GAS FURNACES SL280UHV DAVE LENNOX SIGNATURE ® COLLECTION Upflow / Horizontal - Two-Stage Heat - Variable Speed Blower Bulletin No. 210575 May 2011 Supersedes December 2010 AFUE - 80% Input - 66,000 to 132,000 Btuh Nominal Add-on Cooling - 2 to 5 Tons SL 2 80 UH 070 X V 36 B Unit Type SL = Dave Lennox Signature ® Collection Stages 2 = Two-Stage Nominal Gas Heat Input 070 = 66,000 Btuh 090 = 88,000 Btuh 110 = 110,000 Btuh 135 = 132,000 Btuh Blower V = Variable Speed Blower Motor Nominal Add-On Cooling Capacity 36 = 2-3.5 tons 48 = 4 tons 60 = 4-5 tons Configuration UH = Upflow/Horizontal MODEL NUMBER IDENTIFICATION 1 Indoor coils with the same letter designation will physically match the furnace. 1 Cabinet Width A = 14-1/2 in. B = 17-1/2 in. C = 21 in. D = 24-1/2 in. AFUE 80 = 80% Low NO x = Units meet California Nitrogen Oxides standards PRODUCT SPECIFICATIONS

Upload: others

Post on 09-Apr-2020

2 views

Category:

Documents


0 download

TRANSCRIPT

G A S F U R N A C E S

SL280UHVDAVE LENNOX SIGNATURE® COLLECTION

Upflow / Horizontal - Two-Stage Heat - Variable Speed BlowerBulletin No. 210575

May 2011Supersedes December 2010

AFUE - 80%Input - 66,000 to 132,000 Btuh

Nominal Add-on Cooling - 2 to 5 Tons

SL 2 80 UH 070 X V 36 B

Unit TypeSL = Dave Lennox Signature® Collection

Stages2 = Two-Stage

Nominal Gas Heat Input070 = 66,000 Btuh090 = 88,000 Btuh

110 = 110,000 Btuh135 = 132,000 Btuh

BlowerV = Variable Speed Blower Motor

Nominal Add-On Cooling Capacity36 = 2-3.5 tons48 = 4 tons60 = 4-5 tons

ConfigurationUH = Upflow/Horizontal

MODEL NUMBER IDENTIFICATION

1 Indoor coils with the same letter designation will physically match the furnace.

1 Cabinet WidthA = 14-1/2 in.B = 17-1/2 in.C = 21 in.D = 24-1/2 in.

AFUE80 = 80%

Low NOx = Units meet CaliforniaNitrogen Oxides standards

P R O D U C T S P E C I F I C AT I O N S

SL280UHV / Page 2

WARRANTY

Duralok™ Aluminized Steel Heat Exchanger - Limited twenty year warranty in residential applications, ten years in non-residential applications.All other covered components - Limited ten year warranty in residential applications, one year in non-residential applications.Refer to Lennox Equipment Limited Warranty certificate included with equipment for details.

APPROVALS

Units are certified by AHRI.Units tested and rated according to US DOE test procedures and FTC labeling regulations.“X” models approved by the California Energy Commission and meet California Seasonal Efficiency requirements and California Nitrogen Oxides (NOx) Standards.ISO 9001 Registered Manufacturing Quality System.Blower data from unit tests conducted in Lennox Laboratory air test chamber.

APPLICATIONS

Input capacities of 66,000, 88,000, 110,000 and 132,000 Btuh.Energy efficiency (AFUE) of 80%.Compact cabinet for upflow, horizontal-left or horizontal-right applications.Utility room, alcove, closet, crawl space, basement or attic installation.Lennox add-on indoor coils, high-efficiency air cleaners and humidifiers can easily be added to furnace.Shipped factory assembled with all controls installed and wired.Ready for installation in upflow or horizontal right-hand position without any modifications. Horizontal left-hand requires repositioning of pressure switch. Removable bottom seal panel shipped in place for side return air is easily removed for bottom/end return air applications.Each unit factory test operated to ensure proper operation.Zoning ApplicationsUnits may be used with certain zoning systems.Zone control panel must be able to interface and communicate with the variable speed blower motor in the unit. The Harmony III™ Zoning System has this capability.

FEATURES

Contents

Blower Data . . . . . . . . . . . . . . . . . . . . . . 13Dimensions − Furnace/Coil Combined . . . . . . . . 12Dimensions - Horizontal Position . . . . . . . . . . . 10Dimensions - Upflow Position. . . . . . . . . . . . . 9Features. . . . . . . . . . . . . . . . . . . . . . . . 2Gas Heat Accessories . . . . . . . . . . . . . . . . 8High Altitude Derate. . . . . . . . . . . . . . . . . . 8Installation Clearances . . . . . . . . . . . . . . . . 6Model Number Identification . . . . . . . . . . . . . 1Optional Accessories . . . . . . . . . . . . . . . . . 8Optional Accessory Dimensions . . . . . . . . . . . 11Specifications . . . . . . . . . . . . . . . . . . . . . 7

B

C

I

H

D

EG

F

J

K

L

M

NOTE - SL280UHV FURNACES ARE NOT AVAILABLE IN CANADA!

SL280UHV / Page 3

HEATING SYSTEM

SilentComfort™ TechnologyPatent pending burner sound enclosure and extra cabinet insulation reduces operating sound levels.Lennox Duralok™ Heat Exchanger Assembly

Heavy gauge aluminized steel heat exchanger.Crimped seam clamshell type design.Designed for normal expansion and contraction.Minimum resistance to air flow.Heat exchanger has

been laboratory life cycle tested in excess of industry standards.Compact size of heat exchanger permits low overall design of furnace cabinet.Inshot BurnersAluminized steel inshot burners provide efficient, trouble-free operation.Burner venturi mixes air and gas in correct proportion for proper combustion.Burner assembly is removable from the unit as a single component for ease of service.SureLight® Hot Surface IgnitorTough, reliable, long-life, trouble-free performance.Nitride ignitor.Cemented to steatite block for protection against current leakage.Ignition leads constructed of nickel plated copper enclosed in high temperature Teflon® insulation for dependable operation.Two-Stage Gas Control Valve24 volt redundant combination two-stage gas control valve combines manual shut off switch (On-Off), automatic electric valve (dual) and gas pressure regulation into a compact combination control.Two-Speed Combustion Air InducerHeavy duty, permanent split capacitor (PSC) two-speed blower prepurges heat exchanger and safely vents flue products.Dual pressure switches (low fire/high fire) prove blower operation before allowing gas valve to open.Operates only during heating cycle.Direct access allows inducer assembly to be rotated 90° clockwise or counterclockwise to facilitate easy vent attachment.

A

B

C

D

E

F

Flame Rollout Switches (2)Manual reset switches are factory installed on burner box.Switch provides protection from abnormal operating conditions.Limit ControlsAutomatic reset, primary and secondary limits are accurately located.Primary limit factory installed on vestibule panel on all units, secondary limit factory installed on blower housing.

OPTIONS

High Altitude Pressure Switch KitRequired on most units for proper unit operation at altitudes from 4501 to 10,000 ft.Natural Gas to LPG/Propane Conversion KitRequired for field changeover from natural gas to LPG/Propane.LPG/Propane to Natural Gas Conversion KitRequired for field changeover from LPG/Propane to natural gas.

BLOWER

Variable Speed Direct Drive BlowerEach blower assembly statically and dynamically balanced.Change in blower speed is easily accomplished by simple DIP switch change on furnace control.See Blower Performance tables.Blower assembly easily removed for servicing.Variable Speed Blower MotorVariable speed motor maintains specified air volume from 0 though 0.8 in. w.g. (heating) and 0 through 1.0 in. w.g. (Cooling) static range.Variable speed operation is achieved by the use of an ECM (Electronically Commutated Motor) motor.Motor is controlled by furnace control.Motor is resiliently mounted.When furnaces are used with the Harmony III™ Zoning System, blower motor operates from predetermined minimum - maximum air volumes to satisfy zone requirements.

G

H

I

FEATURES

SL280UHV / Page 4

CONTROLS

SureLight® Integrated Two-Stage / Variable Speed Blower Furnace ControlContains all necessary controls and relays to operate furnace.Combustion air inducer is controlled by control. Prior to ignition, a low speed pre-purge cycle for 15 seconds is initiated. After the main burners are turned off, a post-purge cycle for 5 seconds is run.Ignition control provides a regulated 95 volts to the ignitor for a consistent ignition and long ignitor life.Flame sensor utilizes flame rectification for safe and reliable operation.Should flame fail to ignite, control will initiate 4 re-attempts at ignition before locking out unit operation for 60 minutes.Watchguard type circuit automatically resets ignition controls after one hour of continuous thermostat demand after unit lockout, eliminating nuisance calls for service.Jumper settings for single or two-stage thermostat operation.Two selectable second stage recognition times (10 and 15 minutes) are available when the furnace is used with a single stage thermostat. When used with a two-stage thermostat, furnace will only initiate second stage operation with a second stage thermostat demand.Four LED’s indicate unit status and aid in troubleshooting:1. SPEED LED (green) - Indicates circulating blower

speed. The LED is lit during normal blower operation and is off during a dehumidification demand. In Harmony III™ zoning applications, the brightness of the LED indicates the requested blower speed.

2. CFM LED (green) - Indicates blower cfm.3. STATUS LED (red) - Flashes diagnostic codes.4. E-COM LED (green) - Indicates that the control is

receiving and processing commands and inputs.Two accessory terminals furnished for additional power supply requirements for 120 volt (less than 1 amp) power humidifiers and powered air cleaners. One 24 volt humidifier output furnished.

J

FEATURES

Two blower speeds - second stage heat and second stage cool (with four air volume selections for each) are selected by DIP switches on control. Heat speed can be adjusted to optimize discharge temperature. Cool speed can be adjusted to correct optional cooling capacity. See Blower Performance tables.First stage blower speed is a percentage of second stage speed.The ADJUST switch (DIP) allows normal (NORM), 10% higher (+ plus) or 10% lower ( minus) motor speed selection within HEAT and COOL speeds selected for fine tuning air volume.DELAY switch (DIP) allows one of four de-humidification profiles during cooling mode.Profile A - Motor runs at 50% for 30 seconds, then at 82% for 7-1/2 minutes, then at 100% (if needed) until demand is satisfied. Once demand is met, motor runs at 50% for 30 seconds, then ramps down to stop.Profile B - Motor runs at 82% for 7-1/2 minutes and then at 100% (if needed) until demand is satisfied. Once demand is met,motor ramps down to stop.Profile C - Motor runs at 100% until demand is satisfied. Once demand is met, motor runs at 100% for 60 seconds, then ramps down to stop.Profile D - Motor runs at 100% until demand is satisfied. Once demand is met, motor ramps down to stop.In heat mode, blower on time is fixed at 45 seconds, blower off time is adjustable from 60, 90, 120 and 180 seconds (factory setting - 90 seconds).For air-conditioning applications, blower on time is 2 seconds following thermostat demand for cooling.Controls humidity by controlling blower and compressor speed on two-stage outdoor units when used with humidity control or Lennox ComfortSense® 7000 Touchscreen Thermostat. 24 Volt TransformerFurnished and factory installed in control box. 40VA transformer has circuit breaker wired in series.Note - 50VA transformer is required when unit is used with the Harmony III™ Zoning System. Ordered separately. See Price Book.Field Wiring Make-up BoxFurnished for line voltage wiring.Factory installed internally on left side of furnace.Box may be installed on right side of furnace.

SL280UHV / Page 5

FEATURES

CONTROLS (CONTINUED)

OPTIONS

ComfortSense® 7000 Touchscreen ThermostatElectronic 7-day, universal, multi-stage, programmable, touchscreen thermostat.4 Heat/2 Cool.Auto-changeover.Controls humidity during cooling mode.Offers enhanced capabilities including humidification / dehumidification / dewpoint measurement and control, Humiditrol® control, and equipment maintenance reminders.Easy-to-use, menu driven thermostat with a back-lit, LCD touchscreen.Remote outdoor temperature sensor (optional) allows the thermostat to display outdoor temperature. Required in dual-fuel and Humiditrol® applications.See the ComfortSense® 7000 Product Specifications bulletin in the Controls section for more information.ThermostatThermostat (programmable/non-programmable) is not furnished with unit.See Thermostat bulletins in Controls Section and Lennox Price Book for selection.Night Service KitContains most commonly used service parts:• Furnace Control• Ignitor• Flame sensor• Gas valve• TransformerSafety Night Service KitKit contains:• Primary limits (for each model)• Pressure switches (for each model)• Flame rollout switches (for each model)• Secondary limits (for each model)

INDOOR RH 26%

WED AN 21 12:35AM

MODE

ON

AUTO

HOME SCHEDULE OPTIONS

SET AT

SET AT

HEAT

COOLSCHED

FILTER (NOT FURNISHED)

Filter and provisions for external mounting must be field provided.

OPTIONS

Air Filter and Rack Kit for Horizontal Return Air (End) ApplicationsWashable or vacuum cleanable polyurethane frame type filter and external end return air rack available for field installation.Rack has filter door for easy filter servicing.Flanges on rack allow easy duct connection.See dimension drawing.Air Filter and Rack Kit for Upflow Side Return AirApplications - Not for use with Return Air BaseWashable or vacuum cleanable polyurethane frame type filter and external side return air rack available for field installation.Available in single and ten pack kits.Rack has filter door for easy filter servicing.Flanges on rack allow easy duct connection.Field installs on either side of unit cabinet. See dimension drawing.

CABINET

Low-profile, narrow width cabinet allows easy installation.Heavy-gauge, cold rolled steel construction.Pre-painted cabinet finish.Flue outlet on top of cabinet for upflow applications, can be relocated to either side of cabinet for horizontal applications.Flanges provided on supply air opening for ease of plenum connection or alignment with indoor coil.Fully insulated cabinet with foil faced insulation on sides and back of heating compartment and mat faced insulation in blower compartment.Sealed blower compartment. Inner blower compartment access panel seals blower compartment from air leakage.Cabinet door can be removed without any toolsComplete service access.Safety interlock switch automatically shuts off power to unit when inner blower compartment access panel is removed.Gas piping and electrical inlets are provided in both sides of cabinet.

K

L

M

SL280UHV / Page 6

FEATURES

CABINET (CONTINUED)

Return Air Entry:For bottom/end return-air entry for upflow/horizontal applications, remove furnished bottom seal panel from cabinet.For side return-air entry (upflow applications only), corners are marked on either side of cabinet for return air cut-outs.See dimension drawings.NOTE - 60C and 60D size units that require second stage air volumes over 1800 cfm must have one of the following:1. Single side return air with transition, to accommodate

20 x 25 x 1 in. cleanable air filter. Required to maintain proper air velocity.

2. Single side return air with Optional Return Air Base3. Bottom return air.4. Return air from both sides.5. Bottom and one side return air.See Blower Performance Tables for additional information.Coil Match-upAll furnaces exactly match C33 and CX34 cased upflow indoor coils and CH33 horizontal indoor coils with same letter designation in model number. No adaptor required. Engaging holes furnished on cabinet for alignment.C33 uncased coils match furnaces without any overhang but require an optional adaptor base or field fabricated transition to match furnace opening. See C33 coil bulletin for additional information.

OPTIONS

Horizontal Suspension KitProvides suspension of unit and coil in horizontal applications.Allows complete service access.Consists of corner mounted hanging brackets with vibration isolators, return air end support rail and hardware for assembly.Metal hanging straps must be field provided.Return Air BaseA field fabricated transition or Return Air Base is required when using an IAQ product higher than 14-3/16 in. installed next to the unit and serviced from the front. IAQ products higher than 20 in. require a field fabricated transition.Base must be used for 60C and 60D models with air volumes over 1800 cfm in upflow applications when only one side return is required.Cabinet is shipped flat for easy field assembly and is pre-painted steel to match the furnace.See Dimension Drawing.

UPFLOW POSITIONVent Type Type B1 Type C

Sides 0 (0) 1 0 (0)Rear 0 (0) 0 (0)Top 1 (25) 1 (25)

Front 2-1/4 (57) 2-1/4 (57)Front (service/alcove) 24 (610) 24 (610)

Floor Combustible CombustibleFlue 1 (25) 6 (152)

NOTE − Air for combustion must conform to the methods outlined in the National Fuel Gas Code (NFPA 54/ANSI-Z223.1).

NOTE − In the U.S. flue sizing must conform to the methods outlined in the current National Fuel Gas Code (NFPA 54/ANSI-Z223.1) or applicable provisions of local building codes.

1 Left side requires 4 in. if single wall vent is used on 14-1/2 in. cabinets, 2 in. on 17-1/2 in. cabinets.

INSTALLATION CLEARANCES - INCHES (MM)

HORIZONTAL POSITIONVent Type Type B1 Type C

End 1 2 1 2Rear 0 (0) 0 (0)Top 1 0 (0) 1 0 (0)

Front 2-1/4 (57) 2-1/4 (57)Front (service) 24 (610) 24 (610)

Floor Combustible CombustibleFlue 1 (25) 6 (152)

NOTE − Air for combustion must conform to the methods outlined in the National Fuel Gas Code (NFPA 54/ANSI-Z223.1).

NOTE − In the U.S. flue sizing must conform to the methods outlined in the current National Fuel Gas Code (NFPA 54/ANSI-Z223.1) or applicable provisions of local building codes.

1 Line contact installation permissible between jacket top or sides and building joists.

SL280UHV / Page 7

SPECIFICATIONSGas Heating Performance

Model No. SL280UH070V36A SL280UH090V36B SL280UH090V48BModel No. - Low Nox SL280UH070XV36A - - - SL280UH090XV48B

1 AFUE 80% 80% 80%High Fire

Input - Btuh 66,000 88,000 88,000Output - Btuh 52,000 70,000 70,000

Temperature rise range - °F 40 - 70 40 - 70 40 - 70Gas Manifold Pressure (in. w.g.)

Nat. Gas / LPG/Propane3.5 / 10 3.5 / 10 3.5 / 10

Low Fire

Input - Btuh 43,000 57,000 57,000Output - Btuh 35,000 47,000 47,000

Temperature rise range - °F 25 -55 25 -55 25 -55Gas Manifold Pressure (in. w.g.)

Nat. Gas / LPG/Propane1.7 / 4.9 1.7 / 4.9 1.7 / 4.9

High static - in. w.g. Heating 0.8 0.8 0.8Cooling 1.0 1.0 1.0

Connections in.

Flue connection − in. round 4 4 4Gas pipe size IPS 1/2 1/2 1/2

Indoor Blower

Wheel nominal diameter x width - in. 10 X 8 10 X 9 11-1/2 X 9Motor output - hp 1/2 1/2 1.0

Tons of add-on cooling 2 - 3 2 - 3.5 2.5 - 4Air Volume Range - cfm 606 - 1345 498 - 1393 679 - 2002

Electrical Data Voltage 120 volts - 60 hertz - 1 phaseBlower motor full load amps 7.7 7.7 12.8

Maximum overcurrent protection 15 15 20Shipping Data lbs. - 1 package 128 143 154NOTE - Filters and provisions for mounting are not furnished and must be field provided. 1 Annual Fuel Utilization Efficiency based on DOE test procedures and according to FTC labeling regulations. Isolated combustion system rating for non-weatherized furnaces.

2 Flue connection on the unit is 4 in. diameter. Most applications will require 5 in. venting and field supplied 4 x 5 in. adaptor. See Venting Tables in the Installation Instructions for detailed information.

SPECIFICATIONSGas Heating Performance

Model No. SL280UH090V60C SL280UH110V60C SL280UH135V60DModel No. - Low Nox SL280UH090XV60C SL280UH110XV60C - - -

1 AFUE 80% 80% 80%High Fire

Input - Btuh 88,000 110,000 132,000Output - Btuh 70,000 87,000 105,000

Temperature rise range - °F 35 - 65 35 - 65 40 - 70Gas Manifold Pressure (in. w.g.)

Nat. Gas / LPG/Propane3.5 / 10.0 3.5 / 10.0 3.5 / 10.0

Low Fire

Input - Btuh 57,000 72,000 86,000Output - Btuh 47,000 58,000 69,000

Temperature rise range - °F 25 -55 25 -55 25 -55Gas Manifold Pressure (in. w.g.)

Nat. Gas / LPG/Propane1.7 / 4.9 1.7 / 4.9 1.7 / 4.9

High static - in. w.g. Heating 0.8 0.8 0.8Cooling 1.0 1.0 1.0

Connections in.

Flue connection − in. round 4 4 2 4Gas pipe size IPS 1/2 1/2 1/2

Indoor Blower

Wheel nominal diameter x width - in. 11-1/2 X 10 11-1/2 X 10 11-1/2 X 11Motor output - hp 1.0 1.0 1.0

Tons of add-on cooling 3 - 5 3 - 5 3.5 - 5Air Volume Range - cfm 826 - 2305 812 - 2125 828 - 2257

Electrical Data Voltage 120 volts - 60 hertz - 1 phaseBlower motor full load amps 12.8 12.8 12.8

Maximum overcurrent protection 20 20 20Shipping Data lbs. - 1 package 173 181 199NOTE - Filters and provisions for mounting are not furnished and must be field provided. 1 Annual Fuel Utilization Efficiency based on DOE test procedures and according to FTC labeling regulations. Isolated combustion system rating for non-weatherized furnaces.

2 Flue connection on the unit is 4 in. diameter. Most applications will require 5 in. venting and field supplied 4 x 5 in. adaptor. See Venting Tables in the Installation Instructions for detailed information.

SL280UHV / Page 8

OPTIONAL ACCESSORIES - MUST BE ORDERED EXTRA

“A” Width Models

“B” Width Models

“C” Width Models

“D” Width Models

CABINET ACCESSORIES

Horizontal Suspension Kit - Horizontal only 51W10 51W10 51W10 51W10

Return Air Base - Upflow only 65W75 50W98 50W99 51W00

CONTROLS

ComfortSense® 7000 Thermostat Y0349 Y0349 Y0349 Y0349

Remote Outdoor Sensor (for dual fuel and Humiidtrol®) X2658 X2658 X2658 X2658

FILTERS1 Air Filter and Rack Kit Horizontal (end) 87L95 87L96 87L97 87L98

Size of filter - in. 14 x 25 x 1 18 x 25 x 1 20 x 25 x 1 25 x 25 x 1

Side Return Single 44J22 44J22 44J22 44J22

Ten Pack 66K63 66K63 66K63 66K63

Size of filter - in. 16 x 25 x 1 16 x 25 x 1 16 x 25 x 1 16 x 25 x 1

NIGHT SERVICE KITS

Night Service Kit 51W04 51W04 51W04 51W04

Safety Night Service Kit 51W05 51W05 51W05 51W051 Cleanable polyurethane, frame-type filter.

GAS HEAT ACCESSORIES

InputHigh Altitude

Pressure Switch KitNatural Gas to

LPG/Propane Kit LPG/Propane

to Natural Gas Kit

0 - 4500 ft. 4501 - 7500 ft. 7501 - 10,000 ft. 0 - 7500 ft. 7501 - 10,000 ft. 0 - 7500 ft. 7501 - 10,000 ft.

070 No Change No Change 73W35 77W07 77W05 77W09 77W11

090 No Change 69W56 73W35 77W07 77W05 77W09 77W11

110 No Change 69W56 73W35 77W07 77W05 77W09 77W11

135 No Change 73W33 73W34 77W07 77W05 77W09 77W11

HIGH ALTITUDE DERATE

NOTE - Units may be installed at altitudes up to 4500 ft. above sea level without any modifications. At altitudes above 4500 ft. units must be derated to match information in the shaded area shown below.

NOTE - This is the only permissible derate for these units.

Input

Gas Manifold Pressure (Outlet) in. w.g.

0 - 4500 Feet 4501 -7500 Feet 7501 - 10,000 ft.

Natural Gas LPG/Propane Natural Gas LPG/Propane 1 Natural Gas LPG/Propane

High Fire

Low Fire

High Fire

Low Fire

High Fire

Low Fire

High Fire

Low Fire

High Fire

Low Fire

High Fire

Low Fire

070 3.5 1.7 10 4.9 3.4 1.6 10 4.9 3.5 1.7 10 4.9

090 3.5 1.7 10 4.9 3.2 1.5 10 4.9 3.5 1.7 10 4.9

110 3.5 1.7 10 4.9 3.2 1.5 10 4.9 3.5 1.7 10 4.9

135 3.5 1.7 10 4.9 2.8 1.6 10 4.9 3.5 1.7 10 4.91 Natural Gas High Alitude Orifice Kit required.

SL280UHV / Page 9

DIMENSIONS - INCHES (MM) - UPFLOW POSITION

Model No.A B C D

in. mm in. mm in. mm in. mmSL280UH070V36A 14-1/2 368 13-3/8 340 13 330 4-3/4 121SL280UH090V36BSL280UH090V48B

17-1/2 446 16-3/8 416 16 406 6-1/4 159

SL280UH090V60CSL280UH110V60C

21 533 19-7/8 504 19-1/2 495 8 203

SL280UH135V60D 24-1/2 622 23-3/8 546 23 584 9-3/4 248

AIR FLOW

23(584)

(19)3/4

(19)1 Bottom Return

Air Opening

GAS PIPING INLET(Either Side)

Side ReturnAir Opening(Either Side)

1 Bottom Return

Air Opening

FLUE OUTLET(Top)

ELECTRICAL INLET(Either Side)

SUPPLY AIROPENING

FRONT VIEW SIDE VIEW

TOP VIEW

AB 9/16 (14)

C

D

3/4

27-3/4(705)

19-7/16(494)

23-1/2(597)

1-1/2(38)

9-1/8 (232) Right8-5/8 (219) Left

5-3/8 (137) Right2-3/4 (70) Left

33(838)

3-1/8 (79)

1-15/16 (49)

14(356)

9/16(14)

3 (76) Right7 (178) Left

2 FLUE OUTLET

(Either Side)

3 OPTIONALEXTERNAL

SIDE RETURNAIR FILTER KIT

(Either Side)

16(406)

14-3/4(375)

3 OPTIONALEXTERNAL

SIDE RETURNAIR FILTER KIT

(Either Side)

2 Flue outlet may be horizontal but furnace must bevented vertically

3 Optional External Side Return Air Filter Kit is not for usewith the optional Return Air Base.

1 NOTE - 60C and 60D size units that require second stageair volumes over 1800 cfm must have oneof the following:1. Single side return air with transition, to accommodate

20 x 25 x 1 in. (508 x 635 x 25 mm) cleanable airfilter. Required to maintain proper air velocity.

2. Single side return air with optional Return Air Base3. Bottom return air.4. Return air from both sides.5. Bottom and one side return air.See Blower Performance Tables for additional information.

3-1/4 (83)

5/8(16)

1

3-1/4(83)

23-3/4(603)

25(635)

1-1/2 (38)Front Panel

SL280UHV / Page 10

DIMENSIONS - INCHES (MM) - HORIZONTAL POSITION

Model No.A B C D

in. mm in. mm in. mm in. mmSL280UH070V36A 14-1/2 368 13-3/8 340 13 330 4-3/4 121SL280UH090V36BSL280UH090V48B

17-1/2 446 16-3/8 416 16 406 6-1/4 159

SL280UH090V60CSL280UH110V60C

21 533 19-7/8 504 19-1/2 495 8 203

SL280UH135V60D 24-1/2 622 23-3/8 546 23 584 9-3/4 248

A

TOP VIEW

27-3/4(705)

33(838)

27-3/4(705)

27-3/4(705)

A

(79)

3

GAS PIPING INLET(Top or Bottom)

RETURNAIR

OPENING

FLUE OUTLET(Top)

ELECTRICAL INLET(Top or Bottom)

SUPPLYAIR

OPENING

FRONT VIEW

TOP VIEW

CA

END VIEWEND VIEW

33(838)

27-3/4(705)

19-7/16(494)

9/16(14)

B

23-1/2(597)

3-1/4(108)

(19)

5-3/8 (137) Top2-3/4 (70) Bottom

9-1/8 (232) Top8-5/8 (219) Bottom

3-1/4 (83)

(76)

3-1/8

D

1 FLUEOUTLET

(End)

LEFT-HAND AIR DISCHARGE

1 Flue outlet may be from end butfurnace must be vented vertically

FRONT VIEWEND VIEW END VIEW

1 FLUE OUTLET(Top)

3-1/4 (83)

7(178)

AIRFLOW

GAS PIPING INLET(Top or Bottom)

ELECTRICAL INLET(Top or Bottom)

RIGHT-HAND AIR DISCHARGE

1 Flue outlet may be horizontal butfurnace must be vented vertically

9-1/8 (232) Bottom8-5/8 (219) Top5-3/8 (137) Bottom

2-3/4 (70) Top

9/16(14)

3/4

AIRFLOW

AIRFLOW

19-7/16(494)

9/16(14)B

9/16(14)

D

A

1 FLUE OUTLET(End)

(79)3-1/8

SUPPLYAIR

OPENING

RETURNAIR

OPENING

C

23-1/2(597)

3-1/4(108)

(19)3/4

AIRFLOW

1-1/2 (38)Front Panel

1-1/2 (38)Front Panel

SL280UHV / Page 11

OPTIONAL ACCESSORY DIMENSIONS - INCHES (MM)

1-1/4HORIZONTAL (END) FILTER KIT

FRONT VIEW

24−3/4(629)

AB

23−1/2(597)

5/8(16)

RETURNAIR

OPENING

SIDE VIEW

AIR FLOW

AIR FILTER(Furnished)

(32)

5/8(16)

5/8(16)

5/8(16)

Optional Return Air Base(Upflow Applications Only - For use with A, B, C and D cabinets)

NOTE- Optional Side Return Air Filter Kits are not for use with Optional Return Air Base.1 Both the unit return air opening and the base return air opening must be covered by a single plenum or IAQ cabinet.

Minimum unit side return air opening dimensions for units requiring 1800 cfm or more of air (W x H): 23 x 11 in. (584 x 279 mm).The opening can be cut as needed to accommodate plenum or IAQ cabinet while maintaining dimensions shown.Side return air openings must be cut in the field. There are cutting guides stenciled on the cabinet for the side return airopening. The size of the opening must not extend beyond the markings on the furnace cabinet.

2 To minimize pressure drop, the largest opening height possible, up to 14 in. (356 mm), is preferred.

FURNACEFRONT

AIR FLOW

14-1/2 (368) A Width (65W75)17-1/2 (446) B Width (50W98)21 (533) C Width (50W99)24-1/2 (622) D Width (51W00)

1 Unit side return airOpening

SIDE VIEW

3-1/4(83)

1 23 (584)Overall

(Maximum)

(584)23

3/4(19)

1 22-7/16(570)

Overall(Maximum)

SIDE RETURNAIR OPENINGS

(Either Side)

5-5/8(143)

1 Minimum11 (279)

2 Maximum14 (356)

(683)26-7/8

7-1/4(184)

IF BASEIS USED

WITHOUTIAQ CABINET,

A SINGLERETURN AIR

PLENUMMUST

COVER BOTHUNIT ANDRETURNAIR BASE

OPENINGS

INDOOR AIRQUALITYCABINET

(PCO, FilterCabinet, etc.)

AIR BASE

OPTIONALRETURN

Furnace Cabinet Width

Catalog Number

A B

in. mm in. mm

A 87L95 14 356 12-3/4 324B 87L96 18 457 16-3/4 425C 87L97 21 533 18-3/4 476D 87L98 25 635 23-3/4 603

SL280UHV / Page 12

DIMENSIONS − INCHES (MM) - FURNACE/COIL COMBINED DIMENSIONS

UPFLOW POSITION

Model NoCased Uncased

(CX34 - cased only)A B A B

CX34 C33 in. mm in. mm in. mm in. mm- - - C33-18A 12-1/2 318 45-1/2 1156 9-3/4 248 42-3/4 1086

CX34-19A-6F C33-19A 16-1/2 419 49-1/2 1257 9-3/4 248 42-3/4 1086- - - C33-24A 16-1/2 419 49-1/2 1257 14 356 47 1194

CX34-18/24A-6F CX34-18/24B-6F CX34-18/24C-6F

C33-24B C33-24C

16-1/2 419 49-1/2 1257 13-7/8 352 46-7/8 1191

CX34-25A-6F C33-25A 18-1/2 470 51-1/2 1308 16-1/4 413 49-1/4 1251CX34-25B-6F C33-25B 18-1/2 470 51-1/2 1308 15-7/8 403 48-7/8 1241CX34-30B-6F CX34-30C-6F

C33-30B C33-30C 20-1/2 521 53-1/2 1359 17-3/4 451 50-3/4 1289

CX34-30A-6F C33-30A 20-1/2 521 53-1/2 1359 18 457 51 1295CX34-31A-6F C33-31A 22-1/2 572 55-1/2 1410 21-1/4 540 54-1/4 1378CX34-31B-6F C33-31B 22-1/2 572 55-1/2 1410 20-1/4 514 53-1/4 1353CX34-36A-6F C33-36A 24-1/2 622 57-1/2 1461 22-1/8 562 55-1/8 1400CX34-36B-6F C33-36B 24-1/2 622 57-1/2 1461 21-7/8 556 54-7/8 1394CX34-36C-6F C33-36C 24-1/2 622 57-1/2 1461 21-1/4 540 54-1/4 1378CX34-38A-6F C33-38A 24-1/2 622 57-1/2 1461 22-1/4 565 55-1/4 1403CX34-38B-6F C33-38B 24-1/2 622 57-1/2 1461 22 559 55 1397CX34-42B-6F C33-42B 24-1/2 622 57-1/2 1461 21-7/8 556 54-7/8 1394CX34-43B-6F C33-43B 27-1/2 699 60-1/2 1537 26-1/4 667 59-1/4 1505CX34-43C-6F C33-43C 27-1/2 699 60-1/2 1537 25-3/4 654 58-3/4 1492

- - - C33-44C 24-1/2 622 57-1/2 1461 21-1/2 546 54-1/2 1384CX34-44/48B-6F C33-48B 24-1/2 622 57-1/2 1461 22-1/8 562 55-1/8 1400CX34-44/48C-6F C33-48C 24-1/2 622 57-1/2 1461 21-1/2 546 54-1/2 1384CX34-49C-6F C33-49C 29-1/2 749 62-1/2 1588 28-1/2 724 61-1/2 1562CX34-50/60C-6F C33-50/60C27-1/2 699 60-1/2 1537 24-3/4 629 57-3/4 1467CX34-60D-6F C33-60D 25-1/2 648 58-1/2 1486 24-3/4 629 57-3/4 1467CX34-62C-6F C33-62C 31-1/2 800 64-1/2 1638 30-5/8 778 63-5/8 1616CX34-62D-6F C33-62D 29-1/2 749 62-1/2 1588 28-3/4 730 61-3/4 1568

HORIZONTAL POSITIONModel

NumberA B

in. mm in. mmCH33-18A-2F 21-1/2 546 54-1/2 1384CH33-24/30A-2F CH33-36A-2F CH33-36B-2F CH33-36C-2F

CH33-42B-2F CH33-48C-2F CH33-60D-2F

26-1/2 673 59-1/2 1511

CH33-44/48B-2F CH33-50/60C-2F

CH33-62D-2F 31-1/2 800 64-1/2 1638

33(838)

A

B

33(838)

A

B

SL280UHV / Page 13

BLOWER DATASL280UH070V36A BLOWER PERFORMANCE (less filter)BOTTOM RETURN AIR0 through 0.8 in. w.g. (Heating) and 0 through 1.0 in. w.g. (Cooling) External Static Pressure Range

“ADJUST” Switch

Positions

Speed Switch PositionsSecond Stage “HEAT” Speed - cfm Second Stage “COOL” Speed - cfm

1 1 2 3 4 1 2 3 1 4+ 787 990 1027 1129 995 1080 1215 1335

1 NORM 715 900 934 1026 920 985 1105 1225— 644 810 841 923 820 905 995 1100

“ADJUST” Switch

Positions

First Stage “HEAT” Speed - cfm First Stage “COOL” Speed - cfm

1 1 2 3 4 1 2 3 1 4

+ 747 829 926 1031 735 785 865 9651 NORM 679 754 842 937 690 735 795 885

— 611 679 758 843 650 685 755 7901 Factory default jumper setting.NOTES - The effect of static pressure is included in air volumes shown. First stage HEAT is approximately 91% of the same second stage HEAT speed position. First stage COOL (two-stage air conditioning units only) is approximately 70% of the same second stage COOL speed position. Continuous Fan Only speed is approximately 38% of the same second stage COOL speed position - minimum 500 cfm. Lennox Harmony III™ Zoning System Applications - Minimum blower speed is 426 cfm.

SL28UH070V36A BLOWER MOTOR WATTS (COOLING)

Jumper Speed Positions

Motor Watts @ Various External Static Pressures - in. wg.First Stage Second Stage

0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1.0“+” (Plus) SETTING (“Adjust” Jumper at “+” Setting)

“COOL” Speed

Tap 1 44 60 77 93 110 128 143 159 175 104 121 146 166 186 209 229 248 268 287 311Tap 2 49 70 86 100 123 144 160 179 197 125 145 170 197 219 242 260 288 308 331 355Tap 3 64 82 104 125 144 166 184 204 222 185 204 228 261 284 314 337 358 377 403 422Tap 4 88 110 130 150 173 195 215 237 258 257 279 304 334 359 389 373 430 457 475 499

“NORM” (Normal) SETTING (“Adjust” Jumper at “NORM” Setting)

“COOL” Speed

Tap 1 34 54 65 80 103 116 133 152 165 78 96 117 138 160 184 202 221 242 259 279Tap 2 39 57 72 90 110 125 146 160 177 99 114 141 159 183 206 226 242 264 284 300Tap 3 53 72 90 106 128 146 162 184 199 135 152 183 207 228 253 276 297 320 340 365Tap 4 73 89 114 131 154 170 190 209 228 194 211 241 273 292 318 338 361 383 410 434

“—” (Minus) SETTING (“Adjust” Jumper at “—” Setting)

“COOL” Speed

Tap 1 29 45 60 74 91 106 122 137 153 57 77 96 114 134 158 174 196 217 231 247Tap 2 33 51 66 79 98 116 131 147 164 76 93 113 134 155 175 194 213 232 250 268Tap 3 42 59 77 95 112 131 147 164 181 102 117 144 167 189 209 227 250 270 288 308Tap 4 51 71 88 104 126 147 164 182 201 133 153 179 203 228 250 269 299 317 339 363

SL280UHV / Page 14

BLOWER DATASL280UH070V36A BLOWER PERFORMANCE (less filter)SINGLE SIDE RETURN AIR0 through 0.8 in. w.g. (Heating) and 0 through 1.0 in. w.g. (Cooling) External Static Pressure Range

“ADJUST” Switch

Positions

Speed Switch PositionsSecond Stage “HEAT” Speed - cfm Second Stage “COOL” Speed - cfm

1 1 2 3 4 1 2 3 1 4+ 778 979 1018 1114 1010 1095 1215 1345

1 NORM 707 890 925 1013 915 990 1090 1215— 636 801 833 912 820 895 1015 1105

“ADJUST” Switch

Positions

First Stage “HEAT” Speed - cfm First Stage “COOL” Speed - cfm

1 1 2 3 4 1 2 3 1 4

+ 740 825 950 1044 730 785 860 9351 NORM 673 750 864 949 690 725 795 860

— 606 675 778 854 635 685 730 7951 Factory default jumper setting.NOTES - The effect of static pressure is included in air volumes shown. First stage HEAT is approximately 91% of the same second stage HEAT speed position. First stage COOL (two-stage air conditioning units only) is approximately 70% of the same second stage COOL speed position. Continuous Fan Only speed is approximately 38% of the same second stage COOL speed position - minimum 500 cfm. Lennox Harmony III™ Zoning System Applications - Minimum blower speed is 426 cfm.

SL28UH070V36A BLOWER MOTOR WATTS (COOLING)

Jumper Speed Positions

Motor Watts @ Various External Static Pressures - in. wg.First Stage Second Stage

0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1.0“+” (Plus) SETTING (“Adjust” Jumper at “+” Setting)

“COOL” Speed

Tap 1 40 60 74 89 104 124 140 160 177 94 113 136 159 180 201 224 246 264 283 306Tap 2 47 66 86 98 119 142 158 174 197 118 137 163 192 213 238 267 284 305 330 348Tap 3 56 76 91 117 135 149 176 189 211 170 189 217 244 267 294 319 339 359 381 409Tap 4 72 90 116 131 161 182 201 221 237 237 261 286 307 343 364 393 416 431 468 483

“NORM” (Normal) SETTING (“Adjust” Jumper at “NORM” Setting)

“COOL” Speed

Tap 1 31 50 66 82 97 118 129 151 171 73 90 114 137 158 176 201 218 237 258 278Tap 2 38 58 73 89 108 124 146 163 181 96 114 138 161 184 205 224 246 267 283 309Tap 3 47 64 86 105 127 143 160 180 200 122 142 171 199 220 247 269 297 316 340 364Tap 4 62 84 99 123 146 166 182 204 224 184 205 233 258 287 311 334 354 386 403 431

“—” (Minus) SETTING (“Adjust” Jumper at “—” Setting)

“COOL” Speed

Tap 1 28 46 62 75 90 107 131 141 160 52 71 92 108 131 147 165 187 207 226 246Tap 2 32 49 67 83 102 113 132 149 171 63 86 105 126 128 170 186 208 227 248 265Tap 3 40 61 74 90 109 125 147 163 182 99 115 143 163 186 209 226 244 268 284 313Tap 4 42 63 78 100 114 140 152 169 196 122 144 167 192 216 236 257 287 307 328 353

SL280UHV / Page 15

BLOWER DATASL280UH090V36B BLOWER PERFORMANCE (less filter)BOTTOM RETURN AIR0 through 0.8 in. w.g. (Heating) and 0 through 1.0 in. w.g. (Cooling) External Static Pressure Range

“ADJUST” Switch

Positions

Speed Switch PositionsSecond Stage “HEAT” Speed - cfm Second Stage “COOL” Speed - cfm

1 1 2 3 4 1 2 3 1 4+ 1200 1483 1495 1632 995 1140 1255 1390

1 NORM 1091 1348 1359 1484 875 1055 1145 1245— 982 1213 1223 1336 780 925 1035 1115

“ADJUST” Switch

Positions

First Stage “HEAT” Speed - cfm First Stage “COOL” Speed - cfm

1 1 2 3 4 1 2 3 1 4

+ 1114 1234 1383 1509 625 775 865 8751 NORM 1013 1122 1257 1372 565 675 775 785

— 912 1010 1131 1235 495 590 675 6751 Factory default jumper setting.NOTES - The effect of static pressure is included in air volumes shown. First stage HEAT is approximately 91% of the same second stage HEAT speed position. First stage COOL (two-stage air conditioning units only) is approximately 70% of the same second stage COOL speed position. Continuous Fan Only speed is approximately 38% of the same second stage COOL speed position - minimum 500 cfm. Lennox Harmony III™ Zoning System Applications - Minimum blower speed is 453 cfm.

SL280UH090V36B BLOWER MOTOR WATTS (COOLING)

Jumper Speed Positions

Motor Watts @ Various External Static Pressures - in. wg.First Stage Second Stage

0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1.0“+” (Plus) SETTING (“Adjust” Jumper at “+” Setting)

“COOL” Speed

Tap 1 35 50 65 80 95 109 124 139 154 73 87 114 141 165 183 210 228 247 267 286Tap 2 48 65 82 99 117 134 151 168 186 109 125 162 187 209 242 259 284 309 332 358Tap 3 52 73 94 114 135 156 177 197 218 139 160 198 226 251 291 315 335 365 396 420Tap 4 50 70 91 111 131 151 171 192 212 204 221 270 296 333 366 397 421 444 478 512

“NORM” (Normal) SETTING (“Adjust” Jumper at “NORM” Setting)

“COOL” Speed

Tap 1 28 43 57 70 82 95 110 126 142 61 80 99 119 143 159 181 202 217 241 256Tap 2 36 52 69 85 98 113 133 147 166 89 102 136 155 176 210 231 243 265 286 307Tap 3 37 60 77 90 106 132 147 170 191 108 135 154 184 210 233 259 285 306 337 358Tap 4 41 63 75 92 108 135 147 165 186 145 175 191 230 266 287 322 343 374 401 425

“—” (Minus) SETTING (“Adjust” Jumper at “—” Setting)

“COOL” Speed

Tap 1 22 37 48 59 74 85 100 113 127 45 62 83 95 115 144 158 175 196 207 225Tap 2 29 44 58 70 87 103 116 130 144 64 83 108 127 144 169 189 210 227 253 268Tap 3 31 51 63 76 96 109 128 144 163 85 104 127 149 180 198 217 242 259 277 305Tap 4 39 55 68 82 92 110 126 142 153 109 132 158 185 210 231 262 275 306 335 354

SL280UHV / Page 16

BLOWER DATASL280UH090V36B BLOWER PERFORMANCE (less filter)SINGLE SIDE RETURN AIR0 through 0.8 in. w.g. (Heating) and 0 through 1.0 in. w.g. (Cooling) External Static Pressure Range

“ADJUST” Switch

Positions

Speed Switch PositionsSecond Stage “HEAT” Speed - cfm Second Stage “COOL” Speed - cfm

1 1 2 3 4 1 2 3 1 4+ 1190 1469 1485 1602 975 1120 1220 1345

1 NORM 1082 1335 1350 1456 870 1030 1115 1235— 974 1202 1215 1310 775 915 1010 1100

“ADJUST” Switch

Positions

First Stage “HEAT” Speed - cfm First Stage “COOL” Speed - cfm

1 1 2 3 4 1 2 3 1 4

+ 1086 1194 1360 1469 665 765 835 9501 NORM 987 1085 1236 1335 555 675 770 865

— 888 977 1112 1202 505 620 680 7651 Factory default jumper setting.NOTES - The effect of static pressure is included in air volumes shown. First stage HEAT is approximately 91% of the same second stage HEAT speed position. First stage COOL (two-stage air conditioning units only) is approximately 70% of the same second stage COOL speed position. Continuous Fan Only speed is approximately 38% of the same second stage COOL speed position - minimum 500 cfm. Lennox Harmony III™ Zoning System Applications - Minimum blower speed is 453 cfm.

SL280UH090V36B BLOWER MOTOR WATTS (COOLING)

Jumper Speed Positions

Motor Watts @ Various External Static Pressures - in. wg.First Stage Second Stage

0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1.0“+” (Plus) SETTING (“Adjust” Jumper at “+” Setting)

“COOL” Speed

Tap 1 34 50 65 80 92 108 123 142 157 77 94 116 142 164 186 205 226 246 260 288Tap 2 42 63 75 92 110 130 147 164 183 111 132 159 185 211 233 259 275 307 328 353Tap 3 54 75 94 109 130 150 170 190 208 141 166 189 230 254 280 309 333 364 390 412Tap 4 72 92 113 133 155 179 203 219 235 184 208 248 278 310 335 374 397 435 450 492

“NORM” (Normal) SETTING (“Adjust” Jumper at “NORM” Setting)

“COOL” Speed

Tap 1 26 40 53 68 82 94 113 125 137 57 79 97 115 140 160 180 201 223 243 257Tap 2 31 52 66 77 97 112 131 155 166 80 101 127 147 173 194 212 242 260 283 306Tap 3 42 64 78 95 110 132 149 167 192 108 129 156 188 208 233 256 281 306 332 353Tap 4 52 77 92 111 131 161 175 199 218 132 159 188 219 253 287 308 337 368 397 423

“—” (Minus) SETTING (“Adjust” Jumper at “—” Setting)

“COOL” Speed

Tap 1 28 39 51 62 74 89 101 107 120 45 66 82 97 111 134 150 170 188 202 225Tap 2 32 48 61 74 86 100 114 133 146 65 86 102 125 151 164 187 205 226 245 265Tap 3 37 54 68 82 96 113 129 144 159 86 107 129 151 171 200 216 238 256 282 302Tap 4 42 63 78 92 109 130 145 165 184 106 127 159 176 211 224 249 279 297 319 356

SL280UHV / Page 17

BLOWER DATASL280UH090V36B BLOWER PERFORMANCE (less filter)SIDE RETURN AIR WITH OPTIONAL RETURN AIR BASE0 through 0.8 in. w.g. (Heating) and 0 through 1.0 in. w.g. (Cooling) External Static Pressure Range

“ADJUST” Switch

Positions

Speed Switch PositionsSecond Stage “HEAT” Speed - cfm Second Stage “COOL” Speed - cfm

1 1 2 3 4 1 2 3 1 4+ 1297 1474 1496 1616 985 1105 1210 1335

1 NORM 1179 1340 1360 1469 875 1005 1110 1215— 1061 1206 1224 1322 770 900 1010 1090

“ADJUST” Switch

Positions

First Stage “HEAT” Speed - cfm First Stage “COOL” Speed - cfm

1 1 2 3 4 1 2 3 1 4

+ 1203 1324 1477 1621 650 765 845 9451 NORM 1094 1204 1343 1474 585 685 810 860

— 985 1084 1209 1327 520 600 770 7751 Factory default jumper setting.NOTES - The effect of static pressure is included in air volumes shown. First stage HEAT is approximately 91% of the same second stage HEAT speed position. First stage COOL (two-stage air conditioning units only) is approximately 70% of the same second stage COOL speed position. Continuous Fan Only speed is approximately 38% of the same second stage COOL speed position - minimum 500 cfm. Lennox Harmony III™ Zoning System Applications - Minimum blower speed is 453 cfm.

SL280UH090V36B BLOWER MOTOR WATTS (COOLING)

Jumper Speed Positions

Motor Watts @ Various External Static Pressures - in. wg.First Stage Second Stage

0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1.0“+” (Plus) SETTING (“Adjust” Jumper at “+” Setting)

“COOL” Speed

Tap 1 32 51 63 76 88 105 119 137 156 71 90 113 137 159 179 197 220 242 263 285Tap 2 42 61 76 91 107 124 144 161 175 105 127 150 180 201 220 245 267 295 315 341Tap 3 49 73 87 104 120 145 163 183 203 131 157 182 212 238 266 295 317 346 374 395Tap 4 68 86 111 132 151 172 196 214 235 167 189 227 265 296 326 356 384 416 439 473

“NORM” (Normal) SETTING (“Adjust” Jumper at “NORM” Setting)

“COOL” Speed

Tap 1 29 45 56 68 81 95 110 122 138 57 78 95 114 134 153 171 192 212 230 250Tap 2 36 54 67 81 96 110 129 144 159 81 103 123 148 169 188 211 233 257 276 296Tap 3 46 68 83 98 115 136 154 174 192 106 128 151 179 203 228 252 276 298 320 343Tap 4 61 81 101 121 140 160 184 201 221 135 157 188 222 243 272 299 325 351 375 406

“—” (Minus) SETTING (“Adjust” Jumper at “—” Setting)

“COOL” Speed

Tap 1 25 38 48 60 73 85 101 108 119 43 65 77 91 109 128 145 163 182 197 214Tap 2 30 46 58 71 85 96 114 128 143 58 79 95 117 136 156 177 200 219 237 251Tap 3 43 63 78 92 109 127 145 166 180 82 99 121 146 168 190 209 234 251 267 290Tap 4 54 75 91 111 129 148 172 188 207 102 125 149 179 190 218 243 266 287 311 340

SL280UHV / Page 18

BLOWER DATASL280UH090V48B BLOWER PERFORMANCE (less filter)BOTTOM RETURN AIR0 through 0.8 in. w.g. (Heating) and 0 through 1.0 in. w.g. (Cooling) External Static Pressure Range

“ADJUST” Switch

Positions

Speed Switch PositionsSecond Stage “HEAT” Speed - cfm Second Stage “COOL” Speed - cfm

1 1 2 3 4 1 2 3 1 4+ 1187 1518 1529 1646 1030 1335 1545 1755

1 NORM 1079 1380 1390 1496 940 1200 1405 1600— 971 1242 1251 1346 790 1060 1260 1435

“ADJUST” Switch

Positions

First Stage “HEAT” Speed - cfm First Stage “COOL” Speed - cfm

1 1 2 3 4 1 2 3 1 4

+ 1096 1136 1398 1539 665 890 1035 12101 NORM 996 1033 1271 1399 600 810 960 1090

— 896 930 1144 1259 525 690 850 9851 Factory default jumper setting.NOTES - The effect of static pressure is included in air volumes shown. First stage HEAT is approximately 91% of the same second stage HEAT speed position. First stage COOL (two-stage air conditioning units only) is approximately 70% of the same second stage COOL speed position. Continuous Fan Only speed is approximately 38% of the same second stage COOL speed position - minimum 500 cfm. Lennox Harmony III™ Zoning System Applications - Minimum blower speed is 453 cfm.

SL280UH090V48B BLOWER MOTOR WATTS (COOLING)

Jumper Speed Positions

Motor Watts @ Various External Static Pressures - in. wg.First Stage Second Stage

0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1.0“+” (Plus) SETTING (“Adjust” Jumper at “+” Setting)

“COOL” Speed

Tap 1 40 56 75 86 105 128 141 157 173 93 125 144 161 182 209 237 258 286 307 338Tap 2 64 86 105 122 146 169 187 207 227 167 196 240 262 299 328 367 398 433 467 492Tap 3 93 119 141 163 189 213 237 261 286 259 287 321 374 410 451 481 518 555 581 611Tap 4 128 156 188 219 248 281 308 338 366 372 407 465 493 558 604 661 706 726 764 817

“NORM” (Normal) SETTING (“Adjust” Jumper at “NORM” Setting)

“COOL” Speed

Tap 1 35 51 64 79 92 107 122 138 159 81 105 122 139 159 186 200 221 247 263 286Tap 2 50 65 85 114 130 148 173 179 200 112 142 173 206 234 271 300 323 356 395 419Tap 3 75 98 117 136 159 177 187 207 244 189 221 254 289 335 362 400 431 458 504 526Tap 4 98 122 149 180 194 230 252 278 300 288 321 372 398 433 470 507 554 598 623 653

“—” (Minus) SETTING (“Adjust” Jumper at “—” Setting)

“COOL” Speed

Tap 1 32 44 57 71 82 95 107 121 132 74 94 112 130 147 174 189 206 226 245 264Tap 2 43 60 76 91 109 127 143 159 176 86 119 134 161 185 212 236 257 290 320 342Tap 3 55 70 94 116 132 157 171 190 206 138 170 194 226 269 295 325 357 384 414 442Tap 4 80 100 123 147 166 187 210 231 253 204 235 269 312 342 376 425 450 482 516 546

SL280UHV / Page 19

BLOWER DATASL280UH090V48B BLOWER PERFORMANCE (less filter)SINGLE SIDE RETURN AIR0 through 0.8 in. w.g. (Heating) and 0 through 1.0 in. w.g. (Cooling) External Static Pressure Range

“ADJUST” Switch

Positions

Speed Switch PositionsSecond Stage “HEAT” Speed - cfm Second Stage “COOL” Speed - cfm

1 1 2 3 4 1 2 3 1 4+ 1183 1522 1533 1667 1005 1295 1495 1670

1 NORM 1075 1384 1394 1515 895 1155 1345 1495— 968 1246 1255 1364 795 1045 1210 1405

“ADJUST” Switch

Positions

First Stage “HEAT” Speed - cfm First Stage “COOL” Speed - cfm

1 1 2 3 4 1 2 3 1 4

+ 1096 1136 1398 1539 635 900 1010 11701 NORM 996 1033 1271 1399 570 775 930 1040

— 896 930 1144 1259 525 695 805 9551 Factory default jumper setting.NOTES - The effect of static pressure is included in air volumes shown. First stage HEAT is approximately 91% of the same second stage HEAT speed position. First stage COOL (two-stage air conditioning units only) is approximately 70% of the same second stage COOL speed position. Continuous Fan Only speed is approximately 38% of the same second stage COOL speed position - minimum 500 cfm. Lennox Harmony III™ Zoning System Applications - Minimum blower speed is 453 cfm.

SL280UH090V48B BLOWER MOTOR WATTS (COOLING)

Jumper Speed Positions

Motor Watts @ Various External Static Pressures - in. wg.First Stage Second Stage

0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1.0“+” (Plus) SETTING (“Adjust” Jumper at “+” Setting)

“COOL” Speed

Tap 1 34 54 68 85 102 120 142 159 177 79 107 133 148 172 201 226 253 274 301 327Tap 2 64 85 105 124 145 166 186 206 227 151 179 214 247 276 312 339 370 399 433 464Tap 3 85 112 135 157 184 208 233 258 284 230 261 305 348 379 421 453 490 523 565 602Tap 4 110 139 172 201 234 270 294 326 352 478 369 414 462 506 547 597 643 691 735 781

“NORM” (Normal) SETTING (“Adjust” Jumper at “NORM” Setting)

“COOL” Speed

Tap 1 30 46 59 77 87 106 118 143 152 70 93 115 134 153 172 195 219 242 260 286Tap 2 36 56 76 95 120 136 162 175 196 100 132 163 192 214 244 276 307 338 368 402Tap 3 64 88 106 130 149 173 198 222 238 166 192 231 266 303 342 370 410 444 462 493Tap 4 87 118 141 161 194 223 248 275 302 245 273 333 365 396 432 460 503 546 579 635

“—” (Minus) SETTING (“Adjust” Jumper at “—” Setting)

“COOL” Speed

Tap 1 28 43 53 70 83 97 110 120 135 53 72 88 112 133 150 175 191 205 230 245Tap 2 37 56 72 86 106 124 141 158 176 84 111 134 154 185 215 235 260 284 311 336Tap 3 51 69 90 109 129 152 168 187 205 119 152 182 210 244 276 307 338 370 401 432Tap 4 71 94 119 138 158 181 207 233 250 180 211 248 284 316 355 385 419 450 487 521

SL280UHV / Page 20

BLOWER DATASL280UH090V48B BLOWER PERFORMANCE (less filter)SIDE RETURN AIR WITH OPTIONAL RETURN AIR BASE0 through 0.8 in. w.g. (Heating) and 0 through 1.0 in. w.g. (Cooling) External Static Pressure Range

“ADJUST” Switch

Positions

Speed Switch PositionsSecond Stage “HEAT” Speed - cfm Second Stage “COOL” Speed - cfm

1 1 2 3 4 1 2 3 1 4+ 1187 1520 1529 1646 985 1290 1490 1675

1 NORM 1079 1382 1390 1496 900 1125 1345 1525— 971 1244 1251 1346 810 1035 1220 1385

“ADJUST” Switch

Positions

First Stage “HEAT” Speed - cfm First Stage “COOL” Speed - cfm

1 1 2 3 4 1 2 3 1 4

+ 1079 1150 1405 1554 660 900 1025 11751 NORM 981 1045 1277 1413 595 760 925 1045

— 883 941 1149 1272 535 700 850 9701 Factory default jumper setting.NOTES - The effect of static pressure is included in air volumes shown. First stage HEAT is approximately 91% of the same second stage HEAT speed position. First stage COOL (two-stage air conditioning units only) is approximately 70% of the same second stage COOL speed position. Continuous Fan Only speed is approximately 38% of the same second stage COOL speed position - minimum 500 cfm. Lennox Harmony III™ Zoning System Applications - Minimum blower speed is 453 cfm.

SL280UH090V48B BLOWER MOTOR WATTS (COOLING)

Jumper Speed Positions

Motor Watts @ Various External Static Pressures - in. wg.First Stage Second Stage

0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1.0“+” (Plus) SETTING (“Adjust” Jumper at “+” Setting)

“COOL” Speed

Tap 1 34 54 65 84 101 122 138 156 169 75 104 128 146 170 193 224 244 266 300 326Tap 2 57 74 97 120 137 158 177 197 216 124 160 189 216 254 287 319 351 385 416 449Tap 3 76 102 125 147 174 200 223 248 272 208 238 279 319 350 391 422 457 489 529 564Tap 4 106 134 165 193 224 259 283 313 340 302 346 386 426 470 510 554 596 640 680 722

“NORM” (Normal) SETTING (“Adjust” Jumper at “NORM” Setting)

“COOL” Speed

Tap 1 31 47 59 74 89 105 123 139 150 64 88 107 131 150 173 196 217 241 263 285Tap 2 43 61 82 101 118 144 158 177 194 94 123 150 183 213 243 279 300 331 353 393Tap 3 62 85 104 130 151 173 196 216 239 150 180 219 250 294 333 368 399 428 463 497Tap 4 81 113 131 151 187 211 238 264 291 235 263 312 349 387 426 455 489 522 568 608

“—” (Minus) SETTING (“Adjust” Jumper at “—” Setting)

“COOL” Speed

Tap 1 29 40 53 69 83 93 104 122 129 50 69 85 107 127 149 169 187 201 222 237Tap 2 32 50 66 84 101 116 136 153 172 78 105 126 146 174 199 223 247 272 295 319Tap 3 46 65 86 109 127 146 167 187 207 105 135 166 195 227 262 289 319 348 380 411Tap 4 69 92 112 134 156 175 200 221 245 161 195 230 264 298 334 367 401 434 469 503

SL280UHV / Page 21

BLOWER DATASL280UH090V60C BLOWER PERFORMANCE (less filter)BOTTOM RETURN AIR, RETURN AIR FROM BOTH SIDES OR RETURN AIR FROM BOTTOM AND ONE SIDE0 through 0.8 in. w.g. (Heating) and 0 through 1.0 in. w.g. (Cooling) External Static Pressure Range

“ADJUST” Switch

Positions

Speed Switch PositionsSecond Stage “HEAT” Speed - cfm Second Stage “COOL” Speed - cfm

1 1 2 3 4 1 2 3 1 4+ 1319 1595 1656 1828 1575 1865 2110 2305

1 NORM 1199 1450 1505 1662 1440 1685 1910 2120— 1079 1305 1355 1496 1295 1540 1715 1930

“ADJUST” Switch

Positions

First Stage “HEAT” Speed - cfm First Stage “COOL” Speed - cfm

1 1 2 3 4 1 2 3 1 4

+ 1184 1262 1543 1695 1095 1340 1530 16701 NORM 1076 1147 1403 1541 980 1205 1395 1545

— 968 1032 1263 1387 870 1055 1215 13801 Factory default jumper setting.NOTES - The effect of static pressure is included in air volumes shown. First stage HEAT is approximately 91% of the same second stage HEAT speed position. First stage COOL (two-stage air conditioning units only) is approximately 70% of the same second stage COOL speed position. Continuous Fan Only speed is approximately 38% of the same second stage COOL speed position - minimum 500 cfm. Lennox Harmony III™ Zoning System Applications - Minimum blower speed is 478 cfm.

SL280UH090V60C BLOWER MOTOR WATTS (COOLING)

Jumper Speed Positions

Motor Watts @ Various External Static Pressures - in. wg.First Stage Second Stage

0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1.0“+” (Plus) SETTING (“Adjust” Jumper at “+” Setting)

“COOL” Speed

Tap 1 89 113 136 159 182 204 228 251 275 218 245 291 327 372 398 436 474 505 532 579Tap 2 133 165 198 230 262 295 327 359 391 361 405 453 495 542 590 645 696 732 770 814Tap 3 202 235 273 308 343 384 413 448 480 543 589 639 684 753 809 861 894 951 1004 1035Tap 4 279 316 355 394 432 473 509 547 584 772 808 877 946 1000 1056 1089 1146 1190 1255 1266

“NORM” (Normal) SETTING (“Adjust” Jumper at “NORM” Setting)

“COOL” Speed

Tap 1 70 92 108 134 159 174 196 215 242 160 195 228 265 291 340 364 397 442 469 500Tap 2 99 130 152 183 218 241 265 302 327 282 319 361 401 436 475 518 550 591 644 665Tap 3 148 180 210 250 285 309 343 377 411 385 442 468 531 581 623 676 720 773 813 868Tap 4 214 241 277 318 350 388 423 449 469 553 591 655 713 781 819 868 922 967 1026 1066

“—” (Minus) SETTING (“Adjust” Jumper at “—” Setting)

“COOL” Speed

Tap 1 54 70 91 110 129 154 166 185 200 107 151 177 206 245 272 298 332 398 423 449Tap 2 78 102 127 151 176 201 225 250 274 204 231 265 307 350 383 416 445 481 512 538Tap 3 110 139 166 195 223 249 280 308 338 277 331 355 400 439 488 529 570 603 659 702Tap 4 149 185 217 251 284 314 352 386 422 410 456 505 543 595 635 692 729 777 829 867

SL280UHV / Page 22

BLOWER DATASL280UH090V60C BLOWER PERFORMANCE (less filter)SINGLE SIDE RETURN AIR0 through 0.8 in. w.g. (Heating) and 0 through 1.0 in. w.g. (Cooling) External Static Pressure Range

“ADJUST” Switch

Positions

Speed Switch PositionsSecond Stage “HEAT” Speed - cfm Second Stage “COOL” Speed - cfm

1 1 2 3 4 1 2 3 1 4+ 1253 1540 1610 1789 1515 1680 1915 2225

1 NORM 1139 1400 1464 1626 1385 1540 1735 2055— 1025 1260 1318 1463 1220 1385 1580 1825

“ADJUST” Switch

Positions

First Stage “HEAT” Speed - cfm First Stage “COOL” Speed - cfm

1 1 2 3 4 1 2 3 1 4

+ 1144 1208 1477 1640 1035 1180 1375 16051 NORM 1040 1098 1343 1491 915 1065 1220 1475

— 936 988 1209 1342 825 915 1080 13201 Factory default jumper setting.NOTES - The effect of static pressure is included in air volumes shown. First stage HEAT is approximately 91% of the same second stage HEAT speed position. First stage COOL (two-stage air conditioning units only) is approximately 70% of the same second stage COOL speed position. Continuous Fan Only speed is approximately 38% of the same second stage COOL speed position - minimum 500 cfm. Lennox Harmony III™ Zoning System Applications - Minimum blower speed is 478 cfm.

SL280UH090V60C BLOWER MOTOR WATTS (COOLING)

Jumper Speed Positions

Motor Watts @ Various External Static Pressures - in. wg.First Stage Second Stage

0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1.0“+” (Plus) SETTING (“Adjust” Jumper at “+” Setting)

“COOL” Speed

Tap 1 75 104 122 142 163 189 214 239 264 219 243 283 317 363 384 424 441 484 511 543Tap 2 98 128 150 181 205 236 259 289 317 289 333 351 405 444 490 523 564 604 636 668Tap 3 144 172 205 242 279 306 344 367 396 417 451 507 557 605 655 694 733 788 824 867Tap 4 245 272 307 359 386 421 447 473 520 709 743 795 855 906 955 1009 1049 1095 1131 1165

“NORM” (Normal) SETTING (“Adjust” Jumper at “NORM” Setting)

“COOL” Speed

Tap 1 66 88 109 127 150 165 189 209 236 157 185 219 259 290 328 353 394 425 452 480Tap 2 79 104 127 147 173 201 225 248 268 222 246 284 328 370 397 416 460 490 519 555Tap 3 106 137 164 190 215 250 278 307 333 307 349 387 435 463 505 553 599 634 674 714Tap 4 192 224 260 298 338 365 400 438 467 563 597 664 717 756 820 881 907 972 1007 1039

“—” (Minus) SETTING (“Adjust” Jumper at “—” Setting)

“COOL” Speed

Tap 1 44 65 80 103 121 142 163 180 199 114 141 173 200 230 259 289 318 347 374 401Tap 2 63 82 105 125 145 166 188 203 227 159 187 226 252 288 323 353 388 419 444 475Tap 3 82 108 131 151 178 203 229 253 274 236 263 302 344 382 420 443 478 514 548 583Tap 4 127 159 187 213 252 281 305 338 371 361 393 450 494 537 586 616 672 711 752 787

SL280UHV / Page 23

BLOWER DATASL280UH090V60C BLOWER PERFORMANCE (less filter)SIDE RETURN AIR WITH OPTIONAL RETURN AIR BASE0 through 0.8 in. w.g. (Heating) and 0 through 1.0 in. w.g. (Cooling) External Static Pressure Range

“ADJUST” Switch

Positions

Speed Switch PositionsSecond Stage “HEAT” Speed - cfm Second Stage “COOL” Speed - cfm

1 1 2 3 4 1 2 3 1 4+ 1258 1595 1610 1777 1515 1715 1930 2240

1 NORM 1144 1450 1464 1615 1375 1555 1750 2065— 1030 1305 1318 1454 1215 1400 1580 1830

“ADJUST” Switch

Positions

First Stage “HEAT” Speed - cfm First Stage “COOL” Speed - cfm

1 1 2 3 4 1 2 3 1 4

+ 1124 1205 1476 1646 1025 1185 1375 15701 NORM 1022 1095 1342 1496 945 1070 1250 1465

— 920 986 1208 1346 845 945 1110 13001 Factory default jumper setting.NOTES - The effect of static pressure is included in air volumes shown. First stage HEAT is approximately 91% of the same second stage HEAT speed position. First stage COOL (two-stage air conditioning units only) is approximately 70% of the same second stage COOL speed position. Continuous Fan Only speed is approximately 38% of the same second stage COOL speed position - minimum 500 cfm. Lennox Harmony III™ Zoning System Applications - Minimum blower speed is 478 cfm.

SL280UH090V60C BLOWER MOTOR WATTS (COOLING)

Jumper Speed Positions

Motor Watts @ Various External Static Pressures - in. wg.First Stage Second Stage

0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1.0“+” (Plus) SETTING (“Adjust” Jumper at “+” Setting)

“COOL” Speed

Tap 1 74 97 123 139 160 184 212 233 255 194 217 258 292 328 362 396 428 463 484 509Tap 2 92 121 149 171 200 233 261 283 315 282 320 352 397 428 477 517 550 588 621 655Tap 3 138 170 198 240 269 300 334 363 395 385 420 474 530 566 626 661 708 750 791 835Tap 4 216 245 282 333 364 379 430 455 496 658 686 742 808 864 910 960 1006 1043 1087 1116

“NORM” (Normal) SETTING (“Adjust” Jumper at “NORM” Setting)

“COOL” Speed

Tap 1 63 85 102 123 144 160 183 201 225 145 180 203 239 273 309 335 370 398 432 464Tap 2 74 100 124 149 164 194 221 245 270 217 247 285 319 360 391 415 459 488 522 556Tap 3 104 133 162 188 219 246 276 309 328 293 321 385 421 443 494 547 571 605 663 691Tap 4 178 210 239 281 319 347 380 415 441 518 567 609 683 719 774 831 882 911 976 1026

“—” (Minus) SETTING (“Adjust” Jumper at “—” Setting)

“COOL” Speed

Tap 1 43 62 80 104 123 144 163 180 199 101 128 163 186 214 245 278 299 332 355 391Tap 2 61 83 102 124 142 164 188 206 228 158 184 226 254 284 321 347 383 419 446 470Tap 3 78 108 127 147 172 202 229 252 275 235 265 304 349 382 397 439 470 510 548 583Tap 4 113 146 174 204 238 269 299 326 364 326 362 413 457 501 546 590 632 680 719 746

SL280UHV / Page 24

BLOWER DATASL280UH110V60C BLOWER PERFORMANCE (less filter)BOTTOM RETURN AIR, RETURN AIR FROM BOTH SIDES OR RETURN AIR FROM BOTTOM AND ONE SIDE0 through 0.8 in. w.g. (Heating) and 0 through 1.0 in. w.g. (Cooling) External Static Pressure Range

“ADJUST” Switch

Positions

Speed Switch PositionsSecond Stage “HEAT” Speed - cfm Second Stage “COOL” Speed - cfm

1 1 2 3 4 1 2 3 1 4+ 1546 1935 1950 2175 1535 1705 1905 2205

1 NORM 1405 1759 1773 1977 1400 1560 1710 2015— 1265 1583 1596 1779 1260 1395 1555 1810

“ADJUST” Switch

Positions

First Stage “HEAT” Speed - cfm First Stage “COOL” Speed - cfm

1 1 2 3 4 1 2 3 1 4

+ 1431 1497 1783 1977 1065 1230 1355 15601 NORM 1301 1361 1621 1797 955 1085 1205 1425

— 1171 1225 1459 1617 845 960 1075 12651 Factory default jumper setting.NOTES - The effect of static pressure is included in air volumes shown. First stage HEAT is approximately 91% of the same second stage HEAT speed position. First stage COOL (two-stage air conditioning units only) is approximately 70% of the same second stage COOL speed position. Continuous Fan Only speed is approximately 38% of the same second stage COOL speed position - minimum 500 cfm. Lennox Harmony III™ Zoning System Applications - Minimum blower speed is 483 cfm.

SL280UH110V60C BLOWER MOTOR WATTS (COOLING)

Jumper Speed Positions

Motor Watts @ Various External Static Pressures - in. wg.First Stage Second Stage

0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1.0“+” (Plus) SETTING (“Adjust” Jumper at “+” Setting)

“COOL” Speed

Tap 1 89 116 144 159 201 222 245 274 298 234 259 304 360 385 408 451 484 530 553 596Tap 2 108 135 170 196 228 259 286 320 343 297 340 380 409 459 502 539 570 616 660 702Tap 3 136 164 202 236 269 300 331 370 392 390 420 497 530 585 630 677 727 777 815 854Tap 4 252 275 329 366 396 441 472 493 537 702 734 780 841 907 957 1013 1048 1100 1124 1148

“NORM” (Normal) SETTING (“Adjust” Jumper at “NORM” Setting)

“COOL” Speed

Tap 1 71 98 118 139 166 184 207 237 262 179 203 244 281 329 356 388 425 453 480 519Tap 2 86 118 138 154 187 212 237 266 291 223 251 288 342 377 399 449 474 513 548 578Tap 3 99 132 160 184 222 254 277 308 343 299 341 384 420 472 497 540 599 632 674 709Tap 4 192 227 258 299 333 376 409 434 471 493 540 591 653 705 760 829 869 919 965 1005

“—” (Minus) SETTING (“Adjust” Jumper at “—” Setting)

“COOL” Speed

Tap 1 60 78 104 122 144 168 187 205 226 133 162 191 225 262 289 324 357 385 410 436Tap 2 68 94 116 132 150 177 203 220 251 163 189 224 263 292 333 364 392 431 458 473Tap 3 80 109 128 151 174 204 229 252 279 224 251 293 326 370 398 439 467 491 531 570Tap 4 131 165 196 226 265 300 336 356 397 365 406 460 511 558 603 643 705 743 792 835

SL280UHV / Page 25

BLOWER DATASL280UH110V60C BLOWER PERFORMANCE (less filter)SINGLE SIDE RETURN AIR0 through 0.8 in. w.g. (Heating) and 0 through 1.0 in. w.g. (Cooling) External Static Pressure Range

“ADJUST” Switch

Positions

Speed Switch PositionsSecond Stage “HEAT” Speed - cfm Second Stage “COOL” Speed - cfm

1 1 2 3 4 1 2 3 1 4+ 1505 1880 1925 2094 1505 1685 1855 2125

1 NORM 1368 1709 1750 1904 1375 1525 1685 1935— 1231 1538 1575 1714 1235 1380 1500 1730

“ADJUST” Switch

Positions

First Stage “HEAT” Speed - cfm First Stage “COOL” Speed - cfm

1 1 2 3 4 1 2 3 1 4

+ 1375 1455 1730 1903 1030 1170 1300 15251 NORM 1250 1323 1573 1730 930 1050 1165 1395

— 1125 1191 1416 1557 810 935 1040 12451 Factory default jumper setting.NOTES - The effect of static pressure is included in air volumes shown. First stage HEAT is approximately 91% of the same second stage HEAT speed position. First stage COOL (two-stage air conditioning units only) is approximately 70% of the same second stage COOL speed position. Continuous Fan Only speed is approximately 38% of the same second stage COOL speed position - minimum 500 cfm. Lennox Harmony III™ Zoning System Applications - Minimum blower speed is 483 cfm.

SL280UH110V60C BLOWER MOTOR WATTS (COOLING)

Jumper Speed Positions

Motor Watts @ Various External Static Pressures - in. wg.First Stage Second Stage

0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1.0“+” (Plus) SETTING (“Adjust” Jumper at “+” Setting)

“COOL” Speed

Tap 1 84 116 131 156 193 216 238 265 292 218 245 293 336 378 415 454 488 516 557 601Tap 2 99 128 156 195 216 245 280 309 335 292 333 381 412 454 490 535 577 618 662 704Tap 3 128 157 193 226 266 293 321 360 387 373 412 475 518 573 617 661 710 771 800 857Tap 4 238 274 303 354 388 413 460 493 524 675 717 786 854 898 983 1017 1071 1112 1157 1186

“NORM” (Normal) SETTING (“Adjust” Jumper at “NORM” Setting)

“COOL” Speed

Tap 1 73 96 121 140 154 184 206 228 255 166 192 237 271 319 345 382 419 459 480 515Tap 2 81 108 133 156 175 207 230 253 285 220 248 290 328 372 405 447 474 513 540 577Tap 3 92 123 148 185 209 246 277 302 331 290 328 374 415 452 487 536 576 605 653 701Tap 4 175 202 247 285 327 364 388 426 457 477 511 590 647 690 739 789 843 901 947 998

“—” (Minus) SETTING (“Adjust” Jumper at “—” Setting)

“COOL” Speed

Tap 1 56 74 98 116 141 157 179 199 216 129 157 198 221 259 298 325 354 387 418 451Tap 2 69 92 111 132 155 174 197 214 243 166 186 232 268 289 339 365 389 429 454 479Tap 3 78 107 128 149 172 203 230 249 278 204 225 282 312 353 383 406 452 489 519 552Tap 4 124 157 186 220 261 291 321 352 386 326 372 427 464 526 566 608 658 706 762 808

SL280UHV / Page 26

BLOWER DATASL280UH110V60C BLOWER PERFORMANCE (less filter)SIDE RETURN AIR WITH OPTIONAL RETURN AIR BASE0 through 0.8 in. w.g. (Heating) and 0 through 1.0 in. w.g. (Cooling) External Static Pressure Range

“ADJUST” Switch

Positions

Speed Switch PositionsSecond Stage “HEAT” Speed - cfm Second Stage “COOL” Speed - cfm

1 1 2 3 4 1 2 3 1 4+ 1504 1894 1947 2126 1595 1660 1835 2110

1 NORM 1367 1722 1770 1933 1465 1535 1650 1940— 1230 1550 1593 1740 1310 1365 1510 1735

“ADJUST” Switch

Positions

First Stage “HEAT” Speed - cfm First Stage “COOL” Speed - cfm

1 1 2 3 4 1 2 3 1 4

+ 1377 1450 1734 1924 1110 1175 1300 15151 NORM 1252 1318 1576 1749 970 1050 1160 1380

— 1127 1186 1418 1574 885 920 1055 12101 Factory default jumper setting.NOTES - The effect of static pressure is included in air volumes shown. First stage HEAT is approximately 91% of the same second stage HEAT speed position. First stage COOL (two-stage air conditioning units only) is approximately 70% of the same second stage COOL speed position. Continuous Fan Only speed is approximately 38% of the same second stage COOL speed position - minimum 500 cfm. Lennox Harmony III™ Zoning System Applications - Minimum blower speed is 483 cfm.

SL280UH110V60C BLOWER MOTOR WATTS (COOLING)

Jumper Speed Positions

Motor Watts @ Various External Static Pressures - in. wg.First Stage Second Stage

0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1.0“+” (Plus) SETTING (“Adjust” Jumper at “+” Setting)

“COOL” Speed

Tap 1 81 112 131 153 183 207 237 260 286 221 247 300 343 371 416 441 492 518 557 595Tap 2 87 120 144 171 201 227 261 291 317 245 279 326 369 405 441 488 527 557 605 642Tap 3 131 165 193 219 257 293 317 355 379 315 354 411 463 508 558 603 652 693 741 793Tap 4 196 225 267 307 342 379 411 451 475 541 591 646 696 744 802 859 911 961 1007 1054

“NORM” (Normal) SETTING (“Adjust” Jumper at “NORM” Setting)

“COOL” Speed

Tap 1 64 92 111 133 151 177 203 228 254 170 200 230 270 311 348 383 411 435 474 503Tap 2 72 99 123 144 164 198 224 246 270 196 220 268 304 334 372 399 446 471 500 538Tap 3 97 130 150 185 212 239 276 302 328 243 278 328 370 407 446 482 531 569 604 652Tap 4 142 176 207 245 286 322 349 384 418 383 427 478 529 592 638 687 728 780 829 872

“—” (Minus) SETTING (“Adjust” Jumper at “—” Setting)

“COOL” Speed

Tap 1 53 74 93 113 133 153 175 194 215 115 147 176 207 248 277 310 346 376 403 432Tap 2 57 79 99 124 143 164 185 207 230 136 164 201 236 273 308 342 374 412 440 462Tap 3 81 109 133 151 173 205 224 254 280 184 214 247 290 329 365 402 431 466 489 530Tap 4 101 135 162 191 224 258 292 320 345 272 317 355 396 446 488 529 574 612 650 707

SL280UHV / Page 27

BLOWER DATASL280UH135V60D BLOWER PERFORMANCE (less filter)BOTTOM RETURN AIR, RETURN AIR FROM BOTH SIDES OR RETURN AIR FROM BOTTOM AND ONE SIDE0 through 0.8 in. w.g. (Heating) and 0 through 1.0 in. w.g. (Cooling) External Static Pressure Range

“ADJUST” Switch

Positions

Speed Switch PositionsSecond Stage “HEAT” Speed - cfm Second Stage “COOL” Speed - cfm

1 1 2 3 4 1 2 3 1 4+ 1676 1848 1883 2299 1500 1600 1840 2235

1 NORM 1524 1680 1712 2090 1420 1510 1695 2105— 1372 1512 1541 1881 1220 1320 1505 1840

“ADJUST” Switch

Positions

First Stage “HEAT” Speed - cfm First Stage “COOL” Speed - cfm

1 1 2 3 4 1 2 3 1 4

+ 1554 1665 1742 2113 1030 1120 1310 16351 NORM 1413 1514 1584 1921 940 1020 1175 1485

— 1272 1363 1426 1729 825 900 1050 13351 Factory default jumper setting.NOTES - The effect of static pressure is included in air volumes shown. First stage HEAT is approximately 91% of the same second stage HEAT speed position. First stage COOL (two-stage air conditioning units only) is approximately 70% of the same second stage COOL speed position. Continuous Fan Only speed is approximately 38% of the same second stage COOL speed position - minimum 500 cfm. Lennox Harmony III™ Zoning System Applications - Minimum blower speed is 495 cfm.

SL280UH135V60D BLOWER MOTOR WATTS (COOLING)

Jumper Speed Positions

Motor Watts @ Various External Static Pressures - in. wg.First Stage Second Stage

0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1.0“+” (Plus) SETTING (“Adjust” Jumper at “+” Setting)

“COOL” Speed

Tap 1 72 99 123 145 177 204 228 253 277 180 208 244 299 334 374 408 432 478 511 539Tap 2 80 108 137 164 194 224 252 280 308 214 249 291 340 384 422 450 493 530 579 619Tap 3 119 154 180 227 259 298 328 363 392 309 359 404 464 509 560 622 661 715 757 809Tap 4 239 271 320 370 394 439 477 513 559 655 683 774 832 888 957 1022 1053 1122 1161 1206

“NORM” (Normal) SETTING (“Adjust” Jumper at “NORM” Setting)

“COOL” Speed

Tap 1 52 79 95 120 147 167 188 215 238 127 161 197 238 277 316 349 386 412 457 493Tap 2 63 87 116 137 158 188 210 239 262 160 194 229 280 317 350 395 431 451 502 540Tap 3 86 115 152 174 203 236 270 298 328 227 266 333 369 373 405 445 541 579 601 642Tap 4 160 194 229 278 318 359 394 429 455 468 521 580 647 716 763 819 872 934 994 1053

“—” (Minus) SETTING (“Adjust” Jumper at “—” Setting)

“COOL” Speed

Tap 1 45 65 87 107 128 152 170 191 210 103 133 167 199 235 268 294 325 366 391 425Tap 2 50 70 95 120 140 166 185 208 228 109 143 178 213 247 283 320 359 380 421 455Tap 3 71 97 123 147 175 204 228 254 279 171 203 235 294 328 370 401 439 478 515 543Tap 4 127 160 196 232 265 299 334 369 403 294 343 402 457 510 576 619 673 720 781 835

SL280UHV / Page 28

BLOWER DATASL280UH135V60D BLOWER PERFORMANCE (less filter)SINGLE SIDE RETURN AIR0 through 0.8 in. w.g. (Heating) and 0 through 1.0 in. w.g. (Cooling) External Static Pressure Range

“ADJUST” Switch

Positions

Speed Switch PositionsSecond Stage “HEAT” Speed - cfm Second Stage “COOL” Speed - cfm

1 1 2 3 4 1 2 3 1 4+ 1660 1815 1849 2255 1525 1600 1835 2255

1 NORM 1509 1650 1681 2050 1355 1430 1630 2035— 1358 1485 1513 1845 1235 1315 1515 1845

“ADJUST” Switch

Positions

First Stage “HEAT” Speed - cfm First Stage “COOL” Speed - cfm

1 1 2 3 4 1 2 3 1 4

+ 1521 1640 1724 2078 1020 1115 1320 16351 NORM 1383 1491 1567 1889 940 990 1170 1465

— 1245 1342 1410 1700 825 910 1050 13501 Factory default jumper setting.NOTES - The effect of static pressure is included in air volumes shown. First stage HEAT is approximately 91% of the same second stage HEAT speed position. First stage COOL (two-stage air conditioning units only) is approximately 70% of the same second stage COOL speed position. Continuous Fan Only speed is approximately 38% of the same second stage COOL speed position - minimum 500 cfm. Lennox Harmony III™ Zoning System Applications - Minimum blower speed is 495 cfm.

SL280UH135V60D BLOWER MOTOR WATTS (COOLING)

Jumper Speed Positions

Motor Watts @ Various External Static Pressures - in. wg.First Stage Second Stage

0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1.0“+” (Plus) SETTING (“Adjust” Jumper at “+” Setting)

“COOL” Speed

Tap 1 66 97 120 138 165 195 220 245 279 189 220 259 298 333 378 410 441 486 517 543Tap 2 82 111 140 161 190 218 255 269 306 224 255 298 354 389 422 455 499 549 571 616Tap 3 114 148 177 218 254 288 320 359 381 317 359 418 459 511 557 615 655 701 747 795Tap 4 233 268 307 357 396 430 475 503 544 668 704 766 831 898 941 995 1048 1103 1144 1176

“NORM” (Normal) SETTING (“Adjust” Jumper at “NORM” Setting)

“COOL” Speed

Tap 1 49 76 97 121 146 170 198 223 246 130 166 200 238 281 318 350 398 425 462 490Tap 2 58 89 109 130 161 193 221 238 267 163 185 240 290 318 347 398 432 460 500 538Tap 3 76 109 135 170 200 231 268 290 324 233 281 333 368 408 456 499 539 591 644 693Tap 4 162 195 230 282 318 356 391 425 457 484 529 603 651 721 783 832 898 951 994 1051

“—” (Minus) SETTING (“Adjust” Jumper at “—” Setting)

“COOL” Speed

Tap 1 41 60 86 104 129 149 169 190 212 94 130 161 189 221 259 288 317 355 390 421Tap 2 50 72 96 120 139 160 184 201 235 114 147 177 211 256 290 330 354 385 422 453Tap 3 73 101 123 147 167 196 221 250 274 177 207 245 291 331 370 413 431 475 509 543Tap 4 118 151 181 231 261 303 327 363 399 328 369 431 477 535 580 638 683 723 777 827

SL280UHV / Page 29

BLOWER DATASL280UH135V60D BLOWER PERFORMANCE (less filter)SIDE RETURN AIR WITH OPTIONAL RETURN AIR BASE0 through 0.8 in. w.g. (Heating) and 0 through 1.0 in. w.g. (Cooling) External Static Pressure Range

“ADJUST” Switch

Positions

Speed Switch PositionsSecond Stage “HEAT” Speed - cfm Second Stage “COOL” Speed - cfm

1 1 2 3 4 1 2 3 1 4+ 1651 1815 1855 2257 1525 1610 1825 2235

1 NORM 1501 1650 1686 2052 1360 1445 1645 2035— 1351 1485 1517 1847 1220 1310 1515 1845

“ADJUST” Switch

Positions

First Stage “HEAT” Speed - cfm First Stage “COOL” Speed - cfm

1 1 2 3 4 1 2 3 1 4

+ 1513 1632 1714 2063 1040 1120 1300 16001 NORM 1375 1484 1558 1875 920 1005 1160 1435

— 1238 1336 1402 1688 830 895 1035 13251 Factory default jumper setting.NOTES - The effect of static pressure is included in air volumes shown. First stage HEAT is approximately 91% of the same second stage HEAT speed position. First stage COOL (two-stage air conditioning units only) is approximately 70% of the same second stage COOL speed position. Continuous Fan Only speed is approximately 38% of the same second stage COOL speed position - minimum 500 cfm. Lennox Harmony III™ Zoning System Applications - Minimum blower speed is 495 cfm.

SL280UH135V60D BLOWER MOTOR WATTS (COOLING)

Jumper Speed Positions

Motor Watts @ Various External Static Pressures - in. wg.First Stage Second Stage

0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1.0“+” (Plus) SETTING (“Adjust” Jumper at “+” Setting)

“COOL” Speed

Tap 1 63 90 116 139 160 194 218 248 268 160 195 232 269 314 357 391 438 469 493 531Tap 2 70 104 127 150 183 209 242 265 306 196 233 273 313 363 402 442 470 520 553 592Tap 3 98 134 168 200 243 271 306 342 377 276 331 364 426 473 521 568 618 664 726 761Tap 4 200 239 273 324 362 391 438 474 514 584 628 680 747 812 881 922 985 1035 1069 1116

“NORM” (Normal) SETTING (“Adjust” Jumper at “NORM” Setting)

“COOL” Speed

Tap 1 46 76 96 123 143 168 192 225 252 121 166 187 231 264 310 342 374 414 448 494Tap 2 55 80 111 132 155 188 210 242 260 146 174 224 263 306 344 381 417 464 490 525Tap 3 72 107 127 167 200 228 264 296 316 220 258 316 349 404 441 482 522 571 609 666Tap 4 142 183 215 251 315 334 377 411 454 431 466 550 604 677 725 780 828 888 941 998

“—” (Minus) SETTING (“Adjust” Jumper at “—” Setting)

“COOL” Speed

Tap 1 41 62 86 102 124 145 167 189 210 85 116 154 178 208 242 281 309 340 375 401Tap 2 47 69 93 115 136 157 181 201 228 104 145 174 202 242 281 310 343 374 432 448Tap 3 61 90 117 136 159 191 219 245 272 158 185 228 279 312 352 396 431 466 495 526Tap 4 103 138 176 203 246 274 312 347 382 278 320 383 431 475 542 592 646 686 733 779

NOTE - Due to Lennox’ ongoing commitment to quality, Specifications, Ratings and Dimensions subject to change without notice and without incurring liability. Improper installation, adjustment, alteration, service or maintenance can cause property damage or personal injury. Installation and service must be performed by a qualified installer and servicing agency. ©2010 Lennox Industries, Inc.

Visit us at www.lennox.com

For the latest technical information, www.lennoxdavenet.com

Contact us at 1-800-4-LENNOX