fundamentals of teleprotection systems

28
ABB Automation Utility Communication Systems CHPAU NKT F 1 Fundamentals of Teleprotection Systems 27.06.2001

Upload: mani2010nair

Post on 08-Apr-2015

3.876 views

Category:

Documents


39 download

TRANSCRIPT

Page 1: Fundamentals of Teleprotection Systems

ABB AutomationUtility Communication Systems CHPAU NKT F 1

Fundamentalsof

TeleprotectionSystems

27.06.2001

Page 2: Fundamentals of Teleprotection Systems

ABB AutomationUtility Communication Systems CHPAU NKT F 2

Teleprotection - Contents

• Introduction / Protection Systems

• Protection Schemes / Applications

• Parameters in Teleprotection

• Modulation Methods

• Transmission Principles

• Transmission Equipment

Page 3: Fundamentals of Teleprotection Systems

ABB AutomationUtility Communication Systems CHPAU NKT F 3

Teleprotection - Introduction

• What is it ?-> Tele-Communication + Protection - Signalling

• Where is it used ?-> Mainly at the higher and highest voltage levels

• Why is it used ?-> Clearance of faults within the shortest possible time

Page 4: Fundamentals of Teleprotection Systems

ABB AutomationUtility Communication Systems CHPAU NKT F 4

TPS Standards and Publications

IEC standards:

IEC 60834-1 Teleprotection equipment of power systems - Performance and testing Part 1: Narrow-band systems (First edition, 1988)Part 1: Command systems (Second edition, 1999)

IEC 60834-2 Performance and testing of teleprotection equipment of power systemsPart 2: Analogue comparison systems (First Edition 1993)

CIGRE publications:

"Teleprotection Guide", Study Committees 34 + 35, Joint Working Group on Teleprotection, 1969;

Revised Version "Protection Systems Using Telecommunication", 1985Revised Version "Protection Using Telecommunications", 2000 (in preparation)

Page 5: Fundamentals of Teleprotection Systems

ABB AutomationUtility Communication Systems CHPAU NKT F 5

Protection System Architecture

Substation A

HV-line

Substation B

PhysicalLink

Telecommunication System

Tele-protectionEquipment

Tele-protectionEquipment

Teleprotection System

ProtectionRelay

ProtectionRelay

Protection System

Page 6: Fundamentals of Teleprotection Systems

ABB AutomationUtility Communication Systems CHPAU NKT F 6

Protection Signal Transmission

Type of Information:

• Continuous signals

• Magnitude and/or phase of power frequency currents

• Command type signals (on/off)

• Trip / do not trip

Page 7: Fundamentals of Teleprotection Systems

ABB AutomationUtility Communication Systems CHPAU NKT F 7

Protection Systems

Local Information Information from all points

Signal-transmissionnot required

Signal-transmissionrequired

Not selective Selective

with time delay No time delay

conditionally selective

Protection system based on:

Page 8: Fundamentals of Teleprotection Systems

ABB AutomationUtility Communication Systems CHPAU NKT F 8

Signal Transmission for Line Protection

Amplitudeand/orPhase

command =Blocking

of breaker tripping

command =Permission of / direct

breaker tripping

Quantitative (analogue)Information

Binary (yes / no)Information

commands

SIGNAL TRANSMISSIONIS

ESSENTIAL

SIGNAL TRANSMISSIONIS

SUPPLEMENTARY

Page 9: Fundamentals of Teleprotection Systems

ABB AutomationUtility Communication Systems CHPAU NKT F 9

Distance Protection

B

A, B, C StationsRA,RB, RC Protection RelayTA1, TA2, TA3 Operating Times, Relay ATB1, TB2, TB3 Operating Times, Relay B

Typical stepped distance/time characteristics

RA RB RC

A C

Distance

Operating Time

ZONE 1

ZONE 2

ZONE 3

TA2

TA1

TB2

TB1

TA3

Page 10: Fundamentals of Teleprotection Systems

ABB AutomationUtility Communication Systems CHPAU NKT F 10

Distance Line Protection

NSD

RBC

NSD

RCB

LBC

BC1

CB1

L

FB C

B, C SubstationsLBC Protected line sectionRBC,RCB Protection relayBC1, CB1 Zone 1 reach, 85% of line section

F Line fault

L Communication channel(PLC, Microwave, Cable)

Permissive Underreach Transferred Tripping (PUTT)

Page 11: Fundamentals of Teleprotection Systems

ABB AutomationUtility Communication Systems CHPAU NKT F 11

Distance Line Protection

NSD

RBC

NSD

RCB

LBC

BC1

CB1

L

FB C

B, C SubstationsLBC Protected line sectionRBC,RCB Protection relayBC1, CB1 Zone 1 reach, 130% of line section

F Line fault

L Communication channel(PLC, Microwave, Cable)

Permissive Overreach Transferred Tripping (POTT)

Page 12: Fundamentals of Teleprotection Systems

ABB AutomationUtility Communication Systems CHPAU NKT F 12

Distance Line Protection

NSD

RBC

NSD

RCB

LBC

BC1

CB1

L

FB C

B, C SubstationsLBC Protected line sectionRBC,RCB Protection relayBC1, CB1 Zone 1 reach, 85% of line section

F Line fault

L Communication channel(PLC, Microwave, Cable)

Direct Transfer Tripping (DTT)

Page 13: Fundamentals of Teleprotection Systems

ABB AutomationUtility Communication Systems CHPAU NKT F 13

Transformer ProtectionExample for direct tripping

L

B

C

P Pilot cable

L HV Transmission Line or -Cable

NSD 70C

NSD 70C

P

Page 14: Fundamentals of Teleprotection Systems

ABB AutomationUtility Communication Systems CHPAU NKT F 14

Distance Line Protection

NSD

BCe

NSD

RCB

LBC

BCi

CBi

L

FB C

B, C SubstationsLBC Protected line sectionRBC,RCB Protection relayBCi, CBi Zone 1 reach, 130% in direction of the protected line sectionBCe, CBe Range of protection relay in direction of busbars

F Line faultL Communication channel

(PLC, Microwave, Cable)

Blocking

RBC

CBe

Page 15: Fundamentals of Teleprotection Systems

ABB AutomationUtility Communication Systems CHPAU NKT F 15

Teleprotection command transmission

Transmissiontime

Commandinput (local)

Commandoutput (remote)

GenuineCommand

Disturbance,Impairments

MissingCommand

Dependability

UnwantedCommand

Security

Page 16: Fundamentals of Teleprotection Systems

ABB AutomationUtility Communication Systems CHPAU NKT F 16

Telecommunication Channel Impairments

Impairments resulting from interference and noise

• Isolater / breaker operation• 50/60 Hz harmonics (pilot cables)• Corona noise (PLC channels)• Fading (microwave channels)• Jitter (digital networks)• Temporary loss of synchronism (digital networks)• Signal interruptions• etc.

Disturbed signals may cause protection equipment to maloperate

Page 17: Fundamentals of Teleprotection Systems

ABB AutomationUtility Communication Systems CHPAU NKT F 17

Bandwidth or Data Rate

Optimization / Exchange according to application

TransmissionTime

Performance Criteria for Teleprotection

Dependability

(Probabilityof missingcommand)

Security

(Probability of unwanted command)

Page 18: Fundamentals of Teleprotection Systems

ABB AutomationUtility Communication Systems CHPAU NKT F 18

Line Protection

Designation Short description Typical distance Requirements for trans-relay setting (%) mission channel as regards

Step 1Speed Security Dependability

1 Permissive underreach Starting of distance relay 85 M-H M-H Htransferred tripping permits tripping

2 Permissive overreach Directional comparison 130 H M Htransferred tripping (signal permits tripping)

3 Permissive underreach Carrier acceleration 85 (130*) H L-M Htransferred acceleration by extension of step (*)

4 Blocking (direct overreach, Blocking signals are transmitted 130 S L Htransferred blocking) over healthy lines

5 Blocking Signal inhibits step extension (*) 85 (130*) H-S L M

6 Unblocking Loss of guard signal permits 130 H M Mtripping for limited time only

7 Direct underreach Status of relay at receiving end 85 M-H S Htransferred tripping not taken into account

L = Low M = Medium H = High S = Very severe requirements

Possible Signal Connections Between two Distance Relays

Page 19: Fundamentals of Teleprotection Systems

ABB AutomationUtility Communication Systems CHPAU NKT F 19

Total Fault-Clearance-Time

• Time delay between fault occurrence and line tripping

• The fault-clearance time results from:• Relay-time (fault detection) TREL

• Command transmission time TAC

• Switching delay of line breaker TBR

• Typical values:TTotal = TREL + TAC + TBR

75 ms = 20 ms + 15 ms + 40 ms

• Target: TTotal = less than 100 ms, Worst Case = 4.5 to 5 cycles max. (50 Hz)

Page 20: Fundamentals of Teleprotection Systems

ABB AutomationUtility Communication Systems CHPAU NKT F 20

Typical requirements for different applications

• Line protection with permissive transfer tripping:• Transmission time T0 = 10 ... 20 ms• Dependability Plost command 10-2 ... 10-3

• Security Pfalse command 10-3 ... 10-4

• Line protection with blocking system:• Transmission time T0 = 6 ... 15 ms• Dependability Plost command 10-3

• Security Pfalse command 10-2

• Direct transfer tripping (e.g. transformer protection):• Transmission time T0 = 20 ... 50 ms• Dependability Plost command 10-3 ... 10-4

• Security Pfalse command 10-5 ... 10-6

Page 21: Fundamentals of Teleprotection Systems

ABB AutomationUtility Communication Systems CHPAU NKT F 21

Command Systems, Typical Figures

Blocking• short transmission time Tac < 15 ms < 10 ms• moderate security Puc < 1E-2 < 1E-6• high dependability Pmc < 1E-3 < 1E-3

Permissive tripping• moderate transmission time Tac < 20 ms < 10 ms• moderate to high security Puc < 1E-3 ....1E-4 < 1E-6• moderate to high dependability Pmc < 1E-2 ....1E-3 < 1E-3

Direct tripping• moderate transmission time Tac < 40 ms < 10 ms• very high security Puc < 1E-5 .... 1E-6 < 1E-9• very high dependability Pmc < 1E-3 < 1E-3

Analog systems Digital systems

Page 22: Fundamentals of Teleprotection Systems

ABB AutomationUtility Communication Systems CHPAU NKT F 22

Teleprotection Equipment Command Systems

NSD 50 / NSD550• Plug in unit for multi-purpose Power Line Carrier type ETL

HSD 50• Dedicated protection Power Line Carrier

NSD 70, NSD 70C• for analog bearers

• cables• speech channels of analog and digital links• power line carrier channels

NSD 70D• for digital bearers

• digital multiplexers• digital radio, fibre optic links

• with plug-in fibre optic line unit for dedicated fibres

Page 23: Fundamentals of Teleprotection Systems

ABB AutomationUtility Communication Systems CHPAU NKT F 23

TEBIT: Teleprotection & binary interface

TEBIT as teleprotection interface:

- 4 commands, full-duplex

- addressable

TEBIT as binary interface:

- max. 12 binary inputs

- max. 12 binary outputs

… as „Mini-RTU“

Page 24: Fundamentals of Teleprotection Systems

ABB AutomationUtility Communication Systems CHPAU NKT F 24

Digital Networks

High capacity = large number of channels

Basic channel capacity = 64 kbit/s

PDH (Plesiochronous digital hierarchy)• Multiplexing into 2 Mbit/s ( 30 channels)

8 Mbit/s (120 channels)etc. ( ..... channels)

SDH (Synchronous Digital Hierarchy)• Multiplexing of n * 64 kbit/s or n * 2 Mbit/s into 155 Mbit/s etc.

Cross-connect functionality

Radio or optical fibre links

Page 25: Fundamentals of Teleprotection Systems

ABB AutomationUtility Communication Systems CHPAU NKT F 25

Digital Cross-Connect Networks

Network -Management

Network management activities may have a detrimental impact on a protection system, unless adequate precautions are taken

Digital Cross-Connect

Protection terminal

Digital network

Page 26: Fundamentals of Teleprotection Systems

ABB AutomationUtility Communication Systems CHPAU NKT F 26

Digital Cross-Connect Precautions

Restricted authorisation for re-routing

Inhibit auto-rerouting (possibility of excessive delay)

Use (tele)protection equipment with addressing facility

Use dedicated channels for protection signalling which are non-cross-connectable

Use dedicated links for protection signalling

Incr

easi

ng S

ecur

ity

Page 27: Fundamentals of Teleprotection Systems

ABB AutomationUtility Communication Systems CHPAU NKT F 27

POTT1

PUTT Permissive underreach trippingNSD 70 indirect

POTT 1 Permissive overreach trippingNSD 70 indirect

POTT 2 Permissive overreach trippingNSD 50 indirect

RM 91 Directional comp. prot.NSD 70 indirect

RE 93 Earth fault protectionNSD 50 indirect

BFP Breaker fail protectionNSD 50 direct

GSD Generator protectionNSD 50 direct

A

B

C

D

A

B

NSD 50

ETL 81

PLC I

NSD 70

Coupling

HV transmission line

A

B

C

D

B

NSD 50

ETL 81

PLC II

NSD 70

PUTT

POTT1

POTT2

RM91

RE93

LINE PROT

I

POTT2

RM91

RE93

LINE PROT

II

GSDfrom

generator

Breaker Transducers

BFP

A

PUTT

800 kV redundant Line Protection (with NSD 50 and NSD 70)

Page 28: Fundamentals of Teleprotection Systems

ABB AutomationUtility Communication Systems CHPAU NKT F 28

POTT1

PUTT Permissive underreach trippingNSD 70 indirect

POTT 1 Permissive overreach trippingNSD 70 indirect

POTT 2 Permissive overreach trippingNSD 550 indirect

RM 91 Directional comp. prot.NSD 70 indirect

RE 93 Earth fault protectionNSD 550 indirect

BFP Breaker fail protectionNSD 550 direct

GSD Generator protectionNSD 550 direct

A

B

C

D

A

B

NSD 550

ETL 580

PLC

NSD 70

Coupling

HV transmission line

A

B

C

D FOX515

PUTT

POTT1

POTT2

RM91

RE93

LINE PROT

I

POTT2

RM91

RE93

LINE PROT

II

GSDfrom

generator

Breaker Transducers

BFP

PUTT

800 kV redundant Line Protection

TEBIT

D

A

B

C

D

TEBIT

Optical fiber