ge - mpact mpro acb ( 400a - 4000a )

48
M-PACT Air Circuit Breaker 400-4000A New GE Energy Industrial Solutions

Upload: sugumaran

Post on 28-Apr-2015

215 views

Category:

Documents


1 download

TRANSCRIPT

Page 1: Ge - Mpact Mpro Acb ( 400a - 4000a )

M-PACTAir Circuit Breaker 400-4000A

New

GE EnergyIndustrial Solutions

Page 2: Ge - Mpact Mpro Acb ( 400a - 4000a )

M-PACTAir Circuit Breaker 400-4000A

Page 3: Ge - Mpact Mpro Acb ( 400a - 4000a )

INDEX

Technical OverviewA

B

Fixed Circuit Breaker .............................................................................................................................................................................. A.4

Withdrawable Circuit Breaker ........................................................................................................................................................... A.6

Characteristics .......................................................................................................................................................................................... A.7

State-of-the-Art Electronic Trip Units ............................................................................................................................................. A.9

Time Current Curves ............................................................................................................................................................................A.11

M-PACT Accessories .............................................................................................................................................................................A.19

Mpro 27 & 50 Connection ....................................................................................................................................................................B.2

Dimensional Drawings ...........................................................................................................................................................................B.6

Wiring DiagramsDimensional Drawings

Page 4: Ge - Mpact Mpro Acb ( 400a - 4000a )

M-PACT

A.3 Technical overview

Notes:

Page 5: Ge - Mpact Mpro Acb ( 400a - 4000a )

A.4Technical overview

Specification

Approvals

Rated from 400 to 4000A the M-PACT circuit breaker has been designed to meet the most stringent demands in fault detection and safe interruption thereof.

Available in 2 frame sizes:- frame size 1 ranging from 400 to 2500A- frame size 2 ranging from 800 to 4000A

The range has been developed to be aestheticallyand technically co-ordinated with other protectivedevices within the GE Power Controls industrialproduct ranges.

The breaker range has a common height and depth andis available in both fixed pattern and drawout versionswhich can be manually or electrically operated.

Designed to offer multiple mains connection options italso comes with a wide range of easy-to-install accessories.

M-PACT Air Circuit Breakers comply with the followingspecifications for Low Voltage Switchgear:

IEC 60947-1• IEC 60947-2• IEC 60947-3• Utilisation category B•

KEMA certification in accordance with IEC 60947-2CCC certification in accordance with GB14048-2CCS certification in accordance with China Certification of shipping

3 performance ranges*A -50 kA (Icu)D -65 kA (Icu)H1, H2 -80 kA (Icu)*Ratings shown at 415V AC2 compact frame sizesFrame size 1 - 400 to 2500AFrame size 2 - 800 to 4000AFixed pattern and withdrawable versions3 or 4 pole configurationFront and rear access connections (horizontal/vertical)Devices provided with or without protection relayManual or electrical operationCommon height and depth dimensionsBuilt-in safety features e.g. safety shuttersWide range of protection settings offering full selectivityCombinations of earth fault protectionEasy-to-install accessories, common to entire rangeSimple and efficient servicing on site

Type A Type D Type H1,H2

Fixed Circuit Breaker

Page 6: Ge - Mpact Mpro Acb ( 400a - 4000a )

M-PACT

A.5 Technical overview

Fixed Circuit BreakerAll M-PACT fixed pattern Air Circuit Breakers incorporate a stored energy mechanism. The spring can be charged either manually or electrically via a motor operator that is automatically activated after the closing operation.

IP43 front panel and door escutcheon seals are standard features with IP20 protected secondary isolating contacts.

For enhanced protection, an optional IP54 door panel is also available.

Trip-free operating mechanism• Positive 'ON/OFF' contact indication• Mechanical/electrical anti-pumping device• Charging spring status indication (optional)• Ergonomic manual spring charging handle• Field-mountable range of accessories• Auxiliary switches 5 NO and 3 NC, 10A 250V (standard)• Mechanical trip alarm switch (1NO) (optional)• Padlockable push-button cover• Mechanical cable interlocking (optional)• Termination: rear, horizontal or front access (optional)• Electrical clearances according to IEC60947-2• Front access of secondary terminals for simple connection•

8

9

InstallationFixed pattern M-PACT can be fastened into any suitable switchboard or cubicle arrangement using four M8 bolts.

Clearance is only required above the unit for the removal and inspection of the arc chutes (see dimensional drawings for mounting details and recommended clearance distances).

An earthing point is provided on either side of the circuit breaker.

Power Supply

1. Motorised spring charging unit (optional)2. M-PRO Protection Relay (optional)3. Secondary contacts4. Shunt trip (optional)5. Closing coil (optional)6. Undervoltage release (optional)7. Manual charging handle8. ON/OFF push-buttons9. Push-button padlockable covers10. Positive contact indication11. Charging spring status indication12. Mounting plate

12

3

2

7

10

11

4 5

1

6

Page 7: Ge - Mpact Mpro Acb ( 400a - 4000a )

A.6Technical overview

8 6

Withdrawable Circuit Breaker

Insulated, earthed steel shutters to isolate the main • contact zone

Front access padlocking for safety shutters• Secure padlocking in the "Disconnect" position• Clearly visible operational position indication• Carriage position switch (optional)• Termination: Flat copper palms (standard) with captive M10 •

fixing nuts'T' terminal adaptors for horizontal/vertical connection •

(optional)Front access connections (optional)• Automatic disconnect of secondary circuits• Lifting lugs for ease of removing the circuit breaker from •

the cassetteFront access of secondary terminals for simple connection• Cassette side mounting fixing parts (optional)•

Installation

Power Supply

Circuit breakers are delivered pre-mounted in thecassette (standard)

Versatile fixing arrangements allow mounting onto any switchboard or cubicle using four M8 bolts (see dimensional drawings for mounting details and recommended clearance distances)

Earthing point situated on the right hand side of cassette (front view)

1. Carriage position switch (optional)2. Extension rail3. Earthed steel safety shutter4. Secondary terminals5. 2 way cable interlock mechanism (optional)6. Racking handle (storage)7. Padlocking for safety shutters8. Insertion hole for racking handle9. Padlocking in the DISCONNECTED position10. Operational position indication11. Key interlock (optional)

5

4

11

7

10

9

2

1

3

4

Withdrawable Circuit Breaker

Page 8: Ge - Mpact Mpro Acb ( 400a - 4000a )

M-PACT

A.7 Technical overview

Characteristics

Design and specifications are subject to changes without notice.

Selectivity

The following table shows the conditions to satisfy full selectivity between UP-STREAM and DOWN-STREAM devices. Up-stream: M-PACTDown-stream: M-PACTST delay 50 ms minimum between up-stream and downstream ACB Multipl ication coefficient between LT-ratings≥1,56

Down-stream

- 400 800 1000 1250 1600 2000 2500 3200 4000400 - - - - - - - - -800 Full - - - - - - - -

1000 Full - - - - - - - -1250 Full Full - - - - - - -1600 Full Full Full - - - - - -2000 Full Full Full Full - - - - -2500 Full Full Full Full Full Full - - -3200 Full Full Full Full Full Full - - -4000 Full Full Full Full Full 2000 Full - -

Up-

stre

am

Catalog NO.ConfigurationMP A 3 1 F 16

Ratings:

04-400A, 08-800A10-1000A, 12-1250A16-1600A, 20-2000A25-2500A, 32-3200A40-4000A

Installation: F-fixed W-withdrawable

Type: 1-Frame1 2-Frame2

* Letter 'L' & 'R' only for type selection, not shown on nameplate.

Breaking Capacity: A, D, H1, H2

M-PACT

Pole: 3-3P 4-4P*

Performance DataCharacteristic Symbol UnitsRated current (400C) 400 800 1000 1250 1600 2000 2500 3200 4000

Endurance (number of operating cycles)Mechanical (with maintenance) 20000 20000 20000 20000 20000 20000 20000 20000 20000

Mechanical (without maintenance) 10000 10000 10000 10000 10000 10000 10000 10000 10000Electrical (at rated current) 5000 5000 5000 5000 5000 5000 5000 5000 5000

Rated service voltage (50/60 Hz) Ue V 415 690 415 690 415 690 415 690 415 690 415 690 415 690 415 690 415 690 415 690 415 690 415 690 415 690 415 415 415 690 415 415 415 690Rated insulation voltage (50/60 Hz) Ui V 1000 1000 1000 1000 1000 1000 1000 1000 1000Rated impulse withstand voltage Uimp V 8000 8000 8000 8000 8000 8000 8000 8000 8000

Number of poles 3 & 4 3 & 4 3 & 4 3 & 4 3 & 4 3 & 4 3 & 4 3 & 4 3 & 4Rating of 4th pole 100% 100% 100% 100% 100% 100% 100% 100% 100%

ACB type A D A D H1 H2 A D H1 H2 A D H1 H2 A D H1 H2 A D H1 H2 A D H1 H2 A D H1 H2 A D H1 H2Frame size 1 1 1 1 2 2 1 1 2 2 1 1 2 2 1 1 2 2 1 1 2 2 1 1 2 2 2 2 2 2 2 2 2 2

Rated ultimate short-circuit Icu kA (rms) 220V 50 65 50 65 80 80 50 65 80 80 50 65 80 80 50 65 80 80 50 65 80 80 50 65 80 80 50 65 80 80 50 65 80 80breaking capacity 415V 50 65 50 65 80 80 50 65 80 80 50 65 80 80 50 65 80 80 50 65 80 80 50 65 80 80 50 65 80 80 50 65 80 80

500V - 65 - 65 - 80 - 65 - 80 - 65 - 80 - 65 - 80 - 65 - 80 - 65 - 80 - - - 80 - - - 80600V - 50 - 50 - 65 - 50 - 65 - 50 - 65 - 50 - 65 - 50 - 65 - 50 - 65 - - - 65 - - - 65690V - 40 - 40 - 60 - 40 - 60 - 40 - 60 - 40 - 60 - 40 - 60 - 40 - 60 - - - 60 - - - 60

Rated service short-circuit Ics kA (rms) 220V 50 65 50 65 80 80 50 65 80 80 50 65 80 80 50 50 65 80 50 65 80 80 50 65 80 80 50 65 80 80 50 65 80 80breaking capacity 415V 50 65 50 65 80 80 50 65 80 80 50 65 80 80 50 50 65 80 50 65 80 80 50 65 80 80 50 65 80 80 50 65 80 80

500V - 65 - 65 - 80 - 65 - 80 - 65 - 80 - 50 - 65 - 65 - 80 - 65 - 80 - - - 80 - - - 80600V - 50 - 50 - 65 - 50 - 65 - 50 - 65 - 50 - 50 - 50 - 65 - 50 - 65 - - - 65 - - - 65690V - 40 - 40 - 60 - 40 - 60 - 40 - 60 - 40 - 40 - 40 - 60 - 40 - 60 - - - 60 - - - 60

Rated short time withstand current1 second Icw kA (rms) 50 50 50 50 65 80 50 50 65 80 50 50 65 80 50 50 65 65 80 65 65 80 50 65 65 80 50 65 65 80 50 65 65 803 seconds Icw kA (rms) 40 50 40 50 50 50 40 50 50 50 40 50 50 50 40 40 50 50 50 50 50 50 40 50 50 50 40 50 50 50 40 50 50 50Rated short-circuit making capacity Icm kA (peak) 415V 105 143 105 143 176 176 105 143 176 176 105 143 176 176 105 105 143 176 176 143 176 176 105 143 176 176 105 143 176 176 105 143 176 176

500V - 143 - 143 - 176 - 143 - 176 - 143 - 176 - 105 - 143 - 143 - 176 - 143 - 176 - - - 176 - - - 176600V - 105 - 105 - 143 - 105 - 143 - 105 - 143 - 105 - 105 - 105 - 143 - 105 - 143 - - - 143 - - - 143690V - 84 - 84 - 105 - 84 - 105 - 84 - 105 - 84 - 84 - 84 - 105 - 84 - 105 - - - 105 - - - 105

Power dissipation at In (Fixed breaker) Watts 15 10 63 43 23 20 106 68 36 32 175 105 60 53 284 284 196 98 86 224 163 143 351 351 255 223 418 418 418 366 571 571 571 571Power dissipation at In (Withdrawable) Watts 30 21 127 86 49 43 211 135 77 68 351 211 128 113 574 574 392 209 184 490 347 306 765 765 542 478 888 888 888 783 1224 1224 1224 1224

Page 9: Ge - Mpact Mpro Acb ( 400a - 4000a )

A.8Technical overview

Weights (kg)A range D range H range

Fixed pattern ACB Frame 3 Pole 4 Pole 3 Pole 4 Pole 3 Pole 4 Pole400 to 1600A 1 39 49 39 49 / /

2000 to 2500A 1 43 54 43 54 / /800 to 3200A 2 53 68 53 68 53 68

4000A 2 53 68 53 68 53 68

Withdrawable ACB Frame 3 Pole 4 Pole 3 Pole 4 Pole 3 Pole 4 Pole400 to 1600A 1 68 79 68 79 / /

2000 to 2500A 1 74 85 74 85 / /800 to 3200A 2 90 109 90 109 90 109

4000A 2 113 128 113 128 113 128

Recommended Minimum Copper SizeIn accordance with IEC 60947-2

Rating (A) Copper / phase400 2 x 50 x 5800 2 x 50 x 5

1000 2 x 60 x 51250 2 x 100 x 51600 2 x 100 x 52000 3 x 100 x 52500 4 x 100 x 53200 4 x 100 x 104000 4 x 100 x 10 + 1 x 100 x 5

Dimensions in mmFrame

SizeRating

(A) Poles Type Height(1) Width Depth(2)

1 400 to 2500 3 Withdrawable 440 329 422Fixed 430 342 352

4 Withdrawable 440 429 422Fixed 430 442 352

2 800 to 4000 3 Withdrawable 440 419 424Fixed 430 432 352

4 Withdrawable 440 549 424Fixed 430 562 352

(1) Height is from mounting surface to highest part of the ACB.(2) Depth is from the cubicle door to the back of terminals.* 4P, Neutral on the left or right Please specified on selection form, the default

option is neutral on night.

Performance DataCharacteristic Symbol UnitsRated current (400C) 400 800 1000 1250 1600 2000 2500 3200 4000

Endurance (number of operating cycles)Mechanical (with maintenance) 20000 20000 20000 20000 20000 20000 20000 20000 20000

Mechanical (without maintenance) 10000 10000 10000 10000 10000 10000 10000 10000 10000Electrical (at rated current) 5000 5000 5000 5000 5000 5000 5000 5000 5000

Rated service voltage (50/60 Hz) Ue V 415 690 415 690 415 690 415 690 415 690 415 690 415 690 415 690 415 690 415 690 415 690 415 690 415 690 415 415 415 690 415 415 415 690Rated insulation voltage (50/60 Hz) Ui V 1000 1000 1000 1000 1000 1000 1000 1000 1000Rated impulse withstand voltage Uimp V 8000 8000 8000 8000 8000 8000 8000 8000 8000

Number of poles 3 & 4 3 & 4 3 & 4 3 & 4 3 & 4 3 & 4 3 & 4 3 & 4 3 & 4Rating of 4th pole 100% 100% 100% 100% 100% 100% 100% 100% 100%

ACB type A D A D H1 H2 A D H1 H2 A D H1 H2 A D H1 H2 A D H1 H2 A D H1 H2 A D H1 H2 A D H1 H2Frame size 1 1 1 1 2 2 1 1 2 2 1 1 2 2 1 1 2 2 1 1 2 2 1 1 2 2 2 2 2 2 2 2 2 2

Rated ultimate short-circuit Icu kA (rms) 220V 50 65 50 65 80 80 50 65 80 80 50 65 80 80 50 65 80 80 50 65 80 80 50 65 80 80 50 65 80 80 50 65 80 80breaking capacity 415V 50 65 50 65 80 80 50 65 80 80 50 65 80 80 50 65 80 80 50 65 80 80 50 65 80 80 50 65 80 80 50 65 80 80

500V - 65 - 65 - 80 - 65 - 80 - 65 - 80 - 65 - 80 - 65 - 80 - 65 - 80 - - - 80 - - - 80600V - 50 - 50 - 65 - 50 - 65 - 50 - 65 - 50 - 65 - 50 - 65 - 50 - 65 - - - 65 - - - 65690V - 40 - 40 - 60 - 40 - 60 - 40 - 60 - 40 - 60 - 40 - 60 - 40 - 60 - - - 60 - - - 60

Rated service short-circuit Ics kA (rms) 220V 50 65 50 65 80 80 50 65 80 80 50 65 80 80 50 50 65 80 50 65 80 80 50 65 80 80 50 65 80 80 50 65 80 80breaking capacity 415V 50 65 50 65 80 80 50 65 80 80 50 65 80 80 50 50 65 80 50 65 80 80 50 65 80 80 50 65 80 80 50 65 80 80

500V - 65 - 65 - 80 - 65 - 80 - 65 - 80 - 50 - 65 - 65 - 80 - 65 - 80 - - - 80 - - - 80600V - 50 - 50 - 65 - 50 - 65 - 50 - 65 - 50 - 50 - 50 - 65 - 50 - 65 - - - 65 - - - 65690V - 40 - 40 - 60 - 40 - 60 - 40 - 60 - 40 - 40 - 40 - 60 - 40 - 60 - - - 60 - - - 60

Rated short time withstand current1 second Icw kA (rms) 50 50 50 50 65 80 50 50 65 80 50 50 65 80 50 50 65 65 80 65 65 80 50 65 65 80 50 65 65 80 50 65 65 803 seconds Icw kA (rms) 40 50 40 50 50 50 40 50 50 50 40 50 50 50 40 40 50 50 50 50 50 50 40 50 50 50 40 50 50 50 40 50 50 50Rated short-circuit making capacity Icm kA (peak) 415V 105 143 105 143 176 176 105 143 176 176 105 143 176 176 105 105 143 176 176 143 176 176 105 143 176 176 105 143 176 176 105 143 176 176

500V - 143 - 143 - 176 - 143 - 176 - 143 - 176 - 105 - 143 - 143 - 176 - 143 - 176 - - - 176 - - - 176600V - 105 - 105 - 143 - 105 - 143 - 105 - 143 - 105 - 105 - 105 - 143 - 105 - 143 - - - 143 - - - 143690V - 84 - 84 - 105 - 84 - 105 - 84 - 105 - 84 - 84 - 84 - 105 - 84 - 105 - - - 105 - - - 105

Power dissipation at In (Fixed breaker) Watts 15 10 63 43 23 20 106 68 36 32 175 105 60 53 284 284 196 98 86 224 163 143 351 351 255 223 418 418 418 366 571 571 571 571Power dissipation at In (Withdrawable) Watts 30 21 127 86 49 43 211 135 77 68 351 211 128 113 574 574 392 209 184 490 347 306 765 765 542 478 888 888 888 783 1224 1224 1224 1224

Characteristics

Page 10: Ge - Mpact Mpro Acb ( 400a - 4000a )

M-PACT

A.9 Technical overview

State-of-the-Art Electronic Trip Units

Plug'n Play MPRO-27 & MPRO-50

Main Adjustment Options

A line offering a new range of electronic trip units designed to extend and/or upgrade the • functionality offered by the existing M-PACT Plus Air Circuit Breaker.

Two types are available. The simple and effective MPRO-27 and the MPRO-50 offering extended • functionality .

Each has a LCD screen with ammeter and a menu driven setting interface, allowing a simple and • accurate setting of all parameters.

This global line of electronic trip units uses the most recent technology to offer each user an • unique combination of selectivity speed and functionality.

Electronic trip units are normally supplied factory fitted. However spares are available that can be simply plugged in to breakers installed in the field.

Each trip unit then needs to be adjusted to the required settings. If the installation is not powered up the installed battery pack or the seperately available test kit with Power Pack can be used as alternate power source.

The basic MPRO-27 type has been designed to replace the existing MPRO-17 and MPRO-18 plus units offering an extended functionality and a standard ammeter.

The MPRO-50 type replaces the existing MPRO-30 and MPRO-40 designscovering an extended functionality with protection devices as fuse links,overload protection and reduced instantaneous (RELT). Each MPRO-50 comes with a simple to connect 4 wire modbus communciation option.

LT-LTD protection •

ST-STD protection •

I-protection •

Other protection features •

Each device has an overload setting range of 0.4 to a times In and offer a choice of 22 time bands designed for use with circuit breakers.

A second set of 22 time bands shaped to match the time current curves of fuses is available on the MPRO-50 type.

A timed delayed short circuit protection is installed with a current setting of 2 to 12 times the set LT current value. The short circuit protection time can be set, at one of 17 bands ranging from 90 milliseconds to 1 second.

Optionaly this device can be set to one of three I2t curves.

A switchable and selective instantaneous protection with a setting range of 2 to 15 times the breaker rating that is programmed to wait one half cycle until the downstream device has reacted.

A host of other protection devices is availble including Ground Fault sum and Ground Fault source return (allowing UEF, SEF & REF) and a reduced instantaneous device. The reduced instanataneous device allows the user to conditionally programme the breaker to trip faster and at lower short circuit settings than it would on the standard instantaneuos device.

This RELT device allows the user to reduce the short circuit current level and its time span, thus reducing the amount of electrical energy in the direct vicinity of the breaker.

Page 11: Ge - Mpact Mpro Acb ( 400a - 4000a )

A.10Technical overview

Trip Unit MPRO-27 MPRO-50Setting InterfaceLCD screen allowing access to 4 distinct menu's X XTouch pad adjustments X XMultilingual X XAdjustable manual or automatic RESET option X XLong Time or Overload Current Protection13 current settings Ir 1, 0.95, 0.9. 0,85, 0.8, 0.75, 0.7, 0.65, 0.6, 0.55, 0.5, 0.45 & 0.4 x breaker rating In X X22 thermal protection (C type) time bands available ranging from class 0.5 to 40 (bands at 7.2 x Ir) X X22 I2t protection (F type {fuse} ) time bands available - XNeutral protection 0-50%-63%-100% X XPossibility to switch OFF - XCooling function and thermal memory X XShort Time Short-Circuit Current ProtectionSetting range from 1.5 to 12 x Ir (LT setting) X XSteps of 0.5 (a total of 22 settings) X XPossibility to switch OFF - X17 time delay settings (STDB) ranging from 30 to 940 milliseconds delay setting result ina 90 to 1000 milliseconds X X

Clearance times to IEC 40979-1 and IEC 603643 I2t Protection time bands availableInstantaneous Short-Circuit Current• StandardIi setting range from 2 to 15 x breaker rating In X XSteps of 0.5 (a total of 28 settings) X XPossibility to switch OFF X XSelective execution X XFixed instantaneous or HSIOC protection X X• ReducedIi setting range from 1.5 to 15 x Ie (primary setting) - XSteps of 0.5 (a total of 29 settings) - XPossibility to switch OFF - XRemote and local ON and OFF with position indication signal - XGround or Earth Fault ProtectionSetting range from 0.1 to 1 x In (breaker rating) (1) •(1) •(1)

Steps of 0.01 (a total of 92 settings) • •Possibility to switch OFF • •14 time delay settings (GFDB) ranging from 50 to 840 milliseconds delay setting resulting in a 110 to 900 milliseconds • •

Clearance times to IEC 40979-1 and IEC 60364 • •3 I2t protection time bands available • •1 I4t protection time bands available • •Residual principle (UEF application possible) • •Source ground return principle - •UEF, REF and SEF applications possible - •Combinations of UEF, REF and SEF applications possible - •Other FunctionsCurrent measurement (L1, L2, L3, N) X XTrip target (trip reason indication) X XTrip info (magnitude / phase) X XTrip counter X XEvent logger (trip events) X XGeneral inputs (4 availble) - XGeneral relay outputs (4 available) - XRelay based on current level (load shedding) - XGood & bad health indicator - XWatchdog - XCommunication 2 way - XModbus - X24V DC auxiliary power supply X XTest kit with power support function • •

(1) A 24V auxiliary power supply is required.KeyX = Present• = Optional- = Not possible

State-of-the-art Electronic Trip Units

Page 12: Ge - Mpact Mpro Acb ( 400a - 4000a )

M-PACT

A.11 Technical overview

Time Current CurvesExample of Full Time Current CurveTime Current Curve

The MPRO Electronic trip unit has many sophisticated setting features and an extremely broad setting range. On request we can provide complete Time Current Curves covering all installed protection devices.

The curves can be produced for any current setting within the range of the installed protection devices, for one or for a combination of two breakers.

Please contact your local GE sales office for more information.

MPRO Electronic Trip Unit

0,001

0,01

0,1

1

10

100

1000

10000

000001000010001

x Current in Amps (Strom in Ampere)

Trip

ping

Tim

e in

Sec

onds

(s)

Time Current CurveBreaker In= 2500A----------------------------------LT - Protection deviceSet at Ie= 2400AIr at 0,9 =2160ABand C-10

ST - Protection deviceSet at 6x Ir of 2160AIst=12960ABand STDB 10

I - Protection deviceSet at 12 x Ie of 2400AIi = 28800A

GF - Protection deviceSet at 0,6 x Ie of 2500A(Ig = 1500A)Band GFDB 6I²t ON & OFF

2h

7,2 x

Green & Light Blue Line = Full Clearing timeRed Line & Dark Blue Line = Non Tripping time

LT Band

ST Band

I I Band

HSIOC Band

GF Band

Page 13: Ge - Mpact Mpro Acb ( 400a - 4000a )

A.12Technical overview

Time Current Curves (cold state)LT Protection Device

MPRO 27 & 50 Electronic Trip Unit MPRO 27 & 50 Electronic Trip Unit

MPRO 27 & 50 Electronic Trip Unit MPRO 27 & 50 Electronic Trip Unit

ST protection - OFF

I protection set to 15 x Ie(1)

ST protection - OFF

I protection set to 15 x Ie(1)

ST protection - OFF

I protection set to 15 x Ie(1)

ST protection - OFF

I protection set to 15 x Ie(1)

LT set at Breaker Rating InSetting RangeIe= 0.975, 0.9625, 0.95, 0.45 or 0.4 x InIr= 0.5 to 1 x Ie in steps of 0.25Total Setting Range 0,2 - 1 x In

LT set at Breaker Rating InSetting RangeIe= 0.975, 0.9625, 0.95, 0.45 or 0.4 x InIr= 0.5 to 1 x Ie in steps of 0.25Total Setting Range 0,2 - 1 x In

LT set at Breaker Rating InSetting RangeIe= 0.975, 0.9625, 0.95, 0.45 or 0.4 x InIr= 0.5 to 1 x Ie in steps of 0.25Total Setting Range 0,2 - 1 x In

Time Current Curve

Band C-03Band C-08Band C-13Band C-19

LT-Protection Device-

----

Time Current Curve

Band C-06Band C-11Band C-16Band C-22

LT-Protection Device-

----

Time Current Curve

Band C-02Band C-07Band C-12Band C-17

LT-Protection Device-

----

Time Current Curve

Band C-04Band C-09Band C-14Band C-20

LT-Protection Device-

----

100002h

100002h

1000

100

10

Trip

ping

Tim

e In

Sec

onds

(s)

1

0,11,00 10,00 100,00

x Breaker Rating In

Trip

ping

Tim

e In

Sec

onds

(s)

0,11,00

x Breaker Rating In

7,2x

10,00 100,00

7,2x

Trip

ping

Tim

e In

Sec

onds

(s)

0,11,00

x Breaker Rating In10,00 100,00

7,2x

Setting RangeIe= 0.975, 0.9625, 0.95, 0.45 or 0.4 x InIr= 0.5 to 1 x Ie in steps of 0.25Total Setting Range 0,2 - 1 x In

LT set at Breaker Rating In

1000

10

100

100002h

1000

10

100

1 1

Trip

ping

Tim

e In

Sec

onds

(s)

0,11,00

x Breaker Rating In10,00 100,00

7,2x

100002h

1000

10

100

1

Time Current Curves

Page 14: Ge - Mpact Mpro Acb ( 400a - 4000a )

M-PACT

A.13 Technical overview

MPRO 27 & 50 Electronic Trip Unit MPRO 27 & 50 Electronic Trip Unit

MPRO 27 & 50 Electronic Trip Unit MPRO 27 & 50 Electronic Trip UnitTime Current Curve

Band STDB 02Band STDB 04Band STDB 06Band STDB 08Band STDB 19Band STDB 12Band STDB 14Band STDB 16

ST-Protection DeviceI2t - OFF-

-

--------

Time Current Curve

Band STDB 01Band STDB 03Band STDB 05Band STDB 07Band STDB 09Band STDB 11Band STDB 13Band STDB 15Band STDB 17

ST-Protection DeviceI2t - OFF-

-

---------

Green Line = Full Clearing TimeRed Line = Non Tripping Time

Green Line = Full Clearing TimeRed Line = Non Tripping Time

I protection set to 15 x Ie(1)I protection set to 15 x Ie(1)

LT set at Breaker Rating InSetting RangeIe= 0.975, 0.9625, 0.95, 0.45 or 0.4 x InIr= 0.5 to 1 x Ie in steps of 0.25Total Setting Range 0,2 - 1 x In

LT set at Breaker Rating InSetting RangeIe= 0.975, 0.9625, 0.95, 0.45 or 0.4 x InIr= 0.5 to 1 x Ie in steps of 0.25Total Setting Range 0,2 - 1 x In

Time Current Curve

Band C-05Band C-10Band C-15Band C-21

LT-Protection Device- -

----

Time Current Curve

Band C-01Band C-18

LT-Protection Device--

ST protection - OFF

I protection set to 15 x Ie(1)

ST protection - OFF

I protection set to 15 x Ie(1)

ST set on breaker rating InSetting Range1,5 to 12 x Ir in steps of 0,5

ST set on breaker rating In Setting Range1,5 to 12 x Ir in steps of 0,5

1617

15

17

15

13

11

9

7

5

3

1

13

11

9

7

5

3

1

14

12

10

16

14

12

10

8

6

4

2

8

6

4

2

x Breaker Rating In

x Breaker Rating In

x Breaker Rating In

Trip

ping

Tim

e In

Sec

onds

(s)

Trip

ping

Tim

e In

Sec

onds

(s)

Trip

ping

Tim

e In

Sec

onds

(s)

Trip

ping

Tim

e In

Sec

onds

(s)

1,00 1,00

1,00 10,0010,00 100,00100,00

x Breaker Rating In

1,00

10,00 10,00100,00 100,00

0,001 0,001

0,01 0,01

0,1

1

10

100

1000

2h10000

2h

1000

100

10

1

0,1

10000

0,1 0,1

0,2 0,2

0,4 0,4

0,6 0,6

0,8 0,8

1 1

10 10

7,2x 7,2x

-

-

Time Current Curves (cold state)LT & STDB Protection Device

Page 15: Ge - Mpact Mpro Acb ( 400a - 4000a )

A.14Technical overview

Time Current Curves (cold state)ST Protection Device

MPRO 27 & 50 Electronic Trip Unit MPRO 27 & 50 Electronic Trip Unit

MPRO 27 & 50 Electronic Trip Unit MPRO 27 & 50 Electronic Trip Unit

10,00 100,00

10

0,8

1

0,6

0,4

0,2

0,1

00,1

0,01

1,00

Trip

ping

Tim

e In

Sec

onds

(s)

x Breaker rating In

10,00 100,00

10

0,8

1

0,6

0,4

0,2

0,1

00,1

0,01

1,00

Trip

ping

Tim

e In

Sec

onds

(s)

x Breaker rating In10,00 100,00

10

0,8

1

0,6

0,4

0,2

0,1

00,1

0,01

1,00

Trip

ping

Tim

e In

Sec

onds

(s)

x Breaker rating In

10,00 100,00

10

0,8

0,6

0,4

0,2

0,1

00,1

0,01

1,00

Trip

ping

Tim

e In

Sec

onds

(s)

x Breaker rating In

1716 16

14

12

108

6

42

1614

12

108

6

42

14

12

10

8

6

4

2

16

14

12

10

8

6

4

2

15

1715

1313

1111

99

7

7

5

5

3

3

1

1715

1715

1313

1111

9

7

97

5

5

3

3

1

1

1

Green Iine = Full Clearing timeRed Line = Non Tripping time

Green Iine = Full Clearing timeRed Line = Non Tripping time

I protection set to 15×Ie (1)

Green Iine = Full Clearing timeRed Line = Non Tripping time

I protection set to 15×Ie (1)

I protection set to 15×Ie (1)

ST set at Breaker Rating In

1,5 to 12 × Ir in steps of 0,5Setting Range

ST set at Breaker Rating In

1,5 to 12 × Ir in steps of 0,5Setting Range

ST set at Breaker Rating In

1,5 to 12 × Ir in steps of 0,5Setting Range

- Time Current Curve

- Band STDB 01- Band STDB 03- Band STDB 05- Band STDB 07- Band STDB 09- Band STDB 11- Band STDB 13- Band STDB 15- Band STDB 17

ST- Protection Device

I2t ON “Iow”

- Time Current Curve

- Band STDB 01- Band STDB 03- Band STDB 05- Band STDB 07- Band STDB 09- Band STDB 11- Band STDB 13- Band STDB 15- Band STDB 17

ST- Protection Device

I2t ON “med”

ST set at Breaker Rating In

1,5 to 12 × Ir in steps of 0,5Setting Range

- Time Current Curve

- Band STDB 02- Band STDB 04- Band STDB 06- Band STDB 08- Band STDB 10- Band STDB 12- Band STDB 14- Band STDB 16

ST- Protection Device

I2t ON “Iow”

- Time Current Curve

- Band STDB 02- Band STDB 04- Band STDB 06- Band STDB 08- Band STDB 10- Band STDB 12- Band STDB 14- Band STDB 16

ST- Protection Device

I2t ON “med”

Green Iine = Full Clearing timeRed Line = Non Tripping time

I protection set to 15×Ie (1)

Time Current Curves

Page 16: Ge - Mpact Mpro Acb ( 400a - 4000a )

M-PACT

A.15 Technical overview

MPRO 27 & 50 Electronic Trip Unit MPRO 27 & 50 Electronic Trip Unit

MPRO 27 & 50 Electronic Trip Unit MPRO 27 & 50 Electronic Trip Unit

10,00 100,00

10

0,81

0,6

0,4

0,2

0,1

0,01

0,01

1,00

Trip

ping

Tim

e In

Sec

onds

(s)

x Breaker rating In10,00 100,00

10

0,8

0,6

0,4

0,2

0,1

0,01

0,01

1,00

Trip

ping

Tim

e In

Sec

onds

(s)

x Breaker rating In

ST set at Breaker Rating In

1,5 to 12 × Ir in steps of 0,5Setting Range

I set on breaker rating In

2 to 15 × Ie in steps of 0,5

HSIOC device HSIOC device

HI Setting RangeI set on breaker rating In

2 to 15 × Ie in steps of 0,5HI Setting Range

I set on breaker rating In

1,5 to 15 × Ie in steps of 0,5RELT Setting Range

I set on breaker rating In

1,5 to 15 × Ie in steps of 0,5RELT Setting Range

ST set at Breaker Rating In

1,5 to 12 × Ir in steps of 0,5Setting Range

1715

13

11

9

7

5 3 1

16 16

14 14

1212

1010

8

8

6

6

4 2 4 2

1715

13

11

97

5

3 1

- Time Current Curve

- Band STDB 01- Band STDB 03- Band STDB 05- Band STDB 07- Band STDB 09- Band STDB 11- Band STDB 13- Band STDB 15- Band STDB 17

ST- Protection Device

I2t ON “max”

- Time Current CurveI - Protection Device

RELT - Protection Device

- Time Current CurveHI - Protection Device

RELT - Protection Device

- Time Current Curve

- Band STDB 02- Band STDB 04- Band STDB 06- Band STDB 08- Band STDB 10- Band STDB 12- Band STDB 14- Band STDB 16

ST- Protection Device

I2t ON “max”

Green Iine = Full Clearing timeRed Line = Non Tripping time

Green Iine = Full Clearing timeRed Line = Non Tripping time

I protection set to 15×Ie (1) I protection set to 15×Ie (1)

Green Iine = Full Clearing timeRed Line = Non Tripping time

Green Iine = Full Clearing timeRed Line = Non Tripping time

10,00 100,00

1

0,1

0,01

0,001

1,00

Trip

ping

Tim

e In

Sec

onds

(s)

x Breaker rating In10,00 100,00

1

0,1

0,01

0,001

1,00

Trip

ping

Tim

e In

Sec

onds

(s)

x Breaker rating In

Time Current Curves (cold state)ST, I and Hi Protection Device

Page 17: Ge - Mpact Mpro Acb ( 400a - 4000a )

A.16Technical overview

Time Current Curves (cold state)HSIOC & GF Protection Device

MPRO 27 & 50 Electronic Trip Unit MPRO 27 & 50 Electronic Trip Unit

MPRO 27 & 50 Electronic Trip Unit MPRO 27 & 50 Electronic Trip Unit

- Time Current CurveHSIOC - Protection DeviceI - Present & ON

- Time Current CurveHSIOC - Protection DeviceI - NOT PESENY OR OFF ONI Setting On

sei at 15kA ST Ser at 12,5kASTDB 1

50 kA

100kA

85kA

65kA

50kA

65 kA

85 kA

100 kA

Green Iine = Full Clearing timeRed Line = Non Tripping time

Green Iine = Full Clearing timeRed Line = Non Tripping time

1

0,1

0,01

0,01

1000 10000 100000 10000,00

Trip

ping

Tim

e In

Sec

onds

(s)

Amps

1

0,1

0,01

0,01

1000 10000 100000 10000,00

Trip

ping

Tim

e In

Sec

onds

(s)

Amps

1,00 10,00

10

0,8

0,6

0,4

0,2

0,1

0,01

0,10

Trip

ping

Tim

e In

Sec

onds

(s)

x Breaker rating In1,00 10,00

10

0,8

0,6

0,4

0,2

0,1

0,01

0,10

Trip

ping

Tim

e In

Sec

onds

(s)

x Breaker rating In

GF set on breaker rating In

0,2 to 1 × In in steps of 0,01Setting Range

GF set on breaker rating In

0,2 to 1 × In in steps of 0,01Setting Range

- Time Current Curve

- Band GFDB 01- Band GFDB 03- Band GFDB 05- Band GFDB 07- Band GFDB 09- Band GFDB 11- Band GFDB 13

GF- Protection Device

I2t -OFF-

- Time Current Curve

- Band GFDB 02- Band GFDB 04- Band GFDB 06- Band GFDB 08- Band GFDB 10- Band GFDB 12- Band GFDB 14

GF- Protection Device

I2t -OFF-

1314 14

1212

1010

8

8

6

6

4

4

2

2

13

11

9

7

5

3

1

11

9

7

5

3

1

Green Iine = Full Clearing timeRed Line = Non Tripping time

Green Iine = Full Clearing timeRed Line = Non Tripping time

Time Current Curves

Page 18: Ge - Mpact Mpro Acb ( 400a - 4000a )

M-PACT

A.17 Technical overview

Time Current Curves (cold state)GF Protection Device

MPRO 27 & 50 Electronic Trip Unit MPRO 27 & 50 Electronic Trip Unit

MPRO 27 & 50 Electronic Trip Unit MPRO 27 & 50 Electronic Trip Unit

1,00 10,00

10

1

0,8

0,6

0,4

0,2

0,1

0,01

0,10

Trip

ping

Tim

e In

Sec

onds

(s)

x Breaker rating In

1,00 10,00

10

1

0,8

0,6

0,4

0,2

0,1

0,01

0,10

Trip

ping

Tim

e In

Sec

onds

(s)

x Breaker rating In1,00 10,00

10

1

0,8

0,6

0,4

0,2

0,1

0,01

0,10

Trip

ping

Tim

e In

Sec

onds

(s)

x Breaker rating In

1,00 10,00

10

0,8

0,6

0,4

0,2

0,1

0,01

0,10

Trip

ping

Tim

e In

Sec

onds

(s)

x Breaker rating In

GF set on breaker rating In

0,2 to 1 × In in steps of 0,01Setting Range

GF set on breaker rating In

0,2 to 1 × In in steps of 0,01Setting Range

GF set on breaker rating In

0,2 to 1 × In in steps of 0,01Setting Range

- Time Current Curve

- Band GFDB 01- Band GFDB 03- Band GFDB 05- Band GFDB 07- Band GFDB 09- Band GFDB 11- Band GFDB 13

GF- Protection Device

I2t “low” -ON-

- Time Current Curve

- Band GFDB 02- Band GFDB 04- Band GFDB 06- Band GFDB 08- Band GFDB 10- Band GFDB 12- Band GFDB 14

GF- Protection Device

I2t “low” -ON-

13

1313

11

9

7

5

3

1

11

9

7

5

3

1

1414

1212

1010

8

6

4

2

8

6

4

2

14 14

12

10

8

6

4

2

12

10

8

6

4

2

11

9

7

5

3

1

13

11

9

7

5

3

1

Green Iine = Full Clearing timeRed Line = Non Tripping time

Green Iine = Full Clearing timeRed Line = Non Tripping time

Green Iine = Full Clearing timeRed Line = Non Tripping time

Green Iine = Full Clearing timeRed Line = Non Tripping time

- Time Current Curve

- Band GFDB 01- Band GFDB 03- Band GFDB 05- Band GFDB 07- Band GFDB 09- Band GFDB 11- Band GFDB 13

GF- Protection Device

I2t “med” -ON-

GF set on breaker rating Inv

0,2 to 1 × In in steps of 0,01Setting Range

- Time Current Curve

- Band GFDB 02- Band GFDB 04- Band GFDB 06- Band GFDB 08- Band GFDB 10- Band GFDB 12- Band GFDB 14

GF- Protection Device

I2t “med” -ON-

Page 19: Ge - Mpact Mpro Acb ( 400a - 4000a )

A.18Technical overview

Time Current Curves (cold state)GF Protection Device

MPRO 27 & 50 Electronic Trip Unit

1,00 10,00

MPRO 27 & 50 Electronic Trip Unit10

1

0,8

0,6

0,4

0,2

0,1

0,01

0,10

Trip

ping

Tim

e In

Sec

onds

(s)

x Breaker rating In1,00 10,00

1

0,8

0,6

0,4

0,2

0,1

0,01

0,10

Trip

ping

Tim

e In

Sec

onds

(s)

x Breaker rating In

GF set on breaker rating In

0,2 to 1 × In in steps of 0,01Setting Range

GF set on breaker rating In

0,2 to 1 × In in steps of 0,01Setting Range

- Time Current Curve

- Band GFDB 01- Band GFDB 03- Band GFDB 05- Band GFDB 07- Band GFDB 09- Band GFDB 11- Band GFDB 13

GF- Protection Device

I2t “max” -ON-

- Time Current Curve

- Band GFDB 02- Band GFDB 04- Band GFDB 06- Band GFDB 08- Band GFDB 10- Band GFDB 12- Band GFDB 14

GF- Protection Device

I2t “max” -ON-

1313

11

9

7

5

3

1

11

9

7

5

3

1

14

12

10

8

6

4

4

6

8

10

12

14

2

2

Green Iine = Full Clearing timeRed Line = Non Tripping time

Green Iine = Full Clearing timeRed Line = Non Tripping time

Time Current Curves

Page 20: Ge - Mpact Mpro Acb ( 400a - 4000a )

M-PACT

A.19 Technical overview

M-PACT accessories Shunt trip

Undervoltage release

Auxiliary trip combination

Motorised spring charging unit

Circuit breaker closing coil

A wide range of optional accessories have been developed that are compatible with all M-PACT air circuit breakers, regardless of nominal rating or frame size. Each one incorporates 'easy-fit' design features for quick installation, either in the factory or by the user on site.

Energisation, locally or remote, will instantaneously activate the circuit breaker mechanism, ensuring rapid disconnection of the main contacts.

In addition, a series connected auxiliary switch ensures automatic isolation whenever the circuit breaker is open.

Shunt trip releases also have a wide operational voltage range, and they include the same easy-fit, clip-on/plug-in connectors as the closing coil above.

Instantaneously releases the circuit breaker trip mechanism should the supply voltage dip below the pre-set value.

Simple to install, these devices have the same easy-fit features as previously described.

Note: This is a 'no-volt/ no-close device. The circuit breaker cannot be closed (manually or electrically) unless the undervoltage release coil is energised.

Time delay undervoltage release similar to the above, but this electronic device prevents nuisance tripping of the circuit breaker if circuit interruption is not desirable when supply voltage drop is only transient. Fixed time delay 3 sec ±1sec.

The M-PACT circuit breaker can be equipped with the following auxiliary trips or releases 1 x Shunt trip + 1 x Closing coil + 1 x Undervoltage release or 1 time delay Undervoltage release.

The unique motor/gearbox unit is specially designed to operate with the full range of M-PACT breakers.

It is easily fitted with just two bolts. In the event of circuit breaker closure, this unit will automatically recharge the spring in readiness for instant reclosure should the need arise.

High speed recharging ensures that the springs are fully charged within approximately three seconds following a release.

As an optional feature, a "springs charged" contact is available for the motor unit.

The closing coil is an easy-to-fit, clip-on unit, with simple plug-in connectors. This permits either local or remote release of the spring charged closing mechanism by electrical operation.

An additional anti-pumping safety feature also ensures that the electrical closing signal must be released before further closure is attempted, and a cut-off is instigat-ed should a closing signal be maintained.

Because each coil operates within a wide voltage range, the number of individually rated coils required is drastically reduced.

Page 21: Ge - Mpact Mpro Acb ( 400a - 4000a )

A.20Technical overview

Auxiliary switches Cassette main terminal adaptors

Mechanical operation counter

Key interlock facility

The M-PACT circuit breaker is equipped with 5 NO and 3 NC auxiliary switches as standard. Maximum number of contacts is 8, for alternative configurations please contact for availability.

Combinations of rear and front access connections possible for entire range. Tested and approved from 50 to 80kA.

To simplify main busbar or cable termination, M-Pact provides a full range for rear and/or front access connection.

Bolt-on adaptor kits can be fitted easily to suit either horizontal or vertical connections.

Easily fitted, this useful accessory may be specified for use with either manual or motor charged M-PACT circuit breakers.

It is clearly visible through the front panel, and the counter provides an accurate record of the cumulative number of complete breaker closing operations.

Ready-to-fit interlocking device: Ronis, for installation betweenseparate circuit breakers, available in kit form.

This valuable safeguard ensures that a circuit breaker cannot be closed unless the dedicated key has been inserted and secured within the lock.

Lock and key types

Ronis: Type 1104B lock with standard key, 1/4" turn rotation to trap the key, compulsory spindle size.

M-PACT Accessories

Page 22: Ge - Mpact Mpro Acb ( 400a - 4000a )

M-PACT

A.21 Technical overview

Cable/busbar earthing device Cluster contacts

Carriage position switch

2/3 way cable mechanicalinterlocks

All 'M-PACT' circuit breakers can be fitted with an earthing device. It has a short circuit fault capacity equal to the Icw rating of the breaker. This permits either the feeder cables or the busbar to be safety held at earthed potential and locked during system maintenance operations.

These are the main isolating contacts which are fitted to the rear terminals on the moving portion of the withdrawable unit.

As part of standard inspection and maintenance procedures, cluster contacts have been designed to be easily and quickly removed and replaced using universal cluster pliers.

Available for fixed and withdrawable circuit breakers. These units enable the direct interlocking of M-PACT circuit breakers, either mounted side-by-side or stacked. The interlocking mechanisms are connected by a specially designed cable in '1 from 3' OR '2 from 3' configuration, and any mix of current ratings / pole configurations can be accommodated.

Standard cable lengths available: 1.6, 2.0, 3.0 metres. (Please contact our technical customer service department if longer length is required.)

Available as an optional device for mounting within the base of the cassette, this switch provides six single pole changeover contacts for local or remote electrical indication of the circuit breaker status: Connected, Test and Disconnected.

The Disconnected position is indicated only when minimum isolating distances between contacts on both the main and auxiliary circuits have been achieved.

This option is in addition to the mechanical indicators which are fitted as standard.

When installed, the carriage switch is IP2X protected and includes wiring to a terminal block located on the left-hand side of the cassette.

Note: The carriage position switch is an option only suitable for withdrawable circuit breakers.

Page 23: Ge - Mpact Mpro Acb ( 400a - 4000a )

A.22Technical overview

InterlocksMechanical interlocks can be fitted to the following electrical systems and can link 2 or 3 circuit breakers of anyrating or number of poles, Fixed or Withdrawable.

Typical circuit Interlock configuration Possible combinations

Type AInterlocking between 2 circuit breakers

B1 normal power supplyB2 generator (emergency) supply

B1 B20 0I 00 I

Circuit breaker B1 can only close if B2 is openCircuit breaker B2 can only close if B1 is open

Type BInterlocking between 3 circuit breakers

3 power supplies (generator ortransformers) feeding the samebusbar but parallel operation is prevented.

Available upon request.

B1 B2 B30 0 0I 0 00 I 00 0 I

Only 1 from 3 breakers can be closed

Type CInterlocking between 3 circuit breakers

2 bus sections can be powered by asingle transformer (bus couplerclosed) or by both transformers(bus coupler open).

Available upon request.

B1 B2 B30 0 0I 0 00 I 00 0 II 0 I0 I II I 0

Any 2 from 3 circuit breakers can be closedAny 1 from 3 circuit breakers can be closed

M-PACT Accessories

Page 24: Ge - Mpact Mpro Acb ( 400a - 4000a )

M-PACT

A.23 Technical overview

Circuit breaker insertion interlock Circuit breaker handling truck

Cassette interlock

Sealeddoor panelescutcheonAn optional IP54 complete front door panel is available should a higher degree of protection be necessary.

By incorporating this optional security interlock device into a system, it prevents the inadvertent insertion of an incorrectly rated withdrawable circuit breaker into a cassette.

Avai lable for withdrawable c ircuit breakers only, th is sophisticated interlock system secures the circuit breaker in thedisconnected position by means of a Ronis key.

When the key is removed, the safety shutters are automatically locked in position, thus preventing access to the contacts and also ensuring that the racking mechanism is not operable. For lock and key details refer to key interlock facility section (p. A.21)

Specifically designed for use with the M-PACT range, this dedicated handling truck is a useful accessory when faced with the task of inserting or removing the circuit breaker from its panel, or when transporting the unit should it be outside its cassette. Installers will also find it particularly valuable for top-tier mounted circuit breakers.

Page 25: Ge - Mpact Mpro Acb ( 400a - 4000a )

A.24Technical overview

Accessories Performance Data

DeviceOperating Voltage (V) Rating

(Amps resistive)AC DC Operating range

Auxiliary & carriage switch250 - 10

125 - 5250 - 0.25

Motor operator

220-250 220-250AC-50VADC-50W

110-130 110-130380-440 48, 60 0.85 to 1.1 times

24-30 rated voltage

Closing coil

220-250 220-250AC-300VADC-250W

110-130 110-130380-440 48 0.85 to 1.1 times

24-30 rated voltage

Shunt trip

220-250 220-250AC-300VADC-250W

110-130 110-130380-440 48 0.70 to 1.1 times

24-30 rated voltage

Instantanious Undervoltage release

380-440 110-130 -Inrush power consumption 300VAHolding power consumption 20VA

220-250 30-48 -110-130 -

Auxiliary power unit 110, 220, 380 110, 220 - -

Plug-in Portable Test Unit (PTU) Auxiliary Power Unit (APU)

Specially designed for reliable testing of the MCR and HSISCprotection systems on each phase, by means of tertiaryinjection. The test unit is also used to prove both overcurrentand earth fault pick-up levels. Can also be employedto test for tripping in order to verify efficient microprocessoroperation. The test unit incorporates a set of rechargeablebatteries and includes a charger unit as standard.

Available to be fitted within the circuit breaker cubicle, anAPU ensures that M-PRO receives independent and continuous power at all times. The APU accepts any input supply voltage within 380VAC, 110V, 220V AC/DC. Maximuminput current is 0.5 A. 1m length cable (twisted pair) shouldbe used to connect auxiliary supply and MPRO protectionrelay.

M-PACT Accessories

Page 26: Ge - Mpact Mpro Acb ( 400a - 4000a )

M-PACTAir Circuit Breaker 400-4000A

Page 27: Ge - Mpact Mpro Acb ( 400a - 4000a )

BMpro 27 & 50 Connection ....................................................................................................................................................................B.2

Dimensional Drawings ...........................................................................................................................................................................B.6

Wiring DiagramsDimensional Drawings

Page 28: Ge - Mpact Mpro Acb ( 400a - 4000a )

B.2 Wiring Diagrams - Dimensional Drawings

M-PACT

Connection scheme

N-RC

A15 A14

N-RC- +

N

B 5 B 6

24V+ 24V-

+24-VDC

Electronic Trip Unit MPRO 27

Connection scheme

Relay O/P2

A 6 A 5

Relay O/P1

A 8 A 7

Electronic Trip Unit MPRO 50

N-RC

A15 A14

N-RC- +

N

Relay O/P3 Relay O/P4

A 2 A 1A 4 A 3 B 5 B 6

24V+ 24V-

+24-VDC

EL CT

B 3 B 4

Interposing CT

A12 A11 A10 A 9

1 2 3 4

Input 1 - 4

A13

C

A20 A19

RX- RX+

Communication

A16

SCR

A18 A17

TX- TX+

N

Breaker accessories

OFF ONOFF

C15

AAAAABBBAA

C

D

MLAL

M ST CC UVRUVTD

C13

C11

C9C7C5C3C1

B15

B13

(+VE)(-VE)

B11

C16

C14

C12

C10

LP6

LP5

LP7

C8C6C4C2

B16

B14

(-VE)

B12

B10

B8

LP4

B9B7

(+VE)

B1B2

Mpro 27 & 50 Connection Scheme

Wiring Diagrams

Page 29: Ge - Mpact Mpro Acb ( 400a - 4000a )

B.3Wiring Diagrams - Dimensional Drawings

Dimensional DrawingsHorizontal, rear access connectionFixed patternType A-3 pole- Frame size 1, In=400A to 1600A

Type A-4 pole- Frame size 1, In=400A to 1600A

100 to door

100

Centre line of operating panel

Centre line of operating panel

Centre line ofoperating panel

Centre line ofoperating panel

Copperwork must be supported within 200 mm of breakerconnections-busbars or cables. All connections to be tightened to 50Nm.

Copperwork must be supported within 200 mm of breakerconnections-busbars or cables. All connections to be tightened to 50Nm.

Minimum space to earth metaland for arc chute removal

Minimum space to earth metaland for arc chute removal

Insulated metal or insulatedsheet ( customer supplied )

Insulated metal or insulatedsheet ( customer supplied )

Dimensional Drawings

Page 30: Ge - Mpact Mpro Acb ( 400a - 4000a )

B.4 Wiring Diagrams - Dimensional Drawings

M-PACT

Horizontal, rear access connectionFixed patternType D-3 pole- Frame size 1, In=400A to 1600A

100 to door

100 to door

Centre line of operating panel

Centre line of operating panel

Centre line ofoperating panel

Centre line ofoperating panel

Copperwork must be supported within 200 mm of breakerconnections-busbars or cables. All connections to be tightened to 50Nm.

Copperwork must be supported within 200 mm of breakerconnections-busbars or cables. All connections to be tightened to 50Nm.

Minimum space to earth metaland for arc chute removal

Minimum space to earth metaland for arc chute removal

Insulated metal or insulatedsheet ( customer supplied )

Insulated metal or insulatedsheet ( customer supplied )

Type D-4 pole- Frame size 1, In=400A to 1600A

Page 31: Ge - Mpact Mpro Acb ( 400a - 4000a )

B.5Wiring Diagrams - Dimensional Drawings

100 to door

100 to door

Horizontal, rear access connectionFixed patternType A, D-3 pole- Frame size 1, In=2000A to 2500A

Centre line of operating panel

Centre line of operating panel

Centre line ofoperating panel

Centre line ofoperating panel

Copperwork must be supported within 200 mm of breakerconnections-busbars or cables. All connections to be tightened to 50Nm.

Copperwork must be supported within 200 mm of breakerconnections-busbars or cables. All connections to be tightened to 50Nm.

Minimum space to earth metaland for arc chute removal

Minimum space to earth metaland for arc chute removal

Insulated metal or insulatedsheet ( customer supplied )

Insulated metal or insulatedsheet ( customer supplied )

Type A, D-4 pole- Frame size 1, In=2000A to 2500A

Dimensional Drawings

Page 32: Ge - Mpact Mpro Acb ( 400a - 4000a )

B.6 Wiring Diagrams - Dimensional Drawings

M-PACT

Horizontal, rear access connectionFixed patternType A, D-3 pole- Frame size 2, In=3200A to 4000AType H-3 pole- Frame size 2, In=800A to 4000A

100 to door

100 to door

Centre line of operating panel

Centre line of operating panel

Centre line ofoperating panel

Centre line ofoperating panel

Copperwork must be supported within 200 mm of breakerconnections-busbars or cables. All connections to be tightened to 50Nm.

Copperwork must be supported within 200 mm of breakerconnections-busbars or cables. All connections to be tightened to 50Nm.

Minimum space to earth metaland for arc chute removal

Minimum space to earth metaland for arc chute removal

Insulated metal or insulatedsheet ( customer supplied )

Insulated metal or insulatedsheet ( customer supplied )

Type A, D-4 pole- Frame size 2, In=3200A to 4000AType H-4 pole- Frame size 2, In=800A to 4000A

Page 33: Ge - Mpact Mpro Acb ( 400a - 4000a )

B.7Wiring Diagrams - Dimensional Drawings

Rear access connectionWithdrawable patternType A-3 pole- Frame size 1, In=400A to 1600A

Copperwork must be supported within 200 mm of breakerconnections-busbars or cables. All connections to be tightened to 50Nm.

Copperwork must be supported within 200 mm of breakerconnections-busbars or cables. All connections to be tightened to 50Nm.

Centre line of operating panel

Centre line of operating panel

35 Test50 Disconnected

275 Fully withdrawn

Connected

Ventilation

Minimum clearanceto cassette side

Centre line of operating panel

Centre line of operating panel

35 Test50 Disconnected

275 Fully withdrawn

Connected

Ventilation

Minimum clearanceto cassette side

to door

to door

Type A-4 pole- Frame size 1, In=400A to 1600A

Dimensional Drawings

Page 34: Ge - Mpact Mpro Acb ( 400a - 4000a )

B.8 Wiring Diagrams - Dimensional Drawings

M-PACT

Rear access connectionWithdrawable patternType A-3 pole- Frame size 1, In=2000A & 2500AType D-3 pole- Frame size 1, In=400A to 2500A

Type A-4 pole- Frame size 1, In=2000A & 2500AType D-4 pole- Frame size 1, In=400A to 2500A

Copperwork must be supported within 200 mm of breakerconnections-busbars or cables. All connections to be tightened to 50Nm.

Copperwork must be supported within 200 mm of breakerconnections-busbars or cables. All connections to be tightened to 50Nm.

Centre line of operating panel

Centre line of operating panel

35 Test

50 Disconnected

275 Fully withdrawn

Connected

Ventilation

Minimum clearanceto cassette side

Centre line of operating panel

Centre line of operating panel

35 Test

50 Disconnected275 Fully withdrawn

Connected

Ventilation

Minimum clearanceto cassette side

to door

to door

Page 35: Ge - Mpact Mpro Acb ( 400a - 4000a )

B.9Wiring Diagrams - Dimensional Drawings

Rear access connectionWithdrawable patternType A, D-3 pole- Frame size 2, In=3200AType H-3 pole- Frame size 2, In=800A to 3200A

Type A, D-4 pole- Frame size 2, In=3200AType H-4 pole- Frame size 2, In=800A to 3200A

Copperwork must be supported within 200 mm of breakerconnections-busbars or cables. All connections to be tightened to 50Nm.

Copperwork must be supported within 200 mm of breakerconnections-busbars or cables. All connections to be tightened to 50Nm.

to door

to door

Center line ofoperating panel

Center line ofoperating panel

Center line ofoperating panel

Center line ofoperating panel

50 Disconnected35 Test

275 Fully withdrawn

50 Disconnected35 Test

275 Fully withdrawn

Connected

Connected

Vent

ilatio

nVentilation

Minimum clearance to cassette side

Minimum clearance to cassette side

Dimensional Drawings

Page 36: Ge - Mpact Mpro Acb ( 400a - 4000a )

B.10 Wiring Diagrams - Dimensional Drawings

M-PACT

Rear access connectionWithdrawable pattern

Type A, D,H-3 pole - Frame size 2, ln=4000A

Type A, D,H-4 pole - Frame size 2, ln=4000A

Must not be removedor fitted horizontally

Must not be removedor fitted horizontally

Center line ofoperating panel

Center line ofoperating panel

Center line ofoperating panel

Center line ofoperating panel 50 Disconnected

35 Test

275 Fully withdrawn

50 Disconnected35 Test

275 Fully withdrawn

Connected

Connected

to d

oor

to d

oor Ventilation

Vent

ilatio

n

Minimum clearance to cassette side

Minimum clearance to cassette side

Copperwork must be supported within 200 mm of breakerconnections-busbars or cables. All connections to be tightened to 50Nm.

Copperwork must be supported within 200 mm of breakerconnections-busbars or cables. All connections to be tightened to 50Nm.

Page 37: Ge - Mpact Mpro Acb ( 400a - 4000a )

B.11Wiring Diagrams - Dimensional Drawings

Front access connectionFixed pattern

Type A, D-3 pole - Frame size 1, ln = 400A to 1600A

Type A, D-4 pole - Frame size 1, ln = 400A to 1600A

Center line ofoperating panel

Center line ofoperating panel

Center line ofoperating panel

Center line ofoperating panel

Insulated metalor insulated sheet(customer supplied)

Insulated metalor insulated sheet(customer supplied)

Minimum space to earth metaland for arc chute removal

Minimum space to earth metaland for arc chute removal

100 to door

100 to door

Minimum clearance to breaker side

Minimum clearance to breaker side

Copperwork must be supported within 200 mm of breakerconnections-busbars or cables. All connections to be tightened to 50Nm.

Copperwork must be supported within 200 mm of breakerconnections-busbars or cables. All connections to be tightened to 50Nm.

Dimensional Drawings

Page 38: Ge - Mpact Mpro Acb ( 400a - 4000a )

B.12 Wiring Diagrams - Dimensional Drawings

M-PACT

Front access connectionFixed pattern

Type A, D-3 pole - Frame size 1, ln = 2000A to 2500A

Insulated metalor insulated sheet(customer supplied)

Minimum space to earth metaland for arc chute removal

100 to door

Insulated metalor insulated sheet(customer supplied)

Minimum space to earth metaland for arc chute removal

100 to door

Center line ofoperating panel

Center line ofoperating panel

Center line ofoperating panel

Center line ofoperating panel

Minimum clearance to breaker side

Minimum clearance to breaker side

Copperwork must be supported within 200 mm of breakerconnections-busbars or cables. All connections to be tightened to 50Nm.

Copperwork must be supported within 200 mm of breakerconnections-busbars or cables. All connections to be tightened to 50Nm.

Type A, D-4 pole - Frame size 1, ln = 2000A to 2500A

Page 39: Ge - Mpact Mpro Acb ( 400a - 4000a )

B.13Wiring Diagrams - Dimensional Drawings

Front access connectionFixed pattern

Type A, D-3 pole - Frame size 2, ln = 3200A to 4000AType H-3 pole - Frame size 2, ln = 800A to 4000A

Insulated metalor insulated sheet(customer supplied)

Minimum space to earth metaland for arc chute removal

100 to door

Insulated metalor insulated sheet(customer supplied)

Minimum space to earth metaland for arc chute removal

100 to door

Center line ofoperating panel

Center line ofoperating panel

Center line ofoperating panel

Center line ofoperating panel

Minimum clearance to breaker side

Minimum clearance to breaker side

Copperwork must be supported within 200 mm of breakerconnections-busbars or cables. All connections to be tightened to 50Nm.

Copperwork must be supported within 200 mm of breakerconnections-busbars or cables. All connections to be tightened to 50Nm.

Front Access Connection

Type A, D-4 pole - Frame size 2, ln = 3200A to 4000AType H-4 pole - Frame size 2, ln = 800A to 4000A

Page 40: Ge - Mpact Mpro Acb ( 400a - 4000a )

B.14 Wiring Diagrams - Dimensional Drawings

M-PACT

Center line ofoperating panel

Center line ofoperating panel

Center line ofoperating panel

Center line ofoperating panel

Minimum clearance to cassette side

Minimum clearance to cassette side

Connected

Connected

Disconnected

Disconnected

Test

Test

to d

oor

to d

oor

Copperwork must be supported within 200 mm of breakerconnections-busbars or cables. All connections to be tightened to 50Nm.

Copperwork must be supported within 200 mm of breakerconnections-busbars or cables. All connections to be tightened to 50Nm.

Front access connectionWithdrawable pattern

Type A, D-3 pole - Frame size 1, ln = 400A to 1600A

Type A, D-4 pole - Frame size 1, ln = 400A to 1600A

Page 41: Ge - Mpact Mpro Acb ( 400a - 4000a )

B.15Wiring Diagrams - Dimensional Drawings

Front access connectionWithdrawable pattern

Type A, D-3 pole - Frame size 1, ln = 2000A to 2500A

Center line ofoperating panel

Center line ofoperating panel

Center line ofoperating panel

Center line ofoperating panel

Minimum clearance to cassette side

Minimum clearance to cassette side

Connected

Connected

Disconnected

Disconnected

Test

Test

to d

oor

to d

oor

Copperwork must be supported within 200 mm of breakerconnections-busbars or cables. All connections to be tightened to 50Nm.

Copperwork must be supported within 200 mm of breakerconnections-busbars or cables. All connections to be tightened to 50Nm.

Front Access Connection

Type A, D-4 pole - Frame size 1, ln = 2000A to 2500A

Page 42: Ge - Mpact Mpro Acb ( 400a - 4000a )

B.16 Wiring Diagrams - Dimensional Drawings

M-PACT

Front access connectionFixed pattern

Type A, D-3 pole - Frame size 2, ln = 3200A to 4000AType H-3 pole - Frame size 2, ln = 800A to 4000A

Center line ofoperating panel

Center line ofoperating panel

Center line ofoperating panel

Center line ofoperating panel

Minimum clearance to cassette side

Minimum clearance to cassette side

Connected

Connected

DisconnectedTest

DisconnectedTest

to d

oor

to d

oor

Copperwork must be supported within 200 mm of breakerconnections-busbars or cables. All connections to be tightened to 50Nm.

Copperwork must be supported within 200 mm of breakerconnections-busbars or cables. All connections to be tightened to 50Nm.

Type A, D-4 pole - Frame size 2, ln = 3200A to 4000AType H-4 pole - Frame size 2, ln = 800A to 4000A

Page 43: Ge - Mpact Mpro Acb ( 400a - 4000a )

B.17Wiring Diagrams - Dimensional Drawings

Adaptor connections

Rear Adapter Vertical ConnectionType A - Frame 1 - ln = 400A to 1600A (max)

Rear Adapter Horizontal ConnectionType A - Frame 1 - ln = 400A to 1600A (max)

Type D - Frame 1 - ln = 400A to 2500A (max)

Rear Adapter Vertical / Horizontal Connection

Type A,D,H - Frame 2 - ln = 800A to3200A (max)

Front Access Connection

Page 44: Ge - Mpact Mpro Acb ( 400a - 4000a )

B.18 Wiring Diagrams - Dimensional Drawings

M-PACT

Type A - Frame 1 - ln = 400A to 2500A (max)Type D - Frame 1 - ln = 400A to 2500A (max)

Type A,D - Frame 2 - ln = 3200A to 4000A (max)Type H - Frame 2 - ln = 800A to 4000A (max)

Type A,D,H - Frame 2 - ln = 4000A

Copper connections - Rear access (withdrawable)

IP54 Door (Withdrawable unit only - Frame 1&2 only)

Copper connections - Front access (Fixed and/or withdrawable)

Page 45: Ge - Mpact Mpro Acb ( 400a - 4000a )

B.19Wiring Diagrams - Dimensional Drawings

Type A,D - Frame 2 - ln = 3200A to 4000A (max)Type H - Frame 2 - ln = 800A to 4000A (max)

A. recommend installtion mounting cut

Cassette mounting details

Type A,D - Frame 1 - ln = 400A to 2500A (max)

Terminals

Terminals

Ventilation in base of cassette(leave unobstructed)

Ventilation in base of cassette(leave unobstructed)

Centre line ofoperating panel

Centre line ofoperating panel

3 pole

3 pole 4 pole

4 pole3 pole

4 pole

4 pole

4 pole

3 pole

3 pole

AA

A

A

A A

A

A

Adaptor Connection

Page 46: Ge - Mpact Mpro Acb ( 400a - 4000a )

B.20 Wiring Diagrams - Dimensional Drawings

M-PACT

Door cut-outs

Fixed pattern - Facia cut-out

Withdrawable pattern - Cubicle door/panel

Frame 1 = 42.5Frame 2 = 102.5

The cut-out dimensions shown above givean approximate nominal clearance of 30mm aroundACB fascia. These sizes are for guidanceand can be scaled if different apertureis required.

Escutcheon(LLA11PD055)

Escutcheon seal(LLA11RS001)

ACB facia16 off 3.0 6Self tapping screws

Frame 1 - Up to 2500A max.= 40Frame 2 - Up to 4000A max.= 100

Datum for 16 off 4 holes in door / panel - bottom left hand comer of cassette viewed from front.

Page 47: Ge - Mpact Mpro Acb ( 400a - 4000a )

B.21Wiring Diagrams - Dimensional Drawings

2-Way cable interlocking

Fixed pattern - Front/rear access

Withdrawable pattern - Front/rear access

Min.clearancebelowcassette

Min.clearancebelowcassette

Min.bend radius 120

Min.bend radius 120 Min.bend radius 120

Min.bend radius 120

900

Max

ver

tical

bas

e to

bas

e90

0 M

ax v

ertic

al b

ase

to b

ase

Frame 1-3P = 322Frame 1-4P = 422Frame 2-3P = 410Frame 2-4P = 540

Frame 1-3P = 329Frame 1-4P = 429Frame 2-3P = 419Frame 2-4P = 549

Door Cut-outs

Page 48: Ge - Mpact Mpro Acb ( 400a - 4000a )