installation instructions - lennox · pdf fileinstallation instructions dave lennox signature...

Download INSTALLATION INSTRUCTIONS - Lennox · PDF fileINSTALLATION INSTRUCTIONS Dave Lennox Signature ... 506923−01 7/2012 Supersedes 4/2012 WARNING Improper installation, adjustment, alteration,

If you can't read please download the document

Upload: haque

Post on 06-Feb-2018

227 views

Category:

Documents


2 download

TRANSCRIPT

  • Page 17/2012 50692301

    2012 Lennox Industries Inc.Dallas, Texas, USA

    THIS MANUAL MUST BE LEFT WITH THEHOMEOWNER FOR FUTURE REFERENCE

    WARNINGThe State of California has determined that this productmay contain or produce a chemical or chemicals, in verylow doses, which may cause serious illness or death. Itmay also cause cancer, birth defects, or reproductiveharm.

    General

    This XC21 outdoor unit is designed for use with HFC410Arefrigerant only. This unit must be installed with an ap-proved indoor unit. See the Lennox XC21 Product Specifi-cations bulletin (EHB) for approved indoor componentmatch ups.

    These instructions are intended as a general guide and donot supersede local codes in any way. Consult authoritieshaving jurisdiction before installation.

    INSTALLATIONINSTRUCTIONS

    Dave Lennox Signature

    Collection XC21 System

    AIR CONDITIONERS506923017/2012Supersedes 4/2012

    WARNINGImproper installation, adjustment, alteration, service ormaintenance can cause property damage, personal inju-ry or loss of life.

    Installation and service must be performed by a licensedprofessional installer (or equivalent) or service agency.

    CAUTIONBefore attempting to perform any service or mainte-nance, turn the electrical power to unit OFF at discon-nect switch.

    NOTICE !

    For more indepth information, consult the Installa-tion and Service Procedures manual, available asCorp.1007L2 on DaveNet or through the TechnicalSupport department at 8004536669.

    STEP 1 SETTING THE UNIT Clearances

    CONTROLPANEL ACCESS

    LOCATION

    6 (152)

    36 (914)

    12 (305)30 (762)

    24(610)

    LINE SETCONNECTIONS

    ACCESS PANEL

    REAR VIEW OF UNIT

    48 (1219)

    MINIMUM CLEARANCE BETWEEN TWO UNITS

    CLEARANCE ON ALL SIDES INCHES (MILLIMETERS) MINIMUM CLEARANCEABOVE UNIT

    NOTES: Clearance to access panel must be 30

    inches (762mm).

    Clearance to one of the other threesides must be 36 inches (914mm).

    Clearance to one of the remaining twosides may be 12 inches (305mm) andthe final side may be 6 inches(152mm).

    FIGURE 1

    Litho U.S.A.

  • Page 2

    UNIT DIMENSIONS INCHES (MM)

    391/2

    (1003)351/2

    (902)

    47

    (1194)

    181/2

    (470)

    8 (203)

    1 (25)

    41/2

    (114)LIQUIDLINEINLET

    ELECTRICALINLETS

    SIDE VIEW ACCESS VIEW

    DISCHARGEAIR

    45/8(117)

    BASE WITH ELONGATED LEGS

    167/8(429)

    83/4(222)

    267/8(683)

    33/4 (95)

    303/4(781)

    31/8(79)

    SUCTIOnLINEINLET

    UNIT SUPPORTFEET

    STEP 1 SETTING THE UNIT (Continued) Unit Placement

    WARNINGTo prevent personal injury, as well as damage to panels,unit or structure, observe the following:

    While installing or servicing this unit, carefully stow allremoved panels so that the panels will not cause injuryto personnel, objects or nearby structures. Also, takecare to store panels where they will not be subject todamage (e.g., being bent or scratched).

    While handling or stowing the panels, consider anyweather conditions (especially wind) that may causepanels to be blown around and damaged.

    NOTICE !Roof Damage!

    This system contains both refrigerant and oil. Somerubber roofing material may absorb oil, causing therubber to degrade. Failure to follow this noticecould result in damage to roof surface.

    IMPORTANT !Exhaust vents from dryers, water heaters andfurnaces should be directed away from the outdoorunit. Prolonged exposure to exhaust gases and thechemicals contained within them may causecondensation to form on the steel cabinet and othermetal components of the outdoor unit. This willdiminish unit performance and longevity.

  • Page 3

    XC21 SERIES

    INSTALL UNIT AWAYFROM WINDOWS

    TWO 90 ELBOWS INSTALLED IN LINE SETWILL REDUCE LINE SET VIBRATION

    PLACEMENT

    FIGURE 2

    Install unit level or, if on a slope, maintain slope tolerance of 2degrees (or 2 inches per 5 feet [50 mm per 1.5 m]) away frombuilding structure.

    GROUND LEVEL

    MOUNTINGSLAB

    BUILDINGSTRUCTURE DISCHARGE AIR

    SLAB MOUNTING

    FIGURE 3

    LEG DETAIL

    BASE

    2" (50.8MM) SCH 40FEMALE THREADED

    ADAPTER

    ELEVATED SLAB MOUNTING USING FEET

    EXTENDERS

    2" (50.8MM)SCH 40 MALETHREADEDADAPTER

    Use additional 2" SCH 40 malethreaded adapters which canbe threaded into the femalethreaded adapters to makeadditional adjustments to thelevel of the unit.

    FIGURE 4

    Unit Stabilizer Bracket Use(fieldprovided):

    Always use stabilizers when unit is raisedabove the factory height. (Elevated units could become unstable ingusty wind conditions.)

    Stabilizers may be used on any unit installedon unstable and uneven surfaces.

    Concrete slab use twoplastic anchors (hole drill 1/4")

    COIL

    BASE PAN

    CORNER POST

    STABILIZING BRACKET(18 GAUGE METAL 2"

    WIDTH; HEIGHT ASREQUIRED)

    #10 X 1/2" LONGSELFDRILLING

    SHEET METALSCREWS

    #10 X 11/4" LONGHEX HD SCREW AND

    FLAT WASHER

    STABILIZING UNIT ON UNEVEN SURFACES

    ! IMPORTANT !

    FIGURE 5

    STEP 2 REFRIGERANT PIPING Flush-ing Existing Line Set & Indoor Coil

    Flush the existing line set per the following instruc-tions. For more information, refer to the Installationand Service Procedures manual available on Dave-Net. CAUTION DO NOT attempt to flush and reuse ex-isting line sets or indoor coil when the system con-tains contaminants (i.e., compressor burn out).

    NOTE When installing refrigerant lines longer than 50feet, refer to the Refrigerant Piping Design and FabricationGuidelines manual available on DaveNet (Corp. 9351L9),or contact the Technical Support Department Product Ap-plication group for assistance.

    NOTE For new or replacement line set installation, referto Service and Application Note Corp. 9112L4 (C914).

    TABLE 1REFRIGERANT LINE SET INCHES (MM)

    Models Liquid

    Line

    Vapor/

    Suction

    Line

    L15 Line Set

    024, 036

    and048

    3/8 (10) 7/8 (22) L15 line set sizes are

    dependent on unit match up.

    See XP21 Engineering

    Handbook to determine

    correct line set sizes.

    060 3/8 (10) 11/8 (29) Field Fabricated

    NOTE Some applications may required a fieldprovided 7/8" to11/8" adapter.

  • Page 4

    IMPORTANT !

    If this unit is being matched with an approved lineset or indoor unit coil that was previously chargedwith mineral oil, or if it is being matched with a coilwhich was manufactured before January of 1999,the coil and line set must be flushed prior to installa-tion. Take care to empty all existing traps. Polyol es-ter (POE) oils are used in Lennox units charged withHFC410A refrigerant. Residual mineral oil can actas an insulator, preventing proper heat transfer. Itcan also clog the expansion device and reduce sys-tem performance and capacity.

    Failure to properly flush the system per this instruc-tion and the detailed Installation and Service Proce-dures manual will void the warranty.

    WARNINGWhen using a high pressure gas such asnitrogen to pressurize a refrigeration or airconditioning system, use a regulator thatcan control the pressure down to 1 or 2psig (6.9 to 13.8 kPa).

    WARNINGRefrigerant can be harmful if it is inhaled. Refrigerantmust be used and recovered responsibly.

    Failure to follow this warning may result in personal injuryor death.

    WARNINGFire, Explosion and Personal Safety Haz-ard. Failure to follow this warning could re-sult in damage, personal injury or death.

    Never use oxygen to pressurize or purgerefrigeration lines. Oxygen, when exposedto a spark or open flame, can cause fireand/or an explosion, that could result inproperty damage, personal injury or death.

    WARNINGPolyol ester (POE) oils used with HFC410Arefrigerant absorb moisture very quickly. It is veryimportant that the refrigerant system be kept closedas much as possible. DO NOT remove line set capsor service valve stub caps until you are ready to makeconnections.

    IMPORTANT !Some scroll compressors have an internal vacuumprotector that will unload scrolls when suction pres-sure goes below 20 psig. A hissing sound will beheard when the compressor is running unloaded.Protector will reset when low pressure in system israised above 40 psig. DO NOT REPLACE COM-PRESSOR.

    CAUTIONAs with any mechanical equipment, contact with sharpsheet metal edges can result in personal injury. Takecare while handling this equipment.

  • Page 5

    XC21 SERIES

    STEP 2 REFRIGERANT PIPING Removing Existing Indoor Metering Device

    SENSINGLINE

    TEFLON RING

    FIXED ORIFICE

    BRASS NUT

    LIQUID LINE ASSEMBLY(INCLUDES STRAINER)

    LIQUID LINE ORIFICE HOUSING

    DISTRIBUTOR TUBES

    DISTRIBUTORASSEMBLY

    REMOVE AND DISCARD

    WHITE TEFLON SEAL(IF PRESENT)

    1. On fully cased coils, remove the coil access and plumbing panels.

    2. Remove any shipping clamps from the liquid line and distributor as-sembly.

    3. Using two wrenches, disconnect liquid line from liquid line orifice hous-ing. Take care not to twist or damage distributor tubes during this pro-cess.

    4. Remove and discard fixed orifice, valve stem assembly (if present)and Teflon washer as illustrated above.

    5. Use a fieldprovided fitting to temporarily reconnect the liquid line to theindoor units liquid line orifice housing.

    TYPICAL EXISTING FIXED ORIFICEREMOVAL PROCEDURE (UNCASED COIL SHOWN)

    TYPICAL EXISTING EXPANSION VALVE REMOVALPROCEDURE (UNCASED COIL SHOWN)

    TWOPIECE PATCH PLATE(UNCASED COIL ONLY)

    VAPORLINE

    DISTRIBUTORASSEMBLY

    DISTRIBUTORTUBES

    LIQUIDLINE

    MALE EQUALIZERLINE FITTING

    EQUALIZERLINE

    EXPANSIONVA