E S S E N T I A L S A F E T Y M E A S U R E S M A I N T E N A N C E M A N U A L • B U I L D I N G C O M M I S S I O N

F O R E W O R D

Foreword by the Building Commissioner

Essential saety measures are central to ensuring a sae and healthy built environment in Victoria, and theirmaintenance is vital or the lie, saety and health o occupants over a building’s lietime.

To this end, the Building Regulations 2006 regulate to ensure adequate levels o fre saety and protectiono people in a building or place o public entertainment.

It is important that all those with responsibilities in owning, managing and operating buildings – large orsmall – are ully aware o, and understand, their responsibilities in the ongoing maintenance o the essentialsaety measures in their buildings.

It is the role of the Building Commission to ensure the safety, liveability and sustainability of Victoria’s builtenvironment, and the Essential Saety Measures Maintenance Manual sets out in detail what is required andwithin what parameters building owners and managers must work to meet their regulatory obligations.

This ourth edition o the manual has been designed to be easy-to-use: it is set out in our sections,within which comprehensive inormation is provided on each essential saety measure. It is also availablein electronic form, with a CD-ROM in a plastic sleeve inside the folder.

It is not expected that owners or building property managers will need to read the entire manual. The oursections are clearly defned, enabling users to identiy and read only those parts o the manual, includingparts o individual saety measures, that are relevant to their building’s essential saety measures needs.

It is important or all building owners and managers to be inormed o their obligations regardingmaintenance of the essential safety measures in their buildings. Good maintenance practice of buildingsnot only makes good sense rom a health and saety point o view, it is also a good risk-managementbusiness decision.

Tony Arnel

Building Commissioner

Page 3: Essential Safety Maintenance Manual

8/3/2019 Essential Safety Maintenance Manual

http://slidepdf.com/reader/full/essential-safety-maintenance-manual 3/290

Page 4: Essential Safety Maintenance Manual

8/3/2019 Essential Safety Maintenance Manual

http://slidepdf.com/reader/full/essential-safety-maintenance-manual 4/290

E S S E N T I A L S A F E T Y M E A S U R E S M A I N T E N A N C E M A N U A L • B U I L D I N G C O M M I S S I O N

I N T R O D U C T I O N / P A G E 1

Introduction

What is contained in this manual?

The Essential Saety Measures Maintenance Manual is designed to aid building owners, building property managers and other

persons interested in the regulatory requirements relating to maintenance o essential saety measures.

The manual provides detailed inormation on each essential saety measure listed in Part 12 o the Building Regulations 2006.It has been divided into our parts:

• Part0–BuidingCodeofAutraia–Ueofaternativeoutionandtheiraociatedmaintenancerequirement

• Part1–Buidingcontructedfrom1May2004

Building Fire Integrity

Means o Egress

Signs

Lighting

Fire-Fighting Services and Equipment

Air Handling Systems

Automatic Fire-Detection and Alarm Systems

Occupant Warning Systems

Lits

Standby Power Supply Systems

Building Clearance and Fire Appliances

Other Measures

Building Use and Application

• Part2–Buidingcontructedbetween1Juy1994and30Apri2004

Egress and Access

Electrical Services

Fire-Detection and Suppression Equipment

Fire-Resistance

Mechanical Services

• Part3–Buidingcontructedpriorto1Juy1994

• Appendice

Appendix A – Annual essential saety measures report

Appendix B – Building Regulations 2006 Extract, Part 12 – Maintenance

Appendix C – Sample Log Sheets

Page 5: Essential Safety Maintenance Manual

8/3/2019 Essential Safety Maintenance Manual

http://slidepdf.com/reader/full/essential-safety-maintenance-manual 5/290

E S S E N T I A L S A F E T Y M E A S U R E S M A I N T E N A N C E M A N U A L • B U I L D I N G C O M M I S S I O N

I N T R O D U C T I O N / P A G E 2

This manual provides the ollowing inormation:–

• Reference clause of the Building Code o Australia (BCA) 1990 where applicable

• The performance requirement of BCA 1996 and later published versions up to BCA 2007, including the deemedto satisy clause where applicable

• The relevant Australian Standard for installation and maintenance (if applicable)

• A brief description of the purpose, equipment, requirements and method of operation

• Recommendations on maintenance programs and record-keeping.

Where a relevant building surveyor has approved the installation of an essential safety measure based on a performancerequirement i.e. BCA 2006 Volume 1 Perormance Clause CP1, then he or she may speciy on the occupancy permit orin writing where no occupancy permit is required, a differing or additional level of maintenance. Differing or additionalmaintenance may include additional maintenance procedures specifc to that saety measure or prescribed maintenanceto comply with another country’s building codes or standards.

hoW to use this manual

As noted above, the manual is set out in our sections in which comprehensive inormation is provided on each essential saetymeasure. It is not expected that owners or building property managers would need to read this manual rom cover to cover.The manual is set out so that each part may be read individually or an owner or building manager may only read the relevantpart or an individual essential saety measure without the need to read the entire section.

Page 6: Essential Safety Maintenance Manual

8/3/2019 Essential Safety Maintenance Manual

http://slidepdf.com/reader/full/essential-safety-maintenance-manual 6/290

E S S E N T I A L S A F E T Y M E A S U R E S M A I N T E N A N C E M A N U A L • B U I L D I N G C O M M I S S I O N

I N T R O D U C T I O N / P A G E 3

V I C T O R I A ’ s B U I l D I N G l E G I s l A T I O N

What is the building legislation system in Victoria?

Victoria’s building legislation system was set up under a Victorian Act o Parliament, the Building Act 1993 (the Act). It has

developed into a leading model or other Australian States and Territories, as well as or other countries.

The Act introduced major changes in building control to improve the Victorian building industry. Of particular note, the  Act introduced the concept o building permit approvals by private building surveyors. It also introduced compulsory registrationand insurance or builders and certain other categories o building practitioners.

These innovations have been designed to assist building owners, building surveyors and other industry practitioners to producebuildings that are sae, liveable and energy-efcient in a cost-eective and timely manner or all Victorians.

What legislation goVerns building actiVity?

All building work must comply with the Act, Building Regulations 2006 (the Regulations) and the Building Code o Australia (theBCA) unless specifcally exempted.

The Act sets out the legal ramework or the regulation o construction o buildings, building standards and maintenance ospecifc building saety eatures in Victoria. The objectives o the  Act include:–

• To establish, maintain and improve standards for the construction and maintenance of buildings

• To facilitate the adoption and efcient application of national uniform building standards and the accreditation ofbuilding products

• To enhance the amenity of buildings and protect the safety and health of people who use buildings

• To facilitate and promote the cost-effective construction of buildings

• To provide an efcient and effective system for issuing building and occupancy permits.

The Regulations are derived rom the  Act and contain, amongst other things, the requirements relating to building permits,building inspections, occupancy permits, enorcement o the Regulations and maintenance o buildings. The Regulations call up

the BCA as a technical reerence that must be complied with, giving it legal status.The BCA is produced and maintained by the Australian Building Codes Board on behalf of the Commonwealth Government andeach State and Territory Government. It is a uniform set of technical provisions for the design and construction of buildings andother structures. It is ully perormance-based and includes minimal state variations. A perormance-based approach defnesthe way o achieving a specifed outcome without prescribing a particular method.

Page 7: Essential Safety Maintenance Manual

8/3/2019 Essential Safety Maintenance Manual

http://slidepdf.com/reader/full/essential-safety-maintenance-manual 7/290

E S S E N T I A L S A F E T Y M E A S U R E S M A I N T E N A N C E M A N U A L • B U I L D I N G C O M M I S S I O N

I N T R O D U C T I O N / P A G E 4

Hierarchyofbuidingcontrodocument  

BuidingAct1993

Policy prepared by the State Government in consultation withthe Building Commission and approved by State Parliament.Enforced and administered by the Building Commission/LocalGovernment/building surveyors.

BuidingReguation2006

Prepared by the Building Commission and approved by StateGovernment. Enforced and administered by the BuildingCommission/Local Government and building surveyors.

BuidingCodeofAutraia

Prepared by the Australian Building Codes Board andadministered by States and Territories.

AutraianstandardandotherCode

Prepared by Standards Australia and other organisations andreerenced in the Building Code o Australia.

Miniter’Guideine

Prepared by the Building Commission on behalf of the Minister.

Where does the building commission fit in?

The Building Commission was established on 1 July 1994 by the  Act as a sel-unded body to administer Victoria’s buildingregulation system. Its charter is to serve industry and the community through the development and application o building lawto provide or the cost-eective design, construction and maintenance o healthy, sae, habitable and energy-efcient buildings.

The Commission’s unctions include:

• Reviewing the efciency and effectiveness of the  Act and Regulations;

• Advising the Minister for Planning and the Victorian Government on building matters;

• Registering building practitioners;

• Monitoring the conduct and ability of registered building practitioners;

• Providing building product accreditation;

• Determining disputes and appeals arising from the  Act;

• Monitoring a system of levy collection;

• Informing industry of changes to building legislation; and

• Providing comprehensive information on building activity.

Page 8: Essential Safety Maintenance Manual

8/3/2019 Essential Safety Maintenance Manual

http://slidepdf.com/reader/full/essential-safety-maintenance-manual 8/290

E S S E N T I A L S A F E T Y M E A S U R E S M A I N T E N A N C E M A N U A L • B U I L D I N G C O M M I S S I O N

I N T R O D U C T I O N / P A G E 5

The Commission also provides administrative support to our statutory bodies established by the  Act:

The BuidingAdvioryCounciadvises the Minister, through the Commissioner, on the administration and impact o the

legislation and regulations on the building industry and the community, and issues relating to the building permit levy.

The BuidingAppeaBoardcomprises a chairperson and as many other people who have experience in the buildingindustry or matters related to the industry as the Minister considers necessary. The role of the Board is to hear applicationsor modifcations o the Regulations, hear any disputes or appeals arising rom the  Act, including adjoining owner disputes,determine alternative solutions and hear appeals arising from the Building Practitioners Board.

The BuidingPractitionerBoard comprises building practitioners drawn rom major proessional organisations uponthe recommendation o the Minister. It administers the regulation system or building practitioners and monitors theirperormance. It may also make recommendations to the Minister in relation to qualifcations and insurance matters.

The BuidingReguationAdvioryCommittee comprises the Commissioner, architects, builders, building surveyors,engineers, building owners, lawyers, consumers and representatives rom the fre authorities, local government, StateGovernment and the Melbourne City Council. The role of this Committee is to advise the Minister on draft regulations,accredit building products, systems construction methods, designs and components associated with building work.

PriVate sector alternatiVe

Private sector competition has been introduced as an alternative service to that which was exclusively undertaken bycouncils in the past. The Regulations set out how a private or municipal building surveyor carries out these unctions.The Act places obligations on both municipal and private building surveyors in relation to their appointment, the extento their responsibilities and imposes penalties or unproessional conduct.

liability and insurance

The Act limits liability to a period o 10 years commencing rom the date o issue o the occupancy permit or the certifcateo fnal inspection. The  Act also withdraws the common law doctrine o joint and current tort easor liability so thatdeendants will not pay more than their own share o liability. The  Act also makes insurance compulsory for Registered Building

Practitioners (which include engineers, building surveyors, commercial and domestic builders, and draftspersons). The  Act alsorequires that an architect must be insured. This insurance is to be provided in accordance with the requirements set out in aMinisterial Order.

oPtions for councils

Although municipal councils maintain primary responsibility or administering the law, they now have a range o options orinvolvement in the building control system.

Building permit fees are de-regulated and local councils may charge fees that are competitive with the private sector.

What other serVices does the building commission ProVide?

In addition to administering the statutory bodies, the Building Commission organises and conducts seminars for the buildingindustry in relation to the development and amendment o the BCA, the Act and the Regulations.

The Building Commission also publishes a number of documents which cover items of general interest such asorthcoming seminars, proposed regulatory changes etc; Practice Notes, which provide clarifcation o particular issuesrelating to the Regulations; and Minister’s Guidelines, which relate to fees charged and the functions of private andmunicipal building surveyors.

Building practitioners receive these publications as part of their registration fee. Other people interested in obtainingthe Commission’s publications should telephone (03) 9285 6400 or visit the Building Commission website atwww.buildingcommission.com.au

Page 9: Essential Safety Maintenance Manual

8/3/2019 Essential Safety Maintenance Manual

http://slidepdf.com/reader/full/essential-safety-maintenance-manual 9/290

E S S E N T I A L S A F E T Y M E A S U R E S M A I N T E N A N C E M A N U A L • B U I L D I N G C O M M I S S I O N

I N T R O D U C T I O N / P A G E 6

Where can a coPy of the building legislation be obtained?

The Act, Regulations and other statutory publications are published in hard copy and electronically.

They can be purchased rom:

• Anstat Pty Ltd on (03) 9278 1144

• Information Victoria on 1300 366 356

An electronic copy o the  Act or Regulations can be obtained by accessing the Statute Book on the Victorian Legislationand Parliamentary Documents homepage www.dms.dpc.vic.gov.au

The Minister’s Guidelines are available from the Building Commission’s website www.buildingcommission.com.au

The BCA can be obtained from CanPrint Communications on (02) 6295 4422 or email [email protected]

The Australian Standards can be purchased from Standards Australia on 1300 654 646 or www.saiglobal.com/shop

Page 10: Essential Safety Maintenance Manual

8/3/2019 Essential Safety Maintenance Manual

http://slidepdf.com/reader/full/essential-safety-maintenance-manual 10/290

E S S E N T I A L S A F E T Y M E A S U R E S M A I N T E N A N C E M A N U A L • B U I L D I N G C O M M I S S I O N

I N T R O D U C T I O N / P A G E 7

E s s E N T I A l s A F E T Y M E A s U R E s

What are essential safety measures?

Essential saety measures are the fre, lie saety and health items installed or constructed in a building to ensure adequate

levels o fre saety and protection rom such things as Legionella over the lie o the building.

Essential saety measures include all traditional building fre services such as sprinklers and mechanical services etc., but alsoinclude passive fre saety such as fre doors, fre-rated structures and other building inrastructure items such as paths o travelto exits.

An essential saety measure, or the purpose o the Regulations, is provided or the saety o people in a building or place opublic entertainment.

The term ‘essential saety measure’ has been defned in the Regulations as including:–

1. Saety measures as listed in Table I1.1 to I1.11, excluding artifcial lighting contained in Table I1.4, o the BCA Volume 1;

2. Mechanical ventilation systems, hot water or cooling systems;

3. Any other item listed as an essential saety measure (e.g. result o alternative solution); and 

4. Essential service as defned under the Building Regulations 1994 (Previous Regulations).

This defnition o essential saety measure is sel-explanatory and encompasses the industry practice o reerring to all saetymeasures, essential services, saety fttings, and equipment under the one defnition o essential saety measures. You will notethat Table I1.12, I1.13 and articial lighting under Table I1.4 of the BCA are not included.

Why do they need to be maintained?

The objective o maintenance is to ensure that every essential saety measure continues to perorm at the same level ooperation that existed at the time o commissioning and issue o the occupancy permit.

The maintenance o essential saety measures involves:–

• Ensuring the service is maintained at a level of performance specied by the relevant building surveyor (RBS)(usually to the BCA or an Australian Standard);

• Periodical inspections and checks in accordance with an Australian Standard or other specied method; and

• Maintaining a record of the maintenance inspections and checks in the form of an annual ’essential safetymeasures report’.

Reasons or ensuring maintenance o various services:–

• General wear and tear — i.e. electro-magnetic hold-open devices on re doors, shut down of air conditioning systemin fre situation, replacement o emergency lighting batteries and tubes;

• Reliability of a system operating — i.e. sprinkler system, mechanical ventilation system (used as a smoke hazardmanagement system), early warning and intercommunication system;

• Faults after commissioning of a system — i.e. emergency power supply; and

• General housekeeping — i.e. ensure paths of travel to exits are not obstructed, re-protective coverings aremaintained, portable fre extinguishers remain in place.

Page 11: Essential Safety Maintenance Manual

8/3/2019 Essential Safety Maintenance Manual

http://slidepdf.com/reader/full/essential-safety-maintenance-manual 11/290

E S S E N T I A L S A F E T Y M E A S U R E S M A I N T E N A N C E M A N U A L • B U I L D I N G C O M M I S S I O N

I N T R O D U C T I O N / P A G E 8

What buildings require maintenance of essential safety measures?

The maintenance of essential safety measures applies to Class 1b, 2, 3, 5, 6, 7, 8, and 9 buildings as dened in the BCA Volume

1. These classications include multi-storey residential buildings, hotels/motels, ofces, shops, warehouses, factories andhospitals/public buildings respectively.

Buildings are classied in the BCA Volume 1 as ollows:

Ca1: one or more buildings, which in association constitute:–

(a) Ca1a – a single dwelling being –

(i) a detached house; or

(ii) one of a group of two or more attached dwellings, each being a building, separated by a re-resisting wall,including a row house, terrace house, town house or villa unit; or

(b) Ca1b – a boarding house, guest house, hostel or the like –

(i) with a total area of all oors not exceeding 300 m2

measured over the enclosing walls o the Class 1b; and(ii) in which not more than 12 persons would ordinarily be resident,

which is not located above or below another dwelling or another class o building other than a private garage.

Ca2: a building containing two or more sole-occupancy units, each being a separate dwelling.

Ca3: a residential building, other than a building o Class 1 or 2, which is a common place o long-term or transientliving or a number o unrelated persons, including:–

(a) a boarding-house, guest house, hostel, lodging-house or backpackers accommodation; or

(b) a residential part of a hotel or motel; or

(c) a residential part of a school; or

(d) accommodation for the aged, children or people with disabilities; or

(e) a residential part of a health-care building which accommodates members of staff; or

(f) a residential part of a detention centre.

Ca4: a dwelling in a building that is Class 5, 6, 7, 8 or 9, if it is the only dwelling in the building.

Ca5: an ofce building used for professional or commercial purposes, excluding buildings of Class 6, 7, 8 or 9.

Ca6: a shop or other building or the sale o goods by retail or the supply o services direct to the public, including:–

(a) an eating room, cafe, restaurant, milk or soft-drink bar; or

(b) a dining room, bar, shop or kiosk part of a hotel or motel; or

(c) a hairdresser’s or barber’s shop, public laundry, or undertaker’s establishment; or(d) market or sale room, showroom, or service station.

Ca7: a building which is:–

(a) Ca7a – a car park; or

(b) Ca7b – or storage, or display o goods or produce or sale by wholesale.

Ca8: a laboratory, or a building in which a handicrat or process or the production, assembling, altering, repairing, packing,fnishing, or cleaning o goods or produce is carried on or trade, sale, or gain.

Page 12: Essential Safety Maintenance Manual

8/3/2019 Essential Safety Maintenance Manual

http://slidepdf.com/reader/full/essential-safety-maintenance-manual 12/290

E S S E N T I A L S A F E T Y M E A S U R E S M A I N T E N A N C E M A N U A L • B U I L D I N G C O M M I S S I O N

I N T R O D U C T I O N / P A G E 9

Ca9: a building o a public nature:–

(a) Ca9a – a health-care building, including those parts o the building set aside as a laboratory; or

(b) Ca9b – an assembly building, including a trade workshop, laboratory or the like in a primary or secondary school,but excluding any other parts o the building that are o another Class; or

(c) Ca9c– an aged-care building.

Ca10: a non-habitable building or structure:–

(a) Ca10a – a non-habitable building being a private garage, carport, shed, or the like; or

(b) Ca10b – a structure being a ence, mast, antenna, retaining or ree-standing wall, swimming pool, or the like.

The maintenance provisions o Part 12 o the Regulations are divided into two divisions: Division 1 outlines the requirementsfor maintenance of essential safety measures and Division 2 outlines the maintenance and operation requirements forswimming pools and spas.

Division 1 is further divided into three subdivisions:–

• Subdivision 1 deals with the maintenance of essential safety measures, as determined by the relevant buildingsurveyor, in buildings where building work is, or has been, carried out under the  Act on or after 1 July 1994 and forClass 4 buildings after 14 June 2005.

Excluded from the application are smoke alarms to dwellings in Class 1b, 2, and 4 part of a building.

• Subdivision 2 outlines the maintenance of essential safety measures for buildings and places of public entertainmentconstructed before 1 July 1994.

• Subdivision 3 sets out the requirements for maintenance of exits and paths of travel relating to buildings or places ofpublic entertainment.

Page 13: Essential Safety Maintenance Manual

8/3/2019 Essential Safety Maintenance Manual

http://slidepdf.com/reader/full/essential-safety-maintenance-manual 13/290

E S S E N T I A L S A F E T Y M E A S U R E S M A I N T E N A N C E M A N U A L • B U I L D I N G C O M M I S S I O N

I N T R O D U C T I O N / P A G E 1 0

buildings built on and after 1 July 1994

Part 5 of the Building Act 1993 (the Act) sets out the requirements for occupation of buildings and places of public entertainment.

Among other things this Part specifcally details when occupancy permits are required and the orm and eect o those permits.This Part also details the decision-making responsibilities of the relevant building surveyor (RBS). Most importantly Section 40o the Act requires that a person must not occupy a building in contravention o the occupancy permit. This also includes anyconditions, such as the requirements o maintenance, that occupation may be subject to. There are substantial penalties whichmay be applied, such as 100 penalty units for a person and 500 penalty units for a body corporate, where contravention of the

 Act occurs.

The current regulations have made it mandatory for the RBS to list the required essential safety measures on the occupancypermit. The level o perormance to which the service is to be maintained must also be specifed on the occupancy permit.In the case of an essential safety measure being provided where no occupancy permit is required, the RBS must determinethe level o perormance which must be specifed in writing and given to the owner.

The Regulations require that the owner:–

(a) Display in an approved location a copy of an occupancy permit including any conditions required under

regulation 1008;

(b) Prepare an annual essential safety measures report in accordance with regulation 1209 before each anniversary of thedate of occupancy permit or determination made under regulation 1204; and

(c) Keep all annual essential safety measures reports and records of maintenance checks, service and repair work on thepremises or inspection by the municipal building surveyor or chie ofcer at any time on request.

The carrying out o maintenance procedures is dependent on the complexity o the service and the experience o the personcarrying out the inspection. Systems may be maintained where appropriate by the owner, service installer, maintenancecontractor or internal maintenance personnel. Where the owner appoints a person to undertake the maintenance they mustensure that the person is appropriately qualifed and competent to undertake the work.

It is the purpose o this manual to aid in the understanding, preparation and completion o an essential saety measures report.An example o an essential saety measures report is included in Appendix A.

Whoiacompetentperon?

Owners may appoint a person in certain situations to undertake maintenance, testing, or preparation of the annual report.An owner must ensure that the person they appoint is suitably qualifed and competent in the task that they are perorming.

A competent person is a person who has acquired – through training, qualication or experience (or a combination of them)– the knowledge and skills enabling the person to perorm the task correctly. In the context o this manual, that person wouldneed to be competent in inspecting, testing and maintaining essential safety measures. Whoever is responsible for ensuring aparticular task is carried out must determine that the person engaged to carry out that task is competent to do so.

In determining a person’s competency, due consideration must be given to their qualifcations, the training they have receivedrelevant to the task at hand, and their previous experience in doing similar tasks. Some tasks, or example electrical orplumbing installation, inspection and testing, will require a particular competence, such as a formal qualication and/or licence.Therefore, a qualied and licensed person can only undertake such work. Where other tasks can be carried out by a ‘competentperson’ who does not have ormal qualifcations, such a person must still be able to demonstrate they have the necessarytraining, qualication or experience, (or a combination of them), to carry out the inspecting and testing task in acompetent manner.

buildings built before 1 July 1994

The Regulations require the maintenance o saety equipment, saety fttings and saety measures within existing buildingsbuilt prior to 1 July 1994. These items are dened as essential safety measures, similar to those requirements for buildingsbuilt (issued with occupancy permits) on and after 1 July 1994.

The owner is responsible or ensuring that the saety equipment, saety fttings and saety measures are maintained in a statethat enables them to ulfl their purpose.

The saety equipment, saety fttings and saety measures that are to be maintained are the items installed or constructed inthe building that were required by the Regulations at the time o construction. These will typically be similar to those listed asessential saety measures.

O W N E R ’ s R E s P O N s I B I l I T Y

Page 14: Essential Safety Maintenance Manual

8/3/2019 Essential Safety Maintenance Manual

http://slidepdf.com/reader/full/essential-safety-maintenance-manual 14/290

E S S E N T I A L S A F E T Y M E A S U R E S M A I N T E N A N C E M A N U A L • B U I L D I N G C O M M I S S I O N

I N T R O D U C T I O N / P A G E 1 1

The Regulations require that the owner of a building built prior to 1 July 1994:–

a) Prepare an annual essential safety measures report in accordance with regulation 1209 before each anniversary of the

date of occupancy permit or determination made under regulation 1215; andb) Keep all annual essential safety measures reports and records of maintenance checks, service and repair work on the

premises or inspection by the municipal building surveyor or chie ofcer at any time on request.

Maintenanceofexit

Occupiers are also responsible for the maintenance of exits and paths of travel to exits. The exit paths must be “...maintained in an efcient condition and kept readily accessible, unctional and clear o obstruction so that egress rom the building or 

 place is maintained ”; that is, to ensure proper housekeeping o the paths o travel to exits and keep exit doors and doorhardware unctioning.

Maintenanceandinpectionrecord

The Regulations do not speciy a level o documentation to be kept by the owner. It is recommended that records omaintenance should be completed and made available to the building owner or agent at the time o conducting the systemand equipment maintenance.

It is recommended that records should contain the ollowing inormation:

a) Record reference.

b) Name of building or site.

c) Address of building or site.

d) Date of maintenance/inspection.

e) System or equipment identication and location (Possibly a location plan).

f) Frequency of maintenance activity undertaken.

g) Defects identied.

h) Name of property owner or the agent.

i) Name and signature of the service person.

  j) Date the record was completed.

Formofrecord

I a person, such as a building surveyor, has been used to inspect and nominate essential saety measures, that person shouldprovide advice as to the level o record-keeping required to satisy the level and requency o maintenance, but as a minimumshould include the inormation provided above.

Maintenance records may be electronically based. Hard copy records should be kept on site and be available at all times.Technology in regard to the preparation o maintenance records has advanced considerably in recent years with the advent opurpose-designed sotware. As a minimum, hard copy o records o maintenance are to be made available to organisations suchas regulators, fre authorities, insurance surveyors, fre auditors, etc. at all times. However, the hard copy records required maybe prepared utilising electronic recording systems and this manual acknowledges such technology is designed to deliver anaccurate, accountable, consistent and timely level o service.

Maintenance records can be in the form of maintenance record tags (in the case of hydrant landing valves, hose reels, portableand wheeled re extinguishers and re blankets), or log books (in the case of sprinkler, pumpset, re hydrant, detection, smokeand heat alarm, fre alarm monitoring, sound, intercom, gaseous, aerosol, water mist, passive fre and smoke and HVAC andevacuation systems).

The use o maintenance record tags or labels shall not preclude the need or a separate maintenance record system.

Page 15: Essential Safety Maintenance Manual

8/3/2019 Essential Safety Maintenance Manual

http://slidepdf.com/reader/full/essential-safety-maintenance-manual 15/290

E S S E N T I A L S A F E T Y M E A S U R E S M A I N T E N A N C E M A N U A L • B U I L D I N G C O M M I S S I O N

I N T R O D U C T I O N / P A G E 1 2

Where log books are used they shall have sequentially numbered pages in triplicate. Provision shall be made for the signatureso the building owner, occupier or agent, and the service person. The required distribution o copies shall be printed on eachpage as ollows:–

a) Original ...............................................................................owner/occupier/agent

b) Duplicate ............................................................................................ service person

c) Triplicate ...............................................................................................retain in book

Whathappenifanownerdoen’tcompy?

The Regulations prescribe penalties or non-compliance or each breach o the Regulations and this enorcement can beundertaken by the Commissioner, municipal building surveyor or chief ofcer of the relevant re brigade (Metropolitan Fireand Emergency Services Board (MFB) or the Country Fire Authority (CFA) and may issue a building infringement notice (on-the-spot-ne). This applies under Division 5 of Part 13 of the  Act and Part 17 of the Regulations or an oence against:–

• Subdivision 1, regulations 1205, 1207, 1208, 1211; and

• Subdivision 2, regulations 1214, 1216 and 1217; and

• Subdivision 3, regulation 1218.

Where it is suspected that essential safety measures are not being maintained in accordance with the  Act or the Regulations,an inspection may be carried out under Section 227E of the  Act.

A building inringement notice may be issued as a consequence o this inspection. A building inringement notice must beissued in the form of a Form 8 for the purposes of Section 225(2) of the  Act. The notice sets out the prescribed penalty to bepaid and must also indicate the steps required, i any, to rectiy the oence.

Offenceunderubdiviion1:

Inspections o the essential saety measures provided by the building or place o public entertainment may be carried out bythe chief ofcer and the municipal building surveyor either jointly or separately under Section 227E of the  Act to determine

whether they are being maintained in accordance with subdivision 1 o Part 12. Failure to maintain an essential saety measureto the required standard is an offence under Section 40 of the  Act and Part 12 o the Regulations.

Failing to complete the required documentation constitutes an offence under regulations 1205, 1207, 1208, 1209, 1211.This may include:–

• Failure to comply with a maintenance determination.

• Failure to make a maintenance schedule or determination available for inspection.

• Failure to complete an annual essential safety measures report (in accordance with regulation 1208) beforeeach anniversary o the occupancy permit or relevant building surveyor’s determination.

• Failure to keep all essential safety measure reports and records on the premises for inspection purposes.

Offenceunderubdiviion2:

Failure to maintain any saety equipment, saety ftting or essential saety measure in a state that allows it to ulfl its purposeconstitutes an offence under regulations 1214, 1216 and 1217. Removal of any safety equipment, safety tting or essentialsaety measure rom its approved location unless or maintenance purposes in accordance with the Regulations constitutes anoffence under regulations 1214, 1216 and 1217.

Offenceunderubdiviion3

Failure to ensure that exits and paths o travel are maintained in an efcient condition and kept readily accessible, unctionaland clear of obstruction so that egress from the building is maintained constitutes an offence under regulation 1218.An inringement notice issued under this subdivision is issued to occupier; however, it does not prevent inringement noticesbeing issued on the owner or similar issues under subdivision 1 or 2.

However, the greatest concern or building owners is that i essential saety measures and other saety items are notmaintained, then the risk of failure of the item when it is needed (i.e. in an emergency) increases signicantly.

Page 16: Essential Safety Maintenance Manual

8/3/2019 Essential Safety Maintenance Manual

http://slidepdf.com/reader/full/essential-safety-maintenance-manual 16/290

E S S E N T I A L S A F E T Y M E A S U R E S M A I N T E N A N C E M A N U A L • B U I L D I N G C O M M I S S I O N

I N T R O D U C T I O N / P A G E 1 3

Reguatoryrequirement

The regulatory requirements relating to maintenance o essential saety measures are contained in Part 12 o the Regulations.

An extract o Part 12 o the Regulations is provided in Appendix B.

Referenceddocument

Throughout this manual, documents have been reerenced to help owners, managers and the like understand the level oinstallation and the maintenance standards as a guide to the minimum requirements. This manual is not to be used as a stand-alone document and is should be read in conjunction with the appropriate documentation or the saety measure, associatedinstallation and maintenance standards. Owners should make available a copy of these standards or documents to ensure therelevant inormation is available to their agent, service installer, maintenance contractor or internal maintenance personnel.

Cooingtower

The Building (Legionella) Act 2000 requires all cooling tower systems in Victoria to be registered with the Building Commissionto help track potential sources o Legionnaires’ disease. The Building Act 1993 requires the registration o all cooling tower

systems and the development of a Risk Management Plan (RMP) for each cooling tower system.

The Building (Legionella Risk Management) Regulations 2001 speciy the risks that an RMP must address. The Health(Legionella) Regulations 2001 also prescribe maintenance, testing and associated record-keeping relating to a cooling towerand warm water system that a responsible person must comply with. The owner o the land on which a cooling tower systemis located is required to register and renew the registration of that system on an annual basis. Once on the register, theapplication or renewal o registration will be sent to the owner beore the current registration expires each year.

For urther inormation on registering cooling towers, go to www.buildingcommission.com.au

For information on the Legionella Risk Management Project at the Public Health Division, Department of Human Services,go to www.health.vic.gov.au/environment/legionella

Page 17: Essential Safety Maintenance Manual

8/3/2019 Essential Safety Maintenance Manual

http://slidepdf.com/reader/full/essential-safety-maintenance-manual 17/290

E S S E N T I A L S A F E T Y M E A S U R E S M A I N T E N A N C E M A N U A L • B U I L D I N G C O M M I S S I O N

I N T R O D U C T I O N / P A G E 1 4

Acknowedgement

The Building Commission wishes to acknowledge the many individuals and organisations that assisted in the preparation and

review o this manual.

imPortant notice

AllRIGHTsREsERVED

ISBN: 978-0-9577638-9-0

This publication is copyright. No part may be reproduced by any process except in accordance with the provisions o theCopyright Act 1968. Copyright © 1997, 2000, 2007 is to the Building Commission. Published and printed in Melbourne, Victoria.

Inquiries can be made to:

Building Commission PO Box 536 Melbourne Vic 3001 Telephone: (03) 9285 6400 Fax: (03) 9285 6440

Dicaimer

No person should rely on the contents o this publication without frst obtaining independent expert advice rom a qualifedperson.

This publication is made available on the terms and understanding that:

1. The publisher is not responsible or the accuracy o the inormation contained herein.

2. The publisher is not responsible or the results o any actions taken on the basis o any inormation in this publicationnor or any error in or omission rom this publication.

3. The publisher expressly disclaims all and any liability and responsibility to any person whether a purchaser or readero this publication in respect o anything and o the consequences o anything done or omitted to be done by anysuch person in reliance whether wholly or partially, upon the whole or any part o the contents o this publication.

Page 18: Essential Safety Maintenance Manual

8/3/2019 Essential Safety Maintenance Manual

http://slidepdf.com/reader/full/essential-safety-maintenance-manual 18/290

B  ui   l   d i  n g  C  o d  e of  A  u s  t r  a  l  i   a 

Part 0Building Codeof Australia

Page 19: Essential Safety Maintenance Manual

8/3/2019 Essential Safety Maintenance Manual

http://slidepdf.com/reader/full/essential-safety-maintenance-manual 19/290

E S S E N T I A L S A F E T Y M E A S U R E S M A I N T E N A N C E M A N U A L • B U I L D I N G C O M M I S S I O N

P A R T 0 / P A G E 1

Part 0 – Building Code of AustraliaUse o alternative solutions and theirassociated maintenance requirements

summary

This Part considers issues relating to the perormance-based Building Code of Australia (BCA), assessing alternative solutionsand examines the issues relating to maintenance. It also helps to provide owners who may not be amiliar with perormance-based building codes with an explanation in the use o perormance-based alternative solutions.

The perormance-based BCA signifcantly changed the way building regulations were expressed and applied, by introducing amandatory perormance compliance level.

Two processes can be used to achieve compliance: the traditional prescribed requirements i.e. deemed-to-satisy provisions; orsecondly, alternative solutions.

Where it is chosen to use an alternative solution, verication of compliance with the performance reuirements is satisedby appropriate use o assessment methods. This verifcation o compliance with the perormance requirements also includesensuring the appropriate level o maintenance and requency o maintenance is nominated.

the Performance-based system

The structure o the BCA comprises the ollowing:

a) The Objectives.

b) The Functional Statements.

c) The Performance Reuirements to which all building solutions must comply.

d) The Building Solutions.

The Objectives and the Functional Statements may be used as an aid to interpretation. These are informative only to aid in theinterpretation and the intent of the Performance Reuirements and the deemed-to-satisfy provisions. The Objectives set out

the community expectations and the Functional Statements describe how it is proposed that the building will be designed andconstructed to meet those expectations.

A perormance-based approach defnes the way o achieving a specifed outcome, without prescribing a particular method.

alternatiVe solutions

In the BCA, any means o achieving compliance with the Perormance Requirements that is not included in, or diers in anyway from, a deemed-to-satisfy provision, is referred to as an ‘alternative solution’. Designers, when formulating an alternativesolution, may include the use o reerences such as:–

The International Fire Engineering Guidelines published by the Australian Building Codes Board (ABCB).•

The Fire Brigade Intervention Model (FBIM) developed by the Australasian Fire Authorities Council (AFAC).•

An appropriate international standard or code.•

When using an alternative solution, it is important to ensure that it complies with all relevant Performance Reuirementsin the BCA. No BCA provision can be considered in isolation. Any departure rom the deemed-to-satisy provisions or analternative solution needs to be assessed against the relevant Perormance Requirements within the relevant section othe BCA. Additionally, the proposed alternative solution may also impact on other Perormance Requirements in other BCA sections. Thereore these additional Perormance Requirements, including those or maintenance, need to be considered inrelation to alternative solutions. It is important that a holistic approach is used when determining the appropriatePerormance Requirements.

Page 20: Essential Safety Maintenance Manual

8/3/2019 Essential Safety Maintenance Manual

http://slidepdf.com/reader/full/essential-safety-maintenance-manual 20/290

E S S E N T I A L S A F E T Y M E A S U R E S M A I N T E N A N C E M A N U A L • B U I L D I N G C O M M I S S I O N

P A R T 0 / P A G E 2

determining comPliance With the Performance requirements

The following points provide some guidance for the relevant building survey (RBS) and owners when considering the use of

alternative solutions, the documentation required when determining compliance. It would also be prudent or building ownersto retain this inormation:–

Technical supporting evidence which may include drawings, fre engineering reports and technical documentation.•

Reasons why the deemed-to-satisfy provisions can or cannot be met, or why the designer/owner/builder feels they•are or are not suitable. (This ’negative’ reuest is probably necessary for assessment of the application, especially ifusing euivalence to deemed-to-satisfy.)

The building owner’s reuest/consent/approval for use of performance methodology and outcome.•

Statement as to whether design (or part of the design) has used the alternative solution or deemed-to-satisfy•provision. (Without this, it may be difcult for the RBS to assess the application.)

Other points to consider:–

Does this approval process and/or outcome impinge on owner/occupiers’ occupational health and•safety/workplace responsibilities?

Do all the people involved (owner, other consultants, authorities, RBS etc.) understand the design methodology?•(e.g. does it limit future uses of the building, or reuire additional maintenance provisions?)

consideration of assessment methods, including maintenance

Some reasons which, by themselves, may be inappropriate or insufcient to determine compliance with a PerormanceRequirement are:–

Compliance too costly (e.g. cannot be considered euivalent to deemed-to-satisfy, unless tested to deemed-to-satisfy•and testing is too epensive).

Building Appeals Board or other approval body has previously approved a similar application.•Method proposed has been used beore.•

Supporting argument of compliance with other regulatory reuired items (e.g. stair has handrail, therefore riser height•can be increased).

Regulation not required in other States or Territories.•

Approval by epert judgement when Building Appeals Board/council or other approval body might not approve•(e.g. access for people with disabilities, thermal insulation).

Appropriate maintenance specifed or the essential saety measures that relate to the alternative solution.•

Other points for owners, designers and the RBS to consider are:–

Does insurance and that of all others involved in the project allow design/approval to be eercised to the•degree proposed?

When considering building occupants, don’t forget cleaners, maintenance staff, visitors, emergency services•personnel, etc.

Sensitivity analysis. (Has the alternative solution considered variations to the input data and the effect on•the results?)

Available redundancy. (Is there a heavy reliance on a single sub-system, such as sprinklers and the associated•maintenance, so that a failure of that one sub-system may have signicant conseuences?)

Are safety factors to be applied to any calculations (e.g. in egress calculations, a factor of safety of 2–3 might•be applied)?

Page 21: Essential Safety Maintenance Manual

8/3/2019 Essential Safety Maintenance Manual

http://slidepdf.com/reader/full/essential-safety-maintenance-manual 21/290

E S S E N T I A L S A F E T Y M E A S U R E S M A I N T E N A N C E M A N U A L • B U I L D I N G C O M M I S S I O N

P A R T 0 / P A G E 3

Risk/conseuences. (Is the conseuence greater with the proposed solution than if the deemed-to-satisfy provisions•were used?) If conseuences are greater for the proposed alternative solution, then substantial re-checking and justifcation may be required.

Maintenance o the essential saety measures impacted by the alternative solution.•

consideration of maintenance

Where an alternative solution is proposed or used which reuires measures other than those contained within this manualor which reuires a varied order of maintenance than recommended by the manual, the owner/designer must specify as partof the application to the RBS the maintenance reuired to ensure that any essential safety measure assessed as part of thealternative solution is maintained. It is then the responsibility of the RBS, when assessing the alternative solution, to includean assessment on any maintenance proposed.

It is recommended that when the RBS assesses an alternative solution the designer is consulted to determine the appropriatemaintenance requirements and requency.

When an RBS issues an occupancy permit or a certicate of nal inspection, they specify the essential safety measure and itsmaintenance appropriate to the alternative solution. Owners should note that the maintenance may not be to an AustralianStandard, such as AS 1851, but rather to a specic reuirement developed by the designer. An RBS must ensure that the ownero the building is provided with all the necessary documentation to carry out the maintenance o the essential saety measure.This may include:–

Development of a maintenance regime in consultation with the designer.•

Input into the development o maintenance documentation.•

Use o other documentation such international standards and codes.•

Manuacturer-specifc maintenance requirements.•

Development of specic freuencies of maintenance that may be reuired.•

Development of log sheets for owners.•

Owners or maintenance personnel need to be made fully aware of any alternative solutions in a building and themaintenance requirements o the essential saety measures to ensure that the building always remains compliant withthe alternative solution.

Page 22: Essential Safety Maintenance Manual

8/3/2019 Essential Safety Maintenance Manual

http://slidepdf.com/reader/full/essential-safety-maintenance-manual 22/290

Page 23: Essential Safety Maintenance Manual

8/3/2019 Essential Safety Maintenance Manual

http://slidepdf.com/reader/full/essential-safety-maintenance-manual 23/290

B  ui   l   d i  n g  s  c  on s  t r  u c  t  e d 

f  r  om 1 M a  y2  0  0  4 

Part 1Buildings constructedrom 1 May 2004

Building fre integrity

Means o egress

Signs

Lighting

Fire-fghting services and equipment

Air handling systems

Automatic fre-detection and alarm systems

Occupant warning systems

LitsStandby power supply systems

Building clearance and fre appliances

Mechanical ventilation

Page 24: Essential Safety Maintenance Manual

8/3/2019 Essential Safety Maintenance Manual

http://slidepdf.com/reader/full/essential-safety-maintenance-manual 24/290

E S S E N T I A L S A F E T Y M E A S U R E S M A I N T E N A N C E M A N U A L • B U I L D I N G C O M M I S S I O N

P A R T 1 / P A G E 1

As part of the 2004 amendment to the Building Code of Australia (BCA) Volume 1, safety measures were dened and Part Iintroduced a list o saety measures to be maintained.

The intent o Part I o the BCA Volume 1 is to establish the minimum standard o perormance that all saety measures inbuildings must continually be able to achieve.

Part 1 o the BCA Volume 1 currently groups saety measures as ollows:–

Building re integrity•

Means o egress•

Signs•

Lighting•

Fire-fghting services and equipment•

Air handling systems•

Automatic fre detection and alarm systems•

Occupant warning systems•

Lits•

Standby power supply systems•

Building clearance and re appliances•

Other measures•

Building use and application•

Part 2 – Mechanical ventilation and hot water, warm water and cooling water systems.

Currently, the Building Regulations 2006 (the Regulations) outline the relevant tables of Part 1 of the BCA Volume 1 applicablein Victoria as essential saety measures. The applicable essential saety measures are as listed in Tables 1.1 to 1.11, excludingarticial lighting contained in Table 1.4 and Table 1.12 of the BCA. This manual will only deal with those tables as listed above.

maintenance and insPection records

Records o maintenance shall be completed and made available to the building owner or agent at the time o conducting thesystem and equipment maintenance.

Records shall contain the ollowing inormation:–

a) Record reference.

b) Name of building or site.

c) Address of building or site.

d) Date of maintenance/inspection.

e) System or euipment identication and location (Possibly a location plan).

f) Freuency of maintenance activity undertaken.

g) Defects identied.

h) Name of property owner or the agent.

i) Name and signature of the service person.

  j) Date the record was completed.

Part 1 – Buildings constructed from 1 May 2004

Page 25: Essential Safety Maintenance Manual

8/3/2019 Essential Safety Maintenance Manual

http://slidepdf.com/reader/full/essential-safety-maintenance-manual 25/290

E S S E N T I A L S A F E T Y M E A S U R E S M A I N T E N A N C E M A N U A L • B U I L D I N G C O M M I S S I O N

P A R T 1 / P A G E 2

Form oF records

Maintenance records may be electronically-based. Hard copy records shall be kept on site and be available at all times.

Technology in regard to the preparation o maintenance records has advanced considerably in recent years with the advento purpose-designed sotware. As a minimum, hard copy records o maintenance should be made available to regulators, reauthorities, insurance surveyors, re auditors, etc., at all times. However, the hard copy records required may be preparedutilising electronic recording systems, and this manual acknowledges such technology is designed to deliver an accurate,accountable, consistent and timely level o service.

Maintenance records shall be in the orm o maintenance record tags (in the case o hydrant landing valves, delivery lay fathose, hose reels, portable and wheeled re extinguishers and re blankets), or log books (in the case o sprinkler, pumpset, rehydrant, detection, smoke and heat alarm, re alarm monitoring, sound, intercom, gaseous, aerosol, water mist, passive re andsmoke and HVAC and evacuation systems).

The use o maintenance record tags or labels shall not preclude the need or a separate maintenance record system.

Where log books are used they shall have sequentially numbered pages in triplicate. Provision shall be made or the signatureso the building owner, occupier or agent, and the service person. The required distribution o copies shall be printed on each

page as ollows:–

a) Original ............................................................................... owner/occupier/agent

b) Duplicate ............................................................................................ service person

c) Triplicate ...............................................................................................retain in book

Use oF As 1851-2005

Where an essential saety measure has been nominated as using AS 1851-2005 to provide maintenance within this manual,details o the level o records to be kept are incorporated in the maintenance schedules o Sections 2 to 19 o that Standard.Owners should develop log sheets using the maintenance tables provided in that Standard for each essential safety measure.

Where the essential saety measure nominated in this manual does not use AS 1851-2005 as a minimum level o maintenance,log sheets have been developed and are available in Appendix C o this manual.

It should be noted that building surveyors may speciy a level o maintenance not using AS 1851. In this case, the buildingsurveyor should provide advice as to the level o record-keeping required to satisy the level and requency o maintenance,but as a minimum should include the inormation provided above.

Page 26: Essential Safety Maintenance Manual

8/3/2019 Essential Safety Maintenance Manual

http://slidepdf.com/reader/full/essential-safety-maintenance-manual 26/290

Building freintegrity

B  ui   l   d i  n g 

f r  e

i  n t  e g r i   t  y

Page 27: Essential Safety Maintenance Manual

8/3/2019 Essential Safety Maintenance Manual

http://slidepdf.com/reader/full/essential-safety-maintenance-manual 27/290

S E C T I O N 1 / P A G E 1

E S S E N T I A L S A F E T Y M E A S U R E S M A I N T E N A N C E M A N U A L • B U I L D I N G C O M M I S S I O N

B i i n g F i e I n t e g i t

1.1 BUILDING ELEMENTS REqUIRED TO SATISFY pRESCRIBED FIRE-RESISTANCE LEvEL 2

1.2 MATERIALS AND ASSEMBLIES REqUIRED TO SATISFY pRESCRIBED FIRE hAzARD pROpERTIES 3

1.3 ELEMENTS REqUIRED TO BE NON-COMBUSTIBLE, pROvIDE FIRE-pROTECTION,COMpARTMENTATION OR SEpARATION 4

1.4 WALL-WETTING SpRINkLERS (INCLUDING DOORS AND WINDOWS REqUIRED INCONjUNCTION WITh WALL-WETTING SpRINkLERS) 5

1.5 FIRE DOORS (INCLUDING SLIDING FIRE DOORS AND ThEIR ASSOCIATED WARNING SYSTEMS)AND ASSOCIATED SELF-CLOSING, AUTOMATIC CLOSING AND LATChING MEChANISMS 8

1.6 FIRE WINDOWS (INCLUDING WINDOWS ThAT ARE AUTOMATIC OR pERMANENTLYFIxED IN ThE CLOSED pOSITION) 10

1.7 FIRE ShUTTERS 11

1.8 SOLID CORE DOORS AND ASSOCIATED SELF-CLOSING, AUTOMATIC CLOSINGAND LATChING MEChANISMS 12

1.9 FIRE-pROTECTION AT SERvICE pENETRATIONS ThROUGh ELEMENTS REqUIRED TO BE FIRERESISTING WITh RESpECT TO INTEGRITY OR INSULATION, OR TO hAvE A RESISTANCE TOThE INCIpIENT SpREAD OF FIRE 14

1.10 FIRE-pROTECTION ASSOCIATED WITh CONSTRUCTION jOINTS, SpACES AND ThE LIkE INAND BETWEEN BUILDING ELEMENTS REqUIRED TO BE FIRE-RESISTING WITh RESpECT TOINTEGRITY AND INSULATION 15

1.11 SMOkE DOORS AND ASSOCIATED SELF-CLOSING, AUTOMATIC CLOSING ANDLATChING MEChANISMS 16

1.12 pROSCENIUM WALLS (FIRE CURTAINS) 17

Page 28: Essential Safety Maintenance Manual

8/3/2019 Essential Safety Maintenance Manual

http://slidepdf.com/reader/full/essential-safety-maintenance-manual 28/290

S E C T I O N 1 / P A G E 2

E S S E N T I A L S A F E T Y M E A S U R E S M A I N T E N A N C E M A N U A L • B U I L D I N G C O M M I S S I O N

PURPOSE

Certain elements and structures witin a building must ae a re-resistance leel to maintain structural ability during a re

and restrict te sread of re.

REQUIREMENTS

A re-resisting structure must:–

a) Be roided wit te re-resistance leel secied in te Building Code of Australia; and

b) hae all oenings rotected wit doors, windows, sutters, anels or oter means rated to roidete reuired re-resistance leel.

MAINTENANCE CHECKS

It is recommended tat te releant building sureyor sould reuire an annual insection of tese structures.Te owner may delegate tis function to anoter erson or body were necessary or aroriate.

To ensure te integrity and safety of re-resisting structures, insections sould ensure:–

a) No unautorised enetration or attacment as occurred.

b) proer oeration of deices rotecting oenings.

c) No damage as occurred.

MAINTENANCE RECORDS

Te following information must be recorded:–

a) Te dates te yearly insection was carried out; and

b) Te name of te erson conducting insection; and

c) Any roblems identied in te insection; and

d) Actions taen to rectify roblems identied; and

e) Date te rectication occurred; and

f) Signature of te erson conducting te insection.

A log seet to record tis information is roided in Aendi C of tis manual.

1.1 BuIldING ElEmENTS rEquIrEd TO SATISFyPrESCrIBEd F IrE-rESISTANCE lEvEl BCA: part C, D1.12 

Page 29: Essential Safety Maintenance Manual

8/3/2019 Essential Safety Maintenance Manual

http://slidepdf.com/reader/full/essential-safety-maintenance-manual 29/290

S E C T I O N 1 / P A G E 3

E S S E N T I A L S A F E T Y M E A S U R E S M A I N T E N A N C E M A N U A L • B U I L D I N G C O M M I S S I O N

PURPOSE

To indicate te suitability or oterwise, of building materials, assemblies, linings and surface nises to ae te

ability to resist te sread of ame and generation of smoe.

REQUIREMENTS

General re aard roerties roide a means of assessing building materials and comonents, using standard testsas outlined in AS 1530.3, for teir erformance according to:–

a) Teir tendencies to ignite.

b) Teir tendencies to roagate ame.

c) Te eat tey release once ignition as occurred, and

d) Teir tendencies to release smoe.

Fire aard roerties for oors, ceilings and walls roide a means of assessing materials and comonents for teirerformance according to:–

For oors; critical radiant eat u roided by testing te material in accordance wit AS 9239.1.•

For walls and ceilings; a grou number determined by ysical testing of te material in accordance wit AS ISO•9705; or rediction in accordance wit clause 3 of Secication A2.4 tested in accordance wit AS/NzS 3837.

Using te aboe criteria, selection of suitable material can be made to full a roosed class of building. Testing and selectionof materials taes lace rior to construction and nising of new building wor.

Building owners must ensure tat any new material introduced to teir remises conforms to te reuirements of teBuilding Code of Australia.

MAINTENANCE CHECKS

It is recommended tat te releant building sureyor reuire an annual insection of te building. Tis is to ensure tatmaterials tat do not conform to te re aard indices ae been introduced or occur in te remises. Te owner maydelegate tis function to anoter erson or body were necessary or aroriate.

Te manufacturer or sulier of tese materials sould be able to adise weter teir roduct conforms.

MAINTENANCE RECORDS

To ensure comliance wit te Building Regulations 2006, owners of buildings must record te details of teir yearlyinsections.

Details tat must be recorded include:–

a) Identication of te remises; and

b) Site address; and

c) Name of te building owner; and

d) Date te insection was carried out; and

e) Any non-conforming materials identied; and

f) Stes taen to remoe or relace te non-conforming material; and

g) Name and signature of te erson carrying out te insection.

A log seet to record tis information is included in Aendi C of tis manual.

1.2 mATErIAlS ANd ASSEmBlIES rEquIrEd TOSATISFy PrESCrIBEd F IrE hAzArd PrOPErTIES BCA: C1.10, C1.10a 

Sec A2.4 References: AS 1530.3 

AS 9239.1 AS ISO 9705 AS NzS 3837

Page 30: Essential Safety Maintenance Manual

8/3/2019 Essential Safety Maintenance Manual

http://slidepdf.com/reader/full/essential-safety-maintenance-manual 30/290

S E C T I O N 1 / P A G E 4

E S S E N T I A L S A F E T Y M E A S U R E S M A I N T E N A N C E M A N U A L • B U I L D I N G C O M M I S S I O N

PURPOSE

Certain elements witin a building must ae a resistance to re, to roide re-rotection, comartmentation or

searation to restrict te sread of re and roide occuant safety.

REQUIREMENTS

A re-resisting element must:–

a) Be roided wit te re-resistance leel secied in te Building Code of Australia; and

b) hae all oenings rotected wit doors, windows, sutters, anels or oter means rated to roide tereuired re-resistance leel.

MAINTENANCE CHECKS

It is recommended tat te releant building sureyor reuire an annual insection of tese structures. Te owner maydelegate tis function to anoter erson or body were necessary or aroriate.

To ensure te integrity and safety of re-resisting structures, insections sould ensure:–

a) No unautorised enetration or attacment.

b) proer oeration of deices rotecting oenings.

c) No damage as occurred.

MAINTENANCE RECORDS

Te following information must be recorded:–

a) Te dates te yearly insection was carried out; and

b) Te name of te erson conducting te insections; and

c) Any roblems identied in te insection; and

d) Actions taen to rectify roblems identied; and

e) Date te rectication occurred; and

f) Signature of te erson conducting te insection.

A log seet to record tis information is roided in Aendi C of tis manual.

1.3 ElEmENTS rEquIrEd TO BE NON-COmBu STIBlE ,PrOvIdE F IrE-PrOTECTION, COmPArTmENTATIONOr SEPArATION

BCA: C2.5 to C2.14, C3.3,C3.11,D1.7, D1.8, E1.3, G3.4

Page 31: Essential Safety Maintenance Manual

8/3/2019 Essential Safety Maintenance Manual

http://slidepdf.com/reader/full/essential-safety-maintenance-manual 31/290

S E C T I O N 1 / P A G E 5

E S S E N T I A L S A F E T Y M E A S U R E S M A I N T E N A N C E M A N U A L • B U I L D I N G C O M M I S S I O N

PURPOSE

A wall-wetting srinler system is installed to roide a full-time automatic re rotection system, to rotect a wall or

oening in te eent of a re. Wall-wetting srinlers may be internal or eternal. The Building Code Australia does notreference a secic Standard for te installation of wall-wetting srinlers. howeer, AS 2118.2 may roide guidanceon te installation of wall-wetting drencer systems.

REQUIREMENTS

A wall-wetting srinler system may include:–

a) Wet ie systems and srinlers.

b) vale installations.

c) Electric motor and comression-ignition engines and umsets.

d) Fire brigade booster connections.

e) pre-action systems.

f) Water storage systems.

g) Alarms and interface wit automatic re alarm and detection systems were installed.

REQUIREMENTS OF THE SYSTEM

To roide te reuired rotection, your wall-wetting srinler system must be:–

a) An automatic re srinler system comlying wit te rinciles:– 

a. AS 2118

b) Maintained in accordance wit AS 1851-2005 Section 2 eiter by or under te direct suerision of ersonnel

cometent in srinler system maintenance.

METHOD OF OPERATION

To comly wit AS 2118, te wall-wetting srinler system must ae:–

a) proision for an adeuate water suly; and

b) A uming system to ressurise te srinler system; and

c) A distribution ie system to delier water to eac srinler ead; and

d) Srinler eads to erform according to te ris tey are rotecting; and

e) A local alarm facility to alert te oeration of a srinler system; and

f) A direct alarm connection to an aroed monitoring serice were reuired.

Te srinler system is actiated by a srinler ead or eads resonding to a rise in temerature inside te building oreternally from adoining buildings. Water ows troug tis ead(s), lowering te residual water ressure, wic causeste um system to come into oeration. Water owing troug te system dries te water-motor in te local alarm,sounding te alarm bell. Were tted, a direct alarm is transmitted to a monitoring serice tat will notify te re brigade.

1.4 WAll-WETTING SPrINklErSBCA: C3.4, C3.8, C3.11,

D1.7, D1.8 G3.8 Reference: AS 2118 

AS 1851

Page 32: Essential Safety Maintenance Manual

8/3/2019 Essential Safety Maintenance Manual

http://slidepdf.com/reader/full/essential-safety-maintenance-manual 32/290

S E C T I O N 1 / P A G E 6

E S S E N T I A L S A F E T Y M E A S U R E S M A I N T E N A N C E M A N U A L • B U I L D I N G C O M M I S S I O N

MAINTENANCE CHECKS

It is recommended tat te releant building sureyor reuire tat re mains be maintained weely to AS 1851-2005

Section 2. It sould be noted tat tis is te lowest leel of maintenance routines reuired by te Standards. More rigorousroutines are also reuired by AS 1851-2005 Section 2 and are outlined below. Te owner may delegate tis function to anotererson or body were necessary or aroriate.

Te srinler system maintenance rogram secied in AS 1851-2005 Section 2 and AS 1851-2005 Section 3(for umset maintenance), roides for insection, testing and maintenance at te following freuencies:–

Weely•

Montly•

Si-montly•

Yearly•

Tree-yearly•

Twele-yearly•

Twenty four-yearly•

Wen a system is rendered artially or fully disabled due to maintenance or modications, te following recautionsare mandatory:–

a) Te building owner or is reresentatie must be notied; and

b Monitoring serice to wic te system is connected, or te nearest re station if tere is no connection,must be notied before wor commences and after wor is comleted.

Te following additional recautions sould be obsered, as far as is racticable, weter te system is inoeratie troug anemergency or lanned occurrence:–

a) Under all circumstances, ee as muc of te system fully oerational as is racticable. If te necessary wor is toetend oer seeral days or wees, re-instate te system as far as is racticable at te end of eac woring day.

b) Were te system as to be left disconnected outside woring ours, consideration sould be gien to emloying awatcman wile te system is disconnected.

c) Weneer it is ossible, disconnection of te system sould be undertaen wen roduction macinery is inoeratie.

d) Wile te system is down, smoing sould be banned in te affected areas.

e) Notify senior deartment ersonnel or tenants’ reresentaties of te situation, so tat re-etinguising aliancescan be et immediately aailable, wit trained ersonnel on and to use tem if necessary.

f) Notify te insurer or insurance broer of te situation.

g) hae all necessary euiment and material aailable and do all te wor ossible rior to isolating te srinlers.

) hot cutting or welding sould be aoided, were ossible, in an area were te srinler system it not oerational.Tis includes wor on te srinler system.

i) Aoid all sources of ignition.

Maintenance testing of tese systems sould be carried out in conunction wit te re alarm system testing to assure tatte systems are correctly interfaced.

prior to and following tis test, it is essential tat te monitoring serice tat receies te alarm is adised of te imminenttest, ceced to see te test call was receied, and adised wen te system is re-set and oerational.

MAINTENANCE RECORDS

Records of all maintenance routines must be in a log boo et at te srinler control ales.

It is recommended tat log seets to record te comletion of te maintenance are deeloed from te tables as

secied in AS 1851-2005 Section 2.

Page 33: Essential Safety Maintenance Manual

8/3/2019 Essential Safety Maintenance Manual

http://slidepdf.com/reader/full/essential-safety-maintenance-manual 33/290

S E C T I O N 1 / P A G E 7

E S S E N T I A L S A F E T Y M E A S U R E S M A I N T E N A N C E M A N U A L • B U I L D I N G C O M M I S S I O N

PURPOSE

A re door is installed across an oening in a re wall to maintain te re-resistance rating of tat re wall. Tis includes

sliding re doors, teir associated warning systems and associated self-closing, automatic closing and latcing mecanisms.

REQUIREMENTS OF THE SYSTEM

An aroed re-resistant doorset is one tat is identical in assembly, construction and installation to a rototye of tedoor tat as been submitted to te standard re-resistance test, and as fullled all te releant test reuirements.

A re door must be self-closing or close automatically on te oeration of an aroed sensing deice or on te loss ofower suly. Self-closing means euied wit a deice tat returns te door to te fully closed osition immediatelyafter eac oening.

Eac re door must ae a metal tag attaced as reuired by AS 1905.1, and latc sets and closers sould also be maredas required.

METHOD OF OPERATION

On receit of a signal troug te re alarm system, te old-oen deice of automatic closing doorsets must release te door.Alternatiely, wen electrical ower to tat area fails, te electro-magnetic old-oen deice must ten release te door. Oncereleased, te re door must close cleanly, and be unimaired in its oeration. It is essential tat no unautorised means is usedto old oen a re door.

MAINTENANCE CHECKS

It is recommended tat te releant building sureyor (RBS) sould reuire tat a re door be maintained and insected inaccordance wit AS 1851-2005 Section 17.

Te Standard secies te following maintenance interals:–

Tree-montly•

Si-montly•

Yearly•

Te leel of maintenance reuired by te Standard for te tree-montly, si-montly and yearly cecs is identical. Te RBSsould secify te minimum timeframe. Te owner may delegate tis function to anoter erson or body were necessary oraroriate. It is recommended tat were any correctie action inoles reairs to te door leaf, suc reairs sould be carriedout by te original manufacturer.

Before a re door is rendered unsericeable for maintenance, te following recautions sall be taen by te reairer:–

a) Adise te owner or occuier so tat any necessary recautions can be taen; and

b) Were te door is to be remoed and cannot be re-installed witin tree ours, te nearest re brigade and temonitoring serice to wic te alarm is connected, sould be adised; and

c) If te door rotects an oening in a re-isolated escae route or in a wall reuired to ae a four-our re-resistance,ermission sould be obtained from te regulatory autority (building sureyor) as well as notice gien to temonitoring serice as in (b); and

d) A re door sould not be rendered unsericeable for maintenance wile any re alarm or re suression systemin te building is inoeratie.

It is essential all re doors are maintained in oerational condition at all times.

1.5 F IrE dOOrSBCA: C2.12 to C2.13,

C3.4 to C3.8, C3.10,C3.11, D1.7,D1.8, D1.12

Page 34: Essential Safety Maintenance Manual

8/3/2019 Essential Safety Maintenance Manual

http://slidepdf.com/reader/full/essential-safety-maintenance-manual 34/290

S E C T I O N 1 / P A G E 8

E S S E N T I A L S A F E T Y M E A S U R E S M A I N T E N A N C E M A N U A L • B U I L D I N G C O M M I S S I O N

MAINTENANCE RECORDS

To ensure a roer istory of eac re door in te remises is retained, te following records must be aailable

and maintained:–

1. A log boo,

a) roided by te re door sulier, sowing:–

i) Identication of te building and its owner; and

ii) Te sulier of te doorset; and

iii) Te date(s) of commissioning of te re doorsets in te building.

b) Identication of eac doorset, sowing:–

i) Its identication number; and

ii) Te tye of door, its dimensions and re-resistance leel; and

iii) Te items of ardware installed on it, and were alicable, te marings on tat ardware; and

i) Te items of door furniture tted; and

) Any subseuent reairs or relacement of any art of te doorset.

Te ages of tis log boo must be numbered.

2. A numbered Certicate of Comliance, sulied by te sulier of te re doorsets, giing written eidence tat:–

a) Te doorset is identical wit a tested rototye; and

b) Te door frame as been correctly installed; and

c) Te installation comlies wit AS 1905.1.

It is recommended tat log seets to record te comletion of te maintenance are deeloed from te tables for redoorsets as secied in AS 1851-2005 Section 17.

Page 35: Essential Safety Maintenance Manual

8/3/2019 Essential Safety Maintenance Manual

http://slidepdf.com/reader/full/essential-safety-maintenance-manual 35/290

PURPOSE

To roide rotection to oenings by maintaining te integrity of re searation and comartmentation. Tis also includes

windows tat are automatic or ermanently ed in te closed osition.

REQUIREMENTS OF THE EQUIPMENT

Fire windows must be designed, constructed and installed to aciee te reuired re-resistance leel and may be anautomatic closing or ermanent closure.

METHOD OF OPERATION

Oenable re windows are oerated automatically by a eat-sensing deice incororated in teir design.

MAINTENANCE CHECKS

It is recommended tat te releant building sureyor sould reuire tat a re door be maintained and insected aser te details in AS 1851-2005 Section 17.

Te Standard secies te following maintenance interals:

Si-montly•

Yearly•

Te owner may delegate tis function to anoter erson or body were necessary or aroriate.

MAINTENANCE RECORDS

Te following information must be recorded:–

a) Te si-montly cec to ensure no obstruction to tese items; and

b) Te annual insection to ensure satisfactory oeration of tese items; and

c) Te date cecs and insections were carried out; and

d) Te name and signature of te erson carrying out te cecs and insections; and

e) Any roblems identied during te cecs and insections.

It is recommended tat log seets to record te comletion of te maintenance are deeloed from te tablesfor re-rated glaing as secied in AS 1851-2005 Section 17.

S E C T I O N 1 / P A G E 9

E S S E N T I A L S A F E T Y M E A S U R E S M A I N T E N A N C E M A N U A L • B U I L D I N G C O M M I S S I O N

1.6 F IrE WINdOWSBCA: C3.4, C3.8, C3.11,

D1.7,D1.8

Page 36: Essential Safety Maintenance Manual

8/3/2019 Essential Safety Maintenance Manual

http://slidepdf.com/reader/full/essential-safety-maintenance-manual 36/290

S E C T I O N 1 / P A G E 1 0

E S S E N T I A L S A F E T Y M E A S U R E S M A I N T E N A N C E M A N U A L • B U I L D I N G C O M M I S S I O N

PURPOSE

To roide rotection to oenings by maintaining te integrity of re searation and comartmentation.

REQUIREMENTS OF THE EQUIPMENT

Fire sutters:–

a) Must be designed, constructed and installed identical to a tested and aroed rototye. A steel sutter mustcomly wit AS 1905.2; and

b) Must oerate automatically and close at a rate of between 0.25 and 0.3 metres er second; and

c) Must maintain teir integrity for te time eriod as reuired by te Building Code of Australia.

METHOD OF OPERATION

Fire sutters are oerated automatically by a eat-sensing deice incororated in teir design.

MAINTENANCE CHECKS

It is recommended tat te releant building sureyor sould reuire tat a re sutter be maintained and insected inaccordance wit AS 1851-2005 Section 17.

Te standard secies te following maintenance interals:

Tree-montly•

Si-montly•

Yearly•

Details of te insection and maintenance regime are contained witin AS 1851-2005 Section 17 clause 17.4.5.

Te owner may delegate tis function to anoter erson or body were necessary or aroriate.

MAINTENANCE RECORDS

Te following information must be recorded:–

a) Te tree-montly cec to ensure no obstruction to tese items; and

b) Te annual insection to ensure satisfactory oeration of tese items; and

c) Te date cecs and insections were carried out; and

d) Te name and signature of te erson carrying out te cecs and insections; and

e) Any roblems identied during te cecs or insections.

It is recommended tat log seets to record te comletion of te maintenance are deeloed from te tables forre sutters as secied in AS 1851-2005 Section 17.

1.7 F IrE ShuTTErSBCA: C3.4, C3.5,

D1.7, D1.8Reference: AS 1905.2-1997

Page 37: Essential Safety Maintenance Manual

8/3/2019 Essential Safety Maintenance Manual

http://slidepdf.com/reader/full/essential-safety-maintenance-manual 37/290

PURPOSE

A solid core door is installed across an oening in a re-rated wall to maintain searation of sole occuancy units from ublic

areas or oter sole occuancy units.

REQUIREMENTS OF THE EQUIPMENT

An aroed doorset is one tat is of solid construction tat not less tan 35 mm tic and tigt tting (minimal gasbetween door leaf and frame). Te door must be self-closing or close automatically on te oeration of an aroed sensingdeice or on te loss of ower suly. Self-closing means euied wit a deice tat returns te door to te fully closedosition immediately after eac oening.

METHOD OF OPERATION

On receit of a signal troug te re alarm system, te old-oen deice or automatic closing doorsets must release te door.Alternatiely, wen electrical ower to tat area fails, te electro-magnetic old-oen deice must ten release te door. Once

released, te door must close cleanly and be unimaired in its oeration.

It is essentia tat no natoise eans is se to o open a oo.

MAINTENANCE CHECKS

It is recommended tat te releant building sureyor sould reuire tat solid core doors be insected annually.

Te owner may delegate tis function to anoter erson or body were necessary or aroriate.

It is recommended tat were any correctie action inoles reairs to te door leaf, suc reairs sould be carried outby te original manufacturer.

Before a door is rendered unsericeable for maintenance, te following recautions sall be taen by te reairer:–

Adise te owner or occuier, so tat any necessary recautions can be taen; and•

Were te door is to be remoed and cannot be re-installed witin tree ours, te nearest re brigade, and te•monitoring serice to wic te alarm is connected, sould be adised; and

If te door rotects an oening in a re-isolated escae route or in a wall reuired to ae a four-our re-resistance,•ermission sould be obtained from te regulatory autority (building sureyor) as well as notice gien to temonitoring serice as in (b); and

A door sould not be rendered unsericeable for maintenance wile any re alarm or re suression system in te•building is inoeratie.

It is essential all solid core doors located in re-rated walls are maintained in oerational condition at all times.

1 .8 S Ol Id C Or E dOOr SBCA: C3.11

S E C T I O N 1 / P A G E 1 1

E S S E N T I A L S A F E T Y M E A S U R E S M A I N T E N A N C E M A N U A L • B U I L D I N G C O M M I S S I O N

Page 38: Essential Safety Maintenance Manual

8/3/2019 Essential Safety Maintenance Manual

http://slidepdf.com/reader/full/essential-safety-maintenance-manual 38/290

S E C T I O N 1 / P A G E 1 2

E S S E N T I A L S A F E T Y M E A S U R E S M A I N T E N A N C E M A N U A L • B U I L D I N G C O M M I S S I O N

MAINTENANCE RECORDS

To ensure a roer istory of eac solid core door in a re-rated wall searating ublic areas from sole occuancy units and

doors searating sole occuancy units in te remises is retained, te following records must be aailable and maintained:–

A log boo,

a) sowing:–

i. Identication of te building and its owner; and

ii. Te sulier of te doorset; and

iii. Te date(s) of commissioning of te doorsets in te building.

b) Identifying of eac doorset, sowing:–

i. Its identication number; and

ii. Te tye of door and its dimensions; and

iii. Te items of ardware installed on it and, were alicable, te marings on tat ardware; and

i. Te items of door furniture tted; and

. Any subseuent reairs or relacement of any art of te doorset.

Te ages of tis log boo must be numbered.

A log seet to record tis information is roided in Aendi C of tis manual.

Page 39: Essential Safety Maintenance Manual

8/3/2019 Essential Safety Maintenance Manual

http://slidepdf.com/reader/full/essential-safety-maintenance-manual 39/290

PURPOSE

Maintain te integrity of a serice enetration in a building element tat as a re-resistance leel.

REQUIREMENTS

Were ies or serices enetrate re-rated elements:–

a) Te oening must be neatly formed, cut or drilled; and

b) Minimum clearances must be maintained from:–

i. oter serices; and

ii. combustible material; and

c) Te ga between te ie or serice and te oor, wall or ceiling must be re-stoed wit a material tat willmaintain te re-resistance leel of tat element.

Were an item or serice suc as an electrical switc, outlet or socet is accommodated in an oening or recess in a wall,oor or ceiling:–

a) Te oening or recess must not:–

i. be witin 300 mm oriontally and 600 mm ertically of any oening on te oter side of tat wall, or

ii. etend beyond alf te ticness of te wall.

b) Te ga beind or between te serice and te wall, oor or ceiling must be re stoed.

MAINTENANCE CHECKS

It is recommended tat te releant building sureyor sould reuire a si-montly and yearly insection of te enetrations.AS 1851-2005 Section 17 sets out te reuirements for maintenance and insection interals of enetrations in reresisting elements.

Te owner may delegate tis function to anoter erson or body were necessary or aroriate.

Because of te role of tese enetrations, it is essential tat tey be maintained in a condition tat will not allow teassage of re from one comartment to anoter.

To ensure tis security, isual cecs sould be carried out after maintenance wor tat may ae interfered wit teir integrity.

Any susect area sould be inestigated furter.

Any roblems identied by tese cecs and insections must be rectied as soon as is racticable, by eiter:–

a) Referral bac to te contractor wo carried out te maintenance wor; or

b) By aing maintenance staff or a contractor carry out te necessary reairs.

MAINTENANCE RECORDS

Te following information must be recorded:–

a) Te dates te si-montly maintenance and yearly insections were carried out; and

b) Te name of te erson conducting te insections; and

c) Any roblems identied in te insection; and

d) Actions taen to rectify roblems identied; and

e) Date rectication occurred; and

f) Signature of te erson conducting te insection.

It is recommended tat log seets to record te comletion of te maintenance are deeloed from te tables for sericeenetrations, as secied in AS 1851-2005 Section 17.

S E C T I O N 1 / P A G E 1 3

E S S E N T I A L S A F E T Y M E A S U R E S M A I N T E N A N C E M A N U A L • B U I L D I N G C O M M I S S I O N

1.9 F IrE-PrOTECTION AT SErvICE PENETrATIONS

(Through elements required to be fre resisting with respect to integrityor insulation or to have a resistance to the incipient spread o fre)

BCA: C3.12, C3.13, C3.15

Page 40: Essential Safety Maintenance Manual

8/3/2019 Essential Safety Maintenance Manual

http://slidepdf.com/reader/full/essential-safety-maintenance-manual 40/290

S E C T I O N 1 / P A G E 1 4

E S S E N T I A L S A F E T Y M E A S U R E S M A I N T E N A N C E M A N U A L • B U I L D I N G C O M M I S S I O N

1.10 F IrE-PrOTECTION ASSOCIATEdWIT h C ON S T r u C T ION jOIN T S ,SPACES ANd ThE l IkE

(In and between building elements required to be fre-resisting with respect to integrity and insulation)

BCA: C3.16

PURPOSE

Tese materials, wen assigned to teir articular alications, assist in maintaining te integrity of te re searationbetween oors or re comartments in te building, or roide rotection to structural elements to retain teir integrityin te eent of re.

REQUIREMENTS

To ensure tese materials full teir function:–

a) Te material used must be identical to a rototye or samle of tat material tat as been submitted to and assedte aroriate re test, as referred to in AS 1530.4 or

b) Te material used is listed in Table 1 of Secication A2.3 of te Building Code of Australia; and

c) Te material is alied or constructed in accordance wit tat Standard or tat secication.

MAINTENANCE CHECKS

It is recommended tat te releant building sureyor sould reuire a si-montly and yearly insection in accordance witAS1851-2005 Section 17.

Te owner may delegate tis function to anoter erson or body were necessary or aroriate.

Maintenance cecs are also recommended after maintenance wor tat may ae damaged or remoed a section of material.Tese cecs sould be carried out isually, wit furter inestigation of any susect areas.

Any roblems identied sould be rectied as soon as is racticable, by eiter:–

a) Referral bac to te contractor wo carried out te maintenance wor, orb) haing te owner’s maintenance staff or contractors carry out te necessary reairs.

MAINTENANCE RECORDS

Te following information must be recorded:–

a) Te dates te maintenance and insections were carried out; and

b) Te name of te erson conducting te insections; and

c) Any roblems identied in te insection; and

d) Actions taen to rectify roblems identied; and

e) Date te rectication occurred; and

f) Signature of te erson conducting te insection.

It is recommended tat log seets to record te comletion of te maintenance are deeloed from te tables for re suttersas secied in AS 1851-2005 Section 17.

Page 41: Essential Safety Maintenance Manual

8/3/2019 Essential Safety Maintenance Manual

http://slidepdf.com/reader/full/essential-safety-maintenance-manual 41/290

PURPOSE

Smoe doors are constructed in smoe walls to restrict te assage of smoe between smoe comartments or walls,

or from witin a smoe lobby.

REQUIREMENTS OF THE EQUIPMENT

Smoe doors must be constructed so tat smoe will not ass from one side of te doorway to te oter.

Smoe doors can be of one or two leaes and must:–

a) Be side-ung to swing:–

i. in te direction of egress or

ii. in bot directions; and

b) Be caable of resisting smoe at 200°C for 30 minutes; and

c) hae te leaes tted wit smoe seals; and

a. hae te leaes:–

i. normally closed or

ii. close automatically, wit te closing initiated by smoe detectors or ower failure; and

b. hae te leaes close fully after eac manual oening; and

c. If made of glass, ae te glaing identiable by oaue construction.

MAINTENANCE CHECKS

It is recommended tat te releant building sureyor reuire tat a re door be maintained and insected in accordancewit AS 1851-2005 Section 17.

Te standard secies te following maintenance interals:–

Tree-montly•

Si-montly•

Yearly•

Te owner may delegate te maintenance function to anoter erson or body were necessary or aroriate.

To ensure smoe doors full teir designed function, cec tat:–

a) Te doors and associated euiment are in woring order (seals undamaged, etc.).

b) No unautorised means ae been incororated to retain te doors oen (wedges, cabin oos, etc.).

c) Te automatic closing facilities wor, i.e.:–

i. wen te smoe detectors oerate, or

ii. wen ower failure occurs.

Tese cecs may be carried out in conunction wit te testing of te re alarm system, in accordance wit AS 1851-2005.

S E C T I O N 1 / P A G E 1 5

E S S E N T I A L S A F E T Y M E A S U R E S M A I N T E N A N C E M A N U A L • B U I L D I N G C O M M I S S I O N

1.11 SmOkE dOOrS

(Including associated sel-closing, automatic closingand latching mechanisms)

BCA Secication: C2.5, D2.6

Page 42: Essential Safety Maintenance Manual

8/3/2019 Essential Safety Maintenance Manual

http://slidepdf.com/reader/full/essential-safety-maintenance-manual 42/290

S E C T I O N 1 / P A G E 1 6

E S S E N T I A L S A F E T Y M E A S U R E S M A I N T E N A N C E M A N U A L • B U I L D I N G C O M M I S S I O N

MAINTENANCE RECORDS

A log boo must be maintained to record te insections of eac smoe door. Tis sould sow:–

a) Te date of eac montly insection; and

b) Any roblems identied; and

c) Measures taen to rectify roblems identied; and

d) Date roblems rectied; and

e) Name and signature of te erson carrying out eac insection.

It is recommended tat log seets to record te comletion of te maintenance are deeloed from te tables for smoe doorsas secied in AS 1851-2005 Section 17.

Page 43: Essential Safety Maintenance Manual

8/3/2019 Essential Safety Maintenance Manual

http://slidepdf.com/reader/full/essential-safety-maintenance-manual 43/290

S E C T I O N 1 / P A G E 1 7

E S S E N T I A L S A F E T Y M E A S U R E S M A I N T E N A N C E M A N U A L • B U I L D I N G C O M M I S S I O N

PURPOSE

A roscenium wall (re curtain) is roided in a teatre to reent te assage of smoe and re from te stage area to te

audience area.

REQUIREMENTS OF THE EQUIPMENT

A re curtain must be eiter:–

a) Non-combustible, and tted to inibit smoe enetration around its erimeter wen fully lowered; or

b) A curtain wit secied early re aard indices rotected by a deluge srinler system across its total widt.

Eiter tye of curtain must be:–

a) Caable of closing fully witin 35 seconds; and

b) Oerated automatically by a eat-actiated deice, or manually from eiter te stage side or audience side.

METHOD OF OPERATION

A re curtain must be oerated by:–

a) An automatic system of eat-actiated deices.

b) Manually oerated deices, or

c) By a us-button emergency release deice.

MAINTENANCE CHECKS

It is recommended tat te releant building sureyor reuire an annual insection of tis facility to ensure no mecanical

damage as occurred, or any interference eists tat reents its oeration. Te owner may delegate tis function to anotererson or body were necessary or aroriate.

yEArly ChECk

visual cec of oerating mecanism to ensure no ysical damage or obstruction; and•

visual cec of curtain’s condition; and•

visual cec of eat detection euiment and srinler eads (if roided); and•

After rst isolating te re alarm system and srinler system (if roided), test te oeration of te curtain by:–•

i) Actiating te eat-sensing euiment.

ii) Actiating te manual oerating system.

iii) Actiating te emergency us-button deice.

MAINTENANCE RECORDS

A log boo, included in Aendi C of tis manual must be imlemented to record:-

a) Te 12-montly insections and tests, and roblems identied; and

b) Te date cecs and insections were carried out; and

c) Te name and signature of te erson carrying out te cecs and insections.

1.12 PrOSCENIum WAllS (F IrE CurTAINS)BCA: h1.3

Page 44: Essential Safety Maintenance Manual

8/3/2019 Essential Safety Maintenance Manual

http://slidepdf.com/reader/full/essential-safety-maintenance-manual 44/290

Page 45: Essential Safety Maintenance Manual

8/3/2019 Essential Safety Maintenance Manual

http://slidepdf.com/reader/full/essential-safety-maintenance-manual 45/290

Meansof egress M

 e a n s  of   e g r  e s  s 

Page 46: Essential Safety Maintenance Manual

8/3/2019 Essential Safety Maintenance Manual

http://slidepdf.com/reader/full/essential-safety-maintenance-manual 46/290

S E C T I O N 2 / P A G E 1

E S S E N T I A L S A F E T Y M E A S U R E S M A I N T E N A N C E M A N U A L • B U I L D I N G C O M M I S S I O N

m e a n s o f E g e s s

2.1 pAThS OF TRAvEL TO ExITS 2

2.2 DISChARGE FROM ExITS (INCLUDING pAThS OF TRAvEL FROM OpEN SpACES TO ThE pUBLIC ROADS

TO WhICh ThEY ARE CONNECTED) 3

2.3 ExITS (INCLUDING FIRE-ISOLATED STAIRWAYS AND RAMpS, NON-FIRE ISOLATED STAIRWAYS AND RAMpS,STAIR TREADS, BALUSTRADES AND hANDRAILS ASSOCIATED WITh ExITS, AND FIRE-ISOLATED pASSAGEWAYS) 4

2.4 SMOkE LOBBIES TO FIRE-ISOLATED ExITS 5

2.5 OpEN ACCESS RAMpS OR BALCONIES FOR FIRE-ISOLATED ExITS 6

2.6 DOORS (OThER ThAN FIRE OR SMOkE DOORS) IN A REqUIRED ExIT, FORMING pART OF A REqUIREDExIT OR IN A pATh OF TRAvEL TO A REqUIRED ExIT, AND ASSOCIATED SELF-CLOSING, AUTOMATICCLOSING AND LATChING MEChANISMS 7

Page 47: Essential Safety Maintenance Manual

8/3/2019 Essential Safety Maintenance Manual

http://slidepdf.com/reader/full/essential-safety-maintenance-manual 47/290

S E C T I O N 2 / P A G E 2

E S S E N T I A L S A F E T Y M E A S U R E S M A I N T E N A N C E M A N U A L • B U I L D I N G C O M M I S S I O N

2.1 PAThS Of TrAvEl TO ExITSBCA: D1.6

PURPOSE

Paths of travel to exits are to provide an unobstructed pathway for occupants travelling to an exit.

REQUIREMENTS

To provide a passage to an exit that is o a width and height as specifed by the Building Code of Australia.

METHOD OF OPERATION

To ensure paths of travel to exits are operational and effective, they must not be obstructed or altered in any way.

It is the responsibility o the owner to ensure that all paths o travel to exits are maintained in an efcient condition and keptfunctional and clear of obstruction at all times.

MAINTENANCE CHECKS

It is recommended that the relevant building surveyor should require a three-monthly inspection of this facility. The owner maydelegate this function to another person or body where necessary or appropriate.

It is recommended that in carrying out the required inspections, the following points be covered:–

a) Ensure no obstruction o any nature encroaches on or into the designated paths o travel; and

b) Check that the integrity o the fre-isolation requirements on or in the relevant sections o the path otravel have not been breached or compromised; and

c) Check that no unauthorised alteration has been carried out on these sections.

MAINTENANCE RECORDS

A log book must be kept to record:–

a) The date the inspection was carried out; and

b) Any problems encountered during the inspection; and

c) The name, designation and signature of the person carrying out the inspection.

A log sheet to record this information is provided in Appendix C of this manual.

Page 48: Essential Safety Maintenance Manual

8/3/2019 Essential Safety Maintenance Manual

http://slidepdf.com/reader/full/essential-safety-maintenance-manual 48/290

S E C T I O N 2 / P A G E 3

E S S E N T I A L S A F E T Y M E A S U R E S M A I N T E N A N C E M A N U A L • B U I L D I N G C O M M I S S I O N

PURPOSE

Discharge from exits is to provide an unobstructed pathway for occupants travelling to a road or open space.

REQUIREMENTS

Barriers, such as bollards, must be installed if they are necessary to prevent vehicles blocking access to, or discharge from,an exit.

To provide a passage or occupants travelling to a road or open space, the width o the path must be at least that o the exitas specifed by the Building Code of Australia, and in no case less than one metre.

The link between the exit and road or open space must be open to the sky for its length.

METHOD OF OPERATION

To ensure discharges from exits are operational and effective, they must not be obstructed or altered in any way.

It is the responsibility o the owner to ensure that all discharges and paths o travel to road or open space are maintainedin an efcient condition and kept functional and clear of obstruction.

MAINTENANCE CHECKS

It is recommended that the relevant building surveyor should require a three-monthly inspection. The owner may delegate thisfunction to another person or body where necessary or appropriate.

It is recommended that in carrying out the required inspections, the following points be covered:–

a) Ensure no obstruction o any nature has encroached on or into the designated paths o travel to road or open space;and

b) Ensure that exits have not been blocked and bollards are in place; andc) Check that no unauthorised alteration has been carried out on these sections.

MAINTENANCE RECORDS

A log book must be kept to record:–

a) The date the inspection was carried out; and

b) Any problems encountered during the inspection; and

c) The name, designation and signature of the person carrying out the inspection.

A log sheet to record this information is provided in Appendix C of this manual.

2.2 DISChArGE frOm ExITS

(Incuding pats o tae o open spaces to te pubic oads to wictey ae connected)

BCA: D1.7, D1.9 to D1.11,D2.12,G4.3, G4.6, G4.7

Page 49: Essential Safety Maintenance Manual

8/3/2019 Essential Safety Maintenance Manual

http://slidepdf.com/reader/full/essential-safety-maintenance-manual 49/290

S E C T I O N 2 / P A G E 4

E S S E N T I A L S A F E T Y M E A S U R E S M A I N T E N A N C E M A N U A L • B U I L D I N G C O M M I S S I O N

PURPOSE

Fire-isolated assageways, rams and stairs are to roide occuants wit safe egress from a building.

REQUIREMENTS

Tese elements must be of re-resistant construction at a leel secied in te Building Code of Australia.

At te entrance oint to tese elements, re doors are roided. Fire doors are to be of a secied re-resistance leel, tat areeiter self-closing or ae automatic closing facilities lined to smoe or eat detectors or to a re alarm or srinler systeminstalled in the building.

MAINTENANCE CHECKS

It is recommended tat te releant building sureyor sould reuire an annual insection of tese facilities. Te owner maydelegate tis function to anoter erson or body were necessary or aroriate.

It is essential to ensure:–

a) No unautorised alterations ae been made tat could comromise te integrity of te re-resistance leel; and

b) No obstruction as occurred by stacing of goods or euiment witin tese areas wic may obstruct te doorswing; and

c) No tamering or interference wit te self-closing or automatic oeration of te re doors.

Releant details for te testing and insection of re doors are roided in Section 1.5 – Fire doors of tis manual.

MAINTENANCE RECORDS

Te following information must be recorded:–

a) Te dates tat montly and yearly insections were carried out; and

b) Te name of te erson conducting te insections; and

c) Any roblems identied in te insection; and

d) Actions taen to rectify roblems identied; and

e) Date rectication occurred; and

f) Signature of te erson conducting te insection.

A log seet to record tis information is roided in Aendi C of tis manual.

2 . 3 Ex IT S

(Including fre-isolated stairways and ramps, non-fre isolated stairways and ramps,stair treads, balustrades and handrails associated with exits, and fre-isolated passageways)

BCA: D2.2 to D2.3,D2.8 to D2.11 D2.13, D2.16.D2.17,D2.23

Page 50: Essential Safety Maintenance Manual

8/3/2019 Essential Safety Maintenance Manual

http://slidepdf.com/reader/full/essential-safety-maintenance-manual 50/290

S E C T I O N 2 / P A G E 5

E S S E N T I A L S A F E T Y M E A S U R E S M A I N T E N A N C E M A N U A L • B U I L D I N G C O M M I S S I O N

PURPOSE

Smoe lobbies to re-isolated eits are to roide occuants wit safe egress from a building and reent smoe

entering a stair.

REQUIREMENTS

Tese elements are constructed to reent te assage of smoe at a leel secied in te Building Code of Australia.

Around te entrance oint to te eit, smoe lobbies may be roided. Smoe lobbies are constructed to reent te assageof smoe, into te area and are tted wit smoe doors tat are eiter self-closing or ae automatic closing facilities linedto smoe or eat detectors, or to a re alarm or srinler system installed in te building.

Te smoe lobby may also be ressured if te reuired eit stair is reuired to be ressurised under te smoe azardmanagement roisions.

MAINTENANCE CHECKS

It is recommended tat te releant building sureyor sould reuire an annual insection of smoe lobbies. Te owner maydelegate tis function to anoter erson or body were necessary or aroriate.

It is essential to ensure:–

a) No unautorised alterations ae been made tat could comromise te integrity of te smoe lobby; and

b) No obstruction as occurred by stacing of goods or euiment witin tese areas; and

c) No tamering or interference as occurred wit te self-closing or automatic oeration of te smoe doors.

Details for te testing and insection of smoe doors are roided in Section 1.11 of tis manual.

Details for te testing and insection of ressurisation systems are roided in Section 6.1 of tis manual.

MAINTENANCE RECORDS

Te following information must be recorded:–

a) Te dates tat montly and yearly insections were carried out; and

b) Te name of te erson conducting te insections; and

c) Any roblems identied in te insection; and

d) Actions taen to rectify roblems identied; and

e) Date rectication occurred; and

f) Signature of te erson conducting te insection.

A log seet to record tis information is roided in Aendi C of tis manual.

2 . 4 S mO k E lO B B IES T O F IrE- IS O lAT Ed ExIT SBCA: D1.7, D2.6

Page 51: Essential Safety Maintenance Manual

8/3/2019 Essential Safety Maintenance Manual

http://slidepdf.com/reader/full/essential-safety-maintenance-manual 51/290

S E C T I O N 2 / P A G E 6

E S S E N T I A L S A F E T Y M E A S U R E S M A I N T E N A N C E M A N U A L • B U I L D I N G C O M M I S S I O N

PURPOSE

Oen access rams and balconies are to roide occuants wit safe egress from a building.

REQUIREMENTS

Were oen access rams or balconies are roided to meet te smoe azard management reuirements of te Building Codeof Australia tey must:–

a) hae entilation oenings to outside air wic:–

i. hae a total unobstructed area not less tat te oor area of te ram or balcony; and

ii. Are eenly distributed along te oen sides of te ram or balcony; and

b) Not be enclosed on te oen side aboe a eigt of one metre ecet by an oen grille or te lie aing a free airsace of not less tan 75% of its area.

MAINTENANCE CHECKS

It is recommended tat te releant building sureyor sould reuire an annual insection of te rams or balconies.Te owner may delegate tis function to anoter erson or body were necessary or aroriate.

It is essential to ensure:–

a) No unautorised alterations ae been made tat could comromise te integrity of te entilation reuirements;and

b) No obstruction as occurred by stacing of goods or euiment witin tese areas.

MAINTENANCE RECORDS

Te following information must be recorded:–

a) Te dates tat montly and yearly insections were carried out; and

b) Te name of te erson conducting te insections; and

c) Any roblems identied in te insection; and

d) Actions taen to rectify roblems identied; and

e) Date rectication occurred; and

f) Signature of te erson conducting te insection.

A log seet to record tis information is roided in Aendi C of tis manual.

2 . 5 O P EN A CCES S rA mP S O r B A lCO NIESFO r F IrE- IS O lA T Ed ExIT S BCA: D2.5

Page 52: Essential Safety Maintenance Manual

8/3/2019 Essential Safety Maintenance Manual

http://slidepdf.com/reader/full/essential-safety-maintenance-manual 52/290

S E C T I O N 2 / P A G E 7

E S S E N T I A L S A F E T Y M E A S U R E S M A I N T E N A N C E M A N U A L • B U I L D I N G C O M M I S S I O N

PURPOSE

To roide a means of egress from any art of a building.

REQUIREMENTS OF THE EQUIPMENT

To roide sufcient and safe egress from a building, wit a minimum of effort and delay, and to resent a minimum ofobstruction in an eit at.

METHOD OF OPERATION

An eit door must be caable of simle oeration to full its designed urose. An eit door may be a swinging door or couldbe a sliding door. Sliding doors may be manually oerated or ower oerated.

Swinging doors must be able to be oened readily witout a ey, from te side facing a erson seeing teir way out, by asingle-anded downward or using action on a single deice located between 900 mm and 1.2 m aboe te oor.

It could be tted wit a fail-safe deice tat unlocs te door automatically wen any srinler, smoe or eat detectorsystem is actiated in te building.

Sliding doors must be able to be oened manually under a force of not more tan 110N and if ower oerated:–

Must be able to be oened manually under a force of not more tat 110N if tere is a malfunction of failure•of te ower source; and

If tey lead directly to road or oen sace tey must oen automatically if tere is a ower failure to te door•or on te actiation of a re or smoe alarm anywere in te re comartment sered by te door.

MAINTENANCE CHECKS

It is recommended tat te releant building sureyor sould reuire eit doors to be insected eery tree monts.

Te owner may delegate tis function to anoter erson or body were necessary or aroriate.

Maintenance cecs sould be carried out to ensure tat eit doors comly as follows:–

Swinging Doors:

Intact•

Oerational•

Fitted wit ardware tat conforms to te reuirements of te• Building Code of Australia, Section D (te ardwarenecessary to enable oeration as outlined aboe).

Sliding doors:

Oen doors manually and conrm doors can be oened under a force of not more tan 110N; and•

If ower oerated:–•

• Simulate ower failure and oen doors manually. Conrm door can be oened under a force of not moretan 110N.

• If tey lead directly to road or oen sace:–

- Simulate re alarm witin te re comartment and conrm tat doors oen automatically.

MAINTENANCE RECORDS

A log seet to record te maintenance and insections carried out is included Aendi C of tis manual.

2 . 6 d O O rS

(Other than fre or smoke doors in a required exit, orming part o a required exit or in a patho travel to a required exit, and associated sel-closing, automatic closing and latching mechanisms)

BCA: D1.6, D2.19 to D2.21,D2.23

Page 53: Essential Safety Maintenance Manual

8/3/2019 Essential Safety Maintenance Manual

http://slidepdf.com/reader/full/essential-safety-maintenance-manual 53/290

Page 54: Essential Safety Maintenance Manual

8/3/2019 Essential Safety Maintenance Manual

http://slidepdf.com/reader/full/essential-safety-maintenance-manual 54/290

Signs

 S  i        g n

 s 

Page 55: Essential Safety Maintenance Manual

8/3/2019 Essential Safety Maintenance Manual

http://slidepdf.com/reader/full/essential-safety-maintenance-manual 55/290

S E C T I O N 3 / P A G E 1

E S S E N T I A L S A F E T Y M E A S U R E S M A I N T E N A N C E M A N U A L • B U I L D I N G C O M M I S S I O N

S i g n s

3.1 ExIT SIGNS (INCLUDING DIRECTION SIGNS) 2

3.2 SIGNS WARNING AGAINST ThE USE OF LIFTS IN ThE EvENT OF FIRE 3

3.3 WARNING SIGNS ON SLIDING FIRE DOORS AND DOORS TO NON-REqUIRED STAIRWAYS,RAMpS AND ESCALATORS 4

3.4 SIGNS, INTERCOMMUNICATION SYSTEMS, OR ALARM SYSTEMS ON DOORS OF FIRE-ISOLATED ExITSSTATING ThAT RE-ENTRY TO STOREY IS AvAILABLE 5

3.5 SIGNS ALERTING pERSONS ThAT ThE OpERATION OF DOORS MUST NOT BE IMpAIRED 6

3.6 SIGNS REqUIRED ON DOORS, IN ALpINE AREAS, ALERTING pEOpLE ThAT ThEY OpEN INWARDS 7

3.7 FIRE ORDER NOTICES REqUIRED IN ALpINE AREAS 8

Page 56: Essential Safety Maintenance Manual

8/3/2019 Essential Safety Maintenance Manual

http://slidepdf.com/reader/full/essential-safety-maintenance-manual 56/290

E S S E N T I A L S A F E T Y M E A S U R E S M A I N T E N A N C E M A N U A L • B U I L D I N G C O M M I S S I O N

S E C T I O N 3 / P A G E 2

PurPose

Exit signs are provided to aid occupant identifcation o exits and paths o travel to exits.

requirements of the equiPment

Exit signs must be:–

a) Installed to AS/NzS 2293.1; and

b) Clearly visible at all times to persons having legal right of entry to the building, approaching an eit; and

c) Located in positions where eits are not readily apparent, i.e. corridors, hallways and lobbies, with directionalarrows indicating the direction to an exit; and

d) Located on, above, or adjacent to each door providing egress (as detailed in BCA E4.5); and

e) Clear and legible pictograms as reuired by AS 2293.3; and

f) Provided with emergency illumination in the event of normal power supply failure.

method of oPeration

Exit signs must be set up to operate as ollows:–

Be illuminated at all times by mains power supply or by being a self-contained unit; and•

Be either internally or eternally illuminated; and•

Have a provision or emergency power supply in the event o ailure o the normal power source.•

maintenance checKs

It is recommended that the relevant building surveyor should require maintenance to be carried out at least everysi months to AS 2293.2. It should be noted that this is the lowest level of maintenance reuired by the Standard andother routines are also required on a yearly basis. The owner may delegate this unction to another person or bodywhere necessary or appropriate.

The testing procedures of eit signs are detailed in AS 2293.2. These procedures must be available to your designated testerin a hard bound A4-sie maintenance folder. This folder must be provided by the installer of your system.

maintenance records

A manufacturer’s log book, or an alternative system (this would include this manual) is recommended for the recordingo maintenance inormation.

Log sheets for this purpose are included in the log book provided in Appendi C of this manual.

3 . 1 E x I T S I G N S ( I NC l U D I N G D I R EC T I O N S I G N S )BCA Specication: D1.12, E4.5, E4.6, E4.8 

Reference: AS/NzS 2293.1,AS 22293.2, AS 2293.3

Page 57: Essential Safety Maintenance Manual

8/3/2019 Essential Safety Maintenance Manual

http://slidepdf.com/reader/full/essential-safety-maintenance-manual 57/290

E S S E N T I A L S A F E T Y M E A S U R E S M A I N T E N A N C E M A N U A L • B U I L D I N G C O M M I S S I O N

S E C T I O N 3 / P A G E 3

PURPOSE

Signage is provided to warn occupants against the use o lits in the event o a fre in a building.

requirements

To provide signage adjacent to a lit as specifed by the Building Code of Australia.

method of oPeration

To ensure signs are operational and eective, they must not be obstructed or altered in any way.

It is the responsibility of the owner to ensure that all signage is maintained in an efcient condition and kept functionaland clear o obstruction.

maintenance checKs

It is recommended that the relevant building surveyor should require an annual inspection o signage. The owner maydelegate this unction to another person or body where necessary or appropriate.

It is recommended that in carrying out the required inspections, the ollowing point should be covered:–

Ensure no obstruction or removal o the signage has occurred.•

maintenance records

A log book must be kept to record:–

a) The date the inspection was carried out; and

b) Any problems encountered during the inspection; and

c) The name, designation and signature of the person carrying out the inspection.

A log sheet to record this inormation is provided in Appendix C o this manual.

BCA: E3.3 3 . 2 S IGNSWAR NINGAGAINST T HE USE  

O F l I F T S I N T H E E V E N T O F F I R E

Page 58: Essential Safety Maintenance Manual

8/3/2019 Essential Safety Maintenance Manual

http://slidepdf.com/reader/full/essential-safety-maintenance-manual 58/290

E S S E N T I A L S A F E T Y M E A S U R E S M A I N T E N A N C E M A N U A L • B U I L D I N G C O M M I S S I O N

S E C T I O N 3 / P A G E 4

PurPose

Signage is provided to alert occupants to the operation o sliding doors and the operation o non-required stairs, ramps and

escalators in the event o a fre in the building.

requirements

Signage must be installed to a sliding fre door on each side o the door over the opening stating: Warning–SidingFireDoor,  in lettering not less than 50 mm high in a colour contrasting to the background.

A warning sign must be provided where it can be readily seen to non-required stairways, ramps and escalators which states:–

DONOTUSETHISSTAIRWAYIFTHEREISAFIRE (in 20 mm high lettering) Or Donotusethisstairwayifthereisare (in 16 mm high lettering)

method of oPeration

To ensure signs are operational and eective, they must not be obstructed or altered in any way.

It is the responsibility of the owner to ensure that all signage is maintained in an efcient condition and kept functional andclear o obstruction.

maintenance checKs

It is recommended that the relevant building surveyor should require an annual inspection o signage. The owner may delegatethis unction to another person or body where necessary or appropriate.

It is recommended that in carrying out the required inspections, the ollowing point should be covered:–

Ensure no obstruction or removal o the signage has occurred.•

maintenance records

A log book must be kept to record:–

a) The date the inspection was carried out; and

b) Any problems encountered during the inspection; and

c) The name, designation and signature of the person carrying out the inspection.

A log sheet to record this inormation is provided in Appendix C o this manual.

3. 3 W A R N I N G S I G N S O N S l I D I N G F I R E D O O R S  

ANDDOOR ST ONON-R E qUIR E DST AIR WAYS,  

R AMPSANDE SCAl AT OR S

BCA: C3.6,Specication: D1.12

Page 59: Essential Safety Maintenance Manual

8/3/2019 Essential Safety Maintenance Manual

http://slidepdf.com/reader/full/essential-safety-maintenance-manual 59/290

E S S E N T I A L S A F E T Y M E A S U R E S M A I N T E N A N C E M A N U A L • B U I L D I N G C O M M I S S I O N

S E C T I O N 3 / P A G E 5

PurPose

Signage is provided to alert occupants that re-entry is available to a storey rom within a fre-isolated exit.

requirements

Doors in a re-isolated eit must not be locked from the inside, unless on at least every fourth storey, doors are not able to belocked and a sign is ed on such doors stating that re-entry is available or;

An intercommunication system, audible or visual alarm is fxed adjacent to the door and signage explaining the purpose andmethod o operation.

method of oPeration

To ensure signs, intercommunication device, or alarm are operational and eective, they must not be obstructed or altered inany way.

It is the responsibility o the owner to ensure that all signage, intercommunication devices or alarms are maintained in anefcient condition and kept functional and clear of obstruction.

maintenance checKs

It is recommended that the relevant building surveyor should require an annual inspection o signage, intercommunicationdevice or alarm system. The owner may delegate this unction to another person or body where necessary or appropriate.

It is recommended that in carrying out the required inspections, the ollowing point should be covered:–

Ensure no obstruction or removal o the signage has occurred.•

maintenance records

A log book must be kept to record:–

a) The date the inspection was carried out; and

b) Any problems encountered during the inspection; and

c) The name, designation and signature of the person carrying out the inspection.

A log sheet to record this inormation is provided in Appendix C o this manual.

BCA: D2.22 3 . 4 S I G N S , I N T E R C O M M U N I C A T I O N S Y S T E M S ,  

O R A l A R M S Y S T E M S

(On doors o fre-isolated exits stating that re-entry to a storey is available)

Page 60: Essential Safety Maintenance Manual

8/3/2019 Essential Safety Maintenance Manual

http://slidepdf.com/reader/full/essential-safety-maintenance-manual 60/290

E S S E N T I A L S A F E T Y M E A S U R E S M A I N T E N A N C E M A N U A L • B U I L D I N G C O M M I S S I O N

S E C T I O N 3 / P A G E 6

3 . 5 S IGNSAl E R T INGPE R SONST HAT T HE OPE R AT ION  

O F D O O R S M U S T N O T B E I M P A I R E D BCA: D2.23

PurPose

Signage is provided to warn occupants that the operation o certain doors must not be impaired.

requirements

Signage reuirements apply to a re door providing direct access to a re-isolated eit, a re door in a horiontal eit, anddoors leading from a re-isolated eit, ecept a door providing direct egress from a sole occupancy unit in a Class 2 or 3 orClass 4 part and reuired smoke doors and smoke doors that swing in both directions.

Signage must be in capital letters not less than 20 mm high in a colour contrasting with the background and state:–

For an automatic door held open by a hold open device:

FIRE(SMOkE)DOOR–DONOTOBSTRUCT

 

For a sel-closing door:

FIRE(SMOkE)DOOR

DONOOBSTRUCT

DONOTkEEPOPEN or;

 For a door discharging rom a fre-isolated exit:

FIRESAFETYDOOR–DONOTOBSTRUCT

method of oPeration

To ensure signs are operational and eective, they must not be obstructed or altered in any way.

It is the responsibility of the owner to ensure that all signage is maintained in an efcient condition and kept functional andclear o obstruction.

maintenance checKs

It is recommended that the relevant building surveyor should require an annual inspection o signage. The owner may delegatethis unction to another person or body where necessary or appropriate.

It is recommended that in carrying out the required inspections, the ollowing point should be covered:–

Ensure no obstruction or removal o the signage has occurred.•

maintenance records

A log book must be kept to record:–

a) The date the inspection was carried out; and

b) Any problems encountered during the inspection; and

c) The name, designation and signature of the person carrying out the inspection.

A log sheet to record this inormation is provided in Appendix C o this manual.

Page 61: Essential Safety Maintenance Manual

8/3/2019 Essential Safety Maintenance Manual

http://slidepdf.com/reader/full/essential-safety-maintenance-manual 61/290

E S S E N T I A L S A F E T Y M E A S U R E S M A I N T E N A N C E M A N U A L • B U I L D I N G C O M M I S S I O N

S E C T I O N 3 / P A G E 7

BCA: G4.3 3 . 6 S I G N S R E q U I R E D O N D O O R S , I N A l P I N E A R E A S ,  

A l E R T I N G P E O P l E T H A T T H E Y O P E N I N W A R D S

PurPose

Signage is provided to warn occupants to the operation o certain doors in alpine areas.

requirements

A door ftted to an external doorway within a building in the alpine regions may be subject to the build-up o snow.

The doors must only be capable o opening inwards and be ftted with signage with OPEN INWARDS in lettering not less than75 mm high in a colour contrasting with the background and installed on the inside face of the door.

method of oPeration

To ensure signs are operational and eective, they must not be obstructed or altered in any way.

It is the responsibility of the owner to ensure that all signage is maintained in an efcient condition and kept functional andclear o obstruction.

maintenance checKs

It is recommended that the relevant building surveyor should require an annual inspection o signage. The owner may delegatethis unction to another person or body where necessary or appropriate.

It is recommended that in carrying out the required inspections, the ollowing point should be covered:–

Ensure no obstruction or removal o the signage has occurred.•

maintenance records

A log book must be kept to record:–

a) The date the inspection was carried out; and

b) Any problems encountered during the inspection; and

c) The name, designation and signature of the person carrying out the inspection.

A log sheet to record this inormation is provided in Appendix C o this manual.

Page 62: Essential Safety Maintenance Manual

8/3/2019 Essential Safety Maintenance Manual

http://slidepdf.com/reader/full/essential-safety-maintenance-manual 62/290

E S S E N T I A L S A F E T Y M E A S U R E S M A I N T E N A N C E M A N U A L • B U I L D I N G C O M M I S S I O N

S E C T I O N 3 / P A G E 8

BCA: G4.9 3 . 7 F I R E O R D E R N O T I C E S R E q U I R E D I N A l P I N E A R E A S

PurPose

A fre order notice is provided to alert occupants to the method o operation o the alarm system, location o fre-fghting

equipment, location o exits, and the procedures or evacuation o the building.

requirements

Every Class 2, 3 or 9 building within an alpine area must display a notice that is clearly marked FIRE ORDERS in a suitablelocation near main entrances and on every storey.

A fre order must include inormation on:–

Operation of re alarm system•

Location o fre-fghting equipment•

Location o exits•

Procedures or evacuation o the building.•

method of oPeration

To ensure notices are operational and eective, they must not be obstructed or altered in any way.

It is the responsibility of the owner to ensure that all signage is maintained in an efcient condition and kept functional andclear o obstruction.

maintenance checKs

It is recommended that the relevant building surveyor should require an annual inspection o signage. The owner may delegatethis unction to another person or body where necessary or appropriate.

It is recommended that in carrying out the required inspections, the ollowing point should be covered:–

Ensure no obstruction or removal o the signage has occurred.•

maintenance records

A log book must be kept to record:–

a) The date the inspection was carried out; and

b) Any problems encountered during the inspection; and

c) The name, designation and signature of the person carrying out the inspection.

A log sheet to record this inormation is provided in Appendix C o this manual.

Page 63: Essential Safety Maintenance Manual

8/3/2019 Essential Safety Maintenance Manual

http://slidepdf.com/reader/full/essential-safety-maintenance-manual 63/290

Lighting

L   i        g h   t   i     n   g 

Page 64: Essential Safety Maintenance Manual

8/3/2019 Essential Safety Maintenance Manual

http://slidepdf.com/reader/full/essential-safety-maintenance-manual 64/290

E S S E N T I A L S A F E T Y M E A S U R E S M A I N T E N A N C E M A N U A L • B U I L D I N G C O M M I S S I O N

S E C T I O N 4 / P A G E 1

l i g h t i n g

4.1 EMERGENCY LIGHTING 2

Page 65: Essential Safety Maintenance Manual

8/3/2019 Essential Safety Maintenance Manual

http://slidepdf.com/reader/full/essential-safety-maintenance-manual 65/290

E S S E N T I A L S A F E T Y M E A S U R E S M A I N T E N A N C E M A N U A L • B U I L D I N G C O M M I S S I O N

S E C T I O N 4 / P A G E 2

BCA: E4.2, E4.4 Reference: AS 22939

4 . 1 E M E R G E N C Y l I G H T I N G

PurPose

To saeguard occupants rom injury by providing sufcient lighting to allow sae occupant evacuation in an emergency.

requirements of the equiPment

An emergency lighting system must:–

a) Be installed to AS 2293.1; and

b) Be automatic in operation in the event of failure of power supply to the main lighting system; and

c) Provide a level of luminance appropriate to: -

i. The use and sie in oor area of the building; and

ii. The distance required to reach exits.

method of oPeration

CENTRAllIGHTINGSYSTEM

This type o system will be set up to operate in one o two modes:–

Where the emergency lighting is energised at all times when the building is occupied; or•

Where the emergency lighting is energised only when power to the normal lighting system fails.•

SINGlEPOINTlIGHTSYSTEM

Each unit ’stands alone‘ and illuminates when normal lighting ails. Power is supplied rom a built-in battery which iscontinuously under charge while normal lighting operates.

maintenance checKs

It is recommended that the relevant building surveyor should require maintenance at least every six months. It should be notedthat this is the lowest level o maintenance required by the Standard and more rigorous routines are also required as notedbelow. The owner may delegate this unction to another person or body where necessary or appropriate.

CENTRAllIGHTINGSYSTEM

Checks should be undertaken on the following elements of the system:–

Batteries.•

Battery chargers.•

Inverters.•

Distribution and control euipment.•

Lights and exit signs.•

The complete system.•

Page 66: Essential Safety Maintenance Manual

8/3/2019 Essential Safety Maintenance Manual

http://slidepdf.com/reader/full/essential-safety-maintenance-manual 66/290

E S S E N T I A L S A F E T Y M E A S U R E S M A I N T E N A N C E M A N U A L • B U I L D I N G C O M M I S S I O N

S E C T I O N 4 / P A G E 3

SINGlEPOINTlIGHTINGSYSTEM

SIx-MONTHlYPROCEDURESa) Operate the self-contained emergency lights from their battery supply by turning off the normal lighting power

supply.

b) The lights must remain alight for at least 90 minutes.

c) Replace any faulty lamps.

d) Turn on the normal lighting power supply and check that the battery charger indicator functions properly.

Record the test and correct operation o the system.

Record the replacement o aulty lamps.

TWElVE-MONTHlYPROCEDURES

a) Carry out the si-monthly procedures; and

b) Clean down all light emitting and reecting surfaces.

Record the testing and cleaning.

SIx-MONTHlYTEST

Batteries

a) Lead-acid batteries – using a hydrometer and referring to the maintenance manual, test randomly selected cells for:–

i. Electrolyte density.

ii. State o charge.

Record the result o this test.

a) All batteries, including lead-acid batteries.

i. Visually check electrolyte level of each cell. Record those cells that require topping up.

ii. Visually inspect all cell containers for electrolyte leakage. Have leaking cells repaired or replaced by aqualifed person.

Record any repairs or replacement.

Batterychargers

a) Visually inspect the unit.

b) Clean unit and cubicle of dust and dirt.

c) Check battery voltage reading is within normal limits.

d) Check all connections are tight. Record the carrying out of these checks.

Record battery voltage reading.

Page 67: Essential Safety Maintenance Manual

8/3/2019 Essential Safety Maintenance Manual

http://slidepdf.com/reader/full/essential-safety-maintenance-manual 67/290

E S S E N T I A L S A F E T Y M E A S U R E S M A I N T E N A N C E M A N U A L • B U I L D I N G C O M M I S S I O N

S E C T I O N 4 / P A G E 4

Inverters

a) Visually inspect all components.

b) Record the inspection.

c) Record D.C. input voltage and current.

d) Record A.C. output voltage and current.

Distributionandcontroeuipment

a) Visually inspect relays, contactors, circuit breakers and fuses. Record inspection and any problems identied.

b) Check all connections for tightness. Record the check.

c) Remove any dust and dirt accumulated within the distribution and control euipment enclosures.Record the cleaning.

d) Check that sensing euipment operates the system when isolated from A.C. mains supply. Record the checkand any problems identifed.

Emergencyightsandeitsigns

a) Check all lights and eit signs for correct operation.

b) Replace any faulty lamps. Record the check and any lamps replaced.

Totasystem

a) Check for correct operation when battery charger turned off and mains failure simulated.

b) Check satisfactory operation of the charger-failure alarm while carrying out above check.

c) Record these checks and any problems identied.

Restore the system to normal operation, and check correct charging of batteries.

TWElVE-MONTHlYTEST

Batteries – for any battery reuiring maintenance of electrolyte above a specied level.

lead-acidbatteriesony–foreachce

Using a hydrometer and reerring to the maintenance manual,

a) Check electrolyte density.

b) Check state of charge.

Record the results of these checks.

Atypesofbatteries–(incudingead-acid)

a) Visually check electrolyte level in all cells. Record level for each cell.

b) Visually inspect all cells for electrolyte leakage. Mop up and neutralise any spilt liuid using baking powder dissolvedin water. Record the inspection and any aults ound.

c) Inspect all cell connections for corrosion and tighten any loose joints.

d) Treat all eposed metal surfaces with petroleum jelly or other recognised battery terminal preservative. Record theinspection and treatment.

e) Measure overall battery voltage and individual cell voltages, using a nely calibrated voltmeter. Record any cell witha voltage difference from average of more than + 0.03 volts.

Page 68: Essential Safety Maintenance Manual

8/3/2019 Essential Safety Maintenance Manual

http://slidepdf.com/reader/full/essential-safety-maintenance-manual 68/290

E S S E N T I A L S A F E T Y M E A S U R E S M A I N T E N A N C E M A N U A L • B U I L D I N G C O M M I S S I O N

S E C T I O N 4 / P A G E 5

Batterycharger

a) Carry out tests reuired in si-monthly test. 

Record the test.

b) Check voltmeter calibration. Record the check and result.

c) Check satisfactory operation of battery earth-fault detection system, if tted. Record the check.

d) Check satisfactory operation of the battery low-voltage alarm, if tted. Record the check.

Inverter

a) Carry out tests on items reuired in si-monthly test. Record the tests.

b) Check voltmeter calibration. Record the check and result.

lightsandeitsigns

a) Carry out all checks reuired in the si-monthly test. Record the tests.

b) Clean all light emitting and reecting surfaces. Record the cleaning.

Totasystem

1. Check battery voltage on completion of discharge test, by the following method:–

a. Turn o battery charger.

b. Simulate mains failure (turn off power).

c. Using all the installed emergency lighting, test discharge for at least 90 minutes.

Record battery voltage on completion o this test. I battery voltage is below acceptable limits ater completion o this test,re-service or replace the battery.

Record re-service or replacement.

2. Measure the time taken for the battery charger to change over automatically to the ‘oat charge’ mode, after;

Disconnecting the load,•

Turning on the battery charger,•

Manually selecting ‘boost charge’ mode.•

Record the time taken.

The above testing procedures are detailed in AS 2293.2. Theses procedures must be available to the designated tester.This inormation must be provided by the installer o the system.

maintenance records

A manufacturers’ hard bound log book, or an alternative system (this would include this manual), is recommendedor the recording o maintenance inormation.

Sheets for this purpose are included in the log book provided in Appendi C of this manual.

Page 69: Essential Safety Maintenance Manual

8/3/2019 Essential Safety Maintenance Manual

http://slidepdf.com/reader/full/essential-safety-maintenance-manual 69/290

Page 70: Essential Safety Maintenance Manual

8/3/2019 Essential Safety Maintenance Manual

http://slidepdf.com/reader/full/essential-safety-maintenance-manual 70/290

Fire-fghtingservices andequipment

F i  r  e-f  g h  t i  n g  s  er  vi   c  e s 

 a n d  e q ui   pm en t 

Page 71: Essential Safety Maintenance Manual

8/3/2019 Essential Safety Maintenance Manual

http://slidepdf.com/reader/full/essential-safety-maintenance-manual 71/290

E S S E N T I A L S A F E T Y M E A S U R E S M A I N T E N A N C E M A N U A L • B U I L D I N G C O M M I S S I O N

S E C T I O N 5 / P A G E 1

F i r e - F i g h t i n g S e r v i c e s a n d E u i p m e n t

5.1 FIRE HYDRANT SYSTEM (INCLUDING ON-SITE PUMPSET AND FIRE-SERVICE BOOSTER CONNECTION) 2

5.2 FIRE HOSE REEL SYSTEM 4

5.3 SPRINKLER SYSTEM 6

5.4 PORTABLE FIRE ExTINGUISHERS 9

5.5 FIRE CONTROL CENTRES (OR ROOMS) 10

5.6 PROVISIONS FOR SPECIAL HAzARDS 11

Page 72: Essential Safety Maintenance Manual

8/3/2019 Essential Safety Maintenance Manual

http://slidepdf.com/reader/full/essential-safety-maintenance-manual 72/290

E S S E N T I A L S A F E T Y M E A S U R E S M A I N T E N A N C E M A N U A L • B U I L D I N G C O M M I S S I O N

S E C T I O N 5 / P A G E 2

5 . 1 F I R E H Y D R A N T S Y S T E M ( I N C l U D I N G O N - S I T E  

P U M P S E T A N D F I R E S E RV I C E B O O S T E R C O N N E C T I O N )

PurPose

A fre hydrant system is installed to provide fre-fghting personnel a supply o water or fre-fghting purposes.

requirements of the equiPment

To ulfl its purpose, a hydrant system must:–

a) Be installed to AS 2419.1; and

b) Be located to provide coverage to every part of the building or site reuiring coverage; and

c) Provide a specied minimum ow of water at all times; and

d) Be readily accessible to re-ghting personnel.

method of oPeration

The supply o water to the hydrant system must be provided automatically, once a hydrant valve is opened or, in somesystems, once a fre alarm has been activated.

Any pump incorporated into the system must be powered by a motor that will enable operation regardless o primaryelectrical mains ailure.

The water supply must be acquired rom a source that will provide adequate water or a specifed period o time.

maintenance checKs

It is recommended that the relevant building surveyor (RBS) should reuire that re hydrants and re main systems bemaintained monthly to AS 1851-2005 Section 4. It should be noted that this is the lowest level of maintenance routinesreuired by AS 1851-2005. More rigorous routines are also reuired and are outlined below. The owner may delegate this

unction to another person or body where necessary or appropriate.

Maintenance work, involving inspections, testing and servicing, has been specied in AS 1851-2005 at theollowing requencies:–

Monthly•

Six-monthly•

Yearly•

Five-yearly•

Note: For re hydrant pumpsets, the freuency of inspection and testing shall be carried out weekly as per the reuirementsof AS 1851- 2005 Section 4 clause 4.3.2 see Table 4.4.1 and Table 4.4.2 unless the provisions AS 1851- 2005 Section 3.2.1have been satisfed.

Before maintenance work is carried out, the following precautions must be taken:–

a) Whenever maintenance work will render the system inoperative, or will activate the re alarm system, notifythe monitoring service, the re brigade and the owner of the building, or his agent, before any action is taken.I the fre brigade attends unnecessarily, you could be charged or their attendance; and

b) Before turning off the water, a thorough check of the whole premises must be made, to ensure safety from athreat o fre as much as possible; and

c) Ensure all other re suppression euipment is fully operational.

After this work is completed, the hydrant system must be tested to ensure it operates at its designed performance level, andthe monitoring service and the fre brigade must be notifed that the system is again operational.

Whenever the system is disabled for maintenance or modications, special precautions should be implemented as detailed in

AS 1851-2005 Section 1 Clause 1.14.

BCA: E1.3 Reference: AS 2419

Page 73: Essential Safety Maintenance Manual

8/3/2019 Essential Safety Maintenance Manual

http://slidepdf.com/reader/full/essential-safety-maintenance-manual 73/290

E S S E N T I A L S A F E T Y M E A S U R E S M A I N T E N A N C E M A N U A L • B U I L D I N G C O M M I S S I O N

S E C T I O N 5 / P A G E 3

StreetHydrants

Where the RBS has approved the use of a street hydrant to achieve the hydrant coverage reuirement of AS 2419 – 2005 for

the building, owners should be aware that they do not have a right to maintain the hydrant. Section 165 (4) of the Water Act1989 identifes that the relevant water authority is responsible or the maintenance, identifcation and provisions o water tostreet hydrants.

However, the building owner should, as a minimum, undertake the following precautions for street hydrants:–

Veriy and document the presence o the street hydrant on a six-monthly basis.•

Ensure that the street hydrant is appropriately identifed.•

I the hydrant becomes unavailable or use the building owner must notiy the chie ofcer o the relevant fre•brigade without delay.

maintenance records

The maintenance records must record:–

a) All the inspections, testing and servicing procedures reuired under AS 1851-2005 Section 4; and

b) Details of defects found and unscheduled repairs carried out; and

c) Details of any remedial action taken.

All these details must be systematically entered in the log book established for the hydrant system. This log book should bemaintained by a person responsible for it, and must be available for inspection when reuired. In addition, AS 1851-2005Section 4 reuires that each hydrant must have a tag attached to it, showing the dates on which the si-monthly, yearly andfve-yearly procedures were carried out.

It is recommended that log sheets to record the completion o the maintenance are developed rom the tables or fre hydrantsystem as specied in AS 1851-2005 Section 4.

Page 74: Essential Safety Maintenance Manual

8/3/2019 Essential Safety Maintenance Manual

http://slidepdf.com/reader/full/essential-safety-maintenance-manual 74/290

S E C T I O N 5 / P A G E 4

E S S E N T I A L S A F E T Y M E A S U R E S M A I N T E N A N C E M A N U A L • B U I L D I N G C O M M I S S I O N

5.2 F IrE hOSE rEEl SySTEm

PURPOSE

Fire hose reels are be provided to enable occupants to undertake initial re extinguishment.

REQUIREMENTS OF THE EQUIPMENT

Fire hose reel systems must:–

Provide sucient hose reel length to enable every part o the foor or storey on which it is installed to be reached•by laying the hose along normal lines o access throughout that foor; and

Be provided with a water supply rate of at least 0.33 litres/second for 19 mm hose (AS 2441).•

Be provided with a water supply rate of at least 0.41 litres/second for 25 mm hose (AS 2441).•

METHOD OF OPERATION

The occupants o the premises should be able to operate the system:–

By locating any re hose reel within the building.•

By following the operating instructions displayed on the re hose reel.•

It is essential that all sta personnel on the premises are trained in the sae and ecient operation o re hose reels

MAINTENANCE CHECKS

It is recommended that the relevant building surveyor should require that re hose reels be maintained at six-monthly

intervals to AS 1851-2005 Section 14.

Note: Where a pump set is installed to supply the required water pressure to the re hose reel system, the requency

of inspection and testing shall be carried out weekly as per the requirements of AS 1851- 2005 Section 3.

Maintenance work involving inspections, testing and servicing, has been specied by AS 1851-2005 at theollowing requencies:–

Six-monthly•

Yearly•

When deects are detected•

The maintenance and inspection may be carried out by the owner. The owner may delegate this unction to another person

or body where necessary or appropriate.

It is essential that the hose is rewound in even layers, the nozzle re-engaged correctly in the interlock, the valve shut o, and

the hose de-pressurised by opening the discharge nozzle. Close the nozzle when de-pressurised.

Any deects ound should be reported to management and the necessary repairs or replacement carried out as soon aspossible, to ensure the equipment is ready or use i needed. In addition, a label showing the date o service and a descriptiono the ault should be attached to the side plate o the aulty re hose reel.

Whenever the system is disabled or maintenance or modications, special precautions should be implemented as detailed

in AS 1851-2005 Section 1 Clause 1.14.

BCA: E1.4 Reference: AS 2441

Page 75: Essential Safety Maintenance Manual

8/3/2019 Essential Safety Maintenance Manual

http://slidepdf.com/reader/full/essential-safety-maintenance-manual 75/290

E S S E N T I A L S A F E T Y M E A S U R E S M A I N T E N A N C E M A N U A L • B U I L D I N G C O M M I S S I O N

S E C T I O N 5 / P A G E 5

maintenance records

A log book, showing the location and identifying marks or numbers for each re hose reel on the premises, must be established.

In addition, AS 1851-2005 Section 4 reuires each hydrant to have a tag attached to it, showing the dates on which the si-monthly, yearly and fve-yearly procedures were carried out.

The ollowing inormation must be recorded:–

a) The date of each inspection carried out; and

b) Any defects found; and

c) On the tag attached to each re hose reel, the date of each inspection.

It is recommended that log sheets to record the completion o the maintenance are developed rom the tables or fre hosereel system as specied in AS 1851-2005 Section 4.

Page 76: Essential Safety Maintenance Manual

8/3/2019 Essential Safety Maintenance Manual

http://slidepdf.com/reader/full/essential-safety-maintenance-manual 76/290

E S S E N T I A L S A F E T Y M E A S U R E S M A I N T E N A N C E M A N U A L • B U I L D I N G C O M M I S S I O N

S E C T I O N 5 / P A G E 6

5 . 3 S P R I N k l E R S Y S T E M

PurPose

A sprinkler system is installed to provide a full-time automatic re suppression system, with the ability to summon the re

brigade automatically.

systems and equiPment

Automatic sprinkler systems may include:–

Wet pipe systems and sprinklers;•

Valve installations;•

Electric motor and compression-ignition engines and pumpsets;•

Fire brigade booster connections;•

Pre-action systems;•

Water storage systems;•

Alarms and interace with automatic fre alarm and detection systems where installed.•

requirements of the equiPment

To provide the reuired protection, the sprinkler system must be:–

a) An automatic re sprinkler system complying with:– AS 2118 subject to Building Code of Australia Specication E1.5;or

b) Maintained in accordance with AS 1851-2005 Section 2, either by or under the direct supervision of personnelcompetent in sprinkler system maintenance.

It should be noted that AS 1851-2005 Section 2 only species maintenance for sprinkler systems designed in accordancewith the AS 2118 series. Other sprinkler systems, such as NFPA 13R systems, are specialised systems and reuire specicmaintenance. Further details on maintaining specialised sprinkler systems are provided later in this section.

method of oPeration

To comply with AS 2118, the sprinkler system must have:–

a) Provision for an adeuate water supply; and

b) A pumping system to pressurise the sprinkler system; and

c) A distribution pipe system to deliver water to each sprinkler head; and

d) Sprinkler heads to perform according to the risk they are protecting; and

e) A local alarm facility to alert the operation of a sprinkler system; and

f) A direct alarm connection to the monitoring service (where reuired).

The sprinkler system is activated by a sprinkler head or heads responding to a rise in temperature. Water ows through thehead(s), lowering the residual water pressure, which causes the pump system to come into operation. Water owing throughthe system drives the water-motor in the local alarm, sounding the alarm bell. Where tted, a direct alarm is transmitted tothe monitoring service.

BCA: E1.5, H1.2, G3.8 Reference: AS 2118

Page 77: Essential Safety Maintenance Manual

8/3/2019 Essential Safety Maintenance Manual

http://slidepdf.com/reader/full/essential-safety-maintenance-manual 77/290

E S S E N T I A L S A F E T Y M E A S U R E S M A I N T E N A N C E M A N U A L • B U I L D I N G C O M M I S S I O N

S E C T I O N 5 / P A G E 7

maintenance checKs

It is recommended that the relevant building surveyor reuire that re mains be maintained weekly to AS 1851-2005.

It should be noted that this is the lowest level o maintenance routines required by the Standards. More rigorous routinesare also reuired by AS 1851-2005 Section 2 and are outlined below. The owner may delegate this function to anotherperson or body where necessary or appropriate.

The sprinkler system maintenance program is specied in AS 1851-2005 Section 2. For re pump sets the freuency ofinspection and testing shall be carried out weekly as per the reuirements of AS 1851- 2005 Section 4.3.2 and Table 4.4.1and 4.4.2 unless the provisions AS 1851- 2005 Section 3.2.1 have been satised.

Maintenance work, involving inspections, testing and servicing, have been specied by AS 1851-2005 at theollowing requencies:–

Weekly•

Monthly•

Six-monthly•

Yearly•

Three-yearly•

Twelve-yearly•

Twenty our-yearly•

The detail for these routines are detailed in table form in AS 1851 – Section 2.

Whenever the system is disabled for maintenance or modications, special precautions should be implemented as detailed inAS 1851-2005 Section 1 Clause 1.14.

The ollowing additional precautions should be observed, as ar as is practicable, when your system is inoperative through anemergency or planned occurrence:–

a) Under all circumstances, keep as much of the system fully operational as is practicable. If the necessary work isto etend over several days or weeks, re-instate the system as far as is practicable at the end of each working day.

b) Where the system has to be left disconnected outside working hours, consideration should be given to employinga watchman while the system is disconnected.

c) Whenever it is possible, disconnection of your system should be undertaken when production machineryis inoperative.

d) While the system is down, smoking should be banned in the affected areas.

e) Notify senior department personnel or tenants’ representatives of the situation, so that re-etinguishingappliances can be kept immediately available, with trained personnel on hand to use them if necessary.

f) Notify the insurer or insurance broker of the situation.

g) Have all necessary euipment and material available and do all the work possible prior to isolating the sprinklers.

h) Hot cutting or welding should be avoided, where possible, in an area where the sprinkler system it not operational.This includes work on the sprinkler system.

i) Avoid all sources of ignition.

Maintenance testing o these systems should be carried out in conjunction with the fre alarm system testing to assurethat the systems are correctly interaced.

Prior to and ollowing this test, it is essential that the monitoring service that receives the alarm shall be advised o theimminent test, checked to see the test call was received, and advised when the system is re-set and operational.

Page 78: Essential Safety Maintenance Manual

8/3/2019 Essential Safety Maintenance Manual

http://slidepdf.com/reader/full/essential-safety-maintenance-manual 78/290

E S S E N T I A L S A F E T Y M E A S U R E S M A I N T E N A N C E M A N U A L • B U I L D I N G C O M M I S S I O N

S E C T I O N 5 / P A G E 8

CombinedSprinerandHydrantSystem

Maintenance for combined sprinkler and hydrant systems shall be carried out in accordance with AS 1851-2005 Clauses 2.4.1

to 2.4.1.4 for sprinklers and Clauses 4.4.1 to 4.4.4 for hydrant systems.

SpeciaisedSprinerSystems

Maintenance of sprinkler systems that have been designed for specic purposes, such as Early Suppression Fast Response(ESFR), NFPA 13R systems or FM Global designed reuirements, should be specied by the designer of the system. It isimperative that the designer of the system provide an appropriate maintenance schedule for the sprinklers, pumpsets andre mains in the building. Engineers may specify documents such as NFPA 25 – ‘maintenance of sprinkler systems’ as parto a maintenance regime. It is thereore important that owners obtain copies o the documentation or their records.

maintenance records

Records of all maintenance routines must be in a log book kept at the sprinkler control valves.

It is recommended that log sheets to record the completion o the maintenance are developed rom the tablesfor sprinkler systems as specied in AS 1851-2005 Section 2.

Page 79: Essential Safety Maintenance Manual

8/3/2019 Essential Safety Maintenance Manual

http://slidepdf.com/reader/full/essential-safety-maintenance-manual 79/290

E S S E N T I A L S A F E T Y M E A S U R E S M A I N T E N A N C E M A N U A L • B U I L D I N G C O M M I S S I O N

S E C T I O N 5 / P A G E 9

5 . 4 P O R T A B l E F I R E E x T I N G U I S H E R S

PurPose

Portable re etinguishers provide occupants with an appliance with which to attack a re in its initial stages.

requirements of the equiPment

Fire etinguishers must contain an etinguishing agent suitable for the re haard likely to be encountered. Fire etinguisherscomplying with Australian Standards are marked with a re classication and rating, determined in accordance with AS/NzS1850, which indicates the class and sie of re for which they have been successfully tested.

Each extinguisher must be located in the approved location that must be a conspicuous and readily accessible position.AS 2444 sets out the types and locations reuired for portable re etinguishers, the locations being indicated by theappropriate signage.

method of oPeration

A fre extinguisher is put into operation by transporting the extinguisher close to the fre and ollowing the operatinginstructions clearly displayed on the extinguisher.

It is essential that all sta members are suitably trained in the correct use o fre extinguishers located on the premises.

maintenance checKs

It is recommended that the relevant building surveyor should require that fre extinguishers be maintained six-monthly to AS1851-2005 Section 15. It should be noted that this is the lowest level of maintenance routines reuired by AS 1851-2005.More rigorous routines are also required and are outlined below. The owner may delegate this unction to another person orbody where necessary or appropriate.

The intervals of inspection and service are detailed in AS 1851-2005 Section 15:–

Six-monthly•

Yearly•

Five-yearly•

Ater use o the extinguisher•

A comprehensive maintenance schedule is detailed in AS 1851-2005 Section 15 for all types of re etinguishers.All maintenance work must be carried out by eperienced personnel, observing recognised safety procedures.

maintenance records

For the purpose of maintaining service records, clause 15.2.15 in AS 1851-2005 outlines:–

a) Each etinguisher in the premises must have a uniue site identication mark.

b) If more than 10 etinguishers are located in or on the premises, a site plan showing the location of each etinguisherand its identication, type, sie and rating, must be provided.

c) A maintenance record tag must be attached to each etinguisher.

d) A report on the correct provision and location of etinguishers must be provided by the service agency or personnel.

It is recommended that log sheets to record the completion o the maintenance are developed rom the tables or portable freetinguishers as specied in AS 1851-2005 Section 15.

BCA: E1.6 Reference: AS 2444

Page 80: Essential Safety Maintenance Manual

8/3/2019 Essential Safety Maintenance Manual

http://slidepdf.com/reader/full/essential-safety-maintenance-manual 80/290

E S S E N T I A L S A F E T Y M E A S U R E S M A I N T E N A N C E M A N U A L • B U I L D I N G C O M M I S S I O N

S E C T I O N 5 / P A G E 1 0

5 . 5 F I R E C O N T RO l C E N T R ES ( O R RO O M S )BCA: E1.8

PurPose

A fre control centre is provided as an area rom which fre-fghting operations or emergency procedures can be directed or controlled.

requirements

The fre control centre or room must:–

a) Contain the controls, panels, telephones, furniture and euipment associated with the reuired re services in thebuilding; and

b) Only be used for re-ghting and other reasons concerning the safety or security of the building occupants; and

a. Be accessible via two ways:–

i. rom the ront entrance o the building; or

ii. direct rom outside the building; and

b. Have the following as detailed in Spec E1.8 of the Building Code of Australia:–

i. sufcient oor area for its proper functioning ; and

ii. adequate ventilation; and

iii. suitable power supply; and

iv. emergency lighting; and

v. a sign on the outside o the door identiying it as the ‘Fire Control Centre’; and

vi. low noise level with all fre saety equipment operating.

maintenance checKs

To ensure the fre control centre is operational, it is recommended that maintenance be carried out as ollows:–

YEARlY

It is recommended that the relevant building surveyor should require an annual inspection o this acility. The owner maydelegate this unction to another person or body where necessary or appropriate.

It is also recommended that an eercise be held at least yearly to ensure this facility is workable.

This exercise could be held in conjunction with:–

a) The re authority serving the area.

b) An evacuation eercise for the premises.

maintenance records

The ollowing inormation must be recorded:–

a) The dates the monthly and yearly inspections were carried out; and

b) The name of the person conducting the inspections; and

c) Any problems identied in the inspection; and

d) Actions taken to rectify problems identied; and

e) Date this rectication occurred; and

f) Signature of the person conducting the inspection.

Inormation relating to the conduct o an evacuation exercise could also be recorded.

A log sheet to record this inormation is provided in Appendix C o this manual.

Page 81: Essential Safety Maintenance Manual

8/3/2019 Essential Safety Maintenance Manual

http://slidepdf.com/reader/full/essential-safety-maintenance-manual 81/290

E S S E N T I A L S A F E T Y M E A S U R E S M A I N T E N A N C E M A N U A L • B U I L D I N G C O M M I S S I O N

S E C T I O N 5 / P A G E 1 1

BCA: E1.10 5 . 6 P R O V I S I O N S F O R S P E C I A l H A z A R D S

PurPose

Suitable additional provisions must be made i special fre-fghting problems could arise rom the nature or quantity o

materials stored, displayed, used in a building or stored on the allotment.

The location o the building in relation to available water supply or fre-fghting purposes may also require special equipmentto be installed in the building.

requirements

The application o the special provisions or fre-fghting purposes should be identifed early in the project by the designer othe building in conjunction with the services designers. Input may also be sought from the relevant building surveyor (RBS)at that time. The requirement or the level and requency o maintenance or the special provisions must be listed on thebuilding‘s occupancy permit or part o a determination on a certifcate o fnal inspection.

maintenance checKs

To ensure the special fre-fghting systems remain operational, it is recommended that the designer o the system outline themaintenance required. As the system is specifc to the building, the maintenance may be outside the ordinary requirementsof such standards of AS 1851-2005. It is important that owners ensure that they are aware of any special maintenancerequirements listed on an occupancy permit or determination that may aect their building.

maintenance records

Designers should at a minimum reuire the following information to be recorded:–

a) The dates the monthly and yearly inspections were carried out; and

b) The name of the person conducting the inspections; and

c) Any problems identied in the inspection; and

d) Actions taken to rectify problems identied; and

e) Date this rectication occurred; and

f) Signature of the person conducting the inspection.

A log sheet is not provided in this manual for special provisions. It is recommended that owners seek advice of the systemdesigner and/or the RBS on the appropriate level of documentation reuired.

Page 82: Essential Safety Maintenance Manual

8/3/2019 Essential Safety Maintenance Manual

http://slidepdf.com/reader/full/essential-safety-maintenance-manual 82/290

Page 83: Essential Safety Maintenance Manual

8/3/2019 Essential Safety Maintenance Manual

http://slidepdf.com/reader/full/essential-safety-maintenance-manual 83/290

Air handlingsystems

A i  r h  a n d  l  i  n g  s  y s  t  em s 

Page 84: Essential Safety Maintenance Manual

8/3/2019 Essential Safety Maintenance Manual

http://slidepdf.com/reader/full/essential-safety-maintenance-manual 84/290

E S S E N T I A L S A F E T Y M E A S U R E S M A I N T E N A N C E M A N U A L • B U I L D I N G C O M M I S S I O N

S E C T I O N 6 / P A G E 1

A i r H a n d i n g S y s t e m s

6.1 SMOKE HAzARD MANAGEMENT SYSTEMS 2

6.2 CAR PARK MECHANICAL VENTILATION SYSTEM 6

6.3 ATRIUM SMOKE CONTROL SYSTEM 8

Page 85: Essential Safety Maintenance Manual

8/3/2019 Essential Safety Maintenance Manual

http://slidepdf.com/reader/full/essential-safety-maintenance-manual 85/290

E S S E N T I A L S A F E T Y M E A S U R E S M A I N T E N A N C E M A N U A L • B U I L D I N G C O M M I S S I O N

S E C T I O N 6 / P A G E 2

6 . 1 S M O k E H A z A R D M A N A G E M E N T S Y S T E M SBCA: E2.2 

BCA Specication: E2.2 

Reference: AS 1668

PurPose

Smoke haard management systems ensure that, under re and smoke conditions, occupants have sufcient time to evacuate

before the evacuation route becomes untenable. Smoke and heat vents are installed to assist the discharge of smoke and heatgenerated by a fre.

This section does not apply to air conditioning, mechanical ventilation or natural ventilation systems that are not required tooperate in re and smoke control mode ecept if that system is reuired to shut down in re mode.

This section has been separated into two parts. The frst part deals with mechanical systems installed in accordance with AS1668, and the second specically details the maintenance of smoke and heat vents.

FIREANDSMOkECONTROlFEATURESOFHVACSYSTEMS

requirements of the equiPment

To ulfl its purpose, the system must:–

a) Be installed in accordance with Building Code of Australia (BCA) Specication E2.2 and AS 1668.1 – 1998; and

b) Respond to automatic heat or smoke-sensing euipment; and

c) Remove smoke from the re affected area to the outside atmosphere or, if reuired, provide a pressurised atmospherein re isolated eits to prevent entry of smoke from the re compartment; and

d) Have re and smoke dampers installed where penetrations occur.

METHODOFOPERATION

Air conditioning and mechanical ventilation systems modes o operation are typically classifed as Normal and Fire Mode:–

NormaMode

Systems operate in this mode to maintain acceptable indoor air quality when the building is occupied. Controls may be eithermanual or automatic.

FireMode

In the event o a fre being detected or reported via the fre alarm system, air conditioning and mechanical ventilation systemsare reuired to change over to re mode operation. In re mode the systems provide a purging or oned smoke controlstrategy. Purging strategies discharge air from the smoke one to outside whilst providing adeuate relief air. zoned control  systems aim to maintain the non-fre aected fre compartment at a positive pressure relative to the fre compartment.

Older systems installed prior to the introduction of AS 1668 may simply shut down on re mode to reduce the propagationof smoke through the building.

An automatic air handling system must be provided with manual override operation.Automatic operation can be accomplished by:–

• Time clock switching

• Thermostat-controlled switching

• Atmospheric contaminant monitoring

Page 86: Essential Safety Maintenance Manual

8/3/2019 Essential Safety Maintenance Manual

http://slidepdf.com/reader/full/essential-safety-maintenance-manual 86/290

E S S E N T I A L S A F E T Y M E A S U R E S M A I N T E N A N C E M A N U A L • B U I L D I N G C O M M I S S I O N

S E C T I O N 6 / P A G E 3

The smoke control system must:–

a) Respond to an automatic sensing of a re condition; and

a. Automatically activate the appropriate equipment to:–

i. Vent smoke to the atmosphere; and

ii. Introduce outside air to either within the same fre aected compartment or to the non-fre aectedcompartments; and

iii. Develop a positive air pressure in the re-isolated stairwells (where reuired); and

iv. Have a manual override acility to enable fre-fghting personnel to control the system.

The systematic reaction of the various components in the smoke and air handling systems will have been programmed intothis euipment during the design, installation and commissioning of the euipment in the building. Checks and maintenance ofan air handling system are recommended to be carried out in conjunction with the fre alarm system testing to assure that thesystems are correctly interaced.

maintenance checKs

It is recommended that the relevant building surveyor (RBS) should reuire that maintenance and inspection of smoke controlmeasures and stairwell pressurisation measures be carried out monthly to AS 1851-2005 Section 18.

Periodic testing and inspection is recommended by AS 1851-2005 Section 18 to be implemented:–

• Monthly

• quarterly

• Si-monthly

• Yearly

• Five-yearly

The owner may delegate these unctions to another person or body where necessary or appropriate.

To ensure ull compliance with this requirement, a maintenance program must be prepared, including:–

a) All data relevant to the smoke control system; and

b) A formal strategy and recording system for effective management of a series of maintenance procedures.

Impementation

The maintenance program must be implemented in accordance with the inormation and requirements o the maintenanceroutines set down in Section 18 of AS 1851-2005. Any follow-up action must be implemented as reuired in Section 1 of thatStandard.

maintenance records

Maintenance records should contain the ollowing inormation:–

a) Date, item of plant, euipment or system and nature of service performed; and

b) Details of defects found and rectication procedures undertaken; and

c) The name of the person or company performing the service.

The Standard also requires the provision o operating and maintenance manuals, a maintenance schedule, a plant register and aplant history record.

Page 87: Essential Safety Maintenance Manual

8/3/2019 Essential Safety Maintenance Manual

http://slidepdf.com/reader/full/essential-safety-maintenance-manual 87/290

E S S E N T I A L S A F E T Y M E A S U R E S M A I N T E N A N C E M A N U A L • B U I L D I N G C O M M I S S I O N

S E C T I O N 6 / P A G E 4

Further details for all the information in this section are available in AS 1851-2005 Section 18 Clause 18.2.4.

It is recommended that log sheets to record the completion o the maintenance are developed rom the tables as specifed in

AS 1851-2005 Section 18.

SMOkEANDHEATVENTS,SMOkECURTAINS

requirements of the equiPment

A smoke venting system is made up of the following components:–

a) Vents and their operating mechanism.

b) Draught curtains.

c) Inlet ventilation.

This system must be designed and installed in accordance with AS 2665.

method of oPeration

The system:–

a) Contains the smoke/heat within the connes of the smoke curtains.

b) Activates the vents, using the rising temperature, releasing the trapped smoke/heat to atmosphere.

c) Assists the ventilation process by introducing air to replace the rising smoke/heat column.

Operation of the system must be automatic, with a manual control in addition.

maintenance checKs

It is recommended that the RBS should reuire maintenance to be carried out at least every si months to AS 1851-2005Section 18 Clause 18.4.1.7 for smoke and heat vents and Clause 18.4.1.8 for smoke curtains. The owner may delegate thisunction to another person or body where necessary or appropriate.

Periodic testing and inspection is recommended by AS 1851-2005 to be implemented:–

• Si-monthly

• Yearly

• Five-yearly

maintenance records

Records must be developed and maintained to record the ollowing:–

a) Date of the inspection, test or maintenance; and

b) Name of the person carrying this out; and

c) Details of any faults detected; and

d) Action taken to rectify any faults detected; and

e) Date on which any faults were rectied.

It is recommended that log sheets to record the completion o the maintenance are developed rom the tables as specifed inAS 1851-2005 Section 18.

Page 88: Essential Safety Maintenance Manual

8/3/2019 Essential Safety Maintenance Manual

http://slidepdf.com/reader/full/essential-safety-maintenance-manual 88/290

E S S E N T I A L S A F E T Y M E A S U R E S M A I N T E N A N C E M A N U A L • B U I L D I N G C O M M I S S I O N

S E C T I O N 6 / P A G E 5

SMOkEANDFIREDAMPERS

requirements of the equiPment

Smoke and re dampers are installed within the ducting of HVAC systems to maintain the re and/or smoke integrity of walland oors where those elements are reuired to resist the spread of re or smoke.

Fire and smoke dampers must be designed and installed in accordance with AS 1682.

method of oPeration

a) Fire dampers are activated by using the rising temperature within the HVAC ducting; and

b) Smoke dampers are activated by the detection of smoke within the HVAC ducting; and

c) The system contains the smoke/heat within the connes of the area of origin.

Operation of re and smoke dampers must be automatic.

maintenance checKs

It is recommended that the RBS should reuire maintenance at least every ve years to AS 1851-2005 Section 18 Clause18.4.1.3 for re dampers and Clause 18.4.1.4 for smoke curtains. The owner may delegate this function to another personor body where necessary or appropriate.

Periodic testing and inspection is recommended by AS 1851-2005 to be implemented:–

• Five-yearly

Note: 20% of dampers should be inspected annually so that all dampers have been inspected by the fth year.Tagging, labelling or a log book may be necessary for verication.

maintenance records

Records must be developed and maintained to record the ollowing:–

a) Date of the inspection, test or maintenance; and

b) Name of the person carrying this out; and

c) Details of any faults detected; and

d) Action taken to rectify any faults detected; and

e) Date on which any faults were rectied.

It is recommended that log sheets to record the completion o the maintenance are developed rom the tables as specifed in

AS 1851-2005 Section 18.

Page 89: Essential Safety Maintenance Manual

8/3/2019 Essential Safety Maintenance Manual

http://slidepdf.com/reader/full/essential-safety-maintenance-manual 89/290

E S S E N T I A L S A F E T Y M E A S U R E S M A I N T E N A N C E M A N U A L • B U I L D I N G C O M M I S S I O N

S E C T I O N 6 / P A G E 6

BCA: F4.11 E2.2

Reference: AS1668.1, AS1668.2

6 . 2 C A R P A R k M E C H A N I C A l V E N T I l A T I O N S Y S T E M

PurPose

To ensure that car fumes are adeuately removed and under re and smoke conditions within a car park area, occupants

have sufcient time to evacuate beore the evacuation route becomes untenable.

Note: This section does not apply to an open deck car park because such car parks are provided with adeuate permanentnatural ventilation.

requirements of the equiPment

To full its purpose, a car park ventilation system must:–

a) Be installed in accordance with AS 1668.2 1991, E2.2 or be provided with adeuate natural ventilation; and

b) Respond to automatic heat or smoke sensing euipment; and

c) Be such that supply air ventilation system shuts down on detection of re or smoke; and

d) Continue to operate in the event of re in the car park.

method of oPeration

Car park ventilation systems modes of operation are typically classied as Normal Mode and Fire Mode:

NormaMode

Systems operate in normal mode to maintain acceptable air uality when the car park is occupied. Controls may be eithermanual or automatic.

FireMode

In the event of a re being detected or reported via the re alarm system, car park ventilation systems are reuired to changeover to re mode operation. In re mode the systems provide a purging control strategy. The purging strategy of car parkventilation is to discharge air from the car park to outside.

An automatic air handling system must be provided with manual override operation.

Automatic operation can be accomplished by:–

• Time clock switching; or

• Thermostat controlled switching; or

• Atmospheric contaminant monitoring.

A car park ventilation system shall also be provided with the following in accordance with AS 1668.1 Clause 5.5:–

• Fireisoation – Any mechanical components of the ventilation system located outside the car park re compartment

and within another fre compartment shall be isolated rom that fre compartment with construction to maintain thereuired FRL (Fire Resistance Level).

• Contro – To enable manual control by authorised re personnel, each fan shall be provided with an ON-AUTO-OFFcontrol device installed in the FFCP (Fire Fan Control and Indication Panel).

• Smoedetectors – Smoke detectors shall be installed in the supply air system in accordance with Clause 4.10.5(b)of AS 1668.1.

• Operation – Ehaust air systems shall continue to operate in the event of re in the car park. Where the systemincorporates variable airow rates, it shall automatically switch to its full capacity on activation of any re alarm orsprinkler system in the car park. Supply air systems shall shut down upon the receipt of a re alarm signal from thesupply air detector.

Page 90: Essential Safety Maintenance Manual

8/3/2019 Essential Safety Maintenance Manual

http://slidepdf.com/reader/full/essential-safety-maintenance-manual 90/290

E S S E N T I A L S A F E T Y M E A S U R E S M A I N T E N A N C E M A N U A L • B U I L D I N G C O M M I S S I O N

S E C T I O N 6 / P A G E 7

The systematic re-action of the various components in the car park ventilation will have been programmed into thiseuipment during the design, installation and commissioning of the euipment into your building. Checks and maintenance ofa ventilation system are recommended to be carried out in conjunction with the fre alarm system testing to assure that the

systems are correctly interaced.

maintenance checKs

It is recommended that the relevant building surveyor should reuire that maintenance and inspection of car park ventilationmeasures be carried out monthly to AS 1851-2005 Section 18. The owner may delegate these functions to another person orbody where necessary or appropriate.

To ensure ull compliance with this requirement, a maintenance program must be prepared, including:–

a) All data relevant to the car park ventilation system; and

b) A formal strategy and recording system for effective management of a series of maintenance procedures.

The maintenance program must be implemented in accordance with the inormation and requirements o the maintenanceroutines set down in Section 18 of AS 1851-2005. Any follow-up action must be implemented as reuired in Section 1 ofthat Standard.

maintenance records

Maintenance records should contain the ollowing inormation:–

a) Date, item of plant, euipment or system and nature of service performed; and

b) Details of defects found and rectication procedures undertaken; and

c) The name of the person or company performing the service.

AS 1851-2005 also reuires the provision of operating and maintenance manuals, a maintenance schedule, a plant register and

a plant history record.

Further details for all the information in this section are available in Section 18 of the Standard.

It is recommended that log sheets to record the completion o the maintenance are developed rom the tables as specifed inAS 1851-2005 Section 18.

Page 91: Essential Safety Maintenance Manual

8/3/2019 Essential Safety Maintenance Manual

http://slidepdf.com/reader/full/essential-safety-maintenance-manual 91/290

E S S E N T I A L S A F E T Y M E A S U R E S M A I N T E N A N C E M A N U A L • B U I L D I N G C O M M I S S I O N

S E C T I O N 6 / P A G E 8

BCA: G3.8BCA Specication: G3.8

6 . 3 A T R I U M S M O k E C O N T R O l S Y S T E M

PurPose

Smoke and re control systems within atriums ensure that occupants have sufcient time to evacuate before the evacuation

route becomes untenable. The reason for these additional reuirements is that there is an additional re haard associated withatriums and or the occupants evacuating them.

requirements of the equiPment

A re and smoke control system within an atrium is made up of the following components:–

a) Installation of a sprinkler system in every building which contains an atrium in accordance with Specication E1.5 ofthe Building Code of Australia (BCA); and

b) A mechanical air handling system including the installation of a smoke ehaust system; and

c) A re detection and alarm system; and

d) An emergency warning and intercommunication system; and

e) A standby power system; and

f) A system for ecluding smoke from re-isolated eits.

method of oPeration

Sprinersystems

In addition to Specication E1.5 and AS 2118 to comply with BCA Specication G3.8, the sprinkler system must also have theollowing:–

• Sprinkler heads must protect both the supporting structure and the roof membrane. The operating temperature of thesprinkler heads must be within the range of 79°C – 100°C; and

• The oor of the atrium must be protected with sprinkler heads either sidewall and overhead as dictated by theatrium; and

• If the atrium is separated from the remainder of the building by walls or doors incorporating glaing, wall-wettingsprinklers are to be installed; and

• Appropriate water supply for the building and the atrium sprinkler system must be provided; and

• Stop valves for the atrium sprinklers must be provided.

Smoecontrosystem

A mechanical air handling system in a building containing an atrium must comply with AS/NzS 1668.1 and be varied so that asystem serving the atrium is designed to operate as ollows:–

• Maintain a tenable atmosphere in all paths of travel along balconies to reuired eits; and

• Smoke ehaust fans only operate when smoke enters the atrium; and

• Central plant systems do not use the atrium as a return air path; and

• Activation of the smoke control system must be activated by:–

- Operation of the automatic re alarm; or

- Operation of the a sprinkler system; or

- A manual start switch.

Page 92: Essential Safety Maintenance Manual

8/3/2019 Essential Safety Maintenance Manual

http://slidepdf.com/reader/full/essential-safety-maintenance-manual 92/290

E S S E N T I A L S A F E T Y M E A S U R E S M A I N T E N A N C E M A N U A L • B U I L D I N G C O M M I S S I O N

S E C T I O N 6 / P A G E 9

• All controls for the smoke control system must be:–

- Located in the fre control room or emergency control centre; or

- Adjacent to the sprinkler control valves; or

- Incorporated in the Fire Indicator Board.

• A smoke ehaust system must be specically design to meet the reuirements of Specication G3.8 clause 3.4 and3.5, suitable to the sie of re and height of the smoke plume; and

• Smoke ehaust fans must be capable of continuous and reuired operation for a period of not less than one hourwhen handling ehaust gasses of 200°C; and

• Smoke and heat vents in lieu of ehaust fans may be used; and

• Make up air to the atrium must be provided from the outside and relief air from non-re storeys.

Firedetectionandaarmsystems

Automatic re detection and alarm systems must be provided within the atrium and must comply with AS1670.1 eceptwhere varied by Specication G3.8.

EmergencyWarningandIntercommunicationSystem(EWIS)

A building that contains an atrium must be provided with an EWIS that complies with AS1670.4 and AS 4428.4 and must alsoincorporate a visible warning sign, which, upon the ‘action’ signal, displays the words ‘EVAC AREA’. The lettering must complywith the requirements o the provisions o Building Code of Australia Part E4 for eit signs.

Standbypowersystems

I a required path o travel to an exit is within an atrium, a suitable alternative power supply must be provided to operatereuired safety systems including sprinkler systems, re hydrant pumps, air handling systems alarms, warning and

communication systems and emergency lighting circuits.

Systemforecudingsmoefromre-isoatedeits

Where a re-isolated eits serves an atrium, the eit must be provided with a pressurisation system in accordance with AS/NzS1668.1, commonly known as a stair pressurisation system.

maintenance checKs

Maintenance o the above systems should be included as part o the overall building maintenance. Each system has its ownmaintenance details as provided within this manual:–

• Sprinklers – Section 5.3

• Air Handling systems – Section 6.1

• Fire-Detection and Alarm Systems – Section 7.3

• Emergency Warning and Communication-systems – Section 8.1

• Standby Power – Section 10.1

• System for Ecluding Smoke from Fire-Isolated Eits – Section 6.1

Owners should ensure that where systems include specic provisions for atriums that the maintenance of those essentialsaety measures is included.

maintenance records

As per the appropriate section o this manual or each o the services.

Page 93: Essential Safety Maintenance Manual

8/3/2019 Essential Safety Maintenance Manual

http://slidepdf.com/reader/full/essential-safety-maintenance-manual 93/290

Page 94: Essential Safety Maintenance Manual

8/3/2019 Essential Safety Maintenance Manual

http://slidepdf.com/reader/full/essential-safety-maintenance-manual 94/290

Automaticfre-detectionand alarm

systems

A  u t   om a  t  i   c f r  e- d  e t   e c  t  i   on

 a n d  a  l   a r m  s 

  y s  t   em s 

Page 95: Essential Safety Maintenance Manual

8/3/2019 Essential Safety Maintenance Manual

http://slidepdf.com/reader/full/essential-safety-maintenance-manual 95/290

E S S E N T I A L S A F E T Y M E A S U R E S M A I N T E N A N C E M A N U A L • B U I L D I N G C O M M I S S I O N

S E C T I O N 7 / P A G E 1

A u t o m a t i c F i r e - D e t e c t i o n a n d A a r m S y s t e m s

7.1 SMOKE AND HEAT ALARM SYSTEM 2

7.2 SMOKE AND HEAT-DETECTION SYSTEM 3

7.3 ATRIUM FIRE-DETECTION AND ALARM SYSTEMS 4

Page 96: Essential Safety Maintenance Manual

8/3/2019 Essential Safety Maintenance Manual

http://slidepdf.com/reader/full/essential-safety-maintenance-manual 96/290

E S S E N T I A L S A F E T Y M E A S U R E S M A I N T E N A N C E M A N U A L • B U I L D I N G C O M M I S S I O N

S E C T I O N 7 / P A G E 2

BCA: Clause 3 ofSpecifcation E2.2a

Reference: AS 3786

7 . 1 S M O k E A N D H E A T A l A R M S Y S T E M

PurPose

A smoke alarm system is installed to sense and provide warning of a re in its initial development stage. Proper operation

of this system will afford the building occupants the maimum amount of time to seek safe refuge.

requirements of the equiPment

A smoke alarm system must be installed and operate as follows:–

a) Sense the presence of a re and advise its location; and

b) Advise the re brigade; and

c) Connected to consumer mains; and

d) In a building in which sprinklers are not installed, be connected to a building occupant warning system.

In kitchens and other areas where the use of the area is likely to result in a smoke alarm causing spurious signals, heat alarms

may be installed in lieu of smoke alarms or an alarm acknowledgement facility may be installed. If the kitchen or other area issprinkled then heat alarms need not be installed.

METHODOFOPERATION

Alarms are installed throughout a building to comply with AS 3786. This Standard does not designate the location of where thealarm is to be installed. In a building that is not protected with a sprinkler system the location must be in accordance with thereuirements for smoke detectors in AS 1670.1.

maintenance checKs

It is recommended that the relevant building surveyor should require the acilities to be inspected monthly. It should benoted that this is the lowest level of maintenance routines reuired by AS 1851-2005 Section 7. More rigorous si-monthlyand yearly routines are also required and are detailed in the Standard. The owner may delegate the maintenance unction toanother person or body where necessary or appropriate.

MAINTENANCERECORDS

It is recommended that log sheets to record the completion o the maintenance are developed rom the tables as specifed inAS 1851-2005 Section 7.

Page 97: Essential Safety Maintenance Manual

8/3/2019 Essential Safety Maintenance Manual

http://slidepdf.com/reader/full/essential-safety-maintenance-manual 97/290

E S S E N T I A L S A F E T Y M E A S U R E S M A I N T E N A N C E M A N U A L • B U I L D I N G C O M M I S S I O N

S E C T I O N 7 / P A G E 3

BCA: Clause 4 ofSpecifcation E2.2a

Reference: AS 1670

7 . 2 S M O k E A N D H E A T - D E T E C T I O N S Y S T E M

PurPose

A smoke-detection and alarm system is installed to sense and provide warning of a re in its initial development stage.

Proper operation of this system will afford the building occupants the maimum amount of time to seek safe refuge.

requirements of the equiPment

A smoke-detection system must automatically:–

a) Sense the presence of a re and advise its location; and

b) Advise the re brigade if reuired; and

I installed:–

a) Switch the air handling system into the smoke ventilating mode; and

b) Activate the closure of smoke and re-isolating doors; and

c) Activate necessary re pumps.

In kitchens and other areas where the use of the area is likely to result in smoke detectors causing spurious signals, heatdetectors may be installed in lieu of smoke alarms or an alarm acknowledgement facility may be installed. If the kitchenor other area is sprinklered then heat alarms need not be installed.

In addition to these automatically activated unctions, the alarm system may have a manual means o activation.

method of oPeration

Detectors of differing types are installed throughout the building to comply with AS 1670. The Standard designates thelocation and the suitable detector type to be installed.

A signal rom a detector is relayed to the control and indicating equipment in the system, which activates the various

responses listed above.

maintenance checKs

It is recommended that the relevant building surveyor should require the acilities to be inspected monthly. It should benoted that this is the lowest level of maintenance routines reuired by AS 1851-2005 Section 6. More rigorous routinesare also required and are outlined below. The owner may delegate this unction to another person or body where necessaryor appropriate.

The intervals of inspection and service are detailed in AS 1851-2005 Section 6:–

• Monthly

• Si-monthly

• Yearly

• Five-yearly

maintenance records

It is recommended that log sheets to record the completion o the maintenance are developed rom the tables as specifed inAS 1851-2005 Section 6.

Page 98: Essential Safety Maintenance Manual

8/3/2019 Essential Safety Maintenance Manual

http://slidepdf.com/reader/full/essential-safety-maintenance-manual 98/290

E S S E N T I A L S A F E T Y M E A S U R E S M A I N T E N A N C E M A N U A L • B U I L D I N G C O M M I S S I O N

S E C T I O N 7 / P A G E 4

BCA: Clause 4 ofSpecication G3.8 

Reference: AS1670.1

7 . 3 AT R I U M F I R E - DE T E C T I O N A N D A l A R M S YS T E M S

PurPose

A fre-detection and alarm system installed within an atrium is to sense and provide warning o a fre in its initial development

stage. The Building Code of Australia (BCA) includes variations to AS 1670.1. The reason for these additional reuirements isthere is an additional re haard associated with an atrium and for the occupants evacuating them.

requirements of the equiPment

A re-detection and alarm system must be installed in accordance with AS 1670.1 with the following additions for atriums:–

a) Smoke-detection within an atrium:

a. Must be provided within all outside air intakes and at individual oor return air intakes of all air handling systemsto initiate automatic re mode operation, and where applicable, comply with the restart facilities in AS/NzS1668.1; and

b. Must operate at an obscuration level not greater than 0.5% per metre with compensation for eternal airbornecontamination as necessary; and

c. Must sample air within the atrium and in storeys where the bounding wall is set back more than 3.5 m from theatrium well; and

d. Must be calibrated to compensate for smoke dilution where sampling occurs within return air path common tomore than one room; and

e. May incorporate beam type detectors to sense smoke in an atrium in a Class 5, 6, 7 or 8 building with an effectiveheight of not more than 25 m if:

i. the beam detectors are located at intervals o not more than three storeys; and

ii. arranged to scan at 90 degrees orientation to adjacent beam units.

b) Smoke-detection systems must be located at all return and relief air openings associated with the building air

handling systems and be:a. Of the sampling type system; or

b. The point type optical smoke detector.

c) Alarm systems must include the following:

a. A break-glass re alarm point must be provided at each door to a re-isolated stairway, re-isolated ramp, orfre-isolated passageway.

b. A staged alarm must be provided where an air sampling type smoke detection system is provided for the atrium,and must operate as ollows:

i. Alert building management when abnormal smoke levels of 0.03% obscuration per metre are detected; and

ii. Initiate a second alarm to management and start all smoke control systems including pressurisation of escaperoutes when smoke levels of 0.07% obscuration per metre are detected; and

iii. Automatically call the fre brigade, activate the emergency warning and intercommunication systems, andde-activate all plant not necessary for re safety within the building when smoke levels of 0.09% obscurationper metre are detected.

c. Beam and point type smoke detectors reuired must simultaneously operate all functions referred to above andactivate at the level set out in AS/NzS 1668.1.

Page 99: Essential Safety Maintenance Manual

8/3/2019 Essential Safety Maintenance Manual

http://slidepdf.com/reader/full/essential-safety-maintenance-manual 99/290

E S S E N T I A L S A F E T Y M E A S U R E S M A I N T E N A N C E M A N U A L • B U I L D I N G C O M M I S S I O N

S E C T I O N 7 / P A G E 5

method of oPeration

The method of operation has been detailed in Section 7.2 of this manual ecept where noted above.

maintenance checKs

It is recommended that the relevant building surveyor should require the fre-detection and alarm system within an atriumto be maintained in accordance with the provisions of AS 1851-2005 Section 6. It is recommended that the provisions forre-detection and alarm systems in atriums be maintained in conjunction with smoke detection systems as detailed inSection 7.2 of this manual. The owner may delegate this function to another person or body where necessary or appropriate.

The intervals of inspection and service are detailed in AS 1851-2005 Section 6:–

• Monthly

• Si-monthly

• Yearly

• Five-yearly

maintenance records

It is recommended that log sheets to record the completion o the maintenance are developed rom the tables as specifed inAS 1851-2005 Section 6.

Page 100: Essential Safety Maintenance Manual

8/3/2019 Essential Safety Maintenance Manual

http://slidepdf.com/reader/full/essential-safety-maintenance-manual 100/290

Page 101: Essential Safety Maintenance Manual

8/3/2019 Essential Safety Maintenance Manual

http://slidepdf.com/reader/full/essential-safety-maintenance-manual 101/290

Occupantwarning systems  O c 

 c  u p a n t  w a r ni  n g 

 s  y s  t  em s 

Page 102: Essential Safety Maintenance Manual

8/3/2019 Essential Safety Maintenance Manual

http://slidepdf.com/reader/full/essential-safety-maintenance-manual 102/290

S E C T I O N 8 / P A G E 1

E S S E N T I A L S A F E T Y M E A S U R E S M A I N T E N A N C E M A N U A L • B U I L D I N G C O M M I S S I O N

O c c u p a n t W a r n i n g S y s t e m s

8.1 EMERGENCY wARNING AND INTERCOMMUNICATION SYSTEM 2

8.2 BUILDING OCCUpANT wARNING SYSTEM 4

Page 103: Essential Safety Maintenance Manual

8/3/2019 Essential Safety Maintenance Manual

http://slidepdf.com/reader/full/essential-safety-maintenance-manual 103/290

E S S E N T I A L S A F E T Y M E A S U R E S M A I N T E N A N C E M A N U A L • B U I L D I N G C O M M I S S I O N

S E C T I O N 8 / P A G E 2

BCA: E4.9Clause 6 ofSpecication G3.8 

Reference: AS 1670.4

8 . 1 E ME R GE NCYWAR NINGAND  

I N T E R C O M M U N I C A T I O N S Y S T E M

PurPose

An emergency warning and intercommunication system (EWIS) is installed in a building to alert occupants in the event of an

emergency and enable an orderly evacuation o the building.

requirements of the equiPment

To full its function, the EWIS must have the following facilities:–

a) A master emergency control panel (MECP); and

b) Any necessary additional emergency control panels (ECP); and

c) The necessary distribution system to transmit a warning signal to each evacuation one in the building; and

d) A warden intercommunication point (WIP) located on each oor or in each evacuation one; and

e) A notice at each ECP giving clear instructions on how to operate this euipment correctly; and

f) An interconnection with the building re alarm system.

To ensure the system fulls its purpose, it is essential that all staff/personnel located in the building are given training inidentication of the ’alert‘ and ’evacuation‘ signals, both audible and visible, and take part in an evacuation eercise.

method of oPeration

A key reuirement for this system is the appointment of a house warden and a one warden for each evacuation onein the building.

These people should be appointed and trained to ulfl their respective roles.

In addition, each member of staff should be advised of the house and one wardens appointed, their duties, and the authoritydesignated to these wardens.

On activation of the re alarm system, the EWIS shall transmit the ‘alert’ signal until manual control of the systemis established. I manual control is not established in the pre-determined time or the system, the ‘evacuate’ signal isautomatically transmitted.

The ’alert’ signal must also be capable of manual initiation from each ECP and WIP.

I manual control is established, the house warden:–

• Attends the MECP; and

• Gathers information on the incident; and

• Makes a decision on evacuation; and

• Advises the one wardens of his decision; and

• Supervises the evacuation if ordered; and

• Becomes the focal point of contact with responding emergency services.

maintenance checKs

The maintenance routines in AS 1851-2005 Sections 9 and 10 reuire testing and checking of the system:–

• Monthly

• Si-monthly

• Yearly

• Five-yearly

Page 104: Essential Safety Maintenance Manual

8/3/2019 Essential Safety Maintenance Manual

http://slidepdf.com/reader/full/essential-safety-maintenance-manual 104/290

E S S E N T I A L S A F E T Y M E A S U R E S M A I N T E N A N C E M A N U A L • B U I L D I N G C O M M I S S I O N

S E C T I O N 8 / P A G E 3

Full details of the reuired monthly, si-monthly and yearly maintenance routines and the maintenance checks are detailed inAS 1851-2005 Sections 9 and 10.

These regular checks provide an opportunity to ensure the system is fully operational and to ensure all personnel are familiarwith the warning system.

Before carrying out a simulated re call to test the EWIS, the monitoring service receiving the alarm system shall be notied ofthe impending test. The building owner could be charged or the fre brigade’s attendance at a alse alarm.

Any necessary corrective action must be carried out as soon as practicable, to ensure the system is ully operationalat all times.

maintenance records

The following documents, reuired under AS 1670.4, must be provided for an EWIS by the suppliers of the system:–

a) Operator’s manual – this must give the necessary instruction on how to make the system work; and

b) An as-installed drawing showing the whole system; and

c) A bound log book, with numbered pages, showing the following information:–

i. Identifcation o the building; and

ii. Description of the system components and their location; and

iii. All commissioning data needed or uture maintenance, including:

1. All the necessary discharge rates and charging inormation or the batteries; and

2. Location and items o equipment not at the ECP; and

3. Maimum audio power available for each evacuation one; and

4. The actual audio power reuired for each evacuation one; and5. Date of commissioning; and

6. Pages to record the results of the monthly, si-monthly and yearly maintenance routines.

It is recommended that log sheets to record the completion o the maintenance are developed rom the tables as specifed inAS 1851-2005 Sections 9 and 10.

Page 105: Essential Safety Maintenance Manual

8/3/2019 Essential Safety Maintenance Manual

http://slidepdf.com/reader/full/essential-safety-maintenance-manual 105/290

E S S E N T I A L S A F E T Y M E A S U R E S M A I N T E N A N C E M A N U A L • B U I L D I N G C O M M I S S I O N

S E C T I O N 8 / P A G E 4

BCA: Clause 8 ofSpecication E1.5,Clause 6 ofSpecifcation E2.2a

Reference: AS 1670.4

8 . 2 B U I l D I N G O C C U P A N T W A R N I N G S Y S T E M

PurPose

A building occupant warning system is installed in a building to alert occupants in the event o an emergency and enable an

evacuation o the building.

requirements of the equiPment

To ulfl its unction, the building occupant warning system must have:–

a) A sound system for emergency purposes in accordance with AS 1670.4, initiated by the re-detection system. The realarm system shall monitor the sound system for fault signals reuired by AS 1670.4; or

b) Electronic sounders, or amplied sound systems producing the evacuation signal (with or without verbal message); or

c) The evacuation signal shall operate simultaneously throughout the building. At all places where warning signals areconveyed to building occupants, the A-weighted sound pressure level during the ‘on’ phases o the audible emergencyevacuation signal, measured with the time-weighting characteristic F (fast) (see AS 1259.1), shall comply with theollowing:

a. The reuirements of ISO 8201; and

b. Eceed by a minimum of 10 dB the ambient sound pressure level averaged over a period of 60 sec, not be lessthan 65 dB(A) and not more than 105 dB(A).

It is recommended that the default evacuation signal complying with ISO 8201 consists of a uniformly increasing freuencyduring the 0.5 sec on phase of the signal. Other signals may be more appropriate for use where the ambient noise will maskthe signal.

Measurement should be taken in the normal standing positions on the oor of coverage.

Additional visual and tactile signals shall be provided to augment the audible emergency evacuation signal i the averagedA-weighted sound pressure level of the background noise is higher than 95 dB. If the audible evacuation signal in the buildingis intended to arouse sleeping occupants, the minimum A-weighted sound pressure level of the signal shall be 75 dB at the bed

head, with all doors closed.

NOTE: 75 dB(A) may not be adeuate to awaken all sleeping occupants. Where occupants, such as patients in hospital wards,must not be subject to possible stress imposed by loud noises, the sound pressure level and message content shall be arrangedto provide warning for the staff and minimise patient trauma. The signal path to electronic sounders or speakers shall besupervised or open and short circuit conditions.

To ensure the system fulls its purpose, it is essential that all staff/personnel located in the building are given training inidentication of the ‘alert’ and ‘evacuation’ signals, both audible and visible, and take part in an evacuation eercise.

method of oPeration

A key reuirement for this system is the appointment of a house warden and a one warden for each evacuation one inthe building.

These people should be appointed and trained to ulfl their respective roles.

In addition, each member of staff should be advised of the house and one wardens appointed, their duties, and the authoritydesignated to these wardens.

On activation of the re alarm system, the building occupant warning systems shall transmit the ‘alert’ signal. In thepre-determined time or the system, the ’evacuate’ signal is automatically transmitted.

The ‘alert’ signal must also be capable of manual initiation from each Emergency Control Panel (ECP) and Warden IntercomPhone (WIP).

Page 106: Essential Safety Maintenance Manual

8/3/2019 Essential Safety Maintenance Manual

http://slidepdf.com/reader/full/essential-safety-maintenance-manual 106/290

E S S E N T I A L S A F E T Y M E A S U R E S M A I N T E N A N C E M A N U A L • B U I L D I N G C O M M I S S I O N

S E C T I O N 8 / P A G E 5

maintenance checKs

The maintenance routines in AS 1851-2005 Section 9 reuire testing and checking of the system:–

• Monthly

• Si-monthly

• Yearly

• Five-yearly

Full details of the reuired maintenance routines and maintenance checks are detailed in AS 1851-2005 Section 9.

These regular checks provide an opportunity to ensure the system is fully operational, and to ensure all personnel are familiarwith the warning system.

Before carrying out a simulated re call to test the building occupant warning system, the monitoring service receiving thealarm system, i required to be monitored, shall be notifed o the impending test. The building owner could be charged or the

fre brigade’s attendance at a alse alarm.Any necessary corrective action must be carried out as soon as practicable, to ensure the system is ully operationalat all times.

maintenance records

The ollowing documents must be provided by the suppliers o the system:–

a) Operator’s manual – this must give the necessary instruction on how to make the system work; and

b) An as-installed drawing showing the whole system; and

c) A bound log book, with numbered pages, showing the following information:

i) identication of the building; andii) description of the system components, and their location; and

iii) all commissioning data needed for future maintenance, including:

a) all the necessary discharge rates and charging information for the batteries; and

b) location and items of euipment not at the ECP; and

c) maimum audio power available for each evacuation one; and

d) the actual audio power reuired for each evacuation one; and

iv) date of commissioning; and

v) pages to record the results of the monthly and si-monthly maintenance routines.

It is recommended that log sheets to record the completion o the maintenance are developed rom the tables as specifed inAS 1851-2005 Section 9.

Page 107: Essential Safety Maintenance Manual

8/3/2019 Essential Safety Maintenance Manual

http://slidepdf.com/reader/full/essential-safety-maintenance-manual 107/290

Page 108: Essential Safety Maintenance Manual

8/3/2019 Essential Safety Maintenance Manual

http://slidepdf.com/reader/full/essential-safety-maintenance-manual 108/290

Lifts

L    i      f      t     s 

Page 109: Essential Safety Maintenance Manual

8/3/2019 Essential Safety Maintenance Manual

http://slidepdf.com/reader/full/essential-safety-maintenance-manual 109/290

E S S E N T I A L S A F E T Y M E A S U R E S M A I N T E N A N C E M A N U A L • B U I L D I N G C O M M I S S I O N

S E C T I O N 9 / P A G E 1

l i f t s

9.1 STRETCHER FACILITIES IN LIFTS 2

9.2 EMERGENCY LIFTS 3

9.3 PASSENGER LIFT FIRE SERVICE CONTROLS 4

Page 110: Essential Safety Maintenance Manual

8/3/2019 Essential Safety Maintenance Manual

http://slidepdf.com/reader/full/essential-safety-maintenance-manual 110/290

E S S E N T I A L S A F E T Y M E A S U R E S M A I N T E N A N C E M A N U A L • B U I L D I N G C O M M I S S I O N

S E C T I O N 9 / P A G E 2

9 . 1 S T R E T C H E R F A C I l I T I E S I N l I F T SBCA: E3.2 

AS 1735

PurPose

To provide adequate dimensions in a lit car to allow the use o a stretcher when a person is injured in a building where

ambulance personnel may be required to evacuate them.

requirements of the equiPment

In addition to the normal requirements or sae operation, the emergency lit must:–

a) Be installed in accordance with AS 1735.2; and

b) Have the following minimum clear space dimensions – 600 mm wide 2000 mm long 1400 mm high; and

c) Must be able to accommodate a raised stretcher with a patient on it horiontally.

maintenance checKs

Under the requirements o the Occupational Health and Safety (Plant) Regulations 1995, Clause 902 Part 2, an employer havingcontrol or management of a lift is reuired to ensure any risk to people travelling in the lift or associated with its use must beeliminated or reduced as ar as is practicable.

AS 1735.2 Appendi E reuires periodic inspection and testing of every installation at intervals of not more than one year andregular maintenance o installations at more requent intervals. Maintenance should be carried out in accordance with themanufacturer’s instructions and the periodic testing shall be carried out in accordance with AS 1735.10.

As well as the above reuirement for maintaining the lift the yearly inspection must include a check of the minimum reuiredclear space dimensions.

It is the owner’s responsibility to ensure a maintenance program is carried out eectively.

maintenance records

Records o periodic maintenance should be maintained and provided by your maintenance contractor.

A record o the yearly inspection must record:–

a) Dates the yearly inspections occurred; and

b) Name of the person conducting the inspections; and

c) Any problems identied in the inspection; and

d) Actions taken to rectify problems identied; and

e) Date the rectication occurred; and

f) Signature of the person conducting the inspection.

A log sheet to record this inormation is provided in Appendix C o this manual.

Page 111: Essential Safety Maintenance Manual

8/3/2019 Essential Safety Maintenance Manual

http://slidepdf.com/reader/full/essential-safety-maintenance-manual 111/290

E S S E N T I A L S A F E T Y M E A S U R E S M A I N T E N A N C E M A N U A L • B U I L D I N G C O M M I S S I O N

S E C T I O N 9 / P A G E 3

BCA: E3.4 Reference: AS 1735 

9 . 2 E M E R G E N C Y l I F T S

PurPose

To enable emergency services personnel to access any oor of the building normally serviced by the lift and carry out

emergency procedures and assist in occupant evacuation.

requirements of the equiPment

In addition to the normal requirements or sae operation, the emergency lit must: -

a) Be installed in accordance with AS 1735.2; and

b) Be provided with a re service control on the nominated oor, to enable eclusive control of the lift; and

c) Be provided with a re service control switch inside the lift car; and

d) Be provided with signs saying ’re service’, at the switch on the nominated oor and in the lift car; and

e) Have minimum dimensions suitable to accommodate a person on a stretcher if reuired; and

f) Have an identication label ’special re lift‘ on the mains supply switch for this lift.

maintenance checKs

Under the requirements o the Occupational Health and Safety (Plant) Regulations 1995, Clause 902 Part 2, an employer havingcontrol or management of a lift is reuired to ensure any risk to people traveling in the lift or associated with its use must beeliminated or reduced as ar as is practicable.

AS 1735.2 Appendi E reuires periodic inspection and testing of every installation at intervals of not more than one year andregular maintenance o installations at more requent intervals. Maintenance should be carried out in accordance with themanuacturer’s instructions.

It is the owner’s responsibility to ensure a maintenance program is carried out eectively.

maintenance records

Records o periodic maintenance should be maintained and provided by the maintenance contractor.

A record o the yearly inspection must record:–

a) Dates the yearly inspections occurred; and

b) Name of the person conducting the inspections; and

c) Any problems identied in the inspection; and

d) Actions taken to rectify problems identied; and

e) Date the rectication occurred; and

f) Signature of the person conducting the inspection.

A log sheet to record this inormation is provided in Appendix C o this manual.

 

Page 112: Essential Safety Maintenance Manual

8/3/2019 Essential Safety Maintenance Manual

http://slidepdf.com/reader/full/essential-safety-maintenance-manual 112/290

E S S E N T I A L S A F E T Y M E A S U R E S M A I N T E N A N C E M A N U A L • B U I L D I N G C O M M I S S I O N

S E C T I O N 9 / P A G E 4

BCA: E3.7 Reference: AS 1735 

9 . 3 P A S S E N G E R l I F T F I R E S E R V I C E C O N T R O l S

PurPose

In a passenger lift designed in accordance with AS 1735 Part 1 or 2, all lift cars serving any storey above an effective height of

12 m must be ftted with fre service controls.

requirements of the equiPment

In addition to the normal requirements or sae operation, a lit ftted with fre service controls must:–

a) Be installed in accordance with AS 1735.2; and

b) Be provided with a re service control on the nominated oor, to enable eclusive control of the lift; and

c) Be provided with a re service control switch inside the lift car; and

d) Have signs saying ’re service‘, at the switch on the nominated oor and in the lift car.

maintenance checKs

The fre service controls should be included as part o the yearly maintenance and inspection o the lit acility as set out inSections 9.1 and 9.2.

It is the owner’s responsibility to ensure a maintenance program is carried out eectively.

A log sheet to record this inormation is provided in Appendix C o this manual.

Page 113: Essential Safety Maintenance Manual

8/3/2019 Essential Safety Maintenance Manual

http://slidepdf.com/reader/full/essential-safety-maintenance-manual 113/290

Standby powersupply systems

 S  t  a n d  b 

 y p o w er 

 s  u p p l   y

 s  y s  t  em s 

Page 114: Essential Safety Maintenance Manual

8/3/2019 Essential Safety Maintenance Manual

http://slidepdf.com/reader/full/essential-safety-maintenance-manual 114/290

E S S E N T I A L S A F E T Y M E A S U R E S M A I N T E N A N C E M A N U A L • B U I L D I N G C O M M I S S I O N

S E C T I O N 1 0 / P A G E 1

S t a n d b y P o w e r S u p p y S y s t e m s

10.1 STANDBY POWER SUPPLY SYSTEM 2

Page 115: Essential Safety Maintenance Manual

8/3/2019 Essential Safety Maintenance Manual

http://slidepdf.com/reader/full/essential-safety-maintenance-manual 115/290

E S S E N T I A L S A F E T Y M E A S U R E S M A I N T E N A N C E M A N U A L • B U I L D I N G C O M M I S S I O N

S E C T I O N 1 0 / P A G E 2

1 0 . 1 S T A N D B Y P O W E R S U P P l Y S Y S T E MBCA: E3.4, Clause 6 of

Specication G3.8

PurPose

An emergency power supply is required to ensure the operation o required saety systems in the event o mains power ailure.

requirements of the equiPment

An emergency power supply must:–

a) Be connected automatically if the normal power supply fails; and

b) If located within the building, be separated from the remainder of the building by an enclosure with the reuiredfre-resistance rating; and

c) Be connected to the reuired safety systems by suitable re-resisting cabling.

The power supply can be provided by one o the ollowing:–

a) Two separate cables feeding into the substation; or

b) Two or more separate supplies coming from separate substations outside the building; or

c) Supplied from a generating set capable of starting and taking the necessary electrical load within 30 seconds ofailure o the mains supply.

method of oPeration

On failure of the main electrical supply, the system must:–

a) Automatically switch over to the alternate supply, providing power to at least the reuired safety systems.

b) If provided by a generating set:–

• Start the engine; and

• Bring the engine up to full operating speed; and

• Provide power to at least the reuired safety systems, within 30 seconds of mains failure.

maintenance checKs

It is recommended that the relevant building surveyor should require that emergency power supplies be tested six-monthly.The owner may delegate this unction to another person or body where necessary or appropriate.

Where the alternative supply is provided eternally to the premises by the power supply authority, it is recommended that thepower supply authority is contacted, to request that it test the automatic changeover switching acility, which in most cases ispart o its supply equipment.

I the building surveyor has a generating set, maintenance routines are recommended to be carried out at the ollowing

intervals:–

• Weekly

• Monthly

• Si-monthly

Generatingset:

WEEklY

1. Check water and oil levels. Top up if necessary; and

2. Check reuired spares are on hand – belts, lter cartridges, engine oil; and

Page 116: Essential Safety Maintenance Manual

8/3/2019 Essential Safety Maintenance Manual

http://slidepdf.com/reader/full/essential-safety-maintenance-manual 116/290

E S S E N T I A L S A F E T Y M E A S U R E S M A I N T E N A N C E M A N U A L • B U I L D I N G C O M M I S S I O N

S E C T I O N 1 0 / P A G E 3

3. Where batteries are installed, check batteries and charger for:–

a) Freedom from corrosion on terminals and in battery compartment; and

b) Correct electrolyte level, top up if necessary; and

c) Voltage per cell – using a voltmeter, ensure voltage is not less than 2 volts for lead-acid, batteries, 1.5 volts fornickel-cadmium (If voltage is less, have charger checked by a ualied person).

4. Start the engine by simulating a power failure (turn off monitoring circuit), run engine for at least 10 minutes, thencheck for the following:–

a) Visually check for water, oil or fuel leaks, loose ttings or ancillary euipment; and

b) Visually check belt drives; and

c) Correct operation of battery charging alternator or generator (check volt meter); and

d) Battery charger power-failure alarm, if tted; and

e) Ecessive vibration or heat; and

f) Correct running speed; and

g) After running and shutting down:

i) Check water, oil and fuel levels. Top up if necessary; and

ii) Ensure any strainer or lter, if tted, on the engine water cooling system, is checked and cleaned; and

iii) Ensure the engine ’stop’ mechanism automatically returns to the start position.

MONTHlY

1. Start the engine using the manual control, run the engine at rated speed for at least 30 minutes, and check for correct

operating temperature; and

2. Carry out the weekly procedures.

SIx-MONTHlY

1. Carry out the weekly and monthly procedures.

2. Check, clean and replace, if necessary, engine-fuel sludge and sediment trap, fuel, oil and air lters.

3. Change lubricating oil, if advised by engine manufacturer at this freuency (If not, change at least yearly).

maintenance records

The ollowing records are required:–

Si-monthytest

The following information must be entered in your log book:

a) The date of test and time conducted.

b) Eecution of test-satisfactory or otherwise.

c) Any maintenance work reuired.

d) Name of person carrying out test.

e) Signature of person carrying out test.

Log book sheets for this purpose are included in Appendi C of this manual.

Page 117: Essential Safety Maintenance Manual

8/3/2019 Essential Safety Maintenance Manual

http://slidepdf.com/reader/full/essential-safety-maintenance-manual 117/290

Page 118: Essential Safety Maintenance Manual

8/3/2019 Essential Safety Maintenance Manual

http://slidepdf.com/reader/full/essential-safety-maintenance-manual 118/290

Buildingclearances andfre appliances

B  ui   l   d i  n g 

 c  l   e

 a r  a n c  e s 

 a n d 

f r  e

 a  p p l  i   a n c  e s 

Page 119: Essential Safety Maintenance Manual

8/3/2019 Essential Safety Maintenance Manual

http://slidepdf.com/reader/full/essential-safety-maintenance-manual 119/290

E S S E N T I A L S A F E T Y M E A S U R E S M A I N T E N A N C E M A N U A L • B U I L D I N G C O M M I S S I O N

S E C T I O N 1 1 / P A G E 1

B u i d i n g C e a r a n c e s a n d F i r e A p p i a n c e s

11.1 OPEN SPACE AROUND LARGE ISOLATED BUILDINGS 2

11.2 VEHICULAR ACCESS AROUND LARGE ISOLATED BUILDINGS 3

Page 120: Essential Safety Maintenance Manual

8/3/2019 Essential Safety Maintenance Manual

http://slidepdf.com/reader/full/essential-safety-maintenance-manual 120/290

E S S E N T I A L S A F E T Y M E A S U R E S M A I N T E N A N C E M A N U A L • B U I L D I N G C O M M I S S I O N

S E C T I O N 1 1 / P A G E 2

BCA: C2.3 to C2.411.1 OPENSPACEAROUNDlARGEISOlATEDBUIlDINGS

PurPose

Where a building is permitted to be constructed in ecess of the oor area reuirements of the Building Code of Australia, open

space is required around the building.

requirements

Open space must:–

a) Be wholly within the allotment; and

b) Include emergency vehicle access; and

c) Not be used for storage or processing materials; and

d) Not be built upon ecept for guardhouses and service structures such as electricity substations and pump houses.

maintenance checKs

It is recommended that the relevant building surveyor should require an annual inspection o this acility to confrm openspace is maintained and no encroachment has been made into this area. The owner may delegate this unction to anotherperson or body where necessary or appropriate.

maintenance records

The ollowing inormation must be recorded:–

a) The date of the check or inspection; and

b) The name and status of the person carrying out the task; and

c) Any problems identied; and

d) Date these problems were rectied; and

e) Signature of the person inspecting.

Log sheets or this purpose are provided in Appendix C o this manual.

Page 121: Essential Safety Maintenance Manual

8/3/2019 Essential Safety Maintenance Manual

http://slidepdf.com/reader/full/essential-safety-maintenance-manual 121/290

E S S E N T I A L S A F E T Y M E A S U R E S M A I N T E N A N C E M A N U A L • B U I L D I N G C O M M I S S I O N

S E C T I O N 1 1 / P A G E 3

BCA: C2.3 to C2.4 1 1 . 2 VE HICUl AR ACCE SSAR OUND  

l A R G E I S O l A T E D B U I l D I N G S

PurPose

Where a building is permitted to be constructed in ecess of the oor area reuirements of the Building Code of Australia,

vehicular access is required around that building or emergency services.

requirements

Vehicular access must:–

a) Be capable of providing emergency vehicles access from a public road; and

b) Have a minimum unobstructed width of si metres, with no part of this si metres further than 18 metres from thebuilding, built upon, or used or any purpose other than vehicle or pedestrian movement; and

c) Provide reasonable pedestrian access to the building from the vehicular access; and

d) Have load-bearing capability and unobstructed height to allow passage and operation of re-ghting vehicles.

I a public road adjoining the building ulfls these requirements, it may be used to serve this purpose.

maintenance checKs

It is recommended that the relevant building surveyor should require an annual inspection o this acility to confrm accessis maintained and no encroachment has been made into this access area. The owner may delegate this unction to anotherperson or body where necessary or appropriate.

maintenance records

The ollowing inormation must be recorded:–

a) The date of the check or inspection; and

b) The name and status of the person carrying out the task; and

c) Any problems identied; and

d) Date these problems were rectied; and

e) Signature of the person inspecting.

Log sheets or this purpose are provided in Appendix C o this manual.

Page 122: Essential Safety Maintenance Manual

8/3/2019 Essential Safety Maintenance Manual

http://slidepdf.com/reader/full/essential-safety-maintenance-manual 122/290

Page 123: Essential Safety Maintenance Manual

8/3/2019 Essential Safety Maintenance Manual

http://slidepdf.com/reader/full/essential-safety-maintenance-manual 123/290

Mechanicalventilation

M e c h  a ni   c  a  l   v e

n t i   l   a  t i   on

Page 124: Essential Safety Maintenance Manual

8/3/2019 Essential Safety Maintenance Manual

http://slidepdf.com/reader/full/essential-safety-maintenance-manual 124/290

E S S E N T I A L S A F E T Y M E A S U R E S M A I N T E N A N C E M A N U A L • B U I L D I N G C O M M I S S I O N

S E C T I O N 1 2 / P A G E 1

M e c h a n i c a V e n t i a t i o n

12.1 AIR CONDITIONING SYSTEMS 2

12.2 HOT WATER SYSTEMS 6

12.3 WARM WATER SYSTEMS 8

Page 125: Essential Safety Maintenance Manual

8/3/2019 Essential Safety Maintenance Manual

http://slidepdf.com/reader/full/essential-safety-maintenance-manual 125/290

E S S E N T I A L S A F E T Y M E A S U R E S M A I N T E N A N C E M A N U A L • B U I L D I N G C O M M I S S I O N

S E C T I O N 1 2 / P A G E 2

BCA: E2.2,Reference: AS 1668.2, AS3666

1 2 . 1 A I R C O N D I T I O N I N G S Y S T E M S

PurPose

A mechanical air handling system must safeguard occupants from illness or loss of amenity due to lack of air freshness.

system and equiPment

The ollowing systems and equipment are included within the scope o this section:–

• Air conditioning systems, including air handling systems and thermal plant systems incorporating condenser watersystems.

• Ventilation systems, including car park, evaporative cooling systems and general ehaust systems.

• Smoke spill and smoke control systems including stair pressurisation systems.

• Kitchen ehaust systems.

• System components including re dampers, humidiers, electric duct heaters, etc.

requirements of the equiPment

A mechanical air handling system must:–

a) Be installed in accordance with AS 1668.1, 2 and AS/NzS 3666.1 and 2; and

b) Deliver adeuate amounts of outdoor air and provide sufcient circulation; and

c) Remove contaminants present in the compartment or building to maintain an acceptable air uality.

method of oPeration

Air conditioning and mechanical ventilation system mode o operation are typically classifed as Normal Mode and Fire Mode.

NormaMode

Systems operate in this mode to maintain acceptable indoor air quality when the building is occupied. Controls may be eithermanual or automatic.

FireMode

In the event o a fre being detected or reported via the fre alarm system, air conditioning and mechanical ventilation systemsare required to change over to fre mode operation. Systems required to shut down in fre mode shall be proven to shut downin accordance with AS 1851-2005 Clause 18.4.2.

An automatic air handling system must be provided with manual override operation.

Automatic operation can be accomplished by:–

• Time clock switching; or

• Thermostat-controlled switching; or

• Atmospheric contaminant monitoring.

maintenance checKs

To ensure the ongoing efciency of an air handling system after installation, AS 3666.2 sets out minimum maintenancerequirements to ensure health standards are not compromised.

The maintenance o these systems is an ongoing responsibility. This is a requirement o the Regulations and AS 3666.2

Maintenance o an air handling system can be carried out by the owner or this unction can be delegated to another person orbody where necessary or appropriate.

Page 126: Essential Safety Maintenance Manual

8/3/2019 Essential Safety Maintenance Manual

http://slidepdf.com/reader/full/essential-safety-maintenance-manual 126/290

E S S E N T I A L S A F E T Y M E A S U R E S M A I N T E N A N C E M A N U A L • B U I L D I N G C O M M I S S I O N

S E C T I O N 1 2 / P A G E 3

To ensure ull compliance with this requirement, a maintenance program must be prepared, including:–

a) All data relevant to the air handling system; and

b) A formal strategy and recording system for effective management of a series of maintenance procedures.

The maintenance program must be implemented in accordance with the inormation and requirements o the maintenanceroutines set down in of AS/NzS 3666.2 Section 2. A full description of the reuirements for the maintenance of air handlingsystems, heated water systems and cooling water systems is included and involves routines to be carried out monthly,quarterly, six-monthly and annually.

Systems, which include devices such as automatic air uality monitoring systems for car park ventilation systems and thelike, are covered in Appendi M of AS 1668.2. Owners should also refer to Section 6 for the maintenance reuirements of airhandling systems that are used for smoke control.

Operating and maintenance manuals must be available for all euipment in the system.

other matters to consider – cooling toWers

The Building Act 1993 reuires the registration of all cooling tower systems and the development of a Risk Management Plan(RMP) for each cooling tower system.

The Building (Legionella Risk Management ) Regulations 2001 specify the risks that an RMP must address. The Health(Legionella) Regulations 2001 also prescribe maintenance, testing and associated record-keeping relating to cooling tower andwarm water systems that a responsible person must comply with. ‘Responsible person’ means the person who owns, manages,or controls the cooling tower system or warm water system.

COOlINGTOWERMAINTENANCE

The responsible person must ensure that any cooling tower system that the responsible person owns, manages or controls ismaintained and tested in the manner set out in the Health (Legionella) Regulations 2001, unless the system is shut down, or isotherwise not in use, and is completely drained o water.

Wateruaityandtreatment

a) Ensure that the water of the cooling tower system is maintained in a clean condition.

b) Ensure that the water of the cooling tower system is continuously treated with:–

a. one or more biocides to eectively control the growth o micro-organisms, including Legionella; and

b. chemicals or other agents to minimise scale ormation, corrosion and ouling.

Disinfection,ceaningandre-disinfection

a) Ensure that a chlorine-compatible bio-dispersant is added to the recirculating water of the cooling tower system, andthat the system is then disinected, cleaned and re-disinected:–

a. immediately prior to initial start-up ollowing commissioning, or any shut-down period o greater than onemonth; and

b. at intervals not exceeding six months.

Routineinspectionsandtesting

a) Ensure that the cooling tower system is inspected at least once each month to check that the system is operatingwithout deects; and

b) Ensure that at least once each month a sample of the recirculating water of the cooling tower system is taken and isdelivered to a laboratory or testing and reporting on or heterotrophic colony count.

Page 127: Essential Safety Maintenance Manual

8/3/2019 Essential Safety Maintenance Manual

http://slidepdf.com/reader/full/essential-safety-maintenance-manual 127/290

E S S E N T I A L S A F E T Y M E A S U R E S M A I N T E N A N C E M A N U A L • B U I L D I N G C O M M I S S I O N

S E C T I O N 1 2 / P A G E 4

Highheterotrophiccoonycountdetectedincooingtowersystem

a) Within 24 hours of receiving a report that any sample of water taken from the cooling tower system has a

heterotrophic colony count exceeding 100 000 colony orming units per millilitre, the responsible person mustensure that the ollowing procedure is implemented:–

a. the water o the system must be manually treated with additional quantities o biocide, or with an alternativebiocide; and

b. the water treatment program, tower operation and maintenance program o the system must be reviewed; and

c. any aults must be corrected and any changes necessary to prevent a re-occurrence o those aults must beimplemented.

b) Between two and four days ensure that a further sample of the recirculating water of the system is taken and isdelivered to a laboratory or testing and reporting on or heterotrophic colony count.

c) Within 24 hours of receiving a report that a sample taken has a heterotrophic colony count eceeding 100,000colony orming units per millilitre, the responsible person must ensure that the water o the cooling tower systemis disinected, cleaned and re-disinected.

d) Between two and four days after the water has been re-disinfected, the responsible person must ensure that a furthersample of the recirculating water of the cooling tower system is taken and is delivered to a laboratory for testing andreporting on or heterotrophic colony count.

e) If, after following the above procedures, the heterotrophic colony count still eceeds 100,000 colony forming unitsper millilitre, the responsible person must:–

a. ensure that the steps are repeated until the heterotrophic colony count does not exceed 100,000 colonyforming units per millilitre in two consecutive water samples taken approimately one week apart; or

b. close the cooling tower system until the problem has been remedied.

Whatiflegioneaisdetectedincooingtowersystem?

a) Within 24 hours of receiving a report that Legionella has been detected in a water sample taken from a cooling towersystem that is not associated with any suspected or known case of legionellosis, the responsible person must ensurethat the ollowing procedure is implemented:–

a. the cooling tower system must be disinected; and

b. the water treatment program, tower operation and maintenance program o the system must be reviewed; and

c. any aults must be corrected and any changes necessary to prevent a re-occurrence o those aults must beimplemented.

b) Between two and four days after the disinfection has been completed, the responsible person must ensure thata further sample of the recirculating water of the system is taken and is delivered to a laboratory for testing andreporting on or Legionella.

c) Within 24 hours of receiving a report that Legionella has been detected in a sample taken, the responsible personmust ensure that the water o the cooling tower system is disinected, cleaned and re-disinected.

d) Between two and four days after the disinfection has been completed, the responsible person must ensure thata further sample of the recirculating water of the system is taken and is delivered to a laboratory for testing andreporting on or Legionella.

e) If Legionella is still detected, the responsible person must:–

a. ensure that the steps above are repeated until Legionella is not detected in two consecutive water samples takenapproimately one week apart; or

b. close the cooling tower system until the problem has been remedied.

Page 128: Essential Safety Maintenance Manual

8/3/2019 Essential Safety Maintenance Manual

http://slidepdf.com/reader/full/essential-safety-maintenance-manual 128/290

E S S E N T I A L S A F E T Y M E A S U R E S M A I N T E N A N C E M A N U A L • B U I L D I N G C O M M I S S I O N

S E C T I O N 1 2 / P A G E 5

f) If, while following the procedure of this part, Legionella is detected in three consecutive water samples taken fromthe same system, the responsible person must notify the Secretary to the Department of Human Services of thedetection o the presence o that organism:–

a. immediately by telephone; and

b. by notice in writing within three days o the detection o the organism on the third occasion.

maintenance records

To ensure proper control o the maintenance program, the ollowing documentation should be provided:–

Operating and maintenance manuals should be provided for all plant, euipment and systems that are the subject of thisStandard. Operating and maintenance manuals shall include at least the following:

a) Physical details of the plant, euipment and systems; and

b) Recommendations on maintenance, including water treatment maintenance and management; and

c) Recommended cleaning, disinfection and emergency decontamination procedures; and

d) Start-up, operating and shut-down procedures; and

e) Particulars of the maintenance management program.

Maintenance records shall contain at least the ollowing inormation:

a) Date, item of plant, euipment or system and nature of service performed; and

b) Details of defects found and rectication procedure undertaken; and

c) The name of the person or company performing the service.

Log sheets to record the completion o the maintenance routines are included in Appendix C o this manual.

Log sheets or the testing o cooling towers should be developed in accordance with the requirements o the Health(Legionella) Regulations 2001.

Page 129: Essential Safety Maintenance Manual

8/3/2019 Essential Safety Maintenance Manual

http://slidepdf.com/reader/full/essential-safety-maintenance-manual 129/290

E S S E N T I A L S A F E T Y M E A S U R E S M A I N T E N A N C E M A N U A L • B U I L D I N G C O M M I S S I O N

S E C T I O N 1 2 / P A G E 6

Reference: AS 3500 AS 3666

12.2 HOT WAT E R SYST E MS

PurPose

A hot water system must saeguard occupants rom illness or loss o amenity due to the eect o microbial actors.

Hot water systems are dened as systems that maintain a water temperature above 60 degrees Celsius.

system and equiPment

The ollowing systems and equipment are included within the scope o this section:–

a) Water treatment units.

b) Water tanks and vessels.

c) Valves – the following temperature control valves:

i. Temperature/pressure-relief valves.

ii. Expansion-control valves.

iii. Thermostatic mixing valves.

iv. Tempering valves.

v. Other associated valves/devices.

requirements of the equiPment

A hot water system must be installed in accordance with AS 3500.4 and AS/NzS 3666.1 and 2.

maintenance checKs

To ensure the ongoing efciency of a hot water system after installation, AS 3666.2 sets out minimum maintenancerequirements to ensure health standards are not compromised.

Maintenance o a hot water system should be carried out by a person or body where necessary or appropriate with experiencein microbial control and should include the ollowing items:–

a) Water treatment units – Where installed, water treatment units shall be inspected periodically to ensure properoperation.

b) Vessels and tanks – All vessels and tanks shall be inspected and cleaned periodically.

c) Valves – The following temperature control valves shall be inspected periodically to ensure proper operation.

i. Temperature/pressure-relief valves.

ii. Expansion-control valves.

iii. Thermostatic mixing valves.

iv. Tempering valves.

v. Other associated valves/devices

To ensure ull compliance with this requirement, a maintenance program must be prepared, including:–

a) All data relevant to the hot water system; and

b) A formal strategy and recording system for effective management of a series of maintenance procedures.

The maintenance program must be implemented in accordance with the inormation and requirements o the maintenanceroutines set down in of AS/NzS 3666.2. This Standard recommends that maintenance must be undertaken in accordance withthe provisions of AS3500.4.

In order to ensure maimum performance and length of operation, AS 3500.4 reuires that water heaters shall be periodicallyinspected in accordance with the manuacturer’s instructions.

Page 130: Essential Safety Maintenance Manual

8/3/2019 Essential Safety Maintenance Manual

http://slidepdf.com/reader/full/essential-safety-maintenance-manual 130/290

E S S E N T I A L S A F E T Y M E A S U R E S M A I N T E N A N C E M A N U A L • B U I L D I N G C O M M I S S I O N

S E C T I O N 1 2 / P A G E 7

maintenance records

To ensure proper control o the maintenance program, the ollowing documentation should be provided:–

Operating and maintenance manuals should be provided for all systems. These manuals shall include at least the following:–

a) Physical details of the systems; and

b) Recommendations on maintenance, including water treatment maintenance and management; and

c) Recommended cleaning, disinfection and emergency decontamination procedures; and

d) Start-up, operating and shut-down procedures; and

e) Particulars of the maintenance management program.

Maintenance records shall contain at least the ollowing inormation:

a) Date, item of plant, euipment or system and nature of service performed; and

b) Details of defects found and rectication procedure undertaken; and

c) The name of the person or company performing the service.

Log sheets to record the completion o the maintenance routines should be developed rom the manuacturer’s inormationprovided or the hot water system.

Page 131: Essential Safety Maintenance Manual

8/3/2019 Essential Safety Maintenance Manual

http://slidepdf.com/reader/full/essential-safety-maintenance-manual 131/290

E S S E N T I A L S A F E T Y M E A S U R E S M A I N T E N A N C E M A N U A L • B U I L D I N G C O M M I S S I O N

S E C T I O N 1 2 / P A G E 8

Reference: AS 3500 AS 3666

12.3 WAR MWAT E R SYST E MS

PurPose

A warm water system must saeguard occupants rom illness or loss o amenity due to the eect o microbial actors.

Warm water systems are dened as systems that maintain a water temperature between 30 and 60 degrees Celsius.

system and equiPment

The ollowing systems and equipment are included within the scope o this section:–

a) Water treatment units.

b) Water tanks and vessels.

c) Valves – the following temperature control valves;

a. Temperature/pressure-relief valves.

b. Expansion-control valves.

c. Thermostatic mixing valves.

d. Tempering valves.

e. Other associated valves/devices.

requirements of the equiPment

A warm water system must be installed in accordance with AS 3500.4 and AS/NzS 3666.1 and 2.

maintenance checKs

To ensure the ongoing efciency of a hot water system after installation, AS 3666.2 sets out minimum maintenancerequirements to ensure health standards are not compromised.

Where necessary or appropriate, maintenance of warm water systems should be carried out by a person or body withexperience in microbial control.

Owners should also note that the Health (Legionella) Regulations 2001 also prescribe maintenance, testing and associatedrecord-keeping relating to warm water systems that a responsible person must comply with. ‘Responsible person’ means theperson who owns, manages, or controls the cooling tower system or warm water system.

To ensure ull compliance with this requirement, a maintenance program must be prepared, including:–

a) All data relevant of the warm water system; and

b) A formal strategy and recording system for effective management of a series of maintenance procedures.

The Health (Legionella) Regulations 2001 prescribe the ollowing maintenance:–

Start-upfoowingcommissioning

Ensure that the warm water system is disinected by heat or chlorination and cleaned immediately prior to initial start-upollowing commissioning, or any shut-down period o greater than one month.

Routinedisinfection

Ensure that the warm water system is disinfected by one or more of the following methods—

a) At least once each month by heat or chlorination; or

b) Continuously by means of automatic low level chlorination; or

c) Continuously by means of ultra-violet light treatment.

Page 132: Essential Safety Maintenance Manual

8/3/2019 Essential Safety Maintenance Manual

http://slidepdf.com/reader/full/essential-safety-maintenance-manual 132/290

E S S E N T I A L S A F E T Y M E A S U R E S M A I N T E N A N C E M A N U A L • B U I L D I N G C O M M I S S I O N

S E C T I O N 1 2 / P A G E 9

Routinetesting

I the method o disinection o a warm water system is by ultra-violet light treatment, ensure that a sample o the water o

the system is taken and is delivered to a laboratory for testing and reporting on for Legionella:–

a) At intervals not eceeding one month for a period of 12 months; and

b) If Legionella is not detected in any sample taken and delivered to a laboratory for testing during the previous 12months, at intervals not exceeding three months or so long as Legionella remains undetected in the system; and

c) If Legionella is detected in any sample taken and delivered to a laboratory for testing during the previous 12 months,then according to the intervals specied in paragraph (a).

Additionatestingforpremiseswhereovernightaccommodationandheathorwefareservices areprovided

a) If a warm water system serves premises where overnight accommodation and health or welfare services are provided,ensure that samples of the water are taken from different outlets of the system and delivered to a laboratory for

testing and reporting on or Legionella;

b) If the method of disinfection is by heat or chlorination or low level chlorination:–

i. at intervals not exceeding three months or a period o 12 months; and

ii. if Legionella is not detected in any sample taken and delivered to a laboratory for testing during the previous12 months, at intervals not exceeding six months or so long as Legionella remains undetected in the system; and

iii. if Legionella is detected in any sample taken and delivered to a laboratory for testing during the previous 12months, then according to the intervals specied in sub-paragraph (i).

c) If the method of disinfection is by ultra-violet light treatment or by a method approved under regulation 17(d) ofHealth (Legionella) Regulations 2001, according to the intervals specied in regulation 18 of those regulations;

d) If the system is disinfected at least each month, the samples must be taken just prior to the disinfection.

Warmwateroutets

a) Ensure that at least once during each week all outlets of the warm water system not in use for seven days or moreare ushed at full ow.

b) The period of ushing must be sufcient to remove all stagnant water leading to the outlet, and until thetemperature at which the system is set is reached at the outlet.

Thermostaticmiingvaves

The responsible person must ensure that all thermostatic mixing valves o warm water systems are cleaned and maintained atleast once in each calendar year.

maintenance records

To ensure proper control o the maintenance program, the ollowing documentation should be provided:–

Operating and maintenance manuals should be provided for all systems. Operating and maintenance manuals shall include atleast the ollowing:

a) Physical details of the systems; and

b) Recommendations on maintenance including water treatment maintenance and management; and

c) Recommended cleaning, disinfection and emergency decontamination procedures; and

d) Start-up, operating and shut-down procedures; and

e) Particulars of the maintenance management program.

Page 133: Essential Safety Maintenance Manual

8/3/2019 Essential Safety Maintenance Manual

http://slidepdf.com/reader/full/essential-safety-maintenance-manual 133/290

E S S E N T I A L S A F E T Y M E A S U R E S M A I N T E N A N C E M A N U A L • B U I L D I N G C O M M I S S I O N

S E C T I O N 1 2 / P A G E 1 0

Maintenance records shall contain at least the ollowing inormation:

a) Date, item of plant, euipment or system and nature of service performed; and

b) Details of defects found and rectication procedure undertaken; and

c) The name of the person or company performing the service.

Log sheets to record the completion o the maintenance routines should be developed rom the manuacturer’s inormationprovided or the warm water system.

Page 134: Essential Safety Maintenance Manual

8/3/2019 Essential Safety Maintenance Manual

http://slidepdf.com/reader/full/essential-safety-maintenance-manual 134/290

Page 135: Essential Safety Maintenance Manual

8/3/2019 Essential Safety Maintenance Manual

http://slidepdf.com/reader/full/essential-safety-maintenance-manual 135/290

B  ui   l   d i  n g  s  c  on s  t r  u c  t  e d  b  e t  w e en

1  J   u l   y1  9  9  4  a n d 1 M a  y2  0  0  4 

Part 2Buildings constructedbetween 1 July 1994and 1 May 2004

Egress and access

Electrical servicesFire-detection and suppression equipment

Fire-resistance

Mechanical services

Page 136: Essential Safety Maintenance Manual

8/3/2019 Essential Safety Maintenance Manual

http://slidepdf.com/reader/full/essential-safety-maintenance-manual 136/290

E S S E N T I A L S A F E T Y M E A S U R E S M A I N T E N A N C E M A N U A L • B U I L D I N G C O M M I S S I O N

P A R T 2 / P A G E 1

The Building Regulations 2006 and Part 11 o the Building Regulations 1994 (the Regulations) prescribe the requirements ormaintenance o buildings built on and ater 1 July 1994.

Any essential saety measure in Class 1b, 2, 3, 5, 6, 7, 8 and 9 buildings and places o public entertainment must bemaintained, by the owner, to a working condition that enables them to ull their purpose and meet the expectationso inspecting authorities.

The Regulations make it mandatory or the building surveyor to list the required essential services on the issuing o theoccupancy permit. The level o perormance to which the service is to be maintained must also be specied on the occupancypermit. In the case o an essential service being provided where no occupancy permit is required, then the relevant buildingsurveyor must determine the level o perormance that must be specied in writing and given to the owner.

The Regulations list essential saety measures as:

Part 2 – Buildings Constructed between 1 July 1994

and 1 May 2004

Air conditioning systems Fire mains

Emergency lits Fire-protective coverings

Emergency lighting Fire-rated access panels

Emergency power supply Fire-rated control joints

Emergency warning and intercommunication systems Fire-rated materials applied to building element

Exit doors Fire-resisting shats

Exit signs Fire-resisting structures

Fire brigade connections Fire shutters

Fire control centres Fire windows

Fire control panels Lightweight construction

Fire curtain Mechanical ventilation systems

Fire dampers Paths o travel to exits

Fire detectors and alarm systems Penetrations in re-rated structures

Fire doors Smoke alarms

Fire extinguishers (portable) Smoke control measures

Fire hose reels Smoke doors

Fire hydrants Smoke vents

Fire indices or materials Sprinkler systems

Fire-isolated lit shats Stairwell pressurization systems

Fire-isolated passageways Static water storage

Fire-isolated ramps Vehicular access or large isolated buildings

Fire-isolated stairs Warning systems associated with lits

Page 137: Essential Safety Maintenance Manual

8/3/2019 Essential Safety Maintenance Manual

http://slidepdf.com/reader/full/essential-safety-maintenance-manual 137/290

E S S E N T I A L S A F E T Y M E A S U R E S M A I N T E N A N C E M A N U A L • B U I L D I N G C O M M I S S I O N

P A R T 2 / P A G E 2

Use of As 1851.1 to As 1851.10 - MAintenAnce of fire protection eqUipMent

Where an essential saety measure has been nominated as using AS 1851 to provide maintenance within this part, details o

the level o records to be kept are incorporated in the relevant maintenance sections and schedules o that standard. It is notedthat over time this version o AS1851 may no longer be available and as such log sheets have been provided or AS1851.1to AS1851.10 or historical purposes and to mainatin consistency with previous versions o this manual. These log sheets areavailable in Appendix C o this manual.

It should be noted that where the essential saety measures nominated in this manual do not use AS1851 as a minimum levelo maintenance, log sheets in Appendix C may be modied to suit.

Page 138: Essential Safety Maintenance Manual

8/3/2019 Essential Safety Maintenance Manual

http://slidepdf.com/reader/full/essential-safety-maintenance-manual 138/290

Egress andaccess

E  g r  e s  s 

 a n d   a  c  c  e s  s 

Page 139: Essential Safety Maintenance Manual

8/3/2019 Essential Safety Maintenance Manual

http://slidepdf.com/reader/full/essential-safety-maintenance-manual 139/290

E S S E N T I A L S A F E T Y M E A S U R E S M A I N T E N A N C E M A N U A L • B U I L D I N G C O M M I S S I O N

S E C T I O N 1 / P A G E 1

1.1 EMERGENCY LIFTS 2

1.2 ExIT DOORS 3

1.3 FIRE DOOR 4

1.4 FIRE-ISOLATED pASSAGEwAYS, RAMpS AND STAIRS 6

1.5 SMOkE DOORS 7

1.6 pAThS OF TRAvEL TO ExITS 8

1.7 vEhICULAR ACCESS AROUND LARGE ISOLATED BUILDINGS 9

E g r e s s a n A c c e s s

Page 140: Essential Safety Maintenance Manual

8/3/2019 Essential Safety Maintenance Manual

http://slidepdf.com/reader/full/essential-safety-maintenance-manual 140/290

E S S E N T I A L S A F E T Y M E A S U R E S M A I N T E N A N C E M A N U A L • B U I L D I N G C O M M I S S I O N

S E C T I O N 1 / P A G E 2

pUrpose

To enable emergency services personnel to access any foor o the building normally serviced by the lit and carry out

emergency procedures and assist in occupant evacuation.

reqUireMents of tHe eqUipMent

In addition to the normal requirements or sae operation, the emergency lit must:-

a) Be installed in accordance it AS 1735.2; and

b) Be roided it a re serice control on te nominated oor, to enable eclusie control of te lift; and

c) Be roided it a re serice control sitc inside te lift car; and

d) hae signs saying ‘re serice’ at te sitc on te nominated oor and in te lift car; and

e) hae minimum dimensions suitable to accommodate a erson on a stretcer; and

) Have an identication label ‘special re lit’ on the mains supply switch or this lit.

MAintenAnce cHecKs

Under the requirements o the Occupational Health and Safety (Plant) Regulations 1995, Clause 902 Part 2, an employer havingcontrol or management o a lit is required to ensure any risk to people travelling in the lit or associated with its use must beeliminated or reduced as ar as is practicable.

AS 1735.2 requires periodic inspection and testing o every installation at intervals o not more than one year and regularmaintenance o installations at more requent intervals. Maintenance should be carried out in accordance with themanuacturer’s instructions.

It is the owner’s responsibility to ensure a maintenance program is carried out eectively.

MAintenAnce recorDs

Records o periodic maintenance should be maintained and provided by the maintenance contractor.

A record o the yearly inspection must show:-

a) Date te yearly insection occurred; and

b) Name of te erson conducting te insection; and

c) Any roblems identied in te insection; and

d) Actions taen to rectify roblems identied; and

e) Date te rectication occurred; and

) Signature o the person conducting the inspection.

A log sheet to record this inormation is provided in Appendix C o this manual.

1.1 EmERGENCy l ITSBCA 1990: E3.4 BCA 1996: Ep3.2 (E3.4) Reerence: AS 1735.2

Oh&S (plant)Regulations. 1995

Page 141: Essential Safety Maintenance Manual

8/3/2019 Essential Safety Maintenance Manual

http://slidepdf.com/reader/full/essential-safety-maintenance-manual 141/290

E S S E N T I A L S A F E T Y M E A S U R E S M A I N T E N A N C E M A N U A L • B U I L D I N G C O M M I S S I O N

S E C T I O N 1 / P A G E 3

pUrpose

To provide a means o egress rom any part o a building.

reqUireMents of tHe eqUipMent

To provide sucient and sae egress rom a building, with a minimum o eort and delay and to present a minimum oobstruction in an exit path.

MetHoD of operAtion

An exit door must be capable o simple operation to ull its designed purpose.

It must be able to be opened readily without a key, rom the side acing a person seeking their way out, by a single-handeddownward or pushing action on a single device located between 900 mm and 1.2 m rom the foor.

It could be tted with a ail-sae device which unlocks the door automatically when any sprinkler, smoke or heat detectorsystem in the building is activated, or open automatically i tted with a door which is power operated upon malunction orailure o the power source.

MAintenAnce cHecKs

It is recommended that the relevant building surveyor should require exit doors to be inspected every three months. The ownermay delegate this unction to another person or body where necessary or appropriate.

Maintenance checks should be carried out to ensure the exit door is:-

a) Intact

b) Oerational

c) Fitted with hardware that conorms to the requirements o the Building Code of Australia, Section D(the hardware necessary to enable its operation as outlined above)

MAintenAnce recorDs

A sheet to record the maintenance and inspections carried out is included Appendix C o this manual.

BCA 1990: Section D BCA 1996: Dp4 (Section D) 

1 .2 E x IT dOOR S

Page 142: Essential Safety Maintenance Manual

8/3/2019 Essential Safety Maintenance Manual

http://slidepdf.com/reader/full/essential-safety-maintenance-manual 142/290

E S S E N T I A L S A F E T Y M E A S U R E S M A I N T E N A N C E M A N U A L • B U I L D I N G C O M M I S S I O N

S E C T I O N 1 / P A G E 4

pUrpose

A re door is installed across an opening in a re wall to maintain the re-resistance rating o that re wall.

reqUireMents of tHe eqUipMent

An approved re-resistant doorset is one that is identical in assembly, construction and installation to a prototype o this doorthat has been submitted to the standard re-resistance test, and has ullled all the relevant test requirements.

A re door must be sel-closing or close automatically on the operation o an approved sensing device or on the losso power supply.

Each re door must have a metal tag attached as required by AS 1905.1, and latchsets and closers should also bemarked as required.

MetHoD of operAtion

On receit of a signal troug te re alarm system, te old-oen deice of automatic closing doorsets must release te door.

Alternatively, when electrical power to that area ails, the electro-magnetic hold-open device must then release the door.

Once released, te re door must close cleanly and be unimaired in its oeration.

It is essential that no unauthorised means is used to hold open a re door.

MAintenAnce cHecKs

It is recommended that the relevant building surveyor should require that a re door be inspected monthly. It should be notedthat this is the lowest level o maintenance required by the Standard and more rigorous routines are also required as indicatedbelow. The owner may delegate this unction to another person or body where necessary or appropriate.

Under AS 1851.7, two levels o inspections are required:-

mONTHly

a) A visual and physical inspection o the door and its unctions.

This inspection must be carried out by the owner or occupier o the premises, or by a suitably qualied representative(i.e.: Maintenance Manager, Fire and Safety Ofcer).

yEARly

a) The routine required or the monthly inspections.

b) Comparison o each re doorset with the appropriate specication in the installation log book supplied with the door.

c) The inspection items specied in Appendix A o AS 1851.7, pages 6 to 8.

This inspection should be carried out or supervised by a person competent and experienced in the eld o re doors.

It is recommended that where any corrective action involves repairs to the door lea, such repairs should be carried out by theoriginal manuacturer.

The procedures or the monthly and yearly inspections are contained in AS 1851.7.

BCA 1990: Sec C3.4 BCA 1996: Cp8 (Sec C3.4) Reerence: AS 1905.1

AS 1851.7

 

1.3 IRE dOORS

Page 143: Essential Safety Maintenance Manual

8/3/2019 Essential Safety Maintenance Manual

http://slidepdf.com/reader/full/essential-safety-maintenance-manual 143/290

E S S E N T I A L S A F E T Y M E A S U R E S M A I N T E N A N C E M A N U A L • B U I L D I N G C O M M I S S I O N

S E C T I O N 1 / P A G E 5

Before a re door is rendered unsericeable for maintenance, te folloing recautions sall be taen by te reairer:-

a) Adise te oner or occuier so tat any necessary recautions can be taen; and

b) Where the door is to be removed and cannot be re-installed within three hours, the re brigade nearest to you andte re station to ic te alarm is connected sall be adised; and

c) I the door protects an opening in a re-isolated escape route or in a wall required to have a our-hour re-resistance,permission shall be obtained rom the regulatory authority (building surveyor) as well as notice given to the rebrigade as in (b); and

d) A re door shall not be rendered unserviceable or maintenance while any re alarm or re-suppression systemin the building is inoperative.

It is essential all re doors are maintained in operational condition at all times.

MAintenAnce recorDs

To ensure a proper history o each re door in the premises is retained, the ollowing records must beavailable and maintained:-

1. A log book,

a) Provided by the re door supplier, showing:

a. Identication of te building and its oner; and

b. Te sulier of te doorset; and

c. The date(s) o commissioning o the re doorsets in the building.

b) Identiying each doorset, showing:

a. Its identication number; and

b. Te tye of door, its dimensions, and re-resistance leel; and

c. Te items of ardare installed on it, and ere alicable, te marings on tat ardare; and

d. Te items of door furniture tted; and

e. Any subsequent repairs or replacement o any part o the doorset.

c) pages to record te results of Tye 1 (montly) maintenance routines as called for in AS 1851.7; and

d) Trilicate ages to record te results of Tye 2 (yearly) maintenance routines secied in AS 1851.7; and

The pages o this log book must be numbered.

2. A numbered Certicate o Compliance, supplied by the supplier o the re doorsets, giving written evidence that:-

a) Te doorset is identical it a tested rototye; and

b) Te doorframe as been correctly installed; and

c) The installation complies with AS 1905.1.

All details o the required maintenance records, and the required inspection and reporting procedures, are providedin AS 1851.7.

Page 144: Essential Safety Maintenance Manual

8/3/2019 Essential Safety Maintenance Manual

http://slidepdf.com/reader/full/essential-safety-maintenance-manual 144/290

E S S E N T I A L S A F E T Y M E A S U R E S M A I N T E N A N C E M A N U A L • B U I L D I N G C O M M I S S I O N

S E C T I O N 1 / P A G E 6

pUrpose

Fire-isolated passageways, ramps and stairs are to provide occupants with sae egress rom a building.

reqUireMents of tHe eqUipMent

These elements must be o re-resistant construction at a level specied in the Building Code of Australia.

At the entrance point to these elements, re doors are to be provided. Fire doors are to be o a specied re-resistance level,that are either sel-closing or have automatic closing acilities linked to smoke or heat detectors, or to a re alarm or sprinklersystem installed in the building.

MAintenAnce cHecKs

It is recommended that the relevant building surveyor should require an annual inspection o these acilities. The owner maydelegate this unction to another person or body where necessary or appropriate.

It is essential to ensure:-

a) No unauthorised alterations have been made that could compromise the integrity o their re-resistance level.

b) No obstruction has occurred by stacking o goods or equipment within these areas.

c) No tampering or intererence with the sel-closing or automatic operation o the re doors.

Details for te testing and insection of re doors is roided in Section 1.3 Fire doors of tis part.

MAintenAnce recorDs

The ollowing inormation must be recorded:-

a) Te dates tat montly and yearly insections ere carried out; and

b) Te name of te erson conducting te insections; and

c) Any roblems identied in te insections; and

d) Actions taen to rectify roblems identied; and

e) Date rectication occurred; and

) Signature o the person conducting the inspections.

A log sheet to record this inormation is provided in Appendix C o this manual.

BCA 1990: Section C BCA 1996: Section D 

1.4 IRE ISOl ATEd PASSAGEwAyS,RAmPS ANd STAIRS

Page 145: Essential Safety Maintenance Manual

8/3/2019 Essential Safety Maintenance Manual

http://slidepdf.com/reader/full/essential-safety-maintenance-manual 145/290

E S S E N T I A L S A F E T Y M E A S U R E S M A I N T E N A N C E M A N U A L • B U I L D I N G C O M M I S S I O N

S E C T I O N 1 / P A G E 7

pUrpose

Smoke doors are constructed in smoke walls to restrict the passage o smoke between smoke compartments or walls, or rom

within a smoke lobby.

reqUireMents of tHe eqUipMent

Smoke doors must be constructed so that smoke will not pass rom one side o the doorway to the other.

Smoke doors can be o one or two leaves and must:-

a) Be side-ung to sing:

a. in te direction of egress; or

b. in bot directions; and

b) Be caable of resisting smoe at 200°C for 30 minutes; and

c) hae te leaes tted it smoe seals; and

d) Have the leaves:

a. normally closed; or

b. close automatically, it te closing initiated by smoe detectors or oer failure; and

e) hae te leaes close fully after eac manual oening; and

) I made o glass, have the glazing identiable by opaque construction.

MAintenAnce cHecKs

It is recommended that the relevant building surveyor should require maintenance to be carried out monthly to AS 1851.7.It should be noted that this is the lowest level o maintenance required by the Standard and more rigorous routines are alsorequired. The owner may delegate the maintenance unction to another person or body where necessary or appropriate

To ensure smoke doors ull their designed unction, the ollowing is recommended:-

a) The doors and associated equipment are in working order (seals undamaged, etc.).

b) No unauthorised means have been incorporated to retain the doors open (wedges, cabin hooks, etc.).

c) The automatic closing acilities work, i.e.:

i) en te smoe detectors oerate; or

ii) when power ailure occurs.

These checks may be carried out in conjunction with the testing o the re alarm system, as per AS 1851.8.

MAintenAnce recorDs

A log book must be maintained to record the inspections o each smoke door. This should show:-

a) Te date of eac montly insection; and

b) Any roblems identied; and

c) Measures taen to rectify roblems identied; and

d) Date roblems rectied; and

e) Name and signature o the person carrying out each inspection.

Log sheets or this purpose have been provided or in Appendix C o this manual.

BCA 1990: C2.5 Spec C3.4

BCA 1996: Cp3 (C2.5, Sec C3.4) Reerence: AS 1851.7

AS 1851.8

 

1 .5 S mOk E dOOR S

Page 146: Essential Safety Maintenance Manual

8/3/2019 Essential Safety Maintenance Manual

http://slidepdf.com/reader/full/essential-safety-maintenance-manual 146/290

E S S E N T I A L S A F E T Y M E A S U R E S M A I N T E N A N C E M A N U A L • B U I L D I N G C O M M I S S I O N

S E C T I O N 1 / P A G E 8

pUrpose

Paths o travel to exits are to provide an unobstructed pathway or occupants travelling to an exit.

reqUireMents of tHe eqUipMent

To provide a passage to an exit that is o a width and height as specied by the Building Code of Australia.

MetHoD of operAtion

To ensure paths o travel to exits are operational and eective, they must not be obstructed or altered in any way.

It is the responsibility o the owner to ensure that all paths o travel to exits are maintained in an ecient condition andkept unctional and clear o obstruction.

MAintenAnce cHecKs

It is recommended that the relevant building surveyor should require a three-monthly inspection o this acility. The ownermay delegate this unction to another person or body where necessary or appropriate.

It is recommended that in carrying out the required inspections, the ollowing points be covered:-

a) Ensure no obstruction o any nature has encroached on or into the designated paths o travel.

b) Check that the integrity o the re isolation requirements on or in the relevant sections o the path o travel havenot been breached or compromised.

c) Check that no unauthorised alteration has been carried out on these sections.

MAintenAnce recorDs

A log book must be kept to record:-

a) Te date te insection as carried out; and

b) Any roblems encountered during te insection; and

c) The name, designation and signature o the person carrying out the inspection.

A log sheet to record this inormation is provided in Appendix C o this manual.

1.6 PATHS O TRAvEl TO ExITSBCA 1990: Section D BCA 1996: Dp6 (Section D) 

Page 147: Essential Safety Maintenance Manual

8/3/2019 Essential Safety Maintenance Manual

http://slidepdf.com/reader/full/essential-safety-maintenance-manual 147/290

E S S E N T I A L S A F E T Y M E A S U R E S M A I N T E N A N C E M A N U A L • B U I L D I N G C O M M I S S I O N

S E C T I O N 1 / P A G E 9

pUrpose

Where a building is permitted to be constructed in excess o the foor area requirements o the Building Code of Australia,

vehicular access is required around that building or emergency services.

reqUireMents of tHe eqUipMent

Vehicular access must:-

a) Be caable of roiding emergency eicles access from a ublic road; and

b) Have a minimum unobstructed width o six metres, with no part o this six metres urther than 18 metres romte building, built uon, or used for any urose oter tan eicle or edestrian moement; and

c) proide reasonable edestrian access to te building from te eicular access; and

d) Must have load-bearing capability and unobstructed height to allow passage and operation o re-ghting vehicles.

I a public road adjoining the building ulls these requirements, it may be used to serve this purpose.

MAintenAnce cHecKs

It is recommended that the relevant building surveyor should require an annual inspection o this acility to conrm accessis maintained and no encroachment has been made onto this access area. The owner may delegate this unction to anotherperson or body where necessary or appropriate.

MAintenAnce recorDs

The ollowing inormation must be recorded:-

a) Te date of te cec or insection; and

b) Te name and status of te erson carrying out te tas; and

c) Any roblems identied; and

d) Date tese roblems ere rectied; and

e) Signature o the person inspecting.

Log sheets or this purpose are provided in Appendix C o this manual.

1.7 vEHICulAR ACCESS AROuNd lARGEISOlATEd buIldINGS BCA 1990: C2.4 

BCA 1996: Cp9 (C2.4) 

Page 148: Essential Safety Maintenance Manual

8/3/2019 Essential Safety Maintenance Manual

http://slidepdf.com/reader/full/essential-safety-maintenance-manual 148/290

Page 149: Essential Safety Maintenance Manual

8/3/2019 Essential Safety Maintenance Manual

http://slidepdf.com/reader/full/essential-safety-maintenance-manual 149/290

Electricalservices

E  l   e c  t r i   c  a  l   s  er  vi   c  e s 

Page 150: Essential Safety Maintenance Manual

8/3/2019 Essential Safety Maintenance Manual

http://slidepdf.com/reader/full/essential-safety-maintenance-manual 150/290

S E C T I O N 2 / P A G E 1

E S S E N T I A L S A F E T Y M E A S U R E S M A I N T E N A N C E M A N U A L • B U I L D I N G C O M M I S S I O N

E l e c t r i c a l s e r v i c e s

2.1 EMERGENCY LIGhTING 2

2.2 EMERGENCY pOwER SUppLY 6

2.3 EMERGENCY wARNING AND INTERCOMMUNICATION SYSTEM 8

2.4 EXIT SIGNS 10

 

Page 151: Essential Safety Maintenance Manual

8/3/2019 Essential Safety Maintenance Manual

http://slidepdf.com/reader/full/essential-safety-maintenance-manual 151/290

S E C T I O N 2 / P A G E 2

E S S E N T I A L S E R v I C E S M A I N T E N A N C E M A N U A L • B U I L D I N G C O N T R O L C O M M I S S I O N

pUrpose

To saeguard occupants rom injury by providing sucient lighting to allow sae occupant evacuation in an emergency.

reqUireMents of tHe eqUipMent

An emergency lighting system must:-

a) Be installed to AS 2293.1; and

b) Be automatic in oeration in te eent of failure of oer suly to te main ligting system; and

c) Provide a level o illuminance appropriate:-

a. to te use and size in oor area of te building; and

b. the distance required to reach exits.

MetHoD of operAtion

CENTRAL LIGhTING SYSTEMS

This type o system will be set up to operate in one o two modes:-

a) were te emergency ligting is energised at all times en te building is occuied; or

b) Where the emergency lighting is energised only when power to the normal lighting system ails.

SINGLE pOINT LIGhT SYSTEMS

Each unit ’stands alone‘ and illuminates when normal lighting ails. Power is supplied rom a built-in battery that iscontinuously under charge while normal lighting operates.

MAintenAnce cHecKs

It is recommended that the relevant building surveyor should require maintenance to be carried out at least every six months.It should be noted that this is the lowest level o maintenance required by the Standard and more rigorous routines are alsorequired as noted below. The owner may delegate this unction to another person or body where necessary or appropriate.

Singe point sste

SIx-mONTHly PROCEduRES

a) Oerate te self-contained emergency ligts from teir battery suly by turning off te normallighting power supply.

b) The lights must remain alight or at least 90 minutes.

c) Replace any aulty lamps.

d) Turn on the normal lighting power supply and check that the battery charger indicator unctions properly.

Record the test and correct operation o the system.

Record the replacement o aulty lamps.

TwElvE-mONTHly PROCEduRES

a) Carry out the six-monthly procedures.

b) Clean all light emitting and refecting suraces.

Record the testing and cleaning.

2.1 EmERGENCy l IGHTINGBCA 1990: E3.4 BCA 1996: E3.4 Reerence: AS 2293.1

AS 2293.2

Page 152: Essential Safety Maintenance Manual

8/3/2019 Essential Safety Maintenance Manual

http://slidepdf.com/reader/full/essential-safety-maintenance-manual 152/290

S E C T I O N 2 / P A G E 3

E S S E N T I A L S E R v I C E S M A I N T E N A N C E M A N U A L • B U I L D I N G C O N T R O L C O M M I S S I O N

CENTRAL LIGhTING SYSTEM

Checks should be undertaken on the ollowing elements o your system:-

batteries•

battery chargers•

inverters•

distribution and control equipment•

lights and exit signs•

the complete system•

SIx-mONTHly TEST

batteries

a) Lead-acid batteries - using a hydrometer and reerring to the maintenance manual, test randomly selected cells or:-

a. Electrolyte density.

b. State o charge.

Record the result o this test.

b) All batteries, including lead-acid batteries.

a. Visually check electrolyte level o each cell.Record those cells that require topping up.

b. Visually inspect all cell containers or electrolyte leakage. Have leaking cells repaired or replaced by aqualied person.

Record any repairs or replacement.

batter chargers

a) Visually inspect the unit.

b) Clean unit and cubicle o dust and dirt.

c) Check battery voltage reading is within normal limits.

d) Check all connections are tight.

Record that the checks have been carried out.Record battery voltage reading.

Inerters

a) Visually inspect all components.

Record te insection, te D.C. inut oltage and current and te A.C. outut oltage and current.

distrition an contro eipent

a) Visually inspect relays, contactors, circuit breakers and uses.Record inspection and any problems identied.

b) Check all connections or tightness.Record the check.

c) Remove any dust and dirt accumulated within the distribution and control equipment enclosures.Record the cleaning.

d) Check that sensing equipment operates system when isolated rom A.C. mains supply.Record the check and any problems identied.

Page 153: Essential Safety Maintenance Manual

8/3/2019 Essential Safety Maintenance Manual

http://slidepdf.com/reader/full/essential-safety-maintenance-manual 153/290

S E C T I O N 2 / P A G E 4

E S S E N T I A L S E R v I C E S M A I N T E N A N C E M A N U A L • B U I L D I N G C O N T R O L C O M M I S S I O N

Eergenc ights an eit signs

a) Check all lights and exit signs or correct operation.

b) Replace any aulty lamps.Record the check and any lamps replaced.

Tota sste

a) Check or correct operation when battery charger turned o and mains ailure simulated.

b) Check satisactory operation o the charger-ailure alarm while carrying out above check.

c) Record these checks and any problems identied.

Restore the system to normal operation, and check correct charging o batteries.

TwElvE-mONTHly TEST

Batteries - for any battery requiring maintenance of electrolyte aboe a secied leel.

Lead-acid batteries only - or each cell.

Using a hydrometer and reerring to the maintenance manual,

a) Check electrolyte density.

b) Check state o charge.Record the results o these checks.

A tpes o atteries - (incing ea-aci)

a) Visually check electrolyte level in all cells.Record level or each cell.

b) Visually inspect all cells or electrolyte leakage. Mop up and neutralise any spilt liquid, using baking powderdissolved in water.Record the inspection and any aults ound.

c) Inspect all cell connections or corrosion and tighten any loose joints.

d) Treat all exposed metal suraces with petroleum jelly or other recognised battery terminal preservative.Record the inspection and treatment.

e) Measure overall battery voltage and individual cell voltages, using a nely calibrated voltmeter.

Record any cell with a voltage dierence rom average o more than + 0.03 volt.

batter charger

a) Carry out tests required in six-monthly test.Record the test.

b) Check voltmeter calibration.Record the check and result.

c) Check satisactory operation o battery earth-ault detection system, i tted.Record the check.

d) Check satisactory operation o the battery low-voltage alarm, i tted.Record the check.

Inerter

a) Carry out tests on items required in six-monthly test.Record the tests.

b) Check voltmeter calibration.Record the check and result.

Page 154: Essential Safety Maintenance Manual

8/3/2019 Essential Safety Maintenance Manual

http://slidepdf.com/reader/full/essential-safety-maintenance-manual 154/290

S E C T I O N 2 / P A G E 5

E S S E N T I A L S E R v I C E S M A I N T E N A N C E M A N U A L • B U I L D I N G C O N T R O L C O M M I S S I O N

lights an eit signs

a) Carry out all checks required in the six-monthly test.Record the tests.

b) Clean all light emitting and refecting suraces.Record the cleaning.

Tota sste1. Check battery voltage on completion o discharge test, by the ollowing method:-

a) Turn o battery charger.

b) Simulate mains ailure (turn o power).

c) Using all the installed emergency lighting, test discharge or at least 90 minutes.

Record battery voltage on completion o this test. I battery voltage is below acceptable limits ater completion o this test,re-service or replace the battery.

Record re-service or replacement.

2. Measure te time taen for te battery carger to cange oer automatically to te ’oat carge‘ mode, after;

a) Disconnecting te load.

b) Turning on the battery charger.

c) Manually selecting ’boost charge‘ mode.Record the time taken.

The above testing procedures are detailed in AS 2293.2. Theses procedures must be available to your designated testerin a hard bound A4 size maintenance older. This older must be provided by the installer o your system.

MAintenAnce recorDs

A manuacturers’ hard bound log book, or an alternative system (this would include this manual), is recommendedor the recording o maintenance inormation.

Sheets or this purpose are included in the log book provided in Appendix C o this manual.

Page 155: Essential Safety Maintenance Manual

8/3/2019 Essential Safety Maintenance Manual

http://slidepdf.com/reader/full/essential-safety-maintenance-manual 155/290

E S S E N T I A L S A F E T Y M E A S U R E S M A I N T E N A N C E M A N U A L • B U I L D I N G C O M M I S S I O N

S E C T I O N 2 / P A G E 6

2.2 EmERGENCy POwER SuPPly

pUrpose

An emergency power supply is required to ensure the operation o required saety systems in the event o mains power ailure.

reqUireMents of tHe eqUipMent

An emergency power supply must:-

a) Be connected automatically if te normal oer suly fails; and

b) I located within the building, be separated rom the remainder o the building by an enclosure with the requiredre-resistance rating; and

c) Be connected to te required safety systems by suitable re-resisting cabling.

The power supply can be provided by either o the ollowing:-

a) haing to searate cables feeding into your substation; or

b) haing to or more searate sulies coming from searate substations outside your building; or

c) Supplied rom a generating set capable o starting and taking the necessary electrical load within 30 secondso ailure o the mains supply.

MetHoD of operAtion

On failure of te main electrical suly, te system must:-

a) Automatically switch over to the alternate supply, providing power to at least the required saety systems.

b) I provided by a generating set:-

• Start te engine.

• Bring engine u to full oerating seed.

• proide oer to at least te required safety systems, itin 30 seconds of mains failure.

mAINTENANCE CHECkS

It is recommended that the relevant building surveyor should require that emergency power supplies be tested six-monthly.The owner may delegate this unction to another person or body where necessary or appropriate.

Where your alternative supply is provided externally to your premises by your power supply authority, it is recommended that you make contact with your power supply authority, to request that it test the automatic change-over switching acility, whichin most cases is part o the supply equipment.

I you have a generating set, maintenance routines are recommended to be carried out at the ollowing intervals:-

Weekly•

Monthly•

Six-monthly•

Yearly•

Generating set:

wEEkly

1. Check water and oil levels. Top up i necessary.

2. Check required spares are on hand - belts, lter cartridges, engine oil.

  BCA 1990: Sec G3.8 BCA 1996: G3.8 (Sec G3.8) 

Page 156: Essential Safety Maintenance Manual

8/3/2019 Essential Safety Maintenance Manual

http://slidepdf.com/reader/full/essential-safety-maintenance-manual 156/290

E S S E N T I A L S A F E T Y M E A S U R E S M A I N T E N A N C E M A N U A L • B U I L D I N G C O M M I S S I O N

S E C T I O N 2 / P A G E 7

3. Where batteries are installed, check batteries and charger or:-

a) Freedom rom corrosion on terminals and in battery compartment.

b) Correct electrolyte level, top up i necessary.

c) Voltage per cell - using a voltmeter, ensure voltage is not less than 2 volts or lead-acid, batteries, 1.5 volts ornickel-cadmium (I voltage is less, have charger checked by a qualied person).

4. Start the engine by simulating a power ailure (turn o monitoring circuit), run engine or at least 10 minutes, thencheck or the ollowing:-

a) Visually check or water, oil or uel leaks, loose ttings or ancillary equipment.

b) Visually check belt drives.

c) Correct operation o battery charging alternator or generator (check volt meter).

d) Battery carger oer-failure alarm, if tted.

e) Excessive vibration or heat.

) Correct running speed.

g) Ater running and shutting down:-

i) Check water, oil and uel levels. Top up i necessary.

ii) Ensure any strainer or lter, i tted, on the engine water

ii) Ensure any strainer or lter, i tted, on the engine water cooling system, is checked and cleaned.

iii) Ensure the engine ’stop’ mechanism automatically returns to the start position.

mONTHly

a) Start the engine using the manual control, run the engine at rated speed or at least 30 minutes and checkor correct operating temperature.

b) Carry out the weekly procedures.

SIx-mONTHly

a) Carry out the weekly and monthly procedures.

a. Check, clean and replace, i necessary, engine-uel sludge and sediment trap, uel, oil and air lters.

b) Change lubricating oil, i advised by engine manuacturer at this requency (I not, change at least yearly).

MAintenAnce recorDs

The ollowing records are required:-

SIx-mONTHly TEST

The ollowing inormation must be entered in your log book:-

The date o test and time conducted.•

Execution o test - satisactory or otherwise.•

Any maintenance work required.•

Name o person carrying out test.•

Signature o person carrying out test.•

Log book sheets or this purpose are included in Appendix C o this manual.

Page 157: Essential Safety Maintenance Manual

8/3/2019 Essential Safety Maintenance Manual

http://slidepdf.com/reader/full/essential-safety-maintenance-manual 157/290

E S S E N T I A L S A F E T Y M E A S U R E S M A I N T E N A N C E M A N U A L • B U I L D I N G C O M M I S S I O N

S E C T I O N 2 / P A G E 8

2.3 EmERGENCy wARNING ANdINTERCOmmuNICATION SySTEm

pUrpose

An emergency warning and intercommunication system (EWIS) is installed in a building to alert

occupants in the event o an emergency and enable an orderly evacuation o the building.

reqUireMents of tHe eqUipMent

To ull its unction, the EWIS must have the ollowing acilities:-

a) A master emergency control anel (MECp); and

b) Any necessary additional emergency control anels (ECp); and

c) Te necessary distribution system to transmit a arning signal to eac eacuation zone in te building; and

d) A arden intercommunication oint (wIp) located on eac oor or in eac eacuation zone; and

e) A notice at eac ECp giing clear instructions on o to oerate tis equiment correctly; and

) An inter-connection with the building re alarm system.

To ensure the system ulls its purpose, it is essential that all sta/personnel located in the building are given training inidentication o the ‘alert’ and ‘evacuation’ signals, both audible and visible, and take part in an evacuation exercise.

MetHoD of operAtion

A key requirement or this system is the appointment o a house warden and a zone warden or each evacuation zonein the building.

These people should be appointed and trained to ull their respective roles.

In addition, each member o sta should be advised o the house and zone wardens appointed, their duties, and the authoritydesignated to these wardens.

On actiation of te re alarm system, te EwIS sall transmit te ‘alert’ signal until manual control of te system isestablished. I manual control is not established in the pre-determined time or your system, the ‘evacuate’ signal isautomatically transmitted.

The ‘alert’ signal must also be capable o manual initiation rom each ECP and WIP.

I manual control is established, the house warden:-

Attends the MECP.•

Gaters information on te incident.•

Makes a decision on evacuation.•

Advises the zone wardens o this decision.•

Supervises the evacuation i ordered.•

Becomes te focal oint of contact it resonding emergency serices.•

MAintenAnce cHecKs

The maintenance routines in AS 1851.10 require testing and checking o the system:-

Monthly•

Six-monthly•

Full details o the required monthly and six-monthly maintenance routines and the Levels 1 and 2 maintenance checks aredetailed in AS 1851.10.

BCA 1990: E4.9 Spec E1.5Spec E1.7

BCA 1996: Ep4.3 (E4.9) Reerence: AS 2220.1

AS 2220.2AS 1851.10

Page 158: Essential Safety Maintenance Manual

8/3/2019 Essential Safety Maintenance Manual

http://slidepdf.com/reader/full/essential-safety-maintenance-manual 158/290

Page 159: Essential Safety Maintenance Manual

8/3/2019 Essential Safety Maintenance Manual

http://slidepdf.com/reader/full/essential-safety-maintenance-manual 159/290

PURPOSE

Exit signs are provided to aid occupant identifcation o exits and paths o travel to exits.

REQUIREMENTS OF THE EQUIPMENT

Exit signs must be:-

a) Installed to AS 2293.1; and

b) Clearly visible to persons approaching an exit; and

c) Located in positions where exits are not readily apparent, i.e. corridors, hallways and lobbies, with directional arrowsindicating the direction to an exit; and

d) Located on, above, or adjacent to each door providing egress (as detailed in BCA E4.5); and

e) Clear and legible in writing with adequate size letters and symbols; and

f) Provided with emergency illumination in the event of normal power supply failure.

METHOD OF OPERATION

Exit signs must be set up to operate as follows:-

be illuminated at all times by mains power supply or by being a self contained unit; and•

be either internally or externally illuminated; and•

have a provision or emergency power supply in the event o ailure o the normal power source.•

MAINTENANCE CHECKS

It is recommended that the relevant building surveyor should require maintenance to be carried out at least every six monthsto AS 2293.2. It should be noted that this is the lowest level of maintenance required by the Standard and other routines arealso required on a yearly basis. The owner may delegate this function to another person or body wherenecessary or appropriate.

The testing procedures o exit signs are detailed in AS 2293.2. These procedures must be available to your designated tester

in a hard bound A4 size maintenance older. This older must be provided by the installer o your system.

MAINTENANCE RECORDS

A manufacturers’ hard bound log book, or an alternative system (this would include this manual), is recommended for therecording o maintenance inormation.

Sheets or this purpose are included in the log book provided in Appendix C o this manual.

S E C T I O N 2 / P A G E 1 0

E S S E N T I A L S A F E T Y M E A S U R E S M A I N T E N A N C E M A N U A L • B U I L D I N G C O M M I S S I O N

2 .4 Ex IT S IGN SBCA 1990: E4.5 BCA 1996: EP4.2 (E4.5) Reference: AS 2293.1 

AS 2293.2

Page 160: Essential Safety Maintenance Manual

8/3/2019 Essential Safety Maintenance Manual

http://slidepdf.com/reader/full/essential-safety-maintenance-manual 160/290

Fire-detectionand suppressionequipment

F i  r  e- d  e t   e c  t  i   on a n d 

 s  u  p

  pr  e s  s i   on e  q ui    pm en t  

Page 161: Essential Safety Maintenance Manual

8/3/2019 Essential Safety Maintenance Manual

http://slidepdf.com/reader/full/essential-safety-maintenance-manual 161/290

E S S E N T I A L S A F E T Y M E A S U R E S M A I N T E N A N C E M A N U A L • B U I L D I N G C O M M I S S I O N

S E C T I O N 3 / P A G E 1

3.1 FIRE CONTROL CENTRE 2

3.2 FIRE-DETECTION AND ALARM SYSTEM 3

3.3 FIRE ExTINGUIShERS – pORTABLE 4

3.4 FIRE hOSE REELS AND FIRE MAINS 5

3.5 FIRE hYDRANT SYSTEM AND FIRE MAINS 7

3.6 SMOkE ALARMS 9

3.7 SpRINkLER SYSTEM AND FIRE MAINS 11

3.8 STATIC WATER SUPPLY 13

3.9 PUMPSET SYSTEMS 14

i r e - e t e c t i o n a n s p p r e s s i o n e i p e n t

Page 162: Essential Safety Maintenance Manual

8/3/2019 Essential Safety Maintenance Manual

http://slidepdf.com/reader/full/essential-safety-maintenance-manual 162/290

E S S E N T I A L S A F E T Y M E A S U R E S M A I N T E N A N C E M A N U A L • B U I L D I N G C O M M I S S I O N

S E C T I O N 3 / P A G E 2

3 . 1 F I rE- d ET ECT I O N A Nd S u P P rES S I O N Eq u I P m ENT

PURPOSE

A re control centre is provided as an area rom which re-ghting operations or emergency procedures can be

directed or controlled.

REQUIREMENTS

The re control centre or room must:-

a) Contain the controls, panels, telephones, urniture and equipment associated with the required re servicesin the building; and

b) Only be used for re-ghting and other reasons concerning the safety or security of the building occupants; and

c) Be accessible via two ways:-

a. rom the ront entrance o the building; or

b. direct rom outside the building; and

d) Have the ollowing as detailed in Spec E1.8 o the Building Code of Australia:-

a. sucient foor area or its proper unctioning; and

b. adequate ventilation; and

c. suitable power supply; and

d. emergency lighting; and

e. a sign on the outside o the door identiying it as the ’Fire Control Centre‘; and

. low noise level with all re saety equipment operating.

MAINTENANCE CHECKS

To ensure the re control centre is operational, it is recommended that maintenance be carried out as ollows:-

YEArLY

It is recommended that the relevant building surveyor should require an annual inspection o this acility. The owner maydelegate this unction to another person or body where necessary or appropriate.

It is also recommended that an exercise be held at least yearly, to ensure this acility is workable.

This exercise could be held in conjunction with:-

a) The re authority serving the area.

b) An evacuation exercise or the premises.

MAINTENANCE RECORDS

The ollowing inormation must be recorded:-

a) The dates the monthly and yearly inspections were carried out; and

b) The name o the person conducting the inspections and

c) Any problems identied in the inspections; and

d) Actions taken to rectiy problems identied; and

e) Date this rectication occurred; and

) Signature o the person conducting the inspection.

Inormation relating to the conduct o an evacuation exercise could also be recorded.

A log sheet to record this inormation is provided in Appendix C o this manual.

BCA 1990: E1.8 Spec E1.8

BCA 1996: EP1.6 (E1.8, Spec E1.8) 

Page 163: Essential Safety Maintenance Manual

8/3/2019 Essential Safety Maintenance Manual

http://slidepdf.com/reader/full/essential-safety-maintenance-manual 163/290

E S S E N T I A L S A F E T Y M E A S U R E S M A I N T E N A N C E M A N U A L • B U I L D I N G C O M M I S S I O N

S E C T I O N 3 / P A G E 3

3.2 IRE dETECTION ANd AlARm SySTEm

pUrpose

A re detection and alarm system is installed to sense and provide warning o a re in its initial development stage.

Proper operation o this system will aord the building occupants the maximum amount o time available to seeksae reuge.

reqUireMents of tHe eqUipMent

A re alarm system must automatically:-

a) Sense te resence of a re and adise its location; and

b) Adise te re brigade; and

I installed:-

c) Sitc te air andling system into te smoe entilating mode; and

d) Actiate te closure of smoe and re-isolating doors; and

e) Activate necessary re pumps.

In addition to these automatically activated unctions, the alarm system may have a manual means to activate the system.

MetHoD of operAtion

Detectors of differing tyes are installed trougout te building to comly it AS 1670. Te standard designates te locationand the suitable detector type to be installed.

A signal rom a detector is relayed to the control and indicating equipment in the system, which activates the variousresponses listed above.

MAintenAnce cHecKs

It is recommended that the relevant building surveyor should require the acilities to be inspected weekly. It should be notedthat this is the lowest level o maintenance routines required by AS 1851.8. More rigorous monthly and yearly routines are alsorequired and are detailed in the Standard. The owner may delegate the maintenance unction to another person or body wherenecessary or appropriate.

Weekly tests are required when the alarm is connected to an unmanned re station or when required by the building surveyorbecause o the nature o the premises.

MAintenAnce recorDs

The necessary maintenance records are located in Appendix C o this manual.

BCA 1990: E1.7 Spec E1.8

BCA 1996: Ep2.1, Ep2,2 (Part E2, Spec E2.2a)

Reerence: AS 1670AS 1851.8

Page 164: Essential Safety Maintenance Manual

8/3/2019 Essential Safety Maintenance Manual

http://slidepdf.com/reader/full/essential-safety-maintenance-manual 164/290

E S S E N T I A L S A F E T Y M E A S U R E S M A I N T E N A N C E M A N U A L • B U I L D I N G C O M M I S S I O N

S E C T I O N 3 / P A G E 4

3.3 IRE ExTINGuISHERS – PORTAblEBCA 1990: E1.6 

Spec E1.8BCA 1996: Ep1.6 (E1.8,

Spec E1.8)Reerence: AS 2444

AS 1851.1pUrpose

Portable re extinguishers provide occupants with an appliance with which to attack a re in its initial stages.

reqUireMents of tHe eqUipMent

To provide re extinguishers, containing extinguishing agent suitable or the re hazard likely to be encountered. Fireextinguishers complying with Australian Standards are marked with a re classication and rating, determined in accordancewith AS/NZS 1850, which indicates the class and size o re or which they have been successully tested.

Each extinguisher must be located in a conspicuous and readily accessible position, the location being indicated bythe appropriate signage.

MetHoD of operAtion

A re extinguisher is put into operation by transporting the extinguisher close to the re and ollowing the operating

instructions clearly displayed on the extinguisher.It is essential that all sta members in the premises are suitably trained in the correct use o re extinguishers locatedin the premises.

MAintenAnce cHecKs

It is recommended that the relevant building surveyor should require that re extinguishers be maintained six-monthly to AS1851.1. It should be noted that this is the lowest level o maintenance routines required by AS 1851.1. More rigorous routinesare also required and are outlined below. The owner may delegate this unction to another person or body where necessary orappropriate.

A ve-level inspection and service procedure is detailed in AS 1851.1:-

Six-monthly•

Twelve-monthly•

Three-yearly•

Six-yearly•

Ater use o the extinguisher•

A comprehensive maintenance schedule is detailed in AS 1851.1 or all types o re extinguishers. All maintenance work mustbe carried out by experienced personnel, observing recognised saety procedures (AS 1851.1, Section 2.1.5).

MAintenAnce recorDs

For the purpose o maintaining service records, each extinguisher in the premises must have a unique site•identication mark (AS 1851.1 Section 2.1.1).

I more than 10 extinguishers are located in or on the premises, a site plan showing the location o each extinguisher•and its identication, type, size and rating must be provided (AS 1851.1 Section 2.1.2).

A maintenance record tag as per AS 1851.1 Section 2.3.2, must be attached to each extinguisher.•

A report on the correct provision and location o extinguishers must be provided by the service agency or personnel•(AS 1851.1 Section 2.1.4).

Page 165: Essential Safety Maintenance Manual

8/3/2019 Essential Safety Maintenance Manual

http://slidepdf.com/reader/full/essential-safety-maintenance-manual 165/290

E S S E N T I A L S A F E T Y M E A S U R E S M A I N T E N A N C E M A N U A L • B U I L D I N G C O M M I S S I O N

S E C T I O N 3 / P A G E 5

3.4 IRE HOSE REElS ANd IRE mAINSBCA 1990: E1.6 

Spec E1.8BCA 1996: Ep1.6 (E1.8,

Spec E1.8)Reerence: AS 2444

AS 1851.1pUrpose

Fire hose reels are be provided to enable occupants to undertake initial re extinguishment.

reqUireMents of tHe eqUipMent

Fire hose reel systems must:-

a) Provide sucient hose reel length to enable every part o the foor or storey on which it is installed to be reachedby laying te ose along normal lines of access trougout tat oor; and

b) Be roided it a ater suly rate of at least 0.33 litres/second.(AS 2441).

MetHoD of operAtion

The occupants o the premises should be able to operate the system:-

a) By locating any ose reel itin te building.

b) By folloing te oerating instructions dislayed on te ose reel.

c) It is essential that all sta personnel on the premises are trained in the sae and ecient operation o re hose reels.

MAintenAnce cHecKs

It is recommended that the relevant building surveyor should require that re hose reels be maintained at six-monthly intervalsto AS 1851.2, and re mains maintained weekly to AS 1851.4. Pumpsets servicing the equipment are required to be serviced inaccordance with AS 1851.14 (reer to 3.9). It should be noted that these are the lowest levels o maintenance routines requiredby the Standards. More rigorous routines are also required by AS 1851.2 and are outlined below.

The maintenance and inspection may be carried out by the owner or the owner may delegate this unction to another person

or body where necessary or appropriate.

SIx-mONTHly INSPECTION (As per AS 1851.2 Section 3)

a) Check that the operating instructions on both the hose reel and the manual valve stop assembly are clear and legible.

b) Check that there is no leakage o water exceeding 5 ml in a three minute period rom any point o the hose reelassembly, with the stop valve ully open, the nozzle closed, and the hose partially run out to at least ve metres.

c) Check that the hose runs out reely through the hose guide.

d) Check or signs o corrosion or damage that may aect the operation o the hose reel.

Ater this inspection, it is essential that the hose is rewound in even layers, the nozzle re-engaged correctly in the interlock, thevalve shut o and the hose de-pressurised by opening the discharge nozzle. Close the nozzle when de-pressurised.

TwElvE-mONTHly INSPECTION (As per AS 1851.2 Section 3)

Carry out the checks required or the six-monthly inspection, with the exception o item (b). In addition, the ollowing pointsshould be checked:-

a) With the stop valve turned ully open, the nozzle closed and the hose ully run out, check or any leakage o waterexceeding 5 ml in a three minute period, rom either the valve gland, spindle gland, or discharge nozzle.

b) That the hose can be run out easily in any direction.

c) That the fow rate supplied is not less than 0.33 litres/second, with the nozzle in the jet mode (This will ll a 10-litrebucket in 30 seconds).

As with the six-monthly test, it is essential that the hose is rewound in even layers, the nozzle re-engaged correctly in theinterlock, the valve shut o, and the hose de-pressurised by opening the discharge nozzle. Close the nozzle when de-pressurised.

Any deects ound should be reported to management and the necessary repairs or replacement carried out as soon aspossible, to ensure the equipment is ready or use i needed. In addition, a label showing the date o service and a descriptiono the ault should be attached to the side plate o the aulty hose reel.

Page 166: Essential Safety Maintenance Manual

8/3/2019 Essential Safety Maintenance Manual

http://slidepdf.com/reader/full/essential-safety-maintenance-manual 166/290

E S S E N T I A L S A F E T Y M E A S U R E S M A I N T E N A N C E M A N U A L • B U I L D I N G C O M M I S S I O N

S E C T I O N 3 / P A G E 6

MAintenAnce recorDs

A log book, showing the location and identiying marks or numbers or each hose reel on the premises, must be established.

Sheets or this purpose are included in the appendix C o this manual.

The ollowing inormation must be recorded:-

a) Te date of eac insection; and

b) Any defects found; and

c) On te tag attaced to eac ose reel, te date of eac insection.

For re hose reel pumps, reer to 3.9 o this section.

Page 167: Essential Safety Maintenance Manual

8/3/2019 Essential Safety Maintenance Manual

http://slidepdf.com/reader/full/essential-safety-maintenance-manual 167/290

E S S E N T I A L S A F E T Y M E A S U R E S M A I N T E N A N C E M A N U A L • B U I L D I N G C O M M I S S I O N

S E C T I O N 3 / P A G E 7

3.5 IRE HydRANT SySTEm ANd IRE mAINSBCA 1990: E1.3 BCA 1996: Ep1.3 (E1.3)Reerence: AS 2419

AS 1851.4AS 1851.14

 pUrpose

A re hydrant system is installed to provide re-ghting personnel a supply o water or re-ghting purposes.

reqUireMents of tHe eqUipMent

To ull its purpose, the hydrant system must:-

a) Be installed to AS 2419.1; and

b) Be located to roide coerage to eery art of te building or site requiring coerage; and

c) proide a secied minimum o of ater at all times; and

d) Be readily accessible to re-gting ersonnel.

MetHoD of operAtion

The supply o water to the hydrant system must be provided automatically, once a hydrant valve is opened or, in somesystems, once a re alarm has been activated.

Any pump incorporated into the system must be powered by a motor that will enable operation regardless o primary electricalmains ailure.

The water supply must be acquired rom a source that will provide adequate water or a specied period o time.

MAintenAnce cHecKs

It is recommended that the relevant building surveyor should require that re hydrants and re main systems be maintainedmonthly to AS 1851.4. It should be noted that this is the lowest level o maintenance routines required by AS 1851.4. Morerigorous routines are also required and are outlined below. The owner may delegate this unction to another person or body

where necessary or appropriate.Maintenance work, involving inspections, testing and servicing, has been classied into six levels, at the ollowing requencies:-

Weekly•

Monthly•

Quarterly•

Yearly•

Three-yearly•

Six-yearly•

Note: The weekly maintenance routine relates to the pumpset and is to be carried out in accordance with AS 1851.14

Table 7.1. (Reer to 3.9 o this section)

Complete details o this six-level program are included in AS 1851.4.

Before maintenance or is carried out, te folloing recautions must be taen:-

a) Whenever maintenance work will render the system inoperative, or will activate the re alarm system, notiy the rebrigade and the owner o the building, or his or her agent, beore any action is taken. I you call out the re brigadeunnecessarily, you could be carged for teir attendance; and

b) Before turning off te ater, a toroug cec of all of te remises must be made, to ensure it is as safe froma treat of re as is ossible; and

c) Ensure all the other re suppression equipment is ully operational.

Ater this work is completed, the hydrant system must be tested to ensure it operates at its designed perormance level,and the re brigade must be notied that the system is again operational.

Whenever the system is disabled or maintenance or modications, special precautions should be implementedas detailed in AS 1851.4.

Page 168: Essential Safety Maintenance Manual

8/3/2019 Essential Safety Maintenance Manual

http://slidepdf.com/reader/full/essential-safety-maintenance-manual 168/290

E S S E N T I A L S A F E T Y M E A S U R E S M A I N T E N A N C E M A N U A L • B U I L D I N G C O M M I S S I O N

S E C T I O N 3 / P A G E 8

MAintenAnce recorDs

The maintenance records must record:-

a) All te insections, testing and sericing rocedures required under AS 1851.4; and

b) Details of defects found and unsceduled reairs carried out; and

c) Details of any remedial action taen.

All these details must be systematically entered in the log book established or the hydrant system. This log book should bemaintained by a person responsible or it, and must be available or inspection when required. Record sheets are included inAppendix C o this manual.

In addition, each hydrant must have a tag attached to it, showing the dates on which the yearly, three-yearly and six-yearlyprocedures were carried out.

Page 169: Essential Safety Maintenance Manual

8/3/2019 Essential Safety Maintenance Manual

http://slidepdf.com/reader/full/essential-safety-maintenance-manual 169/290

E S S E N T I A L S A F E T Y M E A S U R E S M A I N T E N A N C E M A N U A L • B U I L D I N G C O M M I S S I O N

S E C T I O N 3 / P A G E 9

3.6 SmOkE AlARmSBCA 1990: E1.7 

Spec E1.7Vic - H101.9Vic - H103

BCA 1996: Ep2.1, Ep2,2 (partE2, Spec E2.2a)

Reerence: AS 3786AS 1851.8

pUrpose

Smoke alarms are installed either singly or in an interconnected circuit, to detect and provide

an early warning o the presence o re.

This early warning is designed to provide as much time as possible to alert occupants o this threat.

reqUireMents of tHe eqUipMent

To carry out its unction, a smoke alarm must be:-

a) A system:-

a. designed in compliance with AS 3786, or

b. listed in te SSL (Scientic Serices Laboratory) Register of accredited products;

b) Connected to te consumer mains suly; and

c) Located in accordance with AS 1670, Specication E1.7 o BCA 90 and Specication E2.2(a) o BCA 96ere alicable; and

d) Must have an external or internal power source, or a combination o both.

MetHoD of operAtion

There are two basic types o smoke alarms:-

a) Te ionization tye, ere smoe entering te camber causes a cange in current o;

b) The optical type, which operates by the scattering or absorption o light by smoke particles in a light beam.

Bot situations cause te alarm to sound locally or at a remote central location.

An alarm system may be required by the Building Code of Australia or building surveyor to also transmit an alarm signalto a re station.

MAintenAnce cHecKs

It is recommended that the relevant building surveyor should require smoke alarms be checked monthly. The owner maydelegate this unction to another person or body where necessary or appropriate.

mONTHly

i) Perorm the operational test o the alarms in accordance with the manuacturer’s instructions.

ii) Visibly check each unit or damage.

yEARly

i) Battery - if not of te recargeable tye, rene battery it a battery as secied on or in te alarm.

ii) I a rechargeable battery, check its voltage, using a voltmeter. I the voltage is as specied on the battery or the alarm,re-install. I voltage is not satisactory, renew the battery and have the charging circuit tested by a qualied serviceprovider.

iii) Using a vacuum cleaner, careully clean the inside and cover o the alarm unit. Avoid physical damage.

iv) Where provided, turn o external power supply to smoke alarm and test as per manuacturer’s instructions. Restorepower supply when completed.

v) Carry out the monthly routine.

Page 170: Essential Safety Maintenance Manual

8/3/2019 Essential Safety Maintenance Manual

http://slidepdf.com/reader/full/essential-safety-maintenance-manual 170/290

E S S E N T I A L S A F E T Y M E A S U R E S M A I N T E N A N C E M A N U A L • B U I L D I N G C O M M I S S I O N

S E C T I O N 3 / P A G E 1 0

MAintenAnce recorDs

A log book must be kept to record:-

a) Te comletion of te montly routine; and

b) Te comletion of te yearly routine; and

c) Any maintenance required on te system; and

d) The date and name o the person testing the system.

Log sheets or this purpose are located in Appendix C o this manual.

Page 171: Essential Safety Maintenance Manual

8/3/2019 Essential Safety Maintenance Manual

http://slidepdf.com/reader/full/essential-safety-maintenance-manual 171/290

E S S E N T I A L S A F E T Y M E A S U R E S M A I N T E N A N C E M A N U A L • B U I L D I N G C O M M I S S I O N

S E C T I O N 3 / P A G E 1 1

3.7 SPRINklER SySTEm ANd IRE mAINSBCA 1990: E1.5 

Part E1BCA 1996: Ep1.4 (E1.5) Reerence: AS 2118

AS 2419.1AS 1851.3AS 1851.4AS 1851.14

pUrpose

A sprinkler system is installed to provide a ull-time automatic re suppression system, with

the ability to summon the re brigade automatically.

sYsteMs AnD eqUipMent

a) Automatic sprinkler systems may include:-

b) Wet pipe systems and sprinklers.

c) Valve installations.

d) Electric motor and compression-ignition engines and pumpsets.

e) Fire brigade booster connections.

) Pre-action systems.

g) Water storage systems.

h) Alarms and interace with automatic re alarm and detection systems where installed.

reqUireMents of tHe eqUipMent

To provide the required protection, the sprinkler system must be:-

a) An automatic re sprinkler system complying with:-

a. AS 2118 subject to Building Code of Australia Secication E1.5; or

b. NFpA 13R tye system; and

b) Maintained in accordance with AS 1851.3, either by or under the direct supervision o personnel competent insprinkler system maintenance.

MetHoD of operAtion

To comply with AS 2118, the sprinkler system must have:-

a) proision for an adequate ater suly; and

b) A uming system to ressurise te srinler system; and

c) A distribution ie system to delier ater to eac srinler ead; and

d) Srinler eads to erform according to te ris tey are rotecting; and

e) A local alarm facility to alert te oeration of a srinler system; and

) A direct alarm connection to the re brigade (where required).

The sprinkler system is activated by a sprinkler head or heads responding to a rise in temperature. Water fows through thehead(s), lowering the residual water pressure, which causes the pump system to come into operation. Water fowing throughthe system drives the water-motor in the local alarm, sounding the alarm bell. Where tted, a direct alarm is transmitted to there brigade.

Page 172: Essential Safety Maintenance Manual

8/3/2019 Essential Safety Maintenance Manual

http://slidepdf.com/reader/full/essential-safety-maintenance-manual 172/290

E S S E N T I A L S A F E T Y M E A S U R E S M A I N T E N A N C E M A N U A L • B U I L D I N G C O M M I S S I O N

S E C T I O N 3 / P A G E 1 2

MAintenAnce cHecKs

It is recommended that the relevant building surveyor require that re mains be maintained weekly to AS 1851.3. It should

be noted that this is the lowest level o maintenance routines required by the Standards. More rigorous routines are alsorequired by AS 1851.3 and are outlined below. The owner may delegate this unction to another person or body wherenecessary or appropriate.

The sprinkler system maintenance program specied in AS 1851.3 and AS 1851.14 (or pumpset maintenance), provides orinspection, testing and maintenance at the ollowing requencies:-

Level 1 routines - weekly•

Level 2 routines - quarterly•

Level 3 routines - yearly•

Level 4 routines - three-yearly•

Level 5 routines - six-yearly•

The detail or these routines is detailed in chart orm in AS 1851.3 (attached).

Pumpset maintenance routines are detailed in AS 1851.14 (reer to 3.9 o this section).

When the system is rendered partially or ully disabled due to maintenance or modications, the ollowing precautionsare mandatory:-

a) Te building oner or is or er reresentatie must be notied; and

b) The re station to which the system is connected, or the nearest re station i there is no connection, must benotied beore work commences and ater work is completed.

The ollowing additional precautions should be observed, as ar as is practicable, whether the system is inoperative throughan emergency or planned occurrence:-

a) Under all circumstances, keep as much o the system ully operational as is practicable. I the necessary work is toextend over several days or weeks, re-instate the system as ar as is practicable at the end o each working day.

b) Where the system has to be let disconnected outside working hours, consideration should be given to employinga watchman while the system is disconnected.

c) Whenever it is possible, disconnection o the system should be undertaken when production machinery is inoperative.

d) While the system is down, smoking should be banned in the aected areas.

e) Notiy senior department personnel or tenants’ representatives o the situation, so that re-extinguishing appliancescan be kept immediately available, with trained personnel on hand to use them i necessary.

) Notiy the insurer or insurance broker o the situation.

g) Have all necessary equipment and material available and do all the work possible prior to isolating the sprinklers.

h) Hot cutting or welding should be avoided, where possible, in an area where the sprinkler system it not operational.This includes work on the sprinkler system.

i) Avoid all sources o ignition.

Maintenance testing o these systems should be carried out in conjunction with the re alarm system testing to assure thatthe systems are correctly interaced.

Prior to and ollowing this test, it is essential that the re brigade that receives the alarm shall be advised o the imminent test,checked to see the test call was received, and advised when the system is re-set and operational.

MAintenAnce recorDs

Records o all maintenance routines must be in a log book kept at the sprinkler control valves.

Suitable recording sheets are attached in Appendix C o this manual.

These correspond to the maintenance routines outlined in AS 1851.3.

Page 173: Essential Safety Maintenance Manual

8/3/2019 Essential Safety Maintenance Manual

http://slidepdf.com/reader/full/essential-safety-maintenance-manual 173/290

E S S E N T I A L S A F E T Y M E A S U R E S M A I N T E N A N C E M A N U A L • B U I L D I N G C O M M I S S I O N

S E C T I O N 3 / P A G E 1 3

3.8 STATIC wATER SuPPlyBCA 1990: part E11 BCA 1996: Ep1.3, Ep1.4 (part E1) Reerence: AS 2419.1

AS 2118AS 1851.14

pUrpose

To provide a water supply to an automatic sprinkler or a re hydrant system.

reqUireMents of tHe eqUipMent

Static water supply must:-

a) Be installed in combination or indiidually (ere aroriate) it AS 2118 or AS 2419.1; and

b) Have sucient water capacity and fow rate as specied in the above standards.

MAintenAnce cHecKs

It is recommended that the relevant building surveyor require an annual inspection o this acility. The owner may delegatethis unction to another person or body where necessary or appropriate.

Pumpset maintenance is to be carried out in accordance with AS 1851.14 (reer to 3.9 o this section).

MAintenAnce recorDs

A log book must be established with the ollowing inormation recorded:-

a) Te date of te cec or insection; and

b) Te name and status of te erson carrying out te tas; and

c) Any roblems identied; and

d) Date tese roblems ere rectied; and

e) Signature o the person inspecting.

Page 174: Essential Safety Maintenance Manual

8/3/2019 Essential Safety Maintenance Manual

http://slidepdf.com/reader/full/essential-safety-maintenance-manual 174/290

E S S E N T I A L S A F E T Y M E A S U R E S M A I N T E N A N C E M A N U A L • B U I L D I N G C O M M I S S I O N

S E C T I O N 3 / P A G E 1 4

pUrpose

To ensure the reliability o re protection equipment that requires a supply o water.

reqUireMents of tHe eqUipMent

A pumpset system must:-

Be selected and installed in accordance it AS 2941 1995 according to te re rotection equiment•it is to support.

MAintenAnce cHecKs

It is recommended that the relevant building surveyor require pumpsets to be maintained weekly to AS 1851.14. It should benoted that this is the lowest level o maintenance routines required by the Standard. More rigorous routines are also requiredby AS 1851.14 and are outlined below. The owner may delegate the maintenance unction to another person or body where

necessary or appropriate. The pumpset maintenance program specied in AS1851.14 provides or inspections, testing andmaintenance at the ollowing requencies:-

Leel 1 routines – eely•

Leel 2 routines – quarterly•

Leel 3 routines – annually•

Leel 4 routines – tree-yearly•

These routines are detailed in table orm in AS 1851.14.

When the pumpset is rendered partially or ully inoperative due to maintenance or modications, the ollowing precautionsshall be taken:-

(a) The building or acility management shall be notied.

(b) The re station to which the system is connected or the nearest re station i there is no brigade connection,shall be notied beore work commences and ater work is completed.

NOTE: It is recommended tat tis ractice be folloed for all umset systems.

The ollowing additional precautions should be observed as ar as is practicable:-

(a) Under all circumstances, as much o the system as is practicable should be kept operational. Should the work extendover a day, the system is to be reinstated as ar as practicable at the end o each day.

(b) Where the system is to be let disconnected outside working hours, the building/acility managementshould be notied. Consideration should be give to the employment o a watchman at the premises orthe period o disconnection.

Where possible, the electrics should be isolated in areas where the re protection has been limited or withdrawn,especially outside working hours.

A warning and advice should be provided at the re indicator panel (FIP) (where provided) or the re pumpset.The warning should include details o equipment outage and contact name and phone number.

(c) Whenever practicable, system disconnection should be undertaken when production machinery is inoperative.

(d) Smoking in the vicinity o the aected areas should be prohibited or the period o disconnection.

(e) Those senior department/tenancy representatives aected should be notied so that re extinguishing equipmentcan be held in special readiness or immediate use with a sucient number o trained personnel available to usethem i required.

() The insurer or insurance broker or the property should be notied.

(g) All needed equipment and materials should be on hand and all work possible should be done prior to isolationo the re protection equipment.

3.9 PumPSET SySTEmSBCA 1990: part E1 BCA 1996: Ep1.1, Ep1.3,

EP1.4 (Part E1)Reerence: AS 2441

AS 2419.1AS 2118AS 1851.14

 

Page 175: Essential Safety Maintenance Manual

8/3/2019 Essential Safety Maintenance Manual

http://slidepdf.com/reader/full/essential-safety-maintenance-manual 175/290

E S S E N T I A L S A F E T Y M E A S U R E S M A I N T E N A N C E M A N U A L • B U I L D I N G C O M M I S S I O N

S E C T I O N 3 / P A G E 1 5

(h) Hot cutting and welding should not be perormed on a re pumpset in situ or in an area where the re protectionequipment is impaired. I such work is unavoidable, it should be carried out in accordance with AS 1674.1and AS 1674.2.

(i) Simultaneous undertaking o other work that may urther reduce the integrity o re protection, or increase the rerisk, should be avoided.

(j) All sources o ignition should be avoided.

MAintenAnce recorDs

A log book must be established with the ollowing inormation recorded:-

a) Te date of te cec or insection; and

b) Te name of te erson or organisation carrying out te tas; and

c) The address o the premises and pumpset identication (i necessary)

d) The pumpset location within the building, the date o manuacture and the date in service.

e) Signature o the person inspecting.

The Standard also requires the use o a pumpset perormance log to record details o the pumpset perormance atcommissioning and any subsequent tests or re-commissioning.

Suitable recording sheets are attached in Appendix C o this manual.

Page 176: Essential Safety Maintenance Manual

8/3/2019 Essential Safety Maintenance Manual

http://slidepdf.com/reader/full/essential-safety-maintenance-manual 176/290

Page 177: Essential Safety Maintenance Manual

8/3/2019 Essential Safety Maintenance Manual

http://slidepdf.com/reader/full/essential-safety-maintenance-manual 177/290

Fire-resistance

F   i     r   e-r   e s 

i      s  t    a n c  e

Page 178: Essential Safety Maintenance Manual

8/3/2019 Essential Safety Maintenance Manual

http://slidepdf.com/reader/full/essential-safety-maintenance-manual 178/290

E S S E N T I A L S A F E T Y M E A S U R E S M A I N T E N A N C E M A N U A L • B U I L D I N G C O M M I S S I O N

S E C T I O N 4 / P A G E 1

4.1 FIRE CURTAINS 2

4.2 FIRE INDICES FOR MATERIAL 3

4.3 FIRE-ISOLATED LIFT ShAFTS 4

4.4 FIRE-pROTECTIvE COvERING, FIRE-RATED CONTROL jOINTS, FIRE-RATED MATERIALS AppLIED TOBUILDING ELEMENTS 5

4.4 FIRE-RATED ACCESS pANELS 6

4.5 FIRE-RESISTING ShAFTS 7

4.6 FIRE-RESISTING STRUCTURES 8

4.7 FIRE ShUTTERS AND FIRE wINDOwS 9

4.8 LIFTS – wARNING SYSTEMS 10

4.9 LIGhTwEIGhT CONSTRUCTION 11

4.10 pENETRATIONS IN FIRE-RATED STRUCTURES 13

i r e - R e s i s t a n c e

Page 179: Essential Safety Maintenance Manual

8/3/2019 Essential Safety Maintenance Manual

http://slidepdf.com/reader/full/essential-safety-maintenance-manual 179/290

E S S E N T I A L S A F E T Y M E A S U R E S M A I N T E N A N C E M A N U A L • B U I L D I N G C O M M I S S I O N

S E C T I O N 4 / P A G E 2

4.1 IRE CuRTAINSBCA 1990: Sec h1.3 BCA 1996: h1.3 (Sec h1.3)

pUrpose

A re curtain is provided in a theatre to prevent the passage o smoke and re rom the stage area to the audience area.

reqUireMents of tHe eqUipMent

A re curtain must be either:-

a) Non-combustible and tted to inibit smoe enetration around its erimeter en fully loered; or

b) A curtain with specied early re hazard indices and protection by a deluge sprinkler system across its total width.

Either type o curtain must be:-

a) Caable of closing fully itin 35 seconds; and

b) Oerated automatically by a eat actiated deice, or manually from eiter te stage side or audience side.

MetHoD of operAtion

A re curtain must be operated by:-

a) An automatic system of eat-actiated deices; or

b) Manually operated devices, or

c) By a us-button emergency release deice.

MAintenAnce cHecKs

It is recommended that the relevant building surveyor should require an annual inspection o this acility to ensure nomechanical damage has occurred or any intererence exists that prevents its operation. The owner may delegate this unction

to another person or body where necessary or appropriate.

TwElvE-mONTHly

a) Visual check o operating mechanism to ensure no physical damage or obstruction.

b) Visual check o curtain’s condition.

c) Visual check o heat detection equipment and sprinkler heads (i provided).

d) Ater rst isolating the re alarm system and sprinkler system (i provided), test the operation o the curtain by:-

a. Activating the heat-sensing equipment.

b. Activating the manual operating system.

c. Activating the emergency push button device.

MAintenAnce recorDs

A log book, included in Appendix C o this manual must be implemented to record:

a) Te 12-montly insections and tests, and roblems identied; and

b) Te date cecs and insections ere carried out; and

c) The name and signature o the person carrying out the checks and inspections.

Page 180: Essential Safety Maintenance Manual

8/3/2019 Essential Safety Maintenance Manual

http://slidepdf.com/reader/full/essential-safety-maintenance-manual 180/290

E S S E N T I A L S A F E T Y M E A S U R E S M A I N T E N A N C E M A N U A L • B U I L D I N G C O M M I S S I O N

S E C T I O N 4 / P A G E 3

4.2 IRE INdICES OR mATERIAlSBCA 1990: C1.10 BCA 1996: Cp4 (C1.10) Reerence: AS 1530.3

pUrpose

To indicate the suitability or otherwise o building materials, assemblies, linings and surace nishes in the ability to resist

spread o fame and generation o smoke.

reqUireMents

The indices provide a means o assessing building materials and components, using standard tests as outlined in AS 1530.3,or their perormance according to:-

a) Teir tendencies to ignite;

b) Teir tendencies to roagate ame;

c) Te eat tey release once ignition as occurred; and

d) Their tendencies to release smoke.

Using the above criteria, selection o suitable material can be made to ull a proposed class o building. Testing and selectiono materials takes place prior to construction and nishing o a new building.

Building oners must ensure tat any ne material introduced to teir remises conforms to te requirements ofthe Building Code of Australia.

MAintenAnce cHecKs

It is recommended that the relevant building surveyor should require an annual inspection o this acility to ensure thatmaterials that do not conorm to the re hazard indices do not occur in or have not been introduced to the premises.The owner may delegate this unction to another person or body where necessary or appropriate.

The manuacturer or supplier o these materials should be able to advise whether their product conorms.

MAintenAnce recorDs

To ensure compliance with the Building Regulations, owners o buildings must record the details o their yearly inspections.

Details tat must be recorded include:-

a) Identication of te remises; and

b) Site address; and

c) Name of building oner; and

d) Date te insection as carried out; and

e) Any non-conforming materials identied; and

f) Stes taen to remoe or relace te non-conforming material; and

g) Name and signature o the person carrying out the inspection.

A log sheet to record this inormation is included in Appendix C o this manual.

Page 181: Essential Safety Maintenance Manual

8/3/2019 Essential Safety Maintenance Manual

http://slidepdf.com/reader/full/essential-safety-maintenance-manual 181/290

E S S E N T I A L S A F E T Y M E A S U R E S M A I N T E N A N C E M A N U A L • B U I L D I N G C O M M I S S I O N

S E C T I O N 4 / P A G E 4

pUrpose

Lit shats are required to be re-isolated to prevent the passage o re via the shat to other foor levels o the building.

reqUireMents

Deending on te building’s tye of construction, te lift saft sould be eiter:-

a) Built to roide a secied leel of re-resistance, or

b) Built of non-combustible material.

The lit-landing doorways must be protected by doors with a specied re-resistance level, constructed and installed inaccordance with AS 1735.11.

These doors must be set to remain closed except when receiving or discharging passengers, goods or vehicles.

MAintenAnce cHecKs

It is recommended that the relevant building surveyor should require an annual inspection o this acility. The owner maydelegate this unction to another person or body where necessary or appropriate.

MAintenAnce recorDs

The ollowing inormation must be recorded:-

a) Te dates te montly and yearly insections ere carried out; and

b) Te name of te erson conducting te insections; and

c) Any roblems identied in te insections; and

d) Actions taen to rectify roblems identied; and

e) Date rectication occurred; and

) Signature o the person conducting the inspection.

A log sheet to record this inormation is provided in Appendix C o this manual.

4.3 IRE- ISOlATEd l IT SHATSBCA 1990: Section C BCA 1996: Cp4 (C1.10) Reerence: AS 1735.11

 

Page 182: Essential Safety Maintenance Manual

8/3/2019 Essential Safety Maintenance Manual

http://slidepdf.com/reader/full/essential-safety-maintenance-manual 182/290

E S S E N T I A L S A F E T Y M E A S U R E S M A I N T E N A N C E M A N U A L • B U I L D I N G C O M M I S S I O N

S E C T I O N 4 / P A G E 5

pUrpose

These materials, when assigned to their particular applications, assist in maintaining the integrity o the

re separation between foors or re compartments in the building, or provide protection to structural elementsto retain their integrity in the event o re.

reqUireMents

To ensure these materials ull their unction:-

a) The material used must be identical to a prototype or sample o that material that has been submitted to,and assed te standard re test, as referred to in AS 1530.4; or

b) The material used is listed and accepted in Table 1 o Specication A2.3 o the Building Code of Australia; and

c) The material applied or constructed in accordance with that standard or that specic action.

MAintenAnce cHecKs

It is recommended that the relevant building surveyor should require an annual inspection o this acility. The owner maydelegate this unction to another person or body where necessary or appropriate.

Maintenance checks are also recommended to be carried out ater maintenance work that may have damaged or removeda section o material.

These checks should be carried out visually, with urther investigation o any suspect areas.

Any problems identied should be rectied as soon as is practicable, by either:-

a) Reerral back to the contractor who carried out the maintenance work, or

b) By aing your on maintenance staff or contractor carry out te necessary reairs.

MAintenAnce recorDs

The ollowing inormation must be recorded:-

a) Te dates of te maintenance and insections; and

b) Te name of te erson conducting te insections; and

c) Any roblems identied in te insection; and

d) Actions taen to rectify roblems identied; and

e) Date te rectication occurred; and

) Signature o the person conducting the inspection.

A log sheet to record this inormation is provided in Appendix C o this manual.

4.4 IRE-PROTECTIvE COvERINGSBCA 1990: A2.3, Sec A2.3 

Section CBCA 1996: A2.3, Cp1,

CP2 (A2.3, Spec A2.3,Section C)

Reerence: AS 1530.4

(Including fre-rated control joints, fre-rated materials applied to building elements)

Page 183: Essential Safety Maintenance Manual

8/3/2019 Essential Safety Maintenance Manual

http://slidepdf.com/reader/full/essential-safety-maintenance-manual 183/290

E S S E N T I A L S A F E T Y M E A S U R E S M A I N T E N A N C E M A N U A L • B U I L D I N G C O M M I S S I O N

S E C T I O N 4 / P A G E 6

pUrpose

Fire-rated access panels are provided where access to shats containing ventilation equipment, pipes, garbage chutes or other

services, is required or maintenance purposes.

reqUireMents

A panel, together with its rame, requires:-

a) A re-resistance level, and

b) Installation to a standard that will maintain the required re-resistance level.

The covering could be constructed as a panel, or as a re door.

MAintenAnce cHecKs

It is recommended that the relevant building surveyor should require that re-rated access panels be inspected annually. Theowner may delegate this unction to another person or body where necessary or appropriate.

It is also recommended that panels be checked visually ater maintenance work.

Where the opening is protected by a re door, constructed and installed in accordance with AS 1905.1, maintenance andinspection o these doors must be in accordance with AS 1851.7 and should be carried out in conjunction with other re doors.

MAintenAnce recorDs

For re rated panels, the ollowing inormation should be recorded:-

a) Te dates of te montly, after maintenance and yearly insections; and

b) Te name of te erson conducting te insections; and

c) Any roblems identied in te insection; and

d) Actions taen to rectify roblems identied; and

e) Date te rectication occurred; and

) Signature o the person conducting the inspection.

A log sheet to record this inormation is provided in Appendix C o this manual.

4.4 IRE-RATEd ACCESS PANElSBCA 1990: part C3 BCA 1996: Cp8 (part C3) Reerence: AS 1905.1

AS 1851.7

 

Page 184: Essential Safety Maintenance Manual

8/3/2019 Essential Safety Maintenance Manual

http://slidepdf.com/reader/full/essential-safety-maintenance-manual 184/290

E S S E N T I A L S A F E T Y M E A S U R E S M A I N T E N A N C E M A N U A L • B U I L D I N G C O M M I S S I O N

S E C T I O N 4 / P A G E 7

pUrpose

Shats provided in buildings or provision o lits, stairs, ventilation or services, passing rom one storey or compartment to

another, must have a re-resistance level to protect those services and the compartments through which they pass.

reqUireMents:

A re resisting shat must:-

a) Be roided it te re-resistance leel as secied in te Building Code of Australia; and

b) Have all openings into the shat protected with doors, panels, or re-stopping material rated to provide the requiredre-resistance leel; and

c) Have its integrity preserved by:-

a. not ermitting any unautorised oening to be constructed; and

b. not permitting storage o any goods, material or equipment in these areas.

MAintenAnce cHecKs

It is recommended that the relevant building surveyor should require an annual inspection o this acility. The owner maydelegate this unction to another person or body where necessary or appropriate.

To ensure the integrity and saety o re resisting shats, inspections should ensure:-

a) No unauthorised penetration o a shat has occurred.

b) Equipment protecting doorways or other openings is operational (re doors protecting openings must be inspectedand maintained in accordance with Section 14 o this manual).

c) No unauthorised goods, material or equipment have been stored in these areas.

MAintenAnce recorDs

The ollowing inormation must be recorded:-

a) Te date te annual insection as carried out; and

b) Te name of te erson conducting te insections; and

c) Any roblems identied in te insection; and

d) Actions taen to rectify roblems identied; and

e) Date te rectication occurred; and

) Signature o the person conducting the inspection.

A log sheet to record this inormation is provided in Appendix C o this manual.

4 .5 IR E -R E S IST IN G S H A T SBCA 1990: A2.3, Sec A2.3 

Section CBCA 1996: A2.3, Cp1,

CP2 (A2.3, Spec A2.3,Section C)

Reerence: AS 1530.4

Page 185: Essential Safety Maintenance Manual

8/3/2019 Essential Safety Maintenance Manual

http://slidepdf.com/reader/full/essential-safety-maintenance-manual 185/290

E S S E N T I A L S A F E T Y M E A S U R E S M A I N T E N A N C E M A N U A L • B U I L D I N G C O M M I S S I O N

S E C T I O N 4 / P A G E 8

pUrpose

Certain elements and structures within the building must have a re-resistance level to maintain structural stability during a

re and restrict the spread o re.

reqUireMents

A re-resisting structure must:-

a) Be roided it te re-resistance leel secied in te Building Code of Australia; and

b) Have all openings protected with doors, windows, shutters, panels or other means rated to provide the required reresistance level.

MAintenAnce cHecKs

It is recommended that the relevant building surveyor should require an annual inspection o these structures. The owner maydelegate this unction to another person or body where necessary or appropriate.

To ensure the integrity and saety o re-resisting structures, inspections should ensure:-

a) No unauthorised penetration or attachment.

b) Proper operation o devices protecting openings.

c) No damage has occurred.

MAintenAnce recorDs

The ollowing inormation must be recorded:-

a) Te dates te tree-montly and yearly insections ere carried out; and

b) Te name of te erson conducting te insections; and

c) Any roblems identied in te insection; and

d) Actions taen to rectify roblems identied; and

e) Date te rectication occurred; and

) Signature o the person conducting the inspection.

A log sheet to record this inormation is provided in Appendix C o this manual.

4.6 IRE-RESIST ING STRuCTuRESBCA 1990: Section C BCA 1996: Cp1, Cp2, Cp6

(Section 6)

Page 186: Essential Safety Maintenance Manual

8/3/2019 Essential Safety Maintenance Manual

http://slidepdf.com/reader/full/essential-safety-maintenance-manual 186/290

E S S E N T I A L S A F E T Y M E A S U R E S M A I N T E N A N C E M A N U A L • B U I L D I N G C O M M I S S I O N

S E C T I O N 4 / P A G E 9

pUrpose

To provide protection to openings by maintaining the integrity o re-separation and compartmentation.

reqUireMents of tHe eqUipMent

ire shtters

Must be designed, constructed and installed as identical to a tested and approved prototype.•A steel sutter must comly it AS 1905.2; and

Must oerate automatically and close at a rate of beteen 0.25 and 0.3 metres er second; and•

Must maintain their integrity or the time period as required by the• Building Code of Australia.

ire inos

Must be designed, constructed and installed to achieve the required re-resistance level and may be an automatic closingor permanent closure.

MetHoD of operAtion

Fire shutters and openable re windows are operated automatically by a heat-sensing device incorporated in their design.

MAintenAnce cHecKs

It is recommended that the relevant building surveyor should require an annual inspection.

The owner may delegate this unction to another person or body where necessary or appropriate.

MAintenAnce recorDs

The ollowing inormation must be recorded:-

a) Te montly cec to ensure no obstruction to tese items; and

b) Te annual insection to ensure satisfactory oeration of tese items; and

c) Te date te cecs and insections ere carried out; and

d) Te name and signature of te erson carrying out te cecs and insections; and

e) Any problems identied during the checks or inspections.

A log sheet to record this inormation is provided in Appendix C o this manual.

4.7 IRE SHuTTERS ANd IRE wINdOwSBCA 1990: Sec C3.4 BCA 1996: Cp8 (Sec C3.4) Reerence: AS 1530.4

Page 187: Essential Safety Maintenance Manual

8/3/2019 Essential Safety Maintenance Manual

http://slidepdf.com/reader/full/essential-safety-maintenance-manual 187/290

E S S E N T I A L S A F E T Y M E A S U R E S M A I N T E N A N C E M A N U A L • B U I L D I N G C O M M I S S I O N

S E C T I O N 4 / P A G E 1 0

pUrpose

Warning systems, associated with passenger lits, are installed to warn occupants o the use o lit during a re.

reqUireMents of tHe eqUipMent

A passenger lit must:-

a) Comply with the Building Code of Australia (BCA) E3.3; and

b) hae a arning sign saying ‘Do not use lifts if tere is a re’ installed on eery oor, near te call button for apassenger lit or group o lits, throughout the building.

Emergency lits (where required) must:-

a) Comply with the BCA E3.4 and AS 1735.2; and

b) Be roided it a notice in te lift car stating te safe oring load of te lift; and

c) Be roided it a to-ay oice communication system (e.g. one), inside te car; and

d) Be roided it an information anel, giing details of te building address and lift number, and oeratinginstructions for te one; and

e) Be roided it an audible alarm, oerated from inside te lift car, and sounding at a location outside te lift.

MAintenAnce cHecKs

Maintenance o these items should be included in the periodic maintenance o lits, required under the Occupational Health& Safety (Plant) Regulations 1995. It is a requirement under AS 1735.2 that a yearly inspection be carried out. This annualinspection must be carried out by the owner o the building. The owner may delegate this unction to another person or bodywhere necessary or appropriate. Included in this inspection should be a review o the maintenance records complied with bythe maintenance contractor, which should be made available to the owner.

MAintenAnce recorDs

A record o the yearly inspection must be kept including:-

a) Dates te yearly insections occurred; and

b) Name of te erson conducting te insections; and

c) Any roblems identied in te insection; and

d) Actions taen to rectify roblems identied; and

e) Date te rectication occurred; and

) Signature o the person conducting the inspection.

A log sheet to record this inormation is provided in Appendix C o this manual.

4.8 l ITS – wARNING SySTEmSBCA 1990: part E3 BCA 1996: Ep3.3 (part E3)Reerence: AS 1735.2

Oh&S (plant) Regs 1995

 

Page 188: Essential Safety Maintenance Manual

8/3/2019 Essential Safety Maintenance Manual

http://slidepdf.com/reader/full/essential-safety-maintenance-manual 188/290

E S S E N T I A L S A F E T Y M E A S U R E S M A I N T E N A N C E M A N U A L • B U I L D I N G C O M M I S S I O N

S E C T I O N 4 / P A G E 1 1

pUrpose

Lightweight construction can be used to provide:-

a) A wall with a re-resistance level.

b) A surround or a lit, stair or service shat.

c) A wall bounding a corridor, passageway or ramp.

d) A re-resisting covering or a steel column.

reqUireMents

Where used as:-

a) A wall with a re-resistance level, it must be:-

a. Constructed to roide tat re-resistance leel; and

b. Subjected to and ull the testing and criteria specied in the Building Code of Australia (BCA) Secication C1.8;and

b) A surround or a lit, stair or service shat, or a wall bounding a corridor, passageway or ramp:-

a. It must be subjected to and ull the testing and criteria specied in the BCA, Sec. C1.8; and

c) The re-resisting covering o a steel column:-

a. It must ull the requirements o Section C1.8 o the BCA.

These criteria will be specied and built into the structure during construction.

MAintenAnce cHecKs

It is recommended that the relevant building surveyor should require an annual inspection o this acility. The owner maydelegate this unction to another person or body where necessary or appropriate.

To ensure the integrity o lightweight construction, the ollowing inspection is recommended:-

a) I the structure has a re-resistance level, the inspection should ensure that:-

a. no unauthorised penetrations or attachments have occurred.

b. no physical damage has occurred.

b) I a surround or a shat or a wall bounding a corridor, passageway or ramp:-

a. no unauthorised attachments.

b. no physical damage.

c) I providing re-resisting covering to a steel column:-

a. damage-prevention equipment is in place e.g.: steel cladding or protective barriers.

b. no physical damage.

4.9 l IGHTwEIGHT CONSTRuCTIONBCA 1990: C1.8

Spec C1.8BCA 1996: Cp1, Cp2

(C1.8, Spec C1.8)

Page 189: Essential Safety Maintenance Manual

8/3/2019 Essential Safety Maintenance Manual

http://slidepdf.com/reader/full/essential-safety-maintenance-manual 189/290

E S S E N T I A L S A F E T Y M E A S U R E S M A I N T E N A N C E M A N U A L • B U I L D I N G C O M M I S S I O N

S E C T I O N 4 / P A G E 1 2

MAintenAnce recorDs

The ollowing inormation must be recorded:-

a) Te dates te tree-montly and yearly insections ere carried out; and

b) Te name of te erson conducting te insections; and

c) Any roblems identied in te insections; and

d) Actions taen to rectify roblems identied; and

e) Date tis rectication occurred; and

) Signature o the person conducting the inspection.

A log sheet to record this inormation is provided in Appendix C o this manual.

Page 190: Essential Safety Maintenance Manual

8/3/2019 Essential Safety Maintenance Manual

http://slidepdf.com/reader/full/essential-safety-maintenance-manual 190/290

E S S E N T I A L S A F E T Y M E A S U R E S M A I N T E N A N C E M A N U A L • B U I L D I N G C O M M I S S I O N

S E C T I O N 4 / P A G E 1 3

4.10 PENETRATIONS IN IRE-RATEd STRuCTuRESBCA 1990: part C3BCA 1996: Cp8 (part C3)

pUrpose

Maintain the integrity o a service penetration in a building element that has a re-resistant level.

reqUireMents

Where pipes or services penetrate re-rated elements:-

a) Te oening must be neatly formed, cut or drilled; and

b) Minimum clearances must be maintained rom:-

a. oter serices; and

b. combustible material; and

c) The gap between the pipe or service and the foor, wall or ceiling must be re stopped to a standard and witha material that will maintain the re-resistance level o that element.

Where an item or service such as an electrical switch, outlet or socket is accommodated in an opening or recess in a wall,foor or ceiling:-

a) The opening or recess must not:-

a. be within 300 mm horizontally and 600 mm vertically o any opening on the other side o that wall, or

b. extend beyond hal the thickness o the wall.

b) The gap behind or between the service and the wall, foor or ceiling must be re-stopped.

MAintenAnce cHecKs

It is recommended that the relevant building surveyor should require an annual inspection o this acility. The owner may

delegate this unction to another person or body where necessary or appropriate.

Because of te role of tese enetrations, it is essential tat tey be maintained in a condition tat ill not allo tepassage o re rom one compartment to another.

To ensure this security, visual checks should be carried out ater maintenance work that may have interered with theirintegrity. Any suspect area should be investigated urther.

Any problems identied by these checks and inspections must be rectied as soon as is practicable, by either:-

a) Referral bac to te contractor o carried out te maintenance or; or

b) By aing your on maintenance staff or contractor carry out te necessary reairs.

MAintenAnce recorDs

The ollowing inormation must be recorded:-

a) Te dates te tree-montly, after maintenance and yearly insections ere carried out; and

b) Te name of te erson conducting te insections; and

c) Any roblems identied in te insection; and

d) Actions taen to rectify roblems identied; and

e) Date rectication occurred; and

) Signature o the person conducting the inspection.

A log sheet to record this inormation is provided in Appendix C o this manual.

Page 191: Essential Safety Maintenance Manual

8/3/2019 Essential Safety Maintenance Manual

http://slidepdf.com/reader/full/essential-safety-maintenance-manual 191/290

Page 192: Essential Safety Maintenance Manual

8/3/2019 Essential Safety Maintenance Manual

http://slidepdf.com/reader/full/essential-safety-maintenance-manual 192/290

Mechanicalservices

M e c h  a ni   c  a 

 l   s  er  vi   c  e s 

Page 193: Essential Safety Maintenance Manual

8/3/2019 Essential Safety Maintenance Manual

http://slidepdf.com/reader/full/essential-safety-maintenance-manual 193/290

E S S E N T I A L S A F E T Y M E A S U R E S M A I N T E N A N C E M A N U A L • B U I L D I N G C O M M I S S I O N

S E C T I O N 5 / P A G E 1

5.1 AIR CONDITIONING AND MEChANICAL vENTILATION SYSTEMS 2

5.2 SMOkE CONTROL MEASURES, STAIRwELL pRESSURISATION SYSTEMS, FIRE DAMpERS 6

5.3 SMOkE vENTS 8

m e c h a n i c a S e r i c e s

Page 194: Essential Safety Maintenance Manual

8/3/2019 Essential Safety Maintenance Manual

http://slidepdf.com/reader/full/essential-safety-maintenance-manual 194/290

E S S E N T I A L S A F E T Y M E A S U R E S M A I N T E N A N C E M A N U A L • B U I L D I N G C O M M I S S I O N

S E C T I O N 5 / P A G E 2

5 .1 A IR C ONdIT ION IN G AN d mE CH AN IC AlvENTIlATION SySTEmS BCA 1990: F4.5 

BCA 1996: Fp4.3, Fp 4.4 Part I1

Reerence: AS 1668.2AS/NZS 3666.1 & 2 AS 1668.1 & 2

 

pUrpose

A mechanical air handling system must saeguard occupants rom illness or loss o amenity due to lack o air reshness.

sYsteM AnD eqUipMent

The ollowing systems and equipment are included within the scope o this section:-

Air conditioning systems, including air handling systems and thermal plant systems incorporating condenser•water systems.

Ventilation systems including car park ventilation systems, evaporative cooling systems and general exhaust systems.•

Smoke spill and smoke control systems including stair pressurisation systems.•

kitcen eaust systems.•

System components including re dampers, humidiers, electric duct heaters, etc.•

reqUireMents of tHe eqUipMent

A mechanical air handling system must:-

a) Be installed in accordance it AS 1668.1, 2 and AS/NZS 3666.1 and 2; and

b) Delier adequate amounts of outdoor air and roide sufcient circulation; and

c) Remove contaminants present in the compartment or building to maintain an acceptable air quality.

MetHoD of operAtion

Air conditioning and mechanical ventilation systems modes o operation are typically classied as Normal and Fire Mode:-

Nora moe

Systems operate in this mode to maintain acceptable indoor air quality when the building is occupied. Controls may be eithermanual or automatic.

ire moe

In the event o a re being detected or reported via the re alarm system, air conditioning and mechanical ventilation systemsare required to change over to re mode operation. This mode o operation is explained urther in 5.2 o this section.

An automatic air handling system must be provided with manual override operation.

Automatic operation can be accomplished by:-

Time clock switching.•

Thermostat-controlled switching.•

Atmospheric contaminant monitoring.•

MAintenAnce cHecKs

To ensure the ongoing eciency o an air handling system ater installation, AS 3666.2 sets out minimum maintenancerequirements to ensure health standards are not compromised.

The maintenance o these systems is an ongoing responsibility. This is a requirement o the Regulations and AS 3666.2

Maintenance o an air handling system can be carried out by the owner or he or she may delegate this unction to anotherperson or body where necessary or appropriate.

Page 195: Essential Safety Maintenance Manual

8/3/2019 Essential Safety Maintenance Manual

http://slidepdf.com/reader/full/essential-safety-maintenance-manual 195/290

E S S E N T I A L S A F E T Y M E A S U R E S M A I N T E N A N C E M A N U A L • B U I L D I N G C O M M I S S I O N

S E C T I O N 5 / P A G E 3

To ensure ull compliance with this requirement, a maintenance program must be prepared, including:-

a) All data relevant to the air handling system.

b) A ormal strategy and recording system or eective management o a series o maintenance procedures.

The maintenance program must be implemented in accordance with the inormation and requirements o the maintenanceroutines set down in Section 2 o AS/NZS 3666.2. A ull description o the requirements or the maintenance o air handlingsystems, heated water systems and cooling water systems is included and involves routines to be carried out on a monthly,quarterly, six-monthly and annual basis.

Systems that include devices such as automatic air quality monitoring systems or car park ventilation systems and the likeare covered in Appendix M o AS 1668.2.

Oerating and maintenance manuals must be aailable for all equiment in te system.

otHer MAtters to consiDer – cooLinG toWers

The Building Act 1993 requires the registration of all cooling tower systems and the development of a Risk ManagementPlan (RMP) for each cooling tower system.

The Building (Legionella Risk Management) Regulations 2001 speciy the risks that an RMP must address. The Health(Legionella) Regulations 2001 also prescribe maintenance, testing and associated record-keeping relating to cooling tower andwarm water system that a responsible person must comply with. ’Responsible person‘ means the person who owns, manages,or controls the cooling tower system or warm water system.

Cooing Toer maintenance

The responsible person must ensure that any cooling tower system that the responsible person owns, manages or controls ismaintained and tested in the manner set out in the Health (Legionella) Regulations 2001, unless the system is shut down, oris otherwise not in use, and is completely drained o water.

water ait an treatent

a) Ensure that the water o the cooling tower system is maintained in a clean condition.

b) Ensure that the water o the cooling tower system is continuously treated with:-

a. one or more biocides to effectiely control te grot of micro-organisms, including Legionella; and

b. chemicals or other agents to minimise scale ormation, corrosion and ouling.

disinection, ceaning an re-isinection

a) Ensure that a chlorine-compatible bio-dispersant is added to the recirculating water o the cooling tower system,and that the system is then disinected, cleaned and re-disinected:-

a. immediately prior to initial start-up ollowing commissioning or any shut-down period o greater thanone mont; and

b. at intervals not exceeding six months.

Rotine inspections an testing

a) Ensure that the cooling tower system is inspected at least once each month to check that the system is operatingwithout deects.

b) Ensure that at least once each month a sample o the recirculating water o the cooling tower system is taken and isdelivered to a laboratory or testing and reporting on or heterotrophic colony count.

Page 196: Essential Safety Maintenance Manual

8/3/2019 Essential Safety Maintenance Manual

http://slidepdf.com/reader/full/essential-safety-maintenance-manual 196/290

E S S E N T I A L S A F E T Y M E A S U R E S M A I N T E N A N C E M A N U A L • B U I L D I N G C O M M I S S I O N

S E C T I O N 5 / P A G E 4

High heterotrophic coon cont etecte in cooing toer sste

a) Within 24 hours o receiving a report that any sample o water taken rom the cooling tower system has a

heterotrophic colony count exceeding 100,000 colony orming units per millilitre, the responsible person must ensurethat the ollowing procedure is implemented:-

a. the water o the system must be manually treated with additional quantities o biocide, or with an alternativebiocide; and

b. te ater treatment rogram, toer oeration and maintenance rogram of te system must be reieed; and

c. any aults must be corrected and any changes necessary to prevent a re-occurrence o those aults must beimplemented.

b) Beteen to and four days ensure tat a furter samle of te recirculating ater of te system is taen and isdelivered to a laboratory or testing and reporting on or heterotrophic colony count.

c) Within 24 hours o receiving a report that a sample taken has a heterotrophic colony count exceeding 100,000colony-orming units per millilitre, the responsible person must ensure that the water o the cooling tower system isdisinected, cleaned and re-disinected.

d) Beteen to and four days after te ater as been re-disinfected te resonsible erson must ensure tat a furtersample o the recirculating water o the cooling tower system is taken and is delivered to a laboratory or testing andreporting on or heterotrophic colony count.

e) I, ater ollowing the above procedures, the heterotrophic colony count still exceeds 100,000 colony orming unitsper millilitre, the responsible person must:-

a. ensure that the steps are repeated until the heterotrophic colony count does not exceed 100,000 colony ormingunits er millilitre in to consecutie ater samles taen aroimately one ee aart; or

b. close the cooling tower system until the problem has been remedied.

what i legionea is etecte in cooing toer sste?

a) Within 24 hours o receiving a report that Legionella has been detected in a water sample taken rom a cooling towersystem that is not associated with any suspected or known case o legionellosis, the responsible person must ensurethat the ollowing procedure is implemented:-

a. te cooling toer system must be disinfected; and

b. te ater treatment rogram, toer oeration and maintenance rogram of te system must be reieed; and

c any aults must be corrected and any changes necessary to prevent a re-occurrence o those aults must beimplemented.

b) Beteen to and four days after te disinfection as been comleted, te resonsible erson must ensure tata urther sample o the recirculating water o the system is taken and is delivered to a laboratory or testing andreporting on or Legionella.

c) Within 24 hours o receiving a report that Legionella has been detected in a sample taken the responsible personmust ensure that the water o the cooling tower system is disinected, cleaned and re-disinected.

d) Beteen to and four days after te disinfection as been comleted, te resonsible erson must ensure tata urther sample o the recirculating water o the system is taken and is delivered to a laboratory or testing andreporting on or Legionella.

e) I, Legionella is still detected, the responsible person must:-

a. ensure that the steps above are repeated until:

i. Legionella is not detected in to consecutie ater samles taen aroimately one ee aart; or

ii. close the cooling tower system until the problem has been remedied.

Page 197: Essential Safety Maintenance Manual

8/3/2019 Essential Safety Maintenance Manual

http://slidepdf.com/reader/full/essential-safety-maintenance-manual 197/290

E S S E N T I A L S A F E T Y M E A S U R E S M A I N T E N A N C E M A N U A L • B U I L D I N G C O M M I S S I O N

S E C T I O N 5 / P A G E 5

) I, while ollowing the procedure, o this Part, Legionella is detected in three consecutive water samples taken romte same system, te resonsible erson must notify te Secretary to te Deartment of human Serices of tedetection o the presence o that organism:-

a. immediately by teleone; and

b. by notice in writing within three days o the detection o the organism on the third occasion.

MAintenAnce recorDs

To ensure proper control o the maintenance program, the ollowing documentation should be provided:-

Oerating and maintenance manuals sould be roided for all lant, equiment and systems ic are te subect of tisStandard. Oerating and maintenance manuals sall include at least te folloing:

a) Physical details o the plant, equipment and systems.

b) Recommendations on maintenance, including water treatment maintenance and management.

c) Recommended cleaning, disinection and emergency decontamination procedures.

d) Start-up, operating and shut-down procedures.

e) Particulars o the maintenance management program.

Maintenance records shall contain at least the ollowing inormation:

a) Date, item of lant, equiment or system and nature of serice erformed.

b) Details of defects found and rectication rocedure undertaen.

c) The name o the person or company perorming the service.

Log sheets to record the completion o the our-level maintenance routines are included in Appendix C o this manual.

Log sheets or the testing o cooling towers should be developed in accordance with the requirements o the Health(Legionella) Regulations 2001.

Page 198: Essential Safety Maintenance Manual

8/3/2019 Essential Safety Maintenance Manual

http://slidepdf.com/reader/full/essential-safety-maintenance-manual 198/290

E S S E N T I A L S A F E T Y M E A S U R E S M A I N T E N A N C E M A N U A L • B U I L D I N G C O M M I S S I O N

S E C T I O N 5 / P A G E 6

pUrpose

To ensure, under re and smoke conditions, occupants have sucient time to evacuate

beore the evacuation route becomes untenable.

reqUireMents of tHe eqUipMent

To ull its purpose, the system must:-

a) Be installed in accordance it AS 1668.1 1991 or Secication E2.2; and

b) Resond to automatic eat or smoe-sensing equiment; and

c) Remove smoke rom the re aected area to the outside atmosphere or i required, provide a pressurised atmospherein re isolated exits to prevent entry o smoke rom the re compartment.

MetHoD of operAtion

Air conditioning and mechanical ventilation systems modes o operation are typically classied as Normal and Fire Mode:-

Nora moe

Systems operate in this mode to maintain acceptable indoor air quality when the building is occupied. Controls may beeither manual or automatic.

ire moe

In the event o a re being detected or reported via the re alarm system, air conditioning and mechanical ventilation systemsare required to change over to re mode operation. In re mode the systems provide a purging or zoned smoke controlstrategy. Purging strategies discharge air rom the smoke zone to outside whilst providing adequate relie air. Zoned controlsystems aim to maintain the non-re aected re compartment at a positive pressure relative to the re compartment.

Older systems installed rior to te introduction of AS 1668 may simly sut don on re mode to reduce te roagationo smoke through the building.

An automatic air handling system must be provided with manual override operation.

Automatic operation can be accomplished by:-

Time clock switching•

Thermostat controlled switching•

Atmospheric contaminant monitoring•

The smoke control system must:-

a) Resond to an automatic sensing of a re condition; andb) Automatically activate the appropriate equipment to:-

a. vent smoe to te atmosere; and

b. Introduce outside air to either within the same re aected compartment or to the non-re aectedcomartments; and

c. Deelo a ositie air ressure in te re-isolated stairells (ere required); and

c) Have a manual override acility to enable re-ghting personnel to control the system.

The systematic re-action o the various components in the smoke and air handling systems will have been programmedinto this equipment during the design, installation and commissioning o the equipment into your building. Checks andmaintenance o an air handling system are recommended to be carried out in conjunction with the re alarm system

testing to assure that the systems are correctly interaced.

BCA 1990: part E2 G3.8 Part H1

BCA 1996: Ep2.1, Ep 2.2 (part E2, G3.8)

Reerence: AS 1668.1AS 1851.6

5.2 SmOkE CONTROl mEASuRES, STAIRwEllPRESSuRISATION SySTEmS, IRE dAmPERS

Page 199: Essential Safety Maintenance Manual

8/3/2019 Essential Safety Maintenance Manual

http://slidepdf.com/reader/full/essential-safety-maintenance-manual 199/290

E S S E N T I A L S A F E T Y M E A S U R E S M A I N T E N A N C E M A N U A L • B U I L D I N G C O M M I S S I O N

S E C T I O N 5 / P A G E 7

MAintenAnce cHecKs

It is recommended that the relevant building surveyor should require that maintenance and inspection o smoke control

measures and stairwell pressurisation measures be carried out monthly to AS 1851.6 Level 1 routines. It should be notedthat the results o a Level 1 routine may initiate a urther three levels o routine maintenance requirements. The owner maydelegate these unctions to another person or body where necessary or appropriate.

To ensure ull compliance with this requirement, a maintenance program must be prepared, including:-

a) All data releant to te smoe control system; and

b) A ormal strategy and recording system or eective management o a series o maintenance procedures.

Ipeentation

The maintenance program must be implemented in accordance with the inormation and requirements o the maintenanceroutines set down in Section 3 o AS 1851.6. Any ollow-up action must be implemented as required in Section 2 othat Standard.

MAintenAnce recorDs

Maintenance records should contain the ollowing inormation:

a) Date, item of lant, equiment or system and nature of serice erformed; and

b) Details of defects found and rectication rocedures undertaen; and

c) The name o the person or company perorming the service.

AS 1851.6 also requires the provision o operating and maintenance manuals, a maintenance schedule, a plant register anda plant history record. Further details or all the inormation in this section are available in AS 1851.6 Sections 2, 3 and 4.

Log sheets to record the completion o the maintenance routines specied in AS 1851.6 are included in Appendix C

o this manual.

Page 200: Essential Safety Maintenance Manual

8/3/2019 Essential Safety Maintenance Manual

http://slidepdf.com/reader/full/essential-safety-maintenance-manual 200/290

E S S E N T I A L S A F E T Y M E A S U R E S M A I N T E N A N C E M A N U A L • B U I L D I N G C O M M I S S I O N

S E C T I O N 5 / P A G E 8

pUrpose

Smoke and heat vents are installed to assist the discharge o smoke and heat

generated by a fre.

reqUireMents of tHe eqUipMent

A smoke venting system is made up o the ollowing components:-

a) Vents and their operating mechanism.

b) Draugt curtains.

c) Inlet ventilation.

This system must be designed and installed in accordance with AS 2665.

MetHoD of operAtion

The system:-

a) Contains the smoke/heat within the connes o the smoke curtains.

b) Activates the vents, using the rising temperature, releasing the trapped smoke/heat to atmosphere.

c) Assists the ventilation process by introducing air to replace the rising smoke/heat column.

Operation of the system must be automatic, with a manual control in addition.

MAintenAnce cHecKs

It is recommended that the relevant building surveyor should require maintenance to be carried out at least every

six months to AS 1851.5. The owner may delegate this unction to another person or body where necessary orappropriate.

Periodic testing and inspection is recommended by AS 1851.5 to be implemented:-

Six-monthly•

Yearly•

Ater maintenance•

MAintenAnce recorDs

Records must be developed and maintained to record the ollowing:-

a) Date of te insection, test or maintenance; and

b) Name of te erson carrying tis out; and

c) Details of any faults detected; and

d) Action taen to rectify any faults detected; and

e) Date on ic any faults ere rectied.

Log sheets or this purpose are provided in Appendix C o this manual.

BCA 1990: part E2.4 G3.8 H1.2Spec H1.2

BCA 1996: Ep2.1, Ep 2.2 (part E2, G3.8)

Reerence: AS 2665AS 1851.5

5.3 SmOkE vENTS

Page 201: Essential Safety Maintenance Manual

8/3/2019 Essential Safety Maintenance Manual

http://slidepdf.com/reader/full/essential-safety-maintenance-manual 201/290

Page 202: Essential Safety Maintenance Manual

8/3/2019 Essential Safety Maintenance Manual

http://slidepdf.com/reader/full/essential-safety-maintenance-manual 202/290

E S S E N T I A L S A F E T Y M E A S U R E S M A I N T E N A N C E M A N U A L • B U I L D I N G C O M M I S S I O N

P A R T 3 / P A G E 1

Part 3 – Buildings constructed before 1 July 1994

The Building Regulations 2006 (the Regulations) require that owners o buildings built prior to 1 July 1994 maintain theessential saety measures installed within the building.

Any essential saety measure in Class 1b, 2, 3, 5, 6, 7, 8 and 9 buildings and places o public entertainment constructed beore1 July 1994 must be maintained by the owner to a working condition that enables them to ull their purpose and meet theexpectations o inspecting authorities.

what essentia saet easres are reire to e aintaine?

Part 12, Subdivision 2 o the Regulations does not explain or dene the terms ‘item o equipment’, ‘orm o construction’or ‘saety strategies’. However, it is expected that building owners will engage suitably qualied and competent personsto establish the essential saety measures and outline a level o maintenance. In some instances this may be a dicult taskand may involve detailed inspection and research o historical documentation to establish the essential saety measureand requency and type o maintenance.

Essential saety measures in this Part means any measure required or the saety o persons using a building or place o publicentertainment. It includes an item o equipment, orm o construction or saety strategies.

Essential saety measures in a building constructed prior to 1 July 1994 could be, but are not limited to:-

Air conditioning systems•

Emergency lits•

Emergency lighting•

Emergency power supply•

Emergency warning and•intercommunication systems

Exit doors•

Exit signs•

Fire brigade connections•

Fire control centres•

Fire control panels•

Fire curtains•

Fire dampers•

Fire detectors and alarm systems•

Fire doors•

Fire extinguishers (portable)•

• Fire ydrants

• Fire indices for materials

• Fire-isolated lift safts

• Fire-isolated assageays

• Fire-isolated rams

• Fire-isolated stairs

• Fire mains

• Fire-rotectie coerings

• Fire-rated access anels

• Fire-rated control oints

• Fire-rated materials alied tobuilding elements

• Fire-resisting safts

• Fire-resisting structures

• Fire sutters

• Fire indos

• Ligteigt construction

• Mecanical entilation systems

• pats of trael to eits

• penetrations in re-rated structures

• Smoe alarms

• Smoe control measures

• Smoe doors

• Smoe ents

• Srinler systems

• Stairell ressurisation systems

• Static ater storage

• veicular access for large isolatedbuildings

• warning systems associatedwith lits

• Any oter re safety matter icis required by the  Act or Regulations 

and the relevant building surveyordesignates on the occupancy permitor otherwise determines in writing

The Regulations require that the owner must ensure that an essential saety measure:-

a) Is maintained in a state ic enables te essential safety measure to full its urose; and

b) Must not be removed rom its approved location except or the purposes o providing maintenance.

Page 203: Essential Safety Maintenance Manual

8/3/2019 Essential Safety Maintenance Manual

http://slidepdf.com/reader/full/essential-safety-maintenance-manual 203/290

E S S E N T I A L S A F E T Y M E A S U R E S M A I N T E N A N C E M A N U A L • B U I L D I N G C O M M I S S I O N

P A R T 3 / P A G E 2

what sho e the ee o aintenance?

I there was no specic standard o maintenance in orce at the time, then any relevant Australian Standards available at the

time may be used as a guide to the level o adequate maintenance. I there was no relevant Australian Standard in existenceat the time o installation, then the rst published edition o a relevant Standard may be used as a guide to what may beadequate maintenance.

The level o maintenance expected in the uture by inspecting authorities should not be greater than that required at the timethe initial maintenance requirement was determined or that existing essential saety measure.

do I nee to pgrae essentia saet easre?

The Regulations do not require the automatic upgrade o systems in buildings where regulations change rom time-to-time.The essential saety measure must be maintained by the owner to a working condition that enables them to ull theirpurpose.

The enorcement provisions o Part 8 o the Act provide or a municipal building surveyor or private building surveyorwhere appointed, to review any risk to the lie, saety, or health o any occupant in a building. As part o the enorcementprocess consideration could be given to upgrading the essential saety measures to current standards and practices.

Cooing Toers

The Building (Legionella) Act 2000 requires all cooling toer systems in victoria to be registered it te Building Commissionto help track potential sources o Legionnaires’ disease. The Building Act 1993 requires the registration o all cooling towersystems and the development o a Risk Management Plan (RMP) or each cooling tower system.

The Building (Legionella Risk Management) Regulations 2001 speciy the risks that an RMP must address. The Health(Legionella) Regulations 2001 also prescribe maintenance, testing and associated record-keeping relating to cooling tower andwarm water systems that a responsible person must comply with.

The owner o the land on which a cooling tower system is located is required to register and renew the registration o thatsystem on an annual basis. Once on te register, te alication for reneal of registration ill be sent to te oner before

their current registration expires each year.

maintenance an inspection recors

For pre-1994 buildings, the Regulations do not speciy a level o documentation to be kept by the owner. It is recommendedthat records o maintenance should be completed and made available to the building owner or agent at the time o conductingthe system and equipment maintenance.

It is recommended that records should contain the ollowing inormation:

a) Record reerence.

b) Name o building or site.

c) Address o building or site.

d) Date of maintenance/insection.

e) System or equipment identication and location (Possibly a location plan).

) Frequency o maintenance activity undertaken.

g) Defects identied.

h) Name o property owner or the agent.

i) Name and signature o the service person.

  ) Date te record as comleted.

or o recors

I a person, such as a building surveyor, has been used to inspect and nominate essential saety measures, that person shouldprovide advice as to the level o record-keeping required to satisy the level and requency o maintenance. As a minimum, itshould include the inormation provided above.

Page 204: Essential Safety Maintenance Manual

8/3/2019 Essential Safety Maintenance Manual

http://slidepdf.com/reader/full/essential-safety-maintenance-manual 204/290

E S S E N T I A L S A F E T Y M E A S U R E S M A I N T E N A N C E M A N U A L • B U I L D I N G C O M M I S S I O N

P A R T 3 / P A G E 3

Appendix C provides examples o log sheets available or 1994 to 2004 buildings. Although these have been developed orbuildings built ater 1 July 1994, the inormation contained within Appendix C Log Sheets can be used by owners to developlog sheets or the pre-1994 buildings.

Maintenance records may be electronically-based. Hard copy records should be kept on site and be available at all times.Technology in regard to the preparation o maintenance records has advanced considerably in recent years with the advent opurpose-designed sotware. As a minimum, a hard copy o records o maintenance are to be made available to organisations,such as regulators, re authorities, insurance surveyors, re auditors, etc., at all times. However, the hard copy records requiredmay be prepared utilising electronic recording systems and this manual acknowledges such technology is designed to deliveran accurate, accountable, consistent and timely level o service.

Maintenance records can be in the orm o maintenance record tags (in the case o hydrant landing valves, hose reels, portableand wheeled re extinguishers and re blankets), or log books (in the case o sprinkler, pumpset, re hydrant, detection, smokeand heat alarm, re alarm monitoring, sound, intercom, gaseous, aerosol, water mist, passive re and smoke and HVAC andevacuation systems).

The use o maintenance record tags or labels shall not preclude the need or a separate maintenance record system.

Where log books are used, they shall have sequentially numbered pages in triplicate. Provision shall be made or the signatureso the building owner, occupier or agent, and the service person. The required distribution o copies shall be printed on eachpage as ollows:

a) Original ............ ............ ............ ............ ............ ............ ............ ............oner/occuier/agent

b) Dulicate ............ ............ ............ ............ ............ ............ ............ ..........serice erson

c) Triplicate ............ ............ ............ ............ ............ ............ ............ ...........retain in book

Preparation o anna report

An owner o a building or a place o public entertainment must ensure that an essential saety measures report is prepared inaccordance with Regulation 1215 in respect o any essential saety measure required to be provided in relation to that buildingor place under the  Act or these Regulations or any corresponding Act or Regulations.

In the case o a rst report, it must be prepared beore the 13 June 2009, and in the case o each subsequent report, beoreeach anniversary o 13 June 2009.

A copy o the annual report is provided in Appendix A o this manual.

Page 205: Essential Safety Maintenance Manual

8/3/2019 Essential Safety Maintenance Manual

http://slidepdf.com/reader/full/essential-safety-maintenance-manual 205/290

Page 206: Essential Safety Maintenance Manual

8/3/2019 Essential Safety Maintenance Manual

http://slidepdf.com/reader/full/essential-safety-maintenance-manual 206/290

A   p  p en d  i     c  e s 

Appendices

Appendix A – Annual Essential SafetyMeasures Report

Appendix B – Building Regulations 2006

Appendix C – Sample Log Sheets

Page 207: Essential Safety Maintenance Manual

8/3/2019 Essential Safety Maintenance Manual

http://slidepdf.com/reader/full/essential-safety-maintenance-manual 207/290

E S S E N T I A L S A F E T Y M E A S U R E S M A I N T E N A N C E M A N U A L • B U I L D I N G C O M M I S S I O N

A P P E N D I X A / P A G E 1

A p p e n d i x A - A n n u a l E s s e n t i a l S a e t y M e a s u r e s R e p o r t

Building Act 1993

Building Regulations 2006

REGULATION 1209 & 1215: ANNUAL ESSENTIAL SAFETY MEASURES REPORT1

Property Address:

Building/s or part o building:

Classifcation o building/s or part o building:

PART A – Post July 1994 building

This part of report is in relation to occupancy permit no: (insert no) issued: (insert date) 

or maintenance determination dated: (insert date) and is required to be prepared before each anniversary of the date

of that occupancy permit or maintenance determination.

Maintenance personnel details

The following personnel carried out maintenance on the essential safety measures in this building during the preceding12 months.

Essential safety measure Name Address

Page 208: Essential Safety Maintenance Manual

8/3/2019 Essential Safety Maintenance Manual

http://slidepdf.com/reader/full/essential-safety-maintenance-manual 208/290

E S S E N T I A L S A F E T Y M E A S U R E S M A I N T E N A N C E M A N U A L • B U I L D I N G C O M M I S S I O N

A P P E N D I X A / P A G E 2

PART b -  All Buildings (pre and post July 1994 Buildings)

1) detais o an inspection report proie ner section 227E2 o the biing Act 1993; an

2) Copiance

I hereby state that I have*/the owner has* taken all reasonable steps to ensure that—* Delete as applicable

(i) eac essential safety measure is oerating at te required leel of erformance or to full its urose; and

(ii) where applicable each essential saety measure has been maintained in accordance with the occupancy permit ormaintenance determination and ill full its urose; and

(iii) since the last annual essential saety measures report there have been no penetrations to required re-resistingconstruction, smoke curtains and the like in the building, other than those or which a building permit has beenissued; and

(iv) since the last annual essential saety measures report there have been no changes to materials or assemblies thatmust comly it articular re azard roerties, oter tan tose for ic a building ermit as been issued; and

(v) the inormation contained in this report is correct.

Signatre

Oner/agent of oner*3

* Delete if inapplicable

Signed: Date:

Notes

1. The owner must ensure that this annual essential saety measures report and records o maintenance checks, serviceand repair work are available on the premises or inspection by the municipal building surveyor or chie ocer ater24 hours notice. The penalty or non-compliance is a maximum o 10 penalty units.

2. Section 227E o the Building Act 1993 provides the power or the chie ocer and municipal building surveyor toinspect essential saety measures.

3. Under section 240 and 248(1) o the Building Act 1993 an agent o the owner must have written authority rom theowner to act as their agent. Also note the general rules o “Agency” also apply.

Page 209: Essential Safety Maintenance Manual

8/3/2019 Essential Safety Maintenance Manual

http://slidepdf.com/reader/full/essential-safety-maintenance-manual 209/290

E S S E N T I A L S A F E T Y M E A S U R E S M A I N T E N A N C E M A N U A L • B U I L D I N G C O M M I S S I O N

A P P E N D I X B / P A G E 1

PART 12 - mAINTENA NCE O buIldI NGS ANdPlACES O Publ IC ENTERTAINmENT

diision 1- maintenance o Essentia Saet measres

Siision 1 - maintenance o Essentia Saet measres in biings an Paces o Pic Entertainent

1201. Appication o this Siision

(1) Subject to sub-regulation (2), this Subdivision applies to -

(a) a Class 1b, 2, 3, 5, 6, 7, 8 or 9 building; and

(b) a Class 4 art of a building; and

(c) a place o public entertainment.

(2) This Subdivision does not apply to a smoke alarm installed in a sole-occupancy unit in a Class 1b or 2 building or a Class 4

part o a building.

1202. defnitions

In this Subdivision -

“essentia saet easre” means -

(a) any o the ollowing items required by or under the Act or these Regulations to be provided in relation to a buildingor a place o public entertainment -

(i) an item listed in Tables I1.1 to I1.11 of volume One of te BCA, ecet te item in Table I1.4 relating to articialligting;

(ii) an item listed in clause I1.2 of volume One of te BCA; or

(b) any other item that is required by or under the Act or these Regulations to be provided in relation to a building orplace o public entertainment or the saety o persons in the event o re and that is designated by the relevantbuilding sureyor as an essential safety measure; or

(c) any oter item tat is an essential safety measure itin te meaning of Diision 1 of part 12 of te Building(Interim) Regulations 2005 as in force before teir reocation;

“aintenance eterination” means a determination made by a relevant building surveyor under -

(a) regulation 1204; or

(b) regulation 1204 of te Building (Interim) Regulations 2005 as in force before teir reocation; or

(c) regulation 11.4 of te Building Regulations 1994 as in force before teir reocation;

“aintenance schee” in relation to a building or a place o public entertainment means a maintenance schedule preparedby a municipal building surveyor or a private building surveyor under regulation 1206 as updated rom time to time under thatregulation.

1203. maintenance reireents or essentia saet easres hen occpanc perit reire

(1) An occupancy permit issued in respect o a building or place o public entertainment must include a condition which -

(a) lists all te essential safety measures ertaining to tat building or lace of ublic entertainment; and (b)species or each essential saety measure listed, the level o perormance determined by the relevant buildingsurveyor to enable the essential saety measure to ull its purpose.

(2) In determining the level o perormance o an essential saety measure, the relevant building surveyor must speciy theprovision o the building regulations with which the installation and operation o the essential saety measure is to complyand the requency and type o maintenance required.

(3) In this regulation “proision o the iing regations” has the same meaning as in section 160 o the Act.

A p p e n i b - b i i n g R e g a t i o n s 2 0 0 6 P a r t 1 2

Page 210: Essential Safety Maintenance Manual

8/3/2019 Essential Safety Maintenance Manual

http://slidepdf.com/reader/full/essential-safety-maintenance-manual 210/290

E S S E N T I A L S A F E T Y M E A S U R E S M A I N T E N A N C E M A N U A L • B U I L D I N G C O M M I S S I O N

A P P E N D I X B / P A G E 2

1204. maintenance reireents o essentia saet easres in other circstances

(1) I an essential saety measure is provided in a building or place o public entertainment as a consequence o an emergency

order or a building order or the carrying out o building work where an occupancy permit is not required to be issued therelevant building surveyor must determine -

(a) te leel of erformance required to enable te essential safety measure to full its urose; and

(b) the requency and type o maintenance required.

(2) A determination under sub-regulation (1) must -

(a) be in riting; and

(b) be given to the owner o the building or place o public entertainment without delay ater it is made.

1205. Oner st cop ith aintenance eterination

The owner o a building or place o public entertainment must comply with a maintenance determination in relation to that

building or place.

Penalty: 10 penalty units.

1206. biing sreor a create or pate a aintenance schee

(1) A municipal building surveyor or a private building surveyor may, on the application o the owner o a building or place opublic entertainment, create a consolidated list o essential saety measures and the maintenance requirements relating tothose essential saety measures -

(a) that are the subject o a condition imposed on an occupancy permit issued in respect o the building or place under -

(i) regulation 1203(1); or

(ii) regulation 1203(1) of te Building (Interim) Regulations 2005 as in force before teir reocation; or

(iii) regulation 11.3(1) of te Building Regulations 1994 as in force before teir reocation; or

(b) that are the subject o a maintenance determination in respect o the building or place.

(2) In creating a maintenance schedule or the rst time in respect o a building or a place o public entertainment, amunicipal building surveyor or a private building surveyor must ensure that -

(a) any essential saety measure reerred to under sub-regulation (1) that exists in the building or place o publicentertainment at the time o creation o the schedule is listed in the schedule along with any maintenancerequirement tat relates to it; and

(b) the essential saety measures and related maintenance requirements are listed in chronological order in the scheduleaccording to the date o the issue o the occupancy permit or the date o making o the maintenance determinationthat relates to each o those essential saety measures.

(3) A municipal building surveyor or a private building surveyor may, on the application o the owner o a building or place opublic entertainment, update a maintenance schedule prepared in respect o the building or place by adding any additionalessential saety measures and related maintenance requirements required to be provided in relation to the building or placeater the date o the creation o the schedule.

(4) Any additional essential saety measures added to a maintenance schedule under sub-regulation (3) must be listed inchronological order in the schedule according to the date o issue o the relevant occupancy permit or the date o makingo the maintenance determination (as the case may be).

1207. maintenance schee an aintenance eterination to e aaiae or inspection

An owner o a building or place o public entertainment must ensure that a copy o any current maintenance scheduleprepared in respect o the building or place, and any current maintenance determination made in respect o the building orplace relating to an essential saety measure that is not listed in a maintenance schedule, is available at that building or place

or inspection by the municipal building surveyor or chie ocer at any time on request ater 24 hours notice.

Penalty: 10 penalty units

Page 211: Essential Safety Maintenance Manual

8/3/2019 Essential Safety Maintenance Manual

http://slidepdf.com/reader/full/essential-safety-maintenance-manual 211/290

E S S E N T I A L S A F E T Y M E A S U R E S M A I N T E N A N C E M A N U A L • B U I L D I N G C O M M I S S I O N

A P P E N D I X B / P A G E 3

1208. Oner st prepare anna report

(1) An owner o a building or place o public entertainment, in respect o which a condition on an occupancy permit lists an

essential saety measure or a maintenance determination has been made, must ensure that an annual essential saetymeasures report is prepared in accordance with regulation 1209 beore each anniversary o the relevant anniversary date.

Penalty: 10 penalty units.

(2) In this regulation “reeant anniersar ate” means -

(a) te date of issue of te occuancy ermit or te date of maing of te maintenance determination; or

(b) i more than one occupancy permit or maintenance determination or both is issued or made, the earliest date oissue or making o those documents.

Note: Regulation 2001 deems an annual essential saety measures report prepared in accordance with regulation 1209 ote Building (Interim) Regulations 2005 before 13 june 2006 to be an annual essential safety measures reort reared inaccordance with this regulation.

1209. Contents an or o anna report

The annual essential saety measures report or the purposes o regulation 1208 must -

(a) be in a form aroed by te Commission; and

(b) be signed by te oner or an agent of te oner; and

(c) secify te address of te building or lace of ublic entertainment tat it relates to; and

(d) include the details o any inspection report made under section 227E o the Act in respect o each essential saetymeasure; and

(e) include a statement that the owner or an agent o the owner has taken all reasonable steps to ensure that—

(i) each essential saety measure is operating at the required level o perormance and has been maintained inaccordance it te releant occuancy ermit or maintenance determination and ill full its urose; and

(ii) since the last annual essential saety measures report, there have been no penetrations to required re-resistingconstruction, smoke curtains and the like in the building or place, other than those or which a building permitas been issued; and

(iii) since the last annual essential saety measures report, there have been no changes to materials or assemblies thatmust comly it articular re azard roerties, oter tan tose for ic a building ermit as been issued;and

(iv) the inormation contained in the report is correct.

1210. Anna reports a e coine

I an annual essential saety measures report is required under regulation 1208 and under regulation 1214 in relation to thesame building or place o public entertainment, the reports may be combined into one consolidated report.

1211. Anna reports an recors to e ae aaiae

An owner o a building or place o public entertainment must ensure that any annual essential saety measures report requiredto be prepared under regulation 1208 and records o all maintenance checks and any service or repair work carried out to anyessential saety measure are available at the building or place or inspection by the municipal building surveyor or chie ocerat any time on request ater 24 hours notice.

Penalty: 10 penalty units.

Page 212: Essential Safety Maintenance Manual

8/3/2019 Essential Safety Maintenance Manual

http://slidepdf.com/reader/full/essential-safety-maintenance-manual 212/290

E S S E N T I A L S A F E T Y M E A S U R E S M A I N T E N A N C E M A N U A L • B U I L D I N G C O M M I S S I O N

A P P E N D I X B / P A G E 4

sUbDivision 2 - MAintenAnce of essentiAL sAfetY MeAsUres in bUiLDinGs AnD pLAces of

pUbLic entertAinMent constrUcteD before 1 JULY 1994

1212. Appication o Siision

This Subdivision applies to all Class 1b, 2, 3, 5, 6, 7, 8 and 9 buildings and places o public entertainment constructed beore 1 July 1994.

1213. defnition o essentia saet easre in this Siision

In this Subdivision, “essentia saet easre” means any measure (including an item o equipment, orm o construction orsaety strategy) required or the saety o persons using a building or place o public entertainment.

1214. Oner o iing or pace constrcte eore 1 J 1994 st prepare anna report

(1) An owner o a building or place o public entertainment must ensure that an annual essential saety measures report isprepared in accordance with regulation 1215 in respect o any essential saety measure required to be provided in relationto that building or place under the Act or these Regulations or any corresponding previous Act or regulations -

(a) in te case of te rst reort, before 13 june 2009; and

(b) in the case o each subsequent report, beore each anniversary o 13 June 2009.

Penalty: 10 penalty units.

(2) Sub-regulation (1) does not apply to any essential saety measure in respect o which an annual report is required to bereared under Subdiision 1 of tis Diision.

1215. Contents an or o anna report or iing or pace constrcte eore 1 J 1994

The annual essential saety measures report or the purposes o regulation 1214 must -

(a) be in a form aroed by te Commission; and

(b) be signed by te oner or an agent of te oner; and

(c) secify te address of te building or lace of ublic entertainment tat it relates to; and

(d) include the details o any inspection report made under section 227E o the Act in respect o each essential saetymeasure; and

(e) include a statement that the owner or an agent o the owner has taken all reasonable steps to ensure that eachessential saety measure -

(i) is oerating and as been maintained in a state tat enables te essential safety measure to full its urose; and

(ii) since the last annual essential saety measures report, there have been no penetrations to required re-resistingconstruction, smoke curtains and the like in the building or place, other than those or which a building permit has

been issued; and

(iii) since the last annual essential saety measures report, there have been no changes to materials or assemblies thatmust comply with particular re hazard properties, other than those or which a building permit has beenissued; and

(iv) the inormation contained in the report is correct.

1216. Anna reports an recors to e ae aaiae oners o iings constrcteeore 1 J 1994

(1) An owner o a building or place o public entertainment must ensure that any annual essential saety measures reportrequired to be prepared under regulation 1214 and records o all maintenance checks and any service or repair work carriedout to any essential saety measure are available at the building or place or inspection by the municipal building surveyor

or chie ocer at any time on request ater 24 hours notice.Penalty: 10 penalty units.

(2) Sub-regulation (1) does not apply until 13 June 2009.

Page 213: Essential Safety Maintenance Manual

8/3/2019 Essential Safety Maintenance Manual

http://slidepdf.com/reader/full/essential-safety-maintenance-manual 213/290

E S S E N T I A L S A F E T Y M E A S U R E S M A I N T E N A N C E M A N U A L • B U I L D I N G C O M M I S S I O N

A P P E N D I X B / P A G E 5

1217. maintenance responsiiit o oner o iing or pace constrcte eore 1 J 1994

The owner o a building or place o public entertainment must ensure that any essential saety measure required to be

provided in relation to that building or place under the Act or these Regulations or any corresponding previous Act orregulations -

(a) is maintained in a state ic enables te essential safety measure to full its urose; and

(b) is not removed rom its approved location except—

(i) for te urose of maintenance; or

(ii) in accordance with these Regulations.

Penalty: 10 penalty units.

sUbDivision 3 - MAintenAnce of exits AnD pAtHs of trAveL reLAtinG to bUiLDinGs or pLAces

of pUbLic entertAinMent

1218. maintenance o eits occpiers o iings or paces o pic entertainent

The occupier o a Class 1b, 2, 3, 5, 6, 7, 8 or 9 building or a place o public entertainment must ensure that -

(a) all eits; and

(b) any ats of trael to eits; and

(c) any paths o travel on the allotment rom exits to a road - required to be provided in relation to that building or placeare maintained in an ecient condition and kept readily accessible, unctional and clear o obstruction so that egressrom the building or place is maintained.

Penalty: 10 penalty units.

Division 2 - sWiMMinG pooL AnD spA MAintenAnce AnD operAtion

1219. Appication o this diision

Tis Diision alies to a simming ool or sa tat is aurtenant to a Class 1, 2, 3 or 10 building or a Class 4 art of” a building.

1220. Siing poo an spa aintenance an operation

(1) The occupier o an allotment or building containing a swimming pool or spa must take all reasonable steps to ensure thatany ence or other barrier, door, gate, lock, latch, catch, bolt or fy screen restricting access to the swimming pool or spa ismaintained and operating eectively at all times.

Penalty: 50 penalty units.(2) The occupier o an allotment or building containing a swimming pool or spa must take all reasonable steps to ensure that

any gate or door orming part o a swimming pool or spa barrier or ence that provides access to the swimming pool orspa is in the closed position except when a person is in the act o entering or leaving the part o the allotment or buildingcontaining the swimming pool or spa.

Penalty: 50 penalty units.

(3) A person who enters or leaves the part o an allotment or building containing a swimming pool or spa must ensure thatany gate or door orming part o the swimming pool or spa barrier or ence that provides access to the swimming pool orspa is in the closed position at all times, except when that person or another person is in the act o entering or leaving thatpart o the allotment or building.

Penalty: 50 penalty units.

Page 214: Essential Safety Maintenance Manual

8/3/2019 Essential Safety Maintenance Manual

http://slidepdf.com/reader/full/essential-safety-maintenance-manual 214/290

Page 215: Essential Safety Maintenance Manual

8/3/2019 Essential Safety Maintenance Manual

http://slidepdf.com/reader/full/essential-safety-maintenance-manual 215/290

E S S E N T I A L S A F E T Y M E A S U R E S M A I N T E N A N C E M A N U A L • B U I L D I N G C O M M I S S I O N

A P P E N D I X C / P A G E 1

A p p e n i C - P a r t 1 - S a p e l o g S h e e t s

Page 216: Essential Safety Maintenance Manual

8/3/2019 Essential Safety Maintenance Manual

http://slidepdf.com/reader/full/essential-safety-maintenance-manual 216/290

E S S E N T I A L S A F E T Y M E A S U R E S M A I N T E N A N C E M A N U A L • B U I L D I N G C O M M I S S I O N

   N  a

  m  e  o      b  u   i   l   d   i  n   g  :

   N  a  m  e  o     o  w  n  e  r  :

   A   d   d  r  e  s  s  :

   L  e  v

  e   l  o     p  e  r     o  r  m  a  n  c  e  a  n   d     r  e  q  u  e  n  c  y  o     m  a   i  n   t  e  n  a  n  c  e    (  a  s  s  p  e  c   i     e   d  o  n  o  c  c  u  p  a  n  c  y  p  e  r  m   i   t    )  :

   D  a   t  e  o   f

   i  n  s  p  e  c   t   i  o  n

   N  a  m  e  a  n   d  a   d   d  r  e  s  s  o     p  e

  r  s  o  n

  c  o  n   d  u  c   t   i  n   g   i  n  s  p  e  c   t   i  o  n

   P  r  o   b   l  e  m  s   i   d  e  n   t   i     e   d

   i  n   i  n  s  p  e  c   t   i  o  n

   A  c   t   i  o  n   t  a   k  e  n   t

  o

  r  e  c   t   i     y  p  r  o   b   l  e  m

   D  a   t  e  o   f

  r  e  c   t   i     c  a   t   i  o  n

   S   i   g  n  a   t  u  r  e

A P P E N D I X C / P A G E 2

    1 .   1

   b   u   I   l   d   I   N   G

   E   l   E   m   E   N   T   S   T   O   S   A   T   I   S      y   P   R   E   S   C   R   I   b   E   d      I   R   E  -   R   E   S   I   S   T   A   N   C   E   l   E   v   E   l

Page 217: Essential Safety Maintenance Manual

8/3/2019 Essential Safety Maintenance Manual

http://slidepdf.com/reader/full/essential-safety-maintenance-manual 217/290

Page 218: Essential Safety Maintenance Manual

8/3/2019 Essential Safety Maintenance Manual

http://slidepdf.com/reader/full/essential-safety-maintenance-manual 218/290

E S S E N T I A L S A F E T Y M E A S U R E S M A I N T E N A N C E M A N U A L • B U I L D I N G C O M M I S S I O N

   N  a

  m  e  o      b  u   i   l   d   i  n   g  :

   N  a  m  e  o     o  w  n  e  r  :

   A   d   d  r  e  s  s  :

   L  e  v

  e   l  o     p  e  r     o  r  m  a  n  c  e  a  n   d     r  e  q  u  e  n  c  y  o     m  a   i  n   t  e  n  a  n  c  e    (  a  s  s  p  e  c   i     e   d  o  n  o  c  c  u  p  a  n  c  y  p  e  r  m   i   t    )  :

   D  a   t  e  o   f

   i  n  s  p  e  c   t   i  o  n

   N  a  m  e  a  n   d  a   d   d  r  e  s  s  o     p  e

  r  s  o  n

  c  o  n   d  u  c   t   i  n   g   i  n  s  p  e  c   t   i  o  n

   P  r  o   b   l  e  m  s   i   d  e  n   t   i     e   d

   i  n   i  n  s  p  e  c   t   i  o  n

   A  c   t   i  o  n   t  a   k  e  n   t

  o

  r  e  c   t   i     y  p  r  o   b   l  e  m

   D  a   t  e  o   f

  r  e  c   t   i     c  a   t   i  o  n

   S   i   g  n  a   t  u  r  e

A P P E N D I X C / P A G E 4

    1 .   3

   E   l   E   m   E   N   T   S   R   E   q   u   I   R   E   d   T   O   b   E   N   O   N  -   C   O   m   b   u   S   T   I   b

   l   E ,   P   R   O   v   I   d   E

       I   R   E   P   R   O   T   E   C   T   I   O   N   C   O

   m   P   A   R   T   m   E   N   T   A   T   I   O   N   O   R

   S   E   P   A   R   A   T   I   O   N

Page 219: Essential Safety Maintenance Manual

8/3/2019 Essential Safety Maintenance Manual

http://slidepdf.com/reader/full/essential-safety-maintenance-manual 219/290

E S S E N T I A L S A F E T Y M E A S U R E S M A I N T E N A N C E M A N U A L • B U I L D I N G C O M M I S S I O N

   N  a

  m  e  o      b  u   i   l   d   i  n   g  :

   N  a  m  e  o     o  w  n  e  r  :

   A   d   d  r  e  s  s  :

   L  e  v

  e   l  o     p  e  r     o  r  m  a  n  c  e  a  n   d     r  e  q  u  e  n  c  y  o     m  a   i  n   t  e  n  a  n  c  e    (  a  s  s  p  e  c   i     e   d  o  n  o  c  c  u  p  a  n  c  y  p  e  r  m   i   t    )  :

   D  a   t  e  o   f

   i  n  s  p  e  c   t   i  o  n

   N  a  m  e  a  n   d  a   d   d  r  e  s  s  o     p  e

  r  s  o  n

  c  o  n   d  u  c   t   i  n   g   i  n  s  p  e  c   t   i  o  n

   P  r  o   b   l  e  m  s   i   d  e  n   t   i     e   d

   i  n   i  n  s  p  e  c   t   i  o  n

   A  c   t   i  o  n   t  a   k  e  n   t

  o

  r  e  c   t   i     y  p  r  o   b   l  e  m

   D  a   t  e  o   f

  r  e  c   t   i     c  a   t   i  o  n

   S   i   g  n  a   t  u  r  e

A P P E N D I X C / P A G E 5

    1 .   8

   S   O   l   I   d   C   O   R   E   d   O   O   R   S

Page 220: Essential Safety Maintenance Manual

8/3/2019 Essential Safety Maintenance Manual

http://slidepdf.com/reader/full/essential-safety-maintenance-manual 220/290

E S S E N T I A L S A F E T Y M E A S U R E S M A I N T E N A N C E M A N U A L • B U I L D I N G C O M M I S S I O N

   N  a

  m  e  o      b  u   i   l   d   i  n   g  :

   N  a  m  e  o     o  w  n  e  r  :

   A   d   d  r  e  s  s  :

   L  e  v

  e   l  o     p  e  r     o  r  m  a  n  c  e  a  n   d     r  e  q  u  e  n  c  y  o     m  a   i  n   t  e  n  a  n  c  e    (  a  s  s  p  e  c   i     e   d  o  n  o  c  c  u  p  a  n  c  y  p  e  r  m   i   t    )  :

   D  a   t  e  o   f

   i  n  s  p  e  c   t   i  o  n

   N  a  m  e  a  n   d  a   d   d  r  e  s  s  o     p  e

  r  s  o  n

  c  o  n   d  u  c   t   i  n   g   i  n  s  p  e  c   t   i  o  n

   P  r  o   b   l  e  m  s   i   d  e  n   t   i     e   d

   i  n   i  n  s  p  e  c   t   i  o  n

   A  c   t   i  o  n   t  a   k  e  n   t

  o

  r  e  c   t   i     y  p  r  o   b   l  e  m

   D  a   t  e  o   f

  r  e  c   t   i     c  a   t   i  o  n

   S   i   g  n  a   t  u  r  e

A P P E N D I X C / P A G E 6

    1 .   1   2

   P   R   O   S   C   E   N   I   u   m   w   A   l   l    (      I   R   E   C   u   R   T   A   I   N    )

Page 221: Essential Safety Maintenance Manual

8/3/2019 Essential Safety Maintenance Manual

http://slidepdf.com/reader/full/essential-safety-maintenance-manual 221/290

E S S E N T I A L S A F E T Y M E A S U R E S M A I N T E N A N C E M A N U A L • B U I L D I N G C O M M I S S I O N

   N  a

  m  e  o      b  u   i   l   d   i  n   g  :

   N  a  m  e  o     o  w  n  e  r  :

   A   d   d  r  e  s  s  :

   L  e  v

  e   l  o     p  e  r     o  r  m  a  n  c  e  a  n   d     r  e  q  u  e  n  c  y  o     m  a   i  n   t  e  n  a  n  c  e    (  a  s  s  p  e  c   i     e   d  o  n  o  c  c  u  p  a  n  c  y  p  e  r  m   i   t    )  :

   D  a   t  e  o   f

   i  n  s  p  e  c   t   i  o  n

   N  a  m  e  a  n   d  a   d   d  r  e  s  s  o     p  e

  r  s  o  n

  c  o  n   d  u  c   t   i  n   g   i  n  s  p  e  c   t   i  o  n

   P  r  o   b   l  e  m  s   i   d  e  n   t   i     e   d

   i  n   i  n  s  p  e  c   t   i  o  n

   A  c   t   i  o  n   t  a   k  e  n   t

  o

  r  e  c   t   i     y  p  r  o   b   l  e  m

   D  a   t  e  o   f

  r  e  c   t   i     c  a   t   i  o  n

   S   i   g  n  a   t  u  r  e

A P P E N D I X C / P A G E 7

    2 .   1

   P   A   T   H   S   O      T   R   A   v   E   l   T   O   E   x   I   T   S

Page 222: Essential Safety Maintenance Manual

8/3/2019 Essential Safety Maintenance Manual

http://slidepdf.com/reader/full/essential-safety-maintenance-manual 222/290

E S S E N T I A L S A F E T Y M E A S U R E S M A I N T E N A N C E M A N U A L • B U I L D I N G C O M M I S S I O N

   N  a

  m  e  o      b  u   i   l   d   i  n   g  :

   N  a  m  e  o     o  w  n  e  r  :

   A   d   d  r  e  s  s  :

   L  e  v

  e   l  o     p  e  r     o  r  m  a  n  c  e  a  n   d     r  e  q  u  e  n  c  y  o     m  a   i  n   t  e  n  a  n  c  e    (  a  s  s  p  e  c   i     e   d  o  n  o  c  c  u  p  a  n  c  y  p  e  r  m   i   t    )  :

   D  a   t  e  o   f

   i  n  s  p  e  c   t   i  o  n

   N  a  m  e  a  n   d  a   d   d  r  e  s  s  o     p  e

  r  s  o  n

  c  o  n   d  u  c   t   i  n   g   i  n  s  p  e  c   t   i  o  n

   P  r  o   b   l  e  m  s   i   d  e  n   t   i     e   d

   i  n   i  n  s  p  e  c   t   i  o  n

   A  c   t   i  o  n   t  a   k  e  n   t

  o

  r  e  c   t   i     y  p  r  o   b   l  e  m

   D  a   t  e  o   f

  r  e  c   t   i     c  a   t   i  o  n

   S   i   g  n  a   t  u  r  e

A P P E N D I X C / P A G E 8

    2 .   2

   d   I   S   C   H   A   R   G   E

      R   O   m

   E   x   I   T   S

Page 223: Essential Safety Maintenance Manual

8/3/2019 Essential Safety Maintenance Manual

http://slidepdf.com/reader/full/essential-safety-maintenance-manual 223/290

E S S E N T I A L S A F E T Y M E A S U R E S M A I N T E N A N C E M A N U A L • B U I L D I N G C O M M I S S I O N

   N  a

  m  e  o      b  u   i   l   d   i  n   g  :

   N  a  m  e  o     o  w  n  e  r  :

   A   d   d  r  e  s  s  :

   L  e  v

  e   l  o     p  e  r     o  r  m  a  n  c  e  a  n   d     r  e  q  u  e  n  c  y  o     m  a   i  n   t  e  n  a  n  c  e    (  a  s  s  p  e  c   i     e   d  o  n  o  c  c  u  p  a  n  c  y  p  e  r  m   i   t    )  :

   D  a   t  e  o   f

   i  n  s  p  e  c   t   i  o  n

   N  a  m  e  a  n   d  a   d   d  r  e  s  s  o     p  e

  r  s  o  n

  c  o  n   d  u  c   t   i  n   g   i  n  s  p  e  c   t   i  o  n

   P  r  o   b   l  e  m  s   i   d  e  n   t   i     e   d

   i  n   i  n  s  p  e  c   t   i  o  n

   A  c   t   i  o  n   t  a   k  e  n   t

  o

  r  e  c   t   i     y  p  r  o   b   l  e  m

   D  a   t  e  o   f

  r  e  c   t   i     c  a   t   i  o  n

   S   i   g  n  a   t  u  r  e

A P P E N D I X C / P A G E 9

    2 .   3

   E   x   I   T   S

Page 224: Essential Safety Maintenance Manual

8/3/2019 Essential Safety Maintenance Manual

http://slidepdf.com/reader/full/essential-safety-maintenance-manual 224/290

E S S E N T I A L S A F E T Y M E A S U R E S M A I N T E N A N C E M A N U A L • B U I L D I N G C O M M I S S I O N

   N  a

  m  e  o      b  u   i   l   d   i  n   g  :

   N  a  m  e  o     o  w  n  e  r  :

   A   d   d  r  e  s  s  :

   L  e  v

  e   l  o     p  e  r     o  r  m  a  n  c  e  a  n   d     r  e  q  u  e  n  c  y  o     m  a   i  n   t  e  n  a  n  c  e    (  a  s  s  p  e  c   i     e   d  o  n  o  c  c  u  p  a  n  c  y  p  e  r  m   i   t    )  :

   D  a   t  e  o   f

   i  n  s  p  e  c   t   i  o  n

   N  a  m  e  a  n   d  a   d   d  r  e  s  s  o     p  e

  r  s  o  n

  c  o  n   d  u  c   t   i  n   g   i  n  s  p  e  c   t   i  o  n

   P  r  o   b   l  e  m  s   i   d  e  n   t   i     e   d

   i  n   i  n  s  p  e  c   t   i  o  n

   A  c   t   i  o  n   t  a   k  e  n   t

  o

  r  e  c   t   i     y  p  r  o   b   l  e  m

   D  a   t  e  o   f

  r  e  c   t   i     c  a   t   i  o  n

   S   i   g  n  a   t  u  r  e

A P P E N D I X C / P A G E 1 0

    2 .   4

   S   m   O   k   E   l   O   b   b   I   E   S   T   O      I   R   E  -   I   S   O

   l   A   T   E   d   E   x   I   T   S

Page 225: Essential Safety Maintenance Manual

8/3/2019 Essential Safety Maintenance Manual

http://slidepdf.com/reader/full/essential-safety-maintenance-manual 225/290

E S S E N T I A L S A F E T Y M E A S U R E S M A I N T E N A N C E M A N U A L • B U I L D I N G C O M M I S S I O N

   N  a

  m  e  o      b  u   i   l   d   i  n   g  :

   N  a  m  e  o     o  w  n  e  r  :

   A   d   d  r  e  s  s  :

   L  e  v

  e   l  o     p  e  r     o  r  m  a  n  c  e  a  n   d     r  e  q  u  e  n  c  y  o     m  a   i  n   t  e  n  a  n  c  e    (  a  s  s  p  e  c   i     e   d  o  n  o  c  c  u  p  a  n  c  y  p  e  r  m   i   t    )  :

   D  a   t  e  o   f

   i  n  s  p  e  c   t   i  o  n

   N  a  m  e  a  n   d  a   d   d  r  e  s  s  o     p  e

  r  s  o  n

  c  o  n   d  u  c   t   i  n   g   i  n  s  p  e  c   t   i  o  n

   P  r  o   b   l  e  m  s   i   d  e  n   t   i     e   d

   i  n   i  n  s  p  e  c   t   i  o  n

   A  c   t   i  o  n   t  a   k  e  n   t

  o

  r  e  c   t   i     y  p  r  o   b   l  e  m

   D  a   t  e  o   f

  r  e  c   t   i     c  a   t   i  o  n

   S   i   g  n  a   t  u  r  e

A P P E N D I X C / P A G E 1 1

    2 .   5

   O   P   E

   N   A   C   C   E   S   S   b   A   l   C   O   N   I   E   S   O

   R   R   A   m   P   S      O   R      I   R   E  -   I   S   O

   l   A   T   E   d   E   x   I   T   S

Page 226: Essential Safety Maintenance Manual

8/3/2019 Essential Safety Maintenance Manual

http://slidepdf.com/reader/full/essential-safety-maintenance-manual 226/290

E S S E N T I A L S A F E T Y M E A S U R E S M A I N T E N A N C E M A N U A L • B U I L D I N G C O M M I S S I O N

   N  a

  m  e  o      b  u   i   l   d   i  n   g  :

   N  a  m  e  o     o  w  n  e  r  :

   A   d   d  r  e  s  s  :

   L  e  v

  e   l  o     p  e  r     o  r  m  a  n  c  e  a  n   d     r  e  q  u  e  n  c  y  o     m  a   i  n   t  e  n  a  n  c  e    (  a  s  s  p  e  c   i     e   d  o  n  o  c  c  u  p  a  n  c  y  p  e  r  m   i   t    )  :

   D  a   t  e  o   f

   i  n  s  p  e  c   t   i  o  n

   N  a  m  e  a  n   d  a   d   d  r  e  s  s  o     p  e

  r  s  o  n

  c  o  n   d  u  c   t   i  n   g   i  n  s  p  e  c   t   i  o  n

   P  r  o   b   l  e  m  s   i   d  e  n   t   i     e   d

   i  n   i  n  s  p  e  c   t   i  o  n

   A  c   t   i  o  n   t  a   k  e  n   t

  o

  r  e  c   t   i     y  p  r  o   b   l  e  m

   D  a   t  e  o   f

  r  e  c   t   i     c  a   t   i  o  n

   S   i   g  n  a   t  u  r  e

A P P E N D I X C / P A G E 1 2

    2 .   6

   d   O   O   R   S   O

   T   H   E   R   T   H   A   N   S   m   O   k   E   O   R

      I   R   E   d   O   O   R   S

Page 227: Essential Safety Maintenance Manual

8/3/2019 Essential Safety Maintenance Manual

http://slidepdf.com/reader/full/essential-safety-maintenance-manual 227/290

E S S E N T I A L S A F E T Y M E A S U R E S M A I N T E N A N C E M A N U A L • B U I L D I N G C O M M I S S I O N

   N  a

  m  e  o      b  u   i   l   d   i  n   g  :

   N  a  m  e  o     o  w  n  e  r  :

   A   d   d  r  e  s  s  :

   L  e  v

  e   l  o     p  e  r     o  r  m  a  n  c  e  a  n   d     r  e  q  u  e  n  c  y  o     m  a   i  n   t  e  n  a  n  c  e    (  a  s  s  p  e  c   i     e   d  o  n  o  c  c  u  p  a  n  c  y  p  e  r  m   i   t    )  :

   D  a   t  e  o   f

   i  n  s  p  e  c   t   i  o  n

   N  a  m  e  a  n   d  a   d   d  r  e  s  s  o     p  e

  r  s  o  n

  c  o  n   d  u  c   t   i  n   g   i  n  s  p  e  c   t   i  o  n

   P  r  o   b   l  e  m  s   i   d  e  n   t   i     e   d

   i  n   i  n  s  p  e  c   t   i  o  n

   A  c   t   i  o  n   t  a   k  e  n   t

  o

  r  e  c   t   i     y  p  r  o   b   l  e  m

   D  a   t  e  o   f

  r  e  c   t   i     c  a   t   i  o  n

   S   i   g  n  a   t  u  r  e

A P P E N D I X C / P A G E 1 3

    3 .   1

   E   x   I   T   S   I   G   N   S

   R   E   F   E   R  :   A   S   2   2   9   3 .   2

Page 228: Essential Safety Maintenance Manual

8/3/2019 Essential Safety Maintenance Manual

http://slidepdf.com/reader/full/essential-safety-maintenance-manual 228/290

E S S E N T I A L S A F E T Y M E A S U R E S M A I N T E N A N C E M A N U A L • B U I L D I N G C O M M I S S I O N

   N  a

  m  e  o      b  u   i   l   d   i  n   g  :

   N  a  m  e  o     o  w  n  e  r  :

   A   d   d  r  e  s  s  :

   L  e  v

  e   l  o     p  e  r     o  r  m  a  n  c  e  a  n   d     r  e  q  u  e  n  c  y  o     m  a   i  n   t  e  n  a  n  c  e    (  a  s  s  p  e  c   i     e   d  o  n  o  c  c  u  p  a  n  c  y  p  e  r  m   i   t    )  :

   D  a   t  e  o   f

   i  n  s  p  e  c   t   i  o  n

   N  a  m  e  a  n   d  a   d   d  r  e  s  s  o     p  e

  r  s  o  n

  c  o  n   d  u  c   t   i  n   g   i  n  s  p  e  c   t   i  o  n

   P  r  o   b   l  e  m  s   i   d  e  n   t   i     e   d

   i  n   i  n  s  p  e  c   t   i  o  n

   A  c   t   i  o  n   t  a   k  e  n   t

  o

  r  e  c   t   i     y  p  r  o   b   l  e  m

   D  a   t  e  o   f

  r  e  c   t   i     c  a   t   i  o  n

   S   i   g  n  a   t  u  r  e

A P P E N D I X C / P A G E 1 4

    3 .   2

   S   I   G   N   w

   A   R   N   I   N   G   A   G   A   I   N   S   T   T   H   E

   u   S   E   O      l   I      T   S   I   N   T   H   E   E   v

   E   N   T   O         I   R   E

Page 229: Essential Safety Maintenance Manual

8/3/2019 Essential Safety Maintenance Manual

http://slidepdf.com/reader/full/essential-safety-maintenance-manual 229/290

E S S E N T I A L S A F E T Y M E A S U R E S M A I N T E N A N C E M A N U A L • B U I L D I N G C O M M I S S I O N

   N  a

  m  e  o      b  u   i   l   d   i  n   g  :

   N  a  m  e  o     o  w  n  e  r  :

   A   d   d  r  e  s  s  :

   L  e  v

  e   l  o     p  e  r     o  r  m  a  n  c  e  a  n   d     r  e  q  u  e  n  c  y  o     m  a   i  n   t  e  n  a  n  c  e    (  a  s  s  p  e  c   i     e   d  o  n  o  c  c  u  p  a  n  c  y  p  e  r  m   i   t    )  :

   D  a   t  e  o   f

   i  n  s  p  e  c   t   i  o  n

   N  a  m  e  a  n   d  a   d   d  r  e  s  s  o     p  e

  r  s  o  n

  c  o  n   d  u  c   t   i  n   g   i  n  s  p  e  c   t   i  o  n

   P  r  o   b   l  e  m  s   i   d  e  n   t   i     e   d

   i  n   i  n  s  p  e  c   t   i  o  n

   A  c   t   i  o  n   t  a   k  e  n   t

  o

  r  e  c   t   i     y  p  r  o   b   l  e  m

   D  a   t  e  o   f

  r  e  c   t   i     c  a   t   i  o  n

   S   i   g  n  a   t  u  r  e

A P P E N D I X C / P A G E 1 5

    3 .   3

   w   A   R   N   I   N   G   S   I   G   N   S   O   N   S

   l   I   d   I   N   G      I   R   E   d   O   O   R   S   A   N

   d   d   O   O   R   S   T   O

   N   O   N  -   R   E   q   u   I   R   E   d   S

   T   A   I   R   w   A   y   S   R   A   m   P   S   A   N   d

   E   S   C   A   l   A   T   O   R   S

Page 230: Essential Safety Maintenance Manual

8/3/2019 Essential Safety Maintenance Manual

http://slidepdf.com/reader/full/essential-safety-maintenance-manual 230/290

   N  a

  m  e  o      b  u   i   l   d   i  n   g  :

   N  a  m  e  o     o  w  n  e  r  :

   A   d   d  r  e  s  s  :

   L  e  v

  e   l  o     p  e  r     o  r  m  a  n  c  e  a  n   d     r  e  q  u  e  n  c  y  o     m  a   i  n   t  e  n  a  n  c  e    (  a  s  s  p  e  c   i   f  e   d  o  n  o  c  c  u  p  a  n  c  y  p  e  r  m   i   t    )  :

   D  a   t  e  o   

   i  n  s  p  e  c   t   i  o  n

   N  a  m  e  a  n   d  a   d   d  r  e  s  s  o     p  e

  r  s  o  n

  c  o  n   d  u  c   t   i  n   g   i  n  s  p  e  c   t   i  o

  n

   P  r  o   b   l  e  m  s   i   d  e  n   t   i   f  e   d

   i  n   i  n  s  p  e  c   t   i  o  n

   A  c   t   i  o  n   t  a   k  e  n   t  o

  r  e  c   t   i     y  p  r  o   b   l  e  m

   D  a   t  e  o   

  r  e  c   t   i   f  c  a   t   i  o  n

   S   i   g  n  a   t  u  r  e

A P P E N D I X C / P A G E 1 6

E S S E N T I A L S A F E T Y M E A S U R E S M A I N T E N A N C E M A N U A L • B U I L D I N G C O M M I S S I O N

   3 .   4

   S   I   G   N   S ,   I   N   t   E

   r   C   o   m

   m

   u   N   I   C   A   t   I   o   N    S

   y   S

   t   E   m

 ,   o   r

   A   l   A   r   m

    S   y   S   t   E   m

    o   N    D

   o   o   r   S

   o   f

   f   I   r   E  -   I   S   o   l   A   t   E   D 

   E   X   I   t   S   S

   t   A   t   I   N   G    t

   h   E

   r   E  -   E   N   t   r   y

   I   S

   A   v   A   I   l   A   b   l   E

Page 231: Essential Safety Maintenance Manual

8/3/2019 Essential Safety Maintenance Manual

http://slidepdf.com/reader/full/essential-safety-maintenance-manual 231/290

E S S E N T I A L S A F E T Y M E A S U R E S M A I N T E N A N C E M A N U A L • B U I L D I N G C O M M I S S I O N

   N  a

  m  e  o      b  u   i   l   d   i  n   g  :

   N  a  m  e  o     o  w  n  e  r  :

   A   d   d  r  e  s  s  :

   L  e  v

  e   l  o     p  e  r     o  r  m  a  n  c  e  a  n   d     r  e  q  u  e  n  c  y  o     m  a   i  n   t  e  n  a  n  c  e    (  a  s  s  p  e  c   i     e   d  o  n  o  c  c  u  p  a  n  c  y  p  e  r  m   i   t    )  :

   D  a   t  e  o   f

   i  n  s  p  e  c   t   i  o  n

   N  a  m  e  a  n   d  a   d   d  r  e  s  s  o     p  e

  r  s  o  n

  c  o  n   d  u  c   t   i  n   g   i  n  s  p  e  c   t   i  o  n

   P  r  o   b   l  e  m  s   i   d  e  n   t   i     e   d

   i  n   i  n  s  p  e  c   t   i  o  n

   A  c   t   i  o  n   t  a   k  e  n   t

  o

  r  e  c   t   i     y  p  r  o   b   l  e  m

   D  a   t  e  o   f

  r  e  c   t   i     c  a   t   i  o  n

   S   i   g  n  a   t  u  r  e

A P P E N D I X C / P A G E 1 7

    3 .   5   S   I

   G   N   A   l   E   R   T   I   N   G   A   P   E   R   S   O   N

   T   H   A   T   T   H   E   O   P   E   R   A   T   I   O   N

   O      d   O   O   R   S   m   u   S   T   N   O   T

   b   E   I   m   P   A   I   R   E   d

Page 232: Essential Safety Maintenance Manual

8/3/2019 Essential Safety Maintenance Manual

http://slidepdf.com/reader/full/essential-safety-maintenance-manual 232/290

E S S E N T I A L S A F E T Y M E A S U R E S M A I N T E N A N C E M A N U A L • B U I L D I N G C O M M I S S I O N

   N  a

  m  e  o      b  u   i   l   d   i  n   g  :

   N  a  m  e  o     o  w  n  e  r  :

   A   d   d  r  e  s  s  :

   L  e  v

  e   l  o     p  e  r     o  r  m  a  n  c  e  a  n   d     r  e  q  u  e  n  c  y  o     m  a   i  n   t  e  n  a  n  c  e    (  a  s  s  p  e  c   i     e   d  o  n  o  c  c  u  p  a  n  c  y  p  e  r  m   i   t    )  :

   D  a   t  e  o   f

   i  n  s  p  e  c   t   i  o  n

   N  a  m  e  a  n   d  a   d   d  r  e  s  s  o     p  e

  r  s  o  n

  c  o  n   d  u  c   t   i  n   g   i  n  s  p  e  c   t   i  o  n

   P  r  o   b   l  e  m  s   i   d  e  n   t   i     e   d

   i  n   i  n  s  p  e  c   t   i  o  n

   A  c   t   i  o  n   t  a   k  e  n   t

  o

  r  e  c   t   i     y  p  r  o   b   l  e  m

   D  a   t  e  o   f

  r  e  c   t   i     c  a   t   i  o  n

   S   i   g  n  a   t  u  r  e

A P P E N D I X C / P A G E 1 8

    3 .   6

   S   I   G   N   S   O   N   d   O   O   R   S   I   N   A

   l   P   I   N   E   A   R   E   A   S   A   l   E   R   T   I   N   G

   P   E   O   P   l   E   T   H   A   T   T   H   E   y   O   P   E   N   I   N   w   A   R   d   S

Page 233: Essential Safety Maintenance Manual

8/3/2019 Essential Safety Maintenance Manual

http://slidepdf.com/reader/full/essential-safety-maintenance-manual 233/290

E S S E N T I A L S A F E T Y M E A S U R E S M A I N T E N A N C E M A N U A L • B U I L D I N G C O M M I S S I O N

A P P E N D I X C / P A G E 1 9

   N  a

  m  e  o      b  u   i   l   d   i  n   g  :

   N  a  m  e  o     o  w  n  e  r  :

   A   d   d  r  e  s  s  :

   L  e  v

  e   l  o     p  e  r     o  r  m  a  n  c  e  a  n   d     r  e  q  u  e  n  c  y  o     m  a   i  n   t  e  n  a  n  c  e    (  a  s  s  p  e  c   i     e   d  o  n  o  c  c  u  p  a  n  c  y  p  e  r  m   i   t    )  :

   D  a   t  e  o   f

   i  n  s  p  e  c   t   i  o  n

   N  a  m  e  a  n   d  a   d   d  r  e  s  s  o     p  e

  r  s  o  n

  c  o  n   d  u  c   t   i  n   g   i  n  s  p  e  c   t   i  o  n

   P  r  o   b   l  e  m  s   i   d  e  n   t   i     e   d

   i  n   i  n  s  p  e  c   t   i  o  n

   A  c   t   i  o  n   t  a   k  e  n   t

  o

  r  e  c   t   i     y  p  r  o   b   l  e  m

   D  a   t  e  o   f

  r  e  c   t   i     c  a   t   i  o  n

   S   i   g  n  a   t  u  r  e

    3 .   7

      I   R   E   O   R   d   E   R   N

   O   T   I   C   E   S   R   E   q   u   I   R   E   d   I   N   A

   l   P   I   N   E   A   R   E   A   S

Page 234: Essential Safety Maintenance Manual

8/3/2019 Essential Safety Maintenance Manual

http://slidepdf.com/reader/full/essential-safety-maintenance-manual 234/290

E S S E N T I A L S A F E T Y M E A S U R E S M A I N T E N A N C E M A N U A L • B U I L D I N G C O M M I S S I O N

A P P E N D I X C / P A G E 2 0

REFER: AS 2293.2

Name o building: Name o owner:

Address:

Level o perormance and requency o maintenance (as specied on occupancy permit):

Unit TaskRoutine 1

i.e. six MonthsRoutine 2

i.e. twelve MonthsSignature

Battery Charger

Visual inspection o unit

Clean unit and cubicle

Check battery voltage - record voltage

Check all connectionsCheck voltmeter calibration - record result

Check battery earth - ault detector operates

Check battery low - voltage alarm operates

Inverter

Visual inspection o unit

Cec D.C. inut oltage - record oltage

Check A.C. output voltage - record voltage

Check voltmeter calibration - record result

Distributionand controlequipment

Visually inspect - relays, contactors, uses, circuit

breakersCheck all connections or tightness

Clean down equipment and enclosures

Check sensing equipment operates systemcorrectly when normal lighting supply isolated

Emergencylights andexit signs

Check all lights operate correctly

Replace aulty lamps

Clean refecting and light emitting suraces

Total system

Check proper operation with battery-charger oand mains supply isolated

Check charger-ailure alarm operatesCheck correct battery-charging when systemrestored

Check and record battery voltage ater dischargetest - 100% o lights or at least 90 minutes

Battery-carger cange oer time to “oatcharge” mode, ater “boost” mode selected.Record time

Record battery re-service or replacement

date Nae o person concting inspection Stats Proesientife

Action torecti

date proerectife

Signatre

4.1 EmERGENCy l IGHTING

SIx-mONTHly ANd TwElvE-mONTHly PROCEduRES

Page 235: Essential Safety Maintenance Manual

8/3/2019 Essential Safety Maintenance Manual

http://slidepdf.com/reader/full/essential-safety-maintenance-manual 235/290

E S S E N T I A L S A F E T Y M E A S U R E S M A I N T E N A N C E M A N U A L • B U I L D I N G C O M M I S S I O N

A P P E N D I X C / P A G E 2 1

   N  a  m  e  o      b  u   i   l   d   i  n   g  :

   N  a  m  e  o     o  w  n  e  r  :

   A   d   d  r  e  s  s  :

   L  e  v  e   l  o     p  e  r     o  r  m  a  n  c  e  a  n   d     r  e  q  u  e  n  c  y  o     m  a   i  n   t  e  n  a  n  c  e    (  a  s  s  p  e  c   i     e   d  o  n  o  c  c  u  p  a  n  c  y  p  e  r  m   i   t    )  :

   D  a   t  e  o   f   i  n  s  p  e  c   t   i  o  n

   D  a   t  e  o   f

  r  e  c   t   i     c  a   t   i  o  n

   S   i   g  n  a   t  u  r  e

   N  a  m  e  o     p  e  r  s  o  n   i  n  s  p  e  c   t   i  n   g

   L   i   g   h   t   N  u  m   b  e  r

   S   t  a   t  u  s

   1

   2

   3

   4

   5

   6

   7

   8

   9

   1 0

   1 1

   1 2

   1 3

   1 4

   1 5

   1 6

   1 7

   1 8

   1 9

   2 0

   E  n   d  u  r  a  n  c  e  o      b  a   t   t  e  r  y  a      t  e  r

  p  o  w  e  r   t  u  r  n  e   d  o      

   T   i  m  e   i  n   M   i  n  s

    (  a   t   l  e  a  s   t   9   0    )

   F  a  u   l   t  y   l  a  m  p  r  e  p   l  a  c  e   d

       

   i   

  r  e  p   l  a  c  e   d

   P  r  o  p  e  r     u  n  c   t   i  o  n  o      b  a   t   t  e  r  y

  c   h  a  r   g  e  r   i  n   d   i  c  a   t  o  r

   Y  e  s

      

   N  o

     

   E  n   d  u  r  a  n  c  e  o      b  a   t   t  e  r  y  a      t  e  r

  p  o  w  e  r   t  u  r  n  e   d  o      

   T   i  m  e   i  n   M   i  n  s

    (  a   t   l  e  a  s   t   9   0    )

   F  a  u   l   t  y   l  a  m  p  r  e  p   l  a  c  e   d

       

   i   

  r  e  p   l  a  c  e   d

   P  r  o  p  e  r     u  n  c   t   i  o  n  o      b  a   t   t  e  r  y

  c   h  a  r   g  e  r   i  n   d   i  c  a   t  o  r

   Y  e  s

      

   N  o

     

   A   l   l   l   i   g   h   t  e  m   i   t   t   i  n   g  a  n   d

  r  e   f  e  c   t   i  n   g  s  u  r     a  c  e  s  c   l  e  a  n  e   d

         w   h  e  n

  c  o  m  p   l  e   t  e   d

   d   a   t   e   o      i   n   s   p   e   c   t   i   o   n

   N   a      e   o      p   e   r   s   o   n

   c   o   n        c   t   i   n   g

   i   n   s   p   e   c   t   i   o   n

   S   t   a   t     s

   P   r   o         e      s   i      e   n   t   i   f   e      o   n   i   n   s   p   e   c   t   i   o   n

   A   c   t   i   o   n   t   a      e   n   t   o   r   e

   c   t   i        p   r   o         e   

   d   a   t   e   o   

   r   e   c   t   i   f   c   a   t   i   o   n

   S   i   g   n   a   t     r   e

    E   m   E   R   G   E   N   C   y   l   I   G   H   T   I   N   G

   S   y   S   T   E   m  —   S   I   N   G   l   E   P   O   I   N

   T   l   I   G   H   T   I   N   G

   R   E   F   E   R  :   A   S   2   2   9   3 .   2

Page 236: Essential Safety Maintenance Manual

8/3/2019 Essential Safety Maintenance Manual

http://slidepdf.com/reader/full/essential-safety-maintenance-manual 236/290

E S S E N T I A L S A F E T Y M E A S U R E S M A I N T E N A N C E M A N U A L • B U I L D I N G C O M M I S S I O N

A P P E N D I X C / P A G E 2 2

    E   m   E   R   G   E   N

   C   y   l   I   G   H   T   I   N   G   S   y   S   T   E   m   S

  —   b   A   T   T   E   R   I   E   S

   N  a

  m  e  o      b  u   i   l   d   i  n   g  :

   N  a  m  e  o     o  w  n  e  r  :

   A   d   d  r  e  s  s  :

   L  e  v

  e   l  o     p  e  r     o  r  m  a  n  c  e  a  n   d     r  e  q  u  e  n  c  y  o     m  a   i  n   t  e  n  a  n  c  e    (  a  s  s  p  e  c   i     e   d  o  n  o  c  c  u  p  a  n  c  y  p  e  r  m   i   t    )  :

   d

   a   t   e

   N   a      e   o      t   e   s   t   e   r

   S   t   a   t     s

   +   P   o   s   i   t   i     e

   C   e      

   N           e   r   s

   N   e   g   a   t   i     e  -

   d   a   t   e

   P   r   o         e

   

   R   e   c   t   i   f   e   

   S   i   g   n   a   t     r   e

   1

   2

   3

   4

   5

   6

   7

   8

   9

   1   0

   1   1

   1   2

   1   3

   1   4

   1   5

   1   6

   L  e  a   d  -  a  c   i   d   b  a   t   t  e  r  y

   E   l  e  c   t  r  o   l  y   t  e   d  e  n  s   i   t

  y

   1   0   %  o     c  e   l   l  s  r  a  n   d

  o  m

   R  e  a   d   i  n   g  o      

   h  y   d  r  o  m  e   t  e  r

   1   0   %  o     c  e   l   l  s  r  a  n   d  o  m

   S   t  a   t  e  o     c   h  a  r   g  e

   H   i   g   h  -   H

   M  e   d   i  u  m  -   M

   L  o  w  -   L

   A   l   l   b  a   t   t  e  r   i  e  s

   E   l  e  c   t  r  o   l  y   t  e   l  e  v  e   l

   H ,   ¾ ,   ½ ,   ¼ ,   l  o  w

   A   l   l  c  e   l   l  s

   E   l  e  c   t  r  o   l  y   t  e   l  e  a   k  a   g

  e

   N  e  u   t  r  a   l   i  s  e  s  p   i   l   l  s

   L  e  a   d  -  a  c   i   d   b  a   t   t  e  r  y

   E   l  e  c   t  r  o   l  y   t  e   d  e  n  s   i   t

  y

   R  e  a   d   i  n   g  o      

   h  y   d  r  o  m  e   t  e  r

   A   l   l  c  e   l   l  s

   S   t  a   t  e  o     c   h  a  r   g  e

   H   i   g   h  -   H

   M  e   d   i  u  m  -   M

   L  o  w  -   L

   A   l   l   b  a   t   t  e  r   i  e  s

   E   l  e  c   t  r  o   l  y   t  e   l  e  v  e   l

   H ,   ¾ ,   ½ ,   ¼ ,   l  o  w

   A   l   l  c  e   l   l  s

   E   l  e  c   t  r  o   l  y   t  e   l  e  a   k  a   g

  e

   N  e  u   t  r  a   l   i  s  e  s  p   i   l   l  s

   C  e   l   l  c  o  n  n  e  c   t   i  o  n  s  -

  c  o  r  r  o  s   i  o  n ,   t   i   g   h   t  n  e  s  s

        w   h  e  n  c   h  e  c   k  e   d

   C  o  a   t  c  o  n  n  e  c   t   i  o  n  s  w   i   t   h

   t  e

  r  m   i  n  a   l  p  r  e  s  e  r  v  a   t   i  v  e

        w   h  e  n  c  o  m  p   l  e   t  e   d

   I  n

   d   i  v   i   d  u  a   l  c  e   l   l  v  o   l   t  a   g  e

   N  o   t  e  a  n  y  >   + .   0   3   V

   O

  v  e  r  a   l   l   b  a   t   t  e  r  y  v  o   l   t  a   g  e

   R  e  a   d   i  n   g  o        v  o   l   t  m  e   t  e  r

   R   E   F   E   R  :   A   S   2   2   9   3 .   2

   d

   a   t   e   o      i   n   s   p   e   c   t   i   o   n

   N   a      e   o      p   e   r   s   o   n

   c   o   n        c   t   i   n   g

   i   n   s   p   e   c   t   i   o   n

   S   t   a   t     s

   P   r   o         e      s   i      e   n   t   i   f

   e      o   n   i   n   s   p   e   c   t   i   o   n

   A   c   t   i   o   n   t   a      e   n

   t   o   r   e   c   t   i        p   r   o         e   

   d   a   t   e

   p   r   o         e   

   r   e   c   t   i   f   c   a   t   i   o   n

   S   i   g   n   a   t     r   e

Page 237: Essential Safety Maintenance Manual

8/3/2019 Essential Safety Maintenance Manual

http://slidepdf.com/reader/full/essential-safety-maintenance-manual 237/290

E S S E N T I A L S A F E T Y M E A S U R E S M A I N T E N A N C E M A N U A L • B U I L D I N G C O M M I S S I O N

A P P E N D I X C / P A G E 2 3

    5 .   5

      I   R   E   C   O   N   T

   R   O   l   C   E   N   T   R   E

   N  a

  m  e  o      b  u   i   l   d   i  n   g  :

   N  a  m  e  o     o  w  n  e  r  :

   A   d   d  r  e  s  s  :

   L  e  v

  e   l  o     p  e  r     o  r  m  a  n  c  e  a  n   d     r  e  q  u  e  n  c  y  o     m  a   i  n   t  e  n  a  n  c  e    (  a  s  s  p  e  c   i     e   d  o  n  o  c  c  u  p  a  n  c  y  p  e  r  m   i   t    )  :

   D  a   t  e  o   f

   i  n  s  p  e  c   t   i  o  n

   N  a  m  e  a  n   d  a   d   d  r  e  s  s  o     p  e

  r  s  o  n

  c  o  n   d  u  c   t   i  n   g   i  n  s  p  e  c   t   i  o  n

   P  r  o   b   l  e  m  s   i   d  e  n   t   i     e   d

   i  n   i  n  s  p  e  c   t   i  o  n

   A  c   t   i  o  n   t  a   k  e  n   t

  o

  r  e  c   t   i     y  p  r  o   b   l  e  m

   D  a   t  e  o   f

  r  e  c   t   i     c  a   t   i  o  n

   S   i   g  n  a   t  u  r  e

Page 238: Essential Safety Maintenance Manual

8/3/2019 Essential Safety Maintenance Manual

http://slidepdf.com/reader/full/essential-safety-maintenance-manual 238/290

E S S E N T I A L S A F E T Y M E A S U R E S M A I N T E N A N C E M A N U A L • B U I L D I N G C O M M I S S I O N

   N  a

  m  e  o      b  u   i   l   d   i  n   g  :

   N  a  m  e  o     o  w  n  e  r  :

   A   d   d  r  e  s  s  :

   L  e  v

  e   l  o     p  e  r     o  r  m  a  n  c  e  a  n   d     r  e  q  u  e  n  c  y  o     m  a   i  n   t  e  n  a  n  c  e    (  a  s  s  p  e  c   i     e   d  o  n  o  c  c  u  p  a  n  c  y  p  e  r  m   i   t    )  :

   D  a   t  e  o   f

   i  n  s  p  e  c   t   i  o  n

   N  a  m  e  a  n   d  a   d   d  r  e  s  s  o     p  e

  r  s  o  n

  c  o  n   d  u  c   t   i  n   g   i  n  s  p  e  c   t   i  o  n

   P  r  o   b   l  e  m  s   i   d  e  n   t   i     e   d

   i  n   i  n  s  p  e  c   t   i  o  n

   A  c   t   i  o  n   t  a   k  e  n   t

  o

  r  e  c   t   i     y  p  r  o   b   l  e  m

   D  a   t  e  o   f

  r  e  c   t   i     c  a   t   i  o  n

   S   i   g  n  a   t  u  r  e

A P P E N D I X C / P A G E 2 4

    5 .   6

   P   R   O   v   I   S   I   O   N   S      O   R   S   P   E   C   I

   A   l   H   A   z   A   R   d   S

Page 239: Essential Safety Maintenance Manual

8/3/2019 Essential Safety Maintenance Manual

http://slidepdf.com/reader/full/essential-safety-maintenance-manual 239/290

E S S E N T I A L S A F E T Y M E A S U R E S M A I N T E N A N C E M A N U A L • B U I L D I N G C O M M I S S I O N

   N  a

  m  e  o      b  u   i   l   d   i  n   g  :

   N  a  m  e  o     o  w  n  e  r  :

   A   d   d  r  e  s  s  :

   L  e  v

  e   l  o     p  e  r     o  r  m  a  n  c  e  a  n   d     r  e  q  u  e  n  c  y  o     m  a   i  n   t  e  n  a  n  c  e    (  a  s  s  p  e  c   i     e   d  o  n  o  c  c  u  p  a  n  c  y  p  e  r  m   i   t    )  :

   D  a   t  e  o   f

   i  n  s  p  e  c   t   i  o  n

   N  a  m  e  a  n   d  a   d   d  r  e  s  s  o     p  e

  r  s  o  n

  c  o  n   d  u  c   t   i  n   g   i  n  s  p  e  c   t   i  o  n

   P  r  o   b   l  e  m  s   i   d  e  n   t   i     e   d

   i  n   i  n  s  p  e  c   t   i  o  n

   A  c   t   i  o  n   t  a   k  e  n   t

  o

  r  e  c   t   i     y  p  r  o   b   l  e  m

   D  a   t  e  o   f

  r  e  c   t   i     c  a   t   i  o  n

   S   i   g  n  a   t  u  r  e

A P P E N D I X C / P A G E 2 5

 

   9 .   1

   S   T   R   E   T   C   H   E   R      A   C   I   l   I   T   I   E   S   I   N   l   I      T   S

Page 240: Essential Safety Maintenance Manual

8/3/2019 Essential Safety Maintenance Manual

http://slidepdf.com/reader/full/essential-safety-maintenance-manual 240/290

E S S E N T I A L S A F E T Y M E A S U R E S M A I N T E N A N C E M A N U A L • B U I L D I N G C O M M I S S I O N

   N  a

  m  e  o      b  u   i   l   d   i  n   g  :

   N  a  m  e  o     o  w  n  e  r  :

   A   d   d  r  e  s  s  :

   L  e  v

  e   l  o     p  e  r     o  r  m  a  n  c  e  a  n   d     r  e  q  u  e  n  c  y  o     m  a   i  n   t  e  n  a  n  c  e    (  a  s  s  p  e  c   i     e   d  o  n  o  c  c  u  p  a  n  c  y  p  e  r  m   i   t    )  :

   D  a   t  e  o   f

   i  n  s  p  e  c   t   i  o  n

   N  a  m  e  a  n   d  a   d   d  r  e  s  s  o     p  e

  r  s  o  n

  c  o  n   d  u  c   t   i  n   g   i  n  s  p  e  c   t   i  o  n

   P  r  o   b   l  e  m  s   i   d  e  n   t   i     e   d

   i  n   i  n  s  p  e  c   t   i  o  n

   A  c   t   i  o  n   t  a   k  e  n   t

  o

  r  e  c   t   i     y  p  r  o   b   l  e  m

   D  a   t  e  o   f

  r  e  c   t   i     c  a   t   i  o  n

   S   i   g  n  a   t  u  r  e

A P P E N D I X C / P A G E 2 6

    9 .   2

   E   m   E   R   G   E   N   C   y   l   I      T   S

Page 241: Essential Safety Maintenance Manual

8/3/2019 Essential Safety Maintenance Manual

http://slidepdf.com/reader/full/essential-safety-maintenance-manual 241/290

Page 242: Essential Safety Maintenance Manual

8/3/2019 Essential Safety Maintenance Manual

http://slidepdf.com/reader/full/essential-safety-maintenance-manual 242/290

E S S E N T I A L S A F E T Y M E A S U R E S M A I N T E N A N C E M A N U A L • B U I L D I N G C O M M I S S I O N

A P P E N D I X C / P A G E 2 8

10.1 STANdby POwER SySTEm

Name o building: Name o owner:

Address:

Level o perormance and requency o maintenance (as specied on occupancy permit):

Unit Task Week 1 Week 2 Week 3 Week 4 Week 5 Month

Date

Generating Set

Check water and oil levels -top up i necessary

Check required spares on hand -belts, lter cartridges, engine oil

Batteries andCharger

Freedom rom corrosion

Check electrolyte level - top upi necessary

Check cell voltageLead acid - 2 voltsni-cad - 1.5 volts

Run engine or10 mins then -

Visual check or leaks - oil,uel, water, loose ttings orequipment

Visual check o belt drives

Check operation o alternator

or generator (check voltmeter)Check battery-charger power-ailure alarm

Check or excessive vibrationor heat

Check or correct running speed

Ater runningand shut-down

Check water, oil, uel levels -top up i necessary

Check cooling system strainersor lters and clean i necessary

Ensure engine “stop”

mechanism automaticallyreturns to “start” position

Start engine

Using manual controlsMonthly routine

Check temp ater 30 minsMonthly routine

Check and clean - uel sludgeand sediment trap, uel, oil andair lters - replace i necessary six-monthly routine

Change engine oil (i not 6months, then yearly) six-monthly routine

Weekly signature

Page 243: Essential Safety Maintenance Manual

8/3/2019 Essential Safety Maintenance Manual

http://slidepdf.com/reader/full/essential-safety-maintenance-manual 243/290

E S S E N T I A L S A F E T Y M E A S U R E S M A I N T E N A N C E M A N U A L • B U I L D I N G C O M M I S S I O N

A P P E N D I X C / P A G E 2 9

   N  a

  m  e  o      b  u   i   l   d   i  n   g  :

   N  a  m  e  o     o  w  n  e  r  :

   A   d   d  r  e  s  s  :

   L  e  v

  e   l  o     p  e  r     o  r  m  a  n  c  e  a  n   d     r  e  q  u  e  n  c  y  o     m  a   i  n   t  e  n  a  n  c  e    (  a  s  s  p  e  c   i     e   d  o  n  o  c  c  u  p  a  n  c  y  p  e  r  m   i   t    )  :

   D  a   t  e  o   f

   i  n  s  p  e  c   t   i  o  n

   N  a  m  e  a  n   d  a   d   d  r  e  s  s  o     p  e

  r  s  o  n

  c  o  n   d  u  c   t   i  n   g   i  n  s  p  e  c   t   i  o  n

   P  r  o   b   l  e  m  s   i   d  e  n   t   i     e   d

   i  n   i  n  s  p  e  c   t   i  o  n

   A  c   t   i  o  n   t  a   k  e  n   t

  o

  r  e  c   t   i     y  p  r  o   b   l  e  m

   D  a   t  e  o   f

  r  e  c   t   i     c  a   t   i  o  n

   S   i   g  n  a   t  u  r  e

    1   1 .   1

   O   P   E   N   S   P   A   C   E   A   R   O   u   N   d   l   A   R   G   E   I   S   O   l   A   T   E   d   b   u   I   l   d   I   N   G   S

Page 244: Essential Safety Maintenance Manual

8/3/2019 Essential Safety Maintenance Manual

http://slidepdf.com/reader/full/essential-safety-maintenance-manual 244/290

E S S E N T I A L S A F E T Y M E A S U R E S M A I N T E N A N C E M A N U A L • B U I L D I N G C O M M I S S I O N

   N  a

  m  e  o      b  u   i   l   d   i  n   g  :

   N  a  m  e  o     o  w  n  e  r  :

   A   d   d  r  e  s  s  :

   L  e  v

  e   l  o     p  e  r     o  r  m  a  n  c  e  a  n   d     r  e  q  u  e  n  c  y  o     m  a   i  n   t  e  n  a  n  c  e    (  a  s  s  p  e  c   i     e   d  o  n  o  c  c  u  p  a  n  c  y  p  e  r  m   i   t    )  :

   D  a   t  e  o   f

   i  n  s  p  e  c   t   i  o  n

   N  a  m  e  a  n   d  a   d   d  r  e  s  s  o     p  e

  r  s  o  n

  c  o  n   d  u  c   t   i  n   g   i  n  s  p  e  c   t   i  o  n

   P  r  o   b   l  e  m  s   i   d  e  n   t   i     e   d

   i  n   i  n  s  p  e  c   t   i  o  n

   A  c   t   i  o  n   t  a   k  e  n   t

  o

  r  e  c   t   i     y  p  r  o   b   l  e  m

   D  a   t  e  o   f

  r  e  c   t   i     c  a   t   i  o  n

   S   i   g  n  a   t  u  r  e

A P P E N D I X C / P A G E 3 0

    1   1 .   2

   v   E   H   I   C   u   l   A   R   A   C   C   E   S   S   A   R   O   u   N   d   l   A   R   G   E   I   S   O   l   A   T   E   d   b   u   I   l   d   I   N   G   S

Page 245: Essential Safety Maintenance Manual

8/3/2019 Essential Safety Maintenance Manual

http://slidepdf.com/reader/full/essential-safety-maintenance-manual 245/290

E S S E N T I A L S A F E T Y M E A S U R E S M A I N T E N A N C E M A N U A L • B U I L D I N G C O M M I S S I O N

A P P E N D I X C / P A G E 3 1

   N  a  m  e  o      b  u   i   l   d   i  n   g  :

   N  a  m  e  o     o  w  n  e  r  :

   A   d   d  r  e  s  s  :

   L  e  v

  e   l  o     p  e  r     o  r  m  a  n  c  e  a  n   d     r  e  q  u  e  n  c  y  o     m  a   i  n   t  e  n  a  n  c  e    (  a  s  s  p  e  c   i     e   d  o  n  o  c  c  u  p  a  n  c  y  p  e  r  m   i   t    )  :

   D  a   t  e  o   f

   i  n  s  p  e  c   t   i  o  n

   I   t  e  m  o     p   l  a  n   t  o  r

  e  q  u   i  p  m  e  n   t

   S  e  r  v   i  c  e  p  e  r     o  r  m  e   d

   D  e   f  e  c   t  s   i   d  e  n   t   i     e   d   i  n

   i  n  s  p  e  c   t   i  o  n

   A  c   t   i  o  n   t  a   k  e  n   t  o  r  e  c   t   i     y

  p

  r  o   b   l  e  m

   D  a   t  e  o   f

  r  e  c   t   i     c  a   t   i  o  n

   N

  a  m  e  o     s  e  r  v   i  c  e  p  e  r  s  o  n

  o  r  c  o  m  p  a  n  y

    1   2 .   1

   A   I   R   C   O   N   d   I   T   I   O   N   I   N   G ,   m

   E   C   H   A   N   I   C   A   l   v   E   N   T   I   l   A   T   I

   O   N   S   y   S   T   E   m   S

   R   E   F   E   R  :   A   S   /   N   Z   S   3   6   6   6 .   2

Page 246: Essential Safety Maintenance Manual

8/3/2019 Essential Safety Maintenance Manual

http://slidepdf.com/reader/full/essential-safety-maintenance-manual 246/290

Page 247: Essential Safety Maintenance Manual

8/3/2019 Essential Safety Maintenance Manual

http://slidepdf.com/reader/full/essential-safety-maintenance-manual 247/290

E S S E N T I A L S A F E T Y M E A S U R E S M A I N T E N A N C E M A N U A L • B U I L D I N G C O M M I S S I O N

A P P E N D I X C / P A G E 3 3

A p p e n i C - P a r t 2 S a p e l o g S h e e t s

Page 248: Essential Safety Maintenance Manual

8/3/2019 Essential Safety Maintenance Manual

http://slidepdf.com/reader/full/essential-safety-maintenance-manual 248/290

E S S E N T I A L S A F E T Y M E A S U R E S M A I N T E N A N C E M A N U A L • B U I L D I N G C O M M I S S I O N

   N  a

  m  e  o      b  u   i   l   d   i  n   g  :

   N  a  m  e  o     o  w  n  e  r  :

   A   d   d  r  e  s  s  :

   L  e  v

  e   l  o     p  e  r     o  r  m  a  n  c  e  a  n   d     r  e  q  u  e  n  c  y  o     m  a   i  n   t  e  n  a  n  c  e    (  a  s  s  p  e  c   i     e   d  o  n  o  c  c  u  p  a  n  c  y  p  e  r  m   i   t    )  :

   D  a   t  e  o   f

   i  n  s  p  e  c   t   i  o  n

   N  a  m  e  a  n   d  a   d   d  r  e  s  s  o     p  e

  r  s  o  n

  c  o  n   d  u  c   t   i  n   g   i  n  s  p  e  c   t   i  o  n

   P  r  o   b   l  e  m  s   i   d  e  n   t   i     e   d

   i  n   i  n  s  p  e  c   t   i  o  n

   A  c   t   i  o  n   t  a   k  e  n   t

  o

  r  e  c   t   i     y  p  r  o   b   l  e  m

   D  a   t  e  o   f

  r  e  c   t   i     c  a   t   i  o  n

   S   i   g  n  a   t  u  r  e

A P P E N D I X C / P A G E 3 4

    1 .   1

   E   m   E   R   G   E   N   C   y   l   I      T   S

Page 249: Essential Safety Maintenance Manual

8/3/2019 Essential Safety Maintenance Manual

http://slidepdf.com/reader/full/essential-safety-maintenance-manual 249/290

E S S E N T I A L S A F E T Y M E A S U R E S M A I N T E N A N C E M A N U A L • B U I L D I N G C O M M I S S I O N

   N  a

  m  e  o      b  u   i   l   d   i  n   g  :

   N  a  m  e  o     o  w  n  e  r  :

   A   d   d  r  e  s  s  :

   L  e  v

  e   l  o     p  e  r     o  r  m  a  n  c  e  a  n   d     r  e  q  u  e  n  c  y  o     m  a   i  n   t  e  n  a  n  c  e    (  a  s  s  p  e  c   i     e   d  o  n  o  c  c  u  p  a  n  c  y  p  e  r  m   i   t    )  :

   D  a   t  e  o   f

   i  n  s  p  e  c   t   i  o  n

   N  a  m  e  a  n   d  a   d   d  r  e  s  s  o     p  e

  r  s  o  n

  c  o  n   d  u  c   t   i  n   g   i  n  s  p  e  c   t   i  o  n

   P  r  o   b   l  e  m  s   i   d  e  n   t   i     e   d

   i  n   i  n  s  p  e  c   t   i  o  n

   A  c   t   i  o  n   t  a   k  e  n   t

  o

  r  e  c   t   i     y  p  r  o   b   l  e  m

   D  a   t  e  o   f

  r  e  c   t   i     c  a   t   i  o  n

   S   i   g  n  a   t  u  r  e

A P P E N D I X C / P A G E 3 5

    1 .   2

   E   x   I   T   d   O   O   R   S

Page 250: Essential Safety Maintenance Manual

8/3/2019 Essential Safety Maintenance Manual

http://slidepdf.com/reader/full/essential-safety-maintenance-manual 250/290

E S S E N T I A L S A F E T Y M E A S U R E S M A I N T E N A N C E M A N U A L • B U I L D I N G C O M M I S S I O N

   N  a

  m  e  o      b  u   i   l   d   i  n   g  :

   N  a  m  e  o     o  w  n  e  r  :

   A   d   d  r  e  s  s  :

   L  e  v

  e   l  o     p  e  r     o  r  m  a  n  c  e  a  n   d     r  e  q  u  e  n  c  y  o     m  a   i  n   t  e  n  a  n  c  e    (  a  s  s  p  e  c   i     e   d  o  n  o  c  c  u  p  a  n  c  y  p  e  r  m   i   t    )  :

   D  a   t  e  o   f

   i  n  s  p  e  c   t   i  o  n

   N  a  m  e  a  n   d  a   d   d  r  e  s  s  o     p  e

  r  s  o  n

  c  o  n   d  u  c   t   i  n   g   i  n  s  p  e  c   t   i  o  n

   P  r  o   b   l  e  m  s   i   d  e  n   t   i     e   d

   i  n   i  n  s  p  e  c   t   i  o  n

   A  c   t   i  o  n   t  a   k  e  n   t

  o

  r  e  c   t   i     y  p  r  o   b   l  e  m

   D  a   t  e  o   f

  r  e  c   t   i     c  a   t   i  o  n

   S   i   g  n  a   t  u  r  e

A P P E N D I X C / P A G E 3 6

    1 .   3

      I   R   E   d   O   O   R   S

   R   E   F   E   R  :   A   S   1   8   5   1 .   7

Page 251: Essential Safety Maintenance Manual

8/3/2019 Essential Safety Maintenance Manual

http://slidepdf.com/reader/full/essential-safety-maintenance-manual 251/290

E S S E N T I A L S A F E T Y M E A S U R E S M A I N T E N A N C E M A N U A L • B U I L D I N G C O M M I S S I O N

   N  a

  m  e  o      b  u   i   l   d   i  n   g  :

   N  a  m  e  o     o  w  n  e  r  :

   A   d   d  r  e  s  s  :

   L  e  v

  e   l  o     p  e  r     o  r  m  a  n  c  e  a  n   d     r  e  q  u  e  n  c  y  o     m  a   i  n   t  e  n  a  n  c  e    (  a  s  s  p  e  c   i     e   d  o  n  o  c  c  u  p  a  n  c  y  p  e  r  m   i   t    )  :

   D  a   t  e  o   f

   i  n  s  p  e  c   t   i  o  n

   N  a  m  e  a  n   d  a   d   d  r  e  s  s  o     p  e

  r  s  o  n

  c  o  n   d  u  c   t   i  n   g   i  n  s  p  e  c   t   i  o  n

   P  r  o   b   l  e  m  s   i   d  e  n   t   i     e   d

   i  n   i  n  s  p  e  c   t   i  o  n

   A  c   t   i  o  n   t  a   k  e  n   t

  o

  r  e  c   t   i     y  p  r  o   b   l  e  m

   D  a   t  e  o   f

  r  e  c   t   i     c  a   t   i  o  n

   S   i   g  n  a   t  u  r  e

A P P E N D I X C / P A G E 3 7

    1 .   4

      I   R   E  -   I   S   O   l   A   T

   E   d   P   A   S   S   A   G   E   w   A   y   S ,   R   A   m

   P   S   &   S   T   A   I   R   S

Page 252: Essential Safety Maintenance Manual

8/3/2019 Essential Safety Maintenance Manual

http://slidepdf.com/reader/full/essential-safety-maintenance-manual 252/290

E S S E N T I A L S A F E T Y M E A S U R E S M A I N T E N A N C E M A N U A L • B U I L D I N G C O M M I S S I O N

   N  a

  m  e  o      b  u   i   l   d   i  n   g  :

   N  a  m  e  o     o  w  n  e  r  :

   A   d   d  r  e  s  s  :

   L  e  v

  e   l  o     p  e  r     o  r  m  a  n  c  e  a  n   d     r  e  q  u  e  n  c  y  o     m  a   i  n   t  e  n  a  n  c  e    (  a  s  s  p  e  c   i     e   d  o  n  o  c  c  u  p  a  n  c  y  p  e  r  m   i   t    )  :

   D  a   t  e  o   f

   i  n  s  p  e  c   t   i  o  n

   N  a  m  e  a  n   d  a   d   d  r  e  s  s  o     p  e

  r  s  o  n

  c  o  n   d  u  c   t   i  n   g   i  n  s  p  e  c   t   i  o  n

   P  r  o   b   l  e  m  s   i   d  e  n   t   i     e   d

   i  n   i  n  s  p  e  c   t   i  o  n

   A  c   t   i  o  n   t  a   k  e  n   t

  o

  r  e  c   t   i     y  p  r  o   b   l  e  m

   D  a   t  e  o   f

  r  e  c   t   i     c  a   t   i  o  n

   S   i   g  n  a   t  u  r  e

A P P E N D I X C / P A G E 3 8

    1 .   5   S   m

   O   k   E   d   O   O   R   S

   R   E   F   E   R  :   A   S   1   8   5   1 .   7

Page 253: Essential Safety Maintenance Manual

8/3/2019 Essential Safety Maintenance Manual

http://slidepdf.com/reader/full/essential-safety-maintenance-manual 253/290

E S S E N T I A L S A F E T Y M E A S U R E S M A I N T E N A N C E M A N U A L • B U I L D I N G C O M M I S S I O N

   N  a

  m  e  o      b  u   i   l   d   i  n   g  :

   N  a  m  e  o     o  w  n  e  r  :

   A   d   d  r  e  s  s  :

   L  e  v

  e   l  o     p  e  r     o  r  m  a  n  c  e  a  n   d     r  e  q  u  e  n  c  y  o     m  a   i  n   t  e  n  a  n  c  e    (  a  s  s  p  e  c   i     e   d  o  n  o  c  c  u  p  a  n  c  y  p  e  r  m   i   t    )  :

   D  a   t  e  o   f

   i  n  s  p  e  c   t   i  o  n

   N  a  m  e  a  n   d  a   d   d  r  e  s  s  o     p  e

  r  s  o  n

  c  o  n   d  u  c   t   i  n   g   i  n  s  p  e  c   t   i  o  n

   P  r  o   b   l  e  m  s   i   d  e  n   t   i     e   d

   i  n   i  n  s  p  e  c   t   i  o  n

   A  c   t   i  o  n   t  a   k  e  n   t

  o

  r  e  c   t   i     y  p  r  o   b   l  e  m

   D  a   t  e  o   f

  r  e  c   t   i     c  a   t   i  o  n

   S   i   g  n  a   t  u  r  e

A P P E N D I X C / P A G E 3 9

    1 .   6

   P   A   T   H   S   O      T   R   A   v   E   l   T   O   E   x   I   T   S

Page 254: Essential Safety Maintenance Manual

8/3/2019 Essential Safety Maintenance Manual

http://slidepdf.com/reader/full/essential-safety-maintenance-manual 254/290

E S S E N T I A L S A F E T Y M E A S U R E S M A I N T E N A N C E M A N U A L • B U I L D I N G C O M M I S S I O N

   N  a

  m  e  o      b  u   i   l   d   i  n   g  :

   N  a  m  e  o     o  w  n  e  r  :

   A   d   d  r  e  s  s  :

   L  e  v

  e   l  o     p  e  r     o  r  m  a  n  c  e  a  n   d     r  e  q  u  e  n  c  y  o     m  a   i  n   t  e  n  a  n  c  e    (  a  s  s  p  e  c   i     e   d  o  n  o  c  c  u  p  a  n  c  y  p  e  r  m   i   t    )  :

   D  a   t  e  o   f

   i  n  s  p  e  c   t   i  o  n

   N  a  m  e  a  n   d  a   d   d  r  e  s  s  o     p  e

  r  s  o  n

  c  o  n   d  u  c   t   i  n   g   i  n  s  p  e  c   t   i  o  n

   P  r  o   b   l  e  m  s   i   d  e  n   t   i     e   d

   i  n   i  n  s  p  e  c   t   i  o  n

   A  c   t   i  o  n   t  a   k  e  n   t

  o

  r  e  c   t   i     y  p  r  o   b   l  e  m

   D  a   t  e  o   f

  r  e  c   t   i     c  a   t   i  o  n

   S   i   g  n  a   t  u  r  e

A P P E N D I X C / P A G E 4 0

    1 .   7

   v   E   H   I   C   u   l   A   R   A   C   C   E   S   S   A   R   O   u   N   d   l   A   R   G   E   I   S   O   l   A   T   E   d   b   u   I   l   d   I   N   G   S

   R   E   F   E   R  :   A   S   1   8   5   1 .   7

Page 255: Essential Safety Maintenance Manual

8/3/2019 Essential Safety Maintenance Manual

http://slidepdf.com/reader/full/essential-safety-maintenance-manual 255/290

E S S E N T I A L S A F E T Y M E A S U R E S M A I N T E N A N C E M A N U A L • B U I L D I N G C O M M I S S I O N

A P P E N D I X C / P A G E 4 1

2.1 EmERGENCy l IGHTING

Name o building: Name o owner:

Address:

Level o perormance and requency o maintenance (as specied on occupancy permit):

Unit TaskRoutine 1

i.e. six MonthsRoutine 2

i.e. twelve MonthsSignature

Battery Charger

Visual inspection o unit

Clean unit and cubicle

Check battery voltage - record voltage

Check all connections

Check voltmeter calibration - record resultCheck battery earth - ault detector operates

Check battery low - voltage alarm operates

Inverter

Visual inspection o unit

Cec D.C. inut oltage - record oltage

Check A.C. output voltage - record voltage

Check voltmeter calibration - record result

Distribution

and controlequipment

Visually inspect - relays, contactors, uses,circuit breakers

Check all connections or tightness

Clean down equipment and enclosures

Check sensing equipment operates systemcorrectly when normal lighting supply isolated

Emergencylights andexit signs

Check all lights operate correctly

Replace aulty lamps

Clean refecting and light emitting suraces

Total system

Check proper operation with battery-charger oand mains supply isolated

Check charger-ailure alarm operates

Check correct battery-charging when systemrestored

Check and record battery voltage ater dischargetest - 100% o lights or at least 90 minutes

Battery-carger cange oer time to “oatcharge” mode, ater “boost” mode selected.Record time

Record battery re-service or replacement

date Nae o person concting inspection Stats Proesientife

Action torecti

date proerectife Signatre

REFER: AS 2293.2

SIx-mONTHly ANd TwElvE-mONTHly PROCEduRES

Page 256: Essential Safety Maintenance Manual

8/3/2019 Essential Safety Maintenance Manual

http://slidepdf.com/reader/full/essential-safety-maintenance-manual 256/290

E S S E N T I A L S A F E T Y M E A S U R E S M A I N T E N A N C E M A N U A L • B U I L D I N G C O M M I S S I O N

A P P E N D I X C / P A G E 4 2

    E   m   E   R   G   E   N   C   y   l   I   G   H   T   I   N   G

   S   y   S   T   E   m

  -   S   I   N   G   l   E   P   O   I   N

   T   l   I   G   H   T   I   N   G

   N  a  m  e  o      b  u   i   l   d   i  n   g  :

   N  a  m  e  o     o  w  n  e  r  :

   A   d   d  r  e  s  s  :

   L  e  v  e   l  o   

  p  e  r     o  r  m  a  n  c  e  a  n   d     r  e  q  u  e  n  c  y  o     m  a   i  n   t  e  n  a  n

  c  e    (  a  s  s  p  e  c   i     e   d  o  n  o  c  c  u  p  a  n  c  y  p  e  r  m   i   t    )  :

   D  a   t  e  o   f   i  n  s  p  e  c   t   i  o  n

   D  a   t  e  o   f

  r  e  c   t   i     c  a   t   i  o  n

   S   i   g  n  a   t  u  r  e

   N  a  m  e  o     p  e  r  s  o  n   i  n  s  p  e  c   t   i  n   g

   L   i   g   h   t   N  u  m   b  e  r

   S   t  a   t  u  s

   1

   2

   3

   4

   5

   6

   7

   8

   9

   1 0

   1 1

   1 2

   1 3

   1 4

   1 5

   1 6

   1 7

   1 8

   1 9

   2 0

   E  n   d  u  r  a  n  c  e  o      b  a   t   t  e  r  y  a      t  e  r

  p  o  w  e  r   t  u  r  n  e   d  o      

   T   i  m  e   i  n   M   i  n  s

    (  a   t   l  e  a  s   t   9   0    )

   F  a  u   l   t  y   l  a  m  p  r  e  p   l  a  c  e   d

       

   i   

  r  e  p   l  a  c  e   d

   P  r  o  p  e  r

     u  n  c   t   i  o  n  o      b  a   t   t  e  r  y

  c   h  a  r   g  e  r   i  n   d   i  c  a   t  o  r

   Y  e  s

      

   N  o

     

   E  n   d  u  r  a  n  c  e  o      b  a   t   t  e  r  y  a      t  e  r

  p  o  w  e  r   t  u  r  n  e   d  o      

   T   i  m  e   i  n   M   i  n  s

    (  a   t   l  e  a  s   t   9   0    )

   F  a  u   l   t  y   l  a  m  p  r  e  p   l  a  c  e   d

       

   i   

  r  e  p   l  a  c  e   d

   P  r  o  p  e  r

     u  n  c   t   i  o  n  o      b  a   t   t  e  r  y

  c   h  a  r   g  e  r   i  n   d   i  c  a   t  o  r

   Y  e  s

      

   N  o

     

   A   l   l   l   i   g   h   t  e  m   i   t   t   i  n   g  a  n   d

  r  e   f  e  c   t   i  n   g  s  u  r     a  c  e  s  c   l  e  a  n  e   d

         w   h  e  n

  c  o  m  p   l  e   t  e   d

   d   a   t   e   o

      i   n   s   p   e   c   t   i   o   n

   N   a      e   o      p   e   r   s   o   n

   c   o   n        c   t   i   n   g

   i   n   s   p   e   c   t   i   o   n

   S   t   a   t     s

   P   r   o         e      s   i      e   n   t   i   f   e      o   n   i   n   s   p   e   c   t   i   o   n

   A   c   t   i   o   n   t   a      e   n   t   o   r   e   c   t   i        p   r   o         e   

   d   a   t   e   o   

   r   e   c   t   i   f   c   a   t   i   o   n

   S   i   g   n   a   t     r   e

   R   E   F   E   R  :   A   S   2   2   9   3 .   2

Page 257: Essential Safety Maintenance Manual

8/3/2019 Essential Safety Maintenance Manual

http://slidepdf.com/reader/full/essential-safety-maintenance-manual 257/290

E S S E N T I A L S A F E T Y M E A S U R E S M A I N T E N A N C E M A N U A L • B U I L D I N G C O M M I S S I O N

A P P E N D I X C / P A G E 4 3

    E   m   E   R   G   E   N

   C   y   l   I   G   H   T   I   N   G   S   y   S   T   E   m   S

  —   b   A   T   T   E   R   I   E   S

   N  a

  m  e  o      b  u   i   l   d   i  n   g  :

   N  a  m  e  o     o  w  n  e  r  :

   A   d   d  r  e  s  s  :

   L  e  v  e   l  o     p  e  r     o  r  m  a  n  c  e  a  n   d     r  e  q  u  e  n  c  y  o     m  a   i  n   t  e  n  a  n  c  e    (  a  s  s  p  e  c   i     e   d  o  n  o  c  c  u  p  a  n  c  y  p  e  r  m   i   t    )  :

   d

   a   t   e

   N   a      e   o      t   e   s   t   e   r

   S   t   a   t     s

   +   P   o   s   i   t   i     e

   C   e      

   N           e   r   s

   N   e   g   a   t   i     e  -

   d   a   t   e

   P   r   o         e

   

   R   e   c   t   i   f   e   

   S   i   g   n   a   t     r   e

   1

   2

   3

   4

   5

   6

   7

   8

   9

   1   0

   1   1

   1   2

   1   3

   1   4

   1   5

   1   6

   L  e  a   d  -  a  c   i   d   b  a   t   t  e  r  y

   E   l  e  c   t  r  o   l  y   t  e   d  e  n  s   i   t  y

   1   0   %  o     c  e   l   l  s  r  a  n   d

  o  m

   R  e  a   d   i  n   g  o      

   h  y   d  r  o  m  e   t  e  r

   1   0   %  o     c  e   l   l  s  r  a  n   d  o  m

   S   t  a   t  e  o     c   h  a  r   g  e

   H   i   g   h  -   H

   M  e   d   i  u  m  -   M

   L  o  w  -   L

   A   l   l   b  a   t   t  e  r   i  e  s

   E   l  e  c   t  r  o   l  y   t  e   l  e  v  e   l

   H ,   ¾ ,   ½ ,   ¼ ,   l  o  w

   A   l   l  c  e   l   l  s

   E   l  e  c   t  r  o   l  y   t  e   l  e  a   k  a   g

  e

   N  e  u   t  r  a   l   i  s  e  s  p   i   l   l  s

   L  e  a   d  -  a  c   i   d   b  a   t   t  e  r  y

   E   l  e  c   t  r  o   l  y   t  e   d  e  n  s   i   t  y

   R  e  a   d   i  n   g  o      

   h  y   d  r  o  m  e   t  e  r

   A   l   l  c  e   l   l  s

   S   t  a   t  e  o     c   h  a  r   g  e

   H   i   g   h  -   H

   M  e   d   i  u  m  -   M

   L  o  w  -   L

   A   l   l   b  a   t   t  e  r   i  e  s

   E   l  e  c   t  r  o   l  y   t  e   l  e  v  e   l

   H ,   ¾ ,   ½ ,   ¼ ,   l  o  w

   A   l   l  c  e   l   l  s

   E   l  e  c   t  r  o   l  y   t  e   l  e  a   k  a   g

  e

   N  e  u   t  r  a   l   i  s  e  s  p   i   l   l  s

   C  e   l   l  c  o  n  n  e  c   t   i  o  n  s  -

  c  o  r  r  o  s   i  o  n ,   t   i   g   h   t  n  e  s  s

        w   h  e  n  c   h  e  c   k  e   d

   C  o  a   t  c  o  n  n  e  c   t   i  o  n  s  w   i   t   h

   t  e  r  m   i  n  a   l  p  r  e  s  e  r  v  a   t   i  v  e

        w   h  e  n  c  o  m  p   l  e   t  e   d

   I  n

   d   i  v   i   d  u  a   l  c  e   l   l  v  o   l   t  a   g  e

   N  o   t  e  a  n  y  >   + .   0   3   V

   O

  v  e  r  a   l   l   b  a   t   t  e  r  y  v  o   l   t  a   g  e

   R  e  a   d   i  n   g  o        v  o   l   t  m  e   t  e  r

   R   E   F   E   R  :   A   S   2   2   9   3 .   2

   d

   a   t   e

   N   a      e   a   n      a         r   e   s   s   o      p   e   r   s   o   n   c   o   n        c   t   i   n   g   i   n   s   p   e   c   t   i   o   n

   P   r   o         e      s   i      e   n   t   i   f   e      o   n   i   n   s   p   e   c   t   i   o   n

   A   c   t   i   o   n   t   a      e   n   t   o   r   e   c   t   i        p   r   o         e   

   d   a   t   e   p   r   o         e   

   r   e   c   t   i   f   e   

   S   i   g   n   a   t     r   e

Page 258: Essential Safety Maintenance Manual

8/3/2019 Essential Safety Maintenance Manual

http://slidepdf.com/reader/full/essential-safety-maintenance-manual 258/290

Page 259: Essential Safety Maintenance Manual

8/3/2019 Essential Safety Maintenance Manual

http://slidepdf.com/reader/full/essential-safety-maintenance-manual 259/290

E S S E N T I A L S A F E T Y M E A S U R E S M A I N T E N A N C E M A N U A L • B U I L D I N G C O M M I S S I O N

A P P E N D I X C / P A G E 4 5

    2 .   3   E   m   E   R   G   E   N   C   y   w   A   R   N   I   N   G   A   N   d   I   N   T   E   R   C   O   m   m   u   N   I   C   A   T

   I   O   N   S   y   S   T   E   m

   N  a

  m  e  o      b  u   i   l   d   i  n   g  :

   N  a  m  e  o     o  w  n  e  r  :

   A   d   d  r  e  s  s  :

   L  e  v

  e   l  o     p  e  r     o  r  m  a  n  c  e  a  n   d     r  e  q  u  e  n  c  y  o     m  a   i  n   t  e  n  a  n  c  e    (  a  s  s  p  e  c   i     e   d  o  n  o  c  c  u  p  a  n  c  y  p  e  r  m   i   t    )  :

   D  a   t  e  o   f

   i  n  s  p  e  c   t   i  o  n

   D  e     c   i  e  n  c   i  e  s   i   d  e  n   t   i     e   d

  r  e  q  u   i  r   i  n   g  r  e  c   t   i     c  a   t   i  o  n

   F  a  u   l   t  s     o  u  n   d  a  n   d

  r  e  m  e   d   i  a   l  a  c   t   i  o  n

   R  e  c  o  r   d  o     a  u   t   h  o  r   i  z  e   d

   d   i  s  c  o  n  n  e  c   t   i  o  n  o  r  r  e  m  o  v  a   l

   D  a   t  e  r  e  c  o  m  m  e  n   d  e   d

  c  o  r  r  e  c   t   i  v  e  a  c   t   i  o  n  c  o  m  p   l  e   t  e   d

   R  e  c  o  r   d  o     p  a  r   t  o      t   h  e

  s  y  s   t  e  m  n  o   t  o  p  e  r  a   t   i  n   g

   S   i   g  n  a   t  u  r  e  o     o  w  n  e  r

   S   i   g  n  a   t  u  r  e  o   

  m  a   i  n   t  e  n  a  n  c  e  p  e  r  s  o  n  n  e   l

   R   E   F   E   R  :   A   S   1   8   5   1 .   1   0

Page 260: Essential Safety Maintenance Manual

8/3/2019 Essential Safety Maintenance Manual

http://slidepdf.com/reader/full/essential-safety-maintenance-manual 260/290

E S S E N T I A L S A F E T Y M E A S U R E S M A I N T E N A N C E M A N U A L • B U I L D I N G C O M M I S S I O N

A P P E N D I X C / P A G E 4 6

    2 .   4

   E   x   I   T   S   I   G   N   S

   N  a

  m  e  o      b  u   i   l   d   i  n   g  :

   N  a  m  e  o     o  w  n  e  r  :

   A   d   d  r  e  s  s  :

   L  e  v

  e   l  o     p  e  r     o  r  m  a  n  c  e  a  n   d     r  e  q  u  e  n  c  y  o     m  a   i  n   t  e  n  a  n  c  e    (  a  s  s  p  e  c   i     e   d  o  n  o  c  c  u  p  a  n  c  y  p  e  r  m   i   t    )  :

   D  a   t  e  o   f

   i  n  s  p  e  c   t   i  o  n

   N  a  m  e  a  n   d  a   d   d  r  e  s  s  o     p  e

  r  s  o  n

  c  o  n   d  u  c   t   i  n   g   i  n  s  p  e  c   t   i  o  n

   P  r  o   b   l  e  m  s   i   d  e  n   t   i     e   d

   i  n   i  n  s  p  e  c   t   i  o  n

   A  c   t   i  o  n   t  a   k  e  n   t

  o

  r  e  c   t   i     y  p  r  o   b   l  e  m

   D  a   t  e  o   f

  r  e  c   t   i     c  a   t   i  o  n

   S   i   g  n  a   t  u  r  e

   R   E   F   E   R  :   A   S   2   2   9   3 .   2

Page 261: Essential Safety Maintenance Manual

8/3/2019 Essential Safety Maintenance Manual

http://slidepdf.com/reader/full/essential-safety-maintenance-manual 261/290

E S S E N T I A L S A F E T Y M E A S U R E S M A I N T E N A N C E M A N U A L • B U I L D I N G C O M M I S S I O N

A P P E N D I X C / P A G E 4 7

   N  a

  m  e  o      b  u   i   l   d   i  n   g  :

   N  a  m  e  o     o  w  n  e  r  :

   A   d   d  r  e  s  s  :

   L  e  v

  e   l  o     p  e  r     o  r  m  a  n  c  e  a  n   d     r  e  q  u  e  n  c  y  o     m  a   i  n   t  e  n  a  n  c  e    (  a  s  s  p  e  c   i     e   d  o  n  o  c  c  u  p  a  n  c  y  p  e  r  m   i   t    )  :

   D  a   t  e  o   f

   i  n  s  p  e  c   t   i  o  n

   N  a  m  e  a  n   d  a   d   d  r  e  s  s  o     p  e

  r  s  o  n

  c  o  n   d  u  c   t   i  n   g   i  n  s  p  e  c   t   i  o  n

   P  r  o   b   l  e  m  s   i   d  e  n   t   i     e   d

   i  n   i  n  s  p  e  c   t   i  o  n

   A  c   t   i  o  n   t  a   k  e  n   t

  o

  r  e  c   t   i     y  p  r  o   b   l  e  m

   D  a   t  e  o   f

  r  e  c   t   i     c  a   t   i  o  n

   S   i   g  n  a   t  u  r  e

    3 .   1

      I   R   E   C   O   N   T

   R   O   l   C   E   N   T   R   E

Page 262: Essential Safety Maintenance Manual

8/3/2019 Essential Safety Maintenance Manual

http://slidepdf.com/reader/full/essential-safety-maintenance-manual 262/290

E S S E N T I A L S A F E T Y M E A S U R E S M A I N T E N A N C E M A N U A L • B U I L D I N G C O M M I S S I O N

A P P E N D I X C / P A G E 4 8

3.2 IRE dETECTION ANd AlARm SySTEmS, IRE bRIGAdECONNECTIONS ANd IRE CONT ROl PANElS

wee checs

Week 1 Week 2 Week 3 Week 4 Week 5

1.1 Fire alarm signal simulation

1.2 Fire alarm bell or warningdevice operation

1.3 Installation reset to normal

1.4 Battery condition

1.5 All switches returned to correct

1.6 Fire alarm signal received at recontrol station

DATE (eely) _____________ _____________ _____________ _____________ _____________

mONTHly CHECkEd yEARly CHECkEd

2.1 All weekly procedures   3.1 All weekly and monthlyprocedures

 2.2 Alarm zone acility operation   3.2 Visual inspection o all detectors and

sampling points 

2.3 Battery condition and terminals   3.3 Fault signal registration or each alarmzone

 2.4 Condition o battery cabinet and battery

storage  3.4 Detector and samling oint testing, as

appropriate 

2.5 Indicator lights correct operation   Enter results on detector test record(see Appendix C)

 2.6 All alarms bells and signaling devices

operation  3.5 Correct operation o all ancillary

control acility 

2.7 Fault condition simulation on allalarm zones and ensure:

  3.6 Correct initiation o each controlleddevice

2.8 All CIE equipment clean and operative   3.7 Oeration of all manual call oints  2.9 All FIP, SIP, RP, and MP clearly visible and

readily accessible  3.8 Power supply supervision alarm  

2.10 All controls returned to normal condition   3.9 Control and indicating or deterioration  2.11 Correct o items previously recorded or

action  3.10 Modication to the system

1. Detector condition2. Building modications

 

3.11 Spare glasses or manual call points  

Place a tick 4 in box where item is satisactory

Place a cross 6in box where item is unsatisactory

NOTE: Gie details of all unsatisfactory items in REpORT section

Name o building: __________________________________________________ Maintenance organisation: _____________________

Address: ________________________________________________________________________________________________________

Telephone: ______________________________________________________________________________________________________

REpORTS

 

SIGNED:_________________________________________ SERvICE pERSON: _________________________________________________

For owner or his agent Print Name

DATE:____________________________________________ ________________________________

REFER: AS 1851.8

Page 263: Essential Safety Maintenance Manual

8/3/2019 Essential Safety Maintenance Manual

http://slidepdf.com/reader/full/essential-safety-maintenance-manual 263/290

E S S E N T I A L S A F E T Y M E A S U R E S M A I N T E N A N C E M A N U A L • B U I L D I N G C O M M I S S I O N

A P P E N D I X C / P A G E 4 9

    3 .   3

      I   R   E   E   x   T   I   N   G   u   I   S   H   E   R   S  —   P   O   R   T   A   b   l   E

   N  a

  m  e  o      b  u   i   l   d   i  n   g  :

   N  a  m  e  o     o  w  n  e  r  :

   A   d   d  r  e  s  s  :

   L  e  v

  e   l  o     p  e  r     o  r  m  a  n  c  e  a  n   d     r  e  q  u  e  n  c  y  o     m  a   i  n   t  e  n  a  n  c  e    (  a  s  s  p  e  c   i     e   d  o  n  o  c  c  u  p  a  n  c  y  p  e  r  m   i   t    )  :

   R   E   F   E   R  :   A   S   1   8   5   1 .   1

Level 5Ater use

 

    Y   e   a   r    6

Level 46 Yearly(end o year 6)

Level 1Mid year 6

    Y   e   a   r    5

Level 2(end o year 5)

Level 1Mid year 5

    Y   e   a   r    4

Level 2(end o year 4)

Level 1Mid year 4

    Y   e   a   r    3

Level 33 Yearly

(end o year 3)

Level 1Mid year 3

    Y   e   a   r    2

Level 2(end o year 2)

Level 1Mid year 2

    Y   e   a   r    1

Level 2Yearly

Level 16 monthly

Extinguisher No.

Page 264: Essential Safety Maintenance Manual

8/3/2019 Essential Safety Maintenance Manual

http://slidepdf.com/reader/full/essential-safety-maintenance-manual 264/290

E S S E N T I A L S A F E T Y M E A S U R E S M A I N T E N A N C E M A N U A L • B U I L D I N G C O M M I S S I O N

A P P E N D I X C / P A G E 5 0

    3 .   4

      I   R   E   H   O   S   E   R   E   E   l   S

 ,      I   R   E   m   A   I   N   S

   N  a  m  e  o      b  u   i   l   d   i  n   g  :

   N  a  m  e  o     o  w  n  e  r  :

   A   d   d

  r  e  s  s  :

   L  e  v  e   l  o     p  e  r     o  r  m  a  n  c  e  a  n   d     r  e  q  u  e  n  c  y  o     m  a   i  n   t

  e  n  a  n  c  e    (  a  s  s  p  e  c   i     e   d  o  n  o  c  c  u  p  a  n  c  y  p  e  r  m   i   t

    )  :

   H  o  s  e  r  e  e   l

   N

  o .   l  o  c  a   t   i  o  n

   R  o  u   t   i  n  e   1  —    i .  e .  s   i  x  -  m  o  n   t   h   l  y

   R  o  u   t   i  n  e   2  —    i .  e .   t  w  e   l  v  e  -  m  o  n   t   h   l  y

   D  a   t  e

   P  r  o   b   l  e  m

  s   i   d  e  n   t   i     e   d

   P  r  o   b   l  e  m  s  r  e  c   t   i     e   d

   S   i   g  n  a   t  u  r  e

   D  a   t  e

   P  r  o

   b   l  e  m  s   i   d  e  n   t   i     e   d

   P  r  o   b   l  e  m  s  r  e  c   t   i     e   d

   S   i   g  n  a   t  u  r  e

   R   E   F   E   R  :   A   S   1   8   5   1 .   2

Page 265: Essential Safety Maintenance Manual

8/3/2019 Essential Safety Maintenance Manual

http://slidepdf.com/reader/full/essential-safety-maintenance-manual 265/290

Page 266: Essential Safety Maintenance Manual

8/3/2019 Essential Safety Maintenance Manual

http://slidepdf.com/reader/full/essential-safety-maintenance-manual 266/290

E S S E N T I A L S A F E T Y M E A S U R E S M A I N T E N A N C E M A N U A L • B U I L D I N G C O M M I S S I O N

A P P E N D I X C / P A G E 5 2

Hydrant record card (yearly, three-yearly and six yearly inspection, testing and maintenance)

Building :______________________________________________________________________________________________________

Maintenance organisation: ______________________________________________________Telephone: ______________________

Address: ______________________________________________________________________________________________________

Place tick 4 a in box where item is satisactoryPlace a cross 6 in box where item is unsatisactory

NOTE: Gie details of all unsatisfactory items in REpORT section

year checs

4.1 All weekly, monthly and quarterly checks

4.2 Alarm wiring and connectors

4.3 Hydrant presence o water

4.4 Tank inspection

4.5 Clean and maintain pipework

4.6 Electric pump starter operation and maintenance

4.7 Filter

4.8 Lubricating oil

Date (yearly) ____

Three-ear checs

5.1 All weekly, monthly, quarterly and yearly checks

5.2 Hydrant presence o water

5.3 Flow test

5.4 Clean tanks

5.5 Oeraul ressure reducing ales

5.6 Oeraul non-return ales

5.7 Test fow switch

Date (tree-yearly) ____

Si-ear checs

6.1 All weekly, monthly, quarterly, yearly andthree-yearly checks

6.2 Hydrostatic test

Date (si-yearly) ____

 

Report:

Hydrant identication (I necessary): _____________________________________Location: ________________________________

Date of manufacture:___________________________________________________Date of serice: ___________________________

_______________________________________________________________________________________________________________

_______________________________________________________________________________________________________________

_______________________________________________________________________________________________________________

_______________________________________________________________________________________________________________

IRE HydRANTS, IRE mAINSREFER: AS 1851.4

ROuTINE 3- yEARly, THREE-yEARly, SIx-yEARly

Page 267: Essential Safety Maintenance Manual

8/3/2019 Essential Safety Maintenance Manual

http://slidepdf.com/reader/full/essential-safety-maintenance-manual 267/290

E S S E N T I A L S A F E T Y M E A S U R E S M A I N T E N A N C E M A N U A L • B U I L D I N G C O M M I S S I O N

A P P E N D I X C / P A G E 5 3

    3 .   6

   S   m

   O   k   E   A   l   A   R   m   S

   N  a

  m  e  o      b  u   i   l   d   i  n   g  :

   N  a  m  e  o     o  w  n  e  r  :

   A   d   d  r  e  s  s  :

   L  e  v

  e   l  o     p  e  r     o  r  m  a  n  c  e  a  n   d     r  e  q  u  e  n  c  y  o     m  a   i  n   t  e  n  a  n  c  e    (  a  s  s  p  e  c   i     e   d  o  n  o  c  c  u  p  a  n  c  y  p  e  r  m   i   t    )  :

   D  a   t  e  o   f

   i  n  s  p  e  c   t   i  o  n

   N  a  m  e  a  n   d  a   d   d  r  e  s  s  o     p  e

  r  s  o  n

  c  o  n   d  u  c   t   i  n   g   i  n  s  p  e  c   t   i  o  n

   P  r  o   b   l  e  m  s   i   d  e  n   t   i     e   d

   i  n   i  n  s  p  e  c   t   i  o  n

   A  c   t   i  o  n   t  a   k  e  n   t

  o

  r  e  c   t   i     y  p  r  o   b   l  e  m

   D  a   t  e  o   f

  r  e  c   t   i     c  a   t   i  o  n

   S   i   g  n  a   t  u  r  e

Page 268: Essential Safety Maintenance Manual

8/3/2019 Essential Safety Maintenance Manual

http://slidepdf.com/reader/full/essential-safety-maintenance-manual 268/290

E S S E N T I A L S A F E T Y M E A S U R E S M A I N T E N A N C E M A N U A L • B U I L D I N G C O M M I S S I O N

A P P E N D I X C / P A G E 5 4

SmOkE AlARmSREFER: AS 1851.8

wee checs

Week 1 Week 2 Week 3 Week 4 Week 5

1.1 Fire alarm signal simulation

1.2 Fire alarm bell or warningdevice operation

1.3 Installation reset to normal

1.4 Battery condition

1.5 All switches returned to correct

1.6 Fire alarm signal received at recontrol station

DATE (eely) _____________ _____________ _____________ _____________ _____________

mONTHly CHECkEd yEARly CHECkEd

2.1 All weekly procedures   3.1 All weekly and monthlyprocedures

 2.2 Alarm zone acility operation   3.2 Visual inspection o all detectors and

sampling points 

2.3 Battery condition and terminals   3.3 Fault signal registration or each alarmzone

 2.4 Condition o battery cabinet and battery

storage  3.4 Detector and samling oint testing, as

appropriate 

2.5 Indicator lights correct operation   Enter results on detector test record(see Appendix C)

 2.6 All alarms bells and signaling devices

operation  3.5 Correct operation o all ancillary

control acility 

2.7 Fault condition simulation on allalarm zones and ensure:

  3.6 Correct initiation o each controlleddevice

2.8 All CIE equipment clean and operative   3.7 Oeration of all manual call oints  2.9 All FIP, SIP, RP, and MP clearly visible and

readily accessible  3.8 Power supply supervision alarm  

2.10 All controls returned to normal condition   3.9 Control and indicating or deterioration  2.11 Correct o items previously recorded or

action  3.10 Modication to the system

1. Detector condition2. Building modications

 

3.11 Spare glasses or manual call points  

Place a tick 4 in box where item is satisactory

Place a cross 6in box where item is unsatisactory

NOTE: Gie details of all unsatisfactory items in REpORT section

Name o building: __________________________________________________ Maintenance organisation: _____________________

Address: ________________________________________________________________________________________________________

Telephone: ______________________________________________________________________________________________________

REpORTS

 

SIGNED:_________________________________________ SERvICE pERSON: _____________________________________________ For owner or his agent Print Name

DATE:____________________________________________ ________________________________Signature

Page 269: Essential Safety Maintenance Manual

8/3/2019 Essential Safety Maintenance Manual

http://slidepdf.com/reader/full/essential-safety-maintenance-manual 269/290

E S S E N T I A L S A F E T Y M E A S U R E S M A I N T E N A N C E M A N U A L • B U I L D I N G C O M M I S S I O N

A P P E N D I X C / P A G E 5 5

3.7 SPRINklER SySTEmS

Name o building: Name o owner:

Address:

Level o perormance and requency o maintenance (as specied on occupancy permit):

Routine Date Problems Identied Remedial Action Taken Name o Tester Signature

1. Level 1

2. Level 1

3. Level 1

4. Level 1

5. Level 1

6. Level 1

7. Level 1

8. Level 1

9. Level 1

10. Level 1

11. Level 1

12. Level 1

13. Level 1

14. Level 1

REFER: AS 1851.3

ROuTINE—lEvEl 1 - wEEkly

Page 270: Essential Safety Maintenance Manual

8/3/2019 Essential Safety Maintenance Manual

http://slidepdf.com/reader/full/essential-safety-maintenance-manual 270/290

E S S E N T I A L S A F E T Y M E A S U R E S M A I N T E N A N C E M A N U A L • B U I L D I N G C O M M I S S I O N

A P P E N D I X C / P A G E 5 6

SPRINklER SySTEmS

Name o building: Name o owner:

Address:

Level o perormance and requency o maintenance (as specied on occupancy permit):

RoutineLevel

Date Problems Identied Remedial Action Taken Name o Tester Signature

Level 2Quarterly

Level 2

Level 2

Level 2

Level 3Yearly

Level 2

Level 2

Level 2

Level 2

Level 3

Level 2

Level 2

Level 2

Level 2

Level 3

Level 43 Yearly

Level 56 Yearly

REFER: AS 1851.3

ROuTINE—lEvEl 2 - quARTERly, lEvEl 3 - ANNuAllylEvEl 4 - THREE-yEARly, lEvEl 5 - SIx-yEARly(NOTE: Eac ne leel incororates te erformance of eac loer leel)

Page 271: Essential Safety Maintenance Manual

8/3/2019 Essential Safety Maintenance Manual

http://slidepdf.com/reader/full/essential-safety-maintenance-manual 271/290

E S S E N T I A L S A F E T Y M E A S U R E S M A I N T E N A N C E M A N U A L • B U I L D I N G C O M M I S S I O N

A P P E N D I X C / P A G E 5 7

   N  a

  m  e  o      b  u   i   l   d   i  n   g  :

   N  a  m  e  o     o  w  n  e  r  :

   A   d   d  r  e  s  s  :

   L  e  v

  e   l  o     p  e  r     o  r  m  a  n  c  e  a  n   d     r  e  q  u  e  n  c  y  o     m  a   i  n   t  e  n  a  n  c  e    (  a  s  s  p  e  c   i     e   d  o  n  o  c  c  u  p  a  n  c  y  p  e  r  m   i   t    )  :

   D  a   t  e  o   f

   i  n  s  p  e  c   t   i  o  n

   N  a  m  e  a  n   d  a   d   d  r  e  s  s  o     p  e

  r  s  o  n

  c  o  n   d  u  c   t   i  n   g   i  n  s  p  e  c   t   i  o  n

   P  r  o   b   l  e  m  s   i   d  e  n   t   i     e   d

   i  n   i  n  s  p  e  c   t   i  o  n

   A  c   t   i  o  n   t  a   k  e  n   t

  o

  r  e  c   t   i     y  p  r  o   b   l  e  m

   D  a   t  e  o   f

  r  e  c   t   i     c  a   t   i  o  n

   S   i   g  n  a   t  u  r  e

    3 .   8

   S   T   A   T   I   C   w   A   T   E   R   S   u   P   P   l   y

Page 272: Essential Safety Maintenance Manual

8/3/2019 Essential Safety Maintenance Manual

http://slidepdf.com/reader/full/essential-safety-maintenance-manual 272/290

E S S E N T I A L S A F E T Y M E A S U R E S M A I N T E N A N C E M A N U A L • B U I L D I N G C O M M I S S I O N

A P P E N D I X C / P A G E 5 8

3.9 PumPSETS

Pumpsets record (Weekly inspection, testing and maintenance)

Premises: ______________________________________________________________________________________________________

Maintenance organisation: _______________________________________________ Telephone: ______________________________

Address: _______________________________________________________________________________________________________

Place a tick 4 in box where item is satisactoryPlace a cross 6 in box where item is unsatisactory

NOTE: Gie details of all unsatisfactory items in REpORT section

wee

wee checs  1 2 3 4

Storage tank water level

Isolation valves

Pump controller cabinet condition

Battery correct tye

Battery corrosion, damage and security

Battery cabinet condition

Battery oat oltage

Eectric otor rien ppset

Pump start and pressure devices

Vibration and noise

Pump running alarms and lights

Pump under load

Pressure relie/fow control valve

CI engine rien ppset

Water, oil , uel levels and drive beltsPump start devices and pressure

Gland/seal and drain

Pump running alarm and lights

Vibration and noise

Running speed

Water, oil and uel leaks

Alternator/generator operation

Engine stop mechanism

Cooling water discharge

Pump casing air relie valve

Charger ail alarm

Pressure relie/fow control valveWater, oil and uel levels

Service person __________________________________

Signed _________________________________________

Date (weely) __________________________________

Report(s): _________________________________________________________ Signed: ______________________________________

Pumpsets identication (i necessary) _________________________________Date:________________________________________

Location _______________________________________________________________________________________________________

Date of Manufacture _______________________________________________Date in serice _______________________________

REFER: AS 1851.14

ROuTINE 1 wEEkly

For owner or agent

Page 273: Essential Safety Maintenance Manual

8/3/2019 Essential Safety Maintenance Manual

http://slidepdf.com/reader/full/essential-safety-maintenance-manual 273/290

E S S E N T I A L S A F E T Y M E A S U R E S M A I N T E N A N C E M A N U A L • B U I L D I N G C O M M I S S I O N

A P P E N D I X C / P A G E 5 9

Premises: ______________________________________________________________________________________________________

Maintenance organisation: _______________________________________________ Telephone: ______________________________

Address: _______________________________________________________________________________________________________

Place a tick 4 in box where item is satisactoryPlace a cross 6 in box where item is unsatisactory

Write N/A where not applicableNOTE: Gie details of all unsatisfactory items in Reort section.

qarter

qarter 1 2 3 4

All weekly checks

Check isolation valves

Check non-return valves

Check pressure relie/fow control valves

CI engine 

Check condensate drains

Run engine 30 min

Check exhaust system leaksCheck exhaust system guards

Service person__________________________Signed: ____________________________Date:________________________________

Report(s): Signed: _________________________________________________________Date:________________________________

Pumpsets identication (i necessary)

Location___________________________________________________Date of Manufacture_____________________

Date in serice______________

Ppsets recor (year inspection, testing an aintenance)

Premises: ______________________________________________________________________________________________________

Maintenance organisation: _______________________________________________ Telephone: ______________________________

Address: _______________________________________________________________________________________________________

Place a tick 4 in box where item is satisactoryPlace a cross 6 in box where item is unsatisactory

Write N/A where not applicableNOTE: Gie details of all unsatisfactory items in Reort section.

yearAll weekly and quarterly checks

Alarm wiring and connectors

Eectric otor rien ppsets 

Check circuit -breakers/uses

Check motor starter

Check starting sequence

Run pumpset or 30 min

Check phase ail alarm

For owner or agent

For owner or agent

Page 274: Essential Safety Maintenance Manual

8/3/2019 Essential Safety Maintenance Manual

http://slidepdf.com/reader/full/essential-safety-maintenance-manual 274/290

E S S E N T I A L S A F E T Y M E A S U R E S M A I N T E N A N C E M A N U A L • B U I L D I N G C O M M I S S I O N

A P P E N D I X C / P A G E 6 0

CI engine rien ppsets 

Service as per AS 2676

Check, clean or replace lters

Inspect and clean heat exchanger strainer

Run pumpset or 30 min

Flush cooling system

CI engine roo

Check room heating

Check ventilation

vaes an pipeor 

Oeraul pRvs

Test non-return valves

Clean, inspect and repaint piping

Check air release valve

Oeraul ressure reducing/o control valves

Service person__________________________

Signed__________________________

Date__________________________

Reort(s): Signed:________________For oner or agent:____________________________Date:__________________

Pumpsets identication (i necessary)

Location___________________________________________________-

Date of Manufacture_______________________________Date in serice______________

Ppsets recor (Three-ear inspect on, testing an aintenance)

Premises _______________ __________________ ___________________ Maintenance organization________________________

Address_____________ __________________ _______________________Telephone_________ ____________________________

Place tick 4 in box where item is satisactoryPlace6 in box where item is unsatisactory

Write N/A where not applicableNOTE: Gie details of all unsatisfactory items in Reort section.

Three-ear

All weekly, quarterly and yearly checksCI rier

Service

Check all saety guards

Service person__________________________

Signed__________________________

Date__________________________

Report(s): Signed:________________For owner or agent

pumsets identication (if necessary) Date:__________________Location___________________________________________

Date of Manufacture_______________________________Date in serice______________

Page 275: Essential Safety Maintenance Manual

8/3/2019 Essential Safety Maintenance Manual

http://slidepdf.com/reader/full/essential-safety-maintenance-manual 275/290

E S S E N T I A L S A F E T Y M E A S U R E S M A I N T E N A N C E M A N U A L • B U I L D I N G C O M M I S S I O N

A P P E N D I X C / P A G E 6 1

   N  a

  m  e  o      b  u   i   l   d   i  n   g  :

   N  a  m  e  o     o  w  n  e  r  :

   A   d   d  r  e  s  s  :

   L  e  v

  e   l  o     p  e  r     o  r  m  a  n  c  e  a  n   d     r  e  q  u  e  n  c  y  o     m  a   i  n   t  e  n  a  n  c  e    (  a  s  s  p  e  c   i     e   d  o  n  o  c  c  u  p  a  n  c  y  p  e  r  m   i   t    )  :

   D  a   t  e  o   f

   i  n  s  p  e  c   t   i  o  n

   N  a  m  e  a  n   d  a   d   d  r  e  s  s  o     p  e

  r  s  o  n

  c  o  n   d  u  c   t   i  n   g   i  n  s  p  e  c   t   i  o  n

   P  r  o   b   l  e  m  s   i   d  e  n   t   i     e   d

   i  n   i  n  s  p  e  c   t   i  o  n

   A  c   t   i  o  n   t  a   k  e  n   t

  o

  r  e  c   t   i     y  p  r  o   b   l  e  m

   D  a   t  e  o   f

  r  e  c   t   i     c  a   t   i  o  n

   S   i   g  n  a   t  u  r  e

    4 .   1   

   I   R   E   C   u   R   T   A   I   N

Page 276: Essential Safety Maintenance Manual

8/3/2019 Essential Safety Maintenance Manual

http://slidepdf.com/reader/full/essential-safety-maintenance-manual 276/290

E S S E N T I A L S A F E T Y M E A S U R E S M A I N T E N A N C E M A N U A L • B U I L D I N G C O M M I S S I O N

   N  a

  m  e  o      b  u   i   l   d   i  n   g  :

   N  a  m  e  o     o  w  n  e  r  :

   A   d   d  r  e  s  s  :

   L  e  v

  e   l  o     p  e  r     o  r  m  a  n  c  e  a  n   d     r  e  q  u  e  n  c  y  o     m  a   i  n   t  e  n  a  n  c  e    (  a  s  s  p  e  c   i     e   d  o  n  o  c  c  u  p  a  n  c  y  p  e  r  m   i   t    )  :

   D  a   t  e  o   f

   i  n  s  p  e  c   t   i  o  n

   N  a  m  e  a  n   d  a   d   d  r  e  s  s  o     p  e

  r  s  o  n

  c  o  n   d  u  c   t   i  n   g   i  n  s  p  e  c   t   i  o  n

   P  r  o   b   l  e  m  s   i   d  e  n   t   i     e   d

   i  n   i  n  s  p  e  c   t   i  o  n

   A  c   t   i  o  n   t  a   k  e  n   t

  o

  r  e  c   t   i     y  p  r  o   b   l  e  m

   D  a   t  e  o   f

  r  e  c   t   i     c  a   t   i  o  n

   S   i   g  n  a   t  u  r  e

A P P E N D I X C / P A G E 6 2

    4 .   2

      I   R   E   I   N   d   I   C   E   S      O   R   m   A   T   E   R   I   A   l   S

Page 277: Essential Safety Maintenance Manual

8/3/2019 Essential Safety Maintenance Manual

http://slidepdf.com/reader/full/essential-safety-maintenance-manual 277/290

   N  a

  m  e  o      b  u   i   l   d   i  n   g  :

   N  a  m  e  o     o  w  n  e  r  :

   A   d   d  r  e  s  s  :

   L  e  v

  e   l  o     p  e  r     o  r  m  a  n  c  e  a  n   d     r  e  q  u  e  n  c  y  o     m  a   i  n   t  e  n  a  n  c  e    (  a  s  s  p  e  c   i   f  e   d  o  n  o  c  c  u  p  a  n  c  y  p  e  r  m   i   t    )  :

   D  a   t  e  o   

   i  n  s  p  e  c   t   i  o  n

   N  a  m  e  a  n   d  a   d   d  r  e  s  s  o     p  e

  r  s  o  n

  c  o  n   d  u  c   t   i  n   g   i  n  s  p  e  c   t   i  o

  n

   P  r  o   b   l  e  m  s   i   d  e  n   t   i   f  e   d

   i  n   i  n  s  p  e  c   t   i  o  n

   A  c   t   i  o  n   t  a   k  e  n   t  o

  r  e  c   t   i     y  p  r  o   b   l  e  m

   D  a   t  e  o   

  r  e  c   t   i   f  c  a   t   i  o  n

   S   i   g  n  a   t  u  r  e

A P P E N D I X C / P A G E 6 3

E S S E N T I A L S A F E T Y M E A S U R E S M A I N T E N A N C E M A N U A L • B U I L D I N G C O M M I S S I O N

    4 .   3

   F   I   R   E  -   I   S   O   L   A   T   E   D 

   L   I   F   T

   S   H   A   F   T   S

Page 278: Essential Safety Maintenance Manual

8/3/2019 Essential Safety Maintenance Manual

http://slidepdf.com/reader/full/essential-safety-maintenance-manual 278/290

E S S E N T I A L S A F E T Y M E A S U R E S M A I N T E N A N C E M A N U A L • B U I L D I N G C O M M I S S I O N

   N  a

  m  e  o      b  u   i   l   d   i  n   g  :

   N  a  m  e  o     o  w  n  e  r  :

   A   d   d  r  e  s  s  :

   L  e  v

  e   l  o     p  e  r     o  r  m  a  n  c  e  a  n   d     r  e  q  u  e  n  c  y  o     m  a   i  n   t  e  n  a  n  c  e    (  a  s  s  p  e  c   i     e   d  o  n  o  c  c  u  p  a  n  c  y  p  e  r  m   i   t    )  :

   D  a   t  e  o   f

   i  n  s  p  e  c   t   i  o  n

   N  a  m  e  a  n   d  a   d   d  r  e  s  s  o     p  e

  r  s  o  n

  c  o  n   d  u  c   t   i  n   g   i  n  s  p  e  c   t   i  o  n

   P  r  o   b   l  e  m  s   i   d  e  n   t   i     e   d

   i  n   i  n  s  p  e  c   t   i  o  n

   A  c   t   i  o  n   t  a   k  e  n   t

  o

  r  e  c   t   i     y  p  r  o   b   l  e  m

   D  a   t  e  o   f

  r  e  c   t   i     c  a   t   i  o  n

   S   i   g  n  a   t  u  r  e

A P P E N D I X C / P A G E 6 4

    4 .   4   

   I   R   E  -   P   R   O   T   E   C   T   I   v   E   C   O   v   E   R

   I   N   G ,      I   R   E  -   R   A   T   E   d   C   O   N   T

   R   O   l   J   O   I   N   T   S ,

      I   R   E  -   R   A   T   E   d   m   A   T   E   R   I   A

   l   S   A   P   P   l   I   E   d   T   O   b   u   I   l   d   I   N

   G   E   l   E   m   E   N   T   S

Page 279: Essential Safety Maintenance Manual

8/3/2019 Essential Safety Maintenance Manual

http://slidepdf.com/reader/full/essential-safety-maintenance-manual 279/290

E S S E N T I A L S A F E T Y M E A S U R E S M A I N T E N A N C E M A N U A L • B U I L D I N G C O M M I S S I O N

   N  a

  m  e  o      b  u   i   l   d   i  n   g  :

   N  a  m  e  o     o  w  n  e  r  :

   A   d   d  r  e  s  s  :

   L  e  v

  e   l  o     p  e  r     o  r  m  a  n  c  e  a  n   d     r  e  q  u  e  n  c  y  o     m  a   i  n   t  e  n  a  n  c  e    (  a  s  s  p  e  c   i     e   d  o  n  o  c  c  u  p  a  n  c  y  p  e  r  m   i   t    )  :

   D  a   t  e  o   f

   i  n  s  p  e  c   t   i  o  n

   N  a  m  e  a  n   d  a   d   d  r  e  s  s  o     p  e

  r  s  o  n

  c  o  n   d  u  c   t   i  n   g   i  n  s  p  e  c   t   i  o  n

   P  r  o   b   l  e  m  s   i   d  e  n   t   i     e   d

   i  n   i  n  s  p  e  c   t   i  o  n

   A  c   t   i  o  n   t  a   k  e  n   t

  o

  r  e  c   t   i     y  p  r  o   b   l  e  m

   D  a   t  e  o   f

  r  e  c   t   i     c  a   t   i  o  n

   S   i   g  n  a   t  u  r  e

A P P E N D I X C / P A G E 6 5

    4 .   5

      I   R   E  -   R   A   T   E   d   A   C   C   E   S   S   P   A   N   E   l   S

Page 280: Essential Safety Maintenance Manual

8/3/2019 Essential Safety Maintenance Manual

http://slidepdf.com/reader/full/essential-safety-maintenance-manual 280/290

E S S E N T I A L S A F E T Y M E A S U R E S M A I N T E N A N C E M A N U A L • B U I L D I N G C O M M I S S I O N

A P P E N D I X C / P A G E 6 6

   N  a

  m  e  o      b  u   i   l   d   i  n   g  :

   N  a  m  e  o     o  w  n  e  r  :

   A   d   d  r  e  s  s  :

   L  e  v

  e   l  o     p  e  r     o  r  m  a  n  c  e  a  n   d     r  e  q  u  e  n  c  y  o     m  a   i  n   t  e  n  a  n  c  e    (  a  s  s  p  e  c   i     e   d  o  n  o  c  c  u  p  a  n  c  y  p  e  r  m   i   t    )  :

   D  a   t  e  o   f

   i  n  s  p  e  c   t   i  o  n

   N  a  m  e  a  n   d  a   d   d  r  e  s  s  o     p  e

  r  s  o  n

  c  o  n   d  u  c   t   i  n   g   i  n  s  p  e  c   t   i  o  n

   P  r  o   b   l  e  m  s   i   d  e  n   t   i     e   d

   i  n   i  n  s  p  e  c   t   i  o  n

   A  c   t   i  o  n   t  a   k  e  n   t

  o

  r  e  c   t   i     y  p  r  o   b   l  e  m

   D  a   t  e  o   f

  r  e  c   t   i     c  a   t   i  o  n

   S   i   g  n  a   t  u  r  e

    4 .   6

      I   R   E  -   R   E   S   I   S   T

   I   N   G   S   H   A      T   S

Page 281: Essential Safety Maintenance Manual

8/3/2019 Essential Safety Maintenance Manual

http://slidepdf.com/reader/full/essential-safety-maintenance-manual 281/290

E S S E N T I A L S A F E T Y M E A S U R E S M A I N T E N A N C E M A N U A L • B U I L D I N G C O M M I S S I O N

A P P E N D I X C / P A G E 6 7

   N  a

  m  e  o      b  u   i   l   d   i  n   g  :

   N  a  m  e  o     o  w  n  e  r  :

   A   d   d  r  e  s  s  :

   L  e  v

  e   l  o     p  e  r     o  r  m  a  n  c  e  a  n   d     r  e  q  u  e  n  c  y  o     m  a   i  n   t  e  n  a  n  c  e    (  a  s  s  p  e  c   i     e   d  o  n  o  c  c  u  p  a  n  c  y  p  e  r  m   i   t    )  :

   D  a   t  e  o   f

   i  n  s  p  e  c   t   i  o  n

   N  a  m  e  a  n   d  a   d   d  r  e  s  s  o     p  e

  r  s  o  n

  c  o  n   d  u  c   t   i  n   g   i  n  s  p  e  c   t   i  o  n

   P  r  o   b   l  e  m  s   i   d  e  n   t   i     e   d

   i  n   i  n  s  p  e  c   t   i  o  n

   A  c   t   i  o  n   t  a   k  e  n   t

  o

  r  e  c   t   i     y  p  r  o   b   l  e  m

   D  a   t  e  o   f

  r  e  c   t   i     c  a   t   i  o  n

   S   i   g  n  a   t  u  r  e

    4 .   7

      I   R   E  -   R   E   S   I   S   T   I   N   G   S   T   R   u   C   T   u   R   E   S

Page 282: Essential Safety Maintenance Manual

8/3/2019 Essential Safety Maintenance Manual

http://slidepdf.com/reader/full/essential-safety-maintenance-manual 282/290

E S S E N T I A L S A F E T Y M E A S U R E S M A I N T E N A N C E M A N U A L • B U I L D I N G C O M M I S S I O N

   N  a

  m  e  o      b  u   i   l   d   i  n   g  :

   N  a  m  e  o     o  w  n  e  r  :

   A   d   d  r  e  s  s  :

   L  e  v

  e   l  o     p  e  r     o  r  m  a  n  c  e  a  n   d     r  e  q  u  e  n  c  y  o     m  a   i  n   t  e  n  a  n  c  e    (  a  s  s  p  e  c   i     e   d  o  n  o  c  c  u  p  a  n  c  y  p  e  r  m   i   t    )  :

   D  a   t  e  o   f

   i  n  s  p  e  c   t   i  o  n

   N  a  m  e  a  n   d  a   d   d  r  e  s  s  o     p  e

  r  s  o  n

  c  o  n   d  u  c   t   i  n   g   i  n  s  p  e  c   t   i  o  n

   P  r  o   b   l  e  m  s   i   d  e  n   t   i     e   d

   i  n   i  n  s  p  e  c   t   i  o  n

   A  c   t   i  o  n   t  a   k  e  n   t

  o

  r  e  c   t   i     y  p  r  o   b   l  e  m

   D  a   t  e  o   f

  r  e  c   t   i     c  a   t   i  o  n

   S   i   g  n  a   t  u  r  e

A P P E N D I X C / P A G E 6 8

    4 .   8

      I   R   E   S   H   u   T   T   E   R   S ,      I   R

   E   w   I   N   d   O   w   S

Page 283: Essential Safety Maintenance Manual

8/3/2019 Essential Safety Maintenance Manual

http://slidepdf.com/reader/full/essential-safety-maintenance-manual 283/290

E S S E N T I A L S A F E T Y M E A S U R E S M A I N T E N A N C E M A N U A L • B U I L D I N G C O M M I S S I O N

   N  a

  m  e  o      b  u   i   l   d   i  n   g  :

   N  a  m  e  o     o  w  n  e  r  :

   A   d   d  r  e  s  s  :

   L  e  v

  e   l  o     p  e  r     o  r  m  a  n  c  e  a  n   d     r  e  q  u  e  n  c  y  o     m  a   i  n   t  e  n  a  n  c  e    (  a  s  s  p  e  c   i     e   d  o  n  o  c  c  u  p  a  n  c  y  p  e  r  m   i   t    )  :

   D  a   t  e  o   f

   i  n  s  p  e  c   t   i  o  n

   N  a  m  e  a  n   d  a   d   d  r  e  s  s  o     p  e

  r  s  o  n

  c  o  n   d  u  c   t   i  n   g   i  n  s  p  e  c   t   i  o  n

   P  r  o   b   l  e  m  s   i   d  e  n   t   i     e   d

   i  n   i  n  s  p  e  c   t   i  o  n

   A  c   t   i  o  n   t  a   k  e  n   t

  o

  r  e  c   t   i     y  p  r  o   b   l  e  m

   D  a   t  e  o   f

  r  e  c   t   i     c  a   t   i  o  n

   S   i   g  n  a   t  u  r  e

A P P E N D I X C / P A G E 6 9

    4 .   9

   l   I      T   S  —   w   A   R   N   I

   N   G   S   y   S   T   E   m   S

Page 284: Essential Safety Maintenance Manual

8/3/2019 Essential Safety Maintenance Manual

http://slidepdf.com/reader/full/essential-safety-maintenance-manual 284/290

E S S E N T I A L S A F E T Y M E A S U R E S M A I N T E N A N C E M A N U A L • B U I L D I N G C O M M I S S I O N

A P P E N D I X C / P A G E 7 0

   N  a

  m  e  o      b  u   i   l   d   i  n   g  :

   N  a  m  e  o     o  w  n  e  r  :

   A   d   d  r  e  s  s  :

   L  e  v

  e   l  o     p  e  r     o  r  m  a  n  c  e  a  n   d     r  e  q  u  e  n  c  y  o     m  a   i  n   t  e  n  a  n  c  e    (  a  s  s  p  e  c   i     e   d  o  n  o  c  c  u  p  a  n  c  y  p  e  r  m   i   t    )  :

   D  a   t  e  o   f

   i  n  s  p  e  c   t   i  o  n

   N  a  m  e  a  n   d  a   d   d  r  e  s  s  o     p  e

  r  s  o  n

  c  o  n   d  u  c   t   i  n   g   i  n  s  p  e  c   t   i  o  n

   P  r  o   b   l  e  m  s   i   d  e  n   t   i     e   d

   i  n   i  n  s  p  e  c   t   i  o  n

   A  c   t   i  o  n   t  a   k  e  n   t

  o

  r  e  c   t   i     y  p  r  o   b   l  e  m

   D  a   t  e  o   f

  r  e  c   t   i     c  a   t   i  o  n

   S   i   g  n  a   t  u  r  e

    4

 .   1   0

   l   I   G   H   T   w   E   I   G   H   T   C   O   N

   S   T   R   u   C   T   I   O   N

Page 285: Essential Safety Maintenance Manual

8/3/2019 Essential Safety Maintenance Manual

http://slidepdf.com/reader/full/essential-safety-maintenance-manual 285/290

E S S E N T I A L S A F E T Y M E A S U R E S M A I N T E N A N C E M A N U A L • B U I L D I N G C O M M I S S I O N

A P P E N D I X C / P A G E 7 1

   N  a

  m  e  o      b  u   i   l   d   i  n   g  :

   N  a  m  e  o     o  w  n  e  r  :

   A   d   d  r  e  s  s  :

   L  e  v

  e   l  o     p  e  r     o  r  m  a  n  c  e  a  n   d     r  e  q  u  e  n  c  y  o     m  a   i  n   t  e  n  a  n  c  e    (  a  s  s  p  e  c   i     e   d  o  n  o  c  c  u  p  a  n  c  y  p  e  r  m   i   t    )  :

   D  a   t  e  o   f

   i  n  s  p  e  c   t   i  o  n

   N  a  m  e  a  n   d  a   d   d  r  e  s  s  o     p  e

  r  s  o  n

  c  o  n   d  u  c   t   i  n   g   i  n  s  p  e  c   t   i  o  n

   P  r  o   b   l  e  m  s   i   d  e  n   t   i     e   d

   i  n   i  n  s  p  e  c   t   i  o  n

   A  c   t   i  o  n   t  a   k  e  n   t

  o

  r  e  c   t   i     y  p  r  o   b   l  e  m

   D  a   t  e  o   f

  r  e  c   t   i     c  a   t   i  o  n

   S   i   g  n  a   t  u  r  e

    4 .   1   1

   P   E   N   E   T   R   A   T   I   O   N   S   I   N      I   R   E  -   R   A   T   E   d   S   T   R   u   C   T   u   R   E   S

Page 286: Essential Safety Maintenance Manual

8/3/2019 Essential Safety Maintenance Manual

http://slidepdf.com/reader/full/essential-safety-maintenance-manual 286/290

E S S E N T I A L S A F E T Y M E A S U R E S M A I N T E N A N C E M A N U A L • B U I L D I N G C O M M I S S I O N

   N  a

  m  e  o      b  u   i   l   d   i  n   g  :

   N  a  m  e  o     o  w  n  e  r  :

   A   d   d  r  e  s  s  :

   L  e  v

  e   l  o     p  e  r     o  r  m  a  n  c  e  a  n   d     r  e  q  u  e  n  c  y  o     m  a   i  n   t  e  n  a  n  c  e    (  a  s  s  p  e  c   i     e   d  o  n  o  c  c  u  p  a  n  c  y  p  e  r  m   i   t    )  :

   D  a   t  e  o   f

   i  n  s  p  e  c   t   i  o  n

   N  a  m  e  a  n   d  a   d   d  r  e  s  s  o     p  e

  r  s  o  n

  c  o  n   d  u  c   t   i  n   g   i  n  s  p  e  c   t   i  o  n

   P  r  o   b   l  e  m  s   i   d  e  n   t   i     e   d

   i  n   i  n  s  p  e  c   t   i  o  n

   A  c   t   i  o  n   t  a   k  e  n   t

  o

  r  e  c   t   i     y  p  r  o   b   l  e  m

   D  a   t  e  o   f

  r  e  c   t   i     c  a   t   i  o  n

   S   i   g  n  a   t  u  r  e

A P P E N D I X C / P A G E 7 2

    5 .   1

   A   I   R   C   O   N   d   I   T   I   O   N   I   N   G ,   m

   E   C   H   A   N   I   C   A   l   v   E   N   T   I   l   A   T   I

   O   N   S   y   S   T   E   m   S

   R   E   F   E   R  :   A   S   /   N   Z   S   3   6   6   6 .   2

Page 287: Essential Safety Maintenance Manual

8/3/2019 Essential Safety Maintenance Manual

http://slidepdf.com/reader/full/essential-safety-maintenance-manual 287/290

E S S E N T I A L S A F E T Y M E A S U R E S M A I N T E N A N C E M A N U A L • B U I L D I N G C O M M I S S I O N

A P P E N D I X C / P A G E 7 3

   L  e  v  e   l  o     p  e  r     o  r  m  a  n  c  e  a  n   d     r  e  q  u  e  n  c  y  o     m  a   i  n   t  e  n  a  n  c  e    (  a  s  s  p  e  c   i     e   d  o  n  o  c  c  u  p  a  n  c  y  p  e  r  m   i   t    )  :______________________________________

________________________________________________________

   I   t   e   

   R   o     t   i   n   e

   q     a   r   t   e   r     

   q     a   r   t   e   r     

   S   i   g   n   a   t     r   e

   H

   a        -     e   a   r     

   H   a        -     e   a   r     

   F  a  n  s

   S  u  p  p   l  y  a  n   d  r  e   t  u  r  n  a   i  r

   B   2

   S  m  o   k  e  -  s  p   i   l   l  a  n   d

  a   i  r  -  p  r  e  s  s  u  r   i  s  a   t   i  o  n

   B   2

   M  o   t  o  r  s ,   i  n   d  u  c   t   i  o  n

   F  a  n   d  r   i  v  e  s ,     r  e  q  u  e  n   t

  u  s  e

   B   3

   F  a  n   d  r   i  v  e  s ,   t  e  s   t  a  n   d

  e  m  e  r   g  e  n  c  y  u  s  e  o  n   l  y

   B   3

   B  a   t   t  e  r   i  e  s   f  o  r     r  e   /  s  m  o     e

  c  o  n   t  r  o   l  s  e  r  v   i  c  e  s

   L  e  a   d  -  a  c   i   d   A   S   2   6   7   6

 .   1

   A   l   k  a   l   i  n  e

   A   S   2   6   7   6 .   2

   F   i  r  e   d  a  m  p  e  r  s

   B   4

   Y  e  a  r   l  y

   F   i  r  e  m  o   d  e  a   i  r   d  a  m  p  e  r  s     o  r  s  m  o   k  e  -  s  p   i   l   l ,     r  e  s   h  a   i  r  a  n   d

  r  e  c  y  c   l  e  a   i  r ,  c  o  m  p   l  e   t  e  w   i   t   h   t   h  e   i  r  a  u   t  o  m  a   t   i  c   g  e  a  r

   B   5

   A  u   t  o

  m  a   t   i  c  s  m  o   k  e   d  e   t  e  c   t  o  r  s     o  r     r  e   /  s  m  o   k  e

  c  o  n   t  r  o   l  s  e  r  v   i  c  e  s

    #

   S  e  r  v   i  c  e   d  u  n   d  e  r   S  e  c   t   i  o  n   3 .   2   A   S   1

   8   5   1 .   8   1   3

   A   i  r   

   l   t  e  r  s

   B   6

   E   l  e  c   t  r   i  c   d  u  c   t   h  e  a   t  e  r  s

   B   7

   Y  e  a  r   l  y

   k   i   t  c   h

  e  n  e  x   h  a  u  s   t  s  y  s   t  e  m

   B   8

   A   i  r  -   h

  a  n   d   l   i  n   g  c   h  a  n   g  e  o  v  e  r  u  n   d  e  r     r  e   /  s  m  o   k  e  c  o  n   d   i   t   i  o  n  s

   B   9

   F   i  r  e  -   i  s  o   l  a   t  e   d  e  s  c  a  p  e  r  o  u   t  e  s  p  r  o   t  e  c   t  e   d   b  y

  a   i  r  -  p

  r  e  s  s  u  r   i  s  a   t   i  o  n  s  y  s   t  e  m  s

   B   1   0

   A  u   t  o

  m  a   t   i  c  s  m  o   k  e   /   h  e  a   t  v  e  n   t   i  n   g  s  y  s   t  e  m  s

   S  e  r  v   i  c  e   d  u  n   d  e  r   S  e  c   t   i  o  n   5 .   3   A   S

   1   8   5   1 .   5

   *  r  e   f  e  r  s   t  o  r  o  u   t   i  n  e  s  c  o  n   t  a   i  n  e   d   i  n   A  p  p  e  n   d   i  x   B  o   f   A

   S   1   8   5   1 .   6

   A  n  n  u  a

   l   I  n  s  p  e  c   t   i  o  n  :

   N  a  m  e

  :_______________________

   S   i   g  n  a   t  u  r  e  :____

________________________

   D  a   t  e  :________________

    5 .   2

   S   m   O   k   E   C   O   N   T   R   O   l   m   E   A   S   u   R   E   S ,   S   T   A   I   R   w   E   l   l   P   R   E   S   S

   u   R   I   S   A   T   I   O   N   S   y   S   T   E   m   S ,      I   R   E   d   A   m   P   E   R   S

   R   E   F   E   R  :   A   S   1   8   5   1 .   6

   R   O   u   T   I   N   E  —   l   E   v   E   l   1

Page 288: Essential Safety Maintenance Manual

8/3/2019 Essential Safety Maintenance Manual

http://slidepdf.com/reader/full/essential-safety-maintenance-manual 288/290

E S S E N T I A L S A F E T Y M E A S U R E S M A I N T E N A N C E M A N U A L • B U I L D I N G C O M M I S S I O N

A P P E N D I X C / P A G E 7 4

   L  e  v

  e   l  o     p  e  r     o  r  m  a  n  c  e  a  n   d     r  e  q  u  e  n  c  y  o     m  a   i  n   t

  e  n  a  n  c  e    (  a  s  s  p  e  c   i     e   d  o  n  o  c  c  u  p  a  n  c  y  p  e  r  m   i   t    )  :___________________________________

__________________________________________________________

   I   t  e  m

   R  o  u   t   i  n  e

   Q  u  a  r   t  e  r   l  y

   Q  u  a  r   t  e  r   l  y

   Q  u  a  r   t  e

  r   l  y

   Q  u  a  r   t  e  r   l  y

   T  w  o  -  y  e  a  r   l  y    (   2    )

   F   i  v  e  -  y  e  a  r   l  y    (   5    )

   I      i  n  s  p  e  c   t   i  o  n

   i  n   d   i  c  a   t  e  s  n  e  c  e  s  s   i   t  y

   S   i  x  -  m  o  n   t   h   l  y

   S   i  x  -  m  o  n   t   h   l  y

   F  a

  n  s

   S  u  p  p   l  y  a  n   d  r  e   t  u  r  n  a   i  r

   B   2

   L  e  v  e   l   2

   L  e  v  e   l   2

   L  e  v  e   l   2

   L  e  v  e   l   2

   B   2

   L  e  v  e   l   3

   S  m  o   k  e  -  s  p   i   l   l  a  n   d  a   i  r  -

  p  r  e  s  s  u  r   i  s  a   t   i  o  n

   B   2

   L  e  v  e   l   2

   L  e  v  e   l   3

   M

  o   t  o  r  s ,   i  n   d  u  c   t   i  o  n

   F  a  n   d  r   i  v  e  s ,     r  e  q  u  e  n   t  u  s  e

   B   3

   L  e  v  e   l   2

   L  e  v  e   l   2

   L  e  v  e   l   2

   L  e  v  e   l   2

   L  e  v  e   l   3

   F  a  n   d  r   i  v  e  s ,   t  e  s   t  a  n   d

  e  m  e  r   g  e  n  c  y  u  s  e  o  n   l  y

   B   3

   L  e  v  e   l   2

   L  e  v  e   l   2

    (   2    )   L  e  v  e   l   3

   B  a   t   t  e  r   i  e  s   f  o  r     r  e   /  s  m  o     e  c  o  n   t  r  o   l  s  e  r  v   i  c  e  s

   L  e  a   d  -  a  c   i   d

   A   l   k  a   l   i  n  e

   F   i  r  e   d  a  m  p  e  r  s

   B   4

    (   5    )   L  e  v  e   l   2

   F   i  r  e  m  o   d  e  a   i  r   d  a  m  p  e  r  s     o  r  s  m  o   k  e  -  s  p   i   l   l ,     r  e  s   h

  a   i  r  a  n   d  r  e  c  y  c   l  e  a   i  r ,

  c  o

  m  p   l  e   t  e  w   i   t   h   t   h  e   i  r  a  u   t  o  m  a   t   i  c   g  e  a  r

   B   5

   L  e  v  e   l   2

   A  u   t  o  m  a   t   i  c  s  m  o   k  e   d  e   t  e  c   t  o  r  s     o  r     r  e   /  s  m  o   k  e  c

  o  n   t  r  o   l  s  e  r  v   i  c  e  s

   S  e  r  v   i  c  e   d  u  n   d  e  r   S  e  c   t   i  o  n   3 .   2   A   S   1   8   5   1 .   8

   A   i  r      l   t  e  r  s

   B   6

   L  e  v  e   l   3

   E   l  e  c   t  r   i  c   d  u  c   t   h  e  a   t  e  r  s

   B   7

    (   2    )   L  e  v  e   l   2

    (   5    )   L  e  v  e   l   3

   k   i   t  c   h  e  n  e  x   h  a  u  s   t  s  y  s   t  e  m  s

   B   8

   L  e  v  e   l   3

   A   i  r  -   h  a  n   d   l   i  n   g  c   h  a  n   g  e  o  v  e  r  u  n   d  e  r     r  e   /  s  m  o   k  e  c

  o  n   d   i   t   i  o  n  s

   B   9

   L  e  v  e   l   2

   F   i  r  e  -   i  s  o   l  a   t  e   d  e  s  c  a  p  e  r  o  u   t  e  s  p  r  o   t  e  c   t  e   d   b  y  a   i  r  -  p  r  e  s  s  u  r   i  s  a   t   i  o  n  s  y  s   t  e  m

   B   1   0

   L  e  v  e   l   2

    (   2    )   L  e  v  e   l   3

   A  u   t  o  m  a   t   i  c  s  m  o   k  e   /   h  e  a   t  v  e  n   t   i  n   g  s  y  s   t  e  m  s

   S  e  r  v   i  c  e   d  u  n   d  e  r   S  e  c   t   i  o  n   5 .   3   A   S   1   8   5   1 .   5

   O

  u   t   d  o  o  r  a   i  r   i  n   t  a     e  s

   B   1   1

   L   2

   L   2

   L   2

   L   2

   L   2

   L   2

   L   2

   L   2

   L   2

   L   2

   L   2

   L   2

   *  r  e

   f  e  r  s   t  o  r  o  u   t   i  n  e  s  c  o  n   t  a   i  n  e   d   i  n   A  p  p  e  n   d   i  x   B  o   f   A   S   1   8   5   1 .

   A  n  n  u  a   l   I  n  s  p  e  c   t   i  o  n  :

   N  a  m  e  :__________________________

   S   i   g  n  a   t  u  r  e  :_________________________

   D  a   t  e  :____

______________

    S   m   O   k   E   C   O   N   T   R   O   l ,   S   T   A   I   R   w   E   l   l   P   R   E   S   S

   u   R   I   S   A   T   I   O   N   S   y   S   T   E   m   S ,      I   R   E   d   A   m   P   E   R   S

   R   O   u   T   I   N   E  —   l   E   v   E   l   S   2 ,   3   A   N   d   4

Page 289: Essential Safety Maintenance Manual

8/3/2019 Essential Safety Maintenance Manual

http://slidepdf.com/reader/full/essential-safety-maintenance-manual 289/290

E S S E N T I A L S A F E T Y M E A S U R E S M A I N T E N A N C E M A N U A L • B U I L D I N G C O M M I S S I O N

A P P E N D I X C / P A G E 7 5

   N  a

  m  e  o      b  u   i   l   d   i  n   g  :

   N  a  m  e  o     o  w  n  e  r  :

   A   d   d  r  e  s  s  :

   L  e  v

  e   l  o     p  e  r     o  r  m  a  n  c  e  a  n   d     r  e  q  u  e  n  c  y  o     m  a   i  n   t  e  n  a  n  c  e    (  a  s  s  p  e  c   i     e   d  o  n  o  c  c  u  p  a  n  c  y  p  e  r  m   i   t    )  :

   D  a   t  e  o   f

   i  n  s  p  e  c   t   i  o  n

   I   t  e  m  o     p   l  a  n   t  o  r  e  q  u   i  p  m  e  n   t

   S  e  r  v   i  c  e  p  e  r     o  r  m  e   d

   D  e   f  e  c   t  s   i   d  e  n   t   i     e   d

   i  n   i  n  s  p  e  c   t   i  o  n

   A  c   t   i  o  n   t  a   k  e  n   t  o

  r  e  c

   t   i     y  p  r  o   b   l  e  m

   D  a   t  e  o   f

  r  e  c   t   i     c  a   t   i  o  n

   N  a  m  e  o     s  e  r  v   i  c  e

  p  e  r  s  o  n  o  r  c  o  m  p  a  n  y

 

   S   m   O   k   E   C   O   N   T   R   O   l ,   S   T   A   I   R   w   E   l   l   P   R   E   S   S

   u   R   I   S   A   T   I   O   N   S   y   S   T   E   m   S ,      I   R   E   d   A   m   P   E   R   S

Page 290: Essential Safety Maintenance Manual

8/3/2019 Essential Safety Maintenance Manual

http://slidepdf.com/reader/full/essential-safety-maintenance-manual 290/290

N   T   S

8   5   1 .   5