general fa-m3 specifications fa-m3 value, value ii · function to communicate with a higher-level...

20
<<Contents>> <<Index>> General Specifications FA-M3 FA-M3 Value, Value II (including base, power supply, sequence CPU and DI/O modules) CONTENTS F3SC21-1N FA-M3 Value ...................................................... 3 F3SC22- , F3SC23- FA-M3 Value II ................................................... 9 GS 34M06C81-01E ©Copyright Oct. 2010 7th Edition: Oct. 2010 Yokogawa Electric Corporation

Upload: others

Post on 12-Mar-2020

5 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: General FA-M3 Specifications FA-M3 Value, Value II · function to communicate with a higher-level computer or display. ... Configuration function (device capacity, data lock-up range

<<Contents>> <<Index>>

General Specifications

FA-M3 FA-M3 Value, Value II (including base, power supply, sequence CPU and DI/O modules)

CONTENTS

F3SC21-1N FA-M3 Value ...................................................... 3

F3SC22- , F3SC23- FA-M3 Value II ................................................... 9

GS 34M06C81-01E©Copyright Oct. 20107th Edition: Oct. 2010Yokogawa Electric Corporation

Page 2: General FA-M3 Specifications FA-M3 Value, Value II · function to communicate with a higher-level computer or display. ... Configuration function (device capacity, data lock-up range

Blank Page

Page 3: General FA-M3 Specifications FA-M3 Value, Value II · function to communicate with a higher-level computer or display. ... Configuration function (device capacity, data lock-up range

<<Content>> <<Index>> 3

General Specifications

F3SC21-1N FA-M3 Value (including base, power supply, sequence CPU and DI/O modules)

General The F3SC21-1N (FA-M3 Value) is a compact programmable controller consisting of the following modules: F3BU04-0N base module (with 4 slots) F3SP05-0P sequence CPU module (with power supply and

memory) F3WD64-3N I/O module (with 32 inputs and 32 outputs) The F3SP05-0P double-slot sequence CPU module is installed in the leftmost slot of the F3BU04-0N 4-slot base module and the F3WD64-3N I/O module in slot 2. You can install any FA-M3 I/O modules in slots 3 and 4.

Features Its compact size greatly reduces installation space. The sequence CPU module has a 100-240 VAC universal power

supply so that the user doesn't have to worry about the power supply environment when using the F3SC21-1N.

The high-speed instruction processing capability of the F3SC21-1N makes it ideal for applications that require high speed response.

The use of a structured ladder programming language facilitates programming and maintenance of ladder programs.

The sequence CPU module has the personal computer link function to communicate with a higher-level computer or display. The user needs no personal computer link module (F3LC11-1N) for this purpose.

Programs and data can be saved on an optional ROM pack.

DC I/OWD64-3N

1234

5678

9101112

13141516

17181920

21222324

25262728

29303132

DISPLAY

CN3

1 2

CPU

RDYRUN

PROGRAMMER

SP05-0P

RDY

CN4

ASSY

S92

6 B

K-0

All Rights Reserved. Copyright © 2010, Yokogawa Electric Corporation GS 34M06C81-01E Oct. 2010-00

Page 4: General FA-M3 Specifications FA-M3 Value, Value II · function to communicate with a higher-level computer or display. ... Configuration function (device capacity, data lock-up range

<< Content >> <<Index>> 4

All Rights Reserved. Copyright © 2010, Yokogawa Electric Corporation GS 34M06C81-01E Oct. 2010-00

Specifications

Item Specification

Number of slots 4

Number of free I/O slots 2 (as the sequence CPU and 64-point I/O modules occupy two slots) Base module (F3BU04-0N)

Weight 140 g

Supply voltage 100-240 V AC, single phase, 50/60 Hz

Supply voltage fluctuation range 85-264 V AC, 50/60 Hz ±3 Hz

Power consumption 35 VA

Inrush current 20 A max. (120 V AC, Ta=25 ºC) 45 A max. (240 V AC, Ta=25 ºC)

Rated output voltage 5 V DC

Rated output current 2.0 A

Insulation resistance 5 MΩ or greater at 500 V DC (between external AC terminals and FG terminal)

Dielectric strength 1500 V AC for 1 minute (between external AC terminals and FG terminal)

FAIL-signal contact output Provided on the front terminal block on the power supply block; contact rating: 24 V DC, 0.3 A (both normally-open and normally-closed terminals available)

Allowable common-mode voltage of FAIL-signal contact

120 V max. AC or DC (between FAIL OUTPUT COM terminal and FG terminal)

Leakage current 0.5 mA max. Allowable momentary power failure time 20 ms

Pow

er s

uppl

y bl

ock

Noise immunity Immune to noise of up to 1500 Vp-p with 1-s pulse width and 1-ns rise time at 25-60 Hz (as measured with a noise simulator).

Control mode Stored program, cyclic execution

I/O control mode Refreshing method/direct I/O instructions

Programming language Structured ladder language, mnemonic language

Basic instructions 25 types Number of instructions Application

instructions 227 types

Basic instructions 0.18-0.36 μs/instruction Instruction processing speed

Application instructions 0.36 μs min./instruction

Program size 5K steps (can be stored in ROM)

Number of I/O points 2048 points max.

Number of program blocks 32 max.

Sampling trace No

Link to personal computer Yes

Monitoring of scan time 10-200 ms variable

Internal relay I: 4096 points max.

Shared relay —

Extended shared relay —

Link relay L: 2048 points

Special relay M: 2048 points

Timer T: 512 points max. (total of internal and external timers and counters)

Counter C: 512 points max. (total of internal and external timers and counters)

Data register D: 5120 points max.

File register —

Link register W: 2048 points

Special register Z: 512 points

Index register V: 32 points

Shared register —

Dev

ices

Extended shared register —

Sequence CPU module*1 (F3SP05-0P)

Sequ

ence

CPU

blo

ck

Self-diagnostics Memory error, CPU error, input/output error, syntax check, etc.

Page 5: General FA-M3 Specifications FA-M3 Value, Value II · function to communicate with a higher-level computer or display. ... Configuration function (device capacity, data lock-up range

<< Content >> <<Index>> 5

All Rights Reserved. Copyright © 2010, Yokogawa Electric Corporation GS 34M06C81-01E Oct. 2010-00

Item Specification

Other features

Configuration function (device capacity, data lock-up range at power failure, output when CPU stops, etc.) Constant scan function (1 ms to 190 ms) Debugging functions (forced SET/RESET, online edit, scan operation, etc.) Error history function (64 records) Date/clock function (year/month/day/hour/minute/second/day of week) Program protection functions ROM programming and data storage Personal computer link function

Sequ

ence

C

PU b

lock

Current consumption 350 mA (5 V DC)*2

External dimensions 58 (W) X 100 (H) X 83.2 (D) mm

Weight 320 g

UL UL508 approved, File No.E188707 (Overvoltage Category*4 II, Pollution Degree*5 2)

CE EMC Directive

EN 61326-1 Class A, Table 2 (For use in industrial locations) EN 61326-2-3*6 EN 55011 Class A, Group 1 EN 61000-6-2, EN 61000-3-2, EN 61000-3-3 compliance

Sequence CPU module*1 (F3SP05-0P)

Com

mon

Compliance with safety and EMC standards*3

C-Tick EMC Framework EN 55011 Class A, Group 1 compliance

Input type DC voltage

Number of points 32

Number of points/common 8 points/common

Isolation method Photocoupler isolation

Rated input voltage 24 V DC

Operating voltage 20.4-26.4 V DC

Rated input current 4.1 mA/point (24 V DC)

ON 6.0 V DC min., 3.2 mA min. Operating voltage/current OFF 5.8 V DC max., 0.9 mA max.

OFF→ON 1.0 ms max. Input

ON→OFF 2.5 ms max.

Inpu

t Blo

ck

Interrupt No

Output type Transistor contact (sink type)

Number of points 32

Number of points/common 8 points/common

Isolation method Photocoupler isolation

Rated load voltage 24 V DC

Maximum load current 0.1 A/point, 0.4 A/common

OFF→ON 1.0 ms max. Output Response ON→OFF 1.0 ms max.

Off-time leakage current 0.1 mA max.

Surge protector Zener diode

Out

put B

lock

External power supply 24 V DC, 60 mA

Input/output status indicator Lit when on (indicates either input or output status by using the selector switch)

Current consumption 200 mA (5 V DC)

External connection Two 40-pin connectors

Input/Output module (F3WD64-3N)

Com

mon

Weight 160 g

*1: When a sequence CPU module is to be used, use the Ladder Diagram Support Program M3, Rev. 2.02 or later. *2: The total current dissipated by the modules in slots 3 and 4 must be less than 1400 mA. *3: For details on conforming modules, see “UL-approved, CE marking and C-Tick mark-compliant Modules” (GS 34M06C11-21E) general specification

brochure. *4: The term Overvoltage Category involves prescriptions on resistance to surge voltage reduction due to lightning and has four categories.

Overvoltage Category II applies to systems with rated voltage of 220/230/240V and applies to electrical appliances, portable devices, etc. *5: The term Pollution Degree represents the degree of pollution with foreign matter, solid, liquid or gaseous, that may produce a reduction of dielectric

strength or surface resistivity in the operating environment of the equipment. Pollution degree 2 refers to an environment where normally only non-conductive pollution occurs but occasionally temporary conductivity caused by condensation is to be expected.

*6: EN 61326-2-3 is applicable only to F3CU04-0S and F3CU04-1S

Page 6: General FA-M3 Specifications FA-M3 Value, Value II · function to communicate with a higher-level computer or display. ... Configuration function (device capacity, data lock-up range

<< Content >> <<Index>> 6

All Rights Reserved. Copyright © 2010, Yokogawa Electric Corporation GS 34M06C81-01E Oct. 2010-00

Base Module

Model and Suffix Codes

Model Suffix Code

Style Code

Option Code Description

F3BU04 -0N · · · · · · · · · · · · 4 slots (excluding slot for power supply)

External Dimensions

4 slots (F3BU04-0N)

O5 mounting hole

9.6

4.5 7.5

85 100

10.588.5

138147

(When mounted on module surface)

(for M4 mounting screw)

Unit: mm

Page 7: General FA-M3 Specifications FA-M3 Value, Value II · function to communicate with a higher-level computer or display. ... Configuration function (device capacity, data lock-up range

<< Content >> <<Index>> 7

All Rights Reserved. Copyright © 2010, Yokogawa Electric Corporation GS 34M06C81-01E Oct. 2010-00

Sequence CPU Module

Components and Functions

FAIL1

COM

FAIL2

N

L

FAIL OUTPUT

SP05-0P

RDY

CPU

Between FAIL1 and COM

Between FAIL2 and COM

Open

Short

Short

Open

During Normal operation

During System and Power Failures

Fail-signal contact outputContact ratings: 24 V DC, 0.3 A

Subject to grounding resistance of 100Ω max independently (JIS class D grounding, previously class 3 grounding)

Connect to FG and grounded

100-240 VAC

Lit when power supply is normal

FG

LG

FG (Frame Ground)

LG (Line filter Ground)

Power supply

RDY LED (green)

FB020301.VSD

INPUT 100-240VAC

RDYRUNALMERR

CPU modulemaintenace LEDs

PROGRAMMER

Programming tool interface connector

Terminal Dimensions

Unit: mm

8.2 mm7.1 mm

M3.5

Examples of Applicable Solderless Terminals

Vender Model Applicable Conductor

Applicable Crimping Torque

Japan Solderless Terminal Mfg. Co., Ltd. V1.25-M3

Nippon Tanshi Co., Ltd. RAV1.25-3.5

AWG22 to 18 (0.33 to 0.82 mm2) (Copper wire)

Japan Solderless Terminal Mfg. Co., Ltd. V1.25-M4

Japan Solderless Terminal Mfg. Co., Ltd. V2-M4

AWG16 to 14 (1.25 to 2.0 mm2) (Copper wire)

0.8 N • m

CPU Error Processing Different levels of errors are identified by different LEDs on the front panel of the CPU module.

LED Meaning

RDY (READY) Green Major failure (when off): The core hardware cannot run. Example: CPU error

Memory error RUN (RUN) Green When lit: The user program is running.

ALM (ALARM) Yellow

Minor failure (when lit): The user program can still run in spite of a failure. Example: Power failure

Communication error

ERR (ERROR) Red

Moderate failure (when lit): The user program cannot start or continue execution. Example: Program error*

I/O comparison error* I/O module error* Memory error Sequence processor error Instruction processing error* Scan timeout*

*: Minor or moderate failure can be defined in the configuration settings.

Model and Suffix Codes

Model Suffix Code

Style Code

Option Code Description

F3SC21 -1N · · · · · · · · · · · · FA-M3 Value (with base, power supply, sequence CPU, and DI/O modules)

F3SP05 -0P · · · · · · · · · · · · Sequence CPU module (with power supply and memory) Memory: 5K steps

External Dimensions

Page 8: General FA-M3 Specifications FA-M3 Value, Value II · function to communicate with a higher-level computer or display. ... Configuration function (device capacity, data lock-up range

<< Content >> <<Index>> 8

All Rights Reserved. Copyright © 2010, Yokogawa Electric Corporation GS 34M06C81-01E Oct. 2010-00

I/O Module (F3WD64-3N)

Internal Circuit Diagram

8

10

9

_

+

+

_

+89

Bus interface

Display selector OUT

IN

1

COM

L

L

COM

~

1

~

Inte

rnal

bus

External Connection Diagram

+

24V

COM46463626160595857

COM24847464544434241

+

COM35655545352515049

COM14039383736353433

2019181716151413121110987654321

2019181716151413121110987654321

B A

LLLLLLLL

24V

LLLLLLLL

+

+

24V

LLLLLLLL

LLLLLLLL

24V

CN2 (Output block)

COM43231302928272625

COM216151413121110 9

–+

+–

+–

–+

COM32423222120191817

COM1 8 7 6 5 4 3 2 1

–+

+–

+–

–+

2019181716151413121110987654321

2019181716151413121110987654321

B ACN1 (Input block)

Note: Viewed from the front of the module.

External Connections Connector Type

Wire connection method Soldered

Applicable wire size AWG23 max. (0.26 mm2 max.)

Applicable External Connectors Connection Method Applicable Connector

Soldered type Fujitsu FCN-361J040-AU connector FCN-360C040-B connector cover

Solderless type Fujitsu FCN-363J040 housing

FCN-363J-AU contact FCN-360C040-B connector cover

Solderless type Fujitsu FCN-367J040-AU / F

Operating Environment There is no restriction on the type of CPU modules that can be used with this module.

Model and Suffix Codes

Model Suffix Code

Style Code

Option Code Description

F3WD64 -3N · · · · · · · · · · · · 24 V DC input/output

Note: See the spare parts in the FA-M3 Range-free Multi-controller (GS 34M6A01-01E) for information on connectors.

External Dimensions F3WD64-3N

Unit: mm

Page 9: General FA-M3 Specifications FA-M3 Value, Value II · function to communicate with a higher-level computer or display. ... Configuration function (device capacity, data lock-up range

<<Content>> <<Index>> 9

All Rights Reserved. Copyright © 2010, Yokogawa Electric Corporation GS 34M06C81-01E Oct. 2010-00

General The F3SC22- or the F3SC23- (FA-M3 Value II) is a compact programmable controller consisting of the following modules: F3SC22-1F F3BU04-0N (4-slot base module) F3SP08-0P (sequence CPU module) F3WD32-3F (32-point I/O module) F3SC22-2F F3BU04-0N (4-slot base module) F3SP08-0P (sequence CPU module) F3WD64-3F (64-point I/O module) F3SC22-1A F3BU04-0N (4-slot base module) F3SP08-0P (sequence CPU module) F3XD16-3F (16-point input module) F3YD14-5A (14-point output module) F3SC23-1F F3BU04-0N (4-slot base module) F3SP08-SP (sequence CPU module) F3WD32-3F (32-point I/O module) F3SC23-2F F3BU04-0N (4-slot base module) F3SP08-SP (sequence CPU module) F3WD64-3F (64-point I/O module) F3SC23-1A F3BU04-0N (4-slot base module) F3SP08-SP (sequence CPU module) F3XD16-3F (16-point input module) F3YD14-5A (14-point output module) F3SC23-2P F3BU04-0N (4-slot base module) F3SP08-SP (sequence CPU module) F3WD64-3P (64-point I/O module) F3SC23-6P F3BU04-0N (4-slot base module) F3SP08-SP (Sequence CPU module) F3WD64-4P (64-point I/O module, 12 V) Install the F3SP08-P sequence CPU module in the leftmost slot of the F3BU04-0N base module and the other I/O module(s) in slot 2 (or slots 2 and 3). The remaining slot(s) is available for a variety of FA-M3 I/O modules.

DC I/OWD32-3F

1234

5678

9101112

13141516

17181920

21222324

25262728

29303132

CN3

CPU

RDYRUN

PROGRAMMER

SP08-0P

RDY

CN4

ASSY

S92

6 B

K-0

Features Its compact size greatly reduces installation space. The sequence CPU module has a 100-240 VAC universal power

supply so that the user doesn't have to worry about the power supply environment.

The high-speed instruction processing capability makes it ideal for applications that require high speed response.

The use of a structured ladder programming language facilitates programming and maintenance of ladder programs.

The sequence CPU module has the personal computer link function to communicate with a higher-level computer or display. The user needs no personal computer link module (F3LC11-1N) for this purpose.

Programs and data can be saved on an optional ROM pack.

General Specifications

F3SC22-, F3SC23- FA-M3 Value II (including base, power supply, sequence CPU and DI/O modules)

Page 10: General FA-M3 Specifications FA-M3 Value, Value II · function to communicate with a higher-level computer or display. ... Configuration function (device capacity, data lock-up range

<<Content>> <<Index>> 10

All Rights Reserved. Copyright © 2010, Yokogawa Electric Corporation GS 34M06C81-01E Oct. 2010-00

Specifications

Common Specifications for F3SC22 and F3SC23 Item Specification

Number of slots 4 2 (for F3SC22-1F, F3SC22-2F, F3SC23-1F, F3SC23-2F, F3SC23-2P, and F3SC23-6P) Number of free I/O slots 1 (for F3SC22-1A and F3SC23-1A)

Base module (F3BU04-0N)

Weight 140 g Supply voltage 100-240 V AC, single phase, 50/60 Hz Supply voltage fluctuation range 85-264 V AC 50/60 Hz 3 Hz

Power consumption 35 VA

Inrush current 20 A max. (120 V AC, Ta=25 C) 45 A max. (240 V AC, Ta=25 C)

Rated output voltage 5 V DC Rated output current 2.0 A Insulation resistance 5 M or greater at 500 V DC (between external AC terminals and FG terminal) Dielectric strength 1500 V AC for 1 minute (between external AC terminals and FG terminal)

FAIL-signal contact output Provided on the front terminal block on the power supply block; contact rating: 24 V DC, 0.3 A (both normally-open and normally-closed terminals available)

Allowable common-mode voltage of FAIL-signal contact

120 V max. AC or DC (between FAIL OUTPUT COM terminal and FG terminal)

Leakage current 0.5 mA max. Allowable momentary power failure time 20 ms

Pow

er S

uppl

y B

lock

Noise immunity Immune to noise of up to 1500 Vp-p with 1-s pulse width and 1-ns rise time at 25-60 Hz (as measured with a noise simulator).

Control mode Stored program, cyclic execution I/O control mode Refreshing method/direct I/O instructions Programming language Structured ladder language, mnemonic language

Basic instructions 25 types Number of

instructions Application instructions 227 types

Basic instructions 0.18-0.36 s/instruction Instruction

Processing speed Application

instructions 0.36 s min./instruction

Program size 10K steps (can be stored in ROM) Number of I/O points 2048 points max. Number of program blocks 32 max. Sampling trace No Link to personal computer Yes Monitoring of scan time 10-200 ms variable

Internal relay I: 4096 points max. Shared relay — Extended shared relay —

Link relay L: 2048 points Special relay M: 2048 points Timer T: 512 points max. (total of internal and external timers and counters) Counter C: 512 points max. (total of internal and external timers and counters) Data register D: 5120 points max. File register — Link register W: 2048 points Special register Z: 512 points Index register V: 32 points Shared register —

Dev

ice

Extended shared register —

Sequence CPU module*1 (F3SP08-0P, F3SP08-SP)*3

Sequ

ence

CPU

Blo

ck

Self-diagnostics Memory error, CPU error, input/output error, syntax check, etc.

Page 11: General FA-M3 Specifications FA-M3 Value, Value II · function to communicate with a higher-level computer or display. ... Configuration function (device capacity, data lock-up range

<<Content>> <<Index>> 11

All Rights Reserved. Copyright © 2010, Yokogawa Electric Corporation GS 34M06C81-01E Oct. 2010-00

Item Specification

Other features

Configuration function (device capacity, data lock-up range at power failure, output when CPU stops, etc.) Constant scan function (1 ms to 190 ms) Debugging functions (forced SET/RESET, online edit, scan operation, etc.) Error history function (64 records) Date/clock function (year/month/day/hour/minute/second/day of week) Program protect functions ROM programming and data storage Personal computer link function

Sequ

ence

CPU

Blo

ck

Current consumption 350 mA (5 V DC)*2 External dimensions 58 (W) 100 (H) 83.2 (D) mm Weight 320 g

UL UL508 approved, File No.E188707 (Overvoltage Category*5 II, Pollution Degree*6 2)

EMC Directive

EN 61326-1 Class A, Table 2 (For use in industrial locations) EN 61326-2-3*7 EN 55011 Class A, Group 1 EN 61000-6-2, EN 61000-3-2, EN 61000-3-3 compliance CE

Low Voltage Directive

EN 61010-1 compliance (only for F3SC23-) (Overvoltage Category*5 II, Pollution Degree*6 2)

Sequence CPU module*1 (F3SP08-0P, F3SP08-SP)*3

Com

mon

Compli- ance with safety and EMC stan- dards*4

C-Tick EMC Frame-work EN 55011 Class A, Group 1 compliance

*1: When a sequence CPU module is to be used, use the FA-M3 programming Tool WideField Rev. 2.06 or later. *2: The total current dissipated by the modules in slots 2 to 4 must be less than 1600 mA. *3: F3SP08-0P and F3SP08-SP have exactly the same dimensions, internal circuitry and other characteristics, except that F3SP08-0P uses

M3.5-screw terminals while F3SP08-SP uses M4-screw terminals. F3SP08-SP is compliant to IEC61010-1 and EN61010-1, but F3SP08-0P is not.

*4 For details on conforming modules, see “UL-approved, CE marking and C-Tick mark-compliant Modules” (GS 34M06C11-21E) general specification brochure.

*5: The term Overvoltage Category involves prescriptions on resistance to surge voltage reduction due to lightning and has four categories. Overvoltage Category II applies to systems with rated voltage of 220/230/240V and applies to electrical appliances, portable devices, etc.

*6: The term Pollution Degree represents the degree of pollution with foreign matter, solid, liquid or gaseous, that may produce a reduction of dielectric strength or surface resistivity in the operating environment of the equipment. Pollution degree 2 refers to an environment where normally only non-conductive pollution occurs but occasionally temporary conductivity caused by condensation is to be expected.

*7: EN 61326-2-3 is applicable only to F3CU04-0S and F3CU04-1S

F3SC22-1F, F3SC23-1F Operating Voltage/

Current Input Response Time Model Input Type Number of Points

Isolation Method

Rated Input Voltage

Rated Input Current

ON OFF OFF→ON ON→OFF

External Connection

Number of Points/

Common

DC Voltage 16 24V DC 4.1mA/point 16V DC min. 3.2mA min.

5.8V DC max.

0.9mA max.

Configu -rable as

2.0ms max. or 17ms

Configu -rable as

3.5ms max. or 18.5ms

40-pin connector

8 points/ common

Output Response Time Output Type

Number of Points

Rated Load Voltage

Maximum Load Current

OFF→ON OFF→ON Surge

Protector External Power Supply

External Connection

Number of Points/

Common

HOLD/REST Output When

Program Stops

F3WD32-3F

Transistor contact

(sink type) 16

Photocoupler isolation

24V DC 0.1A/point 0.8A/common 1ms max. 1ms max. Zener

diode 24V DC 30mA

40-pin connector

8 points/ common

Default: RESET Configurable on module basis.*

* For CPU error, see “Severity of Failures and LED Display” of FA-M3 Range-free Multi-controller (GS34M6A01-01E).

F3SC22-2F, F3SC23-2F Operating Voltage/

Current Input Response Time Model Input Type Number of Points

Isolation Method

Rated Input Voltage

Rated Input Current

ON OFF OFF→ON ON→OFF

External Connection

Number of Points/

Common

DC Voltage 32 24V DC 4.1mA/point 16V DC min. 3.2mA min.

5.8V DC max.

0.9mA max. 1.0ms max. 2.5ms max. 40-pin

connector 8 points/ common

Output Response Time Output Type Number of Points

Rated Load Voltage

Maximum Load Current

OFF→ON OFF→ON

Surge Protector

External Power Supply

External Connection

Number of Points/

Common

HOLD/REST Output When

Program Stops F3WD64-3F

Transistor contact

(sink type) 32

Photocoupler isolation

24V DC 0.1A/point 0.4A/common 1ms max 1ms max Zener

diode 24V DC 60mA

40-pin connector

8 points/ common

Default: RESET Configurable on module basis.*

* For CPU error, see “Severity of Failures and LED Display” of FA-M3 Range-free Multi-controller (GS34M6A01-01E).

Page 12: General FA-M3 Specifications FA-M3 Value, Value II · function to communicate with a higher-level computer or display. ... Configuration function (device capacity, data lock-up range

<<Content>> <<Index>> 12

All Rights Reserved. Copyright © 2010, Yokogawa Electric Corporation GS 34M06C81-01E Oct. 2010-00

F3SC22-1A, F3SC23-1A Operating Voltage/

Current Input Response Time Model Input Type Number of Points

Isolation Method

Rated Input Voltage

Rated Input Current

ON OFF OFF→ON ON→OFF External

Connection Number of Points/ Common

F3XD16-3F DC Voltage (sink/source

type) 16 Photocoupler

isolation 24V DC 4.1mA/ point 24V DC

16V DC min. 3.2mA min.

5.8V DC max.

0.9mA max.

Configu -rable as

2.0ms max. or 17ms

Configu -rable as

3.5ms max. or 18.5ms

18-point terminal

block M3.5 screw

8 points/ Common

Output Response Time Model Output Type

Number of Points

Isolation Method

Rated Input Voltage

Maximum Load

Current OFF→ON ON→OFF

Surge Protector

External Power Supply

External Connection

Number of Points/

Common

HOLD/REST Output When

Program Stops)

F3YD14-5A Transistor Contact

(sink type) 14 Photocoupler

isolation 12-24V DC 0.5A/point 2A/common 1ms max. 1ms max. Zener

diode

18-point terminal

block M3.5 screw

12-24V DC 20mA

8 points/ common 6 points/ common

Default: RESET Configurable on module basis.*

* For CPU error, see “Severity of Failures and LED Display” of FA-M3 Range-free Multi-controller (GS34M6A01-01E).

F3SC23-2P, F3SC23-6P Operating Voltage/

Current Input Response Time Model Input Type Number of Points

Isolation Method

Rated Input Voltage

Rated Input Current ON OFF OFF→ON ON→OFF

External Connection

Number of Points/

Common

DC Voltage 32 24 V DC 4.1mA/point 16VDC min.

3.2mA min. 5.8VDC max.,

0.9mA max. 1.0ms max. 2.5ms max. 40-pin

connector 8 points/ common

Output Response Time Output Type

Number of Points

Rated Load Voltage

Maximum Load Current OFF→ON OFF→ON

Surge Protector

External Power Supply

External Connection

Number of Points/

Common

HOLD/REST Output When

Program Stops) F3WD64-3P

Transistor contact

(sink type) 32

Photocoupler isolation

24 V DC 0.1A/point 0.4A/common 1ms max. 1ms max. Active

clamp 24V DC 55mA

40-pin Connector

8 points/ common

Default: RESET Configurable on module basis.*

Operating Voltage/

Current Input Response Time Model Input Type Number of Points

Isolation Method

Rated Input Voltage

Rated Input Current ON OFF OFF→ON ON→OFF

External Connection

Number of Points/

Common

DC Voltage 32 12 V DC 4.1mA/point 8V DC min.

2.6mA min. 3.4V DC

max., 1.0mA max.

1.0ms max. 2.5ms max. 40-pin connector

8 points/ common

Output Response Time Output Type

Number of Points

Rated Load Voltage

Maximum Load Current OFF→ON OFF→ON

Surge Protector

External Power Supply

External Connection

Number of Points/

Common

HOLD/REST Output When

Program Stops) F3WD64-4P

Transistor contact

(sink type) 32

Photocoupler isolation

12 V DC 0.1A/point 0.4A/common 1ms max. 1ms max. Active

clamp 12V DC 55mA

40-pin Connector

8 points/ common

Default: RESET Configurable on module basis.*

* For CPU error, see “Severity of Failures and LED Display” of FA-M3 Range-free Multi-controller (GS34M6A01-01E).

Base Module Model and Suffix Codes

Model Suffix Code

Style Code

Option Code Description

F3BU04 -0N · · · · · · · · · · · · 4 slots (excluding slots for power supply)

External Dimensions

4 slots (F3BU04-0N)

O5 mounting hole

9.6

4.5 7.5

85 100

10.588.5

138147

(When mounted on module surface)

(for M4 mountingscrew)

Unit: mm

Page 13: General FA-M3 Specifications FA-M3 Value, Value II · function to communicate with a higher-level computer or display. ... Configuration function (device capacity, data lock-up range

<<Content>> <<Index>> 13

All Rights Reserved. Copyright © 2010, Yokogawa Electric Corporation GS 34M06C81-01E Oct. 2010-00

Sequence CPU Module

Components and Functions

Between FAIL1 and COMBetween FAIL2 and COM

OpenShort

ShortOpen

During Normal operation

During System and Power Failures

Fail-signal contact outputContact ratings: 24 V DC, 0.3 A

Subject to JIS class 3 grounding independently.

Subject to JIS class 3 grounding independently for increased noise immunity.

100-240 VAC

Lit when the power supply is normal.

FG

LG

Power supply

CPU module maintenance LEDs

Programming tool interface connector

FAIL1

COM

FAIL2

FG

LG

N

L

FAILOUTPUT

INPUT 100-240 V AC

RDY

SP05-0P CPU

RDYRUNALMERR

PROGRAMMER

Terminal Dimensions F3SP08-0P

8.2 mm7.1 mm

M3.5

Unit: mmF3SP08-SP

8.2 mm7.1 mm

M4

Examples of Applicable Solderless Terminals Applicable

Crimping Torque Vender Model Applicable Conductor

F3SP08-0P F3SP08-SP Japan Solderless Terminal Mfg. Co., Ltd.

V1.25-M3

Nippon Tanshi Co., Ltd. RAV1.25-3.5

Not available

Japan Solderless Terminal Mfg. Co., Ltd.

V1.25-M4

AWG22 to 18 (0.33 to 0.82mm2) (Copper wire)

Japan Solderless Terminal Mfg. Co., Ltd.

V2-M4 AWG16 to 14 (1.25 to 2.0mm2) (Copper wire)

0.8 N • m

1.2 N • m

CPU Error Processing Different levels of errors are identified by different LEDs on the front panel of the CPU module.

LED Meaning

RDY (READY) Green

Major failure (when off): The core hardware cannot run. Example: CPU error Memory error

RUN (RUN) Green When lit: The user program is running.

ALM (ALARM) Yellow

Minor failure (when lit): The user program can still run in spite of a failure. Example: Power failure Communication error

ERR (ERROR) Red

Moderate failure (when lit): The user program cannot start or continue execution. Example: Program error* I/O comparison error* I/O module error* Memory error Sequence processor error Instruction processing error* Scan timeout*

*: Minor or moderate error can be selected in the configuration settings.

Page 14: General FA-M3 Specifications FA-M3 Value, Value II · function to communicate with a higher-level computer or display. ... Configuration function (device capacity, data lock-up range

<<Content>> <<Index>> 14

All Rights Reserved. Copyright © 2010, Yokogawa Electric Corporation GS 34M06C81-01E Oct. 2010-00

Model and Suffix Codes

Model Suffix Code

Style Code

Option Code Description

-1F · · · · · · · · · · · ·

FA-M3 Value II (with base, power supply (M3.5 screws), sequence CPU, and DI/O (F3WD32-3F) modules)

-2F · · · · · · · · · · · ·

FA-M3 Value II (with base, power supply (M3.5 screws), sequence CPU, and DI/O (F3WD64-3F) modules)

F3SC22

-1A · · · · · · · · · · · ·

FA-M3 Value II (with base, power supply (M3.5 screws), sequence CPU, and DI/O (F3XD16-3F, F3YD14-5A) modules)

F3SP08 -0P · · · · · · · · · · · · Sequence CPU Module (with power supply (M3.5 screws) and memory), memory: 10K steps

External Dimensions

83.2 582

100

Unit: mm

Model Suffix Code

Style Code

Option Code Description

-1F · · · · · · · · · · · ·

FA-M3 Value II (with base, power supply (M4 screws), sequence CPU, and DI/O (F3WD32-3F) modules)

-2F · · · · · · · · · · · ·

FA-M3 Value II (with base, power supply (M4 screws), sequence CPU, and DI/O (F3WD64-3F) modules)

-1A · · · · · · · · · · · ·

FA-M3 Value II (with base, power supply (M4 screws), sequence CPU, and DI/O (F3XD16-3F, F3YD14-5A) modules)

-2P · · · · · · · · · · · ·

FA-M3 Value II (with base, power supply (M4 screws), sequence CPU, and DI/O (F3WD64-3P) modules)

F3SC23

-6P · · · · · · · · · · · ·

FA-M3 Value II (with base, power supply (M4 screws), sequence CPU, and DI/O (F3WD64-4P) modules)

F3SP08 SP · · · · · · · · · · · · Sequence CPU Module (with power supply (M4 screws) and memory), memory: 10K steps

Page 15: General FA-M3 Specifications FA-M3 Value, Value II · function to communicate with a higher-level computer or display. ... Configuration function (device capacity, data lock-up range

<<Content>> <<Index>> 15

All Rights Reserved. Copyright © 2010, Yokogawa Electric Corporation GS 34M06C81-01E Oct. 2010-00

I/O Module (F3XD16-3F)

Internal Circuit Diagram F3XD16-3F (DC input module)

Businterface

Inte

rnal

bus

1

8

9

~

COM

+

+

External Connection Diagram

1

3

5

7

9

11

13

15

17

12345678

COM1

2

4

6

8

10

12

14

16

18

+

+

910111213141516

COM2

+

+

F3XD16-3F (DC input module)

Note: Viewed from the front of the module.

External Connections Terminal Block

Applicable conductor 0.33 to 0.82 mm2

Method of connection Solderless

Temperature rating 75°C min.

Material Copper Solderless terminal For 3.5 mm screws

Crimping torque 0.8 N • m

Solderless terminal

Applicable solderless terminal

e.g.: Japan Solderless Terminal Mfg.Co.,Ltd. V1.25-M3 V1.25-M4 V2-M4 Nippon Tanshi Co., Ltd RAV1.25-3.5

Operating Environment There is no restriction on the type of CPU modules that can be used with this module.

Model and Suffix Codes

Model Suffix Code

Style Code

Option Code Description

F3XD16 -3F · · · · · · · · · · · · DC input (sink/source type) 24 V DC, 16 points

External Dimensions

Unit:

F3XD16-3F

mm

Page 16: General FA-M3 Specifications FA-M3 Value, Value II · function to communicate with a higher-level computer or display. ... Configuration function (device capacity, data lock-up range

<<Content>> <<Index>> 16

All Rights Reserved. Copyright © 2010, Yokogawa Electric Corporation GS 34M06C81-01E Oct. 2010-00

I/O Module (F3YD14-5A)

Internal Circuit Diagram

1

8

10

9 COM

F3YD14-5A (Transistor Output Module)

~

L

L+

Businterface

Inte

rnal

bus

External Connection Diagram

F3YD14-5A (Transistor Output Module)

1

3

5

7

9

11

13

15

17

12345678

COM11224V

2

4

6

8

10

12

14

16

18

+

LLLLLLLL

91011121314

COM21224V

+

LLLLLL

Note: Viewed from the front of the module.

External Connections Terminal Block

Applicable conductor 0.33 to 0.82 mm2

Method of connection Solderless

Temperatule rating 75°C min.

Material Copper Solderless terminal For 3.5 mm screws

Crimping torque 0.8 N·m

Solderless terminal

Applicable solderless terminal

ex: Japan Solderless Terminal Mfg.Co.,Ltd. V1.25-M3 V1.25-M4 V2-M4 Nippon Tanshi Co., Ltd RAV1.25-3.5

Operating Environment There is no restriction on the type of CPU modules that can be used with this module.

Model and Suffix Codes

Model Suffix Code

Style Code

Option Code Description

F3YD14 -5A · · · · · · · · · · · · TR output sink type 12-24 V DC, 0.5A, 14 points

External Dimensions

Unit:

F3YD14-5A

mm

Page 17: General FA-M3 Specifications FA-M3 Value, Value II · function to communicate with a higher-level computer or display. ... Configuration function (device capacity, data lock-up range

<<Content>> <<Index>> 17

All Rights Reserved. Copyright © 2010, Yokogawa Electric Corporation GS 34M06C81-01E Oct. 2010-00

I/O Module (F3WD32-3F)

Internal Circuit Diagram

External Connection Diagram

+

LLLLLLLL

24V

+

24V

LLLLLLLL

COM43231302928272625

COM216151413121110 9

COM32423222120191817

COM1 8 7 6 5 4 3 2 1

-

+

+

-

+

-

-

+

2019181716151413121110987654321

2019181716151413121110987654321

B A

Note: Viewed from the front of the module.

External Connections Connector Type

Wire connection method Soldered

Applicable wire size AWG23 max. (0.26 mm2 max.)

Applicable External Connectors Connection Method Applicable Connector

Soldered type Fujitsu FCN-361J040-AU connector FCN-360C040-B connector cover

Solderless type Fujitsu FCN-363J040 housing FCN-363J-AU contact FCN-360C040-B connector cover

Solderless type Fujitsu FCN-367J040-AU / F

Operating Environment This module can be used with the following CPU modules: F3SP08-0P and F3SP08-SP

Model and Suffix Codes

Model Suffix Code

Style Code

Option Code Description

F3WD32 -3F · · · · · · · · · · · · 24 V DC input/output

Note: See the spare parts in the FA-M3 Range-free Multi-controller (GS 34M6A01-01E) for information on connectors.

External Dimensions F3WD32-3F

Unit: mm

Page 18: General FA-M3 Specifications FA-M3 Value, Value II · function to communicate with a higher-level computer or display. ... Configuration function (device capacity, data lock-up range

<<Content>> <<Index>> 18

All Rights Reserved. Copyright © 2010, Yokogawa Electric Corporation GS 34M06C81-01E Oct. 2010-00

I/O Module (F3WD64-3F)

Internal Circuit Diagram

8

10

9

_

+

+

_

+89

Bus interface

Display selector OUT

IN

1

COM

L

L

COM

~

1

~

Inte

rnal

bus

External Connection Diagram

+

24V

COM46463626160595857

COM24847464544434241

+

COM35655545352515049

COM14039383736353433

2019181716151413121110987654321

2019181716151413121110987654321

B A

LLLLLLLL

24V

LLLLLLLL

+

+

24V

LLLLLLLL

LLLLLLLL

24V

CN2 (Output block)

COM43231302928272625

COM216151413121110 9

+

+

+

+

COM32423222120191817

COM1 8 7 6 5 4 3 2 1

+

+

+

+

2019181716151413121110987654321

2019181716151413121110987654321

B ACN1 (Input block)

Note: Viewed from the front of the module.

External Connections Connector Type

Wire connection method Soldered

Applicable wire size AWG23 max. (0.26 mm2 max.)

Applicable External Connectors Connection Method Applicable Connector

Soldered type Fujitsu FCN-361J040-AU connector FCN-360C040-B connector cover

Solderless type Fujitsu FCN-363J040 housing FCN-363J-AU contact FCN-360C040-B connector cover

Solderless type Fujitsu FCN-367J040-AU / F

Operating Environment There is no restriction on the type of CPU modules that can be used with this module.

Model and Suffix Codes

Model Suffix Code

Style Code

Option Code Description

F3WD64 -3F · · · · · · · · · · · · 24 V DC input/output

Note: See the spare parts in the FA-M3 Range-free Multi-controller (GS 34M6A01-01E) for information on connectors.

External Dimensions F3WD64-3F

Unit: mm

Page 19: General FA-M3 Specifications FA-M3 Value, Value II · function to communicate with a higher-level computer or display. ... Configuration function (device capacity, data lock-up range

<<Content>> <<Index>> 19

All Rights Reserved. Copyright © 2010, Yokogawa Electric Corporation GS 34M06C81-01E Oct. 2010-00

I/O Module (F3WD64-3P)

Internal Circuit Diagram

Inte

rnal

bus ~

~

External Connection Diagram

COM4

32

31

30

29

28

27

26

25

COM2

16

15

14

13

12

11

10

9

COM3

24

23

22

21

20

19

18

17

COM1

8

7

6

5

4

3

2

1

20 19 18 17 16 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1

20 19 18 17 16 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1

B ACN1 (Input block)

24V

COM8

64

63

62

61

60

59

58

57

COM6

48

47

46

45

44

43

42

41

COM7

56

55

54

53

52

51

50

49

COM5

40

39

38

37

36

35

34

33

20 19 18 17 16 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1

20 19 18 17 16 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1

B A

L L L L L L L L

24V

L L L L L L L L

24V

L L L L L L L L

L L L L L L L L

24V

CN2 (Output block)

Note: Viewed from the front of the module.

External Connections Connector Type

Wire connection method Soldered

Applicable wire size AWG23 max. (0.26 mm2 max.)

Applicable External Connectors Connection Method Applicable Connector

Soldered type Fujitsu FCN-361J040-AU connector FCN-360C040-B connector cover

Solderless type Fujitsu FCN-363J040 housing FCN-363J-AU contact FCN-360C040-B connector cover

Solderless type Fujitsu FCN-367J040-AU / F

Operating Environment There is no restriction on the type of CPU modules that can be used with this module.

Model and Suffix Codes

Model Suffix Code

Style Code

Option Code Description

F3WD64 -3P · · · · · · · · · · · · 24 V DC input/output (with short-circuit protector)

Note: See the spare parts in the FA-M3 Range-free Multi-controller (GS 34M6A01-01E) for information on connectors.

External Dimensions F3WD64-3P

Unit: mm

Page 20: General FA-M3 Specifications FA-M3 Value, Value II · function to communicate with a higher-level computer or display. ... Configuration function (device capacity, data lock-up range

<<Content>> <<Index>> 20

All Rights Reserved. Copyright © 2010, Yokogawa Electric Corporation GS 34M06C81-01E Oct. 2010-00

I/O Module (F3WD64-4P)

Internal Circuit Diagram

8

10

9 COM

COM

-

+ -+

89

OUT

IN

1 L

L

1

Overheat protectorOvercurrent protector

Constantvoltage circuit

BusInterface

Displayselector

-

+

External Connection Diagram

COM4

32

31

30

29

28

27

26

25

COM2

16

15

14

13

12

11

10

9

COM3

24

23

22

21

20

19

18

17

COM1

8

7

6

5

4

3

2

1

20 19 18 17 16 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1

20 19 18 17 16 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1

B ACN1 (Input block)

12V

COM8

64

63

62

61

60

59

58

57

COM6

48

47

46

45

44

43

42

41

COM7

56

55

54

53

52

51

50

49

COM5

40

39

38

37

36

35

34

33

20 19 18 17 16 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1

20 19 18 17 16 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1

B A

L L L L L L L L

12V

L L L L L L L L

12V

L L L L L L L L

L L L L L L L L

12V

CN2 (Output block)

Note: Viewed from the front of the module.

External Connections Connector Type

Wire connection method Soldered

Applicable wire size AWG23 max. (0.26 mm2 max.)

Applicable External Connectors Connection Method Applicable Connector

Soldered type Fujitsu FCN-361J040-AU connector FCN-360C040-B connector cover

Solderless type Fujitsu FCN-363J040 housing FCN-363J-AU contact FCN-360C040-B connector cover

Solderless type Fujitsu FCN-367J040-AU / F

Operating Environment There is no restriction on the type of CPU modules that can be used with this module.

Model and Suffix Codes

Model Suffix Code

Style Code

Option Code Description

F3WD64 -4P · · · · · · · · · · · · 12 V DC input/output (with short-circuit protector)

Note: See the spare parts in the FA-M3 Range-free Multi-controller (GS 34M6A01-01E) for information on connectors.

External Dimensions F3WD64-4P