energy recovery ventilators · energy costs. recover up to 80 percent of sensible and latent energy...

16
ENERGY RECOVERY VENTILATORS FOR TODAY’S INDOOR ENVIRONMENTAL QUALITY REQUIREMENTS Recapture Cooling and Heating Energy Plus Control Humidity Extremes ®

Upload: others

Post on 17-Mar-2020

3 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: ENERGY RECOVERY VENTILATORS · energy costs. Recover up to 80 percent of sensible and latent energy from the conditioned air as it is exhausted. Reduce extremes in humidity that can

ENERGY RECOVERY VENTILATORSFOR TODAY’S INDOOR ENVIRONMENTAL QUALITY REQUIREMENTS

Recapture Cooling and Heating Energy Plus Control Humidity Extremes

®

Page 2: ENERGY RECOVERY VENTILATORS · energy costs. Recover up to 80 percent of sensible and latent energy from the conditioned air as it is exhausted. Reduce extremes in humidity that can

2

Energy Recovery Ventilators▶▶ Maintain an adequate supply of ventilation air while reducing energy costs.▶▶ Recover up to 80 percent of sensible and latent energy from the conditioned air as it is exhausted.▶▶ Reduce extremes in humidity that can encourage mold growth.▶▶ Remove dangerous gases, bacteria, and other airborne impurities from conditioned air.

Mitsubishi Electric’s Lossnay energyrecovery ventilators offer:

▶▶ Unprecedented energy transfer in a fixed-plate component with no moving parts.▶▶ Reasonable paybacks and reduced peak demand.▶▶ Superior part-load per performance, reducing latent load even at mild outdoor temperatures.▶▶ No wheels to stop turning so outside air is always preconditioned and available.

How does the Lossnay®

core work?

Outside Air Makes the Difference!People need outside air for their health and comfort. Unconditioned outdoor air rarely

meets their needs: it’s usually too hot and humid in the summer and too cold and dry

in the winter. To provide the benefit of ventilation, the air must be preconditioned

before being introduced into the occupied space.

Cooled or heated indoor air soon grows stale and must be exhausted to rid the

building of toxins, odors, viruses, bacteria, and other potentially harmful contaminants.

Exhausting that air and replacing it with outside air, which must be conditioned, is

critical to a healthy and productive environment, but it is a process that can be both

costly and inefficient.

If your air-conditioning system utilizes an energy recovery ventilator (ERV), these costs

are greatly minimized. An ERV helps improve the efficiency of air-conditioning systems

by preheating or precooling incoming outside air with the available energy in the stale

exhaust air.

ERVs save money by decreasing the load on your air-conditioning units;

helping remove noxious indoor pollutants, such as formaldehyde, pollen, cigarette

smoke, dust, and carbon dioxide; and helping equalize humidity levels. An ERV is an

efficient and effective step toward improving overall indoor environmental quality.

At the heart of each Mitsubishi Electric Lossnay energy recovery ventilator is a low-maintenance cross-flow energy exchange core constructed of a specially treated cellulose fiber membrane.

The low-maintenance ERV core prevents the inbound air and exhaust air from intermingling while crossing the airflows, thus preconditioning the air by warming it in the wintertime with the warm exhausted air, or by cooling it in the summertime with the cooler exhaust air.

While the airflows are exchanging heat energy by conduction in the ERV core, the humidity in the airstreams seeks to equalize. In the winter cool dry supply air from outside is partially humidified by the moist exhausted air, and the opposite occurs in the summertime. The special treatment and impregnation applied to the transmission plates allows water vapor molecules to pass through so the differing humidity levels move toward equilibrium in the Lossnay core. Larger molecules are unable to pass through the transmission plates, so the outside air is uncontaminated by stale exhausted air.

OUTDOORS INDOORS

Stale indoor air exhaust

Outside air intake

Supply preconditioned outside air to AC system

Return stale indoor air

ERVTransmission plates Partition plates

OA

SAEA

RA

Page 3: ENERGY RECOVERY VENTILATORS · energy costs. Recover up to 80 percent of sensible and latent energy from the conditioned air as it is exhausted. Reduce extremes in humidity that can

3

FeaturesMitsubishi Electric has responded to the growing need for total, integrated management of building HVAC and indoor air quality by making it easier to interlock and control Lossnay energy recovery ventilators with our air-conditioning systems.

Improved sound attenuation makes Lossnay units quiet enough for places where silence is a must, such as meeting rooms and libraries.

A free-cooling function is standard to help reduce costs and boost efficiency. The integrated bypass damper design makes installation and system integration quick and efficient.

System compatibility

Lossnay is fully compatible with our AE-200A, AE-50A and EW-50A Centralized Controllers and works with the TG-2000A software, LonWorks® interface, and BACnet® interface, further increasing the scope of total system management.

Multifunction LCD remote controlThe PZ-43SMF-E Remote Controller and the PZ-60DR-EM-NET Controller are compact and attractive. In addition to controls for ON/OFF and Ventilation Mode, the schedule for filter maintenance is also displayed. The liquid crystal display has been designed for easy visibility.

High-static pressure blades

By developing blower blades that are thinner, more widely spaced, and possessing a larger diameter of curvature, static pressure has been boosted and sound reduced while ensuring optimal airflow.Higher static pressure means that Lossnay canaccommodate the pressure loss required to meet the specifications of ductwork and terminal devices, increasing the flexibility of system installation.

®

LMAP04U-ETG-2000A

3

SA(Supply air diffuser)

RA(Return air)

0A(Outside air)

Exhaust side filter

Lossnay® Core

Intake side filter

Exhaust fanSupply fan

EA(Exhaust air)

Note: The duct inlet and outlet are arranged in-line in the actual product.

SA: Supply Air RA: Return Air EA: Exhaust Air OA: Outside Air

Note: The duct inlet and outlet are arranged in-line in the actual product.

Lossnay constructionLossnay ERVs are constructed so that the exhaust air passage from the indoor side to the outdoor side (RA EA) and the outside air passage from the outdoor side to the indoor side (OA SA) cross. The Lossnay energy recovery unit features the Lossnay Core, which is installed at this cross point and recovers the heat by conduction through the separating medium between the airflows. This enables the energy loss during exhaust to be greatly reduced.

VentilationWith conventional ERVs, bypass or auto ventilation was impossible without attaching an additional damper and adapter. With the LGH-F-RX5 series, however, these modes are available without using any other parts. Auto mode is the fixed setting when Lossnay is interlocked with air conditioners. When using Lossnay independently with the PZ-43SMF-E remote control (sold separately), Lossnay ventilation, bypass ventilation, or auto mode can be selected.

Reduce cooling load If the air outside is cooler than the air inside the building during the cooling season (such as early morning or at night), bypass ventilation will draw in the cooler outside air and reduce the cooling load on the system.

Cooling using outdoor air During cooler seasons (such as spring and fall), if the people in a room cause the temperature of the room to rise, bypass ventilation will draw in the cool outside air and use it as is to cool the room.

Night purge Bypass ventilation can be used to release hot air from inside the building that has accumulated during a hot summer day.

Office equipment room cooling During the cold season, outdoor air can be drawn in to cool rooms where the temperature has risen due to the use of office equipment. (only when interlocked with CITY MULTI®, M-Series, or P-Series indoor units)

High-static pressure blades Conventional blades

Page 4: ENERGY RECOVERY VENTILATORS · energy costs. Recover up to 80 percent of sensible and latent energy from the conditioned air as it is exhausted. Reduce extremes in humidity that can

4

Comparison of primary building ventilation methodsThere are two main ventilation methods:

Air intake (outside air)

Filters

Air exhaust(stale air)

Lossnay®

Supply fan

Exhaust

Each unit

Independent operation with ceiling-suspended air conditioner

Ceiling-cassette package airconditioner or fan coil unit

Ceiling-cassette or ceiling-suspended-typepackage air conditioner or fan coil unit

Ceiling-mounted-type Lossnay orceiling-embedded-type Lossnay®

Exhaust grillCeiling-recessed-typeLossnay® unit

Exhaust airOutside air

Finished ceiling

Outside airExhaust air

Finished ceiling

Ceiling-embedded-type packageair conditioner or fan coil unit

Ceiling-recessed-type Lossnay®Exhaust grill

Exhaust air Outside air

Finished ceiling

Independent zoned ventilation methodThis is mainly used in small to medium-sized buildings, with areas being ventilated using outside air intakes from independent ventilation devices. The rate of use of this method has recently increased as zone conditioning and independent control is becoming more feasible.

Calculation of total heat recovery efficiencyThe Lossnay Core’s energy recovery efficiency can be considered using the following three transfer rates:1. Temperature (sensible heat) recovery efficiency2. Humidity (latent heat) recovery efficiency3. Enthalpy (total heat) recovery efficiency The heat recovery effect can be calculated if two of the above efficiencies are known. (The temperature and enthalpy efficiencies are indicated on pages 7–10.) Lossnay performance and cost analysis can also be determined using Mitsubishi Electric ERValue® software.• Each recovery efficiency can be calculated with the formulas

in the table below. • When the supply air volume and exhaust air volume are

equal, the heat recovery efficiencies on the supply and exhaust sides are the same.

• When the supply air volume and exhaust air volume are not equal, the total heat recovery efficiency is low if the exhaust volume is lower, and high if the exhaust volume is higher.

OUTDOORS INDOORS

ERV

OA

EA SA

RACalculation of supply air condition leaving LossnayIf the Lossnay energy recovery efficiency and the conditions of the room and outdoor air are known, the conditions of the air entering the room and the air exhausted outdoors can be determined with the following formulas in the table below.

Supply side Exhaust sideTemperature tSA= tOA- (tOA- tRA) x t tEA= tRA + (tOA - tRA) x t

Enthalpy iSA = iOA- (iOA - iRA) x i iEA = iRA + (iOA - iRA) x i

Centralized ventilation methodThis is mainly used in large buildings, with the outside air intake being installed in one machine room. For this method, primary treatment of the outdoor air, such as heat recovery to the intake air and dust removal, is performed before distribution to the building duct system.

ITEM FORMULATemperature recovery efficiency (%)

Enthalpy recovery efficiency (%)

= x 100tOA - tSA

tOA - tRAt [ [= x 100iOA - iSA

iOA - iRAi [ [ =Efficiency (%) t =Dry Bulb Temperature (°F) i =Enthalpy (Btu/lb)

SYSTEM OPERATION WITH CEILING CASSETTE (RECESSED) AIR CONDITIONER

SYSTEM OPERATION WITH DUCTED AIR CONDITIONER

Page 5: ENERGY RECOVERY VENTILATORS · energy costs. Recover up to 80 percent of sensible and latent energy from the conditioned air as it is exhausted. Reduce extremes in humidity that can

5

Lossnay remote controller (PZ-43SMF-E)

Lossnay remote controller (PZ-60DR-E)

Interface condition fortransmission line

Number of Lossnay® units controlled by PZ-43SMF-E

Input voltage: 9VDC-15VDC, 0.02APower received from a Lossnay unit, TM2 5 - 6

Specialized transmission line:DC power + AM modulation

1–15

Interface condition fortransmission line

Number of Lossnay units controlled by PZ-60DR-E

Input voltage: 9VDC-15VDC, 0.02APower received from a Lossnay®

unit, TM2 5 - 6

Specialized transmission line:DC power + AM modulation

1–15

130[5-1/8]19

[3/4]

120[

4-3 /

4]

Source power requirement

Source power requirement

Centralized Controller Outdoor unit

Indoor unit Lossnay

Lossnay Lossnay

Remotecontroller

Indoor unit

Remotecontroller

Lossnay M-NETremote controllerPZ-43SMF-E

Lossnay External signal source

Lossnay M-NETremote controllerPZ-60DR-E

Lossnay M-NETremote controllerPZ-43-SMF-E

Lossnay Unit interlocked with CITY MULTI indoor units

Lossnay Units withPZ-43SMF-E remote controllers

Lossnay Unit interlocked with external devices

OO

Rc

ntralized Contro

Controls

PZ-43SMF-E and PZ-60DR-E controllers cannot be used simultaneously.

Page 6: ENERGY RECOVERY VENTILATORS · energy costs. Recover up to 80 percent of sensible and latent energy from the conditioned air as it is exhausted. Reduce extremes in humidity that can

6

CITY MULTILossnay

remotecontroller

PZ-60DR-E

CITY MULTI/Lossnay connected M-NET transmission line

M- & P-Seriesindoor unit

M-Series or P-Series/Lossnay

connection cable

LOSSNAY® USED INDEPENDENTLY

LGH-RX5 LGH-RX5

INTERLOCKED WITH INDOOR UNITS

Lossnay

remotecontroller

PZ-43SMF-E

indoor unit

CITY MULTILossnay

remotecontroller

PZ-60DR-E

CITY MULTI/Lossnay connected M-NET transmission line

M- & P-Seriesindoor unit

M-Series or P-Series/Lossnay

connection cable

LOSSNAY® USED INDEPENDENTLY

LGH-RX5 LGH-RX5

INTERLOCKED WITH INDOOR UNITS

Lossnay

remotecontroller

PZ-43SMF-E

indoor unit

Interlock simply, effectively, and economicallyBecause the M-NET adapter is included as standard equipment on the LGH Series Lossnay Units, networking Lossnay Units with Mitsubishi Electric CITY MULTI has never been easier. Systems can be assembled simply and logically, reducing construction times and keeping costs low.

Fan speedSelect an appropriate Lossnay model according to the room size, air volume and sound levels. Each unit, (300, 470, 600 and 1,200 CFM), has an extra-high fan speed setting for use with a long duct or when a large air volume is required. Fan speed can also be adjusted for positive or negative zone pressurization.

Lossnay units have a low-sound design. However, for additional sound reduction, a silencer-type supply/return grill, a silencer box and a flexible silencer may be used.

Page 7: ENERGY RECOVERY VENTILATORS · energy costs. Recover up to 80 percent of sensible and latent energy from the conditioned air as it is exhausted. Reduce extremes in humidity that can

7

LGH-F300RX5-E1

Power sourceVentilation modeSpeedCurrent (A) Input (W) Air volume

Model

External static pressureTemperature recovery efficiency (%)Enthalpy recoveryefficiency (%)

Sound pressure level (dB[A])

(Measured at 1.5m under the center of the unit)

Weight (Ibs) Starting current

(CFM)

Heating Cooling

Lossnay ventilation Bypass ventilationExtra High High Low

Single phase 208-230V/60HzLGH-F300RX5-E1

1.33/1.35274/300300/3000.60/0.7865.5/65.5

63/6350/50

34/37

Extra Low0.32/0.36

67/8291/112

0.06/0.0881/7979/7763/61

18/18

1.12/1.18232/268260/3000.46/0.5467.5/65.5

65/6352/50

30.5/33

0.81/0.86168/197203/235

0.28/0.3371/6968/6655/53

25.5/27.5

Extra High 1.33/1.35274/300300/300

0.60/0.78

35/37.5

High1.12/1.18232/268260/300

0.46/0.54

31.5/34.5

Low0.81/0.86168/197203/235

0.28/0.33

25.5/28.5

Extra Low0.32/0.36

67/8291/112

0.06/0.08

18/18.5

732.5A

(In. WG)

LB K E

D

M

13/16

(20)

M

5 7/

8 ~

9 7/

8(1

50~2

50)

AJ J

øG øH

3 3/

4 (9

5)

NF

C

F

N

EA (exhaust air outlet)

Air exhaust fan

OA (outside air intake)

Core, air filter, High-efficiency filter, fan, maintenance space

More

than 2

3 5/8

(600)

Position where duct direction change is possible

Air filters

High-efficiency filter (sold separately) attachment position

Inspection opening

Control boxMaintenance cover

Air supply fan

RA (return air)

SA (supply air)

Bypass damper platePosition where duct direction change is possible

Ceiling suspension fixture (4-1/2” X 13/16” (4-13 X 20) oval)

Power supply cable opening

Lossnay core

UnitDimensions Ceiling suspension fixture pitch Nominal

diameterDuct connecting flange Duct pitch

WeightA B C D E F G H J K L M N

34-15/16

888

40

1016

12-3/8

315

34-1/2

875

41-7/8

1063

2-9/16

65

7-7/8

200

7-9/16

192

8-3/16

208

3-1/8

79

29-3/8

745

5-5/16

135.5

4-7/8

124

1-3/16

30

73 lbs

33 kg

inches

mm

Extra High

High

Enthalpy exchange efficiency(Cooling)

efficiency(Heating)

Enthalpy exchange

Temperature exchange efficiency

Extra Low

Low

Low

Extra Low

efficiency

Temperature exchange

Enthalpy exchange efficiency(Heating)efficiency(Cooling)

Enthalpy exchange

High

Extra High

0 50 100 150 200 250 300 350 400

0.40

0.80

1.20

1.60

2.00

90

80

70

60

50

40

100

200

300

400

0

0 100 200 300 400 500 600 700 7006005004003002001000

0

400

300

200

100

40

50

60

70

80

90

2.00

1.60

1.20

0.80

0.40

400350300250200150100500

60Hz/Single phase 208VExchangeefficiency (%)

Pa

Pa

Ext

erna

l sta

tic p

ress

ure

(CFM)

Air volume (m3/h)

8in. dia.pipe

length

200ft.150ft.100ft.50ft.

(CFM)

50ft.100ft.150ft.200ft.

8in. dia.pipe

length

Air volume (m3/h)

Ext

erna

l sta

tic p

ress

ure

Exchangeefficiency (%)

60Hz/Single phase 230V

inH

2O

inH

2O

Page 8: ENERGY RECOVERY VENTILATORS · energy costs. Recover up to 80 percent of sensible and latent energy from the conditioned air as it is exhausted. Reduce extremes in humidity that can

8

LGH-F470RX5-E1

Power sourceVentilation modeSpeedCurrent (A) Input (W) Air volume

Model

External static pressureTemperature recovery efficiency (%)Enthalpy recoveryefficiency (%)

Sound pressure level (dB[A])

(Measured at 1.5m under the center of the unit)

Weight (Ibs) Starting current

(CFM)

Heating Cooling

Extra High

(In. WG)

LB K E

D

M

13/16

(20)

M

5 7/

8 ~

9 7/

8(1

50~2

50)

AJ J

øG øH

3 3/

4 (9

5)

NF

C

F

N

EA (exhaust air outlet)

Air exhaust fan

OA (outside air intake)

Core, air filter, High-efficiency filter, fan, maintenance space

More

than 2

3 5/8

(600)

Position where duct direction change is possible

Air filters

High-efficiency filter (sold separately) attachment position

Inspection opening

Control boxMaintenance cover

Air supply fan

RA (return air)

SA (supply air)

Bypass damper platePosition where duct direction change is possible

Ceiling suspension fixture (4-9/16” X 13/16” (4-15 X 20) oval)

Power supply cable opening

Lossnay core

UnitDimensions Ceiling suspension fixture pitch Nominal

diameterDuct connecting flange Duct pitch

WeightA B C D E F G H J K L M N

inches

mm

90

Lossnay ventilation Bypass ventilationHigh Low

Single phase 208-230V/60HzLGH-F470RX5-E1

2.40/2.50485/538470/4700.80/0.96

69/6964/6451/51

36/38

Extra Low0.60/0.64120/145147/177

0.07/0.0982/8080/7869/67

18/18.5

2.10/2.20425/490420/4700.54/0.6670.5/6966/6453/51

33/35.5

1.59/1.71330/393330/365

0.33/0.4074/7270/6858/55

28.5/31

Extra High 2.40/2.50485/538470/470

0.80/0.96

36/39

High2.10/2.20425/490420/470

0.54/0.66

33/36

Low1.59/1.71330/393330/365

0.33/0.40

28.5/31.5

Extra Low0.60/0.64120/145147/177

0.07/0.09

18/18

1194.5A

39-1/2

1004

15-3/4

399

39-3/4

1010

40-13/16

1036

15-5/16

389

9-7/8

250

9-1/2

242

10-3/16

258

3-1/8

79

27-3/16

690

6-3/16

157

6-1/2

165

– 119 lbs

54 kg–

45-1/16

1144

Extra Hgh

High

Extra Low

Low

efficiency(Cooling)

Enthalpy exchange

efficiency(Heating)

Enthalpy exchange

Temperature exchange efficiency

1400120010008006004002000

0

100

40

50

60

70

80

2.50

2.00

1.50

1.00

0.50

8007006005004003002001000

200

300

400

500

600

300ft.

10in. dia.pipe

length

Air volume (m3/h)

(CFM)Ext

erna

l sta

tic p

ress

ure

Exchangeefficiency (%)

60Hz/Single phase 208V

200ft.

100ft.Pa

Temperature exchange efficiency

Enthalpy exchangeefficiency(Heating)

Enthalpy exchangeefficiency(Cooling)

High

Extra High

Extra Low

Low

0

90

80

70

60

50

40

0

2.50

2.00

1.50

1.00

0.50

500

400

300

200

100

0 100 800700600500400300200

140012001000800600400200

600

60Hz/Single phase 230VExchangeefficiency (%)

Ext

erna

l sta

tic p

ress

ure

Air volume (m3/h)

(CFM)

100ft.

200ft.

300ft.

10in. dia.pipe

length

Pa

inH

2O

inH

2O

Page 9: ENERGY RECOVERY VENTILATORS · energy costs. Recover up to 80 percent of sensible and latent energy from the conditioned air as it is exhausted. Reduce extremes in humidity that can

9

LGH-F600RX5-E1

Power sourceVentilation modeSpeedCurrent (A) Input (W) Air volume

Model

External static pressureTemperature recovery efficiency (%)Enthalpy recoveryefficiency (%)

Sound pressure level (dB[A])

(Measured at 1.5m under the center of the unit)

Weight (Ibs) Starting current

(CFM)

Heating Cooling

Extra High

(In. WG)

LB K E

D

M

13/16

(20)

M

5 7/

8 ~

9 7/

8(1

50~2

50)

AJ J

øG øH

3 3/

4 (9

5)

NF

C

F

N

EA (exhaust air outlet)

Air exhaust fan

OA (outside air intake)

Core, air filter, High-efficiency filter, fan, maintenance space

More

than 2

3 5/8

(600)

Position where duct direction change is possible

Air filters

High-efficiency filter (sold separately) attachment position

Inspection opening

Control boxMaintenance cover

Air supply fan

RA (return air)

SA (supply air)

Bypass damper platePosition where duct direction change is possible

Ceiling suspension fixture (4-9/16” X 13/16” (4-15 X 20) oval)

Power supply cable opening

Lossnay core

UnitDimensions Ceiling suspension fixture pitch Nominal

diameterDuct connecting flange Duct pitch

WeightA B C D E F G H J K L M N

inches

mm

45-1/16

1144

Lossnay ventilation Bypass ventilationHigh Low

Single phase 208-230V/60HzLGH-F600RX5-E1

2.80/2.90577/637600/6000.56/0.80

67/6764/6450/50

36/38

Extra Low0.72/0.79146/180200/235

0.07/0.0780/7879/7768/67

19/21

2.50/2.70517/605520/6000.48/0.48

68/6765/6453/50

34/36.5

1.56/1.69324/387370/430

0.24/0.2475/7371/6859/56

26.5/29

Extra High 2.80/2.90577/637600/600

0.56/0.80

37/39

High2.50/2.70517/605520/6000.48/0.48

35/37.5

Low1.56/1.69324/387370/430

0.24/0.24

27/30

Extra Low0.72/0.79146/180200/235

0.07/0.07

18.5/20

1325.0A

48-1/2

1231

15-3/4

399

39-3/4

1010

49-3/4

1263

15-5/16

389

9-7/8

250

9-1/2

242

10-3/16

258

3-1/8

79

36-1/8

917

6-3/16

157

6-1/2

165

132 lbs

60 kg

efficiency

Temperature exchange

Enthalpy exchangeefficiency(Heating)

Enthalpy exchangeefficiency(Cooling)

Low

Extra Low

High

Extra High

Low

Extra Low

High

Enthalpy exchange

Enthalpy exchangeefficiency(Heating)

efficiency

Temperature exchange

Extra High efficiency(Cooling)

600600

200 400 600 800 1000 1200 1400

200 300 400 500 600 700 8001000

100

200

300

400

500

0.50

1.00

1.50

2.00

2.50

500

400

300

200

0 100 200 300 400 500 600 700 800

0.50

1.00

1.50

2.00

2.50

90

80

70

60

50

40

100

0

0 200 400 600 800 1000 1200 1400 0

40

50

60

70

80

90

0

100ft.

200ft.

300ft.

10in. dia.pipe

length

100ft.

200ft.

300ft.

10in. dia.pipe

length

60Hz/Single phase 208VExchangeefficiency (%)

Ext

erna

l sta

tic p

ress

ure

(CFM)

Air volume (m3/h)

(CFM)

Air volume (m3/h)

Ext

erna

l sta

tic p

ress

ure

Exchangeefficiency (%)

60Hz/Single phase 230V

Pa

Pa

inH

2O

inH

2O

Page 10: ENERGY RECOVERY VENTILATORS · energy costs. Recover up to 80 percent of sensible and latent energy from the conditioned air as it is exhausted. Reduce extremes in humidity that can

10

LGH-F1200RX5-E1

Power sourceVentilation modeSpeedCurrent (A) Input (W) Air volume

Model

External static pressureTemperature recovery efficiency (%)Enthalpy recoveryefficiency (%)

Sound pressure level (dB[A])

(Measured at 1.5m under the center of the unit)

Weight (Ibs) Starting current

(CFM)

Heating Cooling

Extra High

(In. WG)

UnitDimensions Weight

A B C D

inches

mm

48-1/2

1231

Lossnay ventilation Bypass ventilationSingle phase 208-230V/60Hz

LGH-F1200RX5-E1

90

Temperature exchange efficiency

efficiency(Heating)

Enthalpy exchangeEnthalpy exchangeefficiency(Cooling)

Low

High

Extra High Extra High

High

Low

efficiency(Cooling)

Enthalpy exchange

Enthalpy exchange efficiency(Heating)

efficiency

Temperature exchange

600600

0

100

200

300

400

500

0.50

1.00

1.50

2.00

2.50

500

400

300

200

0

0.50

1.00

1.50

2.00

2.50

80

70

60

50

40

100

0

0 0

40

50

60

70

80

90

0250 500 750 1000 1250 1500 150012501000750500250

400 800 1200 1600 2000 2400 2400200016001200800400

60Hz/Single phase 208VExchangeefficiency (%)

Ext

erna

l sta

tic p

ress

ure

(CFM)

Air volume (m3/h)

(CFM)

Air volume (m3/h)

Ext

erna

l sta

tic p

ress

ure

Exchangeefficiency (%)

60Hz/Single phase 230V

Pa

Pa

inH

2O

inH

2O

39 3/4 (1010)

C DA B

3 1/8 (79)1 3/4 (44)

27 9

/16

(700

) 10

5/8

(270

)

ø9 1

/2(ø

242)

ø10 3

/16(ø

258)

(ø24

2)

(ø25

8)

ø9 1

/2

ø10 3

/16

15 3/4 (399)

31 7/16 (798)

1 1/

8 (2

7)

5 7/

8 ~

9 7/

8(1

50 ~

250

)

4 5/

16 (1

10)

10 5

/8(2

70)

Ceiling suspension fixture (4-9/16 X 1-3/16 (4-15 X 30) oval)

SA (supply air)

RA (return air)EA

(exhaust air outlet)

OA (outside air intake)

Core, air filter, High-efficiency

filter, fan,

maintenance space

High-efficiency filter (sold separately) attachment position

Air exhaust fan

Bypass damper plate

Air supply fan

Maintenance cover

Inspection opening

Air filtersMo

re tha

n 23 5

/8 (60

0)

Power supply cableopening

Control box

45 1/16 (1144)

Lossnay cores

36-1/8

917

36-1/8

917

50-1/8

1272

265 lbs

120 kg)

High Low Extra High High Low5.7/5.8

1185/13031200/12000.43/0.75

67/6764/6450/50

38/40.5

5.0/5.31040/12191012/12000.43/0.43

68/6765/6453/50

36/39

3.1/3.4639/765695/824

0.20/0.2075/7371/6859/56

29/32

5.8/5.81185/13031200/12000.43/0.75

40/42.5

5.1/5.41040/12191012/12000.43/0.43

38/41

3.1/3.4639/765695/824

0.20/0.20

30.5/33.5

26510.0A

Lorem ipsum

Page 11: ENERGY RECOVERY VENTILATORS · energy costs. Recover up to 80 percent of sensible and latent energy from the conditioned air as it is exhausted. Reduce extremes in humidity that can

11

• Clearance should be provided to allow access to the air filter and Lossnay® Core.

• The installer must provide insulation to prevent moisture condensation along the two outside ducts (outside-air intake and exhaust-air outlet).

• Ceiling installation hardware can be attached to the top of the unit.

• The installer must use weather-protected caps or hoods in areas directly exposed to rain.

LGH-F300RX5-E1LGH-F470RX5-E1LGH-F600RX5-E1

LGH-F1200RX5-E1

A

B

D

C

Min

. 23-

5/8" 5-7/8~9-7/8"

Ceilingsuspensionbolt position

Duct normal diameterøE (user-supplied)

Weather cover

Ceiling suspension boltposition (user-supplied)

Duct inclineOver 1/30 (toward the wall)(moisture condensation prevention)

Heat exchanger/filtermaintenance space

Service access area

Service access area

Ceilingsuspensionbolt position

Ceilingsuspensionbolt position

Air-exhaust grill

Air-supply grill

Air-supplyexhaust grill

EA(exhaust-air outlet)

EA(exhaust-air outlet)

OA(fresh-air intake)

OA(outside-air intake) RA

(return air)SA(supply air)

5-7/8~9-7/8"

AE)teltuo ria-tsuahxe(

AO(oustide-air intake)

A

CD

Min.

23-

5/8"

AS)ria ylppus(

B

Duct inclineOver 1/30 (toward the wall)(moisture condensation prevention)

Heat exchanger/filtermaintenance space

Duct diameterø13-3/4" (user-supplied)

Duct diameterø13-3/4" (user-supplied)

Y piping, Reducer(user-supplied)

Service access

Service access area

Ceilingsuspensionbolt position

Ceiling suspensionbolt position

Ceiling suspensionbolt position

Ceiling suspensionbolt position

Exhaust grill(user-supplied)

Exhaust grill(user-supplied)

Air-supply grill

Air-supply grill

Air-supply grillAir-exhaust grill

Air-supply grill(user supplied)

EA(exhaust-air outlet)

OA(outside-air intake)

RA(return air)

SA(supply air)

WALL

WALL

Typical Installation

Duct can be installed in two different directions (OA, EA side)Ducts can be connected in two different directions to the outdoor vents thanks to collars and aperture plates that are interchangeable — either side or bottom locations. This flexibility allows for installations close to the surface of a wall and helps avoid cases where the stale exhaust air vent would be obstructed. This innovative feature simplifies both planning and installation.

STANDARD INSTALLATION INSTALLATION WITH DUCT DIRECTION CHANGED

Page 12: ENERGY RECOVERY VENTILATORS · energy costs. Recover up to 80 percent of sensible and latent energy from the conditioned air as it is exhausted. Reduce extremes in humidity that can

12

Use Lossnay M-NET remote controller PZ-52SF-E.

(Do not use PZ-41SLB-E).

Lossnay transmission connection terminal

Two remote controller system with multiple Lossnay units

It is also possible to operate two remote controller units when using multiple Lossnay units.

Power supply

Power supply

Remote controllerPZ-41SLB-E

Interlocking multiple unitsWhen the operation signal is an uncharged a-contact signal

Interlocking/individual joint systems

By making the group setting, interlock settings have become possible.(Joint use of the CITY MULTI remote controller and Lossnay remotecontroller is possible.)

Interlocking is possible from multiple air conditioning units, etc. (excluding pulse input)(Separately sold parts are necessary depending on the operation signal).

Applicable indoor units use MA remote contoller models. Do not set the air conditioning unit and Lossnay unit to bepart of the same group. When the address number has been changed, the data in the memory

is automatically reset.

Power supply Power supply Power supply Power supply

LossnayA/C A/C A/C

RemotecontrollerPZ-41SLB-E

Air conditioning unit side remote controller

Air conditioning unit side remote controller

Air conditioning unit side remote controller

Indoor unit (01)

Centralisedcontroller(201) Outdoor

unit (51)

Operation settings

MA remote controller

Lossnay (02)

Lossnay M-NET remote controller (PZ-52SF-E)(102)

Group 1 Group 2

Use Lossnay remote controller PZ-41SLB-E

(Do not use PZ-52SF-E).

Lossnay transmission connection terminal

A B S65654321

A B S A65 B S

0 1SA1 SA2

0

2

01

SA1

SA2

SA1

SA2

Transmission cable

Transmissioncable

Round terminal

M-NET transmission cableinput terminal block

Shielded wireM-NET

transmission cable

Remote controller input terminal

Main/Sub selection switch(SW1)

Main Sub

(Set to Main whenshipped from the factory)

( ) address

LGH-F300, F470and F600RX types LGH-F1200RX type

LGH-F300, F470and F600RX types

TB5LGH-F1200RX type

TB5

Setting

SettingLGH-F300, F470 and F600RX types LGH-F1200RX type

Uppercircuitboard[Sub]ex. SA1 = 0, SA2 = 2

Lowercircuitboard[Main]ex. SA1 = 0, SA2 = 1

Operating with external device

The operation of the Lossnay will be connected with the operation orstopping of the external device.Input of level signal or pulse signal (12V DC, 24V DC, unchargeda-contact) is possible.

One Lossnay with one remote controller

One Lossnay unit is operated independently with one remote controller.

Multiple Lossnay units with one remote controller

Up to 15 Lossnay units can be controlled atone time with one remote controller.

Two remote controller system with one Lossnay

Operating with M- and P-Series (A-control) – Interlocked

The Remote controller (A-control) controls the air conditioning device and the Lossnay. It is possible to operate or switch fan speed for the Lossnay individually.

LossnayNon-polar2 wires

Remote controller PZ-43SMF-E

Power supply

LossnayNon-polar2 wires

Power supply

RemotecontrollerPZ-43SMF-E

(Sub)

(Main)

Lossnay

Power supply

LossnayNon-polar2 wires

Remote controller PZ-43SMF-E

Power supply

Air conditioning device and system control

It is possible to operate 16 indoor units per 1 Lossnay

IndoorunitMA remote controller

Outdoor unit

IndoorunitMA remote controller

Lossnay IndoorunitMA remote controller

LossnayIndoorunit

Indoorunit

MA remote controller

IndoorunitMA remote controller

Lossnay IndoorunitMA remote controller

IndoorunitMA remote controller

Lossnay

Indoor unitIndoor unit

Group 1 Group 5Group 3 Group 4Group 2

Outdoor unit Outdoor unit

IndoorunitMA remote controller

Lossnay Lossnay

Group 1

Lossnay

3 puorG2 puorG

Control of start/stop, fan speed and ventilation mode is possible from the Lossnay remote controller PZ-60DR-EControl of start/stop, fan speed and ventilation mode is possible from the centralized controller.It is possible to set a maximum of 16 units for 1 group.

Lossnay remote controller

PZ-60DR-E

Lossnay Lossnay

Group 1

Lossnay remote controller

PZ-60DR-E

Lossnay Lossnay LossnayLossnay

Group 3

Lossnayremote controller

PZ-60DR-E

Lossnay

Group 4Group 2

Powersupplyunit

Lossnay M-NET remote controller

PZ-60DR-E

Lossnay

Group 5

Lossnay

Power supply

Power supply

Remotecontroller

Lossnay

Power supply

Power supply

Remote controller

Indoor unitIndoor unit

RemotecontrollerPZ-43SMF-E

Non-polartwo wires

Centralized controller

PAR-33MAA

Selection of interlocked operation mode is possible. Delayed start interlocked operation is possible

The Lossnay can be controlled from two remote locations. The remote controller gives priority to the last touch

System Control ExamplesBasic System — Stand-alone Lossnay ERV with PZ-41SLB-E Remote Controller

Operation with M-Series or P-Series

CITY MULTI and Lossnay Interlocked

Centralized Management System

M-N

ET

SY

ST

EM

Note: In the LGH-F1200RX type, there are two circuit boards installed in each unit, so count each unit as two Lossnay units.

Page 13: ENERGY RECOVERY VENTILATORS · energy costs. Recover up to 80 percent of sensible and latent energy from the conditioned air as it is exhausted. Reduce extremes in humidity that can

13

Balanced Ventilation A ventilation strategy using both an exhaust air blower and a supply or make-up air blower providing the same airflow and pressure so as not to pressurize or depressurize a building.

CFMCubic Feet per Minute, a measure of air volume.

Delayed OperationThe On/Off operation of the Lossnay unit can be delayed for 30 minutes following the operation of the indoor unit. When using PZ-43SMF-E, the delay can be set for 0:30–24:00 hours.

ESPExternal Static Pressure, available motive force to propel air in a duct system from a blower or ventilator.

Enthalpy ExchangeThe exchange of both sensible and latent heat energy.

Exhaust Air (EA)Air expelled from indoor space.

External Control InputAn On/Off input signal for operating the Lossnay unit that can be sent from an external device. The signal may be a 12V–24V DC or an uncharged a-contact signal.

Interlocked LossnayLossnay unit linked to CITY MULTI, M-, S-, or P-Series Indoor units that receive signals and operates via the indoor unit’s remote controller.

Non-interlocked LossnayLossnay unit controlled independently of CITY MULTI, M-Series, or P-Series indoor units by the Lossnay remote controller and/or centralized controller.

Operation in Cold AreasWhen the outdoor air is less than 14°F, continuous operation of the fan for drawing in supply air is stopped, and intermittent operation is started.

Outdoor Air (OA)Air drawn from outdoors — ventilation air.

Pulse InputWhen the control signal from an external device outputs a pulse such as the one shown at right, the pulse input control is performed by the Lossnay unit. (Optional DIP switch 2-2 ON) 200 ms or more.

Remote OperationThis is used for enabling/disabling the On/Off control signal from an external device and for setting interlocked operation of the external device and the Lossnay unit. ON/OFF interlock: Enables both ON OFF and

OFF ON external signals. ON interlock: Enables OFF ON external signal.

Disables ON OFF external signal. OFF interlock: Enables ON OFF external signal.

Disables OFF ON external signal. External priority: Same as on/off interlock but the

OFF signal from the remote controller is ignored when the external control signal is on.

Return Air (RA)Air drawn from indoor space.

Supply Air (SA)Air supplied to indoor space.

Ventilation Modes Energy Recovery — energy exchange through

Lossnay core at all times. Bypass — no exchange—bypass damper open Automatic — energy exchange or bypass as

determined by present temperature sensor in inlet and discharge airstreams.

Energy Recovery Ventilator Terminology

200 ms or more

Page 14: ENERGY RECOVERY VENTILATORS · energy costs. Recover up to 80 percent of sensible and latent energy from the conditioned air as it is exhausted. Reduce extremes in humidity that can

14

System Selection

ERV-22LGH-F-RX3-E

Lossnay operation when indoor unit is stopped

AvailableNot available

Lossnay stopping when indoor unit is operatingSelecting Lossnay fan speedWhen interlocked with indoor unit for compatibility with R22, R407C and R410A High / Low

Ventilation mode Fixed to automaticFilter maintenance indicatorLossnay error indicatorDelayed operation – selectable times

Delayed operation - selectable times

External control operating mode selection

×

Number of indoor units for interlocked group setting with one Lossnay unit 16 unitsNumber of Lossnay units for interlocked group setting with one indoor unit 1 unit

Interlocked with external device (BMS) Start/StopFan speed selection Fixed to highVentilation mode switching Fixed to automaticFilter maintenance indicator ×Lossnay error indicator ×Delayed operationExternal control operating mode selection

Lossnay unitLGH-RX type

M-NET transmission cable

Remote controller

Interlocked with M-Series or P-Series When using A-control remote controllerLossnay operation when indoor unit is stoppedLossnay stopping when indoor unit is operating ×

×

Other common itemsLossnay error indicator ×Ventilation mode Fixed to automaticFilter maintenance indicator ×

External control operating mode selection ×Number of indoor units for interlocked group setting with one Lossnay unit 1 unitNumber of Lossnay units for interlocked group setting with one indoor unit 1 unit

M- and P-Series Lossnay connecting cable(Enclosed accessory)

Remote controller

Lossnay remotecontroller cannot

Lossnay unitLGH-RX type

Start/StopwoL/hgiHselection deeps naF

Ventilation mode Energy Recovery By-pass/ Auto

Filter maintenance indicatorLossnay error indicatorDelayed operationExternal control operating mode selectionNumber of Lossnay units

15 units( In the case of LGH-200RX type, count each unit as two for calcultion)

stinu 2 srellortnoc etomer fo rebmuN

Lossnay remote controller(PZ-43SMF-E)

EXT. signal sourcefor interlockingto the Lossnay

Lossnay unitLGH-RX type

EXT. signal sourcefor interlockingto the Lossnay

Lossnay unitLGH-RX type

Interlocked with CITY MULTI

Independent Lossnay Unit (not interlocked with CITY MULTI, M-Series, or P-Series systems)

CITY MULTIindoor unit

M-Series or P-Series (A-control)indoor unit

PZ-43SMF-E

Lorem ipsumLossnay fan speed selection High / Low

be used

Page 15: ENERGY RECOVERY VENTILATORS · energy costs. Recover up to 80 percent of sensible and latent energy from the conditioned air as it is exhausted. Reduce extremes in humidity that can

15

Centralized Control System with CITY MULTI

Indoor unit Lossnay Indoor unit

Outdoor unit

A-control M-Series or P-Series outdoor unit

M- and P-Series A-controlPAR-33MAAremote controller

A-controlM-Series or P-Series indoor unit

Lossnay

Lossnayremote controller(PZ-60DR-E)

EXT.signalsource

Lossnayremote controller(PZ-60DR-E)

Remote controller Remote controller

M-NET control adapter

LossnayLossnay

Lossnayremote controller(PZ-43SMF-E)

Lossnay

AE-200A/AE-50ACentralized controller

PAC-SF83MA-E

Page 16: ENERGY RECOVERY VENTILATORS · energy costs. Recover up to 80 percent of sensible and latent energy from the conditioned air as it is exhausted. Reduce extremes in humidity that can

BC4

1340 Satellite Blvd.Suwanee, GA 30024

www.mitsubishipro.com

©2018 Mitsubishi Electric Trane US HVAC LLCMitsubishi Electric, Lossnay, and the three-diamond logo are trademarks of Mitsubishi Electric Corporation. H2i and kumo cloud are registered trademarks of Mitsubishi Electric US, Inc. All other product names mentioned herein are trademarks or registered trademarks of their respective owners.

SKU: ME- EBRE | 06.2018 | Printed in the USA