Range Compact Masterpact Models NS630b to NS1600 NT06 to NT16 NW08 to NW63 Rating (A) 630 to 1600 630 to 1600 800 to 6300 Type of device N/H/L circuit breakers NA switch-disconnectors H1/L1 circuit breakers HA switch-disconnectors N1/H1/H2/H3/L1 circuit breakers NA/HA/HF switch- disconnectors Manual source-changeover systems Interlocking via extended rotary handles DB126590.eps Db101553.eps 2 devices side-by-side. Interlocking via keylocks with captive keys DB126588.eps Db101554.eps Db101555.eps Db101556.eps A number of different devices. Mechanical interlocking using connecting rods DB126585.eps Db101557.eps (1) Db101558.eps Db101559.eps 2 devices one above the other. Mechanical interlocking using cables DB126584.eps Db101560.eps (1) (2) Db101561.eps Db101562.eps 2 or 3 devices one above the other. DB126583.eps 2 or 3 devices side-by-side. For this case and other cases, please consult us DB126580.eps (1) Implemented with NS630b to NS1600 electrically-operated devices only. (2) For source-changeover systems using cables, always respect the installation conditions specified on page A-13. Manual source-changeover systems Compact NS and Masterpact NT/NW 630 A to 6300 A A-3

Upload: rakih-sajid

Post on 18-Nov-2015

239 views

Category:

Documents


0 download

TRANSCRIPT

  • Range Compact MasterpactModels NS630b to NS1600 NT06 to NT16 NW08 to NW63Rating (A) 630 to 1600 630 to 1600 800 to 6300 Type of device N/H/L circuit breakers

    NA switch-disconnectorsH1/L1 circuit breakersHA switch-disconnectors

    N1/H1/H2/H3/L1 circuit breakersNA/HA/HF switch-disconnectors

    Manual source-changeover systemsInterlocking via extended rotary handles

    DB

    1265

    90.e

    ps

    Db1

    0155

    3.ep

    s

    2 devices side-by-side.

    Interlocking via keylocks with captive keys

    DB

    1265

    88.e

    ps

    Db1

    0155

    4.ep

    s

    Opush

    OFF

    Ipush

    ON

    O OFFdisch

    arged

    Opush

    OFF

    Ipush

    ON

    O OFFdisch

    arged

    Db1

    0155

    5.ep

    s

    Db1

    0155

    6.ep

    s

    A number of different devices.

    Mechanical interlocking using connecting rods

    DB

    1265

    85.e

    ps

    Opush

    OFF

    Ipush

    ON

    OOFF

    discharged

    Opush

    OFF

    Ipush

    ON

    OOFF

    discharged

    Db1

    0155

    7.ep

    s

    (1)

    Db1

    0155

    8.ep

    s

    Db1

    0155

    9.ep

    s

    2 devices one above the other.

    Mechanical interlocking using cables

    DB

    1265

    84.e

    ps

    Db1

    0156

    0.ep

    s

    (1)

    (2)

    Db1

    0156

    1.ep

    s

    Db1

    0156

    2.ep

    s

    2 or 3 devices one above the other.

    DB

    1265

    83.e

    ps

    2 or 3 devices side-by-side.For this case and other cases, please consult us

    DB

    1265

    80.e

    ps

    (1) Implemented with NS630b to NS1600 electrically-operated devices only.(2) For source-changeover systems using cables, always respect the installation conditions specified on page A-13.

    Manual source-changeover systems Compact NS and Masterpact NT/NW 630 A to 6300 A

    A-3

    313E.indb 3 09/04/2013 13:04:19

    SESA296812Rectangle

    SESA296812Rectangle

    SESA296812Highlight

    SESA296812Highlight

    SESA296812Rectangle

  • A-10

    Functions and characteristics

    Mechanical interlocking of two or three devices is used to create a remote-operated source-changeover system. A basic mechanical interlocking system enhances the reliability of system operation.

    Interlocking of two Compact NSX100 to 630 devices using a base plateA base plate designed for two Compact circuit breakers can be installed horizontally or vertically on a mounting rail. Interlocking is carried out on the base plate by a mechanism located behind the breakers. Access to the circuit breaker controls and trip units is conserved. Circuit breakers must be fixed or plug-in versions, with or without earth-leakage protection or measurement modules. The base plate and the circuit breakers are supplied separately.

    b Base plate for Compact NSX100 to 250 devicesThis base plate is intended for two Compact NSX100 to 250 devices.

    b Base plate for Compact NSX400 to 630 devicesThis base plate is intended for two Compact NSX400 to 630 devices. It may also be used, without any modifications, to interlock a fixed Compact NSX100 to 250 with a Compact NSX400 or 630 device.An adapter kit is required for plug-in versions of the Compact NSX100 to 250 devices.Compact NSX100 to 250 devices, in both fixed and plug-in versions, may be equipped with spreaders.

    PB

    1051

    06_5

    0.ep

    s

    Possible combinations of Normal and Replacement Compact NSX source circuit breakers

    Interlocking of two electrically-operated Compact NSX circuit breakers using a base plate. Normal N Replacement R

    NSX100 NSX160 NSX250 NSX400 NSX630NSX100Ratings 12,5... 100 A b b b b b NSX160Ratings 12,5...160 A b b b b b NSX250Ratings 12,5...250 A b b b b b NSX400Ratings 160... 400 A b b b b b NSX630Ratings 250... 630 A b b b b b

    DB

    1262

    68.e

    ps Interlocking of two Compact NS630b to 1600 or two Masterpact NT and NW devices using connecting rodsThe two devices must be mounted one above the other (either 2 fixed or 2 withdrawable/drawout devices).Combinations are possible between Compact NS630b to NS1600 devices and between Masterpact NT and Masterpact NW devices.InstallationThis function requires:

    b an adaptation fixture on the right side of each circuit breaker or switch-disconnector

    b a set of connecting rods with no-slip adjustments.The adaptation fixtures, connecting rods and circuit breakers or switch-disconnectors are supplied separately, ready for assembly by the customer.The maximum vertical distance between the fixing planes is 900 mm.

    Possible combinations of Normal and Replacement source circuit breakers

    Normal N Replacement RNS630b to NS1600

    NT06 to NT16 NW08 to NW40

    NW40b to NW63

    NS630b to NS1600Ratings 250... 1600 A b

    Interlocking of two Masterpact NT or NW circuit breakers using connecting rods.

    NT06 to NT16Ratings 250... 1600 A b b b NW08 to NW40Ratings 320... 4000 A b b b NW40b to NW63Ratings 4000... 6300 A b b b

    Remote-operated source-changeover systems Mechanical interlocking Compact NSX, Compact NS or Masterpact NT/NW

    313E.indb 10 09/04/2013 13:04:24

    SESA296812Highlight

    SESA296812Rectangle

    SESA296812Rectangle

    SESA296812Highlight

    SESA296812Highlight

  • A-11

    PB

    1008

    42_6

    8_S

    E.e

    ps Interlocking of two Compact NS630b to 1600 or two Masterpact NT/NW or up to three Masterpact NW devices using cablesFor cable interlocking, the circuit breakers may be mounted one above the other or side-by-side.The interlocked devices may be fixed or drawout, three-pole or four-pole, and have different ratings and sizes.

    Interlocking between two devices (Compact NS630b to 1600 or Masterpact NT and NW)This function requires:

    b an adaptation fixture on the right side of each device b a set of cables with no-slip adjustments.

    The maximum distance between the fixing planes (vertical or horizontal) is 2000 mm.

    Interlocking between three devices (Masterpact NW only)This function requires:

    b a specific adaptation fixture for each type of interlocking, installed on the right side of each device

    b two or three sets of cables with no-slip adjustments.The maximum distance between the fixing planes (vertical or horizontal) is 1000 mm.InstallationThe adaptation fixtures, sets of cables and circuit breakers or switch-disconnectors are supplied separately, ready for assembly by the customer.Installation conditions for cable interlocking systems:

    b cable length: 2.5 m b radius of curvature: 100 mm b maximum number of curves: 3.

    Interlocking of two Masterpact circuit breakers using cables.

    Possible combinations of Normal and Replacement source circuit breakers

    Normal N Replacement RNS630b to NS1600

    NT06 to NT16 NW08 to NW40

    NW40b to NW63

    NS630b to NS1600Ratings 250... 1600 A b NT06 to NT16Ratings 250... 1600 A b b b NW08 to NW40Ratings 320... 4000 A b b b NW40b to NW63Ratings 4000... 6300 A b b b

    It is not possible to combine Compact NS630b to 1600 and Masterpact NT (or Masterpact NW) devices.All combinations of two Masterpact NT and Masterpact NW devices are possible, whatever the rating or size of the devices.

    Possible combinations of three device

    Normal N Replacement RNS630b to NS1600

    NT06 to NT16 NW08 to NW40

    NW40b to NW63

    NS630b to NS1600Ratings 250... 1600 ANT06 to NT16Ratings 250... 1600 ANW08 to NW40Ratings 320... 4000 A b b NW40b to NW63Ratings 4000... 6300 A b b

    Only Masterpact NW may be used for three-device combinations.

    Types of mechanical interlocking and combinationsSee page A-4 to page A-9.

    Mechanical interlocking Compact NS or Masterpact NT/NW

    313E.indb 11 09/04/2013 13:04:25

    SESA296812Rectangle

    SESA296812Highlight

    SESA296812Highlight

    SESA296812Highlight

    SESA296812Highlight

    SESA296812Highlight

    SESA296812Highlight

  • B-14

    Two Masterpact NW devices one above the otherFixed devices Withdrawable devices

    DB

    1077

    48.e

    ps

    DB

    1077

    49.e

    ps

    Remote-operated source-changeover systems Interlocking using connecting rods

    Dimensions

    313E.indb 14 09/04/2013 13:04:47

  • B-16

    Two Masterpact NW devices side-by-sideFixed devices Drawout devices

    Db1

    0166

    6.ep

    s

    Db1

    0166

    7.ep

    s

    Three Masterpact NW devices side-by-side Fixed devices

    Db1

    0166

    8.ep

    s

    Drawout devices

    Db1

    0166

    9.ep

    sRemote-operated source-changeover systemsInterlocking using cables

    Dimensions

    313E.indb 16 09/04/2013 13:04:49

  • B-18

    Two Masterpact NW devices one above the otherFixed devices Drawout devices

    DB

    1077

    51.e

    ps

    DB

    1077

    52.e

    ps

    Two Masterpact NT and NW devices one above the otherFixed devices Drawout devices

    DB

    1077

    53.e

    ps

    DB

    4041

    48.e

    ps

    Remote-operated source-changeover systemsInterlocking using cables

    Dimensions

    313E.indb 18 09/04/2013 13:04:50

  • B-19

    Three Masterpact NW devices one above the otherFixed devices Drawout devices

    DB

    1077

    54.e

    ps

    DB

    1077

    55.e

    ps

    Remote-operated source-changeover systemsInterlocking using cables

    Dimensions

    313E.indb 19 09/04/2013 13:04:50

  • Catalogue numbers and order forms

    Interlocking for source-changeover systems for 2 devicesInterlocking of 2 devices using connecting rods

    DB

    4040

    95.e

    ps Complete assembly with 2 adaptation fixtures + rods2 Masterpact NW fixed devices 486122 Masterpact NW drawout devices 48612Can be used with 1 NW fixed + 1 NW drawout.

    Interlocking of 2 devices using cables (*)Choose 2 adaptation fixtures (1 for each breaker + 1 set of cables)1 adaptation fixture for Masterpact NW fixed devices 479261 adaptation fixture for Masterpact NW drawout devices 479261 set of 2 cables 33209

    (*) Can be used with any combination of NT or NW, fixed or drawout devices.

    Associated controller for 2 devicesThe automatic-control option includes:

    b an IVE electrical-interlocking unit b an ACP control plate b a BA or UA controller, depending on the required functions b a UA/BA adapter kit.

    Note: the circuit breaker auxiliaries (MCH, MX, XF) and the automatic-control components (IVE, ACP, UA or BA) must have the same voltages.IVE electrical-interlocking unit 24 to 250 V DC 48/415 V AC 50/60 Hz

    440 V 60 Hz

    DB

    4040

    93.e

    ps For 2 devices 29356 29352Wiring kit for connection of 2 fixed/drawout devices to the IVE unit 54655

    Control unit option 110/127 V AC 50/60 Hz 220/240 V AC 50/60 Hz 380/415 V AC 50/60 Hz 440 V 60 Hz

    Test

    MERLIN GE

    RIN

    multi9

    P25M

    660V

    AC3-IEC29

    2-1

    0 . OFF

    Test

    MERLIN GE

    RIN

    multi9

    P25M

    660V

    AC3-IEC29

    2-1

    0 . OFF

    DB

    4040

    87.e

    ps ACP + controller BA (1) 29470 29471Plate ACP 29363 29364Controller BA 29376 29377

    ACP + controller UA (1) 29448 29472 29473Plate ACP 29447 29363 29364Controller UA 29446 29378 29380

    ACP + controller UA150 (1) (communication option) 29474 29475Plate ACP 29363 29364Controller UA150 29379 29381

    (1) The supply voltages of the BA/UA controller, ACP plate, IVE unit and circuit breaker operating mechanism must be identical whatever the type of source-changeover system.

    Source-changeover systems for 2 or 3 devicesMasterpact NW circuit breakers and switch-disconnectors