frcme-m_04-2011 (1)
TRANSCRIPT
![Page 1: FRCME-M_04-2011 (1)](https://reader031.vdocuments.mx/reader031/viewer/2022021320/577cc4c41a28aba7119a5c3b/html5/thumbnails/1.jpg)
8/11/2019 FRCME-M_04-2011 (1)
http://slidepdf.com/reader/full/frcme-m04-2011-1 1/2
Hochiki America Corporation7051 Village Drive, Suite 100 Buena Park, CA 90621-2268
Phone: 714/522-2246 Fax: 714/522-2268Technical Support: 800/845-6692 or [email protected] 04/2011
Find latest revision at www.hochiki.com
F0113
Specifications subject to change without notice. Continued on back.
DCP-FRCME-M - FAST RESPONSE CONTACT MODULE
DESCRIPTION
The DCP-FRCME-M is a small design and is suitablefor mounting in a single gang box.
The Hochiki DCP-FRCME-M Fast Response ContactMonitoring Modules are designed to be used with pullstations, water flow switches, and other applicationsrequiring the monitoring of dry contact devices. Theinterrupt driven Digital Communications Protocol (DCP)combines maximum communication reliability and fastresponse to emergency conditions. The DCP-FRCME-M contact monitoring module does not require a sepa-rate 24 VDC power source.
Each addressable contact monitoring module isprogrammed with its own unique Signaling LineCircui t (SLC) loop address. The device address iselectrically programmable and stored in onboardEEPROM. Up to 127 devices can be placed on theHochiki DCP SLC loop. The module supervises the wiringto the contact with an End Of Line (EOL) resistor. It canbe programmed to monitor Normally Open (NO) or Normally Closed (NC) contacts. If a fault conditionoccurs in the wiring, the module sends a trouble statussignal to the fire alarm control panel. When a change of status (contact changes state) is sensed by the DCP-FRCME-M, it sends an interrupt to the control panelindicating that an alarm has occurred.
• UL 864 9th Edition Listed
• Single input contact monitor
• Fast, reliable contact monitoring utilizing the
Hochiki DCP (Digital Communications Protocol)
• 127 devices can be used per DCP loop
•Can be programmed to monitor Normally Open(NO) or Normally Closed (NC) contacts
• Operates on Class A or Class B SLC loop
• Accepts up to 14 AWG wire
STANDARD FEATURES
PRODUCT LISTINGS
S5694
7300-0410:150
CaliforniaState Fire
Marshal
SPECIFICATIONS
Supply Voltage (S-SC) 25.3 ~ 39 VDC
Average Current 339μ A (Typical)
Consumption 358μ A (Alarm)
Programmable Input 1 Monitoring Inputs
EOL Device 10K Ohms Resistor
Max. Quantity Per Loop 127
Dimensions 1.75"W x 2.37"H x 0.5"D
Operating Temperature 32°F (0°C) 120°F (49°C)
Mounting 2" electrical box
Relative Humidity 90% RH Non-Condsensing
![Page 2: FRCME-M_04-2011 (1)](https://reader031.vdocuments.mx/reader031/viewer/2022021320/577cc4c41a28aba7119a5c3b/html5/thumbnails/2.jpg)
8/11/2019 FRCME-M_04-2011 (1)
http://slidepdf.com/reader/full/frcme-m04-2011-1 2/2Specifications subject to change without notice.Hochiki America Corporation FRCME-M
ENGINEERING SPECIFICATIONS
The contractor shall furnish and install where indicated on the plans, addressable contact monitoring modules
Hochiki DCP-FRCME-M. The modules shall be UL listed and compatible with the Hochiki Digital Communication
Protocol (DCP) supporting control panel. The device address shall be electrically programmable and stored in
EEPROM.
The DCP-FRCME-M shall be suitable for mounting to a single gang electrical back box.
WIRING DIAGRAM
ANY NUMBER OF UL LISTED N/O CONTACT CLOSURE
DEVICES MAY BE USED, SUBJECT TO NFPA AND AHJREQUIREMENTS. DO NOT MIX FIRE ALARM ANDSUPERVISORY INITIATING DEVICES ON THE SAME MODULE
ALL CIRCUITS ARE SUPERVISED AND INHERENTLY POWER LIMITED
0400-01046PART NUMBER E.O.L. DEVICE
HOCHIKI AMERICA CORP.
TYPICAL WIRING FOR N/O CONTACTS IN CLASS B (STYLE B)
E.O.L. DEVICEPARTNUMBER 0400-01046
U.L. LISTED
COMPATIBLE
FIRE CONTROLPANEL
OUTPUT TO NEXT INTERFACEMODULE ON THE SLC LOOP