indicators and alarm units specification sheet · 2019. 10. 12. · process alarms four internal...
TRANSCRIPT
-
• Universal input
• Strain gauge input
• Changeover relay
• PV Retransmission
• FM/EN14597 TW Approval
• Scrolling text messages
• Parameter help text
• Recipes
• Modbus comms
• Multi-language support(French, German, Spanishand Italian)
Indicators and Alarm Units Specification Sheet
The Eurotherm range of 3200i indicators offer accurate indication oftemperature and process measurements. Process interlocks, includingovertemperature furnace limits, are implemented using relay outputchannels.
The emphasis is on ease of use. A simple ‘Quick Start’ code is used toconfigure all the functions essential for indication and protecting yourprocess. This includes input sensor type, measurement range and alarmsmaking ‘Out the Box’ operation truly achievable. In operation everyparameter has a scrolling text message describing its function and isavailable in English, German, French, Spanish or Italian. More advancedfeatures, including scrolling text messages, are configured using iTools, aPC based configuration wizard, which is an easy to use and instructiveguide to all the functions available.
Universal inputA wide range of temperature and process inputs can be selected usingthe front panel push buttons without the need for any hardware change.This provides easy on-site set up.
Strain gauge inputMelt pressure and weigh scale inputs can be energised from an internal10Vdc transducer supply. An automatic shunt calibration routine isprovided to remove zero and span offsets. The display on the 32h8i canshow a full 5 digit value.
Process alarmsFour internal alarm setpoints are provided. They can be used to energiseup to three relay outputs, which can be latched if required. A specialmode, known as ‘Alarm Blocking’, is available which ensures that whenthe unit is powered up an alarm must first enter a good state before thealarm becomes active. This is particularly useful for low alarms which canbe blocked while the process is warming up.
SERIES
3200i
-
Eurotherm Part No. HA029043 Issue 4 March 2013 2 3200i Series Specification Sheet
Custom text messagingCustom messages can be created with iTools and downloaded tothe 3200i to display when an event, alarm or process conditionoccurs. This provides the operator with good visibility of what ishappening in the process and provides messages that they canunderstand and act upon.
RecipesiTools recipes can be created that can be used to change theoperating parameters of the 3200i simply by selecting a recipeusing the 3200i push buttons. This is very useful where multipleproducts are processed but require different parameters to beset. It can also be used to change the set-up of a indicatortherefore allowing one unit to be used as a spare for multipleapplications.
Analogue retransmissionThe measured process value can be retransmitted as either a mAor voltage signal with a selection of outputs including 4-20mAand 0-10V dc. In the 32h8i this signal is isolated from all otherelectronics within the unit.
Digital communicationAll units support both EIA232 and EIA485 communication usingthe Modbus protocol as a slave device. It is also possible todigitally retransmit one parameter using a Modbus broadcast toall other Modbus devices on the network.
Configuration adaptorPC configuration to all 3200i indicators can be achieved by usinga configuration adaptor. It provides iTools with the ability tocommunicate with and configure devices without any powerbeing connected.
iTools wizardUsed to simplify the set up of 3200i series indicators, the wizardguides the user through the configuration process with interactivehelp and graphical demonstrations of features.
SpecificationGeneralEnvironmental performance Temperature limits Operation: 0 to 55°C
Storage: -10 to 70°CHumidity limits Operation: 5 to 90% RH non condensing
Storage: 5 to 90% RH non condensingPanel sealing: IP65, Nema 4XShock: BS EN61010Vibration: 2g peak, 10 to 150HzAltitude:
-
Eurotherm Part No. HA029043 Issue 4 March 2013 3 3200i Series Specification Sheet
Process variable inputCalibration accuracy: 600Ω, closed
-
Eurotherm Part No. HA029043 Issue 4 March 2013 4 3200i Series Specification Sheet
X DisabledR Changeover Relay
VH 85-264V acVL 24V ac or dc
AL Standard alarm unitFM FM alarm unitDN EN14597TW alarm unitSG 32h8i Strain Gauge input
ENG EnglishFRA FrenchGER GermanSPA SpanishITA Italian
3216i 48 x 48mm unit32h8i 96 x 48mm horizontal unit3204i 96 x 96mm unit
3216iOP1 OP2
LRXX Logic RelayRRXX Relay RelayLDXX Logic 0-20mADDXX 0-20mA 0-20mADRXX Analogue RelayRXXX Relay None32h8i/3204i
OP1 OP2 OP3RXXX RelayRXDX Relay Isolated
0-20mA
G GreenS Silver
ENG EnglishFRA FrenchGER GermanSPA SpanishITA Italian
XXXXX StandardWL005 Extended
XXXXX NoneCERT1 Certificate of ConformityCERT2 Factory Calibration
Certificate
XXXXX None
XXXXX NoneRES250 250R resistor for 0-5V dc OPRES500 500R resistor for 0-10V dc OP
Function
Supply Voltage
Basic Product
2
1
1 2 3 4 5 6 7 8 9 10 11
Outputs3
AA Relay (OP4)4
Options Board5
Fascia Colour6
Product Language7
Warranty10
Certificates11
12
Manual Language8Custom Label12
Specials and Accessories13
264V ac Double
264V ac Double
264V ac Double
Power
Relays
PowerSupplyCircuits
Rectification
µP &systemcircuits
All logic inputs and Outputs
& DC modules
Micro mountedPV Input
Serial Comms
264V ac Double
264V ac Double
264V ac Double
264V ac Double
Power
264V ac Double
Analogue (OP3)output
Relays
Serial Comms
PowerSupplyCircuits
Rectification
All logic inputs and Outputs
& DC modules
Transmitter PSU
Micro mountedPV Input
µP &systemcircuits
3216i Isolation32h8i/3204i Isolation
Hardware/options coding
Order codes
3216iXXX NoneXXL Digital input A2XL RS232 and Digital input A4XL RS2485 and Digital input A32h8i/3204iXXX NoneXXL Digital input A2XL RS232 and Digital input A4XL RS2485 and Digital input A32h8i/SG OptionsXXX None2XX RS232 4XX RS2485
XX NoneV1 0-10V dcA1 mA burden resistor
(2.49R, 0.1%)
Input Adaptor9
13
3200i AccessoriesHA029005 User guideHA027986 Engineering manualSUB35/ACCESS/249R.1 2.49R Precision resistoriTools/None/3000CK Configuration clipSUB21/IV10 0-10V input adaptorSUB32/SNUBBER RC Snubber
-
Eurotherm Part No. HA029043 Issue 4 March 2013 5 3200i Series Specification Sheet
Optional quick start code (Optional)
ThermocoupleB Type BJ Type JK Type KL Type LN Type NR Type RS Type ST Type TC Custom/Type CRTDP Pt100LinearM 0-80mV2 0-20mA4 4-20mA32h8i onlyLinear0 0-10V dc1 1-5V dc3 2-10V6 0-5VStrain GaugeG Strain guage
X NoneC CentigradeF FahrenheitK KelvinP Percentage32h8i onlyPressure0 Pa1 mPa2 Kpa3 Bar4 mBar5 PSI6 Kg/cm27 mmWG8 inWG9 mmHGA TorrFlow RateB L-HD L-mGeneralE %RHG %O2H %CO2J %CPL VM AmpsR mAT MVU OhmW ppmY RPMZ m-s
Input Type
Display Units
32h8ionly
2
1
1 2 3 4 5 6 7 8 9 10
0 nnnnn1 nnnn.n2 nnn.nn3 nn.nnn4 n.nnnn
Decimal point 3
PV Colour (32h8i only)4
X Not applicableG GreenR RedC Change on any alarm.
Green to Red
X UnconfiguredRelay, Triac or Logic outputsAlarm 1H High AlarmL Low AlarmR Rising Rate of ChangeN New AlarmO Sensor BreakP Power FailCombined with Sensor Break7 High Alarm8 Low Alarm9 Rising Rate of ChangeCombined with Power Fail A High AlarmB Low AlarmC Rising Rate of ChangeCombined with Sensor Break andPower FailE High AlarmF Low AlarmG Rising Rate of ChangeDigital input (3216i only)Logic inputW Alarm AcknowledgeK KeylockU Remote UP ButtonD Remote DOWN buttonJ Alarm InhibitM Peak ResetY Freeze Displayed PVV Recipe 1/2 Select
Home Display5
N PV onlyA First Alarm SP only1 PV + Alarm SP2 PV + Alarm SP (read only)
Range Low6
Enter Value(Limited by decimal point position)
Range High7
Enter Value(Limited by decimal point position)
OP18
OP2 (3216i)/OP3 (32h8i, 3204i)
9
X UnconfiguredAlarm 4 PV RetransmissionH High AlarmL Low AlarmR Rising Rate of ChangeN New AlarmO Sensor BreakP Power FailCombined with Sensor Break 7 High Alarm8 Low Alarm9 Rising Rate of ChangCombined with Power FailA High AlarmB Low AlarmC Rising Rate of ChangeCombined with Sensor Break andPower FailE High AlarmF Low AlarmG Rising Rate of Change
OP4 (AA Relay)10
Digital Input A11
X UnconfiguredW Alarm AcknowledgeK KeylockU Remote UP ButtonD Remote DOWN buttonJ Alarm InhibitM Peak ResetY Freeze Displayed PVV Recipe 1/2 Select
Digital Input B12
X UnconfiguredW Alarm AcknowledgeK KeylockU Remote UP ButtonD Remote DOWN buttonJ Alarm InhibitM Peak ResetY Freeze Displayed PVV Recipe 1/2 Select32h8i Strain Gauge T Tare correctionZ Auto shunt (melt pressure)
Calibration
Notes
1. Range low and range high valuesmust be entered. These two valueswill scale the range of linear inputsand the low and high setpoint limitsfor all input types. By default allalarm outputs will be latched,energised in alarm manual resetting.This gives conformationtoEN14597TW and FM.
2. Digital input B is always fitted inthe 32h8i and 3204i. It is notavailable in 3216i.
X UnconfiguredAnalogue outputsPV Retransmission1 4-20mA2 0-20mA3 0-5V dc4 1-5V dc5 0-10V dc6 2-10V dcRelay or Logic output Alarm 2 (3216i only) H High AlarmL Low AlarmR Rising Rate of ChangeN New AlarmO Sensor BreakP Power FailCombined with Sensor Break 7 High Alarm8 Low Alarm9 Rising Rate of ChangCombined with Power FailA High AlarmB Low AlarmC Rising Rate of ChangeCombined with Sensor Break andPower FailE High AlarmF Low AlarmG Rising Rate of Change
1211
-
ABACHDHEHF
1B2A2BLBLC
Ext+Ext–Cal2Cal1+–
3A3B3C3DLN
AA
AB
AC
HD
HE
HF
1A1B
2A2B
LBLC
CT
CLA
VI
V+
V-
3A3B
3C3D
LN
Dig in 2
COM
A (+)
B (–)
–
+
–
+
Dig in B
mA
RTD
OP4
24V dc Transmitter supply
Line
Neutral
100 to 240V ac24V ac/dc
AA
AB
AC
VI
V+
V-
1A1B
2A2B
LN
Line
Neutral
100 to 240V ac24V ac/dc
COM
A(+)
B(–)
CT
mA
RTD
Dig in A
HD
HE
HF
CT
CLA
32h8i/3204i
3216i
OP3
NO
C
NC
OP4
NO
C
NC
+
–
+
–OP1
NO
C
+
–
+
–OP2
NO
C
32h8i OrientationStrain Guage Input
Signal Txder Supply
Rear Terminals
3208 Panel cut-out 92mm (–0.0 +0.8) x 45mm (–0.0 +0.6)3204 Panel cut-out 92mm (–0.0 +0.8) x 92mm (–0.0 +0.8)
3204i
96mm 90mm101mm
96m
m
32h8 Panel cut-out 45mm (–0.0 +0.6) x 92mm (–0.0 +0.8)3216 Panel cut-out 45mm (–0.0 +0.6) x 45mm (–0.0 +0.6)
48m
m
3216i
48mm 90mm101mm
96mm
32h8i
Mechanical Details
Eurotherm Part No. HA029043 Issue 4 March 2013 6 3200i Series Specification Sheet
Eurotherm Head OfficeFaraday Close, Durrington,Worthing, West Sussex, BN13 3PL
Worldwide Officeswww.eurotherm.com/global
Sales EnquiriesT +44 (01903) 695888F 0845 130 9936
General EnquiriesT +44 (01903) 268500F 0845 265982
Represented by:
© Copyright Eurotherm Limited 2013
Invensys, Eurotherm, the Eurotherm logo, Chessell, EurothermSuite, Mini8, Eycon, Eyris, EPower, EPack, nanodac, piccolo, Foxboro andWonderware are trademarks of Invensys plc, its subsidiaries and affiliates. All other brands may be trademarks of their respective owners.
All rights are strictly reserved. No part of this document may be reproduced, modified, or transmitted in any form by any means, nor may it bestored in a retrieval system other than for the purpose to act as an aid in operating the equipment to which the document relates, without the priorwritten permission of Eurotherm Limited.
Eurotherm Limited pursues a policy of continuous development and product improvement. The specifications in this document may therefore bechanged without notice. The information in this document is given in good faith, but is intended for guidance only.
Eurotherm Limited will accept no responsibility for any losses arising from errors in this document.
Contact Information
Scan forlocal contacts
Eurotherm: International sales and support www.eurotherm.com