Main Document Only.TITLE:
INSTALLATION, OPERATION ANDMAINTENANCE MANUAL FORAUTOMATIC SELF CLEANING
FILTERS
PROJECT:
4X360 MW THERMAL POWER STATION
OWNERS ENGINEER :
FICHTNER CONSULTING ENGG (I) PVT
OWNER :R.K.M POWERGEN PRIVATE LTD.
EMPLOYERS ENGINEER :NORTHEAST ELECTRIC POWER DESIGN.
FEIPL DOC NO. FE/RKM/ASCF/FR-2902 RKMS DRG NO: --
FEIPL JOB NO. : FR-2902 Sheet 1 of 4 Rev.0
FILTERATION ENGINEERS INDIA PVT. LTD. MUMBAI.
INSTALLATION, OPERATION AND
MAINTENANCE MANUAL
FOR
AUTOMATIC SELF CLEANING
FILTERS
-
7/28/2019 I&M Manual Self Cleaning Filter
2/4
Main Document Only.TITLE:
INSTALLATION, OPERATION ANDMAINTENANCE MANUAL FORAUTOMATIC SELF CLEANING
FILTERS
PROJECT:
4X360 MW THERMAL POWER STATION
OWNERS ENGINEER :
FICHTNER CONSULTING ENGG (I) PVT
OWNER :R.K.M POWERGEN PRIVATE LTD.
EMPLOYERS ENGINEER :NORTHEAST ELECTRIC POWER DESIGN.
FEIPL DOC NO. FE/RKM/ASCF/FR-2902 RKMS DRG NO: --
FEIPL JOB NO. : FR-2902 Sheet 2 of 4 Rev.0
FILTERATION ENGINEERS INDIA PVT. LTD. MUMBAI.
INSTALLATION, OPERATION AND MAINTENANCE MANUAL
FOR
AUTOMATIC SELF CLEANING FILTERS
CONSTRUCTION:
The filter is automatic self cleaning type, with automatic backwash arrangement. It is supplied
with automatic drain valve (electrically operated motorized type) to flush out sludge. One more
valve for manual drain arrangement is also provided. Glycerin filled pressure gauges are
provided each at inlet at outlet. Operations are initiated by both timer and the DP switch. Motor
initiates at an interval of 24 hrs. for automatic backwash for 30 sec. After 30 secs. the DV starts
closing and the timer is set for next sequence after 24 hrs. In case the DP switch initiates before
the pre set time, DP switch will override the timer, drain valve will open and same sequence will
be repeated.
The wedge wire elements are characterized by sharp defined perforations with conically shapedcross section. They are a combination of wedge wire support design cores and are non clogging.
A INSTALLATION AND OPERATION:
1. Carefully remove filter from packing case. Please note that care should be taken while
handling the filter.
2. Keep filter in vertical position, check the filter unit visually.
3. Place filter housing on foundation as per the dimensions given in the drawing.
4. Put foundation bolts and do erection of the filters by bolting/packing foundation bolts
as they use may be.
5. Before commissioning the filter remove filter element from inside of filter housing.
Carry out flushing of pipeline to remove any weld particles etc. from the pipeline.
6. After cleaning of the line put filter element in filter housing as shown in the drawing.
Put the cover and tight it with the help of nut bolts. Ensure gasket ring on filter element
and top of cover of filter body.
7. Fill the filter unit with process liquid by keeping vent open. Once the filter is filled with
liquid and all the air is removed then close vent connection.
8. After filling the filter with liquid bring the filter at working pressure to start filtration
cycle.
-
7/28/2019 I&M Manual Self Cleaning Filter
3/4
Main Document Only.TITLE:
INSTALLATION, OPERATION ANDMAINTENANCE MANUAL FORAUTOMATIC SELF CLEANING
FILTERS
PROJECT:
4X360 MW THERMAL POWER STATION
OWNERS ENGINEER :
FICHTNER CONSULTING ENGG (I) PVT
OWNER :R.K.M POWERGEN PRIVATE LTD.
EMPLOYERS ENGINEER :NORTHEAST ELECTRIC POWER DESIGN.
FEIPL DOC NO. FE/RKM/ASCF/FR-2902 RKMS DRG NO: --
FEIPL JOB NO. : FR-2902 Sheet 3 of 4 Rev.0
FILTERATION ENGINEERS INDIA PVT. LTD. MUMBAI.
9. During operation of the filter the differential pressure between inlet and outlet of filter
should not exceed the maximum differential pressure.
10. Once the differential pressure reaches the maximum limit, filter element should be
cleaned by rotating the handle provided for the purpose.
11. At the start up the pressure drop across the filter between inlet and outlet will gradually
start increasing and after some time the filter element may become saturated with
impurities, when the filter element is around 70% clogged condition the pressure drop
will start increasing rapidly.
12. If it so happens that the pressure drop suddenly happens to drop down to almost a zero
value then there may be a chance that either the element has give a weight or the
sealing gasket has given a weight. Stop the lime remove the cover and check for the
causality.
13. In case there is frequent rigid increasing pressure drop which will be the indication of
high impurity load in the stream.
14. When the filter is working at a given pressure drops and implied efficiency, no
maintenance is require on the filter. The less the filter is disturb in the working the
longer will be the life.
ADVANTAGES
1. High open area means higher throughput with the same filter dimensions.
2. Narrow tolerances mean sharp defined filtration range (almost absolute efficiency).
3. Thick plate material (compared to traditional perforated or woven material), and use of
specially chosen slot pattern mean higher durability without changing the open area. In
addition, Chrome plating can be applied for abrasive environments.
4. The use of support tubes to support the EF screen gives the filter element necessary
overall strength for high pressure applications, with a minimum loss of open area.
C. INSTALLATION
1. Install the Filter.
2. Mount the valves.
-
7/28/2019 I&M Manual Self Cleaning Filter
4/4
Main Document Only.TITLE:
INSTALLATION, OPERATION ANDMAINTENANCE MANUAL FORAUTOMATIC SELF CLEANING
FILTERS
PROJECT:
4X360 MW THERMAL POWER STATION
OWNERS ENGINEER :
FICHTNER CONSULTING ENGG (I) PVT
OWNER :R.K.M POWERGEN PRIVATE LTD.
EMPLOYERS ENGINEER :NORTHEAST ELECTRIC POWER DESIGN.
FEIPL DOC NO. FE/RKM/ASCF/FR-2902 RKMS DRG NO: --
FEIPL JOB NO. : FR-2902 Sheet 4 of 4 Rev.0
FILTERATION ENGINEERS INDIA PVT. LTD. MUMBAI.
3. Remove the element and close the filter body.
4. Start up the flow in order to clean up the up steam and down steam pipe in order to
remove any dust particles, spatters, any other harmful foreign particles that may be for
10 15 minutes.
5. When the liquid is shown overflow from the vent now the vent can be close and the line
can be run.
6. During operation the differential pressure between inlet and outlet of the filter should
not exceed the maximum differential pressure limit.
7. Once the differential pressure reaches the maximum limit it is the indication that filter is
to be take for maintenance.
MAINTENANCE OF THE FILTER ELEMENT
The typical wedge wire design is non-clogging type and therefore no dust particles of an
impurity normally interrupt in the filter element, this is the unique advantage of this type of
design and therefore for cleaning the filter element from vessel and direct adequate jet of clean
water if possible in reverse direction. All the impurities will fall down. For further cleaning dip
the element in suitable solvent for about 10 minutes. After removing from the bath again rinse
the element with clean water with adequate jet of water. Ensure that the element is dried as
much as possible before it is replaced it in the vessel this is in order to ensure minimum quantity
of impurities on the element.
For any further assistance you may contact Filteration Engineers India Pvt. Ltd. Head Office as to
the suitable of the proposed clearing procedure on any problem.