Installation TTV-IOM Operation Maintenance Library Service Literature Product Section Unitary Product DX Fan Coil Unit Model TTV Literature Type Installation / Operation / Maintenance Sequence 1 Date September 2003 Commercial Air Cooled Split Air Conditioners -Indoor Units Models TTV250, TTV300 TTV400, TTV500 TTV600. Since The Trane Company has a policy of continuous product improvement. A reserves the right to change specifications and design without notice. The installation and servicing of the equipment referred to in this booklet should be done by qualified experienced technicians.

Upload: others

Post on 11-Apr-2022

14 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: Installation TTV-IOM Operation Maintenance

Installation TTV-IOMOperationMaintenanceLibrary Service LiteratureProduct Section UnitaryProduct DX Fan Coil UnitModel TTVLiterature Type Installation / Operation / MaintenanceSequence 1Date September 2003

CommercialAir Cooled SplitAir Conditioners-Indoor Units

Models TTV250, TTV300TTV400, TTV500TTV600.

Since The Trane Company has a policy of continuous product improvement. A reserves theright to change specifications and design without notice. The installation and servicing of theequipment referred to in this booklet should be done by qualified experienced technicians.

Page 2: Installation TTV-IOM Operation Maintenance

Foreword

These instructions do not attempt to cover all variations insystems, nor to provide for every possible contingency to bemet in connection with installation. Should further informationbe desired or should particular problems arise which are not

sufficiently covered for the purchaser’s purpose, the mattershould be referred to the manufacturer.

Warranty

Warranty is based on the general terms and conditions of theTrane Company. The warranty is void if the equipment isrepaired or modified without the written approval of themanufacturer, if the operating limits are exceeded or if thecontrol system or the electrical wiring is modified. Damage

due to misuse, lack of maintenance or failure to comply withthe manufacturer’s instructions or recommendations is notcovered by the warranty obligation.

Reception

On arrival, inspect the unit before signing the delivery note.Specify any damage on the delivery note, and send a registeredletter of protest to the last carrier of the goods within 72 hoursof delivery. Notify the local Trane Sales Office at the sametime. The unit should be totally inspected within 15 days ofdelivery. If any concealed damage is discovered, stop,unpacking the shipment. Take photos of the damage materialif possible. Notify the Carrier immediately by phone and

registered mail. Notify the local Trane Sales Office. Concealeddamage must be reported within 15 days delivery. Check theunit nameplate to confirm that the proper unit was shipped.Available power supply must be compatible with electricalcharacteristics specified on component nameplates.

General Information

This manual covers the installation, operation and maintenanceof the Trane TTV DX Fan Coil. These new air handler modelsare completely designed to incorporate a single slab coilassembly, improved application flexibility, servicing andmaintenance accessibility and an improved accessory line.TTVs are of the fully vertical discharge type. They are shippedin the vertical position.

Note: “Warning” and “Caution” appear at appropriate placesin this manual. Your personal safety and the proper operationof this machine require that you follow them carefully. Themanufacturer assumes no liability for installations or servicingperformed by unqualified personnel.

Handling

The unit will be supplied within shipping base and protectivepackaging over the unit casing. The packaging should be kepton the unit during handling or storage on site.

If it is necessary to remove the packaging for inspection priorto completion of on site handling, retain packaging parts andreapply them by tapping in position to prevent damage to thecasing. TTVs are supplied with a shipping base which is suitablefor handling by a fork lift truck. If it is necessary to sling theunit, use spreader bars under the shipping base, ensure thatropes do not cause abrasion to the surface of the unit.

( i )© American Standard Inc. 1996

Page 3: Installation TTV-IOM Operation Maintenance

Contents : Page No.

Model Number Description 1

General Data - Indoor Unit 2

Unit Installation - TTV 3 - 4

Operation / Start - up 5

Maintenance 6 - 7

Dimensional Data 8 - 17

Wiring Diagram 18

( ii )

Page 4: Installation TTV-IOM Operation Maintenance

1

MODEL�NUMBER�DESCRIPTION

T T V 2 5 0 A D 0 1 A 0 A 0 0 D1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16

Digit 1, 2, 3 = Airflow ConfigurationV = Vertical Discharge

Digit 4, 5, 6 = Nominal Gross Capacity (MBH)

Digit 7 = Major Design Sequence

Digit 8 = Electrical Rating / Utilization RangeD = 380-415V/3Ph/50Hz

Digit 9 = Motor Control0 = None1 = DOL Starter

Digit 10 = Factory Installed Options0 = No Motor and Drive1 = 3.7 Supply Fan Motor kW2 = 5.5 Supply Fan Motor kW3 = 7.5 Supply Fan Motor kW4 = 11 Supply Fan Motor kW5 = 15 Supply Fan Motor kW

Digit 11 = Minor Design Sequence

Digit 120 = No Discharge Plenum1 = With Discharge Plenum (For TTV250&300)

Digit 13A = Internal Filter Rack ; 1” FilterB = External Filter Rack ; 2” FilterC = Internal Filter Rack ; 1” Filter with Decorative Return Air Grille

Digit 14, 15 = Future Use

Digit 16 = Service

MOTOR SIZEMODEL STANDARD OVER SIZE - 1 OVER SIZE - 2TTV250 5 hp (3.7 kW) 7.5 hp (5.5 kW) 10 hp (7.5 kW)TTV300 7.5 hp (5.5 kW) 10 hp (7.5 kW) 15 hp (11 kW)TTV400 7.5 hp (5.5 kW) 10 hp (7.5 kW) 15 hp (11 kW)TTV500 10 hp (7.5 kW) 15 hp (11 kW) 20 hp (15 kW)TTV600 15 hp (11 kW) 20 hp (15 kW) ---------------

Page 5: Installation TTV-IOM Operation Maintenance

2

General Data Indoor Unit

UNIT MODELS TTV250 TTV300 TTV400 TTV500 TTV600POWER CONNECTION V/ph/Hz 380-415/3/50 380-415/3/50 380-415/3/50 380-415/3/50 380-415/3/50

MCA1 A 9.4 14.6 14.6 18.2 26.6

SYSTEM DATARefrigerant Type R22 R22 R22 R22 R22Refrigerant Connection Type Brazed Brazed Brazed Brazed BrazedSuction Line OD in (mm) 2 1/8 (53.98) 1 5/8 (41.28) 2 1/8 (53.98) 2 1/8 (53.98) 2 1/8 (53.98)Liquid line OD in (mm) 5/8 (15.88) 7/8 (22.23) 1 1/8 (28.58) 1 1/8 (28.58) 1 1/8 (28.58)

COILFace Area sq ft (m2) 16.7 (1.55) 19.2 (1.78) 25.6 (2.38) 34.8 (3.24) 38.0 (3.53)Tube Size OD in (mm) 3/8 (9.53) 3/8 (9.53) 3/8 (9.53) 1/2 (12.7) 1/2 (12.7)Rows 3 3 3 4 4Fins per inch 12 12 12 12 12Refrigerant Flow Control Expansion Valve Expansion Valve Expansion Valve Expansion Valve Expansion ValveDrain Connection Size in (mm) 1 1/4 (31.8) 1 1/4 (31.8) 1 1/4 (31.8) 1 1/4 (31.8) 1 1/4 (31.8)

FANFan Type Centrifugal FC Centrifugal FC Centrifugal FC Centrifugal FC Centrifugal FCNo. used 1 1 2 2 2Diameter in (mm) 15.7 (400) 15.7 (400) 15.4 (390) 17.7 (450) 17.7 (450)Width in (mm) 12.6 (320) 12.6 (320) 15.4 (390) 14.2 (360) 14.2 (360)Fixed Drive Type Belt and Pulley Belt and Pulley Belt and Pulley Belt and Pulley Belt and PulleyFan Pulley Pitch Diameter in 9 10 11 13 13Fan Speed - Std.(Factory set) rpm 828 870 923 725 780 Max. Allowable rpm 1,100 1,100 1,200 1,000 1,000Airflow2 cfm (cmh) - Nominal 7,760 (13,180) 9,240 (15,700) 12,120 (20,590) 15,130 (25,700) 18,080 (30,720) - Max. 8,900 (15,120) 10,600 (18,000) 13,800 (23,445) 16,700 (28,370) 21,800 (37,040) - Min. 5,900 (10,000) 7,000 (11,890) 9,100 (15,460) 11,000 (18,690) 14,400 (24,465)

MOTORMotor Type TEFCNo. of Motor 1 1 1 1 1Motor hp - Std. hp (kW) 5 (3.7) 7.5 (5.5) 7.5 (5.5) 10 (7.5) 15 (11) Hi Static 7.5 (5.5) / 10 (7.5) 10 (7.5) / 15 (11) 10 (7.5) / 15 (11) 15 (11) / 20 (15) 20 (15)No. of Speed 1 1 1 1 1ESP including filters in.wg 1 1 1.2 1.2 1.2Motor Pulley Pitch Diameter in 5 6 7 6.5 7V/ph/Hz 380-415/3/50RLA/LRA 7.5/53.5 11.64/93 11.64/93 14.53/116 21.25/168

FILTERType Washable Washable Washable Washable WashableNo. used 8 9 9 12 9Size (WxLxD) - Std. in 16 x 20 x 1 4 - 15 x 20 x 1 6 - 16 x 25 x 1 2 - 16 x 20 x 1 3 - 20 x 20 x 1

2 - 16 x 20 x 1 3 - 20 x 25 x 1 6 - 16 x 25 x 1 6 - 20 x 25 x 11 - 16 x 25 x 1 1 - 20 x 25 x 12 - 15 x 25 x 1 3 - 25 x 25 x 1

DIMENSION (HxWxD)Uncrated (Net) mm 1219 x 1808 x 1040 1372 x 1808 x 1040 1520 x 2088 x 1040 1653 x 2596 x 1275 1777 x 2596 x 1275

WEIGHTUncrated (Net) kg (lbs) 353 (778) 421 (928) 487 (1073) 685 (1510) 749 (1651)

1 MCA - Minimum Circuit Ampacity ; calculated as follow : 125% of heater R.L Amps plus the fan motor R.L Amps.2 CFM is rated with standard air-dry coil.

Page 6: Installation TTV-IOM Operation Maintenance

3

Unit Installation TTV

WARNING: OPEN AND LOCK UNIT DISCONNECTTO PREVENT INJURY OR DEATH FROM ELECTRICSHOCK OR CONTACT WITH MOVING PARTS BEFOREATTEMPTING ANY INSTALLATION OR MAINTENANCE.

The general location of the air handler is normally selected bythe architect, contractor, and/or buyer. For proper installationthe following items must be considered.1. Available power supply must agree with electrical data on

component nameplate.2. Air handlers shipped wired for 380 - 450 Volt application.3. If external accessories are installed on the unit, additional

clearance must be provided.4. All duct work should be properly insulated to prevent

condensation and heat loss.

Note: It is recommended that the outline drawings on page bestudied and dimensions properly noted and checked againstselected installation site.

Important: If adding external accessories to the unit, additionalclearance must be considered for the overall space needed.

For Installation of accessories available for this air handler,follow the instructions packed with each accessory.

Lifting Recommendations

Before preparing the unit for lifting, the center of gravity shouldbe determined for lifting safety. Because of the placement ofinternal components, the unit weight may be unevenlydistributed.

WARNING: ON SITE LIFTING EQUIPMENT MUST BECAPABLE OF LIFTING THE WEIGHT OF THE UNIT WITHAN ADEQUATE SAFETY FACTOR. THE USE OF UNDER-CAPACITY LIFTING DEVICES MAY RESULT INPERSONAL INJURY OR DEATH AND CAUSE DAMAGETO THE UNIT.

The unit can be moved using a forklift of suitable capacity. Forlifting the unit into an elevated mounting position, run liftingstraps or slings under the unit and attach securely to the liftingdevice. Use spreader bars to protect the unit casing fromdamage. Test lift the unit to determine proper balance andstability.

Caution: Use spreader bars to prevent straps from damagingthe unit. Install the bar between lifting straps, both underneaththe unit and above the unit. This will prevent the straps fromcrushing the unit cabinet or damaging the unit finish.

All units must be mounted level to assure properdrainage and operation.

Vertical - Floor Mounting

It is generally recommended that the unit be mounted on asub-base so that adequate height can be provided for acondensate drain trap. However if adequate drainage can beprovided, the unit may be mounted directly on the floor. It isrecommended that either a polyurethane or thin rubber gasketbe applied to the unit base to prevent paint damage andsubsequent corrosion.

Before installing any unit make sure proper preparation hasbeen made at each unit location for piping and electricalconnections.

Allow adequate space for the unit and free air or serviceclearance. All TTVs can be installed back to the wall. Serviceclearance required is 1m at both left and right hand sides ofthe TTV, 1m in front of the coil is minimum recommended airflowclearance.

(c) Coil piping connections

All refrigerant piping connection are made inside the unit, toprevent from shipping damage. Connections to outdoor unitscan be made from the left or right hand side of the TTV.

Caution: Protect adjacent surfaces from heat damage, whenbrazing around the air handler.

Caution: These air handlers are shipped with a holding chargeof N2 until refrigerant lines are ready to be connected.

All refrigerant piping should be insulated.As TXVs, sensing bulbs and equalizing lines are easily damageby heat, ensure sufficient cooling [with damp cloth] is givenwhen brazing in suction / liquid lines to outdoor unit. Sightglass are not factory provided. Braze in to the liquid line outsidethe TTV.

Important: Ensure that the refrigerant lines passing throughthe cabinet are not resting on sharp sheet metal edges.

Installation, brazing, leak testing, and evacuation ofrefrigeration lines are covered in the installation instructionspackaged with the outdoor unit. Read the instruction beforebeginning installation of refrigerant lines.

Page 7: Installation TTV-IOM Operation Maintenance

4

Condensate Drain Connections

These air handlers come standard with insulated drain pans.The drain can be run through the right hand or left handconnections on the unit sides as required.

Figure 1 - Condensate Drain Evacuation U-trap

• H •, This dimension must be 15 mm at least plus totalstatic pressure.

Filters

Air handlers are shipped with 1’washable filters installed inthe unit. For filter dimensions, refer to page 2. Filters shall beaccessible from the front coil access panel. With ducted returnsystems ensure sufficient access is given for filter change.Optional side access filter rack allows side access and 2” filtercapability.

Duct Connections

The supply and return ducts should be connected to the unitwith flame retardant duct connectors and the use of flexibleconnectors is recommended for all duct connections in orderto reduce vibration transmission. The return duct should besized to the same dimensions as the return inlet of the unit.

H

Drain plug

Coll section

If rigid ductwork is to be attached to the fan section, it must beflaged and fitted with screws into the fan section dischargeface as shown in Figure 2.

Figure 2 : Duct Connection

Electrical Connections

WARNING: WHEN INSTALLING OR SERVICING THISEQUIPMENT, ALWAYS EXERCISE BASIC SAFETYPRECAUTIONS TO AVOID THE POSSIBILITY OFELECTRIC SHOCK THAT COULD RESULT IN SEVEREPERSONAL INJURY OR DEATH.

1. All electrical lines, sizing, protection and grounding mustbe in accordance with the National Electric Code and localcodes.

2. If conduit is used, isolate whenever vibration transmissionmay cause a noise problem within the building structure.

3. Ensure all connections are tight and no wires exposed.

4. All accessories must be installed and wired according tothe instructions packaged with that accessory.

Page 8: Installation TTV-IOM Operation Maintenance

5

Operation / Start-Up

Preparation

Perform the following checks and inspections before operatingthe unit:

Inspection Checklist

Duckwork connections are complete and insulated.

Coil connections are complete and tight.

Condensate drain pan connections are complete andtight.

Electrical connections completed. Wiring is correct andin accordance with the wiring diagram, with all connectionssecure.

Ground connection completed.

Check and retighten if necessary set screws on the drive,fan pulley, fan bearings and wheel.

Rotate fan by hand, to ensure that it runs freely and thatthere is no interference.

Check that fan is centrally located in the housing, axiallyand radially.

Check and retighten, if necessary, drive and bearing bolts,motor clamp plate bolts and isolator bolts.

Check to ensure that pulley are correctly aligned and thatshafts are parallel.

Check belt tension as per instruction given in themaintenance section.

Start-Up Procedures

After completing all installation work, the unit may bestarted and the following checks and adjustmentsperformed:

a. Measure the motor voltage and amps on all phases to insureproper operation. Compare these readings with the motornameplate.

b. Disconnect load and start motor to check the direction ofrotation. If the rotation need to be changed, stop the motorcompletely and change the direction of rotation.

c. After connecting the load, the motor should start quicklyand run smoothly. If it does not, the power supply should beswitched off at once and all connections, as well as thepower supply, be re-checked before re-starting.

d. In the event of excessive vibrations or unusual noises, themotor should be disconnected from the load and checkedfor poor alignment, loose mounting bolts, etc.

e. When the motor has been operated under load for a shortperiod of time, check that the operating current tally withthe nameplate current.

Page 9: Installation TTV-IOM Operation Maintenance

6

Maintenance

WARNING: DISCONNECT ELECTRICAL POWERSOURCE AND SECURE IN DISCONNECTED POSITIONBEFORE SERVICING THE UNIT. FAILURE TO DO SO MAYRESULT IN PERSONAL INJURY OR DEATH FROMELECTRICAL SHOCK.

Monthly Inspection

1. Check condition of air filters and replace them if necessary.

2. Check the drain pan to be sure that it is clean and free tocarry the flow of condensate through the drain line.

3. Check the coil surface for cleanliness. Clean if necessary.

Yearly Inspection

1. Replace filters.

2. Check coil surface. Clean by vaccuming or flushing withcold water. Do not use steam or hot water. High pressuremay damage coil.

3. Carry out checks as detailed in inspection checklist in theOperation Section.

4. Inspect the condition of the evaporator fan belt and replaceif necessary. The belts fitted to TTV units cannot achievedesign performance without the correct tensioning.

5. Check condition of vibration isolators, replace if there is anysign of wear, loosening or material deterioration.

6. Check fan bearings for noisy operation and excessivelubricant leakage. Replace if necessary.

7. Inspect the condensate drain pan and condensate pipingto make sure they are clear and will carry away all water.

8. Inspect the control panel wiring to make sure connectionsare tight and insulation is intact.

Change / Clean Filters

Change or clean air filters at least twice a year. Filters willrequire more frequent care under high load conditions or dirtyair. A clogged air filters reduces airflow, cooling capacity andincreases energy usage.

To clean permanent filters, remove the filter media and wash itin water to remove dust, dirt and lint; allow to dry thoroughlybefore re-installing in the units. Do not rub or wring.

Permanent filters can also be cleaned by blowing withcompressed air in opposite direction of filter airflow.

Belt Maintenance

Clean fan belts and pullies with a dry cloth. Oil and greasemust be kept off belts. The use of a belt dressing is notrecommended. When replacing belts, use a matched set.

Do not force belts onto pullies, but adjust motor position toallow mounting and then re-tighten.

Figure 3 : Belt Tension Measurement

To measure belt tension, use a belt tensioner as shown inFigure 3. Determine actual deflection by depressing one beltwith the belt tensioner and then adjust the belt tension to thecorrect pounds force and tighten all setscrews to the propertorques.

Deflection

Force

Span

Page 10: Installation TTV-IOM Operation Maintenance

7

Evaporator Fan Motor

Continuity test

Open the unit isolating switch and remove the leads from theterminals of the motor. Test continuity of the windings by placingthe probes of an ohmeter against each two terminalcombinations. Meter readings should be obtained across anytwo of the three terminals and each of the readings should beapproximately equal.

Earthed motor

Place one of the test leads of an insulation tester or meggeragainst bare metal and another on each of the motor terminalsin turn. The reading obtained should be in the range 2 megohmto infinity. If the reading is substantially below this range anearthed winding is indicated.

Unit supply voltage.

Voltage at the unit terminals must be within plus or minus 10%of the nominal nameplate rating. Measure the voltage whilethe motor is starling to determine if the voltage drops belowthe minimum value during starting surge. Check voltage atmotor terminals rather than at the isolation switch to detemineif the main supply, loose terminals or defective wiring is causingvoltage problems.

Voltage imbalance

Voltage unbalance on three phase systems can cause motoroverheating and eventual failure.Maximum allowable imbalance is 2.5%. Voltage imbalance isdefined as the sum of the deviation of the three voltages fromthe average without regard to sign, divided by twice the averagevoltage, e.g. if the three measured voltages are 380, 398 and400, the average voltage will be:

Then the percentage imbalance will be

398+400+380 = 393V

3

In this example. 3.2% imbalance is not acceptable and thelocal electricity board should be notified to correct it. This muchvoltage imbalance could result in as much as 20% currentimbalance and an increase in the motor winding temperature.This results in decrease motor life.

Figure 4 : Contactor test Procedure

Contactor

1. Inspect the contacts. If they appear to be pitted or burnedreplace the contactor.

2. Using the ohmmeter, test continuity of the contactor holdingcoil. If the coil does not test continuous, replace it.

3. To test the contactor for continuous circuit:a. Remove the fan motor leads from the contactor.b. Energise the contactor.c. Visually note if the contacts are closed or test with a

voltmeter across terminal, 1-4, 1-6 and 3-2 (see figure4)

4. Test for voltage drop:a. With the fan motor connected to the contactor, energise

the contactor.b. Take readings across terminals 1-2, 3-4 and 5-6.c. A zero voltage reading indicates no voltage drop. If any

reading is obtained, a voltage drop exists and should becorrected. Inspect the contacts and replace if necessary.

1 3 5

2 4 6

100 x (393-380) + (398-393) + (400-393)

2x393

= 3.2%

Page 11: Installation TTV-IOM Operation Maintenance

8

Dimensional DataDX Air Handling unit TTV 250

SIDE VIEW

REAR VIEW

16" X 20" 16" X 20" 16" X 20" 16" X 20"

16" X 20"16" X 20"16" X 20"16" X 20"

1219

13

507

507

1008

1040

17741808

588.5 588.5

COIL

REAR

FRONT

38 DIA. KNOCKOUT FORPOWER SUPPLY AND CONTROL

CO

IL

FIL

TE

RF

ILT

ER 11

67

232342

512622

FAN

MOTOR

CO

IL

2-1/8" SUCTION LINE5/8" LIQUID LINE

1-1/4" DRAIN PIPE

861.5

50

CLEARANCERECOMMENDED750

RECOMMENDEDCLEARANCE

750

CLEA

RANC

ERE

COM

MEN

DED

750

RECO

MM

ENDE

DCL

EARA

NCE

750

TOP VIEW

SIDE VIEW

16" X 20" 16" X 20" 16" X 20" 16" X 20"

16" X 20"16" X 20"16" X 20"16" X 20"

1219

13

1008

1040

COIL

TOP VIEW

FIL

TE

RF

ILT

ER 11

67

232342

512622

FAN

MOTOR

CO

IL

2-1/8" SUCTION LINE5/8" LIQUID LINE

1-1/4" DRAIN PIPE

861.5

507

507

17741808

588.5 588.5

269

750RECOMMENDEDCLEARANCE

750

CLEARANCERECOMMENDED

CLEA

RANC

ERE

COM

MEN

DED

750

RECO

MM

ENDE

DCL

EARA

NCE

38 DIA. KNOCKOUT FORPOWER SUPPLY AND CONTROL

750

REAR VIEW

REAR

FRONT

CO

IL

FAN ARRANGEMENT 1

FAN ARRANGEMENT 2

Page 12: Installation TTV-IOM Operation Maintenance

9

Dimensional DataDX Air Handling unit TTV 250Dimensional DataDX Air Handling unit TTV 250

FAN ARRANGEMENT 3

FAN ARRANGEMENT 4

SIDE VIEW

16" X 20" 16" X 20" 16" X 20" 16" X 20"

16" X 20"16" X 20"16" X 20"16" X 20"

1219

13

1008

1040

COIL

TOP VIEW

CO

IL

FIL

TE

RF

ILT

ER 11

67

232342

512622

FAN

MOTOR

CO

IL

2-1/8" SUCTION LINE5/8" LIQUID LINE

1-1/4" DRAIN PIPE

861.5

50717741808

45

633.5 633.5

51

750RECOMMENDEDCLEARANCE

750

CLEARANCERECOMMENDED

RECO

MM

ENDE

DCL

EARA

NCE

38 DIA. KNOCKOUT FORPOWER SUPPLY AND CONTROL

750

REAR VIEW

REAR

FRONT

SIDE VIEW

16" X 20" 16" X 20" 16" X 20" 16" X 20"

16" X 20"16" X 20"16" X 20"16" X 20"

1219

13

1008

1040

COIL

TOP VIEW

CO

IL

FIL

TE

RF

ILT

ER 11

67

232342

512622

FAN

MOTOR

CO

IL

2-1/8" SUCTION LINE5/8" LIQUID LINE

1-1/4" DRAIN PIPE

861.5

50717741808

633.5 633.5

51

246

750RECOMMENDEDCLEARANCE

750

CLEARANCERECOMMENDED

RECO

MM

ENDE

DCL

EARA

NCE

38 DIA. KNOCKOUT FORPOWER SUPPLY AND CONTROL

750

REAR VIEW

REAR

FRONT

Page 13: Installation TTV-IOM Operation Maintenance

10

Dimensional DataDX Air Handling unit TTV 300

FAN ARRANGEMENT 1

FAN ARRANGEMENT 2

SIDE VIEW

16" X 20" 16" X 20" 16" X 25"

15" X 25"15" X 20"15" X 20"

1372

13

517

517

1008

1040

17741808

583.5 583.5

COIL

CO

IL

FIL

TE

RF

ILT

ER

1320

232342

512622

FAN

MOTOR

CO

IL

2-1/8" SUCTION LINE7/8" LIQUID LINE

1-1/4" DRAIN PIPE

15" X 25"15" X 20"15" X 20"

FIL

TE

R

861.5

50

750RECOMMENDEDCLEARANCE

750

CLEARANCERECOMMENDED

CLEA

RANC

ERE

COM

MEN

DED

750

RECO

MM

ENDE

DCL

EARA

NCE

38 DIA. KNOCKOUT FORPOWER SUPPLY AND CONTROL

750

TOP VIEW

REAR VIEW

REAR

FRONT

SIDE VIEW

16" X 20" 16" X 20" 16" X 25"

15" X 25"15" X 20"15" X 20"

1372

13

1008

1040

CO

IL

FIL

TE

RF

ILT

ER

1320

232342

512622

FA

MOTOR

CO

IL

2-1/8" SUCTION LINE7/8" LIQUID LINE

1-1/4" DRAIN PIPE

15" X 25"15" X 20"15" X 20"

FIL

TE

R

861.5

507

507

17741808

588.5 588.5

269

750RECOMMENDEDCLEARANCE

750

CLEARANCERECOMMENDED

CLEA

RANC

ERE

COM

MEN

DED

750

RECO

MM

ENDE

DCL

EARA

NCE

38 DIA. KNOCKOUT FORPOWER SUPPLY AND CONTROL

750

COIL

TOP VIEW

REAR VIEW

REAR

FRONT

Page 14: Installation TTV-IOM Operation Maintenance

11

Dimensional DataDX Air Handling unit TTV 300

FAN ARRANGEMENT 3

FAN ARRANGEMENT 4

SIDE VIEW

16" X 20" 16" X 20" 16" X 25"

15" X 25"15" X 20"15" X 20"

1372

13

1008

1040

CO

IL

FIL

TE

RF

ILT

ER

1320

232342

512622

FAN

MOTOR

CO

IL

2-1/8" SUCTION LINE7/8" LIQUID LINE

1-1/4" DRAIN PIPE

15" X 25"15" X 20"15" X 20"

FIL

TE

R

861.5

50717741808

45

633.5 633.5

51

750RECOMMENDEDCLEARANCE

750

CLEARANCERECOMMENDED

RECO

MM

ENDE

DCL

EARA

NCE

38 DIA. KNOCKOUT FORPOWER SUPPLY AND CONTROL

750

COIL

TOP VIEW

REAR VIEW

REAR

FRONT

SIDE VIEW

16" X 20" 16" X 20" 16" X 25"

15" X 25"15" X 20"15" X 20"

1372

13

1008

1040

FIL

TE

RF

ILT

ER

1320

232342

512622

FAN

MOTOR

CO

IL

2-1/8" SUCTION LINE7/8" LIQUID LINE

1-1/4" DRAIN PIPE

15" X 25"15" X 20"15" X 20"

FIL

TE

R

861.5

50717741808

633.5 633.5

51

246

750RECOMMENDEDCLEARANCE

750

CLEARANCERECOMMENDED

CLEA

RANC

ERE

COM

MEN

DED

750

RECO

MM

ENDE

DCL

EARA

NCE

38 DIA. KNOCKOUT FORPOWER SUPPLY AND CONTROL

750

COIL

TOP VIEW

REAR VIEW

REAR

FRONT

CO

IL

Page 15: Installation TTV-IOM Operation Maintenance

12

Dimensional DataDX Air Handling unit TTV 400

FAN ARRANGEMENT 1

FAN ARRANGEMENT 2

SIDE VIEW

REAR VIEW

20" X 25"

16" X 25"

1520

1008

1040

COIL

FRONT

REAR

TOP VIEW

CO

IL

FIL

TE

RF

ILT

ER

1468

232342

512622

FAN

MOTOR

2-1/8" SUCTION LINE1-1/8" LIQUID LINE

1-1/4" DRAIN PIPE

FIL

TE

R

16" X 25"

20" X 25"

16" X 25"

16" X 25"

20" X 25"

16" X 25"

16" X 25"

861.5

CO

IL

48120542088

316 370 481 316

414

46

52

ISOMETRIC VIEW

CLEARANCERECOMMENDED750 750

CLEARANCERECOMMENDED

RECO

MM

ENDE

DCL

EARA

NCE

750

RECO

MM

ENDE

DCL

EARA

NCE

750

38 DIA. KNOCKOUT FORPOWER SUPPLY AND CONTROL

SIDE VIEW

REAR VIEW

20" X 25"

16" X 25"

1520

481

1008

1040

20542088

316

COIL

FRONT

REAR

TOP VIEW

CO

IL

FIL

TE

RF

ILT

ER

1468

232342

512622

FAN

MOTOR

2-1/8" SUCTION LINE1-1/8" LIQUID LINE

1-1/4" DRAIN PIPE

FIL

TE

R

16" X 25"

20" X 25"

16" X 25"

16" X 25"

20" X 25"

16" X 25"

16" X 25"

370 481 316

414

254.

5

861.5

CO

IL

CLEARANCERECOMMENDED750 750

CLEARANCERECOMMENDED

RECO

MM

ENDE

DCL

EARA

NCE

750

RECO

MM

ENDE

DCL

EARA

NCE

750

38 DIA. KNOCKOUT FORPOWER SUPPLY AND CONTROL

Page 16: Installation TTV-IOM Operation Maintenance

13

Dimensional DataDX Air Handling unit TTV 400

FAN ARRANGEMENT 3

FAN ARRANGEMENT 4

SIDE VIEW

REAR VIEW

20" X 25"

16" X 25"

1520

1008

1040

COIL

FRONT

REAR

TOP VIEW

CO

IL

FIL

TE

RF

ILT

ER

1468

232342

512622

MOTOR

2-1/8" SUCTION LINE1-1/8" LIQUID LINE

1-1/4" DRAIN PIPE

FIL

TE

R

16" X 25"

20" X 25"

16" X 25"

16" X 25"

20" X 25"

16" X 25"

16" X 25"

861.5

CO

IL

48120542088

FAN

370 481

735.

5

46

361 361

67

CLEARANCERECOMMENDED750 750

CLEARANCERECOMMENDED

RECO

MM

ENDE

DCL

EARA

NCE

750

38 DIA. KNOCKOUT FORPOWER SUPPLY AND CONTROL

SIDE VIEW

REAR VIEW

20" X 25"

16" X 25"

1520

1008

1040

COIL

FRONT

REAR

TOP VIEW

CO

IL

FIL

TE

RF

ILT

ER

1468

232342

512622

MOTOR

2-1/8" SUCTION LINE1-1/8" LIQUID LINE

1-1/4" DRAIN PIPE

FIL

TE

R

16" X 25"

20" X 25"

16" X 25"

16" X 25"

20" X 25"

16" X 25"

16" X 25"

861.5

CO

IL

48120542088

370 481

735.

5

361 361

67

FAN

213.

5

CLEARANCERECOMMENDED750 750

CLEARANCERECOMMENDED

RECO

MM

ENDE

DCL

EARA

NCE

750

38 DIA. KNOCKOUT FORPOWER SUPPLY AND CONTROL

Page 17: Installation TTV-IOM Operation Maintenance

14

Dimensional DataDX Air Handling unit TTV 500

FAN ARRANGEMENT 1

FAN ARRANGEMENT 2

SIDE VIEW

REAR VIEW

25" X 25"

16" X 25"

1653

1241

1275

COIL

FRONT

REAR

TOP VIEW

TO

P C

OIL

FIL

TE

RF

ILT

ER

1601

461571

741851

FAN

MOTOR

2-1/8" SUCTION LINE1-1/8" LIQUID LINE

1-1/4" DRAIN PIPEF

ILT

ER

16" X 25"

25" X 25"

16" X 25"

16" X 25"

20" X 25"

16" X 20"

16" X 20"

BO

TT

OM

CO

IL

16" X 25"

16" X 25"

25" X 25"

1090.5

BO

TT

OM

CO

ILT

OP

CO

IL569

25622596

441 569 441

569

52.5

452

ISOMETRIC VIEW

CLEARANCERECOMMENDED750 750

CLEARANCERECOMMENDED

RECO

MM

ENDE

DCL

EARA

NCE

750

RECO

MM

ENDE

DCL

EARA

NCE

750

38 DIA. KNOCKOUT FORPOWER SUPPLY AND CONTROL

SIDE VIEW

REAR VIEW

25" X 25"

16" X 25"

1653

569

1241

1275

25622596

441

COIL

FRONT

REAR

TOP VIEW

TO

P C

OIL

FIL

TE

RF

ILT

ER

1601

461571

741851

FAN

MOTOR

2-1/8" SUCTION LINE1-1/8" LIQUID LINE

1-1/4" DRAIN PIPE

FIL

TE

R

16" X 25"

25" X 25"

16" X 25"

16" X 25"

20" X 25"

16" X 20"

16" X 20"

569 441

569

299.

5

BO

TT

OM

CO

IL

16" X 25"

16" X 25"

25" X 25"

452

1090.5

BO

TT

OM

CO

ILT

OP

CO

IL

CLEARANCERECOMMENDED750 750

CLEARANCERECOMMENDED

RECO

MM

ENDE

DCL

EARA

NCE

750

RECO

MM

ENDE

DCL

EARA

NCE

750

38 DIA. KNOCKOUT FORPOWER SUPPLY AND CONTROL

Page 18: Installation TTV-IOM Operation Maintenance

15

Dimensional DataDX Air Handling unit TTV 500

FAN ARRANGEMENT 3

FAN ARRANGEMENT 4

SIDE VIEW

REAR VIEW

25" X 25"

16" X 25"

1653

1241

1275

COIL

FRONT

REAR

TOP VIEW

TO

P C

OIL

FIL

TE

RF

ILT

ER

1601

461571

741851

FAN

MOTOR

2-1/8" SUCTION LINE1-1/8" LIQUID LINE

1-1/4" DRAIN PIPE

FIL

TE

R

16" X 25"

25" X 25"

16" X 25"

16" X 25"

20" X 25"

16" X 20"

16" X 20"

BO

TT

OM

CO

IL

16" X 25"

16" X 25"

25" X 25"

1090.5

BO

TT

OM

CO

ILT

OP

CO

IL569

25622596

569452486 486

51

ISOMETRIC VIEW

CLEARANCERECOMMENDED750 750

CLEARANCERECOMMENDED

RECO

MM

ENDE

DCL

EARA

NCE

750

38 DIA. KNOCKOUT FORPOWER SUPPLY AND CONTROL

SIDE VIEW

REAR VIEW

25" X 25"

16" X 25"

1653

1241

1275

COIL

REAR

TOP VIEW

TO

P C

OIL

FIL

TE

RF

ILT

ER

1601

461571

741851

FAN

MOTOR

2-1/8" SUCTION LINE1-1/8" LIQUID LINE

1-1/4" DRAIN PIPE

FIL

TE

R

16" X 25"

25" X 25"

16" X 25"

16" X 25"

20" X 25"

16" X 20"

16" X 20"

BO

TT

OM

CO

IL

16" X 25"

16" X 25"

25" X 25"

1090.5

BO

TT

OM

CO

ILT

OP

CO

IL

56925622596

FRONT

569452486 486

301

ISOMETRIC VIEW

CLEARANCERECOMMENDED750

CLEARANCERECOMMENDED

750

RECO

MM

ENDE

DCL

EARA

NCE

750

38 DIA. KNOCKOUT FORPOWER SUPPLY AND CONTROL

Page 19: Installation TTV-IOM Operation Maintenance

16

Dimensional DataDX Air Handling unit TTV 600

FAN ARRANGEMENT 1

FAN ARRANGEMENT 2

SIDE VIEW

REAR VIEW

20" X 25"

1777

1241

1275

COIL

REAR

TOP VIEW

TO

P C

OILFIL

TE

RF

ILT

ER

1725

461571

741851

FAN

MOTOR

2-1/8" SUCTION LINE1-1/8" LIQUID LINE

1-1/4" DRAIN PIPEF

ILT

ER

20" X 25"20" X 20"

BO

TT

OM

CO

IL

20" X 25"

1090.5

BO

TT

OM

CO

ILT

OP

CO

IL

20" X 25"20" X 20" 20" X 25" 20" X 25"

20" X 25"20" X 20" 20" X 25" 20" X 25"

56925622596

441

FRONT

569 441

569

452CLEARANCERECOMMENDED750

CLEARANCERECOMMENDED

750

RECO

MM

ENDE

DCL

EARA

NCE

750

RECO

MM

ENDE

DCL

EARA

NCE

750

38 DIA. KNOCKOUT FORPOWER SUPPLY AND CONTROL

SIDE VIEW

REAR VIEW

20" X 25"

1777

1241

1275

COIL

REAR

TOP VIEW

TO

P C

OILFIL

TE

RF

ILT

ER

1725

461571

741851

FAN

MOTOR

2-1/8" SUCTION LINE1-1/8" LIQUID LINE

1-1/4" DRAIN PIPE

FIL

TE

R

20" X 25"20" X 20"

BO

TT

OM

CO

IL

20" X 25"

1090.5

BO

TT

OM

CO

ILT

OP

CO

IL

20" X 25"20" X 20" 20" X 25" 20" X 25"

20" X 25"20" X 20" 20" X 25" 20" X 25"

56925622596

441

FRONT

569 441

569

299.

5

452CLEARANCERECOMMENDED750

CLEARANCERECOMMENDED

750

RECO

MM

ENDE

DCL

EARA

NCE

750

RECO

MM

ENDE

DCL

EARA

NCE

750

38 DIA. KNOCKOUT FORPOWER SUPPLY AND CONTROL

Page 20: Installation TTV-IOM Operation Maintenance

17

Dimensional DataDX Air Handling unit TTV 600

FAN ARRANGEMENT 3

FAN ARRANGEMENT 4

SIDE VIEW

REAR VIEW

20" X 25"

1777

1241

1275

COIL

REAR

TOP VIEW

TO

P C

OILFIL

TE

RF

ILT

ER

1725

461571

741851

FAN

MOTOR

2-1/8" SUCTION LINE1-1/8" LIQUID LINE

1-1/4" DRAIN PIPEF

ILT

ER

20" X 25"20" X 20"

BO

TT

OM

CO

IL

20" X 25"

1090.5

BO

TT

OM

CO

ILT

OP

CO

IL

20" X 25"20" X 20" 20" X 25" 20" X 25"

20" X 25"20" X 20" 20" X 25" 20" X 25"

FRONT

56925622596

569452

51

486 486CLEARANCERECOMMENDED750

CLEARANCERECOMMENDED

750

RECO

MM

ENDE

DCL

EARA

NCE

750

38 DIA. KNOCKOUT FORPOWER SUPPLY AND CONTROL

SIDE VIEW

REAR VIEW

20" X 25"

1777

1241

1275

COIL

REAR

TOP VIEW

TO

P C

OILFIL

TE

RF

ILT

ER

1725

461571

741851

FAN

MOTOR

2-1/8" SUCTION 1-1/8" LIQUID LINE

1-1/4" DRAIN

FIL

TE

R

20" X 25"20" X 20"

BO

TT

OM

CO

IL

20" X 25"

1090.5

BO

TT

OM

CO

ILT

OP

CO

IL

20" X 25"20" X 20" 20" X 25" 20" X 25"

20" X 25"20" X 20" 20" X 25" 20" X 25"

56925622596

FRONT

569452

30

486 486CLEARANCERECOMMENDED750

CLEARANCERECOMMENDED

750

RECO

MM

ENDE

DCL

EARA

NCE

750

38 DIA. KNOCKOUT FORPOWER SUPPLY AND CONTROL

Page 21: Installation TTV-IOM Operation Maintenance

18

Wiring Diagram TTV 250 / 600

WITH DOL STARTER

WITHOUT STARTER

L3

L2

L1

TB2

TB1

L1380-415V/3 PHASE/50 Hz

FUSEDDISCONNECT

SWITCH

L2 L3

L3L2L1

EVF–OL

240 VAC

EVF–C

EVFMTR

IMPORTANT

WARNING

NOTES:1 DASHED LINES INDICATE RECOMMENDED FIELD

WIRING BY OTHERS. DASHED LINE ENCLOSURESAND/OR DASHED DEVICE OUTLINES INDICATECOMPONENTS PROVIDED BY THE FIELD. PHANTOMLINE ENCLOSURES INDICATE ALTERNATECIRCUITRY OR AVAILABLE SALES OPTIONS.SOLID LINE INDICATES FACTORY WIRING.

LEGENDDEVICE

DESCRIPTIONDESIGNATION

MTR FAN MOTOR

EVF-C EVAP. FAN CONTACTOR.

TB TERMINAL BLOCK

L1,L2,L3 LINE VOLTAGES

EVF-OL EVAP. FAN O/LOAD.

S1 SYSTEM SWITCH.

HAZARDOUS VOLTAGE!

DISCONNECT ALL ELECTRIC POWERINCLUDING REMOTE DISCONNECTSBEFORE SERVICING.

FAILURE TO DISCONNECT POWERBEFORE SERVICING CAN CAUSESEVERE PERSONAL INJURY OR DEATH.

USE COPPER CONDUCTORS ONLYTO PREVENT EQUIPMENT DAMAGE.

UNIT TERMINALS ARE NOT DESIGNEDTO ACCEPT ANY OTHER WIRING.

1B

J3 J2

J1

E (G)

U1 (R)

V1 (Y)

W1 (B)

W2 (B)

U2 (R)

V2 (Y)

EVFMTR

MOTOR SIZEMODEL STANDARD OVER SIZE - 1 OVER SIZE - 2TTV250 5 hp (3.7 kW) 7.5 hp (5.5 kW) 10 hp (7.5 kW)TTV300 7.5 hp (5.5 kW) 10 hp (7.5 kW) 15 hp (11 kW)TTV400 7.5 hp (5.5 kW) 10 hp (7.5 kW) 15 hp (11 kW)TTV500 10 hp (7.5 kW) 15 hp (11 kW) 20 hp (15 kW)TTV600 15 hp (11 kW) 20 hp (15 kW) ---------------

NOTE:1. FOR DOL STARTING, TEMINATION

INTO TERMINALS U1 , V1 & W1 ONLY2. FOR STAR-DELTA STARTING,

REMOVED JUMPERS J1 , J2 & J3 ANDTERMINATE INTO TERMINALS U1 , V1, W1 , U2 , V2 & W2.

TB = TERMINAL BLOCKEVF MTR = EVAPORATOR FAN MOTOR