energy source power system stabilizer ...advancedpstinc.com/wp-content/uploads/2016/05/espss...*...
TRANSCRIPT
Energy Source Power System Stabilizer (ESPSS) Installation on the 10 MW, 40 MWH Battery Energy Storage System at Chino Substation
Bharat Bhargava
Advanced Power System Technologies, Inc
359 Amberwood Drive,
Walnut, CA 91789
1
*Presentation is based on the paper presented at the 1997 Power Tech Conference at New Delhi, India Copyright © 2016 Advanced Power System Technologies, Inc. All Rights Reserved
PRESENTATION OUTLINE
Project Objectives
WSCC Inter-area Oscillations
Southern California’s Dynamic Stability Problem
PSS and ESPSS
Possible Solutions for Damping Inter area oscillations
Chino Battery Energy Storage System
Power Conditioning System for Chino Batteries
ESPSS Project Status and field installation
ESPSS Field Tests and records 2
ENERGY SOURCE POWER SYSTEM
STABILIZER PROJECT OBJECTIVES:
Determine if the Chino Battery Energy Storage Systems (BESS) with ESPSS design can be used to damp inter-area power system oscillations.
Determine if this concept can be extended to application of ESPSS on machine governors to damp power system oscillations.
3
WSCC INTER AREA OSCILLATIONS
Occur at very low frequencies (0.25-1.0 HZ)
Excited by system disturbances like major line faults, generator or load dropping, etc.
Lower frequencies exhibit weaker system
Similar to spring-mass system oscillations
Some of the large areas in WSCC are:
Pacific Northwest, California and Arizona- New Mexico
Oscillations are generally damped in few seconds
Oscillations can grow if system is loaded beyond its capability and result in system breakup
4
SOUTHERN CALIFORNIA’S DYNAMIC STABILITY PROBLEM
California imports up to:
4800 + 3100 MW (DC) from Northwest (BPA)
6000 MW from Arizona-New Mexico
Imports above this level are limited by:
Northwest-Southwest oscillations at 0.3 HZ
California-Arizona oscillations at 0.7 HZ
Line equipment rating usually series capacitors (can be increased)
5
POSSIBLE SOLUTIONS TO REDUCE INTER AREA OSCILLATIONS AND
INCREASE POWER TRANSFERS
Additional transmission line
Additional series compensation in transmission lines
Flexible AC transmission system devices
Energy Source Power System Stabilizers on BES/generators
Super conducting Magnetic Energy Storage
6
CHINO BATTERY ENERGY STORAGE SYSTEM
Ideally located near SCE’s load center
Battery energy storage of 40 MWH is adequate for damping oscillations
Power output limited to 10 MW because of PCS
Batteries could be used for more effective system oscillations damping with a larger size PCS
7
POWER CONDITIONING SYSTEM FOR CHINO BATTERIES
Supplied by GE and installed in 1988
Designed for 2 KV DC, 12.5 KV AC voltage
Continuous rating 10 MW
Short term rating of 11 MW for 1 minute
GTO based, 18 pulse design
Can control MW and MVAR independently
Ideal for ESPSS test application
Required modification to accept input from the
ESPSS
8
TYPICAL POWER SYSTEM
STABILIZERS (PSS)
Applied on electrical generating machines
Control terminal voltage oscillations of the generator through the excitation system
Control mostly the reactive power output of the generators
Have little impact on generator MW output
Have overall slow response because of large time constants of the machine excitation and field system
Have been successfully used for over 25 years
9
ENERGY SOURCE POWER SYSTEM STABILIZER (ESPSS)
Can be installed on the PCS/SMES or other similar energy storage systems
Could also be used with HVDC systems
Can control MW and MVAR output
Could be applied on generating machines through the machine governor to damp inter area oscillations (0.25 - 0.8 HZ)
10
ENERGY SOURCE POWER SYSTEM STABILIZER FOR BATTERY ENERGY
STORAGE SYSTEM
Control the PCS/battery power output
MW control has been designed on system frequency deviation
Existing 10 MW BESS will provide some system damping
Activates only when the frequency diviation exceeds the dead band (0.03 Hz)
Could also control reactive power output of PCS
11
ENERGY SOURCE POWER SYSTEM STABILIZER PROJECT DETAILS
Installed on December 12, 1994
ESPSS Supplied by GE
PCS modified to except signals from ESPSS
PCS modifications required considerable expense
ESPSS has recorded several incidents including December 14, 1994 disturbance, but tripped on over frequency
PCS equipment has had several problems
12
ENERGY SOURCE POWER SYSTEM
STABILIZER SYSTEM PROGRESS
Battery and ESPSS were operational for last fifteen months (December 15, 94 to -March15, 96).
ESPSS performance was monitored and the ESPSS Gain & Time constants were optimized.
Application of ESPSS on generating machines is being investigated
Equipment for ESPSS on a generator governor has been developed and being installed.
13
ENERGY SOURCE POWER SYSTEM STABILIZER FIELD TEST RESULTS
ESPSS can regulate battery power output to damp inter-area oscillations
Would require larger size PCS for higher power transfer increase
10 MW BESS will provide some nominal damping
Tests confirm that ESPSS and the Battery respond fast enough at up to 1 HZ system
oscillations.
14
ENERGY SOURCE POWER SYSTEM STABILIZER FIELD TESTS
Were conducted in December, 94 and December 95.
Monitoring conducted during 1995 and 96.
ESPSS responds to system disturbances as desired.
Test results compare with the simulated results.
Marginal damping was achieved because of the
PCS size.
15
AERIAL VIEW OF THE CHINO BATTERY ENERGY STORAGE
FACILITY
16
ENERGY SOURCE POWER SYSTEM
STABILIZER IN THE PANEL
17
BATTERY ENERGY STORAGE SYSTEM GRID INTERCONECTION
230kV Bus
To Mira Loma500kV/230kV
Substation
1 2 3
To San Onofre 23kVGenerating Station
To Serrano 500kV/230kV
Substation
66kV Bus66kV Bus
3A230/66kV
Bank
2A230/66kV
Bank
1A230/66kV
Bank
66kV Circuits66kVCircuits No. 5
66/12kVBank
No. 466/12kV
Bank
12kV Circuits
AC CircuitBreaker
PowerConditioning
SystemDC Batteries
2kV
PCSTransf.
18
19
POWER CONDITIONING SYSTEM FOR CHINO BATTERIES
Supplied by GE and installed in 1988
Designed for 2 KV DC, 12.5 KV AC voltage
Continuous rating 10 MW
Short term rating of 11 MW for 1 minute
GTO based, 18 pulse design
Can control MW and MVAR independently
Ideal for ESPSS test application
Required modification to accept input from the ESPSS
20
TYPICAL POWER SYSTEM STABILIZERS (PSS)
Applied on electrical generating machines
Control terminal voltage oscillations of the generator through the excitation system
Control mostly the reactive power output of the generators
Have little impact on generator MW output
Have overall slow response because of large time constants of the machine excitation and field system
Have been successfully used for over 25 years
21
ENERGY SOURCE POWER SYSTEM STABILIZER (ESPSS)
Can be installed on the PCS/SMES or other similar energy storage systems
Can be applied on generating machines through the machine governor to damp inter area oscillations (0.25 - 0.8 HZ)
Could also be used with HVDC systems
Can control MW and MVAR output
ENERGY SOURCE POWER SYSTEM STABILIZER FOR BATTERY ENERGY STORAGE SYSTEM
Control the PCS/battery power output
MW control has been designed on system frequency deviation
Existing 10 MW BESS will provide some system damping
Activates only when the frequency diviation exceeds the dead band (0.03 Hz)
Could also control reactive power output of PCS
22
ENERGY SOURCE POWER SYSTEM STABILIZER PROJECT DETAILS
Installed on December 12, 1994
ESPSS Supplied by GE
PCS modified to except signals from ESPSS
PCS modifications required considerable expense
ESPSS has recorded several incidents including December 14, 1994 disturbance, but tripped on over frequency
PCS equipment has had several problems
23
SCE 10 MW, 40 MWh Battery System
Layout at Chino Substation
24
SCE 10 MW, 40 MWh Battery System A
Battery String in the East side Building
25
SCE 10 MW, 40 MWh Battery System
A Power Conditioning System – Supplied by GE
26
ENERGY SOURCE POWER SYSTEM
STABILIZER IN THE PANEL
27
28
ENERGY SOURCE POWER SYSTEM STABILIZER FIELD TESTS*
Were conducted in December, 94 and December 95.
Monitoring conducted during 1995 and 96.
ESPSS responds to system disturbances as desired.
Test results compare with the simulated results.
Marginal damping was achieved because of the PCS size.
Reference:
* “Energy Source Power System Stabilizer Installation on the 10 MW Battery
Energy Storage System at Chino Substation” , presented at the IEEE Summer PES meeting held at Berlin, Germany from July 20-24, 1997.
29
ESPSS PLOTS SHOWING THE FREQUENCY DEVIATION & THE PSS OUTPUT FOR
THE 14/12/94 WSCC SYSTEM DISTURBANCE
30
POWER OUTPUT OF THE BESS FROM A SINUSOIDAL SIGNAL INPUT
TO ESPSS AT 0.05HZ
31
ESPSS INPUT / OUTPUT FROM A
1.0 HZ INJECTION FREQUENCY SIGNAL
32
POWER OUTPUT OF THE BESS FROM A SQUARE WAVE SIGNAL TO
THE ESPSS AT 0.25HZ
0
+10 MW
-10 MW
0
+10 Volts
-10 Volts
0 1 2 3 4
Seconds
Watts
Amps
Trigger
33
ESPSS PLOTS FROM 12/14/94 DISTURBANCE CAUSED BY TRIPPING OF UNITS
AT IPP IN UTAH
ENERGY SOURCE POWER SYSTEM STABILIZER FIELD TEST RESULTS
ESPSS can regulate battery power output to damp inter-area oscillations
Would require larger size PCS for higher power transfer increase
10 MW BESS will provide some nominal damping
Tests confirm that ESPSS and the Battery respond fast enough at up to 1 HZ system oscillations.
34
ENERGY SOURCE POWER SYSTEM STABILIZER SYSTEM PROGRESS
Battery and ESPSS were operational for fifteen months (December 15, 94 to -March15, 96).
ESPSS performance was monitored and the ESPSS Gain & Time constants were optimized.
Application of ESPSS on generating machines was investigated and tests conducted
Equipment for ESPSS on a generator governor has been supplied and is being installed and tested
35
Any Questions?