Technical Specification DatasheetSCADAPack E Smart RTUCompact, versatile controller for telemetry and remote SCADA solutions
1
SCADAPackSmart RTUs that combine the monitoring and communications capabilities of remote terminal units (RTU) with the processing and data-logging power of programmable logic controllers (PLC), providing superior functionality wherever remote processes require automatic supervision and autonomous control.
SCADAPack E Smart RTUs are the foundation for a range of solutions offering specific software and configuration tools to enhance performance in oil and gas and water/wastewater applications.
2
Selection Guide
• For SCADA fitted with IEC 60870-5-101/104, DNP3 or Modbus protocols • Master protocols supported: DNP3, Modbus, IEC 60870-5-103 or DF1 • IEC61131-3 programming languages • DNP3 Secure Authentication and IEEE 1711 (AGA12) Encryption for DNP3
SCADAPack 300E & SCADAPack ES
312E 313E 314E 330E 333E 334E 337E 350E 357E ES
Analog Inputs1
0-20mA, 4-20mA, 0-5V, 0-10V 4 4 8 – 4 8 8 – 8 –
0-10V/0-40mA,0-5V/0-20mA, 1-5V/4-20mA
– – – – – – – 5 5 –
1-5V/4-20mA – – – – – – – – – 6 or 12
0-32.7V – – – – – – – 1 1 –
Analog Outputs1
4-20mA – – – – – – – – – 2 or 4
0-20mA/4-20mA – 2 – 2 2 or 4 –
Digital Inputs1
12/24V 12 16 – – 16 – 32 – – –
12/24/48/115/125/240V – – 16 – – 16 – – 32 –
10-30V – – – – – – – – – 16 or 32
dry contact, shared with output points – – – – – – – 8 8 –
Digital Outputs1
dry contact 6 10 – – 10 – 16 – 16 –
dry contact or solid state – – 10 – – 10 – – – –
open drain, share with input points – – – – – – – 8 8 –
DPDT Relay, (NO/Common/NC) – – – – – – – – – 8 or 16
Counter Inputs1
0-10Hz – – – – – – – 1 –
0-10Hz/-05kHz (dry contact) 1 – – –
0-10kHz (turbine inputs) 2 –
0-1kHz, shared with Digital Inputs – – – – – – – – – 4
Communication and Configuration Ports
Serial port - RS232 – – – 1 3
Serial port - RS485 – – – – – – – 1 –
Serial port - RS232/ 485 2 1 –
Serial ports - RS232/422/ 485 – – – – – – – – – 2
USB ports 1 –
Ethernet ports (10/100BaseT) – – – 1 2
Logic control
IEC61131 Programming languages option Yes option Yes
Protocols
Modbus slave, IEC60870-5 slave, DNP3 slave, PPP, ftp, DNP3 master
Yes
Modbus master option Yes option Yes
DF1 master option Yes option Yes
IEC 60870-103 master – – Yes – Yes – Yes
DNP3 Secure Authentication option
AGA-12 Encryption for DNP3 protocol2 option
(1) The amount of I/O may be expanded for any SCADAPack E using Expansion I/O modules (refer to individual product data sheets for detailed specifications)(2) Subject to export restrictions, please contact your TRSS business development representative for more details
3
Contents
SCADAPack E Smart RTU SCADAPack 312E Specifications ......................................................................................... 4 Model Code ........................................................................................... 5
SCADAPack 313E Specifications ......................................................................................... 6 Model Code ........................................................................................... 7
SCADAPack 314E Specifications ......................................................................................... 8 Model Code ........................................................................................... 9
SCADAPack 330E | 334E Specifications 330E .............................................................................. 10 Specifications 334E .............................................................................. 11 Model Code ......................................................................................... 12
SCADAPack 333E Specifications ....................................................................................... 13 Model Code ......................................................................................... 14
SCADAPack 337E Specifications ....................................................................................... 15 Model Code ......................................................................................... 16
SCADAPack 350E | 357E Specifications 350E .............................................................................. 17 Specifications 357E .............................................................................. 18 Model Code ......................................................................................... 19
SCADAPack ES Specifications ES ................................................................................. 20 Model Code ......................................................................................... 22
I/O Expansion Modules
Analog Input Modules 5505 - RTD input module ..................................................................... 23 5506 - Analog input module ................................................................. 24
Analog Output Modules 5304 - Analog output module ............................................................... 25
Digital Input Modules 5405 - Digital input module .................................................................. 26 5414 - Compact digital input module ................................................... 27
Digital Output Modules 5411 - Digital output module ................................................................ 28 5415 - Compact relay digital output module ......................................... 29
Combination I/O Modules 5606 - Analog/digital I/O module .......................................................... 30 5607 - Analog/digital I/O module .......................................................... 31 5608 - Analog/digital I/O module ...........................................................32 5610 - Analog/digital I/O module ...........................................................33
UPS Power Supply 5103 - Uninterruptible Power Supply .................................................... 34
Communication Modules
Modems, Interface Modules & Gateways 5902 - Bell 202 radio or leased line modem ......................................... 35 5908 - Wireless data transceiver .......................................................... 36 5908 - W02 - Wireless data transceiver ................................................ 37 5910 - Ethernet switch ......................................................................... 38 5915 - SDI-12 interface module ........................................................... 39
4
312E: 5212 controller board and integrated 5609 I/O board
Controller
Processors • CPU:32-bitARM7microcontroller,32MHzclock,integratedwatchdogtimer• Microcontrollerco-processor,20MHzclock
Memory 16MBFLASHROM,4MBCMOSRAM,4kBEEPROM
Non-VolatileRAM CMOSSRAMwithlithiumbatteryretainscontentsfor2yearswithnopower
EventLoggingCapacity 20,000events
MaximumDatabasePoints 1,000typical
I/O
AnalogInputs • 4softwareconfigurable:0-20/4-20mA/0-5/0-10V(15-bit)• 3internal:measureincomingpowersupplyvoltageforsolarapplications,batteryvoltage,andcontrollertemperature
AnalogOutputs None
DigitalI/O • 12digitalinputs:12/24V• 6relayoutputs:drycontact,drycontactrating:3A,30VDCor240VAC(resistive)
CounterInputs • 1drycontact:0-10Hzor0-5kHz• 2turbineordrycontact:0-10kHz
Communications
SerialPortsCOM1,COM2 • RS-232port,8-pinmodularRJ45jack,fullorhalf-duplex,or• RS-485port,2-wire,half-duplex
BaudRates 300,600,1200,2400,4800,9600,19200,38400,57600,and115200
SerialProtocols DNP3Slave/Master,IEC60870-5-101Slave,ModbusRTUSlave,optionalModbusMasterandDF1Master
IPProtocols (overserialport)DNP3master/slave,IEC60870-5-101/104slave,ModbusRTUslave,NTPServer,TelnetServer,FTPServer
USBPort USB2.0compliantB-typereceptacle,DNP3protocol
Wireless Externalmodem(e.g.SchneiderElectricGPRSmodemref.SR2MOD3)
General
LogicControl OptionalIEC61131-3SCADAPackWorkbenchprogrammingsuite(LD,ST,FBD&SFC)
I/OTerminations 5,6,and9-poleremovableterminalblocks,12to22AWG,15Acontacts
Dimensions 5.65inch(144mm)wide,6.50inch(165mm)high,2.80inch(72mm)deep
Packaging Corrosionresistant,zinc-platedsteelwithblackenamelpaint
Environment 5%RHto95%,non-condensing,–25°C(–13°F)to70°C(158°F)
Power
5212ControllerBoard • 11-30VDC,5.8Wtypical• Add30to90mWwhenenablingtheLEDs• 8.5Wat24Vmaximum,5Vsupplyfully-loaded
5609I/OModule • 11-30VDC,10.3mA• 235mA(max.)at5Vrequiredfrom5212controllerboard
Warranty 3yearsonpartsandlabor
Certifications
• CEmarking• C-Tick• UL508(US/Canada)–cULus• FCC/EN61000-6emissions&immunity
Disclaimer:SchneiderElectricreservestherighttochangeproductspecifications.Formoreinformationvisitwww.schneider-electric.com.
Product Data Sheet SCADAPack 312ESpecifications
5
TBUP312-EA54-AB00representsasamplecodeforaSCADAPack312Ewith12Vdry-contactrelayoutputsandnoIEC61131programmingoption.
Model Select: Controller
TBUP312 SCADAPack312E,32-Bitcontroller,4AnalogInputs,12DigitalInputs,6DigitalOutputs,3CounterInputs
Code Select: Platform
E EFirmwareplatform(SCADAPackEConfiguratorsoftwareincluded),executestwoIEC61131-3kernels(optional),Workbenchrequired
Code Select: SCADA Security
A None
B AGA-12EncryptionforDNP3
C DNP3SecureAuthenticationSAv2
D DNP3SecureAuthenticationwithAGA-12Encryption
Notes:• TheSecurityAdministratorApplicationhastobepurchasedtogenerateandmanagesecuritykeys.• AGA-12Encryptionissubjecttoexportrestrictions.PleaseconsultwithyourTRSSbusinessunitcontact.
Code Select: Protocol Option
5 DNP3Slave/Master,IEC60870-5-101Slave,ModbusRTUSlave
Code Select: License Option
4 Option1:withoutIEC61131,ModbusMasterandDF1Master
5 Option2:withIEC61131-3(executestwokernels,SCADAPackWorkbenchrequired),ModbusMasterandDF1Master
Notes:• BothoptionsincludeDNP3DataConcentratorlicense(limitof500pointsfrom10IEDs),MultipleDNP3MasterLicense(upto3Masters)
• Ifyouorderaproductwithoption1whichyoulaterwanttoupgradetooption2,youhavetoorderaRTUlicenceupdate(ref.TBUM297889)
Code Select: Analog Inputs
A 4
Code Select: Digital Inputs/Outputs
B 12inputsand6outputs
Code Select: Analog Outputs
0 None
Code Select: Future Option
0 None
Product Data Sheet SCADAPack 312EModel Code
6
313E: 5212 controller board and integrated 5611 I/O board
Controller
Processors • CPU:32-bitARM7microcontroller,32MHzclock,integratedwatchdogtimer• Microcontrollerco-processor,20MHzclock
Memory 16MBFLASHROM,4MBCMOSRAM,4kBEEPROM
Non-VolatileRAM CMOSSRAMwithlithiumbatteryretainscontentsfor2yearswithnopower
EventLoggingCapacity 20,000events
MaximumDatabasePoints 1,000typical
I/O
AnalogInputs • 4softwareconfigurable:0-20/4-20mA/0-5/0-10V(15-bit)• 3internal:measureincomingpowersupplyvoltageforsolarapplications,batteryvoltage,andcontrollertemperature
AnalogOutputs • Standard:None• 2,0-20/4-20mA(12-bit)withoptionalcardon5611I/Oboard
DigitalI/O • 16digitalinputs:12/24V• 10relayoutputs:drycontact,drycontactrating:3A,30VDCor240VAC(resistive)
CounterInputs • 1drycontact:0-10Hzor0-5kHz• 2turbineordrycontact:0-10kHz
Communications
SerialPortsCOM1,COM2 • RS-232port,8-pinmodularRJ45jack,fullorhalf-duplex,or• RS-485port,2-wire,half-duplex
BaudRates 300,600,1200,2400,4800,9600,19200,38400,57600,and115200
SerialProtocols DNP3Slave/Master,IEC60870-5-101Slave,ModbusRTUSlave,optionalModbusMasterandDF1Master
IPProtocols (overserialport)DNP3master/slave,IEC60870-5-101/104slave,ModbusRTUslave,NTPServer,TelnetServer,FTPServer
USBPort USB2.0compliantB-typereceptacle,DNP3protocol
Wireless Externalmodem(e.g.SchneiderElectricGPRSmodemref.SR2MOD3)
General
LogicControl OptionalIEC61131-3SCADAPackWorkbenchprogrammingsuite(LD,ST,FBD&SFC)
I/OTerminations 5,6,and9-poleremovableterminalblocks,12to22AWG,15Acontacts
Dimensions 5.65inch(144mm)wide,6.50inch(165mm)high,2.80inch(72mm)deep
Packaging Corrosionresistant,zinc-platedsteelwithblackenamelpaint
Environment 5%RHto95%,non-condensing,–25°C(–13°F)to70°C(158°F)
Power
5212ControllerBoard • 11-30VDC,5.8Wtypical• Add30to90mWwhenenablingtheLEDs• 8.5Wat24Vmaximum,5Vsupplyfully-loaded
5611I/OModule • 11-30VDC,10.3mAplusanalogoutputs• 235mA(max.)at5Vrequiredfrom5212controllerboard
Warranty 3yearsonpartsandlabor
Certifications
• CEmarking• C-Tick• UL508(US/Canada)–cULus• FCC/EN61000-6emissions&immunity
Disclaimer:SchneiderElectricreservestherighttochangeproductspecifications.Formoreinformationvisitwww.schneider-electric.com.
Product Data Sheet SCADAPack 313ESpecifications
7
TBUP313-EA54-AB00representsasamplecodeforaSCADAPack313Ewith12Vdry-contactrelayoutputsandnoIEC61131programmingoption.
Model Select: Controller
TBUP313E SCADAPack313E,32-Bitcontroller,4AnalogInputs,2optionalAnalogOutputs,16DigitalInputs,10DigitalOutputs,3CounterInputs
Code Select: Platform
E EFirmwareplatform(SCADAPackEConfiguratorsoftwareincluded),executestwoIEC61131-3kernels(optional),Workbenchrequired
Code Select: SCADA Security
A None
B AGA-12EncryptionforDNP3
C DNP3SecureAuthenticationSAv2
D DNP3SecureAuthenticationwithAGA-12Encryption
Notes:• TheSecurityAdministratorApplicationhastobepurchasedtogenerateandmanagesecuritykeys.• AGA-12Encryptionissubjecttoexportrestrictions.PleaseconsultwithyourTRSSbusinessunitcontact.
Code Select: Protocol Option
5 DNP3Slave/Master,IEC60870-5-101Slave,ModbusRTUSlave
Code Select: License Option
4 Option1:withoutIEC61131,ModbusMasterandDF1Master
5 Option2:withIEC61131-3(executestwokernels,SCADAPackWorkbenchrequired),ModbusMasterandDF1Master
Notes:• BothoptionsincludeDNP3DataConcentratorlicense(limitof500pointsfrom10IEDs),MultipleDNP3MasterLicense(upto3Masters)
• Ifyouorderaproductwithoption1andthatyoulaterwanttoupgradetooption2,youhavetoorderaRTUlicenceupdate(ref.TBUM297889)
Code Select: Analog Inputs
A 4
Code Select: Digital Inputs/Outputs
B 16inputsand10outputs
Code Select: Analog Outputs
0 None
1 2
Code Select: Future Option
0 None
Product Data Sheet SCADAPack 313EModel Code
8
P314E: 5212 controller board and integrated 56O7 I/O board
Controller
Processors • CPU:32-bitARM7microcontroller,32MHzclock,integratedwatchdogtimer• Microcontrollerco-processor,20MHzclock
Memory 16MBFLASHROM,4MBCMOSRAM,4kBEEPROM
Non-VolatileRAM CMOSSRAMwithlithiumbatteryretainscontentsfor2yearswithnopower
EventLoggingCapacity 20,000events
MaximumDatabasePoints 1,000typical
I/O
AnalogInputs • 8softwareconfigurable:0-20/4-20mA/0-5/0-10V(15-bit)• 3internal:measureincomingpowersupplyvoltageforsolarapplications,batteryvoltage,andcontrollertemperature
AnalogOutputs • Standard:None• 2withoptional5305on5607I/Oboard:0-20/4-20mA(12-bit)
DigitalI/O • 16digitalinputs:12/24V,48V,115/125V,240V• 10relayoutputs:drycontactorDCsolidstate,drycontactrating:3A,30VDCor240VAC(resistive),DCsolidstaterating:3A,60VDC
CounterInputs • 1drycontact:0-10Hzor0-5kHz• 2turbineordrycontact:0-10kHz
Communications
SerialPortsCOM1,COM2 • RS-232port,8-pinmodularRJ45jack,fullorhalf-duplex,or• RS-485port,2-wire,half-duplex
BaudRates 300,600,1200,2400,4800,9600,19200,38400,57600,and115200
SerialProtocols DNP3Slave,DNP3Master,IEC60870-5-101Slave,IEC60870-5-103Master,ModbusRTUMaster,ModbusRTUSlave,DF1
USBPeripheralPort USB2.0compliantB-typereceptacle,DNP3protocol
Wireless1 Spreadspectrumradioat900MHz2and2.4GHz2
General
I/OTerminations 5,6,and9-poleremovableterminalblocks,12to22AWG,15Acontacts
Dimensions 5.65inch(144mm)wide,6.50inch(165mm)high,2.80inch(72mm)deep
Packaging Corrosionresistant,zinc-platedsteelwithblackenamelpaint
Environment 5%RHto95%,non-condensing,–40°C(–40°F)to70°C(158°F)
Power
5212ControllerBoard • 11-30VDC,5.8Wtypical• Add30to90mWwhenenablingtheLEDs• 8.5Wat24Vmaximum,5Vsupplyfully-loaded
5607I/OModule • 11-30VDC,10.3mAplusanalogoutputs• 235mA(max.)at5Vrequiredfrom5212controllerboard
Warranty 3yearsonpartsandlabor
Certifications
HazardousLocationsNorthAmerica
SuitableforuseinClassI,Division2,GroupsA,B,CandDHazardousLocations.TemperatureCodeT4CSAcertifiedtotherequirementsof:• CSAStd.C22.2No.213-M1987-HazardousLocations• ULStd.No.1604-Hazardous(Classified)Locations
HazardousLocationsEurope
ATEXII3G,ExnAIICT4perEN60079-15,protectiontypen(Zone2).DoesnotincludeWirelessversions.
HazardousLocations IECEx,ExnAIICT4perIEC60079-15,protectiontypen(Zone2).DoesnotincludeWirelessversions.
1 Availableonlywithoptionalintegratedwirelessmodulesorwithstand-alonewirelessmodules.2 Notapplicableinallcountries.
Disclaimer:SchneiderElectricreservestherighttochangeproductspecifications.Formoreinformationvisitwww.schneider-electric.com.
Product Data Sheet SCADAPack 314ESpecifications
9
TBUP314-EA55-AB00representsasamplecodeforaSCADAPack314Ewith12Vdrycontactrelayoutputs
Model Select: Controller
TBUP314 SCADAPack314E,32Bitcontroller,8AnalogInputs,16DigitalInputs,10DigitalOutputs,3Accumulators
Code Select: Platform
E EFirmwareplatform(ConfigurationSoftwareincluded),executestwoIEC61131-3kernels,Workbenchrequired
Code Select: SCADA Security
A Authentication
B AuthenticationandAGA-12SCADAEncryptionSecurity
Code Select: Protocol Option
5 Modbus,DNP3,DF1,IEC60870-5-101Slave
6 AddsIEC60870-5-103Master,ProtectionRelayProtocol(fordatatransmissionwithIEDs)
Code Select: License Option
5 DNP3DataConcentratorLicense(limitof500pointsfrom10IEDs),supportsmultipleDNP3Masters(upto3Masters)
Code Select: Analog Inputs
A Adds8selectableas0-20mA,4-20mA,0-5Vor0-10V
Code Select: Digital Inputs/Outputs
B 16DigitalInputs(12/24V)and10DryContactRelayoutputs
D 16DigitalInputs(120V)and10DryContactRelayoutputs
F 16DigitalInputs(12/24V)and10SolidStateRelayoutputs,ATEXCertified(withnoIntegratedradio)
H 16DigitalInputs(120V)and10SolidStateRelayoutputs
Code Select: Analog Outputs
0 None
1 2channelanalogoutputoption,0-20mA
Code Select: Integrated Communication Interfaces
0 None
FreeWave & MDS Radios (requires one RS232 port)
1 900MhzFreeWaveSpreadSpectrumRadio
A 900MHzMDSSpreadSpectrumRadio
Trio Radios - 900MHz (requires one RS232 port)
B 900MHzTrioSpreadSpectrumRadiowithencryption,902-928MHz(FCC/IC)
C 900MHzTrioSpreadSpectrumRadiowithencryption,915-928MHz(AUS)
D 900MHzTrioSpreadSpectrumRadio,915-928MHz(BRAZIL)
E 900MHzTrioSpreadSpectrumRadio,921-928MHz(NZ)
Trio Radios - 2.4GHz (requires one RS232 port)
J 2.4GHzTrioSpreadSpectrumRadio,ETSI/100mW,ATEX(EUROPE)
K 2.4GHzTrioSpreadSpectrumRadiowithEncryption,500mW(CANADA,USA&AUSTRALIA)
L 2.4GHzTrioSpreadSpectrumRadio,500mW(OUTSIDEOFEUROPE,CANADA,USA&AUSTRALIA)
Product Data Sheet SCADAPack 314EModel Code
10
P330E: 5210 controller board only
Controller
Processors • CPU:32-bitARM7microcontroller,32MHzclock,integratedwatchdogtimer• Microcontrollerco-processor,20MHzclock
Memory 16MBFLASHROM,4MBCMOSRAM,4kBEEPROM
Non-VolatileRAM CMOSSRAMwithlithiumbatteryretainscontentsfor2yearswithnopower
EventLoggingCapacity 20,000events
MaximumDatabasePoints 1,000typical
I/O
CounterInputs • 1,0-10Hzor0-5kHz(drycontact)• 2,0-10kHz(turbineordrycontact)
Communications
SerialPortsCOM1,COM2 • RS-232port,8-pinmodularRJ45jack,fullorhalfduplex,or• RS-485port,2-wire,halfduplex
SerialPortCOM3 • RS-232port,8-pinmodularRJ45jack,fullorhalfduplexwithRTS/CTScontrolandoperatorinterfacepowercontrol
BaudRates 300,600,1200,2400,4800,9600,19200,38400,57600,and115200
SerialProtocols DNP3Slave,DNP3Master,IEC60870-5-101Slave,IEC60870-5-103Master,ModbusRTUMaster,ModbusRTUSlave,DF1
EthernetPort RJ45,10/100BaseT
EthernetProtocols DNP3inTCPMaster/Slave,DNP3inUDPMaster/Slave,Modbus/TCPClientandServer,IEC60870-5-104Slave,NTPServer,TelnetServer,FTPServer,BOOTPServer
USBPeripheralPort USB2.0compliant“B”-typereceptacle,DNP3protocol
Wireless1 Spreadspectrumradioat900MHz2and2.4GHz2
General
I/OTerminations 6-poleremovableterminalblock,12to22AWG,15Acontacts
Dimensions 5.65inch(144mm)wide,5.00inch(127mm)high,1.80inch(45mm)deep
Packaging Corrosionresistantzinc-platedsteelwithblackenamelpaint
Environment 5%RHto95%,non-condensing,–40°C(–40°F)to70°C(158°F)
PowerInput • 11-30VDC,3.5Wtypical• Add25to100mWwhenenablingtheLEDs• 12Wat24Vmaximum,5Vsupplyfullyloaded
Warranty 3yearsonpartsandlabor
Certifications
HazardousLocationsNorthAmerica
SuitableforuseinClassI,Division2,GroupsA,B,CandDHazardousLocations.TemperatureCodeT4CSAcertifiedtotherequirementsof:• CSAStd.C22.2No.213-M1987-HazardousLocations.• ULStd.No.1604-Hazardous(Classified)Locations.
HazardousLocations-Europe ATEXII3G,ExnAIICT4perEN60079-15,protectiontypen(Zone2).DoesnotincludeWirelessversions.
HazardousLocations IECEx,ExnAIICT4perIEC60079-15,protectiontypen(Zone2)DoesnotincludeWirelessversions.
1 Availableonlywithoptionalintegratedwirelessmodulesorwithstand-alonewirelessmodules.2 Notapplicableinallcountries.
Disclaimer:SchneiderElectricreservestherighttochangeproductspecifications.Formoreinformationvisitwww.schneider-electric.com.
Product Data Sheet SCADAPack 330ESpecifications
11
P334E: 5210 controller board and integrated 5607 I/O board
Controller
Processors • CPU:32-bitARM7microcontroller,32MHzclock,integratedwatchdogtimer• Microcontrollerco-processor,20MHzclock
Memory 16MBFLASHROM,4MBCMOSRAM,4kBEEPROM
Non-VolaliteRAM CMOSSRAMwithlithiumbatteryretainscontentsfor2yearswithnopower
EventLoggingCapacity 20,000events
MaximumDatabasePoints 1,000typical
I/O
AnalogInputs 8,0-20/4-20mA/0-5/0-10V(15-bit)softwareconfigurable
AnalogOutputs • Standard:None• 2,0-20/4-20mA(12-bit)withoptional5305on5607I/Oboard
DigitalI/O • 16,12/24V,48V,115/125V,240Vdigitalinputs• 10relayoutputs:drycontactorDCsolidstate,drycontactrating:3A,30VDCor240VAC(resistive),DCsolidstaterating:3A,60VDC
CounterInputs 1,0-10Hzor0-5kHz(drycontact);2,0-10kHz(turbineordrycontact)
Communications
SerialPortsCOM1,COM2 • RS-232port,8-pinmodularRJ45jack,fullorhalfduplex,or• RS-485port,2-wire,halfduplex
SerialPortCOM3 RS-232port,8-pinmodularRJ45jack,fullorhalfduplexwithRTS/CTScontrolandoperatorinterfacepowercontrol
BaudRates 300,600,1200,2400,4800,9600,19200,38400,57600,and115200
SerialProtocols DNP3Slave,DNP3Master,IEC60870-5-101Slave,IEC60870-5-103Master,ModbusRTUMaster,ModbusRTUSlave,DF1
EthernetPort RJ45,10/100BaseT
EthernetProtocols DNP3inTCPMaster/Slave,DNP3inUDPMaster/Slave,Modbus/TCPClientandServer,IEC60870-5-104Slave,NTPServer,TelnetServer,FTPServer,BOOTPServer
USBPeripheralPort USB2.0compliant“B”-typereceptacle,DNP3protocol
Wireless1 Spreadspectrumradioat900MHz2and2.4GHz2
General
I/OTerminations 5,6and9-poleremovableterminalblocks,12to22AWG,15Acontacts
Dimensions 5.65inch(144mm)wide,6.50inch(165mm)high,2.80inch(72mm)deep
Packaging Corrosionresistantzinc-platedsteelwithblackenamelpaint
Environment 5%RHto95%,non-condensing,–40°C(–40°F)to70°C(158°F)
Power
5210ControllerBoard • 11-30VDC,8.5Wtypical• Add25to100mWwhenenablingtheLEDs• 12Wat24Vmaximum,5Vsupplyfullyloaded
5607I/OModule • 11-30VDC,10.3mAplusanalogoutputs• 325mA(max.)at5Vrequiredfrom5210controllerboard
Warranty 3yearsonpartsandlabor
Certifications
HazardousLocationsNorthAmerica
SuitableforuseinClassI,Division2,GroupsA,B,CandDHazardousLocations.TemperatureCodeT4CSAcertifiedtotherequire-mentsof:• CSAStd.C22.2No.213-M1987-HazardousLocations.• ULStd.No.1604-Hazardous(Classified)Locations.
HazardousLocations-Europe ATEXII3G,ExnAIICT4perEN60079-15,protectiontypen(Zone2).DoesnotincludeWirelessversions.
HazardousLocations IECEx,ExnAIICT4perIEC60079-15,protectiontypen(Zone2)DoesnotincludeWirelessversions.
1 Availableonlywithoptionalintegratedwirelessmodulesorwithstand-alonewirelessmodules.2 Notapplicableinallcountries.
Disclaimer:SchneiderElectricreservestherighttochangeproductspecifications.Formoreinformationvisitwww.schneider-electric.com.
Product Data Sheet SCADAPack 334ESpecifications
12
TBUP334-EA55-AB00representsasamplecodeforaSCADAPack334Ewith12Vdrycontactrelayoutputs
Model Select: Controller
TBUP330 SCADAPack330E,32Bitcontroller,3Accumulators
TBUP334 SCADAPack334E,withModel5607I/Oboard,comeswithaboveI/Oplus8AnalogI/P,16DigitalI/Pand10DigitalO/P
Code Select: Platform
E EFirmwareplatform(ConfigurationSoftwareincluded),executestwoIEC61131-3kernels,Workbenchrequired
Code Select: SCADA Security
A Authentication
B AuthenticationandAGA-12SCADAEncryptionSecurity
Code Select: Protocol Option
5 Modbus,DNP3,DF1,Modbus/TCP,TCP/IP,IEC60870-5-101/104Slave
6 AddsIEC60870-5-103Master,ProtectionRelayProtocol(fordatatransmissionwithIEDs)
Code Select: License Option
5 DNP3DataConcentratorLicense(limitof500pointsfrom10IEDs),supportsmultipleDNP3Masters(upto3Masters)
Code Select: Analog Inputs
A P330:NoneP334:adds8selectableas0-20mA,4-20mA,0-5Vor0-10V
Code Select: Digital Inputs/Outputs
A P330:None
B P334:16DigitalInputs(12/24V)and10DryContactRelayoutputs
D P334:16DigitalInputs(120V)and10DryContactRelayoutputs
F P334:16DigitalInputs(12/24V)and10SolidStateRelayoutputs,ATEXCertified(withnoIntegratedradio)
H P334:16DigitalInputs(120V)and10SolidStateRelayoutputs
Code Select: Analog Outputs
0 None
1 P334only:2channelAnalogOutputoption,0-20mA
Code Select: Integrated Communication Interfaces
0 None
FreeWave & MDS Radios (requires one RS232 port)
1 900MhzFreeWaveSpreadSpectrumRadio
A 900MHzMDSSpreadSpectrumRadio
Trio Radios - 900MHz (requires one RS232 port)
B 900MHzTrioSpreadSpectrumRadiowithencryption,902-928MHz(FCC/IC)
C 900MHzTrioSpreadSpectrumRadiowithencryption,915-928MHz(AUS)
D 900MHzTrioSpreadSpectrumRadio,915-928MHz(BRAZIL)
E 900MHzTrioSpreadSpectrumRadio,921-928MHz(NZ)
Trio Radios - 2.4GHz (requires one RS232 port)
J 2.4GHzTrioSpreadSpectrumRadio,ETSI/100mW,ATEX(EUROPE)
K 2.4GHzTrioSpreadSpectrumRadiowithEncryption,500mW(CANADA,USA&AUSTRALIA)
L 2.4GHzTrioSpreadSpectrumRadio,500mW(OUTSIDEOFEUROPE,CANADA,USA&AUSTRALIA)
Product Data Sheet SCADAPack 330E | 334EModel Code
13
333E: 5210 controller board and integrated 5611 I/O board
Controller
Processors • CPU:32-bitARM7microcontroller,32MHzclock,integratedwatchdogtimer• Microcontrollerco-processor,20MHzclock
Memory 16MBFLASHROM,4MBCMOSRAM,4kBEEPROM
Non-VolatileRAM CMOSSRAMwithlithiumbatteryretainscontentsfor2yearswithnopower
EventLoggingCapacity 20,000events
MaximumDatabasePoints 1,000typical
I/O
AnalogInputs • 4softwareconfigurable,0-20/4-20mA/0-5/0-10V(15-bit)• 3internal:measureincomingpowersupplyvoltageforsolarapplications,batteryvoltage,andcontrollertemperature
AnalogOutputs • Standard:None• 2,0-20/4-20mA(12-bit)withoptionalcardon5611I/Oboard
DigitalI/O • 16,12/24Vdigitalinputs• 10relayoutputs:drycontact,drycontactrating:3A,30VDCor240VAC(resistive)
CounterInputs 1,0-10Hzor0-5kHz(drycontact);2,0-10kHz(turbineordrycontact)
Communications
SerialPortsCOM1,COM2 • RS-232port,8-pinmodularRJ45jack,fullorhalfduplex,or• RS-485port,2-wire,halfduplex
SerialPortCOM3 RS-232port,8-pinmodularRJ45jack,fullorhalfduplexwithRTS/CTScontrolandoperatorinterfacepowercontrol
BaudRates 300,600,1200,2400,4800,9600,19200,38400,57600,and115200
SerialProtocols DNP3Slave/Master,IEC60870-5-101Slave,ModbusRTUSlave,optionalModbusMasterandDF1Master
EthernetPort RJ45,10/100BaseT
IPProtocols DNP3inTCPMaster/Slave,DNP3inUDPMaster/Slave,Modbus/TCPClient,IEC60870-5-104Slave,NTPServer,TelnetServer,FTPServer,BOOTPServer,optionalModbus/TCPServer
USBPort USB2.0compliant“B”-typereceptacle,DNP3protocol
Wireless Externalmodem(e.g.SchneiderElectricGPRSmodemref.SR2MOD3)
General
LogicControl OptionalIEC61131-3SCADAPackWorkbenchprogrammingsuite(LD,ST,FBD&SFC)
I/OTerminations 5,6and9-poleremovableterminalblocks,12to22AWG,15Acontacts
Dimensions 5.65inch(144mm)wide,6.50inch(165mm)high,2.80inch(72mm)deep
Packaging Corrosionresistantzinc-platedsteelwithblackenamelpaint
Environment 5%RHto95%,non-condensing,–25°C(–13°F)to70°C(158°F)
Power
5210ControllerBoard • 11-30VDC,8.5Wtypical• Add25to100mWwhenenablingtheLEDs• 12Wat24Vmaximum,5Vsupplyfullyloaded
5611I/OModule • 11-30VDC,10.3mAplusanalogoutputs• 325mA(max.)at5Vrequiredfrom5210controllerboard
Warranty 3yearsonpartsandlabor
Certifications
• CEmarking• C-Tick• UL508(US/Canada)-cULus• FCC/EN61000-6emissions&immunity
Disclaimer:SchneiderElectricreservestherighttochangeproductspecifications.Formoreinformationvisitwww.schneider-electric.com.
Product Data Sheet SCADAPack 333ESpecifications
14
TBUP333-EA54-AB00representsasamplecodeforaSCADAPack333Ewith12Vdry-contactrelayoutputsandnoIEC61131programmingoption.
Model Select: Controller
TBUP333 SCADAPack333E,32-Bitcontroller,4AnalogInputs,2optionalAnalogOutputs,16DigitalInputs,10DigitalOutputs,3CounterInputs
Code Select: Platform
E EFirmwareplatform(SCADAPackEConfiguratorsoftwareincluded),executestwoIEC61131-3kernels(optional),Workbenchrequired
Code Select: SCADA Security
A None
B AGA-12EncryptionforDNP3
C DNP3SecureAuthenticationSAv2
D DNP3SecureAuthenticationwithAGA-12Encryption
Notes:• TheSecurityAdministratorApplicationhastobepurchasedtogenerateandmanagesecuritykeys.• AGA-12Encryptionissubjecttoexportrestrictions.PleaseconsultwithyourTRSSbusinessunitcontact.
Code Select: Protocol Option
5 DNP3Slave/Master,IEC60870-5-101/-104Slave,ModbusRTUSlave
Code Select: License Option
4 Option1:withoutIEC61131,ModbusMasterandDF1Master
5 Option2:withIEC61131-3(executestwokernels,SCADAPackWorkbenchrequired),ModbusMasterandDF1Master
Notes:• BothoptionsincludeDNP3DataConcentratorlicense(limitof500pointsfrom10IEDs),MultipleDNP3MasterLicense(upto3Masters)
• Ifyouorderaproductwithoption1whichyoulaterwanttoupgradetooption2,youhavetoorderaRTUlicenceupdate(ref.TBUM297889)
Code Select: Analog Inputs
A 4
Code Select: Digital Inputs/Outputs
B 16inputsand10outputs
Code Select: Analog Outputs
0 None
1 2
Code Select: Future Option
0 None
Product Data Sheet SCADAPack 333EModel Code
15
337E: 5210 controller board and integrated 5606 I/O board
Controller
Processors • CPU:32-bitARM7microcontroller,32MHzclock,integratedwatchdogtimer• Microcontrollerco-processor,20MHzclock
Memory 16MBFLASHROM,4MBCMOSRAM,4kBEEPROM
Non-VolatileRAM CMOSSRAMwithlithiumbatteryretainscontentsfor2yearswithnopower
EventLoggingCapacity 20,000events
MaximumDatabasePoints 1,000typical
I/O
AnalogInputs • 8softwareconfigurable,0-20/4-20mA/0-5/0-10V(15-bit)• 3internal:measureincomingpowersupplyvoltageforsolarapplications,batteryvoltage,andcontrollertemperature
AnalogOutputs • Standard:None• 2,0-20/4-20mA(12-bit)withoptionalcardon5606I/Oboard
DigitalI/O • 32,12/24Vdigitalinputs• 16relayoutputs:drycontact,drycontactrating:3A,30VDCor240VAC(resistive)
CounterInputs 1,0-10Hzor0-5kHz(drycontact);2,0-10kHz(turbineordrycontact)
Communications
SerialPortsCOM1,COM2 • RS-232port,8-pinmodularRJ45jack,fullorhalfduplex,or• RS-485port,2-wire,halfduplex
SerialPortCOM3 RS-232port,8-pinmodularRJ45jack,fullorhalfduplexwithRTS/CTScontrolandoperatorinterfacepowercontrol
BaudRates 300,600,1200,2400,4800,9600,19200,38400,57600,and115200
SerialProtocols DNP3Slave/Master,IEC60870-5-101Slave,ModbusRTUSlave/MasterandDF1Master
EthernetPort RJ45,10/100BaseT
IPProtocols DNP3inTCPMaster/Slave,DNP3inUDPMaster/Slave,Modbus/TCPClient,IEC60870-5-104Slave,NTPServer,TelnetServer,FTPServer,BOOTPServer,optionalModbus/TCPServer
USBPort USB2.0compliant“B”-typereceptacle,DNP3protocol
Wireless Externalmodem(e.g.SchneiderElectricGPRSmodemref.SR2MOD3)
General
LogicControl IEC61131-3SCADAPackWorkbenchprogrammingsuite(LD,ST,FBD&SFC)
I/OTerminations 5,6,9and10-poleremovableterminalblocks,12to22AWG,15Acontacts
Dimensions 8.40inch(213mm)wide,6.13inch(155mm)high,2.80inch(72mm)deep
Packaging Corrosionresistantzinc-platedsteelwithblackenamelpaint
Environment 5%RHto95%,non-condensing,–25°C(–13°F)to70°C(158°F)
Power
5210ControllerBoard • 11-30VDC,8.5Wtypical• Add25to100mWwhenenablingtheLEDs• 12Wat24Vmaximum,5Vsupplyfullyloaded
5606I/OModule • 600mA(max.)at5Vrequiredfrom5210controllerboard• 11-30VDC,12mAplusanalogoutputs
Warranty 3yearsonpartsandlabor
Certifications
• CEmarking• C-Tick• UL508(US/Canada)-cULus• FCC/EN61000-6emissions&immunity
Disclaimer:SchneiderElectricreservestherighttochangeproductspecifications.Formoreinformationvisitwww.schneider-electric.com.
Product Data Sheet SCADAPack 337ESpecifications
16
TBUP337-EA55-AB00representsasamplecodeforaSCADAPack337Ewith12Vdry-contactrelayoutputsandIEC61131-3programming.
Model Select: Controller
TBUP337 SCADAPack337E,withModel5606I/Oboard,comeswith8AnalogI/P,2optionalAnalogO/P,32DigitalI/P,16DigitalO/Pand3CounterI/P
Code Select: Platform
E EFirmwareplatform(SCADAPackEConfiguratorsoftwareincluded),executestwoIEC61131-3kernels(optional),Workbenchrequired
Code Select: SCADA Security
A None
B AGA-12EncryptionforDNP3
C DNP3SecureAuthenticationSAv2
D DNP3SecureAuthenticationwithAGA-12Encryption
Notes:• TheSecurityAdministratorApplicationhastobepurchasedtogenerateandmanagesecuritykeys.• AGA-12Encryptionissubjecttoexportrestrictions.PleaseconsultwithyourTRSSbusinessunitcontact.
Code Select: Protocol Option
5 DNP3Slave/Master,IEC60870-5-101/-104Slave,ModbusRTUSlave/MasterandDF1Master
Code Select: License Option
5 IncludesDNP3DataConcentratorlicense(limitof500pointsfrom10IEDs),MultipleDNP3MasterLicense(upto3Masters)
Code Select: Analog Inputs
A 4
Code Select: Digital Inputs/Outputs
B 32inputsand16outputs
Code Select: Analog Outputs
0 None
1 2
Code Select: Future Option
0 None
Product Data Sheet SCADAPack 337EModel Code
17
P350E: 5209 controller board only
Controller
Processors • CPU:32-bitARM7microcontroller,32MHzclock,integratedwatchdogtimer• TwoMicrocontrollerco-processors,20MHzclock
Memory 16MBFLASHROM,4MBCMOSRAM,4kBEEPROM
Non-VolatileRAM CMOSSRAMwithlithiumbatteryretainscontentsfor2yearswithnopower
EventLoggingCapacity 20,000events
MaximumDatabasePoints 1,000typical
I/O
AnalogInputs • 5,userselectable0-10V(15-bit)or0-20mAplusoverrange(14-bit)• 1,0-32.7VDC(15-bit)
AnalogOutputs • Standard:None• 2,0-20/4-20mA(12-bit)withoptional5305
DigitalI/O 8,userselectableasdrycontactinputsoropendrainoutputs
CounterInputs • 1,0-10Hz(drycontact)• 2,0-10kHz(turbineordrycontact)
Communications
SerialPortCOM1 RS-485port,2-poleremovableterminalblock,2-wire,halfduplex
SerialPortCOM2 • RS-232port,8-pinmodularRJ45jack,fullorhalfduplex,or• RS-485port,2-wire,halfduplex
SerialPortCOM3 RS-232port,8-pinmodularRJ45jack,halfduplexwithRTS/CTScontrolandoperatorinterfacepowercontrol
BaudRates 300,600,1200,2400,4800,9600,19200,38400,57600,and115200
SerialProtocols DNP3Slave,DNP3Master,IEC60870-5-101Slave,IEC60870-5-103Master,ModbusRTUMaster,ModbusRTUSlave,DF1
EthernetPort RJ45,10/100BaseT
EthernetProtocols DNP3inTCPMaster/Slave,DNP3inUDPMaster/Slave,Modbus/TCPClientandServer,IEC60870-5-104Slave,NTPServer,TelnetServer,FTPServer,BOOTPServer
USBPeripheralPort USB2.0compliant“B”-typereceptacle,DNP3protocol
Wireless1 Spreadspectrumradioat900MHz2and2.4GHz2
General
I/OTerminations 6and12-poleremovableterminalblocks,12to22AWG,15Acontacts
Dimensions 8.40inch(213mm)wide,5.00inch(127mm)high,1.80inch(45mm)deep
Packaging Corrosionresistantzinc-platedsteelwithblackenamelpaint
Environment 5%RHto95%,non-condensing,–40°C(–40°F)to70°C(158°F)
PowerInput • 11-30VDC,4.6Wtypical• Add25to100mWwhenenablingtheLED• 12Wat24Vmaximum.5VsupplyfullyloadedandVlooponandboosted,fullyloaded
VoltageConverter 12VDCto24VDC
Warranty 3yearsonpartsandlabor
Certifications
HazardousLocationsNorthAmerica
SuitableforuseinClassI,Division2,GroupsA,B,CandDHazardousLocations.TemperatureCodeT4,ULlistedandCSAcertifiedtotherequirementsof:• CSAStd.C22.2No.213-M1987-HazardousLocations.• ULStd.No.1604-Hazardous(Classified)Locations.
HazardousLocations-Europe ATEXII3G,ExnAIICT4perEN60079-15,protectiontypen(Zone2).DoesnotincludeWirelessversions.
HazardousLocations IECEx,ExnAIICT4perIEC60079-15,protectiontypen(Zone2)DoesnotincludeWirelessversions.
1 Availableonlywithoptionalintegratedwirelessmodulesorwithstand-alonewirelessmodules.2 Notapplicableinallcountries.
Disclaimer:SchneiderElectricreservestherighttochangeproductspecifications.Formoreinformationvisitwww.schneider-electric.com.
Product Data Sheet SCADAPack 350ESpecifications
18
P357E: 52O9 controller board and integrated 56O6 I/O board
Controller
Processors • CPU:32-bitARM7microcontroller,32MHzclock,integratedwatchdogtimer• Microcontrollerco-processor,20MHzclock
Memory 16MBFLASHROM,4MBCMOSRAM,4kBEEPROM
Non-VolatileRAM CMOSSRAMwithlithiumbatteryretainscontentsfor2yearswithnopower
EventLoggingCapacity 20,000events
MaximumDatabasePoints 1,000typical
I/O
AnalogInputs • 5,userselectable0-10V(15-bit)or0-20mAplusoverrange(14-bit)• 1,0-32.7VDC(15-bit);8,0-20/4-20mA/0-5/0-10V(15-bit)softwareconfigurable
AnalogOutputs • Standard:None• 2,0-20/4-20mA(12-bit)withoptional5305on5209controllerboard• 2,0-20/4-20mA(12-bit)withoptional5305on5606I/Oboard
DigitalI/O • 8,userselectableasdrycontactinputsoropendrainoutputs• 32,12/24V,48V,115/125V,240Vdigitalinputs;16,relayoutputs-drycontactorDCsolidstate
CounterInputs 1,0-10Hz(drycontact);2,0-10kHz(turbineordrycontact)
Communications
SerialPortCOM1 RS-485port,2-poleremovableterminalblock,2-wire,halfduplex
SerialPortCOM2 • RS-232port,8-pinmodularRJ45jack,fullorhalfduplexRS-232,or• RS-485port,2-wire,halfduplex
SerialPortCOM3 RS-232port,8-pinmodularRJ45jack,halfduplexwithRTS/CTScontrolandoperatorinterfacepowercontrol
BaudRates 300,600,1200,2400,4800,9600,19200,38400,57600,and115200
SerialProtocols DNP3Slave,DNP3Master,IEC60870-5-101Slave,IEC60870-5-103Master,ModbusRTUMaster,ModbusRTUSlave,DF1
EthernetPort RJ45,10/100BaseT
EthernetProtocols DNP3inTCPMaster/Slave,DNP3inUDPMaster/Slave,Modbus/TCPClientandServer,IEC60870-5-104Slave,NTPServer,TelnetServer,FTPServer,BOOTPServer
USBPeripheralPort USB2.0compliant“B”-typereceptacle,DNP3protocol
Wireless1 Spreadspectrumradioat900MHz2and2.4GHz2
General
I/OTerminations 5,6,9,10and12-poleremovableterminalblocks,12to22AWG,15Acontacts
Dimensions 8.40inch(213mm)wide,6.13inch(155mm)high,2.80inch(72mm)deep
Packaging Corrosionresistantzinc-platedsteelwithblackenamelpaint
Environment 5%RHto95%,non-condensing,–40°C(–40°F)to70°C(158°F)
Power
5209ControllerBoard • 11-30VDC,9.2Wtypical• Add25to100mWwhenenablingtheLEDs• 12Wat24Vmaximum.5VsupplyfullyloadedandVlooponandboosted,fullyloaded
5606I/OModule • 600mA(max.)at5Vrequiredfrom5209controllerboard• 11-30VDC,12mAplusanalogoutputs
VoltageConverter 12VDCto24VDC
Warranty 3yearsonpartsandlabor
CertificationsHazardousLocationsNorthAmerica
SuitableforuseinClassI,Division2,GroupsA,B,CandDHazardousLocations.TemperatureCodeT4,ULlistedandCSAcertifiedtotherequirementsof:• CSAStd.C22.2No.213-M1987-HazardousLocations.• ULStd.No.1604-Hazardous(Classified)Locations.
HazardousLocations-Europe ATEXII3G,ExnAIICT4perEN60079-15,protectiontypen(Zone2).DoesnotincludeWirelessversions.
HazardousLocations IECEx,ExnAIICT4perIEC60079-15,protectiontypen(Zone2)DoesnotincludeWirelessversion
1 Availableonlywithoptionalintegratedwirelessmodulesorwithstand-alonewirelessmodules.2 Notapplicableinallcountries.
Disclaimer:SchneiderElectricreservestherighttochangeproductspecifications.Formoreinformationvisitwww.schneider-electric.com.
Product Data Sheet SCADAPack 357ESpecifications
19
TBUP350-EA55-AA00representsasamplecodeforaSCADAPack350Ewith8digitalI/O
Model Select: Controller
TBUP350 SCADAPack350E,32Bitcontroller,5A/I,8configurableDigitalI/O,3Counters,2RS232,1RS485,2USB,1Ethernet
TBUP357 SCADAPack357E,withModel5606I/Oboard,comeswiththeaboveplus8AnalogI/P,32DigitalI/Pand16DigitalO/P
Code Select: Platform
E EFirmwareplatform(ConfigurationSoftwareincluded),executestwoIEC61131-3kernels,Workbenchrequired
Code Select: SCADA Security
A Authentication
B AuthenticationandAGA-12SCADAEncryptionSecurity
Code Select: Protocol Option
5 Modbus,DNP3,DF1,Modbus/TCP,TCP/IP,IEC60870-5-101/104Slave
6 AddsIEC60870-5-103Master,ProtectionRelayProtocol(fordatatransmissionwithIEDs)
Code Select: License Option
5 DNP3DataConcentratorLicense(limitof500pointsfrom10IEDs),supportsmultipleDNP3Masters(upto3Masters)
Code Select: Analog Inputs
A P350:5selectableas0-10Vor0-20mAP357:adds8selectableas0-20mA,4-20mA,0-5Vor0-10V
Code Select: Digital Inputs/Outputs
A P350:8configurableDigitalI/O,IndividuallyselectableasD/I(DryContact)orDigitalOutput(OpenDrain)
B P357:IncludesP350I/Oplus32DigitalInputs(12/24V),16DryContactRelayOutputs
D P357:IncludesP350I/Oplus32DigitalInputs(120V),16DryContactRelayOutputs
F P357:IncludesP350I/Oplus32DigitalInputs(12/24V),16SolidStateRelayOutputs,ATEXCertified(withnoradio)
H P357:IncludesP350I/Oplus32DigitalInputs(120V),16SolidStateRelayOutputs
Code Select: Analog Outputs
0 None
1 P350orP357:2channelAnalogOutputoption,0-20mA(P357-2channelA/Ooptiononthe5606module)
2 P357only:4channelAnalogOutputoption,0-20mA(includes2channelA/Ooptiononbothmodules)
Code Select: Integrated Communication Interfaces
0 None
FreeWave & MDS Radios (requires one RS232 port)
1 900MhzFreeWaveSpreadSpectrumRadio
A 900MHzMDSSpreadSpectrumRadio
Trio Radios - 900MHz (requires one RS232 port)
B 900MHzTrioSpreadSpectrumRadiowithencryption,902-928MHz(FCC/IC)
C 900MHzTrioSpreadSpectrumRadiowithencryption,915-928MHz(AUS)
D 900MHzTrioSpreadSpectrumRadio,915-928MHz(BRAZIL)
E 900MHzTrioSpreadSpectrumRadio,921-928MHz(NZ)
Trio Radios - 2.4GHz (requires one RS232 port)
J 2.4GHzTrioSpreadSpectrumRadio,ETSI/100mW,ATEX(EUROPE)
K 2.4GHzTrioSpreadSpectrumRadiowithEncryption,500mW(CANADA,USA&AUSTRALIA)
L 2.4GHzTrioSpreadSpectrumRadio,500mW(OUTSIDEOFEUROPE,CANADA,USA&AUSTRALIA)
Product Data Sheet SCADAPack 350E | 357EModel Code
20
SCADAPack ES
Controller
Processor AMD586ElanSC52032-bitembeddedprocessor,100MHz
Memory 128MBSDRAM,32MBFlash,2048KBSRAM,512KBBootFlash
EventLoggingCapacity 40,000events
MaximumDatabasePoints 20,000typical
Temperature -40°C(-40°F)to65°C(150°F)operating,-40°C(-40°F)to70°C(158°F)storage
Humidity 10to95%RH(non-condensing)
InputVoltageRange 10to30VDC
PowerRequirements • 6.3Wat24VDCminimum• Add3.0Wwithallrelaysenergized• Add6.5Wforfullyloadedauxiliarypowersupply• Add.72Wperanalogoutput
AuxiliaryOutputSupply • Isolated24VDC200mAmax.(optional)• Isolated10VDC500mAmax.(optional)• Isolated5VDC1.0Amax.(optional,requiredforI/OExpansionmodulesorOperatorInterfaceTerminal)
Isolation PowerinputandAuxiliaryOutputarefunctionallyisolatedfromeachotherandallIOpoints
CommunicationPorts • Port0,Port1andPort4:RS-232;Port2andPort3:RS-232/RS-422/RS-485(softwareselectable)• Ethernet:Dual10/100Base-TUTPports(transformerisolated)Note:AllRS-232portsarestaticprotectedto±15kV(IEC801-2,Air-gapdischarge)
Protocols • Modbus,DNP3,Modbus/TCP,TCP/IP(standard)• IEC60870-5-103(serialmaster),-101(serialslave),-104(Ethernetslave)optional
RemovableMemorySocket CompactFlashType1:buffered,hot-swapcapable.Supportsupto4GBcard(compactflashcardnotincluded)
Dimensions 11.81inch(300mm)wide,6.89inch(175mm)high,1.57inch(40mm)deep
Digital Inputs
Configuration 16or32inputs
NormalOperationRange 10-30VDC
SequenceofEventsDetection 10mS
ChannelsPerCommon 8
Inversion Stateinversionperchannel
Debounce Adjustableperchannel
Counters 0-40Hzand0-1kHzcounterchannels(sharedwithdigitalinputs)
Digital Outputs
Configuration 8or16outputs
Type FormCSPDTrelay,3-terminalconnection(NO/Common/NC),Non-latching
Isolation 500VACminimumtoRTUelectronics
Maxswitchingvoltage 30VDC,25VAC
Maxswitchingload 60W/50VA(2A)
Specificationscontinueonthenextpage
Product Data Sheet SCADAPack ESSpecifications
21
Product Data Sheet SCADAPack ESSpecifications
SCADAPack ES
Analog Inputs
Configuration 6or12inputs
Type Unipolar
Resolution 12-bit,0.1%offullscaleat77°F(25°C),±0.3%overtemperaturerange
Isolation IsolatedfromchanneltochannelandfromRTUelectronics.Analoginputsmustbewithin50Vacor7VDCofchassisorearth
Range 4-20mAor1-5Vswitchselectable
Analog Outputs
Configuration 2or4outputs
Type Unipolar
Resolution 12bit±0.1%at77°F(25°C)with250ohmload,±0.5%overtemperaturerange
Isolation Optical.500VacminimumtoRTUelectronics
Range 4-20mA(voltageoutputavailablewithexternalprecisionresistor)
LoadRange • 0-100ohmswith9Vsupply• 150-1150ohmswith30Vsupply
Additional I/O
I/OExpansion Supportedmodules:5304,5405,5411,5505,5506and5606
SCADAPackES Supportforadditionalmulti-droppedESSmartRTU,viaserialorEthernetlinks
Certifications
Safety c(CSA)us.CAN/CSA-C22.2No.61010-1.RequirestheuseofSELVpowersuppliesonallpowerandIOpointsforcompliance
HazardousLocations Non-IncendiveElectricalEquipmentforUseinClassI,Division2GroupsA,B,CandD(optional)
Disclaimer:SchneiderElectricreservestherighttochangeproductspecifications.Formoreinformationvisitwww.schneider-electric.com.
22
TBUP500-1A00-AE00NrepresentsasamplecodeforaSCADAPackESwith16D/I,8D/O,6A/Iand2A/O
Model Select: Controller
TBUP500 SCADAPackES
Code Select: Communication Ports
1 3RS232,2RS232/485,2Ethernet10/100BaseT,1CompactFlashsocket(compactFlashcardsoldseparately)
Code Select: Processor/Memory
A AMDElanSC520CPU,100MHz,32MBOperatingSystemFLASH,128MBvolatileSDRAM,2MBBatteryBackedSRAM
Code Select: Protocol Option
0 Modbus,DNP3,DF1,Modbus/TCP,TCP/IP,IEC60870-5-101/104Slave(includedinallSmartRTUs)
1 AddsIEC60870-5-103Master,ProtectionRelayProtocol(fordatatransmissionwithIEDs)
Code Select: Programming Environment & SCADA Security
0 IEC61131-3(ExecutestwoIEC61131-3kernels,includesEConfigurator&extensions,Workbenchrequired)
1 IEC61131-3withAGA-12SCADAEncryptionSecurity
Code Select: License Option
A None(allunitscomestandardwithsupportformultipleDNP3Masters-upto3Masters)
B DNP3DataConcentratorLicense-SCADAPackESactsasaDNPmastertocollectdatafrommultipleslaves
Code Select: I/O Configuration
D/I D/O A/I A/O (SomeI/OExpansionmodulessupported)
B 0 0 0 0
E 16 8 6 2
A 32 16 12 4
Code Select: Power Supply
0 10-30VdcWideRangePowerinput,noauxiliarypowersupply
1 10-30VdcWideRangePowerinput,auxiliarypowersupplywith5Vdcoutput(requiredtopowerVisionDisplays)
2 10-30VdcWideRangePowerinput,auxiliarypowersupplywith10Vdcoutput
3 10-30VdcWideRangePowerinput,auxiliarypowersupplywith24Vdcoutput
Code Select: Approvals
0 c(CSA)us.CAN/CSA-C22.2No.61010-1.Approved-Non-HazardousLocations
1 c(CSA)us.CAN/CSA-C22.2No.61010-1,Class1-Div2(GroupsA,B,C,D).Approved-HazardousLocations
Code Select: Custom Options
N None
V AnalogInputrangesetfor1-5v(defaultrangeis4-20mA)
Product Data Sheet SCADAPack ESModel Code
23
Product Data Sheet 5505 – RTD input moduleSpecifications
5505 RTD input module
General
InputPoints 4,RTD
RTDType 100-ohmplatinum,3and4-wire,auto-detectionandcompensation
Calibration 0.00385Ω/Ω/°CstandardbasedonASTME1137/E1137M-04,ITS-90
Ranges 5505:Canbeconfiguredtoreturndatainohms,°C,°For°K• -200°Cto800°C(-328°Fto1472°F)• 0to500Ω5503Emulation:Dipswitchselectable• 0°Cto200°C(32°Fto392°F)• -100°Cto100°C(-148°Fto212°F)• -200°Cto0°C(-328°Fto32°F)• 0°Cto800°C(32°Fto1472°F)• 0°Cto400°C(32°Fto752°F)• 0to400Ω
DataFormat • 5505:32-bitfloatingpointand12statusbits• 5503Emulation:16-bitsignedinteger
Resolution • 5505:>17-biteffective• 5505Emulation:15-bit
RTDStatus • RTDisgood(notopen)• RTDinrange• RTD3or4-wire• RTDstatusnotavailablein5503Emulation
AccuracyonRTDRanges Percentoffullscaleoveroperationaltemperaturerangeincludinglinearizationerrors:+0.10%/-0.05%
Accuracyon0to500ohms Percentoffullscaleoveroperationaltemperaturerange:±0.03%
ExcitationCurrent 4mA,7.2%dutycyclein4-wiremode,14.4%in3-wiremode,250msscaninterval
LineResistance 100Ωmax.,ineachline
ConverterType 24-bitdelta-sigma
ResponseTime 380mstypicalfor10%to90%signalchangeatminimumfiltersetting
TransientProtection 2.5kVsurge-withstandcapabilityasperANSI/IEEEC37.90.1-1989
Isolation Isolationfromlogicsupplyandchassis,voltage500Vrms
5VPowerRequirements 6mA
11-30VDCPowerRequirements
12Voperation:4mA• plus0.6mAper4-wireRTD• plus1.2mAper3-wireRTD24Voperation:2.2mA• plus0.3mAper4-wireRTD• plus0.6mAper3-wireRTD
11-30VDC-Connector Removable.SharedwithRTDinputs0-1
11-30VDC-Isolation Isolationfromlogicsupplyandchassis
Terminations 8and10pole,removableterminalblock,12to22AWG,15Acontacts
Dimensions 74mmwidex124mmhighx45mmdeep(2.9in.x4.9in.x1.8in.)
Mounting 7.5x35DINrail
Packaging Corrosion-resistantzinc-platedsteelwithblackenamelpaint
Environment 5%RHto95%RH,non-condensing,-40°Cto70°C(-40°Fto158°F)operation,-40°Cto85°C(-40°Fto185°F)storage
Safety • Non-IncendiveElectricalEquipmentforUseinClassI,Division2• GroupsA,BCandDHazardousLocations• ATEXII3GandIECEx:ExnAIICT4perEN60079-15,protectiontypen(Zone2)
PartNumber TBUX297318
Disclaimer:SchneiderElectricreservestherighttochangeproductspecifications.Formoreinformationvisitwww.schneider-electric.com.
24
Product Data Sheet 5506 – Analog input moduleSpecifications
5506 Analog input module
General
InputPoints 8
Ranges • 0-20mA• 4-20mA• 0-5V• 1-5V
LEDIndicators 8redLEDs,indicatingcurrentinput,voltageinputandunderorover-rangesignalapplied
InputConfiguration Individualinputsconfigurablewith4mA/1V(20%)offsetandforvoltage/currentoperationwhenconfiguredasa5506.Allinputsdipswitch-selectablewith4mA/1V(20%)offsetandforvoltage/currentoperationwhenconfiguredtoemulatea5501module.
InputResistance 250ohms-Currentconfiguration;66kohms-Voltageconfiguration
Resolution 15-bitsoverthe0-5Vand0-20mAmeasurementrange
Type Single-ended
Accuracy ±0.1%offullscaleat25°C(77°F);±0.2%overtemperaturerange
TransientProtection 2.5kVsurgewithstandcapabilityasperANSI/IEEEC37.90.1-1989
NormalModeRejectionAt60Hzwith60HzScanning
• 53dBwith3Hzfilter• 50dBwith6Hzfilter• 49dBwith11Hzfilter• 45dBwith30Hzfilter
NormalModeRejectionAt50Hzwith50HzScanning
• 73dBwith3Hzfilter• 56dBwith6Hzfilter• 52dBwith11Hzfilter• 49dBwith30Hzfilter
ResponseTimefor10%to90%SignalChange(60HzScanning)
• 250mswith3Hzfilter• 130mswith6Hzfilter• 60mswith11Hzfilter• 30mswith30Hzfilter
ResponseTimefor10%to90%SignalChange(50HzScanning)
• 300mswith3Hzfilter• 140mswith6Hzfilter• 80mswith11Hzfilter• 40mswith30Hzfilter
Over-ScaleInputCapacity(withoutdamage)
Continuous:0.10A/14Vonthe20mAinputs;0.05A/14Vonthe5Vinputs
Isolation 500Vacisolationfromlogicsupplyandchassis
5VPowerRequirements • 22mA,LEDsoff• 45mA,LEDson
11-30VDCPowerRequirements 11mA
11-30VDC-Connector Removable,4positions
11-30VDC-Isolation Isolationfromlogicsupplyandchassis
Terminations 10pole,removableterminalblock,12to22AWG,15Acontacts
Dimensions 2.9inch(74mm)wide,4.9inch(124mm)high,1.8inch(45mm)deep
Mounting 7.5x35DINrail
Packaging Corrosion-resistantzinc-platedsteelwithblackenamelpaint
Environment 5%RHto95%RH,non-condensing,-40°Cto70°C(-40°Fto158°F)operation,-40°Cto85°C(-40°Fto185°F)storage
Safety • Non-IncendiveElectricalEquipmentforUseinClassI,Division2• GroupsA,BCandDHazardousLocations• ATEXII3GandIECEx:ExnAIICT4perEN60079-15,protectiontypen(Zone2)
PartNumber TBUX297319
Disclaimer:SchneiderElectricreservestherighttochangeproductspecifications.Formoreinformationvisitwww.schneider-electric.com.
25
Product Data Sheet 5304 – Analog output moduleSpecifications
5304 Analog output module
General
Outputpoints 4
OutputModes • Currentmode,jumperlinkselectable• Voltagemode,5Vfullscale,jumperlinkselectable,• Voltagemode,10Vfullscale,jumperlinkselectable
Outputsignalranges • 0-20mAor4-20mA,switchconfigurable• 0-5Vor1-5V,switchconfigurable,0-10Vor2-10V,switchconfigurable
OutputType Singleendedregulationonpositivesidewithcommonnegativereturn
MaximumLoadResistance 1000Ωwith24VDClooppower,400Ωwith12VDClooppower,250Ωwith9VDClooppower
MinimumLoadResistanceinVoltageMode
• 2kΩfor10Vfullscale,withmin20VDCpowerapplied• 1kΩfor5Vfullscale,withmin15VDCpowerapplied
Isolation 500VACfieldtologic
D/AResolution 12-bitoverthe0-20mA/0-5V/0-10Vranges
AbsoluteAccuracy +/-0.05%offullscaleat25ºC(77ºF),+/-0.2%offullscaleovertemperaturerange
NoiseandRipple 0.04%maximum
TransientProtection • 2.5kVsurgewithstandcapabilityasperANSI/IEEEC37.90.1-1989• Inductiveloadprotectiondiodesincluded
ResponseTime 2mstypicalto90%signalchange
Addressing DIPswitchconfigurable
12-24VOperatingVoltageLimits
• 9Vor(20mAxloadresistance)+4V(whicheverisgreater)incurrentmode• (1.5xRange/loadresistance)+Range+2.5Vinvoltagemode,30Vmaximum
PowerRequirements • 6mAmin.,25mAmaximum• 15mAquiescentplus80mAmax.incurrentmode• 15mAquiescentplus20mAmax.involtagemode
Terminations 10pole,removableterminalblock,12to22AWG,15ampcontacts
Dimensions 108mmwidex118mmhighx44mmdeep(4.25in.x4.625in.x1.75in.)
Mounting 7.5x35DINrail
Packaging Corrosionresistantzincplatedsteelwithblackenamelpaint
Environment 5%RHto95%RH,non-condensing,-40°Cto70°C(-40°Fto158°F)
Safety cCSAusandcULusClassI,Division2HazardousAreaRating,UL508listed
Model Part Number Description
5304-20 TBUX297248 4channelisolatedanalogoutputmodule,0-20mA
5304-10 TBUX297252 4channelisolatedanalogoutputmodule,0-10volts
5304-5 TBUX297253 4channelisolatedanalogoutputmodule,0-5volts
5304-C TBUX297254 4channelisolatedanalogoutputmodule,Custom(specifyrangeofeachinput)
Disclaimer:SchneiderElectricreservestherighttochangeproductspecifications.Formoreinformationvisitwww.schneider-electric.com.
26
Product Data Sheet 5405 – Digital input moduleSpecifications
5405 Digital input module
General
InputPoints 32
Ranges 12-24VDC,16-24VAC,120VAC/DC
Over-VoltageTolerance 150%sustainedover-voltagewithoutdamage
InputCurrent • 6.0mAtypical@24VDConthe24Vrange• 3.5mAtypical@24VAConthe24Vrange• 2.5mAtypical@120VDConthe120Vrange• 1.5mAtypical@120VAConthe120Vrange
DCInputLogicLevels • OFFtoONtransitionthresholdistypically7.5VDConthe24VDCrange• OFFtoONtransitionthresholdistypically55VDConthe120VDCrange
ACInputLevels • OFFtoONtransitionthresholdistypically6VAConthe24VACrange• OFFtoONtransitionthresholdistypically45VAConthe120VACrange
TransientProtection 2.5kVsurgewithstandcapabilityasperANSI/IEEEC37.90.1-1989
Isolation • Isolatedin4groupsof8.Inputs0-15areonthebottomedge.• Inputs16-31areonthetopedge.Isolation500VAC/DCfromchassisandlogicground
PowerRequirements 5V@10mAwithallinputsON
Terminations 4:9pole,removableterminalblocks,12to22AWG,15Acontacts
Dimensions 144mmwidex127mmhighx45mmdeep(5.65in.x5.00in.x1.88in.)
Packaging Corrosionresistantzincplatedsteelwithblackenamelpaint
Environment 5%RHto95%RH,non-condensing,-40°Cto60°C(-40°Fto140°F)
Addressing Configurablewith4DIPswitches
AC/DCOperation 2:DIPswitchesdetermineAC/DCand50/60Hzoperation
VisualIndicators 32:RedLED’s,fieldpowered.Cannotbedisabledtoconservepower
Safety cCSAusandcULusClassI,Division2HazardousAreaRating,UL508listed
Model Part Number Description
5405-120 TBUX297249 32point,120Vdiscreteinputmodule
5405-24 TBUX297247 32point,12-24Vdiscreteinputmodule
Disclaimer:SchneiderElectricreservestherighttochangeproductspecifications.Formoreinformationvisitwww.schneider-electric.com.
27
Product Data Sheet 5414 – Compact digital input moduleSpecifications
5414 Compact digital input module
General
NumberofDigitalInputs 16
Ranges Factoryconfigurableas:• 12/24V• 48V• 115/125V• 240V
InputCurrent • 0.6–0.9mAat24Vonthe12/24Vrange• 0.3–0.4mAat48Vonthe48Vrange• 0.3–0.4mAat120Vonthe115/125Vrange• 0.3–0.4mAat240Vonthe240Vrange
Over-voltageTolerance 150%sustainedover-voltagewithoutdamage
PowerRequirements • 5V@6mAwithLEDsoff• 5V@40mAwithLEDson
VisualIndicators LogicpoweredLEDs.Canbedisabledtoconservepower
FieldTerminations 12to22AWG,15Acontacts
Dimensions 74mmwidex124mmhighx45mmdeep(2.90in.x4.90in.x1.80in.)
Mounting 7.5x35DINrail
Packaging Corrosionresistantzincplatedsteelwithblackenamelpaint
Environment • 5%RHto95%RH,non-condensing• –40ºCto70ºC(–40ºFto158ºF)operation• –40ºCto85ºC(–40ºFto185ºF)storage
Safety • ClassI,Division2,GroupsA,B,CandDandCSAcertifiedtoUL508standards• ATEXII3GandIECEx:ExnAIICT4perEN60079-15,protectiontypen(Zone2)(5414-24only)• MaximumpermittedvoltageinCanadaorNorthAmericais240VAC• MaximumpermittedvoltageoutsideofCanadaorNorthAmericais30VAC/42.4PK/60VDC
Model Part Number Signal Range
5414-24 TBUX297378 12/24VAC/DC,ATEXandIECEx
5414-48 TBUX297379 48VAC/DC(NotavailableoutsideofNorthAmerica)
5414-120 TBUX297380 115/125VAC/DC(NotavailableoutsideofNorthAmerica)
5414-240 TBUX297381 240VAC/DC(NotavailableoutsideofNorthAmerica)
Note:Modulenotsupportedon16-bitSCADAPackplatform(SCADAPack,SCADAPackLight,SCADAPackPlus,SCADAPack100andSCADAPackLP)
Disclaimer:SchneiderElectricreservestherighttochangeproductspecifications.Formoreinformationvisitwww.schneider-electric.com.
28
Product Data Sheet 5411 – Digital output moduleSpecifications
5411 Digital output module
General
OutputPoints 32
OutputRating • 1.0Amaximum• 0.35Vmaximumdropat1.0A• 0.05Vmaximumdropat0.1A
TransientProtection • 2.5kVsurgewithstandcapabilityasperANSI/IEEEC37.90.1-1989• Inductiveloadprotectiondiodesincluded
Isolation • Isolatedin2groupsof16• Isolation500VAC/DCfromchassisandlogicground
Terminations • 2:9andtwo10pole,removableterminalblocks• 12to22AWG,15Acontacts
PowerRequirements • 5V@150mAwithallLEDsandoutputsturnedon• 5V@40mAwithallLEDsdisabledandalloutputsturnedon• 24V@5mAwithalloutputsON• 8Vmin.,30Vmax
VisualIndicators 32:RedLED’s,canbedisabledtoconservepower
Dimensions 144mmwidex127mmhighx45mmdeep(5.65in.x5.00in.x1.80in.)
Mounting 7.5x35DINrail
Packaging Corrosionresistantzincplatedsteelwithblackenamelpaint
Environment 5%RHto95%RH,non-condensing,-40°Cto70°C(-40°Fto158°F)
Safety cCSAusandcULusClassI,Division2HazardousAreaRating,UL508listed
PartNumber TBUX297246
Disclaimer:SchneiderElectricreservestherighttochangeproductspecifications.Formoreinformationvisitwww.schneider-electric.com.
29
Product Data Sheet 5415 – Compact relay digital output moduleSpecifications
5415 Compact relay digital output module
General
NumberofDigitalOutputs 12
Type • FormAContacts(Normallyopen),DryContactorSolidStateRelayvariants• 4contactspercommon
ContactRating • 12Amaximumpercommon• DryContactVersion:3A,30VDCor250VAC(Resistive)• SolidStateRelayVersion:60VDCmax.,3Amax.at50°C(122°F),2Amax.at70°C(158°F)
SwitchingCapacity(DryContactVersion)
• 5A,30VDC(150WResistive)• 5AX250VAC(1250VAResistive)
5VPowerRequirements 5mAQuiescentDryContactversion: 150mArelayson,LEDson 130mArelayson,LEDsoff Peakcurrentduringoff-to-ontransitionofany,orallrelays- 280mAtotalfor15msdurationSolidStateRelayversion: Relayson,LEDson-144mA Relayson,LEDsoff-120mA
10-30VDCPowerRequirements
DryContactversion: 1.0Wmaximumwith1.65Wpeakfor15msdurationsSolidStateRelayversion: 1.0Wmaximum
VisualIndicators LogicpoweredLEDs.Canbedisabledtoconservepower
FieldTerminations 12to22AWG,15Acontacts
Dimensions 74mmwidex124mmhighx45mmdeep(2.90in.x4.90in.x1.80in.)
Mounting 7.5x35DINrail
Packaging Corrosionresistantzincplatedsteelwithblackenamelpaint
Environment • 5%RHto95%RH,non-condensing• –40ºCto70ºC(–40ºFto158ºF)operation• –40ºCto85ºC(–40ºFto185ºF)storage
Safety • ClassI,Division2,GroupsA,B,CandDandCSAcertifiedtoUL508standards• ATEXII3GandIECEx:ExnAIICT4perEN60079-15,protectiontypen(Zone2)(5415-Aonly)• MaximumpermittedvoltageinCanadaorNorthAmericais240VAC• MaximumpermittedvoltageoutsideofCanadaorNorthAmericais30VAC/42.4PK/60VDC
Model Part Number Signal Range
5415 TBUX297382 12PointCompactMechanicalRelayOutputModule
5415-A TBUX297384 12PointCompactSolid-StateRelayOutputModule,ATEXandIECEx
Note:Modulenotsupportedon16-bitSCADAPackplatform(SCADAPack,SCADAPackLight,SCADAPackPlus,SCADAPack100andSCADAPackLP)
Disclaimer:SchneiderElectricreservestherighttochangeproductspecifications.Formoreinformationvisitwww.schneider-electric.com.
30
Product Data Sheet 5606 – Analog/digital I/O moduleSpecifications
5606 Analog/digital I/O module
General
DigitalInputPoints • 32• Factoryconfigurable:12/24V,48V,115/125V,240V• 150%sustainedover-voltagewithoutdamage
DigitalOutputPoints • 16• FormA(Normallyopen)relaycontacts• Rating:3A,30Vdcor240Vac(Resistive)• 4contactspercommon
AnalogInputPoints • 8• Single-ended• Softwareconfigurable,0-20mA,4-20mA,0-10V,0-5V• Resolution:15-bitoverthe0-10Vand0-20mAmeasurementrange• Accuracy:±0.1%offullscaleat25°C(77°F),±0.2%overtemperaturerange
AnalogOutputs • 2(withoptional5305module)• 0-20mAsourcing• Resolution:12-bit• Accuracy:(specifiedfrom0.5-20mA.),±0.15%offullscaleat25°C(77°F)• ±0.25%offullscaleovertemperaturerange
5VPowerRequirements • DigitalOutputRelaysContinuous-190mA,DigitalOutputRelaysPeak-375mA• LED’s-195mA,Quiescent-30mA• Total-415to600mA
11-30VDCPowerRequirements • 12mAplusanalogoutputs• 9-30Vdcoperationpossiblewhenoptional5305analogoutputsnotinstalled
Addressing 8modules,DIPswitch-selectable
Dimensions 213mmwidex155mmhighx72mmdeep(8.40in.x6.13in.x1.80in.)
Mounting 7.5x35DINrail
Packaging Corrosion-resistantzinc-platedsteelwithblackenamelpaint
Environment 5%RHto95%RH,non-condensing,–40°Cto70°C(–40°Fto158°F)
Safety cCSAusandcULusClassI,Division2HazardousAreaRating,UL508listedATEXII3GandIECEx:ExnAIICT4perEN60079-15,protectiontypen(Zone2),(24VDI/SolidStateRelaytypeonly)
PartNumber TBUX297328 (5606-24)TBUX297329 (5606-48)TBUX297330 (5606-120)TBUX297331 (5606-240)TBUX297334 (5606-24-AO)TBUX297335 (5606-48-AO)TBUX297336 (5606-120-AO)TBUX297337 (5606-240-AO)TBUX297498 (5606-24-A)TBUX297499 (5606-48-A)TBUX297500 (5606-120-A)TBUX297501 (5606-240-A)TBUX297502 (5606-24-AO-A)TBUX297503 (5606-48-AO-A)TBUX297504 (5606-120-AO-A)TBUX297505 (5606-240-AO-A)
Disclaimer:SchneiderElectricreservestherighttochangeproductspecifications.Formoreinformationvisitwww.schneider-electric.com.
31
Product Data Sheet 5607 – Analog/digital I/O moduleSpecifications
5607 Analog/digital I/O module
General
DigitalInputPoints • 16• Factoryconfigurable:12/24V,48V,115/125V,240V• 150%sustainedover-voltagewithoutdamage
DigitalOutputPoints
ContactRataing
• 10• FormAContacts(Normallyopen)• DryContactRelayorDCSolidStateRelay• 5contactspercommonDryContactRelayVersion:• 3A,30Vdcor250Vac(Resistive)DCSolidStateRelayVersion:• 3Acontinuousmaximumat50ºC(122ºF)ambientTBC• 2Acontinuousmaximumat70ºC(158ºF)ambientTBC• 9Apeak,100ms
AnalogInputPoints • 8• Single-ended• Softwareconfigurable,0-20mA,4-20mA,0-10V,0-5V• Resolution:15bitsoverthe0-10Vmeasurementrange,14bitsoverthe0-5Vand0-20mAmeasurementrange• Accuracy:±0.1%offullscaleat25°C(77°F),±0.2%overtemperaturerange
AnalogOutputs • 2(withoptional5305module)• 0-20mAsourcing• Resolution:12-bit• Accuracy:(specifiedfrom0.5-20mA.),±0.15%offullscaleat25°C(77°F)• ±0.25%offullscaleovertemperaturerange
5VPowerRequirements DryContactRelayversion:• DigitalOutputRelaysContinuous-105mAplus90mAtransients(15ms)whenrelaysswitchon.• LEDs-107mA• Quiescent-23mA• Total-upto235mASolidStateRelayversion:• DigitalOutputRelaysContinuous-100mA• LEDs-110mA• Quiescent-23mA• Total-upto233mA
11-30VDCPowerRequirements • 10.3mAplusanalogoutputs• 9-30Vdcoperationpossiblewhenoptional5305analogoutputsnotinstalled
Addressing 8modules,DIPswitch-selectable
Dimensions 144mmwidex165mmhighx72mmdeep(5.65in.x6.50in.x1.80in.)
Mounting 7.5x35DINrail
Packaging Corrosion-resistantzinc-platedsteelwithblackenamelpaint
Environment 5%RHto95%RH,non-condensing,–40°Cto70°C(–40°Fto158°F)
Safety • ClassI,Division2GroupsA,B,CandDHazardousLocationsandCSAcertifiedtoUL508standards• ATEXII3GandIECEx:ExnAIICT4perEN60079-15,protectiontypen(Zone2),(24VDI/SolidStateRelaytypeonly)
PartNumber TBUX297478 (5607-24)TBUX297479 (5607-48)TBUX297480 (5607-120)TBUX297481 (5607-240)TBUX297482 (5607-24-AO)TBUX297483 (5607-48-AO)TBUX297484 (5607-120-AO)TBUX297485 (5607-240-AO)TBUX297490 (5607-24-A)TBUX297491 (5607-48-A)TBUX297492 (5607-120-A)TBUX297493 (5607-240-A)TBUX297494 (5607-24-AO-A)TBUX297495 (5607-48-AO-A)TBUX297496 (5607-120-AO-A)TBUX297497 (5607-240-AO-A)
Note:5607moduleisnotsupportedbytheSCADAPack100andSCADAPackER.
Disclaimer:SchneiderElectricreservestherighttochangeproductspecifications.Formoreinformationvisitwww.schneider-electric.com.
32
Product Data Sheet 5608Specifications
5608 Digital I/O module
General
DigitalInputPoints • 12• 12-24V• 150%sustainedover-voltagewithoutdamage
DigitalOutputPoints
ContactRating
• 6• FormAContacts(Normallyopen)• DryContactRelay• 5contactspercommon• 3A,30Vdcor250Vac(Resistive)
5VPowerRequirements • DigitalOutputRelaysContinuous-105mAplus90mAtransients(15ms)whenrelaysswitchon.• LEDs-107mA• Quiescent-23mA• Total-upto235mA
11-30VDCPowerRequirements • 10.3mA• 9-30Vdcoperationpossible
Addressing 8modules,DIPswitch-selectable
Dimensions 144mmwidex165mmhighx72mmdeep(5.65in.x6.50in.x1.80in.)
Mounting 7.5x35DINrail
Packaging Corrosion-resistantzinc-platedsteelwithblackenamelpaint
Environment 5%RHto95%RH,non-condensing,–25°Cto70°C(–13°Fto158°F)
Certifications • CEmarking• C-Tick• UL508(US/Canada)–cULus• FCC/EN61000-6emissions&immunity
PartNumber TBUX297177 (5608-24)
33
Product Data Sheet 5610Specifications
5610 Digital I/O module
General
DigitalInputPoints • 16• 12-24V• 150%sustainedover-voltagewithoutdamage
DigitalOutputPoints
ContactRating
• 10• FormAContacts(Normallyopen)• DryContactRelay• 5contactspercommon• 3A,30Vdcor250Vac(Resistive)
5VPowerRequirements • DigitalOutputRelaysContinuous-105mAplus90mAtransients(15ms)whenrelaysswitchon.• LEDs-107mA• Quiescent-23mA• Total-upto235mA
11-30VDCPowerRequirements • 10.3mA• 9-30Vdcoperationpossible
Addressing 8modules,DIPswitch-selectable
Dimensions 144mmwidex165mmhighx72mmdeep(5.65in.x6.50in.x1.80in.)
Mounting 7.5x35DINrail
Packaging Corrosion-resistantzinc-platedsteelwithblackenamelpaint
Environment 5%RHto95%RH,non-condensing,–25°Cto70°C(–13°Fto158°F)
Certifications • CEmarking• C-Tick• UL508(US/Canada)–cULus• FCC/EN61000-6emissions&immunity
PartNumber TBUX297178 (5610-24)
Note:The5608and5610modulesareforusewithSCADAPackERTUsonly.Disclaimer:SchneiderElectricreservestherighttochangeproductspecifications.Formoreinformationvisitwww.schneider-electric.com.
34
Product Data Sheet 5103 – Uninterruptible power supplySpecifications
5103 Uninterruptible power supply
General
AC/DCInput • 16to24VACfor5/24Voutputsoperational,24VACrequiredforbatterycharging• 14.5+/-0.5Vfor5/24Voutputsoperational,20VDCrequiredforbatterycharging
DC/BatteryInput Turnonat11.5V±0.3VDC,Turnoffat10.5V±0.5VDC,Maximuminputis36VDC
InputPower 35VAmaximumat24VAC,1.9Aat13.5VDC
Outputs 5VDCat2.0ampere,24VDCat0.5ampere,17Wtotalavailablefromthetwooutputs11to14VDCbatterychargerat200mA(factoryadjustedto13.5Vforgelledelectrolytelead/acidbattery)
Mode Isolatedswitch-mode,30KHzswitchfrequency
LineRegulation <1%overoperatingrange
LoadRegulation • 5Voutput:5.15V±1%overoperatingrange• 24Voutput:±17%
OutputRipple • 5Voutput:<10mVat20oC(68oF)
• 24Voutput:<50mVat20oC(68oF)
VisualIndicators 5Vand24VgreenLEDsshowpowerstatus
PowerRequirements 35VAmaximum@24VAC,[email protected]
Terminations 10pole,removableterminalblock,12to22AWG,15ampcontacts
Dimensions 108mmwidex118mmhighx44mmdeep(4.25in.x4.625in.x1.75in.)
Mounting 7.5x35DINrail
Packaging Corrosionresistantzincplatedsteelwithblackenamelpaint
Environment • 5%RHto95%RH,non-condensing• -40°Cto60°C(-40°Fto140°F)
Safety Non-IncendiveElectricalEquipmentforUseinClassI,Division2GroupsA,B,CandDHazardousLocations.TemperatureCodeT4at60°Cambient.ULListedtothefollowingstandards:• CSAStd.C22.2No.213-M1987-HazardousLocations.• CSAStd.C22.2No.142-M1987-ProcessControlEquipment.• ULStd.No.1604-Hazardous(Classified)Locations.• ULStd.No.508-IndustrialControlEquipment.
PartNumber TBUX297102
Accessories
Model Part Number Description
1206 TBUX294034 12V6AHgelledelectrolytebattery
ACX-24 TBUX294000 120/24VAC,40VAtransformer
ACX-24E TBUX294167 220/24VAC,40VAtransformer
Disclaimer:SchneiderElectricreservestherighttochangeproductspecifications.Formoreinformationvisitwww.schneider-electric.com.
35
Product Data Sheet 5902 – Bell 202 modemSpecifications
5902 Bell 202 modem
General
DataRate 1200baud
TransmitCarrier Switchedorconstant
Duplex Fullorhalf.HalfduplexrequiresDTEtoimplementhardwareRTS/CTShandshake
Wires Twoorfour
TransmitLevel -35dBmto0dBminto600Ω,potentiometeradjustable
ReceiveSensitivity -30dBmto+3dBm,potentiometeradjustableto-40dBm
OutputandInputImpedance 600Ωbalanced,transformerisolated
Anti-Streaming None,10Sec,30Sec,60Sec
RTS/CTSDelay • Wire:25ms,50ms,125ms,250ms• Radio:67ms,133ms,266ms,1000ms
CTSHoldTime 1ms,8ms
CarrierDetectDelay • Wire:19ms,30ms,51ms,92ms• Radio:33ms,67ms,133ms,265ms
CarrierLossDelay 6ms,10ms,23ms,39ms,constantcarrierreceptionhalfduplex
CarrierDetectLevel -30dBm,adjustablefrom-20dBmto-40dBm
RadioTransmitKeyOutput Opticalcoupleropencollectortransistor,5to15VDC,25mA
VisualIndicators TransmittedDataLED,ReceivedDataLED,CleartoSendLED,RequesttoSendLED,CarrierDetectLED,RadioKeyOutputLED
PowerRequirements • 5902-5V@60mA• 5902SA-115VACat10VA
Terminations 8pole,removableterminalblock,RJ45
Dimensions 4.25inch(108mm)wide,4.625inch(118mm)high,1.75inch(44mm)deep
Packaging Corrosion-resistantzinc-platedsteelwithblackenamelpaint
Environment 5%RHto95%RH,non-condensing,-40°C/Fto60°C/140°F
Safety cCSAusandcULusClassI,Division2HazardousAreaRating,UL508listed
Model Part Number Description
5902 TBUX297120 Bell202modemmodule,1200baud,FSK,2/4wire,withradioPTTkeycontrol&RFcarrierdetect
5902SA TBUX297194 Sameas5902butwitha115VACADadapterforconnectiontootherPC’sorRS-232devices
5902SAF TBUX297195 Sameas5902SAbutwithafullduplextohalfduplexconverter-fordeviceswithoutRTS/CTSsupport
Note:Serialcommunicationcablesoldseparately
Disclaimer:SchneiderElectricreservestherighttochangeproductspecifications.Formoreinformationvisitwww.schneider-electric.com.
36
Product Data Sheet 5908 – Wireless data transceiverSpecifications
5908 Wireless data transceiver
General
Frequency 902to928MHz,230kHzbandwidth
Transmitter
OutputPower 1mWto1W(+30dBm)
Range 60miles(Lineofsightwithunitygainantenna)
Modulation SpreadSpectrumGFSK,120kBs-170kBs
SpreadingMethod Frequencyhopping
Receiver
Sensitivity -108dBmfor10-6BERstandardspeed,-111dBmfor10-6BERlowspeed-110dBmfor10-4BERstandardspeed,-113dBmfor10-4BERlowspeed
Selectivity 20dBatfc±115kHz,60dBatfc±145kHz
SystemGain 140dB
Data Transmission
ErrorDetection 32BitCRC,resendonerror
ForwardErrorCorrection(lowspeed)
(24,12)Golay,retransmitonuncorrectableerror
DataEncryption Substitution,dynamickey
MaxLinkThroughput 115Kbaudstandardspeed,38.4Kbaudlowspeed
DataInterface RS-232/RS-4851200baudto230.4Kbaud,asynch,fullduplex,RJ45connector
Power Requirements
SupplyVoltage 7to30VDC(900MHzmodel)10to30UDC(2.46GHzmodel)5908 5908-2.4GmA@12VDC mA@30VDC mA@12VDC mA@30VDC
Transmit 500 200 325 150
Receive 86 43 115 60
Idle 21 12 30 13
Sleep 6 3 5 2
OperatingModes Point-to-Point,Point-to-Multipoint,Peer-to-Peer,StoreandForwardRepeater
OperatingEnvironment -40°C/Fto75°C/167°F,0to95%humiditynon-condensing
Model Part Number Description
5908 TBUX297270 RadioTransceiver,FreeWave900MHzSpreadSpectrum,poweredby6-30VoltsDC
5908-2.4G* TBUX297283 RadioTransceiver,FreeWave2.4GHzSpreadSpectrum,poweredby6-30VoltsDC
Note:Serialcommunicationcablesoldseparately
*Notavailableinallareas–ConsultSchneiderElectricforavailabilityinyourarea
Disclaimer:SchneiderElectricreservestherighttochangeproductspecifications.Formoreinformationvisitwww.schneider-electric.com.
37
Product Data Sheet 5908-WO2 – Wireless data transceiverSpecifications
5908-WO2 Wireless data transceiver
General
Frequency Upto128frequencieswithin902-928MHz.,configurablein3.2MHzzones
Transmitter
OutputPower 1.0W(+30dBm)maximum(atantennaconnector)
Modulation CPFSK
SpreadingMethod Frequencyhoppingbasedonnetworkaddress
Receiver
Type Doubleconversionsuperheterodyne
Sensitivity -108dBm@1X10-6BER
NetworkAddresses 65,000
Data Transmission
ErrorDetection CRC16;Resendonerror
DataInterface RS-232/RS-485(userselectable)
MaxLinkThroughput Continuousupto115.2kbps
BaudRates 1.2to115.2kbps
Power Requirements
Power 7.5Wmax
SupplyVoltage 9to30VDC
TransmitCurrent [email protected]
ReceiveCurrent [email protected]
SleepModeCurrent [email protected]
OperatingModes Point-to-Point,Point-to-Multipoint,Store-and-ForwardRepeater
OperatingEnvironment -40°C/Fto70°C/158°F,5%RHto95%RH,non-condensing
Model Part Number Description
5908-WO2 TBUX297310 RadioTransceiver,MDS900MHzSpreadSpectrum,poweredby9-30VoltsCD
Note:Serialcommunicationcablesoldseparately
Disclaimer:SchneiderElectricreservestherighttochangeproductspecifications.Formoreinformationvisitwww.schneider-electric.com.
38
Product Data Sheet 5910 – Ethernet switchSpecifications
5910 Ethernet switch
General
EthernetSwitchType 5ports,unmanaged,store&forward,10/100BaseT
EthernetTerminations RJ45ports(shielded)
Protocols IEEE802.3,IEEE802.3u(TBC),IEEE802.3x
SpeedandConnection • Auto-detecting10/100Mbpsoperation,• AutoMDI/MDI-Xoperation(noneedforcross-wiredcables)
MemoryBandwidth 1.4Gbps
DuplexOperation FullduplexIEEE802.3xandhalfduplexbackpressureflowcontrol
MACAddressing Dedicatedlookupenginewith1KMACaddresses.Learning,agingandmigration
EthernetIsolation 1500Vrms
VisualIndicators Eachporthas-ACT/LINKand10/100(Speed)indicators
InputPower • ExternalPower:11-30Vdc• 1.8Wat12Vdc• 2.2Wat30Vdc• BusPower:5Vat375mA
InputPowerTerminations • 4poleterminalstripandremovableterminalblock.• 12to22AWG
Dimensions .25inch(144mm)wide,4.625inch(118mm)high,2.00inch(51mm)deep
Mounting Desktop,rubberfeetor7.5x35DINrail
Packaging Corrosionresistantzincplatedsteelwithblackenamelpaint
Environment 5%RHto95%RH,non-condensing–40oCto70oC–40oFto158oF
Model Part Number Description
5910 TBUX297288 EthernetSwitch,5port,10/100Mbautodetect,12-24Vdcpower
5910SA TBUX297289 Sameas5910,withtheadditionofa115Vacadapter
Disclaimer:SchneiderElectricreservestherighttochangeproductspecifications.Formoreinformationvisitwww.schneider-electric.com.
39
Product Data Sheet 5915 – SDI-12 interface moduleSpecifications
5915 SDI-12 interface module
General
SDI-12busTerminations • 12to22AWG• 15Acontacts
Dimensions 2.90inch(74mm)wide,4.90inch(124mm)high,1.80inch(45mm)deep
Packaging Corrosionresistantzincplatedsteelwithblackenamelpaint
Environment • 5%RHto95%RH,non-condensing• –40oCto70oC(–40oFto158oF)operation• –40oCto85oC(–40oFto185oF)storage
Addressing Nonerequired
Power Requirements
12V • 6mAIdle• 6.5mAactive,withLEDsdisabled• 24mAactive,continuoustransmit,bothLEDson
Communications – Port P1
PortType RS-232compatibleserialport
Connector 8pinmodularjack(RJ45)
PinsUsed Transmit,ReceiveandGround
Connection DTE
Protocol SDI-12only
Baud 1200bps(asperSDI-12protocol)
Bits 7(asperSDI-12protocol)
Parity Even(asperSDI-12protocol)
HardwareHandshaking None
Protection 15kVESDprotected
Communications – Port P2
PortType SDI-12port
Connector 4-wayremovableterminalblock
PinsUsed 12V,Ground,SDI-12data
Protocol SDI-12only
Protection MOVandcurrent-limit
Indicators
Tx IlluminateswhentransmittingdatafromMasterControllertoaslavedeviceonthebus
Rx IlluminateswhenreceivingdatafromaslavedeviceANDwhenevertheMasterControllertransmits.
Model Part Number Description
5915 TBUX297475 SDI-12Module,serialtoSDI-12converterforSCADAPack32andSCADAPack3xx-Series controllers,c/wconfig.CD
Disclaimer:SchneiderElectricreservestherighttochangeproductspecifications.Formoreinformationvisitwww.schneider-electric.com.
Schneider Electric
Telemetry & Remote SCADA Solutions48 Steacie DriveKanata, ON, K2K 2A9, CanadaPhone: +1 (613) 591-1943Fax: +1 (613) 591-1022www.schneider-electric.com
Document Number TBUL00001-15 December 2012
© 2
012
Sch
neid
er E
lect
ric. A
ll rig
hts
rese
rved
.
Make the most of your energy
SCADAPack E