Evaluator: XXX Evaluator: EGM/BL
Date: 06/17/2019
Page 1
07-15-19
ASCE 41-17 Tier 1 Seismic Evaluation
Building Name: Zellerbach Playhouse
CAAN ID: 1802
Auxiliary Building ID: 1802.1
Address: 2425 Bancroft Way, Berkeley, 94720
Site location coordinates: Latitude 37.868889o Longitudinal -122.261111 o
Plan North Elevation
UCOP SEISMIC PERFORMANCE LEVEL (OR “RATING”) BASED ON TIER 1 EVALUATION FINDINGS: V
BUILDING DATA
ASCE 41-17 Model Building Type (Governing Building Type bolded for Seismic Risk Model when multiple
types exist):
a. Longitudinal Direction: C2: Concrete Shear Walls (with Stiff Diaphragms)
b. Transverse Direction: C2: Concrete Shear Walls (with Stiff Diaphragms)
Square Footage: 49,595 sq. ft calculated out of 156,620 sq. ft. total for Zellerbach Auditorium (CAAN ID
1802) and Zellerbach Playhouse (CAAN ID 1802.1) (UCB Records)
Building Length: 181’-0” in N-S direction
Building Width: 92’-0” in E-W direction
Building Height: 43’-0” to the Low Roof, and 73’-9” to the High Roof
Story Height: 13’-6” (Level 2 – Level 3), 7’-10” (Level 3 – Level 4), 12’-8” (Level 4 – Level 5), 9’-0” (Level 5
– Low Roof), and 30’-9” (Low Roof – High Roof). Grade is located at Level 3.
Number of stories above grade: 4
Number of basement stories below grade: 1
Year of Original Construction and Code Year: The building was constructed in 1968. The drawings are
dated 1965, and the 1964 UBC is assumed.
Year of Later Construction and Code Year: None
COST RANGE TO RETROFIT (if applicable): Medium: $50 -$200 per square foot
Building Name: Zellerbach Playhouse Evaluator: EGM/BL
CAAN ID: 1802.1 Date: 06/17/2019
Page 2
BUILDING DESCRIPTION
General
The Zellerbach Playhouse is a performance space primarily utilized by UC Berkeley students. It is located
on the core UC Berkeley campus adjacent to the Spieker Plaza. The Playhouse is situated to the south of
the Alumni House, to the east of the Haas Pavilion and the Spieker Aquatics Complex, and to the west of
the Zellerbach Auditorium. Zellerbach Auditorium is assigned CAAN #1802. Zellerbach Playhouse is
assigned CAAN #1802.1. It is a reinforced concrete building that was constructed in 1968. The structure
contains four stories above grade and one story below grade and has a rectangular footprint measuring
181’-0” in the north-south direction by 92’-0” in the east-west direction.
The Zellerbach Playhouse is programmatically connected to the Zellerbach Auditorium; however, the two
buildings are structurally separated by a 1” wide expansion joint located on the east elevation of the
Playhouse. The below grade story and the area located to the south side of the main stage functions as a
paint shop, a wood shop, and storage space. The stage and seating area are located in the center of the
building. The stage (at Level 3) is located to the south of the seating areas, and the seating is comprised
of two sections. The orchestra seating contains tiered concrete risers, and the gallery seating is comprised
of two mezzanines (at Level 4) located on each side of the tiered seating. Additional mezzanines known
as the fly galleries (at Level 5) are located on each side of the stage. These serve as access corridors to the
gridiron above the stage and the catwalks above the seating. The gridiron contains the rigging required
for the curtains, lighting, and backdrops, while the catwalks contains equipment for lighting, projection,
and sound. The main entrance to the Playhouse is located on the north elevation at Level 3. The entry
lobby is at-grade and does not contain the basement story below which is typical in the remaining
footprint of the structure. This portion of the building contains a roof that slopes from the low roof
elevation down to Level 4.
Structural System
The Zellerbach Playhouse is physically separated from the Zellerbach Auditorium by a 1” expansion joint
that is oriented parallel to the longitudinal shear wall located on the east side of the structure. The gravity
load-carrying system is comprised of one-way reinforced concrete slabs that span to supporting elements.
The slabs are reinforced with #3, #4, and #5 bars spaced at 12” o.c. At the roof, the slab is 8” thick and
spans to 21 WF 55 and 18 WF 70 steel beams that are spaced at 8’-0” o.c. The steel framing is supported
by either a 92’-0” long roof truss or by load-bearing concrete shear walls. The typical floor slab is 6” thick,
and it spans to either concrete beams supported by shear walls or directly to load-bearing concrete shear
walls. The concrete beams range in depth from 24” to 50” and in width from 12” to 60”. They are
reinforced with #6, #8, and #11 longitudinal bars and contain open #3 and #4 shear stirrups spaced at 12”
and 16” o.c. The catwalk floor consists of an 18 gage unfilled metal deck over steel sub-framing and is
hung from the low roof. The bracing of the catwalk is unknown. The stage floor is framed with wood deck
over small steel beams.
The building contains three 20” diameter reinforced concrete columns which are located between Level
2 to Level 3 and are reinforced with 8-#8 longitudinal bars tied with 3/8” diameter spirals at a 2 ½” pitch.
One rectangular column measuring 12” x 18” and two columns measuring 12” x 16” are located between
Level 2 to Level 4 and are reinforced with 6-#6 and 4-#7 longitudinal bars respectively. They contain #3
Building Name: Zellerbach Playhouse Evaluator: EGM/BL
CAAN ID: 1802.1 Date: 06/17/2019
Page 3
ties spaced at 12” o.c. Otherwise, the flat framing is typically supported by load-bearing concrete walls
oriented in the longitudinal direction. At select locations, columns measuring 24” x 30” are embedded
into the walls and are reinforced with 8-#9 longitudinal bars and #4 ties with #3 cross-ties spaced at 18”
o.c. Although girders are supported by the exterior walls, embedded columns are not provided in the walls
at all girder locations.
Reinforced concrete shear walls comprise the lateral force-resisting system in both directions. In the
transverse direction, 14” thick exterior walls are located on the north and south elevations. There are an
additional four lines of interior walls that vary in thickness from 8” to 24”. In the longitudinal direction,
12”, 14”, and 16” walls are located on the east and west elevation. The thicker walls are located in the
center of the building and support the high roof framing above the stage while the thinner walls are
located to the north and south of the stage and support the low roof framing. The typical shear wall
reinforcement ratios range from 0.0020 to 0.0028, and trim steel is located around wall openings. The
walls do not contain reinforcing details that are consistent with special concrete shear walls such as
confined boundary zones.
The floor diaphragms in the Zellerbach Playhouse are highly irregular. In the lobby and seating area
located in the northern half of the structure, the diaphragms are comprised of narrow mezzanines and
balconies as well as stepped slabs provided for tiered seating. The shear walls that support the roof are
typically discontinuous above the seating levels. In the southern half of the structure, no intermediate
floor diaphragms are located between the low roof and the stage floor at Level 3. These walls span 29-6”
from Level 3 to the low roof and serve as demising walls between the stage and the back-of-house
functions. Although, these walls comprise a large portion of the total shear wall area, they will resist shear
from the inertial forces at the roof levels, but may not resist the forces from the seating and mezzanine
floor levels.
The basement floor consists of 5” slab on grade over 5” hot-mopped waterproof membrane, 3” lean
concrete, 4” open graded rock, 4” filter material, and compacted soil. The foundation encompasses spread
footing for columns and strip footing for shear walls.
Building Condition: Good
Date of Site Visit: 03/28/2019, Emma Meehan and Jorge Moreno, Rutherford + Chekene
Limitations of Walk-through: Not all rooms were entered.
SITE INFORMATION
Site Class (A-F): C Basis: Site Specific Zone Map of campus by Geomatrix
Site Specific Ground Motion Study? Yes, 2015 Update to the Site-Specific Seismic Hazard Analyses and
Development of Seismic Design Ground Motions
BSE-1N Spectral Accelerations: Basis: 2015 Update to the Site-Specific Seismic Hazard Analyses and
Development of Seismic Design Ground Motions, Table 5 for 36-75 ft Soil ft based on depth of rock
readings from Site Specific Zone Map of campus by Geomatrix.
SDS: 2.40g SD1: 0.72g
Building Name: Zellerbach Playhouse Evaluator: EGM/BL
CAAN ID: 1802.1 Date: 06/17/2019
Page 4
BSE-2E Spectral Accelerations: Basis: 2015 Update to the Site-Specific Seismic Hazard Analyses and
Development of Seismic Design Ground Motions, Table 6 for 36-75 ft Soil based on depth of rock readings
from Site Specific Zone Map of campus by Geomatrix.
SXS: 3.15g SX1: 1.05g
Level of Seismicity: High
Performance Level: Collapse Prevention Structural Performance
Geologic Hazards:
Fault Rupture: No Basis: CGS website http://maps.conservation.ca.gov/cgs/informationwarehouse/
Liquefaction: No Basis: CGS website http://maps.conservation.ca.gov/cgs/informationwarehouse/
Landslide: No Basis: CGS website http://maps.conservation.ca.gov/cgs/informationwarehouse/
PREVIOUS RATINGS SUMMARY
Fair or Poor - 1997 Preliminary Seismic Evaluation (SAFER), Forell/Elsesser Engineers Inc.
DOCUMENTATION
Architectural Drawings:
Auditorium – Theater, University of California, Berkeley, California, Vernon De Mars and Donald
Hardison, August 23, 1965, A1.1 to A1.7, A2.1 to A2.10, A3.1 to A3.4, A4.1 to A4.4, A5.1 to A5.3,
A6.1 to A6.14, A7.1 to A7.5, A8.1 to A8.5, A9.1 to A9.3, A10.1 to A10.5, A11.1 to A11.15, A12.1,
A12.2.
Structural Drawings:
Auditorium – Theater, University of California, Berkeley, California, Stefan J. Medwadowski, Ph.D.,
August 23, 1965, S1.1, S2.1 to S2.8, S2.10 to S2.13, S3.1 to S3.4, S4.1a to S4.19, S5.1 to S5.15, S6.1
to S6.4, S7.1 to S7.4.
Seismic Evaluations: None
Geotechnical Reports: None
Other Documents: None
CONSTRUCTION DATA
Gravity Load Structural System: Concrete slab that spans to concrete beams that are centered on
concrete columns
Exterior Transverse Walls: Reinforced concrete shear
walls
Opening(s)? Openings occur
for doors,
windows, and
MEP services
Exterior Longitudinal Walls: Reinforced concrete shear
walls
Opening(s)? Openings occur
for doors,
windows, and
MEP services
Building Name: Zellerbach Playhouse Evaluator: EGM/BL
CAAN ID: 1802.1 Date: 06/17/2019
Page 5
LATERAL-FORCE-RESISTING SYSTEM
Longitudinal Transverse
ASCE 41-17 Building Type: C2: conc. shear wall C2: conc. shear wall
Diaphragms: 6” and 8” thick concrete slab 6” and 8” thick concrete slab
Vertical Elements: Concrete columns and
concrete shear walls
Concrete columns and
concrete shear walls
Connections: Beam and slab
reinforcement is dowelled
into walls.
Beam and slab
reinforcement is dowelled
into walls.
Details: S4.1 to S4.5 for framing
details
S4.1 to S4.5 for framing
details
Estimated Fundamental Period, T (sec): 0.50 sec 0.50 sec
BSE-2E Spectral Acceleration, Sa: 2.09g 2.09g
Modification Factor, C: 1.0
(C2: Table 4-7 in ASCE 41-17)
2.0
(C2: Table 4-7 in ASCE 41-17)
Building Weight, W (kips): 11,793 kips 11,793 kips
Seismic Base Shear, V (kips): 24,603 kips 24,603 kips
System Modification Factor, Ms: 4.5 4.5
Roof Materials/Framing: High roof: 8” thick concrete slab supported by concrete beams that
span to reinforced concrete walls.
Low roof : 8” thick concrete slab supported by steel beams in the
N-S direction, and by a single steel truss in the E-W direction that
span to reinforced concrete walls.
Intermediate Floors/Framing: 6” thick concrete slab, and variable thickness slab in main seating
area (6” thick minimum) supported by concrete and steel beams
and girders. 18 gage unfilled metal deck supported by steel sub-
framing. Steel grating supported by steel sub-framing in the
gridiron.
Ground Floor: 5” concrete slab on grade over 5” hot-mopped waterproof
membrane, 3” lean concrete, 4” open graded rock, 4” filter
material, and compacted soil (Detail S3.1)
Columns: Reinforced concrete columns
that are 12”x16”, 12”x18”,
24”x 30”, and 20” round
columns
Foundation: Spread footings
ant columns and
continuous
footings at walls.
General Condition of Structure: Good
Evidence of Settling?: No
Special Features & Comments:
Building Name: Zellerbach Playhouse Evaluator: EGM/BL
CAAN ID: 1802.1 Date: 06/17/2019
Page 6
Significant Structural Deficiencies, Potentially Affecting Seismic Performance Level Designation:
☐ Lateral System Stress Check (wall shear, column shear or flexure, or brace axial as applicable)
☐ Load Path
Adjacent Buildings
☐ Weak Story
☐ Soft Story
Geometry (vertical irregularities)
Torsion
☐ Mass – Vertical Irregularity
☐ Cripple Walls
☐ Wood Sills (bolting)
Diaphragm Continuity
☐ Openings at Shear Walls (concrete or masonry)
☐ Liquefaction
☐ Slope Failure
☐ Surface Fault Rupture
☐ Masonry or Concrete Wall Anchorage at Flexible Diaphragm
☐ URM wall height to thickness ratio
☐ URM Parapets or Cornices
☐ URM Chimney
☐ Heavy Partitions Braced by Ceilings
☐ Appendages
OVERALL SEISMIC DEFICIENCIES & EXPECTED SEISMIC PERFORMANCE
The Zellerbach Playhouse is a five-story structure that is connected to the Zellerbach Auditorium on its
east side. As a theater, it contains almost solid shear walls around its perimeter and closely spaced interior
walls. From the Tier 1 evaluation, the Zellerbach Playhouse has sufficient shear capacity to resist the
BSE2-E level forces, and the calculated wall stresses are relatively low. The maximum stress is 104 psi in
the longitudinal direction and 77 psi in the transverse direction. The Tier 1 Quick Check for wall stress is
an average stress check and does not consider torsion or the potential increase in wall forces due to local
load path through the diaphragm.
The majority of the building mass is located on the northern half of the structure where the seating
mezzanine and balconies are located. However, the shear walls in this location are typically discontinuous
above the seating. The walls which are continuous are located in the southern half of the structure;
however, these walls are not connected to intermediate floor diaphragms. As a result of this irregular
wall and diaphragm configuration, the structure likely contains a torsional irregularity. In addition, the
walls on the north side of the structure can resist load from all floor levels, while those on the south side
may only resist load from the roof. In the case of the Zellerbach Playhouse, the average stress Quick Check
is an over-simplification of the actual wall stresses as the loads in the walls are largely determined by their
connectivity to the floor diaphragms.
Building Name: Zellerbach Playhouse Evaluator: EGM/BL
CAAN ID: 1802.1 Date: 06/17/2019
Page 7
The Zellerbach Playhouse contains a 1” separation gap at its interface with the adjacent Zellerbach
Auditorium. The provided separation gap is less than the 7 ¾” gap required by the Tier 1 Quick Check at a
drift ratio of 1.5%. The floor levels of the Playhouse and the Auditorium do align in elevation at Level 3
and Level 4, but not at Level 5. If pounding occurs, out-of-plane forces may be imposed on the walls of
the Auditorium near Level 5 and damage is likely to concentrate in this region.
There are two major walls oriented in the transverse direction that are discontinuous. These walls span
almost the entire width of the structure and are supported at each end by short wall piers. The wall piers
do not contain boundary zone reinforcing or even standard non-ductile column reinforcing. They are
reinforced as typical wall sections. It is unlikely that these elements were originally designed for vertical
loads induced by overturning of the discontinuous walls. The wall piers lack confinement of their
longitudinal reinforcing which will limit their axial capacity.
Seismic Performance Level Rating
A Seismic Performance Level rating of Level V is assigned to the Zellerbach Playhouse based on the Tier 1
evaluation, including review of the details and analytical results, because of the deficiencies identified
above, including highly irregular diaphragms and discontinuous walls, potentially inadequate seismic
separation between adjacent buildings, and the poor confinement in the wall piers located below the
discontinuous shear walls.
Recommended Next Step
It is recommended that an ASCE 41 Tier 3 linear analysis be completed for this structure to determine the
building drift, required seismic separation for the adjacent structures, and the adequacy of the gravity
columns to resist the expected displacements. A 3D model is required to assess the correct load
distribution based upon the relative wall stiffnesses and the diaphragm connectivity. The wall segments
below discontinuous shear walls can be checked for overturning forces from the walls above. Finally, the
load path through the discontinuous diaphragms can be examined.
Seismic Retrofit Concept Sketches/Description (only if above-listed rating is V or greater):
Retrofit concepts to address the deficiencies noted above include:
• Wrapping of columns with fiber reinforced polymer (FRP) or steel jackets to improve their axial
capacity and to provide enhanced confinement. This can be completed at the wall piers located
below discontinuous shear walls.
Appendices
A. Additional Images
B. ASCE 41-17 Tier 1 Checklists (Structural)
C. UCOP Seismic Safety Policy Falling Hazards Assessment Summary
D. Quick Check Calculations
APPENDIX A
Additional Images
Building Name: Zellerbach Playhouse Evaluator: EMG/BL
CAAN ID: 1802.1 Date: 06/17/19
Page 2
Plan
Longitudinal section (looking east)
Building Name: Zellerbach Playhouse Evaluator: EMG/BL
CAAN ID: 1802.1 Date: 06/17/19
Page 3
North elevation (looking southwest)
West elevation (looking northeast)
Building Name: Zellerbach Playhouse Evaluator: EMG/BL
CAAN ID: 1802.1 Date: 06/17/19
Page 4
South elevation (looking east)
Zellerbach Playhouse east elevation to the left and Zellerbach
Auditorium west elevation to the right
(looking north, taken from the low roof of the Playhouse)
Building Name: Zellerbach Playhouse Evaluator: EMG/BL
CAAN ID: 1802.1 Date: 06/17/19
Page 5
1” expansion joint (Zellerbach Auditorium on the left and Zellerbach
Playhouse on the right looking southeast)
Playhouse Stage (looking northwest)
Building Name: Zellerbach Playhouse Evaluator: EMG/BL
CAAN ID: 1802.1 Date: 06/17/19
Page 6
Theater seating with catwalks hanging from the ceiling (looking north)
Stage house gridirons, framing, and rigging (above stage)
Building Name: Zellerbach Playhouse Evaluator: EMG/BL
CAAN ID: 1802.1 Date: 06/17/19
Page 7
t Corridor at the stage level (looking north). The expansion joint
between the Playhouse and Auditorium is located on the wall to the
right
Woodshop (looking west)
Joint
Building Name: Zellerbach Playhouse Evaluator: EMG/BL
CAAN ID: 1802.1 Date: 06/17/19
Page 8
Paint shop (looking west)
Substage storage area (looking west)
APPENDIX B
ASCE 41-17 Tier 1 Checklists (Structural)
UC Campus: Berkeley Date: 6/17/2019
Building CAAN: 1802.1 Auxiliary CAAN:
By Firm: RUTHERFORD + CHEKENE
Building Name: Zellerbach Playhouse Initials: EGM Checked: BL
Building Address: Core Campus, Berkeley, 94720 Page: 1 of 4
ASCE 41-17
Collapse Prevention Basic Configuration Checklist
Note: C = Compliant NC = Noncompliant N/A = Not Applicable U = Unknown
LOW SEISMICITY
BUILDING SYSTEMS - GENERAL
Description
C NC N/A U
LOAD PATH: The structure contains a complete, well-defined load path, including structural elements and connections, that
serves to transfer the inertial forces associated with the mass of all elements of the building to the foundation. (Commentary:
Sec. A.2.1.1. Tier 2: Sec. 5.4.1.1)
Comments:
C NC N/A U
ADJACENT BUILDINGS: The clear distance between the building being evaluated and any adjacent building is greater than
0.25% of the height of the shorter building in low seismicity, 0.5% in moderate seismicity, and 1.5% in high seismicity.
(Commentary: Sec. A.2.1.2. Tier 2: Sec. 5.4.1.2)
Comments: Zellerbach Playhouse contains a 1” expansion joint to separate it from the Zellerbach Auditorium
located to the east. Based upon a 43 ft height from the seismic base (Level 2) up to lower roof, the gap required
is 7 ¾”.
Both the Auditorium and playhouse are shear wall structures, and it is expected that the interstory drift ratio
would be lower than 1.5%. The floor elevations of the two structures align so pounding damage is expected to be limited.
C NC N/A U
MEZZANINES: Interior mezzanine levels are braced independently from the main structure or are anchored to the seismic-
force-resisting elements of the main structure. (Commentary: Sec. A.2.1.3. Tier 2: Sec. 5.4.1.3)
Comments: The mezzanines located on Level 4 and Level 5 are connected to shear walls on three sides.
BUILDING SYSTEMS - BUILDING CONFIGURATION
Description
C NC N/A U
WEAK STORY: The sum of the shear strengths of the seismic-force-resisting system in any story in each direction is not
less than 80% of the strength in the adjacent story above. (Commentary: Sec. A2.2.2. Tier 2: Sec. 5.4.2.1)
Comments: The horizontal shear wall area increases or remains virtually the same from the high roof
down to Level 2, except for the stories between Level 2 – Level 3, and Level 3 – Level 4 in the longitudinal direction; however, the shear wall areas for these two stories are approximately 90% of the area of the
adjacent story above.
UC Campus: Berkeley Date: 6/17/2019
Building CAAN: 1802.1 Auxiliary CAAN:
By Firm: RUTHERFORD + CHEKENE
Building Name: Zellerbach Playhouse Initials: EGM Checked: BL
Building Address: Core Campus, Berkeley, 94720 Page: 2 of 4
ASCE 41-17
Collapse Prevention Basic Configuration Checklist
Note: C = Compliant NC = Noncompliant N/A = Not Applicable U = Unknown
C NC N/A U
SOFT STORY: The stiffness of the seismic-force-resisting system in any story is not less than 70% of the seismic-force-
resisting system stiffness in an adjacent story above or less than 80% of the average seismic-force-resisting system stiffness
of the three stories above. (Commentary: Sec. A.2.2.3. Tier 2: Sec. 5.4.2.2)
Comments: Excluding the uppermost story, heights between floors vary greatly, from 7’-10” to 13’-6”. The
tallest story is the one between Level 2 and Level 3; it has a shear wall area approximately equal to 90% of
the adjacent story above; nevertheless, this is a partially embedded story. The story between Level 3 and Level 4, which also has a shear wall area approximately equal to 90% of the adjacent story above, is also the
shortest. Thus, a soft story is not likely to occur.
C NC N/A U
VERTICAL IRREGULARITIES: All vertical elements in the seismic-force-resisting system are continuous to the foundation.
(Commentary: Sec. A.2.2.4. Tier 2: Sec. 5.4.2.3)
Comments: In the transverse direction, below Level 5, the walls are discontinuous in the following locations:
- North of Grid 16 between Grid Qq.3 to Tt.6.
- Grid 22 between Grid Qq.3 to Tt.6.
C NC N/A U
GEOMETRY: There are no changes in the net horizontal dimension of the seismic-force-resisting system of more than 30%
in a story relative to adjacent stories, excluding one-story penthouses and mezzanines. (Commentary: Sec. A.2.2.5. Tier 2:
Sec. 5.4.2.4)
Comments: The high roof is located above the stage and comprises approximately one-third of the building
length. It contains shear walls on its north and south elevations. The building enlarges below the high roof in the north and south direction. The shear walls at the lower stories step outwards to the exterior walls of the
enlarged footprint.
C NC N/A U
MASS: There is no change in effective mass of more than 50% from one story to the next. Light roofs, penthouses, and
mezzanines need not be considered. (Commentary: Sec. A.2.2.6. Tier 2: Sec. 5.4.2.5)
Comments: Maximum effective mass reduction occurs between low roof and high roof – reduction is
approximately 55%.
C NC N/A U
TORSION: The estimated distance between the story center of mass and the story center of rigidity is less than 20% of
the building width in either plan dimension. (Commentary: Sec. A.2.2.7. Tier 2: Sec. 5.4.2.6)
Comments: The building footprint is rectangular, and walls are located around the perimeter. However, no
floor levels are located over the stage, and the center of mass shifts towards the north due to the tiered seating, lobby, and mezzanines located in this region.
UC Campus: Berkeley Date: 6/17/2019
Building CAAN: 1802.1 Auxiliary CAAN:
By Firm: RUTHERFORD + CHEKENE
Building Name: Zellerbach Playhouse Initials: EGM Checked: BL
Building Address: Core Campus, Berkeley, 94720 Page: 3 of 4
ASCE 41-17
Collapse Prevention Basic Configuration Checklist
Note: C = Compliant NC = Noncompliant N/A = Not Applicable U = Unknown
MODERATE SEISMICITY (COMPLETE THE FOLLOWING ITEMS IN ADDITION TO THE ITEMS FOR LOW SEISMICITY)
GEOLOGIC SITE HAZARD
Description
C NC N/A U
LIQUEFACTION: Liquefaction-susceptible, saturated, loose granular soils that could jeopardize the building’s seismic
performance do not exist in the foundation soils at depths within 50 ft (15.2m) under the building. (Commentary: Sec. A.6.1.1.
Tier 2: 5.4.3.1)
Comments: Per CGS website http://maps.conservation.ca.gov/cgs/informationwarehouse/, the building is
not located in a liquefaction zone.
C NC N/A U
SLOPE FAILURE: The building site is located away from potential earthquake-induced slope failures or rockfalls so that it is unaffected by such failures or is capable of accommodating any predicted movements without failure. (Commentary: Sec. A.6.1.2. Tier 2: 5.4.3.1)
Comments: Per CGS website http://maps.conservation.ca.gov/cgs/informationwarehouse/, the building is
not located in a slope failure zone.
C NC N/A U
SURFACE FAULT RUPTURE: Surface fault rupture and surface displacement at the building site are not anticipated.
(Commentary: Sec. A.6.1.3. Tier 2: 5.4.3.1)
Comments: Per CGS website http://maps.conservation.ca.gov/cgs/informationwarehouse/, the building is
not located in a surface fault rupture zone.
HIGH SEISMICITY (COMPLETE THE FOLLOWING ITEMS IN ADDITION TO THE ITEMS FOR MODERATE SEISMICITY)
FOUNDATION CONFIGURATION
Description
C NC N/A U
OVERTURNING: The ratio of the least horizontal dimension of the seismic-force-resisting system at the foundation level to the building height (base/height) is greater than 0.6Sa. (Commentary: Sec. A.6.2.1. Tier 2: Sec. 5.4.3.3)
Comments: On Grid 14, B=92 ft, H=73.75ft (high roof), B/H = 1.25
Sa = 2.09 for UCB at BSE-2E 0.6x Sa = 1.25
B/H = 0.6 Sa
UC Campus: Berkeley Date: 6/17/2019
Building CAAN: 1802.1 Auxiliary CAAN:
By Firm: RUTHERFORD + CHEKENE
Building Name: Zellerbach Playhouse Initials: EGM Checked: BL
Building Address: Core Campus, Berkeley, 94720 Page: 4 of 4
ASCE 41-17
Collapse Prevention Basic Configuration Checklist
Note: C = Compliant NC = Noncompliant N/A = Not Applicable U = Unknown
C NC N/A U
TIES BETWEEN FOUNDATION ELEMENTS: The foundation has ties adequate to resist seismic forces where footings, piles, and piers are not restrained by beams, slabs, or soils classified as Site Class A, B, or C. (Commentary: Sec. A.6.2.2. Tier 2: Sec. 5.4.3.4)
Comments: Per “Geologic Hazards and Site Classification Central Campus, University of California,
Berkeley, California” prepared by Geomatrix, the site is located in Site Class C.
UC Campus: Berkeley Date: 6/17/2019
Building CAAN: 1802.1 Auxiliary CAAN:
By Firm: RUTHERFORD + CHEKENE
Building Name: Zellerbach Playhouse Initials: EGM Checked: BL
Building Address: Core Campus, Berkeley, 94720 Page: 1 of 4
ASCE 41-17
Collapse Prevention Structural Checklist For Building Type C2-C2A
Note: C = Compliant NC = Noncompliant N/A = Not Applicable U = Unknown
Low And Moderate Seismicity
Seismic-Force-Resisting System
Description
C NC N/A U
COMPLETE FRAMES: Steel or concrete frames classified as secondary components form a complete vertical-load-carrying system. (Commentary: Sec. A.3.1.6.1. Tier 2: Sec. 5.5.2.5.1) Comments: Reinforced concrete girders are directly supported by shear walls, which are designed for lateral loads. There are no columns to form an independent vertical-load-carrying system.
C NC N/A U
REDUNDANCY: The number of lines of shear walls in each principal direction is greater than or equal to 2. (Commentary: Sec. A.3.2.1.1. Tier 2: Sec. 5.5.1.1)
Comments: There are 2 lines of walls in the longitudinal direction and 6 lines of wall in the transverse direction.
C NC N/A U
SHEAR STRESS CHECK: The shear stress in the concrete shear walls, calculated using the Quick Check procedure of Section 4.4.3.3, is less than the greater of 100 lb/in.2 (0.69 MPa) or 2√f’c. (Commentary: Sec. A.3.2.2.1. Tier 2: Sec. 5.5.3.1.1)
Comments: Calculated wall stresses do not exceed the ASCE 41 limit of 126 psi for f’c = 4000 psi. The maximum stress is 106 psi.
C NC N/A U
REINFORCING STEEL: The ratio of reinforcing steel area to gross concrete area is not less than 0.0012 in the vertical direction and 0.0020 in the horizontal direction. (Commentary: Sec. A.3.2.2.2. Tier 2: Sec. 5.5.3.1.3)
Comments: Based on typical wall reinforcing schedule per S.1:
Thickness (in)
Curtains Typ. Hor. and Vert. Reinf.
As (in2) ρ
6 1 #4 @ 12 " 0.2 0.0028 8 1 #4 @ 10 " 0.2 0.0025
10 1 #5 @ 12 " 0.31 0.0026 12 2 #4 @ 12 " 0.2 0.0028 14 2 #5 @ 18 " 0.31 0.0025 16 2 #5 @ 16 " 0.31 0.0024 18 2 #5 @ 14 " 0.31 0.0025 20 2 #5 @ 12 " 0.31 0.0026 24 2 #6 @ 18 " 0.44 0.0020
UC Campus: Berkeley Date: 6/17/2019
Building CAAN: 1802.1 Auxiliary CAAN:
By Firm: RUTHERFORD + CHEKENE
Building Name: Zellerbach Playhouse Initials: EGM Checked: BL
Building Address: Core Campus, Berkeley, 94720 Page: 2 of 4
ASCE 41-17
Collapse Prevention Structural Checklist For Building Type C2-C2A
Note: C = Compliant NC = Noncompliant N/A = Not Applicable U = Unknown
Connections
Description
C NC N/A U
WALL ANCHORAGE AT FLEXIBLE DIAPHRAGMS: Exterior concrete or masonry walls that are dependent on flexible diaphragms for lateral support are anchored for out-of-plane forces at each diaphragm level with steel anchors, reinforcing dowels, or straps that are developed into the diaphragm. Connections have strength to resist the connection force calculated in the Quick Check procedure of Section 4.4.3.7. (Commentary: Sec. A.5.1.1. Tier 2: Sec. 5.7.1.1)
Comments: The building has rigid diaphragms.
C NC N/A U
TRANSFER TO SHEAR WALLS: Diaphragms are connected for transfer of seismic forces to the shear walls. (Commentary: Sec. A.5.2.1. Tier 2: Sec. 5.7.2)
Comments: Per the details on S4.4, the top and bottom slab bars are doweled into the concrete walls.
C NC N/A U
FOUNDATION DOWELS: Wall reinforcement is doweled into the foundation with vertical bars equal in size and spacing to the vertical wall reinforcing directly above the foundation. (Commentary: Sec. A.5.3.5. Tier 2: Sec. 5.7.3.4)
Comments: Per Det F/S3.1, wall dowels match vertical wall reinforcement.
High Seismicity (Complete The Following Items In Addition To The Items For Low And Moderate Seismicity)
Seismic-Force-Resisting System
Description
C NC N/A U
DEFLECTION COMPATIBILITY: Secondary components have the shear capacity to develop the flexural strength of the components. (Commentary: Sec. A.3.1.6.2. Tier 2: Sec. 5.5.2.5.2)
Comments: The interior and exterior shear walls are gravity load bearing. There is a few number of gravity columns in Zellerbach playhouse, mainly between the Level 2 (substage area) and Level 3 (stage level). The development of flexural strength in typical gravity columns requires a demand similar to the shear capacity. However, shear-controlled columns have sufficient shear capacity to resist the shear forces induced at a conservative estimate for interstory drift of ½”.
C NC N/A U
FLAT SLABS: Flat slabs or plates not part of the seismic-force-resisting system have continuous bottom steel through the column joints. (Commentary: Sec. A.3.1.6.3. Tier 2: Sec. 5.5.2.5.3)
Comments: No flat slabs are located within the building.
C NC N/A U
COUPLING BEAMS: The ends of both walls to which the coupling beam is attached are supported at each end to resist vertical loads caused by overturning. (Commentary: Sec. A.3.2.2.3. Tier 2: Sec. 5.5.3.2.1)
Comments: No coupling beams are located within the building.
UC Campus: Berkeley Date: 6/17/2019
Building CAAN: 1802.1 Auxiliary CAAN:
By Firm: RUTHERFORD + CHEKENE
Building Name: Zellerbach Playhouse Initials: EGM Checked: BL
Building Address: Core Campus, Berkeley, 94720 Page: 3 of 4
ASCE 41-17
Collapse Prevention Structural Checklist For Building Type C2-C2A
Note: C = Compliant NC = Noncompliant N/A = Not Applicable U = Unknown
Diaphragms (Stiff Or Flexible)
Description
C NC N/A U
DIAPHRAGM CONTINUITY: The diaphragms are not composed of split-level floors and do not have expansion joints. (Commentary: Sec. A.4.1.1. Tier 2: Sec. 5.6.1.1)
Comments: Tiered seating, mezzanine floors, and mezzanine balconies are comprised of stepped floor diaphragms.
C NC N/A U
OPENINGS AT SHEAR WALLS: Diaphragm openings immediately adjacent to the shear walls are less than 25% of the wall length. (Commentary: Sec. A.4.1.4. Tier 2: Sec. 5.6.1.3)
Comments: Walls are located adjacent to stair and shaft openings. At these locations, the wall length matches the opening length. In addition, long walls occur on the south side of the stage and the south exterior wall. which support the high roof. These walls span 43 ft from Level 2 to the low roof with no diaphragms located on either side of the walls.
Flexible Diaphragms
Description
C NC N/A U
CROSS TIES: There are continuous cross ties between diaphragm chords. (Commentary: Sec. A.4.1.2. Tier 2: Sec. 5.6.1.2)
Comments: The building has rigid diaphragms.
C NC N/A U
STRAIGHT SHEATHING: All straight-sheathed diaphragms have aspect ratios less than 2-to-1 in the direction being considered. (Commentary: Sec. A.4.2.1. Tier 2: Sec. 5.6.2)
Comments: The building has rigid diaphragms.
C NC N/A U
SPANS: All wood diaphragms with spans greater than 24 ft (7.3 m) consist of wood structural panels or diagonal sheathing. (Commentary: Sec. A.4.2.2. Tier 2: Sec. 5.6.2)
Comments: The building has rigid diaphragms.
C NC N/A U
DIAGONALLY SHEATHED AND UNBLOCKED DIAPHRAGMS: All diagonally sheathed or unblocked wood structural panel diaphragms have horizontal spans less than 40 ft (12.2 m) and aspect ratios less than or equal to 4-to-1. (Commentary: Sec. A.4.2.3. Tier 2: Sec. 5.6.2)
Comments: The building has rigid diaphragms.
C NC N/A U
OTHER DIAPHRAGMS: Diaphragms do not consist of a system other than wood, metal deck, concrete, or horizontal bracing. (Commentary: Sec. A.4.7.1. Tier 2: Sec. 5.6.5)
Comments: The building has rigid diaphragms.
UC Campus: Berkeley Date: 6/17/2019
Building CAAN: 1802.1 Auxiliary CAAN:
By Firm: RUTHERFORD + CHEKENE
Building Name: Zellerbach Playhouse Initials: EGM Checked: BL
Building Address: Core Campus, Berkeley, 94720 Page: 4 of 4
ASCE 41-17
Collapse Prevention Structural Checklist For Building Type C2-C2A
Note: C = Compliant NC = Noncompliant N/A = Not Applicable U = Unknown
Connections
Description
C NC N/A U
UPLIFT AT PILE CAPS: Pile caps have top reinforcement, and piles are anchored to the pile caps. (Commentary: Sec. A.5.3.8. Tier 2: Sec. 5.7.3.5)
Comments: The foundation consists of spread footings at columns and continuous footings at walls.
APPENDIX C
UCOP Seismic Safety Policy Falling Hazards Assessment
Summary
UC Campus: Berkeley Date: 06/17/2019
Building CAAN: 1802.1 Auxiliary CAAN:
By Firm: Rutherford+Chekene
Building Name: Zellerbach playhouse Initials: EGM Checked: BL
Building Address: Core Campus, Berkeley 94720 Page: 1 of 1
UCOP SEISMIC SAFETY POLICY
Falling Hazard Assessment Summary
Note: P= Present, N/A = Not Applicable
Description
P N/A
Heavy ceilings, features or ornamentation above large lecture halls, auditoriums, lobbies, or other areas where large numbers of people congregate (50 ppl or more)
Comments: Ceiling, catwalk, and lighting grid occur over the stage and auditorium seating. The bracing of
these items is not shown in the available documentation.
P N/A
Heavy masonry or stone veneer above exit ways or public access areas
Comments:
P N/A
Unbraced masonry parapets, cornices, or other ornamentation above exit ways or public access areas
Comments:
P N/A
Unrestrained hazardous material storage
Comments: It is unknown if hazardous materials are stored in this building.
P N/A
Masonry chimneys
Comments:
P N/A
Unrestrained natural gas-fueled equipment such as water heaters, boilers, emergency generators, etc.
Comments: The on-site building contact (electrician) indicated that gas is unlikely; however, this is unconfirmed.
P N/A
Other:
Comments:
P N/A
Other:
Comments:
P N/A
Other:
Comments:
Falling Hazards Risk: High, if the catwalks over auditorium seating or the gridiron over the stage are unbraced.
APPENDIX D
Quick Check Calculations
RUTHERFORD + CHEKENE TIER 1 EVALUATION
Flat Load Tables
Seismic Weight Dead Load
High Roof psf psf Remarks
Roofing, Waterproofing, and Insulation 10 10
Slab 100 100 8" NWC slab.
Beams/girders 37 37 RC girders below 8" slab
MEP 5 5 MEP hung from underside of floor slab
Ceiling, lighting and misc. 2 2 No ceiling is located under the roof
Columns 0 0 The girders are supported by the exterior walls
Partitions 0 0
Total 154 154
Seismic Weight Dead Load
Gridiron psf psf Remarks
Grating 5 5
Steel framing 15 15 Steel subframe
Rigging and Lighting 15 15
MEP 0 0 No additional MEP is supported by the gridiron
Ceiling 0 0 No ceiling is supported by the gridiron
Columns 0 0 The gridiron is hung from the roof framing
Partitions 0 0
Total 35 35
Seismic Weight Dead Load
Low Roof psf psf Remarks
Roofing, Waterproofing, and Insulation 10 10
Slab 100 100 8" NWC slab.
Beams/girders 10 10 Steel girders and steel truss below 8" slab
MEP 5 5 MEP hung from underside of floor slab
Ceiling, lighting and misc. 2 2 No ceiling is located under the roof
Columns 0 0 The girders are supported by the exterior walls
Partitions 0 0
Total 127 127
Seismic Weight Dead Load
LEVEL 5
Typical Floor psf psf Remarks
Flooring 5 5 Floor tiles
Slab 75 75 6" NWC slab.
Beams/girders 17 17 RC girders below 6" slab
MEP 5 5 MEP hung from underside of floor slab
Ceiling, lighting and misc. 4 4 hung from underside of floor slab
Columns 5 0 RC columns
Partitions 5 5
Total 116 111
Seismic Weight Dead Load
LEVEL 5
Metal Deck Floor psf psf Remarks
Metal deck 1 1 18 ga sheet metal deck
Beams/girders 10 10 Steel subframing and hangers
MEP 5 5 MEP hung from underside of floor slab
Ceiling, lighting and misc. 4 4 hung from underside of floor slab
Columns 0 0 No columns occur
Partitions 0 0
Total 20 20
1 - High roof is lcoated above the theater stage at elevation 96'-11". The high roof is located between Gridlines 13.5-16.5/U-Q.
1 - Gridiron grating is located 9 ft below the high roof (Elevation 87'-11"). This area lies above the stage between Gridlines 13.5-16.5/U-Q.
1 - Low roof occurs above workshop, seating area, and lobby area and is at elevation 66'-2" between Gridlines 10-13.5/U-Q and 16.5-23/U-Q.
1 - This load table is applied to the upper part of projection, light, & sound control room and narrow walkway at elevation 57'-2" between Gridlines 16.5-17/U-Q, 21.5-22/U-Q, 16.5-22/U-U.5
and 23.5-24/R.5-Q.
1 - This load table is applied to the catwalk space at elevation 56'-11" between Gridlines 18.5-21/Q.5-T.5.
RUTHERFORD + CHEKENE TIER 1 EVALUATION
Seismic Weight Dead Load
LEVEL 4
North Low Roof psf psf Remarks
Roofing 2 2 Batten seam metal roof
Waterproofing / Insulation 5 5
Slab 75 75 NWC slab, variable thickness -- 6" considered
Beams/girders 38 38 Inclined RC girders below slab
MEP 5 5 MEP hung from underside of floor slab
Ceiling, lighting and misc. 4 4 hung from underside of floor slab
Columns 0 0 No columns occur, girders supported by walls
Partitions 0 0
Total 129 129
Seismic Weight Dead Load
LEVEL 4
North Balcony Floor psf psf Remarks
Waterproofing / Insulation and flooring 5 5
Slab 75 75 6" NWC slab
Beams/girders 29 29 RC girders below 6" slab
MEP 5 5 MEP hung from underside of floor slab
Ceiling, lighting and misc. 4 4 hung from underside of floor slab
Columns 0 0 No columns occur, girders supported by walls
Partitions 0 0
Total 118 118
Seismic Weight Dead Load
LEVEL 4
Tiered Seating psf psf Remarks
Flooring 5 5 Floor tiles
Slab 75 75 6" NWC slab
Walls at slab step 38 38 8" walls typ. at slab steps
Beams/girders 21 21 RC girders below 6" slab
MEP 5 5 MEP hung from underside of floor slab
Ceiling, lighting and misc. 4 4 hung from underside of floor slab
Columns 0 0 No columns occur, girders supported by walls
Partitions 0 0
Total 149 149
Seismic Weight Dead Load
LEVEL 4
Walkways psf psf Remarks
Flooring 5 5 Floor tiles
Slab 145 145 NWC slab, variable thickness -- 6" min and 13" max
Beams/girders 21 21 Inclined RC girders below RC slab
MEP 5 5 MEP hung from underside of floor slab
Ceiling, lighting and misc. 4 4 hung from underside of floor slab
Columns 4 0 RC columns
Partitions 0 0
Total 184 180
Seismic Weight Dead Load
LEVEL 3 TO 5
Corridor Floor psf psf Remarks
Flooring 5 5 Floor tiles
Slab 75 75 6" NWC slab.
Beams/girders 0 0 No girders occur
MEP 5 5 MEP hung from underside of floor slab
Ceiling, lighting and misc. 4 4 hung from underside of floor slab
Columns 0 0 No columns occur
Partitions 5 5
Total 94 94
1 - This load table is applied to the balcony and mezzanine lobby at elevation 44'-2" and 44'-8", respectively between Gridlines 22-26/U-Q.
1 - This load table is applied to the main seating area sloping from elevation 46'-3.5" down to 38'-0.5" between Gridlines 19-21/U-Q.
1 - This load table is applied to the projection, light, & sound control room and narrow walkway at elevations 47'-1" up to 50'-0" between Gridlines 21.5-22/U-Q, 17-22/T.5-U, and 17-22/Q-Q.5.
1 - This load table is applied at levels 3 through 5 for the corridor areas between Gridlines 10.25-21.75/P-Q, and at level 5 for the upper part of the assembly area (elevation 55'-6") and fly
galleries (elevation 57'-2") between Gridlines 13.5-16.5/U-U.5, 13.5-16.5/R.5-Q, 13-13.5/T.5-Q, and 10-13.5/Q-Q.75.
1 - This load table is applied to the metal roof above lobby sloping down to elevation 44'-2" between Gridlines 22-26/U-Q.
RUTHERFORD + CHEKENE TIER 1 EVALUATION
Seismic Weight Dead Load
LEVEL 3 & 4
Typical Floor psf psf Remarks
Flooring 5 5 Floor tiles
Slab 75 75 6" NWC slab.
Beams/girders 59 59 RC girders below 6" slab
MEP 5 5 MEP hung from underside of floor slab
Ceiling, lighting and misc. 4 4 hung from underside of floor slab
Columns 1 0 RC columns
Partitions 0 0
Total 149 148
Seismic Weight Dead Load
LEVEL 3
Workshop Floor psf psf Remarks
Flooring 5 5 Floor tiles
Slab 75 75 6" NWC slab.
Beams/girders 100 100 RC girders below 6" slab
MEP 5 5 MEP hung from underside of floor slab
Ceiling, lighting and misc. 4 4 hung from underside of floor slab
Columns 0 0 No columns, RC girders supported by walls
Partitions 0 0
Equipment 15 15
Total 204 204
Seismic Weight Dead Load
LEVEL 3
Wood Stage Floor psf psf Remarks
Flooring 0.5 0.5 Carpet
Wood slab 1 1 Plywood sheathing (assumed)
Beams/girders 10 10 Steel beams and plates below wood diaphragm
MEP 5 5 MEP hung from underside of floor slab
Ceiling, lighting and misc. 4 4 hung from underside of floor slab
Columns 0.0 0 No columns
Partitions 0 0
Total 21 21
1 - This load table is applied to theater stage traps and theater elevator at elevations 36'-8" and 33'-8" between Gridlines 14-16/R.25-S.75 and 17-18/R.5-S.5.
1 - This load table is applied at level 3 where the main seating area and stage are located at elevations 33'-8" up to 34'-8" between Gridlines 13.5-22/U-Q excluding the theater stage traps and
the stage elevator. This load is also considered at level 4 between Gridlines 9-10/R-Q.
1 - This load table is applied to workshop, corridor, assembly area and workshop vestibule at elevation 36'-4.25" up to 36'-8" between Gridlines 10-13.5/U-Q.
RUTHERFORD + CHEKENE TIER 1 EVALUATION
Story Weight
Floor Levels High Roof Gridiron Low RoofLEVEL 5
Typical Floor
LEVEL 5
Metal Deck
Floor
LEVEL 4
North Low
Roof
LEVEL 4
North
Balcony
Floor
LEVEL 4
Tiered
Seating
LEVEL 4
Walkways
LEVEL 3 TO 5
Corridor
Floor
LEVEL 3 & 4
Typical Floor
LEVEL 3
Workshop
Floor
LEVEL 3
Wood Stage Floor
High Roof 3,186 2,910 0 0 0 0 0 0 0 0 0 0 0
Low Roof 0 0 9,711 0 0 0 0 0 0 0 0 0 0
Level 5 0 0 0 1,703 2,038 0 0 0 0 2,662 0 0 0
Level 4 0 0 0 0 0 3,073 3,170 1,520 1,852 1,269 352 0 0
Level 3 0 0 0 0 0 0 0 0 0 1,233 7,179 2,463 1,274
Level 2
Floor Levels High Roof Gridiron Low RoofLEVEL 5
Typical Floor
LEVEL 5
Metal Deck
Floor
LEVEL 4
North Low
Roof
LEVEL 4
North
Balcony
Floor
LEVEL 4
Tiered
Seating
LEVEL 4
Walkways
LEVEL 3 TO 5
Corridor
Floor
LEVEL 3 & 4
Typical Floor
LEVEL 3
Workshop
Floor
LEVEL 3
Wood Stage Floor
Floor
Elevation
(ft)
Wall height
below floor
level (ft)
Wall height
tributary to
each floor
level
(ft)
Wall Area
below (ft2)
Wall Weight
below (kips)
Wall Seismic
Weight
(kips)
Length (ft)
Trib. Wall
Height
[above &
below]
(ft)
Glass Seismic
Weight (kips)
Additional
Weight
(kips)5
Total Seismic
Weight (kips)
High Roof 154 35 127 116 20 129 118 149 184 94 149 204 21 96.92 30.75 15.37 298 1,375 687 0 15.37 0 48 1,327
Low Roof 154 35 127 116 20 129 118 149 184 94 149 204 21 66.17 9.00 19.87 755 1,020 1,197 5 19.87 1 2,428
Level 5 154 35 127 116 20 129 118 149 184 94 149 204 21 57.17 12.67 10.83 943 1,792 1,406 0 10.83 0 1,894
Level 4 154 35 127 116 20 129 118 149 184 94 149 204 21 44.50 7.83 10.25 906 1,065 1,428 25 10.25 4 2,940
Level 3 154 35 127 116 20 129 118 149 184 94 149 204 21 36.67 13.50 10.67 937 1,898 1,481 0 10.67 0 11 3,204
Level 2 23.2
Total Weight = 11,793
Notes:
1 - The gridiron floor is hung from the roof and its mass is lumped at the roof.
2 - The metal roof on the north side slopes down from Level 5 to Level 4. This seismic weight is lumped at Level 4.
3 - The seismic base is set at Level 2.
4 - Glass weight includes area of exterior windows with an assumed weight of 15 psf.
5 - Additional weight includes cantilever walls on roofs, and elevated wood office in Level 3. The office was assumed to be 35 psf in a 18ft x 18ft area.
6 - The floors have been renamed since the construction drawing as follows:
Floor Elevation Current Name 1965 Drawings
96'-11" High roof Roof
87'-11" Gridiron
Stage House
Gridiron
66'-2" Low roof Roof
57'-2" Level 5 Level 5
44'-6" Level 4 Level 4
36'-8" Level 3 Level 3
23'-2" Level 2 Level 2
Stage Level (36'-8"), Lobby (34'-8")
Sub-stage Area (23'-3"), Paint Shop (22'-6)
Concrete Wall Weight3
Exterior Glass Weight4
Floor Area (ft2)
1
Floor Weight (psf)
Lobby Mezzanine (44'-8'), Top of Tiered Seating (47'-8")
1965 Drawing Section Names
Stage House Roof (96'-11")
Gridiron (87'-11")
Shop Roof and Theater Roof (66'-2"),
Light Gallery (57'-2"), Lower chord of Gridiron (56'-11")
RUTHERFORD + CHEKENE TIER 1 EVALUATION
Period
Ct= 0.02
hn (ft)= 73.75
B= 0.75
T= 0.50 sec
Notes:
1- The period calculated per ASCE 41-17 Equation 4-4.
2- Ct and B are for "all other framing system" per ASCE 41-17 Section 4.4.2.4
3- The building height is taken from Level 2 to the High Roof.
RUTHERFORD + CHEKENE TIER 1 EVALUATION
Site Parameters
Period Sa
0 1.26
0.07 3.15
0.33 3.15
0.58 1.800
0.83 1.260
1.00 1.050
1.25 0.840
1.50 0.700
1.75 0.600
2.00 0.525
2.25 0.467
2.50 0.420
2.75 0.382
3.00 0.350
3.25 0.323
SXS = 3.15 g
SX1 = 1.050 g
To = 0.07 s
Ts = 0.33 s
Sa = 2.086 g
T = 0.50 s
Notes:
1- Site Specific spectral accelerations based upon soil type and rock profile are provided in report "2015 Update to the Site-Specific Seismic Hazard
Analyses and Development of Seismic Design Ground Motions, UC Berkeley, 15 July 2015 by URS Corporation. Procedure as specified in ASCE 7-16,
Section 21.4 is used to develop Design Response Spectrum shown above.
2- At this site, rock is located between 36 - 75 feet below grade based upon the borings from Zellerbach and the adjacent RSF complex.
0
0.5
1
1.5
2
2.5
3
3.5
0 0.5 1 1.5 2 2.5 3 3.5
Sp
ect
ral A
cce
lera
tio
n (
g)
Period (sec)
BSE-2E Response Spectrum
RUTHERFORD + CHEKENE TIER 1 EVALUATION
Seismic Force Distribution
Sa= 2.09
W= 11,793 kips
C= 1.0
Per ASCE 41-17
Table 4-7
V= 24,603 kips
k= 1.00
Floor Levels Story Height Total Height, H Weight, W W x Hk
coeff Fx Story Shear, V
(ft) (ft) (kips) (kips) (kips)
High Roof 30.75 73.75 1,327 98,596 0.26 6,470 6,470
Low Roof 9.00 43.00 2,428 105,081 0.28 6,895 13,365
Level 5 12.67 34.00 1,894 64,775 0.17 4,251 17,616
Level 4 7.83 21.33 2,940 63,031 0.17 4,136 21,752
Level 3 13.50 13.50 3,204 43,442 0.12 2,851 24,603
Level 2
74 11,793 374,925 1 24,603
Notes:
1- Base of building is assumed to be at Level 2 which is at grade.
2- Modification Factor, C, per ASCE 41-17, Table 4-7
Per ASCE 41-17 Section 4.4.2.2, K = 1.0 for periods less than
0.5 sec and K = 2.0 for T >2.5 sec. It varies linearly
inbetween 0.5 sec and 2.5 sec period.
RUTHERFORD + CHEKENE TIER 1 EVALUATION
Average Wall Stress Check Under ASCE 41-13 BSE-2E Site Specific Spectra
Average Stresses
Ms = 4.5
f'c = 4000 psi Based upon the 1965 drawings on Sheet S.1
Story Story Shear Wall Area
Average Shear
Stress
Tier 1 Shear
Stress Limit Wall OK?
(kips) (in2) (psi) (psi)
High Roof - Low Roof 6,470 28,335 51 126 OK
Low Roof - Level 5 13,365 64,236 46 126 OK
Level 5 - Level 4 17,616 70,098 56 126 OK
Level 4 - Level 3 21,752 71,088 68 126 OK
Level 3 - Level 2 24,603 71,118 77 126 OK
Story Story Shear Wall Area
Average Shear
Stress
Tier 1 Shear
Stress Limit Wall OK?
(kips) (in2) (psi) (psi)
High Roof - Low Roof 6,470 14,592 99 126 OK
Low Roof - Level 5 13,365 43,330 69 126 OK
Level 5 - Level 4 17,616 65,725 60 126 OK
Level 4 - Level 3 21,752 58,481 83 126 OK
Level 3 - Level 2 24,603 52,632 104 126 OK
Notes:
1 - Ms factor per ASCE 41-17 Table 4-8
Transverse (E-W direction)
Longitudinal (N-S direction)
RUTHERFORD + CHEKENE TIER 1 EVALUATION
COLUMN DEFORMATION COMPATIBILTY (0.9DL)
Material properties
- Concrete f'c 4 ksi (See Note 1).
- Spiral reinforcement fy 70 ksi (See Note 1).
- Tie reinforcement fy 40 ksi (See Note 1).
Other parameters
- Flexural ductility knl 0.7
- Normal weight concrete λ 1.0
b (in) h (in) AG (in2) D or L (in) AS (in
2) D (in) AV (in
2) fy,t (ksi) d' (in) dc (in)
4 hb (in) L (ft) Ln (in) s/d acol Ln/2dc MU/VUd 6f0.5
/(M/Vd) NUG (k) 5
x (ft) y (ft) Atrib (ft2) (1+N/6Af
0.5)
0.5VS (k) VC (k) Vcol (k)
6MP=0 (k-ft)
7M (k-ft)
7 2M/L (k) Vp/Vcol E (ksi) I g(in4) Δ (in) L (in) Vprob (k)
8Acceptance criteria
9
#Ss-20 (Circ)-2F-8#8 Ss-20 (Circ) 2 20 20 314.2 8 #8 1 8.0 2.0 #3 2.5 0.375 0.22 70 2.38 17.13 118.0 13.5 44.0 0.15 1.0 1.3 2.0 0.19 55 21.1 12.0 253.0 1.2 105.9 57.7 114.5 191.8 219.5 119.7 Shear 1.05 3605.0 7,854.0 0.5 162.0 20.0 OK
#Tt.1-14 (X-Dir)-2F-4#7 Tt.1-14 (X-Dir) 2 12 16 192.0 4 #7 0.875 3.1 2.0 #3 12 0.375 0.22 40 2.38 13.19 20.0 13.5 142.0 0.91 0.4 5.4 4.0 0.09 33 18.0 28.6 515.3 1.2 3.5 17.6 14.7 68.7 84.6 14.3 Flexure 0.97 3605.0 4,096.0 0.5 162.0 10.4 -
#Tt.1-14 (X-Dir)-2F-4#7 Tt.1-14 (X-Dir) 2 16 12 192.0 4 #7 0.875 3.1 2.0 #3 12 0.375 0.22 40 2.38 9.19 20.0 13.5 142.0 1.31 0.0 7.7 4.0 0.09 33 18.0 28.6 515.3 1.2 0.0 17.6 12.3 51.6 62.4 10.5 Flexure 0.86 3605.0 2,304.0 0.5 162.0 5.9 -
Notes:
1 - Per general notes on sheet S1 in 1965 drawings, concrete compressive strength of 4,000 psi is defined for concrete Class V; steel yielding strength is 70 ksi for spiral reinforcing (ASTM A82), and 40 ksi for tie reinforcing (intermediate grade).
2 - Column dimensions are based on column schedule on Sheet S5.15 in 1965 Structural Drawings. For analysis, all the columns extend from Level 2 (substage area, EL. 23'-2") to the Level 3 (stage level, EL. 36'-8")
3 - For the rectangular column:
X-Dir of analysis represents the shear force acting in the longitudinal direction; the bending moment capacity is calculated about the weak axis.
Y-Dir of analysis represents the shear force acting in the transverse direction; the bending moment capacity is calculated about the strong axis.
4 - Effective depth, d, is computed as the distance from extreme compression fiber to centroid of tension reinforcement.
5 - Based on 0.9DL. Circular Ss-20 column is carrying self-weight of the 9-10" deep T-3.12 concrete beam.
6 - Shear capacity of column is based on ASCE 41-17 Eq 10-3 using nominal material strengths with φ =1.0.
acol = 1.0 for s/d <= 0.75, 0.0 for s/d >=1.0
7 - Plastic moment capacity of the column is based upon expected flexural strength using 1.5 f'c and 1.25 fy.
8 - Shear induced due to drift of a fixed-fixed column.
9- Vprob is compared to Vcol. If Vprob <Vcol, Shear failure is not likely to occur.
spColumn
Model
Col Location
(Column Type)Level
SIZE2,3 LONGITUDINAL ADDITIONAL CHECK (LIMITED BY DRIFT)SHEAR/FLEX.
CONTROLn-# n - # - s (in)
DIMENSION CONFINEMENT FLEX. YIELD AXIAL SHEAR FLEXURETRANVERSE
RUTHERFORD + CHEKENE TIER 1 EVALUATION
COLUMN DEFORMATION COMPATIBILTY (1.1DL+0.275LL)
Material properties
- Concrete f'c 4 ksi (See Note 1).
- Spiral reinforcement fy 70 ksi (See Note 1).
- Tie reinforcement fy 40 ksi (See Note 1).
Other parameters
- Flexural ductility knl 0.7
- Normal weight concrete λ 1.0
b (in) h (in) AG (in2) D or L (in) AS (in
2) D (in) AV (in
2) fy,t (ksi) d' (in) dc (in)
4 hb (in) L (ft) Ln (in) s/d acol Ln/2dc MU/VUd 6f0.5
/(M/Vd) NUG (k) 5
x (ft) y (ft) Atrib (ft2) (1+N/6Af
0.5)
0.5VS (k) VC (k) Vcol (k)
6MP=0 (k-ft)
7M (k-ft)
7 2M/L (k) Vp/Vcol E (ksi) I g(in4) Δ (in) L (in) Vprob (k)
8Acceptance criteria
9
#Ss-20 (Circ)-2F-8#8 Ss-20 (Circ) 2 20 20 314.2 8 #8 1 8.0 2.0 #3 2.5 0.375 0.22 70 2.38 17.13 118.0 13.5 44.0 0.15 1.0 1.3 2.0 0.19 69 21.1 12.0 253.0 1.3 105.9 59.9 116.0 191.8 226.5 123.5 Shear 1.06 3605.0 7,854.0 0.5 162.0 20.0 OK
#Tt.1-14 (X-Dir)-2F-4#7 Tt.1-14 (X-Dir) 2 12 16 192.0 4 #7 0.875 3.1 2.0 #3 12 0.375 0.22 40 2.38 13.19 20.0 13.5 142.0 0.91 0.4 5.4 4.0 0.09 54 18.0 28.6 515.3 1.3 3.5 19.3 15.9 68.7 94.9 16.0 Shear 1.01 3605.0 4,096.0 0.5 162.0 10.4 OK
#Tt.1-14 (X-Dir)-2F-4#7 Tt.1-14 (X-Dir) 2 16 12 192.0 4 #7 0.875 3.1 2.0 #3 12 0.375 0.22 40 2.38 9.19 20.0 13.5 142.0 1.31 0.0 7.7 4.0 0.09 54 18.0 28.6 515.3 1.3 0.0 19.3 13.5 51.6 69.4 11.7 Flexure 0.87 3605.0 2,304.0 0.5 162.0 5.9 -
Notes:
1 - Per general notes on sheet S1 in 1965 drawings, concrete compressive strength of 4,000 psi is defined for concrete Class V; steel yielding strength is 70 ksi for spiral reinforcing (ASTM A82), and 40 ksi for tie reinforcing (intermediate grade).
2 - Column dimensions are based on column schedule on Sheet S5.15 in 1965 Structural Drawings. For analysis, all the columns extend from Level 2 (substage area, EL. 23'-2") to the Level 3 (stage level, EL. 36'-8")
3 - For the rectangular column:
X-Dir of analysis represents the shear force acting in the longitudinal direction; the bending moment capacity is calculated about the strong axis.
Y-Dir of analysis represents the shear force acting in the transverse direction; the bending moment capacity is calculated about the weak axis.
4 - Effective depth, d, is computed as the distance from extreme compression fiber to centroid of tension reinforcement.
5 - Based on 1.1DL+0.275LL. Circular Ss-20 column is carrying self-weight of the 9-10" deep T-3.12 concrete beam.
6 - Shear capacity of column is based on ASCE 41-17 Eq 10-3 using nominal material strengths with φ =1.0.
acol = 1.0 for s/d <= 0.75, 0.0 for s/d >=1.0
7 - Plastic moment capacity of the column is based upon expected flexural strength using 1.5 f'c and 1.25 fy.
8 - Shear induced due to drift of a fixed-fixed column.
9- Vprob is compared to Vcol. If Vprob <Vcol, Shear failure is not likely to occur.
SHEAR/FLEX.
CONTROLn-# n - # - s (in)
ADDITIONAL CHECK (LIMITED BY DRIFT)DIMENSION CONFINEMENT FLEX. YIELD AXIAL SHEAR FLEXURETRANVERSE spColumn
Model
Col Location
(Column Type)Level
SIZE2,3 LONGITUDINAL