© 2019 tekmar 671_D - 08/19
671_D08/19
Snow Melting Replaces: New
WiFi Snow Melting Control 671Installation & Operation Manual
Features• Automaticsoftwareupdates• Automaticsnow/icedetection• Supportsbothinslab&retrofitaerialsensors• Supportsmultiplezoneswithpriority• ManualStorm• Idling
• WarmWeatherShutDown• ColdWeatherCutOff• EconoMelt• TandemSnow/IceDetection• Pumpexercising• Mobileappisscheduledtobeavailableinearly2020
IntroductionTheWiFiSnowMeltingControl671operateshydronicandelectricheatingequipmentdesignedtomeltsnowand/oricefromroadsandwalkwayssurfaces.ThecontrolworkswithtekmarSnow/IceSensor090orSnowSensor095toautomaticallydetectsnoworiceandoperatesasingleboiler,steamvalveorelectriccabletosupplyheattotheslab.
WiFi Snow Melting Control 671Pulse Width Modulation
PowerRelays
1084-02Designed and assembled in Canada
Date
Cod
eH
2058
A
Blu3
Yel4
Brn/5
SlabMan
6
MeltC7
Blk/2
ComRed1
Boiler HeatRelay
SystemPump
11 12 13Do Not Apply Power
Out10
Com9
tN48 161514
Power17
L
18
N
For product literature:Pour la documentation du produit:Para la literatura del producto:tekmarControls.com
Disconnect all power before opening.WARNING
Coupez l'alimentation avant l'ouverture.ATTENTION
Desconecte la electricidad antes de abrir.ADVERTENCIA
Signal wiring must be rated at least 300 V.Le câblage du signal doit être d'une capacité d'au moins 300 V.Cableado de señal debe tener unacalificación mínima de 300 V.
Contains WiFi transceiver:FCC ID: Z64-CC3100M0DR1Meets FCC Part 15BIC: 4511-CC3100M0DR1Meets CAN ICES-3 (B)/NMB-3(B)
115 V (ac) ±10%, 60 Hz, 20 VA230 V (ac) 5 A 1/3 hp
This is a hole
Manual Melt
Time Left- - : - - hrs
Outdoor32 °F
Settings Status
System is Melting
Stop
10:30 AM
Warming Up
2of36© 2019 tekmar 671_D - 08/19
Table of Contents
Getting Started
ImportantSafetyInformation.............................................3Installation.........................................................................4
Preparation.................................................................... 4PackagingContents...................................................... 4PhysicalDimensions..................................................... 4InstallationLocation....................................................... 4InstallingtheEnclosure................................................. 5Rough-InWiring............................................................. 6SensorWiring................................................................ 7tekmarNet...................................................................... 9ManualMeltInput.......................................................... 9TestingtheSensorWiring............................................ 11TestingtheControlWiring............................................ 11ManualOverride–MaximumHeat.............................. 12ManualOverride–Purge............................................. 12ManualOverride–Test................................................ 12ManualOverride–Off.................................................. 12AccessLevels............................................................... 12
UserInterface...................................................................13HomeScreen................................................................ 13SystemOperation......................................................... 13Symbols........................................................................ 14HelpScreen.................................................................. 14StatusMenuNavigation............................................... 14SystemStatusMenu.................................................... 15SlabStatusScreen....................................................... 15WeatherStatusScreen................................................ 16SettingsMenuNavigation............................................ 16TempMenu................................................................... 18AwayMenu................................................................... 19DisplayMenu................................................................ 19WiFiMenu..................................................................... 20TimeMenu.................................................................... 20EnergyMenu................................................................ 21MonitorMenu................................................................ 21Setup–SystemSetupMenu........................................ 22Setup–BoilerSetupMenu.......................................... 22tekmarNetMenu........................................................... 23ToolboxMenu............................................................... 24OverrideMenu.............................................................. 24
SequenceofOperation....................................................25SnowMeltingOverview................................................ 25
Melt–AutomaticStartandStop.................................. 25Melt–EconoMelt.......................................................... 26AdditionalMeltingTime................................................ 26Melt–AutomaticStartandTimedStop....................... 26TandemSnow/IceDetection........................................ 27Melt–ManualStartandTimedStop........................... 27Melt-TrackedStartandStop...................................... 27IdleOperation............................................................... 28StormOperation........................................................... 28SlabTemperatureControl............................................ 29SnowMeltZonesandPriority...................................... 29WarmWeatherShutDown........................................... 31ColdWeatherCutOff................................................... 31TimeClock.................................................................... 31AwayOperation............................................................ 31tekmarNetSceneOperation......................................... 31PulseWidthModulationZoneOperation..................... 32BoilerOperation............................................................ 32OutdoorSensor............................................................ 33Exercising..................................................................... 33PostPurge.................................................................... 33
Troubleshooting............................................................... 33ErrorMessages(1of2)................................................ 33ErrorMessages(2of2)................................................ 34FrequentlyAskedQuestions........................................ 35
TechnicalData................................................................. 36LimitedWarrantyandProductReturnProcedure........... 36
CongratulationsonthepurchaseofyournewSnowMeltingControl!Thismanualcoversthecompleteinstallation,programmingandsequenceofoperationforthiscontrol.Youwillalsofindinstructionontesting,commissioning,andtroubleshootingthecontrolandsystemthatitoperates.
© 2019 tekmar 671_D - 08/193of36
Theinstallermustensurethatthiscontrolanditswiringareisolatedand/orshieldedfromstrongsourcesofelectromagneticnoise.Conversely,thisClassBdigitalapparatuscomplieswithPart15oftheFCCRulesandmeetsallrequirementsoftheCanadianInterference-CausingEquipmentRegulations.However,ifthiscontroldoescauseharmfulinterferencetoradioortelevisionreception,whichisdeterminedbyturningthecontroloffandon,theuserisencouragedtotrytocorrect
theinterferencebyre-orientatingorrelocatingthereceivingantenna,relocatingthereceiverwithrespecttothiscontrol,and/orconnectingthecontroltoadifferentcircuitfromthattowhichthereceiverisconnected.CetappareilnumériquedelaclasseBrespectetouteslesexi-gencesduRèglementsurlematérielbrouilleurduCanada.
Radio Frequency Interference
Important Safety InformationItisyourresponsibilitytoensurethatthiscontrolissafelyinstalledaccordingtoallapplicablecodesandstandards.tekmarisnotresponsiblefordamagesresultingfromimproperinstallationand/ormaintenance.
Thisisasafety-alertsymbol.Thesafetyalertsymbolisshownaloneorusedwithasignalword(DANGER,WARNING,orCAUTION),apictorialand/orasafetymessagetoidentifyhazards.Whenyouseethissymbolaloneorwithasignalwordonyourequipmentorinthismanual,bealerttothepotentialfordeathorseriouspersonalinjury.
Thispictorialalertsyoutoelectricity,electrocution,andshockhazards.
Thissymbolidentifieshazardswhich,ifnotavoided,couldresultindeathorseriousinjury.
Thissymbolidentifieshazardswhich,ifnotavoided,couldresultinminorormoderateinjury.
Thissymbolidentifiespractices,actions,orfailuretoactwhichcouldresultinpropertydamageordamagetotheequipment.
ReadmanualandallproductlabelsBEFOREusingtheequipment.Donotuseunlessyouknowthesafeandproperoperationofthisequipment.Keepthismanualavailableforeasyaccessbyallusers.ReplacementmanualsareavailableattekmarControls.com
• Itistheinstaller’sresponsibilitytoensurethatthiscontrolissafelyinstalledaccordingtoallapplicablecodesandstandards.
• Improperinstallationandoperationofthiscontrolcouldresultindamagetotheequipmentandpossiblyevenpersonalinjuryordeath.
• Thiscontrolisnotintendedforuseasaprimarylimitcontrol.Othercontrolsthatareintendedandcertifiedassafetylimitsmustbeplacedintothecontrolcircuit.
Donotattempttoservicethecontrol.Therearenouserserviceablepartsinsidethecontrol.Attemptingtoservicethecontrolvoidsthewarranty.
4of36© 2019 tekmar 671_D - 08/19
Preparation
Tools Required-----------------------------------------------------------------------------------------• tekmarorjewelerscrewdriver• Phillipsheadscrewdriver
• Needle-nosepliers• Wirestripper
Materials Required-------------------------------------------------------------------------------------• 18AWGLVTsolidwire(low-voltageconnections)• 14AWGsolidwire(line-voltageconnections)
• Four1/8"-1"woodscrews
Installation Location
Installation
Physical Dimensions
Choosetheplacementofthecontrolearlyintheconstructionprocesstoenableproperwiringduringrough-in.
• Keepthecontroldry.Avoidpotentialleakageontothecontrol.• Maintainrelativehumiditylessthan90%inanon-condensingenvironment.• Avoidexposuretoextremetemperaturesbeyond32-122°F(0-50°C).• Installawayfromequipment,appliances,orothersourcesofelectricalinterference.• Installtoalloweasyaccessforwiring,viewing,andadjustingthedisplayscreen.• Installapproximately5feet(1.5m)offthefinishedfloor.• Locatethecontrolnearpumpsand/orzonevalvesifpossible.• Provideasolidbackingwhichtheenclosurecanbemountedto.Example:plywoodorwallstuds.• Usetheconduitknockoutsprovidedontheupper,lower,backandsidesoftheenclosureforwiring.
Packaging Contents
Thefollowingareincludedintheproductpackaging:• 1WiFiSnowMeltingControl671• 1OutdoorSensor070• 1screwdriver• 1ApplicationBrochure671_A
• 1InstallationandOperationManual671_D• 1UserManual671_U
Front View Side View
2–7/8"(72 mm)
1/2" Knock-out (x 5 back) (x 5 bottom)
Mounting Base
CL
1/2"(13 mm)
7/8"(23 mm)
6–5/8"(170 mm)
7–5/8"(193 mm)
1–7/8" (49 mm)
1/2"(14 mm)
3/16" (5 mm)
WiFi Snow Melting Control 671Pulse Width Modulation
PowerRelays
1084-02Designed and assembled in Canada
Date
Cod
eH
2058
A
Blu3
Yel4
Brn/5
SlabMan
6
MeltC7
Blk/2
ComRed1
Boiler HeatRelay
SystemPump
11 12 13Do Not Apply Power
Out10
Com9
tN48 161514
Power17
L
18
N
For product literature:Pour la documentation du produit:Para la literatura del producto:tekmarControls.com
Disconnect all power before opening.WARNING
Coupez l'alimentation avant l'ouverture.ATTENTION
Desconecte la electricidad antes de abrir.ADVERTENCIA
Signal wiring must be rated at least 300 V.Le câblage du signal doit être d'une capacité d'au moins 300 V.Cableado de señal debe tener unacalificación mínima de 300 V.
Contains WiFi transceiver:FCC ID: Z64-CC3100M0DR1Meets FCC Part 15BIC: 4511-CC3100M0DR1Meets CAN ICES-3 (B)/NMB-3(B)
115 V (ac) ±10%, 60 Hz, 20 VA230 V (ac) 5 A 1/3 hp
This is a hole
Manual Melt
Time Left- - : - - hrs
Outdoor32 °F
Settings Status
System is Melting
Stop
10:30 AM
Warming Up
© 2019 tekmar 671_D - 08/195of36
Installing the Enclosure
• Installthecontrolenclosuretoawallortoanelectricalbox.• Threewiringchamberdividersareincluded.Thedividersprovideabarriertokeeplowvoltagewiringseparatedfromline
voltagewiring.• Ifthedividersarenotused,thenlowvoltagecircuitsmustusewireratedatleast300V.
Press down at the fingertipgripsontopofthefrontcoverandpulloutanddown.
Lift thefrontcoverupandawayfromthecontrol.
Loosen the screws at thefrontofthewiringcover.
Thewiringcoverpullsstraightoutfromthewiringchamber.
Thebaseisreadyformounting.Thecontrolliftsupandawayfromthebase.
Pressthecontrolreleasecliponthebaseinsidethewiringchamberandslidethecontrolupwards.
Remove the safety dividersfrom the wiring chamber bypulling them straight out oftheirgrooves.
Thereare10conduitknock-outsatthebackandbottomofthewiringchamber.
13Mountingholes
Controlrelease
clip
Controlreleaseclip
Thecontrol canbemountedonastandardDINrail.Firstremovethecontrolfromitsbaseandthen,using the hooks and spring cliponthebackofthecontrol,mountitontotheDINrail.Thiswillbeapopularoptionforthosewhoprefertomountthecontrolinsidealargerelectricalpanel.TheDINSnapKitM9303issoldseparately.
The wiring can enter thebottomorthebackoftheenclosure.Knock-outspro-videdinthebaseallowthewiringtoberuninconduitup to the enclosure. Thebase also has holes thatlineupwith themountingholes of most commonelectricalboxes.
6of36© 2019 tekmar 671_D - 08/19
Rough-In Wiring
Low-Voltage Wiring-------------------------------------------------------------------------------------Pull two conductor 18 AWG LVT cable, up to 500 feet (150 m) long, for the following equipment:• Outdoortemperaturesensor• Boilersensor• Single-stageon/offboiler
Pull four conductor 18 AWG LVT cable, up to 500 feet (150 m) long, for the following equipment:• SnowSensor095Pull the Snow/Ice Sensor 090 or 094 cable to the control.
Line-Voltage Wiring------------------------------------------------------------------------------------Pull two conductor 14 AWG cable, up to 500 feet (150 m) long, for the following equipment:• Systempump• Boilerpump
Topreventtheriskofpersonalinjuryand/ordeath,makesurepowerisnotappliedtothecontroluntilitisfullyinstalledandreadyforfinaltesting.Allworkmustbedonewithpowertothecircuitbeingworkedonturnedoff.Pleasebeawarelocalcodesmayrequirethiscontroltobeinstalledorconnectedbyanelectrician.
• Installthesuppliedwiringcompartmentbarriersbyslidingthemintothegroovesprovidedtoisolatethelowandline-voltagewiring.
• Stripallwiringtoalengthof3/8in.or10mmforallterminals.• Acircuitbreakerorpowerdisconnectthatprovidespowertothecontrolshouldbelocatednearbyandclearlylabeled.• Refertothecurrentandvoltageratingsatthebackofthismanualbeforeconnectingdevicestothiscontrol.
© 2019 tekmar 671_D - 08/197of36
• Thetemperaturesensor(thermistor)isbuiltintothesensorenclosure.
• Theoutdoorsensorcaneitherbemounteddirectlyontoawallandthewiringshouldenterthroughthebackorbottomoftheenclosure.Donotmounttheoutdoorsensorwiththeconduitknockoutfacingupwardsbecauseraincouldentertheenclosureanddamagethesensor.
• Inordertopreventheattransmittedthroughthewallfromaffectingthesensorreading,itmaybenecessarytoinstallaninsulatingbarrierbehindtheenclosure.
• Theoutdoorsensorshouldbemountedonanorth-facingwall.Theoutdoorsensorshouldnotbeexposedtoheatsourcessuchasventilationorwindowopenings.
• Theoutdoorsensorshouldbeinstalledatanelevationabovethegroundthatwillpreventaccidentaldamageortampering.
Mounting the Outdoor Sensor--------------------------------------------------------------------------
• Connect18AWGorsimilarwiretothetwoterminalsprovidedintheenclosureandrunthewiresfromtheoutdoorsensortothecontrol.Donotrunthewiresparalleltotelephoneorpowercables.Ifthesensorwiresarelocatedinanareawithstrongsourcesofelectromagneticinterference(EMI),shieldedcableortwistedpairshouldbeusedorthewirescanberuninagroundedmetalconduit.Ifusingshieldedcable,theshieldwireshouldbeconnectedtotheComter-minalonthecontrolandnottoearthground.
• Followthesensortestinginstructionsinthismanualandconnectthewirestothecontrol.
• Replacethefrontcoverofthesensorenclosure.
Wiring the Outdoor Sensor-----------------------------------------------------------------------------
Removecoverby
slidingup-wardsaway
fromthebase.
Towirefromtheback,
removetheknock-outinthesensor
base.
S1S1
Ifusingconduit,
removetheflexibleplug
fromthebasebottom.
S1S1 Attachthe
basetothewall,soffit
orelectricalbox.
S1S1
Wires from outdoorsensor to control’soutdoor sensor andsensor commonterminals
Sensor is built intothe enclosure
Wiresfromoutdoorsensor
andsensorcommon
terminalsontekmarcontrolS1
S1
Sensor Wiring
Atthecontrol:• Connecttheoutdoorsensortoterminals9and10.
Com9
Out10
Com9
Out10
8of36© 2019 tekmar 671_D - 08/19
Snow/Ice Sensor---------------------------------------------------------------------------------------
Snow Sensor-------------------------------------------------------------------------------------------
Slab Sensor--------------------------------------------------------------------------------------------
ASnow/IceSensor090or094canbeconnectedtothecontrol.The090hasa65'(20m)cableandthe094hasa208'(63m)cable.Thecablemaybeextendedtoatotallengthof500'(150m)using18AWGcable.Anyjunctionboxesmustkeptdry.
IftheSnow/IceSensorinputisused:• Connecttheredwiretoterminal1.• Connecttheblackwiretoterminal2.• Connectthebluewiretoterminal3.• Connecttheyellowwiretoterminal4.• Connectthebrownwiretoterminal5.
ASnowSensor095canbeconnectedtothecontrol.
IftheSnowSensorinputisused:• Connecttheredwiretoterminal1.• Connecttheblackwiretoterminal2.• Connectthebluewiretoterminal3.• Connecttheyellowwiretoterminal4.
ASlabSensor072or073canbeinstalledeitheraloneortogetherwithaSnowSensor095.
IftheSlabSensorinputisused:Connecttheslabsensortoterminals2and5.
Blu3
Yel4
Brn/ 5
SlabBlk/2
ComRed1
SnowSensor
095
Blu3
Yel4
Brn/ 5
SlabBlk/2
ComRed1
Blu3
Yel4
Brn/ 5
SlabBlk/2
ComRed1
© 2019 tekmar 671_D - 08/199of36
tekmarNet
The671canbeconnectedtoothertekmarNetcommunicationcompatiblecontrolsusingthetN4bus.
IftekmarNetisused:• ConnecttN4onthe671terminal6tothetN4wiringterminalontheotherdevice.• ConnectConthe671terminal7totheCwiringterminalontheotherdevice.• tekmarNetispolaritysensitive.
other tN4 control
671
6C
7tN4 CtN4
Manual Melt Input
Themanualmeltinputallowsthecontroltobemanuallyswitchedtomeltingoperationusingaswitch.Thisconnectionisoptional.
IftheManualMeltinputisused:Connectaswitchtoterminals8and9.Theswitchmaybeeitherdry(novoltage)oravoltagesignalupto32V(ac).
ManMelt
Com 9 8
10of36© 2019 tekmar 671_D - 08/19
Wiring to a Single-Stage Boiler-------------------------------------------------------------------------
Asingle-stageboilerisenabledthroughtheT-Tcontacts.• ConnectBoilerterminals11and12totheboilerT-Tcontacts.
Stage1T T
Boiler 11 12
WR
Providea15Acircuitfortheinputpower.• Connectthe115V(ac)linewire(L)toterminal17.• Connecttheneutralwire(N)toterminal18.
N
L
Power17
L
18
N
Wiring the Input Power---------------------------------------------------------------------------------
Iftheheatrelayisoperatingapump:Thepumpcanberatedupto230V(ac),5A,1/3hpandswitchedthroughterminals13and14.Forsimplicityinwiringandtroubleshooting,aseparatebreakerforeachpumpisrecommended.• Connectthepowersourcelinewire(L)toterminal14.• Connectawirefromterminal13tothepumpL.• ConnectawirefromthepumpNbacktothepowersourceneutral.• Connectthegroundwire(G)tothepump.
Iftheheatrelayiswiredtoanelectricalcontactor:• Connectawirefromterminal13totheelectricalcontactorR.• Connectawirefromterminal14totheelectricalcontactorC.
Wiring the Heat Relay----------------------------------------------------------------------------------
Asystempumprequiringupto230V(ac),5A,1/3hpcanbeswitchedthroughterminals15and16.Forsimplicityinwiringandtroubleshooting,aseparatebreakerforeachpumpisrecommended.• Connectthepowersourcelinewire(L)toterminal16.• Connectawirefromterminal15tothepumpL.• ConnectawirefromthepumpNbacktothepowersourceneutral.• Connectthegroundwire(G)tothepump.
Wiring the System Pump-------------------------------------------------------------------------------
LNG
LNG
HeatRelay
13 14
HeatRelay
13 14
LNG
LNG
SystemPump
1615
Equipment Wiring
RC
RC
HeatRelay
13 14
Iftheheatrelayiswiredtoa24V(ac)on-offvalve:• Connectthepowersourceredwire(R)toterminal13.• Connectawirefromterminal14tothevalveR.• ConnectawirefromthevalveCtothepowersourcecommon.
© 2019 tekmar 671_D - 08/1911of36
Agoodqualitytestmetercapableofmeasuringupto5,000kΩ(1kΩ=1000Ω)isrequiredtomeasurethesensorresistance.Inaddition,theactualtemperaturemustbemeasuredwitheitherahigh-qualitydigitalthermometer,orifathermometerisnotavailable,asecondsensorcanbeplacedalongsidetheonetobetestedandthereadingscompared.First,measurethetemperatureusingthethermometerandthenmeasuretheresistanceofthesensoratthecontrol.Thewiresfromthesensormustnotbeconnectedtothecontrolwhilethetestisperformed.Usingthechartbelow,estimate
thetemperaturemeasuredbythesensor.Thesensorandthermometerreadingsshouldbeclose.Ifthetestmeterreadsaveryhighresistance,theremaybeabrokenwire,apoorwiringconnectionoradefectivesensor.Iftheresistanceisverylow,thewiringmaybeshorted,theremaybemoistureinthesensororthesensormaybedefective.Totestforadefectivesensor,measuretheresistancedirectlyatthesensorlocation.Do not apply voltage to a sensor at any time as damage to the sensor may result.
Testing the Sensor Wiring
Temperature Resistance Temperature Resistance Temperature Resistance Temperature Resistance°F °C °F °C °F °C °F °C-50 -46 490,813 20 -7 46,218 90 32 7,334 160 71 1,689-45 -43 405,710 25 -4 39,913 95 35 6,532 165 74 1,538-40 -40 336,606 30 -1 34,558 100 38 5,828 170 77 1,403-35 -37 280,279 35 2 29,996 105 41 5,210 175 79 1,281-30 -34 234,196 40 4 26,099 110 43 4,665 180 82 1,172-25 -32 196,358 45 7 22,763 115 46 4,184 185 85 1,073-20 -29 165,180 50 10 19,900 120 49 3,760 190 88 983-15 -26 139,403 55 13 17,436 125 52 3,383 195 91 903-10 -23 118,018 60 16 15,311 130 54 3,050 200 93 829-5 -21 100,221 65 18 13,474 135 57 2,754 205 96 7630 -18 85,362 70 21 11,883 140 60 2,490 210 99 7035 -15 72,918 75 24 10,501 145 63 2,255 215 102 64810 -12 62,465 80 27 9,299 150 66 2,045 220 104 59815 -9 53,658 85 29 8,250 155 68 1,857 225 107 553
Testing the Control WiringRemovethefrontcoverfromthecontrol.Testing the Power-------------------------------• Useanelectricalmetersettomeasure(ac)voltage.• MeasurebetweentheLandNterminals.• Thereadingshouldbe115V(ac)+/–10%.Hand Manual Override---------------------------ThecontrolincludesaHandManualOverridemenutocheckifthecontrol’srelaysareoperatingandthatthecontroliswiredcorrectlytothesnowmeltingequipment.Step1: PressSettingsbutton.Step2: PressOverridebutton.Step3: PressManualOverride.Step4: SelectManualOverridetoHand.Step5: PressBackbutton.Step6: Thefollowingoutputscanbeoperated:• SystemPumprelay• HeatRelay• BoilerRelayFor each relay output• Useanelectricalmetersettomeasure(ac)voltage.• Measurebetweentherelaywiringterminals.• Whentherelayisoff,thevoltageshouldbe115V(ac).• Whentherelayison,thevoltageshouldbe0V(ac).Exiting the Hand Manual Override---------------• ExittheManualOverridebyselectingAuto.• Installthefrontcover.
12of36© 2019 tekmar 671_D - 08/19
Manual Override – Maximum HeatInhydronicapplicationmodes,thecontrolincludesaMaximumHeatoperationwherethecontroloperatesthesnowmeltingsystemtomaintainthemaximumallowedheatingsetpoints.Thisallowstestingofthesnowmeltingsystemduringwarmweather.
Step1: PressSettingsbutton.Step2: PressOverridebutton.Step3: PressManualOverride.Step4: SelectManualOverridetoMaxHeat.Step5: PressBackbutton.ThecontrolstartstheMaxHeat
operation.Step6: ExittheManualOverridebyselectingAuto.
Whenoperatingahydronicsnowmeltingsystem,itisnecessarytopurgeandbleedallairoutofthesystem.ThecontrolincludesaPurgeoperationwherethesystem,primaryandboilerpumpsareallturnedontoassistinpurgingairfromthesystem.
Step1: PressSettingsbutton.Step2: PressOverridebutton.Step3: PressManualOverride.Step4: SelectManualOverridetoPurge.Step5: PressBackbutton.ThecontrolstartsthePurge
operation.Step6: ExittheManualOverridebyselectingAuto.
Manual Override – Purge
ThesnowmeltingsystemcanbemanuallyturnedoffandthecontrolremainsoffuntilmanuallychangedbacktoAuto.Thisallowstheinstallerorendusertopermanentlydisablethesnowmeltingsystemwithoutremovingpowerfromthecontrol.
Step1: PressSettingsbutton.Step2: PressOverridebutton.Step3: PressManualOverride.Step4: SelectManualOverridetoOff.Step5: PressBackbutton.Thecontrolisnowintheoffmanual
override.Step6: ExittheManualOverridebyselectingAuto.
Manual Override – Off
Access LevelsThecontrolisshippedpre-programmedwithcommonsettings.Thecontrolhasan“Installer”accesslevelthatallowsfullaccesstoallsettingsanda“User”accesslevelthatrestrictsthenumberofsettingsavailable.Thecontroldefaultstothe“User”accesslevelafter12hoursofoperation.
Tochangetothe“Installer”accesslevel:• Step1:PresstheSettingsbutton.• Step2:PresstheToolboxbutton.• Step3:PressAccessLevel.• Step4:PresstheInstallerradiobutton.
© 2019 tekmar 671_D - 08/1913of36
Home Screen
User Interface
System Operation
Viewstatusofsensorreadingsandequipment
Remainingmeltingruntime
Systemoperationinformation
Gotosettingsmenutosetupcontrol
Informationaboutslabandoutdoorconditions
SYSTEM IS MELTING• Thecontrolhaseitherdetectedsnow/iceandautomaticallystartedorthecontrolwasmanually
started.• "WarmingUp"isshownwhentheslabisbelowtheslabtargettemperature.
SYSTEM IS OFF• Thesnowmeltingsystemisoffandisreadytodetectsnoworice.• "WarmWeatherShutDown"isshownwhentheslabandoutdoortemperatureareabovethe
WWSDsetting.DuringWWSD,thesnowwillmeltnaturallyduetowarmoutdoortemperatures.• "ColdWeatherCutOff"isshownwhentheoutdoortemperatureisbelowtheCWCOsetpoint.The
outdoortemperatureissocoldtheheatingsystemdoesnothavecapacitytomeltsnow.• "MeltPending"isshownwhenthesystemisoffduringCWCObutwillresumemeltingoncethe
outdoortemperatureincreasesabovetheCWCOsetpoint.
SYSTEM IS IDLING• Thecontrolispre-heatingtheslabtotheidlingsetpoint.Thisreducestheamountoftimeneeded
toreachthemeltingsetpointintheeventsnoworiceisdetected.
SYSTEM IN OVERRIDE / SYSTEM IN EXERCISING• Thecontrolisinamanualoverridefortesting,commissioningorexercising.• Thedescriptionfieldexplainswhichtypeofoverrideisactive.
14of36© 2019 tekmar 671_D - 08/19
Symbols
!WARNING SYMBOLThecontrolhasaerrormessage.Pressthewarningsymboltodeterminetheerrorcodeandinformationonhowtotakecorrectiveaction.RefertotheTroubleshootingsectionforalistoferrorcodes.
Help Screen
ThedisplayincludesaHelpscreenforeachsetting.TheHelpscreenprovidesadescriptionofthesettingthatisidenticaltothedescriptionfoundintheInstallationandOperationManual.
Status Menu NavigationStep1:PresstheStatusbuttonontheHomeScreen.Step2:PresseithertheSystem,SlaborWeatherbutton.Step3:Pressupordownbuttonstoscrollthroughthelist.
© 2019 tekmar 671_D - 08/1915of36
System Status MenuDescription Range Access
MANUAL MELT INPUTWhenManualMeltwiringterminal8isshortedtocommonwiringterminal9,thecontrolisenabledandentersthemeltingoperationunlesspreventedbywarmweathershutdownorcoldweathercutoff.Whenthemanualmeltinputisdisconnected,thecontrolcompletesthemeltingcycleandthenreturnstooff,idleorstormoperation.Conditions:Available
Off,Enabled UserInstaller
TEKMARNETWhentekmarNetcommunicationispresent,thestatusshowsactive.WhenthereisnotekmarNetcommunication,thestatusisoff.Conditions:Available
Off,Active UserInstaller
BOILERCurrentstatusoftheBoilerrelay.Conditions:Alwaysavailable
OnorOff UserInstaller
SYSTEM PUMPCurrentstatusofthesystemlooppump.Conditions:Alwaysavailable
OnorOff UserInstaller
HEAT RELAYCurrentstatusoftheheatrelay.Conditions:Alwaysavailable
OnorOff UserInstaller
Slab Status ScreenDescription Range Access
OUTDOORCurrentoutdoorairtemperatureasmeasuredbytheoutdoorsensororfromthetekmarNetsystem.“–––”isdisplayedwhennooutdoortemperaturereadingisavailable.
–––,-67to149°F
(-55.0to65.0°C)
UserInstaller
SLAB TARGETTheslabtargetcalculatedbythecontrolbasedonoutdoortemperatureandthemelting,idling,orstormsetpoints.“---”isdisplayedwhennoheatisrequired.
–––,32to110°F
(0to43.0°C)
UserInstaller
SLAB SENSORCurrentslabsensortemperature. -58to167°F
(-50.0to75.0°C)User
Installer
SENSOR WATER STATUSCurrentstatusofsnow/icesensormoisturedetector. DRYorWET User
Installer
16of36© 2019 tekmar 671_D - 08/19
Weather Status Screen
Currentoutdoorconditions
WhenWiFiisturnedon,thecontrolreceivesweatherdatafromtheInternet.Thecurrentweather,outdoortemperatureandforecastsnowfallinformationisdisplayed.
Settings Menu Navigation
Step1:PresstheSettingsbuttonontheHomeScreen.Step2:Pressoneofthetenbuttons.Step3:Pressupordownbuttonstoscrollthroughthelist.Step4:Pressthehighlightedsettingnametochangethesettingvalue.
© 2019 tekmar 671_D - 08/1917of36
18of36© 2019 tekmar 671_D - 08/19
Description Range Access
MELTING SETPOINTSelectthedesiredtemperatureofthesnowmeltsurfacewhenmelting.
32to95°F(0.0to35.0°C)Default=36°F
(2.0°C)
UserInstaller
IDLING SETPOINTSelectthedesiredtemperatureofthesnowmeltsurfacewhenidling.Idlingpreheatstheslabwhentheslabisdrybutcoldandallowsfasterreactiontimetoreachthemeltingtemperaturewhensnowisdetected.Recommendedforcommercialuseonly.
OFF,20to95°F(-6.5to35.0°C)
Default=Off
UserInstaller
STORM SETPOINTSelectthedesiredtemperatureofthesnowmeltsurfacewhileoperatinginthestormoperation.Stormoperationtemporarilypreheatstheslabtoallowfasterreactiontimetoreachthemeltingtemperaturewhensnowisdetected.
OFF,20to95°F(-6.5to35.0°C)
Default=Off
UserInstaller
MANUAL MELT TIMESelecttheamountofrunningtimewhenmanuallystartingthesystem.
0:30to24:00hours
Default=4:00hours
UserInstaller
ADD MELT TIMESelecttheamountofadditionalmeltingtimeaftertheSnow/IceSensorisdry.Thisallowslowspotsontheslabtofullydrybeforethesnowmeltingsystemisshutoff.
0:00to6:00hours
Default=0:00hours
Installer
STORM RUN TIMESelecttheamountofstormruntimetopre-heattheslabwhenadvisedofawinterstormwarning.
0:30to24:00hours
Default=8:00hours
Installer
SENSITIVITYSelecthowsensitiveSnow/IceSensoristowaterdetection.
Auto,Min,-2,-1,Mid,+1,+2,MaxDefault=Auto
Installer
WWSDSelectthetemperatureabovewhichthesnowmeltingsystemisshutoffduringwarmweather.Thisallowsthesnoworicetomeltofftheslabnaturally.
Auto,32to95°F(0.0to35.0°C)Default=Auto
Installer
CWCOSelectthetemperaturebelowwhichthesnowmeltingsystemisshutoffduringextremelycoldweather.Belowthistemperature,theheatlossoftheslabexceedsthecapacityoftheboilerorheatingappliance.
Off,-30to50°F(-34.5to10.0°C)Default=10°F
(-12.0°C)
Installer
Temp Menu
© 2019 tekmar 671_D - 08/1919of36
Away Menu
Display Menu
Description Range Access
TEMPERATURE UNITSSelectFahrenheitorCelsiustemperatureunits.Conditions:Alwaysavailable.
°For°C UserInstaller
SCREEN BRIGHTNESSSelectthescreenbrightness.Conditions:Alwaysavailable.
0to100%Default=75%
UserInstaller
CLEAN SCREENTheCleanScreentimerlocksthescreenfor10secondsallowingtheusertowipethescreenwithamoistcloth.Donotusesolventstocleanthescreen.Conditions:Alwaysavailable.
No,Yes UserInstaller
AwaySelectawaytopreventsnowmeltingoperationandsaveenergy.
At HomeSelectathometoallowauto-maticsnowmeltingoperation.
Thehome/awaychangesdevicessystem-wide.AllthermostatsandcontrolsthataregroupedtogetheronatekmarNetsystemwillalsochangetogether.
20of36© 2019 tekmar 671_D - 08/19
WiFi Menu
Time Menu
Description Range Access
WIFIEnableordisableWiFiconnectivity.Thehelpscreendisplaysthefollowinginformation:• IPAddress• SubnetMask• Gateway• MACAddressConditions:Alwaysavailable.
OfforOn UserInstaller
NETWORK SSIDSelecttheWiFinetworkfromthelist.Conditions:WiFiissettoOn.
ListofWiFiNetworks
UserInstaller
ZIP/POSTAL CODEEnteraUSZIPorCanadianpostalcode.TheZIP/PostalCodeisusedtoprovidethelocationfortheweatherinformation.TheweatherserviceisavailableintheUSAandCanadaonlyConditions:WiFiissettoOn.
USZIPformat12345
CanadaPostalCodeformat
A1B2C3
UserInstaller
TIME SOURCESelecttosettothetimeautomaticallyormanually.Conditions:WiFiissettoOn.
Auto,Manual
UserInstaller
Description Range Access
TIME SOURCESelecttosettothetimeautomaticallyormanually.AutoisonlyavailablewhenWiFiissettoOn.Conditions:Alwaysavailable.
Auto,Manual
UserInstaller
SET TIME AND DATEConditions:Timesourcesettomanual.
N/A UserInstaller
TIME FORMATSelecteither12or24hourformat.Conditions:Alwaysavailable.
12hr,24hr
Default=12hr
UserInstaller
TIME ZONESelectthelocation'stimezone.Conditions:AvailablewhenTimeSourceissettoManual.
Hawaii,Alaska,Pacific,Mountain,Central,Eastern,
Atlantic,NFLD,
(Newfoundland)
UserInstaller
DAYLIGHT SAVINGSSetDaylightSavingstoOntoautomaticallyadjustfortimechangesinthespringandfall.Conditions:Alwaysavailable.
OfforOnDefault=On
UserInstaller
BeforeusingtheWiFifeaturesofthisproduct,youmustaccepttheTermsofUse,asamendedfromtimetotimeandavailableatWatts.com/terms-of-use.Ifyoudonotaccepttheseterms,thisproductcanstillbeusedwithoutWiFifeatures.
• Pressboxfield.• Thenadjustwitharrowbuttons.
© 2019 tekmar 671_D - 08/1921of36
Energy Menu
Amountoftimethesystemhasbeenoninhoursperday. Amountoftimethesystemhasbeenoninhourspermonth.
Description Range Access
MELTING HOURSRecordsthenumberofmeltinghourssincethecounterwaslastreset.Conditions:Alwaysavailable.
0to999999hours
UserInstaller
HEAT HOURSRecordsthenumberofhourstheboilerfiredortheelectriccableheatedsincethecounterwaslastreset.
0to999999hours
UserInstaller
HEAT CYCLESRecordsthenumberofcyclestheboilerturnedonortheelectriccableheatedsincethecounterwaslastreset.
0to999999cycles Installer
SYSTEM PUMPRecordsthenumberofhoursthesystempumphasoperatedsincethecounterwaslastreset.
0to999999hours Installer
SLAB SENSOR HIGHRecordsthehighestmeasuredslabtemperaturesincethecounterwaslastreset.Conditions:AvailablewhenSnow/IceissettoIn-slaborSlabSensorissettoOn
-58to167°F(-50.0to75.0°C) Installer
SLAB SENSOR LOWRecordsthelowestmeasuredslabtemperaturesincethecounterwaslastreset.Conditions:AvailablewhenSnow/IceissettoIn-slaborSlabSensorissettoOn
-58to167°F(-50.0to75.0°C) Installer
OUTDOOR HIGHRecordsthehighestmeasuredoutdoorairtemperaturesincethecounterwaslastreset.Conditions:Alwaysavailable.
-67to149°F(-55.0to65.0°C) Installer
OUTDOOR LOWRecordsthelowestmeasuredoutdoorairtemperaturesincethecounterwaslastreset.Conditions:Alwaysavailable.
-67to149°F(-55.0to65.0°C) Installer
RESET ALL?Resetsallthecountersinthemonitormenuatonce.Conditions:AlwaysAvailable.
No,Yes Installer
Monitor Menu
22of36© 2019 tekmar 671_D - 08/19
Setup – System Setup MenuDescription Range Access
SNOW/ICE SENSORSelectifaSnow/IceSensor090or094"Inslab",oraSnowSensor095"Aerial"isinstalled.Conditions:Alwaysavailable.
None,In-slab,Aerial
Default=In-slabInstaller
SLAB SENSORSelectifaSlabSensor072or073isinstalled.Conditions:Availablewhensnow/icesensorissettoNoneorAerial.
OfforOnDefault=Off Installer
ECONOMELTEconoMeltallowstheusertomechanicallyremovesnowthenmanuallystartthesystemtomelttheremainingthinsnowlayeroricewithanautomaticstopwhenthesensorisdry.Requiressnow/icesensortobesettoin-slab
OfforOnDefault=Off Installer
MAX MELT DAYSLimittheamountofmeltingruntimeaftersnowisautomaticallydetectedbyaSnow/IceSensor090or094,oraSnowSensor095.Conditions:Alwaysavailable.
Off,0.5to7daysDefault=3days Installer
OUTDOOR SENSORSelectiftheoutdoorairtemperatureismeasuredbythecontrol,byatekmarNetsystemorbytheInternetweatherservice.Conditions:Alwaysavailable.
Control,tekmarNet,
InternetDefault=Control
Installer
Setup – Boiler Setup MenuDescription Range Access
BOILER TYPESelectthetypeofboileroperatedbythecontrol.Enable=Boilerrelayturnsontheheatsource.Control=CallforheattotekmarNetcontrol.Conditions:Availablewhenthe671isconnectedtoatekmarNetsystem.
Enable,Control Installer
© 2019 tekmar 671_D - 08/1923of36
tekmarNet Menu
Description Range Access
ADDRESSINGThetekmarNetaddressofthiscontrol.Tomanuallysettheaddress,usetheupordownbuttons.
Auto,x:01tobusx:24, Installer
AUTO ADDRESSThetekmarNetaddressofthiscontrol.Conditions:AddressingissettoAuto
Autob:01tob:241:01to1:242:01to2:243:01to3:24
Installer
MANUAL ADDRESSThetekmarNetaddressofthiscontrolwhenmanuallyassignedConditions:AddressingissettoManual
Manualb:01tob:241:01to1:242:01to2:243:01to3:24
DEVICE COUNTProvidesacountofallthetekmarNetthermostats,setpointcontrolsandsnowmeltingcontrolsonthetekmarNetSystem. 1to24 Installer
SNOW MELT ZONESelectthesnowmeltingzonethatthiscontroloperates.Snowzone1hasthehighestprioritywhilesnowzone12hasthelowestpriority. 1to12 Installer
TRACK ZONESelecttotrackandrecordtherunninghoursofsnowzone1andrepeatthisruntimeonthiscontrol.Thisallowssnowmeltingzoneswithoutasnow/icesensortoautomaticallystart. OfforOn Installer
MELT GROUPAUserSwitchorGatewaymaybeusedtomanuallystartmeltingthezone.SettheMeltGroupnumbertothecorrespondingSetpointEnablenumberontheUserSwitch. 1to12 Installer
STORM GROUPAUserSwitchmaybeusedtomanuallystartstormoperationofthesnowzone.SettheMeltGroupnumbertothecorrespondingSetpointEnablenumberontheUserSwitch.
1to12 Installer
PRIORITYSelectthepriorityofthesnowmeltingsystem.
Off,Conditional,Full
Default=OffInstaller
AWAY SCENE SelectifthecontrolshouldacceptorignoretheawaycommandfromatekmarNetsystem.Conditions:Alwaysavailable.
OfforOnDefault=On Installer
TN4 SYSTEM PUMP SelectifthesystempumplocatedonthetekmarNetSystemControlshouldoperatewhenthesnowmeltzoneisheating.
OfforOn Installer
24of36© 2019 tekmar 671_D - 08/19
Toolbox MenuDescription Range Access
ERROR CODEThecurrenterrorcodeisdisplayed.Conditions:Alwaysavailable.
SeeErrorCodeSection
UserInstaller
ACCESS LEVELSelecttheaccesslevelofthecontrol.Thisdetermineswhichmenusanditemsareavailablethroughtheuserinterface.Conditions:Alwaysavailable.
UserorInstallerDefault=Installer
UserInstaller
TYPE 671Productinformation.SW:J12881.0.0SVN:XXXConditions:Alwaysavailable.
J1288Last3numbers
indicatesoftwareversion
UserInstaller
LOAD DEFAULTSSelect“Yes”toreloadthefactorydefaultsonthecontrol.Conditions:Alwaysavailable.
No,Yes UserInstaller
Description Range Access
MANUAL OVERRIDEManuallyoverridethenormalautomaticoperationofthecontroltotesttheequipmentoroperatethesystematthemaximumtemperaturelimits.Auto=Normaloperation.MaxHeat=Operatehydronicsystematmaximumheat.Hand=Manualoverrideofeachrelayoutput.Purge=Hydronicsystempurgeoperatespumpstohelpbleedairfromthesystem.
Auto,Hand,
MaxHeat,Purge,
Off
UserInstaller
SYSTEM PUMPManuallyturnonthesystempumpduringtheHANDManualOverride.
OfforOnDefault=Off
UserInstaller
HEAT RELAYManuallyturnontheheatrelayduringtheHANDManualOverride.
OfforOnDefault=Off
UserInstaller
BOILER ENABLEManuallyturnontheboilerduringtheHANDManualOverride.
OfforOnDefault=Off
UserInstaller
HAND DURATIONSelecttheamountoftimethattheHANDOverrideisineffectbeforereturningtoAutomaticoperation.
0:10to72:00hours
Default=0:10hour
UserInstaller
MAX HEAT DURATIONSelecttheamountoftimethatMaxHeatisineffectbeforereturningtoAutomaticoperation.
0:10to72:00hours
Default=24:00hour
UserInstaller
PURGE DURATIONSelecttheamountoftimethatthePurgeisineffectbeforereturningtoAutomaticoperation.
0:10to72:00hours
Default=0:10hour
UserInstaller
Override Menu
© 2019 tekmar 671_D - 08/1925of36
Sequence of OperationSnow Melting OverviewAsnowmeltingsystemcanofferasafe,convenient,andcosteffectivewayofremovingsnowandicefromthesnowmeltingslabandsimilarsurfaces.Safetyisincreasedbyactivatingthesnowmeltingsystemassoonasthesnowfallsratherthanwaitingformechanicalsnowremovalaftersnowhasaccumulated.Thiseliminatessliphazardsandreducestheriskofinjurybymechanizedsnowmeltingequipment,therebyreducingpotentialliabilitycosts.Theeliminationofsnowplowequipmentandcorrosivesaltsalsoreducesdamagetotheslabsurfaceandtotheenvironment.Whencontrolledcorrectly,snowmeltingsystemscanbecostcompetitivecomparedtomechanicalsnowremoval.Thesnowmeltingcontrolcanoperateinoneoffourdifferentways:
Melt Heatstheslabtomeltsnoworice.Defaultis36°F(2°C)Idle Preheatstheslabjustbelowfreezingtoshortenthe
timerequiredtomeltsnow.Defaultisoff.
Melt – Automatic Start and StopAutomaticstartandstopoperationrequirestheinstallationofaSnow/IceSensor090(65'or20mcable)or094(208'or63mcable).Thesensorisinstalledin-slablevelwiththemeltingsurface.Thecontrolcontinuallymonitorsthesensorforthepresenceofmoistureandslabtemperatureconditionsinwhichsnoworicemaybepresent.Whenmoistureisdetected,thecontrolshows“SensorWaterStatus–Wet”intheSlabStatusmenu.Whenthesensorisdrythecontrolshows“SensorWaterStatus–Dry”.ThecontrolincludesaSensitivitysettingintheTemperaturesmenuthatallowstheinstallertoadjusttheamountofmoisturerequiredtostartandstopthemeltingoperation.Inareaswithlowamountsofdustand/orairpollution,thesensitivitymayneedtobeincreased.ThedefaultsensitivitysettingisAuto.Thissettingallowsthecontroltoautomaticallydeterminethebestsuitablesensitivity
PushSTOPButton
090or094andSlabDryandAddMeltTimeElapses
or
Idle
Off WWSD
Gateway482or486StopMessage
090or094DetectsWater
ExitsCWCOMelt
Suspended
EntersCWCO
Melting
AutoStart/AutoStop
settingfortheinstallation.WhenmoistureisdetectedandthecontrolisnotinWWSDorCWCOorAway,thecontrolwillautomaticallystartthesnowmeltingsystem.Asthesnoworicemeltsandtheslabdriesoff,thesensoralsodriesoffatthesametime.Whenthesensorisdry,thesnowmeltsystemautomaticallyshutsoff.Iftherearelowspotsontheslabsurfacethatdryoffslowerthanthesensor,additionalmeltingruntimecanbeincludedbyadjustingtheAdditionalMeltTimesettingintheTemperaturesmenu.If the snow melting system is manually stopped, the snow/ice sensor must fully dry before it is able to detect a new snow fall and automatically start the snow melting system.
Snow/Ice Sensor 090 or 094
Theslabtemperaturemustreachtheslabtargetinorderforthesystemtoshutoffautomatically.Thecapacityoftheheatsourcemustbesizedtoensuremeltingaslowasthecoldweathercutoff.Inaddition,theheatsourcemaximumtemperaturesetting
mustbesettoprovidethefullcapacityoftheheatingappliance.Forexample,boileraquastatsshouldbesetto180°F(82°C).Failuretomeettheserequirementsmayresultinthesnowmeltingsystemnotautomaticallyshuttingoffwhentheslabisdry.
OutdoorTemperature
SlabTemperature
MELT
IDLEorSTORM
WWSD
CWCO
ControlentersIdleandwaits
forMeltEnable
Storm Temporarilypreheatstheslabjustbelowfreezingtoshortenthetimerequiredtomeltsnow.Defaultisoff.
Off SnowmeltingsystemisoffThedisplayshowsthecontroloperationinthehomescreen.
26of36© 2019 tekmar 671_D - 08/19
Melt – EconoMelt
WhenaSnow/IceSensor090or094isinstalled,theinstallercanchoosetoselecttoeitherautomaticallyormanuallystartthesnowmeltingsystem.SelectingEconoMelttoOnallowssnowremovalusingasnowploworshovel.Theremainingthinlayerofsnoworicethatmechanicalsnowremovalmethodsareunabletoremovecanbemeltedusingthemanualstartoperation.Thesnowmeltingsystemstopswhenthesensorisdry.ThefactorydefaultforEconoMeltisOff.
PushMeltButton
Gateway482or486MeltMessage
ManualMeltSwitch
090andSlabDryandAddMeltTimeElapses
WWSD
PressStopButton
Melting
ManualStart/AutoStop
Off
ExitsCWCOMelt
Suspended
EntersCWCO
Melt – Automatic Start and Timed Stop
Automaticstartwithatimedstopoperationrequirestheinstal-lationofaSnowSensor095.Thesensorisaerialmountedonapolenearthemeltingsurface.ItishighlyrecommendedtoalsoinstallaSlabSensor072(20’or6mcable)or073(40’or12mcable)inordertoregulatetheslabtemperatureandoperatethesnowmeltingsystematthehighestpossibleefficiency.Thecontrolcontinuallymonitorsthesnowsensorforthepresenceofmoistureandslabtemperatureconditionsinwhichsnoworicemaybepresent.Whenmoistureisdetected,thecontrolwillshow“SensorWaterStatusWet”intheSlabStatusmenu.Whenthesensorisdrythecontrolwillshow“SensorWaterStatusDry”.ThecontrolincludesaSensitivitysettingintheTemperaturesmenuthatallowstheinstallertoadjusttheamountofmoisturerequiredtostartand
stopthemeltingoperation.Inareaswithlowamountsofdustand/orairpollution,thesensitivitymayneedtobeincreased.ThedefaultsensitivitysettingisAuto.Thissettingallowsthecontroltoautomaticallydeterminethebestsuitablesensitivitysettingfortheinstallation.WhenmoistureisdetectedandthecontrolisnotinWWSDorCWCOorAway,thecontrolautomaticallystartsthesnowmeltingsystem.ThesnowmeltingsystemoperatestoheattheslabtotheslabtargettemperatureandcontinuestooperateuntilthetimesetbytheManualMeltRunTimeintheTemperaturesmenuelapses.Ifthe095re-detectswater,thetimerisrestartedtooperateforthefullruntime.
Snow Sensor 095
095DetectsWater
ManualMeltRunTimeElapses
WWSD
PushStopButton
Gateway482or486StopMessage
CWCO
Melting
AutoStart/TimedStop
or
Idle
Off
095RedetectsWater
Additional Melting Time
DrySnow Ice Sensor
ASnow/IceSensor090or094automaticallyshutsoffthesnowmeltingsystemwhenthewatersensorisdry.Duetotheconstructionoftheslabandthelayoutoftheheatingpipeorelectricalcable,theremaybeareasthatdonotmeltcom-pletely.TheAdditionalMeltTimesettingintheTemperaturesmenuallowstheinstallertosetadditionmeltingtimeafterthesensorisdry.
© 2019 tekmar 671_D - 08/1927of36
Melt – Manual Start and Timed StopThesnowmeltingsystemcanbestartedmanuallybyoneofthethreedifferentmethods:• TouchtheMeltbuttononthecontroldisplay• ThroughaGateway482or486meltrequestmessage• BymanuallyconnectingtheManualMeltandComwiring
terminals8and9together.Oncemanuallystartedandtheslabwarmsuptotheslabtarget,
PushMeltButton
Gateway482or486MeltMessageManualMeltSwitch
ManualMeltRunTimeElapses
WWSD
PushStopButton
Gateway482or486StopMessage
CWCO
Melting
ManualStart/TimedStop
or
Idle
Off
thesnowmeltingsystemrunsuntilthetimesetbytheManualMeltRunTimesettingintheTemperaturesmenuelapses.
IfamanualstarthasbeenprovidedandaSnow/IceSensordetectswater,thecontrolchangesfrommanualmelttoautomaticoperation.ThesnowmeltingsystemrunsuntilthesensorisdryandtheAdditionalMeltTimeelapses.
Tandem Snow/Ice Detection
The671canbepairedtogetherwitha654toallowtwoSnow/Icesensors090or094orSnowSensors095tobeinstalledforasinglezone.Thisprovidesfullredundancyandincreasesthesnowdetectionarea.Bothsensorsareusedtodetectsnoworiceandifeithersensoriswetthesnowmeltingzonestartsmelting.Thecontrolcontinuestooperateuntilbothsensorsaredry.Thisallowssnoworicedetectionoverawiderarea.Intheeventofasensorfailure,thecontrolcontinuestooperatenormally,givingbuildingmaintenancestafftimetotroubleshootandreplacethefaultysensorifnecessary.
PressMeltbuttontostartmeltingoperation
Melt - Tracked Start and StopThesnowmeltingsystemcanhavemultiplezones.Zoneshavetheoptiontotrackthemeltingruntimeofzone1.Thisisusefulincaseswherezone1hasanautomaticSnow/IceSensorinstalledandtheremainingzonesdonot.Thisallowszones2to12togainthefunctionalityofautomaticstartingandstoppingwithonlyoneSnow/Icesensorinstalledinthesystem.Whenzone1detectssnoworice,itstartsmelting.Zoneswithtrackingenabledcanalsostartmeltingunlesspriorityisselected.Whenthesensorinzone1isdryortheManualMeltRunTimehasfullyelapsed,itsendsasignaltothetrackedzonesthatzone1hasstopped.EachzonecancontinuetooperatetocompletetheirownAdditionalMeltTimeafterwhichthezonestopsheatingandreturnstotheOfforIdleoperation.Zoneswithpriorityselectedstartafterzone1hasfinishedmeltingandrepeatthesameruntimeaszone1.
Zone1
TrackMeltStartandStop
RecordsRun Time
Snow / IceSensor
SlabSensor
SlabSensor
Zone2 Zone3
RepeatsZone 1 RunTime + AddMelt Time
RepeatsZone 1 RunTime + AddMelt Time
28of36© 2019 tekmar 671_D - 08/19
Idle OperationWhenthesnowmeltingsystemstartsfromacoldtemperature,theremaybealongtimedelaybeforetheslabiswarmenoughtomeltsnow.Thistimedelayallowssnowtoaccumulateontheslabwhichisnotacceptableinsomecommercialandinstitutionalapplications.Todecreasethestart-uptime,theslabcanbepre-heatedtomaintainaminimumtemperature.ThisisknownastheIdletemperature.Idlingrequireslargeenergyconsumptionandisgenerallyrecommendedforinstitutionaland/orcommercialinstallationswheresafetyconcernsareparamount.Thedisplayshows"SystemisIdling"whenthecontrolisinidleoperation.Whendesigningasnowmeltingsystem,anengineermayspecifytheamountofallowedsnowaccumulationastheSnow-FreeAreaRatio.Therearethreedifferentlevels.ASnow-FreeAreaRatioof1isdefinedasasystemthatmeltsallsnowasitfallswithnoallowedaccumulation.ThisrequiresthattheIdletemperaturebesetjustbelowfreezing.Examplesofthesetypesofapplicationsinclude:• Hospitalemergencyareas• Helicopterlandingpads• Parkinggarageramps
ASnow-FreeAreaRatioof0.5isdefinedasasystemwithpartialsnowaccumulationontheslabbutnotinallareas.
ThesetypesofsystemsmayalsouseIdlingbutusuallysetatatemperatureseveraldegreesbelowfreezingtoreduceenergyconsumption.Applicationsmayinclude:• Steepresidentialdriveways• Commercialsidewalks• LoadingdocksASnow-FreeAreaRatioof0isdefinedasasystemthatallowssnowaccumulation.Thesesystemsoperatethesnowmeltingsystemfromacoldstartresultinginthelowestenergyconsumptioncostsandthelongesttimestostartmeltingsnow.InthiscasesettheIdletooff.Thisisrecommendedformostresidentialapplicationssuchas:• Flatresidentialdriveways• Patios• ResidentialsidewalksSomesystemsaredesignedforkeepingaslabsurfacefreeoficeratherthanfreeofsnow.Themostcommonapplicationsinclude:• Carwashbaysandaprons• Aircrafthangeraprons• TurfconditioningongolfcoursegreensThesesystemsrequiretheuseofIdlingatornearfreezingthroughoutthewinterandmayresultinhighenergyconsumption.
Storm Operation
TheStormoperationcombinesthebenefitsofafastresponsetimetogetherwithloweroperatingcosts.Typicallythestormtemperatureissetbelowfreezingtomaximizeenergysavings.Whenthestormoperationismanuallystarted,thesnowmeltsystemheatstheslabuptothemeltingtemperatureandcompletesameltingcycle.
Manual Storm-----------------------------------ThestormoperationismanuallystartedbyaUserSwitch480and481oraGateway482.ThemanualstormusestheStormGroupnumberinthetekmarNetmenu.SetupProcedureStep1:Setthe671StormGroupnumberfrom1to12.Thedefaultis12.Step2:SettheUserSwitchortheGatewaytousethecorre-spondingStormGroupnumber.WhentheUserSwitchbuttonispressed,the671willentertheStormOperation.Likewise,activatingtheStormGroupontheGatewaycausethe671toentertheStormOperation.
UserSwitchButton
Gateway482StormEnable
StormRunTimeElapses
Awayscene
UserSwitchButton
Gateway482StormDisable
WWSDCWCO
StormOff
If
Then
forecast
© 2019 tekmar 671_D - 08/1929of36
671
tekmarNet
Snow MeltZone 1
Snow MeltZone 2
671
Snow Melt Zones and Priority
Dividingasystemintoanumberofsnowmeltingzonesandprioritizingthezoneoperationreducesthesizerequirementsofthehydronicheatingplantortheamperageoftheelectricalservicepanel.Thisresultsinlowerinitialcapitalcostofthesnowmeltingsystem.Thetradeoffisthatsomesnowmeltzonesmaynotbeabletomeltassoonasthesnowfallbeginsandtheusermusttoleratesnowaccumulationontheslab.ThesnowmeltsystemusingSnowMeltingControl654,670and671mayhaveupto12snowmeltzones.Zone1hasthehighestpriorityandzone12hasthelowest.TheprioritysettinginthetekmarNet®menuallowstheinstallertoselectthelevelofzonepriorityfortheentiresnowmeltsystem.Changingtheprioritysettingononecontrolwillupdateonallothersnowmeltcontrolsatthesametime.Thezonepriorityhas3settinglevels.Thereissomeriskthatlowerpriorityzonesmayiceupwhentheyareshutoffbythehigherpriorityzone.Forexample,ifahighpriorityzoneshouldfinishmeltingandallowalowerpriorityzonetostartmelting,andthenanewsnowfalloccurs,thehighpriorityzonewillshutoffthelowerpriorityzones.Thismaypotentiallyallowthelowerpriorityzonestoiceover.The
limitationsofzoningandusingprioritymustbecarefullyconsideredanddiscussedwiththebuildingownersandoccupantswhendesigningthesnowmeltingsystem.PrioritydoesnotapplywhentheapplicationmodeissettoBoiler.Inthismode,theboilerisdedicatedtoasinglesnowmeltingzonesopriorityisnolongerapplicable.
Slab Temperature Control
Controllingtheslabtemperatureiscriticaltominimizingthecostofsnowmelting.ThisrequiresthateitheraSnow/IceSensor090or094oraSlabSensor072or073isinstalled.TheSnow/IceSensorcontainsabuilt-inslabtemperaturesensor.Whilethecontrolcanoperatewithoutaslabsensorinstalled,operatingcostsaremuchhigher.Theslabisoperatedusingslaboutdoorreset.Astheoutdoortemperaturegetscolder,theheatlossoftheslabincreases.Inordertokeeptheslabsurfaceataconstanttemperaturewhileoperating,theinnercoreoftheslabmustbeheatedabovethemelt,idleorstormtemperaturesetting.Theamountthattheslabinnercoretemperatureisabovethemelt,idleorstormsettingisproportionaltotheoutdoortemperature.Sincetheslabsensorisinstalledbelowthesurfaceoftheslab,itisnotmeasuringthetrueslabsurfacetemperaturebutrathertheinnercoretemperature.Thecontrolautomaticallycompensatesforthistemperaturedifference.TheSlabitemin
theStatusmenudisplaystheactualmeasuredtemperature,soitisnormaltoviewslabtemperaturesthatexceedthemelt,idle,orstormtemperaturesettings.
Surface temperature = 35ϒF
Decreasing Air Temperature
Incr
easi
ng S
lab
Cor
e Te
mpe
ratu
re
SlabSurfaceTemperatureisConstant
SlabOutdoorResetSlabOutdoorReset
Core(sensor)iswarmer
30of36© 2019 tekmar 671_D - 08/19
Priority = NoneAllzoneshavethesamepriorityandcanoperateatthesametime.Thissettingisrecommendedwhentheboilerplantcapacityissizedlargerthantheheatlossofallzonesatdesignconditions.
Priority = ConditionalThezonewiththelowerprioritystartsmeltingwhenthezonewithhigherpriorityiswarmenoughtomeltsnoworice.Thissettingisrecommendedwhentheboilerplantcapacityissizedtobelargerthantheheatlossofeachzonewithsomeextracapacity.
Priority = FullThezonewiththelowerprioritystartsmeltingoncethezonewithhigherpriorityhasfinishedmeltingallsnoworicefromtheslab.Thissettingisrecommendedwhentheboilerplantcapacityissizedtobethesameastheheatlossofeachzoneatdesignconditions.
Hydronic Priority Levels--------------------------------------------------------------------------------
Zone 1
MELT
OFF
Zone 2
MELT
OFF
Zone 1
MELT
OFF
Zone 2
MELT
OFF
Zone 1
MELT
OFF
Zone 2
MELT
OFF
© 2019 tekmar 671_D - 08/1931of36
Thecontrolhasabuilt-intimeclockthatcanbesetmanually.Abattery-lessbackupallowsthecontroltokeeptimeforupto4hourswithoutpower.ThetimeclocksupportsautomaticadjustmentforDaylightSavingTime(DST)oncetheday,
monthandyearareentered.UsetheTimemenutosetthecorrecttime,day,monthandyear.
Time Clock
Away Operation
tekmarNet Scene Operation
Whileonvacationandawayfromabuilding,itmaynotbenecessarytooperatethesnowmeltingsystem.Theawayfeatureallowstheusertoshutoffthesnowmeltingsystemtomaximizeenergysavings.TheAwayfeaturecanbeactivatedthroughthe:
• Awaymenu• tekmarNetUserSwitch480or481• tekmarNetGateway482or486
ThetekmarNetsystemsupportsupto8scenes.The671supportstekmarNetscenes1(normaloperation)and2(away).DuringtekmarNetscenes3through8,the671remainsinscene1(normaloperation).
Warm Weather Shut Down
Cold Weather Cut Off
Duringwarmweather,theslabiswarmenoughtonaturallymeltsnoworice.ThecontrolhasaWarmWeatherShutDown(WWSD)settingintheTemperaturesmenuthatpreventsthecontrolfromenteringMelt,IdleorStormoperationinordertoconserveenergy.Thecontrolshows,"SystemisOff–WarmWeatherShutDown"onthedisplaywhenWWSDisineffect.
Automatic (Auto)ThecontrolentersWWSDwhenboththeslabtemperatureandtheoutdoortemperatureexceedtheMeltingSetpointtemperaturesettingbymorethan2°F(1°C).
Manual WWSDThecontrolentersWWSDwhentheoutdoorairtemperatureexceedstheWWSDsettingby1°F(0.5°C)andwhentheslabtemperatureexceeds34°F(1°C).ThecontrolexitsWWSDwhentheoutdoorairtemperaturefalls1°F(0.5°C)belowtheWWSDsettingoriftheslabtemperaturefallsbelow34°F(1°C).ThisallowstheMeltingSetpointsettingtobesethigherthantheWWSD.Thisisusefulwhenhighslabtemperaturesarerequiredtomeltthesnoworice.Anexampleofthisareinstallationsusingpavingbricksontopofsandandconcretelayers.
Maintainingthemeltingoridlingsetpointtemperatureduringextremelycoldtemperaturesisnotonlyexpensivebutmaybeimpossibleiftheheatlossoftheslabexceedstheinputcapacityoftheheatingplantorelectriccable.ThecontrolturnsthesnowmeltingsystemoffwhentheoutdoorairtemperaturedropsbelowtheColdWeatherCutOff(CWCO)temperature.Thisisasafetyandenergysavingmeasure.Thecontrolshows,"SystemisOff–ColdWeatherCutOff"onthedisplay
whenCWCOisineffect.WhenthetemperaturereachestheCWCOsettinginanactivelymeltingsystemwithan090or094,meltingissuspendeduntiltheoutdoortemperaturerisesabovetheCWCOsettingatwhichtimemeltingisresumed.Ifan090or094isnotinstalled,meltingisstoppedwhenCWCOisineffectandmeltingdoesnotresumewhenthetemperaturerisesabovetheCWCOsetting.
32of36© 2019 tekmar 671_D - 08/19
Pulse Width Modulation Zone OperationThecontroloperatesthesystempumptooperatecontinuouslyduringmelt,idleandstormoperation.Theboilerrelaysandheatpumpsrelaysoperateona20-minutepulsewidthmodulationcycle.Therelayontimeisdeterminedbythecalculatedslabtargetandbythemeasuredslabtemperaturereading.Astheslabtemperaturereachestheslabtarget,theontimepercycleoftherelayisreducedtopreventtheslabtemperaturefromovershooting.Ifnoslabsensorisinstalledtheheatrelayremainson100%ofthetimeuntiltheMeltcirclehascompleted.
WhenconnectedtoatekmarNetsystem,the671canoperateaboiler(BoilerTypesettoEnable)oritcancallforheatfromthetekmarNetboilercontrol(BoilerTypesettoControl)
Relay operation:• Systempump—operatescontinuouslyduringmelting,
idlingorstorm• Heatrelay—cycleson/offusingPulseWidthModulationto
controltheslabtemperature• Boiler—cycleson/offusingPulseWidthModulationtocon-
troltheslabtemperature
© 2019 tekmar 671_D - 08/1933of36
Post Purge
ExercisingThecontroloperatesthesystempumpandheatrelayevery3daystopreventpumpandvalveseizure.
Theboilerorheatsourceisshutoffandthesnowmeltingsystemcontinuestooperatefor20secondstopostpurgeheatfromtheboilertotheload.
Outdoor SensorAnoutdoorairtemperatureisrequiredforproperoperation.ThecontrolhastheoptiontomeasureanoutdoorairsensorortheoutdoortemperaturecanbeprovidedthroughthetekmarNet
systemorthroughtheInternetweatherservice.ThisisselectedbytheOutdoorSensorsettingintheSystemSetupmenu.
1.Find:IfthecontrolshowstheWarningSymbol onthescreen,itisindicatingaproblemonthesystem.2.Identify:PresstheWarningSymboltoviewtheerrorcode.3.Solve:Usethechartbelowtomatchtheerrorcodetotheoneonthecontrol.Usethedescriptiontosolve
theproblem.
Error Messages (1 of 3)Description
TEMPERATURE MENU MEMORY ERRORAmemoryerroroccurredandthecontrolreloadedthefactorydefaultsettings.ThecontrolstopsoperationuntilallsettingsintheSetpointsmenuarechecked.Tocleartheerror,settheaccessleveltoInstallerandcheckallsettingsintheTempmenu.
SYSTEM SETUP MENU MEMORY ERRORAmemoryerroroccurredandthecontrolreloadedthefactorydefaultsettings.ThecontrolstopsoperationuntilallsettingsintheSystemSetupmenuarechecked.Tocleartheerror,settheaccessleveltoInstallerandcheckallsettingsintheSystemSetupmenu.
BOILER SETUP MENU MEMORY ERRORAmemoryerroroccurredandthecontrolreloadedthefactorydefaultsettings.ThecontrolstopsoperationuntilallsettingsintheBoilerSetupmenuarechecked.Tocleartheerror,settheaccessleveltoInstallerandcheckallsettingsintheBoilerSetupmenu.
tekmarNet MENU MEMORY ERRORAmemoryerroroccurredandthecontrolreloadedthefactorydefaultsettings.Thecontrolcontinuesoperationasnormal.Tocleartheerror,settheaccessleveltoInstallerandcheckallsettingsinthetekmarNetmenu.
WiFi MENU MEMORY ERRORAmemoryerroroccurredandthecontrolreloadedthefactorydefaultsettings.Thecontrolcontinuesoperationasnormal.Tocleartheerror,settheaccessleveltoInstallerandcheckallsettingsintheWiFimenu.
MAX MELT DAYS ERRORThecontrolhasoperatedinmeltingforthetimesetbytheMaximumMeltDayssetting.Thiserrorisusuallycreatedwhenthereisamechanicalsystemfailureresultinginthesnowmeltslabnotheatingcorrectly.CleartheerrormessagebytouchingtheResetbuttonwhileviewingtheerrormessage.
tekmarNet Communications ErrorThetekmarNetcommunicationbushaseitheranopenorashortcircuit.Theresultisthattherearenocommunications.Theerrorclearsautomaticallyoncethewiringfaulthasbeencorrected.Toforcetheerrortoclearwhileallowingashortoropencircuittocontinue,touchtheResetkey.
Troubleshooting
!Itisrecommendedtocompleteallwiringtoensuretroublefreeoperation.Shouldanerroroccur,simplyfollowthesesteps:
34of36© 2019 tekmar 671_D - 08/19
Description
ADDRESS TAKEN ERRORTwodeviceshavebeenmanuallysettothesameaddress.ThedevicecontinuestooperatewiththiserrorbutdoesnotcommunicatewiththetekmarNetsystem.Toclearthiserror,selectanunusedtekmarNetaddressorselectautomaticaddressing.
SNOW ZONE TAKEN ERRORTwosnowmeltingcontrolshavebeenmanuallysettothesamesnowzonenumber.Thecontrolcontinuestooperatewiththiserror.Toclearthiserror,selectanunusedsnowzonenumber.
SYSTEM CONTROL LOST ERRORThethermostatcannolongercommunicatetothetekmarNetsystemcontrol.CheckforopenorshortcircuitsinthetekmarNetcommunicationwiring.TheerrorautomaticallyclearsoncethetekmarNetsystemcontrolhasbeendetected.IfthetekmarNetsystemcontrolwasintentionallyremovedfromthesystem,presstheResetbutton.
TANDEM SNOW/ICE SENSOR ERRORTherearetwoSnow/IceSensorsinstalledinthezoneandthetandemsnowmeltingcontrol654sensorhasaproblem.LocatetheothersnowmeltingcontrolandnavigatetotheToolboxmenutodetermineandcorrecttheproblem.Thecontrolcontinuestooperatewiththiserror.PresstheResetbuttontocleartheerror.
DEVICE LIMIT ERRORMorethan24deviceshavebeenconnectedtothetekmarNetcommunicationbus.Tocleartheerror,removeandrelocatedevicestootheravailablebusesuntilthedevicecountis24orless.
OUTDOOR SENSOR OPEN CIRCUIT ERRORThecontrolisunabletoreadtheOutdoorSensor070.Thecontrolcontinuestooperateandassumesanoutdoortemperatureof32°F(0°C).Checkforwiringfaultsanditmaybenecessarytoreplacethesensor.Oncetheerrorhasbeencorrected,theerrormessageautomaticallyclears.
OUTDOOR SENSOR SHORT CIRCUIT ERRORThecontrolisunabletoreadtheOutdoorSensor070.Thecontrolcontinuestooperateandassumesanoutdoortemperatureof32°F(0°C).Checkforwiringfaultsanditmaybenecessarytoreplacethesensor.Oncetheerrorhasbeencorrected,theerrormessageautomaticallyclears.
SLAB SENSOR OPEN CIRCUITThecontrolisunabletoreadtheSlabSensor072or073.Checkforwiringfaultsanditmaybenecessarytoreplacetheslabsensor.Oncetheerrorhasbeencorrected,theerrormessageautomaticallyclears.
SLAB SENSOR SHORT CIRCUITThecontrolisunabletoreadtheSlabSensor072or073.Checkthewireforfaultsanditmaybenecessarytoreplacetheslabsensor.Oncetheerrorhasbeencorrected,theerrormessageautomaticallyclears.
SNOW SENSOR YELLOW WIRE OPEN CIRCUITThecontrolisunabletoreadtheyellowwireconnectedtotheSnow/IceSensor090or094ortheSnowSensor095.Automaticoperationisdisabledbutmanualstartisstillavailable.Checkthesnow/icesensoryellowandblackwiresandanywiresplicesforfaults.Itmaybenecessarytoreplacethesensor.Oncetheerrorhasbeencorrected,theerrormessageautomaticallyclears.
SNOW SENSOR BLUE WIRE OPEN CIRCUIT ERRORDuetoanopencircuit,thecontrolisunabletoreadthebluewireconnectedtotheSnow/IceSensor090or094,ortheSnowSensor095onterminals2and3.Thecontrolcannolongerautomaticallydetectsnoworice,butmanualstartofthesnowmeltingsystemisstillavailable.Checkthesnow/icesensororsnowsensorblueandblackwiresandanywiresplicesforopencircuitsaccordingtothesensorinstallationmanual.Itmaybenecessarytoreplacethesensor.Oncetheerrorhasbeencorrected,theerrormessageautomaticallyclears.
SNOW SENSOR BROWN WIRE SHORT CIRCUIT ERRORThecontrolisunabletoreadthebrownwireconnectedtotheSnow/IceSensor090or094.Checkthesnow/icesensorbrownandblackwiresforfaults.Itmaybenecessarytoreplacethesensor.Oncetheerrorhasbeencorrected,theerrormessageautomaticallyclears.
SNOW SENSOR BROWN WIRE OPEN CIRCUIT ERRORDuetoanopencircuit,thecontrolisunabletoreadthebrownwireconnectedtotheSnow/IceSensor090or094onterminals2and5.IdlingandStormisdisabledandenergysavingfeaturessuchasWarmWeatherShutDown(WWSD)andColdWeatherCutOff(CWCO)areoperatedusingtheoutdoortemperatureonly.Checkthesnow/icesensorbrownandblackwiresforopencircuitsaccordingtothesensorinstallationmanual.Itmaybenecessarytoreplacethesensor.Oncetheerrorhasbeencorrected,theerrormessageautomaticallyclears.
Error Messages (2 of 3)
© 2019 tekmar 671_D - 08/1935of36
Symptom Look For... Corrective Action
Touchscreen is off Power to control Useelectricalmetertomeasure115V(ac)voltageoninputpowerLandN
terminals.
System pump always on Display shows Idle Idleoperationrequiresthatthesystempumpoperatecontinuouslywhilebelowthe
meltingtemperaturesetting.
Blue short Dirt or salt on snow/ice sensor
Thesnow/icesensorrequiresregularcleaning.Avoidusingroadsaltonthesnowmeltingslab.
Slab is above melt temperature
Slab Target Theslabisheatedtotheslabtarget.
System running with no snow
System is Idling IdlingheatstheslabwhenthetemperaturefallsbelowtheIdletemperature.
System is MeltingDuringcoldweathercutoff(CWCO),thesystemisshutoff.Ifitshutsoffduringameltcycle,thesystemresumesmeltingoncetheoutdoortemperatureisaboveCWCO.
Remaining Run Time Systemmanuallystarted.
Slab and Slab Target
Theslabmustreachtheslabtargettemperatureinorderforthesystemtoshutoff.Lowerthecoldweathercutoff(CWCO)orincreasetheboileraquastatsetting.
Snow on slab but system did not start
System is Off Systemhasbeenmanuallystoppedandtheautomaticsnow/icesensorneverdried,therebypreventingthesystemfromautomaticallystarting.
Cannot register device
Check WiFi signal strength Mayneedtomovecontrolorrouterlocation.
Frequently Asked Questions Description
SNOW/ICE SENSOR ERRORThecontrolisunabletoproperlydetecttheSnow/IceSensor090or094onterminals1,2,3,4and5.Thecontrolcannolongerautomaticallydetectsnoworice,butmanualstartofthesnowmeltingsystemisstillavailable.Checkthesnow/icesensorbrown,yellow,redandblackwiresaccordingtothesensorinstallationmanual.Itisimportanttocheckanycablesplicesforloosewiringconnections.Itmaybenecessarytoreplacethesensor.Oncetheerrorhasbeencorrected,theerrormessageautomaticallyclears.
SNOW SENSOR ERRORThecontrolisunabletoproperlydetecttheSnowSensor095onterminals1,2,3,and4.Thecontrolcannolongerautomaticallydetectsnowbutmanualstartofthesnowmeltingsystemisstillavailable.Checkthesnowsensoryellow,redandblackwiresaccordingtothesensorinstallationmanual.Itmaybenecessarytoreplacethesensor.Oncetheerrorhasbeencorrected,theerrormessageautomaticallyclears.
Frequently Asked Questions
671_D - 08/19 36 of 36 © 2019 tekmar
Tel: (250) 545-7749 • Fax: (250) 984-0815 tekmarControls.com
All specifications are subject to change without notice
Limited Warranty The liability of tekmar under this warranty is limited. The Purchaser, by taking receipt of any tekmar product (“Product”), acknowl-edges the terms of the Limited Warranty in effect at the time of such Product sale and acknowledges that it has read and understands same.
The tekmar Limited Warranty to the Purchaser on the Products sold hereunder is a manufacturer’s pass-through warranty which the Purchaser is authorized to pass through to its customers. Under the Limited Warranty, each tekmar Prod-uct is warranted against defects in workmanship and materials if the Product is installed and used in compliance with tekmar’s instructions, ordinary wear and tear excepted. The pass-through warranty period is for a period of twen-ty-four (24) months from the production date if the Product is not installed during that period, or twelve (12) months from the documented date of installation if installed within twenty-four (24) months from the production date.
The liability of tekmar under the Limited Warranty shall be limited to, at tekmar’s sole discretion: the cost of parts and labor provided by tekmar to repair defects in materials and / or workmanship of the defective product; or to the exchange of the defective product for a warranty replacement product; or to the granting of credit limited to the original cost of the defective product, and such repair, exchange or credit shall be the sole remedy available from tekmar, and, without limiting the foregoing in any way, tekmar is not responsible, in contract, tort or strict prod-uct liability, for any other losses, costs, expenses, inconveniences, or damages, whether direct, indirect, special, secondary, incidental or consequential, arising from ownership or use of the product, or from defects in workmanship or materials, including any liability for fundamental breach of contract.
The pass-through Limited Warranty applies only to those defective Products returned to tekmar during the warranty period. This Limited Warranty does not cover the cost of the parts or labor to remove or transport the defective Product, or to reinstall the repaired or replacement Product, all such costs and expenses being subject to Purchaser’s agreement and warranty with its customers.
Any representations or warranties about the Products made by Purchaser to its cus-tomers which are different from or in excess of the tekmar Limited Warranty are the Purchaser’s sole responsibility and obligation. Purchaser shall indemnify and hold
tekmar harmless from and against any and all claims, liabilities and damages of any kind or nature which arise out of or are related to any such representations or war-ranties by Purchaser to its customers.
The pass-through Limited Warranty does not apply if the returned Product has been damaged by negligence by persons other than tekmar, accident, fire, Act of God, abuse or misuse; or has been damaged by modifications, alterations or attachments made subsequent to purchase which have not been authorized by tekmar; or if the Product was not installed in compliance with tekmar’s instructions and / or the local codes and ordinances; or if due to defective installation of the Product; or if the Prod-uct was not used in compliance with tekmar’s instructions.
THIS WARRANTY IS IN LIEU OF ALL OTHER WARRANTIES, EXPRESS OR IMPLIED, WHICH THE GOVERNING LAW ALLOWS PARTIES TO CONTRACTU-ALLY EXCLUDE, INCLUDING, WITHOUT LIMITATION, IMPLIED WARRANTIES OF MERCHANTABILITY AND FITNESS FOR A PARTICULAR PURPOSE, DURA-BILITY OR DESCRIPTION OF THE PRODUCT, ITS NON-INFRINGEMENT OF ANY RELEVANT PATENTS OR TRADEMARKS, AND ITS COMPLIANCE WITH OR NON-VIOLATION OF ANY APPLICABLE ENVIRONMENTAL, HEALTH OR SAFETY LEGISLATION; THE TERM OF ANY OTHER WARRANTY NOT HEREBY CONTRACTUALLY EXCLUDED IS LIMITED SUCH THAT IT SHALL NOT EXTEND BEYOND TWENTY-FOUR (24) MONTHS FROM THE PRODUCTION DATE, TO THE EXTENT THAT SUCH LIMITATION IS ALLOWED BY THE GOVERNING LAW.
Product Warranty Return Procedure All Products that are believed to have defects in workmanship or materials must be returned, together with a written description of the defect, to the tekmar Representative assigned to the territory in which such Product is located. If tekmar receives an inquiry from someone other than a tekmar Representative, including an inquiry from Purchaser (if not a tekmar Representative) or Purchaser’s customers, regarding a potential warranty claim, tekmar’s sole obligation shall be to provide the address and other contact informa-tion regarding the appropriate Representative.
WARNING: This product contains chemicals known to the State of California to cause cancer and birth defects or other reproductive harm. For more information: Watts.com/prop65
Limited Warranty and Product Return Procedure
Technical DataWiFi Snow Melting Control 671 Pulse Width ModulationLiterature 671_A,671_C,671_D,671_J,671_UControl Microprocessorcontrol.Thisisnotasafety(limit)control.Packagedweight 4.3lb.(1960g)Dimensions 6-5/8"Hx7-9/16"Wx2-13/16"D(170x193x72mm)Display 3.5",colortouchscreenEnclosure BluePVCplastic,NEMAtype1Approvals CSACUS,meetsclassB:ICES&FCCPart15Ambientconditions -4to122°F(-20to50°C),<90%RHnon-condensing,outdoorusepermittedwhenusedinNEMA3enclosurePowersupply 115V(ac)±10%,60Hz,20VARelays 230V(ac),5A,1/3hpManualmeltcall Shortor0-32V(ac)Communications WiFi802.11n,2.4GHz,WPA2encryptionSensors NTCthermistor,10kΩ@77°F(25°C±0.2°C)ß=3892
–Included OutdoorSensor070–Optional tekmartype:072,073,087,090,094,095