i technical specification datasheet - amazon web...

41
i Technical Specification Datasheet SCADAPack E Smart RTU Compact, versatile controller for telemetry and remote SCADA solutions

Upload: phamliem

Post on 28-Apr-2018

241 views

Category:

Documents


2 download

TRANSCRIPT

i

Technical Specification DatasheetSCADAPack E Smart RTUCompact, versatile controller for telemetry and remote SCADA solutions

1

SCADAPackSmart RTUs that combine the monitoring and communications capabilities of remote terminal units (RTU) with the processing and data-logging power of programmable logic controllers (PLC), providing superior functionality wherever remote processes require automatic supervision and autonomous control.

SCADAPack E Smart RTUs are the foundation for a range of solutions offering specific software and configuration tools to enhance performance in oil and gas and water/wastewater applications.

2

Selection Guide

• For SCADA fitted with IEC 60870-5-101/104, DNP3 or Modbus protocols • Master protocols supported: DNP3, Modbus, IEC 60870-5-103 or DF1 • IEC61131-3 programming languages • DNP3 Secure Authentication and IEEE 1711 (AGA12) Encryption for DNP3

SCADAPack 300E & SCADAPack ES

312E 313E 314E 330E 333E 334E 337E 350E 357E ES

Analog Inputs1

0-20mA, 4-20mA, 0-5V, 0-10V 4 4 8 – 4 8 8 – 8 –

0-10V/0-40mA,0-5V/0-20mA, 1-5V/4-20mA

– – – – – – – 5 5 –

1-5V/4-20mA – – – – – – – – – 6 or 12

0-32.7V – – – – – – – 1 1 –

Analog Outputs1

4-20mA – – – – – – – – – 2 or 4

0-20mA/4-20mA – 2 – 2 2 or 4 –

Digital Inputs1

12/24V 12 16 – – 16 – 32 – – –

12/24/48/115/125/240V – – 16 – – 16 – – 32 –

10-30V – – – – – – – – – 16 or 32

dry contact, shared with output points – – – – – – – 8 8 –

Digital Outputs1

dry contact 6 10 – – 10 – 16 – 16 –

dry contact or solid state – – 10 – – 10 – – – –

open drain, share with input points – – – – – – – 8 8 –

DPDT Relay, (NO/Common/NC) – – – – – – – – – 8 or 16

Counter Inputs1

0-10Hz – – – – – – – 1 –

0-10Hz/-05kHz (dry contact) 1 – – –

0-10kHz (turbine inputs) 2 –

0-1kHz, shared with Digital Inputs – – – – – – – – – 4

Communication and Configuration Ports

Serial port - RS232 – – – 1 3

Serial port - RS485 – – – – – – – 1 –

Serial port - RS232/ 485 2 1 –

Serial ports - RS232/422/ 485 – – – – – – – – – 2

USB ports 1 –

Ethernet ports (10/100BaseT) – – – 1 2

Logic control

IEC61131 Programming languages option Yes option Yes

Protocols

Modbus slave, IEC60870-5 slave, DNP3 slave, PPP, ftp, DNP3 master

Yes

Modbus master option Yes option Yes

DF1 master option Yes option Yes

IEC 60870-103 master – – Yes – Yes – Yes

DNP3 Secure Authentication option

AGA-12 Encryption for DNP3 protocol2 option

(1) The amount of I/O may be expanded for any SCADAPack E using Expansion I/O modules (refer to individual product data sheets for detailed specifications)(2) Subject to export restrictions, please contact your TRSS business development representative for more details

3

Contents

SCADAPack E Smart RTU SCADAPack 312E Specifications ......................................................................................... 4 Model Code ........................................................................................... 5

SCADAPack 313E Specifications ......................................................................................... 6 Model Code ........................................................................................... 7

SCADAPack 314E Specifications ......................................................................................... 8 Model Code ........................................................................................... 9

SCADAPack 330E | 334E Specifications 330E .............................................................................. 10 Specifications 334E .............................................................................. 11 Model Code ......................................................................................... 12

SCADAPack 333E Specifications ....................................................................................... 13 Model Code ......................................................................................... 14

SCADAPack 337E Specifications ....................................................................................... 15 Model Code ......................................................................................... 16

SCADAPack 350E | 357E Specifications 350E .............................................................................. 17 Specifications 357E .............................................................................. 18 Model Code ......................................................................................... 19

SCADAPack ES Specifications ES ................................................................................. 20 Model Code ......................................................................................... 22

I/O Expansion Modules

Analog Input Modules 5505 - RTD input module ..................................................................... 23 5506 - Analog input module ................................................................. 24

Analog Output Modules 5304 - Analog output module ............................................................... 25

Digital Input Modules 5405 - Digital input module .................................................................. 26 5414 - Compact digital input module ................................................... 27

Digital Output Modules 5411 - Digital output module ................................................................ 28 5415 - Compact relay digital output module ......................................... 29

Combination I/O Modules 5606 - Analog/digital I/O module .......................................................... 30 5607 - Analog/digital I/O module .......................................................... 31 5608 - Analog/digital I/O module ...........................................................32 5610 - Analog/digital I/O module ...........................................................33

UPS Power Supply 5103 - Uninterruptible Power Supply .................................................... 34

Communication Modules

Modems, Interface Modules & Gateways 5902 - Bell 202 radio or leased line modem ......................................... 35 5908 - Wireless data transceiver .......................................................... 36 5908 - W02 - Wireless data transceiver ................................................ 37 5910 - Ethernet switch ......................................................................... 38 5915 - SDI-12 interface module ........................................................... 39

4

312E: 5212 controller board and integrated 5609 I/O board

Controller

Processors • CPU:32-bitARM7microcontroller,32MHzclock,integratedwatchdogtimer• Microcontrollerco-processor,20MHzclock

Memory 16MBFLASHROM,4MBCMOSRAM,4kBEEPROM

Non-VolatileRAM CMOSSRAMwithlithiumbatteryretainscontentsfor2yearswithnopower

EventLoggingCapacity 20,000events

MaximumDatabasePoints 1,000typical

I/O

AnalogInputs • 4softwareconfigurable:0-20/4-20mA/0-5/0-10V(15-bit)• 3internal:measureincomingpowersupplyvoltageforsolarapplications,batteryvoltage,andcontrollertemperature

AnalogOutputs None

DigitalI/O • 12digitalinputs:12/24V• 6relayoutputs:drycontact,drycontactrating:3A,30VDCor240VAC(resistive)

CounterInputs • 1drycontact:0-10Hzor0-5kHz• 2turbineordrycontact:0-10kHz

Communications

SerialPortsCOM1,COM2 • RS-232port,8-pinmodularRJ45jack,fullorhalf-duplex,or• RS-485port,2-wire,half-duplex

BaudRates 300,600,1200,2400,4800,9600,19200,38400,57600,and115200

SerialProtocols DNP3Slave/Master,IEC60870-5-101Slave,ModbusRTUSlave,optionalModbusMasterandDF1Master

IPProtocols (overserialport)DNP3master/slave,IEC60870-5-101/104slave,ModbusRTUslave,NTPServer,TelnetServer,FTPServer

USBPort USB2.0compliantB-typereceptacle,DNP3protocol

Wireless Externalmodem(e.g.SchneiderElectricGPRSmodemref.SR2MOD3)

General

LogicControl OptionalIEC61131-3SCADAPackWorkbenchprogrammingsuite(LD,ST,FBD&SFC)

I/OTerminations 5,6,and9-poleremovableterminalblocks,12to22AWG,15Acontacts

Dimensions 5.65inch(144mm)wide,6.50inch(165mm)high,2.80inch(72mm)deep

Packaging Corrosionresistant,zinc-platedsteelwithblackenamelpaint

Environment 5%RHto95%,non-condensing,–25°C(–13°F)to70°C(158°F)

Power

5212ControllerBoard • 11-30VDC,5.8Wtypical• Add30to90mWwhenenablingtheLEDs• 8.5Wat24Vmaximum,5Vsupplyfully-loaded

5609I/OModule • 11-30VDC,10.3mA• 235mA(max.)at5Vrequiredfrom5212controllerboard

Warranty 3yearsonpartsandlabor

Certifications

• CEmarking• C-Tick• UL508(US/Canada)–cULus• FCC/EN61000-6emissions&immunity

Disclaimer:SchneiderElectricreservestherighttochangeproductspecifications.Formoreinformationvisitwww.schneider-electric.com.

Product Data Sheet SCADAPack 312ESpecifications

5

TBUP312-EA54-AB00representsasamplecodeforaSCADAPack312Ewith12Vdry-contactrelayoutputsandnoIEC61131programmingoption.

Model Select: Controller

TBUP312 SCADAPack312E,32-Bitcontroller,4AnalogInputs,12DigitalInputs,6DigitalOutputs,3CounterInputs

Code Select: Platform

E EFirmwareplatform(SCADAPackEConfiguratorsoftwareincluded),executestwoIEC61131-3kernels(optional),Workbenchrequired

Code Select: SCADA Security

A None

B AGA-12EncryptionforDNP3

C DNP3SecureAuthenticationSAv2

D DNP3SecureAuthenticationwithAGA-12Encryption

Notes:• TheSecurityAdministratorApplicationhastobepurchasedtogenerateandmanagesecuritykeys.• AGA-12Encryptionissubjecttoexportrestrictions.PleaseconsultwithyourTRSSbusinessunitcontact.

Code Select: Protocol Option

5 DNP3Slave/Master,IEC60870-5-101Slave,ModbusRTUSlave

Code Select: License Option

4 Option1:withoutIEC61131,ModbusMasterandDF1Master

5 Option2:withIEC61131-3(executestwokernels,SCADAPackWorkbenchrequired),ModbusMasterandDF1Master

Notes:• BothoptionsincludeDNP3DataConcentratorlicense(limitof500pointsfrom10IEDs),MultipleDNP3MasterLicense(upto3Masters)

• Ifyouorderaproductwithoption1whichyoulaterwanttoupgradetooption2,youhavetoorderaRTUlicenceupdate(ref.TBUM297889)

Code Select: Analog Inputs

A 4

Code Select: Digital Inputs/Outputs

B 12inputsand6outputs

Code Select: Analog Outputs

0 None

Code Select: Future Option

0 None

Product Data Sheet SCADAPack 312EModel Code

6

313E: 5212 controller board and integrated 5611 I/O board

Controller

Processors • CPU:32-bitARM7microcontroller,32MHzclock,integratedwatchdogtimer• Microcontrollerco-processor,20MHzclock

Memory 16MBFLASHROM,4MBCMOSRAM,4kBEEPROM

Non-VolatileRAM CMOSSRAMwithlithiumbatteryretainscontentsfor2yearswithnopower

EventLoggingCapacity 20,000events

MaximumDatabasePoints 1,000typical

I/O

AnalogInputs • 4softwareconfigurable:0-20/4-20mA/0-5/0-10V(15-bit)• 3internal:measureincomingpowersupplyvoltageforsolarapplications,batteryvoltage,andcontrollertemperature

AnalogOutputs • Standard:None• 2,0-20/4-20mA(12-bit)withoptionalcardon5611I/Oboard

DigitalI/O • 16digitalinputs:12/24V• 10relayoutputs:drycontact,drycontactrating:3A,30VDCor240VAC(resistive)

CounterInputs • 1drycontact:0-10Hzor0-5kHz• 2turbineordrycontact:0-10kHz

Communications

SerialPortsCOM1,COM2 • RS-232port,8-pinmodularRJ45jack,fullorhalf-duplex,or• RS-485port,2-wire,half-duplex

BaudRates 300,600,1200,2400,4800,9600,19200,38400,57600,and115200

SerialProtocols DNP3Slave/Master,IEC60870-5-101Slave,ModbusRTUSlave,optionalModbusMasterandDF1Master

IPProtocols (overserialport)DNP3master/slave,IEC60870-5-101/104slave,ModbusRTUslave,NTPServer,TelnetServer,FTPServer

USBPort USB2.0compliantB-typereceptacle,DNP3protocol

Wireless Externalmodem(e.g.SchneiderElectricGPRSmodemref.SR2MOD3)

General

LogicControl OptionalIEC61131-3SCADAPackWorkbenchprogrammingsuite(LD,ST,FBD&SFC)

I/OTerminations 5,6,and9-poleremovableterminalblocks,12to22AWG,15Acontacts

Dimensions 5.65inch(144mm)wide,6.50inch(165mm)high,2.80inch(72mm)deep

Packaging Corrosionresistant,zinc-platedsteelwithblackenamelpaint

Environment 5%RHto95%,non-condensing,–25°C(–13°F)to70°C(158°F)

Power

5212ControllerBoard • 11-30VDC,5.8Wtypical• Add30to90mWwhenenablingtheLEDs• 8.5Wat24Vmaximum,5Vsupplyfully-loaded

5611I/OModule • 11-30VDC,10.3mAplusanalogoutputs• 235mA(max.)at5Vrequiredfrom5212controllerboard

Warranty 3yearsonpartsandlabor

Certifications

• CEmarking• C-Tick• UL508(US/Canada)–cULus• FCC/EN61000-6emissions&immunity

Disclaimer:SchneiderElectricreservestherighttochangeproductspecifications.Formoreinformationvisitwww.schneider-electric.com.

Product Data Sheet SCADAPack 313ESpecifications

7

TBUP313-EA54-AB00representsasamplecodeforaSCADAPack313Ewith12Vdry-contactrelayoutputsandnoIEC61131programmingoption.

Model Select: Controller

TBUP313E SCADAPack313E,32-Bitcontroller,4AnalogInputs,2optionalAnalogOutputs,16DigitalInputs,10DigitalOutputs,3CounterInputs

Code Select: Platform

E EFirmwareplatform(SCADAPackEConfiguratorsoftwareincluded),executestwoIEC61131-3kernels(optional),Workbenchrequired

Code Select: SCADA Security

A None

B AGA-12EncryptionforDNP3

C DNP3SecureAuthenticationSAv2

D DNP3SecureAuthenticationwithAGA-12Encryption

Notes:• TheSecurityAdministratorApplicationhastobepurchasedtogenerateandmanagesecuritykeys.• AGA-12Encryptionissubjecttoexportrestrictions.PleaseconsultwithyourTRSSbusinessunitcontact.

Code Select: Protocol Option

5 DNP3Slave/Master,IEC60870-5-101Slave,ModbusRTUSlave

Code Select: License Option

4 Option1:withoutIEC61131,ModbusMasterandDF1Master

5 Option2:withIEC61131-3(executestwokernels,SCADAPackWorkbenchrequired),ModbusMasterandDF1Master

Notes:• BothoptionsincludeDNP3DataConcentratorlicense(limitof500pointsfrom10IEDs),MultipleDNP3MasterLicense(upto3Masters)

• Ifyouorderaproductwithoption1andthatyoulaterwanttoupgradetooption2,youhavetoorderaRTUlicenceupdate(ref.TBUM297889)

Code Select: Analog Inputs

A 4

Code Select: Digital Inputs/Outputs

B 16inputsand10outputs

Code Select: Analog Outputs

0 None

1 2

Code Select: Future Option

0 None

Product Data Sheet SCADAPack 313EModel Code

8

P314E: 5212 controller board and integrated 56O7 I/O board

Controller

Processors • CPU:32-bitARM7microcontroller,32MHzclock,integratedwatchdogtimer• Microcontrollerco-processor,20MHzclock

Memory 16MBFLASHROM,4MBCMOSRAM,4kBEEPROM

Non-VolatileRAM CMOSSRAMwithlithiumbatteryretainscontentsfor2yearswithnopower

EventLoggingCapacity 20,000events

MaximumDatabasePoints 1,000typical

I/O

AnalogInputs • 8softwareconfigurable:0-20/4-20mA/0-5/0-10V(15-bit)• 3internal:measureincomingpowersupplyvoltageforsolarapplications,batteryvoltage,andcontrollertemperature

AnalogOutputs • Standard:None• 2withoptional5305on5607I/Oboard:0-20/4-20mA(12-bit)

DigitalI/O • 16digitalinputs:12/24V,48V,115/125V,240V• 10relayoutputs:drycontactorDCsolidstate,drycontactrating:3A,30VDCor240VAC(resistive),DCsolidstaterating:3A,60VDC

CounterInputs • 1drycontact:0-10Hzor0-5kHz• 2turbineordrycontact:0-10kHz

Communications

SerialPortsCOM1,COM2 • RS-232port,8-pinmodularRJ45jack,fullorhalf-duplex,or• RS-485port,2-wire,half-duplex

BaudRates 300,600,1200,2400,4800,9600,19200,38400,57600,and115200

SerialProtocols DNP3Slave,DNP3Master,IEC60870-5-101Slave,IEC60870-5-103Master,ModbusRTUMaster,ModbusRTUSlave,DF1

USBPeripheralPort USB2.0compliantB-typereceptacle,DNP3protocol

Wireless1 Spreadspectrumradioat900MHz2and2.4GHz2

General

I/OTerminations 5,6,and9-poleremovableterminalblocks,12to22AWG,15Acontacts

Dimensions 5.65inch(144mm)wide,6.50inch(165mm)high,2.80inch(72mm)deep

Packaging Corrosionresistant,zinc-platedsteelwithblackenamelpaint

Environment 5%RHto95%,non-condensing,–40°C(–40°F)to70°C(158°F)

Power

5212ControllerBoard • 11-30VDC,5.8Wtypical• Add30to90mWwhenenablingtheLEDs• 8.5Wat24Vmaximum,5Vsupplyfully-loaded

5607I/OModule • 11-30VDC,10.3mAplusanalogoutputs• 235mA(max.)at5Vrequiredfrom5212controllerboard

Warranty 3yearsonpartsandlabor

Certifications

HazardousLocationsNorthAmerica

SuitableforuseinClassI,Division2,GroupsA,B,CandDHazardousLocations.TemperatureCodeT4CSAcertifiedtotherequirementsof:• CSAStd.C22.2No.213-M1987-HazardousLocations• ULStd.No.1604-Hazardous(Classified)Locations

HazardousLocationsEurope

ATEXII3G,ExnAIICT4perEN60079-15,protectiontypen(Zone2).DoesnotincludeWirelessversions.

HazardousLocations IECEx,ExnAIICT4perIEC60079-15,protectiontypen(Zone2).DoesnotincludeWirelessversions.

1 Availableonlywithoptionalintegratedwirelessmodulesorwithstand-alonewirelessmodules.2 Notapplicableinallcountries.

Disclaimer:SchneiderElectricreservestherighttochangeproductspecifications.Formoreinformationvisitwww.schneider-electric.com.

Product Data Sheet SCADAPack 314ESpecifications

9

TBUP314-EA55-AB00representsasamplecodeforaSCADAPack314Ewith12Vdrycontactrelayoutputs

Model Select: Controller

TBUP314 SCADAPack314E,32Bitcontroller,8AnalogInputs,16DigitalInputs,10DigitalOutputs,3Accumulators

Code Select: Platform

E EFirmwareplatform(ConfigurationSoftwareincluded),executestwoIEC61131-3kernels,Workbenchrequired

Code Select: SCADA Security

A Authentication

B AuthenticationandAGA-12SCADAEncryptionSecurity

Code Select: Protocol Option

5 Modbus,DNP3,DF1,IEC60870-5-101Slave

6 AddsIEC60870-5-103Master,ProtectionRelayProtocol(fordatatransmissionwithIEDs)

Code Select: License Option

5 DNP3DataConcentratorLicense(limitof500pointsfrom10IEDs),supportsmultipleDNP3Masters(upto3Masters)

Code Select: Analog Inputs

A Adds8selectableas0-20mA,4-20mA,0-5Vor0-10V

Code Select: Digital Inputs/Outputs

B 16DigitalInputs(12/24V)and10DryContactRelayoutputs

D 16DigitalInputs(120V)and10DryContactRelayoutputs

F 16DigitalInputs(12/24V)and10SolidStateRelayoutputs,ATEXCertified(withnoIntegratedradio)

H 16DigitalInputs(120V)and10SolidStateRelayoutputs

Code Select: Analog Outputs

0 None

1 2channelanalogoutputoption,0-20mA

Code Select: Integrated Communication Interfaces

0 None

FreeWave & MDS Radios (requires one RS232 port)

1 900MhzFreeWaveSpreadSpectrumRadio

A 900MHzMDSSpreadSpectrumRadio

Trio Radios - 900MHz (requires one RS232 port)

B 900MHzTrioSpreadSpectrumRadiowithencryption,902-928MHz(FCC/IC)

C 900MHzTrioSpreadSpectrumRadiowithencryption,915-928MHz(AUS)

D 900MHzTrioSpreadSpectrumRadio,915-928MHz(BRAZIL)

E 900MHzTrioSpreadSpectrumRadio,921-928MHz(NZ)

Trio Radios - 2.4GHz (requires one RS232 port)

J 2.4GHzTrioSpreadSpectrumRadio,ETSI/100mW,ATEX(EUROPE)

K 2.4GHzTrioSpreadSpectrumRadiowithEncryption,500mW(CANADA,USA&AUSTRALIA)

L 2.4GHzTrioSpreadSpectrumRadio,500mW(OUTSIDEOFEUROPE,CANADA,USA&AUSTRALIA)

Product Data Sheet SCADAPack 314EModel Code

10

P330E: 5210 controller board only

Controller

Processors • CPU:32-bitARM7microcontroller,32MHzclock,integratedwatchdogtimer• Microcontrollerco-processor,20MHzclock

Memory 16MBFLASHROM,4MBCMOSRAM,4kBEEPROM

Non-VolatileRAM CMOSSRAMwithlithiumbatteryretainscontentsfor2yearswithnopower

EventLoggingCapacity 20,000events

MaximumDatabasePoints 1,000typical

I/O

CounterInputs • 1,0-10Hzor0-5kHz(drycontact)• 2,0-10kHz(turbineordrycontact)

Communications

SerialPortsCOM1,COM2 • RS-232port,8-pinmodularRJ45jack,fullorhalfduplex,or• RS-485port,2-wire,halfduplex

SerialPortCOM3 • RS-232port,8-pinmodularRJ45jack,fullorhalfduplexwithRTS/CTScontrolandoperatorinterfacepowercontrol

BaudRates 300,600,1200,2400,4800,9600,19200,38400,57600,and115200

SerialProtocols DNP3Slave,DNP3Master,IEC60870-5-101Slave,IEC60870-5-103Master,ModbusRTUMaster,ModbusRTUSlave,DF1

EthernetPort RJ45,10/100BaseT

EthernetProtocols DNP3inTCPMaster/Slave,DNP3inUDPMaster/Slave,Modbus/TCPClientandServer,IEC60870-5-104Slave,NTPServer,TelnetServer,FTPServer,BOOTPServer

USBPeripheralPort USB2.0compliant“B”-typereceptacle,DNP3protocol

Wireless1 Spreadspectrumradioat900MHz2and2.4GHz2

General

I/OTerminations 6-poleremovableterminalblock,12to22AWG,15Acontacts

Dimensions 5.65inch(144mm)wide,5.00inch(127mm)high,1.80inch(45mm)deep

Packaging Corrosionresistantzinc-platedsteelwithblackenamelpaint

Environment 5%RHto95%,non-condensing,–40°C(–40°F)to70°C(158°F)

PowerInput • 11-30VDC,3.5Wtypical• Add25to100mWwhenenablingtheLEDs• 12Wat24Vmaximum,5Vsupplyfullyloaded

Warranty 3yearsonpartsandlabor

Certifications

HazardousLocationsNorthAmerica

SuitableforuseinClassI,Division2,GroupsA,B,CandDHazardousLocations.TemperatureCodeT4CSAcertifiedtotherequirementsof:• CSAStd.C22.2No.213-M1987-HazardousLocations.• ULStd.No.1604-Hazardous(Classified)Locations.

HazardousLocations-Europe ATEXII3G,ExnAIICT4perEN60079-15,protectiontypen(Zone2).DoesnotincludeWirelessversions.

HazardousLocations IECEx,ExnAIICT4perIEC60079-15,protectiontypen(Zone2)DoesnotincludeWirelessversions.

1 Availableonlywithoptionalintegratedwirelessmodulesorwithstand-alonewirelessmodules.2 Notapplicableinallcountries.

Disclaimer:SchneiderElectricreservestherighttochangeproductspecifications.Formoreinformationvisitwww.schneider-electric.com.

Product Data Sheet SCADAPack 330ESpecifications

11

P334E: 5210 controller board and integrated 5607 I/O board

Controller

Processors • CPU:32-bitARM7microcontroller,32MHzclock,integratedwatchdogtimer• Microcontrollerco-processor,20MHzclock

Memory 16MBFLASHROM,4MBCMOSRAM,4kBEEPROM

Non-VolaliteRAM CMOSSRAMwithlithiumbatteryretainscontentsfor2yearswithnopower

EventLoggingCapacity 20,000events

MaximumDatabasePoints 1,000typical

I/O

AnalogInputs 8,0-20/4-20mA/0-5/0-10V(15-bit)softwareconfigurable

AnalogOutputs • Standard:None• 2,0-20/4-20mA(12-bit)withoptional5305on5607I/Oboard

DigitalI/O • 16,12/24V,48V,115/125V,240Vdigitalinputs• 10relayoutputs:drycontactorDCsolidstate,drycontactrating:3A,30VDCor240VAC(resistive),DCsolidstaterating:3A,60VDC

CounterInputs 1,0-10Hzor0-5kHz(drycontact);2,0-10kHz(turbineordrycontact)

Communications

SerialPortsCOM1,COM2 • RS-232port,8-pinmodularRJ45jack,fullorhalfduplex,or• RS-485port,2-wire,halfduplex

SerialPortCOM3 RS-232port,8-pinmodularRJ45jack,fullorhalfduplexwithRTS/CTScontrolandoperatorinterfacepowercontrol

BaudRates 300,600,1200,2400,4800,9600,19200,38400,57600,and115200

SerialProtocols DNP3Slave,DNP3Master,IEC60870-5-101Slave,IEC60870-5-103Master,ModbusRTUMaster,ModbusRTUSlave,DF1

EthernetPort RJ45,10/100BaseT

EthernetProtocols DNP3inTCPMaster/Slave,DNP3inUDPMaster/Slave,Modbus/TCPClientandServer,IEC60870-5-104Slave,NTPServer,TelnetServer,FTPServer,BOOTPServer

USBPeripheralPort USB2.0compliant“B”-typereceptacle,DNP3protocol

Wireless1 Spreadspectrumradioat900MHz2and2.4GHz2

General

I/OTerminations 5,6and9-poleremovableterminalblocks,12to22AWG,15Acontacts

Dimensions 5.65inch(144mm)wide,6.50inch(165mm)high,2.80inch(72mm)deep

Packaging Corrosionresistantzinc-platedsteelwithblackenamelpaint

Environment 5%RHto95%,non-condensing,–40°C(–40°F)to70°C(158°F)

Power

5210ControllerBoard • 11-30VDC,8.5Wtypical• Add25to100mWwhenenablingtheLEDs• 12Wat24Vmaximum,5Vsupplyfullyloaded

5607I/OModule • 11-30VDC,10.3mAplusanalogoutputs• 325mA(max.)at5Vrequiredfrom5210controllerboard

Warranty 3yearsonpartsandlabor

Certifications

HazardousLocationsNorthAmerica

SuitableforuseinClassI,Division2,GroupsA,B,CandDHazardousLocations.TemperatureCodeT4CSAcertifiedtotherequire-mentsof:• CSAStd.C22.2No.213-M1987-HazardousLocations.• ULStd.No.1604-Hazardous(Classified)Locations.

HazardousLocations-Europe ATEXII3G,ExnAIICT4perEN60079-15,protectiontypen(Zone2).DoesnotincludeWirelessversions.

HazardousLocations IECEx,ExnAIICT4perIEC60079-15,protectiontypen(Zone2)DoesnotincludeWirelessversions.

1 Availableonlywithoptionalintegratedwirelessmodulesorwithstand-alonewirelessmodules.2 Notapplicableinallcountries.

Disclaimer:SchneiderElectricreservestherighttochangeproductspecifications.Formoreinformationvisitwww.schneider-electric.com.

Product Data Sheet SCADAPack 334ESpecifications

12

TBUP334-EA55-AB00representsasamplecodeforaSCADAPack334Ewith12Vdrycontactrelayoutputs

Model Select: Controller

TBUP330 SCADAPack330E,32Bitcontroller,3Accumulators

TBUP334 SCADAPack334E,withModel5607I/Oboard,comeswithaboveI/Oplus8AnalogI/P,16DigitalI/Pand10DigitalO/P

Code Select: Platform

E EFirmwareplatform(ConfigurationSoftwareincluded),executestwoIEC61131-3kernels,Workbenchrequired

Code Select: SCADA Security

A Authentication

B AuthenticationandAGA-12SCADAEncryptionSecurity

Code Select: Protocol Option

5 Modbus,DNP3,DF1,Modbus/TCP,TCP/IP,IEC60870-5-101/104Slave

6 AddsIEC60870-5-103Master,ProtectionRelayProtocol(fordatatransmissionwithIEDs)

Code Select: License Option

5 DNP3DataConcentratorLicense(limitof500pointsfrom10IEDs),supportsmultipleDNP3Masters(upto3Masters)

Code Select: Analog Inputs

A P330:NoneP334:adds8selectableas0-20mA,4-20mA,0-5Vor0-10V

Code Select: Digital Inputs/Outputs

A P330:None

B P334:16DigitalInputs(12/24V)and10DryContactRelayoutputs

D P334:16DigitalInputs(120V)and10DryContactRelayoutputs

F P334:16DigitalInputs(12/24V)and10SolidStateRelayoutputs,ATEXCertified(withnoIntegratedradio)

H P334:16DigitalInputs(120V)and10SolidStateRelayoutputs

Code Select: Analog Outputs

0 None

1 P334only:2channelAnalogOutputoption,0-20mA

Code Select: Integrated Communication Interfaces

0 None

FreeWave & MDS Radios (requires one RS232 port)

1 900MhzFreeWaveSpreadSpectrumRadio

A 900MHzMDSSpreadSpectrumRadio

Trio Radios - 900MHz (requires one RS232 port)

B 900MHzTrioSpreadSpectrumRadiowithencryption,902-928MHz(FCC/IC)

C 900MHzTrioSpreadSpectrumRadiowithencryption,915-928MHz(AUS)

D 900MHzTrioSpreadSpectrumRadio,915-928MHz(BRAZIL)

E 900MHzTrioSpreadSpectrumRadio,921-928MHz(NZ)

Trio Radios - 2.4GHz (requires one RS232 port)

J 2.4GHzTrioSpreadSpectrumRadio,ETSI/100mW,ATEX(EUROPE)

K 2.4GHzTrioSpreadSpectrumRadiowithEncryption,500mW(CANADA,USA&AUSTRALIA)

L 2.4GHzTrioSpreadSpectrumRadio,500mW(OUTSIDEOFEUROPE,CANADA,USA&AUSTRALIA)

Product Data Sheet SCADAPack 330E | 334EModel Code

13

333E: 5210 controller board and integrated 5611 I/O board

Controller

Processors • CPU:32-bitARM7microcontroller,32MHzclock,integratedwatchdogtimer• Microcontrollerco-processor,20MHzclock

Memory 16MBFLASHROM,4MBCMOSRAM,4kBEEPROM

Non-VolatileRAM CMOSSRAMwithlithiumbatteryretainscontentsfor2yearswithnopower

EventLoggingCapacity 20,000events

MaximumDatabasePoints 1,000typical

I/O

AnalogInputs • 4softwareconfigurable,0-20/4-20mA/0-5/0-10V(15-bit)• 3internal:measureincomingpowersupplyvoltageforsolarapplications,batteryvoltage,andcontrollertemperature

AnalogOutputs • Standard:None• 2,0-20/4-20mA(12-bit)withoptionalcardon5611I/Oboard

DigitalI/O • 16,12/24Vdigitalinputs• 10relayoutputs:drycontact,drycontactrating:3A,30VDCor240VAC(resistive)

CounterInputs 1,0-10Hzor0-5kHz(drycontact);2,0-10kHz(turbineordrycontact)

Communications

SerialPortsCOM1,COM2 • RS-232port,8-pinmodularRJ45jack,fullorhalfduplex,or• RS-485port,2-wire,halfduplex

SerialPortCOM3 RS-232port,8-pinmodularRJ45jack,fullorhalfduplexwithRTS/CTScontrolandoperatorinterfacepowercontrol

BaudRates 300,600,1200,2400,4800,9600,19200,38400,57600,and115200

SerialProtocols DNP3Slave/Master,IEC60870-5-101Slave,ModbusRTUSlave,optionalModbusMasterandDF1Master

EthernetPort RJ45,10/100BaseT

IPProtocols DNP3inTCPMaster/Slave,DNP3inUDPMaster/Slave,Modbus/TCPClient,IEC60870-5-104Slave,NTPServer,TelnetServer,FTPServer,BOOTPServer,optionalModbus/TCPServer

USBPort USB2.0compliant“B”-typereceptacle,DNP3protocol

Wireless Externalmodem(e.g.SchneiderElectricGPRSmodemref.SR2MOD3)

General

LogicControl OptionalIEC61131-3SCADAPackWorkbenchprogrammingsuite(LD,ST,FBD&SFC)

I/OTerminations 5,6and9-poleremovableterminalblocks,12to22AWG,15Acontacts

Dimensions 5.65inch(144mm)wide,6.50inch(165mm)high,2.80inch(72mm)deep

Packaging Corrosionresistantzinc-platedsteelwithblackenamelpaint

Environment 5%RHto95%,non-condensing,–25°C(–13°F)to70°C(158°F)

Power

5210ControllerBoard • 11-30VDC,8.5Wtypical• Add25to100mWwhenenablingtheLEDs• 12Wat24Vmaximum,5Vsupplyfullyloaded

5611I/OModule • 11-30VDC,10.3mAplusanalogoutputs• 325mA(max.)at5Vrequiredfrom5210controllerboard

Warranty 3yearsonpartsandlabor

Certifications

• CEmarking• C-Tick• UL508(US/Canada)-cULus• FCC/EN61000-6emissions&immunity

Disclaimer:SchneiderElectricreservestherighttochangeproductspecifications.Formoreinformationvisitwww.schneider-electric.com.

Product Data Sheet SCADAPack 333ESpecifications

14

TBUP333-EA54-AB00representsasamplecodeforaSCADAPack333Ewith12Vdry-contactrelayoutputsandnoIEC61131programmingoption.

Model Select: Controller

TBUP333 SCADAPack333E,32-Bitcontroller,4AnalogInputs,2optionalAnalogOutputs,16DigitalInputs,10DigitalOutputs,3CounterInputs

Code Select: Platform

E EFirmwareplatform(SCADAPackEConfiguratorsoftwareincluded),executestwoIEC61131-3kernels(optional),Workbenchrequired

Code Select: SCADA Security

A None

B AGA-12EncryptionforDNP3

C DNP3SecureAuthenticationSAv2

D DNP3SecureAuthenticationwithAGA-12Encryption

Notes:• TheSecurityAdministratorApplicationhastobepurchasedtogenerateandmanagesecuritykeys.• AGA-12Encryptionissubjecttoexportrestrictions.PleaseconsultwithyourTRSSbusinessunitcontact.

Code Select: Protocol Option

5 DNP3Slave/Master,IEC60870-5-101/-104Slave,ModbusRTUSlave

Code Select: License Option

4 Option1:withoutIEC61131,ModbusMasterandDF1Master

5 Option2:withIEC61131-3(executestwokernels,SCADAPackWorkbenchrequired),ModbusMasterandDF1Master

Notes:• BothoptionsincludeDNP3DataConcentratorlicense(limitof500pointsfrom10IEDs),MultipleDNP3MasterLicense(upto3Masters)

• Ifyouorderaproductwithoption1whichyoulaterwanttoupgradetooption2,youhavetoorderaRTUlicenceupdate(ref.TBUM297889)

Code Select: Analog Inputs

A 4

Code Select: Digital Inputs/Outputs

B 16inputsand10outputs

Code Select: Analog Outputs

0 None

1 2

Code Select: Future Option

0 None

Product Data Sheet SCADAPack 333EModel Code

15

337E: 5210 controller board and integrated 5606 I/O board

Controller

Processors • CPU:32-bitARM7microcontroller,32MHzclock,integratedwatchdogtimer• Microcontrollerco-processor,20MHzclock

Memory 16MBFLASHROM,4MBCMOSRAM,4kBEEPROM

Non-VolatileRAM CMOSSRAMwithlithiumbatteryretainscontentsfor2yearswithnopower

EventLoggingCapacity 20,000events

MaximumDatabasePoints 1,000typical

I/O

AnalogInputs • 8softwareconfigurable,0-20/4-20mA/0-5/0-10V(15-bit)• 3internal:measureincomingpowersupplyvoltageforsolarapplications,batteryvoltage,andcontrollertemperature

AnalogOutputs • Standard:None• 2,0-20/4-20mA(12-bit)withoptionalcardon5606I/Oboard

DigitalI/O • 32,12/24Vdigitalinputs• 16relayoutputs:drycontact,drycontactrating:3A,30VDCor240VAC(resistive)

CounterInputs 1,0-10Hzor0-5kHz(drycontact);2,0-10kHz(turbineordrycontact)

Communications

SerialPortsCOM1,COM2 • RS-232port,8-pinmodularRJ45jack,fullorhalfduplex,or• RS-485port,2-wire,halfduplex

SerialPortCOM3 RS-232port,8-pinmodularRJ45jack,fullorhalfduplexwithRTS/CTScontrolandoperatorinterfacepowercontrol

BaudRates 300,600,1200,2400,4800,9600,19200,38400,57600,and115200

SerialProtocols DNP3Slave/Master,IEC60870-5-101Slave,ModbusRTUSlave/MasterandDF1Master

EthernetPort RJ45,10/100BaseT

IPProtocols DNP3inTCPMaster/Slave,DNP3inUDPMaster/Slave,Modbus/TCPClient,IEC60870-5-104Slave,NTPServer,TelnetServer,FTPServer,BOOTPServer,optionalModbus/TCPServer

USBPort USB2.0compliant“B”-typereceptacle,DNP3protocol

Wireless Externalmodem(e.g.SchneiderElectricGPRSmodemref.SR2MOD3)

General

LogicControl IEC61131-3SCADAPackWorkbenchprogrammingsuite(LD,ST,FBD&SFC)

I/OTerminations 5,6,9and10-poleremovableterminalblocks,12to22AWG,15Acontacts

Dimensions 8.40inch(213mm)wide,6.13inch(155mm)high,2.80inch(72mm)deep

Packaging Corrosionresistantzinc-platedsteelwithblackenamelpaint

Environment 5%RHto95%,non-condensing,–25°C(–13°F)to70°C(158°F)

Power

5210ControllerBoard • 11-30VDC,8.5Wtypical• Add25to100mWwhenenablingtheLEDs• 12Wat24Vmaximum,5Vsupplyfullyloaded

5606I/OModule • 600mA(max.)at5Vrequiredfrom5210controllerboard• 11-30VDC,12mAplusanalogoutputs

Warranty 3yearsonpartsandlabor

Certifications

• CEmarking• C-Tick• UL508(US/Canada)-cULus• FCC/EN61000-6emissions&immunity

Disclaimer:SchneiderElectricreservestherighttochangeproductspecifications.Formoreinformationvisitwww.schneider-electric.com.

Product Data Sheet SCADAPack 337ESpecifications

16

TBUP337-EA55-AB00representsasamplecodeforaSCADAPack337Ewith12Vdry-contactrelayoutputsandIEC61131-3programming.

Model Select: Controller

TBUP337 SCADAPack337E,withModel5606I/Oboard,comeswith8AnalogI/P,2optionalAnalogO/P,32DigitalI/P,16DigitalO/Pand3CounterI/P

Code Select: Platform

E EFirmwareplatform(SCADAPackEConfiguratorsoftwareincluded),executestwoIEC61131-3kernels(optional),Workbenchrequired

Code Select: SCADA Security

A None

B AGA-12EncryptionforDNP3

C DNP3SecureAuthenticationSAv2

D DNP3SecureAuthenticationwithAGA-12Encryption

Notes:• TheSecurityAdministratorApplicationhastobepurchasedtogenerateandmanagesecuritykeys.• AGA-12Encryptionissubjecttoexportrestrictions.PleaseconsultwithyourTRSSbusinessunitcontact.

Code Select: Protocol Option

5 DNP3Slave/Master,IEC60870-5-101/-104Slave,ModbusRTUSlave/MasterandDF1Master

Code Select: License Option

5 IncludesDNP3DataConcentratorlicense(limitof500pointsfrom10IEDs),MultipleDNP3MasterLicense(upto3Masters)

Code Select: Analog Inputs

A 4

Code Select: Digital Inputs/Outputs

B 32inputsand16outputs

Code Select: Analog Outputs

0 None

1 2

Code Select: Future Option

0 None

Product Data Sheet SCADAPack 337EModel Code

17

P350E: 5209 controller board only

Controller

Processors • CPU:32-bitARM7microcontroller,32MHzclock,integratedwatchdogtimer• TwoMicrocontrollerco-processors,20MHzclock

Memory 16MBFLASHROM,4MBCMOSRAM,4kBEEPROM

Non-VolatileRAM CMOSSRAMwithlithiumbatteryretainscontentsfor2yearswithnopower

EventLoggingCapacity 20,000events

MaximumDatabasePoints 1,000typical

I/O

AnalogInputs • 5,userselectable0-10V(15-bit)or0-20mAplusoverrange(14-bit)• 1,0-32.7VDC(15-bit)

AnalogOutputs • Standard:None• 2,0-20/4-20mA(12-bit)withoptional5305

DigitalI/O 8,userselectableasdrycontactinputsoropendrainoutputs

CounterInputs • 1,0-10Hz(drycontact)• 2,0-10kHz(turbineordrycontact)

Communications

SerialPortCOM1 RS-485port,2-poleremovableterminalblock,2-wire,halfduplex

SerialPortCOM2 • RS-232port,8-pinmodularRJ45jack,fullorhalfduplex,or• RS-485port,2-wire,halfduplex

SerialPortCOM3 RS-232port,8-pinmodularRJ45jack,halfduplexwithRTS/CTScontrolandoperatorinterfacepowercontrol

BaudRates 300,600,1200,2400,4800,9600,19200,38400,57600,and115200

SerialProtocols DNP3Slave,DNP3Master,IEC60870-5-101Slave,IEC60870-5-103Master,ModbusRTUMaster,ModbusRTUSlave,DF1

EthernetPort RJ45,10/100BaseT

EthernetProtocols DNP3inTCPMaster/Slave,DNP3inUDPMaster/Slave,Modbus/TCPClientandServer,IEC60870-5-104Slave,NTPServer,TelnetServer,FTPServer,BOOTPServer

USBPeripheralPort USB2.0compliant“B”-typereceptacle,DNP3protocol

Wireless1 Spreadspectrumradioat900MHz2and2.4GHz2

General

I/OTerminations 6and12-poleremovableterminalblocks,12to22AWG,15Acontacts

Dimensions 8.40inch(213mm)wide,5.00inch(127mm)high,1.80inch(45mm)deep

Packaging Corrosionresistantzinc-platedsteelwithblackenamelpaint

Environment 5%RHto95%,non-condensing,–40°C(–40°F)to70°C(158°F)

PowerInput • 11-30VDC,4.6Wtypical• Add25to100mWwhenenablingtheLED• 12Wat24Vmaximum.5VsupplyfullyloadedandVlooponandboosted,fullyloaded

VoltageConverter 12VDCto24VDC

Warranty 3yearsonpartsandlabor

Certifications

HazardousLocationsNorthAmerica

SuitableforuseinClassI,Division2,GroupsA,B,CandDHazardousLocations.TemperatureCodeT4,ULlistedandCSAcertifiedtotherequirementsof:• CSAStd.C22.2No.213-M1987-HazardousLocations.• ULStd.No.1604-Hazardous(Classified)Locations.

HazardousLocations-Europe ATEXII3G,ExnAIICT4perEN60079-15,protectiontypen(Zone2).DoesnotincludeWirelessversions.

HazardousLocations IECEx,ExnAIICT4perIEC60079-15,protectiontypen(Zone2)DoesnotincludeWirelessversions.

1 Availableonlywithoptionalintegratedwirelessmodulesorwithstand-alonewirelessmodules.2 Notapplicableinallcountries.

Disclaimer:SchneiderElectricreservestherighttochangeproductspecifications.Formoreinformationvisitwww.schneider-electric.com.

Product Data Sheet SCADAPack 350ESpecifications

18

P357E: 52O9 controller board and integrated 56O6 I/O board

Controller

Processors • CPU:32-bitARM7microcontroller,32MHzclock,integratedwatchdogtimer• Microcontrollerco-processor,20MHzclock

Memory 16MBFLASHROM,4MBCMOSRAM,4kBEEPROM

Non-VolatileRAM CMOSSRAMwithlithiumbatteryretainscontentsfor2yearswithnopower

EventLoggingCapacity 20,000events

MaximumDatabasePoints 1,000typical

I/O

AnalogInputs • 5,userselectable0-10V(15-bit)or0-20mAplusoverrange(14-bit)• 1,0-32.7VDC(15-bit);8,0-20/4-20mA/0-5/0-10V(15-bit)softwareconfigurable

AnalogOutputs • Standard:None• 2,0-20/4-20mA(12-bit)withoptional5305on5209controllerboard• 2,0-20/4-20mA(12-bit)withoptional5305on5606I/Oboard

DigitalI/O • 8,userselectableasdrycontactinputsoropendrainoutputs• 32,12/24V,48V,115/125V,240Vdigitalinputs;16,relayoutputs-drycontactorDCsolidstate

CounterInputs 1,0-10Hz(drycontact);2,0-10kHz(turbineordrycontact)

Communications

SerialPortCOM1 RS-485port,2-poleremovableterminalblock,2-wire,halfduplex

SerialPortCOM2 • RS-232port,8-pinmodularRJ45jack,fullorhalfduplexRS-232,or• RS-485port,2-wire,halfduplex

SerialPortCOM3 RS-232port,8-pinmodularRJ45jack,halfduplexwithRTS/CTScontrolandoperatorinterfacepowercontrol

BaudRates 300,600,1200,2400,4800,9600,19200,38400,57600,and115200

SerialProtocols DNP3Slave,DNP3Master,IEC60870-5-101Slave,IEC60870-5-103Master,ModbusRTUMaster,ModbusRTUSlave,DF1

EthernetPort RJ45,10/100BaseT

EthernetProtocols DNP3inTCPMaster/Slave,DNP3inUDPMaster/Slave,Modbus/TCPClientandServer,IEC60870-5-104Slave,NTPServer,TelnetServer,FTPServer,BOOTPServer

USBPeripheralPort USB2.0compliant“B”-typereceptacle,DNP3protocol

Wireless1 Spreadspectrumradioat900MHz2and2.4GHz2

General

I/OTerminations 5,6,9,10and12-poleremovableterminalblocks,12to22AWG,15Acontacts

Dimensions 8.40inch(213mm)wide,6.13inch(155mm)high,2.80inch(72mm)deep

Packaging Corrosionresistantzinc-platedsteelwithblackenamelpaint

Environment 5%RHto95%,non-condensing,–40°C(–40°F)to70°C(158°F)

Power

5209ControllerBoard • 11-30VDC,9.2Wtypical• Add25to100mWwhenenablingtheLEDs• 12Wat24Vmaximum.5VsupplyfullyloadedandVlooponandboosted,fullyloaded

5606I/OModule • 600mA(max.)at5Vrequiredfrom5209controllerboard• 11-30VDC,12mAplusanalogoutputs

VoltageConverter 12VDCto24VDC

Warranty 3yearsonpartsandlabor

CertificationsHazardousLocationsNorthAmerica

SuitableforuseinClassI,Division2,GroupsA,B,CandDHazardousLocations.TemperatureCodeT4,ULlistedandCSAcertifiedtotherequirementsof:• CSAStd.C22.2No.213-M1987-HazardousLocations.• ULStd.No.1604-Hazardous(Classified)Locations.

HazardousLocations-Europe ATEXII3G,ExnAIICT4perEN60079-15,protectiontypen(Zone2).DoesnotincludeWirelessversions.

HazardousLocations IECEx,ExnAIICT4perIEC60079-15,protectiontypen(Zone2)DoesnotincludeWirelessversion

1 Availableonlywithoptionalintegratedwirelessmodulesorwithstand-alonewirelessmodules.2 Notapplicableinallcountries.

Disclaimer:SchneiderElectricreservestherighttochangeproductspecifications.Formoreinformationvisitwww.schneider-electric.com.

Product Data Sheet SCADAPack 357ESpecifications

19

TBUP350-EA55-AA00representsasamplecodeforaSCADAPack350Ewith8digitalI/O

Model Select: Controller

TBUP350 SCADAPack350E,32Bitcontroller,5A/I,8configurableDigitalI/O,3Counters,2RS232,1RS485,2USB,1Ethernet

TBUP357 SCADAPack357E,withModel5606I/Oboard,comeswiththeaboveplus8AnalogI/P,32DigitalI/Pand16DigitalO/P

Code Select: Platform

E EFirmwareplatform(ConfigurationSoftwareincluded),executestwoIEC61131-3kernels,Workbenchrequired

Code Select: SCADA Security

A Authentication

B AuthenticationandAGA-12SCADAEncryptionSecurity

Code Select: Protocol Option

5 Modbus,DNP3,DF1,Modbus/TCP,TCP/IP,IEC60870-5-101/104Slave

6 AddsIEC60870-5-103Master,ProtectionRelayProtocol(fordatatransmissionwithIEDs)

Code Select: License Option

5 DNP3DataConcentratorLicense(limitof500pointsfrom10IEDs),supportsmultipleDNP3Masters(upto3Masters)

Code Select: Analog Inputs

A P350:5selectableas0-10Vor0-20mAP357:adds8selectableas0-20mA,4-20mA,0-5Vor0-10V

Code Select: Digital Inputs/Outputs

A P350:8configurableDigitalI/O,IndividuallyselectableasD/I(DryContact)orDigitalOutput(OpenDrain)

B P357:IncludesP350I/Oplus32DigitalInputs(12/24V),16DryContactRelayOutputs

D P357:IncludesP350I/Oplus32DigitalInputs(120V),16DryContactRelayOutputs

F P357:IncludesP350I/Oplus32DigitalInputs(12/24V),16SolidStateRelayOutputs,ATEXCertified(withnoradio)

H P357:IncludesP350I/Oplus32DigitalInputs(120V),16SolidStateRelayOutputs

Code Select: Analog Outputs

0 None

1 P350orP357:2channelAnalogOutputoption,0-20mA(P357-2channelA/Ooptiononthe5606module)

2 P357only:4channelAnalogOutputoption,0-20mA(includes2channelA/Ooptiononbothmodules)

Code Select: Integrated Communication Interfaces

0 None

FreeWave & MDS Radios (requires one RS232 port)

1 900MhzFreeWaveSpreadSpectrumRadio

A 900MHzMDSSpreadSpectrumRadio

Trio Radios - 900MHz (requires one RS232 port)

B 900MHzTrioSpreadSpectrumRadiowithencryption,902-928MHz(FCC/IC)

C 900MHzTrioSpreadSpectrumRadiowithencryption,915-928MHz(AUS)

D 900MHzTrioSpreadSpectrumRadio,915-928MHz(BRAZIL)

E 900MHzTrioSpreadSpectrumRadio,921-928MHz(NZ)

Trio Radios - 2.4GHz (requires one RS232 port)

J 2.4GHzTrioSpreadSpectrumRadio,ETSI/100mW,ATEX(EUROPE)

K 2.4GHzTrioSpreadSpectrumRadiowithEncryption,500mW(CANADA,USA&AUSTRALIA)

L 2.4GHzTrioSpreadSpectrumRadio,500mW(OUTSIDEOFEUROPE,CANADA,USA&AUSTRALIA)

Product Data Sheet SCADAPack 350E | 357EModel Code

20

SCADAPack ES

Controller

Processor AMD586ElanSC52032-bitembeddedprocessor,100MHz

Memory 128MBSDRAM,32MBFlash,2048KBSRAM,512KBBootFlash

EventLoggingCapacity 40,000events

MaximumDatabasePoints 20,000typical

Temperature -40°C(-40°F)to65°C(150°F)operating,-40°C(-40°F)to70°C(158°F)storage

Humidity 10to95%RH(non-condensing)

InputVoltageRange 10to30VDC

PowerRequirements • 6.3Wat24VDCminimum• Add3.0Wwithallrelaysenergized• Add6.5Wforfullyloadedauxiliarypowersupply• Add.72Wperanalogoutput

AuxiliaryOutputSupply • Isolated24VDC200mAmax.(optional)• Isolated10VDC500mAmax.(optional)• Isolated5VDC1.0Amax.(optional,requiredforI/OExpansionmodulesorOperatorInterfaceTerminal)

Isolation PowerinputandAuxiliaryOutputarefunctionallyisolatedfromeachotherandallIOpoints

CommunicationPorts • Port0,Port1andPort4:RS-232;Port2andPort3:RS-232/RS-422/RS-485(softwareselectable)• Ethernet:Dual10/100Base-TUTPports(transformerisolated)Note:AllRS-232portsarestaticprotectedto±15kV(IEC801-2,Air-gapdischarge)

Protocols • Modbus,DNP3,Modbus/TCP,TCP/IP(standard)• IEC60870-5-103(serialmaster),-101(serialslave),-104(Ethernetslave)optional

RemovableMemorySocket CompactFlashType1:buffered,hot-swapcapable.Supportsupto4GBcard(compactflashcardnotincluded)

Dimensions 11.81inch(300mm)wide,6.89inch(175mm)high,1.57inch(40mm)deep

Digital Inputs

Configuration 16or32inputs

NormalOperationRange 10-30VDC

SequenceofEventsDetection 10mS

ChannelsPerCommon 8

Inversion Stateinversionperchannel

Debounce Adjustableperchannel

Counters 0-40Hzand0-1kHzcounterchannels(sharedwithdigitalinputs)

Digital Outputs

Configuration 8or16outputs

Type FormCSPDTrelay,3-terminalconnection(NO/Common/NC),Non-latching

Isolation 500VACminimumtoRTUelectronics

Maxswitchingvoltage 30VDC,25VAC

Maxswitchingload 60W/50VA(2A)

Specificationscontinueonthenextpage

Product Data Sheet SCADAPack ESSpecifications

21

Product Data Sheet SCADAPack ESSpecifications

SCADAPack ES

Analog Inputs

Configuration 6or12inputs

Type Unipolar

Resolution 12-bit,0.1%offullscaleat77°F(25°C),±0.3%overtemperaturerange

Isolation IsolatedfromchanneltochannelandfromRTUelectronics.Analoginputsmustbewithin50Vacor7VDCofchassisorearth

Range 4-20mAor1-5Vswitchselectable

Analog Outputs

Configuration 2or4outputs

Type Unipolar

Resolution 12bit±0.1%at77°F(25°C)with250ohmload,±0.5%overtemperaturerange

Isolation Optical.500VacminimumtoRTUelectronics

Range 4-20mA(voltageoutputavailablewithexternalprecisionresistor)

LoadRange • 0-100ohmswith9Vsupply• 150-1150ohmswith30Vsupply

Additional I/O

I/OExpansion Supportedmodules:5304,5405,5411,5505,5506and5606

SCADAPackES Supportforadditionalmulti-droppedESSmartRTU,viaserialorEthernetlinks

Certifications

Safety c(CSA)us.CAN/CSA-C22.2No.61010-1.RequirestheuseofSELVpowersuppliesonallpowerandIOpointsforcompliance

HazardousLocations Non-IncendiveElectricalEquipmentforUseinClassI,Division2GroupsA,B,CandD(optional)

Disclaimer:SchneiderElectricreservestherighttochangeproductspecifications.Formoreinformationvisitwww.schneider-electric.com.

22

TBUP500-1A00-AE00NrepresentsasamplecodeforaSCADAPackESwith16D/I,8D/O,6A/Iand2A/O

Model Select: Controller

TBUP500 SCADAPackES

Code Select: Communication Ports

1 3RS232,2RS232/485,2Ethernet10/100BaseT,1CompactFlashsocket(compactFlashcardsoldseparately)

Code Select: Processor/Memory

A AMDElanSC520CPU,100MHz,32MBOperatingSystemFLASH,128MBvolatileSDRAM,2MBBatteryBackedSRAM

Code Select: Protocol Option

0 Modbus,DNP3,DF1,Modbus/TCP,TCP/IP,IEC60870-5-101/104Slave(includedinallSmartRTUs)

1 AddsIEC60870-5-103Master,ProtectionRelayProtocol(fordatatransmissionwithIEDs)

Code Select: Programming Environment & SCADA Security

0 IEC61131-3(ExecutestwoIEC61131-3kernels,includesEConfigurator&extensions,Workbenchrequired)

1 IEC61131-3withAGA-12SCADAEncryptionSecurity

Code Select: License Option

A None(allunitscomestandardwithsupportformultipleDNP3Masters-upto3Masters)

B DNP3DataConcentratorLicense-SCADAPackESactsasaDNPmastertocollectdatafrommultipleslaves

Code Select: I/O Configuration

D/I D/O A/I A/O (SomeI/OExpansionmodulessupported)

B 0 0 0 0

E 16 8 6 2

A 32 16 12 4

Code Select: Power Supply

0 10-30VdcWideRangePowerinput,noauxiliarypowersupply

1 10-30VdcWideRangePowerinput,auxiliarypowersupplywith5Vdcoutput(requiredtopowerVisionDisplays)

2 10-30VdcWideRangePowerinput,auxiliarypowersupplywith10Vdcoutput

3 10-30VdcWideRangePowerinput,auxiliarypowersupplywith24Vdcoutput

Code Select: Approvals

0 c(CSA)us.CAN/CSA-C22.2No.61010-1.Approved-Non-HazardousLocations

1 c(CSA)us.CAN/CSA-C22.2No.61010-1,Class1-Div2(GroupsA,B,C,D).Approved-HazardousLocations

Code Select: Custom Options

N None

V AnalogInputrangesetfor1-5v(defaultrangeis4-20mA)

Product Data Sheet SCADAPack ESModel Code

23

Product Data Sheet 5505 – RTD input moduleSpecifications

5505 RTD input module

General

InputPoints 4,RTD

RTDType 100-ohmplatinum,3and4-wire,auto-detectionandcompensation

Calibration 0.00385Ω/Ω/°CstandardbasedonASTME1137/E1137M-04,ITS-90

Ranges 5505:Canbeconfiguredtoreturndatainohms,°C,°For°K• -200°Cto800°C(-328°Fto1472°F)• 0to500Ω5503Emulation:Dipswitchselectable• 0°Cto200°C(32°Fto392°F)• -100°Cto100°C(-148°Fto212°F)• -200°Cto0°C(-328°Fto32°F)• 0°Cto800°C(32°Fto1472°F)• 0°Cto400°C(32°Fto752°F)• 0to400Ω

DataFormat • 5505:32-bitfloatingpointand12statusbits• 5503Emulation:16-bitsignedinteger

Resolution • 5505:>17-biteffective• 5505Emulation:15-bit

RTDStatus • RTDisgood(notopen)• RTDinrange• RTD3or4-wire• RTDstatusnotavailablein5503Emulation

AccuracyonRTDRanges Percentoffullscaleoveroperationaltemperaturerangeincludinglinearizationerrors:+0.10%/-0.05%

Accuracyon0to500ohms Percentoffullscaleoveroperationaltemperaturerange:±0.03%

ExcitationCurrent 4mA,7.2%dutycyclein4-wiremode,14.4%in3-wiremode,250msscaninterval

LineResistance 100Ωmax.,ineachline

ConverterType 24-bitdelta-sigma

ResponseTime 380mstypicalfor10%to90%signalchangeatminimumfiltersetting

TransientProtection 2.5kVsurge-withstandcapabilityasperANSI/IEEEC37.90.1-1989

Isolation Isolationfromlogicsupplyandchassis,voltage500Vrms

5VPowerRequirements 6mA

11-30VDCPowerRequirements

12Voperation:4mA• plus0.6mAper4-wireRTD• plus1.2mAper3-wireRTD24Voperation:2.2mA• plus0.3mAper4-wireRTD• plus0.6mAper3-wireRTD

11-30VDC-Connector Removable.SharedwithRTDinputs0-1

11-30VDC-Isolation Isolationfromlogicsupplyandchassis

Terminations 8and10pole,removableterminalblock,12to22AWG,15Acontacts

Dimensions 74mmwidex124mmhighx45mmdeep(2.9in.x4.9in.x1.8in.)

Mounting 7.5x35DINrail

Packaging Corrosion-resistantzinc-platedsteelwithblackenamelpaint

Environment 5%RHto95%RH,non-condensing,-40°Cto70°C(-40°Fto158°F)operation,-40°Cto85°C(-40°Fto185°F)storage

Safety • Non-IncendiveElectricalEquipmentforUseinClassI,Division2• GroupsA,BCandDHazardousLocations• ATEXII3GandIECEx:ExnAIICT4perEN60079-15,protectiontypen(Zone2)

PartNumber TBUX297318

Disclaimer:SchneiderElectricreservestherighttochangeproductspecifications.Formoreinformationvisitwww.schneider-electric.com.

24

Product Data Sheet 5506 – Analog input moduleSpecifications

5506 Analog input module

General

InputPoints 8

Ranges • 0-20mA• 4-20mA• 0-5V• 1-5V

LEDIndicators 8redLEDs,indicatingcurrentinput,voltageinputandunderorover-rangesignalapplied

InputConfiguration Individualinputsconfigurablewith4mA/1V(20%)offsetandforvoltage/currentoperationwhenconfiguredasa5506.Allinputsdipswitch-selectablewith4mA/1V(20%)offsetandforvoltage/currentoperationwhenconfiguredtoemulatea5501module.

InputResistance 250ohms-Currentconfiguration;66kohms-Voltageconfiguration

Resolution 15-bitsoverthe0-5Vand0-20mAmeasurementrange

Type Single-ended

Accuracy ±0.1%offullscaleat25°C(77°F);±0.2%overtemperaturerange

TransientProtection 2.5kVsurgewithstandcapabilityasperANSI/IEEEC37.90.1-1989

NormalModeRejectionAt60Hzwith60HzScanning

• 53dBwith3Hzfilter• 50dBwith6Hzfilter• 49dBwith11Hzfilter• 45dBwith30Hzfilter

NormalModeRejectionAt50Hzwith50HzScanning

• 73dBwith3Hzfilter• 56dBwith6Hzfilter• 52dBwith11Hzfilter• 49dBwith30Hzfilter

ResponseTimefor10%to90%SignalChange(60HzScanning)

• 250mswith3Hzfilter• 130mswith6Hzfilter• 60mswith11Hzfilter• 30mswith30Hzfilter

ResponseTimefor10%to90%SignalChange(50HzScanning)

• 300mswith3Hzfilter• 140mswith6Hzfilter• 80mswith11Hzfilter• 40mswith30Hzfilter

Over-ScaleInputCapacity(withoutdamage)

Continuous:0.10A/14Vonthe20mAinputs;0.05A/14Vonthe5Vinputs

Isolation 500Vacisolationfromlogicsupplyandchassis

5VPowerRequirements • 22mA,LEDsoff• 45mA,LEDson

11-30VDCPowerRequirements 11mA

11-30VDC-Connector Removable,4positions

11-30VDC-Isolation Isolationfromlogicsupplyandchassis

Terminations 10pole,removableterminalblock,12to22AWG,15Acontacts

Dimensions 2.9inch(74mm)wide,4.9inch(124mm)high,1.8inch(45mm)deep

Mounting 7.5x35DINrail

Packaging Corrosion-resistantzinc-platedsteelwithblackenamelpaint

Environment 5%RHto95%RH,non-condensing,-40°Cto70°C(-40°Fto158°F)operation,-40°Cto85°C(-40°Fto185°F)storage

Safety • Non-IncendiveElectricalEquipmentforUseinClassI,Division2• GroupsA,BCandDHazardousLocations• ATEXII3GandIECEx:ExnAIICT4perEN60079-15,protectiontypen(Zone2)

PartNumber TBUX297319

Disclaimer:SchneiderElectricreservestherighttochangeproductspecifications.Formoreinformationvisitwww.schneider-electric.com.

25

Product Data Sheet 5304 – Analog output moduleSpecifications

5304 Analog output module

General

Outputpoints 4

OutputModes • Currentmode,jumperlinkselectable• Voltagemode,5Vfullscale,jumperlinkselectable,• Voltagemode,10Vfullscale,jumperlinkselectable

Outputsignalranges • 0-20mAor4-20mA,switchconfigurable• 0-5Vor1-5V,switchconfigurable,0-10Vor2-10V,switchconfigurable

OutputType Singleendedregulationonpositivesidewithcommonnegativereturn

MaximumLoadResistance 1000Ωwith24VDClooppower,400Ωwith12VDClooppower,250Ωwith9VDClooppower

MinimumLoadResistanceinVoltageMode

• 2kΩfor10Vfullscale,withmin20VDCpowerapplied• 1kΩfor5Vfullscale,withmin15VDCpowerapplied

Isolation 500VACfieldtologic

D/AResolution 12-bitoverthe0-20mA/0-5V/0-10Vranges

AbsoluteAccuracy +/-0.05%offullscaleat25ºC(77ºF),+/-0.2%offullscaleovertemperaturerange

NoiseandRipple 0.04%maximum

TransientProtection • 2.5kVsurgewithstandcapabilityasperANSI/IEEEC37.90.1-1989• Inductiveloadprotectiondiodesincluded

ResponseTime 2mstypicalto90%signalchange

Addressing DIPswitchconfigurable

12-24VOperatingVoltageLimits

• 9Vor(20mAxloadresistance)+4V(whicheverisgreater)incurrentmode• (1.5xRange/loadresistance)+Range+2.5Vinvoltagemode,30Vmaximum

PowerRequirements • 6mAmin.,25mAmaximum• 15mAquiescentplus80mAmax.incurrentmode• 15mAquiescentplus20mAmax.involtagemode

Terminations 10pole,removableterminalblock,12to22AWG,15ampcontacts

Dimensions 108mmwidex118mmhighx44mmdeep(4.25in.x4.625in.x1.75in.)

Mounting 7.5x35DINrail

Packaging Corrosionresistantzincplatedsteelwithblackenamelpaint

Environment 5%RHto95%RH,non-condensing,-40°Cto70°C(-40°Fto158°F)

Safety cCSAusandcULusClassI,Division2HazardousAreaRating,UL508listed

Model Part Number Description

5304-20 TBUX297248 4channelisolatedanalogoutputmodule,0-20mA

5304-10 TBUX297252 4channelisolatedanalogoutputmodule,0-10volts

5304-5 TBUX297253 4channelisolatedanalogoutputmodule,0-5volts

5304-C TBUX297254 4channelisolatedanalogoutputmodule,Custom(specifyrangeofeachinput)

Disclaimer:SchneiderElectricreservestherighttochangeproductspecifications.Formoreinformationvisitwww.schneider-electric.com.

26

Product Data Sheet 5405 – Digital input moduleSpecifications

5405 Digital input module

General

InputPoints 32

Ranges 12-24VDC,16-24VAC,120VAC/DC

Over-VoltageTolerance 150%sustainedover-voltagewithoutdamage

InputCurrent • 6.0mAtypical@24VDConthe24Vrange• 3.5mAtypical@24VAConthe24Vrange• 2.5mAtypical@120VDConthe120Vrange• 1.5mAtypical@120VAConthe120Vrange

DCInputLogicLevels • OFFtoONtransitionthresholdistypically7.5VDConthe24VDCrange• OFFtoONtransitionthresholdistypically55VDConthe120VDCrange

ACInputLevels • OFFtoONtransitionthresholdistypically6VAConthe24VACrange• OFFtoONtransitionthresholdistypically45VAConthe120VACrange

TransientProtection 2.5kVsurgewithstandcapabilityasperANSI/IEEEC37.90.1-1989

Isolation • Isolatedin4groupsof8.Inputs0-15areonthebottomedge.• Inputs16-31areonthetopedge.Isolation500VAC/DCfromchassisandlogicground

PowerRequirements 5V@10mAwithallinputsON

Terminations 4:9pole,removableterminalblocks,12to22AWG,15Acontacts

Dimensions 144mmwidex127mmhighx45mmdeep(5.65in.x5.00in.x1.88in.)

Packaging Corrosionresistantzincplatedsteelwithblackenamelpaint

Environment 5%RHto95%RH,non-condensing,-40°Cto60°C(-40°Fto140°F)

Addressing Configurablewith4DIPswitches

AC/DCOperation 2:DIPswitchesdetermineAC/DCand50/60Hzoperation

VisualIndicators 32:RedLED’s,fieldpowered.Cannotbedisabledtoconservepower

Safety cCSAusandcULusClassI,Division2HazardousAreaRating,UL508listed

Model Part Number Description

5405-120 TBUX297249 32point,120Vdiscreteinputmodule

5405-24 TBUX297247 32point,12-24Vdiscreteinputmodule

Disclaimer:SchneiderElectricreservestherighttochangeproductspecifications.Formoreinformationvisitwww.schneider-electric.com.

27

Product Data Sheet 5414 – Compact digital input moduleSpecifications

5414 Compact digital input module

General

NumberofDigitalInputs 16

Ranges Factoryconfigurableas:• 12/24V• 48V• 115/125V• 240V

InputCurrent • 0.6–0.9mAat24Vonthe12/24Vrange• 0.3–0.4mAat48Vonthe48Vrange• 0.3–0.4mAat120Vonthe115/125Vrange• 0.3–0.4mAat240Vonthe240Vrange

Over-voltageTolerance 150%sustainedover-voltagewithoutdamage

PowerRequirements • 5V@6mAwithLEDsoff• 5V@40mAwithLEDson

VisualIndicators LogicpoweredLEDs.Canbedisabledtoconservepower

FieldTerminations 12to22AWG,15Acontacts

Dimensions 74mmwidex124mmhighx45mmdeep(2.90in.x4.90in.x1.80in.)

Mounting 7.5x35DINrail

Packaging Corrosionresistantzincplatedsteelwithblackenamelpaint

Environment • 5%RHto95%RH,non-condensing• –40ºCto70ºC(–40ºFto158ºF)operation• –40ºCto85ºC(–40ºFto185ºF)storage

Safety • ClassI,Division2,GroupsA,B,CandDandCSAcertifiedtoUL508standards• ATEXII3GandIECEx:ExnAIICT4perEN60079-15,protectiontypen(Zone2)(5414-24only)• MaximumpermittedvoltageinCanadaorNorthAmericais240VAC• MaximumpermittedvoltageoutsideofCanadaorNorthAmericais30VAC/42.4PK/60VDC

Model Part Number Signal Range

5414-24 TBUX297378 12/24VAC/DC,ATEXandIECEx

5414-48 TBUX297379 48VAC/DC(NotavailableoutsideofNorthAmerica)

5414-120 TBUX297380 115/125VAC/DC(NotavailableoutsideofNorthAmerica)

5414-240 TBUX297381 240VAC/DC(NotavailableoutsideofNorthAmerica)

Note:Modulenotsupportedon16-bitSCADAPackplatform(SCADAPack,SCADAPackLight,SCADAPackPlus,SCADAPack100andSCADAPackLP)

Disclaimer:SchneiderElectricreservestherighttochangeproductspecifications.Formoreinformationvisitwww.schneider-electric.com.

28

Product Data Sheet 5411 – Digital output moduleSpecifications

5411 Digital output module

General

OutputPoints 32

OutputRating • 1.0Amaximum• 0.35Vmaximumdropat1.0A• 0.05Vmaximumdropat0.1A

TransientProtection • 2.5kVsurgewithstandcapabilityasperANSI/IEEEC37.90.1-1989• Inductiveloadprotectiondiodesincluded

Isolation • Isolatedin2groupsof16• Isolation500VAC/DCfromchassisandlogicground

Terminations • 2:9andtwo10pole,removableterminalblocks• 12to22AWG,15Acontacts

PowerRequirements • 5V@150mAwithallLEDsandoutputsturnedon• 5V@40mAwithallLEDsdisabledandalloutputsturnedon• 24V@5mAwithalloutputsON• 8Vmin.,30Vmax

VisualIndicators 32:RedLED’s,canbedisabledtoconservepower

Dimensions 144mmwidex127mmhighx45mmdeep(5.65in.x5.00in.x1.80in.)

Mounting 7.5x35DINrail

Packaging Corrosionresistantzincplatedsteelwithblackenamelpaint

Environment 5%RHto95%RH,non-condensing,-40°Cto70°C(-40°Fto158°F)

Safety cCSAusandcULusClassI,Division2HazardousAreaRating,UL508listed

PartNumber TBUX297246

Disclaimer:SchneiderElectricreservestherighttochangeproductspecifications.Formoreinformationvisitwww.schneider-electric.com.

29

Product Data Sheet 5415 – Compact relay digital output moduleSpecifications

5415 Compact relay digital output module

General

NumberofDigitalOutputs 12

Type • FormAContacts(Normallyopen),DryContactorSolidStateRelayvariants• 4contactspercommon

ContactRating • 12Amaximumpercommon• DryContactVersion:3A,30VDCor250VAC(Resistive)• SolidStateRelayVersion:60VDCmax.,3Amax.at50°C(122°F),2Amax.at70°C(158°F)

SwitchingCapacity(DryContactVersion)

• 5A,30VDC(150WResistive)• 5AX250VAC(1250VAResistive)

5VPowerRequirements 5mAQuiescentDryContactversion: 150mArelayson,LEDson 130mArelayson,LEDsoff Peakcurrentduringoff-to-ontransitionofany,orallrelays- 280mAtotalfor15msdurationSolidStateRelayversion: Relayson,LEDson-144mA Relayson,LEDsoff-120mA

10-30VDCPowerRequirements

DryContactversion: 1.0Wmaximumwith1.65Wpeakfor15msdurationsSolidStateRelayversion: 1.0Wmaximum

VisualIndicators LogicpoweredLEDs.Canbedisabledtoconservepower

FieldTerminations 12to22AWG,15Acontacts

Dimensions 74mmwidex124mmhighx45mmdeep(2.90in.x4.90in.x1.80in.)

Mounting 7.5x35DINrail

Packaging Corrosionresistantzincplatedsteelwithblackenamelpaint

Environment • 5%RHto95%RH,non-condensing• –40ºCto70ºC(–40ºFto158ºF)operation• –40ºCto85ºC(–40ºFto185ºF)storage

Safety • ClassI,Division2,GroupsA,B,CandDandCSAcertifiedtoUL508standards• ATEXII3GandIECEx:ExnAIICT4perEN60079-15,protectiontypen(Zone2)(5415-Aonly)• MaximumpermittedvoltageinCanadaorNorthAmericais240VAC• MaximumpermittedvoltageoutsideofCanadaorNorthAmericais30VAC/42.4PK/60VDC

Model Part Number Signal Range

5415 TBUX297382 12PointCompactMechanicalRelayOutputModule

5415-A TBUX297384 12PointCompactSolid-StateRelayOutputModule,ATEXandIECEx

Note:Modulenotsupportedon16-bitSCADAPackplatform(SCADAPack,SCADAPackLight,SCADAPackPlus,SCADAPack100andSCADAPackLP)

Disclaimer:SchneiderElectricreservestherighttochangeproductspecifications.Formoreinformationvisitwww.schneider-electric.com.

30

Product Data Sheet 5606 – Analog/digital I/O moduleSpecifications

5606 Analog/digital I/O module

General

DigitalInputPoints • 32• Factoryconfigurable:12/24V,48V,115/125V,240V• 150%sustainedover-voltagewithoutdamage

DigitalOutputPoints • 16• FormA(Normallyopen)relaycontacts• Rating:3A,30Vdcor240Vac(Resistive)• 4contactspercommon

AnalogInputPoints • 8• Single-ended• Softwareconfigurable,0-20mA,4-20mA,0-10V,0-5V• Resolution:15-bitoverthe0-10Vand0-20mAmeasurementrange• Accuracy:±0.1%offullscaleat25°C(77°F),±0.2%overtemperaturerange

AnalogOutputs • 2(withoptional5305module)• 0-20mAsourcing• Resolution:12-bit• Accuracy:(specifiedfrom0.5-20mA.),±0.15%offullscaleat25°C(77°F)• ±0.25%offullscaleovertemperaturerange

5VPowerRequirements • DigitalOutputRelaysContinuous-190mA,DigitalOutputRelaysPeak-375mA• LED’s-195mA,Quiescent-30mA• Total-415to600mA

11-30VDCPowerRequirements • 12mAplusanalogoutputs• 9-30Vdcoperationpossiblewhenoptional5305analogoutputsnotinstalled

Addressing 8modules,DIPswitch-selectable

Dimensions 213mmwidex155mmhighx72mmdeep(8.40in.x6.13in.x1.80in.)

Mounting 7.5x35DINrail

Packaging Corrosion-resistantzinc-platedsteelwithblackenamelpaint

Environment 5%RHto95%RH,non-condensing,–40°Cto70°C(–40°Fto158°F)

Safety cCSAusandcULusClassI,Division2HazardousAreaRating,UL508listedATEXII3GandIECEx:ExnAIICT4perEN60079-15,protectiontypen(Zone2),(24VDI/SolidStateRelaytypeonly)

PartNumber TBUX297328 (5606-24)TBUX297329 (5606-48)TBUX297330 (5606-120)TBUX297331 (5606-240)TBUX297334 (5606-24-AO)TBUX297335 (5606-48-AO)TBUX297336 (5606-120-AO)TBUX297337 (5606-240-AO)TBUX297498 (5606-24-A)TBUX297499 (5606-48-A)TBUX297500 (5606-120-A)TBUX297501 (5606-240-A)TBUX297502 (5606-24-AO-A)TBUX297503 (5606-48-AO-A)TBUX297504 (5606-120-AO-A)TBUX297505 (5606-240-AO-A)

Disclaimer:SchneiderElectricreservestherighttochangeproductspecifications.Formoreinformationvisitwww.schneider-electric.com.

31

Product Data Sheet 5607 – Analog/digital I/O moduleSpecifications

5607 Analog/digital I/O module

General

DigitalInputPoints • 16• Factoryconfigurable:12/24V,48V,115/125V,240V• 150%sustainedover-voltagewithoutdamage

DigitalOutputPoints

ContactRataing

• 10• FormAContacts(Normallyopen)• DryContactRelayorDCSolidStateRelay• 5contactspercommonDryContactRelayVersion:• 3A,30Vdcor250Vac(Resistive)DCSolidStateRelayVersion:• 3Acontinuousmaximumat50ºC(122ºF)ambientTBC• 2Acontinuousmaximumat70ºC(158ºF)ambientTBC• 9Apeak,100ms

AnalogInputPoints • 8• Single-ended• Softwareconfigurable,0-20mA,4-20mA,0-10V,0-5V• Resolution:15bitsoverthe0-10Vmeasurementrange,14bitsoverthe0-5Vand0-20mAmeasurementrange• Accuracy:±0.1%offullscaleat25°C(77°F),±0.2%overtemperaturerange

AnalogOutputs • 2(withoptional5305module)• 0-20mAsourcing• Resolution:12-bit• Accuracy:(specifiedfrom0.5-20mA.),±0.15%offullscaleat25°C(77°F)• ±0.25%offullscaleovertemperaturerange

5VPowerRequirements DryContactRelayversion:• DigitalOutputRelaysContinuous-105mAplus90mAtransients(15ms)whenrelaysswitchon.• LEDs-107mA• Quiescent-23mA• Total-upto235mASolidStateRelayversion:• DigitalOutputRelaysContinuous-100mA• LEDs-110mA• Quiescent-23mA• Total-upto233mA

11-30VDCPowerRequirements • 10.3mAplusanalogoutputs• 9-30Vdcoperationpossiblewhenoptional5305analogoutputsnotinstalled

Addressing 8modules,DIPswitch-selectable

Dimensions 144mmwidex165mmhighx72mmdeep(5.65in.x6.50in.x1.80in.)

Mounting 7.5x35DINrail

Packaging Corrosion-resistantzinc-platedsteelwithblackenamelpaint

Environment 5%RHto95%RH,non-condensing,–40°Cto70°C(–40°Fto158°F)

Safety • ClassI,Division2GroupsA,B,CandDHazardousLocationsandCSAcertifiedtoUL508standards• ATEXII3GandIECEx:ExnAIICT4perEN60079-15,protectiontypen(Zone2),(24VDI/SolidStateRelaytypeonly)

PartNumber TBUX297478 (5607-24)TBUX297479 (5607-48)TBUX297480 (5607-120)TBUX297481 (5607-240)TBUX297482 (5607-24-AO)TBUX297483 (5607-48-AO)TBUX297484 (5607-120-AO)TBUX297485 (5607-240-AO)TBUX297490 (5607-24-A)TBUX297491 (5607-48-A)TBUX297492 (5607-120-A)TBUX297493 (5607-240-A)TBUX297494 (5607-24-AO-A)TBUX297495 (5607-48-AO-A)TBUX297496 (5607-120-AO-A)TBUX297497 (5607-240-AO-A)

Note:5607moduleisnotsupportedbytheSCADAPack100andSCADAPackER.

Disclaimer:SchneiderElectricreservestherighttochangeproductspecifications.Formoreinformationvisitwww.schneider-electric.com.

32

Product Data Sheet 5608Specifications

5608 Digital I/O module

General

DigitalInputPoints • 12• 12-24V• 150%sustainedover-voltagewithoutdamage

DigitalOutputPoints

ContactRating

• 6• FormAContacts(Normallyopen)• DryContactRelay• 5contactspercommon• 3A,30Vdcor250Vac(Resistive)

5VPowerRequirements • DigitalOutputRelaysContinuous-105mAplus90mAtransients(15ms)whenrelaysswitchon.• LEDs-107mA• Quiescent-23mA• Total-upto235mA

11-30VDCPowerRequirements • 10.3mA• 9-30Vdcoperationpossible

Addressing 8modules,DIPswitch-selectable

Dimensions 144mmwidex165mmhighx72mmdeep(5.65in.x6.50in.x1.80in.)

Mounting 7.5x35DINrail

Packaging Corrosion-resistantzinc-platedsteelwithblackenamelpaint

Environment 5%RHto95%RH,non-condensing,–25°Cto70°C(–13°Fto158°F)

Certifications • CEmarking• C-Tick• UL508(US/Canada)–cULus• FCC/EN61000-6emissions&immunity

PartNumber TBUX297177 (5608-24)

33

Product Data Sheet 5610Specifications

5610 Digital I/O module

General

DigitalInputPoints • 16• 12-24V• 150%sustainedover-voltagewithoutdamage

DigitalOutputPoints

ContactRating

• 10• FormAContacts(Normallyopen)• DryContactRelay• 5contactspercommon• 3A,30Vdcor250Vac(Resistive)

5VPowerRequirements • DigitalOutputRelaysContinuous-105mAplus90mAtransients(15ms)whenrelaysswitchon.• LEDs-107mA• Quiescent-23mA• Total-upto235mA

11-30VDCPowerRequirements • 10.3mA• 9-30Vdcoperationpossible

Addressing 8modules,DIPswitch-selectable

Dimensions 144mmwidex165mmhighx72mmdeep(5.65in.x6.50in.x1.80in.)

Mounting 7.5x35DINrail

Packaging Corrosion-resistantzinc-platedsteelwithblackenamelpaint

Environment 5%RHto95%RH,non-condensing,–25°Cto70°C(–13°Fto158°F)

Certifications • CEmarking• C-Tick• UL508(US/Canada)–cULus• FCC/EN61000-6emissions&immunity

PartNumber TBUX297178 (5610-24)

Note:The5608and5610modulesareforusewithSCADAPackERTUsonly.Disclaimer:SchneiderElectricreservestherighttochangeproductspecifications.Formoreinformationvisitwww.schneider-electric.com.

34

Product Data Sheet 5103 – Uninterruptible power supplySpecifications

5103 Uninterruptible power supply

General

AC/DCInput • 16to24VACfor5/24Voutputsoperational,24VACrequiredforbatterycharging• 14.5+/-0.5Vfor5/24Voutputsoperational,20VDCrequiredforbatterycharging

DC/BatteryInput Turnonat11.5V±0.3VDC,Turnoffat10.5V±0.5VDC,Maximuminputis36VDC

InputPower 35VAmaximumat24VAC,1.9Aat13.5VDC

Outputs 5VDCat2.0ampere,24VDCat0.5ampere,17Wtotalavailablefromthetwooutputs11to14VDCbatterychargerat200mA(factoryadjustedto13.5Vforgelledelectrolytelead/acidbattery)

Mode Isolatedswitch-mode,30KHzswitchfrequency

LineRegulation <1%overoperatingrange

LoadRegulation • 5Voutput:5.15V±1%overoperatingrange• 24Voutput:±17%

OutputRipple • 5Voutput:<10mVat20oC(68oF)

• 24Voutput:<50mVat20oC(68oF)

VisualIndicators 5Vand24VgreenLEDsshowpowerstatus

PowerRequirements 35VAmaximum@24VAC,[email protected]

Terminations 10pole,removableterminalblock,12to22AWG,15ampcontacts

Dimensions 108mmwidex118mmhighx44mmdeep(4.25in.x4.625in.x1.75in.)

Mounting 7.5x35DINrail

Packaging Corrosionresistantzincplatedsteelwithblackenamelpaint

Environment • 5%RHto95%RH,non-condensing• -40°Cto60°C(-40°Fto140°F)

Safety Non-IncendiveElectricalEquipmentforUseinClassI,Division2GroupsA,B,CandDHazardousLocations.TemperatureCodeT4at60°Cambient.ULListedtothefollowingstandards:• CSAStd.C22.2No.213-M1987-HazardousLocations.• CSAStd.C22.2No.142-M1987-ProcessControlEquipment.• ULStd.No.1604-Hazardous(Classified)Locations.• ULStd.No.508-IndustrialControlEquipment.

PartNumber TBUX297102

Accessories

Model Part Number Description

1206 TBUX294034 12V6AHgelledelectrolytebattery

ACX-24 TBUX294000 120/24VAC,40VAtransformer

ACX-24E TBUX294167 220/24VAC,40VAtransformer

Disclaimer:SchneiderElectricreservestherighttochangeproductspecifications.Formoreinformationvisitwww.schneider-electric.com.

35

Product Data Sheet 5902 – Bell 202 modemSpecifications

5902 Bell 202 modem

General

DataRate 1200baud

TransmitCarrier Switchedorconstant

Duplex Fullorhalf.HalfduplexrequiresDTEtoimplementhardwareRTS/CTShandshake

Wires Twoorfour

TransmitLevel -35dBmto0dBminto600Ω,potentiometeradjustable

ReceiveSensitivity -30dBmto+3dBm,potentiometeradjustableto-40dBm

OutputandInputImpedance 600Ωbalanced,transformerisolated

Anti-Streaming None,10Sec,30Sec,60Sec

RTS/CTSDelay • Wire:25ms,50ms,125ms,250ms• Radio:67ms,133ms,266ms,1000ms

CTSHoldTime 1ms,8ms

CarrierDetectDelay • Wire:19ms,30ms,51ms,92ms• Radio:33ms,67ms,133ms,265ms

CarrierLossDelay 6ms,10ms,23ms,39ms,constantcarrierreceptionhalfduplex

CarrierDetectLevel -30dBm,adjustablefrom-20dBmto-40dBm

RadioTransmitKeyOutput Opticalcoupleropencollectortransistor,5to15VDC,25mA

VisualIndicators TransmittedDataLED,ReceivedDataLED,CleartoSendLED,RequesttoSendLED,CarrierDetectLED,RadioKeyOutputLED

PowerRequirements • 5902-5V@60mA• 5902SA-115VACat10VA

Terminations 8pole,removableterminalblock,RJ45

Dimensions 4.25inch(108mm)wide,4.625inch(118mm)high,1.75inch(44mm)deep

Packaging Corrosion-resistantzinc-platedsteelwithblackenamelpaint

Environment 5%RHto95%RH,non-condensing,-40°C/Fto60°C/140°F

Safety cCSAusandcULusClassI,Division2HazardousAreaRating,UL508listed

Model Part Number Description

5902 TBUX297120 Bell202modemmodule,1200baud,FSK,2/4wire,withradioPTTkeycontrol&RFcarrierdetect

5902SA TBUX297194 Sameas5902butwitha115VACADadapterforconnectiontootherPC’sorRS-232devices

5902SAF TBUX297195 Sameas5902SAbutwithafullduplextohalfduplexconverter-fordeviceswithoutRTS/CTSsupport

Note:Serialcommunicationcablesoldseparately

Disclaimer:SchneiderElectricreservestherighttochangeproductspecifications.Formoreinformationvisitwww.schneider-electric.com.

36

Product Data Sheet 5908 – Wireless data transceiverSpecifications

5908 Wireless data transceiver

General

Frequency 902to928MHz,230kHzbandwidth

Transmitter

OutputPower 1mWto1W(+30dBm)

Range 60miles(Lineofsightwithunitygainantenna)

Modulation SpreadSpectrumGFSK,120kBs-170kBs

SpreadingMethod Frequencyhopping

Receiver

Sensitivity -108dBmfor10-6BERstandardspeed,-111dBmfor10-6BERlowspeed-110dBmfor10-4BERstandardspeed,-113dBmfor10-4BERlowspeed

Selectivity 20dBatfc±115kHz,60dBatfc±145kHz

SystemGain 140dB

Data Transmission

ErrorDetection 32BitCRC,resendonerror

ForwardErrorCorrection(lowspeed)

(24,12)Golay,retransmitonuncorrectableerror

DataEncryption Substitution,dynamickey

MaxLinkThroughput 115Kbaudstandardspeed,38.4Kbaudlowspeed

DataInterface RS-232/RS-4851200baudto230.4Kbaud,asynch,fullduplex,RJ45connector

Power Requirements

SupplyVoltage 7to30VDC(900MHzmodel)10to30UDC(2.46GHzmodel)5908 5908-2.4GmA@12VDC mA@30VDC mA@12VDC mA@30VDC

Transmit 500 200 325 150

Receive 86 43 115 60

Idle 21 12 30 13

Sleep 6 3 5 2

OperatingModes Point-to-Point,Point-to-Multipoint,Peer-to-Peer,StoreandForwardRepeater

OperatingEnvironment -40°C/Fto75°C/167°F,0to95%humiditynon-condensing

Model Part Number Description

5908 TBUX297270 RadioTransceiver,FreeWave900MHzSpreadSpectrum,poweredby6-30VoltsDC

5908-2.4G* TBUX297283 RadioTransceiver,FreeWave2.4GHzSpreadSpectrum,poweredby6-30VoltsDC

Note:Serialcommunicationcablesoldseparately

*Notavailableinallareas–ConsultSchneiderElectricforavailabilityinyourarea

Disclaimer:SchneiderElectricreservestherighttochangeproductspecifications.Formoreinformationvisitwww.schneider-electric.com.

37

Product Data Sheet 5908-WO2 – Wireless data transceiverSpecifications

5908-WO2 Wireless data transceiver

General

Frequency Upto128frequencieswithin902-928MHz.,configurablein3.2MHzzones

Transmitter

OutputPower 1.0W(+30dBm)maximum(atantennaconnector)

Modulation CPFSK

SpreadingMethod Frequencyhoppingbasedonnetworkaddress

Receiver

Type Doubleconversionsuperheterodyne

Sensitivity -108dBm@1X10-6BER

NetworkAddresses 65,000

Data Transmission

ErrorDetection CRC16;Resendonerror

DataInterface RS-232/RS-485(userselectable)

MaxLinkThroughput Continuousupto115.2kbps

BaudRates 1.2to115.2kbps

Power Requirements

Power 7.5Wmax

SupplyVoltage 9to30VDC

TransmitCurrent [email protected]

ReceiveCurrent [email protected]

SleepModeCurrent [email protected]

OperatingModes Point-to-Point,Point-to-Multipoint,Store-and-ForwardRepeater

OperatingEnvironment -40°C/Fto70°C/158°F,5%RHto95%RH,non-condensing

Model Part Number Description

5908-WO2 TBUX297310 RadioTransceiver,MDS900MHzSpreadSpectrum,poweredby9-30VoltsCD

Note:Serialcommunicationcablesoldseparately

Disclaimer:SchneiderElectricreservestherighttochangeproductspecifications.Formoreinformationvisitwww.schneider-electric.com.

38

Product Data Sheet 5910 – Ethernet switchSpecifications

5910 Ethernet switch

General

EthernetSwitchType 5ports,unmanaged,store&forward,10/100BaseT

EthernetTerminations RJ45ports(shielded)

Protocols IEEE802.3,IEEE802.3u(TBC),IEEE802.3x

SpeedandConnection • Auto-detecting10/100Mbpsoperation,• AutoMDI/MDI-Xoperation(noneedforcross-wiredcables)

MemoryBandwidth 1.4Gbps

DuplexOperation FullduplexIEEE802.3xandhalfduplexbackpressureflowcontrol

MACAddressing Dedicatedlookupenginewith1KMACaddresses.Learning,agingandmigration

EthernetIsolation 1500Vrms

VisualIndicators Eachporthas-ACT/LINKand10/100(Speed)indicators

InputPower • ExternalPower:11-30Vdc• 1.8Wat12Vdc• 2.2Wat30Vdc• BusPower:5Vat375mA

InputPowerTerminations • 4poleterminalstripandremovableterminalblock.• 12to22AWG

Dimensions .25inch(144mm)wide,4.625inch(118mm)high,2.00inch(51mm)deep

Mounting Desktop,rubberfeetor7.5x35DINrail

Packaging Corrosionresistantzincplatedsteelwithblackenamelpaint

Environment 5%RHto95%RH,non-condensing–40oCto70oC–40oFto158oF

Model Part Number Description

5910 TBUX297288 EthernetSwitch,5port,10/100Mbautodetect,12-24Vdcpower

5910SA TBUX297289 Sameas5910,withtheadditionofa115Vacadapter

Disclaimer:SchneiderElectricreservestherighttochangeproductspecifications.Formoreinformationvisitwww.schneider-electric.com.

39

Product Data Sheet 5915 – SDI-12 interface moduleSpecifications

5915 SDI-12 interface module

General

SDI-12busTerminations • 12to22AWG• 15Acontacts

Dimensions 2.90inch(74mm)wide,4.90inch(124mm)high,1.80inch(45mm)deep

Packaging Corrosionresistantzincplatedsteelwithblackenamelpaint

Environment • 5%RHto95%RH,non-condensing• –40oCto70oC(–40oFto158oF)operation• –40oCto85oC(–40oFto185oF)storage

Addressing Nonerequired

Power Requirements

12V • 6mAIdle• 6.5mAactive,withLEDsdisabled• 24mAactive,continuoustransmit,bothLEDson

Communications – Port P1

PortType RS-232compatibleserialport

Connector 8pinmodularjack(RJ45)

PinsUsed Transmit,ReceiveandGround

Connection DTE

Protocol SDI-12only

Baud 1200bps(asperSDI-12protocol)

Bits 7(asperSDI-12protocol)

Parity Even(asperSDI-12protocol)

HardwareHandshaking None

Protection 15kVESDprotected

Communications – Port P2

PortType SDI-12port

Connector 4-wayremovableterminalblock

PinsUsed 12V,Ground,SDI-12data

Protocol SDI-12only

Protection MOVandcurrent-limit

Indicators

Tx IlluminateswhentransmittingdatafromMasterControllertoaslavedeviceonthebus

Rx IlluminateswhenreceivingdatafromaslavedeviceANDwhenevertheMasterControllertransmits.

Model Part Number Description

5915 TBUX297475 SDI-12Module,serialtoSDI-12converterforSCADAPack32andSCADAPack3xx-Series controllers,c/wconfig.CD

Disclaimer:SchneiderElectricreservestherighttochangeproductspecifications.Formoreinformationvisitwww.schneider-electric.com.

Schneider Electric

Telemetry & Remote SCADA Solutions48 Steacie DriveKanata, ON, K2K 2A9, CanadaPhone: +1 (613) 591-1943Fax: +1 (613) 591-1022www.schneider-electric.com

Document Number TBUL00001-15 December 2012

© 2

012

Sch

neid

er E

lect

ric. A

ll rig

hts

rese

rved

.

Make the most of your energy

SCADAPack E