fr f700 na aplica

Upload: ronnie-ayala-sandoval

Post on 03-Jun-2018

222 views

Category:

Documents


0 download

TRANSCRIPT

  • 8/12/2019 Fr f700 Na Aplica

    1/412

    INSTRUCTION MANUAL

    INVERTER

    3PRECAUTIONS FOR USEOF THE INVE RTER

    4

    PARAMETERS

    5PROTECTIVE FUNCTIONS

    6PRECAUTIONS FORMAINTENANCE AND INSPECTION

    7SPECIFICATIONS

    WIRING

    OUTLINE

    2

    1

    FR-F720-00046 to 04750-NA

    FR-F740-00023 to 12120-NA

  • 8/12/2019 Fr f700 Na Aplica

    2/412

    Thank you for choosing this Mitsubishi Inverter.This Instruction Manual provides instructions for advanced use of the FR-F700 series inverters.Incorrect handling might cause an unexpected fault. Before using the inverter, always read this Instruction Manual Guideline [IB-0600218ENG] packed with the product carefully to use the equipment to its optimum.

    1. Electric Shock Prevention

    2. Fire Prevention

    3. Injury Prevention

    4. Additional Instructions Also the following points must be noted toelectric shock, etc.

    This section is specifically about safety mattersDo not attempt to install, operate, maintain or inspect the inverter until you have read through Installation Guideline and appendeddocuments carefully and can use the equipment correctly. Do notuse the inverter until you have a full knowledge of the equipment,safety information and instructions. In this Instruction Manual, thesafety instruction levels are classified into "WARNING" and"CAUTION".

    Incorrect handling may cause hazardous

    conditions, resulting in death or severe injury.Incorrect handling may cause hazardousconditions, resulting in medium or slightinjury, or may cause only material damage.

    The level may even lead to a serious consequenceaccording to conditions. Both instruction levels must be followedbecause these are important to personal safety.

    While power is ON or when the inverter is running, do not openthe front cover. Otherwise you may get an electric shock.

    Do not run the inverter with the front cover or wiring cover removed.Otherwise you may access the exposed high-voltage terminalsor the charging part of the circuitry and get an electric shock.

    Even if power is OFF, do not remove the front cover except for wiring or periodic inspection. You may accidentally touch thecharged inverter circuits and get an electric shock.

    Before wiring, inspection or switching EMC filter ON/OFFconnector, power must be switched OFF. To confirm that, LEDindication of the operation panel must be checked. (It must beOFF.) Any person who is involved in wiring, inspection or switching EMC filter ON/OFF connector shall wait for at least 10minutes after the power supply has been switched OFF andcheck that there are no residual voltage using a tester or the like.The capacitor is charged with high voltage for some time after power OFF, and it is dangerous.

    This inverter must be earthed (grounded). Earthing (grounding)must conform to the requirements of national and local safety

    regulations and electrical code (NEC section 250, IEC 536 class1 and other applicable standards). A neutral-point earthed (grounded) power supply for 400V classinverter in compliance with EN standard must be used.

    Any person who is involved in wiring or inspection of thisequipment shall be fully competent to do the work.

    The inverter must be installed before wiring. Otherwise you mayget an electric shock or be injured.

    WARNING

    CAUTION

    CAUTION

    WARNING

    Inverter must be installed on a nonthat nobody touches the inverter Mounting it to or near flammable m

    If the inverter has become faultswitched OFF. A continuous flow o

    Do not connect a resistor directly-. Doing so could cause a fire.

    Daily and periodic inspections min the Instruction Manual. If the pany inspection, it may cause a bu

    The voltage applied to each termin the Instruction Manual. Otheoccur.

    The cables must be connectOtherwise burst, damage, etc. ma

    Polarity must be correct. Otheroccur.

    While power is ON or for somtouch the inverter since the inverso can cause burns.

    (1) Transportation and installation

    The product must be transpocorresponds to the weight. Failure

    Do not stack the boxes containumber recommended.

    The product must be installed tothe weight of the product accoInstruction Manual.

    Do not install or operate the invemissing. This can result in breakd

    When carrying the inverter, do nsetting dial; it may fall off or fail

    Do not stand or rest heavy object The inverter mounting orientatio Foreign conductive objects must

    inverter. That includes screws flammable substance such as oil.

    As the inverter is a precision inst

    CA

    CA

    CA

  • 8/12/2019 Fr f700 Na Aplica

    3/412

    (2) Wiring

    Do not install a power factor correction capacitor, surgesuppressor or capacitor type filter on the inverter output side.These devices on the inverter output side may be overheated or burn out.

    The connection orientation of the output cables U, V, W to themotor affects the rotation direction of the motor.

    (3) Test operation and adjustment

    Before starting operation, each parameter must be confirmed andadjusted. A failure to do so may cause some machines to makeunexpected motions.

    (4) Operation

    Any person must stay away from the equipment when the retryfunction is set as it will restart suddenly after trip.

    Since pressing key may not stop output depending on thefunction setting status, separate circuit and switch that make anemergency stop (power OFF, mechanical brake operation for emergency stop, etc.) must be provided.

    OFF status of the start signal must be confirmed before resettingthe inverter fault. Resetting inverter alarm with the start signalON restarts the motor suddenly.

    The inverter must be used for three-phase induction motors.Connection of any other electrical equipment to the inverter output may damage the equipment.

    Do not modify the equipment. Do not perform parts removal which is not instructed in this

    manual. Doing so may lead to fault or damage of the inverter.

    The electronic thermal relay function does not guaranteeprotection of the motor from overheating. It is recommended toinstall both an external thermal and PTC thermistor for overheatprotection.

    Do not use a magnetic contactor on the inverter input for frequentstarting/stopping of the inverter. Otherwise the life of the inverter decreases.

    The effect of electromagnetic interference must be reduced byusing a noise filter or by other means. Otherwise nearbyelectronic equipment may be affected.

    Appropriate measures must be taken to suppress harmonics.Otherwise power supply harmonics from the inverter may heat/damage the power factor correction capacitor and generator.

    When driving a 400V class motor by the inverter, the motor mustbe an insulation-enhanced motor or measures must be taken tosuppress surge voltage. Surge voltage attributable to the wiringconstants may occur at the motor terminals, deteriorating theinsulation of the motor

    CAUTION

    CAUTION

    WARNING

    CAUTION

    (5) Emergency stop

    A safety backup such as an emergency to prevent hazardous condition to the mcase of inverter failure.

    When the breaker on the inverter input sbe checked for fault (short circuit), inverter for a damage, etc. The cauidentified and removed before turninbreaker.

    When any protective function is activataction must be taken, and the inverteresuming operation.

    (6) Maintenance, inspection and parts repla

    Do not carry out a megger (insulationcontrol circuit of the inverter. It will cau

    (7) Disposing of the inverter

    The inverter must be treated as industria

    General instructions

    Many of the diagrams and drawings inshow the inverter without a cover or partiNever operate the inverter in this mannalways reinstalled and the instruction inmust be followed when operating the inver

    CAUTI

    CAUTI

    CAUTI

  • 8/12/2019 Fr f700 Na Aplica

    4/412

    CONTENTS1 OUTLINE

    1.1 Product checking and parts identification ............................................1.2 Inverter and peripheral devices ............................................................

    1.2.1 Peripheral devices.................................................................................................

    1.3 Method of removal and reinstallation of the front cover.......................

    1.4 Installation of the inverter and enclosure design ...................................

    1.4.1 Inverter installation environment..........................................................................1.4.2 Cooling system types for inverter enclosure.........................................................

    1.4.3 Inverter placement................................................................................................

    2 WIRING

    2.1 Wiring.................................................................................................2.1.1 Terminal connection diagram ...............................................................................

    2.1.2 EMC filter .............................................................................................................

    2.2 Main circuit terminal specifications .....................................................

    2.2.1 Specification of main circuit terminal ..................................................................

    2.2.2 Terminal arrangement of the main circuit terminal, power supply and the motor

    2.2.3 Cables and wiring length ......................................................................................

    2.2.4 When connecting the control circuit and the main circuit separately to the powe

    2.3 Control circuit specifications ...............................................................

    2.3.1 Control circuit terminals .......................................................................................

    2.3.2 Changing the control logic ....................................................................................

    2.3.3 Control circuit terminal layout .............................................................................

    2.3.4 Wiring instructions ...............................................................................................

    2.3.5 Mounting the operation panel (FR-DU07) on the enclosure surface ....................

    2.3.6 RS-485 terminal block ..........................................................................................

    2.3.7 Communication operation.....................................................................................

    2 4 C i f d l i i

  • 8/12/2019 Fr f700 Na Aplica

    5/412

    3.1 EMC and leakage currents ........................................................................

    3.1.1 Leakage currents and countermeasures ......................................................................

    3.1.2 EMC measures............................................................................................................

    3.1.3 Power supply harmonics.............................................................................................

    3.2 Installation of a reactor.............................................................................

    3.3 Power-OFF and magnetic contactor (MC).................................................

    3.4 Inverter-driven 400V class motor..............................................................

    3.5 Precautions for use of the inverter.............................................................3.6 Failsafe of the system which uses the inverter...........................................

    4 PARAMETERS

    4.1 Operation panel (FR-DU07) .....................................................................

    4.1.1 Component of the operation panel (FR-DU07)...........................................................

    4.1.2 Basic operation (factory setting) .................................................................................

    4.1.3 Easy operation mode setting (easy setting mode).......................................................

    4.1.4 Changing the parameter setting value.........................................................................

    4.1.5 Displaying the set frequency.......................................................................................

    4.2 Parameter list............................................................................................

    4.2.1 Parameter list...............................................................................................................

    4.3 Adjustment of the output torque (current) of the motor.............................

    4.3.1 Manual torque boost (Pr. 0, Pr. 46) ............................................................................

    4.3.2 Simple magnetic flux vector control (Pr.80, Pr.90) ....................................................

    4.3.3 Slip compensation (Pr. 245 to Pr. 247)........................................................................

    4.3.4 Stall prevention operation(Pr. 22, Pr. 23, Pr. 48, Pr. 49, Pr. 66, Pr. 148, Pr. 149, Pr. 154, Pr. 156, Pr. 157) .......

    4.3.5 Multiple rating (Pr. 570) .............................................................................................

    4.4 Limiting the output frequency...................................................................

    4.4.1 Maximum/minimum frequency (Pr. 1, Pr. 2, Pr. 18)...................................................

  • 8/12/2019 Fr f700 Na Aplica

    6/412

  • 8/12/2019 Fr f700 Na Aplica

    7/412

    4.13.3 Input/output phase loss protection selection (Pr. 251, Pr. 872)...................................

    4.14 Energy saving operation and energy saving monitor .................................

    4.14.1 Energy saving control and Optimum excitation control (Pr. 60).................................4.14.2 Energy saving monitor (Pr. 891 to Pr. 899) ................................................................

    4.15 Motor noise, EMI measures, mechanical resonance ..................................

    4.15.1 PWM carrier frequency and Soft-PWM control (Pr. 72, Pr. 240, Pr. 260)..................

    4.15.2 Speed smoothing control (Pr. 653, Pr. 654) ................................................................

    4.16 Frequency setting by analog input (terminal 1, 2, 4) .................................

    4.16.1 Analog input selection (Pr. 73, Pr. 267) ......................................................................

    4.16.2 Analog input compensation (Pr. 73, Pr. 242, Pr. 243, Pr. 252, Pr. 253) ......................

    4.16.3 Response level of analog input and noise elimination (Pr. 74)...................................

    4.16.4 Bias and gain of frequency setting voltage (current)(Pr. 125, Pr. 126, Pr. 241, C2(Pr. 902) to C7(Pr. 905)) ..............................................

    4.16.5 4mA input check of current input (Pr. 573, Pr. 777, Pr. 778) ......................................

    4.17 Misoperation prevention and parameter setting restriction ........................4.17.1 Reset selection/disconnected PU detection/PU stop selection (Pr. 75) .......................

    4.17.2 Parameter write selection (Pr. 77) ...............................................................................

    4.17.3 Reverse rotation prevention selection (Pr. 78) ...........................................................

    4.17.4 Display of applied parameters and user group function (Pr. 160, Pr. 172 to Pr. 174) .

    4.17.5 Password function (Pr. 296, Pr. 297)...........................................................................

    4.18 Selection of operation mode and operation location ..................................

    4.18.1 Operation mode selection (Pr. 79)...............................................................................

    4.18.2 Operation mode at power ON (Pr. 79, Pr. 340) ...........................................................

    4.18.3 Start command source and speed command source duringcommunication operation (Pr. 338, Pr. 339, Pr. 550, Pr. 551)....................................

    4.19 Communication operation and setting........................................................

    4.19.1 Wiring and configuration of PU connector .................................................................

    4.19.2 Wiring and configuration of RS-485 terminals ...........................................................

    4.19.3 Initial settings and specifications of RS-485 communication(Pr. 117 to Pr. 124, Pr. 331 to Pr. 337, Pr. 341, Pr. 549).................... .........................

    4.19.4 Communication EEPROM write selection (Pr. 342) ..................................................

  • 8/12/2019 Fr f700 Na Aplica

    8/412

    4.20.3 Pre-charge function (Pr.760 to Pr. 769).................................................................

    4.20.4 Second PID function (Pr.753 to Pr. 758, Pr.765 to Pr.769) ..................................

    4.20.5 Advanced PID function (pump function) (Pr. 554, Pr. 575 to Pr. 591).................

    4.21 Special operation and frequency control ...............................................

    4.21.1 Bypass-inverter switchover function (Pr. 57, Pr. 58, Pr. 135 to Pr. 139, Pr. 159).

    4.21.2 Regeneration avoidance function (Pr. 665, Pr. 882 to Pr. 886).............................

    4.22 Useful functions...................................................................................

    4.22.1 Cooling fan operation selection (Pr. 244) .............................................................

    4.22.2 Display of the life of the inverter parts (Pr. 255 to Pr .259)..................................4.22.3 Maintenance timer alarm (Pr. 503, Pr. 504) ..........................................................

    4.22.4 Current average value monitor signal (Pr. 555 to Pr. 557) ...................................

    4.22.5 Free parameter (Pr. 888, Pr. 889) ..........................................................................

    4.22.6 Initiating a fault (Pr.997) ......................................................................................

    4.22.7 Setting multiple parameters as a batch (Pr.999) ....................................................

    4.23 Setting from the parameter unit, operation panel..................................4.23.1 PU display language selection (Pr. 145) ...............................................................

    4.23.2 Setting dial potentiometer mode/key lock selection (Pr. 161)...............................

    4.23.3 Buzzer control (Pr. 990)........................................................................................

    4.23.4 PU contrast adjustment (Pr. 991) ..........................................................................

    4.24 Setting of FR-PU07-01 ........................................................................

    4.24.1 PID display bias/gain setting menu ......................................................................

    4.24.2 Unit selection for the PID parameter/PID monitored items (Pr. 759)...................

    4.24.3 PID set point direct setting menu..........................................................................

    4.24.4 3-line monitor selection (Pr. 774 to Pr.776) ..........................................................

    4.25 Parameter clear ....................................................................................

    4.26 All parameter clear...............................................................................

    4.27 Parameter copy and parameter verification ...........................................

    4.27.1 Parameter copy .....................................................................................................

    4.27.2 Parameter verification...........................................................................................

    4 28 I i i l l h li

  • 8/12/2019 Fr f700 Na Aplica

    9/412

    5.5 Check first when you have a trouble.........................................................

    5.5.1 Motor does not start....................................................................................................

    5.5.2 Motor or machine is making abnormal acoustic noise................................................

    5.5.3 Inverter generates abnormal noise..............................................................................

    5.5.4 Motor generates heat abnormally...............................................................................

    5.5.5 Motor rotates in the opposite direction.......................................................................

    5.5.6 Speed greatly differs from the setting.........................................................................

    5.5.7 Acceleration/deceleration is not smooth.....................................................................

    5.5.8 Speed varies during operation....................................................................................

    5.5.9 Operation mode is not changed properly.....................................................................5.5.10 Operation panel (FR-DU07) display is not operating.................................................

    5.5.11 Motor current is too large............................................................................................

    5.5.12 Speed does not accelerate...........................................................................................

    5.5.13 Unable to write parameter setting................................................................................

    5.5.14 Power lamp is not lit....................................................................................................

    6 PRECAUTIONS FOR MAINTENANCE AND INSPECTION

    6.1 Inspection item.........................................................................................

    6.1.1 Daily inspection..........................................................................................................

    6.1.2 Periodic inspection......................................................................................................

    6.1.3 Daily and periodic inspection.....................................................................................

    6.1.4 Display of the life of the inverter parts .......................................................................

    6.1.5 Checking the inverter and converter modules ............................................................

    6.1.6 Cleaning......................................................................................................................

    6.1.7 Replacement of parts...................................................................................................

    6.1.8 Inverter replacement...................................................................................................

    6.2 Measurement of main circuit voltages, currents and powers......................

    6.2.1 Measurement of voltages and currents .......................................................................

    6.2.2 Measurement of powers .............................................................................................

    6.2.3 Measurement of voltages and use of PT.....................................................................

    6.2.4 Measurement of currents.............................................................................................

    6 2 5 Use of CT and transducer

  • 8/12/2019 Fr f700 Na Aplica

    10/412

    7.4 Heatsink protrusion attachment procedure ...........................................

    7.4.1 When using a heatsink protrusion attachment (FR-A7CN) ..................................

    7.4.2 Protrusion of heatsink of the FR-F740-04320 or higher ......................................

    APPENDICES

    Appendix 1 For customers who are replacing the conventional modelwith this inverter................... ....................... ........................

    Appendix 1-1 Replacement of the FR-F500 series .........................................................

    Appendix 1-2 Replacement of the FR-A100 series ...............................

    Appendix 2 Parameter clear, parameter copy and instruction code list ........

    Appendix 3 Specification change ...............................................................

    Appendix 3-1 SERIAL number check .............................................................................

    Appendix 3-2 Changed functions ...................................................................................

  • 8/12/2019 Fr f700 Na Aplica

    11/412

    1 OUTLINE

    This chapter describes the basic "OUTLINE" for useproduct.

    Always read the instructions before using the equipment.

    1.1 Product checking and parts identification ..............1.2 Inverter and peripheral devices .............................1.3 Method of removal and reinstallation of the front

    cover.....................................................................1.4 Installation of the inverter and enclosure design ...

    DU ............................................Operation panel (FR-DU07)PU..................................................Operation panel (FR-DU07) and parameter unit (FR-P

    PU07(-01))Inverter .....................................Mitsubishi inverter FR-F700 seriesFR-F700 ...................................Mitsubishi inverter FR-F700 seriesPr. .............................................Parameter Number (Number assigned to function)PU operation ............................. Operation using the PU (FR-DU07/FR-PU04/FR-PU07External operation ....................Operation using the control circuit signalsCombined operation .................Combined operation using the PU (FR-DU07/FR-

    PU07(-01)) and external operation.Mitsubishi standard motor ........SF-JRMitsubishi constant torque motor SF HRCA

  • 8/12/2019 Fr f700 Na Aplica

    12/412

  • 8/12/2019 Fr f700 Na Aplica

    13/412

    Inverter

    1.2 Inverter and peripheral devices

    Power regenerationcommon converter(FR-CV *1) Resistor unit

    Brake unit(FR-BU2, FR-BU *1, MT-BU5 *2)

    High power factor

    P/+

    P/+

    PR

    PR

    PULL

    USB

    MODE

    RUNERR

    USER

    BATBOOT

    PULL

    POWER RUNT.PASS

    SDERR

    MNGD.LINKRDERR

    RUNT.PASS

    SDERR

    MNGD.LINKRDERR

    Programmablecontroller

    Human machineinterface

    Three-phase AC power supply

    AC reactor (FR-HAL)

    DC reactor(FR-HEL) R/L1 S/L2 T/L3P/+ N/-P/+P1 U V W

    Moulded case circuitbreaker (MCCB)or earth leakage circuitbreaker (ELB), fuse

    Magnetic contactor (MC)

    RS-485 terminal block

    Devices connect

    Use within the permissible power supplyspecifications of the inverter.

    Install the magnetic contactor to ensure safety.Do not use this magnetic contactor to start andstop the inverter.Doing so will cause the inverter life to beshortened.

    The inverter can be connectedwith a computer such as aprogrammable controller andwith GOT (human machineinterface).It supports Mitsubishi inverterprotocol, Modbus-RTU (binary)protocol and BACnet MS/TP

    protocol.

    Do not install a powesurge suppressor or noutput side of the invWhen installing a mooutput side of the inv

    The breaker must be selected carefully sincean in-rush current flows in the inverter atpower ON.

    Earth(Ground)

    Earth(Ground

    For the FR-F720-03160 (FR-F740-01800) or higher, a DCreactor is supplied.

    Always install the reactor.

    Reactor (FR-HAL, FR-HEL)Install reactors to suppress harmonics and toimprove the power factor. An AC reactor (FR-HAL)(option) is required when installing the inverter neara large power supply system (1000kVA or more).The inverter may be damaged if you do not usereactors.Select the reactor according to the model.For the FR-F720-02330 (FR-F740-01160) or lower,remove the jumpers across terminals P/+ and P1 toconnect to the DC reactor.

    Noise filter(ferrite core)(FR-BLF)The FR-F720-02330(FR-F740-01160) orlower has a built-incommon mode choke.

    (Refer to page 370 )

    (Refer to page 4 )

    (Refer to page 4 )

    (Refer to page 4 )

    Inverter (FR-F700)The life of the invetemperature. The suras low as possible wibe noted especially enclosure. (Refer toWrong wiring mightcontrol signal lines mcircuit to protect them

    Refer to page 15 for

  • 8/12/2019 Fr f700 Na Aplica

    14/412

    Inverter and peripheral devices

    1.2.1 Peripheral devices

    Check the inverter model of the inverter you purchased. Appropriate peripheral devices must be selected the capacity. Refer to the following list and prepare appropriate peripheral devices:

    200V class

    MotorOutput

    (kW(HP))*1

    Applicable InverterModel

    Moulded Case Circuit Breaker(MCCB) *2 or Earth Leakage Circuit

    Breaker (ELB)Input Sid

    Power factor improving(AC or DC) reactor

    Pow(

    Without with Without0.75 (1) FR-F720-00046-NA 10A 10A S-N10

    1.5 (2) FR-F720-00077-NA 15A 15A S-N102.2 (3) FR-F720-00105-NA 20A 15A S-N103.7 (5) FR-F720-00167-NA 30A 30A S-N20, S-N21

    5.5 (7.5) FR-F720-00250-NA 50A 40A S-N257.5 (10) FR-F720-00340-NA 60A 50A S-N2511 (15) FR-F720-00490-NA 75A 75A S-N3515 (20) FR-F720-00630-NA 125A 100A S-N50

    18.5 (25) FR-F720-00770-NA 150A 125A S-N6522 (30) FR-F720-00930-NA 175A 150A S-N8030 (40) FR-F720-01250-NA 225A 175A S-N9537 (50) FR-F720-01540-NA 250A 225A S-N15045 (60) FR-F720-01870-NA 300A 300A S-N18055 (75) FR-F720-02330-NA 400A 350A S-N220

    75 (100) FR-F720-03160-NA 400A 90 (125) FR-F720-03800-NA 400A

    110 (150) FR-F720-04750-NA 500A

    *1 Selections for use of the Mitsubishi 4-pole standard motor with power supply voltage of 200VAC 50Hz.*2 Select the MCCB according to the power supply capacity.

    Install one MCCB per inverter.For installation in the United States or Canada, select a fuse in accordance with UL, cUL, the NationalElectrical Code and any applicable local codes, or use UL 489 Molded Case Circuit Breaker (MCCB).(Refer to the Installation Guideline.)

    *3 Magnetic contactor is selected based on the AC-1 class. The electrical durability of magnetic contactor is 500,000 times. Wcontactor is used for emergency stop during motor driving, the electrical durability is 25 times.If using an MC for emergency stop during motor driving, select an MC regarding the inverter input side current as JEM103current. When using an MC on the inverter output side for commercial-power supply operation switching using a general purpoMC regarding the motor rated current as JEM1038-AC-3 class rated current.

    CAUTIONWhen the inverter capacity i s larger than the motor capacity, select an MCCB and a magnetic contactor according tomodel and cable and reactor according to the motor output.When the breaker on the inverter primary side trips, check for the wiring fault (short circuit), damage to interninverter, etc. Identify the cause of the trip, then remove the cause and power ON the breaker.

  • 8/12/2019 Fr f700 Na Aplica

    15/412

    Inverter

    400V class

    MotorOutput

    (kW(HP))*1

    Applicable InverterModel

    Moulded Case Circuit Breaker(MCCB) *2 or Earth Leakage Circuit

    Breaker (ELB)Input

    Power factor improving(AC or DC) reactor

    Without with With0.75 (1) FR-F740-00023-NA 5A 5A S-N11.5 (2) FR-F740-00038-NA 10A 10A S-N102.2 (3) FR-F740-00052-NA 10A 10A S-N103.7 (5) FR-F740-00083-NA 20A 15A S-N10

    5.5 (7.5) FR-F740-00126-NA 30A 20A S-N20, S-N

    7.5 (10) FR-F740-00170-NA 30A 30A S-N20, S-N11 (15) FR-F740-00250-NA 50A 40A S-N20, S-N15 (20) FR-F740-00310-NA 60A 50A S-N25

    18.5 (25) FR-F740-00380-NA 75A 60A S-N2522 (30) FR-F740-00470-NA 100A 75A S-N3530 (40) FR-F740-00620-NA 125A 100A S-N5037 (50) FR-F740-00770-NA 150A 125A S-N6545 (60) FR-F740-00930-NA 175A 150A S-N8055 (75) FR-F740-01160-NA 200A 175A S-N80

    75 (100) FR-F740-01800-NA 225A90 (125) FR-F740-01800-NA 225A

    110 (150) FR-F740-02160-NA 225A132 (200) FR-F740-02600-NA 400A160 (250) FR-F740-03250-NA 400A185 (300) FR-F740-03610-NA 400A220 (350) FR-F740-04320-NA 500A250 (400) FR-F740-04810-NA 600A280 (450) FR-F740-05470-NA 600A315 (500) FR-F740-06100-NA 700A355 (550) FR-F740-06830-NA 800A400 (600) FR-F740-07700-NA 900A

    450 (700) FR-F740-08660-NA 1000A

    500 (750) FR-F740-09620-NA 1200A

    560 (800) FR-F740-10940-NA 1500A

    630 (850) FR-F740-12120-NA 2000A

    *1 Selections for use of the Mitsubishi 4-pole standard motor with power supply voltage of 400VAC 50Hz.*2 Select the MCCB according to the power supply capacity. Install one MCCB per inverter.

    For installation in the United States or Canada, select a fuse in accordance with UL, cUL, the NationalElectrical Code and any applicable local codes or use UL 489 Molded Case Circuit Breaker (MCCB)

    Method of removal and reinstallation of the

  • 8/12/2019 Fr f700 Na Aplica

    16/412

    Method of removal and reinstallation of thefront cover

    1.3 Method of removal and reinstallation of the front cover Removal of the operation panel

    1) Loosen the two screws on the operation panel.(These screws cannot be removed.)

    2) Push the left and right hooksand pull the operation panel to

    When reinstalling the operation panel, insert it straight to reinstall securely and tighten the fixedoperation panel. (Tightening torque: 0.40N m to 0.45N m)

    FR-F720-01250-NA or lower, FR-F740-00620-NA or lower Removal

    Reinstallation

    Install

    Front cover Front cover

    1) Loosen the installation screws of thefront cover.

    2) Pull the front cover toward you to remove binstallation hook using left fixed hooks as s

    1) Insert the two fixed hooks on the left side ofthe front cover into the sockets of theinverter.

    2) Using the fixed hooks as supports,securely press the front coveragainst the inverter.(Although installation can be donewith the operation panel mounted,

    3)

    Method of remov

  • 8/12/2019 Fr f700 Na Aplica

    17/412

    Method of remov

    FR-F720-01540-NA or higher, FR-F740-00770-NA or higher Removal

    Reinstallation

    Front cover 2

    Front cover 1

    1) Remove installation screws on

    the front cover 1 to remove thefront cover 1.

    2) Loosen the installation

    screws of the front cover 2.

    3) Pull the fron

    remove by phook on the fixed hooks

    Front cover 2 Front cover

    1) Insert the two fixed hooks on the left side of thefront cover 2 into the sockets of the inverter.

    2) Using the fixed hookpress the front cover

    (Although installatiooperation panel mounconnector is securely

    3) Fix the front cover 2 with theinstallation screws.

    4) Fix the front installation s

    Installation of the inverter and

  • 8/12/2019 Fr f700 Na Aplica

    18/412

    Installation of the inverter andenclosure design

    1.4 Installation of the inverter and enclosure design

    When an inverter enclosure is to be designed and manufactured, heat generated by contained equipmenenvironment of an operating place, and others must be fully considered to determine the enclosure structu

    equipment layout. The inverter unit uses many semiconductor devices. To ensure higher reliability and looperation, operate the inverter in the ambient environment that completely satisfies the equipment specific

    1.4.1 Inverter installation environment

    As the inverter installation environment should satisfy the standard specifications indicated in the fooperation in any place that does not meet these conditions not only deteriorates the performance aninverter, but also causes a failure. Refer to the following points and take adequate measures.

    * 2.9m/s 2 or less for the FR-F740-04320 or higher.

    (1) Temperature

    The permissible surrounding air temperature of the inverter is -10 C (14F) to +50 C (122F)(14F) to +40 C (104F) (when SLD is set). Always operate the inverter within this temperature range. Othis range will considerably shorten the service lives of the semiconductors, parts, capacitors and othefollowing measures so that the surrounding air temperature of the inverter falls within the specified range.1) Measures against high temperature

    Use a forced ventilation system or similar cooling system. (Refer to page 10.) Install the enclosure in an air-conditioned electrical chamber. Block direct sunlight. Provide a shield or similar plate to avoid direct exposure to the radiated heat and wind of a heat sour Ventilate the area around the enclosure well.

    2) Measures against low temperature Provide a space heater in the enclosure. Do not power OFF the inverter. (Keep the start signal of the inverter OFF.)

    3) Sudden temperature changes Select an installation place where temperature does not change suddenly. Avoid installing the inverter near the air outlet of an air conditioner. If temperature changes are caused by opening/closing of a door, install the inverter away from the do

    (2) Humidity

    Normally operate the inverter within the 45 to 90% range of the ambient humidity. Too high humidity willof reduced insulation and metal corrosion. On the other hand, too low humidity may produce a spabreakdown. The insulation distance specified in JEM1103 "Control Equipment Insulator" is defined as h

    Environmental standard specifications of inverter

    Item Description

    Surrounding air temperatureLD -10 to +50C (14F to 122F) (non-freezing)SLD(Initial setting) -10 to +40C (14F to 104F) (non-freezing)

    Ambient humidity 90% RH maximum (non-condensing) Atmosphere Indoors (free from corrosive gas, flammable gas, oil mist, dust and dirt)

    Maximum Altitude 1,000m (3280.80 feet) or less

    Vibration 5.9m/s 2 or less * at 10 to 55Hz (directions of X, Y, Z axes)

    Install

  • 8/12/2019 Fr f700 Na Aplica

    19/412

    Install

    (3) Dust, dirt, oil mist

    Dust and dirt will cause such faults as poor contact of contact points, reduced insulation or reduced cto moisture absorption of accumulated dust and dirt, and in-enclosure temperature rise due to clogged In the atmosphere where conductive powder floats, dust and dirt will cause such faults as malfunctinsulation and short circuit in a short time.Since oil mist will cause similar conditions, it is necessary to take adequate measures.

    Countermeasures Place in a totally enclosed enclosure.

    Take measures if the in-enclosure temperature rises. (Refer to page 10.) Purge air.

    Pump clean air from outside to make the in-enclosure pressure higher than the outside-air pressure.

    (4) Corrosive gas, salt damage

    If the inverter is exposed to corrosive gas or to salt near a beach, the printed board patterns and partsthe relays and switches will result in poor contact.In such places, take the measures given in Section (3) .

    (5) Explosive, flammable gases

    As the inverter is non-explosion proof, it must be contained in an explosion proof enclosure.

    In places where explosion may be caused by explosive gas, dust or dirt, an enclosure cannot bestructurally complies with the guidelines and has passed the specified tests. This makes the enclosure (including the test charges).The best way is to avoid installation in such places and install the inverter in a non-hazardous place.

    (6) Highland

    Use the inverter at the altitude of within 1000m (3280.80 feet).If it is used at a higher place, it is likely that thin air will reduce the cooling effect and low air press

    dielectric strength.

    (7) Vibration, impact

    The vibration resistance of the inverter is up to 5.9m/s 2 (2.9m/s 2 for the FR-F740-0432frequency (directions of X, Y, Z axes) and 1mm (0.04 inches) amplitude.Vibration or impact, if less than the specified value, applied for a long time may make the mechanismpoor contact to the connectors.Especially when impact is imposed repeatedly, caution must be taken as the part pins are likely to brea

    Countermeasures Provide the enclosure with rubber vibration isolators. Strengthen the structure to prevent the enclosure from resonance. Install the enclosure away from sources of vibration.

    Installation of the inverter and

  • 8/12/2019 Fr f700 Na Aplica

    20/412

    Installation of the inverter andenclosure design

    1.4.2 Cooling system types for inverter enclosure

    From the enclosure that contains the inverter, the heat of the inverter and other equipment (transformresistors, etc.) and the incoming heat such as direct sunlight must be dissipated to keep the in-enclosure t

    lower than the permissible temperatures of the in-enclosure equipment including the inverter.The cooling systems are classified as follows in terms of the cooling calculation method.1) Cooling by natural heat dissipation from the enclosure surface (Totally enclosed type)2) Cooling by heatsink (Aluminum heatsink, etc.)3) Cooling by ventilation (Forced ventilation type, pipe ventilation type)4) Cooling by heat exchanger or cooler (Heat pipe, cooler, etc.)

    1.4.3 Inverter placement

    (1) Installation of the Inverter

    Cooling System Enclosure Structure Comment

    Naturalcooling

    Natural ventilation(Enclosed, open type)

    Low in cost and generally used, bincreases as the inverter capacity small capacities.

    Natural ventilation(Totally enclosed type)

    Being a totally enclosed type, thehostile environment having dust, enclosure size increases dependincapacity.

    Forcedcooling

    Heatsink coolingHaving restrictions on the heatsinarea, and designed for relative sm

    Forced ventilation For general indoor installation. Adownsizing and cost reduction, an

    Heat pipe Totally enclosed type for enclosure

    Installation on the enclosure

    INV

    INV

    INVheatsink

    INV

    INV

    Heatpipe

    CAUTION

    Install

  • 8/12/2019 Fr f700 Na Aplica

    21/412

    (2) Clearances around the inverter

    To ensure ease of heat dissipation and maintenance, leave at least the shown clearances around the invthe following clearances are required under the inverter as a wiring space, and above the inverter as a hspace.

    (3) Inverter mounting orientation

    Mount the inverter on a wall as specified. Do not mount it horizontally or any other way.

    (4) Above the inverter

    Heat is blown up from inside the inverter by the small fan built in the unit. Any equipment placed should be heat resistant.

    (5) Arrangement of multiple inverters

    REMARKS For replacing the cooling fan of the FR-F740-04320 or higher, 30cm(11.8 inches) of space is nece

    the inverter. Refer to page 359 for fan replacement.

    When multiple inverters are placed in the sameenclosure, generally arrange them horizontally asshown in the right figure (a). When it is inevitable toarrange them vertically to minimize space, take suchmeasures as to provide guides since heat from thebottom inverters can increase the temperatures in thetop inverters, causing inverter failures.

    When mounting multiple inverters, fully take cautionnot to make the surrounding air temperature of theinverter higher than the permissible value by providingventilation and increasing the enclosure size.

    Arrangement of multip

    ClearancesSurrounding air temperature and humidity

    Measurementposition

    Measurementposition

    Inverter

    Leave enough clearances as acooling measure.

    Humidity: 90% RH maximum

    FR-F720-02330 or lower FR-F740-01160 or lower

    FR-F720-03160 or higher FR-F740-01800 or higher

    5cm(1.97inches)

    5cm(1.97inches)

    5cm(1.97inches)

    10cm (3.94inches) or more

    20cm (7.87inches)or more

    20cm (7.87inches)or more

    10cm (3.94inches) or more

    5cm(1.97inches) or more *

    5cm(1.97inches)or more *

    10cm(3.94inches)or more

    10cm(3.94inches) or more

    Temperature: -10C to 50C (14F to 122F)

    (LD) -10C to 40C (14F to 104F) (SLD)

    (front)

    * 1cm (0.39 inches) or more for FR-F720-00167, FR-740-00083 or lower

    *

    Gui

    Enclosure

    (a) Horizontal arrangement

    Inve

    InveInverter Inverter

  • 8/12/2019 Fr f700 Na Aplica

    22/412

    MEMO

  • 8/12/2019 Fr f700 Na Aplica

    23/412

    2 WIRING

    This chapter explains the basic "WIRING" for use of this p Always read the instructions before using the equipment.

    2.1 Wiring ...................................................................2.2 Main circuit terminal specifications ......................2.3 Control circuit specifications .................................2.4 Connection of stand-alone option units .................

    Wiring

  • 8/12/2019 Fr f700 Na Aplica

    24/412

    Wiring

    2.1 Wiring2.1.1 Terminal connection diagram

    Three-phase ACpower supply

    MCCB

    Jumper

    R/L1S/L2T/L3

    R1/L11S1/L21

    PC

    10E (+10V)10 (+5V)

    23

    1

    Control input signals (No voltage input allowed)

    Jumper

    Relay ou(Fault o

    C1

    B1

    A1

    UVW

    AM

    5

    *1

    Main circuit terminalControl circuit terminal

    MC

    Main circuitControl circuit

    C2B2

    A2Relay o

    AU

    PTC

    S I N K

    S O U R C E

    Terminal functions varywith the input terminalassignment( Pr. 178 to Pr. 189 )

    *3

    STF

    STR

    STOP

    RH

    RM

    RL

    JOG

    RT

    MRS

    RES

    AU

    CS

    SD

    RUN

    SU

    IPF

    OL

    FU

    SE

    EMC filter ON/OFFconnector

    ON

    OFF

    Frequency setting signal (Analog)

    Frequency setting potentiometer

    1/2W1k 2

    (Analog common)

    0 to 5VDC0 to 10VDC selectable0 to 20mADC *45

    PUconnector

    0 t 10VDC

    Frequency

    Open colSink/sou

    Running

    Up to frequ

    Instantane

    power failOverload

    Terminal 4 input selection(Current input selection)

    Selection of automatic restartafter instantaneous

    power failure

    Output stop

    Reset

    *3. AU terminal can beused as PTC inputterminal.

    Middle speed

    High speed

    Low speed

    Jog operation

    Second function selection

    Multi-speedselection

    Forwardrotation

    startReverserotation

    start

    Start self-holding selection

    PR *7 PX*7

    Jumper *7.

    *5

    *2. To supply power to thecontrol circuit separately,remove the jumper acrossR1/L11 and S1/L21.

    *2

    Do noPleaseconne

    Initiall

    Initial value

    *4. Terminal input specificationscan be changed by analog

    ON 4 2OFF

    Voltage/currentinput switch

    *4

    Resistor unit(Option)

    Brake unit(Option)

    CN8*6

    24V

    Inrush currentlimit circuit

    N/-P/+P1

    Sink logic

    Earth(Ground)

    Earth(Ground)

    CACACA

    24VDC power supply(Common for external power supply transistor)

    Contact input common

    *6.*1. DC reactor (FR-HEL)Be sure to connect the DC reactor

    supplied with the FR-F720-03160(FR-F740-01800) or more .When a DC reactor is connected tothe 02330 (FR-F740-01160) or lower,remove the jumper across P1 and P/+.

    *8. The are nconn

    *8

    (Refer to page 124 )

  • 8/12/2019 Fr f700 Na Aplica

    25/412

    2.1.2 EMC filter

    This inverter is equipped with a built-in EMC filter (capacitive filter) and common mode choke.The EMC filter is effective for reduction of air-propagated noise on the input side of the inverter.

    The EMC filter is factory-set to disable (OFF). To enable it, fit the EMC filter ON/OFF connector to thThe input side common mode choke, built-in the FR-F720-02330(FR-F740-01160) or lower invertregardless of ON/OFF of the EMC filter ON/OFF connector.

    The FR-F720-00046 and 00077 are not provided with the EMC filter ON/OFF connector. (Always ON)

    (1) Before removing a front cover, check to make sure that the indication of the inverter operation for at least 10 minutes after the power supply has been switched OFF, and check that there are no using a tester or the like. (For the front cover removal method, refer to page 6 .)

    (2) When disconnecting the connector, push the fixing tab and pull the connector straight without pforcibly pulling the connector with the tab fixed. When installing the connector, also engage the If it is difficult to disconnect the connector, use a pair of long-nose pliers, etc.

    EMC filter OFF EMC filter OFF EMC filterEMC filter ON EMC filter ON(initial setting) (initial setting) (initial settin

    FR-F720-00105 to 00250FR-F740-00023 to 00126

    FR-F720-00340, 00490FR-F740-00170, 00250

    FR-F720-00105 to 00250FR-F740-00023 to 00126

    FR-F720-00340, 00490FR-F740-00170, 00250

    FR-F720-00630FR-F740-00310, 00380

    FR-F720-00770 to 01250FR-F740-00470, 00620

    FRFR

    Main circuit terminal specifications

  • 8/12/2019 Fr f700 Na Aplica

    26/412

    Main circuit terminal specifications

    2.2 Main circuit terminal specifications

    2.2.1 Specification of main circuit terminal

    2.2.2 Terminal arrangement of the main circuit terminal, power supply and the mwiring

    200V class

    TerminalSymbol

    TerminalName Description

    R/L1,S/L2,T/L3

    AC powerinput

    Connect to the commercial power supply.Keep these terminals open when using the high power factoconverter (FR-HC, MT-HC) or power regeneration common (FR-CV).

    U, V, W Inverter output Connect a three-phase squirrel-cage motor.

    R1/L11,S1/L21

    Power supplyfor controlcircuit

    Connected to the AC power supply terminals R/L1 and S/L2retain the fault display and fault output or when using the hifactor converter (FR-HC, MT-HC) or power regeneration coconverter (FR-CV), remove the jumpers from terminals R/LL11, and S/L2 and S1/L21 and apply external power to thesterminals.The power capacity necessary when separate power is suppliR1/L11 and S1/L21 differs according to the inverter capacity

    P/+, N/- Brake unitconnection

    Connect the brake unit (FR-BU2, FR-BU, BU and MT-BU5), regeneration common converter (FR-CV), high power factor (FR-HC and MT-HC) or power regeneration converter (MT-R

    P/+, P1 DC reactorconnection

    For the FR-F720-02330 (FR-F740-01160) or lower, remove

    jumper across terminals P/+ and P1 and connect the DC reacsure to connect the DC reactor supplied with the FR-F720-0(FR-F740-01800) or higher.)When a DC reactor is not connected, the jumper across termP/+ and P1 should not be removed.

    PR, PX Please do not remove or use terminals PR and PX or the jumper connected.

    Earth (ground) For earthing (grounding) the inverter chassis. Must be earth(grounded).

    200Vclass

    FR-F720-00630 or lower 60VA

    FR-F720-0077080VA

    FR-F

    400Vclass

    FR-F740-00310 or lower 60VA

    FR-F740-0038060VA

    FR-F

    Main circui

  • 8/12/2019 Fr f700 Na Aplica

    27/412

    FR-F720-00340, 00490-NA FR-F720-00630-NA

    FR-F720-00770 to 01250-NA FR-F720-01540 to 02330-NA

    FR-F720-03160 to 04750-NA

    R/L1 S/L2 T/L3

    N/- P/+ PR

    PX

    R1/L11 S1/L21

    IM

    Jumper Jumper

    Charge lamp

    Motor Power supply

    Charge lamp

    R/L1 S/L2 T/L3 N/- P/+

    PR

    R1/L11 S1/L21

    IM

    Jumper

    Jumper

    Charge lamp

    Motor Power supply

    R/L1 S/L2 T/L3 N/-

    R1/L

    Power supply

    R1/L11 S1/L21

    Charge lamp

  • 8/12/2019 Fr f700 Na Aplica

    28/412

    Main circui

  • 8/12/2019 Fr f700 Na Aplica

    29/412

    FR-F740-03250 to 04810-NA FR-F740-05470 to 12120-NA

    CAUTION The power supply cables must be connected to R/L1, S/L2, T/L3. (Phase sequence needs not to be matched.)

    the power cable to the U, V, W of the inverter. Doing so will damage the inverter. Connect the motor to U, V, W. At this time, turning ON the forward rotation switch (signal) rotat

    counterclockwise direction when viewed from the motor shaft. When wiring the inverter main circuit conductor of the FR-F740-05470 or higher, tighten a nut from t

    conductor. When wiring two wires, place wires on both sides of the conductor. (Refer to the drawing belowbolts (nuts) provided with the inverter.

    IM

    R/L1 S/L2 T/L3 N/-

    P/+

    R1/L11 S1/L21

    P/+

    P/+

    Jumper Charge lamp

    Motor Power supplyDC reactor

    R/L1 S/L2 T/L3 N/-

    R1/L11 S1/L21

    Power supplyDC rea

    Main circuit terminal specifications

  • 8/12/2019 Fr f700 Na Aplica

    30/412

    Wiring cover and Handling (FR-F720-00930 (FR-F740-00620) or lower)1) Remove the wiring cover of the inverter. Punch out a knockout by firmly tapping it with such as a ham

    any sharp edges and burrs from knockout holes of the wiring cover.

    2) Install conduits and fix with conduits clamps. Pass the cable always through the conduit.

    CAUTIONWhen handling the wiring cover, care must be taken not to cut fingers or hands with sharp edges and burrs.To avoid wire offcuts and other foreign matter to enter the inverter, conduits must be installed to the all knockout hole

    WARNINGDo not wire without using conduits. Otherwise, the cable sheathes may be scratched by the wiring cresulting in a short circuit or earth (ground) fault.

    Wiring cover

    Knockout

    Main circui

  • 8/12/2019 Fr f700 Na Aplica

    31/412

    2.2.3 Cables and wiring length(1) Applicable cable sizeSelect the recommended cable size to ensure that a voltage drop will be 2% or less.If the wiring distance is long between the inverter and motor, a main circuit cable voltage drop wi

    torque to decrease especially at the output of a low frequency.The following table indicates a selection example for the wiring length of 20m (65.62feet).200V class (when input power supply is 220V)

    Applicable InverterModel

    TerminalScrewSize *4

    TighteningTorque

    Nm

    CrimpingTerminal

    Cable Siz

    HIV, etc. (mm 2) *1 AWG

    R/L1,S/L2,T/L3

    U, V, WR/L1,S/L2, T/L3

    U, V, W P/+, P1Earthing

    (grounding)cable

    R/L1S/L2T/L3

    FR-F720-00046 to00105-NA

    M4 1.5 2-4 2-4 2 2 2 2 14

    FR-F720-00167-NA M4 1.5 5.5-4 5.5-4 3.5 3.5 3.5 3.5 12 12FR-F720-00250-NA M4 1.5 5.5-4 5.5-4 5.5 5.5 5.5 5.5 10 10FR-F720-00340-NA M5(M4) 2.5 14-5 8-5 14 8 14 5.5 6 8FR-F720-00490-NA M5(M4) 2.5 14-5 14-5 14 14 14 8 6 6FR-F720-00630-NA M5 2.5 22-5 22-5 22 22 22 14 4 6 (FR-F720-00770-NA M6 4.4 38-6 38-6 38 38 38 14 2 2

    FR-F720-00930-NA M8(M6) 7.8 38-8 38-8 38 38 38 22 2 2FR-F720-01250-NA M8(M6) 7.8 60-8 60-8 60 60 60 22 1/0 1/0FR-F720-01540-NA M8(M6) 7.8 80-8 80-8 80 80 80 22 3/0 3/0FR-F720-01870-NA M10(M8) 14.7 100-10 100-10 100 100 100 38 4/0 4/0FR-F720-02330-NA M10(M8) 14.7 100-10 100-10 100 100 100 38 4/0 4/0FR-F720-03160-NA M12(M10) 24.5 150-12 150-12 125 125 150 38 250 250FR-F720-03800-NA M12(M10) 24.5 150-12 150-12 150 150 2 100 38 2 4/FR-F720-04750-NA M12(M10) 24.5 100-12 100-12 2 100 2 100 2 100 60 2 4/*1 The recommended cable size is that of the cable (e.g. HIV cable (600V class 2 vinyl-insulated cable)) with co

    temperature of 75C (167F). Assumes that the surrounding air temperature is 50C (122F) or less and the wiring distancles s.

    *2 The recommended cable size is that of the cable (THHW cable) with continuous maximum permissible temperature of that the surrounding air temperature is 40C (104F) or l es s and the wiring distance is 20m (65.62feet) or less.(Selection example for use mainly in the United States.)

    *3 For the FR-F720-00930 or lower, the recommended cable size is that of the cable (PVC cable) with continuoutemperature of 70C (158F). Assumes that the surrounding air temperature is 40C (104F) or less and thless.For the FR-F720-01250 or higher, the recommended cable size is that of the cable (XLPE cable) with continuoutemperature of 90C (194F). As sum es that the surrounding air temperature is 40C (104F) or less and wiring is pe(Selection example for use mainly in Europe.)

    *4 The terminal screw size indicates the terminal size for R/L1, S/L2, T/L3, U, V, W, PR, PX, P/+, N/-, P1 and a screw for earThe screw size for earthing (grounding) of the FR-F720-00930 or higher is indicated in ( ).

    *5 When connecting the option unit to P/+, P1, N/-, use THHN cables for the option and terminals R/L1, S/L2, T/L3, U, V, W

    Main circuit terminal specifications

  • 8/12/2019 Fr f700 Na Aplica

    32/412

    400V class (when input power supply is 440V based on the rated current for 110% overload for 1 minute)

    Applicable InverterModel

    TerminalScrew Size

    *4TighteningTorque Nm

    Crimping(Compression)

    Terminal

    Cable Sizes

    HIV, etc. (mm2) *1AWG/M

    *2R/L1,S/L2,T/L3

    U, V, WR/L1,S/L2,T/L3

    U, V, WP/+, P1Earthing

    (grounding)cable

    R/L1,S/L2,T/L3

    FR-F740-00023 to00083-NA

    M4 1.5 2-4 2-4 2 2 2 2 14 1

    FR-F740-00126-NA M4 1.5 2-4 2-4 2 2 3.5 3.5 12 14FR-F740-00170-NA M4 1.5 5.5-4 5.5-4 3.5 3.5 3.5 3.5 12 12FR-F740-00250-NA M4 1.5 5.5-4 5.5-4 5.5 5.5 5.5 5.5 10 10FR-F740-00310-NA M5 2.5 8-5 8-5 8 8 8 5.5 8 8

    FR-F740-00380-NA M5 2.5 14-5 8-5 14 8 14 8 6 8FR-F740-00470-NA M6 4.4 14-6 14-6 14 14 22 14 6 6FR-F740-00620-NA M6 4.4 22-6 22-6 22 22 22 14 4 4FR-F740-00770-NA M6 4.4 22-6 22-6 22 22 22 14 4 4FR-F740-00930-NA M8 7.8 38-8 38-8 38 38 38 22 1 2FR-F740-01160-NA M8 7.8 60-8 60-8 60 60 60 22 1/0 1/0FR-F740-01800-NA M8(M10) 7.8 60-8 60-8 60 60 60 22 1/0 1/0FR-F740-02160-NA M10 14.7 100-10 100-10 80 80 80 22 3/0 3/0FR-F740-02600-NA M10 14.7 100-10 100-10 100 100 100 38 4/0 4/0FR-F740-03250-NA M10(M12) 14.7 150-10 150-10 125 125 100 38 250 250

    FR-F740-03610-NA M10(M12) 14.7 150-10 150-10 150 150 150 38 300 300FR-F740-04320-NA M12(M10) 24.5 100-12 100-12 2 100 2 100 2 100 60 2 4/0FR-F740-04810-NA M12(M10) 24.5 100-12 100-12 2 100 2 100 2 100 60 2 4/0FR-F740-05470-NA M12(M10) 46 150-12 150-12 2 125 2 125 2 125 60 2 250FR-F740-06100-NA M12(M10) 46 150-12 150-12 2 150 2 150 2 125 60 2 300FR-F740-06830-NA M12(M10) 46 200-12 200-12 2 200 2 200 2 150 100 2 350FR-F740-07700-NA M12(M10) 46 C2-200 C2-200 2 200 2 200 2 200 100 2 400FR-F740-08660-NA M12(M10) 46 C2-250 C2-250 2 250 2 250 2 200 100 2 500FR-F740-09620-NA M12(M10) 46 C2-250 C2-250 2 250 2 250 2 250 2100 2500FR-F740-10940-NA M12(M10) 46 C2-200 C2-200 3 200 3 200 3 200 2100 3 350FR-F740-12120-NA M12(M10) 46 C2-200 C2-200 3 200 3 200 3 200 2100 3400*1 For the FR-F740-01160 or lower, the recommended cable size is that of the cable (e.g. HIV cable (600V class 2 vinyl-insulate

    maximum permissible temperature of 75C (167F). Assumes that the surrounding air temperature is 50C (122F) or less a20m (65.62feet) or less.For the FR-F740-01800 or higher, the recommended cable size is that of the cable (e.g. LMFC (heat resistant flexible cinsulated cable)) with continuous maximum permissible temperature of 90C (194F). Assumes that the surrounding air temor less and wiring is performed in an enclosure.

    *2 For the FR-F740-00930 or lower, the recommended cable size is that of the cable (THHW cable) with continuous maximumof 75C (167F). Assumes that the surrounding air temperature is 40C (104F) or less and the wiring distance is 20m (65.6For the FR-F740-01160 or higher, the recommended cable size is that of the cable (THHN cable) with continuous maximumof 90C (194F). Assumes that the surrounding air temperature is 40C (104F) or less and wiring is performed in an enclos

    (Selection example for use mainly in the United States.)*3 For the FR-F740-00930 or lower, the recommended cable size is that of the cable (PVC cable) with continuous maximum p70C (158F). Assumes that the surrounding air temperature is 40C (104F) or less and the wiring distance is 20m (65.62feFor the FR-F740-01160 or higher, the recommended cable size is that of the cable (XLPE cable) with continuous maximumof 90C (194F). Assumes that the surrounding air temperature is 40C (104F) or less and wiring is performed in an enclos(Selection example for use mainly in the Europe.)

    *4 The terminal screw size indicates the terminal size for R/L1, S/L2, T/L3, U, V, W, P/+, N/-, P1, and a screw for earthing (groThe screw size of the terminals P/+, N/-, and P1 in FR-F740-01800 is indicated in parentheses.

    Main circui

  • 8/12/2019 Fr f700 Na Aplica

    33/412

    (2) Notes on earthing (grounding)

    Always earth (ground) the motor and inverter.1)Purpose of earthing (grounding)

    Generally, an electrical apparatus has an earth (ground) terminal, which must be connected to th

    use. An electrical circuit is usually insulated by an insulating material and encased. However, manufacture an insulating material that can shut off a leakage current completely, and actually, a sinto the case. The purpose of earthing (grounding) the case of an electrical apparatus is to prevegetting an electric shock from this leakage current when touching it.To avoid the influence of external noises, this earthing (grounding) is important to audio eqcomputers and other apparatuses that handle low-level signals or operate very fast.

    2)Earthing (Grounding) methods and earthing (grounding) work As described previously, earthing (grounding) is roughly classified into an electrical shock prevnoise-affected malfunction prevention type. Therefore, these two types should be discriminatefollowing work must be done to prevent the leakage current having the inverter's high frequencyentering the malfunction prevention type earthing (grounding):(a) If possible, use (l) independent earthing (grounding) in figure below for the inv

    earthing(grounding) is not available, use (ll) common earthing (grounding) in the figuinverter is connected with the other equipment at an earthing (grounding) point.The (lll) common earthing (grounding) as in the figure below, which inverter shares (grounding) cable with the other equipment, must be avoided.

    A leakage current including many high frequency components flows in the earthing (grouninverter and inverter-driven motor. Therefore, use the independent earthing (groundingearthing (grounding) cable of the inverter from equipment sensitive to EMI.In a high building, it may be effective to use the EMI prevention type earthing (groundiniron structure frame, and electric shock prevention type earthing (grounding) with the in(grounding) together.

    (b) This inverter must be earthed (grounded). Earthing (Grounding) must conform to the requiand local safety regulations and electrical code (NEC section 250, IEC 536 class 1 anstandards).

    A neutral-point earthed (grounded) power supply for 400V class inverter in compliance witbe used.

    (c) Use the thickest possible earthing (grounding) cable. The earthing (grounding) cable size than the size indicated in the table on the previous page.

    (d) The earthing (grounding) point should be as close as possible to the inverter, and the earwire length should be as short as possible.

    (e) Run the earthing (grounding) cable as far away as possible from the I/O wiring of equnoises and run them in parallel in the minimum distance.

    To be compliant with the EU Directive (Low Voltage Directive) refer to the

    Inverter Other

    equipment

    (I) Independent earthing (grounding).......Best

    Inverter Otherequipment

    (II) Common earthing (grounding).......Good (III) Com

  • 8/12/2019 Fr f700 Na Aplica

    34/412

    Main circui

  • 8/12/2019 Fr f700 Na Aplica

    35/412

    2.2.4 When connecting the control circuit and the main circuit separately to th power supply

    FR-F720-00046 to 00250, FR-F740-00023 to 00126

    FR-F720-00340, 00490, FR-F740-00170, 00250

    When fault occurs, opening of the electromagnetic coninverter power supply side results in power lossdisabling the fault output signal retention. Terminals provided for when retention of a fault signal is requirethe power supply terminals R1/L11 and S1/L21 of tprimary side of the MC.Do not connect the power cable to incorrect terdamage the inverter.

    1)Loosen the upper screws.2)Remove the lower screws.3)Remove the jumper 4)Connect the separate power

    supply cable for the controlcircuit to the lower terminals(R1/L11, S1/L21).

    1)Remove the upper screws.2)Remove the lower screws.3)Remove the jumper.

    4)Connect the separate powersupply cable for the controlcircuit to the upper terminals(R1/L11, S1/L21).

    Inverter MC R/L1

    S/L2

    T/L3

    R1/L11

    S1/L21

    Remove the jumper

    Main circuit terminal block

    R1/L11 S1/L21

    3)

    1)

    2)

    4)

    S/L2T/L3

    R/L1

    3)

    1)

    2)

    R1/L11S1/L21

  • 8/12/2019 Fr f700 Na Aplica

    36/412

    Con

  • 8/12/2019 Fr f700 Na Aplica

    37/412

    2.3 Control circuit specifications

    2.3.1 Control circuit terminals

    indicates that terminal functions can be selected using Pr. 178 to Pr. 196 (I/O terminal function s

    (1) Input signals

    T y p e Terminal

    SymbolTerminal

    NameDescription

    C o n

    t a c t

    i n p u

    t

    STF Forwardrotation startTurn ON the STF signal to start forwardrotation and turn it OFF to stop.

    When the STF andSTR signals are turnedON simultaneously, the

    stop command is givenSTR Reverse

    rotation start

    Turn ON the STR signal to start reverse

    rotation and turn it OFF to stop.

    STOPStart self-holdingselection

    Turn ON the STOP signal to self-hold the start signal.

    RH,RM, RL

    Multi-speedselection

    Multi-speed can be selected according to the combination of RH,RM and RL signals.

    JOG Jog modeselectionTurn ON the JOG signal to select Jog operation (initial setting)and turn ON the start signal (STF or STR) to start Jog operation.

    RT

    Second

    functionselection

    Turn ON the RT signal to select second function.When the second function such as "second torque boost" and"second V/F (base frequency)" are set, turning ON the RT signalselects these functions.

    MRS Output stop

    Turn ON the MRS signal (20ms or more) to stop the inverteroutput.Use to shut off the inverter output when stopping the motor byelectromagnetic brake.

    RES Reset

    Used to reset fault output provided when fault occurs.Turn ON the RES signal for more than 0.1s, then turn it OFF.Initial setting is for reset always. By setting Pr.75 , reset can be setto enabled only at fault occurrence. Inverter recovers about 1safter the reset is released.

    AU

    Terminal 4input selection

    Terminal 4 is valid only when the AU signal is turned ON. (Thefrequency setting signal can be set between 0 and 20mADC.)Turning the AU signal ON makes terminal 2 (voltage input)invalid.

    PTC input AU terminal is used as PTC input terminal (thermal protection ofthe motor). When using it as PTC input terminal, set the AU/PTCswitch to PTC.

    CS

    Selection ofautomaticrestart afterinstantaneouspower failure

    When the CS signal is left ON, the inverter restarts automatically at

    power restoration. Note that restart setting is necessary for thisoperation. In the initial setting, a restart is d isabled.(Refer to page 154 for Pr. 57 Restart coasting time)

    Contact inputcommon (sink)(initial setting)

    Common terminal for contact input terminal (sink logic)

    l h l h l l f

    Control circuit specifications

  • 8/12/2019 Fr f700 Na Aplica

    38/412

    *1 Set Pr. 73 , Pr. 267 , and a voltage/current input switch correctly, then input an analog signal in accordance with the setting. Applying a voltage signal with voltage/current input switch ON (current input is selected) or a current signal with switch O

    selected) could cause component damage of the inverter or analog circuit of signal output devices. (For details,

    F r e q u e n c y s e

    t t i n g

    10EFrequencysetting powersupply

    When connecting the frequency setting potentiometer at an initial

    status, connect it to terminal 10.Change the input specifications of terminal 2 when connecting itto terminal 10E. (Refer to page 177 for Pr. 73 Analog input selection.)10

    2Frequencysetting(voltage)

    Inputting 0 to 5VDC (or 0 to 10V, 0 to 20mA) provides themaximum output frequency at 5V (10V, 20mA) and makes inputand output proportional. Use Pr. 73 to switch from among input 0to 5VDC (initial setting), 0 to 10VDC, and 0 to 20mA.Set the voltage/current input switch in the ON position to selectcurrent input (0 to 20mA). *1

    VI1MpvCI2Mpc

    4Frequencysetting(current)

    Inputting 4 to 20mADC (or 0 to 5V, 0 to 10V) provides themaximum output frequency at 20mA (5V, 10V) makes input andoutput proportional. This input signal is valid only when the AUsignal is ON (terminal 2 input is invalid). Use Pr. 267 to switchfrom among input 4 to 20mA (initial setting), 0 to 5VDC, and 0 to10VDC. Set the voltage/current input switch in the OFF positionto select voltage input (0 to 5V/0 to 10V). *1

    1Frequencysettingauxiliary

    Inputting 0 to 5 VDC or 0 to 10VDC adds this signal to terminal2 or 4 frequency setting signal. Use Pr.73 to switch between theinput 0 to 5VDC and 0 to 10VDC (initial setting).

    I1Mp

    5Frequencysetting

    common

    Common terminal for frequency setting signal (terminal 2, 1 or 4)and analog output terminal AM and CA. Do not earth (ground).

    P T C t h e r m

    i s t o r

    102

    PTCthermistorinput

    For connecting PTC thermistor output.When PTC thermistor protection is valid ( Pr. 561 "9999"), terminal 2is not available for frequency setting.

    AtsHr5(

    T y p e Terminal

    SymbolTerminal

    Name Description

    Con

  • 8/12/2019 Fr f700 Na Aplica

    39/412

    (2) Output signals

    (3) Communication

    T y p e Terminal

    SymbolTerminal

    NameDescription

    R e l a y

    A1,B1,C1

    Relay output 1(Fault output)

    1 changeover contact output indicates that the invertersprotective function has activated and the output stopped.Fault: No conduction across B and C (Across A and C Continuity),Normal: Across B and C Continuity (No conduction across A and C)

    A2,B2,C2

    Relay output 2 1 changeover contact output

    O p e n c o

    l l e c t o r

    RUNInverterrunning

    Switched low when the inverter output frequency is equal to orhigher than the starting frequency (initial value 0.5Hz). Switchedhigh during stop or DC injection brake operation.

    SUUp tofrequency

    Switched low when the outputfrequency reaches within the range of10% (initial value) of the set frequency.Switched high during acceleration/deceleration and at a stop.

    Alarm code (4bit)output

    OLOverloadwarning

    Switched low when stall prevention isactivated by the stall preventionfunction. Switched high when stallprevention is cancelled.

    IPF Instantaneouspower failure

    Switched low when an instantaneouspower failure and under voltageprotections are activated.

    FUFrequencydetection

    Switched low when the inverter outputfrequency is equal to or higher than thepreset detected frequency and highwhen less than the preset detectedfrequency.

    SEOpen collectoroutput common

    Common terminal for terminals RUN, SU, OL, IPF, FU

    A n a

    l o g

    CA Analog currentoutput

    Select one e.g. output frequency frommonitor items. (Not output duringinverter reset.)The output signal is proportional to themagnitude of the correspondingmonitoring item.To set a full-scale value for monitoringthe output frequency and the outputcurrent, set Pr. 55 and Pr. 56 .( Refer to page 149 )

    Output item:Output frequency(initial setting)

    AM Analog voltageoutput

    T y p e Terminal

    SymbolTerminal

    Name Description

    Control circuit specifications

  • 8/12/2019 Fr f700 Na Aplica

    40/412

    2.3.2 Changing the control logic

    The input signals are set to sink logic (SINK) when shipped from the factory.To change the control logic, the jumper connector on the back of the control circuit terminal block must beother position.(The output signals may be used in either the sink or source logic independently of the jumper connector p1) Loosen the two installation screws in both ends of the control circuit terminal block. (These scre

    removed.)Pull down the terminal block from behind the control circuit terminals.

    2) Change the jumper connector set to the sink logic (SINK) on the rear panel of the control circuit tersource logic (SOURCE).

    3) Using care not to bend the pins of the inverter's control circuit connector, reinstall the control circuit and fix it with the mounting screws.

    Jumper connector

    Con

    4)Si k l i d l i

  • 8/12/2019 Fr f700 Na Aplica

    41/412

    4)Sink logic and source logicIn sink logic, a signal switches ON when a current flows from the corresponding signal input termTerminal SD is common to the contact input signals. Terminal SE is common to the open collectIn source logic, a signal switches ON when a current flows into the corresponding signal input teTerminal PC is common to the contact input signals. Terminal SE is common to the open collecto

    When using an external power supply for transistor output

    Sink logic typeUse terminal PC as a common terminal, and performwiring as shown below. (Do not connect terminal SD of the inverter with terminal 0V of the external power supply. When using terminals PC and SD as a 24VDCpower supply, do not install a power supply in parallel inthe outside of the inverter. Doing so may cause amalfunction due to undesirable current.)

    Source logic typeUse terminal SD as a commwiring as shown below. (Do the inverter with terminal +supply. When using terminalpower supply, do not install aparallel with the inverter. malfunction in the inverter du

    Current

    PC

    STF R

    STRR

    Source logic

    Current

    SD

    STFR

    STRR

    Sinkconnector

    Sink logic

    Current flow concerning the input/output signalwhen sink logic is selected

    Current flow concerning the input/ouwhen source logic is selected

    24V

    RUN

    SE

    Inverter

    Curr

    ++-

    DC input (sink type)

    Inverter

    24VDC

    RUN

    SE

    TB1

    TB17

    R

    R

    Current flow

    TB1

    TB2 STR

    STF 24VDC(SD)

    QY40P type transistoroutput unit

    Inverter

    TB

    QY80 type transistoroutput unit

    Control circuit specifications

    2 3 3 Control circuit terminal layout

  • 8/12/2019 Fr f700 Na Aplica

    42/412

    2.3.3 Control circuit terminal layout

    (1) Common terminals of the control circuit (SD, 5, SE)Terminals SD, 5, and SE are all common terminals (0V) for I/O signals and are isolated from each earth(ground) these terminals.

    Avoid connecting the terminal SD and 5 and the terminal SE and 5.Terminal SD is a common terminal for the contact input terminals (STF, STR, STOP, RH, RM, RL, JOG, RT

    AU, CS).The open collector circuit is isolated from the internal control circuit by photocoupler.Terminal 5 is a common terminal for frequency setting signal (terminal 2, 1 or 4), analog current outputand analog output terminal AM.

    It should be protected from external noise using a shielded or twisted cable.Terminal SE is a common terminal for the open collector output terminal (RUN, SU, OL, IPF, FU).The contact input circuit is isolated from the internal control circuit by photocoupler.

    (2) Signal inputs by contactless switches

    The contacted input terminals of the inverter (STF, STR, STOP,RH, RM, RL, JOG, RT, MRS, RES, AU, CS) can be controlledusing a transistor instead of a contacted switch as shown on the

    right.

    External signal input us

    A1 B1 C1 A2

    STOPAURTRHRMRL

    OLIPFSURUN

    B2 C2 10E 10

    SDRESMRS

    STFSDSDFU PCCSJOGSTR

    2 5 4

    1AMCA

    SE

    CTeT

    Con

    2 3 4 Wiring instructions

  • 8/12/2019 Fr f700 Na Aplica

    43/412

    2.3.4 Wiring instructions

    1) It is recommended to use the cables of 0.75mm 2 gauge for connection to the control circIf the cable gauge used is 1.25mm 2 or more, the front cover may be lifted when there are

    the cables are run improperly, resulting in an operation panel contact fault.2) The maximum wiring length should be 30m (98.43feet).3) Use two or more parallel micro-signal contacts or twin contacts to

    prevent a contact faults when using contact inputs since thecontrol circuit input signals are micro-currents.

    4) Use shielded or twisted cables for connection to the control circuit terminals and run them away fpower circuits (including the 200V relay sequence circuit).

    5) Do not apply a voltage to the contact input terminals (e.g. STF) of the control circuit.6) Always apply a voltage to the fault output terminals (A, B, C) via a relay coil, lamp, etc. Wiring of the control circuit of the FR-F720-03160 (FR-F740-01800) or higher

    For wiring of the control circuit of the FR-F720-03160 (FR-F740-01800) or higher, separate awaythe main circuit.Make cuts in rubber bush of the inverter side and lead wires.

    Micro signa

  • 8/12/2019 Fr f700 Na Aplica

    44/412

    2.3.5 Mounting the operation panel (FR DU07) on the enclosure surface

    Having an operation panel on the enclosure surface is convenient. With a connection coperation panel (FR-DU07) or the parameter unit (FR-PU07) to the enclosure surface, and connect it to thUse the option FR-CB2 , or the connector and cable available on the market.(For mounting the operation panel (FR-DU07), the optional connector (FR-ADP) is required.)Securely insert one end of connection cable until the stoppers are fixed.

    Refer to page 216 for RS-485 communication.

    REMARKS Refer to the following when fabricating the cable on the user side. Keep the total cable length within 20m (65.6 feet).

    Commercially available product examples (as of February 2012)

    S TF FWD P U

    Parameter unit connection cable(FR-CB2 )(option)

    Operation panel(FR-DU07)

    Parameter unit (FR-PU07)(option)

    Operation panel connection connector (FR-ADP)(option)

    * Do not use pins No. 2, 8 of the communication cable.

    Product Type Maker

    Communication cableSGLPEV-T (Cat5e/300m)

    24AWG 4P*Mitsubishi Cable Industries, Ltd.

    RJ-45 connector 5-554720-3 Tyco Electronics Corporation

    Con

    2.3.6 RS-485 terminal block

  • 8/12/2019 Fr f700 Na Aplica

    45/412

    2.3.6 RS 485 terminal block

    2.3.7 Communication operation

    Using the PU connector or RS-485 terminal, you can perform communication operation from a persoWhen the PU connector is connected with a personal, FA or other computer by a communication cablecan run and monitor the inverter or read and write to parameters.For the Mitsubishi inverter protocol (computer link operation), communication can be performed withand RS-485 terminal.For the Modbus-RTU protocol and BACnet MS/TP protocol, communication can be performedterminal.For further details, refer to page 211 .

    Conforming standard: EIA-485(RS-485)Transmission format: Multidrop linkCommunication speed: MAX 38400bps

    (76800bps for BACnet MS/TP protocol)Overall length: 500mConnection cable:Twisted pair cable

    (4 pairs)

    RRDA1(RXD1+)RDB1

    (RXD1-)RDA2

    (RXD2+)RDB2

    (RXD2-)

    SDA1(TXD1+)

    SDB1(TXD1-)

    SDA2(TXD2+)

    SDB2(TXD2-)

    P5S(VCC)

    SG(GND)

    P5S(VCC)

    SG(GND) V

    TXD

    OPEN

    100

    Terminating resistor sFactory-set to "OPENSet only the terminatithe remotest inverter t

    Connection of stand-alone option units

    2.4 Connection of stand-alone option units

  • 8/12/2019 Fr f700 Na Aplica

    46/412

    2.4 Connection of stand alone option units

    The inverter accepts a variety of stand-alone option units as required.Incorrect connection will cause inverter damage or accident. Connect and operate the option uniaccordance with the corresponding option unit manual.

    2.4.1 Connection of the brake unit (FR-BU2)Connect the brake unit (FR-BU2) as shown below to improve the braking capability at deceleration.(1) Connection example with the GRZG type discharging resistor

    *1 Connect the inverter terminals (P/+, N/-) and brake unit (FR-BU2) terminals so that their terminal names m(Incorrect connection will damage the inverter and brake unit.)

    *2 When the power supply is 400V class, install a step-down transformer.*3 Keep a wiring distance of within 5m (16.4feet) between the inverter, brake unit (FR-BU2) and dischargin

    the wiring is twisted, the cable length must not exceed 10m (32.8feet).*4 It is recommended to install an external thermal relay to prevent overheat of discharging resistors.*5 Refer to FR-BU2 manual for connection method of discharging resistor.

    Brake Unit Discharging Resistor Recommended External Thermal Relay

    FR-BU2-1.5K GZG 300W-50 (one) TH-N20CXHZ 1.3AFR-BU2-3.7K GRZG 200-10 (three in series) TH-N20CXHZ 3.6AFR-BU2-7.5K GRZG 300-5 (four in series) TH-N20CXHZ 6.6AFR-BU2-15K GRZG 400-2 (six in series) TH-N20CXHZ 11AFR-BU2-H7.5K GRZG 200-10 (six in series) TH-N20CXHZ 3.6AFR-BU2-H15K GRZG 300-5 (eight in series) TH-N20CXHZ 6.6AFR-BU2-H30K GRZG 400-2 (twelve in series) TH-N20CXHZ 11A

    CAUTION

    UVW

    P/+N/-

    R/L1S/L2T/L3

    Motor

    IM

    Inverter PR

    N/-BUESD

    P/+

    A

    BC

    FR-BU2

    GRZG typedischarging resist

    External thermalrelay

    RR

    Three-phase ACpower supply

    MCCB MC

    ON

    MCT

    *1*1

    *3

    *3

    *2

    MC

    *4

    OCR

    5m (16.4feet) or less

    To th

    unit

    Connection of st

    (2) FR-BR-(H) connection example with resistor unit

  • 8/12/2019 Fr f700 Na Aplica

    47/412

    (3) Connection example with MT-BR5 type resistor unit

    *1 Connect the inverter terminals (P/+, N/-) and brake unit (FR-BU2) terminals so that their terminal nam(Incorrect connection will damage the inverter and brake unit.)

    *2 When the power supply is 400V class, install a step-down transformer.*3 The wiring distance between the inverter, brake unit (FR-BU) and resistor unit (FR-BR) should be

    when the wiring is twisted, the cable length must not exceed 10m (32.8feet).

    *4 The contact between TH1 and TH2 is closed in the normal status and is open at a fault.

    CAUTIONDo not remove a jumper across terminal P/+ and P1 except when connecting a DC reactor.

    *1 Connect the inverter terminals (P/+, N/-) and brake unit (FR-BU2) terminals so that their terminal nam(Incorrect connection will damage the inverter and brake unit.)

    *2 When the power supply is 400V class, install a step-down transformer.*3 The wiring distance between the inverter, brake unit (FR-BU2) and resistor unit (MT-BR5) should

    UVW

    P/+N/-

    R/L1S/L2T/L3

    Motor

    IM

    Inverter PR

    N/-BUESD

    P/+

    P

    FR-BU

    FR-B

    T

    TPR

    Three phase ACpower supply

    MCCB MCMC

    O

    MT

    *1 *1

    5m or less*3

    *3

    *2

    MCR/L1 Motor

    IM

    Inverter

    S/L2T/L3

    UV

    P/+N/- P

    PR

    5mor less

    W

    Three phase ACpower supply

    MCCB OFFON

    MC

    CR1

    T

    *3

    *1 *1*3

    *5

    PNBUESD

    PPR

    Brake unitFR-BU2

    ResiM

    *2

    Connection of stand-alone option units

    2.4.2 Connection of the brake unit (FR-BU/MT-BU5)

  • 8/12/2019 Fr f700 Na Aplica

    48/412

    When connecting the brake unit (FR-BU(H)/MT-BU5) to improve the brake capability at deceleration, maas shown below.(1) Connection with the FR-BU (FR-F720-02330 (FR-F740-01160) or lower)

    (2) Connection with the MT-BU5 (FR-F720-03160 (FR-F740-01800) or higher) After making sure that the wiring is correct, set "1" in Pr.30 Regenerative function selection . ( R

    *1 Connect the inverter terminals (P/+, N/-) and brake unit (FR-BU (H)) terminals so that their terminal signalwith each other. (Incorrect connection will damage the inverter.)

    *2 When the power supply is 400V class, install a step-down transformer.*3 The wiring distance between the inverter, brake unit (FR-BU) and resistor unit (FR-BR) should be within

    feet). If twisted wires are used, the distance should be within 10m(32.8feet).

    CAUTIONIf the transistors in the brake unit should become faulty, the resistor can be unusually hot, causing a fire. Therefomagnetic contactor on the inverters input side to configure a circuit so that a current i s shut off in case of fault.Do not remove a jumper across terminal P/+ and P1 except when connecting a DC reactor.

    U

    V

    W

    P /+

    N/

    R/L1

    S/L2

    T/L3

    Motor

    IM

    Inverter PR

    N/

    P/+

    P

    FR

    FR

    PR

    *1 *

    Three-phase AC

    power supply

    MCCB M C

    T *2

    MC

    *35m (16.4feet)

    or less

    MC

    R/L1 Motor

    IM

    Inverter

    S/L2

    T/L3

    U

    V

    P/+N/

    PPR

    P

    P

    W

    Three-phase AC power

    supply

    MCCB OFFON

    MC

    T *1

    5m(16.4feet)or less

    *2

    Connection of st

    M k t i bb b h f th ti f th i t d l d bl

  • 8/12/2019 Fr f700 Na Aplica

    49/412

    Make cuts in rubber bush of the upper portion of the inverter and lead a cable.1) Make cuts in the rubber bush for leading the CN8 connector cable with a nipper or cutter knife.

    2) Insert a connector on the MT-BU5 side through a rubber bush to connect to a connector on the inv

    CAUTIONClamp the CN8 connector cable on the inverter side with a wire clamp securely.

    Parameters referred to Pr. 30 Regenerative function selection Refer to page 115 Pr. 70 Special regenerative brake duty Refer to page 115

    Rubber bushes

    Make cuts inrubber bush

    CN8 connector Wire clamp

    Connection of stand-alone option units

    2.4.3 Connection of the brake unit (BU type)

  • 8/12/2019 Fr f700 Na Aplica

    50/412

    Connect the brake unit (BU type) correctly as shown below. Incorrect connection will damage the inverter. Removacross terminals HB and PC and terminals TB and HC of the brake unit and fit it to across terminals PC and TB.

    2.4.4 Connection of the high power factor converter (FR-HC/MT-HC)When connecting the high power factor converter (FR-HC) to suppress power harmonics, perform wiring securelIncorrect connection will damage the high power factor converter and inverter.

    After making sure that the wiring is correct, set "2" in Pr. 30 Regenerative function selection . ( Refer t(1) Connection with the FR-HC (FR-F720-02330 (FR-F740-01160) or lower)

    *1 When the power supply is 400V class, install a step-down transformer.

    CAUTIONThe wiring distance between the inverter, brake unit and discharging resistor should be within 2m(6.56feet). If twisused, the distance should be within 5m(16.4feet).If the transistors in the brake unit should become faulty, the resistor can be unusually hot, causing a fire. Therefomagnetic contactor on the inverter's power supply side to shut off a current in case of fault.Do not remove a jumper across terminal P/+ and P1 except when connecting a DC reactor.

    U

    V

    WIM Brake un

    (BU type

    Dischargingresistor

    R/L1

    S/L2

    T/L3

    N/-

    P/+

    MC

    P

    PR