General Specifications GP10/GP20 Paperless Recorder (Portable type) Yokogawa Electric Corporation 2-9-32, Nakacho, Musashino-shi, Tokyo, 180-8750 Japan GS 04L52B01-01EN GS 04L52B01-01EN ©Copyright Octorber 2012 18th Edition Jul. 9, 2018 OVERVIEW The GP10/GP20 are portable type paperless recorders that display real-time measured data on a touch screen and save data on an external storage medium (SD card). For the input/output module specification, please see GX90XA/GX90XD/GX90YD/GX90WD/GX90XP/ GX90YA Input/Output Module and GX90UT PID Control Module General Specification (GS 04L53B01- 01EN, GS 04L53B01-31EN.) The number of analog input is a maximum of 100 channels in GP10 with expandable I/O *1 , GM sub unit *1 , a maximum of 100 channels in GP20 standard type (GP20-1) with expandable I/O,and a maximum of 450 channels *2 in GP20 large memory type (GP20-2) with expandable I/O, GM sub unit. *1 A unit for expanding the number of channels. *2 Max. number of input/output channels is 500 channels. The GP10/GP20 have the large internal memory (GP10/GP20-1: 500MB, GP20-2: 1.2 GB), and prolonged record and preservation are possible. As the input signal, a DC voltage, thermocouple, resistance temperature detector, DI (DCV input (TTL), contact signal), or mA (DC current) can be set to each channel. Analog output is capable of retransmission output of various types of channels and also manual output. It provides current output with channels that are isolated. (Analog output module) Input and output have module structure and it can extend them easily. (GP10: max. 3*, GP20: max. 10*) * In case of using expandable I/O, GM sub unit, GP10 can extend two units, GP20 can extend 9 units. A module type is seven types, an analog input, a analog output, a digital input, a digital output, a digital input/output, a pulse input, and a PID control. Up to 6 units of expandable I/O units and GM sub units can be connected to the GP10/GP20. Each expandable I/O and GM sub unit can incorporate a maximum of six modules. With expandable I/O, GM sub unit connected, GP10 and the large memory type GP20 can use multiple channels. Furthermore, the I/O ports can be installed in separate locations from where GP10/GP20 is located, helping you reduce wiring requirements and build a decentralized configuration. The intuitive operation by flick, pinch in, and pinch out are possible. The past trend under recording can be seamlessly displayed on a trend screen. Moreover, the measurement data of the time specified on the calendar screen can be searched and displayed. Various functions, such as a freehand message, a PDF/Excel output of a report file, a direct output to a network printer, a scale movement of a trend display, and a buzzer, are equipped. It can be hooked up to network via Ethernet, which enables to inform by Email and to monitor on Web site as well as to transfer files by using FTP. Also, it can communicate with Modbus/RTU or Modbus/ TCP. Safe measurement up to withstand voltage of 600 V between input terminal and ground is possible by using a high withstand voltage analog input module. In high-speed measurement, measurement at the shortest interval of 1 ms is possible by using a highspeed analog input module (high-speed AI). In dual interval measurement, measurement can be performed by setting two different scan intervals. The PID control function enables PID control on up to 20 loops (6 loops for the GP10/GP20-1) by installing a PID control module. The program control function enables program control of up to 99 patterns by using a PID control module and program control function (/PG option). Up to 32 time events and 32 PV events can be set for each segment. * For PID control module, PID control Function, and program control function (/PG), see the GX90UT PID Control Module General Specifications (GS 04L53B01-31EN) * The contents of this general specifications correspond to the GP10/GP20 with release number 4 and style number 2. Release number: firmware ID number Style number: hardware ID number GP10 GP20 Release R4

Upload: others

Post on 19-Apr-2020

10 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: General GP10/GP20 6SHFL¿FDWLRQV (Portable type) · General 6SHFL¿FDWLRQV GP10/GP20 Paperless Recorder (Portable type) Yokogawa Electric Corporation 2-9-32, Nakacho, Musashino-shi,

GeneralSpecifications

GP10/GP20Paperless Recorder(Portable type)

Yokogawa Electric Corporation2-9-32, Nakacho, Musashino-shi, Tokyo, 180-8750 Japan

GS 04L52B01-01EN

GS 04L52B01-01EN©Copyright Octorber 2012

18th Edition Jul. 9, 2018

OVERVIEWThe GP10/GP20 are portable type paperless recorders that display real-time measured data on a touch screen and save data on an external storage medium (SD card).For the input/output module specification, please see GX90XA/GX90XD/GX90YD/GX90WD/GX90XP/GX90YA Input/Output Module and GX90UT PID Control Module General Specification (GS 04L53B01-01EN, GS 04L53B01-31EN.)● Thenumberofanaloginputisamaximumof

100channelsinGP10withexpandableI/O*1, GM sub unit*1,amaximumof100channelsinGP20standardtype(GP20-1)withexpandableI/O,andamaximumof450channels*2inGP20largememorytype(GP20-2)withexpandableI/O,GMsubunit.*1Aunitforexpandingthenumberofchannels.*2Max.numberofinput/outputchannelsis500

channels.● TheGP10/GP20havethelargeinternalmemory

(GP10/GP20-1: 500MB, GP20-2: 1.2 GB), and prolongedrecordandpreservationarepossible.

● Astheinputsignal,aDCvoltage,thermocouple,resistancetemperaturedetector,DI(DCVinput(TTL),contactsignal),ormA(DCcurrent)canbeset to each channel.

● Analogoutputiscapableofretransmissionoutputofvarioustypesofchannelsandalsomanualoutput.

Itprovidescurrentoutputwithchannelsthatareisolated.(Analogoutputmodule)

● Inputandoutputhavemodulestructureanditcanextendthemeasily.(GP10:max.3*,GP20:max.10*)* IncaseofusingexpandableI/O,GMsubunit,

GP10canextendtwounits,GP20canextend9units.

● Amoduletypeisseventypes,ananaloginput,aanalog output, a digital input, a digital output, a digitalinput/output,apulseinput,andaPIDcontrol.

● Upto6unitsofexpandableI/OunitsandGMsubunits can be connected to the GP10/GP20. Each expandableI/OandGMsubunitcanincorporateamaximumofsixmodules.WithexpandableI/O,GMsubunitconnected,GP10andthelargememorytypeGP20canusemultiplechannels.Furthermore,theI/OportscanbeinstalledinseparatelocationsfromwhereGP10/GP20islocated,helpingyoureducewiringrequirementsandbuildadecentralizedconfiguration.

● Theintuitiveoperationbyflick,pinchin,andpinchout are possible.

● Thepasttrendunderrecordingcanbeseamlesslydisplayed on a trend screen.

● Moreover,themeasurementdataofthetimespecifiedonthecalendarscreencanbesearchedand displayed.

● Variousfunctions,suchasafreehandmessage,aPDF/Exceloutputofareportfile,adirectoutputtoanetworkprinter,ascalemovementofatrenddisplay, and a buzzer, are equipped.

● ItcanbehookeduptonetworkviaEthernet,whichenablestoinformbyEmailandtomonitoronWebsiteaswellastotransferfilesbyusingFTP.Also,itcancommunicatewithModbus/RTUorModbus/TCP.

● Safemeasurementuptowithstandvoltageof600Vbetweeninputterminalandgroundis possible by usingahighwithstandvoltageanalog inputmodule.

● Inhigh-speedmeasurement,measurementattheshortestintervalof1msispossiblebyusingahighspeedanaloginputmodule(high-speedAI).

● Indualintervalmeasurement,measurementcanbeperformedbysettingtwodifferentscanintervals.

● ThePIDcontrolfunctionenablesPIDcontrolonupto20loops(6loopsfortheGP10/GP20-1)byinstallingaPIDcontrolmodule.

● Theprogramcontrolfunctionenablesprogramcontrolofupto99patternsbyusingaPIDcontrolmoduleandprogramcontrolfunction(/PGoption).Upto32timeeventsand32PVeventscanbesetforeachsegment.

* ForPIDcontrolmodule,PIDcontrolFunction,andprogramcontrolfunction(/PG),seetheGX90UTPIDControlModuleGeneralSpecifications(GS04L53B01-31EN)

*ThecontentsofthisgeneralspecificationscorrespondtotheGP10/GP20withreleasenumber4andstylenumber2.

Releasenumber:firmwareIDnumber Stylenumber:hardwareIDnumber

GP10 GP20

Release R4

Page 2: General GP10/GP20 6SHFL¿FDWLRQV (Portable type) · General 6SHFL¿FDWLRQV GP10/GP20 Paperless Recorder (Portable type) Yokogawa Electric Corporation 2-9-32, Nakacho, Musashino-shi,

2

All Rights Reserved. Copyright © 2012, Yokogawa Electric Corporation GS 04L52B01-01EN Jul. 9, 2018-00

● Varioustypesofcomputationarepossiblewiththemathfunction(/MToption).Thereportfunctionenablescreationofhourly,daily,andmonthlyreportsandothertypesofdata.Logicmathoutputsresultsofcomputationas0sor1stointernalswitchesandDOchannels.

● AsetupofGPcanbeperformedon-linefromthewebbrowseronPC.Asetupbyoff-lineisalsopossible.

● UniversalViewersoftwareallowsaPCtodisplaywaveformsonitsscreenandtoprintoutwaveforms.

● Themeasuringaccuraciesnotedinthegeneralspecificationshaveamarginoferrorthattakesintoaccounttheproduct'scomponentsandtheequipmentusedforadjustmentandtesting.However,theactualvaluescalculatedfromtheaccuracytestingdatauponshipmentoftheinstrumentfromthefactoryareasfollows.Inputtype Measuring accuracy*1(typicalvalue*2)

DCV 20mV ±(0.01%ofrdg+5μV)

60mV ±(0.01%ofrdg+5μV)

6 V (1-5 V) ±(0.01%ofrdg+2mV)

TC*3 R, S ± 1.1 °C

B ± 1.5 °C

K (-200.0 to 1370.0 °C)

±(0.01%ofrdg+0.2°C)for0.0to 1370.0 °C;±(0.15%ofrdg+0.2°C)for-200.0 to 0.0 °C

K (-200.0 to 500.0 °C)

±0.2°Cfor0.0to500.0°C;±(0.15%ofrdg+0.2°C)for-200.0 to 0.0 °C)

J ±0.2°Cfor0.0to1100.0°C;±(0.10%ofrdg+0.2°C)for-200.0 to 0.0 °C

T ±0.2°Cfor0.0to400.0°C;±(0.10%ofrdg+0.2°C)for-200.0 to 0.0 °C

N ±(0.01%ofrdg+0.2°C)for0.0to 1300.0 °C;±(0.22%ofrdg+0.2°C)for-200.0 to 0.0 °C

RTD Pt100(-200.0 to 850.0 °C)

±(0.02%ofrdg+0.2°C )

Pt100(high resolution)(-150.0 to 150.0 °C)

±(0.02%ofrdg+0.16°C)

*1 AppliestoGX90XA-10-U2,A/Dintegrationtime16.67msormore,Generaloperatingconditions:23±2ºC,55±10%RH,supplyvoltage90–132,180–264VAC,supplyfrequencywithin50/60Hz±1%,warm-upof30minutesormore,novibrationsorotherhindrancestoperformance.

*2 Forthemeasuringaccuracy(guaranteed),seethemodule'sgeneralspecifications(GS04L53B01-01EN).

*3 Thesevaluesdonotincludethereferencejunctioncompensationaccuracy.

rdg:readingvalue

MAIN UNIT SPECIFICATIONS■ FUNCTIONALSPECIFICATION

Input/OutputSpecifications PleaseseeGX90XA/GX90XD/GX90YD/GX90WD/

GX90XP/GX90YAI/OModuleandGX90UTPIDControlModuleGeneralSpecifications.Model Name General

SpecificationNo.GX90XA Analoginputmodule GS 04L53B01-01EN

GX90DX Digitalinputmodule

GX90YD Digitaloutputmodule

GX90WD Digitalinput/outputmodule

GX90XP Pulseinputmodule

GX90YA Analogoutputmodule

GX90UT PIDcontrolmodule GS 04L53B01-31EN

MeasuringFunctions• ThenumberofinstallablemodulesandI/O

channels(totalforGP,expandableI/OandGMsubunit)

GP10/GP20-1Item GP10/GP20-1

Numberofmodule Max.10

Numberofinput/outputmodule Max.100

GP20-2Item GP20-2

Numberofmodule Max.45

Numberofinput/outputmodule Max.500(ormax.450forAIonly)

Moduleinstallationlimitations:See“Limitations”and“NotesonModuleInstallation.”• ExpandableI/O,GMsubunitconnection Numberofconnectableunits:Upto6unitstotal

* ConnectionisnotpossibleifthemeasurementmodeissettoHighspeed.

FordetailsonexpandableI/OunitsandGMsubunits,seetherespectiveGeneralSpecifications(GS 04L53B00-01EN, GS 04L55B01-01EN).

Page 3: General GP10/GP20 6SHFL¿FDWLRQV (Portable type) · General 6SHFL¿FDWLRQV GP10/GP20 Paperless Recorder (Portable type) Yokogawa Electric Corporation 2-9-32, Nakacho, Musashino-shi,

3

All Rights Reserved. Copyright © 2012, Yokogawa Electric Corporation GS 04L52B01-01EN Jul. 9, 2018-00

Scaninterval:1,2,5,10,20,50,100,200,500ms,1,2,5sNote) Someintervalswillbeunavailabledependingon

thesystemconfigurationandmodules. Fordetails,seetheI/OModuleGeneral

Specifications(GS04L53B01-01EN)and“Limitations”inthismanual.

Measurmentmode:● Normal Amodeinwhichtheshortestmeasurement

intervalis100ms Numberofmeasurmentgroups:1 Filetype:Displaydata,eventdata Dataformat:Binaryortext Scaninterval:100ms(fastest) Compatiblemodules:Allmodules● Highspeed Amodeinwhichhigh-speedmeasurementis

possibleattheshortestmeasurementintervalof1ms

Numberofmeasurmentgroups:1 Filetype:Eventdataonly Dataformat:Binaryonly Scaninterval:1ms(fastest) Compatiblemodules:High-speedAI(GX90XA-

04-H0),DI(GX90XD),DIO(GX90WD) However,onemodule,eitherDIorDIO,can

beinstalled.DIinputisfixedtoremotemode.Measurementandrecordingarenotpossible.

● Dualinterval Amodeinwhichmeasurementispossible

bysettingdifferentscanintervalsonthetwomeasurementgroups.

Numberofmeasurementgroups:2 Filetype:Eventdataonly Dataformat:Binaryonly Scaninterval:

Model measurementgroup1

measurementgroup2

GP10/GP20-1 5ms(fastest) 100ms(fastest)

GP20-2 1ms(fastest) 100ms(fastest)

Compatiblemodules:AllmodulesexceptPIDcontrolmodule* Dependingonthemeasurementmode,thereisa

limittothenumberofmeasurementchannelsandrecordingchannelsatscanintervalsshorterthan100ms.See“Limitations.”

DisplayFunctionsDisplaygroups: Numberofgroups;GP10:30,GP20-1:50,

GP20-2:60 Numberofchannelsthatcanbeassignedto

each group; GP10: 10, GP20: 20Displaycolor(Trend/Bargraph/Digitaldisplay): Channel:Selectfrom24colors Adesireddisplaycolorcanbeselectedfreely

usingitsRGBvalue. Background:Selectfromwhiteorblack

Displaytype:● Trenddisplay(T-Y) Displaymethod:

Direction:Horizontal,verticalTrendinterval(Recordinginterval):50ms/div

(1ms),100ms/div(2ms),250ms/div(5ms),500ms/div(10ms),1s/div(20ms),2.5s/div(50ms),5s/div(100ms),10s/div(200ms),15s/div(500ms),30s/div(1s),1min/div(2s),2min/div(4s),5min/div(10s),10min/div(20s),15min/div(30s),20min/div(40s),30min/div(1min),1h/div(2min),2h/div(4min),4h/div(8min),10h/div(20min)

• Trendintervalshorterthan30s/div(1s)cannotbesetonelectromagneticrelaytypeanaloginputmodules.

• Trendintervalshorterthan15s/div(500ms)cannotbesetonlowwithstandvoltagerelaytypeanaloginputmodules.

• Scanintervalshorterthan5s/div(100ms)cannotbespecifiedwhenthemeasurementmodeissettoHighspeedorDualinterval.

• OntheGP10/GP20-1,scanintervalshorterthan250ms/divcannotbespecifiedindualintervalmode.

Trendlinewidth:Thick,normal,thin Scale;GP10:Max.6,GP20:Max.10

Currentvaluebargraph,colorscaleband,andalarmpointmarkscanbedisplayedonthe scale.

Abitmapimagescalecanbeattached.Movingscale;Scalecanbemovedonany

waveform. Others; Grid (Auto, 4 to 12), Trip line, Message,

Zonedisplay,Partialexpandeddisplay● Historicaltrenddisplay(T-Ydisplay) Redisplaysthedisplaydataoreventdatainthe

internalmemoryorexternalstoragemedium Timeaxisoperation:Thetimeaxiscanbe

reducedorexpanded. Datasearch:Waveformsfromtheinternal

memorycanbedisplayedthroughthespecificationofadateandtime,calendar,eachsummary

All historical trends can be displayed in one screen.

● Bargraphdisplay Direction:Verticalorhorizontal Scale:Displayascaleforeachchannel

Colorscaleband,andalarmpointmarkscanbe displayed on the scale.

● Digitaldisplay Displaysmeasuredvaluesnumerically ADIinputstatecanbedisplayedasanarbitrary

characterstring(0=Off/1=On,etc.) Updaterate:0.5s

Page 4: General GP10/GP20 6SHFL¿FDWLRQV (Portable type) · General 6SHFL¿FDWLRQV GP10/GP20 Paperless Recorder (Portable type) Yokogawa Electric Corporation 2-9-32, Nakacho, Musashino-shi,

4

All Rights Reserved. Copyright © 2012, Yokogawa Electric Corporation GS 04L52B01-01EN Jul. 9, 2018-00

● Overviewdisplay Displayformat:Allchannels,eachgroups Displaysthemeasuredvaluesofallchannels

andthealarmstatuses Displayingroupsonlywhenthemaximum

numberofchannelsthatcanbedisplayed(30ontheGP10,100ontheGP20)isexceeded.

● Alarmsummarydisplay Displaysalogofupto1000alarms Specifyanalarmwiththecursorandjumpto

the corresponding section on the historical trend display.

● Messagesummarydisplay Timeandcontentofupto500messages

(simultaneouswriting:450,additionalwriting:50) Specifyamessagewiththecursorandjumpto

the corresponding section on the historical trend display.

● Memorysummarydisplay Displaystheinformation(upto500(GP10/GP20-

1)orupto1000(GP20-2)ofthedatainthememory

Specifyafilewiththecursorandjumptothecorresponding section on the historical trend display.

● Reportdisplay Displaysthereportdataresidingintheinternal

memory Formoredetails,see"MATHEMATICAL

FUNCTIONSWITHREPORTFUNCTION(/MT)."● Logdisplay Displaystheeventlog,errorlog,communication

log,FTPlog,Weblog,e-maillog,SNTPlog,DHCPlog,ModbuslogandSLMPlog.

● Multi-paneldisplay(OnlyforGP20) Dividesthescreenintotwotosixsectionsand

displayssomedifferentdisplayformats.● Internalswitch/relaystatedisplay DisplaystheinternalswitchandON/OFFstateof

DO OperatestheinternalswitchandON/OFFstate● Controlscreendisplay(whenaPIDcontrol

moduleisinstalled) Controlgroup,controloverview,tuning,control

summary,controlalarmsummary,programoperation,*programselection*

* Only when the /PG option is installed● Otherdisplays Networkinformationdisplay Systeminformationdisplay Systemconfigurationdisplay

Autoscroll: Thedisplayedgroupscanbeautomatically

switchedataspecifiedinterval. The display switches in ascending group order.

Namesofchannels:

Channel number; Analog input: 01 to 10 Digital input: 01 to 16 Digital output: 01 to 06 Digital input/output; DI: 01 to 08, DO: 09 to 14 Pulse input: 01 to 10 Analog output: 01 to 04 PID control Input, output: 01 to 26

X X X X

Slot number; GP10: 0 to 2, GP20: 0 to 9 Expandable I/O/GM sub unit: 0 to 5Unit number; Main unit: 0, Expandable I/O/GM sub unit: 1 to 6

Tags:• TagandTagnumberscanbedisplayed.• Tagnumber;Numberofcharacters:Upto16 Displayablecharacters:Alphanumericcharacters Tagnumberscanbeenabledordisabled.• Tag;Numberofcharacters:Upto32 Displayablecharacters:Alphanumericcharacters

Message:• Writemessagestothetrenddisplay.• Numberofmessages:100• Numberofcharacters:Upto32• Writemethod:Writeapresetmessageorwrite

anarbitrarymessageonthespot.• Writedestination:Selectonlythedisplayed

group or all groups.• Automessage:WriteamessagewhentheGP

recoversfromapowerfailurewhilememorysamplingisinprogress.

Writeamessagewhenthetrendintervalisswitchedduringmemorysampling.

Addmessage:• Writemessagestothepastdatapositions.• Message:Thesameasthe“Message”item

above Numberofwritablemessagesperfile:50

messages(including10freehandmessages)Freehandmessage:• Canbewrittenbydedicatedpen. Numberofwritablemessagesperfile:50

messages(including10Addmessages)

DataSavingFunctionsInternalmemory:• Temporarilysavesvarioustypesofdata.• Medium:Flashmemory• Filestoragecapacity; GP10, GP20-1: 500 MB GP20-2: 1.2 GB

Externalstoragemedium:• MediumSDcard(SD/SDHC)(upto32GB)• Format:FAT32orFAT16

Datatype:• Displaydata,Eventdata,Alarmsummarydata,

Manualsampleddata,Screenimagedata,Setupdata, and Report data

Page 5: General GP10/GP20 6SHFL¿FDWLRQV (Portable type) · General 6SHFL¿FDWLRQV GP10/GP20 Paperless Recorder (Portable type) Yokogawa Electric Corporation 2-9-32, Nakacho, Musashino-shi,

5

All Rights Reserved. Copyright © 2012, Yokogawa Electric Corporation GS 04L52B01-01EN Jul. 9, 2018-00

Displaydata:• Target:Measurement(input/outputmodule)/

math/communicationchannels,alarmsummary,messagesummary

Description:Maximumorminimumvalueperrecordlinginterval

• Recordingintervals:Determinedbythetrendinterval,recordingdatatype(displaydata/displaydata+eventdata,GP20-2)

• Numberofchannelsthatcanberecorded ForGP20-1

Trendinterval(div) Numberofchannels5 s 100

10 s 200

15 s or longer 500

ForGP20-2Trendinterval(div) Numberofchannels

Displaydata

Displaydata+Eventdata

5 s 200 100

10 s 500 200

15 s 1000 500

30 s or longer 1000 1000

Notethatthemaximumnumberofchannelsisfixedat100intheGP10.

• Datasize; Analog input data: 12 bytes/ch. Analog output data: 12 bytes/ch. DigitalI/Odata:4bytes/ch. Pulse input data: 12 bytes/ch.

Math channel data: 12 bytes/ch. Communicationchanneldata:12bytes/ch.

• Filesize:Upto18MB• NumberoffilesforGP10,GP20-1:Upto500

(includingeventdata),forGP20-2;Upto1000(includingeventdata) Operationintheinternalmemory:FIFO(FirstInFirstOut)

• Dataformat:Binaryortext• Recording:Recordsdataatalltimes.• Displaydatafilesampletime

Measurementchannel=30.MathChannel=0InternalMemory 500 MB

Trendinterval(minute/div) 30minutes

Recordinginterval(s) 60s

Totalsampletime Approx.2.5yearsEventdata:• Target:Measurement(input/outputmodule)/

math/communicationchannels,alarmsummary,messagesummary,operationlog

Description:Instantaneousvalueperrecordinginterval

• Recordingintervals:Determinedbythescaninterval,recordingdatatype(displaydata/displaydata+eventdata)

• Numberofchannelsthatcanberecorded: Measurmentmode:Normal

ForGP20-1Recordinginterval Numberofchannels*1

100ms 100

200ms 200

500msorlonger 500

ForGP20-2Recordinginterval Numberofchannels*1

Displaydata

Displaydata+Eventdata

100ms 500 100

200ms 500 200

500ms 1000 500

1 s or longer 1000 1000

Notethatthemaximumnumberofchannelsis100 in the GP10.

Measurmentmode:HighspeedRecordinginterval Numberofchannels*1

GP10 GP20-1 GP20-21ms 2 2 10

2ms 4 4 20

5ms 10 10 50

10ms 20 20 100

20ms 40 40 150

50ms 100 100 150

100ms 100 100 200

200ms 100 200 500

500ms 100 500 1000

1 s or longer 100 500 1000

Measurmentmode:DualintervalRecordinginterval Numberofchannels *1 *2

GP10 GP20-1 GP20-21ms — — 5

2ms — — 10

5ms 5 5 25

10ms 10 10 40

20ms 20 20 50

50ms 50 50 50

100ms 100 100 100

200ms 100 100 200

500ms 100 250 600

1 s or longer 100 250 600

*1 TotalnumberincludingI/Ochannels,mathchannels,andcommunicationchannels

*2 Numberofchannelsthatcanberecordedisthesameforscangroup1andscangroup2.

Page 6: General GP10/GP20 6SHFL¿FDWLRQV (Portable type) · General 6SHFL¿FDWLRQV GP10/GP20 Paperless Recorder (Portable type) Yokogawa Electric Corporation 2-9-32, Nakacho, Musashino-shi,

6

All Rights Reserved. Copyright © 2012, Yokogawa Electric Corporation GS 04L52B01-01EN Jul. 9, 2018-00

• Datasize; Analoginputdata:6bytes/ch. Analogoutputdata:6bytes/ch. DigitalI/Odata:2bytes/ch. Pulseinputdata:6bytes/ch.

Mathchanneldata:6bytes/ch. Communicationchanneldata:6bytes/ch.

• Filesize:Upto18MB• NumberoffilesforGP10,GP20-1:Upto500

(includingdisplaydata),forGP20-2;Upto1000(including display data)

• Operationintheinternalmemory:FIFO(FirstInFirstOut)

• Dataformat:Binaryortext• Mode;Free:Recordsdataatalltimes.

Trigger: Starts recording data when a certaineventoccursandrecordsforthespecifiedinterval.

Repetitiontrigger:RepeatTriggermode• Eventdatafilesampletime Measurementchannel=30.MathChannel=0

InternalMemory 500 MB

Recording period (s) 1 s

Totalsampletime Approx.1month

AlarmFunctions• Numberofalarms:Uptofouralarms(level)for

eachmeasurementchannels• Alarmtype:Highlimit,lowlimit,differencehigh

limit,differencelowlimit,highlimitonrate-of-changealarm,lowlimitonrate-of-changealarm,delayhighlimit,anddelaylowlimit

• Alarmdelaytime:1sto24hours(foreachchannel)

• Rate-of-changecalculationintervalofrate-of-changealarms:1to32timesthescaninterval(commontoallchannels)

• Hysteresis:0.0to5.0%ofthespan(foreachalarm(level))

• Alarmoutput:Outputtotheinternalswitch,relay Internalswitch/relayoperation:AND/OR

operation selectable• Display:Displaysthestatusontherespective

operationscreenandanalarmicononthestatusdisplaysectionwhenanalarmoccurs.

Displayoperation:Holdornotholdthedisplayuntilthealarmacknowledgeoperation

• Alarmhidefunction(alarmnologgingfunction) Usedforrelayandinternalswitchoutputand

eventsofeventactionandnotrecordedinalarmdisplayoralarmsummary(eachchannel)

• Alarminformation:Displaysalogofalarmoccurrencesonthealarmsummary

• Reflash:Thedurationforwhichthereflashrelaysaredeactivatedcanbesetto500ms,1s,or2s.

• IndividualalarmACKfunction: Alarmdisplayandrelayoutputcanbecancelled

onindividualalarms

EventActionFunctions• Eventaction:Executeaspecifiedoperation

whenagiveneventoccurs.• Numberofsettings:50 Events:Remotecontrolinput,etc. Numberoftimers:12 Numberofmatchtimetimers:12 Action:Specifymemorystart/stop,alarmACK,

etc.

ControlEventActionFunctionsSeeGX90UTPIDControlModuleGeneral

Specifications(GS04L53B01-31EN).

SecurityFunctions• Operationlockfunction:Limitationstotouch

operation,accesstotheexternalstoragemedium,andvariousoperations

• Loginfunction:Onlyregistereduserscanoperate the GP.

Itcanbesettoeachoftouchoperationandcommunicationaccess.

SystemadministratorsandUsers:50(totally) NumberofAuthorityofuser:10level

ManualSampledData• Item:Instantaneousvalueatanarbitrarytime• Target:Measurement(input/outputmodule)/

math/communicationchannels• Numberofrecordingchannels; GP10,GP20-1:Max.50 GP20-2:Max.100• Maximumnumberofdatavaluesthattheinternal

memorycanstore:400• Dataformat:Text

ReportData• Item:Reportateachscheduledtimeofreport• Target:Measurement(input/outputmodule)/

math/communicationchannels• Maximumnumberofreportsthattheinternal

memorycanstore:800• Dataformat:Text

SnapshotData• Item:Displayedscreenimagedata• Dataformat:PNG• Outputdestination:Externalmediumor

communicationoutput

SetupData• Item:GPsetupdata• Dataformat:text• Output/readdestination(forsaving/loading):

Externalmedium

ClockFunctions• Clock:Withacalendarfunction• Accuracy:±5ppm(0to50°C),excludingadelay

(of1second,maximum)causedeachtimethepower is turned on.

• Timedifferencebetweenunits:±2msmax.(timedifferencebetweenaGPandI/OBaseUnit(ExpandableI/O))

Page 7: General GP10/GP20 6SHFL¿FDWLRQV (Portable type) · General 6SHFL¿FDWLRQV GP10/GP20 Paperless Recorder (Portable type) Yokogawa Electric Corporation 2-9-32, Nakacho, Musashino-shi,

7

All Rights Reserved. Copyright © 2012, Yokogawa Electric Corporation GS 04L52B01-01EN Jul. 9, 2018-00

• Timesetting:Usingtouchoperation,communicationcommand,eventactionfunction,orSNTPclientfunction

• Timeadjustmentmethod: Limitinwhichthetimeisgraduallyadjusted:

Selectfromtheavailablesettingsbetween5sand 15 s.

Whethertochangeanout-of-limitoperationimmediatelyorreportitasanerrorcanbeselected.

Whilememorysampling:Correctsthetimeby1msforeachsecond.

Whilememoryisstopped:Immediatelychangethetime.

• DST:Thedate/timeforswitchingbetweenstandardtimeandDSTcanbespecified.

• Timezone:SetsthetimedifferencefromGMT.• Dateformat:Select"YYYY/MM/DD","MM/DD/

YYYY","DD/MM/YYYY"or"DD.MM.YYYY". MMexpressioncanbeselectedfromthenumericcharacterorellipsis.Ex.January:01orJan Thedelimitercanbeselectedfrom"/",".","-".

EthernetCommunicationFunctions• Electricalspecifications:ConformstoIEEE802.3• Connection:Ethernet(10BASE-T/100BASE-TX)• Max.segmentlength:100m• Max.connectingconfiguration:CascadeMax.4

level(10BASE-T),Max.2level(100BASE-TX)• Connector:RJ-45• Protocols:TCP,UDP,IP,ICMP,ARP,DHCP,

HTTP,FTP,SMTP,SNTP,Modbus,anddedicated protocols

• E-mailclient:Automaticallysende-mailatspecifiedtimes.

E-mailissentbyeventsasbelow.- Alarmoccurring/alarmcanceling(Max.50ch)- Recoverfrompowerfailure- Report data generating- Storagemediumerror,FTPclientfunction

error- Specifiedtimeperiod

POPbeforeSMTPandSMTPauthentication(PLAINandCRAM-MD5)isavailable.

• FTPclient:AutomaticallytransferdatafilestotheFTPserver.

Applicablefiles:Displaydata,eventdata,screenimagedata,reportdata,etc.

• FTPServer:Transferfiles,deletefiles,manipulatedirectories,andoutputfilelistsoftheGP.

Numberofthesimultaneousconnection:Max.4• Webserver:Webapplication,GPreal-time

monitoringandsettingchanges/operationscanbeperformedwiththeWebbrowser.

Numberofthesimultaneousconnection:Max.4• SNTPclient:InquiresthetimetotheSNTP

serverandsetstheGP.• SNTPserver:OutputstheGPtime. Timeresolution:5ms• DHCPclient:Automaticallyobtainthenetwork

addresssettingsfromtheDHCPserver.

• Modbusclient*:Readsdatafromanotherdeviceand writes to the registers.

Numberofconnectablesever; GP10,GP20-1:Max.16 GP20-2:Max.32 *: Required /MC option• Modbusserver:Loadsmeasurementandmath

channel data Loadsandwritescommunicationchanneldata Somecontrolcommandssuchasmemorystart Modbusclient*registeraccesslimitations

*: Required /MC option Numberofthesimultaneousconnection:Max.4• Setting/Measurementserver:Operate,set,and

outputdataoftheGPusingadedicatedprotocol. Numberofthesimultaneousconnection:Max.4• DARWINcompatiblecommunicationserver:

SupportssomeDARWINcommands CommunicationwithGPispossibleusing

DARWINcommunicationcommands. • Output-relatedcommands:Output

measurement(IO)channeldata,Outputcalculation channel data, Output relay status, Outputthepositionofthedecimalpointforthemeasurement(IO)channel,Outputthepositionofthedecimalpointforthecalculationchannel,Outputtheinformationonsystemconfiguration

• Setup-relatedcommands:Range,Scaleunit,Alarm,Time,Movingaverage,zone

• Operation-relatedcommands:Resetalarm,Resettimer,StartMATHcalculation,Rebuildsystem,Initialize,Inputcommunication,OutputcommunicationDO,Writemessage

BatchFunction• Function:Datamanagementusingbatchnames.

Entertextfieldsandbatchcommentsinthedatafile.• Batchname:Addedtothefilenameofthe

displaydataandeventdata. Structure:Batchnumber(upto32characters)+

lotnumber(upto8digits) Use/notuseselectableforlotnumber,on/off

selectableforautoincrementfunction.• Textfield:Addstexttothedisplaydataandevent

data. Thereare24availabletextfields. Upto20titlecharactersand30othercharacters

canbeenteredperfield.• Batchcomment:Addstexttothedisplaydata

andeventdata. 3comments(max.50characters)areavailable.

PrinterOutputFunction• SnapshotDatacanbeprintedoutwithany

LAN-connected printer supporting the HP PCL5c language and the port 9100.

Page 8: General GP10/GP20 6SHFL¿FDWLRQV (Portable type) · General 6SHFL¿FDWLRQV GP10/GP20 Paperless Recorder (Portable type) Yokogawa Electric Corporation 2-9-32, Nakacho, Musashino-shi,

8

All Rights Reserved. Copyright © 2012, Yokogawa Electric Corporation GS 04L52B01-01EN Jul. 9, 2018-00

SSLCommunicationFunctions Communicationthatsendsandreceivesinformation

encrypted by the SSL (Secure Socket Layer) protocol is possible.• Serverfunction: Supportedservers:HTTPserverandFTPserver

(Portnumber:443whenencryptionisused) Privatekey:CreatedinGPandsavedinthe

internalmemory Servercertificate:Servercertificatescreatedby

userscanbesavedintheinternalmemory. Self-signedcertificatescanbecreatedinGP.• Clientfunction: Supportedclients:FTPclient(onlyExplicitmode

is supported) and SMTP client (only STARTTLS is supported)

Trustedcertificate:Trustedcertificates(atotalofupto80KB)canbesavedintheinternalmemory.

ElectronicSignatureFunction Electronicsignaturescanbeaddedtoreportfiles

createdinPDFformatusingthePDFformcreationfunction.Anelectronicsignatureisprovidedeachtimeareportfileiscreated.• Certificateforelectronicsignature:Certificates

forelectronicsignaturescreatedbyuserscanbesavedintheinternalmemory.

LoopcontrolFunction(WithPIDcontrolmodule)SeeGX90UTPIDControlModuleGeneral

Specifications(GS04L53B01-31EN).

OtherFunctions• Buzzer:GPmakesabuzzersoundattouch

screenoperation,orwhenalarmoccurs.• Backlightsaverfunction:Dimorturnoffthe

LCDbacklightifthereisnokeyoperationforaspecifiedtime.

• Favoritedisplay:RegisterfrequentlyuseddisplaystotheFavoriteandshowthemthroughsimpleoperation.

• ThemainalarmisindicatedusingtheMENUkeyLED.

Noalarm:Blue(sameconditionaspower-on) Alarmcondition:Red.• Userfunctionfeature:Abuttontowhichtheuser

canassignadesiredfunctionisprovided.Itcanbeassignedtoaneventtriggeredbytheeventactionfunction.

• Firmwareupdatefunction:TheWebapplication,theIOmodule,ortheexpansionmodulefirmwarecanbeupdatedbyoperatingGP.

HARDWARE SPECIFICATIONS (MAINUNIT)

DisplayDisplayunit*:GP10:5.7-inchTFTcolorLCD(640×480dots)GP20:12.1-inchTFTcolorLCD(800×600dots)* Asmallnumberofmissingorsteady-onLCD

pixelsandminorvariationsinbrightnessuniformityisanormaldisplaycharacteristicandnotamalfunction.

Touchscreen:4wireresistivetouchscreen

Construction• Material;

Case: Metal plate Bezelanddisplaycover:Polycarbonate

• Color; Case:Smokeblue(Munsell4.1PB6.0/4.5equivalent) Bezel: Light grey (Munsell 5.2PB8.2/1.0 equivalent)

• Externaldimensions: Wheninstallingmodules GP10:144(W)×168(H)×248(D)mm

GP20:288(W)×318(H)×248(D)mm Whenuninstallingmodules

GP10:144(W)×168(H)×197(D)mm GP20:288(W)×318(H)×197(D)mm (D:depthfromthepanelmountingplane)• Weight:

GP10:Approx.1.9kg,GP20:Approx.5.4kg (excludingmodules)

PowerSupply[Powersupplysuffixcode:1]• Ratedsupplyvoltage:100to240VAC• Allowablepowersupplyvoltagerange:90to132,

180to264VAC• Ratedpowersupplyfrequency:50/60Hz• Powerconsumption:Supplyvoltage

LCDbacklightoff

Normaloperation

Maximum

100VAC GP10:16VAGP20:28VA

GP10:20VAGP20:34VA

GP10:48VAGP20:90VA

240VAC GP10:24VAGP20:38VA

GP10:30VAGP20:45VA

GP10:60VAGP20:110VA

* ThefollowingcombinationsareassumedforLCDbacklightoffandnormaloperation.

GP10:1AImodule,1DOmodule,1DImoduleGP20:5AImodules,4DOmodules,1DImodule

• Modulepowersupplyvoltage:Thetotalallowablepowerconsumptionofrespectivemodulesisupto6WintheGP10andupto20WintheGP20.

• Allowableinterruptiontime:Lessthan1cycleofthepowersupplyfrequency

[Powersupplysuffixcode:2]• Ratedsupplyvoltage:12VDC• Allowablepowersupplyvoltagerange:10to20

VDC

Page 9: General GP10/GP20 6SHFL¿FDWLRQV (Portable type) · General 6SHFL¿FDWLRQV GP10/GP20 Paperless Recorder (Portable type) Yokogawa Electric Corporation 2-9-32, Nakacho, Musashino-shi,

9

All Rights Reserved. Copyright © 2012, Yokogawa Electric Corporation GS 04L52B01-01EN Jul. 9, 2018-00

• Powerconsumption:Supplyvoltage

LCDbacklightoff

Normaloperation

Maximum

12VDC 7VA 10VA 26VA

Isolation• Insulationresistance:BetweentheEthernet,

RS-422/485,andeachinsulationterminalsandearth:20MΩorgreaterat500VDC

• Withstandvoltage: Betweenthepowerterminalandearth(IncaseofPowersupplysuffixcode:1):3000VACat50/60Hzforoneminute

Betweenthepowerterminalandearth(IncaseofPowersupplysuffixcode:2):500VACat50/60Hzforoneminute

Betweenthecontactoutputterminalandearth:3000VACat50/60Hzforoneminute

Betweentheinput/outputmodulesandearth:DependsonthespecificationofI/Omodule.

• Grounding:Besuretosetalowgroundingresistance.

• Isolation:

Power terminal

The circuits divided by lines are insulated mutually.

Internal circuit

FAIL output terminalEthernet portRS-422/485 terminalInput and output module terminal

Input and output module internal circuitEarth (PE) terminalRS-232 terminalSD card slotUSB port

SafetyandEMCStandards• CSA: CAN/CSA22.2No.61010.1,overvoltagecategory

II orI*1, and pollution degree 2 *2 CAN/CSA-C22.2NO.61010-2-030 CAN/CSA-IEC61010-201*4 • UL:UL61010-1,UL61010-2-030(CSANRTL/C) UL61010-2-201(CSANRTL/C)• CE/EMCdirective: EN61326-1compliance,ClassATable2 EN61000-3-2compliance EN61000-3-3compliance EN55011 Class A Group 1• CE/Lowvoltagedirective: EN61010-1,EN61010-2-030 OvervoltagecategoryIIorI*1 Pollution degree 2 *2

Measurementcategory*3 EN61010-2-201*4

• C-Tick:EN55011compliance,ClassAGroup1• KCmarking:Electromagneticwaveinterference

preventionstandard,electromagneticwaveprotectionstandardcompliance*1 Overvoltagecategory: Describesanumberwhichdefinesatransient

overvoltagecondition. Impliestheregulationforimpulsewithstandvoltage. “II”appliestoelectricalequipmentwhich

issuppliedfromthefixedinstallationlikeadistribution board.

II:Appliedtopowersupplyvoltagecode1(100-240VAC) I:Appliedtopowersupplyvoltagecode2(10-20VDC)

*2 Pollution degree 2: Describesthedegreetowhichasolid,liquid,

or gas which deteriorates dielectric strength or surfaceresistivityisadhering.

“2”appliestonormalindooratmosphere.Normally,onlynon-conductivepollutionoccurs.

*3 Measurementcategory:Dependsonthespecificationofeachmodules

*4 Thisproductisdesignedasopenequipmentundertherelevantstandard,installitasfollows:

•TomaketheGP10/GP20complywiththerelevantstandard,supportthepartsofthedeviceotherthanthefront-panelcontrolareawithaninstrumentationpanelorthelike,andinstallitinalocationwherepeoplecannottouchtheterminalscarelessly or in a panel.

•InstalltheGX60/GMunitinapanelwithadoor. •Theinstrumentationpanelorpanelusedfor

supportmustcomplywithCSA/UL/EN61010-2-201ormustbeatleastIP1X(degreesofprotection)andatleastIK09.

Category Measurementcategory

Description Remarks

II CATII Availableinthetestingandmeasuringcircuitsdirectly connected to a usage location (receptacle or the like) ofalow-voltagemainpowersupplyfacility.

Appliances, portable equipment,etc.

III CATIII Availableinthetestingandmeasuringcircuitsconnected to a power distributionportionofalow-voltagemainpowersupplyfacility.

Distributionboard, circuit breaker, etc.

IV CATIV Availableinthetestingandmeasuringcircuitsconnected to a power sourceofalow-voltagemainpowersupplyfacility.

verheadwire, cable systems,etc.

• WEEEDirective:CompliantNormalOperatingConditions:

• Powersupplyvoltage:100to240VAC±10%• Powersupplyfrequency:50/60Hz±2%• Ambienttemperature:0to50°C• Ambienthumidity:20to80%RH(at5to40°C)

(no condensation)• Magneticfield:400A/morless(DCand50/60

Hz)• Vibration: 5≤f<8.4Hzamplitude3.5mm(peak) 8.4≤f≤160Hzacceleration9.8m/s2

• Shock: Non-energization,500m/s2 orless,approximate10ms,6directions(±X,±Y,±Z),3timesineachdirection

• Mountingposition:Canbeinclinedupto30degreesbackward.Leftandrighthorizontalwheninstallingthepanelmountandwallmount.

• Altitude:2000morless• Installationlocation:Indoors• Warm-uptime:Atleast30minutesafterpower

on

Page 10: General GP10/GP20 6SHFL¿FDWLRQV (Portable type) · General 6SHFL¿FDWLRQV GP10/GP20 Paperless Recorder (Portable type) Yokogawa Electric Corporation 2-9-32, Nakacho, Musashino-shi,

10

All Rights Reserved. Copyright © 2012, Yokogawa Electric Corporation GS 04L52B01-01EN Jul. 9, 2018-00

OtherSpecifications:• Memorybackup:Abuilt-inlithiumbatterybacks

up the settings and runs the clock• RecommendedreplacementperiodsofBattery:

Approximately10years(atroomtemperature)TransportandStorageConditions:

• Ambienttemperature:–25to60°C• Ambienthumidity:5to95%RH(no

condensation)• Vibration:10to60Hz,4.9m/s2maximum• Shock:392m/s2maximum(inpackaged

condition)

EXTERNAL DIMENSIONS AND PANEL CUTOUT DIMENSIONSGP10:

*1: with modules*2: without moduels

Unit: mm (approx. inch)Unless otherwise specified, tolerance is ±3% (however, tolerance is ±0.3 mm when below 10 mm).

(*1)

(*2)MAX 

8(0.

31)

8(0.

31)

144.

9(5.

70)

(0.5

9)15

196.8(7.75)

247.2(9.73)144(5.67)

144.

9(5.

70)

15 (0.5

9)

143.6(5.65)

When using the stand, GP10 is upward 12 degrees.

Rearview

Power supply, Inlet (Power supply code:1)

Power supply, Screw terminal (Power supply code:1)

I/O module (slot 1)

RS-422A/485 terminal (/C3)or RS232 terminal (/C2)USB port (/UH)Ethernet portFAIL/STATUS terminal (/FL)

I/O module (slot 2)

I/O module (slot 0)

Page 11: General GP10/GP20 6SHFL¿FDWLRQV (Portable type) · General 6SHFL¿FDWLRQV GP10/GP20 Paperless Recorder (Portable type) Yokogawa Electric Corporation 2-9-32, Nakacho, Musashino-shi,

11

All Rights Reserved. Copyright © 2012, Yokogawa Electric Corporation GS 04L52B01-01EN Jul. 9, 2018-00

GP20:

Unit: mm (approx. inch)Unless otherwise specified, tolerance is ±3% (however, tolerance is ±0.3 mm when below 10 mm).

*1: with modules*2: without moduels

(*1)

(*2)MAX 

288(11.34)

196.8(7.75)

287(

11.3

0)8(

0.31

)23 (0

.91)

247.2(9.73)

288(

11.3

4)

288(11.34) 8(0.

31)

22 (0.8

7)

Rearview

Power supplyRS-422A/485 terminal (/C3)or RS232 terminal (/C2)USB port (/UH)Ethernet portFAIL/STATUS terminal (/FL)VGA output terminal (/D5)

I/O module (slot 0)I/O module (slot 1)I/O module (slot 2)I/O module (slot 3)I/O module (slot 4)

I/O module (slot 5)I/O module (slot 6)I/O module (slot 7)I/O module (slot 8)I/O module (slot 9)

PrecautionstoBeTakenWhileWiringWithascrewterminal,werecommendthatyouuseacrimp-onlugwithaninsulationsleeve(M4forpowersupplywiring,M3forsignal wiring).Recommendedsignalwiringcrimp-onlugN1.25-MS3(JSTMfg.Co.,Ltd.)

SPECIFICATIONS OF OPTIONAL FUNCTIONS

ADVANCEDSECURITYFUNCTION(/AS) Securityandelectronicrecord/signaturefunctions

havebeenaddedthatarecompliantwiththeUSA’sFDAtitle21CFRPart11.• Enabling/disablingtheadvancedsecurity

function: Youcanenableordisabletheadvancedsecurity

function.* Thesetvaluesanddatastoredintheinternal

memoryareinitializedeachtimethefunctionisenabled or disabled.

• Dataanti-tamperfunction: Settingsandmeasureddataaresavedas

encryptedbinaryfiles.• Datatype: Onlyfordisplayorevent Triggermodeisnotpossiblewitheventdata.• Loginfunction: Usingtheloginfunctiondescribedbelow,you

canentersecuritysettingsontheinstrument• Username• Password• UserID(dependonsetting)• Userlevelandnumberofusers: Systemadministrator(allcanbeoperated),

Generaluser(Withuserrestrictions,youcansetrestrictionsonperformingoperations and sign authority.), Monitor user(monitoringonly),totally100users

• Userrestrictionssetting:10kinds(forgeneral users)

• Passwordexpirationtime: selectformOff,1month,3month,6month• Passwordcontrolfunction: LoginsareverifiedbyaKerberosv5

authenticationserver*(onlyusernameandpassword)

Encryptionmethod:AES128-CTS-HMAC-SHA1-96AES256-CTS-HMAC-SHA1-96ARCFOUR-HMAC-MD5

Pre-Authfunction:use* Thefunctionhasconfirmedcompatibilitywith

WindowsServer2003SP2/WindowsServer2008SP2/WindowsServer2012ActiveDirectory

• Signaturefunction: Aftercheckingdatathathasfinishedbeing

recorded,youcanaddthreelevelsofelectronicsignature,selectapass/fail,andentercomments(50charactersmaximum)

• Audittrailfunction: The operation log, the settings change log and

thesettingsfilewhenthechangewasmadearesaved.

• Measurementmodelimitations HighspeedandDualintervalmeasurement

modesarenotsupported.• Modulelimitations PIDcontrolmodulesarenotsupported.

Page 12: General GP10/GP20 6SHFL¿FDWLRQV (Portable type) · General 6SHFL¿FDWLRQV GP10/GP20 Paperless Recorder (Portable type) Yokogawa Electric Corporation 2-9-32, Nakacho, Musashino-shi,

12

All Rights Reserved. Copyright © 2012, Yokogawa Electric Corporation GS 04L52B01-01EN Jul. 9, 2018-00

SERIALCOMMUNICATIONINTERFACE(/C2,/C3)• Connection:EIARS-232(/C2)orEIARS-

422/485(/C3)• Protocol:Dedicatedprotocol,Modbus/RTU,or

DARWINcompatiblecommunication• Setting/measurementserverfunction:Operation,

settingoroutputofmeasurementdataareavailablebydedicatedprotocol.

• Synchronization:Start-stopsynchronization• Transmissionmode(RS-422/485):

RS-422:Four-wirehalf-duplexmulti-dropconnection (1:n (n = 1 to 31)) RS485:Two-wirehalf-duplexmulti-dropconnection (1:n (n = 1 to 31))

• Baudrate:1200,2400,4800,9600,19200,38400,57600,or115200bps

• Datalength7or8bits• Startbit:1bit• Stopbit:1bitor2bit• Parity:ODD,EVEN,orNONE• HandshakingOff:Off,XON:XON,XON:RS,and

CS: RS• Communicationdistance;RS-422/485:1200m

(57600bpsorless),600m(115200bps) RS-232:15m• Modbus/RTUcommunication:Readingorwriting

ofmeasurementdataonotherinstrumentsisavailablebyModbusprotocol.

Communicationchannelfunctionoption(/MC)isneededtoreadmeasurementdatafromotherinstruments.

• Operationmodes:Masterorslave• Executionofacommunicationcommandusinga

barcode:Theenteredtextcanbeexecutedasacommunicationcommand.

CUSTOMDISPLAY(/CG) UsingDXA170DAQStudio,screencreation

software,acustomscreencanbeconstructedanddisplayedinwhichdisplaycomponents(suchastrend,digital,andbargraphs)arefreelyplaced.

ThescreendataistransferredfromDAQStudiototheinternalmemoryviacommunication,orloadedfromanexternalmediumtotheinternalmemoryand displayed.• Numberofscreens:30(internalmemory)• Displaycomponents:

• Normalcomponents(digitalvalue,bargraph,tagNo.,tagcomment,simpledigitalvalue,simplebargraph,alarmmark,unit,alarmindicator,lower-limitspanvalue,upper-limitspanvalue,groupname,systemicon,memorysamplebar,date/timeview,batchname,andusername)

• Trendcomponents(trendgroupdisplay(with scale board))

• Listcomponents(alarmlistviewandmessagelistview)

• Operationcomponents(DO(DOoperable),internal switch (internal switch operable), numericvalueoperations(viewingdataofandwritingdatatocommunicationchannels), and button operations (writing numericvalues,operatingbits,switchingscreens,andexecutingcommunicationcommands)

• Textcomponents(labels)

• Figurecomponents(lineview,rectangleview,andcircleview)

• Imagecomponents(PNGimagedata)• Batchcomponents(Batchnumber,Lot

number,Textfield,Batchcomment,Batchgroupnumber*)

* OnlyonGPwiththeMultibatchfunction(/BT option)

• Controlcomponent(controller,controlalarmindicator,externalcontroller)

• Configuringscreens:Screencreationsoftware CreationusingDXA170DAQStudio(GPdoes

nothaveacreationfunction)• Saving/loadingscreendata: Aspecifiedscreenorallthescreensis/are

loadedfromanexternalstoragemediumtotheinternalmemory,oraspecifiedscreenorallthescreensintheinternalmemoryis/aresavedonanexternalstoragemedium.

VGAVIDEOOUTPUT(/D5)(OnlyforGP20)• Externaldisplay: Resolution:800×600dots(VGA) Connector:15-pinD-Sub(female)

EtheNet/IPCOMMUNICATION(PLCcommunicationprotocol)(/E1)

CanbejoinedtoanEthernet/IPnetworkasanadapter(oraserver).• LoadingdatafromtheI/Ochannelorcalculation

channel (/MT) I/Ochannel: GP10: 100, GP20-1: 100, GP20-2: 500 Calculation channel: GP10: 50, GP20-1: 100, GP20-2: 200• Loadingandwritingdatafrom/tothe

communicationchannel(/MC) Communicationchannel: GP10: 50, GP20-1: 300, GP20-2: 500• Implementationlevel:Level2• Supportedprotocols:EIP/PCCC,EIP/native• Numberofthesimultaneousconnection:Max.

10(Explicitmessage)

WTCOMMUNICATION(/E2) CollectsdatabyconnectingtoWTequipment

manufacturedbyYokogawaMeters&InstrumentsCorp.viaEthernetcommunication*.* The /MC option is required.• Supportedmodels:WT1800E(commandtype

WT1800),WT1800,WT300E(commandmodeWT300),WT500,andWT300

• Numberofconnectableunits: GP10: 8 GP20:16• Communicationcycle:500ms/1s/2s/5s/10s/20

s/30 s• Typesofdatathatcanbeobtained:Voltage,

current,power,powerfactor,phase,electricalenergy,high-frequencywave,etc.

• Numberofdataallocations GP20:300 GP10:50

Page 13: General GP10/GP20 6SHFL¿FDWLRQV (Portable type) · General 6SHFL¿FDWLRQV GP10/GP20 Paperless Recorder (Portable type) Yokogawa Electric Corporation 2-9-32, Nakacho, Musashino-shi,

13

All Rights Reserved. Copyright © 2012, Yokogawa Electric Corporation GS 04L52B01-01EN Jul. 9, 2018-00

FAILOUTPUT(/FL)• Contact:Ccontact,1point• FAILoutput: The relay contact output on the rear panel

indicatestheoccurrenceofCPUfailure. Relayoperation:Energizedduringnormal

operationandde-energizedonCPUfailure.• Statusoutput:Therelaycontact,whichisde-

energizedinnormaloutputstate,isenergizedupontheoccurrenceofamemory/mediaerror,measurementerror,communicationerror,recordingstop,oralarm.

• Ratedpowersupplyvoltage:24VDCor250VAC or less

• Ratedloadcurrent:3A(DC)/3A(AC),resistanceload

• Min.loadcurrent:100mA• Recommendedreplacementperiodsofcontact: Electrical:30,000moreON-OFFoperations,

Mechanical:5,000,000moreON-OFFoperations

LogSCALE(/LG) Alogarithmicvoltagethathasbeenconvertedfrom

aphysicalvalueisappliedtotheGP,andthentheGP’sLogscale(logarithmicscale)isusedtodisplayandrecordthephysicalvalue.• Inputtype:Loginput(logarithmicinput),Pseudo

log input: An input that supports pseudo logs,Loglinearinput:Inputthatislinearonalogarithmicscale.

• Range:20mV/60mV/200mV/1V/2V/6V/20V/50V/100V

• Scalablerange:• Loginput: 1.00E-15to1.00E+15(15decade

maximum) Scale_L<Scale_U Ifthelowerlimitmantissais1.00,the

differencebetweentheexponentsmustbe1ormore.

Ifthelowerlimitmantissaisavalueotherthan1.00,thedifferencebetweentheexponentsmustbe2ormore.

• PseudoLogInput/Loglinearinput 1.00E-15to1.00E+15(15decade

maximum) Thehigherlimitmantissaisthesameas

thelowerlimitmantissa). Ifthelowerlimitmantissais1.00,thevalue

mustbebetween1.00E–15and1.00E+15,thedifferencebetweentheexponentsmustbe1ormore,andthemaximumdecadesis15.

Ifthelowerlimitmantissaisavalueotherthan1.00,thevaluemustbebetween1.01E–15and9.99E+14,thedifferencebetweentheexponentsmustbe1ormoreandthemaximumdecadesis15.

• Alarmtype:Highlimit,lowlimit,delayhighlimit,anddelaylowlimit

• Alarmsettingrange:TherangeconvertedintotheLOGscalecorrespondingto-5%to105%ofthe span width.

• Alarmhysteresis:Fixedto0

• Greenbandsettingrange:Thelowerlimittotheupperlimitofthescale.However,thelowerlimitofthedisplaypositionmustbesmallerthantheupperlimit.

• Positionofthedecimalpoint:1to2• Misc:Nonlinearinputispossiblebycorrecting

theinputvalue

MATHEMATICAL FUNCTIONS WITH REPORT FUNCTION(/MT)MathematicalFunction:• Numberofmathchannels;GP10:50,GP20-1:

100, GP20-2: 200Note) Note:Dependingonthemeasurementmode,

thereisalimittothenumberofmathchannelsatscanintervalsshorterthan100ms.See“Limitations.”

• ScanintervalMeasurementmode Scaninterval

Normal Scaninterval

High speed Scaninterval

Dualinterval Masterscaninterval*

* WhenthemeasurementmodeisDualinterval,thisitemsetswhichscanintervaltouse,theintervalofmeasurementgroup1orthatofscangroup2,forcreatingmeasuredvaluesofmathorcommunicationchannelsandothersimilaroperations.

• Numberofexpressions:• Operation: Generalarithmeticoperations:Fourarithmetic

operations(+,-,*,/),squareroot,absolute,commonlogarithm,naturallogarithm,exponential,andpower

Relationaloperations:<,≤,>,≥,=,and≠ Logicoperations:AND,OR,NOT,andXOR Statisticaloperations:TLOG(maximum,

minimum,average,sum,P-Pvaluesoftimeseriesdata)orCLOG(maximum,minimum,average,sum,P-Pvaluesofaspecifiedchannel)

Specialoperations:PRE,HOLD,RESET,andCARRY

Conditionaloperation:[a?b:c] Bitoperation:BIT Integerextractingoperation:INT Remainderextractingoperation:MOD Trigonometricfunctions:SIN,COS CP operations: CP.02, CP.CO2• Computationaccuracy:Double-precisionfloating

point• Datathatcanbeused; Channeldata:Measurementchannels(0001to

6516to6516),mathematicalchannels(GP10:A001 to A050, GP20-1: A001 to A100, GP20-2: A001toA200),Communicationchannels(GP10:C001 to C050, GP20-1: C001 to C300, GP20-2: C001toC500),Communicationchannelsrawdata (GP10: RC001 to RC050, GP20-1: C001 to C300,GP20-2: RC001 to RC500),Constants: K001toK100,Variableconstant:W001toW100,Internalswitch:S001toS100,Flag:F01toF20,Recording state (REC01), Integer data: Z000 to Z999

Page 14: General GP10/GP20 6SHFL¿FDWLRQV (Portable type) · General 6SHFL¿FDWLRQV GP10/GP20 Paperless Recorder (Portable type) Yokogawa Electric Corporation 2-9-32, Nakacho, Musashino-shi,

14

All Rights Reserved. Copyright © 2012, Yokogawa Electric Corporation GS 04L52B01-01EN Jul. 9, 2018-00

USBINTERFACE(/UH)• USBport:ComplieswithUSB2.0andhost

function• Numberofports:2(oneeachonthefrontpanel

and rear panel)• Connectabledevices:Onlyconnectthedevices

listedbelowtopreventdamagetothedevices.Keyboard:ComplieswithHIDClassVer.1.1 104/89keyboard(US)and109/89

keyboard (Japanese)Mouse:ComplieswithHIDClassVer.1.1Externalmedium:USBflashmemory Doesnotguaranteetheoperationofall

USBflashmemories Externalmediumsuchasaharddisk,ZIP,

MO, and optical discs are not supported.Barcodereader:USBHIDClassVer.1.1

compatible English(U.S.)standardUSBkeyboard

compatible• Executionofacommunicationcommandusinga

barcode:Theenteredtextcanbeexecutedasacommunicationcommand.

• Powersupply:5V±10%,500mA*1*1: Deviceswhichneedmorethan500mAtotalbus

powerfor2portscannotbeconnectedatthesametime.

Forlowpowereddevices(buspower<100mA):5V±5%

Forhighpowereddevices(buspower<500mA):5V±10%

AEROSPACEHEATTREATMENT(/AH)SupportsheattreatmentapplicationAMS2750/

NADCAP.Schedulemanagementforperiodicallyexecuting

calibrationcorrectionconfigurationandthelike.Incorrectioncoefficientmodeofcalibration

correction,twobiasescanbespecified:onebasedonthermocoupleandanotherbasedondevice

• Numberofmanageableschedules GP20-1:6 GP20-2: 12• Calibrationcorrectionmode: Off,Linearizerapproximation,Linearizerbias,

correctionfactor• Numberofsetpoints:2to12• Notificationcontents Title,Notificationmessage,DuedateNotificationbuzzercanbesounded.

Logicmathfunction:Afunctionthatoutputscalculatedresultsas0or1

toDOsorinternalswitches• Numberoflogiccalculationsmaths: GP10: 20, GP20-1/GP20-2: 50• Expression:Upto120characters• Computationtype:Basicarithmetic,relational,

logical, conditional, bit• Datathatcanbeused:Allchanneldata• Logicmath:LM001toLM020(GP10),LM001to

LM050 (GP20-1/GP20-2)• Outputdestination:DOchannels,internal

switches (only when set to Manual in either case)• Settingchange:Cannotbechangedduring

recording• Mathinterval:100ms(fastest)

Reportfunction:• Numberofreportchannels;GP10:50,GP20:60Note) Dependingonthemeasurementmode,thereis

alimittothenumberofreportchannelsatscanintervalsshorterthan100ms.See“Limitations.”

• ScanintervalMeasurementmode Scaninterval

Normal Scaninterval

High speed Scaninterval

Dualinterval Scanintervalofeachmeasurementgroup

• Reporttypes:Hourly+daily,daily+weekly,daily+monthly,Batch,Daycustom

• Computationtypes:Average,maximum,minimum,sum,orinstantaneousvalue

• Unitofsum:OFF,/s,/min,/hour,/day• Reporttemplates:OfficeOpenXMLspreadsheet

files(whichcanbedisplayedwithMicrosoftOfficeExcel)orPDFfilescanbeoutputorprinted out with any LAN-connected printer supporting the HP PCL5c language and the port 9100.

COMMUNICATIONCHANNELFUNCTIONS(/MC)• Numberofcommunicationchannels; GP10: 50 (C001 to C050) GP20-1: 300 (C001 to C300) GP20-2: 500 (C001 to C500)Note) Dependingonthemeasurementmode,thereis

alimittothenumberofcommunicationchannelsatscanintervalsshorterthan100ms.See“Limitations.”

Theminimumcommunicationchannelupdateintervalis100ms.

• ScanintervalMeasurementmode Scaninterval

Normal Scaninterval

High speed Scaninterval

Dualinterval Masterscaninterval

* RequiredtorecorddatafromEtherNet/IP(/E1),Modbusdevices,orPCsontheGPandtowritedataintheremotedevicefromtheGPviaModbus.

• Calibrationcorrection Mode:LinearizerApproximation,LinearizerBias,

Correctionfactor* Numberofsetpoints:2to12* Only when the /AH option is installed

Page 15: General GP10/GP20 6SHFL¿FDWLRQV (Portable type) · General 6SHFL¿FDWLRQV GP10/GP20 Paperless Recorder (Portable type) Yokogawa Electric Corporation 2-9-32, Nakacho, Musashino-shi,

15

All Rights Reserved. Copyright © 2012, Yokogawa Electric Corporation GS 04L52B01-01EN Jul. 9, 2018-00

MULTI-BATCHFUNCTION(/BT)Recordingstart/stopanddatafilecreationis

possibleforeachbatch.• Numberofmulti-batches: GP10/GP20-1:max.6,GP20-2:max.12• Batchsingleoperation:Memorystart/stop,math

reset,messagewriting• Batchoverviewoperation:Computationstart/

stop,reportstart/stop,manualsampling,setupdatasave/load

• Scaninterval:500ms,1s,2s,5s(commontoall batches)

• Datatype:DisplayoreventonlyTriggermodenotavailableforeventdata.

• Recordinginterval:Commontoallbatches• Datafile:Displayoreventdatafilecreatedfor

each batch• Numberofdisplaygroups: GP10:6max.perbatch

Numberofchannelspergroup:10 GP20-1:6max.perbatch

Numberofchannelspergroup:20 GP20-2:12max.perbatch

Numberofchannelspergroup:20 Channelsassignedtothedisplaygroupofeach

batch and those set as recording channels are recordedtodatafiles.

• Batchsinglesettings:Group,tripline,fileheader,datafilename,textfield,batchnumber,lotnumber

• Measurementmodelimitations HighspeedandDualintervalmeasurement

modesarenotsupported.

OPC-UASERVER(/E3)DataacquiredbytheGPcanbeaccessedthrough

Ethernetcommunicationfromahostsystem(OPC-UAclient).

• Communication Mode:OPC-UAServer Encoding:UABinary Protocol:OPCUATCP Maximumnumberofconnections:3sessions Profile MicroEmbeddedDeviceServer• Security Type: None Encryption: None Login:Anonymous,Username• Dataacquisition: Measurementvalue,alarmstatus,andalarm

value Computationvalue,alarmstatus,andalarm

value Communicationvalue,alarmstatus,andalarm

value Batchinformation PV,SP,OUT,R/S,A/M/C,R/L,Alarmstatusin

loop• Datawriting:Measurementchannel(DOchannel

only),communicationchannel,alarmvalue,batchinformation,OUT,R/S,A/M/C,R/L

• Otheracquiredinformation:Devicename,serialnumber,time,devicestatus

• Portnumber:4840(changeable:1to65535)• Numberofitems: GP10:100max.(MonitoredItem/Session) GP20:300max.(MonitoredItem/Session)

• Fastestperiod:100ms• Serviceset:Discovery FindServers,GetEndpoints

SecureChannel OpenSecureChannel,CloseSecureChannel

Session CreateSession,ActivateSession,CloseSession

View Browse,BrowseNext,TranslateBrowsePathsToNodeIds

Attribute Read,Write

MonitoredItem CreateMonitoredItems,ModifyMonitoredItems,DeleteMonitoredItems,SetMonitoringMode

Subscription CreateSubscription,ModifySubscription,DeleteSubscriptions,Publish,Republish,SetPublishingMode

SLMPCOMMUNICATION(MitsubishiPLC)(/E4)CC-LinkfamilySLMPcommunicationprotocol

function,whichenablesconnectionfromaGPto Mitsubishi Electric PLCs without sequencer programs.

TheGPoperatesasanSLMPclient.WritingGPmeasurementdatatoaPLCandreadingPLCdataintocommunicationchannels*arepossible.* Thecommunicationchannelfunction(/MCoption)

is required.• Numberofconnectiondestinationservers:16max.• Readcycle:100ms/200ms/500ms/1s/2s/5s/10s/2

0s/30s/1min• Numberofcommandsthatcanberegistered GX10:50 GX20-1:100 GX20-2:200• Communicableinternaldata: Specialrelay(SM),specialregister(SD),input

(X),output(Y),internalrelay(M),latchrelay(L),annunciator(F),edgerelay(V),linkrelay(B),dataregister(D),linkregister(W),timercontact(TS),timercoil(TC),currenttimervalue(TN),integrationtimercontact(SS),integrationtimercoil(SC),currentintegrationtimervalue(SN),counter contact (CS), counter coil (CC), current countervalue(CN),speciallinkrelay(SB),speciallinkregister(SW),directaccessinput(DX),directaccessoutput(DY),indexregister(Z),fileregister(R,ZR),extendeddataregister(D),extendedlinkregister(W)

Devicecodeisindicatedinparentheses.

Programcontrolfunction(/PG)SeeGX90UTPIDControlModuleGeneral

Specifications(GS04L53B01-31EN)

Page 16: General GP10/GP20 6SHFL¿FDWLRQV (Portable type) · General 6SHFL¿FDWLRQV GP10/GP20 Paperless Recorder (Portable type) Yokogawa Electric Corporation 2-9-32, Nakacho, Musashino-shi,

16

All Rights Reserved. Copyright © 2012, Yokogawa Electric Corporation GS 04L52B01-01EN Jul. 9, 2018-00

LimitationsSystemlimitations

MaximumnumberofchannelsSystem Measurment

modeMaximumnumberofmoduleconnections

MaximumnumberofchannelsInput/output Communication Math Report

GP10 Normal 10 100 50 50 50

High speed 3 12 50 50 50

Dualinterval 10 50 25 25 25

GP20-1 Normal 10 100 300 100 60

High speed 10 40 300 100 60

Dualinterval 10 50 150 50 30

GP20-2 Normal 45 500 500 200 60

High speed 10 40 500 200 60

Dualinterval 45 250 250 100 30

LimittothenumberofexpandableI/OunitsorGMsubunits•Uptosixunitscanbeconnected.•ConnectionisnotpossibleifthemeasurementmodeissettoHighspeed.

LimittothenumberofGPmainunitmodulesModule GP10 GP20-1 GP20-2

WhenGX90XA-04-H0andGX90YAareincluded

2* 9 9

WhenGX90UTisincluded 2* 8 8

* Whenthe12VDC(PowersupplySuffixCode2)model.

LimitonModules•Upto10modulesconsistingofGX90YD,GX90WD,andGX90UTcanbeinstalledintothesystem.•OneGX90WDmodulecanbeinstalledinaGP.OnemodulecanbeinstalledinaGX60(expandableI/O)andeach

GM sub unit.•OneGX90YAmodulecanbeinstalledinaGP10.TwomodulescanbeinstalledineachoftheGP20,GX60(expandableI/O)andGMsubunit.

•Upto10GX90YAmodulescanbeinstalledinaGP10/GP20-1systemandupto12inaGP20-2system.•IfthemeasurementmodeisHighspeed,aGX90XDorGX90WDmodulecanbeinstalledinthesystem.•IfthemeasurementmodeisHighspeed,onlyGX90XA-04-H0(high-speedAI),GX90XD(DI),andGX90WD(DIO)aredetected.DIandDIOarefixedtoremotemode.Measurementandrecordingarenotpossible.

•IfthemeasurementmodeisDualinterval,GX90UTisnotdetected.

LimittotheNumberofMeasurementChannelsThefollowinglimitationappliestothenumberofchannelsthatcanmeasureatscanintervalsshorterthan100ms.IfthemeasurementmodeisDualinterval,thelimitationappliesatthescangrouplevel.However,therearescanintervalsyoucannotset.

● MeasurementmodeisHighspeedGP10

Channel Scaninterval1ms 2ms 5ms 10ms 20ms 50ms

Input/output 1 2 5 10 12 12

math – 1 2 5 10 25

communication – 1 2 5 10 25

Report – 1 2 5 10 25

Page 17: General GP10/GP20 6SHFL¿FDWLRQV (Portable type) · General 6SHFL¿FDWLRQV GP10/GP20 Paperless Recorder (Portable type) Yokogawa Electric Corporation 2-9-32, Nakacho, Musashino-shi,

17

All Rights Reserved. Copyright © 2012, Yokogawa Electric Corporation GS 04L52B01-01EN Jul. 9, 2018-00

GP20-1

Channel Scaninterval1ms 2ms 5ms 10ms 20ms 50ms

Input.output 1 2 5 10 20 40

math 1 2 5 10 20 50

communication 3 6 15 30 60 150

Report 1 2 5 10 20 50

GP20-2

Channel Scaninterval1ms 2ms 5ms 10ms 20ms 50ms

Input.output 5 10 25 40 40 40

math 2 4 10 20 40 100

communication 5 10 25 50 100 250

Report 2 4 10 20 40 60

● MeasurementmodeisDualintervaGP10

Channel Scaninterval1ms 2ms 5ms 10ms 20ms 50ms

Input.output – – 5 10 12 12

math – – 1 2 5 12

communication – – 1 2 5 12

Report – – 1 2 5 12

GP20-1

Channel Scaninterval1ms 2ms 5ms 10ms 20ms 50ms

Input.output – – 5 10 20 40

math – – 2 5 10 25

communication – – 7 15 30 75

Report – – 2 5 10 25

GP20-2

Channel Scaninterval1ms 2ms 5ms 10ms 20ms 50ms

Input.output 5 10 25 40 40 40

math 1 2 5 10 20 50

communication 2 5 12 25 50 125

Report 1 2 5 10 20 30

Page 18: General GP10/GP20 6SHFL¿FDWLRQV (Portable type) · General 6SHFL¿FDWLRQV GP10/GP20 Paperless Recorder (Portable type) Yokogawa Electric Corporation 2-9-32, Nakacho, Musashino-shi,

18

All Rights Reserved. Copyright © 2012, Yokogawa Electric Corporation GS 04L52B01-01EN Jul. 9, 2018-00

LimittotheNumberofRecordingChannelsinEachMeasurementModeI/Ochannel+mathchannel+communicationchannel

Model Measurmentmode

Recordinginterval1ms 2ms 5ms 10ms 20ms 50ms 100ms 200ms 500ms 1sor

moreGP10 Normal – – – – – – 100 100 100 100

High speed 1 4 9 20 32 62 100 100 100 100

Dualinterval – – 5 10 20 36 100 100 100 100

GP20-1 Normal – – – – – – 100 200 500 500

High speed 2 4 10 20 40 100 100 200 500 500

Dualinterval – – 5 10 20 50 100 100 250 250

GP20-2 Normal – – – – – – 500 500 1000 1000

High speed 10 20 50 100 150 150 200 500 1000 1000

Dualinterval 5 10 25 40 50 50 100 20 600 600

Note) Numberofactiverecordablechannels.

NotesonModuleInstallation•WhenthereferencejunctioncompensationofthisproductisusedwiththethermocoupleinputofaGX90XA-10-U2,GX90XA-10-L1,GX90XA-10-T1, GX90XA-10-V1orGX90XA-04-H0,ifthefollowingmoduleisinstalledtotheright(slotwiththesmallernumber)oftheGX90XAmoduleasseenfromtheGPrearpanel,thereferencejunctioncompensationaccuracyofthatmodulemaydeviatefromtheguaranteedrange(exceptwhenGX90XA-04-H0isinstalledtoadjacentslots).

GX90XA-10-C1,GX90XA-04-H0,GX90WD,GX90YA,GX90UT•OntheGP20,whenthereferencejunctioncompensationofthisproductisusedwiththethermocoupleinputofaGX90XA-10-U2,GX90XA-10-L1,GX90XA-10-T1, GX90XA-10-V1orGX90XA-04-H0,ifthefollowingmoduleisinstalledabove,below,totheright,ortotheleft(slotwiththesmallernumber)oftheGX90XAmoduleasseenfromtheGPrearpanel,thereferencejunctioncompensationaccuracyofthatmodulemaydeviatefromtheguaranteedrange.

GX90YA,GX90UT•IfyouwanttousetheDIofaGX90XDorGX90WD,onlyasinglemoduleinstalledintheGPmainunitcanbeused.•IfthemaximumnumberofI/OchannelsareassignedandthelastchannelisassignedtoanintermediatechannelofaconnectedI/Omodule,thatmoduleandsubsequentmoduleswillnotberecognized.

Modulen

• • •

1

10

Module1

:

81

90

:

91

100

106

:

:Maximum number of I/O channels

This module will not be detected.

Example GP10/GP20-1

DualIntervalFileSearchingofUniversalViewer

Recordingmode Linkdualintervalwaveform*1 Showdualintervalintegratedlinkview*2

Free+Free

Free+Trigger(single/repeat) – –

Trigger(single/repeat)+Trigger(single/repeat)

– –

*1 Linkdualintervalwaveform:Afunctionthatsearchesafolderforanddisplaysthefilethatformsapairwiththedisplayedfile.

*2 Showdualintervalintegratedlinkview:AfunctionthatdisplaysfromtheresultofSearchOpenoneofthefilesthatformsapair and displays both trends when it is clicked.

PIDprogrampatternsettingfromtheWebapplicationYoucannotsetfromtheWebapplication.HardwareConfiguratorisrequiredforsettingprogrampatterns.

Page 19: General GP10/GP20 6SHFL¿FDWLRQV (Portable type) · General 6SHFL¿FDWLRQV GP10/GP20 Paperless Recorder (Portable type) Yokogawa Electric Corporation 2-9-32, Nakacho, Musashino-shi,

19

All Rights Reserved. Copyright © 2012, Yokogawa Electric Corporation GS 04L52B01-01EN Jul. 9, 2018-00

INPUT/OUTPUT MODULE SPECIFICATIONS

ANALOGINPUTMODULE(ModelGX90XAorOption/Uxx0)

DIGITALINPUTMODULE(ModelGX90XDorOptions/CRx1)

DIGITALOUTPUTMODULE(ModelGX90YD,orOptions/CR1x,/CR2x,/CR4x)

DIGITAL INPUT/OUTPUT MODULE (ModelGX90WD)

PULSEINPUTMODULE(ModelGX90XP)

ANALOGOUTPUTMODULE(ModelGX90YA)

PIDCONTROLMODULE(ModelGX90UT)

PleaseseeGX90XA/GX90YA/GX90XD/GX90YD/GX90WD/GX90XPInput/OutputModuleandPIDControl(GS04L53B01-31EN)GeneralSpecification(GS 04L53B01-01EN.)

APPLICATION SOFTWARESMARTDAC+STANDARD• Universalviewer• Hardwareconfigurator(withProgrampattern

setting)

DownloadthelatestversionofthesoftwarefromthefollowingURL; www.smartdacplus.com/software/en/

OperatingenvironmentOS:

OS TypeWindows7 HomePremiumSP1(32-bitand64-bit

Editions)

ProfessionalSP1(32-bitand64-bitEditions)

Windows8.1 Update

ProUpdate

Windows10 Home(32-bitand64-bitEditions)

Pro(32-bitand64-bitEditions)

Processorandmainmemory:OS Processorandmainmemory

Windows7Windows8.1Windows10

32-biteditionIntelPentium4,3GHzorfasterx64orx86,2GBormore64-biteditionIntelx64processorthatisequivalenttoIntelPentium4,3GHzorfaster,2GBormore

Browser:Supportedbrowser:InternetExplorer11HTTP1.1andJavaScriptareused.

Harddisk:• 100MBormoreoffreespace

Display:• AvideocardthatisrecommendedfortheOS

and a display that is supported by the OS, has a resolutionof1024x768orhigher,andthatcanshow65,536colors(16-bit,highcolor)ormore.

UniversalViewersoftwareTheuniversalviewercandisplaythefollowingdatagenerated by the recorder on the screen and print it out on the printer.• Displaydatafile• Eventdatafile• Reportdatafile(IncludingHour,Day,Week

Month)• Manualsampledatafile

• Viewerfunction Waveformdisplay,digitaldisplay,circulardisplay,

list display, report display, operation log display etc.

• Dataconversion: FileconversiontoASCIIorMS-Excelformat• Signinfunction

Webapplication/Hardwareconfigurator• OnlinesettingonWebbrowser(IE)• OfflinesettingonWebbrowser(IE)BothsettingscanbemadeusingbrowserssuchasInternetExplorer11.

Page 20: General GP10/GP20 6SHFL¿FDWLRQV (Portable type) · General 6SHFL¿FDWLRQV GP10/GP20 Paperless Recorder (Portable type) Yokogawa Electric Corporation 2-9-32, Nakacho, Musashino-shi,

20

All Rights Reserved. Copyright © 2012, Yokogawa Electric Corporation GS 04L52B01-01EN Jul. 9, 2018-00

MODEL AND SUFFIX CODESModel SuffixCode Optionalcode DescriptionGP10 Paperlessrecorder(Portabletype,Smalldisplay)*13

GP20 Paperless recorder (Portable type, Large display) *13

Type -1 Standard(Max.measurementchannels:100ch)

-2 Largememory(Max.measurementchannels:500ch)*12

Displaylanguage E English,degF,DST(summer/wintertime)*9

Power supply 1 100VAC,240VAC*16

2 12VDC*17

Power cord D PowercordUL/CSAstandard

F PowercordVDEstandard

R Power cord AS standard

Q Power cord BS standard

H Power cord GB standard

N Power cord NBR standard

W Screwterminal,powercordnotincluded

Optionalfeatures /AH Aerospaceheattreatment

/AS Advancedsecurityfunction(Part11)*23

/BT Multi-batchfunction*24

/C2 RS-232 *1

/C3 RS-422/485 *1

/CG Customdisplay*15

/D5 VGAoutput*2

/E1 EtherNet/IPcommunication(PLCcommunicationprotocol)*20

/E2 WTcommunication*14

/E3 OPC-UAserver

/E4 SLMPcommunication(MitsubishiPLC)*21

/FL Failoutput,1point

/LG Log scale

/MT Mathematicalfunction(withreportfunction)*18 *19

/MC Communicationchannelfunction*21

/PG Programcontrolfunction*25

/UH USBinterface(Host2ports)

Page 21: General GP10/GP20 6SHFL¿FDWLRQV (Portable type) · General 6SHFL¿FDWLRQV GP10/GP20 Paperless Recorder (Portable type) Yokogawa Electric Corporation 2-9-32, Nakacho, Musashino-shi,

21

All Rights Reserved. Copyright © 2012, Yokogawa Electric Corporation GS 04L52B01-01EN Jul. 9, 2018-00

Analoginputmodule,DigitalI/Omodule:Pleaseaddthefollowingsuffixcodestothemainunitmodelandspecificationcodes.

Option Optionalcode DescriptionOptionalfeatures(Analog input) *3*11

/UC10 Withanaloginputmodule,10ch(Clampterminal)

/UC20 Withanaloginputmodule,20ch(Clampterminal)*7

/UC30 Withanaloginputmodule,30ch(Clampterminal)*8

/UC40 Withanaloginputmodule,40ch(Clampterminal)*5

/UC50 Withanaloginputmodule,50ch(Clampterminal)*5

/US10 Withanaloginputmodule,10ch(M3screwterminal)

/US20 Withanaloginputmodule,20ch(M3screwterminal)*7

/US30 Withanaloginputmodule,30ch(M3screwterminal)*8

/US40 Withanaloginputmodule,40ch(M3screwterminal)*5

/US50 Withanaloginputmodule,50ch(M3screwterminal)*5

Optionalfeatures(DigitalI/O)*4

/CR01 WithdigitalI/Omodule,(Output:0,Input:16)*8 *9 *18

/CR10 WithdigitalI/Omodule,(Output:6,Input:0)*8

/CR11 WithdigitalI/Omodule,(Output:6,Input:16)*7 *8 *9 *18

/CR20 WithdigitalI/Omodule,(Output:12,Input:0)*6

/CR21 WithdigitalI/Omodule,(Output:12,Input:16)*6*9 *18

/CR40 WithdigitalI/Omodule,(Output:24,Input:0)*6

/CR41 WithdigitalI/Omodule,(Output:24,Input:16)*6*9 *18

*1 /C2and/C3cannotbespecifiedtogether.*2 /D5canbespecifiedonlyfortheGP20.*3 Onlyoneoptioncanbespecified.*4 Onlyoneoptioncanbespecified.*5 /UC40,/UC50,/US40and/US50cannotbespecifiedfortheGP10.*6 /CR20,/CR21,/CR40and/CR41cannotbespecifiedfortheGP10.*7 If/UC20or/US20isspecified,/CR11cannotbespecifiedfortheGP10.*8 If/UC30or/US30isspecified,/CR01,/CR10and/CR11cannotbespecifiedfortheGP10.*9 DigitalinputmodulehaveM3screwterminals.*10 TheDisplaylanguageisselectablefromEnglish,German,French,Russian,Korean,Chinese,Japanese.(AsofMar.,2013) Toconfirmthecurrentavailablelanguages,pleasevisitthefollowingwebsite. URL:http://www.yokogawa.com/ns/language/*11Universaltype(TypeSuffixCode:-U2).Ifyouneedtheelectromagneticrelaytype(TypeSuffixCode:-T1),current(mA)

inputtype(TypeSuffixCode:-C1),Lowwithstandvoltagerelay,type(TypeSuffixCode:-L1),High-speeduniversaltype(TypeSuffixCode:-H0),4-wireRTD/resistancetype(TypeSuffixCode:-R1),purchaseitseparately.

*12LargememorytypecanbespecifiedonlyfortheGP20.*13ToconnectanexpandableI/O,GMsubunit,youwillneedoneexpansionmodulefortheGP.*14/MCmustbeseparatelyspecifiedwhentheWTcommunicationisselected.*15CreatingcustomdisplaysrequiresDXA170DAQStudio(soldseparately).(GPdoesnothaveacreationfunction.)*16PowercodecanbespecifiedthesuffixcodeD,F,R,Q,H,orN..*1712VDCpowersupplycanbespecifiedonlyfortheGP10withoutpowercode(suffixcode:W).*18Optionalcode/MT(MATH)requiredifusingtheGX90XD'sorGX90WD'spulseinput.*19The/MToption(computation)isrequiredtoperformpulseintegrationonGX90XPpulseinputmodules.*20IfyouwanttowritefromaPLCtotheGPviaEtherNet/IPcommunication,aseparatecommunicationchannel(/MC)is

required.*21Aseparatecommunicationchannel(/MC)isrequiredtoperformSLMPcommunication.*22Acommunicationchannel(/MC)isrequiredtoconfiguretheModbusclientfunctionandforotherdevicestowritetotheGP

Modbusserver.*23WhentheadvancedsecurityfunctionissettoON,thescanintervalissetto100msorlonger.Inaddition,thedualinterval

functionandPIDmodulescannotbeused.*24Whenthemulti-batchfunctionissettoON,thescanintervalissetto500msorlonger.Inaddition,thedualintervalfunction

cannot be used.*25APIDcontrolmoduleisrequiredtousetheprogramcontrolfunction.

Page 22: General GP10/GP20 6SHFL¿FDWLRQV (Portable type) · General 6SHFL¿FDWLRQV GP10/GP20 Paperless Recorder (Portable type) Yokogawa Electric Corporation 2-9-32, Nakacho, Musashino-shi,

22

All Rights Reserved. Copyright © 2012, Yokogawa Electric Corporation GS 04L52B01-01EN Jul. 9, 2018-00

ModuleinstallationpositionsofanaloginputmodulesanddigitalI/Omoduleswhentheyarepreinstalled

GP10

Moduletype OptionalcodeSlotnumber

2 1 0

AnalogInput(GX90XA-10-U2)

/UC10or/US10 --- --- AI

/UC20or/US20 --- AI AI

/UC30or/US30 AI AI AI

DigitalI/O(GX90XD,GX90YD)

/CR01 --- --- DI

/CR10 --- --- DO

/CR11 --- DO DI

AnalogInput(GX90XA-10-U2+DigitalI/O(GX90XD,GX90YD)

/UC10or/US10,/CR01 --- DI AI

/UC10or/US10,/CR10 --- DO AI

/UC20or/US20,/CR01 DI AI AI

/UC20or/US20,/CR101 DI AI AI

•Analoginputmodulesspecifiedwith/U□□0areinstalledinslots0to2.•Digitalinputanddigitaloutputmodulesspecifiedwith/CR□□areinstalledinslots0and1. Thedigitalinputmoduleisinstalledwithhigherprecedencethanthedigitaloutputmodule.•Ifboth/U□□0and/CR□□arespecified,themodulesareinstalledtoslots0to2inthefollowingorderof

precedence: analog input, digital input, digital output.•AI:GX90XA-10-U2N-□N,DI:GX90XD-16-11N-3N,DO:GX90YD-06-11N-3N

Slotnumber

GP10 Rear

012

Page 23: General GP10/GP20 6SHFL¿FDWLRQV (Portable type) · General 6SHFL¿FDWLRQV GP10/GP20 Paperless Recorder (Portable type) Yokogawa Electric Corporation 2-9-32, Nakacho, Musashino-shi,

23

All Rights Reserved. Copyright © 2012, Yokogawa Electric Corporation GS 04L52B01-01EN Jul. 9, 2018-00

GP20

Moduletype Optionalcode

Slotnumber

9 8 7 6 5

4 3 2 1 0

AnalogInpu(GX90XA-10-U2)

/UC10or/US10 --- --- --- --- ---

--- --- --- --- AI

/UC20or/US20 --- --- --- --- ---

--- --- --- AI AI

/UC30or/US30 --- --- --- --- ---

--- --- AI AI AI

/UC40or/US40 --- --- --- --- ---

--- AI AI AI AI

/UC50or/US50 --- --- --- --- ---

AI AI AI AI AI

DigitalI/O(GX90XD,X90YD)

/CR01 --- --- --- --- DI

--- --- --- --- ---

/CR10 --- --- --- --- DO

--- --- --- --- ---

/CR11 --- --- --- DO DI

--- --- --- --- ---

/CR20 --- --- --- DO DO

--- --- --- --- ---

/CR21 --- --- DO DO DI

--- --- --- --- ---

/CR40 --- DO DO DO DO

--- --- --- --- ---

/CR41 DO DO DO DO DI

--- --- --- --- ---

•Analoginputmodulesspecifiedwith/U□□0areinstalledinslots0to2.•Digitalinputanddigitaloutputmodulesspecifiedwith/CR□□areinstalledinslots0and1. Thedigitalinputmoduleisinstalledwithhigherprecedencethanthedigitaloutputmodule.•Ifboth/U□□0and/CR□□arespecified,eachmoduleisinstalledinitscorrespondingposition.•AI:GX90XA-10-U2N-□N,DI:GX90XD-16-11N-3N,DO:GX90YD-06-11N-3N

Slotnumber

01234

56789

GP20 Rear

Page 24: General GP10/GP20 6SHFL¿FDWLRQV (Portable type) · General 6SHFL¿FDWLRQV GP10/GP20 Paperless Recorder (Portable type) Yokogawa Electric Corporation 2-9-32, Nakacho, Musashino-shi,

24

All Rights Reserved. Copyright © 2012, Yokogawa Electric Corporation GS 04L52B01-01EN Jul. 9, 2018-00

Analoginput/outputmodule,DigitalI/Omodule(soldseparately):MODELandSUFFIXCode(GX90XA)MODELandSUFFIXCode(GX90XD)MODELandSUFFIXCode(GX90YD)MODELandSUFFIXCode(GX90WD)MODELandSUFFIXCode(GX90XP)MODELandSUFFIXCode(GX90YA)MODELandSUFFIXCode(GX90UT) PleaseseeGX90XA/GX90XD/GX90YD/GX90WD/GX90XP/GX90YAInput/OutputModuleGeneralSpecification

(GS04L53B01-01EN.)andPIDControlModule(GS04L53B01-31EN)When connecting the Expandable I/O PleaseseeGX60ExpandableI/O,GX90EXExpansionModuleGeneralSpecification(GS04L53B00-01EN.)

StandardAccessoriesProduct Qty

SDmemorycard(1GB) 1

Stylus pen (touch pen) 1

Tagsheet(forGP10orGP20) 1

Sheet(forGP10orGP20) 1

Power cord 1*

Dummycover(Foremptyslots) -

* ExceptGP10powersupplysuffixcode:2

ApplicationSoftware(SoldSeparately)Model Description OS

DXA170 DAQStudiosoftware Windows7/8/8.1/10

GA10 DataLoggingSoftware Windows7/8.1/10WindowsServer2008/2012/2016

OptionalAccessories(SoldSeparately)Product Model/partno.

ModelSDmemorycard(1GB) 773001

Stylus pen (touch pen) B8740BZ

ShuntresisterforM3terminal(250Ω±0.1%) 415940

ShuntresisterforM3terminal(100Ω±0.1%) 415941

ShuntresisterforM3terminal(10Ω±0.1%) 415942

ShuntresisterforClampterminal(250Ω±0.1%) 438920

ShuntresisterforClampterminal(100Ω±0.1%) 438921

ShuntresisterforClampterminal(10Ω±0.1%) 438922

Dummycover B8740CZ

ValidationDocuments(For/ASoption)*1 773230

*1 ProvisionofValidationDocuments A license sheet containing the license key

requiredforinstallationisprovided. Downloadthevalidationdocumentfromthe

followingURL. http://www.smartdacplus.com/software/en/

Page 25: General GP10/GP20 6SHFL¿FDWLRQV (Portable type) · General 6SHFL¿FDWLRQV GP10/GP20 Paperless Recorder (Portable type) Yokogawa Electric Corporation 2-9-32, Nakacho, Musashino-shi,

25

All Rights Reserved. Copyright © 2012, Yokogawa Electric Corporation GS 04L52B01-01EN Jul. 9, 2018-00

Calibrationcertificate(soldseparately)WhenorderingtheGP10/GP20withoptions(analoginput),thecalibrationcertificateforthemodulesisincludedinandshippedwiththecalibrationcertificateofthemainunit.Whenorderingananaloginputmoduleseparately,eachmodulegetsitsowncalibrationcertificate(onecertificatepermodule).

Testcertificate(QIC,soldseparately)WhenorderingtheGP10/GP20withoptions(analog/digialI/O),theQICforeachmoduleisincludedinandshippedwiththeQICofthemainunit.WhenorderinganaloginputmodulesanddigitalI/Omodulesseparately,eachmodulegetsitsownQIC(oneQICpermodule).

User'sManualProductuser'smanualscanbedownloadedorviewedatthefollowingURL.Toviewtheuser'smanual,youneedtouseAdobeReader7orlaterbyAdobeSystems.URL:www.smartdacplus.com/manual/en/

ProductPurchaseSpecificationsTheGP10/GP20iscomposedofthemainunit,I/Omodules,ExpandableI/O,andExpansionmodule.TherearetwowaystopurchaseI/Omodules.OnewayistopurchasethemindividuallybyspecifyingmodelsGX90XA,GX90XD,GX90YD,GX90WDandGX90XP,GX90YA,GX90UT.Theotherwayistopurchasethemasanoption(/UCxxor/USxx).Purchasingthemasanoptionisconvenient,butthisplaceslimitationsonthenumberofanaloginputsthatyoucanobtain.Ifyouwanttousemorethan50channels,pleasepurchasetheI/Omodulesindividually.ToconnectexpandableI/O(GX60),GMsubunittoGP10orGP20,youmustpurchaseoneunitofexpansionmodule(GX90EX)forGP10/GP20inadditiontotheexpandableI/O,GMsubunit.

Trademarks TheTCP/IPsoftwareusedinthisproductandthedocumentforthatTCP/IPsoftwarearebasedinpartonBSDnetworkingsoftware,Release1licensedfromTheRegentsoftheUniversityofCalifornia.

•SMARTDAC+andSMARTDACPLUSaretrademarksofYokogawaElectricCorporation.•Microsoft,MSandWindowsareregisteredtrademarksofMicrosoftCorporationUSA.•PentiumareregisteredtrademarksofIntelCorporation.•ModbusisaregisteredtrademarkofAEGSchneider.•KerberosisatrademarkofMIT.•JavaandJava-relatedtrademarksaretrademarksorregisteredtrademarksofSunMicrosystems,Inc.intheUnited

States and/or other countries.•Othercompanyand/orproductnamesareregisteredtrademarkoftheirmanufactures.

Page 26: General GP10/GP20 6SHFL¿FDWLRQV (Portable type) · General 6SHFL¿FDWLRQV GP10/GP20 Paperless Recorder (Portable type) Yokogawa Electric Corporation 2-9-32, Nakacho, Musashino-shi,

26

All Rights Reserved. Copyright © 2012, Yokogawa Electric Corporation GS 04L52B01-01EN Jul. 9, 2018-00

MODEL SELECTION GUIDESelectionofthesystemconfigurationandGP10,GP20type

Model-Type Internalmemory Numberofinput/outputchannelsMainunitonly Main+expandableI/O

GP10 500 MB 48 ch (30 ch) 100 ch

GP20-1 500 MB 100 ch 100 ch

GP20-2 1.2 GB 100 ch 500 ch (450 ch)* Thevaluesinsideparenthesesareforwhenonlyanaloginputchannelsareavailable.

I/OModulesModel Suffixcode Productname Description Numberof

channelsMeasurement

interval(shortest)

GX90XA -10-C1N-□N AnalogInputModule

DCcurrent(mA),DCcurrentstandardsignal(4-20mA)

10 100ms

-10-L1N-□N DCvoltage,standardsignal,thermocouple(TC),DI(voltage,contact),andDCcurrent(byaddinganexternalshuntresistor)

500ms

-10-U2N-□N DCvoltage,standardsignal,thermocouple(TC),resistancetemperaturedetector(RTD),DI(voltage,contact),andDCcurrent(byaddinganexternalshuntresistor)

100ms

-10-T1N-□N DCvoltage,standardsignal,thermocouple(TC),DI(voltage,contact),andDCcurrent(byaddinganexternalshuntresistor)

1 s

-10-V1N-□N DCvoltage,standardsignal,thermocouple(TC),DI(voltage,contact),andDCcurrent(byaddinganexternalshuntresistor)

100ms

-04-H0N-□N DCvoltage,standardsignal,thermocouple,resistancetemperaturedetector(RTD),DI(voltage,contact),DCcurrent(whenanexternalshuntresistorisconnected)

4 1ms

-06-R1N-□N 4-wireRTD,4-wireresistance 6 100ms

GX90XD -16-11N-□N DigitalInputModule Remotecontrolinput,pulseinput 16 100ms

GX90XP -10-11N-□N PulseInputModule Pulseinput(flowsumandthelike) 10 100ms

GX90YD -06-11N-3N DigitalOutputModule

Alarmoutput,etc 6 100ms(updateinterval)

GX90WD -0806-01N-3N DigitalInput/OutputModule

Remotecontrolinput,pulseinput DI:8DO:6

100ms

GX90YA -04-C1N-□N Analog Output Module

Transmissionoutput,manualoutput 4 100ms(updateinterval)

GX90UT -02-11N-3N PIDControlModule Controloftemperature,flow,pressureetc. 2 loops 100ms(updateinterval)

Page 27: General GP10/GP20 6SHFL¿FDWLRQV (Portable type) · General 6SHFL¿FDWLRQV GP10/GP20 Paperless Recorder (Portable type) Yokogawa Electric Corporation 2-9-32, Nakacho, Musashino-shi,

27

All Rights Reserved. Copyright © 2012, Yokogawa Electric Corporation GS 04L52B01-01EN Jul. 9, 2018-00

GP10SystemConfiguration(upto100channels)

GX90[ ][ ]I/O Module

GX90EXExpandable I/O

GX90[ ][ ]I/O Module

GX90EXExpandable I/O

GP10 Configuration example (maximum) GX60 Configuration example (maximum)

•GP10:1 •GX60:2

•GX90[][]:2 •GX90[][]:8

•GX90EX:1 •GX90EX:2(AlreadyinstalledintheGX60)

GP10(Unit0)

SLOT 2 SLOT 1 SLOT 0

GX90EX GX90[][] GX90[][]

ExpandableI/O)GX60(Unit1)

SLOT 5 SLOT 4 SLOT 3 SLOT 2 SLOT 1 SLOT 0 EXT

GX90[][] GX90[][] GX90[][] GX90[][] GX90[][] GX90[][] GX90EX

ExpandableI/O)GX60(Unit2)

SLOT 5 SLOT 4 SLOT 3 SLOT 2 SLOT 1 SLOT 0 EXT

--- --- --- --- GX90[][] GX90[][] GX90EX

Page 28: General GP10/GP20 6SHFL¿FDWLRQV (Portable type) · General 6SHFL¿FDWLRQV GP10/GP20 Paperless Recorder (Portable type) Yokogawa Electric Corporation 2-9-32, Nakacho, Musashino-shi,

28

All Rights Reserved. Copyright © 2012, Yokogawa Electric Corporation GS 04L52B01-01EN Jul. 9, 2018-00

GP20SystemConfiguration(upto450channels)

GX90[ ][ ]I/O Module

GX90EXExpandable I/O

GX90[ ][ ]I/O Module

GX90EXExpandable I/O

GP20 Configuration example (maximum) GX60 Configuration example (maximum)

•GP20:1 •GX60:6

•GX90[][]:9 •GX90[][]:36

•GX90EX:1 •GX90EX:6(AlreadyinstalledintheGX60)

GP20(Unit0)

SLOT 9 SLOT 8 SLOT 7 SLOT6 SLOT 5

GX90EX GX90[][] GX90[][] GX90[][] GX90[][]

SLOT 4 SLOT 3 SLOT 2 SLOT 1 SLOT 0

GX90[][] GX90[][] GX90[][] GX90[][] GX90[][]

ExpandableI/O)GX60(Unit1)

SLOT 5 SLOT 4 SLOT 3 SLOT 2 SLOT 1 SLOT 0 EXT

GX90[][] GX90[][] GX90[][] GX90[][] GX90[][] GX90[][] GX90EX

ExpandableI/O)GX60(Unit2)

SLOT 5 SLOT 4 SLOT 3 SLOT 2 SLOT 1 SLOT 0 EXT

GX90[][] GX90[][] GX90[][] GX90[][] GX90[][] GX90[][] GX90EX

ExpandableI/O)GX60(Unit3)

SLOT 5 SLOT 4 SLOT 3 SLOT 2 SLOT 1 SLOT 0 EXT

GX90[][] GX90[][] GX90[][] GX90[][] GX90[][] GX90[][] GX90EX

ExpandableI/O)GX60(Unit4)

SLOT 5 SLOT 4 SLOT 3 SLOT 2 SLOT 1 SLOT 0 EXT

GX90[][] GX90[][] GX90[][] GX90[][] GX90[][] GX90[][] GX90EX

ExpandableI/O)GX60(Unit5)

SLOT 5 SLOT 4 SLOT 3 SLOT 2 SLOT 1 SLOT 0 EXT

GX90[][] GX90[][] GX90[][] GX90[][] GX90[][] GX90[][] GX90EX

ExpandableI/O)GX60(Unit6)

SLOT 5 SLOT 4 SLOT 3 SLOT 2 SLOT 1 SLOT 0 EXT

GX90[][] GX90[][] GX90[][] GX90[][] GX90[][] GX90[][] GX90EX