energy recovery ventilators · energy costs. recover up to 80 percent of sensible and latent energy...
TRANSCRIPT
ENERGY RECOVERY VENTILATORSFOR TODAY’S INDOOR ENVIRONMENTAL QUALITY REQUIREMENTS
Recapture Cooling and Heating Energy Plus Control Humidity Extremes
®
2
Energy Recovery Ventilators▶▶ Maintain an adequate supply of ventilation air while reducing energy costs.▶▶ Recover up to 80 percent of sensible and latent energy from the conditioned air as it is exhausted.▶▶ Reduce extremes in humidity that can encourage mold growth.▶▶ Remove dangerous gases, bacteria, and other airborne impurities from conditioned air.
Mitsubishi Electric’s Lossnay energyrecovery ventilators offer:
▶▶ Unprecedented energy transfer in a fixed-plate component with no moving parts.▶▶ Reasonable paybacks and reduced peak demand.▶▶ Superior part-load per performance, reducing latent load even at mild outdoor temperatures.▶▶ No wheels to stop turning so outside air is always preconditioned and available.
How does the Lossnay®
core work?
Outside Air Makes the Difference!People need outside air for their health and comfort. Unconditioned outdoor air rarely
meets their needs: it’s usually too hot and humid in the summer and too cold and dry
in the winter. To provide the benefit of ventilation, the air must be preconditioned
before being introduced into the occupied space.
Cooled or heated indoor air soon grows stale and must be exhausted to rid the
building of toxins, odors, viruses, bacteria, and other potentially harmful contaminants.
Exhausting that air and replacing it with outside air, which must be conditioned, is
critical to a healthy and productive environment, but it is a process that can be both
costly and inefficient.
If your air-conditioning system utilizes an energy recovery ventilator (ERV), these costs
are greatly minimized. An ERV helps improve the efficiency of air-conditioning systems
by preheating or precooling incoming outside air with the available energy in the stale
exhaust air.
ERVs save money by decreasing the load on your air-conditioning units;
helping remove noxious indoor pollutants, such as formaldehyde, pollen, cigarette
smoke, dust, and carbon dioxide; and helping equalize humidity levels. An ERV is an
efficient and effective step toward improving overall indoor environmental quality.
At the heart of each Mitsubishi Electric Lossnay energy recovery ventilator is a low-maintenance cross-flow energy exchange core constructed of a specially treated cellulose fiber membrane.
The low-maintenance ERV core prevents the inbound air and exhaust air from intermingling while crossing the airflows, thus preconditioning the air by warming it in the wintertime with the warm exhausted air, or by cooling it in the summertime with the cooler exhaust air.
While the airflows are exchanging heat energy by conduction in the ERV core, the humidity in the airstreams seeks to equalize. In the winter cool dry supply air from outside is partially humidified by the moist exhausted air, and the opposite occurs in the summertime. The special treatment and impregnation applied to the transmission plates allows water vapor molecules to pass through so the differing humidity levels move toward equilibrium in the Lossnay core. Larger molecules are unable to pass through the transmission plates, so the outside air is uncontaminated by stale exhausted air.
OUTDOORS INDOORS
Stale indoor air exhaust
Outside air intake
Supply preconditioned outside air to AC system
Return stale indoor air
ERVTransmission plates Partition plates
OA
SAEA
RA
3
FeaturesMitsubishi Electric has responded to the growing need for total, integrated management of building HVAC and indoor air quality by making it easier to interlock and control Lossnay energy recovery ventilators with our air-conditioning systems.
Improved sound attenuation makes Lossnay units quiet enough for places where silence is a must, such as meeting rooms and libraries.
A free-cooling function is standard to help reduce costs and boost efficiency. The integrated bypass damper design makes installation and system integration quick and efficient.
System compatibility
Lossnay is fully compatible with our AE-200A, AE-50A and EW-50A Centralized Controllers and works with the TG-2000A software, LonWorks® interface, and BACnet® interface, further increasing the scope of total system management.
Multifunction LCD remote controlThe PZ-43SMF-E Remote Controller and the PZ-60DR-EM-NET Controller are compact and attractive. In addition to controls for ON/OFF and Ventilation Mode, the schedule for filter maintenance is also displayed. The liquid crystal display has been designed for easy visibility.
High-static pressure blades
By developing blower blades that are thinner, more widely spaced, and possessing a larger diameter of curvature, static pressure has been boosted and sound reduced while ensuring optimal airflow.Higher static pressure means that Lossnay canaccommodate the pressure loss required to meet the specifications of ductwork and terminal devices, increasing the flexibility of system installation.
®
LMAP04U-ETG-2000A
3
SA(Supply air diffuser)
RA(Return air)
0A(Outside air)
Exhaust side filter
Lossnay® Core
Intake side filter
Exhaust fanSupply fan
EA(Exhaust air)
Note: The duct inlet and outlet are arranged in-line in the actual product.
SA: Supply Air RA: Return Air EA: Exhaust Air OA: Outside Air
Note: The duct inlet and outlet are arranged in-line in the actual product.
Lossnay constructionLossnay ERVs are constructed so that the exhaust air passage from the indoor side to the outdoor side (RA EA) and the outside air passage from the outdoor side to the indoor side (OA SA) cross. The Lossnay energy recovery unit features the Lossnay Core, which is installed at this cross point and recovers the heat by conduction through the separating medium between the airflows. This enables the energy loss during exhaust to be greatly reduced.
VentilationWith conventional ERVs, bypass or auto ventilation was impossible without attaching an additional damper and adapter. With the LGH-F-RX5 series, however, these modes are available without using any other parts. Auto mode is the fixed setting when Lossnay is interlocked with air conditioners. When using Lossnay independently with the PZ-43SMF-E remote control (sold separately), Lossnay ventilation, bypass ventilation, or auto mode can be selected.
Reduce cooling load If the air outside is cooler than the air inside the building during the cooling season (such as early morning or at night), bypass ventilation will draw in the cooler outside air and reduce the cooling load on the system.
Cooling using outdoor air During cooler seasons (such as spring and fall), if the people in a room cause the temperature of the room to rise, bypass ventilation will draw in the cool outside air and use it as is to cool the room.
Night purge Bypass ventilation can be used to release hot air from inside the building that has accumulated during a hot summer day.
Office equipment room cooling During the cold season, outdoor air can be drawn in to cool rooms where the temperature has risen due to the use of office equipment. (only when interlocked with CITY MULTI®, M-Series, or P-Series indoor units)
High-static pressure blades Conventional blades
4
Comparison of primary building ventilation methodsThere are two main ventilation methods:
Air intake (outside air)
Filters
Air exhaust(stale air)
Lossnay®
Supply fan
Exhaust
Each unit
Independent operation with ceiling-suspended air conditioner
Ceiling-cassette package airconditioner or fan coil unit
Ceiling-cassette or ceiling-suspended-typepackage air conditioner or fan coil unit
Ceiling-mounted-type Lossnay orceiling-embedded-type Lossnay®
Exhaust grillCeiling-recessed-typeLossnay® unit
Exhaust airOutside air
Finished ceiling
Outside airExhaust air
Finished ceiling
Ceiling-embedded-type packageair conditioner or fan coil unit
Ceiling-recessed-type Lossnay®Exhaust grill
Exhaust air Outside air
Finished ceiling
Independent zoned ventilation methodThis is mainly used in small to medium-sized buildings, with areas being ventilated using outside air intakes from independent ventilation devices. The rate of use of this method has recently increased as zone conditioning and independent control is becoming more feasible.
Calculation of total heat recovery efficiencyThe Lossnay Core’s energy recovery efficiency can be considered using the following three transfer rates:1. Temperature (sensible heat) recovery efficiency2. Humidity (latent heat) recovery efficiency3. Enthalpy (total heat) recovery efficiency The heat recovery effect can be calculated if two of the above efficiencies are known. (The temperature and enthalpy efficiencies are indicated on pages 7–10.) Lossnay performance and cost analysis can also be determined using Mitsubishi Electric ERValue® software.• Each recovery efficiency can be calculated with the formulas
in the table below. • When the supply air volume and exhaust air volume are
equal, the heat recovery efficiencies on the supply and exhaust sides are the same.
• When the supply air volume and exhaust air volume are not equal, the total heat recovery efficiency is low if the exhaust volume is lower, and high if the exhaust volume is higher.
OUTDOORS INDOORS
ERV
OA
EA SA
RACalculation of supply air condition leaving LossnayIf the Lossnay energy recovery efficiency and the conditions of the room and outdoor air are known, the conditions of the air entering the room and the air exhausted outdoors can be determined with the following formulas in the table below.
Supply side Exhaust sideTemperature tSA= tOA- (tOA- tRA) x t tEA= tRA + (tOA - tRA) x t
Enthalpy iSA = iOA- (iOA - iRA) x i iEA = iRA + (iOA - iRA) x i
Centralized ventilation methodThis is mainly used in large buildings, with the outside air intake being installed in one machine room. For this method, primary treatment of the outdoor air, such as heat recovery to the intake air and dust removal, is performed before distribution to the building duct system.
ITEM FORMULATemperature recovery efficiency (%)
Enthalpy recovery efficiency (%)
= x 100tOA - tSA
tOA - tRAt [ [= x 100iOA - iSA
iOA - iRAi [ [ =Efficiency (%) t =Dry Bulb Temperature (°F) i =Enthalpy (Btu/lb)
SYSTEM OPERATION WITH CEILING CASSETTE (RECESSED) AIR CONDITIONER
SYSTEM OPERATION WITH DUCTED AIR CONDITIONER
5
Lossnay remote controller (PZ-43SMF-E)
Lossnay remote controller (PZ-60DR-E)
Interface condition fortransmission line
Number of Lossnay® units controlled by PZ-43SMF-E
Input voltage: 9VDC-15VDC, 0.02APower received from a Lossnay unit, TM2 5 - 6
Specialized transmission line:DC power + AM modulation
1–15
Interface condition fortransmission line
Number of Lossnay units controlled by PZ-60DR-E
Input voltage: 9VDC-15VDC, 0.02APower received from a Lossnay®
unit, TM2 5 - 6
Specialized transmission line:DC power + AM modulation
1–15
130[5-1/8]19
[3/4]
120[
4-3 /
4]
Source power requirement
Source power requirement
Centralized Controller Outdoor unit
Indoor unit Lossnay
Lossnay Lossnay
Remotecontroller
Indoor unit
Remotecontroller
Lossnay M-NETremote controllerPZ-43SMF-E
Lossnay External signal source
Lossnay M-NETremote controllerPZ-60DR-E
Lossnay M-NETremote controllerPZ-43-SMF-E
Lossnay Unit interlocked with CITY MULTI indoor units
Lossnay Units withPZ-43SMF-E remote controllers
Lossnay Unit interlocked with external devices
OO
Rc
ntralized Contro
Controls
PZ-43SMF-E and PZ-60DR-E controllers cannot be used simultaneously.
6
CITY MULTILossnay
remotecontroller
PZ-60DR-E
CITY MULTI/Lossnay connected M-NET transmission line
M- & P-Seriesindoor unit
M-Series or P-Series/Lossnay
connection cable
LOSSNAY® USED INDEPENDENTLY
LGH-RX5 LGH-RX5
INTERLOCKED WITH INDOOR UNITS
Lossnay
remotecontroller
PZ-43SMF-E
indoor unit
CITY MULTILossnay
remotecontroller
PZ-60DR-E
CITY MULTI/Lossnay connected M-NET transmission line
M- & P-Seriesindoor unit
M-Series or P-Series/Lossnay
connection cable
LOSSNAY® USED INDEPENDENTLY
LGH-RX5 LGH-RX5
INTERLOCKED WITH INDOOR UNITS
Lossnay
remotecontroller
PZ-43SMF-E
indoor unit
Interlock simply, effectively, and economicallyBecause the M-NET adapter is included as standard equipment on the LGH Series Lossnay Units, networking Lossnay Units with Mitsubishi Electric CITY MULTI has never been easier. Systems can be assembled simply and logically, reducing construction times and keeping costs low.
Fan speedSelect an appropriate Lossnay model according to the room size, air volume and sound levels. Each unit, (300, 470, 600 and 1,200 CFM), has an extra-high fan speed setting for use with a long duct or when a large air volume is required. Fan speed can also be adjusted for positive or negative zone pressurization.
Lossnay units have a low-sound design. However, for additional sound reduction, a silencer-type supply/return grill, a silencer box and a flexible silencer may be used.
7
LGH-F300RX5-E1
Power sourceVentilation modeSpeedCurrent (A) Input (W) Air volume
Model
External static pressureTemperature recovery efficiency (%)Enthalpy recoveryefficiency (%)
Sound pressure level (dB[A])
(Measured at 1.5m under the center of the unit)
Weight (Ibs) Starting current
(CFM)
Heating Cooling
Lossnay ventilation Bypass ventilationExtra High High Low
Single phase 208-230V/60HzLGH-F300RX5-E1
1.33/1.35274/300300/3000.60/0.7865.5/65.5
63/6350/50
34/37
Extra Low0.32/0.36
67/8291/112
0.06/0.0881/7979/7763/61
18/18
1.12/1.18232/268260/3000.46/0.5467.5/65.5
65/6352/50
30.5/33
0.81/0.86168/197203/235
0.28/0.3371/6968/6655/53
25.5/27.5
Extra High 1.33/1.35274/300300/300
0.60/0.78
35/37.5
High1.12/1.18232/268260/300
0.46/0.54
31.5/34.5
Low0.81/0.86168/197203/235
0.28/0.33
25.5/28.5
Extra Low0.32/0.36
67/8291/112
0.06/0.08
18/18.5
732.5A
(In. WG)
LB K E
D
M
13/16
(20)
M
5 7/
8 ~
9 7/
8(1
50~2
50)
AJ J
øG øH
3 3/
4 (9
5)
NF
C
F
N
EA (exhaust air outlet)
Air exhaust fan
OA (outside air intake)
Core, air filter, High-efficiency filter, fan, maintenance space
More
than 2
3 5/8
(600)
Position where duct direction change is possible
Air filters
High-efficiency filter (sold separately) attachment position
Inspection opening
Control boxMaintenance cover
Air supply fan
RA (return air)
SA (supply air)
Bypass damper platePosition where duct direction change is possible
Ceiling suspension fixture (4-1/2” X 13/16” (4-13 X 20) oval)
Power supply cable opening
Lossnay core
UnitDimensions Ceiling suspension fixture pitch Nominal
diameterDuct connecting flange Duct pitch
WeightA B C D E F G H J K L M N
34-15/16
888
40
1016
12-3/8
315
34-1/2
875
41-7/8
1063
2-9/16
65
7-7/8
200
7-9/16
192
8-3/16
208
3-1/8
79
29-3/8
745
5-5/16
135.5
4-7/8
124
1-3/16
30
73 lbs
33 kg
inches
mm
Extra High
High
Enthalpy exchange efficiency(Cooling)
efficiency(Heating)
Enthalpy exchange
Temperature exchange efficiency
Extra Low
Low
Low
Extra Low
efficiency
Temperature exchange
Enthalpy exchange efficiency(Heating)efficiency(Cooling)
Enthalpy exchange
High
Extra High
0 50 100 150 200 250 300 350 400
0.40
0.80
1.20
1.60
2.00
90
80
70
60
50
40
100
200
300
400
0
0 100 200 300 400 500 600 700 7006005004003002001000
0
400
300
200
100
40
50
60
70
80
90
2.00
1.60
1.20
0.80
0.40
400350300250200150100500
60Hz/Single phase 208VExchangeefficiency (%)
Pa
Pa
Ext
erna
l sta
tic p
ress
ure
(CFM)
Air volume (m3/h)
8in. dia.pipe
length
200ft.150ft.100ft.50ft.
(CFM)
50ft.100ft.150ft.200ft.
8in. dia.pipe
length
Air volume (m3/h)
Ext
erna
l sta
tic p
ress
ure
Exchangeefficiency (%)
60Hz/Single phase 230V
inH
2O
inH
2O
8
LGH-F470RX5-E1
Power sourceVentilation modeSpeedCurrent (A) Input (W) Air volume
Model
External static pressureTemperature recovery efficiency (%)Enthalpy recoveryefficiency (%)
Sound pressure level (dB[A])
(Measured at 1.5m under the center of the unit)
Weight (Ibs) Starting current
(CFM)
Heating Cooling
Extra High
(In. WG)
LB K E
D
M
13/16
(20)
M
5 7/
8 ~
9 7/
8(1
50~2
50)
AJ J
øG øH
3 3/
4 (9
5)
NF
C
F
N
EA (exhaust air outlet)
Air exhaust fan
OA (outside air intake)
Core, air filter, High-efficiency filter, fan, maintenance space
More
than 2
3 5/8
(600)
Position where duct direction change is possible
Air filters
High-efficiency filter (sold separately) attachment position
Inspection opening
Control boxMaintenance cover
Air supply fan
RA (return air)
SA (supply air)
Bypass damper platePosition where duct direction change is possible
Ceiling suspension fixture (4-9/16” X 13/16” (4-15 X 20) oval)
Power supply cable opening
Lossnay core
UnitDimensions Ceiling suspension fixture pitch Nominal
diameterDuct connecting flange Duct pitch
WeightA B C D E F G H J K L M N
inches
mm
90
Lossnay ventilation Bypass ventilationHigh Low
Single phase 208-230V/60HzLGH-F470RX5-E1
2.40/2.50485/538470/4700.80/0.96
69/6964/6451/51
36/38
Extra Low0.60/0.64120/145147/177
0.07/0.0982/8080/7869/67
18/18.5
2.10/2.20425/490420/4700.54/0.6670.5/6966/6453/51
33/35.5
1.59/1.71330/393330/365
0.33/0.4074/7270/6858/55
28.5/31
Extra High 2.40/2.50485/538470/470
0.80/0.96
36/39
High2.10/2.20425/490420/470
0.54/0.66
33/36
Low1.59/1.71330/393330/365
0.33/0.40
28.5/31.5
Extra Low0.60/0.64120/145147/177
0.07/0.09
18/18
1194.5A
39-1/2
1004
15-3/4
399
39-3/4
1010
40-13/16
1036
15-5/16
389
9-7/8
250
9-1/2
242
10-3/16
258
3-1/8
79
27-3/16
690
6-3/16
157
6-1/2
165
– 119 lbs
54 kg–
45-1/16
1144
Extra Hgh
High
Extra Low
Low
efficiency(Cooling)
Enthalpy exchange
efficiency(Heating)
Enthalpy exchange
Temperature exchange efficiency
1400120010008006004002000
0
100
40
50
60
70
80
2.50
2.00
1.50
1.00
0.50
8007006005004003002001000
200
300
400
500
600
300ft.
10in. dia.pipe
length
Air volume (m3/h)
(CFM)Ext
erna
l sta
tic p
ress
ure
Exchangeefficiency (%)
60Hz/Single phase 208V
200ft.
100ft.Pa
Temperature exchange efficiency
Enthalpy exchangeefficiency(Heating)
Enthalpy exchangeefficiency(Cooling)
High
Extra High
Extra Low
Low
0
90
80
70
60
50
40
0
2.50
2.00
1.50
1.00
0.50
500
400
300
200
100
0 100 800700600500400300200
140012001000800600400200
600
60Hz/Single phase 230VExchangeefficiency (%)
Ext
erna
l sta
tic p
ress
ure
Air volume (m3/h)
(CFM)
100ft.
200ft.
300ft.
10in. dia.pipe
length
Pa
inH
2O
inH
2O
9
LGH-F600RX5-E1
Power sourceVentilation modeSpeedCurrent (A) Input (W) Air volume
Model
External static pressureTemperature recovery efficiency (%)Enthalpy recoveryefficiency (%)
Sound pressure level (dB[A])
(Measured at 1.5m under the center of the unit)
Weight (Ibs) Starting current
(CFM)
Heating Cooling
Extra High
(In. WG)
LB K E
D
M
13/16
(20)
M
5 7/
8 ~
9 7/
8(1
50~2
50)
AJ J
øG øH
3 3/
4 (9
5)
NF
C
F
N
EA (exhaust air outlet)
Air exhaust fan
OA (outside air intake)
Core, air filter, High-efficiency filter, fan, maintenance space
More
than 2
3 5/8
(600)
Position where duct direction change is possible
Air filters
High-efficiency filter (sold separately) attachment position
Inspection opening
Control boxMaintenance cover
Air supply fan
RA (return air)
SA (supply air)
Bypass damper platePosition where duct direction change is possible
Ceiling suspension fixture (4-9/16” X 13/16” (4-15 X 20) oval)
Power supply cable opening
Lossnay core
UnitDimensions Ceiling suspension fixture pitch Nominal
diameterDuct connecting flange Duct pitch
WeightA B C D E F G H J K L M N
inches
mm
–
–
45-1/16
1144
Lossnay ventilation Bypass ventilationHigh Low
Single phase 208-230V/60HzLGH-F600RX5-E1
2.80/2.90577/637600/6000.56/0.80
67/6764/6450/50
36/38
Extra Low0.72/0.79146/180200/235
0.07/0.0780/7879/7768/67
19/21
2.50/2.70517/605520/6000.48/0.48
68/6765/6453/50
34/36.5
1.56/1.69324/387370/430
0.24/0.2475/7371/6859/56
26.5/29
Extra High 2.80/2.90577/637600/600
0.56/0.80
37/39
High2.50/2.70517/605520/6000.48/0.48
35/37.5
Low1.56/1.69324/387370/430
0.24/0.24
27/30
Extra Low0.72/0.79146/180200/235
0.07/0.07
18.5/20
1325.0A
48-1/2
1231
15-3/4
399
39-3/4
1010
49-3/4
1263
15-5/16
389
9-7/8
250
9-1/2
242
10-3/16
258
3-1/8
79
36-1/8
917
6-3/16
157
6-1/2
165
132 lbs
60 kg
efficiency
Temperature exchange
Enthalpy exchangeefficiency(Heating)
Enthalpy exchangeefficiency(Cooling)
Low
Extra Low
High
Extra High
Low
Extra Low
High
Enthalpy exchange
Enthalpy exchangeefficiency(Heating)
efficiency
Temperature exchange
Extra High efficiency(Cooling)
600600
200 400 600 800 1000 1200 1400
200 300 400 500 600 700 8001000
100
200
300
400
500
0.50
1.00
1.50
2.00
2.50
500
400
300
200
0 100 200 300 400 500 600 700 800
0.50
1.00
1.50
2.00
2.50
90
80
70
60
50
40
100
0
0 200 400 600 800 1000 1200 1400 0
40
50
60
70
80
90
0
100ft.
200ft.
300ft.
10in. dia.pipe
length
100ft.
200ft.
300ft.
10in. dia.pipe
length
60Hz/Single phase 208VExchangeefficiency (%)
Ext
erna
l sta
tic p
ress
ure
(CFM)
Air volume (m3/h)
(CFM)
Air volume (m3/h)
Ext
erna
l sta
tic p
ress
ure
Exchangeefficiency (%)
60Hz/Single phase 230V
Pa
Pa
inH
2O
inH
2O
10
LGH-F1200RX5-E1
Power sourceVentilation modeSpeedCurrent (A) Input (W) Air volume
Model
External static pressureTemperature recovery efficiency (%)Enthalpy recoveryefficiency (%)
Sound pressure level (dB[A])
(Measured at 1.5m under the center of the unit)
Weight (Ibs) Starting current
(CFM)
Heating Cooling
Extra High
(In. WG)
UnitDimensions Weight
A B C D
inches
mm
48-1/2
1231
Lossnay ventilation Bypass ventilationSingle phase 208-230V/60Hz
LGH-F1200RX5-E1
90
Temperature exchange efficiency
efficiency(Heating)
Enthalpy exchangeEnthalpy exchangeefficiency(Cooling)
Low
High
Extra High Extra High
High
Low
efficiency(Cooling)
Enthalpy exchange
Enthalpy exchange efficiency(Heating)
efficiency
Temperature exchange
600600
0
100
200
300
400
500
0.50
1.00
1.50
2.00
2.50
500
400
300
200
0
0.50
1.00
1.50
2.00
2.50
80
70
60
50
40
100
0
0 0
40
50
60
70
80
90
0250 500 750 1000 1250 1500 150012501000750500250
400 800 1200 1600 2000 2400 2400200016001200800400
60Hz/Single phase 208VExchangeefficiency (%)
Ext
erna
l sta
tic p
ress
ure
(CFM)
Air volume (m3/h)
(CFM)
Air volume (m3/h)
Ext
erna
l sta
tic p
ress
ure
Exchangeefficiency (%)
60Hz/Single phase 230V
Pa
Pa
inH
2O
inH
2O
39 3/4 (1010)
C DA B
3 1/8 (79)1 3/4 (44)
27 9
/16
(700
) 10
5/8
(270
)
ø9 1
/2(ø
242)
ø10 3
/16(ø
258)
(ø24
2)
(ø25
8)
ø9 1
/2
ø10 3
/16
15 3/4 (399)
31 7/16 (798)
1 1/
8 (2
7)
5 7/
8 ~
9 7/
8(1
50 ~
250
)
4 5/
16 (1
10)
10 5
/8(2
70)
Ceiling suspension fixture (4-9/16 X 1-3/16 (4-15 X 30) oval)
SA (supply air)
RA (return air)EA
(exhaust air outlet)
OA (outside air intake)
Core, air filter, High-efficiency
filter, fan,
maintenance space
High-efficiency filter (sold separately) attachment position
Air exhaust fan
Bypass damper plate
Air supply fan
Maintenance cover
Inspection opening
Air filtersMo
re tha
n 23 5
/8 (60
0)
Power supply cableopening
Control box
45 1/16 (1144)
Lossnay cores
36-1/8
917
36-1/8
917
50-1/8
1272
265 lbs
120 kg)
High Low Extra High High Low5.7/5.8
1185/13031200/12000.43/0.75
67/6764/6450/50
38/40.5
5.0/5.31040/12191012/12000.43/0.43
68/6765/6453/50
36/39
3.1/3.4639/765695/824
0.20/0.2075/7371/6859/56
29/32
5.8/5.81185/13031200/12000.43/0.75
40/42.5
5.1/5.41040/12191012/12000.43/0.43
38/41
3.1/3.4639/765695/824
0.20/0.20
30.5/33.5
26510.0A
Lorem ipsum
11
• Clearance should be provided to allow access to the air filter and Lossnay® Core.
• The installer must provide insulation to prevent moisture condensation along the two outside ducts (outside-air intake and exhaust-air outlet).
• Ceiling installation hardware can be attached to the top of the unit.
• The installer must use weather-protected caps or hoods in areas directly exposed to rain.
LGH-F300RX5-E1LGH-F470RX5-E1LGH-F600RX5-E1
LGH-F1200RX5-E1
A
B
D
C
Min
. 23-
5/8" 5-7/8~9-7/8"
Ceilingsuspensionbolt position
Duct normal diameterøE (user-supplied)
Weather cover
Ceiling suspension boltposition (user-supplied)
Duct inclineOver 1/30 (toward the wall)(moisture condensation prevention)
Heat exchanger/filtermaintenance space
Service access area
Service access area
Ceilingsuspensionbolt position
Ceilingsuspensionbolt position
Air-exhaust grill
Air-supply grill
Air-supplyexhaust grill
EA(exhaust-air outlet)
EA(exhaust-air outlet)
OA(fresh-air intake)
OA(outside-air intake) RA
(return air)SA(supply air)
5-7/8~9-7/8"
AE)teltuo ria-tsuahxe(
AO(oustide-air intake)
A
CD
Min.
23-
5/8"
AS)ria ylppus(
B
Duct inclineOver 1/30 (toward the wall)(moisture condensation prevention)
Heat exchanger/filtermaintenance space
Duct diameterø13-3/4" (user-supplied)
Duct diameterø13-3/4" (user-supplied)
Y piping, Reducer(user-supplied)
Service access
Service access area
Ceilingsuspensionbolt position
Ceiling suspensionbolt position
Ceiling suspensionbolt position
Ceiling suspensionbolt position
Exhaust grill(user-supplied)
Exhaust grill(user-supplied)
Air-supply grill
Air-supply grill
Air-supply grillAir-exhaust grill
Air-supply grill(user supplied)
EA(exhaust-air outlet)
OA(outside-air intake)
RA(return air)
SA(supply air)
WALL
WALL
Typical Installation
Duct can be installed in two different directions (OA, EA side)Ducts can be connected in two different directions to the outdoor vents thanks to collars and aperture plates that are interchangeable — either side or bottom locations. This flexibility allows for installations close to the surface of a wall and helps avoid cases where the stale exhaust air vent would be obstructed. This innovative feature simplifies both planning and installation.
STANDARD INSTALLATION INSTALLATION WITH DUCT DIRECTION CHANGED
12
Use Lossnay M-NET remote controller PZ-52SF-E.
(Do not use PZ-41SLB-E).
Lossnay transmission connection terminal
Two remote controller system with multiple Lossnay units
It is also possible to operate two remote controller units when using multiple Lossnay units.
Power supply
Power supply
Remote controllerPZ-41SLB-E
Interlocking multiple unitsWhen the operation signal is an uncharged a-contact signal
Interlocking/individual joint systems
By making the group setting, interlock settings have become possible.(Joint use of the CITY MULTI remote controller and Lossnay remotecontroller is possible.)
Interlocking is possible from multiple air conditioning units, etc. (excluding pulse input)(Separately sold parts are necessary depending on the operation signal).
Applicable indoor units use MA remote contoller models. Do not set the air conditioning unit and Lossnay unit to bepart of the same group. When the address number has been changed, the data in the memory
is automatically reset.
Power supply Power supply Power supply Power supply
LossnayA/C A/C A/C
RemotecontrollerPZ-41SLB-E
Air conditioning unit side remote controller
Air conditioning unit side remote controller
Air conditioning unit side remote controller
Indoor unit (01)
Centralisedcontroller(201) Outdoor
unit (51)
Operation settings
MA remote controller
Lossnay (02)
Lossnay M-NET remote controller (PZ-52SF-E)(102)
Group 1 Group 2
Use Lossnay remote controller PZ-41SLB-E
(Do not use PZ-52SF-E).
Lossnay transmission connection terminal
A B S65654321
A B S A65 B S
0 1SA1 SA2
0
2
01
SA1
SA2
SA1
SA2
Transmission cable
Transmissioncable
Round terminal
M-NET transmission cableinput terminal block
Shielded wireM-NET
transmission cable
Remote controller input terminal
Main/Sub selection switch(SW1)
Main Sub
(Set to Main whenshipped from the factory)
( ) address
LGH-F300, F470and F600RX types LGH-F1200RX type
LGH-F300, F470and F600RX types
TB5LGH-F1200RX type
TB5
Setting
SettingLGH-F300, F470 and F600RX types LGH-F1200RX type
Uppercircuitboard[Sub]ex. SA1 = 0, SA2 = 2
Lowercircuitboard[Main]ex. SA1 = 0, SA2 = 1
Operating with external device
The operation of the Lossnay will be connected with the operation orstopping of the external device.Input of level signal or pulse signal (12V DC, 24V DC, unchargeda-contact) is possible.
One Lossnay with one remote controller
One Lossnay unit is operated independently with one remote controller.
Multiple Lossnay units with one remote controller
Up to 15 Lossnay units can be controlled atone time with one remote controller.
Two remote controller system with one Lossnay
Operating with M- and P-Series (A-control) – Interlocked
The Remote controller (A-control) controls the air conditioning device and the Lossnay. It is possible to operate or switch fan speed for the Lossnay individually.
LossnayNon-polar2 wires
Remote controller PZ-43SMF-E
Power supply
LossnayNon-polar2 wires
Power supply
RemotecontrollerPZ-43SMF-E
(Sub)
(Main)
Lossnay
Power supply
LossnayNon-polar2 wires
Remote controller PZ-43SMF-E
Power supply
Air conditioning device and system control
It is possible to operate 16 indoor units per 1 Lossnay
IndoorunitMA remote controller
Outdoor unit
IndoorunitMA remote controller
Lossnay IndoorunitMA remote controller
LossnayIndoorunit
Indoorunit
MA remote controller
IndoorunitMA remote controller
Lossnay IndoorunitMA remote controller
IndoorunitMA remote controller
Lossnay
Indoor unitIndoor unit
Group 1 Group 5Group 3 Group 4Group 2
Outdoor unit Outdoor unit
IndoorunitMA remote controller
Lossnay Lossnay
Group 1
Lossnay
3 puorG2 puorG
Control of start/stop, fan speed and ventilation mode is possible from the Lossnay remote controller PZ-60DR-EControl of start/stop, fan speed and ventilation mode is possible from the centralized controller.It is possible to set a maximum of 16 units for 1 group.
Lossnay remote controller
PZ-60DR-E
Lossnay Lossnay
Group 1
Lossnay remote controller
PZ-60DR-E
Lossnay Lossnay LossnayLossnay
Group 3
Lossnayremote controller
PZ-60DR-E
Lossnay
Group 4Group 2
Powersupplyunit
Lossnay M-NET remote controller
PZ-60DR-E
Lossnay
Group 5
Lossnay
Power supply
Power supply
Remotecontroller
Lossnay
Power supply
Power supply
Remote controller
Indoor unitIndoor unit
RemotecontrollerPZ-43SMF-E
Non-polartwo wires
Centralized controller
PAR-33MAA
Selection of interlocked operation mode is possible. Delayed start interlocked operation is possible
The Lossnay can be controlled from two remote locations. The remote controller gives priority to the last touch
System Control ExamplesBasic System — Stand-alone Lossnay ERV with PZ-41SLB-E Remote Controller
Operation with M-Series or P-Series
CITY MULTI and Lossnay Interlocked
Centralized Management System
M-N
ET
SY
ST
EM
Note: In the LGH-F1200RX type, there are two circuit boards installed in each unit, so count each unit as two Lossnay units.
13
Balanced Ventilation A ventilation strategy using both an exhaust air blower and a supply or make-up air blower providing the same airflow and pressure so as not to pressurize or depressurize a building.
CFMCubic Feet per Minute, a measure of air volume.
Delayed OperationThe On/Off operation of the Lossnay unit can be delayed for 30 minutes following the operation of the indoor unit. When using PZ-43SMF-E, the delay can be set for 0:30–24:00 hours.
ESPExternal Static Pressure, available motive force to propel air in a duct system from a blower or ventilator.
Enthalpy ExchangeThe exchange of both sensible and latent heat energy.
Exhaust Air (EA)Air expelled from indoor space.
External Control InputAn On/Off input signal for operating the Lossnay unit that can be sent from an external device. The signal may be a 12V–24V DC or an uncharged a-contact signal.
Interlocked LossnayLossnay unit linked to CITY MULTI, M-, S-, or P-Series Indoor units that receive signals and operates via the indoor unit’s remote controller.
Non-interlocked LossnayLossnay unit controlled independently of CITY MULTI, M-Series, or P-Series indoor units by the Lossnay remote controller and/or centralized controller.
Operation in Cold AreasWhen the outdoor air is less than 14°F, continuous operation of the fan for drawing in supply air is stopped, and intermittent operation is started.
Outdoor Air (OA)Air drawn from outdoors — ventilation air.
Pulse InputWhen the control signal from an external device outputs a pulse such as the one shown at right, the pulse input control is performed by the Lossnay unit. (Optional DIP switch 2-2 ON) 200 ms or more.
Remote OperationThis is used for enabling/disabling the On/Off control signal from an external device and for setting interlocked operation of the external device and the Lossnay unit. ON/OFF interlock: Enables both ON OFF and
OFF ON external signals. ON interlock: Enables OFF ON external signal.
Disables ON OFF external signal. OFF interlock: Enables ON OFF external signal.
Disables OFF ON external signal. External priority: Same as on/off interlock but the
OFF signal from the remote controller is ignored when the external control signal is on.
Return Air (RA)Air drawn from indoor space.
Supply Air (SA)Air supplied to indoor space.
Ventilation Modes Energy Recovery — energy exchange through
Lossnay core at all times. Bypass — no exchange—bypass damper open Automatic — energy exchange or bypass as
determined by present temperature sensor in inlet and discharge airstreams.
Energy Recovery Ventilator Terminology
200 ms or more
14
System Selection
ERV-22LGH-F-RX3-E
Lossnay operation when indoor unit is stopped
AvailableNot available
Lossnay stopping when indoor unit is operatingSelecting Lossnay fan speedWhen interlocked with indoor unit for compatibility with R22, R407C and R410A High / Low
Ventilation mode Fixed to automaticFilter maintenance indicatorLossnay error indicatorDelayed operation – selectable times
Delayed operation - selectable times
External control operating mode selection
×
Number of indoor units for interlocked group setting with one Lossnay unit 16 unitsNumber of Lossnay units for interlocked group setting with one indoor unit 1 unit
Interlocked with external device (BMS) Start/StopFan speed selection Fixed to highVentilation mode switching Fixed to automaticFilter maintenance indicator ×Lossnay error indicator ×Delayed operationExternal control operating mode selection
Lossnay unitLGH-RX type
M-NET transmission cable
Remote controller
Interlocked with M-Series or P-Series When using A-control remote controllerLossnay operation when indoor unit is stoppedLossnay stopping when indoor unit is operating ×
×
Other common itemsLossnay error indicator ×Ventilation mode Fixed to automaticFilter maintenance indicator ×
External control operating mode selection ×Number of indoor units for interlocked group setting with one Lossnay unit 1 unitNumber of Lossnay units for interlocked group setting with one indoor unit 1 unit
M- and P-Series Lossnay connecting cable(Enclosed accessory)
Remote controller
Lossnay remotecontroller cannot
Lossnay unitLGH-RX type
Start/StopwoL/hgiHselection deeps naF
Ventilation mode Energy Recovery By-pass/ Auto
Filter maintenance indicatorLossnay error indicatorDelayed operationExternal control operating mode selectionNumber of Lossnay units
15 units( In the case of LGH-200RX type, count each unit as two for calcultion)
stinu 2 srellortnoc etomer fo rebmuN
Lossnay remote controller(PZ-43SMF-E)
EXT. signal sourcefor interlockingto the Lossnay
Lossnay unitLGH-RX type
EXT. signal sourcefor interlockingto the Lossnay
Lossnay unitLGH-RX type
Interlocked with CITY MULTI
Independent Lossnay Unit (not interlocked with CITY MULTI, M-Series, or P-Series systems)
CITY MULTIindoor unit
M-Series or P-Series (A-control)indoor unit
PZ-43SMF-E
Lorem ipsumLossnay fan speed selection High / Low
be used
15
Centralized Control System with CITY MULTI
Indoor unit Lossnay Indoor unit
Outdoor unit
A-control M-Series or P-Series outdoor unit
M- and P-Series A-controlPAR-33MAAremote controller
A-controlM-Series or P-Series indoor unit
Lossnay
Lossnayremote controller(PZ-60DR-E)
EXT.signalsource
Lossnayremote controller(PZ-60DR-E)
Remote controller Remote controller
M-NET control adapter
LossnayLossnay
Lossnayremote controller(PZ-43SMF-E)
Lossnay
AE-200A/AE-50ACentralized controller
PAC-SF83MA-E
BC4
1340 Satellite Blvd.Suwanee, GA 30024
www.mitsubishipro.com
©2018 Mitsubishi Electric Trane US HVAC LLCMitsubishi Electric, Lossnay, and the three-diamond logo are trademarks of Mitsubishi Electric Corporation. H2i and kumo cloud are registered trademarks of Mitsubishi Electric US, Inc. All other product names mentioned herein are trademarks or registered trademarks of their respective owners.
SKU: ME- EBRE | 06.2018 | Printed in the USA