flow measurement - control globalflow measurement. fall, 2019. ehandbook. table of contents. how to...
TRANSCRIPT
FlowMeasurementFall, 2019
eHANDBOOK
TABLE OF CONTENTSHow to specify a control valve 4
Understand valve anatomy, terminology, data sheets and what could go wrong.
How to optimize pumping costs 10
Use a variable-speed pump and minimize valve pressure drops.
Remote control of fractionation 15
Can smart differential pressure (DP) cells be used for custody transfer?
Compressor surge control 18
Deeper understanding and simulation can virtually eliminate instabilities.
AD INDEXAcromag • http://www.Acromag.com 3
Kobold Instruments • https://koboldusa.com 9
Krohne • http://us.krohne.com 14
Endress+Hauser • http://www.us.endress.com 17
eHANDBOOK: Flow Measurement, Fall, 2019 2
www.ControlGlobal.com
Visit www.Acromag.com/SCTO LEARN MORE
You can depend on Acromag for all
your monitoring and control solutions.
New Dual-Channel ProgrammableTransmitters & Signal Splitters
■ Dual channel saves you money
■ Front facing terminal blocks saves you time
■ High performance increases accuracy
Acromag.com
877-295-7066
Linkedin.com/company/acromag
MADE IN USA
ISO9001AS9100
IECEx
Valve specification begins with the control
loop, which includes the transmitter that
forwards signals to the computer, positioner
and actuator. The control valve assembly
consists of the actuator that opens and
closes the valve, positioner that converts
electric signals to pneumatic signals, and
valve that partially obstructs flow to control
a process parameter.
VALVE ANATOMIESUp close, the positioner has a lot of moving
parts, but it’s typically a box mounted directly
to the valve; it hooks up to the instrument
air supply; supplies the actuator with air to
control valve position; and often provides
diagnostic information for the valve.
Meanwhile, the actuator receives a pneu-
matic signal from the positioner; amplifies
it to overcome process pressure; and pro-
vides a safe failure direction in the event of
signal loss, such as “open, closed, last.” The
two main types of actuators are:
• Diaphragm actuators, in which air pressure
acts on a diaphragm with high surface
area, and it’s opposed by a Fall that dic-
tates fail direction. They’re low-friction;
provide a fast response to small changes
(which account for most changes in a pro-
cess); and have a longer response time for
larger changes. They’re the process indus-
try standard.
• Piston actuators are selected when more
thrust or greater stroke length is needed.
They’re single-acting or double-acting.
While double-acting provides better thrust
and is more precise, it also requires a
How to specify a control valveUnderstand valve anatomy, terminology, data sheets and what could go wrong.
by Eric Lofland
eHANDBOOK: Flow Measurement, Fall, 2019 4
www.ControlGlobal.com
volume tank that needs maintenance, as
well as a locking mechanism to fail in any
position other than last.
The valve body’s primary features include
the process connections, such as flange, NPT
or wafer, which join it to the pipe; stem that
moves the final element to partially obstruct
process flow; and vena contracta, which is the
point where the stream has the lowest flow
area. There are two main design families:
• Rotary valves are modulated by a rotating
stem, and are generally classified by the
design of the closing member. They’re
full-port and free draining, have high
capacity for a given line size, and have a
narrower optimal control range. The main
types include butterfly, v-notch ball and
eccentric plug valves.
• Sliding stem valves are modulated by
moving the stem in a linear fashion. They
have lower capacity for a given line size,
and a wide control range. Their two
varieties are balanced and unbalanced.
Unbalanced moves against process pres-
sure, and is easier to seal. Balanced uses
holes to transfer pressure, and doesn’t
require as much force from the actuator,
but requires a seal between the plug and
the cage.
THE DATA SHEETSo how do users describe what valve
technology they need? They use the data
sheet. Examples here use the ISA’s (www.
isa.org) format, but vendors also provide
data sheets. And, though most have a
similar structure, many client sites have
a preferred format that supersedes the
ISA’s requirements.
We recommend filling out a data sheet by
answering the well-known riddle, “How do
you eat an elephant?” One bite at a time.
This means separating the data sheet by
sections, and tackling each section individu-
ally. The typical sections are:
• Revision block lists people or groups with
information, instrument history, project
history and changes over time. It’s the
best place to start because it’s informa-
tion you already have.
• Process data is a thumbprint of the
application, and should be filled out by a
process engineer or someone else who
knows the process. It helps determine
chemical compatibility, physical design
specifications and sizing. More informa-
tion is better! For example, if you’re sizing
for three flowing conditions, each needs
a unique flow, inlet and outlet pressure.
Ask questions that might not be apparent
about the section, such as, is the service
dirty/corrosive, erosive, toxic or flamma-
ble? You can always remove unnecessary
information when the data sheet is issued.
• Manufacturers and valve type includes
picking a manufacturer from the site’s
approved manufacturer list; consider
the body style (rotary or sliding stem)
that suits the application best; and
find a model type that suits the design
www.ControlGlobal.com
eHANDBOOK: Flow Measurement, Fall, 2019 5
temperature, shutoff pressure, and line
size of your application.
• Actuator is generally selected based on
valve type, and sized by the vendor. A
hydraulic calculation is used based on
valve requirements and minimum avail-
able air pressure. A safety factor of 10%,
25% or 50% is usually included based on
how likely the service is to clog the valve
or inhibit valve movement.
• Positioner is chosen by input type and
desired diagnostics. High performance
is often available for applications where
response time is critical.
• Materials include two types: external and
trim. Requirements for trim are more
stringent as small changes to these
surfaces can drastically affect valve
performance.
• Notes is a great place for information that
doesn’t fit in the body of the data sheet.
This can include testing and certifica-
tion requirements or references to other
relevant documents. However, avoid
installation notes here, or specifications
that won’t be provided to the vendor.
It’s also important for all valve specification
team members to communicate needs and
expectations clearly, as real specifications
generally require compromises in certain
areas to optimize performance.
SIZING THEORYFlow isn’t all that defines flow capacity
(Cv) or contributes to selecting the right
valve. It’s only part of the overall puzzle. Cv
defines flow capacity required by process
conditions (Figure 2).
Most manufacturers supply sizing software.
Users enter process variables, and the
software outputs the Cv for each flow con-
dition. Users look at the flow Cv curve to
pick an appropriately sized valve. The curve
plots Cv travel % for a value that’s differ-
ent for each valve, and supplied by most
vendor software.
Placing the operating points at favorable
control points on the Cv curve is important.
Plus, characteristics vary by valve type.
WHAT COULD GO WRONG? PLENTYThe three primary issues that can adversely
impact valves and specifying them are
material such as corrosion and erosion,
FLOW CAPACITY EQUATIONSFlow is not all that defines flow capacity (Cv) required by process conditions, but these equa-tions do. Most manufacturers supply sizing soft-ware, users enter their process variables, and the software outputs the Cv for each flow condition. Users then look at the flow Cv curve to pick an appropriately sized valve. Source: Ambitech
Q = flowFP = piping geometryΔP = valve pressure dropGL = liquid specific gravityZ = compressibilty factor of gas
N = empirical constant (manufacturer dependent)
P1 = valve inlet pressureT1 = valve inlet temperature Gg = gas specific gravity
∙Cv (liquid) = Q
NFP ΔPGL
Q
NFP P1 ∙ΔPP1
GgT1 Z
Cv (gas) =
www.ControlGlobal.com
eHANDBOOK: Flow Measurement, Fall, 2019 6
capacity such as high and low Cv require-
ments, and phase change such as flashing,
cavitation and two-phase flow.
Corrosion solutions can be found by: con-
sulting a material compatibility table;
consulting a materials expert in your orga-
nization; investigating other applications for
a similar service; and considering a corro-
sion-resistant alloy such as Hastelloy, Monel
or titanium-based alloys.
Erosion solutions include: hardening wetted
parts with martensitic alloys or stellite
facing, installing a filter upstream; avoid-
ing restricted trims; using a rotary design
to maximize surface area and minimizing
path changes.
High Cv applications have high through-
put with low pressure drop, and are often
found in pump suction or as an add-on to a
system already hydraulically stretched. The
solution for high Cv is to have the largest
vena contracta possible, and use an open
port, which usually means rotary valves.
Low Cv applications have low throughput
and high pressure drop, are often injection
or purge applications, or in level settings
on highly pressurized vessels. The solution
for low Cv is to use the smallest vena con-
tracta, often to employ restricted trim, and
to recognize that these applications are
sensitive to plugging and that there are lim-
ited anti-cavitation options.
Turndown = Cv max / Cv min are addressed
by solutions available for high or low Cv
applications, though it’s difficult to do both.
Talk to the expert users of the process, and
find out what’s most imporant to them if
you find no valve exists that can control at
both the minimum and maximum points.
Phase changes include flashing, cavitation
and two-phase inlet flow. These involve big
physical changes that can cause a lot of
stress. Phase change risk factors include:
when the initial phase is liquid, vapor pres-
sure that’s close to inlet or outlet pressure,
or a pressure drop that’s a large percent-
age of inlet pressure. When fluid moves
through a valve, flow remains constant
through the system.
Flash occurs when flow goes in as a liquid
and out as a vapor, which can cause a lot of
damage due to hydrodynamic stress. While
there’s no way to reliably predict the extent
or rate of damage, reducing the velocity
of the stream can help, as can redirect-
ing the impact to non-valve surfaces, and
hardening all control surfaces. Frequently,
this means angle valves or rotary valves in
reverse flow.
Cavitation is a liquid-vapor-liquid phase
change that can be very violent. Solutions
include beefing up with restricted or hard-
ened trims like stellite, which can mitigate
damage, but won’t prevent it. Users can
also deploy special anti-cavitation trims
www.ControlGlobal.com
eHANDBOOK: Flow Measurement, Fall, 2019 7
to prevent cavitation, such as: cage type
with small holes, though they can plug and
may need service, or notch type that uses a
series of notches to redirect flow. The idea
is to stage the pressure drop, so cavitation
doesn’t occur, but this also means restricted
flow profiles and minimum flows.
Two-phase flows come in two types:
gas-liquid that contains two different com-
ponents in two phases such as air and
water, and vapor-liquid that contains one
components in two phases such as steam
and water.
No method exists to analytically calculate
Cv in a two-phase system. Consequently,
the first rule for sizing a control valve for
two-phase flow is—don’t! However, if you
must size for two phases, then think happy
thoughts, ensure you have flow data on
both phases, approximate the Cv by adding
the Cv of each phase, and in vapor-liquid
phases, include overcapacity to account for
possible process upsets.
Eric Lofland is senior engineer in the Instrumentation
and Controls Dept. at Ambitech Engineering Corp.,
which is a Zachary Group company. He can be reached
www.ControlGlobal.com
eHANDBOOK: Flow Measurement, Fall, 2019 8
www.koboldusa.com 1801 Parkway View Drive, Pittsburgh, PA, 15205 1-800-998-1020
• Durable Metal Housing • 2 Configurable Outputs• Superior Measuring Accuracy• Bi-directional Flow Measurement• Extremely High Turndown Ratio
MISMIM+ Revolutionary Economical Magnetic Inductive Flowmeters
HPC A Worldwide First in Coriolis Technology Architecture
The MIM magmeter delivers a revolutionary design for measuring and monitoring the flow and temperature of
conductive liquids in pipes. The compact design offers exceptional features and functions, at an economical price.
Engineered to exceed the competition, the MIM triumphs with: a superior measuring accuracy, four times the turndown ratio, easy onsite programming, batching functionality, and bi-directional flow measurement.
The MIM is built to last, with a rugged stainless steel body. The display is both configurable and rotatable. The MIM is an ideal solution for a variety of applications; with ranges from 0.48...48 GPH to 0.4...90 GPM, temperatures to 284 °F, and pressures up to 230 PSI.
The MIS is a full bore electromagnetic flowmeter featuring the same unique and versatile electronics module and is suitable for a wide range of applications.
New Products from KOBOLD Instruments: Setting the Standard for Cutting Edge Technology in the Field of Instrumentation
The HPC breaks the barriers of low-flow measurement for Coriolis flow meters. Most low-flow options employ a single tube design where external interference increases dramatically, requiring costly decoupling. Another challenge most low-flow options face is that the weight influence of the sensor coils compared to the pipe diameter limits the potential design size. The
revolutionary HPC employs lightweight magnets that are mounted onto the pipes themselves. This provides
the sensor with significantly noise-reduced and predictable dynamic behavior, capable of functioning at higher frequencies, further decoupling the sensor‘s measurement from any external vibrations.
• Batching Function is Standard• Grand and Resettable Totalizer• Color, Multi-parameter Touchscreen• Display Rotates in 90° Increments• Intuitive Set-up via Touch Keys
• Unique Coriolis Technology • For Very Low Flow Rates• Rugged Flow Body
• Exceptional Accuracy• Vibration Resistant• Modular Mounting Concept
Like the MIM, the MIS can accomodate all flow directions due to the rotating digital TFT display screen. The rugged flow bodies are made of cast steel. The MIM and MIS feature a convienent IO-Link, especially useful for Industry 4.0 compliance. Analog, frequency, and pulse outputs are standard along with alarm, batching, and totalizing features.
The HPC integrates up to 4 sensor coils which increases the resolution accordingly. HPC sensor coils are mounted between the pipes, not on them. This new concept delivers an extremely small meter with exceptional accuracy and resistance to external interference.
Q: Delivery of transmix fuel to two sepa-
ration towers is being upgraded. Coriolis
meters were installed and are currently
functioning. Two PID flow control loops
currently maintain flow. The transmix
liquid passes through a series of heat
exchangers on its way to the towers.
It’s estimated that between the friction
losses in the heat exchangers and the
elevation change, the head loss is on the
order of 30 psi.
The Coriolis meters require minimum pres-
sure to function. Now, the pump can’t meet
the minimum pressure for both towers in
service, so only one tower is in service.
A new pump and VFD will be installed.
Two pressure transmitters will also be
installed—one right after the pump, the
other up by the towers just before the
split to the two flowmeters. There’s an
estimated 30- to 45-second lag between
a change in pump speed and an observed
change in pressure at the flowmeters.
The plan is to use a new PID pressure loop
to maintain the pressure just downstream
of the new pump by adjusting the VFD.
The second transmitter up by the flowme-
ters will be used with logic that helps avoid
low pressure at the flowmeters. If pressure
up there falls below a threshold, logic will
put the flow loops in manual and start clos-
ing the valves to build pressure back up.
The question is whether this design concept
is sound and valid, or will there surely be
interaction? Or maybe it will work, but we
have to try it and fine tune it?
William Love. [email protected]
How to optimize pumping costsUse a variable-speed pump and minimize valve pressure drops.
by Béla Lipták
eHANDBOOK: Flow Measurement, Fall, 2019 10
www.ControlGlobal.com
A: This is a valuable question because it
applies to all pumping system applications.
The important point to remember is that
one can’t independently control both the
pressure and the flow of liquids flowing in
a pipeline because pressure is dependent
on flow. Therefore, the proposed control
system is unworkable (Figure 1).
The relationship between flow and pressure
is determined by the pump and system
curves, and the operating pressure (sum of
static head and friction loss) is at the point
where the two curves cross (Figure 2).
Liquids are incompressible, so there is no
dead time between flow and pressure.
Therefore, the cited dead time of 30-45
seconds is in error. Cascade control can’t
be used because the flow and pressure time
constants are nearly identical, while for
good cascade control, the slave must be an
order of magnitude faster than the master.
If you want to save pumping energy, you
can control the speed of the variable-speed
pump using a valve position controller
(VPC). The VPC minimizes the valve pres-
sure drops by opening the valve that is
most open to 90%, all the time. As shown
in Figure 3, if the system was designed, so
that normal operation would require an
average speed of about 50%, you’ll require
only 13% of the horsepower of using a con-
stant speed pump (100% speed in Figure 3).
For a variety of other pump optimization
schemes, read the pump chapter in the 4th
edition of Volume 2 of my handbook.
My recommendation for your system is
shown in Figure 4. Note that I also added
PC
FC
PT
FC
Lowpressure
logic
Transmixfuel Delete
Head
Capacity
Pump head—capacity curve
System head—capacity curveFriction andminor losses
Total statichead
OPERATING POINTFigure 2: The system curve determines the rela-tionship between flow and pressure. The operat-ing pressure will be at the point where the pump (dotted) and the system (solid) curves cross.
AS-PLANNED SYSTEMFigure 1: Delete pressure controls because pres-sure and flow can’t be independently controlled. Once flow is controlled, the pressure is deter-mined by the system.
www.ControlGlobal.com
eHANDBOOK: Flow Measurement, Fall, 2019 11
a pressure safety valve (PSV) to protect your system
against overpressure.
Millions of dollars could be saved in various industrial
applications if all pumping energy costs were minimized
the same way as shown in Figure 4.
Béla Lipták, [email protected]
FIGURE HEADFigure 3: If a valve position controller (VPC) is added, this inde-pendent control loop can keep the most open valve always 90% open by modulating the pump speed. If the pump is oversized, the operating cost savings can be substantial.
F2 F1
Head or pressure
Flow
100% speed
67% speed
P1
P2
Thro
ttled
Unthrottled
RECOMMENDED CONFIGURATIONFigure 4: When optimized, the the valve position controller (VPC) always minimizes the system pressure drop by keeping the most open valve at 90% open.
Transmix fuel
FC FCVPTVPT
VPC
PSV
>
SP: 90%
A: I suggest that you review
the design of the centrifugal
pump. With a given impel-
ler, the pump will pump a
volume of liquid at a given
head at a given speed. If
the pump can’t provide the
required head at a given
speed, then increasing the
rotational speed at the VFD
will increase the head. The
governing law of physics is
the Pump Affinity Law:
1. The flow (GPM) varies pro-
portionally with the change
in speed. This means that
twice the speed is twice the
flow. One-third speed is one-
third the flow.
2. The pump head (pressure)
varies with the square of the
change in the speed. Dou-
bling the speed generates
four times the head. At 80%
speed, the head generated
is 64%.
3. The power requirement
(horsepower or kilowatts)
varies by the cube of the
change in speed. Twice the
speed would consume eight
times the power; half the
speed would require one-
eighth the power to drive
the pump.
www.ControlGlobal.com
eHANDBOOK: Flow Measurement, Fall, 2019 12
A speed change at the pump must imme-
diately appear as a pressure increase at the
flowmeter in this liquid-filled system. The
30- to 45-second delay is just not physically
possible; the pumped liquid has to go some-
where. If the VFD responds to the speed
change properly, the pressure increase
should be instantaneous. Many VFDs have
filters installed on speed change to prevent
too rapid a speed change that might result
in pipe hammer. However, 30-45 seconds
seems out of reason.
In a filled piping system, VFD speed change
will result in an immediate change in flow
rate and pressure head unless a ramping
function is configured or the pipe isn’t filled
with liquid. What you describe isn’t possible
with a filled pipe.
Dick Caro, [email protected]
www.ControlGlobal.com
eHANDBOOK: Flow Measurement, Fall, 2019 13
Accurate, reliable and durable flow measurement in chemical processesOPTIFLUX 5000 series – technology driven by KROHNE• ½ to 12“ Electromagnetic flowmeters with ceramic measuring tube for corrosive
or abrasive fluids
• Vacuum and over pressure resistant, leak proof with fused-in Cermet electrodes
• –40 to +180 °C (–40 to +356 °F) , thermal shock resistant materials
• Hazardous area approved
fact
More facts about the OPTIFLUX 5000: us.krohne.com/optiflux5000
products solutions services
gal/h
ft/sft3/h
°F
Q: I work as a product manager for Emer-
son. In the column on custody transfer
(July ’18, p. 43, www.controlglobal.com/
articles/2018/why-can-a-dp-flowmeter-
be-used-for-gas-but-not-liquid), you
stated that the DP flow turndown on
liquid service is 3:1 to 4:1, and does not
have the ability to compensate for dis-
charge coefficient. Rosemount’s 3051SMV
with Ultra for Flow dynamically compen-
sates for changes in discharge coefficient
22 times per second, and is capable of
±1% of mass flow measurement over a 14:1
turndown on flow.
Ben Goulet, [email protected]
A: My column discussed standard DP cells—
you are right that smart ones provide 200:1
P or 14:1 flow rangeability.
Concerning discharge coefficient compen-
sation, which is provided to correct for gas
expansion, and concerning thermal expan-
sion factors in the DP mass flow equation, it
should be emphasized that the value of nat-
ural gas is a function of its composition and
heating value, and pressure and/or tempera-
ture don’t detect either of them, no matter
how often the calculation is performed.
In addition, the DP cell doesn’t measure
mass flow (nor volumetric flow); it measures
the square root of the pressure differential
across a flow element. Also, the DP cell is
only one component in the flow detection
loop, and therefore it’s misleading to imply
that the DP accuracy and the flow measure-
ment accuracy are the same. They are not.
The flow measurement error is the sum of
Remote control of fractionationCan smart differential pressure (DP) cells be used for custody transfer?
by Béla Lipták
eHANDBOOK: Flow Measurement, Fall, 2019 15
www.ControlGlobal.com
all other loop component errors, including
installation ones.
You say your flow measurement error is
±1% without stating ±1% of what. If you are
claiming a ±1% AR (actual reading) accuracy
at minimum flow (full flow divided by 14),
then you’re claiming that your detector’s
full scale flow accuracy is 1/14 = ±0.071%
FS. If that’s what you claim, that means that
in terms of P, you’re claiming an accuracy
of 1/200 = ±0.005% FS, which is obvi-
ously unrealistic.
On the other hand, if your ±1% flow accu-
racy claim refers to ±1% FS, that error at
minimum flow corresponds to an error
of ±14% AR, which makes the measure-
ment useless.
Béla Lipták, [email protected]
A: Regarding the use of DP flowmeters for
custody transfer, my advice has always
been, don’t. Aside from the fact that
dP flowmeters were never intended for
measuring mass flow, there’s the frequent
error of installation and wear of the orifice,
which doesn’t maintain a sharp edge.
For the ISA CAP course, I teach that an
orifice/DP flowmeter is great for control
purposes, since even when incorrect, it is
consistently incorrect and highly useful for
flow control. I’ve even used orifice/DP for
measuring steam flow in an energy/mass
balance situation on a paper machine, but
that’s far from custody transfer.
However, even with pressure and tempera-
ture compensation, it just isn’t accurate
enough for custody transfer. I recommend
a Coriolis flowmeter, or for some liquids in a
low-flow situation, a positive displacement
pump. In class, I use an example of meter
accuracy vs. tank level measurement for
custody transfer. Only a Coriolis flowmeter
can rival the accuracy of custody transfer
through tank level measurement.
Dick Caro , ISA Life Fellow, [email protected]
www.ControlGlobal.com
eHANDBOOK: Flow Measurement, Fall, 2019 16
Proline 300/500 - Flow measuring technology for the future
• Added value throughout the entire life cycle of your plant, based on decades of experience in safety-related application
• Entirely developed according to SIL (IEC 61508). Maximized plant safety and availability due to unique features – such as webserver, WLAN, WirelessHART, Industrial Ethernet, or Heartbeat Technology with comprehensive diagnostic and verifi cation functions
• Multifunctional transmitters – combinable with all tried-and-tested Promass and Promag sensors
• Seamless system integration via HART, PROFIBUS PA/DP, FOUNDATION Fieldbus, Modbus RS485, EtherNet/IP and PROFINET
We understand you need insightful process information to help you run your plant e� ciently.
You make confi dent decisions backed by process data and a complete portfolio of services and solutions to support you.
Do you want to learn more?www.us.endress.com/proline-simply-clever
MEASURED VALUE+ ADDED VALUE
Axial and centrifugal compressor control
is exceptionally challenging due to the
extraordinary speed and severity of prob-
lems, and the extreme consequences in
terms of plant safety and performance. The
fastest and most dangerous phenomenon
is compressor surge. An axial or centrifugal
compressor can reverse flow in 0.03 sec-
onds, going from a large positive flow to
a large negative flow. Often, the negative
flow is not measurable by flowmeters, leav-
ing the actual situation to your imagination.
If you knew exactly what was happening,
it would be even scarier, motivating you to
seek greater understanding and prevention
of the problems. Presently, we tend to rely
on companies specializing in surge control
to protect you and your plant, but what
happens if something is not quite right in
the middle of the night, causing a surging
fright and piping to take flight?
UNDERSTANDING COMPRESSOR SURGEThe surge point on the compressor map
(typically a plot of compressor pressure rise
versus suction flow) is the point where the
slope of the characteristic curve becomes
zero. Each characteristic curve corresponds
to a particular speed or inlet guide vane
position. The blue plot in Figure 1 shows the
compressor characteristic curve seen and
unseen. Compressor manufacturers often
don’t show the compressor characteristic
curve to the left of the surge point, creating
mystery and vulnerability.
A first-principle model has provided the
knowledge of how negative and positive
Compressor surge controlDeeper understanding and simulation can virtually eliminate instabilities.
by Greg McMillan, Chris Stuart and Thomas Hildebrand
eHANDBOOK: Flow Measurement, Fall, 2019 18
www.ControlGlobal.com
feedback occurs from the
sign and magnitude of
slopes seen and unseen in
the compressor character-
istic curve. The negative
slope of the curve to the
right of the surge point
provides some nega-
tive feedback to help
with stability. As the flow
decreases, the pressure
rise increases, creating a
greater downstream valve
pressure drop and possibly
flow. If the downstream
valve position continues
to decrease, the operating
point proceeds to walk to
the left from point A along
the characteristic curve.
When the operating point
reaches the zero-slope
point, it jumps in about 0.03
seconds to a negative flow,
signifying the beginning of
the surge cycle.
It’s kind of like walking up a
mountain, then falling off a
cliff. The compressor char-
acteristic curve to the left
of the surge point creates
a total characteristic curve
that looks like a sine wave,
as seen in Figure 1. The pos-
itive slope immediately to
the left of the surge point
(maximum compressor
pressure rise) creates pos-
itive feedback that causes
the operating point to jump
from point B to point C, the
start of the negative slope.
The operating point walks
along the negative slope
from C to D, the point of
zero slope (minimum com-
pressor pressure rise), and
then jumps to the right back
to the starting point A. If a
surge valve is not opened,
the process repeats itself,
resulting in oscillations.
Note that the jumps in the
suction flow measurement
between peaks and valleys
are not seen in pressure
measurements due to the
smoothing by suction and
header volumes.
The jumps are highly dis-
ruptive and damaging
due to high axial thrust
and radial vibration. Surge
cycles damage bearings
and decrease efficiency
with each cycle. For axial
compressors, the damage
may be measureable after a
10.0
8.33
6.67
5.00
3.33
1.67
0.00
10.0
8.33
6.67
5.00
3.33
1.67
0.00
Callouts: [note that the outer oval loop is the “path,” the inner S-shaped
Positive slope creates positive feedback that causes flow to jump from B to C and D to A
Characteristic curve stops at zero slope
Curv
e, p
si
Path
, psi
BC
D21
A
-300 -187 -75 37 150 262 375 487 600acfm
SURGE AS SEEN AND UNSEENFigure 1: At point B, where the compressor characteristic curve slope is zero, the operating point jumps to point C. The precipi-tous drop in pressure signals the start of the surge cycle and flow reversal (negative ACFM). As the plenum volume is emptied, the operating point follows the curve from point C to point D, where the slope is again zero, and then jumps to point A.
www.ControlGlobal.com
eHANDBOOK: Flow Measurement, Fall, 2019 19
few surge cycles. The total
number of surge cycles
provides a good metric of
the total loss in compressor
efficiency. It is imperative
to prevent the surge and
ensure sustained recovery.
SURGE SETPOINTThe surge controller set-
point should be offset to
the right of the surge curve
on the compressor map,
as shown in Figure 2. If the
surge setpoint follows the
shape of surge curve, the
offset can be optimized to
be on the longitudinal axis
of the efficiency ellipses.
The size of the offset
depends on the speed of
the automation system and
the tuning of the surge con-
troller. Some plants may
think of the surge curve as
being the point where the
surge valve opens. In this
case, integral action must
be greater than the pro-
portional action. However,
the extra integral action
causes a larger overshoot of
the surge setpoint, neces-
sitating the setpoint offset
to be increased accord-
ingly, which generally
corresponds to lower oper-
ating efficiency.
Most other plants see the
surge setpoint as being
the best operating point,
when surge valves are open
through tuning so that pro-
portional action dominates
integral action, preventing
overshoot. Using higher
controller gain rather than
a lower reset time gives a
faster correction. Whether
an automation system
can achieve this depends
on attention to the surge
valve’s 86% response time,
transmitter update rate
and damping setting, and
controller scan time and
execution rate. In general,
the summation of the valve
response time, transmitter
damping and ½ of each
update rate, scan time and
execution rate must be less
than 2 seconds. For closer
operation to the surge
curve and to reduce dire
consequences from surge,
the total must be less than
[if you can label all three lines with one “speed”, then just 60%, 80%, 100%]
Pres
sure
rise
, psi
Long
axis Efficiency
ellipses80%60%
Surg
e cur
ve
Contr
oller s
etpoin
t 100% speed
80% speed
60% speed
Inlet flow, acfm
EFFICIENT EVASIONFigure 2: The optimum surge setpoint follows the shape of the surge curve with an offset to intersect longitudinal efficiency el-lipses. The offset is large enough to prevent surge.
www.ControlGlobal.com
eHANDBOOK: Flow Measurement, Fall, 2019 20
1 second. How fast the automation system
really needs to be and the required tuning
of the surge controller is best determined
by running a first-principle dynamic model
that includes a momentum balance as well
as material and energy balances. A word
of caution here is that some I/O scan rates
may be much slower than the fastest con-
troller execution rate.
SURGE CONTROL SYSTEMEven a fast feedback controller is unable
to get a compressor out of severe surge
because of the huge jumps in flow. What’s
needed is an open-loop backup that forces
the surge valves to immediately open,
and holds them open for sufficient time
to sustain operating point stability before
allowing the feedback controller to start
to close the surge valves. The open-loop
backup is triggered by a large predicted
overshoot of the surge setpoint to prevent
surge, or a precipitous drop in flow indicat-
ing an actual surge.
An innovation uses a predicted overshoot
via a fast future value that’s generated by
the rate of change of a decreasing flow,
with a good signal-to-noise ratio multiplied
by the total loop dead time, with updates
every controller execution. The open-loop
backup simply puts the feedback controller
into a remote output mode that is seen by
operator. The remote output is immedi-
ately stepped up to a position that typically
prevents surge, but is incremented every
execution until the future value stabilizes,
putting the surge controller bumplessly
back in cascade with the surge setpoint
computed to sustain an offset from the
surge curve. Many suppliers of standalone
compressor controllers have proprietary
control strategies providing feedback
control, with a backup requiring special
expertise and tuning.
External-reset feedback (ERF), also known
as dynamic reset limit, in the surge con-
troller, with a fast readback of actual valve
position, enables up and down setpoint rate
limits in the analog output blocks to provide
fast opening and slow closing of the surge
valves without the need to retune the surge
controller. ERF can also eliminate oscilla-
tions from valve resolution and sensitivity
limits (as seen in the Control feature article,
“How to specify valves and positioners that
don’t compromise control,” March ’16, p.
39, www.controlglobal.com/articles/2016/
how-to-specify-valves-and-positioners-that-
dont-compromise-control).
The surge control system principles are
basically the same for surge vent valves
and surge recycle valves. At least two
valves in parallel are used to provide
redundancy, particularly since surge valves
might not open after sustained operation
in closed position, where stiction from seal
or seat friction is greatest. For multiple
stages, there are generally recycle surge
valves and a compressor surge control
www.ControlGlobal.com
eHANDBOOK: Flow Measurement, Fall, 2019 21
system for each stage. Ratio dividing may
be used to proportion the different pres-
sure rises for each stage.
Figure 3 shows the surge control system
with recycle surge valves and two down-
stream users feeding reactors. Many
systems have more reactors. A valve posi-
tion controller can minimize the pressure
setpoint to increase compressor efficiency
by pushing a user valve to the maximum
effective throttle position (e.g., 60%). The
valve position controller has external reset
feedback with setpoint rate limits on the
compressor pressure controller to provide
a gradual, smooth optimization with a fast
getaway for a disruption.
Not shown in Figure 3 is feedforward action
to deal with the fast closing of user valves.
What may seem to be a slow enough clos-
ing of a user valve can be troublesome
because of the quick opening character-
istic of on-off valves triggered by safety
Suction
RecycleW
BY1-1
ZC1-4
ZY1-4
DY1-1
SC1-2
FC2-2
FC2-1
FT2-2
PC1-3
FC1-1
ST1-2
FT1-1
FY1-1
DPT1-1
PY1-1a
PY1-1b
PT1-3
FT2-1
Openloop
backup ROUT
Maximumfeed valveposition
Derivativeof flow
Steam
Driver CompressorDischarge
Hi signalselector
Reactor 2feed
Reactor 1feed
Furthestopen valve
positionSP
SP
SP
SP
OPEN LOOP BACKUP AND OPTIMIZATIONFigure 3: The surge flow controller FC1-1 and enhanced PID valve position controller ZC1-4 have ex-ternal reset feedback for directional move suppression for fast opening with slow closing of surge valves for fast getaway in abnormal situations and gradual optimization. The derivative of the suction flow computed by DY1-1 uses a deadtime block to provide immediate updates. This derivative can be multiplied by the deadtime and added to the current suction flow to predict flow one deadtime into the future. Each reactor feed valve position can be used to provide a feedforward signal.
www.ControlGlobal.com
eHANDBOOK: Flow Measurement, Fall, 2019 22
instrumented systems, where nearly all of
the flow change occurs within 10% of closed
position. The feedback and feedforward
signals must be linearized based on the
installed flow characteristics of the surge
valves and user valves, respectively. If a
high-rangeability, fast and reliable user flow
measurement is used for the feedforward,
the characterization of the feedforward
signal for the feedforward summer is unnec-
essary. Much more detail, with a focus on
practical essentials, is offered in the book
Centrifugal and Axial Compressor Con-
trol (www.momentumpress.net/books/
centrifugal-and-axial-compressor-control).
In Figure 3, the derivative of the suction
flow computed by DY1-1 uses a deadtime
block to provide immediate updates with
good signal-to-noise ratio. This derivative
can be multiplied by the deadtime and
added to the current suction flow to give
a predicted flow one deadtime into the
future. This plus reactor feed valve position
can be used to provide a feedforward signal
to help surge control deal with user (i.e.
reactor) shutdown.
The same type of calculation used to
give a future value can be used to find
and document surge points on the surge
curve on the compressor map. Detecting
a nearly zero rate of change in pressure
for a change in suction flow indicates a
surge point. Detecting a severe rate of
change of suction flow indicates a surge
cycle, with extreme negative rate of
change signifying the beginning and an
extreme positive rate of change signify-
ing the end of each surge cycle. Future
values can be computed with a good
signal-to-noise ratio and preemptive cor-
rections (as noted in the Control Talk blog,
“Future PV values are the future,” www.
controlglobal.com/blogs/controltalkblog/
future-pv-values-are-the-future).
COMPRESSOR MODELDeeper understanding of compressor surge
control, the dynamic requirements of the
automation system, setpoint optimization,
surge control system design with future
values, and surge curve identification is
best achieved by using a virtual plant
(digital twin) with a complete compressor
model. This digital twin can generate all
of the plots in this article and give much
more. This knowledge is nearly impossi-
ble to obtain elsewhere, and is essential
for preventing compressor damage, loss
of compressor efficiency, shutdowns and
hazardous operation of downstream exo-
thermic reactors.
The compressor models seen in indus-
try to date critically lack the momentum
balance needed to show the path, and
to include the normally unseen compres-
sor characteristic curve to the left of the
surge point. The momentum balance inte-
grated into the digital twin, which is the
basis of this article, is developed from
www.ControlGlobal.com
eHANDBOOK: Flow Measurement, Fall, 2019 23
innovative research documented by E. M.
Greitzer in “The Stability of Pumping Sys-
tems—The 1980 Freeman Scholar Lecture”
(Journal of Fluids Engineering, June ’81,
p. 193–242) and subsequently confirmed
through testing by K.E. Hansen et al. in
“Experimental and Theoretical Study of
Surge in a Small Centrifugal Compressor”
(Journal of Fluids Engineering, September
1981, p. 391–395).
The surge model results and automation
system requirements are also described in
the previously mentioned book, Centrifugal
and Axial Compressor Control. Additional
guidance and a video demonstration are
at www.controlglobal.com/articles/2018/
compressor-control-resources.
Invest some of your own time to see the
future of a synergy between modeling and
control. Use the model to learn what’s truly
important and what’s really needed. Don’t
take a back seat, but instead, seek to pro-
vide the leadership to show what you and
our profession can do to make plants safer
and more productive.
Greg McMillan is a Control columnist, Hall of Fame
member and ISA Lifetime Achievement Award recipient.
Chris Stuart, software engineer, R&D/Engineering and
Thomas Hildebrand, simulation engineer 1, Systems/
Project Engineering at Emerson Automation Solutions
can be reached at [email protected] and
www.ControlGlobal.com
eHANDBOOK: Flow Measurement, Fall, 2019 24