University of Houston Mechanical Engineering Department N207 Engineering Building 1 Houston, TX 77204 May 3, 2015 Dr. Richard Bannerot University of Houston 4800 Calhoun Rd Houston, TX 77004 Dear Dr. Bannerot: I am submitting the attached final technical report entitled Microchannel Heat Exchanger Flow Loop. This report contains the results of the construction and validation of a microchannel heat exchanger flow loop suitable for use in the thermal fluids lab at the University of Houston. Computing power is increasing at an exponential rate and modern cooling methods are becoming increasingly insufficient as the number of transistors per unit area substantially increases the heat produced by the system. In order to mitigate this problem, water is becoming a necessary replacement for air as a convection agent due to its higher convection coefficient and therefore increased ability to remove heat. The flow loop described within this report will serve as an experimental gateway for students in the thermal fluids lab to learn applications of their fluids and heat transfer coursework related to a new, lucrative technology. The flow loop was constructed and manuals for two labs, as well as a manual for general operation were completed so that students can conduct the enclosed experiments and analyze the system with the amount of heat removed from the heat exchanger. Hopefully, this report will educate students and generate future studies into effective methods of heat 1

Upload: jeremy-evans

Post on 11-Apr-2017

338 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: Final Technical Report

University of Houston Mechanical Engineering Department

N207 Engineering Building 1

Houston, TX 77204

May 3, 2015

Dr. Richard BannerotUniversity of Houston4800 Calhoun RdHouston, TX 77004

Dear Dr. Bannerot:

I am submitting the attached final technical report entitled Microchannel Heat Exchanger Flow Loop.

This report contains the results of the construction and validation of a microchannel heat exchanger flow loop suitable for use in the thermal fluids lab at the University of Houston. Computing power is increasing at an exponential rate and modern cooling methods are becoming increasingly insufficient as the number of transistors per unit area substantially increases the heat produced by the system. In order to mitigate this problem, water is becoming a necessary replacement for air as a convection agent due to its higher convection coefficient and therefore increased ability to remove heat. The flow loop described within this report will serve as an experimental gateway for students in the thermal fluids lab to learn applications of their fluids and heat transfer coursework related to a new, lucrative technology. The flow loop was constructed and manuals for two labs, as well as a manual for general operation were completed so that students can conduct the enclosed experiments and analyze the system with the amount of heat removed from the heat exchanger.

Hopefully, this report will educate students and generate future studies into effective methods of heat dissipation so that the next era of technological advancement may come to fruition.

Sincerely,

Jeremy Evans, Olivia Pacheco, Michael Russo, John-Roland EspinosaTeam 16 MECE 4341

Attached: Microchannel Heat Exchanger Flow Loop

1

Page 2: Final Technical Report

Microchannel Heat Exchanger Flow Loop

FINAL TECHNICAL REPORT

FOR

Department of Mechanical Engineering

Project Advisor: Dr. Dong Liu

Team Number 16

Team Members:John-Roland Espinosa

Jeremy EvansOlivia PachecoMichael Russo

MECE 4341: ME Capstone IIDepartment of Mechanical Engineering

University of Houston

2

Page 3: Final Technical Report

Abstract

This document is a technical report for the design and construction of a

microchannel heat exchanger flow loop for the cooling of electronic components. It was

prepared by Team 16 for the senior capstone project for MECE 4341. The design,

construction and testing of the finished project was completed on time and the results

have been validated and approved by Dr. Dong Liu. Based on testing of the flow loop,

the microchannel heat exchanger is an effective tool for removing heat from sources that

produce high heat fluxes such as those from modern integrated circuits. Experiments

were run to compare the measured Nusselt number and friction factor data to their

theoretical values and it was shown that the measured values were close to those

predicted. After construction and testing of the flow loop, Dr. Liu reviewed the flow loop

and experimental data and gave his approval of the results, thus validating the project.

Microchannel heat sinks are proving to be a viable option for the cooling of modern

electronic components. The project will be used by future mechanical engineering

students in MECE 4371 to learn micro scale applications of their fluids and thermal

knowledge from MECE undergraduate coursework. This project will demonstrate an

emerging field in research in thermal management of modern integrated circuits while

reiterating fundamental concepts of heat transfer and fluid mechanics.

3

Page 4: Final Technical Report

ContentsIntroduction.................................................................................................................................................................... 4

Statement of Work....................................................................................................................................................... 6

Accomplishments.........................................................................................................................................................6

Methodology.................................................................................................................................................................. 7

Process.............................................................................................................................................................................. 9

Constraints....................................................................................................................................................................13

Standards.......................................................................................................................................................................15

Results........................................................................................................................................................................... 16

Conclusion....................................................................................................................................................................22

Recommendations..................................................................................................................................................... 23

Appendix A – Friction Factor Experiment........................................................................................................24

Appendix B – Nusselt Number Experiment.....................................................................................................30

Appendix C – Flow Loop Operational Manual...............................................................................................36

4

Page 5: Final Technical Report

IntroductionThis document is a technical report for the design and construction of a

microchannel heat exchanger flow loop for the cooling of electronic components. It has

been prepared by Team 16 for the senior capstone project for MECE 4341.The sponsor

for this project is the mechanical engineering department and the advisor is Dr. Dong Liu.

The results of this project will be used by future mechanical engineering students at the

University of Houston for the MECE 4371 lab. This project addresses the problems

associated with the large amounts of heat generated by integrated circuits (ICs) in modern

computers. A microchannel heat exchanger was used to remove heat from ICs and keep

the temperature of the electronics at an acceptable level. A coolant flow loop was used to

circulate coolant through the microchannels of the heat exchanger and cause convection

to occur within the channels to remove heat. Parameters such as flow rate and heat flux

were determined to simulate the heat flux produced by a modern IC. Parts were designed

and fabricated to complete the coolant flow loop and to cover the micro-channels,

ensuring that there is no fluid communication between the channels. Planning for this

project began in August 2014 and construction and testing of the flow loop was

completed in April 2015.

According to Moore's law, the number of transistors on a two square centimeter

IC doubles approximately every two years as shown in Figure 1. As transistors in ICs get

smaller, the heat produced per unit area increases on the silicon chip in which the IC is

etched. When the temperature of the circuit components increases past a certain limit the

performance of the IC suffers. Proper thermal management is needed to keep the

components of ICs at an acceptable temperature to maintain optimal processor and

5

Page 6: Final Technical Report

computer performance. Thermal flux, q’’, is related to the surface temperature, Ts, and

the external temperature, T∞, as shown in Equation 1. Microchannel heat exchangers

allow engineers to obtain large values of the heat transfer coefficient, h, without losing

surface area due to the large number of microchannels that are etched into the surface of

the heat exchanger. Micro-channel heat exchangers can be fabricated using micro-

electrical-mechanical-systems (MEMS) machining techniques and are a viable option for

thermal management in future ICs.

Figure 1: Moore's law demonstrating transistor density as a function of time.

http://home.fnal.gov/~carrigan/pillars/web_Moores_law.htm

q ' '=h(T s−T ∞) Equation 1

6

Page 7: Final Technical Report

Statement of WorkTeam 16 designed, fabricated and tested a coolant flow loop containing a micro-

channel heat exchanger for use in MECE 4371 at UH as specified by Dr. Liu. The flow

loop and recorded data were then reviewed by Dr. Liu for validation of the project.

AccomplishmentsTeam 16 successfully completed all milestones set at the beginning of the

academic year. The first important accomplishment was component fabrication and

procurement which was completed over the course of a couple of months. The first major

shipment arrived in early March and included the stainless steel cart, reservoir,

thermocouples, pressure transducers, piping, G10 material and heat cartridges. All

necessary components that could not be found at a local hardware store were procured

before April. Sealants, braces, bolts, nuts and washers were purchased as needed. Not all

components were initially known and thus Team 16 required multiple trips to local

hardware stores.

After receiving all of the aforementioned components, Team 16 completed the

flow loop on April 18th. The flow loop and the data that it produced were inspected and

approved by the advisor, Dr. Liu, on April 28th. The advisor made several

recommendations for future work on the project that will be addressed by Team 16.

The final written deliverables were completed on time and accepted by the

advisor, including two lab manuals and one operational safety manual. The first lab

verifies that the friction factor varies linearly with the Reynolds number for developing

laminar flow. The second lab shows that Nusselt number varies linearly with the

Reynolds number under the same conditions. The operational manual provides

7

Page 8: Final Technical Report

information about the flow loop lay out and components, as well as operational

instructions required to run the flow loop safely while minimizing experimental error

without risking damage to the components.

MethodologyAfter determining the requirements and nature of the project, Team 16 began with

thorough research on the topic of microchannel heat exchangers by consulting the

internet, prior MECE coursework and Dr. Dong Liu’s thesis. A review of internal flow

convection problems in heat exchangers was completed. This included the Nusselt

Number and friction factor relations compared to the Reynolds number. Dr. Liu’s

doctorate thesis was closely analyzed in order to further inform the direction of the

project.

At the completion of the initial project research, the main components to complete

the flow loop were determined to be as follows: a stainless steel reservoir, a variable

drive gear pump, a 7 micron filter, a rotameter, the microchannel heat exchanger and

assembly as provided by Dr. Liu, a liquid to liquid heat exchanger, thermocouples,

pressure transducers, a data acquisition system and ¼ inch stainless steel piping with

ferrule tube fittings. The necessary specifications were calculated for the pump and heat

cartridges to remove an approximate 100 watts per square centimeter from the

microchannel heat exchanger to simulate a modern IC. The components were tested as

they were received to ensure proper function. With all components received and in

working order, the flow loop was then constructed in a methodical and careful manner.

The layout was determined such that the bending in the piping and the height variation

were minimized while all flow loop components were contained on the top tier of a

8

Page 9: Final Technical Report

stainless steel cart and all the electronics and electrical components were contained on the

bottom tier. Following precise measurements, the steel piping was bent and cut, the G10

insulation base was cut to size and holes were drilled into it for the microchannel heat

exchanger assembly bolts to pass through. Fixtures for the pump, rotameter,

microchannel heat exchanger assembly and the liquid to liquid heat exchanger were built

and installed. DataLogger software was installed and configured on a local computer

which was compatible with the data acquisition system containing a multiplexer with

pressure transducers and thermocouples routed into it.

Once the flow loop construction was completed, it was tested by plotting both the

Nusselt number and friction factor versus Reynolds number for the system against the

theoretical predictions. The discrepancies were accounted for and deviations were

deemed acceptable for the project. The results were approved by Dr. Liu to complete the

project.

ProcessThe analysis of the components and the determination of their specifications

required many careful calculations. All calculations were completed in order for the

components to successfully work together to produce a flow loop capable of removing

the heat and providing accurate and useful data. The microchannel heat exchanger copper

block was provided by Dr. Liu at the project’s start without any machine drawings due to

the extensive amount of time that had passed since its manufacture. Team 16 used the

MECE department’s shadow graph in order to measure the channel cross section and

determine the number of microchannels. Furthermore, a caliper was used to determine the

length of the channels, as well as the diameter and length of the heat cartridge holes.

9

Page 10: Final Technical Report

These measurements provided the critical dimensions for the channels and the geometric

constraints for the heat cartridges as shown in Table 1 below.

Table 1: Critical dimensions for the microchannel heat exchanger

Critical Dimensions

Hydraulic Diameter: Dh 214µm

Length: L 2.54cm

Channel Width: W c 192µm

Channel Height: H c 242µm

Number of Channels: N 50

The next task for Team 16 was to determine the specifications of the heat

cartridges. In order to provide the amount of heat flux needed to simulate the heat from a

CPU, 100 W/cm^2, eight heat cartridges were ordered, each capable of supplying 50 W

of power as shown in the calculations below.

Cross sectional area of top part of mic rochannelheat exchanger=3.884 cm2

Total power ¿be supplied=( 100Wc m2 ) (3.884 c m2 )=388.4 W

Power ¿be supplied byeach of 8cartridges=388.48

≈ 50 W

It was determined that the flow rate required to avoid boiling with a heat flux of

100 W/cm^2 was approximately 170 mL/min, thus creating a pressure drop across the

microchannels of approximately 0.8 psi as shown in the calculations below.

10

Page 11: Final Technical Report

m=qs ' ' PL

C p (Tm, o−T m , i)=169.5 mL /min

Where m is the mass flow rate in mL/min and qs' ' is the heat flux at 100 W

cm2 , P is

perimeter, L is channel length, C pis the specific heat and T m,o and T m,i are the mean

outlet and inlet temperatures respectively.

∆ P=fρum

2 Dh=0.8 psi

Where ∆ P is pressure drop in psi, f is the friction factor from the Moody diagram,

ρ is the density, um is the mean velocity calculated from the flow rate, and Dh is the

hydraulic diameter.

These flow rate and pressure drop requirements were used to determine which

pump and pressure transducers were needed. It was decided that the operating

temperature would vary from room temperature to 100⁰ C at the absolute maximum in

order to maintain single phase flow. Therefore, type T thermocouples were chosen due to

their relatively low temperature range and higher resolution. In order to ensure no leakage

occurred between components and piping, Team 16 followed recommendations from Dr.

Liu to go with ferrule type tube fittings to allow for easy connection/disconnection while

sealing properly. The data acquisition requirements were determined so that

thermocouple and pressure transducer voltage data could be converted to temperature and

pressure values and recorded as the flow rates varied. To meet those requirements while

remaining cost effective, an HP Agilent 34970A data acquisition and a corresponding

multiplexer module were purchased.

11

Page 12: Final Technical Report

In order for Team 16 to determine which correlations were needed for the

experimental and theoretical data, the fluid and thermal entrance lengths first needed to

be calculated to determine if the flow was fully developed or developing. The fluid entry

length varied depending on the Reynolds number and thus a relationship was used that

accounted for flow that was developing or fully developed with regards to the friction

factor experiment. For the entire channel length, the flow was thermally developing,

therefore it was determined that correlations and formulas relating to developing flow

could be used with minimal error in reference to the heat transfer experiment. The entry

length calculations and the decided upon correlations will be discussed at length in the

Results section of this document.

The flow loop construction required specialized tools, sealants and thermal

compounds. A pipe cutter and bender were utilized for forming the ¼ inch stainless steel

piping sections while maintaining precision and keeping the pipe from being crushed. For

the machining of the G10 insulation and the L brackets for fixturing, the table saw, drill

press and related safety equipment from Dr. Song’s lab were employed. A hand drill was

used to create bolt holes in the cart for fixturing and hand taps were used in order to re-

thread the ports in the polymer block. The thermocouple welder in the thermal fluids lab

was used to connect the ends of the thermocouples. Several different sealants, such as

Loctite, RTV, exhaust and silicone sealants, were utilized to prevent leakage from around

the thermocouples and from threaded connections. After it was observed that flow was

being drawn into the multiplexer by the capillary effect, the thermocouple sheaths were

sealed to prevent damage to the multiplexer. A method of pump priming was determined

in order to minimize the amount of air in the lines of the pump and to minimize the risk

12

Page 13: Final Technical Report

of the pump running dry. It was found after initial flow loop testing that that a sizeable

amount of heat was being lost to the surroundings. As a solution to this problem, exhaust

header wrap was tightly wound around the microchannel heat exchanger in layers to

prevent excessive heat loss to the air.

ConstraintsThe flow loop design was mainly constrained by the space and portability desired

by the advisor. In order to facilitate portability, Team 16 purchased a two-tiered stainless

steel cart with each tier 19.5 inches wide by 35 inches long and 4 inches depth. The top

tier of the cart held the entire flow loop in order to prevent pressure drops from height

differentials. Therefore, all of the loop's components had to fit within the available space

of the top level. The bottom level held the data acquisition hardware. In order to prevent

accidental spillage of water onto the lower level, a cart with a high wall on the top level

was purchased.

The design specifications for this project stated that the water must remain

laminar and single phase as it passes through the microchannels. This narrowed the

available pumps since it was necessary to calculate the mass flow rate of the water

compared to the hydraulic diameter of the piping between components. The Reynolds

number was then calculated to determine whether this would result in laminar or

turbulent flow within the microchannels. Furthermore, it was necessary to eliminate back

flow and head loss as much as possible between components with varying entry and exit

diameters. Proper fittings were necessary to facilitate these diametric conversions while

maintaining steady flow.

13

Page 14: Final Technical Report

All software and computer systems attached to the data acquisition hardware had

to be compatible. Team 16 ensured that the hardware and software could acquire inputs

from both pressure transducers and thermocouples and that the software was readily

available. Type T thermocouples were chosen due to their relatively low temperature

range and higher resolution and due to the operational limitations requiring temperatures

below 100°C to maintain single phase operation. Furthermore, the experiment required

several feet of thermocouple wire to accommodate the seven input sites and the length

required to reach the data acquisition system. The heat cartridges and pressure

transducers necessary for this experiment were fitted for the lengths and diameters of

their corresponding cavities.

Time and cost restraints were stringent therefore it was necessary to conserve both

as much as possible. Initially, the budget was estimated to be approximately $7,000

which was within the capabilities of the MECE department. Through price comparisons

and thorough market research, Team 16 was able to reduce this cost to about $5,000. The

two semesters given to the capstone course provided the main time constraint. The

involved nature of this project necessitated that Team 16 spend the majority of the first

semester learning about this application of heat transfer while planning out the

construction of the flow loop. Therefore, the components were not fully known until the

end of the fall semester. Many of the more specialized components required a month to

ship from the vendor, thus reducing the time allowed for the construction of the loop.

After all components arrived, Team 16 had slightly less than a month to construct the

flow loop.

14

Page 15: Final Technical Report

Material considerations played a large role in component selection. Stainless steel

was chosen for the majority of the flow loop due to its low corrosivity. The primary piece

of the loop is the copper microchannel heat exchanger. Copper is used due to its high

thermal conductivity. All other components were selected around the design of this

copper microchannel heat exchanger. Dr. Liu’s original thesis called for deionized water

to be pumped through the flow loop. After some research, it was discovered that

deionized water causes corrosion in copper components over extended periods of time.

For this reason, reverse osmosis water was chosen in order to preserve the copper block

and do to its wider accessibility. This decision allowed for reduced cost because copper

became permissible in place of stainless steel for the liquid to liquid heat exchanger.

Finally, it was necessary that the housing of the copper heat exchanger be completely

insulated in order to prevent heat loss to the surroundings and obtain an accurate

representation of inlet and outlet flow temperatures. To this end, G10 material was

chosen and the entire housing was covered in insulating exhaust wrap. In order to view

the flow and the inlet and outlet thermocouples, the housing was covered by a

transparent, polycarbonate top.

StandardsThe pump, condenser, pressure transducers, thermocouples, reservoir, flow meter

and the instrumentation follow ANSI, ISO, ASTM, ASME, EPA, GLP, and GMP

standards, respectively. Standards are accreditations that give assurance to the consumer

of the quality of the product and calibration of the instruments that are being used.

While ordering parts we encountered many of these standards. Although there

were many standards that were not readily available to the public, acknowledging their

15

Page 16: Final Technical Report

existence is important. A private company, Innocal, applied testing standards to the pump

which pertained to verifying flow rates, power, pump head and pump curves. The

standards used were ISO, EPA, GLP and GMP standards. The heat exchanger was

manufactured by Lytron and was certified under ISO, 9001:2008 and AS9100:2009 under

managerial standards as well as codes of practice in reference to heat exchangers. Codes

of practice are common within the industry and have been widely used for components

such as the reservoir that is considered an unfired pressure vessel in ASME standards.

ASME has several standards that it produced especially for stainless steel fittings that

will be used for piping within the flow loop. The fittings and piping also follow ASTM

and ANSI standards for material properties that have been tested and documented online

for reference. ASTM is also responsible for standards such as calibration that were

utilized in the manufacturing process of the pressure transducers, data acquisition system,

and thermocouples.

ResultsThe final results of construction are shown below in Figures 2 and 3. The top tier

of the mobile cart is presented in Figure 2. The contents and detailed reasoning behind

these component choices were presented in the methodology section of this document. As

shown, all components were arranged in a way that worked well geometrically and was

aesthetically pleasing. Every component could be easily broken down from the others to

facilitate maintenance and cleaning. The bottom tier, which contained all of the electrical

equipment, is shown in Figure 3. This equipment powered the pump, pressure

transducers, heat cartridges and the data acquisition system. The high lip of the top tier

16

Page 17: Final Technical Report

was designed to protect this equipment in case of accidental leakage during maintenance

or operation.

Figure 2: Flow loop assembly on top tier of cart.

Figure 3: Electronic components on bottom tier of cart.

The heart of the system is shown below in Figure 4. Upon close inspection it is

possible to see what appears to be a rough surface on top of the copper block. Those are

the microchannels of this heat exchanger where fluid flows during normal operation. The

17

Page 18: Final Technical Report

heat exchanger is visible in Figure 2 through the transparent top of the housing. There

was a sufficient seal provided by the polycarbonate top so that there would be no

communication between the individual microchannels of the copper block. There were

thermocouples attached to the five inlet sites shown in the T-shape of the heat exchanger,

as seen in Figure 4. Each thermocouple gave realistic readings that corresponded to the

appropriate temperature distribution resulting from the heat flux with and without fluid

flow. Furthermore, the inlet and outlet of the channels each had a thermocouple for these

flow temperatures. The water was able to sufficiently remove heat from the copper block

in order to simulate the heat that would be removed by fluid in a modern integrated

circuit.

Figure 4: Copper microchannel heat exchanger.

The received data followed the same trends as the theoretical predictions as

shown below in Figures 5 and 6. Any offsets can be explained by minor head losses and

imperfect insulation of the entire system. The trends are very close to predicted values

18

Page 19: Final Technical Report

and show a strong correlation when the factors mentioned previously are included. In

order to find the measured friction factor, f, Equation 2 was used. The pressure drop, ΔP,

was measured using the pressure transducers at the inlet and outlet of the fluid flow. The

pressure drop was divided by the density of water, ρ, in order to find the major head loss,

hl. The characteristic length, L, and hydraulic diameter, Dh, were previously measured

using a shadowgraph. The velocity, V, was found through the rotameter by dividing the

flow rate by the cross sectional area of all 50 microchannels combined. Then, it was

necessary to find the Reynolds number, Re, through Equation 3. Here, µ is the dynamic

viscosity which can be found from tables and all other variables were described

previously. The theoretical value for the friction factor for fully developed flow in a

channel with an aspect ratio, α, was determined using Equation 4. It was determined that

the developing hydrodynamic entrance length in the microchannels was significant for all

Reynolds numbers tested according to Equation 5. Therefore, Equation 6 was used to

account for the mixture of developing and fully developed flow. This equation solved for

the non-dimensional flow distance, x+, which is dependent on variables described above.

The non-dimensional flow distance was then used to find the apparent friction factor, fapp,

through Equation 7. Finally, Equation 7 was used to create the theoretical curve shown in

Figure 5.

hl=f LV 2

2 Dh=∆ P

ρEquation 2

ℜ=ρV D h/µ Equation 3

fRe fd=96¿ Equation 4

19

Page 20: Final Technical Report

xe,l

Dh=0.05ℜ Equation 5

x+¿=L/(Dh ∙ ℜ)¿ Equation 6

f app ℜ=¿¿ Equation 7

Figure 5: Friction factor vs. Reynolds number.

The relationships necessary to find the Nusselt number, Nu, are found through

Equations 8-14 presented below. Begin by finding the total heat transfer, q, from

Equation 8. The fluid properties are the density, ρ, and the specific heat, Cp, which were

found in the fluid tables. The volumetric flow rate, Q, was found using the rotameter,

while the inlet and outlet temperatures, Tm,o and Tm,i were obtained using the

thermocouples that were placed directly into the flow. The effective heat flux, q”eff, was

found according to Equation 9 where N is the number of microchannels on top of the heat

exchanger and A is the wetted area. Then, Equation 10 can be used to find the heat

20

Page 21: Final Technical Report

transfer coefficient, h. Tw can be attained by reading the temperatures of the

thermocouples at the top of the microchannel heat exchanger and using Equation 11

where TAVG is the average of the temperatures of the thermocouples along the length of

the channel for a given flow rate. The variable s is the distance between the

thermocouples and the channels, and kcu is the thermal conductivity of the copper. Tm is

an average of the inlet and outlet flow temperatures. Tm is valid due to the fact that Tm

varies linearly across the channel length due to the constant heat flux. Afterwards, the

Nusselt number is realized through Equation 12 where kf is the conduction coefficient of

the fluid. It was determined that the flow in the microchannels was thermally developing

for the entire length of the channel for all Reynolds numbers tested using Equation 13.

Here, xt,l represents the thermal entry length, the Prandtl number, Pr, is a thermal fluid

property of the water and the other variables were described previously. Also, the

Reynolds number, Re, was found the same way as described for the friction factor

experiment. The final theoretical relation is shown in Equation 14 and plotted in Figure 6.

Here, the Reynolds number is found the same way as was described above for the friction

factor experiment. The dynamic viscosity of the water at its mean temperature and the

dynamic viscosity of the water at the wall temperature are represented by µf and µw,

respectively.

q=ρ C pQ(T m, o−T m,i) Equation 8

qeff} = {q} over {NA¿ Equation 9

h=qeff } over {( {T} rsub {w} - {T} rsub {m} ) ¿Equation 10

T w=T AVG−sqeff} / {k} rsub {cu ¿ Equation 11

21

Page 22: Final Technical Report

Nu=h Dh

k fEquation 12

xt ,l

D h=0.05 RePr Equation 13

Nu=1.86 ( RePr Dh /L )1 /3( μ f

μw)

0.14

Equation 14

Figure 6: Nusselt number vs. Reynolds number.

ConclusionThermal management in computers is becoming more of a priority as technology

advances and the number of transistors on a standard size integrated circuit continues to increase.

Microchannel heat exchanger liquid coolant systems for ICs are a viable option due to the high

thermal conductivity and specific heat of the liquids used. Several methods have been used to

construct and test the flow loop. Methods include taking measurements and calculations into

consideration when ordering components, working with tools to construct the flow loop and

creating laboratory documents after administering several tests. The measured data from the flow

22

Page 23: Final Technical Report

loop closely followed predictions made by theoretical correlations. Dr. Liu reviewed the

construction of the flow loop and the measured data and validated the project. The project has

been completed within the desired time and the team has successfully submitted all required

deliverables to the MECE department.

RecommendationsThere are several recommendations that are a part of the self-evaluation process

of the capstone design project. Moving through the flow loop, starting with the

microchannel heat exchanger, suggestions were made to improve the overall performance

of the flow loop. There was a small gap in between the copper block and the ported white

polycarbonate top. This gap exists due to uncertainty in machining the top and can be

fixed by adding a small layer of sealant between the two components. A silver based

thermal compound was placed between the heat cartridges and the copper block in order

to reduce thermal resistance. Team 16 recommends that a silicone based thermal

compound be used for future work due to the unavoidable fact that the compound can get

too close to the leads and if electrically conductive, it can cause temporary arcing until

the compound dissipates. Laminar flow was the only flow regime that could be analyzed

due to limitations imposed by the pressure transducers which were rated only for 0 – 15

psi, which does not allow for a high enough inlet pressure to produce turbulent flow. It’s

recommended that pressure transducers of 0 – 50 psi range are ordered for future use. If

more precision is required, a rotameter with smaller increments than the current 100ccm

could be implemented.

23

Page 24: Final Technical Report

Appendix A – Friction Factor Experiment

Experiment #1 – Darcy Friction Factor Verification

*Note: cartridge heaters not necessary for this first experiment*

Objective: Show that experimental results for friction factor (f*Re) correlate closely to the theoretical predictions for laminar flow through micro-channels.

Background:

This experiment examines the pressure drop that occurs as fluid flows through

channels that have hydraulic diameters that are on the scale of micrometers. It also

examines the relationship between the Reynolds number and friction factor for

developing, laminar, internal flow. The results are used to compare fluid flow

relations on the micro and macro scale. Pressure drop is a phenomenon that occurs

as a result of a fluid experiencing internal flow. For this experiment the internal flow

will be through a channel.

For internal flow, the observed pressure drop is caused by two factors, major and

minor head loss. The major head loss accounts for the pressure drop caused by

friction effects in the channel. The major head loss will be used to calculate the

friction factor in this experiment. The equation used to find the friction factor for

fully developed flow is as follows:

hl=f LV 2

2 Dh=∆ p

ρ Equation 1

Where hl is the major head loss, f is the friction factor, L is the length of the channel,

V is the average velocity of the fluid, p is the measured pressure, is the fluid ρdensity and Dh is the hydraulic diameter. The average velocity can be found by

dividing the volumetric flow rate of the fluid by the cross-sectional area of the

channel. For laminar flow, the friction factor is proportional to the Reynolds

number.

24

Page 25: Final Technical Report

Shah & London provide a theoretical correlation for f*Re with respect to the aspect

ratio for fully developed laminar flow as shown below in Equation 2 and another

correlation to modify for developing flow as shown in Equation 3.

Equation 2

Where is the aspect ratio for the microchannels. Since the hydraulic diameter and αlength of the channels are small, we can assume that the flow is not fully developed. The relation used to calculate the apparent friction factor for developing laminar flow can be seen in Equation 3.

f app ℜ=¿¿ Equation 3

where entrance length is defined as

x+¿=L/(Dh ∙ ℜ)¿ Equation 4

Pre-Lab Questions:

1. Familiarize yourself with the apparatus and the flow loop operations manual.2. Determine expressions for the uncertainty of ℜ ,∆ P ,∧f .3. Calculate the entrance length for a microchannel with critical dimensions as

described and determine if flow is transitional or fully developed.

25

fRe fd=96¿

Page 26: Final Technical Report

Apparatus:

Figure 2: Piping and Instrument Diagram (P&ID)

26

Page 27: Final Technical Report

Figure 3: Microchannel Heat Exchanger

Figure 4: Profile of Microchannels

27

Page 28: Final Technical Report

Critical Dimensions

Hydraulic Diameter: Dh 214µm

Length: L 2.54cm

Multiplexer Channel Measurement and Location

1 TC – flow inlet

2 TC – Copper block – top right (near outlet)

3 TC – Copper block – top middle

4 TC – Copper block – top left (near inlet)

9 PT – flow inlet

10 PT – flow outlet

18 TC – Copper block – second from bottom

19 TC – Copper block – bottom

20 TC – flow outlet

Procedure:

1. Have the TA check the data acquisition hardware and software to make sure it is set up properly.

2. Provide water flow to heat exchanger by turning on the sink.3. Turn on the pump and vary flow rate and therefore pressure drop along the

microchannels. Then obtain the measured data of the flow rate and the corresponding voltage produced by the pressure transducers between the inlet and outlet of the test sections.

28

Page 29: Final Technical Report

In-Lab Analysis:

1. Calculate average velocity and Reynolds Number to confirm laminar flow:

ℜ=ρU Dh

μ Equation 5

Where ρ is the density of the reverse osmosis water, U is the average velocity, Dh is the hydraulic diameter, and μ is the dynamic viscosity.

Calculate the pressure drop across the microchannels using the calibration data for the pressure transducers.

2. Calculate friction factor, f, for each data point using Equation 1.

3. Plot Reynolds number vs. Friction factor and show that for laminar flow, the slope is approximately constant.

4. Calculate theoretical friction constant f*Re for laminar fully developed flow and compare using the theoretical equations and assumptions in Dr. Liu’s thesis

Deliverables:

Worksheet 1: Measured voltage data

Worksheet 2: Measured pressure drop, Reynolds number, friction factor, theoretical

friction factor and uncertainties for each.

Worksheet 3: A plot of the measured and theoretical friction factor. Explain any

discrepancies between the measured data and the theoretical curve.

Post-Lab Analysis:

1. Compare the experimental data for f vs. Re with the correlation in Equation 2. Explain the possible causes behind the discrepancies between the two sets of data.

2. Derive an expression for major head loss from the following energy balance equation:

29

Page 30: Final Technical Report

Q−W s−W shear−W other=∂∂t ∫CV

eρdV +∫CS

(u+ ρv+ V 2

2¿+gz )ρ V ∙dA ¿

Equation 6

30

Page 31: Final Technical Report

Appendix B – Nusselt Number Experiment

Experiment #2 –Nusselt Number vs. Reynolds Number Verification

Objective: Show that experimental results for Nu as a function of Re correlate closely to the theoretical predictions for developing laminar flow through microchannels.

Background:

This experiment examines the variation of Nusselts number with increasing Reynolds number for developing laminar fluid flow through microchannels. The Nusselts number is then used to find heat transfer coefficients for the flow. The results are used to compare heat transfer relations on the micro and macro scale.

The Nusselts number for laminar developing flow in a channel is a function of both Reynolds number and Prandtl number. There are several empirically determined relations for the average Nusselts number for developing flow. The theoretical Sieder-Tate relation that will be used in this experiment is shown in Equation 1.

Nu=1.86(RePr Dh

L)1 /3

(μ f

μw)

0.14

Equation 1

Where Re is Reynolds number, Pr is Prandtl number, Dh is the hydraulic diameter, L is the length of the channels, µf is the dynamic viscosity of the fluid at the mean fluid temperature and µw is the dynamic viscosity of the fluid at the wall temperature. The average heat transfer coefficient for the flow can then be determined by using the relation in Equation 2.

Nu=h Dh

k f Equation 2

Where kf is the thermal conductivity of the fluid and h is the average heat transfer coefficient. Because the hydraulic diameter and length of the channels are small we can assume that the flow is not fully developed for the entire length of the channel for low Reynolds numbers.

Pre-Lab Questions:

1. Familiarize yourself with the apparatus and the flow loop manual.

31

Page 32: Final Technical Report

2. Determine expressions for the uncertainty for Re and Nu

Apparatus:

Figure 5: Piping and Instrument Diagram (P&ID)

32

Page 33: Final Technical Report

Figure 6: Microchannel Heat Exchanger

Figure 7: Profile Microchannel

33

Page 34: Final Technical Report

Critical Dimensions

Hydraulic Diameter: Dh

214µm

Length: L 2.54cm

Channel Width: W c 192µm

Channel Height: H c 242µm

Number of Channels: N

50

Multiplexer Channel Measurement and Location

1 TC – flow inlet

2 TC – Copper block – top right (near outlet)

3 TC – Copper block – top middle

4 TC – Copper block – top left (near inlet)

9 PT – flow inlet

10 PT – flow outlet

18 TC – Copper block – second from bottom

19 TC – Copper block – bottom

20 TC – flow outlet

Procedure:

1. Review the voltage to pressure conversion chart for the pressure transducers and the method used to read a flow meter.

2. Ensure that the data acquisition system is set up properly for the experiment by asking the TA.

3. Supply cooling water to the second heat exchanger by turning on the valve for the sink.

34

Page 35: Final Technical Report

4. Turn on the transformer and set the voltage to 60VAC to power the heater cartridges. Once the maximum measured temperature reaches 70⁰C turn on the pump so that the flow rate is 200ml/min.

5. Vary the flow rate over four points from 200ml/min to 500ml/min and record the corresponding pressure drop for each flow rate. Allow for temperatures to reach steady state (+/- 0.2⁰C) for each flow rate before moving to the next flow rate.

6. Calculate average velocity in the channels using the measured volumetric flow rate.

In-Lab Analysis:

1. Calculate Reynold’s Number and confirm laminar flow:

ℜ=ρU Dh

μ Equation 1

Where ρ is the density, U is the average velocity, Dh is the hydraulic diameter, and μ is the dynamic viscosity of the reverse osmosis water.

2. Calculate the steady state heat gain of the coolant for each flow rate using the following formula:

q=ρ C pQ(T m, o−T m ,i) Equation 2

Where C p is the specific heat, Q is the flow rate, and the temperatures are the mean fluid temperatures at the outlet and inlet, respectively. Note: all fluid properties should be calculated for water at the mean fluid temperature.

3. Calculate the effective heat flux in the micro-channels:

qeff} = {q} over {NA¿ Equation 3

Where N is the total number of channels and A is the area available for convection per channel which would equate to:

A=L(W c+2 H c) Equation 4

Where L is the length of the channel, Wc is the width of the channel and Hc is the height of the channel

4. Determine the average heat transfer coefficient

35

Page 36: Final Technical Report

h=qeff } over {( {T} rsub {w} - {T} rsub {m} ) ¿ Equation 5

Where Tw is the temperature of the wall of the channel (extrapolated from the nearest thermocouple) and the mean fluid temperature.

5. Calculate the average Nusselt’s number

Nu=h Dh

kf Equation 6

Where kf is the conductivity of the fluid.

6. Plot Reynold’s number vs. Nusselt’s Number and show that at Nu increases approximately linearly with Re at low flow rate (laminar flow) with a different constant slope at high flow rates.

7. Obtain the theoretically predicted curves for Re vs. Nu by using Equation 8 and compare the experimental results with the theoretical predictions and discuss.

Nu=1.86( RePrDL )

13 (

μf

μw)

0.14

Equation 7

Deliverables:

Worksheet 1: Measured Temperature Data

Worksheet 2: Average temperature for each channel at each flow rate at steady state, q, qeff, Tm, and Tw, and uncertainty calculations for each.

Worksheet 3: Measured h and Nu, theoretical Nu, Reynolds number and uncertainty calculations for each.

Worksheet 4: A graph comparing the measured Nu vs Re and the theoretical Nu vs Re and an explanation of any deviation of your measured values from theory.

Post-Lab Analysis:

1. Compare the experimental data for Nu vs. Re with the correlation in Equation 7. Explain the possible causes behind the discrepancies between the two sets of data.

2. Using Equation 8 prove that the mean temperature, Tm, varies linesrly with position along the microchannels, thus validating our use of an average for Tm in this experiment.

T m (x )=Tm, i+qs ' 'm c p

x withqs ' '

36

Page 37: Final Technical Report

Appendix C – Flow Loop Operational ManualMicrochannel Heat Exchanger Flow Loop for MECE 4371

Purpose:

This document provides operational instructions for the microchannel heat

exchanger flow loop developed by Team 16 as a part of the MECE 4341 Capstone

Design course at the University of Houston. The loop will be used in the thermal fluids

lab of MECE 4371.

Layout

Visual representations of the flow loop are provided below in Figures 1 and 2.

Flow travels through each component through ¼” stainless steel piping. Each connection

is provided by Swagelok ferrule fittings that provide a tight seal to prevent leakage. The

flow originates from the reservoir where clean, reverse osmosis water is stored. It is

important that the reservoir remains sealed, unless it is necessary to add or remove water

since impurities can easily clog the microchannels. Water is then drawn from this

reservoir into the pump and then filtered before going into the rotameter where the flow

rate is measured. The flow then proceeds into the housing which contains a

microchannel heat exchanger which is a copper block with small channels that were

etched into the top through photolithography.

37

Page 38: Final Technical Report

Figure 8: Flow loop layout on top tier of steel cart.

Figure 9: Piping and instrument diagram (P&ID) for flow loop.

The housing consists of a translucent polycarbonate top, a ported polymer block, a

G10 insulating base, exhaust wrap insulation, the copper microchannel heat exchanger

38

Page 39: Final Technical Report

and instrumentation for measuring pressure drop and temperature as shown in Figure 3

below. The polycarbonate top separates the individual microchannels and prevents fluid

communication between them. The exhaust wrap insulation ensures that heat lost to the

surroundings is minimized. The white ported polymer block separates the copper from

the polycarbonate thus providing the inlet and outlet to the microchannels as well as ports

for the pressure transducers and thermocouples. The ends of the polymer block were

threaded in order to accept the fittings necessary for inlet and outlet piping.

This block was manufactured specifically to accept the top part of the copper

block with a tight fit. An o-ring made from Buna-N type material is placed in a small

groove etched at the top of the white polymer block. This o-ring creates a seal between

this block and the polycarbonate top that prevents water from leaking out of the sides.

Another o-ring of the same type was placed at the bottom of the polymer block in order

to prevent leakage in this area.

Thermocouples were placed at the inlet and the outlet of the flow in order to

measure the temperature distribution across the copper block. The thermocouples were

held in place by an RTV silicone sealant that was used to fill the fittings and secure the

thermocouple wire in place. An additional five thermocouples were placed directly into

the copper block to obtain temperature distribution data throughout the block itself. A

constant heat flux is provided by eight heat cartridges which are placed in small cavities

at the bottom of the heat exchanger. A silver thermal compound was placed around the

cylindrical heat cartridges in order to minimize thermal resistance between the cartridges

and the copper block. In order to insulate the bottom of the heat exchanger, a flat plate of

G10 material was used. Bolts were used to create a tight seal within the housing that

39

Page 40: Final Technical Report

would prevent fluid communication between channels while avoiding deformation of the

channel walls. These bolts were driven through the polycarbonate top, the ported polymer

block and the G10 material. Eight holes were drilled into the G10 material so that the

heat cartridge wiring could be routed into the transformer discussed below. Finally,

pressure transducers were placed at the flow inlet and outlet to determine the pressure

drop across the microchannels. Loctite Thread Locker was used to seal the threads of the

pressure transducers and the inlet and outlet fittings. Flow then leaves the housing and

enters a liquid to liquid copper heat exchanger where tap water removes heat from the

RO water before the flow returns to the reservoir and the loop is complete.

Figure 10: Microchannel heat exchanger housing with polycarbonate top, ported polymer block, copper microchannel heat exchanger and G10 insulating base.

All of the components described above were placed on the top tier of a two-tier,

stainless steel cart as shown in Figure 1. The bottom tier contains all of the electronic

40

Page 41: Final Technical Report

components required for the system as seen in Figure 4. Output from the thermocouples

and pressure transducers is transferred to the data acquisition system on the bottom tier.

The data acquisition system then communicates with a local computer for data

processing. Data processing occurs through the Data Logger 3 program. The heat

cartridges required a transformer in order to convert the wall outlet voltage from 120

VAC to a variable AC voltage based on the heat required for each experiment. The

pressure transducers require an input between 9 and 30 volts. In order to power these, a

12 volt power supply is used that converts AC voltage to DC. A power strip was used to

provide outlets for the data acquisition system, the pressure transducers, the transformer

and the pump. Finally, clear plastic tubing was used for the inlet and outlet flows of the

tap water which passed through the liquid to liquid copper heat exchanger. The inlet was

fitted so that it could run from a generic garden hose. The fitting can be removed and the

tubing can be attached and hose clamped onto the barbed outlet of the laboratory sink if

necessary as well. The outlet is simple tubing that was made long enough to reach the

nearest drain.

Figure 11: Bottom tier of cart containing data acquisition and transformer.

41

Page 42: Final Technical Report

Operation Safety

1. Do not use pure deionized water or pure reverse osmosis water in this system!

The lack of ions in the water will cause it to strip copper ions from the

microchannel heat exchanger and the liquid to liquid copper heat exchanger

which will erode the components over time. The approved water for this

system is commercially available reverse osmosis water with some mineral

enhancement. The mineral parts per million should be fairly low, but it must

be present so that some ions will exist in the water. The system was initially

tested with Nestle ® Pure Life ® water purchased from CVS. This water is

clean enough to avoid clogging the microchannels and has enough ions to

avoid eroding the copper.

2. Always assure that the pump is sufficiently primed prior to operation. This

means that fluid must have contact with the pump’s moving components

before it can be safely activated. In order to prime the pump, undo the fitting

on the outlet of the reservoir. Rotate this piece of piping away from the pump

so that a tube can be fitted onto the end that was originally the reservoir outlet.

Elevate the tubing and use a funnel to direct water through the piping and use

gravity to drive the water into the pump. The water should fill the quarter inch

piping up to the highest bend that occurs right after the reservoir outlet. Then

reconnect the piping to the reservoir outlet. This will assure that the pipe is

mostly filled with water and only a small pocket of air will enter the pump

through the small piece of piping that goes into the reservoir. Excessively

running the pump while dry will destroy the unit! Furthermore, take care

42

Page 43: Final Technical Report

when running the pump past 1000 CCM according to the system’s rotameter.

Leakage began to occur at this flow rate and better sealing is necessary in

order to achieve a higher internal system pressure.

3. The heat cartridges are controlled through a variable voltage available through

the transformer. Do not push the transformer above 70 VAC without

approval from Dr. Liu! If fluid is not flowing over the microchannels,

then the heat exchanger can easily reach 100°C with less than 40VAC.

Excessive voltage or heating of the copper block without fluid flow will

create a fire hazard and possibly melt the white polymer housed on top of

the copper block. Any time that the heat cartridges are active, be sure to

watch and listen carefully. If any sounds come from the heat cartridges or

if a plume of smoke is seen, then turn off the transformer immediately to

prevent damage to the system.

4. When operating the data acquisition system (DAQ), assure that data is logical

for the experiment. Very inaccurate data may indicate that fluid has

entered the system. The thermocouples are currently sealed, but it is still

possible for the seal to break and for fluid to go through the outer sheath of the

thermocouple wiring and use the capillary effect to deposit water into the

thermocouple channels of the multiplexer. Be very careful and stop flow

operation immediately if data is wildly inaccurate. Furthermore, do not power

off the data acquisition system in the middle of a scan. The computer

software and the DAQ are in constant communication. If the DAQ hardware

is powered off mid scan, then the software will still interpret that a scan is

43

Page 44: Final Technical Report

necessary. The software will reactivate the DAQ which will then proceed to

start a new scan instead of finishing the old one. This will result in the

retrieval of bad data, so always assure that scanning is complete before

powering off the DAQ.

44