0L1-0L1-0L1-0L1-1L1-1L1-1L1-1
1
19
345678910111213
15161718
20
14
2
24
212223
25
L2
Output 00Output 01Output 02Output 03
Output 04Output 05Output 06Output 07
IMPORTANT
64 Rockwell Automation Publication 1492-SG121E-EN-P - July 2016
Wiring Diagrams - Digital Outputs
1771-OND to 1756-ON8
Conversion Module1492-CM1771-LD006
Cable1492-CONCAB005S2�
There are several key application considerations and system specifications (bottom of drawing) when using these components (conversion module, cable and input module). Read and understand these considerations before installation.
Conversion Module Installation and Application Considerations
� This Bul. 1492 cable consists of a cable wired to two 1756-ON8 RTB. Recommended cable lengths of0.5M or 1.0M (005=0.5M, 010=1.0M). See table 2 for other lengths.
� The 1771-OND module output current limits versus (2)1756-ON8 limits are as follows: 1771-OND 1756-ON8 w/ 1492-CONCAB005S2a) Current/Point 2A 2Ab) Current/Module 8A 5Ac) Surge Current/Point 25A for 100ms 20A for 43ms
� The L2 terminal (Terminal E) on the 1771-ON8 module was an optional connection, but it is required for the 1756-OA16. This connection must be added if it was not connected.
� The 1771-OND is rated 24V AC. The 1756-ON8 is rated 10V to 30V AC.
� Refer to your 1771-OND and 1756-ON8 Installation Manual wiring schematics and diagrams for more details. Ensure1756 output module ratings are not exceeded. [Reference Doc: 41171-008 (Version 00)]
1756-ON8
1756-ON8
10L1-0
OUT-01
OUT-13
OUT-25
OUT-37
OUT-4OUT-5
11
OUT-6
13
OUT-7
1517
Black
WhiteRed
Green
Orange
Blue
White/Black
Red/BlackGreen/Black
Orange/BlackBlue/Black
Black/White
Red/White
Green/White
Blue/White
Black/Red
White/Red
Orange/Red
Blue/Red
Red/Green
L1-114
L1-1
A
1
00
19
013
024
035
046
057
068
079
E
10111012111312
13151416151716
17 18
20
14
2
Output 00
L1
L2
1771-WH, WHF Swing ArmFrom 1771-OND
B
CD
L1
L1L1
L1
L2
OutputDevice
Output 01Output 02Output 03Output 04Output 05Output 06Output 07Output 10
Output 11Output 12Output 13Output 14Output 15Output 16Output 17
24
212223
25
L1-0L1-0L1-0L1-0
L1-11618
L1-1L1-1
2468
20
10L1-0
OUT-81
OUT-93
OUT-105
OUT-117
OUT-12OUT-13
11
OUT-14
13
OUT-15
1517
L1-114
L1-1
L1-0L1-0L1-0L1-0
L1-11618
L1-1L1-1
2468
20
NOT USED
NOT USED
NOT USED
19
9
9
NOT USED19
IMPORTANT
Rockwell Automation Publication 1492-SG121E-EN-P - July 2016 65
Wiring Diagrams - Digital Outputs
1771-OQ to 1756-OB16I
There are several key application considerations and system specifications (bottom of drawing) when using these components (conversion module, cable and input module). Read and understand these considerations before installation.
Conversion Module1492-CM1771-LA004
Conversion Module1492-CM1771-LA004
1771-WF Swing ArmFrom 1771-OQ
1771-WF Swing ArmFrom 1771-OQ
Cable1492-C005005XT� 1756-OB16I
181716151413121110
987
432
6
1
5
Orange/Red
White/Red
Green/White
Blue/White
Orange/Black
Red/White
Black/Red
Blue/Black
Black/White
Green/Black
Blue
Orange
Red/Black
White/Black
18
14131211
8
65
171615
4321
109
7
Black
White
RedGreen
214
3
10
14
13
DC-1OUTPUT-0
OUTPUT 1
DC-2
OUTPUT 2
DC-2
6
8
12
5
9
7
11
15
OUTPUT 3
DC-3
DC-3
DC-4
16DC-4
DC-1
OUTPUT-4
OUTPUT 5OUTPUT 6
OUTPUT 7
LOAD
+
-
LOAD
181716151413121110
987
432
6
1
5
Orange/Red
White/Red
Green/White
Blue/White
Orange/Black
Red/White
Black/Red
Blue/Black
Black/White
Green/Black
Blue
Orange
Red/Black
White/Black
18
14131211
8
65
171615
4321
109
7
Black
White
RedGreen
181720
19
26
30
29
DC-1OUTPUT-8
OUTPUT 9
DC-2
OUTPUT 10
DC-2
22
24
28
21
25
23
27
31
OUTPUT 11
DC-3
DC-3
DC-4
32DC-4
DC-1
OUTPUT-12
OUTPUT 13OUTPUT 14
OUTPUT 15
LOAD
+
-
LOAD
NOT USED33343536
NOT USEDNOT USEDNOT USED
Cable “B”
Cable “A”DC-1
OUTPUT-0
OUTPUT 1
DC-2OUTPUT 2
DC-2OUTPUT 3
DC-3
DC-3
DC-4
DC-4
DC-1
OUTPUT-4
OUTPUT 5
OUTPUT 6
OUTPUT 7
Not Used
Not Used
DC-1OUTPUT-8
OUTPUT 9
DC-2OUTPUT 10
DC-2OUTPUT 11
DC-3
DC-3
DC-4
DC-4
DC-1
OUTPUT-12
OUTPUT 13
OUTPUT 14
OUTPUT 15
Not Used
Not Used
Conversion Module Installation and Application Considerations� This Bul. 1492 cable consists of 2 separate cables (cable “A” and cable “B”) wired to one 1756-OB16I RTB. Each cable can be either0.5M or 1.0M (005=0.5M, 010=1.0M). Ensure that cable A and cable B are connected to the correct module in the conversion
� The 1771-OQ module output resistive current limits versus 1756-OB16I limits are as follows: 1771-OQ 1756-OB16I w/ 1492-C005005XT a) Current/Point 2.25A 2A b) Current/Module 9A 8A c) Surge Current/Point 4A for 10ms 4A for 10ms
� The 1771-OQ is rated 10V to 32V DC. The 1756-OB16I is rated 10V to 30V DC.
� Refer to your 1771-OQ and 1756-OB16I Installation Manual wiring schematics and diagrams for more details. Ensure 1756 output module ratings are not exceeded. [Reference Doc: 41171-033 (Version 00)]
IMPORTANT
66 Rockwell Automation Publication 1492-SG121E-EN-P - July 2016
Wiring Diagrams - Digital Outputs
1771-OQ16 to 1756-OB16I
There are several key application considerations and system specifications (bottom of drawing) when using these components (conversion module, cable and input module). Read and understand these considerations before installation.
WARNING
� This Bul. 1492 cable consists of a cable wired to one 1756-OB16I RTB. Recommended cable lengths of 0.5M or 1.0M (005=0.5M, 010=1.0M). See table 2 for other lengths.
� The 1771-OQ16 module output current limits versus 1756-OB16I limits are as follows: 1771-OQ16 1756-OB16I w/ 1492-CONCAB005Ya) Current/Point 2A 2Ab) Current/Module 32A 8Ac) Surge Current/Point 4A for 10ms 4A for 10ms
� The 1771-OQ16 has sixteen (16) 3A, 250V rectifier fuses. The 1756-OB16I is NOT fused, as such sixteen(16) 2AG fuses and clips are provided on the 1492-CM1771-LD010F conversion module. Max fuse rating is 1.5A based on 1756-OA16I.
� The 1771-OQ16 is rated 10V to 32V DC. The 1756-OB16I is rated 10V to 30V DC.
� Refer to your 1771-OQ16 and 1756-OB16I Installation Manual wiring schematics and diagrams for more details. Ensure1756 output module ratings are not exceeded. [Reference Doc: 41171-010 (Version 00)]
Conversion Module Installation and Application Considerations
1771-WN Swing ArmFrom 1771-OQ16
12345678910111213
151617181920
14
21222324252627282930313233
353637
34
OUT-0
21
OUT-1
43
OUT-2
65
OUT-3
87
OUT-4
109
OUT-5
1211
OUT-6
1413
Orange
Blue
White/Black
Red/BlackGreen/Black
Orange/BlackBlue/Black
Black/White
Red/White
Green/White
Blue/White
Black/Red
White/Red
Orange/Red
Blue/Red
Red/GreenOUT-7
1615
OUT-8
1817
OUT-9
2019
OUT-10
2221
OUT-11
2423
OUT-12
2625
OUT-13
2827
OUT-14
3029
Orange/Green
Black/White/Red
White/Black/Red
Red/Black/WhiteGreen/Black/White
Orange/Black/WhiteBlue/Black/White
Black/Red/Green
White/Red/Green
Red/Black/Green
Green/Black/Orange
Orange/Black/Green
Blue/White/Orange
Black/White/Orange
White/Red/Orange
Orange/White/BlueOUT-15
3231
DC-0
DC-1
DC-2
DC-3
DC-4
DC-5
DC-6
DC-7
DC-8
DC-9
DC-10
DC-11
DC-12
DC-13
DC-14
DC-15
+
-
40
21Ouput 0
3Ouput 1
5Ouput 2
7Ouput 3
11Ouput 4
13Ouput 5
15Ouput 6
17Ouput 7
21Ouput 8
23Ouput 9
25Ouput 10
27Ouput 11
31Ouput 12
33Ouput 13
35Ouput 14
37Ouput 15
DC-0
DC-1
DC-2
DC-3
DC-4
DC-5
DC-6
DC-7
DC-8
DC-9
DC-10
DC-11
DC-12
DC-13
DC-14
DC-15
4
6
8
29
12
14
16
18
30
22
24
26
28
39
32
34
36
38
910
20
19
Not Used
Not UsedNot UsedNot Used
Not Used
Not UsedNot UsedNot Used
LOAD
Conversion Module1492-CM1771-LD010F
1756-OB16I Cable
1492-CONCAB005Y�
IMPORTANT
Rockwell Automation Publication 1492-SG121E-EN-P - July 2016 67
Wiring Diagrams - Digital Outputs
1771-OR to 1756-OB16I
Conversion Module1492-CM1771-LD012
Conversion Module1492-CM1771-LD012
1771-WD Swing ArmFrom 1771-OR
1771-WD Swing ArmFrom 1771-OR
Cable1492-C005005XR� 1756-OA16I
There are several key application considerations and system specifications (bottom of drawing) when using these components (conversion module, cable and input module). Read and understand these considerations before installation.
WARNING
Conversion Module Installation and Application Considerations� This Bul. 1492 cable consists of 2 separate cables (cable “A” and cable “B”) wired to one 1756-OA16I RTB. Each cable can be either0.5M or 1.0M (005=0.5M, 010=1.0M). Ensure that cable A and cable B are connected to the correct module in the conversion
� The 1771-OR module output resistive current limits versus 1756-OA16I limits are as follows: 1771-OR 1756-OA16I w/ 1492-C005005XR a) Current/Point 2A 2A b) Current/Module 6A 5A @ 60°C c) Surge Current/Point 15A for 100ms 20A for 43ms
� The 1771-OR module had a jumper selection of N.O. and N.C. outputs. The 1756-OA16I has both N.O. and N.C. outputs, but selection is by wiring termination on the 1756 swing arm. The 1492-CM1771-LD012 conversion module replaces the functionalityof the 1771-OR jumpers with eight jumpers (JMP0 through JMP7). In the default position, the output will be N.O. If a N.C. output isrequired, change the jumper from pins 1-2 to pins 3-4.
� Refer to your 1771-OR and 1756-OA16I Installation Manual wiring schematics and diagrams for more details. Ensure 1756 output module ratings are not exceeded. [Reference Doc: 41171-017 (Version 00)]
2
1
5
468
9
11
293031
NOT USEDNOT USED
L2-0
L1-0L1-1L1-2
L2-2L2-1
L1-3
L2-3
L1-4
CABLE ”A”
NOT USED
12345
678910111213
151617181920
14
21222324252627282930313233
353637
34
1492-CONCAB005Y
Orange
Blue
White/Black
Red/BlackGreen/Black
Orange/BlackBlue/Black
Black/White
Red/White
Green/White
Blue/White
Black/Red
White/Red
Orange/Red
Blue/Red
Red/Green
Orange/Green
Black/White/Red
White/Black/Red
Red/Black/WhiteGreen/Black/White
Orange/Black/WhiteBlue/Black/White
Black/Red/Green
White/Red/Green
Red/Black/Green
Green/Black/Orange
Orange/Black/Green
Blue/White/Orange
Black/White/Orange
White/Red/Orange
Orange/White/Blue
1
56789101112
0-OUT
0-IN234
1-IN
2-IN
1-OUT
2-OUT
3-OUT
3-IN
4-IN
5-IN4-OUT
5-OUT
1
3
2
4
N.O.
N.C.
1
3
2
4
N.O.
N.C.
JMP0
JMP1
1
3
2
4
N.O.
N.C.
JMP2
1
3
2
4
N.O.
N.C.
1
3
2
4
N.O.
N.C.
JMP3
JMP4
1
3
2
4
N.O.
N.C.
JMP5
1
3
2
4
N.O.
N.C.
JMP6
1
3
2
4
N.O.
N.C.
JMP7
L1-5
L2-4L2-5
12345
678910111213
151617181920
14
21222324252627282930313233
353637
34
LOAD
Orange
Blue
White/Black
Red/BlackGreen/Black
Orange/BlackBlue/Black
Black/White
Red/White
Green/White
Blue/White
Black/Red
White/Red
Orange/Red
Blue/Red
Red/Green
Orange/Green
Black/White/Red
White/Black/Red
Red/Black/WhiteGreen/Black/White
Orange/Black/WhiteBlue/Black/White
Black/Red/Green
White/Red/Green
Red/Black/Green
Green/Black/Orange
Orange/Black/Green
Blue/White/Orange
Black/White/Orange
White/Red/Orange
Orange/White/Blue
1
56789101112
234
1
3
2
4
N.O.
N.C.
1
3
2
4
N.O.
N.C.
JMP0
JMP1
1
3
2
4
N.O.
N.C.
JMP2
1
3
2
4
N.O.
N.C.
1
3
2
4
N.O.
N.C.
JMP3
JMP4
1
3
2
4
N.O.
N.C.
JMP5
1
3
2
4
N.O.
N.C.
JMP6
1
3
2
4
N.O.
N.C.
JMP7
3
13
CABLE ”B”
L1L2
LOAD
L1L2
10
12
6-OUT
6-IN
7-IN
8-IN
7-OUT
8-OUT
9-OUT
9-IN
10-IN
11-IN10-OUT
11-OUT
14
15
19
161820
21
23
L2-6
L1-6L1-7L1-8
L2-8L2-7
L1-9
L2-9
L1-10
L1-11
L2-10L2-11
17
25
22
24
262728
NOT USEDNOT USED
NOT USED
343536
NOT USEDNOT USED
NOT USED
3233
NOT USEDNOT USED
IMPORTANT
68 Rockwell Automation Publication 1492-SG121E-EN-P - July 2016
Wiring Diagrams - Digital Outputs
1771-OVN to 1756-OV16E
There are several key application considerations and system specifications (bottom of drawing) when using these components (conversion module, cable and input module). Read and understand these considerations before installation.
WARNING
10L1-0L2-0
1OUT-0
2OUT-1
3OUT-2
4
OUT-12
5
OUT-13
6
OUT-14
7
OUT-15
81112131415161718
Black
WhiteRed
Green
Orange
Blue
White/Black
Red/BlackGreen/Black
Orange/BlackBlue/Black
Black/White
Red/White
Green/White
Blue/White
Black/Red
White/Red
12345
78910
18
111213
151617
14
L1-119
9
OUT-3
20
L2-1
OUT-4OUT-5OUT-6OUT-7OUT-8OUT-9OUT-10OUT-11
1771-WN Swing ArmFrom 1771-OVN
10
123456781112131415161718
19
9
20
20 Red/Green
21 Orange/Green
22 Black/White/Red
24 Red/Black/White
25 Green/Black/White
26 Orange/Black/White27 Blue/Black/White28 Black/Red/Green29 White/Red/Green
30 Red/Black/Green
31 Green/Black/Orange
32 Orange/Black/Green33 Blue/White/Orange
34 Black/White/Orange
35 White/Red/Orange
36White/Red/Blue37
A EL
UD
OM
B EL
UD
OM
30
202
40
43
65
87
129
34
13
1
1615
1817
22
19
2423
2625
2827
3229
11
33
10L2L2
L2L2
Output 00Output 01Output 02Output 03Output 04Output 05Output 06Output 07Output 10Output 11
Output 13
Output 15
Output 12
Output 17
L1
35
31
14
L1
21L1
Output 14
Output 16
38
3637
39
L1
Output 00Output 01Output 02Output 03
Output 04Output 05Output 06Output 07Output 10Output 11
Output 13
Output 15
Output 12
Output 17
Output 14
Output 16
Orange/Red
6
L1-0L2-0OUT-0OUT-1OUT-2
OUT-12OUT-13OUT-14OUT-15L1-1
OUT-3
L2-1
OUT-4OUT-5OUT-6OUT-7OUT-8OUT-9OUT-10OUT-11
23 White/Black/Red
Orange/White/Blue
L1
L2
OutputDevice
19 Blue/Red
1756-OV16E
1756-OV16E
Conversion Module1492-CM1771-LD013
Cable1492-CONCAB005S3�
�
�
�
�
Conversion Module Installation and Application Considerations� This Bul. 1492 cable consists of a cable wired to two 1756-OV16E RTB. Recommended cable lengths of 0.5M or 1.0M (005=0.5M, 010=1.0M). See table 2 for other lengths.
� The 1771-OVN module output current limits versus 1756-OV16E limits are as follows: 1771-OVN 1756-OV16E w/ 1492-CONCAB005S3a) Current/Point 0.5A 1Ab) Current/Module 8A (32 pts) 8A (16 pts)c) Surge Current/Point 2A for 10ms 2A for 10ms
� The 1771-OVN has 4 groups (allowing 4 separate power supplies). This module/cable combination ties all 4 groups from the 1771-OVN together. Field wiring modification must be made to accommodate this if mulitple supplies were used. If more than 1 supply was used, all but 1 of the power supplies must be removed.
� The 1771-OVN did not allow connections for L2, however the 1756-OV16E requires an L2 connection for proper operation. The 1771-OVN did not use terminals 10, 20, 30, 40. These terminals have been reassigned for an L2 connection in this application. The installer must rewire L2 to one of these terminals.
� Refer to your 1771-OVN and 1756-OV16E Installation Manual wiring schematics and diagrams for more details. Ensure 1756 output module ratings are not exceeded.
� This configuration uses two (2) 1756-OV16E output modules to replace a single 1771-OVN output module. This may require the use of a larger 1756 I/O chassis and conversion mounting assembly. Ensure there is sufficient panel space to allow for this possibility.
[Reference Doc: 41171-018 (Version 00)]
IMPORTANT
Rockwell Automation Publication 1492-SG121E-EN-P - July 2016 69
Wiring Diagrams - Digital Outputs
1771-OW to 1756-OX8I
There are several key application considerations and system specifications (bottom of drawing) when using these components (conversion module, cable and input module). Read and understand these considerations before installation.
Conversion Module1492-CM1771-LD012
1771-WD Swing ArmFrom 1771-OW
Cable1492-CONCAB005Y�
Conversion Module Installation and Application Considerations� This Bul. 1492 cable consists of a cable wired to one 1756-OX8I RTB. Recommended cable lengths of 0.5M or 1.0M (005=0.5M), 010=1.0M). See table 2 for other lengths.
� The 1771-OW module output resistive current limits versus 1756-OX8I limits are as follows:(NOTE: For switching and inductive current ratings, refer to the modules Installation Instructions) 1771-OW 1756-OX8I w/ 1492-CONCAB005Y a) Current/Point 0.2A @ 138V AC 2A @ 240V AC 1A @ 30V DC 2A @ 30V DC 0.25A @ 125V DC 0.25A @ 125V DC
� The 1771-OW module had a jumper selection of N.O. and N.C. outputs. The 1756-OX8I has both N.O. and N.C. outputs, but selection is by wiring termination on the 1756 swing arm. The 1492-CM1771-LD012 conversion module replaces the functionalityof the 1771-OW jumpers with eight jumpers (JMP0 through JMP7). In the default position, the output will be N.O. If a N.C. output isrequired, change the jumper from pins 1-2 to pins 3-4.
� Refer to your 1771-OW and 1756-OX8I Installation Manual wiring schematics and diagrams for more details. Ensure 1756 output module ratings are not exceeded. [Reference Doc: 41170-941 (Version 01)]
4 3
2 1
N.C.
N.O.
4 3
2 1
N.C.
N.O.
4 3
2 1
N.C.
N.O.
4 3
2 1
N.C.
N.O.
4 3
2 1
N.C.
N.O.
4 3
2 1
N.C.
N.O.
L1-0OUT-0 N.C.L1-0
OUT-0 N.O.L1-1OUT-1 N.C.L1-1OUT-1 N.O.L1-2OUT-2 N.C.L1-2OUT-2 N.O.L1-3OUT-3 N.C.L1-3OUT-3 N.O.L1-4OUT-4 N.C.
L1-4OUT-4 N.O.L1-5OUT-5 N.C.L1-5OUT-5 N.O.L1-6OUT-6 N.C.
L1-6OUT-6 N.O.L1-7OUT-7 N.C.L1-7
OUT-7 N.O.
12
345678910
1112131415161718
192021222324
25262728293031323334353637
Orange
Blue
White/Black
Red/Black
Green/Black
Orange/Black
Blue/Black
Black/White
Red/White
Green/White
Blue/White
Black/Red
White/Red
Orange/Red
Blue/Red
Red/Green
Orange/Green
Black/White/Red
White/Black/Red
Red/Black/White
Green/Black/White
Orange/Black/White
Blue/Black/White
Black/Red/Green
White/Red/Green
Red/Black/Green
Green/Black/Orange
Orange/Black/Green
Blue/White/Orange
Black/White/Orange
White/Red/Orange
Orange/White/Blue
4 3
2 1
N.C.
N.O.
JMP74 3
2 1
N.C.
N.O.
JMP6
JMP5
JMP4
JMP3
JMP2
JMP1
JMP0
1234
56
789
101112
LOAD
L1
L2
LOAD
+
-
Out-0 N.O./N.C.+V0/1
Out-1 N.O./N.C.Out-2 N.O./N.C.
+V2/3Out-3 N.O./N.C.Out-4 N.O./N.C.
+V4/5Out-5 N.O./N.C.
Out-6 N.O./N.C.+V6/7
Out-7 N.O./N.C.
2143658710912111413161518172019222124232625282730293231
1756-OX8I
IMPORTANT
70 Rockwell Automation Publication 1492-SG121E-EN-P - July 2016
Wiring Diagrams - Digital Outputs
1771-OW16 to 1756-OW16I
Conversion Module Installation and Application Considerations� The 1771-OW16 module output resistive current limits versus 1756-OW16I limits are as follows: 1771-OW16 1756-OW16I w/ 1492-CONCAB005Ya) Current/Point 2A @ 250V AC 2A @ 240V AC 2A @ 30V DC 2A @ 30V DC 0.3A @ 150V DC 0.25A @ 125V AC� The 1492-CONCAB005Y is limited to 3A per pin.� The 1771-OW16 has N.O. and N.C. relay contact outputs. The 1756-OW16I has N.O. relay contact outputs only. The conver-sion module does not convert the N.C. to N.O. contacts. If the 1771-OW16 N.C. outputs were being used, the installer must rewire the 1771-WN swing arm and move the N.C. wires to the N.O. output terminals. In addition, the control Logix programming will need to be changed to simulate a N.C. relay with this output.� Refer to your 1771-OW16 and 1756-OW16I Installation Manual wiring schematics and diagrams for more details. Ensure 1756 output module ratings are not exceeded. Reference Doc: 41170-940 (Version 01)]
There are several key application considerations and system specifications (bottom of drawing) when using these components (conversion module, cable and input module). Read and understand these considerations before installation.
1 2
17202326
4
365
8
71091211141316151918
2221252428
273130
3433
37364039
29323538
Output 14 (NO)
Output 16 (NO)
Output 15 (NO)
Output 04
Output 06
Output 05
Output 07
Output 00
Output 02
Output 01
Output 03
Output 10 (NO)
Output 12 (NO)
Output 11(NO)
Output 13 (NO)
Output 17 (NO)Output 14 (NC)Output 15 (NC)Output 16 (NC)Output 17 (NC)
12345678910111213
151617181920
14
21222324252627282930313233
353637
34
OUT-0 N.O.
21
OUT-1 N.O.
43
OUT-2 N.O.
65
OUT-3 N.O.
87
OUT-4 N.O.
109
OUT-5 N.O.
1211
OUT-6 N.O.
1413
Orange
Blue
White/Black
Red/BlackGreen/Black
Orange/BlackBlue/Black
Black/White
Red/White
Green/White
Blue/White
Black/Red
White/Red
Orange/Red
Blue/Red
Red/GreenOUT-7 N.O.
1615
OUT-8 N.O.
1817
OUT-9 N.O.
2019
OUT-10 N.O.
2221
OUT-11 N.O.
2423
OUT-12 N.O.
2625
OUT-13 N.O.
2827
OUT-14 N.O.
3029
Orange/Green
Black/White/Red
White/Black/Red
Red/Black/WhiteGreen/Black/White
Orange/Black/WhiteBlue/Black/White
Black/Red/Green
White/Red/Green
Red/Black/Green
Green/Black/Orange
Orange/Black/Green
Blue/White/Orange
Black/White/Orange
White/Red/Orange
Orange/White/BlueOUT-15 N.O.
3231
L1-0
L1-1
L1-2
L1-3
L1-4
L1-5
L1-6
L1-7
L1-8
L1-9
L1-10
L1-11
L1-12
L1-13
L1-14
L1-15
L1
L2
Common 00
Common 01
Common 02
Common 03
Common 04
Common 05
Common 06
Common 07
Common 10
Common 11
Common 12
Common 13
Common 14
Common 15
Common 16
Common 17
Output 10 (NC)Output 11 (NC)Output 12 (NC)Output 13 (NC)
+
- LOAD
LOAD
Conversion Module1492-CM1771-LD011
Cable1492-CONCAB005Y� 1756-OW16I
1771-WN Swing ArmFrom 1771-OW16
IMPORTANT
Rockwell Automation Publication 1492-SG121E-EN-P - July 2016 71
Wiring Diagrams - Digital Outputs
1771-OWNA to 1756-OW16I
There are several key application considerations and system specifications (bottom of drawing) when using these components (conversion module, cable and input module). Read and understand these considerations before installation.
1771-WN Swing ArmFrom 1771-OWNA
2L1-0L2-0
1OUT-0
3OUT-1
5OUT-2
7
OUT-12
9
OUT-13
11
OUT-14
13
OUT-15
151719212325272931
Black
WhiteRed
Green
Orange
Blue
White/Black
Red/BlackGreen/Black
Orange/BlackBlue/Black
Black/White
Red/White
Green/White
Blue/White
Black/Red
White/Red
12345
78910
18
111213
151617
14
L1-1
OUT-3
4
L1-1
OUT-4OUT-5OUT-6OUT-7OUT-8OUT-9OUT-10OUT-11
20 Red/Green
21 Orange/Green
22 Black/White/Red
24 Red/Black/White
25 Green/Black/White
26 Orange/Black/White27 Blue/Black/White28 Black/Red/Green29 White/Red/Green
30 Red/Black/Green
31 Green/Black/Orange
32 Orange/Black/Green33 Blue/White/Orange
34 Black/White/Orange
35 White/Red/Orange
36White/Red/Blue37
AB
ELU
DO
MEL
UD
OM
30
202
40
43
65
87
129
34
13
1
1615
1817
22
19
2423
2625
2827
3229
11
33
10L2L2
L2L2
Output 00Output 01Output 02Output 03Output 04Output 05Output 06Output 07Output 10Output 11
Output 13
Output 15
Output 12
Output 17
L1
35
31
14
L1
21L1
Output 14
Output 16
38
3637
39
L1
Output 00Output 01Output 02Output 03
Output 04Output 05Output 06Output 07Output 10Output 11
Output 13
Output 15
Output 12
Output 17
Output 14
Output 16
Orange/Red
6
23 White/Black/Red
Orange/White/Blue
L1
L2
OutputDevice
19 Blue/Red
L1-1
L1-1
6
3234
2L1-0L2-0
1OUT-0
3OUT-1
5OUT-2
7
OUT-12
9
OUT-13
11
OUT-14
13
OUT-15
151719212325272931
L1-1
OUT-3
4
L1-1
OUT-4OUT-5OUT-6OUT-7OUT-8OUT-9OUT-10OUT-11
L1-1
L1-1
6
3234
1756-OW16I
1756-OW16I
Conversion Module1492-CM1771-LD013
Cable1492-CONCAB005S4�
�
��
�
�
Conversion Module Installation and Application Considerations� This Bul. 1492 cable consists of a cable wired to two 1756-OW16I RTB. Recommended cable lengths of 0.5M or 1.0M (005=0.5M, 010=1.0M). See table 2 for other lengths.
� The 1771-OWNA module output current limits versus 1756-OW16I limits are as follows: 1771-OWNA 1756-OW16I w/ 1492-CONCAB005S4a) Current/Point 1A 0.5Ab) Current/Module 12A (32 pts) 2A (16 pts)
� The 1771-OWNA has 4 groups (allowing 4 separate power supplies). This module/cable combination ties all 4 groups from the 1771-OWNA together. Field wiring modification must be made to accommodate this if mulitple supplies were used. If more than 1 supply was used, all but 1 of the power supplies must be removed.
� The 1771-OWNA did not allow connections for L2, however the 1756-OW16I requires an L2 connection for proper operation. The 1771-OWNA did not use terminals 10, 20, 30, 40. These terminals have been reassigned for an L2 connection in this application. The installer must rewire L2 to one of these terminals.
� Refer to your 1771-OWNA and 1756-OW16I Installation Manual wiring schematics and diagrams for more details. Ensure 1756 output module ratings are not exceeded.
� This configuration uses two (2) 1756-OW16I output modules to replace a single 1771-OWNA output module. This may require the use of a larger 1756 I/O chassis and conversion mounting assembly. Ensure there is sufficient panel space to allow for this possibility.
� 1756-OW16I output modules has all inputs jumpered together pins 2 through 34 even. [Reference Doc: 41171-019 (Version 00)]
IMPORTANT
72 Rockwell Automation Publication 1492-SG121E-EN-P - July 2016
Wiring Diagrams - Digital Outputs
1771-OY to 1756-OX8I
41171-011 (00)
12345
678910111213
151617181920
14
21222324252627282930313233
353637
34
LOAD
1756-OX8I
OUT-0 N.C.
21
OUT-0 N.O.
43
OUT-1 N.C.
65
OUT-1 N.O.
87
OUT-2 N.C.
109
OUT-2 N.O.
1211
OUT-3 N.C.
1413
1492-CONCAB005YOrange
Blue
White/Black
Red/BlackGreen/Black
Orange/BlackBlue/Black
Black/White
Red/White
Green/White
Blue/White
Black/Red
White/Red
Orange/Red
Blue/Red
Red/GreenOUT-3 N.O.
1615
OUT-4 N.C.
1817
OUT-4 N.O.
2019
OUT-5 N.C.
2221
OUT-5 N.O.
2423
OUT-6 N.C.
2625
OUT-6 N.O.
2827
OUT-7 N.C.
3029
Orange/Green
Black/White/Red
White/Black/Red
Red/Black/WhiteGreen/Black/White
Orange/Black/WhiteBlue/Black/White
Black/Red/Green
White/Red/Green
Red/Black/Green
Green/Black/Orange
Orange/Black/Green
Blue/White/Orange
Black/White/Orange
White/Red/Orange
Orange/White/BlueOUT-7 N.O.
3231
L1-0
L1-0
L1-1
L1-1
L1-2
L1-2
L1-3
L1-3
L1-4
L1-4
L1-5
L1-5
L1-6
L1-6
L1-7
L1-7
L1
L2
+
- LOAD
1
56789101112
1492-CM1771-LD012
+V0/1
Out-0 N.O./N.C.
1771-WD Swing ArmFrom 1771-OY
234
Out-1 N.O./N.C.
+V2/3
Out-2 N.O./N.C.
Out-3 N.O./N.C.
+V4/5
Out-4 N.O./N.C.
Out-5 N.O./N.C.
+V6/7
Out-6 N.O./N.C.
Out-7 N.O./N.C.
1
3
2
4
N.O.
N.C.
1
3
2
4
N.O.
N.C.
JMP0
JMP1
1
3
2
4
N.O.
N.C.
JMP2
1
3
2
4
N.O.
N.C.
1
3
2
4
N.O.
N.C.
JMP3
JMP4
1
3
2
4
N.O.
N.C.
JMP5
1
3
2
4
N.O.
N.C.
JMP6
1
3
2
4
N.O.
N.C.
JMP7
The 1771-OY module output resistive current limits versus 1756-OX8I limits are as follows: (NOTE: for switching and inductive current ratings, refer to the modules Installation Instructions) 1771-OY 1756-OX8I w/ 1492-CONCAB005Y a) Current/Point 100mA @ 138V AC 2A @ 240V AC 100mA @ 125V DC 2A @ 30V DC 0.25A @ 125V DC
CONVERSION MODULE INSTALLATION AND APPLICATION CONSIDERATIONS
The 1771-OY module had a jumper selection of N.O. and N.C. outputs. The 1756-OX8I has both N.O. and N.C. relay outputs, but selection is by wiring termination on the 1756 swing arm. The 1492-CM1771-LD012 conversion module replaces the functionality of the 1771-OY jumpers with eight jumpers (JMP0 through JMP7). In the default position, the output will be N.O.. If a N.C. output is required, change the jumper from pins 1-2 to pins 3-4.
Refer to your 1771-OY and 1756-OX8I Installation Manual wiring schematics and diagrams for more details. Ensure 1756 output module ratings are not exceeded.
There are several key application considerations and system specifications (bottom of drawing) when usingthese components (conversion module, cable and output module). Read and understand these considerationsbefore installation. In addition, refer to the current draw requirements of the existing loads for this configurationto ensure they are within the current ratings of the 1756 output module.
Conversion Module
Cable
This Bul. 1492 cable consists of a cable wired to one 1756-OX8I RTB. Recommended cable lengths of 0.5M or 1.0M (005=0.5M, 010=1.0M). See table 2 for other lengths.
IMPORTANT
Rockwell Automation Publication 1492-SG121E-EN-P - July 2016 73
Wiring Diagrams - Digital Outputs
1771-OYL to 1756-OX8I
41171-012 (00)
12345
678910111213
151617181920
14
21222324252627282930313233
353637
34
LOAD
1756-OX8I
OUT-0 N.C.
21
OUT-0 N.O.
43
OUT-1 N.C.
65
OUT-1 N.O.
87
OUT-2 N.C.
109
OUT-2 N.O.
1211
OUT-3 N.C.
1413
1492-CONCAB005Y
Orange
Blue
White/Black
Red/BlackGreen/Black
Orange/BlackBlue/Black
Black/White
Red/White
Green/White
Blue/White
Black/Red
White/Red
Orange/Red
Blue/Red
Red/GreenOUT-3 N.O.
1615
OUT-4 N.C.
1817
OUT-4 N.O.
2019
OUT-5 N.C.
2221
OUT-5 N.O.
2423
OUT-6 N.C.
2625
OUT-6 N.O.
2827
OUT-7 N.C.
3029
Orange/Green
Black/White/Red
White/Black/Red
Red/Black/WhiteGreen/Black/White
Orange/Black/WhiteBlue/Black/White
Black/Red/Green
White/Red/Green
Red/Black/Green
Green/Black/Orange
Orange/Black/Green
Blue/White/Orange
Black/White/Orange
White/Red/Orange
Orange/White/BlueOUT-7 N.O.
3231
L1-0
L1-0
L1-1
L1-1
L1-2
L1-2
L1-3
L1-3
L1-4
L1-4
L1-5
L1-5
L1-6
L1-6
L1-7
L1-7
L1
L2
+
- LOAD
1
56789101112
1492-CM1771-LD012
+V0/1
Out-0 N.O./N.C.
1771-WD Swing ArmFrom 1771-OYL
234
Out-1 N.O./N.C.
+V2/3
Out-2 N.O./N.C.
Out-3 N.O./N.C.
+V4/5
Out-4 N.O./N.C.
Out-5 N.O./N.C.
+V6/7
Out-6 N.O./N.C.
Out-7 N.O./N.C.
1
3
2
4
N.O.
N.C.
1
3
2
4
N.O.
N.C.
JMP0
JMP1
1
3
2
4
N.O.
N.C.
JMP2
1
3
2
4
N.O.
N.C.
1
3
2
4
N.O.
N.C.
JMP3
JMP4
1
3
2
4
N.O.
N.C.
JMP5
1
3
2
4
N.O.
N.C.
JMP6
1
3
2
4
N.O.
N.C.
JMP7
The 1771-OYL module output resistive current limits versus 1756-OX8I limits are as follows: (NOTE: for switching and inductive current ratings, refer to the modules Installation Instructions) 1771-OYL 1756-OX8I w/ 1492-CONCAB005Y a) Current/Point 100mA @ 24V AC 2A @ 240V AC 100mA @ 24V DC 2A @ 30V DC 0.25A @ 125V DC
CONVERSION MODULE INSTALLATION AND APPLICATION CONSIDERATIONS
The 1771-OYL module had a jumper selection of N.O. and N.C. outputs. The 1756-OX8I has both N.O. and N.C. relay outputs, but selection is by wiring termination on the 1756 swing arm. The 1492-CM1771-LD012 conversion module replaces the functionality of the 1771-OYL jumpers with eight jumpers (JMP0 through JMP7). In the default position, the output will be N.O.. If a N.C. output is required, change the jumper from pins 1-2 to pins 3-4.
Refer to your 1771-OYL and 1756-OX8I Installation Manual wiring schematics and diagrams for more details. Ensure 1756 output module ratings are not exceeded.
There are several key application considerations and system specifications (bottom of drawing) when usingthese components (conversion module, cable and output module). Read and understand these considerationsbefore installation. In addition, refer to the current draw requirements of the existing loads for this configurationto ensure they are within the current ratings of the 1756 output module.
Cable
This Bul. 1492 cable consists of a cable wired to one 1756-OX8I RTB. Recommended cable lengths of 0.5M or 1.0M (005=0.5M, 010=1.0M). See table 2 for other lengths.
Conversion Module
IMPORTANT
74 Rockwell Automation Publication 1492-SG121E-EN-P - July 2016
Wiring Diagrams - Digital Outputs
1771-OZ to 1756-OX8I
There are several key application considerations and system specifications (bottom of drawing) when using these components (conversion module, cable and input module). Read and understand these considerations before installation.
WARNING
1771-WD Swing ArmFrom 1771-OZ
Conversion Module Installation and Application Considerations� This Bul. 1492 cable consists of a cable wired to one 1756-OX8I RTB. Recommended cable lengths of 0.5M or 1.0M (005=0.5M), 010=1.0M). See table 2 for other lengths.
� The 1771-OZ module output resistive current limits versus 1756-OX8I limits are as follows:(NOTE: For switching and inductive current ratings, refer to the modules Installation Instructions) 1771-OZ 1756-OX8I w/ 1492-CONCAB005Y a) Current/Point 100mA @ 138V AC 2A @ 240V AC 100mA @ 138V DC 2A @ 30V DC 0.25A @ 125V DC
� The 1771-OZ module had a jumper selection of N.O. and N.C. outputs. The 1756-OX8I has both N.O. and N.C. outputs, but selection is by wiring termination on the 1756 swing arm. The 1492-CM1771-LD012 conversion module replaces the functionalityof the 1771-OZ jumpers with eight jumpers (JMP0 through JMP7). In the default position, the output will be N.O. If a N.C. output isrequired, change the jumper from pins 1-2 to pins 3-4.
� Refer to your 1771-OZ and 1756-OX8I Installation Manual wiring schematics and diagrams for more details. Ensure 1756 output module ratings are not exceeded. [Reference Doc: 41171-013 (Version 00)]
Cable1492-CONCAB005Y� 1756-OX8I
Conversion Module1492-CM1771-LD012
12345
678910111213
151617181920
14
21222324252627282930313233
353637
34
LOAD
OUT-0 N.C.
21
OUT-0 N.O.
43
OUT-1 N.C.
65
OUT-1 N.O.
87
OUT-2 N.C.
109
OUT-2 N.O.
1211
OUT-3 N.C.
1413
Orange
Blue
White/Black
Red/BlackGreen/Black
Orange/BlackBlue/Black
Black/White
Red/White
Green/White
Blue/White
Black/Red
White/Red
Orange/Red
Blue/Red
Red/GreenOUT-3 N.O.
1615
OUT-4 N.C.
1817
OUT-4 N.O.
2019
OUT-5 N.C.
2221
OUT-5 N.O.
2423
OUT-6 N.C.
2625
OUT-6 N.O.
2827
OUT-7 N.C.
3029
Orange/Green
Black/White/Red
White/Black/Red
Red/Black/WhiteGreen/Black/White
Orange/Black/WhiteBlue/Black/White
Black/Red/Green
White/Red/Green
Red/Black/Green
Green/Black/Orange
Orange/Black/Green
Blue/White/Orange
Black/White/Orange
White/Red/Orange
Orange/White/BlueOUT-7 N.O.
3231
L1-0
L1-0
L1-1
L1-1
L1-2
L1-2
L1-3
L1-3
L1-4
L1-4
L1-5
L1-5
L1-6
L1-6
L1-7
L1-7
L1
L2
+
- LOAD
1
56789101112
+V0/1
Out-0 N.O./N.C.
234
Out-1 N.O./N.C.
+V2/3
Out-2 N.O./N.C.
Out-3 N.O./N.C.
+V4/5
Out-4 N.O./N.C.
Out-5 N.O./N.C.
+V6/7
Out-6 N.O./N.C.
Out-7 N.O./N.C.
1
3
2
4
N.O.
N.C.
1
3
2
4
N.O.
N.C.
JMP0
JMP1
1
3
2
4
N.O.
N.C.
JMP2
1
3
2
4
N.O.
N.C.
1
3
2
4
N.O.
N.C.
JMP3
JMP4
1
3
2
4
N.O.
N.C.
JMP5
1
3
2
4
N.O.
N.C.
JMP6
1
3
2
4
N.O.
N.C.
JMP7
IMPORTANT
Rockwell Automation Publication 1492-SG121E-EN-P - July 2016 75
Wiring Diagrams - Digital Outputs
1771-OZL to 1756-OX8I
There are several key application considerations and system specifications (bottom of drawing) when using these components (conversion module, cable and input module). Read and understand these considerations before installation.
WARNING
1771-WD Swing ArmFrom 1771-OZL
Conversion Module Installation and Application Considerations� This Bul. 1492 cable consists of a cable wired to one 1756-OX8I RTB. Recommended cable lengths of 0.5M or 1.0M (005=0.5M), 010=1.0M). See table 2 for other lengths.
� The 1771-OZL module output resistive current limits versus 1756-OX8I limits are as follows:(NOTE: For switching and inductive current ratings, refer to the modules Installation Instructions) 1771-OZL 1756-OX8I w/ 1492-CONCAB005Y a) Current/Point 100mA @ 138V AC 2A @ 240V AC 100mA @ 138V DC 2A @ 30V DC 0.25A @ 125V DC
� The 1771-OZL module had a jumper selection of N.O. and N.C. outputs. The 1756-OX8I has both N.O. and N.C. outputs, but selection is by wiring termination on the 1756 swing arm. The 1492-CM1771-LD012 conversion module replaces the functionalityof the 1771-OZL jumpers with eight jumpers (JMP0 through JMP7). In the default position, the output will be N.O. If a N.C. output isrequired, change the jumper from pins 1-2 to pins 3-4.
� Refer to your 1771-OZL and 1756-OX8I Installation Manual wiring schematics and diagrams for more details. Ensure 1756 output module ratings are not exceeded. [Reference Doc: 41171-014 (Version 00)]
Cable1492-CONCAB005Y� 1756-OX8I
Conversion Module1492-CM1771-LD012
12345
678910111213
151617181920
14
21222324252627282930313233
353637
34
LOAD
OUT-0 N.C.
21
OUT-0 N.O.
43
OUT-1 N.C.
65
OUT-1 N.O.
87
OUT-2 N.C.
109
OUT-2 N.O.
1211
OUT-3 N.C.
1413
Orange
Blue
White/Black
Red/BlackGreen/Black
Orange/BlackBlue/Black
Black/White
Red/White
Green/White
Blue/White
Black/Red
White/Red
Orange/Red
Blue/Red
Red/GreenOUT-3 N.O.
1615
OUT-4 N.C.
1817
OUT-4 N.O.
2019
OUT-5 N.C.
2221
OUT-5 N.O.
2423
OUT-6 N.C.
2625
OUT-6 N.O.
2827
OUT-7 N.C.
3029
Orange/Green
Black/White/Red
White/Black/Red
Red/Black/WhiteGreen/Black/White
Orange/Black/WhiteBlue/Black/White
Black/Red/Green
White/Red/Green
Red/Black/Green
Green/Black/Orange
Orange/Black/Green
Blue/White/Orange
Black/White/Orange
White/Red/Orange
Orange/White/BlueOUT-7 N.O.
3231
L1-0
L1-0
L1-1
L1-1
L1-2
L1-2
L1-3
L1-3
L1-4
L1-4
L1-5
L1-5
L1-6
L1-6
L1-7
L1-7
L1
L2
+
- LOAD
1
56789101112
+V0/1
Out-0 N.O./N.C.
234
Out-1 N.O./N.C.
+V2/3
Out-2 N.O./N.C.
Out-3 N.O./N.C.
+V4/5
Out-4 N.O./N.C.
Out-5 N.O./N.C.
+V6/7
Out-6 N.O./N.C.
Out-7 N.O./N.C.
1
3
2
4
N.O.
N.C.
1
3
2
4
N.O.
N.C.
JMP0
JMP1
1
3
2
4
N.O.
N.C.
JMP2
1
3
2
4
N.O.
N.C.
1
3
2
4
N.O.
N.C.
JMP3
JMP4
1
3
2
4
N.O.
N.C.
JMP5
1
3
2
4
N.O.
N.C.
JMP6
1
3
2
4
N.O.
N.C.
JMP7
IMPORTANT
76 Rockwell Automation Publication 1492-SG121E-EN-P - July 2016
Wiring Diagrams - Analog Inputs and Outputs
1771-IFE to 1756-IF16 Differential Current
41170-946 (0)
1
6
7 8 9
5 10 15 20
19
21
11 12 13 14 16 17 18
1492-CM1771-LA002
1771-WG Swing Arm
2
3 4
1492-CONACAB005D
Black
White
Red
Green
Orange
Blue
White/Black
Red/Black
Orange/Black
Blue/Black
Green/White
Blue/White
Black/Red
White/Red
Orange/Red
Blue/Red
Red/Green
Orange/Green
1 2 3 4 5 6 7 8 9 10 11 12 13
14 15 16 17 18 19 20 21
SH
Not Used
Channel 1+
Channel 1-
Channel 2+ Channel 2-
Channel 3+ Channel 3- Channel 4+ Channel 4-
Not Used Not Used
Module Common Module Common
Channel 5+
Channel 5- Channel 6+ Channel 6- Channel 7+ Channel 7- Channel 8+ Channel 8-
22 23 24 25
2 4 6 8 12 14 16 18 10
22 20
26 24
36 34 32 30
5 1
15 11
23 19
33
IN-0 IN-1 IN-2 IN-3 IN-4 IN-5 IN-6 IN-7 R TN
IN-9 IN-8
IN-11 IN-10
IN-15 IN-14 IN-13 IN-12
iR TN-2 iR TN-0
iR TN-6 iR TN-4
iR TN-10 iR TN-8
iR TN-14 iR TN-12
29
TransmitterPower Supply +
-
4-Wire Transmitter
+ -
1756-IF16
3 The 1771-IFE analog input ranges were configured via software, as is the input range for the 1756-IF16. Please ensure the correct input range is configured in the 1756-IF16.
1 SHIELD GROUNDING: In some installations, the field wiring shield was grounded on the 1771 chassis. If this was the case, the installer must remove these shield connections from the 1771 chassis and they can be connected to the grounding stud on the 1492-CM1771-LA002 module. The pre-wired cable used between the 1492-CM1771-LA002 module and the 1756-IF16 [1492-CONACAB005D] provides a shield ground lug to ground the shield at the 1756 ControlLogix chassis, this must be connected. Do NOT connect this ground lug to the conversion module grounding stud.
CONVERSION MODULE INSTALLATION AND APPLICATION CONSIDERATIONS
2 This design assumes that all inputs on the1771-IFE were connected to current transmitters. If there was a mix of current and voltage transmitters, then modification of the pre-wired cable [1492-CONACAB005D] will need to occur at the 1756-IF16 terminal block. Refer to the 1756-IF16 Installation Manual for modification details.
4 Refer to your 1771-IFE and 1756-IF16 Installation and User Manuals for additional information concerning comparisons of module wiring, features and configuration details.
WARNING There are several key application considerations and system specifications (bottom of drawing) when using these components (conversion module, cable and output module). Read and understand these considerations before installation.
1
1
IMPORTANT
Rockwell Automation Publication 1492-SG121E-EN-P - July 2016 77
Wiring Diagrams - Analog Inputs and Outputs
1771-IFE to 1756-IF16 Differential Voltage
41170-947 (1)
1
6
7 8 9
5 10 15 20
19
21
11 12 13 14 16 17 18
1492-CM1771-LA002
1771-WG Swing Arm
2
3 4
1492-CONACAB005C
Black
White
Red
Green
Orange
Blue
White/Black
Red/Black
Orange/Black
Blue/Black
Green/White
Blue/White
Black/Red
White/Red
Orange/Red
Blue/Red
Red/Green
Orange/Green
1 2 3 4 5 6 7 8 9 10 11 12 13
14 15 16 17 18 19 20 21
SH
Not Used
Channel 1+
Channel 1-
Channel 2+ Channel 2-
Channel 3+ Channel 3- Channel 4+ Channel 4-
Not Used Not Used
Module Common Module Common
Channel 5+
Channel 5- Channel 6+ Channel 6- Channel 7+ Channel 7- Channel 8+ Channel 8-
22 23 24 25
1756-IF16 2
IN-0 IN-1
4
IN-2 6
IN-3 8
IN-4 12
IN-5 14
IN-6 16
IN-7 18
R TN 10
IN-9 22
IN-8 20
IN-11 26
IN-10 24
IN-15 36
IN-14 34
IN-13 32
IN-12 30
3 The 1771-IFE analog input ranges were configured via software, as is the input range for the 1756-IF16. Please ensure the correct input range is configured in the 1756-IF16.
1 SHIELD GROUNDING: In some installations, the field wiring shield was grounded on the 1771 chassis. If this was the case, the installer must remove these shield connections from the 1771 chassis and they can be connected to the grounding stud on the 1492-CM1771-LA002 module. The pre-wired cable used between the 1492-CM1771-LA002 module and the 1756-IF16 [1492-CONACAB005C] provides a shield ground lug to ground the shield at the 1756 ControlLogix chassis, this must be connected. Do NOT connect this ground lug to the conversion module grounding stud.
CONVERSION MODULE INSTALLATION AND APPLICATION CONSIDERATIONS
2 This design assumes that all inputs on the1771-IFE were connected to voltage transmitters. If there was a mix of current and voltage transmitters, then modification of the pre-wired cable [1492-CONACAB005C] will need to occur at the 1756-IF16 terminal block. Refer to the 1756-IF16 Installation Manual for modification details.
4 Refer to your 1771-IFE and 1756-IF16 Installation and User Manuals for additional information concerning comparisons of module wiring, features and configuration details.
There are several key application considerations and system specifications (bottom of drawing) when using these components (conversion module, cable and input module). Read and understand these considerationsbefore installation.
TransmitterPower Supply+
-
4-Wire Transmitter
+ -
1
1
IMPORTANT
78 Rockwell Automation Publication 1492-SG121E-EN-P - July 2016
Wiring Diagrams - Analog Inputs and Outputs
1771-IFE to 1756-IF16 Single End Current
41170-944 (1)
1
6
7 8 9
5 10 15 20
19
21
11 12 13 14 16 17 18
1492-CM1771-LA001
1771-WG Swing Arm
2
3 4
1756-IF16 2
IN-0 IN-1
4
IN-2 6
IN-3 8
IN-4 12
IN-5 14
IN-6 16
IN-7 18
R TN 10
R TN
27 R TN
28
IN-9 22
IN-8 20
IN-11 26
IN-10 24
IN-15 36
IN-14 34
1492-CONACAB005B
Black
R TN 9
White
Red
Green
Orange
Blue
White/Black
Red/Black
Green/Black
Orange/Black
Blue/Black
Black/White
IN-13 32
IN-12 30
Green/White
Blue/White
Black/Red
White/Red
Orange/Red
Blue/Red
Red/Green
Orange/Green
iR TN-1 3
iR TN-0 1
iR TN-3 7
iR TN-2 5
iR TN-7 17
iR TN-6 15
iR TN-5 13
iR TN-4 11
iR TN-9 21
iR TN-8 19
iR TN-11 25
iR TN-10 23
iR TN-15 35
iR TN-14 33
iR TN-13 31
iR TN-12 29
1 2 3 4 5 6 7 8 9 10 11 12 13
14 15 16 17 18 19 20 21
SH
Module Common T r ansmitt er
P o w er Supply +
2-W ir e T r ansmitt er
-
Channel 1
Channel 2
Channel 3 Channel 4
Channel 5 Channel 6 Channel 7 Channel 8
Module Common Module Common Module Common Module Common
Channel 9
Channel 10 Channel 11 Channel 12 Channel 13 Channel 14 Channel 15 Channel 16
22 23 24 25
3 The 1771-IFE analog input ranges were configured via software, as is the input range for the 1756-IF16. Please ensure the correct input range is configured in the 1756-IF16.
1 SHIELD GROUNDING: In some installations, the field wiring shield was grounded on the 1771 chassis. If this was the case, the installer must remove these shield connections from the 1771 chassis and they can be connected to the grounding stud on the 1492-CM1771-LA001 module. The pre-wired cable used between the 1492-CM1771-LA001 module and the 1756-IF16 [1492-CONACAB005B] provides a shield ground lug to ground the shield at the 1756 ControlLogix chassis, this must be connected. Do NOT connect this ground lug to the conversion module grounding stud.
CONVERSION MODULE INSTALLATION AND APPLICATION CONSIDERATIONS
2 This design assumes that all inputs on the1771-IFE were connected to current transmitters. If there was a mix of current and voltage transmitters, then modification of the pre-wired cable [1492-CONACAB005B] will need to occur at the 1756-IF16 terminal block. Refer to the 1756-IF16 Installation Manual for modification details.
4 Refer to your 1771-IFE and 1756-IF16 Installation and User Manuals for additional information concerning comparisons of module wiring, features and configuration details.
WARNING There are several key application considerations and system specifications (bottom of drawing) when using these components (conversion module, cable and input module). Read and understand these considerationsbefore installation.
1
1
IMPORTANT
Rockwell Automation Publication 1492-SG121E-EN-P - July 2016 79
Wiring Diagrams - Analog Inputs and Outputs
1771-IFE to 1756-IF16 Single End Voltage
41170-945 (1)
1
6
7 8 9
5 10 15 20
19
21
11 12 13 14 16 17 18
1492-CM1771-LA001
1771-WG Swing Arm
2
3 4
1756-IF16 1492-CONACAB005A
Black
White
Red
Green
Orange
Blue
White/Black
Red/Black
Green/Black
Orange/Black
Blue/Black
Black/White
Green/White
Blue/White
Black/Red
White/Red
Orange/Red
Blue/Red
Red/Green
Orange/Green
1 2 3 4 5 6 7 8 9 10 11 12 13
14 15 16 17 18 19 20 21
SH
Module Common
Channel 1
Channel 2
Channel 3 Channel 4
Channel 5 Channel 6 Channel 7 Channel 8
Module Common Module Common Module Common Module Common
Channel 9
Channel 10 Channel 11 Channel 12 Channel 13 Channel 14 Channel 15 Channel 16
22 23 24 25
T r ansmitt er
P o w er Supply
+ -
3-W ir e T r ansmitt er 2
IN-0 IN-1
4
IN-2 6
IN-3 8
IN-4 12
IN-5 14
IN-6 16
IN-7 18
R TN 10
R TN
27 R TN
28
IN-9 22
IN-8 20
IN-11 26
IN-10 24
IN-15 36
IN-14 34
R TN 9
IN-13 32
IN-12 30
3 The 1771-IFE analog input ranges were configured via software, as is the input range for the 1756-IF16. Please ensure the correct input range is configured in the 1756-IF16.
1 SHIELD GROUNDING: In some installations, the field wiring shield was grounded on the 1771 chassis. If this was the case, the installer must remove these shield connections from the 1771 chassis and they can be connected to the grounding stud on the 1492-CM1771-LA001 module. The pre-wired cable used between the 1492-CM1771-LA001 module and the 1756-IF16 [1492-CONACAB005A] provides a shield ground lug to ground the shield at the 1756 ControlLogix chassis, this must be connected. Do NOT connect this ground lug to the conversion module grounding stud.
CONVERSION MODULE INSTALLATION AND APPLICATION CONSIDERATIONS
2 This design assumes that all inputs on the1771-IFE were connected to voltage transmitters. If there was a mix of current and voltage transmitters, then modification of the pre-wired cable [1492-CONACAB005A] will need to occur at the 1756-IF16 terminal block. Refer to the 1756-IF16 Installation Manual for modification details.
4 Refer to your 1771-IFE and 1756-IF16 Installation and User Manuals for additional information concerning comparisons of module wiring, features and configuration details.
WARNING There are several key application considerations and system specifications (bottom of drawing) when using these components (conversion module, cable and input module). Read and understand these considerationsbefore installation.
1
1
IMPORTANT
80 Rockwell Automation Publication 1492-SG121E-EN-P - July 2016
Wiring Diagrams - Analog Inputs and Outputs
1771-IFF to 1756-IF16 Differential Current
41171-025 (00)
1
6
789
5101520
19
21
11121314161718
1492-CM1771-LA002
1771-WG Swing ArmFrom 1771-IFF
2
34
1492-CONACAB005DBlack
White
Red
Green
Orange
Blue
White/Black
Red/Black
Orange/Black
Blue/Black
Green/White
Blue/White
Black/Red
White/Red
Orange/Red
Blue/Red
Red/Green
Orange/Green
12345678910111213
1415161718192021
SH
Not Used
Channel 1+
Channel 1-
Channel 2+Channel 2-
Channel 3+Channel 3-Channel 4+Channel 4-
Not UsedNot Used
Module CommonModule Common
Channel 5+
Channel 5-Channel 6+Channel 6-Channel 7+Channel 7-Channel 8+Channel 8-
22232425
24681214161810
2220
2624
36343230
51
1511
2319
33
IN-0IN-1IN-2IN-3IN-4IN-5IN-6IN-7RTN
IN-9IN-8
IN-11IN-10
IN-15IN-14IN-13IN-12
iRTN-2iRTN-0
iRTN-6iRTN-4
iRTN-10iRTN-8
iRTN-14iRTN-12
29
TransmitterPower Supply+
-
4-Wire Transmitter
+ -
1756-IF16
The 1771-IFF analog input ranges were configured via software, as is the input range for the 1756-IF16. Pleaseensure the correct input range is configured in the 1756-IF16.
SHIELD GROUNDING: In some installations, the field wiring shield was grounded on the 1771 chassis. If this was the case, the installer must remove these shield connections from the 1771 chassis and they can be connectedto the grounding stud on the 1492-CM1771-LA002 module. The pre-wired cable used between the 1492-CM1771-LA002module and the 1756-IF16 [1492-CONACAB005D] provides a shield ground lug to ground the shield at the 1756ControlLogix chassis, this must be connected. Do NOT connect this ground lug to the conversion module grounding stud.
CONVERSION MODULE INSTALLATION AND APPLICATION CONSIDERATIONS
This design assumes that all inputs on the1771-IFF were connected to current transmitters. If there was a mix of currentand voltage transmitters, then modification of the pre-wired cable [1492-CONACAB005D] will need to occur at the 1756-IF16terminal block. Refer to the 1756-IF16 Installation Manual for modification details.
Refer to your 1771-IFF and 1756-IF16 Installation and User Manuals for additional information concerning comparisonsof module wiring, features and configuration details.
WARNING There are several key application considerations and system specifications (bottom of drawing) when usingthese components (conversion module, cable and input module). Read and understand these considerationsbefore installation.
Conversion ModuleCable
This Bul. 1492 cable consists of a cable wired to one 1756-IF16 RTB. Recommended cable lengths of 0.5M or 1.0M (005=0.5M, 010=1.0M). See table 2 for other lengths.
IMPORTANT
Rockwell Automation Publication 1492-SG121E-EN-P - July 2016 81
Wiring Diagrams - Analog Inputs and Outputs
1771-IFF to 1756-IF16 Differential Voltage
41171-026 (00)
1
6
789
5101520
19
21
11121314161718
1492-CM1771-LA002
1771-WG Swing ArmFrom 1771-IFF
2
34
1492-CONACAB005C
Black
White
Red
Green
Orange
Blue
White/Black
Red/Black
Orange/Black
Blue/Black
Green/White
Blue/White
Black/Red
White/Red
Orange/Red
Blue/Red
Red/Green
Orange/Green
12345678910111213
1415161718192021
SH
Not Used
Channel 1+
Channel 1-
Channel 2+Channel 2-
Channel 3+Channel 3-Channel 4+Channel 4-
Not UsedNot Used
Module CommonModule Common
Channel 5+
Channel 5-Channel 6+Channel 6-Channel 7+Channel 7-Channel 8+Channel 8-
22232425
1756-IF162
IN-0IN-1
4
IN-26
IN-38
IN-412
IN-514
IN-616
IN-718
RTN10
IN-922
IN-820
IN-1126
IN-1024
IN-1536
IN-1434
IN-1332
IN-1230
The 1771-IFF analog input ranges were configured via software, as is the input range for the 1756-IF16. Pleaseensure the correct input range is configured in the 1756-IF16.
SHIELD GROUNDING: In some installations, the field wiring shield was grounded on the 1771 chassis. If this was the case, the installer must remove these shield connections from the 1771 chassis and they can be connectedto the grounding stud on the 1492-CM1771-LA002 module. The pre-wired cable used between the 1492-CM1771-LA002module and the 1756-IF16 [1492-CONACAB005C] provides a shield ground lug to ground the shield at the 1756ControlLogix chassis, this must be connected. Do NOT connect this ground lug to the conversion module grounding stud.
CONVERSION MODULE INSTALLATION AND APPLICATION CONSIDERATIONS
This design assumes that all inputs on the1771-IFF were connected to voltage transmitters. If there was a mix of currentand voltage transmitters, then modification of the pre-wired cable [1492-CONACAB005C] will need to occur at the 1756-IF16terminal block. Refer to the 1756-IF16 Installation Manual for modification details.
Refer to your 1771-IFF and 1756-IF16 Installation and User Manuals for additional information concerning comparisonsof module wiring, features and configuration details.
There are several key application considerations and system specifications (bottom of drawing) when usingthese components (conversion module, cable and input module). Read and understand these considerationsbefore installation.
TransmitterPower Supply+
-
4-Wire Transmitter
+ -
This Bul. 1492 cable consists of a cable wired to one 1756-IF16 RTB. Recommended cable lengths of 0.5M or 1.0M (005=0.5M, 010=1.0M). See table 2 for other lengths.
Conversion Module Cable
IMPORTANT
82 Rockwell Automation Publication 1492-SG121E-EN-P - July 2016
Wiring Diagrams - Analog Inputs and Outputs
1771-IFF to 1756-IF16 Single End Current
41171-023 (00)
1
6
789
5101520
19
21
11121314161718
1492-CM1771-LA001
1771-WG Swing ArmFrom 1771-IFF
2
34
1756-IF162
IN-0IN-1
4
IN-26
IN-38
IN-412
IN-514
IN-616
IN-718
RTN10
RTN
27RTN
28
IN-922
IN-820
IN-1126
IN-1024
IN-1536
IN-1434
1492-CONACAB005BBlack
RTN9
White
Red
Green
Orange
Blue
White/Black
Red/Black
Green/Black
Orange/Black
Blue/Black
Black/White
IN-1332
IN-1230
Green/White
Blue/White
Black/Red
White/Red
Orange/Red
Blue/Red
Red/Green
Orange/Green
iRTN-13
iRTN-01
iRTN-37
iRTN-25
iRTN-717
iRTN-615
iRTN-513
iRTN-411
iRTN-921
iRTN-819
iRTN-1125
iRTN-1023
iRTN-1535
iRTN-1433
iRTN-1331
iRTN-1229
12345678910111213
1415161718192021
SH
Module CommonTransmitter
Power Supply+
2-Wire Transmitter
-
Channel 1
Channel 2
Channel 3Channel 4
Channel 5Channel 6Channel 7Channel 8
Module CommonModule CommonModule CommonModule Common
Channel 9
Channel 10Channel 11Channel 12Channel 13Channel 14Channel 15Channel 16
22232425
The 1771-IFF analog input ranges were configured via software, as is the input range for the 1756-IF16. Please ensure the correct input range is configured in the 1756-IF16.
SHIELD GROUNDING: In some installations, the field wiring shield was grounded on the 1771 chassis. If this was the case, the installer must remove these shield connections from the 1771 chassis and they can be connected to the grounding stud on the 1492-CM1771-LA001 module. The pre-wired cable used between the 1492-CM1771-LA001 module and the 1756-IF16 [1492-CONACAB005B] provides a shield ground lug to ground the shield at the 1756 ControlLogix chassis, this must be connected. Do NOT connect this ground lug to the conversion module grounding stud.
CONVERSION MODULE INSTALLATION AND APPLICATION CONSIDERATIONS
This design assumes that all inputs on the1771-IFF were connected to current transmitters. If there was a mix of current and voltage transmitters, then modification of the pre-wired cable [1492-CONACAB005B] will need to occur at the 1756-IF16 terminal block. Refer to the 1756-IF16 Installation Manual for modification details.
Refer to your 1771-IFF and 1756-IF16 Installation and User Manuals for additional information concerning comparisons of module wiring, features and configuration details.
There are several key application considerations and system specifications (bottom of drawing) when using these components (conversion module, cable and input module). Read and understand these considerationsbefore installation.
Conversion ModuleCable
This Bul. 1492 cable consists of a cable wired to one 1756-IF16 RTB. Recommended cable lengths of 0.5M or 1.0M (005=0.5M, 010=1.0M). See table 2 for other lengths.
IMPORTANT
Rockwell Automation Publication 1492-SG121E-EN-P - July 2016 83
Wiring Diagrams - Analog Inputs and Outputs
1771-IFF to 1756-IF16 Single End Voltage
41171-024 (00)
1
6
789
5101520
19
21
11121314161718
1492-CM1771-LA001
1771-WG Swing ArmFrom 1771-IFF
2
34
1756-IF161492-CONACAB005ABlack
White
Red
Green
Orange
Blue
White/Black
Red/Black
Green/Black
Orange/Black
Blue/Black
Black/White
Green/White
Blue/White
Black/Red
White/Red
Orange/Red
Blue/Red
Red/Green
Orange/Green
12345678910111213
1415161718192021
SH
Module Common
Channel 1
Channel 2
Channel 3Channel 4
Channel 5Channel 6Channel 7Channel 8
Module CommonModule CommonModule CommonModule Common
Channel 9
Channel 10Channel 11Channel 12Channel 13Channel 14Channel 15Channel 16
22232425
Transmitter
Power Supply
+ -
3-Wire Transmitter2
IN-0IN-1
4
IN-26
IN-38
IN-412
IN-514
IN-616
IN-718
RTN10
RTN
27RTN
28
IN-922
IN-820
IN-1126
IN-1024
IN-1536
IN-1434
RTN9
IN-1332
IN-1230
The 1771-IFF analog input ranges were configured via software, as is the input range for the 1756-IF16. Pleaseensure the correct input range is configured in the 1756-IF16.
SHIELD GROUNDING: In some installations, the field wiring shield was grounded on the 1771 chassis. If this was the case, the installer must remove these shield connections from the 1771 chassis and they can be connectedto the grounding stud on the 1492-CM1771-LA001 module. The pre-wired cable used between the 1492-CM1771-LA001module and the 1756-IF16 [1492-CONACAB005A] provides a shield ground lug to ground the shield at the 1756ControlLogix chassis, this must be connected. Do NOT connect this ground lug to the conversion module grounding stud.
CONVERSION MODULE INSTALLATION AND APPLICATION CONSIDERATIONS
This design assumes that all inputs on the1771-IFF were connected to voltage transmitters. If there was a mix of currentand voltage transmitters, then modification of the pre-wired cable [1492-CONACAB005A] will need to occur at the 1756-IF16terminal block. Refer to the 1756-IF16 Installation Manual for modification details.
Refer to your 1771-IFF and 1756-IF16 Installation and User Manuals for additional information concerning comparisonsof module wiring, features and configuration details.
There are several key application considerations and system specifications (bottom of drawing) when using these components (conversion module, cable and input module). Read and understand these considerationsbefore installation.
This Bul. 1492 cable consists of a cable wired to one 1756-IF16 RTB. Recommended cable lengths of 0.5M or 1.0M (005=0.5M, 010=1.0M). See table 2 for other lengths.
Conversion ModuleCable
IMPORTANT
84 Rockwell Automation Publication 1492-SG121E-EN-P - July 2016
Wiring Diagrams - Analog Inputs and Outputs
1771-IL to 1756-IF8I Current
The 1771-IL input configuration was software configured, as is the 1756-IF8I. Please ensure the correct configuration in the 1756-IF8I.
SHIELD GROUNDING: In some installations, the field wiring shield was grounded on the 1771 chassis. If this was the case, the installer must remove these shield connections from the 1771 chassis and they can be connected to the grounding stud on the 1492-CM1771-LA004 module. The pre-wired cable used between the 1492-CM1771-LA004 module and the 1756-IF8I [1492-CONACAB005K8] provides a shield ground lug to ground the shield at the 1756 ControlLogix chassis, this must be connected. Do NOT connect this ground lug to the conversion module grounding stud.
CONVERSION MODULE INSTALLATION AND APPLICATION CONSIDERATIONS
Refer to your 1771-IL and 1756-IF8I Installation and User Manuals for additional information concerning comparisons of module wiring, features and configuration details.
There are several key application considerations and system specifications (bottom of drawing) when usingthese components (conversion module, cable and input module). Read and understand these considerationsbefore installation.
This Bul. 1492 cable consists of a cable wired to one 1756-IF6I RTB. Recommended cable lengths of 0.5M or 1.0M (005=0.5M, 010=1.0M).
18
1492-CM1771-LA004
1716151413121110
987
SH
432
6
1
5
1492-CONACAB005K8
Orange/Red
White/Red
Green/White
Blue/White
Orange/Black
Red/White
Black/Red
Blue/Black
Black/White
Green/Black
Blue
Orange
Red/Black
White/Black
18
14131211
8
65
1771-WF Swing ArmFrom 1771-IL
171615
4321
109
7
Channel6 Channel7Channel7 Orange
Blue
White / BlackRed / Black
Channel5 Channel5Channel6
Channel4Channel4
Channel3 Channel3
Channel0
Channel2Channel2
Channel1Channel1
Channel0 TransmitterPower Supply
+
-
4-Wire Transmitter
+ -
2-WireTransmitter
+
-
Conversion ModuleCable 1756-IF8I
4
3027
11
12
20
3
28
19
5
6
13
14
21
22
29
Iin_CH0RTN_CH0Iin_CH1RTN_CH1Iin_CH2RTN_CH2Iin_CH3RTN_CH3
Iin_CH4RTN_CH4Iin_CH5RTN_CH5Iin_CH6
RTN_CH7Iin_CH7RTN_CH6
2625
32
31
3433
2
1
98
1510
1716
23
18
7
24N.C.N.C.
N.C.N.C.N.C.N.C.N.C.N.C.N.C.
N.C.N.C.
N.C.
3635
N.C.N.C.
N.C.N.C.N.C.N.C.N.C.
N.C.
IMPORTANT
Rockwell Automation Publication 1492-SG121E-EN-P - July 2016 85
Wiring Diagrams - Analog Inputs and Outputs
1771-IL to 1756-IF8I Voltage
There are several key application considerations and system specifications (bottom of drawing) when usingthese components (conversion module, cable and input module). Read and understand these considerationsbefore installation.
The 1771-IL input configuration was software configured, as is the 1756-IF8I. Please ensure the correct configuration in the 1756-IF8I.
SHIELD GROUNDING: In some installations, the field wiring shield was grounded on the 1771 chassis. If this was the case, the installer must remove these shield connections from the 1771 chassis and they can be connected to the grounding stud on the 1492-CM1771-LA004 module. The pre-wired cable used between the 1492-CM1771-LA004 module and the 1756-IF8I [1492-CONACAB005L8] provides a shield ground lug to ground the shield at the 1756 ControlLogix chassis, this must be connected. Do NOT connect this ground lug to the conversion module grounding stud.
Refer to your 1771-IL and 1756-IF8I Installation and User Manuals for additional information concerning comparisons of module wiring, features and configuration details.
This Bul. 1492 cable consists of a cable wired to one 1756-IF8I RTB. Recommended cable lengths of 0.5M or 1.0M (005=0.5M, 010=1.0M).
18
1492-CM1771-LA004
1716151413121110
987
SH
432
6
1
5
1492-CONACAB005L8
Orange/Red
White/Red
Green/White
Blue/White
Orange/Black
Red/White
Black/Red
Blue/Black
Black/White
Green/Black
Blue
Orange
Red/Black
White/Black
18
14131211
8
65
1771-WF Swing ArmFrom 1771-IL
171615
4321
109
7
TransmitterPower Supply+
-
4-Wire Transmitter
+ -
Conversion ModuleCable
3
1756-IF8I
2
3025
9
10
18
1
26
17
3
5
6
13
14
21
22
29
Vout_CH0RTN_CH0Vout_CH1RTN_CH1Vout_CH2RTN_CH2Vout_CH3RTN_CH3
Vout_CH4RTN_CH4Vout_CH5RTN_CH5Vout_CH6
RTN_CH7Vout_CH7RTN_CH6
2724
31
28
3332
4
3
35
8
1211
1615
2019
7
23N.C.N.C.
N.C.N.C.N.C.N.C.N.C.N.C.N.C.
N.C.N.C.
N.C.
36
34
N.C.N.C.
N.C.N.C.N.C.N.C.N.C.
N.C.
Vout_CH0RTN_CH0Vout_CH1RTN_CH1Vout_CH2RTN_CH2Vout_CH3RTN_CH3
Vout_CH4RTN_CH4Vout_CH5RTN_CH5Vout_CH6
RTN_CH7Vout_CH7RTN_CH6
Orange
Blue
White / BlackRed / Black
IMPORTANT
86 Rockwell Automation Publication 1492-SG121E-EN-P - July 2016
Wiring Diagrams - Analog Inputs and Outputs
1771-IL to 1756-IF6I — 6-ch Current
41171-030 (00)
18
1492-CM1771-LA004
1716151413121110
987
SH
432
6
1
5
1492-CONACAB005K
Orange/Red
White/Red
Green/White
Blue/White
Orange/Black
Red/White
Black/Red
Blue/Black
Black/White
Green/Black
Blue
Orange
Red/Black
White/Black
18
14131211
8
65
1771-WF Swing ArmFrom 1771-IL
171615
4321
109
7
Channel6 Channel7Channel7
1756-IF6I
Black
White
RedGreen
Channel5 Channel5Channel6
Channel4Channel4
Channel3 Channel3
Channel0
Channel2Channel2
Channel1Channel1
Channel0
The 1771-IL input configuration was software configured, as is the 1756-IF6I. Please ensure the correct configuration in the 1756-IF6I.
SHIELD GROUNDING: In some installations, the field wiring shield was grounded on the 1771 chassis. If this was the case, the installer must remove these shield connections from the 1771 chassis and they can be connected to the grounding stud on the 1492-CM1771-LA004 module. The pre-wired cable used between the 1492-CM1771-LA004 module and the 1756-IF6I [1492-CONACAB005K] provides a shield ground lug to ground the shield at the 1756 ControlLogix chassis, this must be connected. Do NOT connect this ground lug to the conversion module grounding stud.
CONVERSION MODULE INSTALLATION AND APPLICATION CONSIDERATIONS
Refer to your 1771-IL and 1756-IF6I Installation and User Manuals for additional information concerning comparisons of module wiring, features and configuration details.
There are several key application considerations and system specifications (bottom of drawing) when using these components (conversion module, cable and input module). Read and understand these considerationsbefore installation.
53
64
119
1210
1917
16152018
1
278
RET-0
IN-0/I
IN-1/V
IN-4/IRET-4IN-5/IRET-5
TransmitterPower Supply+
-
4-Wire Transmitter
+ -
RET-1
IN-1/I
IN-0/V
RET-3
IN-3/I
IN-2/VIN-3/V
RET-2IN-2/I
IN-4/VIN-5/V
This Bul. 1492 cable consists of a cable wired to one 1756-IF6I RTB. Recommended cable lengths of 0.5M or 1.0M (005=0.5M, 010=1.0M). See table 2 for other lengths.
2-WireTransmitter
+
-
Conversion ModuleCable
IMPORTANT
Rockwell Automation Publication 1492-SG121E-EN-P - July 2016 87
Wiring Diagrams - Analog Inputs and Outputs
1771-IL to 1756-IF6I — 6-ch Voltage
41171-029 (00)
18
1492-CM1771-LA004
1716151413121110
987
SH
432
6
1
5
1492-CONACAB005L
Orange/Red
White/Red
Green/White
Blue/White
Orange/Black
Red/White
Black/Red
Blue/Black
Black/White
Green/Black
Blue
Orange
Red/Black
White/Black
18
14131211
8
65
1771-WF Swing ArmFrom 1771-IL
171615
4321
109
7
1756-IF6I
Black
White
RedGreen
ARNING There are several key application considerations and system specifications (bottom of drawing) when using these components (conversion module, cable and input module). Read and understand these considerationsbefore installation.
152
47
118
12
1718
1915
1413
2016
109
RET-0IN-0
RET-1IN-1
RET-2IN-2
RET-3
IN-4RET-4IN-5RET-5
NO CONNECTNO CONNECT
TransmitterPower Supply+
-
2-Wire Transmitter
+ -
IN-3
43 NO CONNECT
NO CONNECTNO CONNECTNO CONNECTNO CONNECTNO CONNECT
Conversion ModuleCable
The 1771-IL input configuration was software configured, as is the 1756-IF6I. Please ensure the correct configuration in the 1756-IF6I.
SHIELD GROUNDING: In some installations, the field wiring shield was grounded on the 1771 chassis. If this was the case, the installer must remove these shield connections from the 1771 chassis and they can be connected to the grounding stud on the 1492-CM1771-LA004 module. The pre-wired cable used between the 1492-CM1771-LA004 module and the 1756-IF6I [1492-CONACAB005L] provides a shield ground lug to ground the shield at the 1756 ControlLogix chassis, this must be connected. Do NOT connect this ground lug to the conversion module grounding stud.
Refer to your 1771-IL and 1756-IF6I Installation and User Manuals for additional information concerning comparisons of module wiring, features and configuration details.
This Bul. 1492 cable consists of a cable wired to one 1756-IF6I RTB. Recommended cable lengths of 0.5M or 1.0M (005=0.5M, 010=1.0M). See table 2 for other lengths.
Channel6 Channel7Channel7
Channel5 Channel5Channel6
Channel4Channel4
Channel3 Channel3
Channel0
Channel2Channel2
Channel1Channel1
Channel0
IMPORTANT
88 Rockwell Automation Publication 1492-SG121E-EN-P - July 2016
Wiring Diagrams - Analog Inputs and Outputs
1771-IL to 1756-IF6I — (2 x 4-ch) Current
Conversion Module1492-CM1771-LA004
1771-WF Swing ArmFrom 1771-IL
Cable1492-CONACAB005T1� 1756-IF6I
1756-IF6I
Conversion Module Installation and Application Considerations� This Bul. 1492 cable consists of a cable wired to two 1756-IF6I RTB. Recommended cable lengths of 0.5M or 1.0M (005=0.5M, 010=1.0M). See table 2 for other lengths.
� SHIELD GROUNDING: In some installations, the field wiring shield was grounded on the 1771 chassis. If this was the case, the installer must remove these shield connections from the 1771 chassis and they can be connected to the grounding stud on the 1492-CM1771-LA004 module. The pre-wired cable used between the 1492-CM1771-LA004 module and the 1756-IF6I [1492-CONACAB005T1] provides a shield ground lug to ground the shield at the 1756 ControlLogix chassis, this must be connected. Do NOT connect this ground lug to the conversion module grounding stud.
� The 1771-IL input configuration was software configured, as is the 1756-IF6I. Please ensure the correct configuration in the 1756-IF6I.
� Refer to your 1771-IL and 1756-IF6I Installation and User Manuals for additional information concerning comparisons of module wiring, features and configuration details.
� This configuration uses two (2) 1756-IF6I output modules to replace a single 1771-IL output module. This may require the use of a larger 1756 I/O chassis and conversion mounting assembly. Ensure there is sufficient panel space to allow for this possibility. [Reference Doc: 41171-032 (Version 00)]
181716151413121110
987
SH
432
6
1
5
Orange/Red
White/Red
Green/White
Blue/White
Orange/Black
Red/White
Black/Red
Blue/Black
Black/White
Green/Black
Blue
Orange
Red/Black
White/Black
18
14131211
8
65
171615
4321
109
7
Channel6 Channel7Channel7 Black
White
RedGreen
Channel5 Channel5Channel6
Channel4Channel4
Channel3 Channel3
Channel0
Channel2Channel2
Channel1Channel1
Channel0 53
64
119
1210
1917
16152018
1
278
RET-0
IN-0/I
IN-1/V
IN-4/IRET-4IN-5/IRET-5
TransmitterPower Supply+
-
4-Wire Transmitter
+ -
RET-1
IN-1/I
IN-0/V
RET-3
IN-3/I
IN-2/VIN-3/V
RET-2IN-2/I
IN-4/VIN-5/V
2-WireTransmitter
+
-
��
53
64
119
1210
1917
16152018
1
278
RET-0
IN-0/I
IN-1/V
IN-4/IRET-4IN-5/IRET-5
RET-1
IN-1/I
IN-0/V
RET-3
IN-3/I
IN-2/VIN-3/V
RET-2IN-2/I
IN-4/VIN-5/V
IMPORTANT
Rockwell Automation Publication 1492-SG121E-EN-P - July 2016 89
Wiring Diagrams - Analog Inputs and Outputs
1771-IL to 1756-IF6I — (2 x 4-ch) Voltage
There are several key application considerations and system specifications (bottom of drawing) when using these components (conversion module, cable and input module). Read and understand these considerations before installation.
1771-WF Swing ArmFrom 1771-IL
Conversion Module1492-CM1771-LA004 Cable
1492-CONACAB005T2 1756-IF6I
1756-IF6I
Conversion Module Installation and Application Considerations This Bul. 1492 cable consists of a cable wired to two 1756-IF6I RTB. Recommended cable lengths of 0.5M or
1.0M (005=0.5M, 010=1.0M). See table 2 for other lengths.
SHIELD GROUNDING: In some installations, the field wiring shield was grounded on the 1771 chassis. If this was the case, the installer must remove these shield connections from the 1771 chassis and they can be connected to the grounding stud on the 1492-CM1771-LA004 module. The pre-wired cable used between the 1492-CM1771-LA004 module and the 1756-IF6I [1492-CONACAB005T2] provides a shield ground lug to ground the shield at the 1756 ControlLogix chassis, this must be connected. Do NOT connect this ground lug to the conversion module grounding stud.
The 1771-IL input configuration was software configured, as is the 1756-IF6I. Please ensure the correct configuration in the 1756-IF6I.
Refer to your 1771-IL and 1756-IF6I Installation and User Manuals for additional information concerning comparisons of module wiring, features and configuration details.
This configuration uses two (2) 1756-IF6I output modules to replace a single 1771-IL output module. This may require the use of a larger 1756 I/O chassis and conversion mounting assembly. Ensure there is sufficient panel space to allow for this possibility. 41171-031 (00)
181716151413121110
987
SH
432
6
1
5
Orange/Red
White/Red
Green/White
Blue/White
Orange/Black
Red/White
Black/Red
Blue/Black
Black/White
Green/Black
Blue
Orange
Red/Black
White/Black
18
14131211
8
65
171615
4321
109
7
Black
White
RedGreen
152
67
118
12
1718
1915
1413
2016
109
RET-0IN-0
RET-1IN-1
RET-2IN-2
RET-3
IN-4RET-4IN-5RET-5
NO CONNECTNO CONNECT
TransmitterPower Supply+
-
4-Wire Transmitter
+ -
IN-3
43 NO CONNECT
NO CONNECTNO CONNECTNO CONNECTNO CONNECTNO CONNECT
Channel6 Channel7Channel7
Channel5 Channel5Channel6
Channel4Channel4
Channel3 Channel3
Channel0
Channel2Channel2
Channel1Channel1
Channel0
152
47
118
12
1718
1915
1413
2016
109
RET-0IN-0
RET-1IN-1
RET-2IN-2
RET-3
IN-4RET-4IN-5RET-5
NO CONNECTNO CONNECT
IN-3
43 NO CONNECT
NO CONNECTNO CONNECTNO CONNECTNO CONNECTNO CONNECT
2-WireTransmitter
+
-
IMPORTANT
90 Rockwell Automation Publication 1492-SG121E-EN-P - July 2016
Wiring Diagrams - Analog Inputs and Outputs
1771-IR to 1756-IRT8I
181716151413121110
987
SH
432
6
1
5
18
14131211
8
65
171615
4321
109
7
Channel6 - CChannel6 - BChannel6 - A
643
10
87
1412
1811
2022
1516
19262423
3-Wire RTD
2-Wire RTD
Channel5 - CChannel5 - BChannel5 - A
Channel4 - C
Channel4 - BChannel4 - A
Channel3 - CChannel3 - B
Channel3 - A
Channel2 - C
Channel2 - BChannel2 - A
Channel1 - CChannel1 - B
Channel1 - A
WARNING There are several key application considerations and system sp cations (bottom of drawing) when usingthese components (conversion module, cable and output module). Read and understand these considerationsbefore installation.
IN_0/RTD C
IN_1/RTD C
IN_1(-)/B
IN_1(+)/A
IN_2/RTD C
IN_2(-)/B
IN_2(+)/A
IN_3/RTD C
IN_3(-)/B
IN_3(+)/A
IN_4/RTD C
IN_4(-)/B
IN_4(+)/A
IN_5(+)/A
IN_5(-)/B
IN_5/RTD C
3130
33
32
3534
2
1
139
2117
2725
28
5
29N.C.N.C.
N.C.N.C.N.C.N.C.N.C.N.C.
N.C.N.C.
N.C.
36
N.C.N.C.
N.C.N.C.N.C.N.C.
N.C.
IN_0(+)AIN_0(-)/B
Conversion Module Installation and Application Considerations� Cables are available in lengths of 0.5M or 1.0M (005=0.5M, 010=1.0M)
� shield connections from the 1771 chassis and they can be connected to the grounding stud on the 1492-CM1771-LA004 module. The pre-wired cable used between the 1492-CM1771-LA004 module and the 1756-IRT8I [1492-CONACAB005F8] provides a shield ground lug to ground the shield at the 1756 ControlLogix chassis, this must be connected. Do NOT connect this ground lug to the conversion module grounding stud.
�
� Refer to your 1771-IR and 1756-IRT8I Installation and User Manuals for additional information concerning comparisons of module wiring, features and
Cable�
�
�
�
�
IMPORTANT
Rockwell Automation Publication 1492-SG121E-EN-P - July 2016 91
Wiring Diagrams - Analog Inputs and Outputs
1771-IR to 1756-IR6I
41170-950 (1)
18
1492-CM1771-LA004
17 16 15 14 13 12 11 10
9 8 7
SH
4 3 2
6
1
5
1492-CONACAB005F
Orange/Red
White/Red
Green/White
Blue/White
Orange/Black
Red/White
Black/Red
Blue/Black
Black/White
Green/Black
Blue
Orange
Red/Black
White/Black
18
14 13 12 11
8
6 5
1771-WF Swing Arm
17 16 15
4 3 2 1
10 9
7
Channel6 - C Channel6 - B Channel6 - A
1756-IR6I
5
IN-0/A
R TN-0/C 3
IN-1/A
1
R TN-1/C 6
IN-2/A
4
R TN-2/C
2
IN-3/A
11
R TN-3/C
9
R TN-4/C
12
IN-4/A
7
IN-0/B
17
IN-3/B
19
R TN-5/C
8
IN-5/A
10
IN-1/B
15
IN-2/B
20
IN-4/B
18 IN-5/B
16
3-W ir e R TD
2-W ir e R TD
Black
White
Red Green
Channel5 - C Channel5 - B Channel5 - A
Channel4 - C
Channel4 - B Channel4 - A
Channel3 - C Channel3 - B
Channel3 - A
Channel2 - C
Channel2 - B Channel2 - A
Channel1 - C Channel1 - B
Channel1 - A
2 The 1771-IR input configuration was software configured, as is the 1756-IR6I. Please ensure the correct configuration in the 1756-IR6I.
1 SHIELD GROUNDING: In some installations, the field wiring shield was grounded on the 1771 chassis. If this was the case, the installer must remove these shield connections from the 1771 chassis and they can be connected to the grounding stud on the 1492-CM1771-LA004 module. The pre-wired cable used between the 1492-CM1771-LA004 module and the 1756-IR6I [1492-CONACAB005F] provides a shield ground lug to ground the shield at the 1756 ControlLogix chassis, this must be connected. Do NOT connect this ground lug to the conversion module grounding stud.
CONVERSION MODULE INSTALLATION AND APPLICATION CONSIDERATIONS
3 Refer to your 1771-IR and 1756-IR6I Installation and User Manuals for additional information concerning comparisons of module wiring, features and configuration details.
WARNING There are several key application considerations and system specifications (bottom of drawing) when using these components (conversion module, cable and input module). Read and understand these considerationsbefore installation.
1
1
IMPORTANT
92 Rockwell Automation Publication 1492-SG121E-EN-P - July 2016
Wiring Diagrams - Analog Inputs and Outputs
1771-IXE to 1756-IT6I2
41170-951 (1)
1492-CM1771-LA005
SH
Input 1+
1756-IT6I2 5
IN-0 R TN-0
6
IN-1 7
R TN-1 8
IN-2 9
R TN-2 10
IN-3 11
R TN-3 12
R TN-4 14
IN-4 13
CJC- 4
CJC+ 3
1492-CONACAB005G
R TN-5 16
IN-5 15
T her mo c ouple
+
-
T
18
14 13 12 11
8
6 5
1771-WI Swing Arm
17 16 15
4 3 2 1
10 9
7
Input 1- Input 2+ Input 2- Input 3+ Input 3- Input 4+ Input 4-
Input 5+ Input 5- Input 6+ Input 6-
18 17 16 15 14 13 12 11 10 9 8 7 6 5
Orange/Red
White/Red
Green/White
Blue/White
Orange/Black
Red/White
Black/Red
Blue/Black
Black/White
Green/Black
Blue
Orange
Red/Black
White/Black
4 3 2 1
2 The 1771-IXE has 8 input channels. The 1756-IT6I2 only has 6 input channels. This module combination can only be used to convert the signals if 6 or less channels were used on the 1771-IXE.
1 SHIELD GROUNDING: In some installations, the field wiring shield was grounded on the 1771 chassis. If this was the case, the installer must remove these shield connections from the 1771 chassis and they can be connected to the grounding stud on the 1492-CM1771-LA005 module. The pre-wired cable used between the 1492-CM1771-LA005 module and the 1756-IT6I2 [1492-CONACAB005G] provides a shield ground lug to ground the shield at the 1756 ControlLogix chassis, this must be connected. Do NOT connect this ground lug to the conversion module grounding stud.
CONVERSION MODULE INSTALLATION AND APPLICATION CONSIDERATIONS
3 The 1771-IXE has built CJC (cold junction compensation) into the swing-arm. The conversion module [1492-CM1771-LA005] passes this CJC signal to the 1756-IT6I2. Ensure that the 1756-IT6I2 is configured for external CJC.
4 The 1771-IXE input configuration was software configured, as is the 1756-IT6I2. Please ensure the correct configuration in the 1756-IT6I2.
5 Refer to your 1771-IXE and 1756-IT6I2 Installation and User Manuals for additional information concerning comparisons of module wiring, features and configuration details.
There are several key application considerations and system specifications (bottom of drawing) when using these components (conversion module, cable and input module). Read and understand these considerationsbefore installation.
1
1
IMPORTANT
Rockwell Automation Publication 1492-SG121E-EN-P - July 2016 93
Wiring Diagrams - Analog Inputs and Outputs
1771-IXE to 1756-IRT8I
There are several key application considerations and system specifications (bottom of drawing) when using these components (conversion module , cable and input module). Read and understand these considerations bef ore installation.
1492-CM1771-LA005 SER “B”
SH
1492-CONACAB005G8Thermocouple
+
-
T
18
14131211
8
65
1771-WI Swing ArmFrom 1771-IXE
171615
4321
109
7
18171615141312111098765
Orange/Red
White/Red
Green/White
Blue/White
Orange/Black
Red/White
Black/Red
Blue/Black
Black/White
Green/Black
Blue
Orange
Red/Black
White/Black
4321
SHIELD GROUNDING: In some installations, the field wiring shield was grounded on the 1771 chassis. If this was the case, the installer must remove these shield connections from the 1771 chassis and they can be connected to the grounding stud on the 1492-CM1771-LA005 SER”B” module. The pre-wired cable used between the 1492-CM1771-LA005 SER”B” module and the 1756-IRT8I [1492-CONACAB005G8] provides a shield ground lug to ground the shield at the 1756 ControlLogix chassis, this must be connected. Do NOT connect this ground lug to the conversion module grounding stud.
CONVERSION MODULE INSTALLATION AND APPLICATION CONSIDERATIONS
The 1771-IXE has built CJC (cold junction compensation) into the swing-arm. The conversion module [1492-CM1771-LA005 SER”B”] passes this CJC signal to the 1756-IRT8I. Ensure that the 1756-IRT8I is configured for external CJC.
The 1771-IXE input configuration was software configured, as is the 1756-IRT8I. Please ensure the correct configuration in the 1756-IRT8I.
Refer to your 1771-IXE and 1756-IRT8I Installation and User Manuals for additional information concerning comparisons of module wiring, features and configuration details.
Conversion ModuleCable
This Bul. 1492 cable consists of a cable wired to one 1756-IRT8I RTB. Recommended cable lengths of 0.5M or 1.0M (005=0.5M, 010=1.0M).
1756-IRT8I3
32
31
15
11
19
7
27
23
2
8
4
16
12
24
20
28
1 CJC+CJC-
In_CH0+In_CH0-In_CH1+In_CH1- In_CH2+In_CH2- In_CH3+In_CH3-
In_CH4+In_CH4- In_CH5+In_CH5-
In_CH6+In_CH6-
In_CH7+In_CH7-
2625
3029
96
1310
1714
21185
22
N.C.N.C.
N.C.N.C.N.C.N.C.
N.C.N.C.N.C.N.C.N.C.
N.C.
N.C.N.C.
Blue
Orange
Red/Black
White/Black
CJC+CJC-
In_CH0+In_CH0-In_CH1+In_CH1- In_CH2+In_CH2- In_CH3+In_CH3-
In_CH4+In_CH4- In_CH5+In_CH5- In_CH6+In_CH6-
In_CH7+In_CH7-
IMPORTANT
94 Rockwell Automation Publication 1492-SG121E-EN-P - July 2016
Wiring Diagrams - Analog Inputs and Outputs
1771-IXHR to 1756-IT6I2
41171-035 (00)
1492-CM1771-LA005
SH
Input 1+
1756-IT6I25
IN-0RTN-0
6
IN-17
RTN-18
IN-29
RTN-210
IN-311
RTN-312
RTN-414
IN-413
CJC-4
CJC+3
1492-CONACAB005G
RTN-516
IN-515
Thermocouple
+
-
T
18
14131211
8
65
1771-WI Swing ArmFrom 1771-IXHR
171615
4321
109
7
Input 1-Input 2+Input 2-Input 3+Input 3-Input 4+Input 4-
Input 5+Input 5-Input 6+Input 6-
18171615141312111098765
Orange/Red
White/Red
Green/White
Blue/White
Orange/Black
Red/White
Black/Red
Blue/Black
Black/White
Green/Black
Blue
Orange
Red/Black
White/Black
4321
The 1771-IXHR has 8 input channels. The 1756-IT6I2 only has 6 input channels. This module combination can only be used to convert the signals if 6 or less channels were used on the 1771-IHER.
SHIELD GROUNDING: In some installations, the field wiring shield was grounded on the 1771 chassis. If this was the case, the installer must remove these shield connections from the 1771 chassis and they can be connected to the grounding stud on the 1492-CM1771-LA005 module. The pre-wired cable used between the 1492-CM1771-LA005 module and the 1756-IT6I2 [1492-CONACAB005G] provides a shield ground lug to ground the shield at the 1756 ControlLogix chassis, this must be connected. Do NOT connect this ground lug to the conversion module grounding stud.
CONVERSION MODULE INSTALLATION AND APPLICATION CONSIDERATIONS
The 1771-IXHR has built CJC (cold junction compensation) into the swing-arm. The conversion module [1492-CM1771-LA005] passes this CJC signal to the 1756-IT6I2. Ensure that the 1756-IT6I2 is configured for external CJC.
The 1771-IXHR input configuration was software configured, as is the 1756-IT6I2. Please ensure the correct configuration in the 1756-IT6I2.
Refer to your 1771-IXHR and 1756-IT6I2 Installation and User Manuals for additional information concerning comparisons of module wiring, features and configuration details.
There are several key application considerations and system specifications (bottom of drawing) when usingthese components (conversion module, cable and input module). Read and understand these considerationsbefore installation.
Conversion ModuleCable
This Bul. 1492 cable consists of a cable wired to one 1756-IT6I2 RTB. Recommended cable lengths of 0.5M or 1.0M (005=0.5M, 010=1.0M). See table 2 for other lengths.
IMPORTANT
Rockwell Automation Publication 1492-SG121E-EN-P - July 2016 95
Wiring Diagrams - Analog Inputs and Outputs
1771-IXHR to 1756-IRT8I
1492-CM1771-LA005 SER “B”
SH
1492-CONACAB005G8Thermocouple
+
-
T
18
14131211
8
65
1771-WI Swing ArmFrom 1771-IXHR
171615
4321
109
7
18171615141312111098765
Orange/Red
White/Red
Green/White
Blue/White
Orange/Black
Red/White
Black/Red
Blue/Black
Black/White
Green/Black
Blue
Orange
Red/Black
White/Black
4321
SHIELD GROUNDING: In some installations, the field wiring shield was grounded on the 1771 chassis. If this was the case, the installer must remove these shield connections from the 1771 chassis and they can be connected to the grounding stud on the 1492-CM1771-LA005 SER”B” module. The pre-wired cable used between the 1492-CM1771-LA005 SER”B” module and the 1756-IRT8I [1492-CONACAB005G8] provides a shield ground lug to ground the shield at the 1756 ControlLogix chassis, this must be connected. Do NOT connect this ground lug to the conversion module grounding stud.
CONVERSION MODULE INSTALLATION AND APPLICATION CONSIDERATIONS
The 1771-IXHR has built CJC (cold junction compensation) into the swing-arm. The conversion module [1492-CM1771-LA005 SER”B”] passes this CJC signal to the 1756-IRT8I. Ensure that the 1756-IRT8I is configured for external CJC.
The 1771-IXHR input configuration was software configured, as is the 1756-IRT8I. Please ensure the correct configuration in the 1756-IRT8I.
Refer to your 1771-IXHR and 1756-IRT8I Installation and User Manuals for additional information concerning comparisons of module wiring, features and configuration details.
There are several key application considerations and system specifications (bottom of drawing) when usingthese components (conversion module, cable and input module). Read and understand these considerationsbefore installation.
Conversion ModuleCable
This Bul. 1492 cable consists of a cable wired to one 1756-IRT8I RTB. Recommended cable lengths of 0.5M or 1.0M (005=0.5M, 010=1.0M).
1756-IRT8I3
32
31
15
11
19
7
27
23
2
8
4
16
12
24
20
28
1 CJC+CJC-
In_CH0+In_CH0-In_CH1+In_CH1- In_CH2+In_CH2- In_CH3+In_CH3-
In_CH4+In_CH4- In_CH5+In_CH5-
In_CH6+In_CH6-
In_CH7+In_CH7-
2625
3029
96
1310
1714
21185
22
N.C.N.C.
N.C.N.C.N.C.N.C.
N.C.N.C.N.C.N.C.N.C.
N.C.
N.C.N.C.
Blue
Orange
Red/Black
White/Black
CJC+CJC-
In_CH0+In_CH0-In_CH1+In_CH1- In_CH2+In_CH2- In_CH3+In_CH3-
In_CH4+In_CH4- In_CH5+In_CH5- In_CH6+In_CH6-
In_CH7+In_CH7-
IMPORTANT
96 Rockwell Automation Publication 1492-SG121E-EN-P - July 2016
Wiring Diagrams - Analog Inputs and Outputs
1771-OFE1 to 1756-OF6VI
41170-949 (1)
1492-CM1771-LA003
SH
Channel 1 Out +
Not Used
1756-OF6VI 1
OUT-0 R TN-0
5
OUT-1 2
R TN-1 6
OUT-2 7
R TN-2 11
OUT-3 8
R TN-3 12
R TN-4 19
OUT-4 15
N ot U sed 14
N ot U sed 13
1492-CONACAB005E
20 16
VoltageLoad
+ -
A
3 4 5 6 7 B
1771-WC Swing Arm
0 1 2
Not Used
Channel 1 Out -
Channel 2 Out + Channel 2 Out - Channel 3 Out + Channel 3 Out - Channel 4 Out + Channel 4 Out -
2 The 1771-OFE1 analog output range was configured by jumpers, the output range for the 1756-OF6VI is software configured. Please ensure the correct output range is configured in the 1756-OF6VI.
1 SHIELD GROUNDING: In some installations, the field wiring shield was grounded on the 1771 chassis. If this was the case, the installer must remove these shield connections from the 1771 chassis and they can be connected to the grounding stud on the 1492-CM1771-LA003 module. The pre-wired cable used between the 1492-CM1771-LA003 module and the 1756-OF6VI [1492-CONACAB005E] provides a shield ground lug to ground the shield at the 1756 ControlLogix chassis, this must be connected. Do NOT connect this ground lug to the conversion module grounding stud.
CONVERSION MODULE INSTALLATION AND APPLICATION CONSIDERATIONS
3 Refer to your 1771-OFE1 and 1756-OF6VI Installation and User Manuals for additional information concerning comparisons of module wiring, features and configuration details.
There are several key application considerations and system specifications (bottom of drawing) when using these components (conversion module, cable and output module). Read and understand these considerations before installation.
1
1
Red/White
Green/Black/White
Black/White/Red
White/Black/Red
Orange/Green
Red/Black/White
Orange/Red
Blue/Red
Not UsedNot Used
13252423222119181716123456789101112141520
IMPORTANT
Rockwell Automation Publication 1492-SG121E-EN-P - July 2016 97
Wiring Diagrams - Analog Inputs and Outputs
1771-OFE1 to 1756-OF8I
using these components (conversion module, cable and input module). Read and understand these considerations before installation.
Conversion Module Installation and Application Considerations� Cables are available in lengths of 0.5M or 1.0M (005=0.5M, 010=1.0M)
� shield connections from the 1771 chassis and they can be connected to the grounding stud on the 1492-CM1771-LA003 module. The pre-wired cable used between the 1492-CM1771-LA003 module and the 1756-OF8I [1492-CONACAB005E8V] provides a shield ground lug to ground the shield at the 1756 ControlLogix chassis, this must be connected. Do NOT connect this ground lug to the conversion module grounding stud.
�
� Refer to your 1771-OFE1 and 1756-OF8I Installation and User Manuals for additional information concerning comparisons of module wiring, features and
1771-WC Swing ArmFrom 1771-OFE1
Conversion Module1492-CM1771-LA003
Cable1492-CONACAB005E8V� 1756-OF8I
�
�
1325242322211918171612
SH
Channel 1 Out +
Not Used
2OUT_0/VRTN_0
6
OUT_1/V1
RTN_15
OUT_2/V10
RTN_214
OUT_3/V9
RTN_313
VoltageLoad
+ -
A
34567B
012
Not Used
Channel 1 Out -
Channel 2 Out +Channel 2 Out -Channel 3 Out +Channel 3 Out -Channel 4 Out +Channel 4 Out -
3456789101112141520�
�
2928
31
30
3332
11
8
1615
1817
2019
26
12
27N.C.N.C.
N.C.N.C.N.C.N.C.N.C.N.C.
N.C.N.C.
N.C.
34
N.C.N.C.
N.C.N.C.N.C.N.C.
N.C.
2423
2574
3N.C.N.C.
N.C. N.C.N.C.N.C.
22
21 3536
N.C.N.C.
N.C.N.C.
IMPORTANT
98 Rockwell Automation Publication 1492-SG121E-EN-P - July 2016
Wiring Diagrams - Analog Inputs and Outputs
1771-OFE1(2) to 1756-OF8I
using these components (conversion module, cable and input module). Read and understand these considerations before installation.
Conversion Module Installation and Application Considerations This Bul. 1492 cable consists of 2 separate cables (cable “A” and cable “B”) wired to one 1756-OF8I. Each cable can be either 0.5M or 1.0M (005=0.5M,010=1.0M). Ensure that cable A and cable B are connected to the correct module in the conversion.
shield connections from the 1771 chassis and they can be connected to the grounding stud on the 1492-CM1771-LA003 module. The pre-wired cable used between the 1492-CM1771-LA003 module and the 1756-OF8I [1492-C005005E8V] provides a shield ground lug to ground the shield at the 1756 ControlLogix chassis, this must be connected. Do NOT connect this ground lug to the conversion module grounding stud.
�
� Refer to your 1771-OFE1 and 1756-OF8I Installation and User Manuals for additional information concerning comparisons of module wiring, features and
DIR 10002306858 (Version 00)
1771-WC Swing ArmFrom 1771-OFE1
Conversion Module1492-CM1771-LA003
1492-C005005E8V Cable “A”
1756-OF8I
1325242322211918171612
SH
Channel 1 Out +
Not Used
2OUT_0/VRTN_0
6
OUT_1/V1
RTN_15
OUT_2/V10
RTN_214
OUT_3/V9
RTN_313
� � � � � � � � �
� � � � � � � � � � � � � �
� � � � � � � � � � � � � �
� � � � � � � � � � � � � �
� � � � � � � � �
� � � � � � � � � � � � � �
� � � � � � � � �
� � � � � � �
VoltageLoad
+ -
A
34567B
012
Not Used
Channel 1 Out -
Channel 2 Out +Channel 2 Out -Channel 3 Out +Channel 3 Out -Channel 4 Out +Channel 4 Out -
3456789101112141520�
�
2724
31
28
3332
3
87
1211
1615
4
23N.C.
N.C.
N.C.
N.C.
N.C.
N.C.
N.C.
N.C.
N.C.
34
N.C.
N.C.
N.C.
N.C.
N.C.
N.C.
N.C.
20
19 3536
N.C.
N.C.
N.C.
N.C.
1771-WC Swing ArmFrom 1771-OFE1
Conversion Module1492-CM1771-LA003 Cable “B”
1325242322211918171612
SH
Channel 1 Out +
Not Used
18OUT_4/VRTN_4
22
OUT_5/V17
RTN_521
OUT_6/V26
RTN_630
OUT_7/V25
RTN_729
� � � � � � � � �
� � � � � � � � � � � � � �
� � � � � � � � � � � � � �
� � � � � � � � � � � � � �
� � � � � � � � �
� � � � � � � � � � � � � �
� � � � � � � � �
� � � � � � �
VoltageLoad
+ -
A
34567B
012
Not Used
Channel 1 Out -
Channel 2 Out +Channel 2 Out -Channel 3 Out +Channel 3 Out -Channel 4 Out +Channel 4 Out -
3456789101112141520�
�
IMPORTANT
Rockwell Automation Publication 1492-SG121E-EN-P - July 2016 99
Wiring Diagrams - Analog Inputs and Outputs
1771-OFE2 to 1756-OF6CI
41170-948 (1)
1756-OF6CI
CurrentLoad
13
1492-CM1771-LA003
2524232221191817 1612
SH
Channel 1 Out +
Not Used
1
1 OUT-0 R TN-0
5
OUT-1 2
R TN-1 6
OUT-2 7
R TN-2 11
OUT-3 8
R TN-3 12
R TN-4 19
OUT-4 15
N ot U sed 14
N ot U sed 13
1492-CONACAB005E
Red/White
Green/Black/White
Black/White/Red
White/Black/Red
Orange/Green
Red/Black/White
Orange/Red
Not Used20
Not Used16
Blue/Red
+ -
A
3 4 5 6 7 B
1771-WC Swing Arm
0 1 2
Not Used
Channel 1 Out -
Channel 2 Out + Channel 2 Out - Channel 3 Out + Channel 3 Out - Channel 4 Out + Channel 4 Out -
34 56789101112141520
3 The 1771-OFE2 analog output ranges were factory set, the output range for the 1756-OF6CI is software configured. Please ensure the correct output range is configured in the 1756-OF6CI.
1 SHIELD GROUNDING: In some installations, the field wiring shield was grounded on the 1771 chassis. If this was the case, the installer must remove these shield connections from the 1771 chassis and they can be connected to the grounding stud on the 1492-CM1771-LA003 module. The pre-wired cable used between the 1492-CM1771-LA003 module and the 1756-OF6CI [1492-CONACAB005E] provides a shield ground lug to ground the shield at the 1756 ControlLogix chassis, this must be connected. Do NOT connect this ground lug to the conversion module grounding stud.
CONVERSION MODULE INSTALLATION AND APPLICATION CONSIDERATIONS
2 IMPORTANT: The 1771-OFE2 module required the use of an external power supply to drive the analog device. The 1756-OF6CI analog output provides the drive power to the analog device. ENSURE the external power supply is REMOVED from the current loop before applying power to the 1756-OF6CI module or the analog output module may be damaged.
4 The 1756-OF6CI module can drive a load up to 550 ohms with the standard pre-configured cable [1492-CONACAB005E]. If greater than a 550 ohm drive current is required, the pre-wired cable can be modified at the 1756-OF6CI terminal block to drive up to a 1000 ohms. Refer to the 1756-OF6CI Installation Manual for modification details. 5 Refer to your 1771-OFE2 and 1756-OF6CI Installation and User Manuals for additional information concerning comparisons of module wiring, features and configuration details.
WARNING There are several key application considerations and system specifications (bottom of drawing) when using these components (conversion module, cable and output module). Read and understand these considerations before installation.
1
IMPORTANT
100 Rockwell Automation Publication 1492-SG121E-EN-P - July 2016
Wiring Diagrams - Analog Inputs and Outputs
1771-OFE2 to 1756-OF8I
using these components (conversion module, cable and input module). Read and understand these considerations before installation.
WARNING
Conversion Module Installation and Application Considerations� Cables are available in lengths of 0.5M or 1.0M (005=0.5M, 010=1.0M)
� shield connections from the 1771 chassis and they can be connected to the grounding stud on the 1492-CM1771-LA003 module. The pre-wired cable used between the 1492-CM1771-LA003 module and the 1756-OF8I [1492-CONACAB005E8C] provides a shield ground lug to ground the shield at the 1756 ControlLogix chassis, this must be connected. Do NOT connect this ground lug to the conversion module grounding stud.
�
� Refer to your 1771-OFE1 and 1756-OF8I Installation and User Manuals for additional information concerning comparisons of module wiring, features and
DIR 10002306853 (Version 00)
1771-WC Swing ArmFrom 1771-OFE2
Conversion Module1492-CM1771-LA003
Cable1492-CONACAB005E8C� 1756-OF8I
�
�
1325242322211918171612
SH
Channel 1 Out +
Not Used
4OUT_0/IRTN_0
6
OUT_1/I3
RTN_15
OUT_2/I12
RTN_214
OUT_3/I11
RTN_313
CurrentLoad
+ -
A
34567B
012
Not Used
Channel 1 Out -
Channel 2 Out +Channel 2 Out -Channel 3 Out +Channel 3 Out -Channel 4 Out +Channel 4 Out -
3456789101112141520�
�
2928
31
30
3332
9
8
1615
1817
2019
26
10
27N.C.N.C.
N.C.N.C.N.C.N.C.N.C.N.C.
N.C.N.C.
N.C.
34
N.C.N.C.
N.C.N.C.N.C.N.C.
N.C.
2423
2572
1N.C.N.C.
N.C. N.C.N.C.N.C.
22
21 3536
N.C.N.C.
N.C.N.C.
IMPORTANT
Rockwell Automation Publication 1492-SG121E-EN-P - July 2016 101
Wiring Diagrams - Analog Inputs and Outputs
1771-OFE2(2) to 1756-OF8I
using these components (conversion module, cable and input module). Read and understand these considerations before installation.
Conversion Module Installation and Application Considerations This Bul. 1492 cable consists of 2 separate cables (cable “A” and cable “B”) wired to one 1756-OF8I. Each cable can be either 0.5M or 1.0M (005=0.5M,010=1.0M). Ensure that cable A and cable B are connected to the correct module in the conversion.
shield connections from the 1771 chassis and they can be connected to the grounding stud on the 1492-CM1771-LA003 module. The pre-wired cable used between the 1492-CM1771-LA003 module and the 1756-OF8I [1492-C005005E8C] provides a shield ground lug to ground the shield at the 1756 ControlLogix chassis, this must be connected. Do NOT connect this ground lug to the conversion module grounding stud.
�
� Refer to your 1771-OFE2 and 1756-OF8I Installation and User Manuals for additional information concerning comparisons of module wiring, features and
DIR 10002306859 (Version 00)
1771-WC Swing ArmFrom 1771-OFE1
Conversion Module1492-CM1771-LA003
1492-C005005E8C Cable “A”
1756-OF8I
1325242322211918171612
SH
Channel 1 Out +
Not Used
4OUT_0/IRTN_0
6
OUT_1/I3
RTN_15
OUT_2/I12
RTN_214
OUT_3/I11
RTN_313
� � � � � � � � �
� � � � � � � � � � � � � �
� � � � � � � � � � � � � �
� � � � � � � � � � � � � �
� � � � � � � � �
� � � � � � � � � � � � � �
� � � � � � � � �
� � � � � � �
CurrentLoad
+ -
A
34567B
012
Not Used
Channel 1 Out -
Channel 2 Out +Channel 2 Out -Channel 3 Out +Channel 3 Out -Channel 4 Out +Channel 4 Out -
3456789101112141520�
�
2524
31
26
3332
1
87
1615
1615
2
23N.C.
N.C.
N.C.
N.C.
N.C.
N.C.
N.C.
N.C.
N.C.
34
N.C.
N.C.
N.C.
N.C.
N.C.
N.C.
N.C.
18
17 3536
N.C.
N.C.
N.C.
N.C.
1771-WC Swing ArmFrom 1771-OFE1
Conversion Module1492-CM1771-LA003 Cable “B”
1325242322211918171612
SH
Channel 1 Out +
Not Used
20OUT_4/IRTN_4
22
OUT_5/I19
RTN_521
OUT_6/I28
RTN_630
OUT_7/I27
RTN_729
� � � � � � � � �
� � � � � � � � � � � � � �
� � � � � � � � � � � � � �
� � � � � � � � � � � � � �
� � � � � � � � �
� � � � � � � � � � � � � �
� � � � � � � � �
� � � � � � �
CurrentLoad
+ -
A
34567B
012
Not Used
Channel 1 Out -
Channel 2 Out +Channel 2 Out -Channel 3 Out +Channel 3 Out -Channel 4 Out +Channel 4 Out -
3456789101112141520�
�
IMPORTANT
102 Rockwell Automation Publication 1492-SG121E-EN-P - July 2016
Wiring Diagrams - High Resolution Isolated AnalogStandard High Resolution I/O
1771-NOC to 1756-OF8I
[Reference Doc: DIR 10002306650]
B1B2B3B4B5A4A5B8B9A6A7B12B13A8A9B16B17A10A11
3
2
W2SH
W3
I8
I7
I6
I5
I4
I3
I1
I2
R8
R7
R6
R5
R4
R3
R2
R1CURRENT LOAD
A1A2A3B12B13A12A13B14B15A14A15B16B17A16A17B18B19
A18A19
CRW1
CL
O8
O7
O6
O5
O4
O3
O1
O2
S8
S7
S6
S5
S4
S3
S2
S1
15
418
721
1024
13
6
4
15
418
721
1024
13
3
14
12
11
OUT_0/I
OUT_1/I
OUT_2/I
OUT_3/I
RTN_0
RTN_2
1492-CONACAB020N88
22
20
19
30
28
27
OUT_4/I
OUT_5/I
OUT_6/I
OUT_7/I
RTN_4
RTN_6
Cable”A”
Cable”B”
2524
31
26
3332
1
87
109
1615
2
23N.C.
N.C.N.C.N.C.N.C.N.C.N.C.
N.C.N.C.
34
N.C.N.C.
N.C.N.C.N.C.N.C.
N.C.
18
17 3536
N.C.N.C.
N.C.N.C.
21 RTN_5
29 RTN_7
13 RTN_3
5 RTN_1
There are several key application considerations and system specifications (bottom of drawing) when using these components (conversion module, cable and input module). Read and understand these considerations before installation.
Interface Module Installation and Application Considerations Cables are available in lengths of 2.0M or 5.0M (020=2.0M, 050=5.0M)
Terminals starting with A are the lower row of terminals, B terminals are the upper row.
Follow your PLC Analog User Manual for proper shield grounding instructions.
Terminals w1, w2, w3, are spares used for field wire convenience. NOTE: This is only true for module RTP3 and RTP4. cable does not connect to these terminals.
Interface Module
1771-RTP3 or 1771-RTP4
IMPORTANT
Rockwell Automation Publication 1492-SG121E-EN-P - July 2016 103
Wiring Diagrams - High Resolution Isolated Analog
1771-NOC to 1756-OF8
41171-079 (00)
B1B2B3B4B5A4A5B8B9A6A7B12B13A8A9B16B17A10A11
RTP3 OR RTP4
3
2
4
W2SH
W3
I8
I7
I6
I5
I4
I3
I1
I2
R8
R7
R6
R5
R4
R3
R2
R1
1756-OF8
CURRENT LOAD
5
A1A2A3B12B13A12A13B14B15A14A15B16B17A16A17B18B19
A18A19
CRW1
CL
O8
O7
O6
O5
O4
O3
O1
O2
S8
S7
S6
S5
S4
S3
S2
S1
15
418
721
1024
13
5
3
1516
41819
72122
10242513
9
15
13
19
Black
White
Green
Orange
White/Black
White/Red
White/Orange
Gray
Black
White
Green
Orange
White/Black
White/Red
White/Orange
Gray
I-OUT-0
I-OUT-1
I-OUT-2
I-OUT-3
I-RTN
I-RTN
1492-CONACAB020N8
1 Cables are available in 2.0m, or 5.0m
2 Terminals starting with A are the lower row of terminals, B terminals are the upper row.
3 Follow your PLC Analog User Manual for propershield grounding instructions.
4 RTN terminals are internally connected on the 1756-OF8.
5 Terminals w1, w2, w3, are spares used f or field wire convenience. NOTE: this is only truefor modules RTP3 and RTP4. The Bul. 1492cable does not connect to these terminals.
CONVERSION MODULE INSTALLATION AND APPLICATION CONSIDERATIONS
6 The 1771 - NOC module provides channel to channel isolation, the 1756-OF8 does not. A conversion from 1771-NOC to an isolated 1756-OF8 is avalible.
5
3
9
15
13
19
I-OUT-0
I-OUT-1
I-OUT-2
I-OUT-3
I-RTN
I-RTN
1492-CONACAB020N8
6
Cable”A”
Cable”B”
There are several key application considerations and system specifications (bottom of drawing) when using these components (conversion module, cable and input module). Read and understand these considerations before installation.
IMPORTANT
104 Rockwell Automation Publication 1492-SG121E-EN-P - July 2016
Wiring Diagrams - High Resolution Isolated Analog
1771-NOC to 1756-OF6CI
There are several key application considerations and system specifications (bottom of drawing) when using these components (conversion module, cable and input module). Read and understand these considerations before installation.
1756-OF6CI
1756-OF6CI Cable “A”1492-CONACAB020N1
Cable “B”1492-CONACAB020N1
B1B2B3B4B5A4A5B8B9A6A7B12B13A8A9B16B17A10A11
Interface Module 1771-RTP3 or RTP4
W2SH
W3
I8
I7
I6
I5
I4
I3
I1
I2
R8
R7
R6
R5
R4
R3
R2
R1CURRENT LOAD
A1A2A3B12B13A12A13B14B15A14A15B16B17A16A17B18B19
A18A19
CRW1
CL
O8
O7
O6
O5
O4
O3
O1
O2
S8
S7
S6
S5
S4
S3
S2
S1
15
418
721
1024 5
1
2
6
11
7
8
12
Black
White
Green
Orange
White/Black
White/Red
White/Orange
Gray
Black
White
Green
Orange
White/Black
White/Red
White/Orange
Gray
OUT-0
OUT-1
OUT-2
OUT-3
RTN-0
RTN-1
RTN-2
RTN-3
N/A
N/A
N/A
13
5
1
2
6
11
7
8
12
N/A
N/A
N/A
+
-
OUT-0
OUT-1
OUT-2
OUT-3
RTN-0
RTN-1
RTN-2
RTN-315
418
721
1024
13
Conversion Module Installation and Application Considerations Cables are available in 2.0m, or 5.0m
Terminals starting with A are the lower row of terminals, B terminals are the upper row.
Follow your PLC Analog User Manual for proper shield grounding instructions.
RTN terminals are internally connected on the 1756-OF6CI.
Terminals w1, w2, w3, are spares used for field wire convenience. NOTE: This is only true for modules RTP3 and RTP4. The Bul. 1492 cable does not connect to these terminals. [Reference Doc: 41171-072 (Version 00)]
IMPORTANT
Rockwell Automation Publication 1492-SG121E-EN-P - July 2016 105
Wiring Diagrams - High Resolution Isolated Analog
1771-NIS to 1756-IF8I
B1B2B3B4B5A4A5B8B9A6A7B12B13A8A9B16B17A10A11
3
2
W2SH
W3
I8
I7
I6
I5
I4
I3
I1
I2
R8
R7
R6
R5
R4
R3
R2
R1
A1A2A3B12B13A12A13B14B15A14A15B16B17A16A17B18B19
A18A19
CRW1
CL
O8
O7
O6
O5
O4
O3
O1
O2
S8
S7
S6
S5
S4
S3
S2
S1
1516
1819
2122
2425
N/A
N/A
N/A
4 N/A
N/A
N/A
1492-CONACAB020N38
CURRENT LOAD
-
CURRENT LOAD
-
+
24VDCSUPPLY
24VDCSUPPLY
+
1516
1819
2122
2425
29 RTN_7
2625
32
31
3433
2
1
98
1510
1716
23
7
24N.C.N.C.
N.C.N.C.N.C.N.C.N.C.N.C.
N.C.N.C.
N.C.
35
N.C.N.C.
N.C.N.C.N.C.N.C.
N.C.
27 IN_7/I/SRC
CABLE “B”
CABLE “A”
30 RTN_628 IN_6/I/SRC
21 RTN_519 IN_5/I/SRC
22 RTN_420 IN_4/I/SRC
13 RTN_311 IN_3/I/SRC
14 RTN_212 IN_2/I/SRC
5 RTN_13 IN_1/I/SRC
6 RTN_04 IN_0/I/SRC
18 N.C. 36 N.C.
Interface Module Installation and Application Considerations Cables are available in lengths of 2.0M or 5.0M (020=2.0M, 050=5.0M)
Terminals starting with A are the lower row of terminals, B terminals are the upper row.
Follow your PLC Analog User Manual for proper shield grounding instructions.
for module RTP4. The Bul. 1492 .slanimret eseht ot tcennoc ton seod elbac
DIR 10002306457 (Version 00)
using these components (conversion module, cable and input module). Read and understand these considerations before installation.
WARNING
Interface Module
IMPORTANT
106 Rockwell Automation Publication 1492-SG121E-EN-P - July 2016
Wiring Diagrams - High Resolution Isolated Analog
1771-NIS to 1756-IF6CIS
41171-073 (01)
B1B2B3B4B5A4A5B8B9A6A7B12B13A8A9B16B17A10A11
1771-RTP4
3
2
4
W2SH
W3
I7
I6
I5
I4
I3
I2
I0
I1
R7
R6
R5
R4
R3
R2
R1
R0
1756-IF6CIS
CURRENT LOAD
5
A1A2A3B12B13A12A13B14B15A14A15B16B17A16A17B18B19
A18A19
CRW1
CL
O7
O6
O5
O4
O3
O2
O0
O1
S7
S6
S5
S4
S3
S2
S1
S0
1 Cables are available in 2.0m, or 5.0m
2 Terminals starting with A are the lower row of terminals, B terminals are the upper row.
3 Follow your PLC Analog User Manual for propershield grounding instructions.
4 RTN terminals are internally connected on the 1756-IF6CIS.
5 Terminals w1, w2, w3, are spares used f or field wire convenience. NOTE: this is only truefor modules RTP4. The Bul. 1492cable does not connect to these terminals.
CONVERSION MODULE INSTALLATION AND APPLICATION CONSIDERATIONS
N/A
N/A
N/A
N/A
N/A
N/A
-
4
1492-CONACAB020N2
1492-CONACAB020N2
CURRENT LOAD
+
-24VDCSUPPLY
24VDCSUPPLY
+
Cable “B”
Cable “A”
1516
1819
2122
2425
13
10
7
4
53
46
119
10
12
I-RTN-4
I-RTN-5
I-RTN-6
I-RTN-7
I-IN-4
I-IN-6
I-IN-7
I-IN-5
1
2
7
8
V-OUT-4
V-OUT-6
V-OUT-7
V-OUT-5
CURRENT LOAD
+
-
1516
1819
2122
2425
13
10
7
4
53
46
119
10
12
I-RTN-0
I-RTN-1
I-RTN-2
I-RTN-3
I-IN-0
I-IN-2
I-IN-3
I-IN-1
1
2
7
8
V-OUT-0
V-OUT-2
V-OUT-3
V-OUT-1
1756-IF6CIS
LOOP POWER SUPPLIED INTERNALLY
USER SUPPLIEDLOOP POWER SUPPLIED INTERNALLY
Black
Brown
Green
Yellow
White/Black
White/Red
Violet
Red
White/Yellow
White/Green
White/Brown
White/Violet
Black
Brown
Green
Yellow
White/Black
White/Red
Violet
Red
White/Yellow
White/Green
White/Violet
White/Brown
using these components (conversion module, cable and input module). Read and understand these considerations before installation.
IMPORTANT
Rockwell Automation Publication 1492-SG121E-EN-P - July 2016 107
Wiring Diagrams - High Resolution Isolated Analog
1771-NIV to 1756-IF8I — Current
DIR 10002306458 (Version 00)
B1B2B3B4B5A4A5B8B9A6A7B12B13A8A9B16B17A10A11
3
2
W2SH
W3
I8
I7
I6
I5
I4
I3
I1
I2
R8
R7
R6
R5
R4
R3
R2
R1
� � � � � � � � �
A1A2A3B12B13A12A13B14B15A14A15B16B17A16A17B18B19
A18A19
CRW1
CL
O8
O7
O6
O5
O4
O3
O1
O2
S8
S7
S6
S5
S4
S3
S2
S1
1516
1819
2122
2425 � �
� � � � �
� � � � �
� � � � � �
� � � � � � � �
� � � � � � � � �
� � � � � � � � � � � �
� � � �
N/A
N/A
N/A
4N/A
N/A
N/A
� � � � � � �
� � � � �
� � � � � �
� � � � � � � �
� � � � � � � � �
� � � � � � � � � � � �
� � � �
1492-CONACAB020N38
CURRENT LOAD
-
CURRENT LOAD
+
-
24VDCSUPPLY
24VDCSUPPLY
+
1516
1819
2122
2425
29 RTN_7
2625
32
31
3433
2
1
98
1510
1716
23
7
24N.C.
N.C.
N.C.
N.C.
N.C.
N.C.
N.C.
N.C.
N.C.
N.C.
N.C.
35
N.C.
N.C.
N.C.
N.C.
N.C.
N.C.
N.C.
27 IN_7/I/SRC
CABLE “B”
CABLE “A”
30 RTN_628 IN_6/I/SRC
21 RTN_519 IN_5/I/SRC
22 RTN_420 IN_4/I/SRC
13 RTN_311 IN_3/I/SRC
14 RTN_212 IN_2/I/SRC
5 RTN_13 IN_1/I/SRC
6 RTN_04 IN_0/I/SRC
18 N.C. 36 N.C.
There are several key application considerations and system specifications (bottom of drawing) when using these components (conversion module, cable and input module). Read and understand these considerations before installation.
Interface Module Installation and Application Considerations Cables are available in lengths of 2.0M or 5.0M (020=2.0M, 050=5.0M)
Terminals starting with A are the lower row of terminals, B terminals are the upper row.
� Follow your PLC Analog User Manual for proper shield grounding instructions.
� Terminals w1, w2, w3, are spares used for field wire convenience. NOTE: This is only true for module RTP3 and RTP4. The Bul. 1492 cable does not connect to these terminals.
Interface Module 1771-RTP3
IMPORTANT
108 Rockwell Automation Publication 1492-SG121E-EN-P - July 2016
Wiring Diagrams - High Resolution Isolated Analog
1771-NIV to 1756-IF6I — Current
41171-074 (00)
B1B2B3B4B5A4A5B8B9A6A7B12B13A8A9B16B17A10A11
1771-RTP4
3
2
4
W2SH
W3
I8
I7
I6
I5
I4
I3
I1
I2
R8
R7
R6
R5
R4
R3
R2
R1
1756-IF6I5
A1A2A3B12B13A12A13B14B15A14A15B16B17A16A17B18B19
A18A19
CRW1
CL
O8
O7
O6
O5
O4
O3
O1
O2
S8
S7
S6
S5
S4
S3
S2
S1
1516
1819
2122
2425 3
5
46
119
10
12
BlackWhite
Green
Orange
White/Black
White/Red
White/Orange
Gray
IN-0/I
IN-1/I
IN-2/I
IN-3/I
RTN-0
RTN-2
RTN-3
CABLE “B”
1 Cables are available in 2.0m, or 5.0m
2 Terminals starting with A are the lower row of terminals, B terminals are the upper row.
3 Follow your PLC Analog User Manual for propershield grounding instructions.
4 RTN terminals are internally connected on the 1756-IF6I.
5 Terminals w1, w2, w3, are spares used f or field wire convenience. NOTE: this is only truefor modules RTP3. The Bul. 1492cable does not connect to these terminals.
CONVERSION MODULE INSTALLATION AND APPLICATION CONSIDERATIONS
1756-IF6IN/A
N/A
N/A
4
N/A
N/A
N/A
RTN-1
1 IN-0/V
2 IN-1/V
7 IN-2/V
8 IN-3/V
35
46
119
10
12
BlackWhite
Green
Orange
White/Black
White/Red
White/Orange
Gray
1
2
7
8
1492-CONACAB010N3
CABLE “A”1492-CONACAB010N3
CURRENT LOAD
-
CURRENT LOAD
+
-24VDCSUPPLY
24VDCSUPPLY
+
1516
1819
2122
2425 IN-0/I
IN-1/I
IN-2/I
IN-3/I
RTN-0
RTN-2
RTN-3
RTN-1
IN-0/V
IN-1/V
IN-2/V
IN-3/V
using these components (conversion module, cable and input module). Read and understand these considerations before installation.
IMPORTANT
Rockwell Automation Publication 1492-SG121E-EN-P - July 2016 109
Wiring Diagrams - High Resolution Isolated Analog
1771-NIV to 1756-IF8I — Voltage
DIR 10002306478 (Version 00)
B1B2B3B4B5A4A5B8B9A6A7B12B13A8A9B16B17A10A11
3
2
W2SH
W3
I8
I7
I6
I5
I4
I3
I1
I2
R8
R7
R6
R5
R4
R3
R2
R1
� � � � � � � � �
A1A2A3B12B13A12A13B14B15A14A15B16B17A16A17B18B19
A18A19
CRW1
CL
O8
O7
O6
O5
O4
O3
O1
O2
S8
S7
S6
S5
S4
S3
S2
S1
1516
1819
2122
2425 � � �
� � � � �
� � �
� �
� � � � � � � � �
� � � � � �
� � � � �
� � � � �
N/A
N/A
N/A
4 N/A
N/A
N/A
� � �� � � � �
� � �
� �
� � � � � � � � �
� � � � � �
� � � � �
� � � � �
1492-CONACAB020N78
VOLTAGE LOAD
VOLTAGE LOAD
+
-
1516
1819
2122
2425
29 RTN_7
2827
32
31
3433
4
3
118
1512
1916
23
7
24N.C.
N.C.
N.C.
N.C.
N.C.
N.C.
N.C.
N.C.
N.C.
N.C.
N.C.
35
N.C.
N.C.
N.C.
N.C.
N.C.
N.C.
N.C.
25 IN_7/V
CABLE “B”
CABLE “A”
30 RTN_626 IN_6/V
21 RTN_517 IN_5/V
22 RTN_418 IN_4/V
13 RTN_39 IN_3/V
14 RTN_210 IN_2/V
5 RTN_11 IN_1/V
6 RTN_02 IN_0/V
20 N.C. 36 N.C.
Interface Module Installation and Application Considerations Cables are available in lengths of 2.0M or 5.0M (020=2.0M, 050=5.0M) Terminals starting with A are the lower row of terminals, B terminals are the upper row.
� Follow your PLC Analog User Manual for proper shield grounding instructions.
� for module RTP4. The Bul. 1492 cable does not connect to these terminals.
There are several key application considerations and system specifications (bottom of drawing) when using these components (conversion module, cable and input module). Read and understand these considerations before installation.
Interface Module1771-RTP4
IMPORTANT
110 Rockwell Automation Publication 1492-SG121E-EN-P - July 2016
Wiring Diagrams - High Resolution Isolated Analog
1771-NIV to 1756-IF6I — Voltage
There are several key application considerations and system specifications (bottom of drawing) when using these components (conversion module, cable and input module). Read and understand these considerations before installation.
Cable “A”1492-CONACAB020N7
Cable “B”1492-CONACAB020N7
Interface Module 1771-RTP4 or 1771-RTP4
1756-IF6I
1756-IF6I
B1B2B3B4B5A4A5B8B9A6A7B12B13A8A9B16B17A10A11
W2SH
W3
I8
I7
I6
I5
I4
I3
I1
I2
R8
R7
R6
R5
R4
R3
R2
R1VOLTAGE LOAD
A1A2A3B12B13A12A13B14B15A14A15B16B17A16A17B18B19
A18A19
CRW1
CL
O8
O7
O6
O5
O4
O3
O1
O2
S8
S7
S6
S5
S4
S3
S2
S1
1516
1819
2122
2425 1
5
26
117
8
12
VioletBlack
Green
Red
White/Black
White/Red
Yellow
Brown
IN-0V
IN-1V
IN-2V
IN-3V
RTN-0
RTN-2
RTN-3
N/A
N/A
N/A
N/A
N/A
N/A
+
-
RTN-1
15
26
117
8
12
VOLTAGE LOAD
+
-
IN-0V
IN-1V
IN-2V
IN-3V
RTN-0
RTN-2
RTN-3
RTN-1
1516
1918
2221
2425 Violet
Black
Green
Red
White/Black
White/Red
Yellow
Brown
Conversion Module Installation and Application Considerations Cables are available in 2.0m, or 5.0m
Terminals starting with A are the lower row of terminals, B terminals are the upper row.
Follow your PLC Analog User Manual for proper shield grounding instructions.
RTN terminals are internally connected on the 1756-IF6I.
Terminals w1, w2, w3, are spares used for field wire convenience. NOTE: This is only true for module RTP4. The Bul. 1492 cable does not connect to these terminals. 41171-080 Ver (00)
IMPORTANT
Rockwell Automation Publication 1492-SG121E-EN-P - July 2016 111
Wiring Diagrams - High Resolution Isolated Analog
1771-NIV to 1756-IF6I — Current and Voltage
There are several key application considerations and system specifications (bottom of drawing) when using these components (conversion module, cable and input module). Read and understand these considerations before installation.
Cable “B”1492-CONACAB020N7
Interface Module 1771-RTP4
1756-IF6I
B1B2B3B4B5A4A5B8B9A6A7B12B13A8A9B16B17A10A11
W2SH
W3
I8
I7
I6
I5
I4
I3
I1
I2
R8
R7
R6
R5
R4
R3
R2
R1CURRENT LOAD
A1A2A3B12B13A12A13B14B15A14A15B16B17A16A17B18B19
A18A19
CRW1
CL
O8
O7
O6
O5
O4
O3
O1
O2
S8
S7
S6
S5
S4
S3
S2
S1
1516
1819
2122
2425 Violet
Black
Green
Red
White/Black
White/Red
Yellow
Brown
N/A
N/A
N/A
N/A
N/A
N/A
+
-
15
26
117
8
12
VOLTAGE LOAD
+
-
IN-0V
IN-1V
IN-2V
IN-3V
RTN-0
RTN-2
RTN-3
RTN-1
1516
1918
2221
2425 Violet
Black
Green
Red
White/Black
White/Red
Yellow
Brown
Conversion Module Installation and Application Considerations Cables are available in 2.0m, or 5.0m
Terminals starting with A are the lower row of terminals, B terminals are the upper row.
Follow your PLC Analog User Manual for proper shield grounding instructions.
RTN terminals are internally connected on the 1756-IF6I.
Terminals w1, w2, w3, are spares used for field wire convenience. NOTE: This is only true for module RTP4. The Bul. 1492 cable does not connect to these terminals. 41171-039 Ver (00)
3
4
35
46
119
10
12
BlackWhite
Green
Orange
White/Black
White/Red
White/Orange
Gray
IN-0/I
IN-1/I
IN-2/I
IN-3/I
RTN-0
RTN-2
RTN-3
1756-IF6I
RTN-1
1 IN-0/V
2 IN-1/V
7 IN-2/V
8 IN-3/V
CABLE “A”1492-CONACAB010N3
(Voltage)
(Current)
IMPORTANT
112 Rockwell Automation Publication 1492-SG121E-EN-P - July 2016
Wiring Diagrams - High Resolution Isolated Analog
1771-NIV to 1756-IF6I — Voltage and Current
41171-038 (00)
B1B2B3B4B5A4A5B8B9A6A7B12B13A8A9B16B17A10A11
1771-RTP4
3
2
W2SH
W3
I8
I7
I6
I5
I4
I3
I1
I2
R8
R7
R6
R5
R4
R3
R2
R1
5
A1A2A3B12B13A12A13B14B15A14A15B16B17A16A17B18B19
A18A19
CRW1
CL
O8
O7
O6
O5
O4
O3
O1
O2
S8
S7
S6
S5
S4
S3
S2
S1
1516
1819
2122
2425 Black
White
Green
Orange
White/Black
White/Red
White/Orange
Gray
1 Cables are available in 2.0m, or 5.0m
2 Terminals starting with A are the lower row of terminals, B terminals are the upper row.
3 Follow your PLC Analog User Manual for propershield grounding instructions.
4 RTN terminals are internally connected on the 1756-IF6I.
5 Terminals w1, w2, w3, are spares used f or field wire convenience. NOTE: this is only truefor modules RTP3. The Bul. 1492cable does not connect to these terminals.
CONVERSION MODULE INSTALLATION AND APPLICATION CONSIDERATIONS
N/A
N/A
N/A
N/A
N/A
N/A
BlackWhite
Green
Orange
White/Black
White/Red
White/Orange
Gray
CABLE “A”1492-CONACAB010N7
Voltage LOAD
-
CURRENT LOAD
+
-
+
1516
1819
2122
2425
There are several key application considerations and system specifications (bottom of drawing) when using these components (conversion module, cable and input module). Read and understand these considerations before installation.
(Voltage)
CABLE “B”1492-CONACAB010N3
(Current)4
35
46
119
10
12
IN-0/I
IN-1/I
IN-2/I
IN-3/I
RTN-0
RTN-2
RTN-3
1756-IF6I
RTN-1
1 IN-0/V
2 IN-1/V
7 IN-2/V
8 IN-3/V
1756-IF6I
15
26
117
8
12
IN-0V
IN-1V
IN-2V
IN-3V
RTN-0
RTN-2
RTN-3
RTN-1
IMPORTANT
Rockwell Automation Publication 1492-SG121E-EN-P - July 2016 113
Wiring Diagrams - High Resolution Isolated Analog
1771-NR to 1756-IRT8I
B1B2B3B4B5A4A5B8B9A6A7B12B13A8A9B16B17A10A11
3
2
W2SH
W3
I8
I7
I6
I5
I4
I3
I1
I2
R8
R7
R6
R5
R4
R3
R2
R1
� � � � � � � � �
A1A2A3B12B13A12A13B14B15A14A15B16B17A16A17B18B19
A18A19
CRW1
CL
O8
O7
O6
O5
O4
O3
O1
O2
S8
S7
S6
S5
S4
S3
S2
S1
2425 4
3
� � �
� � � � �
� � � � �� � � � � �
� � � � � � � � �
� � � � � � � � �
� � � �
1492-CONACAB020N48
N/A
N/A
N/A
13
N/A
N/A
N/A
RTD TRANSMITTER
6
� � � � � � � � � � � �
� � � � � �
� � � �
� � � � �
� � �
22
10
721
41819
1516
8
7
10
12
11
14
16
15
18
242513
22
10
721
41819
1516
RTD TRANSMITTER
2019
IN_4(-)/B
IN_4(+)/A
22 IN_4/RTD C
24
23
26
28
27
30
32
31
34
IN_5(-)/B
IN_5(+)/A
IN_5/RTD C
IN_6(-)/B
IN_6(+)/A
IN_6/RTD C
IN_7(-)/B
IN_7(+)/A
IN_7/RTD C
Cable “A”
Cable “B”
3533
36
2
1
139
2117
25
5
29N.C.
N.C.
N.C.
N.C.
N.C.
N.C.
N.C.
N.C.
N.C. N.C.
N.C.
N.C.
� � �
� � � � �
� � � � �� � � � � �
� � � � � � � � �
� � � � � � � � �
� � � �
� � � � � � � � � � � �
� � � � � �
� � � �
� � � � �
� � �
IN_0(-)/B
IN_0(+)/A
IN_0/RTD C
IN_1(-)/B
IN_1(+)/A
IN_1/RTD C
IN_2(-)/B
IN_2(+)/A
IN_2/RTD C
IN_3(-)/B
IN_3(+)/A
IN_3/RTD C
There are several key application considerations and system specifications (bottom of drawing) when using these components (conversion module, cable and input module). Read and understand these considerations before installation.
DIR 10002306848 (Version 00)
Interface Module Installation and Application Considerations Cables are available in lengths of 2.0M or 5.0M (020=2.0M, 050=5.0M)
Terminals starting with A are the lower row of terminals, B terminals are the upper row.
� Follow your PLC Analog User Manual for proper shield grounding instructions.
� Terminals w1, w2, w3, are spares used for field wire convenience. NOTE: This is only true for module RTP3 and RTP4. The Bul. 1492 cable does not connect to these terminals.
4
Interface Module1771-RTP4
IMPORTANT
114 Rockwell Automation Publication 1492-SG121E-EN-P - July 2016
Wiring Diagrams - High Resolution Isolated Analog
1771-NR to 1756-IR6I
41171-075 (00)
B1B2B3B4B5A4A5B8B9A6A7B12B13A8A9B16B17A10A11
1771-RTP4
3
2
4
W2SH
W3
I8
I7
I6
I5
I4
I3
I1
I2
R8
R7
R6
R5
R4
R3
R2
R1
1756-IR6I5
A1A2A3B12B13A12A13B14B15A14A15B16B17A16A17B18B19
A18A19
CRW1
CL
O8
O7
O6
O5
O4
O3
O1
O2
S8
S7
S6
S5
S4
S3
S2
S1
2425 3
1
Black
White
GreenOrange
White/Black
White/Red
Gray
IN-0/B
IN-0/A
1492-CONACAB020N4
1 Cables are available in 2.0m, or 5.0m
2 Terminals starting with A are the lower row of terminals, B terminals are the upper row.
3 Follow your PLC Analog User Manual for propershield grounding instructions.
4 RTN terminals are internally connected on the 1756-IR6I.
5 Terminals w1, w2, w3, are spares used f or field wire convenience. NOTE: this is only truefor modules RTP4. The Bul. 1492cable does not connect to these terminals.
CONVERSION MODULE INSTALLATION AND APPLICATION CONSIDERATIONS
1756-IR6IN/A
N/A
N/A
13
N/A
N/A
N/A
RTD TRANSMITTER
5 RTN-0
White/Orange
Violet
Brown
Yellow
Red
22
10
721
41819
1516
4
2
6
9
7
11
10
8
12
IN-1/B
IN-1/A
RTN-1
IN-2/B
IN-2/A
RTN-2
IN-3/B
IN-3/A
RTN-3
4
242513
22
10
721
41819
1516
RTD TRANSMITTER
1492-CONACAB020N4
31
IN-0/B
IN-0/A
5 RTN-0
4
2
6
9
7
11
10
8
12
IN-1/B
IN-1/A
RTN-1
IN-2/B
IN-2/A
RTN-2
IN-3/B
IN-3/A
RTN-3
Cable “A”
Cable “B”
Black
White
GreenOrange
White/Black
White/Red
Gray
White/Orange
Violet
Brown
Yellow
Red
There are several key application considerations and system specifications (bottomusing these components (conversion module, cable and input module). Read andconsiderations before installation.
IMPORTANT
Rockwell Automation Publication 1492-SG121E-EN-P - July 2016 115
Wiring Diagrams - High Resolution Isolated Analog
1771-NT1 or -NT2 to 1756-IRT8I
DIR 10002306849 (Version 00)
B1A1B2B3A2A3B4B5A4A5
B6B7A6A7B8B9A9A8
3
2W1SH
I4
I3
I2
I1
R4
R3
R2
R1
1756-IRT8I4
O4
O3
O2
O1
S4
S3
S2
S1
1492-CONACAB020N68
1516
1918
2524
2122
+
-
Black
Red
Green
Brown
White/Black
White/Red
Yellow
Violet
THERMOCOUPLE
1920
2423
2728
3132
IN_4(-)/B
IN_5(-)/B
IN_6(-)/B
IN_7(-)/B
IN_4(+)/A
IN_6(+)/A
IN_7(+)/A
IN_5(+)/A
CJC1
CJC1Thermocouple
35
36
Cable “B”
B1A1B2B3A2A3B4B5A4A5
B6B7A6A7B8B9A9A8
2W1SH
I4
I3
I2
I1
R4
R3
R2
R1
4
O4
O3
O2
O1
S4
S3
S2
S1
1516
1918
2524
2122
+
-
Black
Red
Green
Brown
White/Black
White/Red
Yellow
Violet
THERMOCOUPLE
34
87
1112
1516
Thermocouple1
2
Cable “A”
3
1
White/Violet
White/Grey
White/Violet
White/Grey
2522
26
6
5
1310
1714
18
9
21N.C.N.C.
N.C.N.C.N.C.N.C.
N.C.N.C.
N.C. N.C.N.C.N.C.
2930
N.C.N.C.
14
1
IN_0(-)/B
IN_1(-)/B
IN_2(-)/B
IN_3(-)/B
IN_0(+)/A
IN_2(+)/A
IN_3(+)/A
IN_1(+)/A
CJC0
CJC0
14
1
3334
N.C.N.C.
There are several key application considerations and system specifications (bottom of drawing) when using these components (conversion module, cable and input module). Read and understand these considerations before installation.
Interface Module Installation and Application Considerations Cables are available in lengths of 2.0M or 5.0M (020=2.0M, 050=5.0M)
Terminals starting with A are the lower row of terminals, B terminals are the upper row.
� Follow your PLC Analog User Manual for proper shield grounding instructions.
� Terminals w1, w2, w3, are spares used for field wire convenience. NOTE: This is only true for module RTP3 and RTP4. The Bul. 1492 cable does not connect to these terminals.
This conversion solution requires replacement of the exisiting (1) 1771-RTP1 interface module with (2) 1771-RT41 interface modules. Each 1771-RTP1 and RT41 module has there own cold junction compensation thermocouple attached to the interface module.
1771-RT41
Interface Module
1771-RT41Interface Module
IMPORTANT
116 Rockwell Automation Publication 1492-SG121E-EN-P - July 2016
Wiring Diagrams - High Resolution Isolated Analog
1771-NT1 to 1756-IT6I
41171-076 (01)
B1A1B2B3A2A3B4B5A4A5
B6B7A6A7B8B9A9A8
1771-RT41
3
2W1SH
I4
I3
I2
I1
R4
R3
R2
R1
1756-IT6I4
O4
O3
O2
O1
S4
S3
S2
S1
1492-CONACAB020N5
CONVERSION MODULE INSTALLATION AND APPLICATION CONSIDERATIONS
1516
1918
2524
2122
+
-
Black
Red
Green
Brown
White/Black
White/Red
Yellow
Violet
THERMOCOUPLE
15
62
711
812
RTN-0
RTN-1
RTN-2
RTN-3
IN-0
IN-2
IN-3
IN-1
Cables are available in 2.0M or 5.0M.Terminals starting with A are the lower row of
terminals, B terminals are the upper row.Follow your PLC Analog User Manual for proper
shield grounding instructions.Terminals W1, W2 and W3 are spares used for field wire
convenience. NOTE. This is only true for modules RT41 . The Bul. 1492 cable does not connect to these terminals.
CJC+
CJC-Thermocouple
10
14
Cable “B”
B1A1B2B3A2A3B4B5A4A5
B6B7A6A7B8B9A9A8
1771-RT41
2W1SH
I4
I3
I2
I1
R4
R3
R2
R1
1756-IT6I4
O4
O3
O2
O1
S4
S3
S2
S1
1492-CONACAB020N5
1516
1918
2524
2122
+
-
Black
Red
Green
Brown
White/Black
White/Red
Yellow
Violet
THERMOCOUPLE
15
62
711
812
RTN-0
RTN-1
RTN-2
RTN-3
IN-0
IN-2
IN-3
IN-1
CJC+
CJC-Thermocouple
10
14
Cable “A”
3
1
1
White/Violet
White/Grey
White/Violet
White/Grey
There are several key application considerations and system specifications (bottomusing these components (conversion module, cable and input module). Read andconsiderations before installation.
IMPORTANT
Rockwell Automation Publication 1492-SG121E-EN-P - July 2016 117
Wiring Diagrams - High Resolution Isolated Analog
1771-NOV to 1756-OF8I
DIR 10002306686 (Version 00)
B1B2B3B4B5A4A5B8B9A6A7B12B13A8A9B16B17A10A11
3
2
W2SH
W3
I8
I7
I6
I5
I4
I3
I1
I2
R8
R7
R6
R5
R4
R3
R2
R1
� � � � � � � �
VOLTAGE LOAD
A1A2A3B12B13A12A13B14B15A14A15B16B17A16A17B18B19
A18A19
CRW1
CL
O8
O7
O6
O5
O4
O3
O1
O2
S8
S7
S6
S5
S4
S3
S2
S1
15
418
721
1024
13
6
2
15
418
721
1024
13
1
14
10
9
� � �
� � � � �
� � � � �� � � � � �
� � � � � � � � �
� � � � � � � � �
� � � � � � � � � � � �
� � � �
� � �
� � � � �
� � � � �� � � � � �
� � � � � � � � �
� � � � � � � � �
� � � � � � � � � � � �
� � � �
OUT_0/V
OUT_1/V
OUT_2/V
OUT_3/V
RTN_0
RTN_2
1492-CONACAB020N18
22
18
17
30
26
25
OUT_4/V
OUT_5/V
OUT_6/V
OUT_7/V
RTN_4
RTN_6
Cable”A”
Cable”B”
2524
31
26
3332
1
87
109
1615
2
23N.C.
N.C.N.C.N.C.N.C.N.C.N.C.
N.C.N.C.
34
N.C.N.C.
N.C.N.C.N.C.N.C.
N.C.
18
17 3536
N.C.N.C.
N.C.N.C.
21 RTN_5
29 RTN_7
13 RTN_3
5 RTN_1
-
+
Interface Module Installation and Application Considerations Cables are available in lengths of 2.0M or 5.0M (020=2.0M, 050=5.0M)
Terminals starting with A are the lower row of terminals, B terminals are the upper row.
� Follow your PLC Analog User Manual for proper shield grounding instructions.
� Terminals w1, w2, w3, are spares used for field wire convenience. NOTE: This is only true for module RTP3 and RTP4. The Bul. 1492 cable does not connect to these terminals.
There are several key application considerations and system specifications (bottom of drawing) when using these components (conversion module, cable and input module). Read and understand these considerations before installation.
�
Interface Module1771-RTP3 or 1771-RTP4
IMPORTANT
118 Rockwell Automation Publication 1492-SG121E-EN-P - July 2016
Wiring Diagrams - High Resolution Isolated Analog
1771-NOV to 1756-OF6VI
There are several key application considerations and system specifications (bottom of drawing) when using these components (conversion module, cable and input module). Read and understand these considerations before installation.
1756-OF6VI
1756-OF6VI Cable “A”1492-CONACAB020N1
Cable “B”1492-CONACAB020N1
B1B2B3B4B5A4A5B8B9A6A7B12B13A8A9B16B17A10A11
Interface Module 1771-RTP3 or RTP4
W2SH
W3
I8
I7
I6
I5
I4
I3
I1
I2
R8
R7
R6
R5
R4
R3
R2
R1VOLTAGE LOAD
A1A2A3B12B13A12A13B14B15A14A15B16B17A16A17B18B19
A18A19
CRW1
CL
O8
O7
O6
O5
O4
O3
O1
O2
S8
S7
S6
S5
S4
S3
S2
S1
15
418
721
1024 5
1
2
6
11
7
8
12
Black
White
Green
Orange
White/Black
White/Red
White/Orange
Gray
Black
White
Green
Orange
White/Black
White/Red
White/Orange
Gray
OUT-0
OUT-1
OUT-2
OUT-3
RTN-0
RTN-1
RTN-2
RTN-3
N/A
N/A
N/A
13
5
1
2
6
11
7
8
12
N/A
N/A
N/A
+
-
OUT-0
OUT-1
OUT-2
OUT-3
RTN-0
RTN-1
RTN-2
RTN-315
418
721
1024
13
Conversion Module Installation and Application Considerations Cables are available in 2.0m, or 5.0m
Terminals starting with A are the lower row of terminals, B terminals are the upper row.
Follow your PLC Analog User Manual for proper shield grounding instructions.
RTN terminals are internally connected on the 1756-OF6VI.
Terminals w1, w2, w3, are spares used for field wire convenience. NOTE: This is only true for modules RTP3 and RTP4. The Bul. 1492 cable does not connect to these terminals. 41171-081 Ver(00)
IMPORTANT
Rockwell Automation Publication 1492-SG121E-EN-P - July 2016 119
Wiring Diagrams - High Resolution Isolated Analog
1771-NIV1 to 1756-IF8I
DIR 10002306486 (Version 00)
B1B2B3B4B5A4A5B8B9A6A7B12B13A8A9B16B17A10A11
3
2
W2SH
W3
I8
I7
I6
I5
I4
I3
I1
I2
R8
R7
R6
R5
R4
R3
R2
R1
� � � � � � � � �
A1A2A3B12B13A12A13B14B15A14A15B16B17A16A17B18B19
A18A19
CRW1
CL
O8
O7
O6
O5
O4
O3
O1
O2
S8
S7
S6
S5
S4
S3
S2
S1
1516
1819
2122
2425 � � �
� � � � �
� � �
� �
� � � � � � � � �
� � � � � �
� � � � �
� � � � �
N/A
N/A
N/A
4 N/A
N/A
N/A
� � �� � � � �
� � �
� �
� � � � � � � � �
� � � � � �
� � � � �
� � � � �
1492-CONACAB020N78
VOLTAGE LOAD
VOLTAGE LOAD
-
+
1516
1819
2122
2425
29 RTN_7
2827
32
31
3433
4
3
118
1512
1916
23
7
24N.C.N.C.
N.C.N.C.N.C.N.C.N.C.N.C.
N.C.N.C.
N.C.
35
N.C.N.C.
N.C.N.C.N.C.N.C.
N.C.
25 IN_7/V
CABLE “B”
CABLE “A”
30 RTN_626 IN_6/V
21 RTN_517 IN_5/V
22 RTN_418 IN_4/V
13 RTN_39 IN_3/V
14 RTN_210 IN_2/V
5 RTN_11 IN_1/V
6 RTN_02 IN_0/V
20 N.C. 36 N.C.
-
+
There are several key application considerations and system specifications (bottom of drawing) when using these components (conversion module, cable and input module). Read and understand these considerations before installation.
Interface Module Installation and Application Considerations Cables are available in lengths of 2.0M or 5.0M (020=2.0M, 050=5.0M)
Terminals starting with A are the lower row of terminals, B terminals are the upper row.
� Follow your PLC Analog User Manual for proper shield grounding instructions.
� Terminals w1, w2, w3, are spares used for field wire convenience. NOTE: This is only true for module RTP3 and RTP4. The Bul. 1492 cable does not connect to these terminals.
Interface Module 1771-RTP4
IMPORTANT
120 Rockwell Automation Publication 1492-SG121E-EN-P - July 2016
Wiring Diagrams - High Resolution Isolated Analog
1771-NIV1 to 1756-IF6I
41171-078 (00)
B1B2B3B4B5A4A5B8B9A6A7B12B13A8A9B16B17A10A11
RTP4
3
2
4
W2SH
W3
I8
I7
I6
I5
I4
I3
I1
I2
R8
R7
R6
R5
R4
R3
R2
R1
1756-IF6I
VOLTAGE LOAD
5
A1A2A3B12B13A12A13B14B15A14A15B16B17A16A17B18B19
A18A19
CRW1
CL
O8
O7
O6
O5
O4
O3
O1
O2
S8
S7
S6
S5
S4
S3
S2
S1
1516
1918
2221
2425 1
5
62
713
8
12
VioletBlack
Green
Red
White/Black
White/Red
Yellow
Brown
IN-0V
IN-1V
IN-2V
IN-3V
RTN-0
RTN-2
RTN-3
1 Cables are available in 2.0m, or 5.0m
2 Terminals starting with A are the lower row of terminals, B terminals are the upper row.
3 Follow your PLC Analog User Manual for propershield grounding instructions.
4 RTN terminals are internally connected on the 1756-IF6I.
5 Terminals w1, w2, w3, are spares used f or field wire convenience. NOTE: this is only truefor modules RTP3 and RTP4. The Bul. 1492cable does not connect to these terminals.
CONVERSION MODULE INSTALLATION AND APPLICATION CONSIDERATIONS
1756-IF6IN/A
N/A
N/A
4
N/A
N/A
N/A
+
-
RTN-1
15
62
713
8
12
VOLTAGE LOAD
+
-
IN-0V
IN-1V
IN-2V
IN-3V
RTN-0
RTN-2
RTN-3
RTN-1
VioletBlack
Green
Red
White/Black
White/Red
Yellow
Brown
1516
1918
2221
2425
1492-CONACAB020N7
1492-CONACAB020N7
Cable”B”
Cable”A”
of drawing) when understand these
There are several key application considerations and system specifications (bottomusing these components (conversion module, cable and input module). Read andconsiderations before installation.
IMPORTANT
Rockwell Automation Publication 1492-SG121E-EN-P - July 2016 121
Wiring Diagrams - High Resolution Isolated Analog
1771-NT2 to 1756-IRT8I
DIR 10002306849 (Version 00)
B1A1B2B3A2A3B4B5A4A5
B6B7A6A7B8B9A9A8
3
2W1SH
I4
I3
I2
I1
R4
R3
R2
R1
1756-IRT8I4
O4
O3
O2
O1
S4
S3
S2
S1
1492-CONACAB020N68
1516
1918
2524
2122
+
-
Black
Red
Green
Brown
White/Black
White/Red
Yellow
Violet
THERMOCOUPLE
1920
2423
2728
3132
IN_4(-)/B
IN_5(-)/B
IN_6(-)/B
IN_7(-)/B
IN_4(+)/A
IN_6(+)/A
IN_7(+)/A
IN_5(+)/A
CJC1
CJC1Thermocouple
35
36
Cable “B”
B1A1B2B3A2A3B4B5A4A5
B6B7A6A7B8B9A9A8
2W1SH
I4
I3
I2
I1
R4
R3
R2
R1
4
O4
O3
O2
O1
S4
S3
S2
S1
1516
1918
2524
2122
+
-
Black
Red
Green
Brown
White/Black
White/Red
Yellow
Violet
THERMOCOUPLE
34
87
1112
1516
Thermocouple1
2
Cable “A”
3
1
White/Violet
White/Grey
White/Violet
White/Grey
2522
26
6
5
1310
1714
18
9
21N.C.N.C.
N.C.N.C.N.C.N.C.
N.C.N.C.
N.C. N.C.N.C.N.C.
2930
N.C.N.C.
14
1
IN_0(-)/B
IN_1(-)/B
IN_2(-)/B
IN_3(-)/B
IN_0(+)/A
IN_2(+)/A
IN_3(+)/A
IN_1(+)/A
CJC0
CJC0
14
1
3334
N.C.N.C.
There are several key application considerations and system specifications (bottom of drawing) when using these components (conversion module, cable and input module). Read and understand these considerations before installation.
Interface Module Installation and Application Considerations Cables are available in lengths of 2.0M or 5.0M (020=2.0M, 050=5.0M)
Terminals starting with A are the lower row of terminals, B terminals are the upper row.
� Follow your PLC Analog User Manual for proper shield grounding instructions.
� Terminals w1, w2, w3, are spares used for field wire convenience. NOTE: This is only true for module RTP3 and RTP4. The Bul. 1492 cable does not connect to these terminals.
This conversion solution requires replacement of the exisiting (1) 1771-RTP1 interface module with (2) 1771-RT41 interface modules. Each 1771-RTP1 and RT41 module has there own cold junction compensation thermocouple attached to the interface module.
1771-RT41
Interface Module
1771-RT41Interface Module
IMPORTANT
122 Rockwell Automation Publication 1492-SG121E-EN-P - July 2016
Wiring Diagrams - High Resolution Isolated Analog
1771-NT2 to 1756-IT6I2
41171-077 (01)
B1A1B2B3A2A3B4B5A4A5
B6B7A6A7B8B9A9A8
1771-RT41
3
2W1SH
I4
I3
I2
I1
R4
R3
R2
R1
1756-IT6I24
O4
O3
O2
O1
S4
S3
S2
S1
1492-CONACAB020N6
CONVERSION MODULE INSTALLATION AND APPLICATION CONSIDERATIONS
1516
1918
2524
2122
+
-
Black
Red
Green
Brown
White/Black
White/Red
Yellow
Violet
THERMOCOUPLE
56
87
910
1112
RTN-0
RTN-1
RTN-2
RTN-3
IN-0
IN-2
IN-3
IN-1
Cables are available in 2.0M or 5.0M.Terminals starting with A are the lower row of
terminals, B terminals are the upper row.Follow your PLC Analog User Manual for proper
shield grounding instructions.Terminals W1, W2 and W3 are spares used for field wire
convenience. NOTE. This is only true for modules RT41 . The Bul. 1492 cable does not connect to these terminals.
CJC+
CJC-Thermocouple
3
4
Cable “B”
B1A1B2B3A2A3B4B5A4A5
B6B7A6A7B8B9A9A8
1771-RT41
2W1SH
I4
I3
I2
I1
R4
R3
R2
R1
1756-IT6I24
O4
O3
O2
O1
S4
S3
S2
S1
1492-CONACAB020N6
1516
1918
2524
2122
+
-
Black
Red
Green
Brown
White/Black
White/Red
Yellow
Violet
THERMOCOUPLE
56
87
910
1112
RTN-0
RTN-1
RTN-2
RTN-3
IN-0
IN-2
IN-3
IN-1
CJC+
CJC-Thermocouple
3
4
Cable “A”
3
1
1
White/Violet
White/Grey
White/Violet
White/Grey
of drawing) when understand these
There are several key application considerations and system specifications (bottomusing these components (conversion module, cable and input module). Read andconsiderations before installation.
IMPORTANT
Rockwell Automation Publication 1492-SG121E-EN-P - July 2016 123
Wiring Diagrams - High Resolution Isolated Analog
Combination High Resolution I/O
1771-NIVR to1756-IRT8I and -IF8I
using these components (conversion module, cable and input module). Read and understand these considerations before installation.
�
1492-CONACAB020N74
1492-CONACAB020N44
Interface Module1771-RTP4
1756-IF8I
B1B2B3B4B5A4A5B8B9A6A7B12B13A8A9B16B17A10A11
W2SH
W3
I8
I7
I6
I5
I4
I3
I1
I2
R8
R7
R6
R5
R4
R3
R2
R1VOLTAGE LOAD
A1A2A3B12B13A12A13B14B15A14A15B16B17A16A17B18B19
A18A19
CRW1
CL
O8
O7
O6
O5
O4
O3
O1
O2
S8
S7
S6
S5
S4
S3
S2
S1
1516
1819
2122
2425 2
6
15
1410
9
13
� � � � � �
� � �
� � � �
� � �
� � � � � � � � �
� � � � � � � � �
� � � � � �
� � � �
IN_0/V
IN_1/V
IN_2/V
IN_3/V
RTN_0
RTN_2
RTN_3
N/A
N/A
N/A
N/A
N/A
N/A
+
-
RTN_1
� 1756-IRT8I
242513
22
10
721
41819
1516
RTD ANSMITTER
43
IN_0(-)/BIN_0(+)/A
6 IN_0/RTD C
8
7
10
12
11
14
16
15
18
IN_1(-)/B
IN_1(+)/A
IN_1/RTD C
IN_2(-)/B
IN_2(+)/A
IN_2/RTD C
IN_3(-)/B
IN_3(+)/A
IN_3/RTD C� � � � � � � � �
� � �
� � � � �
� � � �
� � � � � �
� � � � � � � � � � �
� � � � � � � � �
� � � �
� � � �
� � �
� � � � � �
� � � � �
CABLE “B”
CABLE “A”
Interface Module Installation and Application Considerations Cables are available in lengths of 2.0M or 5.0M (020=2.0M, 050=5.0M)
Terminals starting with A are the lower row of terminals, B terminals are the upper row.
� Follow your PLC Analog User Manual for proper shield grounding instructions.
� Terminals w1, w2, w3, are spares used for field wire convenience. NOTE: This is only true for module RTP3 and RTP4. The Bul. 1492 cable does not connect to these terminals.
DIR 10002306496(Version 00)
IMPORTANT
124 Rockwell Automation Publication 1492-SG121E-EN-P - July 2016
Wiring Diagrams - High Resolution Isolated Analog
1771-NIVR to 1756-IR6Iand -IF6I
Conversion Module Installation and Application Considerations Cables are available in 2.0m, or 5.0m
Terminals starting with A are the lower row of terminals, B terminals are the upper row.
Follow your PLC Analog User Manual for proper shield grounding instructions.
RTN terminals are internally connected on the 1756-IF6I.
Terminals w1, w2, w3, are spares used for field wire convenience. NOTE: This is only true for module RTP4. The Bul. 1492 cable does not connect to these terminals. [Reference Doc: 41171-082 (Version 00)]
There are several key application considerations and system specifications (bottom of drawing) when using these components (conversion module, cable and input module). Read and understand these considerations before installation.
Cable “A”1492-CONACAB020N7
Cable “B”1492-CONACAB020N4
Interface Module 1771-RTP4
1756-IF6I
B1B2B3B4B5A4A5B8B9A6A7B12B13A8A9B16B17A10A11
W2SH
W3
I8
I7
I6
I5
I4
I3
I1
I2
R8
R7
R6
R5
R4
R3
R2
R1VOLTAGE LOAD
A1A2A3B12B13A12A13B14B15A14A15B16B17A16A17B18B19
A18A19
CRW1
CL
O8
O7
O6
O5
O4
O3
O1
O2
S8
S7
S6
S5
S4
S3
S2
S1
1516
1819
2122
2425 1
5
26
117
8
12
VioletBlack
Green
Red
White/Black
White/Red
Yellow
Brown
IN-0V
IN-1V
IN-2V
IN-3V
RTN-0
RTN-2
RTN-3
N/A
N/A
N/A
N/A
N/A
N/A
+
-
RTN-1
1756-IR6I
242513
22
10
721
41819
1516
RTD TRANSMITTER
31
IN-0/BIN-0/A
5 RTN-0
4
2
6
9
7
11
10
8
12
IN-1/B
IN-1/A
RTN-1
IN-2/B
IN-2/A
RTN-2
IN-3/B
IN-3/A
RTN-3
IMPORTANT
Rockwell Automation Publication 1492-SG121E-EN-P - July 2016 125
Wiring Diagrams - High Resolution Isolated Analog
1771-NIVR to 1756-IRT8I and -IF8I
using these components (conversion module, cable and input module). Read and understand these considerations before installation.
�
1492-CONACAB020N34
1492-CONACAB020N44
Interface Module1771-RTP4
1756-IF8I
B1B2B3B4B5A4A5B8B9A6A7B12B13A8A9B16B17A10A11
W2SH
W3
I8
I7
I6
I5
I4
I3
I1
I2
R8
R7
R6
R5
R4
R3
R2
R1CURRENT LOAD
A1A2A3B12B13A12A13B14B15A14A15B16B17A16A17B18B19
A18A19
CRW1
CL
O8
O7
O6
O5
O4
O3
O1
O2
S8
S7
S6
S5
S4
S3
S2
S1
1516
1819
2122
2425 4
6
35
1412
11
13
� � � � �
� � �
� �
� � � �
� � � � � � � � �
� � � � � �
� � � � � � � �
� � � �
IN_0/I/SRC
IN_1/I/SRC
IN_2/I/SRC
IN_3/I/SRC
RTN_0
RTN_2
RTN_3
N/A
N/A
N/A
N/A
N/A
N/A
+
-
RTN_1
� 1756-IRT8I
242513
22
10
721
41819
1516
RTD TRANSMITTER
43
IN_0(-)/BIN_0(+)/A
6 IN_0/RTD C
8
7
10
12
11
14
16
15
18
IN_1(-)/B
IN_1(+)/A
IN_1/RTD C
IN_2(-)/B
IN_2(+)/A
IN_2/RTD C
IN_3(-)/B
IN_3(+)/A
IN_3/RTD C� � � � � �
� �
� � � �
� �
� � � � �
� � � � � � � �
� � � � � � � � �
� � � �
� � � �
� � � � �
� � � �
� � �
Interface Module Installation and Application Considerations Cables are available in lengths of 2.0M or 5.0M (020=2.0M, 050=5.0M)
Terminals starting with A are the lower row of terminals, B terminals are the upper row.
� Follow your PLC Analog User Manual for proper shield grounding instructions.
� Terminals w1, w2, w3, are spares used for field wire convenience. NOTE: This is only true for module RTP3 and RTP4. The Bul. 1492 cable does not connect to these terminals.
DIR 10002306490 (Version 00)
CABLE “B”
CABLE “A”
IMPORTANT
126 Rockwell Automation Publication 1492-SG121E-EN-P - July 2016
Wiring Diagrams - High Resolution Isolated Analog
1771-NIVR to 1756-IR6I and -IF6I
Conversion Module Installation and Application Considerations Cables are available in 2.0m, or 5.0m
Terminals starting with A are the lower row of terminals, B terminals are the upper row.
Follow your PLC Analog User Manual for proper shield grounding instructions.
RTN terminals are internally connected on the 1756-IF6I.
Terminals w1, w2, w3, are spares used for field wire convenience. NOTE: This is only true for module RTP4. The Bul. 1492 cable does not connect to these terminals. [Reference Doc: 41171-083 (Version 00)]
There are several key application considerations and system specifications (bottom of drawing) when using these components (conversion module, cable and input module). Read and understand these considerations before installation.
Cable “B”1492-CONACAB020N4
Interface Module 1771-RTP4
B1B2B3B4B5A4A5B8B9A6A7B12B13A8A9B16B17A10A11
W2SH
W3
I8
I7
I6
I5
I4
I3
I1
I2
R8
R7
R6
R5
R4
R3
R2
R1VOLTAGE LOAD
A1A2A3B12B13A12A13B14B15A14A15B16B17A16A17B18B19
A18A19
CRW1
CL
O8
O7
O6
O5
O4
O3
O1
O2
S8
S7
S6
S5
S4
S3
S2
S1
N/A
N/A
N/A
N/A
N/A
N/A
+
-
1756-IR6I
242513
22
10
721
41819
1516
RTD TRANSMITTER
31
IN-0/BIN-0/A
5 RTN-0
4
2
6
9
7
11
10
8
12
IN-1/B
IN-1/A
RTN-1
IN-2/B
IN-2/A
RTN-2
IN-3/B
IN-3/A
RTN-3
Cable “A”1492-CONACAB010N3
1756-IF6I
1516
1819
2122
2425 3
5
46
119
10
12
BlackWhite
Green
Orange
White/Black
White/Red
White/Orange
Gray
IN-0/I
IN-1/I
IN-2/I
IN-3/I
RTN-0
RTN-2
RTN-3
RTN-1
1 IN-0/V
2 IN-1/V
7 IN-2/V
8 IN-3/V
IMPORTANT
Rockwell Automation Publication 1492-SG121E-EN-P - July 2016 127
Wiring Diagrams - High Resolution Isolated Analog
1771-NIVT to 1756-IRT8I and -IF8I
using these components (conversion module, cable and input module). Read and understand these considerations before installation.
DIR 10002306594 (Version 00)
26
15
1410
9
13
IN_0/V
IN_1/V
IN_2/V
IN_3/V
RTN_0
RTN_2
RTN_3
RTN_1
B1B2B3B4B5A4A5B8B9A6A7B12B13A8A9B16B17A10A11
3
2W2SH
W3
I8
I7
I6
I5
I4
I3
I1
I2
R8
R7
R6
R5
R4
R3
R2
R1
1756-IRT8I4
A1A2A3B12B13A12A13B14B15A14A15B16B17A16A17B18B19
A18A19
CRW1
CL
O8
O7
O6
O5
O4
O3
O1
O2
S8
S7
S6
S5
S4
S3
S2
S1
1492-CONACAB020N54
1516
1918
2524
2122
+
-
Black
Red
Green
Brown
White/Black
White/Red
Yellow
Violet
THERMOCOUPLE
34
87
1112
1516
IN_0(-)/B
IN_1(-)/B
IN_2(-)/B
IN_3(-)/B
IN_0(+)/A
IN_2(+)/A
IN_3(+)/A
IN_1(+)/A
CJC+CJC-
Thermocouple
1492-CONACAB020N74
1516
1819
2122
2425
� � � � � �
� � �
� � � �
� � �
� � � � � � � � �
� � � � � � � � �
� � � � � �
� � � �
VOLTAGE LOAD
+
-
Interface Module1771-RTP1
10
1414
1
1756-IF8I
Interface Module Installation and Application Considerations Cables are available in lengths of 2.0M or 5.0M (020=2.0M, 050=5.0M)
Terminals starting with A are the lower row of terminals, B terminals are the upper row.
� Follow your PLC Analog User Manual for proper shield grounding instructions.
� Terminals w1, w2, w3, are spares used for field wire convenience. NOTE: This is only true for module RTP3 and RTP4. The Bul. 1492 cable does not connect to these terminals.
CABLE “B”
CABLE “A”
IMPORTANT
128 Rockwell Automation Publication 1492-SG121E-EN-P - July 2016
Wiring Diagrams - High Resolution Isolated Analog
1771-NIVT to 1756-IT6I and -IF6I
B1B2B3B4B5A4A5B8B9A6A7B12B13A8A9B16B17A10A11
3
2W2SH
W3
I8
I7
I6
I5
I4
I3
I1
I2
R8
R7
R6
R5
R4
R3
R2
R1
1756-IT6I4
A1A2A3B12B13A12A13B14B15A14A15B16B17A16A17B18B19
A18A19
CRW1
CL
O8
O7
O6
O5
O4
O3
O1
O2
S8
S7
S6
S5
S4
S3
S2
S1
CABLE “B”
1492-CONACAB010N5CABLE “B”
1516
1918
2524
2122
+
-
Black
Red
Green
Brown
White/Black
White/Red
Yellow
Violet
THERMOCOUPLE
56
87
910
1112
RTN-0
RTN-1
RTN-2
RTN-3
IN-0
IN-2
IN-3
IN-1
CJC+CJC-
Thermocouple
Cable “A”1492-CONACAB020N7
1756-IF6I
1516
1819
2122
2425 1
5
26
117
8
12
VioletBlack
Green
Red
White/Black
White/Red
Yellow
Brown
IN-0V
IN-1V
IN-2V
IN-3V
RTN-0
RTN-2
RTN-3
RTN-1
VOLTAGE LOAD
+
-
Conversion Module Installation and Application Considerations Cables are available in 2.0m, or 5.0m
Terminals starting with A are the lower row of terminals, B terminals are the upper row.
Follow your PLC Analog User Manual for proper shield grounding instructions.
RTN terminals are internally connected on the 1756-IF6I.
Terminals w1, w2, w3, are spares used for field wire convenience. NOTE: This is only true for module RTP4. The Bul. 1492 cable does not connect to these terminals. [Reference Doc: 41171-084 (Version 00)]
There are several key application considerations and system specifications (bottom of drawing) when using these components (conversion module, cable and input module). Read and understand these considerations before installation.
Interface Module 1771-RTP1
10
1414
1
IMPORTANT
Rockwell Automation Publication 1492-SG121E-EN-P - July 2016 129
Wiring Diagrams - High Resolution Isolated Analog
1771-NIVT to 1756-IRT8I and -IF8I
Interface Module Installation and Application Considerations This Bul. 1492 cable consists of a cable wired to one 1756-IF8I (or 1756-IRT8I). Recommended cable lengths of 2.0M or 5.0M (020=2.0M, 050=5.0M). See table 2 for other lengths.
Terminals starting with A are the lower row of terminals, B terminals are the upper row.
� Follow your PLC Analog User Manual for proper shield grounding instructions.
� for module RTP4. The Bul. 1492 cable does not connect to these terminals.
DIR 10002306504 (Version 00)
B1B2B3B4B5A4A5B8B9A6A7B12B13A8A9B16B17A10A11
3
2W2SH
W3
I8
I7
I6
I5
I4
I3
I1
I2
R8
R7
R6
R5
R4
R3
R2
R1
1756-IRT8I4
A1A2A3B12B13A12A13B14B15A14A15B16B17A16A17B18B19
A18A19
CRW1
CL
O8
O7
O6
O5
O4
O3
O1
O2
S8
S7
S6
S5
S4
S3
S2
S1
1492-CONACAB020N54
1516
1918
2524
2122
+
-
Black
Red
Green
Brown
White/Black
White/Red
Yellow
Violet
THERMOCOUPLE
34
87
1112
1516
IN_0(-)/B
IN_1(-)/B
IN_2(-)/B
IN_3(-)/B
IN_0(+)/A
IN_2(+)/A
IN_3(+)/A
IN_1(+)/A
CJC+CJC-
Thermocouple
1492-CONACAB020N34
1516
1819
2122
2425CURRENT
LOAD+
-
Interface Module1771-RTP1
10
1414
1
1756-IF8I
46
35
1412
11
13
IN_0/I/SRC
IN_1/I/SRC
IN_2/I/SRC
IN_3/I/SRC
RTN_0
RTN_2
RTN_3
RTN_1
� � � � �
� � �
� �
� � � �
� � � � � � � � �
� � � � � �
� � � � � � � �
� � � �
There are several key application considerations and system specifications (bottom of drawing) when using these components (conversion module, cable and input module). Read and understand these considerations before installation.
CABLE “B”
CABLE “A”
IMPORTANT
130 Rockwell Automation Publication 1492-SG121E-EN-P - July 2016
Wiring Diagrams - High Resolution Isolated Analog
1771-NIVT to 1756-IT6I and -IF6I
B1B2B3B4B5A4A5B8B9A6A7B12B13A8A9B16B17A10A11
2W2SH
W3
I8
I7
I6
I5
I4
I3
I1
I2
R8
R7
R6
R5
R4
R3
R2
R1
1756-IT6I4
A1A2A3B12B13A12A13B14B15A14A15B16B17A16A17B18B19
A18A19
CRW1
CL
O8
O7
O6
O5
O4
O3
O1
O2
S8
S7
S6
S5
S4
S3
S2
S1
CABLE “B”
1492-CONACAB010N5CABLE “B”
1516
1918
2524
2122
+
-
Black
Red
Green
Brown
White/Black
White/Red
Yellow
Violet
THERMOCOUPLE
15
62
711
812
RTN-0
RTN-1
RTN-2
RTN-3
IN-0
IN-2
IN-3
IN-1
CJC+CJC-
Thermocouple
CURRENT LOAD
+
-
Conversion Module Installation and Application Considerations Cables are available in 2.0m, or 5.0m
Terminals starting with A are the lower row of terminals, B terminals are the upper row.
Follow your PLC Analog User Manual for proper shield grounding instructions.
RTN terminals are internally connected on the 1756-IF6I.
Terminals w1, w2, w3, are spares used for field wire convenience. NOTE: This is only true for module RTP4. The Bul. 1492 cable does not connect to these terminals. 41171-085 Ver (00)
There are several key application considerations and system specifications (bottom of drawing) when using these components (conversion module, cable and input module). Read and understand these considerations before installation.
Interface Module 1771-RTP1
N/A
N/A
N/A
1756-IF6I
1516
1819
2122
2425 3
5
46
119
10
12
BlackWhite
Green
Orange
White/Black
White/Red
White/Orange
Gray
IN-0/I
IN-1/I
IN-2/I
IN-3/I
RTN-0
RTN-2
RTN-3
RTN-1
1 IN-0/V
2 IN-1/V
7 IN-2/V
8 IN-3/V
10
1414
1
1492-CONACAB010N3CABLE “A”
IMPORTANT
Rockwell Automation Publication 1492-SG121E-EN-P - July 2016 131
Publication 1492-SG121E-EN-P - July 2016Supersedes Publication 1492-SG121D-EN-P - October 2014 Copyright © 2016 Rockwell Automation, Inc. All rights reserved. Printed in the U.S.A.
Rockwell Automation SupportUse the following resources to access support information.
Documentation FeedbackYour comments will help us serve your documentation needs better. If you have any suggestions on how to improve this document, complete the How Are We Doing? form at http://literature.rockwellautomation.com/idc/groups/literature/documents/du/ra-du002_-en-e.pdf.
Technical Support Center Knowledgebase Articles, How-to Videos, FAQs, Chat, User Forums, and Product Notification Updates.
www.rockwellautomation.com/knowledgebase
Local Technical Support Phone Numbers Locate the phone number for your country. www.rockwellautomation.com/global/support/get-support-now.page
Direct Dial Codes Find the Direct Dial Code for your product. Use the code to route your call directly to a technical support engineer.
www.rockwellautomation.com/global/support/direct-dial.page
Literature Library Installation Instructions, Manuals, Brochures, and Technical Data.
www.rockwellautomation.com/literature
Product Compatibility and Download Center (PCDC)
Get help determining how products interact, check features and capabilities, and find associated firmware.
www.rockwellautomation.com/global/support/pcdc.page
Allen-Bradley, ControlLogix, LISTEN. THINK. SOLVE, Rockwell Automation, and Rockwell Software are trademarks of Rockwell Automation, Inc.Trademarks not belonging to Rockwell Automation are property of their respective companies.
Rockwell Automation maintains current product environmental information on its website at http://www.rockwellautomation.com/rockwellautomation/about-us/sustainability-ethics/product-environmental-compliance.page.