ieee generator protection tutorial presentation

211
Special Publication of the IEEE Power System Relaying Committee Copyright © IEEE 2011

Upload: shailesh-kumar

Post on 19-Feb-2015

1.089 views

Category:

Documents


26 download

DESCRIPTION

IEEE Generator Protection Tutorial by Power System Relaying Committee.These references can be downloaded from IEEE PSRC website for free.

TRANSCRIPT

Page 1: IEEE Generator Protection Tutorial Presentation

Special Publication of the IEEE Power System Relaying Committee

Copyright © IEEE 2011

Page 2: IEEE Generator Protection Tutorial Presentation

IEEE TUTORIAL ON THE PROTECTION OF SYNCHRONOUS GENERATORS

Copyright © IEEE 2011

Page 3: IEEE Generator Protection Tutorial Presentation

Developed by a working group of the Power System Relay Committee (PSRC)

First published in 1995 – widely presented within the industry, including a presentation at the 2003 PPIC Conference

Updated, published, and presented for the first time at the 2011 57th IEEE Pulp and Paper Industry Conference

Page 4: IEEE Generator Protection Tutorial Presentation

Michael Thompson, ChairChristopher Ruckman, Vice ChairHasnain AshrafiGabirel BenmouyalZeeky BukhalaStephen P. ConradEverett FennellDale FinneyDale FredricksonJonathan D. GardellJuan GersRandy HamiltonWayne HartmannGerald JohnsonPatrick M. KerriganSungsoo KimPrem Kumar

Hugo MonterrubioCharles MozinaMukesh NagpalBrent OxandaleRussell W. PattersonMike ReichardMohindar SachdevKevin StephanSudhir ThakurDemetrios TziouvarasJoe UchiyamaQuintin Verzosa, Jr.Thomas WiedmanMichael WrightJohn WangMurty V. V. S. Yalla

Page 5: IEEE Generator Protection Tutorial Presentation

5

Michael J. Thompson received his BS, magna cum laude, from Bradley University in 1981 and an MBA from Eastern Illinois University in 1991. He has broad experience in the field of power system operations and protection. Upon graduating, he served nearly 15 years at Central Illinois Public Service (now AMEREN), where he worked in distribution and substation field engineering before taking over responsibility for system protection engineering. Prior to joining Schweitzer Engineering Laboratories, Inc. in 2001, he was involved in the development of several numerical protective relays while working at Basler Electric. He is presently a Principal Engineer in SEL’s Engineering Services Division; a senior member of the IEEE; a main committee member of the IEEE PES Power System Relaying Committee; and a registered professional engineer. Michael was a contributor to the reference book, Modern Solutions for the Protection Control and Monitoring of Electric Power Systems, has published numerous technical papers, and has a number of patents associated with power system protection and control.

Page 6: IEEE Generator Protection Tutorial Presentation

6

Charles (Chuck) Mozina received a B.S. degree in electrical engineering from Purdue University, West Lafayette, in 1965. He is a Consultant, for Beckwith Electric Co. Inc., specializing in power plant and generator protection. His consulting practice involves projects relating to protective relaying applications, protection system design and coordination. Chuck is an active 25-year member of the IEEE PES Power System Relay Committee and was the past chairman of the Rotating Machinery Subcommittee. He is active in the IEEE IAS I&CPS, PCIC and PPIC Committees, which address industrial protection systems. He is the past U.S. representative to CIGRE Study Committee 34 (now B-5) on System Protection. He has over 25 years of experience as a protective engineer at Centerior Energy (now part of FirstEnergy), a major utility in Ohio, where he was Manager of System Protection. For 10 years, he was employed by Beckwith Electric as the Manager of Application Engineering for Protection Systems. He is now a consultant for that company. He is a registered Professional Engineer in the state of Ohio and a Liife Fellow of the IEEE.

Page 7: IEEE Generator Protection Tutorial Presentation

FundamentalsMultifunction Generator Protection SystemsStator Phase Fault ProtectionStator Ground Fault ProtectionField Fault ProtectionSystem Backup ProtectionGenerator Breaker FailureAbnormal Frequency ProtectionOverexcitation and Overvoltage Protection

Page 8: IEEE Generator Protection Tutorial Presentation

Underexcitation / Loss-of-Excitation ProtectionCurrent Unbalance (Negative-Sequence) ProtectionLoss of Prime Mover (Antimotoring) ProtectionOut-of-Step ProtectionVoltage Transformer Signal LossInadvertent Energization ProtectionOther Protective ConsiderationsTripping Modes

Page 9: IEEE Generator Protection Tutorial Presentation

IEEE TUTORIAL ON THE PROTECTION OF SYNCHRONOUS GENERATORS

Copyright © IEEE 2011

Page 10: IEEE Generator Protection Tutorial Presentation

Basic design and operation of synchronous generators

Power system connections

Behavior under short-circuit conditions

Generator grounding

Generator stability

IEEE guidelines

Device numbers

Page 11: IEEE Generator Protection Tutorial Presentation
Page 12: IEEE Generator Protection Tutorial Presentation
Page 13: IEEE Generator Protection Tutorial Presentation

0

+MVAR

Overexcited

Underexcited

–MVAR

Reactive Power Into System

Reactive Power Into Generator

Overexcitation Limiter (OEL)

Rotor Winding Limited

Underexcitation Limiter (UEL)

Stator End Iron Limited

Steady-State Stability Limit

Stator Winding Limited

+ MW Real Power Into System

MVARNormal Overexcited Operation

Underexcited Operation

GMW

System

GMVAR

MWSystem

Page 14: IEEE Generator Protection Tutorial Presentation
Page 15: IEEE Generator Protection Tutorial Presentation

β

X

–X

R–R

Z

2C

V

RkVMVA AngleZ R

⎛ ⎞= β⎜ ⎟

⎝ ⎠2

C

V

RkVZ AngleMVA R

⎛ ⎞= β⎜ ⎟

⎝ ⎠

Page 16: IEEE Generator Protection Tutorial Presentation
Page 17: IEEE Generator Protection Tutorial Presentation
Page 18: IEEE Generator Protection Tutorial Presentation
Page 19: IEEE Generator Protection Tutorial Presentation
Page 20: IEEE Generator Protection Tutorial Presentation
Page 21: IEEE Generator Protection Tutorial Presentation
Page 22: IEEE Generator Protection Tutorial Presentation
Page 23: IEEE Generator Protection Tutorial Presentation
Page 24: IEEE Generator Protection Tutorial Presentation

Cur

rent

Cur

rent

Cur

rent

Page 25: IEEE Generator Protection Tutorial Presentation
Page 26: IEEE Generator Protection Tutorial Presentation
Page 27: IEEE Generator Protection Tutorial Presentation

0

2000

4000

6000

8000

time, seconds0.01 0.1 1 10

wattseconds

wat

tsec

onds

TotalGenerator

System

Accumulation of Damage Over Time

Most damage occurs in period after the generator breaker opens

Page 28: IEEE Generator Protection Tutorial Presentation
Page 29: IEEE Generator Protection Tutorial Presentation

Types of Instability Steady-State

Transient

Dynamic

Page 30: IEEE Generator Protection Tutorial Presentation

( )g se g s

E EP sin

X= θ − θ

g smax

E EP

X=

g gE ∠θL4

Power Flow

L1

L3L2

POWERSYSTEM

Power System

s sE ∠θ

Page 31: IEEE Generator Protection Tutorial Presentation

X

R

Xe

d eX X2−

d eX X2+

R-X Diagram Plot

Per-Unit MVAR

Per-Unit MW

MW-MVAR Per-Unit Plot

2

e d

V 1 12 X X⎛ ⎞

+⎜ ⎟⎝ ⎠

2

e d

V 1 12 X X⎛ ⎞

−⎜ ⎟⎝ ⎠

G

Generator GSU System Reactance

Xd

VXT

XS

Where:Xe = XT + XS

Page 32: IEEE Generator Protection Tutorial Presentation

Power System

1 2

78

G

78 = Out-of-Step ProtectionEs = System VoltageEg = Generator Voltage

s = System Voltage Phase Angleg = Generator Voltage Phase Angle

T

Three-Phase Short CircuitSubstation

GSU

s sE ∠Θ

g gE ∠Θ

Page 33: IEEE Generator Protection Tutorial Presentation

g smax

E EP

X=

Maximum Power

Transfer

PM = Pe

A1

A2

All Lines in ServiceBreakers 1 and 2

Tripped

θC

0 90° 180°θg – θs

( )g se g s

E EP sin

X= θ − θ

Page 34: IEEE Generator Protection Tutorial Presentation

Occurs when fast-acting AVR control amplifies rather than damps small MW oscillations

Most likely to occur when generators are remote from load centers

Power system stabilizer (PSS) damps oscillations – required in Western United States

Page 35: IEEE Generator Protection Tutorial Presentation

Latest developments reflected inStd. 242, IAS Buff BookC37.102, IEEE Guide for Generator ProtectionC37.101, IEEE Guide for AC Generator Ground ProtectionC37.106, IEEE Guide for Abnormal Frequency Protection for Power Generating Plants

Created / maintained by the IEEE PSRC & IAS –updated every 5 years

Page 36: IEEE Generator Protection Tutorial Presentation

C37.102-2006 updated version now available – includes significant changes

and additions

Page 37: IEEE Generator Protection Tutorial Presentation

Device Number Function Tutorial Chapter11 Multifunction Protection System 5.2

21 Distance Relay – Backup for System and Generator Zone Phase Faults 2.4

24 Volts / Hertz Protection for GeneratorOverexcitation 3.2

27TN 100 Percent Stator Ground Fault Protection 2.2

32 Reverse Power Relay – Antimotoring Protection 3.5

40 Loss-of-Field Protection 3.3

46 Negative-Sequence Current UnbalanceProtection for Generators 3.4

49 Stator Thermal Protection –51G Time-Overcurrent Ground Relay 2.2

51TG 1&2 Backup for Ground Faults –

Page 38: IEEE Generator Protection Tutorial Presentation

Device Number Function Tutorial Chapter

51VVoltage-Controlled or Voltage-Restrained

Time-Overcurrent Relay – Backup for System and Generator Phase Faults

2.4

59 Overvoltage Protection 3.2

59G Overvoltage Relay – Stator Ground Fault Protection for Generators 2.2

60 Voltage Balance Relay – Detection of Blown Voltage Transformer Fuses 3.7

63 Transformer Fault Pressure Relay –62B Breaker Failure Timer 2.564F Field Ground Fault Protection 2.371 Transformer Oil or Gas Level –78 Loss-of-Synchronism Protection 3.6

Page 39: IEEE Generator Protection Tutorial Presentation

Device Number Function Tutorial Chapter

81 Frequency Relay – Both Underfrequency and Overfrequency Protection 3.1

86 Hand-Reset Lockout Auxiliary Relay 5.1

87G Differential Relay – Primary Phase Fault Protection for Generators 2.1

87N Stator Ground Fault Differential Protection 2.2

87T Differential Relay – Primary Protection for Transformers –

87U Differential Relay – Overall Generator and Transformer Protection 2.2

Page 40: IEEE Generator Protection Tutorial Presentation

60

87O

50/27

87T

S

Unit Transformer

Unit Differential

71

63Transformer Fault Pressure

Oil Low

51TG151

TG2Transformer Neutral

Overcurrent

5364F

41

Field Ground

242

Voltage Balance

Second V/Hz

78

40

81

241

Frequency

V/Hz

Loss of Synchronism

Loss of Field

59

87G

49

32

ReversePower

Generator Differential

Auxiliary VTs

46 21/51V

Negative Sequence

System Backup(Note 2)

Stat. Temp

59G

50/51G

Generator Neutral

Overvoltage

Generator Neutral

Overcurrent

63

71

UAT Oil Low

UAT Fault Pressure

UAT

5051

UAT Backup

51TG1

51TG2

UAT Neutral Overcurrent

Unit Auxiliary Bus Phase Time

Overcurrent

51

A 87T UAT Differential

(Note 1)

Inadv. Energ.(Note 4)

27TN

100 Percent Stator Ground

(Note 3)1. Dotted devices optional.2. Device 21 requires external timer. See Chapter 2.4.3. See Chapter 2.2 regarding 100 percent ground protection.4. Device 50 requires external timer. See Chapter 4.1.

Notes:

Field Breaker

Overvoltage

Page 41: IEEE Generator Protection Tutorial Presentation

IEEE TUTORIAL ON THE PROTECTION OF SYNCHRONOUS GENERATORS

Copyright © IEEE 2011

Page 42: IEEE Generator Protection Tutorial Presentation

Generator protective relaying technology has evolved from discrete electromechanical and static relays to digital multifunction protection systems

With availability, additional performance, economic advantages, and reliability of digital multifunction protection systems, this advanced technology is incorporated into most new protection schemes

Page 43: IEEE Generator Protection Tutorial Presentation

In most cases, new generators are protected with one of the following:

Dual MGPSs

Single MGPS, possibly backed up by single-function relays

Page 44: IEEE Generator Protection Tutorial Presentation

Microprocessor

Other Analog Inputs

One or More Power Supplies

Digital Inputs

ROM

RAM

Data Acquisition

System

Inputs Outputs

Voltage Inputs

Current Inputs

Targets

User Interface

EEPROM

Communications

Digital Outputs

Page 45: IEEE Generator Protection Tutorial Presentation

11GMGPS #1

Relaying Functions24

27/5932-132-240464950

51V or 2150/51G

59G607881

87G27TH or 59THD or 64S

11GMGPS #2

Relaying Functions24

27/5932-132-240464950

51V or 2150/51G

59G60

64F81

87G27TH or 59THD or 64S

52

87O

87AT87T

52

Generator Transformer

High-Voltage System Bus

Auxiliary Bus

Field

Note: Only use functions as appropriate.

Page 46: IEEE Generator Protection Tutorial Presentation

IEEE TUTORIAL ON THE PROTECTION OF SYNCHRONOUS GENERATORS

Copyright © IEEE 2011

Page 47: IEEE Generator Protection Tutorial Presentation
Page 48: IEEE Generator Protection Tutorial Presentation
Page 49: IEEE Generator Protection Tutorial Presentation
Page 50: IEEE Generator Protection Tutorial Presentation
Page 51: IEEE Generator Protection Tutorial Presentation

Saturation

Page 52: IEEE Generator Protection Tutorial Presentation
Page 53: IEEE Generator Protection Tutorial Presentation

Stator differential protection does not detect turn-to-turn faults

Current can be 6 to 7 times nominal and can damage stator

Use turn-to-turn protection schemes to detect and avoid damage

Page 54: IEEE Generator Protection Tutorial Presentation
Page 55: IEEE Generator Protection Tutorial Presentation
Page 56: IEEE Generator Protection Tutorial Presentation
Page 57: IEEE Generator Protection Tutorial Presentation

Imperfection in generator construction

Temperature variations

Winding connections

External faults

Terminal voltage and load variations

Page 58: IEEE Generator Protection Tutorial Presentation

IEEE TUTORIAL ON THE PROTECTION OF SYNCHRONOUS GENERATORS

Copyright © IEEE 2011

Page 59: IEEE Generator Protection Tutorial Presentation

The Method of Generator Neutral Grounding Determines its Performance During Ground Faults

Solidly GroundedLow ImpedanceHigh ImpedanceHybrid GroundingUngrounded

Page 60: IEEE Generator Protection Tutorial Presentation

Multiple Bus (No/Low Z/High Z)Directly connected to busLikely in industrial, commercial, and isolated systemsMay have problems with circulating 3rd harmonic▪ Use of single grounded machine

can helpAdds complexity to discriminate ground fault source if ground resistance is high (less than 25A)

BUS

G G G

Same type of grounding used on 1 or mutiple generators

Page 61: IEEE Generator Protection Tutorial Presentation
Page 62: IEEE Generator Protection Tutorial Presentation

62

400 A

2000/5

2000/5

8780%

• 45MVA Generator

• 2000/5 CTs

• 87 Set at 0.2A Pickup

• 20% of Winding Not Protected

Low Resistance Grounding Systems

Page 63: IEEE Generator Protection Tutorial Presentation

Percentage of Stator Winding Unprotected

Page 64: IEEE Generator Protection Tutorial Presentation

87G – Generator Differential

87GD – Generator Ground Differential

51N – Neutral Overcurrent

Page 65: IEEE Generator Protection Tutorial Presentation

IG

IA

IB

IC

3I0IG

Residual currentcalculated fromindividual phasecurrents. ParalleledCTs shown toillustrate principle.

0

90

180

270IG

3IO

-3Io x IG cos (180) = 3IoIG

Page 66: IEEE Generator Protection Tutorial Presentation

IG

IA

IB

IC

3I0IG

Residual currentcalculated fromindividual phasecurrents. ParalleledCTs shown toillustrate principle.

0

90

180

270

IG

3IO-3Io x IG cos (0) = -3IoIG

Page 67: IEEE Generator Protection Tutorial Presentation

59N, 3V0 overvoltage, covers ≈ 95% of windingTuned to the fundamental frequencyMust work properly from 10 to 80 Hz during startup.

3rd Harmonic methods cover remaining 5% of winding near neutral

27TN, 3rd harmonic undervoltage59D, Ratio of 3rd harmonic voltage at terminal and neutral ends of winding

64S, Subharmonic voltage injection, covers 100% of winding

Page 68: IEEE Generator Protection Tutorial Presentation

High-impedance ground limits ground fault current (limits damage on internal winding to ground fault)

Conventional neutral or zero-sequence overvoltage relay (59G) provides coverage for the ground faults involving up to 90%–95% of the winding from phase terminal

51G connected in the primary or secondary neutral circuit can be used as a backup to 59G

R 59G

Page 69: IEEE Generator Protection Tutorial Presentation

Last 5%–10% near neutral not covered by neutral overvoltage relay (59G) because a ground fault in this winding region bypasses grounding transformer or resistor (R) or 59G, solidly grounding the machine

R 59G

Page 70: IEEE Generator Protection Tutorial Presentation

R 59G

XHL Sensitively set 59G relay to detect ground faults (up to 95% of the winding) can also pick up for faults on the HV side of GSU or in the VT secondary circuit

Page 71: IEEE Generator Protection Tutorial Presentation

R

Co CHL

3Io

Io

Zero-Sequence Network

3R Xo

XHLV0VR

0R 0

0 HL

ZV : V •Z X

⎛ ⎞= ⎜ ⎟+⎝ ⎠

Page 72: IEEE Generator Protection Tutorial Presentation

Third-harmonic voltage develops in stator due to inherent presence of third harmonic flux in the rotor field

Rotor MMF

Page 73: IEEE Generator Protection Tutorial Presentation

R

Co

3I3h

I3h A, B, C

Generator winding and terminal capacitances provide path for the third-harmonic stator current via grounding resistor

Page 74: IEEE Generator Protection Tutorial Presentation

Machine construction – the pitch of the stator

Levels of excitation (MVAR) and machine output (MW)

Terminal capacitance

Page 75: IEEE Generator Protection Tutorial Presentation

Present in terminal and neutral ends

Can vary with loading

Detects ground faults near neutral

Note: If third harmonic goes away across neutral resistor, conclude a

ground fault near neutral

Full Load

No LoadNeutral

–V3RD

Fault at Terminal

Terminal

Fault at Neutral +V3RD

Terminal

Full LoadNo Load

Neutral

Normal OperationFull LoadNo Load

Terminal

NeutralNo Load

Full Load

+V3RD

–V3RD

Page 76: IEEE Generator Protection Tutorial Presentation

R 59G

C0

Under normal conditions, 27N3 is picked up because of the third-harmonic voltage drop across neutral resistor

I3h

27N33I3h

Page 77: IEEE Generator Protection Tutorial Presentation

R 59G

C0

For a fault close to neutral of the stator winding, 27N3 drops out because the fault bypasses the neutral resistor

A supervisory overvoltage (59C) relay located at the generator terminal blocks 27N3 operation during startup or shutdown to avoid misoperation

I3h

27N33I3h

Page 78: IEEE Generator Protection Tutorial Presentation

R 59G 27N3

59G

27N3

0%5%

100%~95% of winding from terminal by 59G

~15%–30% of winding from neutral by 27N3

Page 79: IEEE Generator Protection Tutorial Presentation

R 59G

59D

Compares third-harmonic voltage magnitude at the generator neutral to that at the generator terminals

Ferroresonance damping resistor

Page 80: IEEE Generator Protection Tutorial Presentation

R 59G

59G

59D0%5%

100%

59D

59D

~95% of winding from terminal by 59G

~15%–30% of winding from neutral and terminal by 59D

Page 81: IEEE Generator Protection Tutorial Presentation

Does not rely on third-harmonic signature of generator

Provides full coverage protection

Provides online and offline protection –prevents serious damage upon application of excitation

Is frequency independent

Page 82: IEEE Generator Protection Tutorial Presentation

64S

20 Hz Generator

Injection Signal

Pickup Setting

Measurement Value

20 Hz Filter

Measurement Signal For stator ground fault, 20 Hz increases and relay (64S) operates

Page 83: IEEE Generator Protection Tutorial Presentation

IEEE TUTORIAL ON THE PROTECTION OF SYNCHRONOUS GENERATORS

Copyright © IEEE 2011

Page 84: IEEE Generator Protection Tutorial Presentation

Hazards of field faults

Field ground protection

Tripping considerations

Field ground relay selection and settings

Field overcurrent

Page 85: IEEE Generator Protection Tutorial Presentation

Exciter Field Breaker

Voltage Relay

Grounding Brush

Field

64F

DC

Page 86: IEEE Generator Protection Tutorial Presentation

Shorts out part of field winding – expect unit vibrations, possible damageCauses local rotor current – expect rotor heating, distorted rotor, vibrationCauses arc damage at fault points

Ground #1

Ground #2

Page 87: IEEE Generator Protection Tutorial Presentation

Use on generators with brushes

Has variable detection sensitivity

Exciter Field Breaker

Voltage Relay

Grounding Brush

Field

64F

DC

Page 88: IEEE Generator Protection Tutorial Presentation

Exciter64F

+

Generator

Field Breaker Control

R2

R2

Voltage Relay

Varistor

Generator Field

Positive

Negative

Field Breaker Control

Test Pushbutton(optional)

Page 89: IEEE Generator Protection Tutorial Presentation

ExciterField

Breaker

Brush

Field

+

CR

C1

C2

RR

64F

AC

Page 90: IEEE Generator Protection Tutorial Presentation
Page 91: IEEE Generator Protection Tutorial Presentation
Page 92: IEEE Generator Protection Tutorial Presentation

Immediate tripping is recommended on first ground

However, most installations alarm and shutdown the machine in orderly manner if ground alarm persists

Relays should also be provided with time delays to override transients

Page 93: IEEE Generator Protection Tutorial Presentation

IEEE TUTORIAL ON THE PROTECTION OF SYNCHRONOUS GENERATORS

Copyright © IEEE 2011

Page 94: IEEE Generator Protection Tutorial Presentation

System backup protection for generators consists of time-delayed protection for phase-to-ground and multiphase fault conditions

Backup generator protection schemes protect against failure of system protection and subsequent long-clearing system faults

Page 95: IEEE Generator Protection Tutorial Presentation

Relay settings for backup relaying must be sensitive to detect low fault current conditions

Settings must balance opposing sensitivity requirements to detect distant faults and security to prevent unnecessary generator tripping

Page 96: IEEE Generator Protection Tutorial Presentation

Use either distance or voltage-restrained overcurrent relay to

detect system multiphase faults.

Note locations of current and voltage transformers.

Use a time-inverse transformer neutral connected overcurrent relay for system ground faults.

Page 97: IEEE Generator Protection Tutorial Presentation

98

Page 98: IEEE Generator Protection Tutorial Presentation

Choose protection based on line relay type

If distance type, back up with distance

If time-overcurrent type, back up with V-R or V-C overcurrent

Time coordinate with system relays including breaker failure relaying

Page 99: IEEE Generator Protection Tutorial Presentation

Voltage element supervises (torque controls) a sensitive, low pickup time-overcurrent element

Under fault conditions, voltage drops below set level – dropping out voltage element and permitting overcurrent element to operate

Cur

rent

Lev

el

Page 100: IEEE Generator Protection Tutorial Presentation

V-R overcurrent consists of an overcurrent element whose pickup level varies as a function of voltage applied to relay

Normally, generator terminal voltage is above voltage setting, VS1, and current pickup setting is IS

Cur

rent

Pic

kup

Leve

l

Page 101: IEEE Generator Protection Tutorial Presentation

When close-in fault occurs, voltage can drop below voltage setting, VS2, and current pickup level is reduced by factor k to kISFor voltages between VS1 and VS2, pickup level varies proportionately between IS and kIS

Cur

rent

Pic

kup

Leve

l

Page 102: IEEE Generator Protection Tutorial Presentation

Set pickup below generator fault current using synchronous reactance

V-C pickup will likely be below rated current

V-R pickup must be above rated current

Calculate 51V voltage element setting to avoid 51V relay misoperation under extreme emergency conditions (with lowest expected system voltage)

Page 103: IEEE Generator Protection Tutorial Presentation

To allow for selectivity, time-delay settings must be coordinated with transmission system primary and backup protection, including breaker failure time

Coordination is usually calculated with zero voltage restraint

Page 104: IEEE Generator Protection Tutorial Presentation

Use three V-C or V-R time-overcurrent relays for complete multiphase fault coverage

Note that generator fault current may decay rapidly when low voltage is at generator terminals – overcurrent phase fault backup may not operate for system faults

Check setting with fault current decrement curve for particular generator and excitation system

Page 105: IEEE Generator Protection Tutorial Presentation

Setting detects line fault when protection equipment fails

Relay impedance reach and time delay must be coordinated with system primary and backup protection, including breaker failure time

Setting must remain conservatively above machine rating to prevent inadvertent trips on generator swings and severe voltage disturbances

Page 106: IEEE Generator Protection Tutorial Presentation

F5

F4

F3

FLT

F1

F2

The impedance relay for each generator requires sensitive settings to detect

faults at the ends of long lines in the

presence of other sources.

Page 107: IEEE Generator Protection Tutorial Presentation

Sensitive settings may cause backup relays to unnecessarily trip generator under some loading conditions or for minor, stable swings

With this system configuration, it is generally possible to set backup relays to detect only close-in faults

Redundant line relaying and breaker failure relaying are necessary for line, bus, and transformer protection

Page 108: IEEE Generator Protection Tutorial Presentation

Set impedance relay to smallest of thethree following criteria:

120% of longest line (with infeed) – if unit is connected to breaker-and-a-half bus, calculate percent using adjacent line length

50%–66.7% of load impedance (200%–150% of generator capability curve) at machine-rated power factor

80%–90% of load impedance (125%–111% of generator capability curve) at relay maximum torque angle (MTA)

Page 109: IEEE Generator Protection Tutorial Presentation

30.0

25.0

20.0

15.0

10.0

5.0

0 20.015.010.0–10.0 5.0–5.0

–5.0

50-67% of GCC @ RPFA

Shortest Line (No Infeed)

Transformer High Side

Zone 2

Zone 1

MTA

RPFA

GCC

Longest Line(With Infeed)75.5 Ohms

jX

R

GCCZone 1Zone 2System

Zone 1 set to cover 120% of GSU impedance.

Zone 2 limited to 67% of generator capability curve

at rated power factor.

Zone 2 reach will not provide adequate phase fault system backup protection as it would

require an extremely large setting. The only way to ensure adequate protection to avoid sustained currents to the fault is to provide redundant transmission system protection.

Page 110: IEEE Generator Protection Tutorial Presentation

IEEE TUTORIAL ON THE PROTECTION OF SYNCHRONOUS GENERATORS

Copyright © IEEE 2011

Page 111: IEEE Generator Protection Tutorial Presentation

Provides for tripping of backup breakers when the generator breaker does not open after trip initiation upon detection of

FaultAbnormalcondition

Page 112: IEEE Generator Protection Tutorial Presentation

Open circuit to trip coilMechanism fails to open breakerBreaker opens but breaker contacts fail to interrupt faultTripping of circuit breaker left open after maintenance

Page 113: IEEE Generator Protection Tutorial Presentation

Generator trips may not always be from high-current events (faults)

Overexcitation

Overvoltage

Sequential tripping

Page 114: IEEE Generator Protection Tutorial Presentation

Need to include breaker auxiliary contact status in addition to current detectionBF protection should be fast enough to maintain stability but not so fast as to compromise tripping security

Page 115: IEEE Generator Protection Tutorial Presentation
Page 116: IEEE Generator Protection Tutorial Presentation

Breaker flashover is a type of breaker failureBreaker flashover is most likely to occur just prior to synchronizing or just after generator is removed from service

Page 117: IEEE Generator Protection Tutorial Presentation

Three-phase simultaneous flashovers are rare, thus most protection schemes are designed to detect the flashover of one

or two poles

Page 118: IEEE Generator Protection Tutorial Presentation
Page 119: IEEE Generator Protection Tutorial Presentation

IEEE TUTORIAL ON THE PROTECTION OF SYNCHRONOUS GENERATORS

Copyright © IEEE 2011

Page 120: IEEE Generator Protection Tutorial Presentation

Underfrequency occurs as the result of sudden reduction in input power through loss of generators or key intertie importing power

Overfrequency occurs as the result of sudden loss of load or key intertie exporting power

Page 121: IEEE Generator Protection Tutorial Presentation

Regional reliability councils will typically provide settings for underfrequency load shedding and generator tripping

Load shedding schemes must coordinate and meet regional criteria

Generator tripping criteria must accommodate any frequency excursion during any islanding scenario

Page 122: IEEE Generator Protection Tutorial Presentation

Generator tripping permitted on or below curve without requiring additional equivalent automatic

load shedding.

60

59

58

57

56

550.1 3.31 10 100 300

Time (s)

Freq

uenc

y (H

z)

Page 123: IEEE Generator Protection Tutorial Presentation

Operation outside shaded area is limited in extent, duration, and frequency of occurrence

Severe restrictionscould be imposed onthe generator itself

Possibility of frequency operational limits exists for the generator in the form of time-frequency characteristics

V%

f%

106

104

102

100 102

98

96

104

94

989694

Copyright ©2005 IEC, Geneva Switzerland

Page 124: IEEE Generator Protection Tutorial Presentation

Protection of the long tuned blading in the low-pressure turbine element for steam units

Possibility of cumulative blading fatigue and blading failure

Similar limitations for combustion and combined-cycle turbines

Virtually no frequency limitations for hydro generating units

Page 125: IEEE Generator Protection Tutorial Presentation

Example of fictitious steam turbine operational limits shown in the plot

Prohibited OperationRestricted Time

Operating Frequency Limits

Continuous Operation

Restricted Time Operating Frequency Limits

Prohibited Operation

62

61

60

59

58

57

56

0.0010.005

0.010.05

0.100.50

1.05.0

10.050.0

100.0Time (Minutes)

Page 126: IEEE Generator Protection Tutorial Presentation

Obtain turbine capability from manufacturer

Verify if IEC 60034-3:2007 is applicable

Have manufacturer approve protectionscheme

63

62

61

60

59

58

57

56

55

541000100101

Continuous Operating Region

10-Minute Maximum

Total Accumulated Time Limit (Minutes)

Page 127: IEEE Generator Protection Tutorial Presentation

Limits similar to steam turbine

Example of frequency limits in the plotFr

eque

ncy

(Hz)

Page 128: IEEE Generator Protection Tutorial Presentation

IEEE TUTORIAL ON THE PROTECTION OF SYNCHRONOUS GENERATORS

Copyright © IEEE 2011

Page 129: IEEE Generator Protection Tutorial Presentation

V/Hz application can result in:

Heating of stator core iron

Stray flux increasing beyond design limits causing additional heating

Overvoltage application:

Stresses stator insulation and connected components

Cannot be reliably detected using V/Hz alone

Page 130: IEEE Generator Protection Tutorial Presentation

Offline generator voltage regulator problems

Operating error during unit synchronizing

Control failure

VT fuse loss in voltage regulator (AVR)System problems

Unit load rejection: full load, partial rejection

Power system islanding during major disturbances

Page 131: IEEE Generator Protection Tutorial Presentation

Generators: 1.05 pu (generator base)

Transformers:

1.05 pu at rated load at 0.8 PF

1.1 pu at no load

Page 132: IEEE Generator Protection Tutorial Presentation

V%

f%

106

104

102

100 102

98

96

104

94

989694

Copyright ©2005 IEC, Geneva, Switzerland

Page 133: IEEE Generator Protection Tutorial Presentation
Page 134: IEEE Generator Protection Tutorial Presentation

100

105

110

115

120

125

130

0.1 1 10 100

Page 135: IEEE Generator Protection Tutorial Presentation

Time (minutes)

110

120

130

140

0.01 0.1 1 10 100

Individual manufacturers should be consulted for limits

of a specific transformer.

Page 136: IEEE Generator Protection Tutorial Presentation
Page 137: IEEE Generator Protection Tutorial Presentation

V/H

z (%

)

Page 138: IEEE Generator Protection Tutorial Presentation

IEEE TUTORIAL ON THE PROTECTION OF SYNCHRONOUS GENERATORS

Copyright © IEEE 2011

Page 139: IEEE Generator Protection Tutorial Presentation

Limiting factors are rotor and stator thermal limits

Underexcited limiting factoris stator end iron heat

Excitation control setting control is coordinated with steady-state stability limit (SSSL)

Minimum excitation limiter (MEL) prevents exciter from reducing the field below SSSL

Reactive Power Into System

Reactive Power Into Generator

Rotor Winding Limited

MEL

Stator End Iron Limited

SSSL

Stator Winding Limited

+ MWReal Power Into System0

+MVAR

Overexcited

Underexcited

–MVAR G

MVAR

MWSystem

MVARG

MWSystem

Page 140: IEEE Generator Protection Tutorial Presentation

Field open circuit

Field short circuit (flashover across slip rings)

Accidental tripping of field breaker

Voltage regulator control system failure

LOF to main exciter

Loss of ac supply to excitation system

Page 141: IEEE Generator Protection Tutorial Presentation

Machine that initially operates at 30% load and underexcited. Impedance locus follows path from E to F to G and oscillates in region between F and G

Generally for any loading, impedance terminates on or varies from D to L

Impedance variation with the machine operating at or near full load – locus follows path from C to D

Page 142: IEEE Generator Protection Tutorial Presentation

Two modern offset mho relays can be used

Relay with 1.0 pu impedance diameter detects LOF condition from full load to about 30% load

First relay is set with short time delay; 0.1-second delay suggested for security against misoperation during transients

Diameter = 1.0 puOffset =

Diameter = Xd

0.5

–R

–1

–2

–1 –X 1 2

+X

+R

′dX2

Page 143: IEEE Generator Protection Tutorial Presentation

Second relay is set with time delay; 0.5 to 0.6 seconds provides protection for LOE condition up to no load

Two offset mho relays provide LOE protection for any loading level

Both relays are set with offset of X′d/2

Diameter = 1.0 puOffset =

Diameter = Xd

0.5

–R

–1

–2

–1 –X 1 2

+X

+R

′dX2

Experience has shown that these settings are secure over a wide range of system conditions. However, transient

stability analysis should be performed to verify this.

Page 144: IEEE Generator Protection Tutorial Presentation

MEL and LOF characteristicare coordinated so they do not overlap

MEL prevents leading var excursions into the LOF characteristic to avoid relay misoperation for system transients

Negative-offset mho element characteristic leaves underprotected area relative to SSSL and stator end iron limit curve of the machine capability

0.8

0.4

0

–0.4

–0.8

0.4 0.8 1.20

Generator Capability

SSSL

LOF Relay

pu (MW)

Q

P

MEL

Page 145: IEEE Generator Protection Tutorial Presentation

Generator

G

GSU SystemReactance

VXd XT

XSWhere

Xe=XT + XS

V2 1_ + 1 2 Xe Xd

Per Unit MW

Per Unit Mvar

V2 1 1 2 Xe Xd

MW - Mvar PER UNIT PLOT

X

R

Xd + Xe 2

Xe

Xd - Xe 2

R-X DIAGRAM PLOT

Page 146: IEEE Generator Protection Tutorial Presentation

This scheme combines positive-offset mho relay, directional relay, and undervoltage relay applied at generator terminals and set to look into machine

Directional unit supervises mho unit because positive-offset allows it to operate for faults external to generator terminals

XS

1.1 (Xd)

Offset =

Machine Capability

MEL

SSSL

Z2 Setting

Z1 Setting

R

X

′dX2

Improves coverage

Page 147: IEEE Generator Protection Tutorial Presentation

IEEE TUTORIAL ON THE PROTECTION OF SYNCHRONOUS GENERATORS

Copyright © IEEE 2011

Page 148: IEEE Generator Protection Tutorial Presentation

System AsymmetriesOpen system circuits

Downed conductors

Stuck breaker poles or open switchesUnbalanced loads

Untransposed transmission lines

Single-phase GSU with unequal impedancesUnbalanced system faults

Page 149: IEEE Generator Protection Tutorial Presentation

Strongest I2 source is generator phase-to-phase fault

Generators connected with delta-wye GSU transformer

System ground faults appear as phase-to-phase faults to the generator

Generator ground faults typically do not create as much I2

Page 150: IEEE Generator Protection Tutorial Presentation

I2 in the stator creates a magnetic field component that rotates in opposite direction of rotor and power system (positive-sequence) field component

Page 151: IEEE Generator Protection Tutorial Presentation

As a result, double-frequency current is induced in rotor

At twice fundamental frequency, skin effect promotes current in rotor surface areas and, to a smaller degree, in the field winding

Page 152: IEEE Generator Protection Tutorial Presentation

Beyond a point, the induced surface currents can cause heating of metal

wedges that hold field windings and / or retaining rings on rotor ends, causing them

to anneal, expand, and loosen with catastrophic results

Page 153: IEEE Generator Protection Tutorial Presentation
Page 154: IEEE Generator Protection Tutorial Presentation

For salient-pole machines, double-frequency currents concentrate at pole faces and teeth

Much current appears in the pole-face amortisseur windings

Page 155: IEEE Generator Protection Tutorial Presentation

Continuous Unbalance Current CapabilityGenerator Type Permissible I2 Stator

Rating PercentSalient Pole

Connected Amortisseur WindingsNonconnected Amortisseur Windings

105

Cylindrical RotorIndirectly CooledDirectly Cooled

To 350 MVA351–1250 MVA1251–1600 MVA

10

88 – [(MVA-350)/300)]

5

Page 156: IEEE Generator Protection Tutorial Presentation

Short-Time Unbalance Current Capability

Generator TypeK Permissible

(I2 in pu)Salient Pole 40Synchronous Condenser 30Cylindrical Rotor

Indirectly CooledDirectly Cooled

0–800 MVA801–1600 MVA

30

10See Graph (next slide)

22I t

Page 157: IEEE Generator Protection Tutorial Presentation

[ ]= − −22I t 10 (0.00625)(MVA 800)

=22I t 10

2 2It C

apab

ility

Page 158: IEEE Generator Protection Tutorial Presentation

Values shown in Tables I and II of this chapter are for machines manufactured to IEEE C50 standards since 2005

Equipment nameplate data and / or the manufacturer may be consulted to verify machine capabilities

Page 159: IEEE Generator Protection Tutorial Presentation

2

Page 160: IEEE Generator Protection Tutorial Presentation

Has limited I2 sensitivity of about 60% of generator full-load rating

Generally insensitive to load unbalances or open conductors

Limited protection as damaging heat can occur even at low levels of I2

Allows backup protection for unbalanced faults (high levels of I2)

Page 161: IEEE Generator Protection Tutorial Presentation

Allows relay characteristics that can match generator I2 capabilities

Allows I2 pickup settings down to 0.03 pu

Can be set to alarm at lower than generator limits, allowing plant operator to attempt to reduce I2 before trip occurs

Page 162: IEEE Generator Protection Tutorial Presentation

Minimum Pickup 0.04 pu

K Setting Adjustable Over

Range 2–40

10

40

2

5

Negative-Sequence Current (per unit)0.1 101

0.10.01

1 • 103

100

1

10

Tim

e (s

econ

ds)

Page 163: IEEE Generator Protection Tutorial Presentation

IEEE TUTORIAL ON THE PROTECTION OF SYNCHRONOUS GENERATORS

Copyright © IEEE 2011

Page 164: IEEE Generator Protection Tutorial Presentation
Page 165: IEEE Generator Protection Tutorial Presentation

Generator Type Potential Damage

Diesel Risk of Explosion

Gas Turbine Gear Damage

Hydro Blade Cavitation

Steam Overheating

Page 166: IEEE Generator Protection Tutorial Presentation

Generator Type Typical Motoring Power

Diesel 5% - 25%

Gas Turbine > 50%

Hydro 0.2 - 2%

Steam 0.5% - 3%

Page 167: IEEE Generator Protection Tutorial Presentation
Page 168: IEEE Generator Protection Tutorial Presentation

IEEE TUTORIAL ON THE PROTECTION OF SYNCHRONOUS GENERATORS

Copyright © IEEE 2011

Page 169: IEEE Generator Protection Tutorial Presentation

The 78 protection scheme protects the generator from OOS or pole-slip conditions

Common relay schemes for detecting generator OOS events include:

Single blinder

Double blinder

Concentric circle

Page 170: IEEE Generator Protection Tutorial Presentation

When a Generator Goes Out-of-Step (Synchronism) with the Power System, High Levels of Transient Shaft Torque are Developed.

If the Slip Frequency Approaches Natural Shaft Frequency, Torque Produced can Break the Shaft.

High Stator Core End Iron Flux can Overheat and Damage the Generator Stator Core.

GSU Subjected to High Transient Currents and Mechanical Stresses.

171

Page 171: IEEE Generator Protection Tutorial Presentation

172

Page 172: IEEE Generator Protection Tutorial Presentation

One pair of blinders (vertical lines)

Supervisory offset mho

Mho limits reach of scheme to swings near the generator

Page 173: IEEE Generator Protection Tutorial Presentation

Double Lens

Scheme

Double BlinderScheme

Page 174: IEEE Generator Protection Tutorial Presentation

The most popular OOS protection is the single blinder scheme

Pickup area is restricted to shaded area defined by inner region of mho circle and area between Blinders A and B

Z3(t3)

Z0(t0)Z2(t2)

Z1(t1)

A B

Page 175: IEEE Generator Protection Tutorial Presentation

Positive-sequence impedance must originate outside either Blinder A or Blinder B

It should swing through the pickup area and progress to the opposing blinder

Swing time should be greater than time-delay setting

Page 176: IEEE Generator Protection Tutorial Presentation

Rotor Angle Generator G_1

Ang

le (d

egre

es)

Time (seconds)

–— Case 1 (tc = 90 ms), with controls

–— Case 2 (tc = 180 ms), with controls

–— Case 3 (tc = 190 ms), with controls

– – Case 1 (tc = 90 ms), without controls

– – Case 2 (tc = 180 ms), without controls

– – Case 3 (tc = 190 ms), without controls

Page 177: IEEE Generator Protection Tutorial Presentation

R-X diagrams show trajectory followed by impedance seen by relay during disturbance

When an oscillation in the generator is stable, the point of impedance does not cross the line of the system

When an OOS condition occurs, the point of impedance crosses the line of the system impedance each time the slip is completed

Page 178: IEEE Generator Protection Tutorial Presentation

R-X Diagram for Case 1R-X Diagram for Case 1R-X Diagram for Case 1

Case 1Tc = 0.09 ms

Case 2Tc = 0.18 ms

Case 3Tc = 0.19 ms

R (ohm) R (ohm)

X (o

hm)

R (ohm)

X (o

hm)

.

Page 179: IEEE Generator Protection Tutorial Presentation

Apply OOS if swing impedance passes through GSU or generator

This zone is protected by differential relays that do not respond to power swings

Consider application of OOS if swing passes outside GSU but line protection is blocked or does not respond to swings

Page 180: IEEE Generator Protection Tutorial Presentation

IEEE TUTORIAL ON THE PROTECTION OF SYNCHRONOUS GENERATORS

Copyright © IEEE 2011

Page 181: IEEE Generator Protection Tutorial Presentation

Common causesWiring failureOpen in VT draw-out assemblyBlown fuse due to short-circuitFuse left out after maintenance

Affected functions21, 27, 32, 40, 50/27, 51V, 67N, 78, 81Automatic voltage regulator (AVR runaway)

Page 182: IEEE Generator Protection Tutorial Presentation

When fuse blows, unbalanced voltages created

Two sets of VTs required

Page 183: IEEE Generator Protection Tutorial Presentation

Loss of One or Two Phases

Negative-sequence voltage & no negative-sequence current = fuse loss

Negative-sequence voltage & negative-sequence current = fault

Three-Phase Loss

Low three-phase voltages & low three-phase current & positive-sequence current = fuse loss

Low three-phase voltages & high three-phase currents = fault

Page 184: IEEE Generator Protection Tutorial Presentation

Wye-wye grounded VTs on ungrounded system

Mitigation

Line-to-line rated VTs

Broken-delta VTs

VT loading resistor

Page 185: IEEE Generator Protection Tutorial Presentation

IEEE TUTORIAL ON THE PROTECTION OF SYNCHRONOUS GENERATORS

Copyright © IEEE 2011

Page 186: IEEE Generator Protection Tutorial Presentation

Operating errors

Breaker head flashovers

Control circuit malfunctions

Combination of above

Page 187: IEEE Generator Protection Tutorial Presentation

Typically, normal generator relaying is not adequate to detect inadvertent energizing

Generator behaves as induction motor

Flux induced into generator rotor causing rapid rotor heating

Rotor current is forced into negative-sequence path in rotor body

Page 188: IEEE Generator Protection Tutorial Presentation

X1S = system positive-sequence reactance

X1T = transformer positive-sequence reactance

X2G = generator negative-sequence reactance

EG = generator terminal voltage

ES = system voltage

ET = transformer high-side voltage

I = current

R2G = generator negative-sequence resistance

UnitStep-Up

Transformer

EquivalentHigh-Voltage

System

Equivalent SystemVoltage

X1T X1S

X2G

R2G

Gen.EG ET ES

Gen.

I

Page 189: IEEE Generator Protection Tutorial Presentation

Undervoltage (27) supervises low-set, instant overcurrent (50) –recommended 27 setting is 50% or lower of normal voltage

Pickup timer ensures generator is dead for fixed time to ride through three-phase system faults

Dropout timer ensures that overcurrent elementgets a chance to trip if voltage is higher than 27 setting during event

Page 190: IEEE Generator Protection Tutorial Presentation

GeneratorPhaseVoltage

Generator Phase

Currents

Fault Inception

Breaker Opens

Page 191: IEEE Generator Protection Tutorial Presentation

IEEE TUTORIAL ON THE PROTECTION OF SYNCHRONOUS GENERATORS

Copyright © IEEE 2011

Page 192: IEEE Generator Protection Tutorial Presentation

Large gas turbines are started as a motor using static frequency converter

V/Hz is maintained constant until rated voltage is reached, after which rated voltage is maintained

Extended operation occurs at low speeds while purging and firing cycles are completed

Generator must be protected during low-frequency operation

Page 193: IEEE Generator Protection Tutorial Presentation

Some protection such as phase overcurrent and phase unbalance is provided by converter controls

To be effective, multifunction generator relays must maintain protection down to low frequencies

At lower frequencies, protective functions may deviate from normal specifications

In some cases, protective functions may have to be disabled during starting because of possible false operation

Page 194: IEEE Generator Protection Tutorial Presentation

Fault-to-ground on dc link cannot be detected by converter controls

Fault causes dc current to flow through any wye-connected VTs and generator ground

.

Page 195: IEEE Generator Protection Tutorial Presentation

DC current saturates magnetic elements (VTs and distribution transformer in generator neutral)Damage can occur if fault is not cleared – PT can be damaged in approximately 50 msTwo strategies to address this fault include

Measure dc current in generator neutral (e.g., with transducer) and use dc relay and turn converter off before damage occurs

Eliminate any ground path through magnetic elements during starting (use delta-connected VTs and disconnect generator neutral while starting)

Page 196: IEEE Generator Protection Tutorial Presentation

To avoid damage to generator or GSU unit, synchronizing across breaker should be done within tight limitsTypical recommendations are

Electrical degrees ±10

Voltage 0 to +5 percent

Frequency difference < 0.067 Hz

Synchronizing equipment or supervising relays should take into account breaker closing time and relative slip, closing breaker in advance so that angle between generator and system at closing is as close to zero as possible

Page 197: IEEE Generator Protection Tutorial Presentation

Generators may be operated at lower frequency during startup and shutdown

Electromechanical relays can become very insensitive at off nominal frequencies

Plunger-type overcurrent relays have flat characteristics down to low frequencies and are used to provide supplementary protection during start up and shutdown –these relays cannot be energized continuously and have to be disconnected during normal operation

Microprocessor-based relays can provide protection down to lower frequencies and generally do not require supplementary protection

(E)(D)(C)(B)(D)

(B)

(E)

(C)

(A)

(A)(F)

8

7

6

5

4

3

2

1

0 70 80605040302010

Pic

kup

in M

ultip

les

of 6

0 H

z P

icku

p

Frequency in Hz

Harmonic Restraint Transformer Differential Relay

Plunger-Type Current RelayInduction Overcurrent RelayGenerator Differential RelayGenerator Ground Relay

Plunger-Type Voltage Relay

(A)(B)(C)(D)(E)(F)

Page 198: IEEE Generator Protection Tutorial Presentation

IEEE TUTORIAL ON THE PROTECTION OF SYNCHRONOUS GENERATORS

Copyright © IEEE 2011

Page 199: IEEE Generator Protection Tutorial Presentation

Generator protection functions with same trip / shutdown modes are grouped together

Page 200: IEEE Generator Protection Tutorial Presentation

Operated by protective functions, auxiliary lockout relays, 86G (usually hand-reset), perform most tripping

Where possible, primary and backup relays trip via separate paths / lockouts

Page 201: IEEE Generator Protection Tutorial Presentation

Includes tripping of all electrical and mechanical power sources

Provides fastest way to isolate generator

Page 202: IEEE Generator Protection Tutorial Presentation

Does not shut down prime mover

Used when abnormality can be corrected quickly allowing fast reconnection

Page 203: IEEE Generator Protection Tutorial Presentation

Only trips generator breaker(s)

Used when disturbance is on system and it is desired to have generator run its own auxiliaries

Page 204: IEEE Generator Protection Tutorial Presentation

Used to prevent overspeed when delayed tripping of breakers is not detrimental –following a prime mover trip, planned or unplanned, breakers are tripped after reverse or low (hydro) power is detected

Not used for clearing faults

Page 205: IEEE Generator Protection Tutorial Presentation

Much tripping philosophy depends on ability of generating unit to continue operating after disconnection from system (full load rejection)

If unit cannot support its own auxiliaries, then a tripping mode that transfers auxiliaries should be incorporated

Page 206: IEEE Generator Protection Tutorial Presentation

Table II provides suggested steam unit trip logic by IEEE protective function numbers

Some functions are alarmed only

In general, G means “generator” and Nmeans “neutral” or “ground”

Page 207: IEEE Generator Protection Tutorial Presentation

21 or 51V2432404650/2750/51G51TG250/51 UAT59

59G6363UAT67N7887G87GN87T87T UAT87O

Page 208: IEEE Generator Protection Tutorial Presentation

51TG1 and 81 are examples of functions set to trip in unit separation mode

Page 209: IEEE Generator Protection Tutorial Presentation

Table III provides typical tripping for hydroelectric units

Trip requirements are similar to thermal generators but may need slightly different slip / shutdown operations

Slower rotation devices

Different mechanical control devices

Page 210: IEEE Generator Protection Tutorial Presentation

A generator disconnect switch is often used when tie to transmission system is dual-breaker arrangement

Page 211: IEEE Generator Protection Tutorial Presentation

Sometimes generator protective functions are enabled / disabled by utilizing auxiliary switch contacts based on position of disconnect switch

Be cautious about bad or incorrect disconnect position status leaving generator unprotected