hazardous building materials assessment report · 2014-05-29 · the objective of the assessment...
TRANSCRIPT
Pinchin West Ltd. Suite #200, 13775 Commerce Parkway, Richmond, BC V6V 2V4
Tel: 604.244.8101 Fax: 604.244.8491 Toll-free: 877.322.4744 www.pinchinwest.com
Hazardous Building Materials Assessment Report
Berwick House 1375 Nicola Street
Vancouver, BC
Prepared for: Colliers International
15th Floor, 200 Granville Street Vancouver, BC. V6C 2R6
Attention: Cristina Toader Senior Property Manager
May 28, 2014
Pinchin West Project: 12661K-22
Copyright © by Pinchin West Ltd.
EXECUTIVE SUMMARY
© 2014 Pinchin West Ltd. Page i
Colliers International (Client) retained Pinchin West Ltd. (PWL) to conduct a hazardous building material assessment of Berwick House located at 1375 Nicola Street. The assessment was performed on May 12, 2014.
The objective of the assessment was to identify specified hazardous building materials, evaluate their current condition and potential exposure risk to building occupants and develop corrective action plans as required. The findings from this assessment should only be used for the purpose of building management and routine maintenance. The results of this assessment are not intended to be used for construction, renovation, demolition or project tendering purposes.
Summary of Findings
The following is a summary of significant findings. Refer to the body of the report for specific findings and testing results.
Asbestos: Asbestos-containing materials (ACM) were confirmed to be present as follows:
Parging cement insulation on pipe elbows in the Sprinkler Room (Location 7) and the Parkade (Location 25); and
Aircell pipe insulation on straight pipe sections in the Parkade (Location 25).
Lead: Lead was confirmed present in select paints/surface coatings and is present in emergency light batteries and lead flashing on rooftop drainage pipes, and pipe fittings.
Silica: Crystalline silica is present in concrete, mortar, brick, masonry, ceramics, granite, slate, stone, asphalt, etc., where present in the building.
Mercury: Mercury vapour is present in lamp bulbs and fluorescent light tubes throughout the building. Mercury liquid is present in thermostats throughout the building.
Polychlorinated Biphenyls (PCBs): The building has not been comprehensively re-lamped with new energy efficient light ballasts and lamps, and as such, a percentage of light ballasts will be pre-1980 and contain PCBs.
Halocarbons: No halocarbons were observed during the assessment.
Mould: No mould-impacted items were observed during the assessment.
Summary of Recommendations
The following recommendations are made at this time; please refer to Section 5.0 of this report for detailed recommendations on the hazardous materials identified.
1. Remediate the following materials:
Remove asbestos-containing parging cement insulation on pipe elbow in poor condition in the Sprinkler Room (Location 7) and the Parkade (Location 25).
Remove damaged asbestos-containing air-cell pipe insulation on pipe straight in poor condition in the Parkade (Location 25).
This Executive Summary is subject to the same standard limitations as contained in the report and must be read in conjunction with the entire report.
TABLE OF CONTENTS
© 2014 Pinchin West Ltd. Page ii
1.0 INTRODUCTION AND SCOPE ............................................................................. 1 1.1 Scope of Assessment ................................................................................. 1 1.2 Limitations on Scope ................................................................................... 1
2.0 GENERAL METHODOLOGY ................................................................................ 2
3.0 BACKGROUND INFORMATION .......................................................................... 2 3.1 Building Description .................................................................................... 2
4.0 FINDINGS ............................................................................................................. 3 4.1 Asbestos ..................................................................................................... 3 4.2 Lead ............................................................................................................ 5 4.3 Silica ........................................................................................................... 5 4.4 Mercury ....................................................................................................... 6 4.5 Polychlorinated Biphenyls ........................................................................... 6 4.6 Halocarbons ................................................................................................ 6 4.7 Mould .......................................................................................................... 6
5.0 RECOMMENDATIONS ......................................................................................... 6 5.1 General ....................................................................................................... 6 5.2 Building Demolition or Renovation .............................................................. 7 5.3 Remedial Recommendations ...................................................................... 7
6.0 STANDARD LIMITATIONS ................................................................................... 8
7.0 CLOSURE ............................................................................................................. 9
8.0 REFERENCES .................................................................................................... 10
APPENDICES
Appendix I Specific Methods and Criteria
Appendix II Locations Summary
Appendix III Hazardous Materials Summary
Appendix IV Hazardous Materials Findings by Location
Appendix V-A Asbestos Laboratory Certificates
Appendix V-B Lead Laboratory Certificates
Appendix VI Photographs
Appendix VII Drawings
Hazardous Building Materials Assessment Final Report 1375 Nicola Street, Vancouver BC May 28, 2014 Colliers International Pinchin West Project: 12661K-22
© 2014 Pinchin West Ltd. Page 1
1.0 INTRODUCTION AND SCOPE
Colliers International (Client) retained Pinchin West Ltd. (PWL) to conduct a hazardous building materials assessment of Berwick House located at 1375 Nicola Street, Vancouver BC.
The assessment was performed by Nadia Slakov, Technologist on May 12, 2014. The assessor was accompanied by Margaret Van Der Gun, Building Manager for Colliers International during the assessment.
The objective of the assessment was to identify specified hazardous building materials, evaluate their current condition and potential exposure risk to building occupants and to recommend corrective action plans as required.
1.1 Scope of Assessment
The assessment was performed to establish the location and type of hazardous building materials incorporated in the structure(s) and its finishes.
For the purpose of the assessment, and this report, hazardous building materials are defined as those containing the following:
Asbestos;
Lead;
Silica;
Mercury;
Polychlorinated biphenyls (PCBs);
Halocarbons; or
Mould.
The assessed area consisted of all parts of the building. This assessment did not include demolition of building materials or equipment to view concealed conditions behind solid walls, enclosures shafts and chases.
1.2 Limitations on Scope
The findings from this assessment should only be used for the purpose of building management and routine maintenance. The results of this assessment are not intended to be used for construction, renovation, demolition or project tendering purposes.
This assessment excluded the following:
Owner or occupant articles (e.g. stored items, furniture, appliances, etc.);
Underground materials or equipment (e.g. vessels, drums, underground storage tanks, pipes, etc.);
Building envelope, structural components or items where sampling may cause consequential damage to the property (e.g. fire doors, exterior wall cavities, roofing materials, caulking and putties);
Hazardous Building Materials Assessment Final Report 1375 Nicola Street, Vancouver BC May 28, 2014 Colliers International Pinchin West Project: 12661K-22
© 2014 Pinchin West Ltd. Page 2
Inaccessible items or materials (e.g. exterior soffits, material concealed behind structure, materials above solid ceilings, material below flooring, items inside ductwork, adhesives);
Energized systems (e.g. internal boiler components, elevators, mechanical or electrical components);
Controlled products (e.g. stored chemicals, operational or process-related substances);
Other components (e.g. settled dust, mastic, coatings, etc.; and
Inaccessible areas or locked rooms.
2.0 GENERAL METHODOLOGY
A representative assessment was conducted in the building to identify the hazardous materials listed in the scope of work and included all common areas of the building and a minimum of 10% of the suites on each floor.
Representative samples were collected and/or visual observation of the hazardous materials was conducted. A risk assessment was conducted to develop corrective action or ongoing management strategies.
A unique location number was assigned to each room or homogenous area to identify each part or location of the building.
Specific methods and criteria used in this assessment are further detailed in Appendix I.
3.0 BACKGROUND INFORMATION
3.1 Building Description
The building was originally constructed in 1957 and is 9 storeys above grade with 1 level below grade. The use of the building is residential apartments. The total area is approximately 35,000 ft2.
A summary of the site building, including a basic description of the building systems is provided below:
Item/System Details
Structure Concrete
Exterior Cladding Concrete
HVAC Boiler and hot water heating to radiators
Roof Built-up roofing
Flooring Vinyl sheet flooring, concrete, ceramic tile, laminate, carpet
Hazardous Building Materials Assessment Final Report 1375 Nicola Street, Vancouver BC May 28, 2014 Colliers International Pinchin West Project: 12661K-22
© 2014 Pinchin West Ltd. Page 3
Item/System Details
Interior Walls Concrete block, plaster
Ceilings Plaster
4.0 FINDINGS
The following sections present the results of the hazardous materials assessment and include a discussion of significant findings for each material.
Information collected during the assessment has been presented in this report as follows:
Assigned location numbers, location descriptions, and inaccessible areas are listed in Appendix II;
A summary of the hazardous materials inspection and testing results, including specific material descriptions and locations is provided in Appendix III;
Room-by-room details of material locations, assessment, sample results, quantities, etc., are presented in Appendix IV;
Copies of the laboratory analytical reports are provided in Appendix V;
Photographs referenced in the sections below are provided in Appendix VI; and
Drawings, indicating location numbers, sample locations are provided in Appendix VII.
4.1 Asbestos
4.1.1 Suspect ACM Not Present
The following materials are typically suspected to contain asbestos but were not observed in the building and are not discussed in the report findings:
Spray-applied fireproofing or thermal insulation;
Acoustic ceiling tiles;
Drywall joint compound; and
Vinyl floor tiles.
4.1.2 Texture Finishes (Acoustic/Decorative)
Texture finish is present on ceilings throughout the building. Texture finish was determined to be non-asbestos.
4.1.3 Pipe Insulation
Asbestos-containing parging cement is present on pipe elbows on piping systems in the Sprinkler Room (Location 7) and the Parkade (Location 25). Parging cement is a friable
Hazardous Building Materials Assessment Final Report 1375 Nicola Street, Vancouver BC May 28, 2014 Colliers International Pinchin West Project: 12661K-22
© 2014 Pinchin West Ltd. Page 4
insulation, jacketed with canvas and is in good condition, with the exception of one pipe elbow in the Sprinkler Room (Location 7) and one pipe elbow in the Parkade (Location 25) that are in poor condition. Refer to Photo No. 1 to 3 in Appendix VI.
Asbestos-containing preformed insulation (known as “aircell’,) is present on straight sections of steam system pipes in the Parkade (Location 25). The pipe insulation is friable, jacketed with canvas and is in good condition, with the exception of 15 linear feet in fair condition and one linear foot in poor condition. Refer to Photos No. 4 to 5 in Appendix VI.
Remaining pipes were inspected and non-asbestos fibreglass insulation is present on straight sections of piping systems. There was no asbestos parging cement noted on the seams of the insulation at the locations inspected.
4.1.4 Duct Insulation
All ducts are either un-insulated or insulated with non-asbestos fibreglass.
4.1.5 Mechanical Equipment Insulation
All mechanical equipment is either un-insulated or insulated with non-asbestos fibreglass.
4.1.6 Vermiculite
Concrete block walls and/or solid ceilings were not demolished to determine if vermiculite is present. Loose fill vermiculite is not present in accessible areas.
4.1.7 Plaster
All plaster walls and ceilings were determined to be non-asbestos.
4.1.8 Vinyl Sheet Flooring
A total of one distinct types of vinyl sheet flooring is present in the assessed area, and was determined to be non-asbestos.
4.1.9 Other Building Materials
Cementitious firestopping was sampled and determined to be non-asbestos.
4.1.10 Presumed Asbestos Materials
A number of materials which might contain asbestos were not sampled during our assessment due to limitations in scope and methodology. Where present, these materials must be presumed to be an asbestos material and are best sampled immediately prior to disturbance. Materials presumed to contain asbestos include:
roofing, felts and tar
concrete floor levelling compound
elevator and lift brakes
Hazardous Building Materials Assessment Final Report 1375 Nicola Street, Vancouver BC May 28, 2014 Colliers International Pinchin West Project: 12661K-22
© 2014 Pinchin West Ltd. Page 5
electrical components or wiring within control centers, breakers, motors or lights, insulation on wiring
insulation under metal clad boilers and vessels
vermiculite in concrete block wall cavities
adhesives and duct mastics
caulking
paints and coatings
mechanical packing, ropes and gaskets
fire resistant doors or metal clad finishes
exterior cladding
4.2 Lead
4.2.1 Paints and Surface Coatings
Lead-containing paints were found in various areas. Refer to the Appendices for complete testing results. All lead-based paints were found to be in good condition.
4.2.2 Lead Products and Applications
Lead-containing batteries are present in emergency lighting units found throughout the building.
4.2.3 Presumed Lead Materials
Lead may be present in a number of materials which were not sampled as part of our assessment. The following materials, where found, should be considered lead-containing:
caulking in bell and spigot fittings on cast iron pipes
electrical components, including wiring connectors, fibre optic cable sheathing, grounding conductors, and solder
glazing on ceramic tiles
4.3 Silica
Crystalline silica is a presumed component of the following building materials where present in the building:
poured or pre-cast concrete
masonry or other stonework
refractory ceramic materials in high temperature mechanical equipment
ceramic tiles, grout and plaster
concrete block, brickwork, and associated mortar compounds
Hazardous Building Materials Assessment Final Report 1375 Nicola Street, Vancouver BC May 28, 2014 Colliers International Pinchin West Project: 12661K-22
© 2014 Pinchin West Ltd. Page 6
4.4 Mercury
4.4.1 Lamp Bulbs
Mercury vapour is present in all fluorescent lamps found throughout the building.
4.4.2 Mercury-Containing Devices
Mercury is present as a liquid in a thermostat found in the Washroom (Location 6).
4.5 Polychlorinated Biphenyls
4.5.1 Lighting Ballasts
The building has not been comprehensively re-lamped with new energy efficient light ballasts and lamps, and as such, a percentage of light ballasts will be pre-1980 and contain PCBs.
4.5.2 Transformers
Transformers were not found during the assessment.
4.5.3 Presumed PCB Materials
A number of items which might contain PCBs were not sampled during our assessment. Materials presumed to contain PCBs include:
oil impregnated cables
voltage regulators
4.6 Halocarbons
Equipment containing halocarbons was not found during the assessment.
4.7 Mould
Suspect visible mould growth was not found during the assessment.
5.0 RECOMMENDATIONS
5.1 General
The following general recommendations are made at this time:
1. All asbestos-containing materials are required to be identified with labels or signs or if not practicable, other effective means. “Other effective means” can be a floor plan showing locations of ACMs.
2. When PCB ballasts are removed from service they must be packaged and incinerated in accordance with applicable regulations. All PCB must be eliminated from use and sent for destruction on or before December 31, 2025.
Hazardous Building Materials Assessment Final Report 1375 Nicola Street, Vancouver BC May 28, 2014 Colliers International Pinchin West Project: 12661K-22
© 2014 Pinchin West Ltd. Page 7
5.2 Building Demolition or Renovation
As this report is not intended for building renovation or demolition purposes; a detailed destructive assessment is recommended prior to these activities. A destructive assessment typically involves; sampling of materials presumed to be hazardous that were not sampled (i.e. roofing, window caulking, mastics), destructive testing and investigation (i.e. coring of block walls, removal of building components).
5.3 Remedial Recommendations
The following items have been identified where remedial action is recommended.
Location Hazmat Type and Quantity
Action and Procedure
Estimated Cost
Sprinkler Room (Location 7)
Asbestos parging cement insulation on one pipe elbow
Remove ACM as soon as possible.
$750.00
Parkade (Location 25)
Asbestos parging cement insulation on one pipe elbow
Remove ACM as soon as possible.
$750.00
Parkade (Location 25)
Aircell insulation 1 linear foot
Remove damaged ACM as soon as possible.
$750.00
Hazardous Building Materials Assessment Final Report 1375 Nicola Street, Vancouver BC May 28, 2014 Colliers International Pinchin West Project: 12661K-22
© 2014 Pinchin West Ltd. Page 8
6.0 STANDARD LIMITATIONS
The work performed by Pinchin West Ltd. (PWL) was conducted in accordance with generally accepted engineering or scientific practices current in this geographical area at the time the work was performed. No warranty is either expressed or implied by furnishing written reports or findings. The Client acknowledges that subsurface and concealed conditions may vary from those encountered or inspected. PWL can only comment on the environmental conditions observed on the date(s) the assessment is performed. The work is limited to those materials or areas of concern identified by the Client or outlined in our proposal. Other areas of concern may exist but were not investigated within the scope of this assignment.
PWL makes no other representations whatsoever, including those concerning the legal significance of its findings, or as to other legal matters touched on in this report, including, but not limited to, ownership of any property, or the application of any law to the facts set forth herein. With respect to regulatory compliance issue, regulatory statutes are subject to interpretation and these interpretations may change over time. PWL accepts no responsibility for consequential financial effects on transactions or property values, or requirements for follow-up actions and costs.
The liability of PWL, or its staff, will be limited to the lesser of the fees paid or actual damages incurred by the Client. PWL will not be responsible for any consequential or indirect damages. PWL is only liable for damages resulting from negligence of PWL. All claims by the Client shall be deemed relinquished if not made within two years after last date of services provided.
Information provided by PWL is intended for Client use only. PWL will not provide results or information to any party unless disclosure by PWL is required by law. Any use by a third party of reports or documents authored by PWL or any reliance by a third party on or decisions made by a third party based on the findings described in said documents, is the sole responsibility of such third parties. PWL accepts no responsibility for damages suffered by any third party as a result of decisions made or actions conducted. No other warranties are implied or expressed.
Hazardous Building Materials Assessment Final Report 1375 Nicola Street, Vancouver BC May 28, 2014 Colliers International Pinchin West Project: 12661K-22
© 2014 Pinchin West Ltd. Page 9
7.0 CLOSURE
If you have any questions, please contact Vanessa McNeil at 604-238-2941.
Authored by:
Pinchin West Ltd.
Reviewed by:
Pinchin West Ltd.
Per:
Per:
Nadia Slakov, B.Env.D, Dipl. T Technologist [email protected]
Vanessa McNeil, B.A., LEED AP Senior Project Manager [email protected]
12661K-22 1375 Nicola Street.docx
Hazardous Building Materials Assessment Final Report 1375 Nicola Street, Vancouver BC May 28, 2014 Colliers International Pinchin West Project: 12661K-22
© 2014 Pinchin West Ltd. Page 10
8.0 REFERENCES
The following legislation and documents were referenced in completing the assessment and this report:
1. Occupational Health and Safety Regulation (B.C. Reg. 296/97, as amended), under WorkSafe BC.
2. Safe Work Practices for Handling Asbestos, WorkSafe BC, 2006 Edition.
3. Hazardous Waste Regulation, BC Ministry of Environment; including amendments up to B.C. Reg. 261/2006, September 21, 2006.
4. Ozone Depleting Substances and Other Halocarbons Regulation, B.C. Reg. 220/2006, Environmental Management Act.
5. PCB Regulations, SOR/2008-273, Canadian Environmental Protection Act.
6. Lead-Containing Paint and Coatings, Preventing Exposure in the Construction Industry, WorkSafe BC, June 2011.
7. Transportation of Dangerous Goods Regulations SOR/2008-34, Transportation of Dangerous Goods Act.
8. Federal Register, 40 CFR Part 745 Lead; Identification of Dangerous Levels of Lead; Final Rule, Environmental Protection Agency, January 5, 2001.
9. Mould Guidelines for the Canadian Construction Industry, Standard Construction Document CCA 82 – 2004, Canadian Construction Association.
APPENDIX I
SPECIFIC METHODS AND CRITERIA
Specific Methods and Criteria Appendix I
© 2014 Pinchin West Ltd. Page 1
1.1 Asbestos
An inspection for the presence of friable and non-friable asbestos-containing materials (ACM) was conducted. A friable material is a material that when dry can be crumbled, pulverized or powdered by hand pressure.
A separate set of samples was collected of each type of homogenous material suspected to contain asbestos. A homogenous material is defined by the US EPA1 as material that is uniform in texture and appearance, was installed at one time, and is unlikely to consist of more than one type or formulation of material.
Samples were collected at a rate that was in compliance with the requirements of local regulations and guidelines.
The homogeneous materials were determined by visual examination, available information on the phases of the construction and prior renovations.
The sampling strategy was also based on known ban dates and phase out dates of the use of asbestos; sampling of certain building materials was not conducted after specific construction dates. In addition, to be conservative, several years past these dates have been added to account for some uncertainty in the exact start / finish date of construction and associated usage of ACM.
In some cases, manufactured products such as asbestos cement pipe were visually identified without sample confirmation.
Drywall joint compound was sampled at exterior walls, columns or other locations to determine the presence of asbestos in the original drywall joint compound. Delineation of asbestos-containing drywall joint compound from non-asbestos drywall joint compound was not conducted.
Bulk samples were submitted to a NVLAP2 accredited laboratory for analysis. The analysis was performed in accordance with Test Method EPA/600/R-93/116: Method for the Determination of Asbestos in Bulk Building Materials, July 1993.
The asbestos analysis was completed using a stop positive approach. Only one result of greater than the regulated criteria is required to determine that a material is asbestos-containing, but all samples must be analyzed to conclusively determine that a material is non-asbestos. The laboratory stopped analyzing samples from a homogeneous material once greater than the regulated criteria was detected in any of the samples of that material. All samples of a homogeneous material were analyzed if no asbestos was detected. In some cases, all sampled were analyzed in the sample set regardless of result.
An asbestos-containing material is defined as 0.5% or any amount if vermiculite.
1 Environmental Protection Agency 2 National Voluntary Laboratory Accreditation Program
Specific Methods and Criteria Appendix I
© 2014 Pinchin West Ltd. Page 2
Asbestos materials were evaluated in order to make recommendations regarding remedial work. For each ACM identified, a risk assessment was performed which included; condition, friability, air movement or if located in an air plenum and accessibility. Remedial action was then determined from the risk assessment and/or if mandated by regulatory requirements.
PWL used an action matrix based on an evaluation of the accessibility and condition of ACM to make recommendations for compliance with current regulations and industry best practice. Refer to the assessment methodology at the end of this section.
1.2 Lead
Each distinctive paint finish likely to be disturbed by the planned renovation and present in more than very limited application was sampled for lead content. Paint samples were collected and submitted to a laboratory for analysis.
Analysis for lead in paints or surface coatings is performed in accordance with EPA Method No. 3050B/Method No. 7420; flame atomic absorption at an accredited laboratory.
For this report, all paints containing lead at a concentration of 0.009% or greater have been discussed. Paint and surface coatings were evaluated for condition.
Lead building products (e.g. batteries, lead sheeting, flashing) were identified by visual observation only.
1.3 Silica
Building materials suspected of containing crystalline silica (e.g. concrete, cement, tile, brick, masonry, mortar) were identified by knowledge of current and historic applications and visual inspection only. Sampling of these materials for laboratory analysis of crystalline silica content was not performed.
1.4 Mercury
Building materials/products/equipment (e.g. thermostats, barometers, pressure gauges, light tubes), suspected to contain mercury were identified by visually inspection only. Dismantling of equipment suspected of containing mercury was not performed. Sampling of these materials for laboratory analysis of mercury content was not performed.
Spills or damaged equipment was recorded where observed.
1.5 Polychlorinated Biphenyls
Light ballast and wet transformers suspected to contain PCB were determined based on the age of the building, a review of maintenance records and examination of labels on equipment, where present and accessible. The information was compared to known ban dates of PCBs and Environment Canada publications.
Dry transformers are presumed to be free of dielectric fluids and hence non-PCB. Spills or leakage of suspect PCB-containing fluids was recorded where observed or identified in historical documents.
Specific Methods and Criteria Appendix I
© 2014 Pinchin West Ltd. Page 3
Fluids (mineral oil, hydraulic or Askeral) in transformers or other equipment were not sampled for PCB content.
1.6 Halocarbons
Air conditioning units, chillers and fire suppression systems (fixed and portable) suspected of containing halocarbons or other ODS were determined by visual inspection of manufactures labels and maintenance records only.
1.7 Visible Mould
Mould was identified if visibly present in a significant quantity on exposed building surfaces. If any mould growth is concealed within wall cavities it was not addressed in this assessment.
Specific Methods and Criteria Appendix I
© 2014 Pinchin West Ltd. Page 4
2.0 Asbestos Risk Assessment
For each ACM identified, a risk assessment was performed which included; condition, friability (those materials that can easily be crumbled or powdered with hand pressure) air movement or if located in an air plenum and accessibility. Remedial action was then determined from the risk assessment and/or if mandated by regulatory requirements. PWL used the following action matrix based on an evaluation of the accessibility and condition of ACM to make recommendations for compliance with current regulations and industry best practice.
Action Matrix (Friable)
Access Condition
Debris GOOD FAIR POOR
A 5 5 3 1
B 7 6 3 1
C (Visible) 7 6 3 2
C (Not Visible) 7 7 4 2
D 7 7 7 7
Any access with air movement
5 5 3 1
Action Matrix (Non-Friable)
Access Condition
Debris GOOD FAIR POOR
A 7 7 3 1
B 7 7 3 1
C (Visible) 7 7 4 2
C (Not Visible) 7 7 4 2
D 7 7 7 7
Air movement in access A, B, C
7 7 3 1
Air movement in access D 7 7 7 7
Specific Methods and Criteria Appendix I
© 2014 Pinchin West Ltd. Page 5
Definitions of Actions
Action Explanation
1 Clean-Up of ACM Debris – High Priority Restrict access that is likely to cause a disturbance of the ACM Debris and clean up ACM Debris immediately.
2 Clean-Up of ACM Debris – Medium Priority Restrict access that is likely to cause a disturbance of the ACM Debris and clean up ACM Debris.
3 ACM Removal – High Priority Remove ACM as soon as possible. Until it is removed, restrict access to the material so it is not disturbed.
4 ACM Removal – Medium Priority Remove ACM. Until it is removed, restrict access to the material so it is not disturbed.
5 ACM Control – Low Priority Proactively remove, enclose or encapsulate ACM in conjunction with other building activities.
6 ACM Repair Repair ACM.
7 Asbestos Management Program with Routine Surveillance Implement an Asbestos Management Program, including routine surveillance of ACM. Reassess materials regularly (typically once per year).
Specific Methods and Criteria Appendix I
© 2014 Pinchin West Ltd. Page 6
Definitions of Condition
ACM Material GOOD FAIR POOR
Friable Surfacing Materials (spray applied fireproofing, sprayed thermal insulation, texture finishes)
Surface of material shows no significant signs of damage, deterioration or delamination. Good condition includes unencapsulated or unpainted fireproofing or texture finishes, where no delamination or damage is observed, or encapsulated fireproofing or texture finishes where the encapsulant or paint has been applied after the damage or fallout occurred.
N/A A sprayed material that shows signs of significant damage or is significantly delaminating or deteriorating. This may be limited to surface delamination or some portion of the substrate may be exposed. Presence of debris.
Friable Manufactured Products (ceiling tiles)
No significant damage or deterioration. Condition is at or near to the condition when it was installed. Still serving its intended use as a building material or finish.
Showing signs of some cracking or breakage, but is not deteriorating (e.g. broken but in place ceiling tile, etc.). The material is still serving its intended use as a building material or finish but may require repair for mainly cosmetic purposes.
Significant deterioration or breaking apart of the material. Material has deteriorated to the point it is not serving its intended use as building material or finish. Is not repairable and requires at least localized removal and replacement. Presence of debris.
Specific Methods and Criteria Appendix I
© 2014 Pinchin West Ltd. Page 7
ACM Material GOOD FAIR POOR
Friable Thermal System Insulation (mechanical insulation on vessels, boilers, breeching, ducts, pipes, fan units, equipment etc.)
Insulation is completely covered in jacketing and exhibits no evidence of damage or deterioration. No insulation is exposed. Includes conditions where the jacketing has minor damage (i.e. scuffs or stains), but the jacketing is not penetrated.
Minor penetrating damage to jacketed insulation (cuts, tears, nicks, deterioration or delamination) or undamaged insulation that had never been jacketed. Insulation is exposed but not showing surface disintegration. The extent of missing insulation ranges from minor to none. Damage can be repaired.
Original insulation jacket is missing, damaged, deteriorated or delaminated. Insulation is exposed and significant areas have been dislodged. Damage cannot be readily repaired. Includes components where insulation may have been removed incompletely. Presence of debris.
Non-friable materials (i.e. drywall and manufactured products such as cement products)
No significant damage or deterioration. Condition is at or near to the condition when it was installed. Still serving its intended use as a building material or finish.
Showing signs of some cracking or damage but has not deteriorated. The material is still serving its intended use as a building material or finish and does not require repair or removal from an asbestos hazard perspective.
Significant deterioration or breaking apart of the material to the point at which it cannot be repaired and it will require at least local removal. Material has deteriorated to the point it is not serving its intended use as building material or finish. Material may have deteriorated to a point where traffic or disturbance may cause it to become friable.
Specific Methods and Criteria Appendix I
© 2014 Pinchin West Ltd. Page 8
Definitions of Accessibility
Access Explanation
A
Common areas of the building within reach of all building users (approximately 9’ from floor or standard ceiling height). Includes other areas where occupant activities may result in disturbance of material that is not normally within reach from floor level, but may be disturbed by common activities (e.g. gymnasiums, workshops, warehouses)
B
Areas of the building accessed primarily by Maintenance, Caretaking, Janitorial Staff and within reach without use of a ladder. Includes areas within reach in Boiler Rooms, Electrical Rooms, Janitors Closets, Elevator Rooms, Mechanical Rooms, etc. Includes materials within reach from fixed ladders or catwalks, mezzanines, and accessible pipe chases.
C visible
Areas of the building above 9’ where use of a ladder or scaffold is required to reach the ACM. Only includes ACM that are visible to view without the removal or opening of other building components such as ceiling tiles or service access panels.
C not visible
Areas of the building above 9’ where use of a ladder or scaffold is required to reach the ACM. Includes ACM that are not visible to view and require the removal of a building component, such as ceilings tiles or access panels to view and access. Includes rarely entered crawl spaces, attic spaces, etc. Observations will be limited to the extent visible from the access points.
D
Areas of the building behind inaccessible solid ceiling systems, walls or equipment etc. where demolition of the ceiling, wall or equipment etc. is required to reach the ACM. Material inaccessible due to height or location or is only reached under unusual situations. Evaluation of condition and extent of ACM is limited.
Definition of Air Erosion, Air Plenum or Air Movement
The ACM is in a return air plenum or in a direct airstream or there is evidence of air erosion (i.e. ducts for heating or air conditioning blowing directly on ACM).
APPENDIX II
LOCATIONS SUMMARY
LOCATIONS LIST
1-877-322-4744 www.pinchinwest.com
Victoria * Kelowna * Nakusp * Calgary * Edmonton * Red Deer * Regina * Saskatoon Website: www.pinchinwest.com * 1-877-322-4744 Page 1 of 1.
Project #: 12661K-22 Site: 1375 Nicola Street, Vancouver, BC Building Name: Berwick House Surveyor: Nadia Slakov Survey Date:
2014-05-12 Location No. Name or Description Size (ft2) Floor No. Notes
1 Boiler Room 200 1 2 Electrical Room And Storage 150 1
3 Laundry Room 150 1
4 Office 75 1
5 First Floor Hallway 150 1
6 Washroom 25 1
7 Sprinkler Room 150 1
8 Storage Lockers 150 1
9 Entrance Vestibule 250 1
10 Suite 102 700 1
11 Suite 201 700 2
12 Second Floor Hall 200 2
13 Suite 302 700 3
14 Third Floor Hall 200 3
15 Suite 403 700 4
16 Fourth Floor Hall 200 4
17 Suite 501 700 5
18 Fifth Floor Hall 200 5 19 Suite 603 700 6
20 Sixth Floor Hall 200 6 21 Suite 704 700 7
22 Seventh Floor Hall 200 7 23 Stairwell 1000 ALL
24 Penthouse NO ACCESS 8
25 Parkade 1000 B
APPENDIX III
HAZARDOUS MATERIALS SUMMARY
HAZARDOUS MATERIALS SUMMARY
1-877-322-4744 www.pinchinwest.com
Victoria * Kelowna * Nakusp * Calgary * Edmonton * Red Deer * Regina * Saskatoon Website: www.pinchinwest.com * 1-877-322-4744 Page 1 of 2.
Project #: 12661K-22 Site: 1375 Nicola Street, Vancouver, BC Building Name: Berwick House Surveyor: Nadia Slakov Survey Date: 2014-05-12 HAZARDOUS MATERIALS SUMMARY - ASBESTOS CONTAINING MATERIALS (ACM)
Sample No. System Material/Notes Friable Location(s) Substance Amount Unit Positive
S0001 OTHER CEMENTITIOUS FIRESTOPPING Yes 2,5,7,8 None Detected No S0002 WALL PLASTER No 3,4,5,6,9,10,11,12,13,14,15,16,17,18,19,20,21,22,23 None Detected No
S0003 FLOOR VINYL SHEET FLOORING, BEIGE W BLACK DOTS Yes 5,6 None Detected No
S0004 CEILING TEXTURE FINISH ( TEXTURE COAT) Yes 5,9,23 None Detected No
S0006 PIPE PARGING CEMENT INSULATION Yes 7,25 Chrysotile 20 % Yes
S0007 CEILING TEXTURE FINISH ( TEXTURE COAT) Yes 10,11,13,15,17,19,21 None Detected No
S0008 OTHER CEMENTITIOUS FIRESTOPPING Yes 25 None Detected No V9000 PIPE AIRCELL Yes 25 Visually Confirmed Yes
Project #: 12661K-22 Site: 1375 Nicola Street, Vancouver, BC Building Name: Berwick House Surveyor: Nadia Slakov Survey Date: 2014-05-12 HAZARDOUS MATERIALS SUMMARY - LEAD BASED PAINT (LBP)
Sample No. System Description Location(s) Substance Amount Unit Positive
L0001 WALL WHITE 1,3,4,5,9,12,14,16,18,20,22,23,25 Lead <0.004 % No L0002 FLOOR GREY 1,2,3,7,8 Lead 0.95 % Yes L0003 WALL TEAL 2,7,8 Lead 0.004 % No L0004 OTHER TAN 5,9,23 Lead 0.17 % Yes
Project #: 12661K-22 Site: 1375 Nicola Street, Vancouver, BC Building Name: Berwick House Surveyor: Nadia Slakov Survey Date: 2014-05-12 HAZARDOUS MATERIALS SUMMARY - LEAD (PB) PRODUCTS
Component Total Quantity (Estimated)
Location(s)
BATTERIES IN EMER. LIGHTS 15 12,14,16,18,20,22,23,25
HAZARDOUS MATERIALS SUMMARY
1-877-322-4744 www.pinchinwest.com
Victoria * Kelowna * Nakusp * Calgary * Edmonton * Red Deer * Regina * Saskatoon Website: www.pinchinwest.com * 1-877-322-4744 Page 2 of 2.
Project #: 12661K-22 Site: 1375 Nicola Street, Vancouver, BC Building Name: Berwick House Surveyor: Nadia Slakov Survey Date: 2014-05-12 HAZARDOUS MATERIALS SUMMARY - MERCURY (HG)
Component Total Quantity (Estimated)
Location(s)
THERMOSTAT 1 6
FLUORESCENT LIGHT TUBE 51 12,14,16,18,2,20,22,25,3,4,4,5,7,8
APPENDIX IV
HAZARDOUS MATERIALS FINDINGS BY LOCATION
ALL DATA REPORT
1-877-322-4744 www.pinchinwest.com
2014-05-23 Victoria * Kelowna * Nakusp * Calgary * Edmonton * Red Deer * Regina * Saskatoon Website: www.pinchinwest.com * 1-877-322-4744 Page 1 of 22.
Project #: 12661K-22 Site: 1375 Nicola Street, Vancouver, BC Building Name: Berwick House Surveyor: Nadia Slakov Survey Date: 2014-05-12 Location #: 1 Location Name: Boiler room Floor: 1 Room #: Square ft: 200
ASBESTOS
System Component Material Friable Item Covering Access Visible Air Plenum
Good Fair Poor Unit Sample Asbestos Type Amount Asbestos
FLOOR ALL CONCRETE (POURED) No ~ No CEILING NOT FOUND No ~ No
WALL ALL CONCRETE (POURED) No ~ No STRUCTURE ALL CONCRETE (POURED) No ~ No
DUCT ALL NOT INSULATED No ~ No PIPE ALL FIBREGLASS No STRAIGHT PIPE PAPER ~ No PIPE
1 ALL FIBREGLASS No PIPE ELBOW ~ No MECHANICAL ALL NOT INSULATED No ~ No MECHANICAL COMPRESSOR NOT INSULATED No ~ No
1 - covered plastic
Project #: 12661K-22 Site: 1375 Nicola Street, Vancouver, BC Building Name: Berwick House Surveyor: Nadia Slakov Survey Date: 2014-05-12 Location #: 2 Location Name: Electrical room and Storage Floor: 1 Room #: Square ft: 150
ASBESTOS
System Component Material Friable Item Covering Access Visible Air Plenum
Good Fair Poor Unit Sample Asbestos Type Amount Asbestos
FLOOR ALL CONCRETE (POURED) No ~ No CEILING NOT FOUND No ~ No
WALL ALL CONCRETE (POURED) No ~ No STRUCTURE ALL CONCRETE (POURED) No ~ No
DUCT NOT FOUND No ~ No PIPE
1 ALL FIBREGLASS No PIPE ELBOW ~ No PIPE
2 DRAIN NOT INSULATED No ALL ~ No MECHANICAL NOT FOUND No ~ No
OTHER FIRESTOPPING CEMENTITIOUS FIRESTOPPING Yes ALL B Y N 5 SF S0001 NON-ASBESTOS No 1 - covered plastic 2 - cast iron
ALL DATA REPORT
1-877-322-4744 www.pinchinwest.com
2014-05-23 Victoria * Kelowna * Nakusp * Calgary * Edmonton * Red Deer * Regina * Saskatoon Website: www.pinchinwest.com * 1-877-322-4744 Page 2 of 22.
Project #: 12661K-22 Site: 1375 Nicola Street, Vancouver, BC Building Name: Berwick House Surveyor: Nadia Slakov Survey Date: 2014-05-12 Location #: 3 Location Name: Laundry Room Floor: 1 Room #: Square ft: 150
ASBESTOS
System Component Material Friable Item Covering Access Visible Air Plenum
Good Fair Poor Unit Sample Asbestos Type Amount Asbestos
FLOOR ALL CERAMIC TILES No ~ No CEILING ALL PLASTER No ALL C Y N 150 SF V0002 NON-ASBESTOS No
WALL ALL PLASTER No A Y N 500 SF S0002a NON-ASBESTOS No STRUCTURE ALL CONCRETE (POURED) No ~ No
DUCT NOT FOUND No ~ No PIPE
1 DRAIN NOT INSULATED No ALL ~ No MECHANICAL NOT FOUND No ~ No
1 - cast iron
Project #: 12661K-22 Site: 1375 Nicola Street, Vancouver, BC Building Name: Berwick House Surveyor: Nadia Slakov Survey Date: 2014-05-12 Location #: 4 Location Name: Office Floor: 1 Room #: Square ft: 75
ASBESTOS
System Component Material Friable Item Covering Access Visible Air Plenum
Good Fair Poor Unit Sample Asbestos Type Amount Asbestos
FLOOR ALL CERAMIC TILES No ~ No CEILING ALL PLASTER No ALL C Y N 150 SF V0002 NON-ASBESTOS No
WALL ALL PLASTER No A Y N 150 SF V0002 NON-ASBESTOS No STRUCTURE ALL CONCRETE (POURED) No ~ No
DUCT NOT FOUND No ~ No PIPE
1 DRAIN NOT INSULATED No ALL ~ No MECHANICAL NOT FOUND No ~ No
1 - cast iron
ALL DATA REPORT
1-877-322-4744 www.pinchinwest.com
2014-05-23 Victoria * Kelowna * Nakusp * Calgary * Edmonton * Red Deer * Regina * Saskatoon Website: www.pinchinwest.com * 1-877-322-4744 Page 3 of 22.
Project #: 12661K-22 Site: 1375 Nicola Street, Vancouver, BC Building Name: Berwick House Surveyor: Nadia Slakov Survey Date: 2014-05-12 Location #: 5 Location Name: First floor hallway Floor: 1 Room #: Square ft: 150
ASBESTOS
System Component Material Friable Item Covering Access Visible Air Plenum
Good Fair Poor Unit Sample Asbestos Type Amount Asbestos
FLOOR ALL VINYL SHEET FLOORING, BEIGE W BLACK DOTS Yes ALL A Y N 150 SF S0003 NON-ASBESTOS No
CEILING ALL PLASTER No ALL C Y N 150 SF V0001 NON-ASBESTOS No CEILING ALL PLASTER No A Y N SF S0002c NON-ASBESTOS No CEILING ALL PLASTER No A Y N SF S0002d NON-ASBESTOS No CEILING ALL PLASTER No A Y N 150 SF S0002b NON-ASBESTOS No CEILING ALL TEXTURE FINISH ( TEXTURE COAT) Yes SURFACE C Y N 150 SF S0004a NON-ASBESTOS No CEILING ALL TEXTURE FINISH ( TEXTURE COAT) Yes SURFACE C Y N SF S0004b NON-ASBESTOS No CEILING ALL TEXTURE FINISH ( TEXTURE COAT) Yes SURFACE C Y N SF S0004c NON-ASBESTOS No
WALL ALL PLASTER No A Y N 500 SF V0002 NON-ASBESTOS No WALL ALL TEXTURE FINISH ( TEXTURE COAT) Yes SURFACE A Y N 500 SF V0004 NON-ASBESTOS No
STRUCTURE ALL CONCRETE (POURED) No ~ No DUCT NOT FOUND No ~ No PIPE DOMESTIC WATER FIBREGLASS No INSULATION PAPER ~ No PIPE
1 DRAIN NOT INSULATED No ALL ~ No MECHANICAL NOT FOUND No ~ No
OTHER FIRESTOPPING CEMENTITIOUS FIRESTOPPING Yes ALL B Y N 6 SF V0001 NON-ASBESTOS No 1 - cast iron
ALL DATA REPORT
1-877-322-4744 www.pinchinwest.com
2014-05-23 Victoria * Kelowna * Nakusp * Calgary * Edmonton * Red Deer * Regina * Saskatoon Website: www.pinchinwest.com * 1-877-322-4744 Page 4 of 22.
Project #: 12661K-22 Site: 1375 Nicola Street, Vancouver, BC Building Name: Berwick House Surveyor: Nadia Slakov Survey Date: 2014-05-12 Location #: 6 Location Name: Washroom Floor: 1 Room #: Square ft: 25
ASBESTOS
System Component Material Friable Item Covering Access Visible Air Plenum
Good Fair Poor Unit Sample Asbestos Type Amount Asbestos
FLOOR ALL VINYL SHEET FLOORING Yes ALL A Y N 25 SF V0003 NON-ASBESTOS No CEILING ALL PLASTER No ALL C Y N 25 V0002 NON-ASBESTOS No
WALL ALL PLASTER No ALL A Y N 150 SF S0002e NON-ASBESTOS No STRUCTURE ALL CONCRETE (POURED) No ~ No
DUCT NO ACCESS THROUGH CEILING No ~ No
PIPE NO ACCESS THROUGH CEILING No ~ No
MECHANICAL NOT FOUND No ~ No
Project #: 12661K-22 Site: 1375 Nicola Street, Vancouver, BC Building Name: Berwick House Surveyor: Nadia Slakov Survey Date: 2014-05-12 Location #: 7 Location Name: Sprinkler Room Floor: 1 Room #: Square ft: 150
ASBESTOS
System Component Material Friable Item Covering Access Visible Air Plenum
Good Fair Poor Unit Sample Asbestos Type Amount Asbestos
FLOOR ALL CONCRETE (POURED) No ~ No CEILING NOT FOUND No ~ No
WALL ALL CONCRETE (POURED) No ~ No STRUCTURE ALL CONCRETE (POURED) No ~ No
DUCT NOT FOUND No ~ No PIPE
1 ALL FIBREGLASS No PIPE ELBOW ~ No PIPE DOMESTIC WATER PARGING CEMENT INSULATION Yes PIPE ELBOW CANVAS A Y N 1 (3) EA S0006a CHRYSOTILE 20% Yes PIPE
2 DRAIN NOT INSULATED No ALL ~ No MECHANICAL
3 ALL NOT INSULATED No ALL ~ No OTHER FIRESTOPPING CEMENTITIOUS FIRESTOPPING Yes ALL B Y 5 SF V0001 NON-ASBESTOS No
1 - covered plastic 2 - cast iron 3 - sprinkler pump
ALL DATA REPORT
1-877-322-4744 www.pinchinwest.com
2014-05-23 Victoria * Kelowna * Nakusp * Calgary * Edmonton * Red Deer * Regina * Saskatoon Website: www.pinchinwest.com * 1-877-322-4744 Page 5 of 22.
Project #: 12661K-22 Site: 1375 Nicola Street, Vancouver, BC Building Name: Berwick House Surveyor: Nadia Slakov Survey Date: 2014-05-12 Location #: 8 Location Name: Storage lockers Floor: 1 Room #: Square ft: 150
ASBESTOS
System Component Material Friable Item Covering Access Visible Air Plenum
Good Fair Poor Unit Sample Asbestos Type Amount Asbestos
FLOOR ALL CONCRETE (POURED) No ~ No CEILING NOT FOUND No ~ No
WALL ALL CONCRETE (POURED) No ~ No STRUCTURE ALL CONCRETE (POURED) No ~ No
DUCT NOT FOUND No ~ No PIPE
1 DRAIN NOT INSULATED No ALL ~ No MECHANICAL NOT FOUND No ~ No
OTHER FIRESTOPPING CEMENTITIOUS FIRESTOPPING Yes ALL B Y 5 SF V0001 NON-ASBESTOS No 1 - cast iron
Project #: 12661K-22 Site: 1375 Nicola Street, Vancouver, BC Building Name: Berwick House Surveyor: Nadia Slakov Survey Date: 2014-05-12 Location #: 9 Location Name: Entrance vestibule Floor: 1 Room #: Square ft: 250
ASBESTOS
System Component Material Friable Item Covering Access Visible Air Plenum
Good Fair Poor Unit Sample Asbestos Type Amount Asbestos
FLOOR ALL CARPET No ~ No CEILING ALL PLASTER No ALL C Y N 250 SF V0002 NON-ASBESTOS No CEILING ALL PLASTER No A Y N 250 SF V0002 NON-ASBESTOS No CEILING ALL TEXTURE FINISH ( TEXTURE COAT) Yes SURFACE C Y N 75 SF V0004 NON-ASBESTOS No
WALL ALL PLASTER No A Y N 100 SF V0002 NON-ASBESTOS No WALL ALL TEXTURE FINISH ( TEXTURE COAT) Yes SURFACE A Y N 100 SF V0004 NON-ASBESTOS No WALL ALL WOOD No SURFACE ~ No
STRUCTURE ALL CONCRETE (POURED) No ~ No DUCT NOT FOUND No ~ No
PIPE1 NO ACCESS
THROUGH CEILING No ALL ~ No
MECHANICAL NOT FOUND No ~ No 1 - cast iron
ALL DATA REPORT
1-877-322-4744 www.pinchinwest.com
2014-05-23 Victoria * Kelowna * Nakusp * Calgary * Edmonton * Red Deer * Regina * Saskatoon Website: www.pinchinwest.com * 1-877-322-4744 Page 6 of 22.
Project #: 12661K-22 Site: 1375 Nicola Street, Vancouver, BC Building Name: Berwick House Surveyor: Nadia Slakov Survey Date: 2014-05-12 Location #: 10 Location Name: Suite 102 Floor: 1 Room #: Square ft: 700
ASBESTOS
System Component Material Friable Item Covering Access Visible Air Plenum
Good Fair Poor Unit Sample Asbestos Type Amount Asbestos
FLOOR ALL CARPET No ~ No FLOOR ALL PLASTIC LAMINATE No ~ No
CEILING ALL PLASTER No ALL C Y N 700 SF V0002 NON-ASBESTOS No CEILING ALL TEXTURE FINISH ( TEXTURE COAT) Yes ALL C Y N 500 SF V0007 NON-ASBESTOS No
WALL ALL PLASTER No ALL A Y N 1000 SF V0002 NON-ASBESTOS No STRUCTURE ALL CONCRETE (POURED) No ALL ~ No
DUCT NO ACCESS THROUGH CEILING No ~ No
PIPE NO ACCESS THROUGH CEILING No ~ No
MECHANICAL NOT FOUND No ~ No
Project #: 12661K-22 Site: 1375 Nicola Street, Vancouver, BC Building Name: Berwick House Surveyor: Nadia Slakov Survey Date: 2014-05-12 Location #: 11 Location Name: Suite 201 Floor: 2 Room #: Square ft: 700
ASBESTOS
System Component Material Friable Item Covering Access Visible Air Plenum
Good Fair Poor Unit Sample Asbestos Type Amount Asbestos
FLOOR ALL CARPET No ~ No FLOOR ALL PLASTIC LAMINATE No ~ No
CEILING ALL PLASTER No ALL C Y N 700 SF V0002 NON-ASBESTOS No CEILING ALL TEXTURE FINISH ( TEXTURE COAT) Yes ALL C Y N 7000 SF V0007 NON-ASBESTOS No
WALL ALL PLASTER No ALL A Y N 1000 SF V0002 NON-ASBESTOS No STRUCTURE ALL CONCRETE (POURED) No ALL ~ No
DUCT NO ACCESS THROUGH CEILING No ~ No
PIPE NO ACCESS THROUGH CEILING No ~ No
MECHANICAL NOT FOUND No ~ No
ALL DATA REPORT
1-877-322-4744 www.pinchinwest.com
2014-05-23 Victoria * Kelowna * Nakusp * Calgary * Edmonton * Red Deer * Regina * Saskatoon Website: www.pinchinwest.com * 1-877-322-4744 Page 7 of 22.
Project #: 12661K-22 Site: 1375 Nicola Street, Vancouver, BC Building Name: Berwick House Surveyor: Nadia Slakov Survey Date: 2014-05-12 Location #: 12 Location Name: Second floor hall Floor: 2 Room #: Square ft: 200
ASBESTOS
System Component Material Friable Item Covering Access Visible Air Plenum
Good Fair Poor Unit Sample Asbestos Type Amount Asbestos
FLOOR ALL CARPET No ~ No CEILING ALL PLASTER No ALL C Y N 200 V0002 NON-ASBESTOS No
WALL ALL PLASTER No ALL A Y N 400 SF S0002g NON-ASBESTOS No STRUCTURE ALL No ~ No
DUCT NO ACCESS THROUGH CEILING No ~ No
PIPE NO ACCESS THROUGH CEILING No ~ No
MECHANICAL NOT FOUND No ~ No
Project #: 12661K-22 Site: 1375 Nicola Street, Vancouver, BC Building Name: Berwick House Surveyor: Nadia Slakov Survey Date: 2014-05-12 Location #: 13 Location Name: Suite 302 Floor: 3 Room #: Square ft: 700
ASBESTOS
System Component Material Friable Item Covering Access Visible Air Plenum
Good Fair Poor Unit Sample Asbestos Type Amount Asbestos
FLOOR ALL CARPET No ~ No FLOOR ALL PLASTIC LAMINATE No ~ No
CEILING ALL PLASTER No ALL C Y N 700 SF V0002 NON-ASBESTOS No CEILING ALL TEXTURE FINISH ( TEXTURE COAT) Yes ALL C Y N 7000 SF S0007c NON-ASBESTOS No
WALL ALL PLASTER No ALL A Y N 1000 SF V0002 NON-ASBESTOS No STRUCTURE ALL CONCRETE (POURED) No ALL ~ No
DUCT NO ACCESS THROUGH CEILING No ~ No
PIPE NO ACCESS THROUGH CEILING No ~ No
MECHANICAL NOT FOUND No ~ No
ALL DATA REPORT
1-877-322-4744 www.pinchinwest.com
2014-05-23 Victoria * Kelowna * Nakusp * Calgary * Edmonton * Red Deer * Regina * Saskatoon Website: www.pinchinwest.com * 1-877-322-4744 Page 8 of 22.
Project #: 12661K-22 Site: 1375 Nicola Street, Vancouver, BC Building Name: Berwick House Surveyor: Nadia Slakov Survey Date: 2014-05-12 Location #: 14 Location Name: Third floor hall Floor: 3 Room #: Square ft: 200
ASBESTOS
System Component Material Friable Item Covering Access Visible Air Plenum
Good Fair Poor Unit Sample Asbestos Type Amount Asbestos
FLOOR ALL CARPET No ~ No CEILING ALL PLASTER No ALL C Y N 200 V0002 NON-ASBESTOS No
WALL ALL PLASTER No A Y N 400 SF V0002 NON-ASBESTOS No STRUCTURE ALL No ~ No
DUCT NO ACCESS THROUGH CEILING No ~ No
PIPE NO ACCESS THROUGH CEILING No ~ No
MECHANICAL NOT FOUND No ~ No
Project #: 12661K-22 Site: 1375 Nicola Street, Vancouver, BC Building Name: Berwick House Surveyor: Nadia Slakov Survey Date: 2014-05-12 Location #: 15 Location Name: Suite 403 Floor: 4 Room #: Square ft: 700
ASBESTOS
System Component Material Friable Item Covering Access Visible Air Plenum
Good Fair Poor Unit Sample Asbestos Type Amount Asbestos
FLOOR ALL CARPET No ~ No FLOOR ALL PLASTIC LAMINATE No ~ No
CEILING ALL PLASTER No ALL C Y N 700 SF V0002 NON-ASBESTOS No CEILING ALL TEXTURE FINISH ( TEXTURE COAT) Yes ALL C Y N 7000 SF V0007 NON-ASBESTOS No
WALL ALL PLASTER No ALL A Y N 1000 SF V0002 NON-ASBESTOS No STRUCTURE ALL CONCRETE (POURED) No ALL ~ No
DUCT NO ACCESS THROUGH CEILING No ~ No
PIPE NO ACCESS THROUGH CEILING No ~ No
MECHANICAL NOT FOUND No ~ No
ALL DATA REPORT
1-877-322-4744 www.pinchinwest.com
2014-05-23 Victoria * Kelowna * Nakusp * Calgary * Edmonton * Red Deer * Regina * Saskatoon Website: www.pinchinwest.com * 1-877-322-4744 Page 9 of 22.
Project #: 12661K-22 Site: 1375 Nicola Street, Vancouver, BC Building Name: Berwick House Surveyor: Nadia Slakov Survey Date: 2014-05-12 Location #: 16 Location Name: Fourth floor hall Floor: 4 Room #: Square ft: 200
ASBESTOS
System Component Material Friable Item Covering Access Visible Air Plenum
Good Fair Poor Unit Sample Asbestos Type Amount Asbestos
FLOOR ALL CARPET No ~ No CEILING ALL PLASTER No ALL C Y N 200 V0002 NON-ASBESTOS No
WALL ALL PLASTER No ALL A Y N 400 SF V0002 NON-ASBESTOS No STRUCTURE ALL No ~ No
DUCT NO ACCESS THROUGH CEILING No ~ No
PIPE NO ACCESS THROUGH CEILING No ~ No
MECHANICAL NOT FOUND No ~ No
Project #: 12661K-22 Site: 1375 Nicola Street, Vancouver, BC Building Name: Berwick House Surveyor: Nadia Slakov Survey Date: 2014-05-12 Location #: 17 Location Name: Suite 501 Floor: 5 Room #: Square ft: 700
ASBESTOS
System Component Material Friable Item Covering Access Visible Air Plenum
Good Fair Poor Unit Sample Asbestos Type Amount Asbestos
FLOOR ALL CARPET No ~ No FLOOR ALL PLASTIC LAMINATE No ~ No
CEILING ALL PLASTER No ALL C Y N 700 SF V0002 NON-ASBESTOS No CEILING ALL TEXTURE FINISH ( TEXTURE COAT) Yes ALL C Y N 7000 SF V0007 NON-ASBESTOS No
WALL ALL PLASTER No ALL A Y N 1000 SF V0002 NON-ASBESTOS No STRUCTURE ALL CONCRETE (POURED) No ALL ~ No
DUCT NO ACCESS THROUGH CEILING No ~ No
PIPE NO ACCESS THROUGH CEILING No ~ No
MECHANICAL NOT FOUND No ~ No
ALL DATA REPORT
1-877-322-4744 www.pinchinwest.com
2014-05-23 Victoria * Kelowna * Nakusp * Calgary * Edmonton * Red Deer * Regina * Saskatoon Website: www.pinchinwest.com * 1-877-322-4744 Page 10 of 22.
Project #: 12661K-22 Site: 1375 Nicola Street, Vancouver, BC Building Name: Berwick House Surveyor: Nadia Slakov Survey Date: 2014-05-12 Location #: 18 Location Name: Fifth floor hall Floor: 5 Room #: Square ft: 200
ASBESTOS
System Component Material Friable Item Covering Access Visible Air Plenum
Good Fair Poor Unit Sample Asbestos Type Amount Asbestos
FLOOR ALL CARPET No ~ No CEILING ALL PLASTER No ALL C Y N 200 V0002 NON-ASBESTOS No
WALL ALL PLASTER No ALL A Y N 400 SF S0002f NON-ASBESTOS No STRUCTURE ALL No ~ No
DUCT NO ACCESS THROUGH CEILING No ~ No
PIPE NO ACCESS THROUGH CEILING No ~ No
MECHANICAL NOT FOUND No ~ No
Project #: 12661K-22 Site: 1375 Nicola Street, Vancouver, BC Building Name: Berwick House Surveyor: Nadia Slakov Survey Date: 2014-05-12 Location #: 19 Location Name: Suite 603 Floor: 6 Room #: Square ft: 700
ASBESTOS
System Component Material Friable Item Covering Access Visible Air Plenum
Good Fair Poor Unit Sample Asbestos Type Amount Asbestos
FLOOR ALL CARPET No ~ No FLOOR ALL PLASTIC LAMINATE No ~ No
CEILING ALL PLASTER No ALL C Y N 700 SF V0002 NON-ASBESTOS No CEILING ALL TEXTURE FINISH ( TEXTURE COAT) Yes ALL C Y N 7000 SF S0007b NON-ASBESTOS No
WALL ALL PLASTER No ALL A Y N 1000 SF V0002 NON-ASBESTOS No STRUCTURE ALL CONCRETE (POURED) No ALL ~ No
DUCT NO ACCESS THROUGH CEILING No ~ No
PIPE NO ACCESS THROUGH CEILING No ~ No
MECHANICAL NOT FOUND No ~ No
ALL DATA REPORT
1-877-322-4744 www.pinchinwest.com
2014-05-23 Victoria * Kelowna * Nakusp * Calgary * Edmonton * Red Deer * Regina * Saskatoon Website: www.pinchinwest.com * 1-877-322-4744 Page 11 of 22.
Project #: 12661K-22 Site: 1375 Nicola Street, Vancouver, BC Building Name: Berwick House Surveyor: Nadia Slakov Survey Date: 2014-05-12 Location #: 20 Location Name: Sixth floor hall Floor: 6 Room #: Square ft: 200
ASBESTOS
System Component Material Friable Item Covering Access Visible Air Plenum
Good Fair Poor Unit Sample Asbestos Type Amount Asbestos
FLOOR ALL CARPET No ~ No CEILING ALL PLASTER No ALL C Y N 200 V0002 NON-ASBESTOS No
WALL ALL PLASTER No ALL A Y N 400 SF V0002 NON-ASBESTOS No STRUCTURE ALL No ~ No
DUCT NO ACCESS THROUGH CEILING No ~ No
PIPE NO ACCESS THROUGH CEILING No ~ No
MECHANICAL NOT FOUND No ~ No
Project #: 12661K-22 Site: 1375 Nicola Street, Vancouver, BC Building Name: Berwick House Surveyor: Nadia Slakov Survey Date: 2014-05-12 Location #: 21 Location Name: Suite 704 Floor: 7 Room #: Square ft: 700
ASBESTOS
System Component Material Friable Item Covering Access Visible Air Plenum
Good Fair Poor Unit Sample Asbestos Type Amount Asbestos
FLOOR ALL CARPET No ~ No FLOOR ALL PLASTIC LAMINATE No ~ No
CEILING ALL PLASTER No ALL C Y N 700 SF V0002 NON-ASBESTOS No CEILING ALL TEXTURE FINISH ( TEXTURE COAT) Yes ALL C Y N 7000 SF S0007a NON-ASBESTOS No
WALL ALL PLASTER No ALL A Y N 1000 SF V0002 NON-ASBESTOS No STRUCTURE ALL CONCRETE (POURED) No ALL ~ No
DUCT NO ACCESS THROUGH CEILING No ~ No
PIPE NO ACCESS THROUGH CEILING No ~ No
MECHANICAL NOT FOUND No ~ No
ALL DATA REPORT
1-877-322-4744 www.pinchinwest.com
2014-05-23 Victoria * Kelowna * Nakusp * Calgary * Edmonton * Red Deer * Regina * Saskatoon Website: www.pinchinwest.com * 1-877-322-4744 Page 12 of 22.
Project #: 12661K-22 Site: 1375 Nicola Street, Vancouver, BC Building Name: Berwick House Surveyor: Nadia Slakov Survey Date: 2014-05-12 Location #: 22 Location Name: Seventh floor hall Floor: 7 Room #: Square ft: 200
ASBESTOS
System Component Material Friable Item Covering Access Visible Air Plenum
Good Fair Poor Unit Sample Asbestos Type Amount Asbestos
FLOOR ALL CARPET No ~ No CEILING ALL PLASTER No ALL C Y N 200 V0002 NON-ASBESTOS No
WALL ALL PLASTER No ALL A Y N 400 SF V0002 NON-ASBESTOS No STRUCTURE ALL No ~ No
DUCT NO ACCESS THROUGH CEILING No ~ No
PIPE NO ACCESS THROUGH CEILING No ~ No
MECHANICAL NOT FOUND No ~ No
Project #: 12661K-22 Site: 1375 Nicola Street, Vancouver, BC Building Name: Berwick House Surveyor: Nadia Slakov Survey Date: 2014-05-12 Location #: 23 Location Name: Stairwell Floor: ALL Room #: Square ft: 1000
ASBESTOS
System Component Material Friable Item Covering Access Visible Air Plenum
Good Fair Poor Unit Sample Asbestos Type Amount Asbestos
FLOOR ALL CARPET No ~ No CEILING ALL PLASTER No ALL C Y N 1000 SF V0002 NON-ASBESTOS No CEILING ALL TEXTURE FINISH ( TEXTURE COAT) Yes SURFACE C Y N 1000 SF V0004 NON-ASBESTOS No
WALL ALL PLASTER No A Y N 1000 SF V0002 NON-ASBESTOS No WALL ALL TEXTURE FINISH ( TEXTURE COAT) Yes SURFACE A Y N SF S0004e NON-ASBESTOS No WALL ALL WOOD No SURFACE ~ No WALL ALL TEXTURE FINISH ( TEXTURE COAT) Yes SURFACE A Y N 1000 SF S0004d NON-ASBESTOS No
STRUCTURE ALL CONCRETE (POURED) No ~ No DUCT NOT FOUND No ~ No PIPE
1 NOT FOUND No ALL ~ No MECHANICAL NOT FOUND No ~ No
1 - cast iron
ALL DATA REPORT
1-877-322-4744 www.pinchinwest.com
2014-05-23 Victoria * Kelowna * Nakusp * Calgary * Edmonton * Red Deer * Regina * Saskatoon Website: www.pinchinwest.com * 1-877-322-4744 Page 13 of 22.
Project #: 12661K-22 Site: 1375 Nicola Street, Vancouver, BC Building Name: Berwick House Surveyor: Nadia Slakov Survey Date: 2014-05-12 Location #: 25 Location Name: Parking Floor: B Room #: Square ft: 1000
ASBESTOS
System Component Material Friable Item Covering Access Visible Air Plenum
Good Fair Poor Unit Sample Asbestos Type Amount Asbestos
FLOOR ALL CONCRETE (POURED) No ~ No CEILING NOT FOUND No ~ No
WALL ALL CONCRETE (POURED) No ~ No STRUCTURE ALL CONCRETE (POURED) No ~ No
DUCT NOT FOUND No ~ No PIPE DOMESTIC WATER AIRCELL Yes INSULATION CANVAS A Y N 230 (5) 15 (5) 1 (3) LF V9000 CONFIRMED Yes PIPE
1 DRAIN NOT INSULATED No ALL ~ No PIPE HOT WATER HEATING PARGING CEMENT INSULATION Yes PIPE ELBOW C Y N 26 (7) 1 (3) EA S0006b CHRYSOTILE 20% Yes PIPE SPRINKLER NOT INSULATED No ~ No
MECHANICAL NOT FOUND No ~ No OTHER FIRESTOPPING CEMENTITIOUS FIRESTOPPING Yes ALL C Y N 2 SF S0008 NON-ASBESTOS No
1 - cast iron
ALL DATA REPORT
1-877-322-4744 www.pinchinwest.com
2014-05-23 Victoria * Kelowna * Nakusp * Calgary * Edmonton * Red Deer * Regina * Saskatoon Website: www.pinchinwest.com * 1-877-322-4744 Page 14 of 22.
Project #: 12661K-22 Site: 1375 Nicola Street, Vancouver, BC Building Name: Berwick House Surveyor: Nadia Slakov Survey Date: 2014-05-12 Location #: 1 Location Name: Boiler room Floor: 1 Room #: Square ft: 200
LEAD PAINT
System Item Good Poor Unit Sample Sample Description Result Description Amount Lead FLOOR CONCRETE (POURED) 200 SF L0002 grey 0.95% Yes CEILING CONCRETE (POURED) 200 SF V0001 white <0.004% No
WALL CONCRETE (POURED) 500 SF L0001 white <0.004% No
Project #: 12661K-22 Site: 1375 Nicola Street, Vancouver, BC Building Name: Berwick House Surveyor: Nadia Slakov Survey Date: 2014-05-12 Location #: 2 Location Name: Electrical room and Storage Floor: 1 Room #: Square ft: 150
LEAD PAINT
System Item Good Poor Unit Sample Sample Description Result Description Amount Lead FLOOR CONCRETE (POURED) 150 SF V0002 grey 0.95% Yes WALL WOOD 200 SF L0003 teal 0.004% No
Project #: 12661K-22 Site: 1375 Nicola Street, Vancouver, BC Building Name: Berwick House Surveyor: Nadia Slakov Survey Date: 2014-05-12 Location #: 3 Location Name: Laundry Room Floor: 1 Room #: Square ft: 150
LEAD PAINT
System Item Good Poor Unit Sample Sample Description Result Description Amount Lead FLOOR CONCRETE (POURED) 150 SF V0002 grey 0.95% Yes
Project #: 12661K-22 Site: 1375 Nicola Street, Vancouver, BC Building Name: Berwick House Surveyor: Nadia Slakov Survey Date: 2014-05-12 Location #: 5 Location Name: First floor hallway Floor: 1 Room #: Square ft: 150
LEAD PAINT
System Item Good Poor Unit Sample Sample Description Result Description Amount Lead OTHER METAL 160 SF L0004 tan 0.17% Yes
Project #: 12661K-22 Site: 1375 Nicola Street, Vancouver, BC Building Name: Berwick House Surveyor: Nadia Slakov Survey Date: 2014-05-12 Location #: 7 Location Name: Sprinkler Room Floor: 1 Room #: Square ft: 150
LEAD PAINT
System Item Good Poor Unit Sample Sample Description Result Description Amount Lead FLOOR CONCRETE (POURED) 150 SF V0002 grey 0.95% Yes WALL WOOD 200 SF V0003 teal 0.004% No
ALL DATA REPORT
1-877-322-4744 www.pinchinwest.com
2014-05-23 Victoria * Kelowna * Nakusp * Calgary * Edmonton * Red Deer * Regina * Saskatoon Website: www.pinchinwest.com * 1-877-322-4744 Page 15 of 22.
Project #: 12661K-22 Site: 1375 Nicola Street, Vancouver, BC Building Name: Berwick House Surveyor: Nadia Slakov Survey Date: 2014-05-12 Location #: 8 Location Name: Storage lockers Floor: 1 Room #: Square ft: 150
LEAD PAINT
System Item Good Poor Unit Sample Sample Description Result Description Amount Lead FLOOR CONCRETE (POURED) 150 SF V0002 grey 0.95% Yes WALL WOOD 200 SF V0003 teal 0.004% No
Project #: 12661K-22 Site: 1375 Nicola Street, Vancouver, BC Building Name: Berwick House Surveyor: Nadia Slakov Survey Date: 2014-05-12 Location #: 9 Location Name: Entrance vestibule Floor: 1 Room #: Square ft: 250
LEAD PAINT
System Item Good Poor Unit Sample Sample Description Result Description Amount Lead OTHER METAL 40 SF V0004 tan 0.17% Yes
ALL DATA REPORT
1-877-322-4744 www.pinchinwest.com
2014-05-23 Victoria * Kelowna * Nakusp * Calgary * Edmonton * Red Deer * Regina * Saskatoon Website: www.pinchinwest.com * 1-877-322-4744 Page 16 of 22.
Project #: 12661K-22 Site: 1375 Nicola Street, Vancouver, BC Building Name: Berwick House Surveyor: Nadia Slakov Survey Date: 2014-05-12 Location #: 23 Location Name: Stairwell Floor: ALL Room #: Square ft: 1000
LEAD PAINT
System Item Good Poor Unit Sample Sample Description Result Description Amount Lead FLOOR CONCRETE (POURED) 1000 SF V0004 tan 0.17% Yes OTHER METAL 140 SF V0004 tan 0.17% Yes
Project #: 12661K-22 Site: 1375 Nicola Street, Vancouver, BC Building Name: Berwick House Surveyor: Nadia Slakov Survey Date: 2014-05-12 Location #: 25 Location Name: Parking Floor: B Room #: Square ft: 1000
LEAD PAINT
System Item Good Poor Unit Sample Sample Description Result Description Amount Lead WALL CONCRETE (POURED) 1000 SF V0001 white <0.004% No
ALL DATA REPORT
1-877-322-4744 www.pinchinwest.com
2014-05-23 Victoria * Kelowna * Nakusp * Calgary * Edmonton * Red Deer * Regina * Saskatoon Website: www.pinchinwest.com * 1-877-322-4744 Page 17 of 22.
Project #: 12661K-22 Site: 1375 Nicola Street, Vancouver, BC Building Name: Berwick House Surveyor: Nadia Slakov Survey Date: 2014-05-12 Location #: 12 Location Name: Second floor hall Floor: 2 Room #: Square ft: 200
Pb Products
Component Quantity Unit
BATTERIES IN EMER. LIGHTS 2 EA
Project #: 12661K-22 Site: 1375 Nicola Street, Vancouver, BC Building Name: Berwick House Surveyor: Nadia Slakov Survey Date: 2014-05-12 Location #: 14 Location Name: Third floor hall Floor: 3 Room #: Square ft: 200
Pb Products
Component Quantity Unit
BATTERIES IN EMER. LIGHTS 2 EA
Project #: 12661K-22 Site: 1375 Nicola Street, Vancouver, BC Building Name: Berwick House Surveyor: Nadia Slakov Survey Date: 2014-05-12 Location #: 16 Location Name: Fourth floor hall Floor: 4 Room #: Square ft: 200
Pb Products
Component Quantity Unit
BATTERIES IN EMER. LIGHTS 2 EA
Project #: 12661K-22 Site: 1375 Nicola Street, Vancouver, BC Building Name: Berwick House Surveyor: Nadia Slakov Survey Date: 2014-05-12 Location #: 18 Location Name: Fifth floor hall Floor: 5 Room #: Square ft: 200
Pb Products
Component Quantity Unit
BATTERIES IN EMER. LIGHTS 2 EA
Project #: 12661K-22 Site: 1375 Nicola Street, Vancouver, BC Building Name: Berwick House Surveyor: Nadia Slakov Survey Date: 2014-05-12 Location #: 20 Location Name: Sixth floor hall Floor: 6 Room #: Square ft: 200
Pb Products
Component Quantity Unit
BATTERIES IN EMER. LIGHTS 2 EA
Project #: 12661K-22 Site: 1375 Nicola Street, Vancouver, BC Building Name: Berwick House Surveyor: Nadia Slakov Survey Date: 2014-05-12 Location #: 22 Location Name: Seventh floor hall Floor: 7 Room #: Square ft: 200
Pb Products
Component Quantity Unit
ALL DATA REPORT
1-877-322-4744 www.pinchinwest.com
2014-05-23 Victoria * Kelowna * Nakusp * Calgary * Edmonton * Red Deer * Regina * Saskatoon Website: www.pinchinwest.com * 1-877-322-4744 Page 18 of 22.
BATTERIES IN EMER. LIGHTS 2 EA
Project #: 12661K-22 Site: 1375 Nicola Street, Vancouver, BC Building Name: Berwick House Surveyor: Nadia Slakov Survey Date: 2014-05-12 Location #: 23 Location Name: Stairwell Floor: ALL Room #: Square ft: 1000
Pb Products
Component Quantity Unit
BATTERIES IN EMER. LIGHTS 2 EA
Project #: 12661K-22 Site: 1375 Nicola Street, Vancouver, BC Building Name: Berwick House Surveyor: Nadia Slakov Survey Date: 2014-05-12 Location #: 25 Location Name: Parking Floor: B Room #: Square ft: 1000
Pb Products
Component Quantity Unit
BATTERIES IN EMER. LIGHTS 1 EA
ALL DATA REPORT
1-877-322-4744 www.pinchinwest.com
2014-05-23 Victoria * Kelowna * Nakusp * Calgary * Edmonton * Red Deer * Regina * Saskatoon Website: www.pinchinwest.com * 1-877-322-4744 Page 19 of 22.
Project #: 12661K-22 Site: 1375 Nicola Street, Vancouver, BC Building Name: Berwick House Surveyor: Nadia Slakov Survey Date: 2014-05-12 Location #: 2 Location Name: Electrical room and Storage Floor: 1 Room #: Square ft: 150
MERCURY
Component Quantity Unit
FLUORESCENT LIGHT TUBE1 2 EA
1 - T12
Project #: 12661K-22 Site: 1375 Nicola Street, Vancouver, BC Building Name: Berwick House Surveyor: Nadia Slakov Survey Date: 2014-05-12 Location #: 3 Location Name: Laundry Room Floor: 1 Room #: Square ft: 150
MERCURY
Component Quantity Unit
FLUORESCENT LIGHT TUBE1 6 EA
1 - T8
Project #: 12661K-22 Site: 1375 Nicola Street, Vancouver, BC Building Name: Berwick House Surveyor: Nadia Slakov Survey Date: 2014-05-12 Location #: 4 Location Name: Office Floor: 1 Room #: Square ft: 75
MERCURY
Component Quantity Unit
FLUORESCENT LIGHT TUBE1 2 EA
FLUORESCENT LIGHT TUBE2 6 EA
1 - T12 2 - T8
Project #: 12661K-22 Site: 1375 Nicola Street, Vancouver, BC Building Name: Berwick House Surveyor: Nadia Slakov Survey Date: 2014-05-12 Location #: 5 Location Name: First floor hallway Floor: 1 Room #: Square ft: 150
MERCURY
Component Quantity Unit
FLUORESCENT LIGHT TUBE1 2 EA
1 - T12
Project #: 12661K-22 Site: 1375 Nicola Street, Vancouver, BC Building Name: Berwick House Surveyor: Nadia Slakov Survey Date: 2014-05-12 Location #: 6 Location Name: Washroom Floor: 1 Room #: Square ft: 25
MERCURY
Component Quantity Unit
THERMOSTAT 1 EA
ALL DATA REPORT
1-877-322-4744 www.pinchinwest.com
2014-05-23 Victoria * Kelowna * Nakusp * Calgary * Edmonton * Red Deer * Regina * Saskatoon Website: www.pinchinwest.com * 1-877-322-4744 Page 20 of 22.
Project #: 12661K-22 Site: 1375 Nicola Street, Vancouver, BC Building Name: Berwick House Surveyor: Nadia Slakov Survey Date: 2014-05-12 Location #: 7 Location Name: Sprinkler Room Floor: 1 Room #: Square ft: 150
MERCURY
Component Quantity Unit
FLUORESCENT LIGHT TUBE1 2 EA
1 - T12
Project #: 12661K-22 Site: 1375 Nicola Street, Vancouver, BC Building Name: Berwick House Surveyor: Nadia Slakov Survey Date: 2014-05-12 Location #: 8 Location Name: Storage lockers Floor: 1 Room #: Square ft: 150
MERCURY
Component Quantity Unit
FLUORESCENT LIGHT TUBE1 2 EA
1 - T12
Project #: 12661K-22 Site: 1375 Nicola Street, Vancouver, BC Building Name: Berwick House Surveyor: Nadia Slakov Survey Date: 2014-05-12 Location #: 12 Location Name: Second floor hall Floor: 2 Room #: Square ft: 200
MERCURY
Component Quantity Unit
FLUORESCENT LIGHT TUBE 3 EA
ALL DATA REPORT
1-877-322-4744 www.pinchinwest.com
2014-05-23 Victoria * Kelowna * Nakusp * Calgary * Edmonton * Red Deer * Regina * Saskatoon Website: www.pinchinwest.com * 1-877-322-4744 Page 21 of 22.
Project #: 12661K-22 Site: 1375 Nicola Street, Vancouver, BC Building Name: Berwick House Surveyor: Nadia Slakov Survey Date: 2014-05-12 Location #: 14 Location Name: Third floor hall Floor: 3 Room #: Square ft: 200
MERCURY
Component Quantity Unit
FLUORESCENT LIGHT TUBE 3 EA
Project #: 12661K-22 Site: 1375 Nicola Street, Vancouver, BC Building Name: Berwick House Surveyor: Nadia Slakov Survey Date: 2014-05-12 Location #: 16 Location Name: Fourth floor hall Floor: 4 Room #: Square ft: 200
MERCURY
Component Quantity Unit
FLUORESCENT LIGHT TUBE 3 EA
Project #: 12661K-22 Site: 1375 Nicola Street, Vancouver, BC Building Name: Berwick House Surveyor: Nadia Slakov Survey Date: 2014-05-12 Location #: 18 Location Name: Fifth floor hall Floor: 5 Room #: Square ft: 200
MERCURY
Component Quantity Unit
FLUORESCENT LIGHT TUBE 3 EA
Project #: 12661K-22 Site: 1375 Nicola Street, Vancouver, BC Building Name: Berwick House Surveyor: Nadia Slakov Survey Date: 2014-05-12 Location #: 20 Location Name: Sixth floor hall Floor: 6 Room #: Square ft: 200
MERCURY
Component Quantity Unit
FLUORESCENT LIGHT TUBE 3 EA
Project #: 12661K-22 Site: 1375 Nicola Street, Vancouver, BC Building Name: Berwick House Surveyor: Nadia Slakov Survey Date: 2014-05-12 Location #: 22 Location Name: Seventh floor hall Floor: 7 Room #: Square ft: 200
MERCURY
Component Quantity Unit
FLUORESCENT LIGHT TUBE 3 EA
Project #: 12661K-22 Site: 1375 Nicola Street, Vancouver, BC Building Name: Berwick House Surveyor: Nadia Slakov Survey Date: 2014-05-12 Location #: 25 Location Name: Parking Floor: B Room #: Square ft: 1000
MERCURY
Component Quantity Unit
FLUORESCENT LIGHT TUBE1 11 EA
1 - T12
ALL DATA REPORT
1-877-322-4744 www.pinchinwest.com
2014-05-23 Victoria * Kelowna * Nakusp * Calgary * Edmonton * Red Deer * Regina * Saskatoon Website: www.pinchinwest.com * 1-877-322-4744 Page 22 of 22.
Legend:
Sample number Units Other
S#### Sample collected. SF Square feet SVM Suspect Visible Mould
V#### Material is visually identified to be identical to S#### LF Linear feet
V0000 Known non asbestos material. EA Each
V9000 Material is visually identified to contain asbestos. % Percentage
V9500 Material is presumed to contain asbestos. Access Condition
A Accessible to all building occupants Good No visible damage or deterioration
B Accessible to maintenance and operations staff without a ladder Fair Minor, repairable damage, cracking or deterioration.
C Accessible to maintenance and operations staff with a ladder. Also rarely entered, locked areas. Poor Irreparable damage or deterioration with exposed and
missing material.
D Not normally accessible or without demolition Action (1) Clean up of ACM Debris (2) Precautions for Access Which may Disturb ACM Debris (3) ACM removal
(4) Precautions for Work Which may Disturb ACM in Poor Condition (5) Proactive ACM removal (Minimum repair required for fair
condition) (6) ACM repair
(7) Management program and surveillance
APPENDIX V-A
ASBESTOS LABORATORY CERTIFICATES
By Polarized Light MicroscopyEPA Method: 600/R-93/116 and 600/M4-82-020
LAB #173190
1408720Lab Order ID:
Berwick House 1375 Nicola Street 12661K-22
Project:
5/13/2014Date Received:
5/20/2014Date Reported:
Sample ID
Lab Sample ID
Description
Lab NotesAsbestos Fibrous
ComponentsNon-Fibrous Components
Attributes
Treatment
Vanessa McNeilNadia Slakov
Attn:
1408720_PLMAnalysis ID:
Customer: Pinchin West Ltd.Suite 200, 13775 Commerce ParkwayRichmond BC V6V 2V4
None DetectedS0001Cementitious firestopping, Loc:2
GrayNon FibrousHeterogeneous
Crushed1408720PLM_1
Other100%
None DetectedS0002A - A PLASTER,wall,Loc:3
finish
WhiteNon FibrousHeterogeneous
Crushed1408720PLM_2
Other100%
None DetectedS0002A - B PLASTER,wall,Loc:3
base
GrayNon FibrousHeterogeneous
Crushed1408720PLM_21
Other100%
None DetectedS0002B - A PLASTER,ceiling,Loc:5
finish
TanNon FibrousHeterogeneous
Crushed1408720PLM_3
Other100%
None DetectedS0002B - B PLASTER,ceiling,Loc:5
base
GrayNon FibrousHeterogeneous
Crushed1408720PLM_22
Other100%
None DetectedS0002C - A PLASTER,ceiling,Loc:5
finish
TanNon FibrousHeterogeneous
Crushed1408720PLM_4
Other100%
None DetectedS0002C - B PLASTER,ceiling,Loc:5
base 1
TanNon FibrousHeterogeneous
Crushed1408720PLM_23
Other100%
None DetectedS0002C - C PLASTER,ceiling,Loc:5
base 2
GrayNon FibrousHeterogeneous
Crushed1408720PLM_24
Other100%
Disclaimer: Due to the nature of the EPA 600 method, asbestos may not be detected in samples containing low levels of asbestos. We strongly recommended that analysis of floor tiles, vermiculite, and/or heterogeneous soil samples be conducted by TEM for confirmation of “None Detected” by PLM. This report relates only to the samples tested and may not be reproduced, except in full, without the written approval of SAI. This report may not be used by the client to claim product endorsement by NVLAP or any other agency of the U.S. government. Estimated MDL is 0.5%.
Page 1 of 4
Approved SignatoryAnalyst
Scientific Analytical Institute, Inc. 4604 Dundas Dr. Greensboro, NC 27407 (336) 292-3888
Dorlos Ammerman (29)
plm_3.3.009
By Polarized Light MicroscopyEPA Method: 600/R-93/116 and 600/M4-82-020
LAB #173190
1408720Lab Order ID:
Berwick House 1375 Nicola Street 12661K-22
Project:
5/13/2014Date Received:
5/20/2014Date Reported:
Sample ID
Lab Sample ID
Description
Lab NotesAsbestos Fibrous
ComponentsNon-Fibrous Components
Attributes
Treatment
Vanessa McNeilNadia Slakov
Attn:
1408720_PLMAnalysis ID:
Customer: Pinchin West Ltd.Suite 200, 13775 Commerce ParkwayRichmond BC V6V 2V4
None DetectedS0002D - A PLASTER,ceiling,Loc:5
finish
WhiteNon FibrousHeterogeneous
Crushed1408720PLM_5
Other100%
None DetectedS0002D - B PLASTER,ceiling,Loc:5
base
GrayNon FibrousHeterogeneous
Crushed1408720PLM_25
Other100%
None DetectedS0002E - A PLASTER,wall,Loc:6
finish
WhiteNon FibrousHeterogeneous
Crushed1408720PLM_6
Other100%
None DetectedS0002E - B PLASTER,wall,Loc:6
base
GrayNon FibrousHeterogeneous
Crushed1408720PLM_26
Other100%
None DetectedS0002F - A PLASTER,wall,Loc:18
finish
WhiteNon FibrousHeterogeneous
Crushed1408720PLM_7
Other100%
None DetectedS0002F - B PLASTER,wall,Loc:18
base
GrayNon FibrousHeterogeneous
Crushed1408720PLM_27
Other100%
None DetectedS0002G - A PLASTER,wall,Loc:12
finish
WhiteNon FibrousHeterogeneous
Crushed1408720PLM_8
Other100%
None DetectedS0002G - B PLASTER,wall,Loc:12
base
GrayNon FibrousHeterogeneous
Crushed1408720PLM_28
Other100%
Disclaimer: Due to the nature of the EPA 600 method, asbestos may not be detected in samples containing low levels of asbestos. We strongly recommended that analysis of floor tiles, vermiculite, and/or heterogeneous soil samples be conducted by TEM for confirmation of “None Detected” by PLM. This report relates only to the samples tested and may not be reproduced, except in full, without the written approval of SAI. This report may not be used by the client to claim product endorsement by NVLAP or any other agency of the U.S. government. Estimated MDL is 0.5%.
Page 2 of 4
Approved SignatoryAnalyst
Scientific Analytical Institute, Inc. 4604 Dundas Dr. Greensboro, NC 27407 (336) 292-3888
Dorlos Ammerman (29)
plm_3.3.009
By Polarized Light MicroscopyEPA Method: 600/R-93/116 and 600/M4-82-020
LAB #173190
1408720Lab Order ID:
Berwick House 1375 Nicola Street 12661K-22
Project:
5/13/2014Date Received:
5/20/2014Date Reported:
Sample ID
Lab Sample ID
Description
Lab NotesAsbestos Fibrous
ComponentsNon-Fibrous Components
Attributes
Treatment
Vanessa McNeilNadia Slakov
Attn:
1408720_PLMAnalysis ID:
Customer: Pinchin West Ltd.Suite 200, 13775 Commerce ParkwayRichmond BC V6V 2V4
None DetectedS0003 - A
VINYL SHEET FLOORING,beige w black dots,Loc:5
vinyl
BeigeNon FibrousHeterogeneous
Dissolved1408720PLM_9
Fiber Glass Other5% 95%
None DetectedS0003 - B
VINYL SHEET FLOORING,beige w black dots,Loc:5
mastic
YellowNon FibrousHeterogeneous
Dissolved1408720PLM_29
Cellulose Other2% 98%
None DetectedS0004ATEXTURE FINISH ( TEXTURE COAT),ceiling,Loc:5
TanNon FibrousHeterogeneous
Crushed1408720PLM_10
Other100%
None DetectedS0004BTEXTURE FINISH ( TEXTURE COAT),ceiling,Loc:5
TanNon FibrousHeterogeneous
Crushed1408720PLM_11
Other100%
None DetectedS0004CTEXTURE FINISH ( TEXTURE COAT),ceiling,Loc:5
TanNon FibrousHeterogeneous
Crushed1408720PLM_12
Other100%
None DetectedS0004DTEXTURE FINISH ( TEXTURE COAT),wall,Loc:23
TanNon FibrousHeterogeneous
Crushed1408720PLM_13
Other100%
None DetectedS0004ETEXTURE FINISH ( TEXTURE COAT),wall,Loc:23
TanNon FibrousHeterogeneous
Crushed1408720PLM_14
Other100%
None DetectedS0006APARGING CEMENT INSULATION,,Loc:7
GrayFibrousHeterogeneous
Teased1408720PLM_15
Cellulose Fiber Glass
Other 20%
5%75%
Disclaimer: Due to the nature of the EPA 600 method, asbestos may not be detected in samples containing low levels of asbestos. We strongly recommended that analysis of floor tiles, vermiculite, and/or heterogeneous soil samples be conducted by TEM for confirmation of “None Detected” by PLM. This report relates only to the samples tested and may not be reproduced, except in full, without the written approval of SAI. This report may not be used by the client to claim product endorsement by NVLAP or any other agency of the U.S. government. Estimated MDL is 0.5%.
Page 3 of 4
Approved SignatoryAnalyst
Scientific Analytical Institute, Inc. 4604 Dundas Dr. Greensboro, NC 27407 (336) 292-3888
Dorlos Ammerman (29)
plm_3.3.009
By Polarized Light MicroscopyEPA Method: 600/R-93/116 and 600/M4-82-020
LAB #173190
1408720Lab Order ID:
Berwick House 1375 Nicola Street 12661K-22
Project:
5/13/2014Date Received:
5/20/2014Date Reported:
Sample ID
Lab Sample ID
Description
Lab NotesAsbestos Fibrous
ComponentsNon-Fibrous Components
Attributes
Treatment
Vanessa McNeilNadia Slakov
Attn:
1408720_PLMAnalysis ID:
Customer: Pinchin West Ltd.Suite 200, 13775 Commerce ParkwayRichmond BC V6V 2V4
20% ChrysotileS0006BPARGING CEMENT INSULATION,,Loc:25
GrayFibrousHeterogeneous
Crushed1408720PLM_16
Mineral Wool Other10% 70%
None DetectedS0007ATEXTURE FINISH ( TEXTURE COAT),ceiling,Loc:21
WhiteNon FibrousHeterogeneous
Crushed1408720PLM_17
Cellulose Other5% 95%
None DetectedS0007BTEXTURE FINISH ( TEXTURE COAT),ceiling,Loc:19
WhiteNon FibrousHeterogeneous
Crushed1408720PLM_18
Cellulose Other5% 95%
None DetectedS0007CTEXTURE FINISH ( TEXTURE COAT),ceiling,Loc:13
WhiteNon FibrousHeterogeneous
Crushed1408720PLM_19
Cellulose Other5% 95%
None DetectedS0008Cementitious firestopping,,Loc:25
GrayNon FibrousHeterogeneous
Crushed1408720PLM_20
Other100%
Disclaimer: Due to the nature of the EPA 600 method, asbestos may not be detected in samples containing low levels of asbestos. We strongly recommended that analysis of floor tiles, vermiculite, and/or heterogeneous soil samples be conducted by TEM for confirmation of “None Detected” by PLM. This report relates only to the samples tested and may not be reproduced, except in full, without the written approval of SAI. This report may not be used by the client to claim product endorsement by NVLAP or any other agency of the U.S. government. Estimated MDL is 0.5%.
Page 4 of 4
Approved SignatoryAnalyst
Scientific Analytical Institute, Inc. 4604 Dundas Dr. Greensboro, NC 27407 (336) 292-3888
Dorlos Ammerman (29)
plm_3.3.009
APPENDIX V-B
LEAD LABORATORY CERTIFICATES
Pinchin West Ltd.Suite 200, 13775 Commerce ParkwayRichmond BC V6V 2V4
Customer:
Analysis ID: 1408723_PBP
Attn: Vanessa McNeilNadia Slakov
Date Reported: 5/16/2014
Date Received: 5/13/2014
Project: Berwick House 1375 Nicola Street 12661K-22
Lab Order ID: 1408723
Lab Notes
Description
Lab Sample ID
Sample ID
by Flame Atomic Absorption SpectroscopyEPA SW-846 3rd Ed. Method No. 3050B/Method No. 7420
Analytical Sensitivity
(% by weight)(g)
Mass Concentration
(% by weight)
1408723PBP_1
WALL, CONCRETE (POURED), white,Loc:1L00010.001%0.1139 < 0.004%
1408723PBP_2
FLOOR, CONCRETE (POURED), grey,Loc:1L00020.001%0.1023 0.95%
1408723PBP_3
WALL, WOOD, teal,Loc:2L00030.001%0.1155 0.004%
1408723PBP_4
OTHER, METAL, tan,Loc:5L00040.002%0.0712 0.17%
The quality control samples run with the samples in this report have passed all AIHA required specifications unless otherwise noted. This report relates only to the samples tested and may not be reproduced, except in full, without the written approval of SAI. This report may not be used by the client to claim product endorsement by AIHA or any
other agency of the U.S. government. (R.L. = 0.01 wt.%)
Kristin Cooke (4)
Scientific Analytical Institute, Inc. 4604 Dundas Dr. Greensboro, NC 27407 (336) 292-3888
Analyst Laboratory DirectorPage 1 of 1
pbRpt_3.4.02/pbCalc_3.4.01
APPENDIX VI
PHOTOGRAPHS
Photographs Appendix VI
© 2014 Pinchin West Ltd. Page 1
Photo 1 – Asbestos-containing parging cement insulation on pipe elbows in the Parkade
(Location 25) and the Sprinkler Room (Location 7).
Photo 2 – Asbestos-containing parging cement insulation on pipe elbow in poor condition in the Sprinkler Room (Location 7).
Photographs Appendix VI
© 2014 Pinchin West Ltd. Page 2
Photo 3 – Asbestos-containing parging cement insulation on pipe elbow in poor condition in the Parkade (Location 25).
Photo 4 – Asbestos-containing aircell pipe insulation on straight pipe sections in the Parkade (Location 25).
Photographs Appendix VI
© 2014 Pinchin West Ltd. Page 3
Photo 5– One linear foot of aircell pipe insulation in poor condition in the Parkade (Location 25).
Photo 6 – Leaded grey paint on floors (Location 1, 2, 3, 7, and 8).
Photographs Appendix VI
© 2014 Pinchin West Ltd. Page 4
Photo 7 – Leaded tan paint on metal doors (Locations 5, 9, and 23).
APPENDIX VII
DRAWINGS