expansion automats calculation

4
10 20 30 40 50 60 70 80 90 100 110 120 1 0 2 3 4 5 6 Temperature [°C] Increase in volume [%] Basic Concepts for the Calculation of Expansion Automats To select the right expansion automat it is necessary to understand the following principles: Static height This is the height of the system between the connection of the Flexcon expansion appliance and the highest point, measured in water column metres (1 wcm = 0.1 bar). Sizing Expansion Automats System water capacity This is the total volume of water in the entire system including heat source, radiators, pipe work etc. Increase in water volume (in %) The table below shows the percentage volume increase of water as temperature increases from 10 °C to 110 °C. Expansion volume The expansion volume is determined in the following way: expansion volume = capacity x increase in volume at the average heating temperature. Example: heating temperature 90/70 °C (average 80 °C) = 2.89%. FLEXCON M-K / U Set system pressure [bar] Heating capacity [MW] 2 x K-042 1 x K-042 1 x K-04 1 x K-031 1 x K-11 1 x K/C 2 x K-11 2 x K-04 2 x K-031 PN16 PN6 PN10 10 9 8 7 6 5 4 3 2 1 0 0 1 2 3 4 5 6 7 8 9 10 11 12 Flexcon M-K Compressor Curves Flexcon M-K selection graph. Typical heating installation (nominal characteristics) Increase in temperature [°C] Increase in volume [%] 10 - 25 0.35 10 - 30 0.43 10 - 35 0.63 10 - 40 0.75 10 - 45 0.96 10 - 50 1.18 10 - 55 1.42 10 - 60 1.68 10 - 70 2.25 10 - 80 2.89 10 - 90 3.58 10 - 100 4.34 10 - 110 5.16

Upload: trhieufans

Post on 07-Aug-2015

13 views

Category:

Engineering


2 download

TRANSCRIPT

10

FLAMC 1273

20 30 40 50 60 70 80 90 100 110 120

1

0

2

3

4

5

6

Temperature [°C]

Incr

ease

in v

olum

e [%

]

Basic Concepts for the Calculation of Expansion Automats

To select the right expansion automat it is necessary to understand the following principles:

• Static height This is the height of the system between the connection of the Flexcon expansion appliance and the highest point, measured in water column metres (1 wcm = 0.1 bar).

Sizing Expansion Automats• System water capacity

This is the total volume of water in the entire system including heat source, radiators, pipe work etc.

• Increase in water volume (in %) The table below shows the percentage volume increase of water as temperature increases from 10 °C to 110 °C.

• Expansion volume The expansion volume is determined in the following way: expansion volume = capacity x increase in volume at the average heating temperature. Example: heating temperature 90/70 °C (average 80 °C) = 2.89%.

FlExCon M-K / U

Set s

yste

m p

ress

ure

[bar

]

Heating capacity [MW]

2 x K-042

1 x K-0421 x K-041 x K-031

1 x K-111 x K/C

2 x K-11

2 x K-04

2 x K-031

PN16

PN6

PN10

10

9

8

7

6

5

4

3

2

1

0

0 1 2 3 4 5 6 7 8 9 10 11 12

Flexcon M-K Compressor CurvesFlexcon M-K selection graph. Typical heating installation (nominal characteristics)

Increase in temperature [°C]

Increase in volume[%]

10 - 25 0.3510 - 30 0.4310 - 35 0.6310 - 40 0.7510 - 45 0.9610 - 50 1.1810 - 55 1.4210 - 60 1.6810 - 70 2.2510 - 80 2.8910 - 90 3.5810 - 100 4.3410 - 110 5.16

Flamcomat Pump Curves

1 2 3 4 5 6 7 8 9 10 11 12

8,587,576,565,554,543,532,521,510,50 9,59 10

000

1

2

3

4

5

6

7

8

9

10

11

12

13

14

M20

D20M80 D80D80

M130 D130

Boiler output [MW]

Nominal flow rate [m³/h]

Uppe

r lim

it: m

ax. w

orki

ng p

ress

ure

pum

p [b

ar]

Low

er li

mit:

wor

king

pre

ssur

e -

switc

h on

pre

ssur

e of

the

pum

p [b

ar]

FlaMCoMaT

Selection diagram Flamcomat. Typical heating installation (nominal characteristics)

0 0,5 1

1 2 3 4 5 6 7 8 9 10 11 12

8,587,576,565,554,543,532,521,510,50 9,59 10

000

1

2

3

4

5

6

7

8

9

10

11

12

13

14

MM /DM

MMDM M0 M01M02 D02

M10 D10

M60 D60

M100 D100

Boiler output [MW]

Nominal flow rate [m³/h]

Uppe

r lim

it: m

ax. w

orki

ng p

ress

ure

pum

p [b

ar]

Low

er li

mit:

wor

king

pre

ssur

e -

switc

h on

pre

ssur

e of

the

pum

p [b

ar]

For cooling systems other selection conditions apply. For questions, please contact Flamco. Pump specific charts can be found at the Flamcomat pumps later in this catalog.

Sizing Expansion Automats• Heating/Cooling power

This is the sum of the nominal heating capacities.

• Capacity of the expansion automat The capacity of a pump expansion automat is determined in the following way: capacity of expansion appliance = 1.3 x expansion volume (in the case of the Flexcon M-K / C the factor is 1.4).

The factor of 1.3 is based on the following assumptions:• The expansion vessel has to hold at least 10%

more than the calculated expansion volume.• The volume of the vessel allows for refilling

and min./max. levels.• Corrections to tolerances which, according to

various standards, are admissible for parts of the system.

Calculations for Expansion Automats in Heating InstallationsExAMPlE 1

DATA- heating power = 1,500 kW- average heating temperature (90/70 ºC) = 80 ºC- static height = 20 metres- system volume = 15,400 litres- provision for expansion (vessel) situated at the bottom of the system.

CAlCUlATION OF VESSEl CAPACITYIncreaseinvolumein% =2.89% ≈2.9%

15,400 x 2.9Expansion volume = ––––––––––––– = 447 litres 100

Required expansion reservoir capacity = 447 x 1.3 = 581 litres

YOUR CHOICEalternative I : Flamcomat GB 600. Calculation - control unit with pump. nominal operating pressure = 2 + 1 = 3 bar. The 1.5 MW - 3 bar point is under the M 02 pump curve (see Flamcomat pump characteristics graph). Selected: Flamcomat GB 600/M 02.

alternative II : M-K/U 600, 6 bar model, possibly in combination with an ENA 20 de-aeration appliance.

ExAMPlE 2

DATA- heating power = 7,000 kW- average heating temperature (70/40ºC) = 55 ºC- static height = 37 metres- system volume = unknown- provision for expansion (vessel) situated at the bottom of the system.- system components: mixed utility.

CAlCUlATION OF VESSEl CAPACITYSystem capacity calculation = 7,000 x 10 = 70,000 litresIncrease in volume in % = 1.42%

7,000 x 1.42Expansion volume = ––––––––––– = 994 litres 100Required expansion reservoir capacity = 994 x 1.3 = 1,292 litres

YOUR CHOICE alternative I : Flamcomat GB 1600. Calculation - control unit with pump. nominal operating pressure = 3.7 + 1 = 4.7 bar. The 7 MW - 4.7 bar point is on the D 20 group curve (see Flamcomat pump characteristics graph). Selected: Flamcomat GB 1600/D 20.

alternative II : M-K/U 1600, 6 bar model, possibly in combination with an ENA 30 de-aeration appliance.

Calculation for Expansion Automats in Chilled Water SystemsExAMPlE 1

DATA- heating power = 5,400 kW- system volume = 95,000 litres- static height = < 5 metres (with vessel above)- temperature (6/12 ºC) = 9 °C- max. ambient temperature = 30 °C- no glycol

CAlCUlATION OF VESSEl CAPACITYIncrease in volume at 30 °C, without glycol = 0.43%

95,000 x 0.43Expansion volume = ––––––––––––– = 409 litres 100Required expansion reservoir capacity = 409 x 1.3 = 531 litres

YOUR CHOICEalternative I : Flexcon M-K/U 600, 6 bar model, possibly in combination with an ENA 10 de-aeration appliance.

alternative II : Calculation - control unit with pump. nominal operating pressure = 0.5 + 1 = 1.5 bar. as the selection table shows heat capacity, the aforementioned cooling capacity will have to be converted using a conversion factor of 0.412. The selection point is then 5,400 kW x 0.412 = 2,225 kW (2.2 MW) and 1.5 bar. The 2.2 MW - 1.5 bar point is on the M 02 pump curve (see Flamcomat pump characteristics graph). Selected: Flamcomat GB 600/M 02.

YOUR CHOICE alternative I : Flamcomat GB 1600. Calculation - control unit with pump. nominal operating pressure = 3.7 + 1 = 4.7 bar. The 7 MW - 4.7 bar point is on the D 20 group curve (see Flamcomat pump characteristics graph). Selected: Flamcomat GB 1600/D 20.

alternative II : M-K/U 1600, 6 bar model, possibly in combination with an ENA 30 de-aeration appliance.

Calculation for Expansion Automats in Chilled Water SystemsExAMPlE 1

DATA- heating power = 5,400 kW- system volume = 95,000 litres- static height = < 5 metres (with vessel above)- temperature (6/12 ºC) = 9 °C- max. ambient temperature = 30 °C- no glycol

CAlCUlATION OF VESSEl CAPACITYIncrease in volume at 30 °C, without glycol = 0.43%

95,000 x 0.43Expansion volume = ––––––––––––– = 409 litres 100Required expansion reservoir capacity = 409 x 1.3 = 531 litres

YOUR CHOICEalternative I : Flexcon M-K/U 600, 6 bar model, possibly in combination with an ENA 10 de-aeration appliance.

alternative II : Calculation - control unit with pump. nominal operating pressure = 0.5 + 1 = 1.5 bar. as the selection table shows heat capacity, the aforementioned cooling capacity will have to be converted using a conversion factor of 0.412. The selection point is then 5,400 kW x 0.412 = 2,225 kW (2.2 MW) and 1.5 bar. The 2.2 MW - 1.5 bar point is on the M 02 pump curve (see Flamcomat pump characteristics graph). Selected: Flamcomat GB 600/M 02.