harmonics study on distrubution transformer

Upload: suresh-babu-b-v

Post on 08-Apr-2018

223 views

Category:

Documents


0 download

TRANSCRIPT

  • 8/6/2019 Harmonics Study on Distrubution Transformer

    1/31

    TTHHEE DDEETTAA IILLEEDD II NNVVEESSTT IIGGAATT IIOONN OOFF

    TTHHEE EEFFFFEECCTTSS OOFF HH IIGGHH HHAARRMMOONN IICCSS

    AANNDD LLOOWW PPOOWWEERR FFAACCTTOORR OOFF LLOOWW

    CCOOSSTT EENNEERRGGYY EEFFFF IICC IIEENNTT LL IIGGHHTT IINNGG

    DDEEVV IICCEESS II NN AA TTYYPP IICCAALL RRUURRAALL

    EELLEECCTTRR IICCAALL DD IISSTTRR IIBBUUTT IIOONN SSYYSSTTEEMM

    P R O J E C T R E P O R T

    Prepared By

    INTEGRATED RURAL TECHNOLOGY CENTREM U N D U R , P A L A K K A D

    Submitted To

    KERALA STATE ELECTRICITY BOARDThiruvananthapuram

  • 8/6/2019 Harmonics Study on Distrubution Transformer

    2/31

    P R O J E C T T E A M

    Principal Investigator

    Dr. M. P. Parameswaran

    Fellow, IRTC

    Co-investigators

    Dr. R. V. G. Menon (Fellow, IRTC)Mr. K. Bhaskaran (Fellow, IRTC)Mr. R.Satheesh (Scientist, IRTC)

    Mr. B.V. Suresh Babu (Scientist, IRTC)

    Mr. Haynes Davis (Scientist, IRTC)Mr. Bency Zachariah (Scientist, IRTC)

    Mr. Vimal Raj ((Scientist, IRTC)

  • 8/6/2019 Harmonics Study on Distrubution Transformer

    3/31

    C O N T E N T S

    ACKNOWLEDGMENT .................................. 5

    1 INTRODUCTION .............................. .......... 6

    2 SPECIFIC OBJECTIVES OF THE PROJECT ............ 7

    3 METHODOLOGY ................................. ....... 7

    3.1 Laboratory Study .......................... .... 8

    3.2 Real Time Field Study ........................ 8

    4 ANALYSIS OF TEST RESULTS ......................... 9

    4.1 Laboratory Study .......................... .... 9

    4.2 Real Time Field Study ........................ 10

    5 CONCLUSIONS ................................ ......... 11

    6 ECONOMIC SIGNIFICANCE OF THE STUDY .......... 12

    6.1 Consumer End .......................... ....... 12

    6.2 Provider End ............................. ...... 12

    7 RECOMMENDATIONS ............................ ...... 13

    ANNEXE 1

    LABORATORY AND FIELD DATA ..................... 15

    ANNEXE 2

    VOLTAGE AND CURRENT WAVEFORMS ............. 26

  • 8/6/2019 Harmonics Study on Distrubution Transformer

    4/31

    ANNEXE 1

    L A B O R A T O R Y A N D F I E L D D A T A

    1. LABORATORY DATA

    TABLE 1 CFLs of different brands

    TABLE 2 CFLs added in 11 steps in single phaseTABLE 3 CFLs connected in balanced condition

    TABLE 4 CFLs connected in unbalanced conditionTABLE 5 Transformer loss and primary & secondary harmonics for CFL and

    incandescent lamp circuits

    TABLE 6 Transformer temperature for the CFL circuitTABLE 7 Transformer temperature for the incandescent lamp circuitTABLE 8 Lumen per watt for different makes of CFLs and incandescent lampsTABLE 9 Simulation of a domestic consumer's load

    2. FIELD DATA

    TABLE 10 Data at the consumer test pointsTABLE 11 Connected load at test point 1 and 2 as on the dates of measurementsTABLE 12 Data at the transformer end before the replacement

    TABLE 13 Data at the transformer end after the replacementTABLE 14 No. of incandescent lamps replaced

    ANNEXE 2

    V O L T A G E A N D C U R R E N T W A V E F O R M S

    1. LAB STUDY

    1.1 Addition of CFLs in 11 steps

    2. REAL TIME FIELD STUDY

    2.1 Test point 12.2 Test point 22.3 Transformer point

  • 8/6/2019 Harmonics Study on Distrubution Transformer

    5/31

    ACKNOWLEDGMENT

    IRTC is very happy to extend its thanks to all who participated for the successful completion

    of the project.

    We are grateful to all the officials of Kerala State Electricity Board who is supported this

    project.

    We also remember all the advices given by Dr. Padmanabhan Nambiar, Chairman, Dept. of

    Electrical Engineering, AITS, Coimbatore.

    The support and co-operation of the all the eminent personalities of various institutions and

    the natives of Poriyani, Palakkad where the fieldwork was carried out are remembered with

    gratitude.

    Thank you.

  • 8/6/2019 Harmonics Study on Distrubution Transformer

    6/31

    6

    1. INTRODUCTION

    It is well accepted that energy conservation has equal or even more

    importance compared with installation of new generating capacities in meeting

    the demand for electrical energy. The relevance of Demand Side

    Management (DSM), i.e., the energy planning strategy with emphasis on

    reducing the energy demand by the use of energy efficient technologies at the

    user end, over the Supply Side Management (SSM), has been now

    universally recognised.

    According to a study done by IRTC, about one third of the total power

    consumption of Kerala and three fourth of the peak load, is for lighting

    purpose. The study also revealed that the energy consumption could be

    reduced significantly if energy-efficient lighting devices like fluorescent tubes

    and Compact Fluorescent Lamps (CFLs) are used instead of the ordinary

    incandescent bulbs.

    However CFLs and other fluorescent lamps with electronic chokes if used in

    large numbers may cause, it is feared, severe depression in the power factor

    on the one hand and induce high levels of harmonics within the system, which

    may lead to higher losses and system instabilities.

    Because of the huge demand for the CFLs and electronic choke for the

    fluorescent tubes, a number of manufacturers have ventured into this

    business and flooded the market with cheap and low quality products. Since

    the market is very competitive, the manufacturers are compromising on the

    quality of the product so as to offer their products at lower prices. Even the

    multinationals and the reputed manufacturers are selling low quality products.

    A typical high quality CFL with over voltage protection and well-suppressed

    harmonics can cost anywhere between Rs. 300 to Rs. 450. As many as 70 to

    80 component parts are required to make the chokes of necessary quality.

  • 8/6/2019 Harmonics Study on Distrubution Transformer

    7/31

    7

    Compared to this cheaper CFLs, without any of the above is being sold at Rs

    100 to 120. CFLs that are ridiculously cheap have been dumped with in the

    market from China (LEUCI Brand), SreeLanka (Honey Queen), Japan

    (MYOTA) and are sold Rs 25 to 30. A large number of consumers maychangeover from incandescent lamps to these CFLs. Electricity Board and

    Government may want to encourage this. It has become urgent to the study

    the technical performance of these lamps i.e.; impact of harmonics cost

    effectiveness etc.

    It was suspected that high harmonics and low power factor caused by these

    devices might damage the power quality and efficiency of the distribution

    system. In this context it was felt necessary that a detailed study on the effect

    of substantial induction of low quality compact fluorescent lamps in a rural

    distribution system be carried out. This is the context of present study carried

    out jointly by IRTC and KSEB.

    2. SPECIFIC OBJECTIVES OF THE PROJECT

    1. To conduct a series of laboratory investigations to measure the level of

    high harmonics and low power factor of the low quality CFLs.

    2. To conduct a real-time field study in a selected transformer in a typical

    electrical major section to investigate the impact of high harmonics and

    low power factor on the electrical distribution system.

    3. To prepare technical recommendations and guidelines for formulating

    policies regarding the propagation/popularisation of the energy efficient

    lighting devices.

    3. METHODOLOGY

    The study was conducted in two phases,

    1.The laboratory study.

    2.The real time field study

    The Poriyani 160 kVA transformer under Electrical Major Section, Kongad in

    Electrical Division, Palakkad was selected for the investigation after

  • 8/6/2019 Harmonics Study on Distrubution Transformer

    8/31

    8

    consultations with the Deputy Chief Engineer, Palakkad. A 4kVA transformer

    was made available for carrying out a laboratory test by simulating load

    conditions

    3.1. Laboratory Test

    The laboratory test was conducted in the following phases.

    1. Loading the test transformer with incandescent lamps, totaling to

    wattage of about 3000 W in R, Y & B phases in balanced and

    unbalanced conditions in different steps and combinations

    2. Loading the transformer with compact fluorescent lamps totaling to a

    wattage of 3000 W to R, Y & B phases in balanced and unbalanced

    conditions in different steps and combinations

    3. Taking different measurements in both cases, of the following

    parameters

    a. Level of current harmonics and distortion on the transformer

    b. Level of voltage harmonics and distortion

    c. Effect of heating on the core and winding of the transformer

    d. Effect on the power factor of the system

    e. Energy loss due to the lighting loadsf. Lumens/Watt

    4. The load conditions of an ideal domestic consumer were simulated on

    the lab transformer and all the relevant parameters were measured.

    3.2. Real Time Field Study

    The methodology for the detailed investigation in the field i.e.; on

    Poriyani 160kVA transformer was finalised in consultation with experts in a

    workshop held on 18-06-2003. In the discussions that followed KSEB

    engineers provided the details of the existing consumers connected to the

    transformer, which has two low tension distribution feeders. In the field the

    study was carried out in the following phases

  • 8/6/2019 Harmonics Study on Distrubution Transformer

    9/31

    9

    1. Taking all the relevant readings at the transformer mains and

    sending end terminals of feeders I & II in the existing load

    conditions.

    2. Taking all the relevant readings at two selected domestic consumerpremises connected to feeder II in the existing load conditions.

    3. Replacing 190 incandescent lamps in 45 domestic premises

    connected to feeder II.

    4. Taking all the relevant readings at two selected domestic consumer

    premises connected to feeder II after replacement of incandescent

    lamps by CFLs.

    5. Taking all the relevant readings at the transformer mains and

    sending end terminals of feeders I & II after replacement of

    incandescent lamps.

    4. ANALYSIS OF TEST RESULTS

    4.1. Laboratory Study

    1.The Power factor of individual low cost CFLs is found to be very low in the

    order of 0.5 to 0.6. (TABLE 1)

    2.The power factor was found to improve as the total number of CFLs in thecircuit increased. (TABLE 2 -4)

    3.The total harmonic distortion is high for the individual CFLs. (TABLE 1). But

    THD decreased as the number of CFLs in the circuit increased. (TABLES 2

    - 4)

    4.Harmonics induced at the transformer primary was found to be much lesser

    than that at the secondary. (TABLE 5)

    5.Transformer loss was found to be higher for the CFLs compared to the

    incandescent circuit of equivalent wattage (TABLE 5).

    6.Due to the low power factor of the CFLs high current was drawn, higher

    than the incandescent lamps for the same wattage. As a result the

    temperature increase was greater for the CFL circuit but only three or four

    degrees. (TABLES 6 & 7)

  • 8/6/2019 Harmonics Study on Distrubution Transformer

    10/31

    10

    7.Lumen per watt for the CFLs is much higher than that for the incandescent

    lamps. There is no much variation in lumen out put even at system voltage

    as low as 130 V, when CFLs are used (TABLE 8)

    8.For the same lumen output much lesser power is consumed in the case ofCFLs and hence much lower current is drawn. Therefore the temperature

    rise and the transformer loss would be ultimately reduced.

    9.Load condition of a typical consumer was simulated in the lab. The load of

    CFLs (39 W) is of smaller percentage of the total connected load (732 W

    &2080 W with and without pump motor respectively). The power factor

    improves considerably with motors and CFLs used concurrently in the

    system (TABLE 9)

    10. Waveforms distortions were very much higher at the test points due to

    other loads such as television as compared to the addition of CFLs.

    (TABLE 9)

    4.2. Field study

    1. Poriyani- II (160 kVA) transformer was selected for the field study. The

    transformer is too under loaded (only around 60 kVA at peak hours) and

    unbalanced to obtain an objective assessment of the impact of replacing

    incandescent lamps with CFL on the transformer performance.

    2.The power quality varied extensively from test point to test point due to

    system fluctuations.

    3.The nature of the waveforms at various test points depended mainly on the

    load nature. The connected load at the two test points for different dates of

    measurement is given in TABLE 11.

    4.At the peak hours the power factor at the transformer was found to be unity

    and the harmonics much lesser before the lamps were replaced.

    5.As the incandescent lamps were replaced with the CFLs the power factor of

    the system decreased only nominally, but the total harmonic distortion

    increased noticeably. (TABLE 10 ,12 & 13)

  • 8/6/2019 Harmonics Study on Distrubution Transformer

    11/31

    11

    5. CONCLUSIONS

    1.The field study revealed that the replacement of the existing incandescent

    lamps with CFLs resulted in a reduction of load current (by 33 % in the LT

    feeder under investigation). Calculation showed that the distribution loss in the

    local network could be reduced substantially (about 40 % in the feeder

    concerned).

    2. The total power consumed by the CFLs to give the equivalent lumen

    output will be less than 20 to 25 % of the power consumed by the

    incandescent lamps. This reduces the total current in the transformer, thereby

    reducing the transformer losses.

    3.The effects of low power factor and high harmonics in the system by the

    addition of the low quality CFLs were not found predominant in the rural

    distribution system under investigation where electrical appliances of

    heterogeneous nature such as TV, fridge, pumping motor etc. are connected.

    The overall power factor was observed to fall from unity to 0.95 only. This is

    not very much significant taking the overall system characteristic into

    consideration.

    4.Electrical appliances such as TV cause much more harmonic distortions

    than by CFLs5. The present study is adequate to show,

    a) For identical end use conditions (same or slightly improved illumination)

    total replacement of incandescent lamps by CFLs doesnt cause

    1) Any disturbance to the operation of other equipments like TV, radio,

    computer etc.

    2) Does provide comparatively more illumination at lower voltages as is

    usual in Kerala rural areas.

    3) The overall load current and hence line and transformer losses

    come down. The actual value depends upon the original share of lighting load

    in the system

    4) When the transformer are fully loaded in kVA rating the active power

    outputs will be lesser because of reduced power factor, but can serve more

  • 8/6/2019 Harmonics Study on Distrubution Transformer

    12/31

    12

    consumers because the power required by each for the same end use

    services is reduced.

    b) It will be, therefore, reasonable to argue that a total change over to CFLs in

    the entire system can be thought of.

    c) The next stage of the experiment could be to replace the incandescent

    lamps in an overloaded section by CFLs at Electricity Boards expense and

    observe the consequent reduction in load, reduction in the line losses and

    work out the real economy of such a program.

    It has been found the cheap CFLs are poorer in quality than the

    costlier ones, not only in current quality and lumen output per watt, but also

    with respect to the overall lifetime. 25 % of the lamps purchased failed before

    they reached three hundred hours of total operation. The present estimation

    based on the performance of remaining lamps is that average life will not be

    more than 1000 hours, as compared to the normally claimed life of 6000

    hours for good quality CFLs. A study of the failure mode of these cheap

    imported CFLs might reveal some common features, which possibly can be

    rectified with out considerable increase in cost. The following simple

    calculation compares the economic performance of the cheap and high quality

    CFLs for 6000 hours. The 60 W incandescent lamp, 10 W high quality CFL

    and 15 W low quality CFL are having comparable lumen output.

    Average unit cost of electricity = Rs 2.50

    No. of hours of burning = 4 hours per day on an average

    Expense for the three options for a period of 6000 hours

    Incandescent

    lamp (60 W)

    High quality

    CFL (10 W)

    Low quality

    CFL (15 W)

    Life 1000 6000 1000

    Cost per piece (Rs) 12 350 30

    Capital cost (Rs) * 72 350 180

    Interest 19 140 47

    Energy consumption 360 60 90

    Energy cost 900 150 225

    Total expenditure 991 640 452

  • 8/6/2019 Harmonics Study on Distrubution Transformer

    13/31

    13

    * (Six replacements are to be made for incandescent lamp and low quality CFL)

    For the consumer cheap CFLs work out cheaper, for identical lumen output.

    From Electricity Boards point of viewCapital cost per watt delivered at consumer end = Rs 50. Distribution loss is

    30% with incandescent lamps and 20 % with CFLs. To deliver 60 W at user

    end 87 W has to be generated by the Board.

    Savings due to the replacement of a 60 W incandescent bulb by high quality

    and low quality CFLs having comparable lumen output

    *(@ 20 % distribution loss)

    Here the difference in the savings when using the high quality CFLs and the

    low quality CFLs is only marginal.

    6. RECOMMENDATIONS

    1) Energy-efficient lighting devices like fluorescent tubes and Compact

    Fluorescent Lamps (CFLs) have 6tob be promoted by the KSEB instead of

    ordinary incandescent lamps.2) Energy-efficient lighting devices like fluorescent tubes and Compact

    Fluorescent Lamps (CFLs) have to be distributed to the consumers at the

    board's expense.

    3) As the first step towards this and as the continuation of this study a typical

    urban section and also a rural section have to be selected and the long term

    High quality

    CFL (10 W)

    Low quality CFL

    (15 W)

    Wattage to be generated* 12.5 18.75

    Savings in wattage 87-12.5 = 74.5 87-18.75 = 68.25

    Savings in generation cost

    @ Rs 50 / W3725 3412.5

    Amount to be invested (Rs) 350 180

    Net savings (Rs) 3375 3232.5

  • 8/6/2019 Harmonics Study on Distrubution Transformer

    14/31

    14

    implications has to be studied and also the quantitative analysis of the savings

    made has to be made for a period of at least six months .

    4) For maintaining the quality of the electric supply the KSEB has to begin

    with those electronic equipment such as the television, UPS etc. whichproduce larger harmonic current in the electric distribution system

    5) The active filters or the static compensators can be installed at the

    transformer end or at the substation level to suppress the harmonic current

    and also to improve the power factor of the system.

    6) Advanced researches are to be promoted in this field.

  • 8/6/2019 Harmonics Study on Distrubution Transformer

    15/31

    15

    ANNEXE 1

    TABLE 1

    LABORATORY TEST RESULTS WITH CFLS

    Brand V (V) I (mA) W (W) PF THD %-V THD %-I Harmonics

    honey queen 220 73.00 9.40 0.59 3.229 101.983

    3rd79.112

    9th18.372

    31st2.237

    5th49.355

    11th16.445

    41st1.5

    7th26.312

    21st4.573

    51st1.824

    myota 220 63.40 7.72 0.56 3.272 78.133

    3rd60.617

    9th15.334

    31st4.597

    5th23.584

    11th15.15

    41st3.572

    7th15.035

    21st10.4

    51st2.799

    leuci 220 60.80 7.91 0.59 3.383 107.336

    3rd81.195

    9th14.636

    31st4.988

    5th

    51.62211th

    15.91341st

    3.617th

    22.8421st

    9.83951st

    2.758

  • 8/6/2019 Harmonics Study on Distrubution Transformer

    16/31

    16

    TABLE 2

    LABORATORY TEST RESULTS WITH CFLS (added in 11 steps in single

    phase)

    STEP V I W PF THD %-V THD %-I Harmonics

    1 222 2.83 339.00 0.54 4.625 119.2

    3rd83.596

    9th31.203

    31st1.975

    5th61.742

    11th18.382

    41st0.283

    7th44.854

    21st0.857

    51st0.074

    2 217 5.04 659.00 0.6 5.993 112.1

    3rd84.485

    9th20.393

    31st0.635

    5th59.619

    11th10.117

    41st0.338

    7th36.252

    21st1.104

    51st0.162

    3 218 6.83 970.00 0.65 6.597 98.09

    3rd80.076

    9th10.027

    31st0.121

    5th49.868

    11th4.425

    41st0.316

    7th24.33

    21st0.937

    51st0.158

    4 210 8.56 1220.00 0.68 7.871 90.92

    3rd 77.5069th

    4.8231st

    0.2515th

    44.097

    11th

    4.776

    41st

    0.1897th16.012

    21st0.326

    51st0.288

    5 207 10.10 1460.00 0.7 9.318 86.67

    3rd75.315

    9th6.546

    31st0.264

    5th39.937

    11th5.086

    41st0.188

    7th12.732

    21st0.478

    51st0.292

    6 205 11.70 1740.00 0.72 9.571 75.26

    3rd68.661

    9th7.714

    31st0.431

    5th28.435

    11th2.578

    41st0.386

    7th7.886

    21st0.723

    51st0.239

    7 191 13.20 1860.00 0.74 9.221 71.79

    3rd66.555

    9th6.024

    31st0.242

    5th25.215

    11th0.887

    41st0.106

    7th6.718

    21st0.841

    51st0.201

    8 195 14.60 2160.00 0.76 10.593 70.59

    3rd65.855

    9th5.304

    31st0.232

    5th 24.174 11th 0.759 41st 0.1157th

    5.17621st

    0.74251st

    0.046

    9 192 16.10 2380.00 0.77 12.173 67.85

    3rd64.056

    9th5.489

    31st0.171

    5th21.165

    11th1.431

    41st0.184

    7th3.747

    21st0.524

    51st0.035

    10 195 17.90 2720.00 0.78 13.59 64.54

    3rd61.621

    9th1.845

    31st0.232

    5th17.769

    11th1.127

    41st0.176

    7th4.287

    21st0.245

    51st0.06

    11 191 19.70 2990.00 0.8 13.734 57.83

    3rd55.916

    9th3.363

    31st0.244

    5th10.913

    11th2.2

    41st0.17

    7th8.518

    21st0.59

    51st0.153

  • 8/6/2019 Harmonics Study on Distrubution Transformer

    17/31

    17

    TABLE 3

    LABORATORY TEST RESULTS WITH CFLS CONNECTED IN BALANCED

    CONDITION

    STEP 1V I W PF THD %-V THD %-I Harmonics

    R 207 2.43 335.00 0.67 7.319 106.1

    3rd84.317

    9th7.931

    31st0.61

    5th56.596

    11th3.745

    41st0.523

    7th28.213

    21st1.561

    51st0.404

    Y 204 2.33 312.00 0.66 6.914 109.6

    3rd85.258

    9th11.24

    31st1.644

    5th59.233

    11th3.621

    41st0.471

    7th32.203

    21st1.231

    51st0.23

    B 200 2.28 291.00 0.64 6.369 108

    3rd84.925

    9th9.757

    31st0.743

    5th58.124

    11th1.845

    41st0.322

    7th30.474

    21st0.72

    51st0.084

    STEP 2

    R 217 4.41 679.00 0.71 9.72 91.68

    3rd77.522

    9th5.4

    31st0.437

    5th45.098

    11th5.455

    41st0.336

    7th17.188

    21st1.145

    51st0.326

    Y 216 4.07 617.00 0.7 8.683 96.39

    3rd79.981

    9th6.022

    31st0.524

    5th48.871

    11th5.839

    41st0.428

    7th20.198

    21st1.264

    51st0.253

    B 214 4.15 614.00 0.69 8.123 95.14

    3rd79.861

    9th6.094

    31st0.672

    5th47.034

    11th6.221

    41st0.446

    7th18.818

    21st1.136

    51st0.207

    STEP 3

    R 209 5.99 960.00 0.77 11.194 77.11

    3rd

    70.519th

    5.17431st

    0.3375th30.233

    11th2.505

    41st0.152

    7th3.557

    21st0.59

    51st0.022

    Y 205 5.68 876.00 0.75 10.045 79.39

    3rd71.752

    9th5.702

    31st0.345

    5th32.69

    11th3.75

    41st0.236

    7th5.218

    21st0.712

    51st0.15

    B 204 5.67 858.00 0.74 9.572 77.83

    3rd70.746

    9th5.254

    31st0.468

    5th31.499

    11th2.578

    41st0.585

    7th3.986

    21st0.417

    51st0.036

  • 8/6/2019 Harmonics Study on Distrubution Transformer

    18/31

    18

    TABLE 4LABORATORY TEST RESULTS WITH CFLS CONNECTED IN UNBALANCEDCONDITION

    V I W PF THD %-V THD %-I Harmonics

    R 212 5.90 956.00 0.76 12.375 74.61

    3rd68.629

    9th6.049

    31st0.28

    5th28.012

    11th2.847

    41st0.264

    7th4.057

    21st0.602

    51st0.155

    Y 208 5.67 888.00 0.75 10.047 79.52

    3rd71.877

    9th6.4

    31st0.376

    5th32.544

    11th3.774

    41st0.15

    7th5.744

    21st0.593

    51st0.141

    B 219 2.55 323.00 0.63 5.324 105

    3rd83.668

    9th6.987

    31st0.507

    5th56.095

    11th3.508

    41st0.77

    7th27.774

    21st1.16

    51st0.446

    STEP 2

    R 212 6.09 976.00 0.76 11.293 74.65

    3rd68.755

    9th5.512

    31st0.467

    5th28.004

    11th3.036

    41st0.389

    7th2.245

    21st0.609

    51st0.289

    Y 203 5.65 847.00 0.74 10.156 80.69

    3rd72.459

    9th4.954

    31st0.592

    5th34.111

    11th3.518

    41st0.182

    7th6.804

    21st0.952

    51st0.059

    B 210 4.10 597.00 0.69 7.805 89.8

    3rd77.25

    9th2.108

    31st0.345

    5th43.162

    11th4.597

    41st0.165

    7th13.747

    21st0.78

    51st0.223

    STEP 3

    R 209 5.99 960.00 0.77 11.194 77.11

    3rd70.51

    9th5.174

    31st0.337

    5th 30.233 11th 2.505 41st 0.1527th

    3.55721st

    0.5951st

    0.022

    Y 205 5.68 876.00 0.75 10.045 79.39

    3rd71.752

    9th5.702

    31st0.345

    5th32.69

    11th3.75

    41st0.236

    7th5.218

    21st0.712

    51st0.15

    B 204 5.67 858.00 0.74 9.572 77.83

    3rd70.746

    9th5.254

    31st0.468

    5th31.499

    11th2.578

    41st0.585

    7th3.986

    21st0.417

    51st0.036

    STEP 1

  • 8/6/2019 Harmonics Study on Distrubution Transformer

    19/31

    19

    TABLE 5

    LABORATORY TEST RESULTS WITH CFLS AND INCANDESCENT LAMPSTransformer loss and primary & secondary harmonics

    WITH CFL ALONE (33 NUMBERS)

    PRIMARYTOTALINPUT SECONDARY

    TOTALOUTPUT

    PERCENTAGELOSS

    R Y B R Y B

    5.24

    VOLTAGE 229 229 224 235 236 232

    CURRENT 2.09 2 2.02 2.58 2.39 2.42

    WATT 380.974 366.4 362.44 1109.81 373.481 345.19 332.934 1051.607

    PF 0.796 0.8 0.801 0.616 0.612 0.593

    THD % V 2.184 2.095 2.859 5.789 5.834 4.466

    ITHD % I 64.148 72.883 63.676 107.92 108.61 111.539

    WITH INCANDESCENT LAMP ALONE

    R Y B R Y B

    1.04

    VOLTAGE 224 207 213 231 231 229

    CURRENT 1.69 1.68 1.6 1.58672 1.5039 1.49342

    WATT 378.56 347.76 340.8 1067.12 366.532 347.4 341.993 1055.922

    PF 1 1 1 1 1 1

    THD % V 2.805 2.204 4.312 2.24 2.843 2.885

    THD % I 2.599 2.363 3.292 2.203 2.885 2.308

  • 8/6/2019 Harmonics Study on Distrubution Transformer

    20/31

    20

    TABLE 6LABORATORY TEST

    TRANSFORMER TEMPERATURE WITH CFL ALONE: Total wattage = 1052(Power parameters given in TABLE 5)

    TIME CORE TEMP (

    o

    C) WINDING TEMP (

    o

    C)0:00 28 28

    0:10 29 30

    0:20 30 32

    0:30 31 33

    0:40 32 34

    0:50 33 36

    1:00 34 37

    1:10 34 37

    1:20 35 38

    1:30 36 39

    1:40 36 39

    1:50 37 402:00 37 40

    2:10 38 41

    2:20 38 41

    2:30 39 42

    2:40 40 42

    2:50 40 42

    3:00 40 42

    TEMPERATURE VERSUS TIME PLOT FOR CFL CIRCUIT

    0

    10

    20

    30

    40

    50

    0:00

    0:30

    1:00

    1:30

    2:00

    2:30

    3:00

    CORE

    TEMP

    WINDING

    TEMP

  • 8/6/2019 Harmonics Study on Distrubution Transformer

    21/31

    21

    TABLE 7LABORATORY TEST

    TRANSFORMER TEMPERATURE WITH INCANDESCENT LAMP ALONE:Total wattage = 1056

    (Power parameters given in TABLE 5)

    TIME CORE TEMP (oC) WINDING TEMP (

    oC)

    0:00 28 28

    0:10 30 31

    0:20 31 31

    0:30 31 32

    0:40 32 33

    0:50 33 33

    1:00 34 34

    1:10 34 35

    1:20 35 35

    1:30 35 36

    1:40 36 36

    1:50 36 372:00 37 37

    2:10 37 37

    2:20 37 37

    2:30 37 37

    2:40 37 37

    2:50 37 37

    3:00 37 37

    TEMPERATURE VERSUS TIME PLOT FOR INCANDESCENT LAMP CIRCUIT

    0

    10

    20

    30

    40

    0:00

    0:30

    1:00

    1:30

    2:00

    2:30

    3:00

    CORETEMP

    WINDING

    TEMP

  • 8/6/2019 Harmonics Study on Distrubution Transformer

    22/31

    22

    TABLE 8MEASUREMENT OF LUMEN PER WATT WITH DIFFERENT MAKES OF CFLS AND

    INCANDESCENT LAMPS

    LUMEN PER WATT at

    230 V 210 V 190 V 170 V 150 V 130 V

    LOW COST

    HONEY QUEEN 4.6 4.7 4.66 4.57 4.52 4.36

    MYOTA 3.71 3.48 3.38 3.15 2.9 2.32

    LEUCI 4.61 4.57 4.38 4.27 4.31 4.1

    HIGH COST13 W (PARISHAD) 6.26 6.27 6.15 6.02 5.71 5.11

    11 W (PARISHAD) 5.53 5.46 5.33 5.08 4.53 4.19

    INCANDESCENT

    100 W 1.16 0.98 0.82 0.65 0.52 0.43

    60 W 0.91 0.76 0.63 0.51 0.39 0.29

    40 W 1.05 0.89 0.7 0.61 0.43 0.35

    TABLE 9SIMULATION OF A DOMESTIC CONSUMERS LOAD AT THE LABORATORY USING CFLS

    AND INCANDESCENT LAMPS ALONG WITH DIFFERENT ELECTRICAL APPLIANCES

    FRIDGE

    2 FAN TV300 W

    INCLAMP

    4 CFLS MOTOR

    FRIDGE +2FAN+TV

    +300WINC LAMP

    FRIDGE+2FAN+TV+

    4CFLS

    FRIDGE+2FAN+TV+300W INCLAMP+MOTOR

    FRIDGE+2

    FAN+TV+4CFLS+

    MOTOR

    V (V) 209 209 220 219 225 216 222 222 209 213

    I (A) 1.17 0.67 0.4 1.334 0.23 6.73 3.36 2.3 9.9325 8.7375

    W (W) 173.372 139.89 67.32 292.146 38.502 1452.23 731.747 486.091 2079.95 1753.9

    pf 0.709 0.999 0.765 1 0.744 0.999 0.981 0.952 0.998 0.994Fundamentalcurrent

    (A)

    1.168 0.674 0.309 1.332 0.197 6.719 3.342 2.277 9.926 8.718

    THD%V

    3.053 4.775 4.382 2.053 1.753 1.538 1.885 2.741 2.048 2.018

    THD %I

    4.24 6.312 78.049 2.084 60.493 3.477 9.117 14.355 2.643 3.114

  • 8/6/2019 Harmonics Study on Distrubution Transformer

    23/31

    23

    TABLE 10FIELD TEST READINGS - BEFORE REPLACEMENT OF INCANDESCENT LAMPS WITH

    CFLS

    Test Point No.1

    Date V I W PFTHD %-

    V

    THD %-

    I

    Harmonics

    5-Mar-04 202 1.56 307.00 0.98 1.985 15.42

    3rd10.649

    9th2.975

    31st0.74

    5th7.685

    11th1.776

    41st0.396

    7th6.582

    21st0.989

    51st0.261

    6-Mar-04 201 1.35 259.00 0.96 2.245 19.071

    3rd12.658

    9th2.71

    31st0.313

    5th10.434

    11th0.933

    41st0.532

    7th8.194

    21st0.864

    51st0.365

    7-Mar-04 200 1.99 389.00 0.98 2.326 15.287

    3rd10.419

    9th2.567

    31st0.29

    5th7.959

    11th1.033

    41st0.313

    7th6.607

    21st0.558

    51st0.232

    Test Point No.2Date V I W PF Thd.V% Thd.I% Harmonics

    5-Mar-04 218 1.99 432.00 1 3.215 2.961

    3rd1.879

    9th0.303

    31st0.102

    5th2.143

    11th0.026

    41st0.107

    7th0.352

    21st0.114

    51st0.008

    6-Mar-04 201 2.25 452.00 1 2.685 2.431

    3rd0.688

    9th0.28

    31st0.023

    5th2.185

    11th0.166

    41st0.031

    7th0.489

    21st0.155

    51st0.043

    7-Mar-04 203 0.89 179.00 0.99 2.433 2.059

    3rd0.452

    9st0.302

    31st0.047

    5th1.797

    11th0.07

    41st0.029

    7th0.624

    21st0.043

    51st0.032

    FIELD TEST READINGS -AFTER REPLACEMENT OF INCANDESCENT LAMPS WITH CFLS

    Test Point No.1

    Date V I W PFTHD %-

    VTHD %-

    IHarmonics

    8-Mar-04 199 2.90 497.00 0.86 2.86 31.39

    3rd 24.729 9st 4.117 31st 0.6855th

    13.25911th

    2.38341st

    1.0427th

    11.65621st

    0.81251st

    0.935

    9-Mar-04 202 2.15 351.00 0.85 2.637 26.188

    3rd20.643

    9st4.493

    31st0.633

    5th10.095

    11th0.854

    41st0.875

    7th10.266

    21st0.291

    51st0.68

    10-Mar-04 201 1.56 301.00 0.96 2.157 18.985

    3rd14.274

    9st4.882

    31st0.382

    5th6.051

    11th0.217

    41st0.733

    7th9.063

    21st0.256

    51st0.717

    Test Point No.2Date V I W PF Thd.V% Thd.I% Harmonics

    8-Mar-04 212 0.72 146.00 0.96 3.595 20.348

    3rd10.146

    9st8.22

    31st0.48

    5th 9.872 11th 5.347 41st 1.0087th

    9.55121st

    1.32151st

    0.533

    9-Mar-04 198 0.80 269.00 0.98 3.596 20.755

    3rd12.17

    9st7.482

    31st0.532

    5th10.282

    11th5.32

    41st0.411

    7th7.742

    21st2.069

    51st0.347

    10-Mar-04 213 0.64 130.00 0.95 3.262 23.806

    3rd12.999

    9st9.131

    31st0.45

    5th10.912

    11th6.106

    41st0.588

    7th10.595

    21st1.993

    51st0.769

  • 8/6/2019 Harmonics Study on Distrubution Transformer

    24/31

    24

    TABLE 11

    FIELD TESTConnected load in the premises of test point 1 and 2 as on dates of measurements

    5/3/04 6/3/04 7/3/04 8/3/04 9/3/04 10/3/04

    TESTPOINT 1

    FAN X 2 FAN X 2 FAN X 1 FAN X 2 FAN X 3 FAN X 2

    40 W IL X 1 40 W IL X 1 60 W IL X 2 CFL X 3 CFL X 5 CFL X 2

    60 W IL X 3 60 W IL X 3

    100 W IL X 1 100 W IL X 1

    TESTPOINT 2

    FRIDGE FRIDGE FRIDGE FRIDGE FRIDGE FRIDGE

    FAN X 1 FAN X 1 FAN X 2 FAN X 3 FAN X 2 FAN X 2

    TV TV TV TV TV TV

    FLUORESCENT LAMP X 1

    FLUORESCENT LAMP X 1

    FLUORESCENT LAMP X 1

    FLUORESCENT LAMP X 2

    FLUORESCENT LAMP X 1 CFL X 3

    60 W IL X 1 60 W IL X 1 CFL X 5 CFL X 4

    TABLE 12FIELD TEST READINGS AT THE TRANSFORMER END BEFORE THE REPLACEMENT

    Date Phase V I W PF Thd.V% Thd.I% Harmonics

    5-Mar-04

    R 223 26.50 5900.00 1 2.372 3.264

    3rd2.273

    9st0.146

    31st0.051

    5th2.263

    11th0.084

    41st0.025

    7th0.309

    21st0.146

    51st0.033

    Y 217 10.40 2190.00 0.97 2.241 6.711

    3rd5.306

    9st2.712

    31st0.203

    5th0.501

    11th1.735

    41st0.05

    7th1.985

    21st0.032

    51st0.331

    B 217 12.20 2620.00 0.99 2.411 6.638

    3rd5.758

    9st1.408

    31st0.188

    5th1.826

    11th0.682

    41st0.085

    7th

    1.97721st

    0.34351st

    0.15Date Phase V I W PF Thd.V% Thd.I% Harmonics

    6-Mar-04

    R 214 31.40 6690.00 1 2.533 5.264

    3rd4.072

    9st0.952

    31st0.055

    5th1.999

    11th0.389

    41st0.053

    7th1.955

    21st0.228

    51st0.057

    Y 210 1.10 2320.00 1 2.375 7.243

    3rd4.739

    9st2.635

    31st0.184

    5th3.807

    11th1.799

    41st0.061

    7th1.95

    21st0.351

    51st0.035

    B 210 16.50 3440.00 1 2.265 5.021

    3rd3.886

    9st1.46

    31st0.27

    5th1.747

    11th0.704

    41st0.128

    7th1.604

    21st0.381

    51st0.129

    Date Phase V I W PF Thd.V% Thd.I% Harmonics

    7-Mar-04

    R 209 33.20 6920.00 1 2.389 3.314

    3rd

    2.9629st

    0.08631st

    0.0085th

    1.23511th

    0.23441st

    0.0117th

    0.58421st

    0.0951st

    0.074

    Y 206 13.60 2790.00 1 2.1 2.841

    3rd1.318

    9st1.105

    31st0.076

    5th1.3

    11th1.412

    41st0.017

    7th0.505

    21st0.036

    51st0.118

    B 206 17.10 3510.00 1 2.139 4.239

    3rd3.099

    9st1.204

    31st0.092

    5th1.683

    11th0.668

    41st0.064

    7th1.658

    21st0.12

    51st0.051

  • 8/6/2019 Harmonics Study on Distrubution Transformer

    25/31

    25

    TABLE 13FIELD TEST READINGS AT THE TRANSFORMER END AFTER THE REPLACEMENT

    Date Phase V I W PF Thd.V% Thd.I% Harmonics

    8-Mar-04

    R 209 17.70 3560.00 0.96 2.298 21.87

    3rd17.94

    9st3.521

    31st0.106

    5th 10.57 11th 0.905 41st 0.127th

    5.40521st

    0.23351st

    0.014

    Y 205 9.26 1840.00 0.97 2.176 9.792

    3rd7.347

    9st1.971

    31st0.073

    5th5.436

    11th0.356

    41st0.101

    7th2.57

    21st0.247

    51st0.037

    B 205 9.78 1940.00 0.97 2.226 25.75

    3rd21.31

    9st9.301

    31st0.105

    5th3.138

    11th4.369

    41st0.133

    7th9

    21st0.681

    51st0.118

    Date Phase V I W PF Thd.V% Thd.I% Harmonics

    9-Mar-04

    R 213 16.80 3410.00 0.95 2.167 26.45

    3rd21.58

    9st4.069

    1.5420.173

    5th12.35

    11th1.542

    41st0.094

    7th7.667

    21st0.044

    51st0.14

    Y 207 9.15 1870.00 0.99 2.236 11.71

    3rd8.335

    9st4.048

    31st0.224

    5th3.595

    11th2.309

    41st0.703

    7th5.109

    21st0.195

    51st0.252

    B 208 10.90 2200.00 0.97 2.185 26.05

    3rd22.5

    9st8.728

    31st0.166

    5th3.491

    11th4.662

    41st0.335

    7th7.055

    21st0.677

    51st0.1

    Date Phase V I W PF Thd.V% Thd.I% Harmonics

    10-Mar-04

    R 209 17.50 3480.00 0.97 2.318 22.36

    3rd18.44

    9st4.173

    31st0.147

    5th9.976

    11th1.388

    41st0.224

    7th6.181

    21st0.285

    51st0.165

    Y 204 8.34 1650.00 0.97 2130 14.16

    3rd10.97

    9st3.538

    31st0.147

    5th

    5.282

    11th

    860

    41st

    0.4667th5.469

    21st0.605

    51st0.764

    B 205 9.94 1960.00 0.96 2.267 27.74

    3rd23.84

    9st8.845

    31st0.188

    5th2.005

    11th3.319

    41st0.658

    7th9.454

    21st0.229

    51st0.314

    TABLE 14

    FIELD TEST NO. OF INCANDESCENT LAMPS REPLACED IN FEEDER 2 OF PORIYANI160 KVA TRANSFORMER

    FEEDER 140 W 60 W 100 W

    NO. OF LAMPS REPLACED 63 109 18190

    TOTAL W2520 6540 1800

    10860

    Number of CFLs placed = 190

    Total watts = 1900

  • 8/6/2019 Harmonics Study on Distrubution Transformer

    26/31

    26

    ANEXE 2

    VOLTAGE AND CURRENT WAVEFORMS(Channel 1shows the voltage waveform and channel two shows the current

    waveform)

    1. LAB STUDY

    1.1. ADITION OF CFLS IN 11 STEPS (REFERENCE TABLE 1)

    STEP 1

    STEP 4

  • 8/6/2019 Harmonics Study on Distrubution Transformer

    27/31

    27

    STEP 7

    STEP 11

  • 8/6/2019 Harmonics Study on Distrubution Transformer

    28/31

    28

    2. FIELD STUDY

    2.1. TEST POINT 1(REFERENCE TABLE 10)

    BEFORE REPLACEMENT OF INCANDESCENT LAMPS

    AFTER REPLACEMENT

  • 8/6/2019 Harmonics Study on Distrubution Transformer

    29/31

    29

    2.2. TEST POINT 2 (REFERENCE TABLE 10)

    BEFORE REPLACEMENT

    AFTER REPLACEMENT

  • 8/6/2019 Harmonics Study on Distrubution Transformer

    30/31

    30

    2.3. TRANSFORMER POINT (REFERENCE TABLE 12)

    BEFORE REPLACEMENTR PHASE

    Y PHASE

    B PHASE

  • 8/6/2019 Harmonics Study on Distrubution Transformer

    31/31

    AFTER REPLACEMENTR PHASE

    Y PHASE

    B PHASE