Refer to figures 1, 2 and 3 for details of opening preparation and fire damper installations in wood stud and steel stud 1 hr. and 2 hr. rated walls. See notes 2 and 3 for joint detail. Damper shall be secured to sleeve with # 10 sheet metal screws 6" on center, 1/4" diameter nuts and bolts, welding, 3/16" steel pop rivets or clinching (toggle). Angles shall be a minimum of 1-1/2" x 1-1/2" x 16 gauge and may be of a unit type construction. Fasten to sleeve with 1/4" diameter nuts and bolts, welding 8" on center, # 8 sheet metal screws 8" on center, or 3/16" steel pop rivets. (See NOTE 4 for clearance and overlap). NOTES 1. Sleeves shall be of the SAME GAUGE or heavier as the duct to which it is attached. Gauges shall conform to SMACNA or ASHRAE duct standards. Collars shall extend approximately 3" on either side of wall or floor to facilitate the joining of the collar to the duct. In cases where the width of the retaining angle is such that it would inhibit joining the collar to the duct, the collar may extend approximately 2" beyond the edge of the angles. See Note 3. 2. The following duct-sleeve connections may be used on all systems. • Inside slip • Angle slip • Plain “S” slip • Double “S” slip • Hemmed “S” slip • Cup slip • Bar slip• Drive slip • Alternate bar slip (standing slip) • Pocket lock • Reinforced bar slip (cleat) Refer to separate “Breakaway Connection” sheet for further information. 2 A. Duct-sleeve connections may be of the rigid or fixed type when fire dampers are installed in sleeves that are 16 ga. up to 36" W x 24" H or 14 ga. for size exceeding 36" W x 24" H. 3. When the duct work terminates at the damper, retaining angles on the opposite side of the opening may be reversed providing the size of the opening is increased by an amount equal to twice the combined thickness of the angle and the height of the screw or bolthead to maintain expansion clearance. (See NOTE 4) In this case the collar at the open end may be made flush with the edge of the retaining angle. 4. Clearance between the sleeve and wall/floor opening shall be a maximum 1/8" per foot on height and width of sleeve to a maximum of 1-1/2" (e.g. damper 47-3/4" x 47-3/4", collar 48" x 48", opening 49-1/2" x 49-1/2". Minimum clearance shall be 1/4”. Perimeter angles shall overlap the wall/floor by a minimum of 1". 5. As with all joints, contractor must seal duct-collar connection in field, after installation. IMPORTANT Do Not Cast Damper In Place Do Not Fasten Retaining Angles Or Damper Directly To Wall Cycle Damper After Installation To Insure Free Movement Do Not Install Damper Out Of Square Or Out Of Flat Install Damper In Plane Of Fire Separation INSTALLATION INSTRUCTIONS FOR FIRE DAMPERS IN DRYWALL TYPE CONSTRUCTION 1 HOUR AND 2 HOUR RATED FIRE AND CEILING RADIATION DAMPERS UL CLASSIFIED (SEE COMPLETE MARKING ON PRODUCT) WALL COLLAR (SLEEVE) DUCT TYPE-A VERTICAL MOUNTING COLLAR (SLEEVE) DUCT TYPE-B VERTICAL MOUNTING COLLAR (SLEEVE) DUCT TYPE-C VERTICAL MOUNTING

Upload: abidch143

Post on 26-Oct-2014

48 views

Category:

Documents


2 download

TRANSCRIPT

Page 1: Fire Damper

Refertofigures1,2and3fordetailsofopening preparationandfiredamperinstallationsinwood studandsteelstud1hr.and2hr.ratedwalls.

Seenotes2and3forjointdetail.

Dampershallbesecuredtosleevewith#10sheetmetalscrews6"oncenter,1/4"diameternutsandbolts,welding,3/16"steelpoprivetsorclinching(toggle).

Anglesshallbeaminimumof1-1/2"x1-1/2"x16gaugeandmaybeofa unittypeconstruction.

Fastentosleevewith1/4"diameternutsandbolts,welding8"oncenter,#8sheetmetalscrews8"oncenter,or3/16"steelpoprivets.(SeeNOTE 4forclearanceandoverlap).

NOTES1. Sleeves shall be of the SAMEGAUGE or heavier as the duct towhich it is attached.Gauges shall conform toSMACNAorASHRAEduct standards.Collars shallextendapproximately3"oneithersideofwallorfloortofacilitatethejoining of thecollartotheduct. Incaseswherethewidthoftheretainingangle issuch thatitwouldinhibitjoiningthecollartotheduct,thecollarmayextendapproximately 2"beyondtheedgeoftheangles.SeeNote3.

2. Thefollowingduct-sleeveconnectionsmaybeusedonallsystems. •Insideslip •Angleslip •Plain“S”slip •Double“S”slip •Hemmed“S”slip •Cupslip •Barslip•Driveslip •Alternatebarslip(standingslip) •Pocketlock •Reinforcedbarslip(cleat)

Refertoseparate“BreakawayConnection”sheetforfurtherinformation.

2A.Duct-sleeveconnectionsmaybeoftherigidorfixedtypewhenfiredampersare installedin sleeves that are 16 ga. up to 36"W x 24" H or 14 ga. for size exceeding36"Wx24"H.

3. Whentheductworkterminatesatthedamper,retaininganglesontheoppositeside oftheopeningmaybereversedprovidingthesizeoftheopeningisincreasedby anamountequaltotwicethecombinedthicknessoftheangleandtheheightofthe screworboltheadtomaintainexpansionclearance.(SeeNOTE 4)Inthiscasethe collarattheopenendmaybemadeflushwiththeedgeoftheretainingangle.

4. Clearancebetweenthesleeveandwall/flooropeningshallbeamaximum1/8"per footonheightandwidthofsleevetoamaximumof1-1/2"(e.g.damper47-3/4"x 47-3/4",collar48"x48",opening49-1/2"x49-1/2".Minimumclearanceshallbe 1/4”.Perimeteranglesshalloverlapthewall/floorbyaminimumof1".

5. As with all joints, contractormust seal duct-collar connection in field, after installation.

IMPORTANTDoNotCastDamperInPlaceDoNotFastenRetainingAnglesOrDamperDirectlyToWallCycleDamperAfterInstallationToInsureFreeMovementDoNotInstallDamperOutOfSquareOrOutOfFlatInstallDamperInPlaneOfFireSeparation

INSTALLATION INSTRUCTIONS FOR FIRE DAMPERS

INDRYWALLTYPECONSTRUCTION1HOURAND2HOURRATEDFIRE AND CEILING RADIATION DAMPERS

ULCLASSIFIED(SEECOMPLETEMARKINGONPRODUCT)

WALL

COLLAR(SLEEVE)

DUCT

TYPE-AVERTICALMOUNTING

COLLAR(SLEEVE)

DUCT

TYPE-BVERTICALMOUNTING

COLLAR(SLEEVE)

DUCT

TYPE-CVERTICALMOUNTING

ABID G
Highlight
Page 2: Fire Damper

DETAIL OF OPENING PREPARATION AND FIRE DAMPER INSTALLATIONWALL RATING - 1 HR.

FIG. 1

2

NOTE:THE RETAINING ANGLES ONBOTH SIDES OF THE FIREDAMPER MAY BE INVERTEDIN ORDER TOACCOMODATEAREGISTERORGRILLE.SEEFIG.2

2-1/2"STUDORRUNNER

1/2"GYPSUMWALLBOARD

RETAININGANGLE

DAMPERSLEEVE

FIREDAMPER

DUCT

1/2"THICKFILLERPIECES-2-1/2"WIDETOBEINSTALLEDAROUNDENTIREOPENING-SCREWED12"O.C.TOWEBOFRUNNERSANDSTUDS.NOTE:REQUIREDFORWOODSTUDTYPECONSTRUCTIONONLY.

Page 3: Fire Damper

FIG. 2

DETAIL OF OPENING PREPARATION AND FIRE DAMPER INSTALLATIONWALL RATING - 2 HR.

3

NOTE:THE RETAINING ANGLES ONBOTH SIDES OF THE FIREDAMPER MAY BE INVERTEDIN ORDER TOACCOMODATEAREGISTERORGRILLE.

2-1/2"STUDORRUNNER

1/2"GYPSUMWALLBOARD

RETAININGANGLE

DAMPERSLEEVE

FIREDAMPER

DUCT

1/2"THICKFILLERPIECES-2-1/2"WIDETOBEINSTALLEDAROUNDENTIREOPENING-SCREWED12"O.C.TOWEBOFRUNNERSANDSTUDS.NOTE:REQUIREDFORWOODSTUDTYPECONSTRUCTIONONLY.

Page 4: Fire Damper

METAL OR WOOD STUD FRAMING FOR FIRE DAMPERSIN WALLBOARD PARTITIONS

NOTE: GypsumWallboardscrewedtoallstudandrunnerflanges.12”O.C.maximum,surroundingopening

Litho in U.S.A.©2011Metal-Fab,Inc.FormNo.L1746-11/11

88814

MAXIMUM SIZE TABLE

MODELSingle Section Multiple Section

Vertical Horizontal Vertical HorizontalMax. Width Max. Height Max. Width Max. Height Max. Width Max. Height Max. Width Max. Height

MFD 60 60 40 40 120 120 80 40MFD3 48 48 40 40 - - 80 40MDFD 36 36 18 18 - - 36 36MDFD3 36 36 18 18 - - 36 36MFDS 48 48 48 48 - - - -MFDS3 48 48 48 48 - - - -MDFDS 36 36 18 18 - - 36 36MDFDS3 36 36 18 18 - - 36 36MFDUS 48 48 - - - - - -MFDUS3 48 48 - - - - - -

NOTE: Formaximumsinglesectionsizesrefertomaximumsizetable.Foropeningslargerthangivenforsinglesection,multipledampersarerequired.Foropeningslargerthangiveninmultiplesectionsa12”widebrickorreinforcedmullionmustbeprovidedbetweenadjacentassemblies.

FIG. 3FLOORRUNNER

2EACHPANHEADSCREWS

RUNNER90°BEND

16"

A A

16"24"ONCENTER

12"

97-1/2"MAXIMUM

109-1/2"MAXIMUM

2"

2"

CEILINGRUNNER

SCREWS

SECTION"A-A"

2-1/2"STUDS

SCREWS

2-1/2"RUNNER

NOTE:DOUBLESTUDDINGMUSTBEUSEDONTHEVERTICALSIDESOFTHEOPENING.NOTREQUIREDONOPENINGS36"X36"ORSMALLER.