indicators and alarm units specification sheet · 2019. 10. 12. · process alarms four internal...

6
Universal input Strain gauge input Changeover relay PV Retransmission FM/EN14597 TW Approval Scrolling text messages Parameter help text Recipes Modbus comms Multi-language support (French, German, Spanish and Italian) Indicators and Alarm Units Specification Sheet The Eurotherm range of 3200i indicators offer accurate indication of temperature and process measurements. Process interlocks, including overtemperature furnace limits, are implemented using relay output channels. The emphasis is on ease of use. A simple ‘Quick Start’ code is used to configure all the functions essential for indication and protecting your process. This includes input sensor type, measurement range and alarms making ‘Out the Box’ operation truly achievable. In operation every parameter has a scrolling text message describing its function and is available in English, German, French, Spanish or Italian. More advanced features, including scrolling text messages, are configured using iTools, a PC based configuration wizard, which is an easy to use and instructive guide to all the functions available. Universal input A wide range of temperature and process inputs can be selected using the front panel push buttons without the need for any hardware change. This provides easy on-site set up. Strain gauge input Melt pressure and weigh scale inputs can be energised from an internal 10Vdc transducer supply. An automatic shunt calibration routine is provided to remove zero and span offsets. The display on the 32h8i can show a full 5 digit value. Process alarms Four internal alarm setpoints are provided. They can be used to energise up to three relay outputs, which can be latched if required. A special mode, known as ‘Alarm Blocking’, is available which ensures that when the unit is powered up an alarm must first enter a good state before the alarm becomes active. This is particularly useful for low alarms which can be blocked while the process is warming up. SERIES 3200i

Upload: others

Post on 04-Feb-2021

3 views

Category:

Documents


0 download

TRANSCRIPT

  • • Universal input

    • Strain gauge input

    • Changeover relay

    • PV Retransmission

    • FM/EN14597 TW Approval

    • Scrolling text messages

    • Parameter help text

    • Recipes

    • Modbus comms

    • Multi-language support(French, German, Spanishand Italian)

    Indicators and Alarm Units Specification Sheet

    The Eurotherm range of 3200i indicators offer accurate indication oftemperature and process measurements. Process interlocks, includingovertemperature furnace limits, are implemented using relay outputchannels.

    The emphasis is on ease of use. A simple ‘Quick Start’ code is used toconfigure all the functions essential for indication and protecting yourprocess. This includes input sensor type, measurement range and alarmsmaking ‘Out the Box’ operation truly achievable. In operation everyparameter has a scrolling text message describing its function and isavailable in English, German, French, Spanish or Italian. More advancedfeatures, including scrolling text messages, are configured using iTools, aPC based configuration wizard, which is an easy to use and instructiveguide to all the functions available.

    Universal inputA wide range of temperature and process inputs can be selected usingthe front panel push buttons without the need for any hardware change.This provides easy on-site set up.

    Strain gauge inputMelt pressure and weigh scale inputs can be energised from an internal10Vdc transducer supply. An automatic shunt calibration routine isprovided to remove zero and span offsets. The display on the 32h8i canshow a full 5 digit value.

    Process alarmsFour internal alarm setpoints are provided. They can be used to energiseup to three relay outputs, which can be latched if required. A specialmode, known as ‘Alarm Blocking’, is available which ensures that whenthe unit is powered up an alarm must first enter a good state before thealarm becomes active. This is particularly useful for low alarms which canbe blocked while the process is warming up.

    SERIES

    3200i

  • Eurotherm Part No. HA029043 Issue 4 March 2013 2 3200i Series Specification Sheet

    Custom text messagingCustom messages can be created with iTools and downloaded tothe 3200i to display when an event, alarm or process conditionoccurs. This provides the operator with good visibility of what ishappening in the process and provides messages that they canunderstand and act upon.

    RecipesiTools recipes can be created that can be used to change theoperating parameters of the 3200i simply by selecting a recipeusing the 3200i push buttons. This is very useful where multipleproducts are processed but require different parameters to beset. It can also be used to change the set-up of a indicatortherefore allowing one unit to be used as a spare for multipleapplications.

    Analogue retransmissionThe measured process value can be retransmitted as either a mAor voltage signal with a selection of outputs including 4-20mAand 0-10V dc. In the 32h8i this signal is isolated from all otherelectronics within the unit.

    Digital communicationAll units support both EIA232 and EIA485 communication usingthe Modbus protocol as a slave device. It is also possible todigitally retransmit one parameter using a Modbus broadcast toall other Modbus devices on the network.

    Configuration adaptorPC configuration to all 3200i indicators can be achieved by usinga configuration adaptor. It provides iTools with the ability tocommunicate with and configure devices without any powerbeing connected.

    iTools wizardUsed to simplify the set up of 3200i series indicators, the wizardguides the user through the configuration process with interactivehelp and graphical demonstrations of features.

    SpecificationGeneralEnvironmental performance Temperature limits Operation: 0 to 55°C

    Storage: -10 to 70°CHumidity limits Operation: 5 to 90% RH non condensing

    Storage: 5 to 90% RH non condensingPanel sealing: IP65, Nema 4XShock: BS EN61010Vibration: 2g peak, 10 to 150HzAltitude:

  • Eurotherm Part No. HA029043 Issue 4 March 2013 3 3200i Series Specification Sheet

    Process variable inputCalibration accuracy: 600Ω, closed

  • Eurotherm Part No. HA029043 Issue 4 March 2013 4 3200i Series Specification Sheet

    X DisabledR Changeover Relay

    VH 85-264V acVL 24V ac or dc

    AL Standard alarm unitFM FM alarm unitDN EN14597TW alarm unitSG 32h8i Strain Gauge input

    ENG EnglishFRA FrenchGER GermanSPA SpanishITA Italian

    3216i 48 x 48mm unit32h8i 96 x 48mm horizontal unit3204i 96 x 96mm unit

    3216iOP1 OP2

    LRXX Logic RelayRRXX Relay RelayLDXX Logic 0-20mADDXX 0-20mA 0-20mADRXX Analogue RelayRXXX Relay None32h8i/3204i

    OP1 OP2 OP3RXXX RelayRXDX Relay Isolated

    0-20mA

    G GreenS Silver

    ENG EnglishFRA FrenchGER GermanSPA SpanishITA Italian

    XXXXX StandardWL005 Extended

    XXXXX NoneCERT1 Certificate of ConformityCERT2 Factory Calibration

    Certificate

    XXXXX None

    XXXXX NoneRES250 250R resistor for 0-5V dc OPRES500 500R resistor for 0-10V dc OP

    Function

    Supply Voltage

    Basic Product

    2

    1

    1 2 3 4 5 6 7 8 9 10 11

    Outputs3

    AA Relay (OP4)4

    Options Board5

    Fascia Colour6

    Product Language7

    Warranty10

    Certificates11

    12

    Manual Language8Custom Label12

    Specials and Accessories13

    264V ac Double

    264V ac Double

    264V ac Double

    Power

    Relays

    PowerSupplyCircuits

    Rectification

    µP &systemcircuits

    All logic inputs and Outputs

    & DC modules

    Micro mountedPV Input

    Serial Comms

    264V ac Double

    264V ac Double

    264V ac Double

    264V ac Double

    Power

    264V ac Double

    Analogue (OP3)output

    Relays

    Serial Comms

    PowerSupplyCircuits

    Rectification

    All logic inputs and Outputs

    & DC modules

    Transmitter PSU

    Micro mountedPV Input

    µP &systemcircuits

    3216i Isolation32h8i/3204i Isolation

    Hardware/options coding

    Order codes

    3216iXXX NoneXXL Digital input A2XL RS232 and Digital input A4XL RS2485 and Digital input A32h8i/3204iXXX NoneXXL Digital input A2XL RS232 and Digital input A4XL RS2485 and Digital input A32h8i/SG OptionsXXX None2XX RS232 4XX RS2485

    XX NoneV1 0-10V dcA1 mA burden resistor

    (2.49R, 0.1%)

    Input Adaptor9

    13

    3200i AccessoriesHA029005 User guideHA027986 Engineering manualSUB35/ACCESS/249R.1 2.49R Precision resistoriTools/None/3000CK Configuration clipSUB21/IV10 0-10V input adaptorSUB32/SNUBBER RC Snubber

  • Eurotherm Part No. HA029043 Issue 4 March 2013 5 3200i Series Specification Sheet

    Optional quick start code (Optional)

    ThermocoupleB Type BJ Type JK Type KL Type LN Type NR Type RS Type ST Type TC Custom/Type CRTDP Pt100LinearM 0-80mV2 0-20mA4 4-20mA32h8i onlyLinear0 0-10V dc1 1-5V dc3 2-10V6 0-5VStrain GaugeG Strain guage

    X NoneC CentigradeF FahrenheitK KelvinP Percentage32h8i onlyPressure0 Pa1 mPa2 Kpa3 Bar4 mBar5 PSI6 Kg/cm27 mmWG8 inWG9 mmHGA TorrFlow RateB L-HD L-mGeneralE %RHG %O2H %CO2J %CPL VM AmpsR mAT MVU OhmW ppmY RPMZ m-s

    Input Type

    Display Units

    32h8ionly

    2

    1

    1 2 3 4 5 6 7 8 9 10

    0 nnnnn1 nnnn.n2 nnn.nn3 nn.nnn4 n.nnnn

    Decimal point 3

    PV Colour (32h8i only)4

    X Not applicableG GreenR RedC Change on any alarm.

    Green to Red

    X UnconfiguredRelay, Triac or Logic outputsAlarm 1H High AlarmL Low AlarmR Rising Rate of ChangeN New AlarmO Sensor BreakP Power FailCombined with Sensor Break7 High Alarm8 Low Alarm9 Rising Rate of ChangeCombined with Power Fail A High AlarmB Low AlarmC Rising Rate of ChangeCombined with Sensor Break andPower FailE High AlarmF Low AlarmG Rising Rate of ChangeDigital input (3216i only)Logic inputW Alarm AcknowledgeK KeylockU Remote UP ButtonD Remote DOWN buttonJ Alarm InhibitM Peak ResetY Freeze Displayed PVV Recipe 1/2 Select

    Home Display5

    N PV onlyA First Alarm SP only1 PV + Alarm SP2 PV + Alarm SP (read only)

    Range Low6

    Enter Value(Limited by decimal point position)

    Range High7

    Enter Value(Limited by decimal point position)

    OP18

    OP2 (3216i)/OP3 (32h8i, 3204i)

    9

    X UnconfiguredAlarm 4 PV RetransmissionH High AlarmL Low AlarmR Rising Rate of ChangeN New AlarmO Sensor BreakP Power FailCombined with Sensor Break 7 High Alarm8 Low Alarm9 Rising Rate of ChangCombined with Power FailA High AlarmB Low AlarmC Rising Rate of ChangeCombined with Sensor Break andPower FailE High AlarmF Low AlarmG Rising Rate of Change

    OP4 (AA Relay)10

    Digital Input A11

    X UnconfiguredW Alarm AcknowledgeK KeylockU Remote UP ButtonD Remote DOWN buttonJ Alarm InhibitM Peak ResetY Freeze Displayed PVV Recipe 1/2 Select

    Digital Input B12

    X UnconfiguredW Alarm AcknowledgeK KeylockU Remote UP ButtonD Remote DOWN buttonJ Alarm InhibitM Peak ResetY Freeze Displayed PVV Recipe 1/2 Select32h8i Strain Gauge T Tare correctionZ Auto shunt (melt pressure)

    Calibration

    Notes

    1. Range low and range high valuesmust be entered. These two valueswill scale the range of linear inputsand the low and high setpoint limitsfor all input types. By default allalarm outputs will be latched,energised in alarm manual resetting.This gives conformationtoEN14597TW and FM.

    2. Digital input B is always fitted inthe 32h8i and 3204i. It is notavailable in 3216i.

    X UnconfiguredAnalogue outputsPV Retransmission1 4-20mA2 0-20mA3 0-5V dc4 1-5V dc5 0-10V dc6 2-10V dcRelay or Logic output Alarm 2 (3216i only) H High AlarmL Low AlarmR Rising Rate of ChangeN New AlarmO Sensor BreakP Power FailCombined with Sensor Break 7 High Alarm8 Low Alarm9 Rising Rate of ChangCombined with Power FailA High AlarmB Low AlarmC Rising Rate of ChangeCombined with Sensor Break andPower FailE High AlarmF Low AlarmG Rising Rate of Change

    1211

  • ABACHDHEHF

    1B2A2BLBLC

    Ext+Ext–Cal2Cal1+–

    3A3B3C3DLN

    AA

    AB

    AC

    HD

    HE

    HF

    1A1B

    2A2B

    LBLC

    CT

    CLA

    VI

    V+

    V-

    3A3B

    3C3D

    LN

    Dig in 2

    COM

    A (+)

    B (–)

    +

    +

    Dig in B

    mA

    RTD

    OP4

    24V dc Transmitter supply

    Line

    Neutral

    100 to 240V ac24V ac/dc

    AA

    AB

    AC

    VI

    V+

    V-

    1A1B

    2A2B

    LN

    Line

    Neutral

    100 to 240V ac24V ac/dc

    COM

    A(+)

    B(–)

    CT

    mA

    RTD

    Dig in A

    HD

    HE

    HF

    CT

    CLA

    32h8i/3204i

    3216i

    OP3

    NO

    C

    NC

    OP4

    NO

    C

    NC

    +

    +

    –OP1

    NO

    C

    +

    +

    –OP2

    NO

    C

    32h8i OrientationStrain Guage Input

    Signal Txder Supply

    Rear Terminals

    3208 Panel cut-out 92mm (–0.0 +0.8) x 45mm (–0.0 +0.6)3204 Panel cut-out 92mm (–0.0 +0.8) x 92mm (–0.0 +0.8)

    3204i

    96mm 90mm101mm

    96m

    m

    32h8 Panel cut-out 45mm (–0.0 +0.6) x 92mm (–0.0 +0.8)3216 Panel cut-out 45mm (–0.0 +0.6) x 45mm (–0.0 +0.6)

    48m

    m

    3216i

    48mm 90mm101mm

    96mm

    32h8i

    Mechanical Details

    Eurotherm Part No. HA029043 Issue 4 March 2013 6 3200i Series Specification Sheet

    Eurotherm Head OfficeFaraday Close, Durrington,Worthing, West Sussex, BN13 3PL

    Worldwide Officeswww.eurotherm.com/global

    Sales EnquiriesT +44 (01903) 695888F 0845 130 9936

    General EnquiriesT +44 (01903) 268500F 0845 265982

    Represented by:

    © Copyright Eurotherm Limited 2013

    Invensys, Eurotherm, the Eurotherm logo, Chessell, EurothermSuite, Mini8, Eycon, Eyris, EPower, EPack, nanodac, piccolo, Foxboro andWonderware are trademarks of Invensys plc, its subsidiaries and affiliates. All other brands may be trademarks of their respective owners.

    All rights are strictly reserved. No part of this document may be reproduced, modified, or transmitted in any form by any means, nor may it bestored in a retrieval system other than for the purpose to act as an aid in operating the equipment to which the document relates, without the priorwritten permission of Eurotherm Limited.

    Eurotherm Limited pursues a policy of continuous development and product improvement. The specifications in this document may therefore bechanged without notice. The information in this document is given in good faith, but is intended for guidance only.

    Eurotherm Limited will accept no responsibility for any losses arising from errors in this document.

    Contact Information

    Scan forlocal contacts

    Eurotherm: International sales and support www.eurotherm.com