Page 1: Fire damper actuators. Selection and integration. · damper • 3 LEDs for indicating operating statuses and faults • Function test of fire damper actuator • Potential-free auxiliary

Fire damper actuators.Selection and integration.

Page 2: Fire damper actuators. Selection and integration. · damper • 3 LEDs for indicating operating statuses and faults • Function test of fire damper actuator • Potential-free auxiliary

2

Motorised fire dampers are shut-off devices that

prevent fire and smoke from spreading through

ventilation systems. In the event of a fire, they

protect people and tangible assets.

Fire dampers are equipped with a thermoelectric

tripping device. To prevent smoke from spreading,

they can also be triggered by smoke detectors.

They are powered by Belimo fire safety actuators.

Page 3: Fire damper actuators. Selection and integration. · damper • 3 LEDs for indicating operating statuses and faults • Function test of fire damper actuator • Potential-free auxiliary

3

Belimo supplies cost-effective and easy-to-integrate solutions for the motorisation of fire dampers.

Proven product range.Simple motorisation solutions.

Belimo safety actuators

for fire dampers

Type BLF... BF... BFG...

Torque 6 Nm4 Nm

18 Nm12 Nm

11 Nm8.5 Nm

Dimensioning:AC / DC 24 VAC 230 V

7 VA7 VA

10 VA11 VA

10 VA11 VA

Angle of rotation 95° 95° 180°

Running time 40...75 s< 20 s

< 120 s< 16 s

< 120 s< 20 s

Damper rotation / form fit 12 mm (8/10 mm possible) 12 mm (10 mm possible) 10 mm

Triggering:• thermal (-T)• as option via smoke detector

M

5¡� TABLEAU

1 32

M

5¡� TABLEAU

1 32

M

5¡� TABLEAU

1 32

M

5¡� TABLEAU

1 32

Page 4: Fire damper actuators. Selection and integration. · damper • 3 LEDs for indicating operating statuses and faults • Function test of fire damper actuator • Potential-free auxiliary

4

Conventional and digital control and monitoring.

Conventional control with position feedback

Control and monitoring via SBS-Control

4- to 6-wire(feedback open/closed provided by auxiliary switches)

2-wire(control and feedback)

2-wire(control and feedback)

2

2

2-wire (control open-close)

Au

tom

ati

on

sta

tio

nD

DC

/ p

rog

ram

ma

ble

co

ntr

olle

rA

uto

ma

tio

n s

tati

on

DD

C /

pro

gra

mm

ab

le c

on

tro

ller

up to 9 fire dampers

*

*

*

* Optional: smoke detector with potential-free contact

Page 5: Fire damper actuators. Selection and integration. · damper • 3 LEDs for indicating operating statuses and faults • Function test of fire damper actuator • Potential-free auxiliary

5

Conventional and digital control and monitoring.

Connection to control cabinet Actuator types

•Cablesformotorandauxiliaryswitcheswireddirectlytocontrolcabinet.

• For24 Vactuators,thevoltagedropoverlonglinesshouldbenoted.Thevoltageatthe

actuator must be within the tolerance stated in the data sheet.

• Feedbackofdamperpositionbymeansofauxiliaryswitches.

BLF24-T, BLF230-T

BLF24, BLF230

BF24-T, BF230-T

BF24, BF230

BFG24-T, BFG230-T

BFG24, BFG230

Connection to automation station Sensors Actuator types

Communication and control unit

BKS24-1B and plug socket ZSO-11

• Forcontrollingandmonitoringofafire

damper

• 3LEDsforindicatingoperatingstatuses

and faults

• Functiontestoffiredamperactuator

•Potential-freeauxiliary

contacts for integration

into system

Communication and

power supply unit

BKN230-24

•Decentralisedpower

supply unit for 24 V fire

damper actuators

• Localpowersupply

AC 230 V

• IntegratedLEDstatus

indicator

•Connectionforasmoke

detector contact and/or

a thermoelectric tripping

device

-T

Smoke

detector

(optional)

BLF24-T-ST

BLF24-ST

BF24-T-ST

BF24-ST

BFG24-T-ST

BFG24-ST

Communication and control unit

BKS24-9A

•Controlsandmonitorsupto9fire

dampers

• LEDstatusdisplayindicatingoperating

statuses and fault messages

• Functiontestoffiredamperactuators

•Potential-freeauxiliarycontactsfor

integration into system

• Zonecontrol,summarisedalarms

Page 6: Fire damper actuators. Selection and integration. · damper • 3 LEDs for indicating operating statuses and faults • Function test of fire damper actuator • Potential-free auxiliary

66

Connection

To Modbus RTU via Belimo field unit BKN230-24-MOD

To Modbus RTU or BACnet MS/TP via MP-Bus® and Belimo Gateways

To various protocols via MP-Bus® and DDC controller

To LonWorks® via gateway from third-party manufacturer**

** Support for gateway is provided by third-party manufacturer

* Optional: smoke detector with potential-free contact Eth

ern

et

/ B

AC

ne

t /

Pro

fib

us

etc

.LonW

orks

®

1...8 dampers

* *

DDC

* Optional: smoke detector with potential-free contact

Mo

db

us

RT

U

1...64 dampers

**

* Optional: smoke detector with potential-free contact Mo

db

us

RT

U /

BA

Cn

et

1...8 dampers

**

Control and monitoringvia communicative bus solutions.

Page 7: Fire damper actuators. Selection and integration. · damper • 3 LEDs for indicating operating statuses and faults • Function test of fire damper actuator • Potential-free auxiliary

7

Control and monitoringvia communicative bus solutions.

7

Gateways Connection modules Sensors Actuator types

-T

Smoke

detector

(optional)

BLF24-T-ST

BLF24-ST

BF24-T-ST

BF24-ST

BFG24-T-ST

BFG24-ST

Belimo UK24BAC / UK24MOD

• InterfacetoBACnetMS/TPorto

ModbusRTU

•Connectionofupto8firedamper

actuators

•Summaryordetailedfault

message for each

fire damper

DDC controller with MP interface

•BelimoprovidestheMPspecifications

toallmanufacturersofDDCcontrollers.

Theycanusethesespecificationsto

implement own hardware/software

design into their devices.

Direct connection to gateway

• e.g.LonWorks® gateway

•Starwiringoffiredamperactuators

* BLF24-T, BLF230-T

* BF24-T, BF230-T

* BFG24-T, BFG230-T

*Dependingonthegateway, actuators with plugs can also beused(..-ST)

Communication and

power supply unit

BKN230-24-MOD

•InterfacetoModbusRTU

•Baudrateupto76'800Bd

•Terminationcanbeswitched

•Parametrisation

adjustable

viaDILswitch

Communication and

power supply unit

BKN230-24-C-MP

• InterfacetoMP-Bus

•Decentralisedpower

supply unit for 24 V fire

damper actuators

• Localpowersupply

AC 230 V

• IntegratedLEDstatus

indicator

•Connectionforasmoke

detector contact and/or a

thermoelectric tripping

device

Page 8: Fire damper actuators. Selection and integration. · damper • 3 LEDs for indicating operating statuses and faults • Function test of fire damper actuator • Potential-free auxiliary

Belimo worldwide: www.belimo.com

Head office

BELIMOAutomationAG

Brunnenbachstrasse 1

CH-8340Hinwil,Switzerland

Tel. +41438436111

Fax+41438436268

[email protected]

ENG–05.20

13–0.5M–Prin

tedinSwitzerland

–DEDruck

–Sub

jecttoch

ange

sCon

ceptand

des

ign:ago

rag

,Zurich

5-year warranty

On site around the globe

A complete range of products from one source

Testedquality

Short delivery times

Comprehensive support

Korr2013_